<<

INSTALLATION GUIDELINES

Eldorado Stone endorses and supports the Masonry Veneer Manufacturers Association (MVMA) Installation Guidelines. The mission of the MVMA organization is “To advance the growth of the manufactured masonry veneer products industry through proactive technical, advocacy, and awareness efforts.” One of the most important projects completed by the MVMA Technical Committee was the development of a highly detailed and carefully researched installation guide. The latest version of that guide can be downloaded at www.eldoradostone.com/resources. These guidelines are intended to share over 45 years of knowledge, experience and understanding regarding the proper installation of manufactured stone veneer products. For any specific or unique installation questions or challenges, including: • Traditional masonry installation methods • Installation over board using polymer modified • Installation over thick foam; fastener selection • Installation of large format profiles Please contact Eldorado Stone’s Technical Support Service directly at 800.925.1491.

Note: It is important to recognize that Eldorado Stone and veneer products are an adhered veneer or façade which are attached directly to a cementitious substrate for purposes of providing ornamentation and a first layer of weatherization protection. Adhered Masonry Veneers are not intended as a structural product or a waterproofing element. Most importantly, the real subject matter expert is your local building department and the local building code. Your local building code will supersede all other written or verbal installation guides provided by Eldorado Stone or the MVMA. Go to ncma.org/manufactured-stone-veneer for more information about the MVMA.

eldoradostone.com 800.925.1491

033018 Installation Guide and Detailing Options for Compliance with ASTM C1780 For Adhered Manufactured Stone Veneer 5 th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org Table of Contents Definitions/Abbreviations...... 4 References...... 4 Workmanship...... 7 Material Requirements...... 7 Surface Preparation...... 9 Installation of Adhered Manufactured Stone Veneer...... 12 Cautions...... 14 Drawings/Cross Sections Figure 1. Installation Over Wood ...... 15 Figure 2. Installation Over Concrete Masonry Units...... 16 Figure 3. Assembly Transition...... 17 Figure 4a. Typical Frame Wall Section...... 18 Figure 4b. Typical Frame Wall Section Over Continuous Rigid Insulation...... 19 Figure 5a. Foundation Wall Base...... 20 Figure 5b. Foundation Wall Base Over Continuous Rigid Insulation...... 21 Figure 6. Foundation Wall Base-AMSV Overlapping Foundation...... 22 Figure 7. Foundation Wall-Transition to AMSV Continuing Down Foundation...... 23 Figure 8a. Cladding Transition...... 24 Figure 8b. Cladding Transition Over Continuous Rigid Insulation...... 25 Figure 9a. Outside Corner...... 26 Figure 9b. Outside Corner Over Continuous Insulation...... 27 Figure 10a. Inside Corner...... 28 Figure 10b. Inside Corner Over Continuous Insulation...... 29 Figure 11a. Horizontal Transition...... 30 Figure 11b. Horizontal Transition Over Continuous Insulation...... 31 Figure 12a. Vertical Transition...... 32 Figure 12b. Vertical Transition Over Continuous Insulation...... 33 Figure 13a. Open Eave-Overhang...... 34 Figure 13b. Open Eave-Overhang Over Continuous Insulation...... 35 Figure 14. Open Eave-Flush...... 36 Figure 15. Rake-Overhang...... 37 Figure 16. Rake-Flush...... 38 Figure 17a. Side Wall-Composition Shingles...... 39 Figure 17b. Side Wall-Composition Shingles Over Continuous Insulation...... 40 Figure 18. Side Wall-Composition Shingles Curbing...... 41 Figure 19. Side Wall-Tile Roofing...... 42 Figure 20. Side Wall-Tile Roofing Curbing...... 43 Figure 21a. Window Sill...... 44

