To, THE DIRECTOR OF BOILERS, New Secretariat Building (8th floor) 1, K.S. Roy Road, - 700001

Sir, Name of the Owner: Agarpara Kutir Silpa Pratisthan

Locality: South Station Road. Agarpara , , North 24 Parganas, P.O : Agarpara,

Boiler Registration No: UP2528, Boiler Type: Water Tube, Date of Inspection: 10-08-2017

Sub:- Dry and Through inspection of boiler. Reference above and my subsequent visit to above premises this is to report that the above mentioned boiler was inspected thoroughly in dry condition and found as follows:- i) General condition of the boiler pressure parts were checked thoroughly and found to be in order. ii) All mountings & fittings of the boiler were inspected in dismantled and cleaned condition and found to be in order. iii) The year of make of the boiler is 1940 and working pressure of the boiler is 10.50 kg/cm2. And the operating temperature is less than 400 Degree C. In view of the above the drums and headers of such boilers shall be inspected by Ultrasonic Testing, Magnetic Particle Testing ,Dye Penetrant Test by Remnant Life Assessment Organization approved by the Central Boilers Board as per requirement of Reg 391A Clause (b)sub clause (ii) of IBR 1950 .. Provisional order for steaming is kept withheld pending the followings: 1) The above said test. 2) Satisfactory Hydraulic test of the boiler.

Your’s faithfully

Sri Subhashis Das, Assistant Director of Boilers, W.B.

No. WB/R/2017/0207.date 12-08-2017 Copy forwarded for information and necessary action to:- i)Agarpara Kutir Silpa Pratisthan, Village : South Station Road. Agarpara , Subdivision : Barrackpore, P.O. : Agarpara District : North 24 Parganas, ii)Sri Subhashis Das, Assistant Director of Boilers, W.B.

Joint Director of Boilers, W.B.

Powered by TCPDF (www.tcpdf.org)