2 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Table of Contents (continued) Disclaimer Drawings/Cross Sections (continued) This Guide addresses generally ac- Figure 21b. Window Sill Over Continuous Insulation...... 45 cepted methods and details for the Figure 22. Window Jamb...... 46 installation of Adhered Manufactured Stone Veneer. To the best of our knowl- Figure 23. Window Head...... 47 edge, it is correct and up to date. The Figure 24. Kick-Out Flashing...... 48 document, however, is designed only as a guide and it is not intended for Figure 25. Cricket...... 49 any specific construction project. The Figure 26. Chimney Chase...... 50 MVMA and NCMA make no express or Figure 27. Column Base...... 51 implied warranty or guarantee of the techniques, construction methods or Figure 28. Penetration, Flanged...... 52 materials identified herein. Figure 29. Penetration Non-Flanged, with Building Paper WRB...... 53 It is understood that there are alter- Figure 30. Penetration Non-Flanged, with Housewrap WRB...... 54 native means or methods that might be required and/or recommended Figure 31. Penetration, Fixture...... 55 based on project conditions, manu- Figure 32. Penetration, Dryer Vent...... 56 facturer’s recommendations, or prod- uct characteristics. Figure 33. Deck Termination...... 57 This Guide is for builders, architects, Figure 34. Wall Cap...... 58 designers, masons, installers and Figure 35. Wall Assembly-Rainscreen System-Drainage System...... 59 other construction professionals who can interpret the illustrations and typi- Figure 36. Wall Assembly-Rainscreen System-Strapped...... 60 cal applications of Adhered Manu- Figure 37. Foundation Wall Base-Rainscreen System...... 61 factured Stone Veneer presented. Details in this guide that address the Figure 38. Typical Wall Section-Rainscreen System...... 62 installation and detailing of Adhered Figure 39. (CMU)...... 63 Manufactured Stone Veneer and its interface with other building compo- Figure 40. Stone Wrap Under Straight Overhang...... 64 nents are not intended as specific rec- Figure 41a. Forward Mounted Commercial Window...... 65 ommendations. It is the responsibility Figure 41b. Forward Mounted Commercial Window Over of all design and construction profes- sionals to determine the applicability Continuous Insulation...... 66 and appropriate application of any Figure 42. Forward Mounted Commercial Window-Top View...... 67 detail to any specific project. Figure 43. Commercial Storefront Window-Top View...... 68 About Figure 44. Commercial Storefront Window...... 69 Figure 45. Wall-Section Multi-Floor Joint Detail...... 70 Masonry Veneer Manufacturers Asso- ciation (MVMA), an affiliate of NCMA, Figure 46a. Wall-Section CMU...... 71 represents the adhered manufac- Figure 46b. Wall-Section Over Continuous Rigid Insulation...... 72 tured stone veneer industry’s manu- Figure 47. Wall-Section Parapet with Stone Cap...... 73 facturing companies and their suppli- ers. The mission of the organization is Figure 48. Wall-Section Parapet with Steel Cap...... 74 to advance the growth of the manu- Notes ...... 75 factured masonry veneer products industry through proactive technical, advocacy, and awareness efforts. Masonry Veneer Manufacturers Association National Concrete Masonry Association 13750 Sunrise Valley Drive Herndon, VA 20171 Phone: (703) 713-1900 Copyright © 2018 by the National Con- www.masonryveneer.org crete Masonry Association. All rights re- www.ncma.org served. 5th Edition, 2nd Printing

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 3 Masonry Veneer Manufacturers Association www.masonryveneer.org Definitions References Adhered Manufactured Stone Veneer (AMSV) — light- AC191 — ICC-ES Acceptance Criteria for Metal Bases weight, architectural, non-load-bearing product that is (Lath) manufactured by wet cast blending of cementitious ma- AC275 — ICC-ES Acceptance Criteria for Fiber Lath used in terials and aggregates, with or without pigments, admix- Cementitious Exterior Wall Coating or Exterior Cement Plaster tures, or other materials to simulate the appearance of () natural stone and other masonry materials. AC376 — ICC-ES Acceptance Criteria for Reinforced Cementi- Note: The MVMA recognizes there are many names used tious Sheets used as Wall and Ceiling Sheathing and Floor Un- to describe Adhered Manufactured Stone Veneer products. derlayment (Cement Board) Adhered Manufactured Stone Veneer is used commonly ANSI Accredited Evaluation Service — (or equivalent) third-party throughout the industry and by some manufacturers. In organization that issues an evaluation report affirming a specific the International Building Code, Adhered Manufactured building product meets building code requirements. Stone Veneer products are referred to as Adhered Masonry Veneer. This guide will use AMSV (Adhered Manufactured International Code Council - Evaluation Service (ICC-ES) — An Stone Veneer) when referencing the product. organization that performs technical evaluations on building products, components, and construction methods for building Backup – The interior or exterior assembly to which code compliance. In the case where the building code is silent AMSV systems are installed. or ambiguous as to a product’s requirements or a specific con- CMU – . struction method, ICC-ES may develop “Acceptance Criteria” Corrosion Resistant – A material that is intrinsically re- (AC) for the product or construction method. www.icc-es.org sistant to degradation or physically or chemically treated International Building Code — Building code that provides the to be so under expected exposure conditions. Examples minimum requirements for safety, health, and welfare of life and include: -based materials stabilized for exposure property from hazards of the built environment. The provisions of to UV light, galvanized ferrous metals, and stainless steel. this code apply to the construction, alteration, addition, replace- Fasteners — Corrosion resistant hardware used to secure ment, repair, use and occupancy of all buildings except one and two family dwellings, and single-family townhomes not more than lath, screed, and flashing materials to backup systems. three stories in height. www.iccsafe.org Flashing — Corrosion resistant material used to restrict the movement of water around any intersection or pro- International Residential Code — Building code that provides minimum requirements for safety, health, and welfare of life and jection of materials in an assembly. property from hazards of the built environment. The provisions Lath — Corrosion resistant mesh fas- of this code apply to the construction, alteration, addition, re- tened to the substrate to act as base for adhering mortar. placement, repair, use and occupancy of detached one and two Mortar — A mixture of cementitious material, water, and family dwellings and single-family townhomes not more than aggregate, with or without the addition of admixtures or three stories in height. www.iccsafe.org additives to alter one or more plastic or hardened prop- ANSI — American National Standards Institute, www.ansi.org erties, used to bond masonry construction materials to- ANSI A118.1 — American National Standards Institute Specifica- gether and fill spaces between. tions for Dry-Set Portland Cement Mortar Pointing Mortar — Also known as grouting mortar, ANSI A118.4 — American National Standards Institute Specifica- mortar mixture used to fill joints and cavities in AMSV tions for Modifed Dry-Set Cement Mortars construction. ANSI A118.15 — American National Standards Institute Specifica- Mortar Scratch Coat — Base coat of mortar used dur- tions for Improved Modified Dry-Set Cement Mortar ing the installation of AMSV; cross-raked to improve bond of subsequent mortar layers. TMS 402 — Building Code Requirements for Masonry Structures. This standard is produced through the efforts of The Masonry Mortar Screen — Sheet material installed to prevent Society (TMS). www.masonrysociety.org the mortar scratch coat from filling the drainage space behind an AMSV assembly containing a rainscreen sys- TMS 602 — Specification for Masonry Structures. This standard tem. is produced through the efforts of The Masonry Society (TMS). www.masonrysociety.org Mortar Setting Bed — Mortar used to adhere the AMSV to the substrate or scratch coat. ICRI — International Concrete Repair Institute, Technical Guide- line No. 310.2. www.icri.org Water Resistive Barrier (WRB) — Material used to re- strict the transmission of water to the surface behind. ASTM International — ASTM is a developer of technical stan- dards for products, systems, and services. www.astm.org

4 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org References (continued) ASTM C270 — Standard Specification for Mortar for Unit Masonry ASTM C1325 — Standard Specification for Non-Asbestos Fiber- Mat Reinforced Cementitious Backer Units ASTM C482 — Standard Test Method for Bond Strength of Ce- ramic Tile to Portland CementPasteStandard Specification for ASTM C1384 — Standard Specification for Admixtures for Ma- Metal Lath sonry Mortars ASTM C578 - Standard Specification for Rigid, Cellular Polysty- ASTM C1670/C1670M — Standard Specification for Adhered rene Thermal Insulation Manufactured Stone Masonry Veneer Units ASTM C847 — Standard Specification for Surface Applied ASTM C1714/C1714M — Standard Specification for Preblended Bonding Compounds for Exterior Plastering Dry Mortar Mix for Unit Masonry ASTM C933 — Standard Specification for Welded Wire Lath ASTM C1780 — Standard Practice for Installation Methods for Adhered Manufactured Stone Masonry Veneer ASTM C979/979M — Standard Specification for Pigments for Integrally Colored Concrete ASTM C1788 - Standard Specification for Non Metallic Plaster Bases (Lath) Used with Portland Cement Based Plaster in Verti- ASTM C1032 — Standard Specification for Woven Wire Plaster cal Wall Applications Base ASTM E2556/E2556M — Standard Specification for Vapor Per- ASTM C1059/1059M — Standard Specification for Latex Agents meance Flexible Sheet Water-Resistive Barriers Intended for for Bonding Fresh to Hardened Concrete Mechanical Attachment ASTM C1063 — Standard Specification for Installation of Lath- ASTM D226/D226M — Standard Specification for Asphalt Satu- ing and Furring to Receive Interior and Exterior Portland Ce- rated Organic Felt Used in Roofing and Water Proofing ment Based Plaster ASTM F1667 — Standard Specification for Driven Fasteners, ASTM C1289 - Standard Specification for Faced Rigid Cellular Nails, Spikes, and Staples Polyisocyanurate Thermal Insulation Board

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 5 Masonry Veneer Manufacturers Association www.masonryveneer.org

Table 1—AMSV Installation Requirements Summary1 Water Backup Wall Sheathing/ Setting Bed Resistive Lath Type Lath Fasteners3 Scratch Coat System10 Substrate5 Mortar Barrier2 • Gypsum Corrosion resistant; Wall Board Type N or S mortar minimum penetration • Plywood Any complying with ASTM Interior Wood 3/ in. (19 mm) into • OSB Optional6 approved 4 C270 or ASTM C1714; See Table 2 or Steel Stud wood framing member • Fiber lath7 minimum nominal Framing; or 3/ in. (10 mm) into Board 8 thickness 1/ in. (13 mm) maximum steel framing member 2 spacing 16 in. (406 mm)4 ANSI A118.4 • Cement Not Not Not Applicable Not Required or ANSI Board Required Required A118.15 • Gypsum Corrosion resistant; Wall Board Type N or S mortar minimum penetration • Plywood Minimum Any complying with ASTM Exterior 3/ in. (19 mm) into • OSB two layers approved 4 C270 or ASTM C1714; See Table 2 Wood or Steel wood framing member • Fiber WRB lath7 minimum nominal Stud Framing; or 3/ in. (10 mm) into Board 8 thickness 1/ in. (13 mm) maximum steel framing member 2 spacing 16 in. (406 mm) Minimum ANSI A118.4 • Cement Not two layers Not Applicable Not Required or ANSI Board Required WRB A118.15 Not Not Not Not Applicable Not Required See Table 2 Applicable Required Required Concrete or Corrosion resistant Type N or S mortar Concrete Any concrete screws, complying with ASTM 8,9 Not Masonry Optional9 approved masonry nails, or C270 or ASTM C1714; See Table 2 Applicable lath7,9 powder actuated minimum nominal 9 1 9 fasteners thickness /2 in. (13 mm) Corrosion resistant Type N or S mortar Any concrete screws, complying with ASTM Clay Not Optional9 approved masonry nails, or C270 or ASTM C1714; See Table 2 Masonry8,9 Applicable lath7 powder actuated minimum nominal 1 fasteners thickness /2 in. (13 mm) 1 Refer to AMSV manufacturer for installation recommendations addressing conditions not listed. 2 WRB complying with ASTM D226, ASTM E2556, or equivalent. 3 Fastener type and spacing must comply with ASTM C1063. Refer to Tables 3 and 4 for minimum fastening requirements for direct attach- ment of AMSV systems over continuous insulation. 4 For interior applications exposed to moisture, refer to corresponding exterior wall detailing requirements. 5 Sheathing/substrate material shall be approved for intended application and installed in accordance with manufacturer’s recommendations. 6 A single layer of WRB is recommended where the sheathing/substrate is moisture sensitive. 7 Approved lath options include: A) 2.5 lb/yd2 (1.4 kg/m2) (or heavier) self-furring metal lath meeting ASTM C847. 3 2 2 B) /8 inch (9.5 mm) rib (high rib), 3.4 lb/yd (1.8 kg/m ) (or heavier), self-furring metal lath meeting ASTM C847. C) Welded wire lath complying with ASTM C933. D) 18 gauge (or heavier) woven wire lath meeting ASTM C1032. E) Non-metallic lath complying with ASTM C1788. F) Alternate lath products showing compliance with ICC-ES AC 275, or equivalent. 8 AMSV systems cannot be installed over existing anchored masonry veneers. 9 When installing AMSV over concrete or concrete masonry where good bond cannot be achieved or the concrete or concrete masonry is unsound, install AMSV over lath. l 10 Backup systems should be designed to limit out-of-plane deflections to /360 when subjected to 42% of the components and cladding wind pressure.

6 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Introduction Material Requirements This guide focuses on the installation of AMSV systems Units for backup assemblies addressed in the summary ta- ble. Other backup systems, such as structural insulated AMSV units installed in accordance with this guide panels (SIPs), may require a specifically-designed sys- must meet the minimum requirements of ASTM C1670/ tem of installation for AMSVs. AMSV systems should C1670M. not be installed over deteriorating or unsound backup assemblies or exterior insulation and finishing sys- Flashing tems (EIFS). All flashing and flashing accessories must be corrosion resistant and integrated with the WRB materials (if pres- Workmanship ent). For exterior applications, flashing must be installed at all through-wall penetrations and at lower boundaries This Installation Guide assumes that construction per- of AMSV installations. Flashing is not required for interior sonnel have knowledge of the materials described and applications of AMSV systems not exposed to water. For their knowledge and experience of proper methods of interior applications that are exposed to water, treat as installation. an exterior assembly. Prior to commencing activity related to the scope of this In some applications, the use of self-adhering flash- Guide, review all adjacent products and other work that ing, also known as flashing tape, can be used. It is rec- precedes the installation of AMSV to ensure that proper ommended that applicable building codes as well as workmanship is reflected and that there are no recogniz- manufacturer's instructions are reviewed and followed able errors or deficiencies that may compromise the instal- to ensure they are permissible for the given project or lation or performance of the AMSV. application. Additionally, the manufacturer of the AMSV Quality should be contacted prior to construction to ensure the compatibility of the two products. A successful project requires the use of quality materials, proper design and detailing for the application, and a Rainscreen Drainage Plane Systems high standard of care during installation. Unfortunately, Rainscreens are optional building techniques used to the execution of these components in the field can be improve the drainage of incidental water behind the subject to value-engineering resulting in materials se- cladding and reduce drying time. Rainscreen products lected based solely on price and installation techniques (such as drainage mats or formed polymer sheeting) or that focus on speed rather than quality. While the per- construction techniques (such as strapping or furring) formance of AMSV systems depends upon all three of that create a capillary break/air space between the clad- these components, field workmanship issues tend to be ding and the water resistive barrier can be effectively the dominate source of problems when performance is- incorporated into AMSV applications. Refer to the man- sues surface in the field. Installing AMSV in accordance ufacturer’s recommendation for rainscreen / drainage with the recommended practices of this guide and system applications with adhered manufactured stone ASTM C1780 helps to ensure AMSV systems perform as veneer wall systems. Details of various applications uti- intended for decades. lizing rainscreen drainage plane systems can be found Building Code Requirements in Figures 35-38. Building codes may allow a single layer of a water resistive barrier when a drainage space is in- Building code requirements vary from area to area. Check corporated in the wall system (i.e. rainscreen). Require- with local authorities for building code requirements for ments for rainscreens vary by region. Verify local jurisdic- your area and application. Carefully read all sections of this tional requirements regarding the use and application of guide and follow the manufacturer’s installation instruc- rainscreens and/or drainage products. tions before proceeding with your AMSV application. In the event the manufacturer’s installation instructions con- Weep Screeds and Casing Beads flict with the intent of statements made in this document, Weep screeds and casing beads must be corrosion resis- contact the manufacturer for additional guidance. tant, with weep screeds having a minimum vertical attach- Project Site Requirements ment flange of 3.5 inches (89 mm) that terminates behind the water resistive barrier (if present). The minimum thick- Jobsite safety is outside of the scope of this guide, how- ness of metal weep screeds and casing beads should not ever, users should always follow proper job site safety be less than 0.0179 inches (0.45 mm) (26 gage). For plas- requirements including local, state, and federal laws tic weep screeds or casing beads, the minimum thickness when installing AMSV products and systems. is 0.050 inches (1.3 mm).

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 7 Masonry Veneer Manufacturers Association www.masonryveneer.org

Lath N) with cement board installations. Refer to ASTM C1780 and manufacturer recommendations for additional de- Multiple lath materials have been used successfully for tails on cement board installations. Refer to Figures 4a the installation of AMSV systems, including: and 4b for references to the primary difference between • 2.5 lb/yd2 (1.4 kg/m2) (or heavier) self-furring metal lath and cement board applications. Other construction lath meeting ASTM C847; details illustrated in this guide are applicable to cement 3 2 2 boards installations as well. • /8 inch (9.5 mm) rib (high rib), 3.4 lb/yd (1.8 kg/m ) (or heavier), self-furring metal lath meeting ASTM C847; Mortar • Welded wire lath complying with ASTM C933; Mortars used for the installation of AMSV systems can be • 18 gauge (or heavier) woven wire lath meeting ASTM grouped into three different categories; scratch coat mor- C1032; or tar, setting bed mortar, and pointing mortar. Depending • The lath product is consistent with the AMSV manufac- upon the type of mortar used and whether it is batched turer’s installation instructions and has an evaluation ac- on site or delivered premixed to the project, each mortar ceptance report from an accredited evaluation service must meet minimum requirements as described below: showing compliance with ICC-ES Acceptance Criteria Scratch Coat Mortars – Scratch coat mortars are applied 275 (AC275), or equivalent, and ASTM C1788. directly to the lath or substrate to which AMSV systems All lath and lath accessories must be corrosion resistant, are adhered. As the name implies, this first layer of mor- consisting of either galvanized or stainless steel mate- tar is intentionally scratched or roughened before hard- rials or consisting of materials complying with AC 275, ening to provide enhanced mechanical bond between and ASTM C1788. All lath material must be self-furred the scratch coat and setting bed mortars. Recommenda- or use self-furring fasteners. Refer to the Summary Table tions for the scratch coat mortar are as follows: of this guide for specific lath and fastener recommenda- - Site Mixed: Meets the requirements of ASTM C270 tions. Type N or Type S Fasteners - Preblended: Meets the requirements of ASTM C1714 /C1714M Type N or Type S Corrosion resistant fasteners are used to secure flash- ing and lath to the backup system. A variety of fasten- Setting Bed Mortars – After the scratch coat mortar has ers are available such as staples, screws, and nails, pro- cured sufficiently, the setting bed mortar is used to ad- vided the heads or washers of these fasteners are large here the AMSV units to the backing. The setting bed enough to not pull through the lath and the fastener mortar is applied directly to the scratch coat or to the is of sufficient length to penetrate into the supporting back of the AMSV units (back-buttering), or a combina- material. For specific fastener selection criteria, refer to tion of both application methods. Recommendations for ASTM C1063. setting bed mortars based on specific applications are described as follows in Table 2. • Wood framing - Corrosion resistant staples, corrosion resistant roofing nails, or corrosion resistant screws Pointing Mortars – Pointing mortars, also referred to as and washers, of sufficient length to penetrate a mini- grouting mortars or mortar used to mortar joints, 3 are used to fill the joints between individual AMSV units mum of /4 inch (19 mm) into framing members. once the setting bed mortar has sufficiently cured. Not • Metal framing or panels - Corrosion resistant, self-tap- 3 all AMSV systems incorporated mortar between the ping screws with sufficient length to penetrate /8 inch units, while others allow the distance between units to (9.5 mm) through metal studs or panels. be varied to create alternative architectural finishes. Rec- • Masonry or concrete walls or panels - Corrosion resis- ommendations for the pointing mortar are as follows: tant concrete screws or powder actuated fasteners (or - Site Mixed: Meets the requirements of ASTM C270 cap fastener). Type N or Type S Cement Board - Preblended: Meets the requirements of ASTM C1714/C1714M Type N or Type S Cement board may be used in place of lath and scratch coat, if desired. When used, cement board must comply It is important to note that mortars mixed with higher with ASTM C1325. They must also be evaluated for in- amounts of cement will tend to be less workable and terior or exterior use in accordance with ICC-ES AC376 may be prone to increased shrinkage cracking, but based on the desired applications. When using cement will provide greater bond strength. Type N mortars are board, only modified mortars complying with ANSI generally easier to work with than Type S mortars due A118.4 or ANSI A118.15 should be used as the setting to the higher cement content of Type S mortars. bed mortar. Do not use conventional mortars (Type S or

8 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Table 2—Application Based Setting Bed Mortar Recommendations1 Type S Mortar Type N Mortar ANSI A118.4 or (ASTM C270 or Application (ASTM C270 or ANSI A118.15 ASTM C1714) or ASTM C1714) Mortar ANSI A118.1 Mortar Interior Applications Less than 10 ft (3 m) in height above finished floor Recommended Recommended Recommended All other interior applications Not Recommended Recommended Recommended Exterior Single Family Residential Applications Grouted2 Not Recommended Recommended Recommended All other exterior single family residential applications Not Recommended Recommended Recommended Exterior Commercial Applications Less than 10 ft (3 m) in height above finished grade Not Recommended Recommended Recommended All other exterior commercial applications Not Recommended Not Recommended Recommended Special Applications Installed directly on cement board Not Recommended Not Recommended Recommended Non-vertical applications3,4 Not Recommended Not Recommended Recommended 1 If the surface area of an AMSV unit exceeds 1 ft2 (0.1 m2) or 24 in. (610 mm) in any dimension, then install using setting bed mortar complying with ANSI A118.4 or ANSI A118.15. 1 ² Requires a minimum nominal mortar joint thickness of /4 in. (6.4 mm) around AMSV units. ³ Requires a fastening system designed by a professional engineer. 4 AMSV units should not be subjected to pedestrian or vehicular traffic.

General Mortar Considerations interchangeable, consult with mortar or additive manu- facturers to ensure compatibility of mortar and admix- When considering mortar selections, verify the mor- ture components. tar can provide a minimum shear bond strength of 50 lb/ in.2 (345 kPa) when tested in accordance with ASTM C482, is consistent with the stone manufacturer's recom- Surface Preparation mendations, and is suitable for installation of adhered Verify that the surface to which the AMSV is to be in- manufactured stone veneer. Prepackaged/preblended stalled is structurally sound, free of any coatings or ma- mortars should be mixed and installed per mortar manu- terials that would inhibit bonding, and capable of sup- facturer's instructions porting the intended AMSV system. The majority of the In some cases additives or admixtures are added to discussion and details in this guide focuses on the instal- mortars to modify one or more plastic or hardened lation of AMSV systems on backup systems consisting of properties of the mortar; such as workability enhanc- wood or steel framing with rigid sheathing and concrete ers, water repellents, or bond enhancers. When a modi- or concrete masonry construction; however, virtually any fier is introduced to a mortar comply with ASTM C270 backup system can be used when properly designed or ASTM C1714, the additional requirements of ASTM and prepared to receive AMSV systems. C1384 must also be met. Modifiers used in the produc- Masonry walls, poured-in-place concrete walls, and tion of mortar complying with ANSI A118.4 or ANSI concrete tilt up panels must be free of dirt, waterproof- A118.15 are specifically designed to increase the mor- ing, paint, form oil, or any other substance that could tar's bond strength. inhibit the mortar bond and must readily accept/absorb As reflected in Table 2, modified mortars containing water in order to achieve good bond. The Internation- bond enhancers and mortars with higher cement con- al Concrete Repair Institute, (ICRI), provides guidance tents are better suited for challenging installations or for concrete surface preparation and assessment. The where increased bond strength is desired. Examples surfaces intended to receive AMSV units must have a of these installations include exterior applications or rough texture to ensure good mortar bond. Refer to ICRI when directly bonding to substrates such as cement Technical Guideline 310.2 for additional information on board. As not all mortar admixtures are compatible or concrete surface preparation, including information on

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 9 Masonry Veneer Manufacturers Association www.masonryveneer.org

Concrete Surface Profile (CSP), a standardized method of the lower layer by a minimum of 2 inches (51 mm). to measure concrete surface roughness. A CSP equal The vertical joints of the WRB should be lapped a mini- to or greater than 2 is usually acceptable for the instal- mum of 6 inches (152 mm). Inside and outside corners lation of AMSV over concrete and masonry assemblies. must be overlapped a minimum of 16 inches (406 mm) If necessary, cleaning may be done with power washing past the corner in both directions. The WRB should be or mechanical methods (i.e. shot or bead blasting). If a installed in accordance with the manufacturer’s recom- bondable surface cannot be achieved, attach lath and mendations and be integrated with all flashing accesso- scratch coat before installing AMSV. This guide does ries, adjacent WRBs, doors, windows, penetrations, and not address the installation of AMSV systems over open cladding transitions. stud backup systems. Acceptable WRBs: Wall Systems with Exterior Continuous • Two layers of WRB complying with ASTM D226, Insulation E2556, or approved equal. AMSV may be installed on walls insulated with con- • As discussed in the “Rainscreen Drainage Plane Sys- tems”, building codes may allow a single layer of a tinuous insulation such as foam insulation. See Tables WRB to be used when a drainage space is incorpo- 3 and 4 for requirements on fastening over continous rated in the wall system. Requirements for the rain- insulation, which are adopted from similar provisions in screens vary by region. Verify with the local jurisdic- Chapter 26 of the International Building Code. The re- tional requirements regarding the use an application quirements are contained within the IBC. The allowable of rainscreens. Refer to Figures 35-38 for details on insulation thicknesses are based upon the fastener such construction method. type, fastener spacing, cladding weight, and support- ing backup system. • When transitioning to another cladding (such as that shown in Figure 8), refer to the applicable building Water Resistive Barrier code requirements for WRB behind that specific clad- ding system. Despite the number of layers required Where a water resistive barrier (WRB) is required, it for the non-AMSV cladding, there must be two (2) lay- should be installed in two separate layers in shingle fash- ers of WRB present behind the AMSV. ion, starting from the bottom of the wall. The inner layer of WRB should be installed, along with flashings, to cre- • Some types of continuous insulation may be substi- ate a drainage plane. The outer layer of WRB is intended tuted for the inner layer of WRB provided it is installed to keep the scratch coat from contacting the inner layer and sealed and/or taped in accordance with the insu- of WRB. The upper layer of the WRB should lap on top lation manufacturer's installation instructions and ap-

Table 3—Cladding Minimum Fastening Requirements for Direct Attachment of AMSV Over Insulation for Steel Framinga

Maximum Thickness of Foam Claddening Claddening Cladding Fastener Cladding Fastener Sheathingc (in.) Fastener Fastener through Foam Type and Minimum Horizontal Vertical Cladding System Weightd Sheathing into: Sizeb Spacing ( in.) Spacing ( in.) 11 psf 18 psf 25 psf #8 screw into 33 mil 16 6 2.95 2.20 1.45 steel or thicker #10 screw into Steel framing (minimum penetration of steel 33 mil 16 6 3.50 2.70 1.95 thickness plus 3 steel or thicker threads) #10 screw into 43 mil 16 6 4.00 4.00 3.60 steel or thicker For SI: 1 in. = 25.4 mm; 1 pound per square foot (psf) = 0.0479 kPa, 1 pound per square inch = 0.00689 MPa. DR = design required; a Steel framing shall be minimum 33 ksi steel for 33 mil and 43 mil steel and 50 ksi steel for 54 mil steel or thicker. b Screws shall comply with the requirements of AISI S200. c Foam sheathing shall have a minimum compressive strength of 15 pounds per square inch in accordance with ASTM C578 or ASTM C1289. d Cladding System Weight includes the installed weight of the AMSV units, setting bed mortar, lath, and scratch coat.

10 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org Table 4—Cladding Minimum Fastening Requirements for Direct Attachment of AMSV over Insulation for Wood Framinga

Claddening Claddening c Cladding Maximum Thickness of Foam Sheathing (in.) Cladding Fastener Fastener Fastener Fastener Type through Foam Horzintal Vertical d and Minimum Cladding System Weight Sheathing into: Spacing Spacing Sizeb ( in.) ( in.) 11 psf 18 psf 25 psf

0.113 in. 16 6 1.45 0.75 DR diameter nail 0.120 in. 16 6 1.70 0.90 0.55 Wood framing diameter nail 1 (minimum 1 /4 in. 0.131 in. pentration) 16 6 2.15 1.20 0.75 diameter nail 0.162 in. 16 6 3.55 2.05 1.40 diameter nail For SI: 1 inch = 25.4 mm; 1 pound per square foot (psf) = 0.0479 kPa DR = design required a. Wood framing shall be Spruce-Pine-Fir or any wood species with a specific gravity of 0.42 or greater in accordance with AFPA/NDS. b. Nail fasteners shall comply with ASTM F1667, except nail length shall be permitted to exceed ASTM F1667 standard lengths. c. Foam sheathing shall have a minimum compressive strength of 15 psi in accordance with ASTM C578 or ASTM C1289. d Cladding System Weight includes the installed weight of the AMSV units, setting bed mortar, lath, and scratch coat.

proved for such applications. Continuous insulation is While recommendations vary, existing codes and stan- commonly applied on the exterior side of the framing dards do not stipulate the orientation of the lath “cups” or on the exterior side of sheathing, runs continuous- (keys) once installed. More important than the orientation ly, and has minimal thermal bridging. Ensure WRB(s) of the lath cups is ensuring the lath is embedded within, selected are approved for wall applications. Some and bonded to, the mortar scratch coat for a successful WRB's intended for roofs are not appropriate for walls. AMSV installation. Lath is considered to be embedded 1 For example, 15 pound felt is not the same product as within the mortar scratch coat when there is a /4 in. (6 mm) No. 15 felt. For details of this practice, please refer to nominal thickness of mortar between the back plane of the continuous insulation figures shown throughout the lath and the back plane of the scratch coat for at least the figures section of this guide. one-half (50%) of the surface area of the installation. Lath Please refer to Figures 1 and 2 for general details on lath installation based on backing. The installation of lath should be in accordance with ASTM C1063. Lath should be applied horizontally (per- Flashings/Weep Screeds/Casing Bead/ pendicular to framing, if present) per manufacturer’s Movement Joints instructions, and should overlap a minimum of 1 in. (25 1 All flashing and accessory detailing pieces should be mm) at the vertical seams and a minimum of /2 in. (13 mm) at the horizontal seams. Vertical seams should be corrosion resistant. staggered. Lath should be wrapped around inside and Verify that all flashing, including roofing kickout flashing, outside corners a minimum of 12 in. (305 mm). Lath has been properly installed. Although roof flashings are should be fastened every 7 in. (178 mm) vertically on not part of the wall cladding system, they are necessary each stud. The spacing of studs should not exceed 16 for proper water management. Flashing material should in. (406 mm). A similar spacing should be used on con- extend above horizontal terminations, roofing material, crete or masonry wall surfaces, when used. Do not place and drainage planes or drainage products. seams at inside/outside corner framing. All flashing material should be integrated with wa- If not installed in accordance with ASTM C1063, alter- ter resistive barriers to mitigate water penetration nate lath installation practices should be in accordance into the structure. The WRB should overlap the weep with manufacturer’s instructions. Acceptable installation screed flange. practices for metal lath should be evaluated in accor- Some applications may not require the use of flash- dance with AC191 and ASTM C933. ing, weep screeds, and casing beads to prevent water

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 11 Masonry Veneer Manufacturers Association www.masonryveneer.org penetration. In cases where there is no WRB present, a Installation of Adhered weep screed is usually not required but a weep screed or casing bead can still be used for aesthetic purposes. Manufactured Stone Veneer In cases where a drip edge is needed based on a clad- Prior to commencing installation of AMSV, ensure the ding transition, then flashing is required. The use of both WRB and flashing are properly installed and integrated. flashing and a weep screed simultaneously is not typi- Refer to the flashing details, referenced in this guide, for cally necessary. detailing around windows, doors, through-wall penetra- Movement Joints - Different elements and materials within tions, and AMSV terminations.

any structure move differently in response to applied loads 1 After the lath is installed, apply a nominal /2 in. (13 mm) or as a result of fluctuations in temperature or moisture con- thick layer of mortar ensuring the lath is completely en- tent. In determining if and where movement joints may capsulated with mortar. The mortar should be applied be needed as part of an AMSV installation, consideration with sufficient pressure and thickness to fully embed should be given to where differential movement is expect- the lath in mortar. Once the mortar is thumbprint hard, ed—for example, at the intersection of dissimilar materials; scratch (score) the surface horizontally to create the mor- or where movement may be concentrated—for example, tar scratch coat. at the transition between a framed backup assembly and a concrete masonry assembly. Additional information is Moist curing the mortar scratch coat will help reduce available in "Are Control Joints Needed with Adhered Con- cracking and ensure proper hydration during curing. Be- crete Masonry Veneer" through MVMA's website: www. fore applying AMSV, the mortar scratch coat should be masonryveneer.org. dampened so that the surface appears wet but free of standing water. Plan ahead with the various trades to integrate flash- ing and water resistive barriers to effectively shed water Before installing AMSV, lay out a minimum of 25 sq ft 2 down and out of the wall system. This may require the (2.3 m ) of AMSV units at the jobsite so there is a variety preceding trade on the job to install flashing or WRBs for of sizes, shapes, and colors from which to choose. Mix- integration with the next trade on the job. ing AMSV sizes, shapes, textures and color will allow for variety and contrast in the design to achieve the desir- Clearances able finished project. Follow AMSV manufacturers rec- ommendations regarding mixing of product to achieve On exterior frame walls, weep screeds and other base desired results. flashings should be held a minimum of 4 in. (102 mm) above grade or a minimum of 2 in. (51 mm) above paved The following guidance for grouted and tight-fit appli- 1 surfaces. This minimum can be reduced to /2 in. (13 mm) cation of adhered masonry veneer applies to conven- if the paved surface is a walking surface supported by the tional Type N and Type S mortars. If a modified mortar same foundation that supports the wall. See Figure 5. is used, some of the working properties and installation techniques may vary from those of conventional Type N Where the backing is concrete or masonry, maintain 2 in. or Type S mortars. Consult the mortar manufacturer for (51 mm) clearance from grade or ½ in. (13 mm) from a guidance and instructions. For typical details of AMSV paved surface provided that frost heave of adjacent sur- systems, please refer to Figures 1-5. faces is taken into consideration. Interior Applications Grouted Adhered Manufactured Stone Veneer Application Interior applications in non-wet locations (areas not ex- posed to water) for AMSV are similar to exterior applica- Tip: Installing AMSV from the top down will minimize tions with the following alternatives: cleanup requirements. • Two layers of WRB are not necessary behind the lath Prior to the application of mortar to the scratch coat or and scratch coat. A single layer of WRB is recom- the back of the AMSV, the scratch coat and back of the mended protect moisture sensitive materials during AMSV should be moistened so that the surfaces appear AMSV installation. damp but are free of standing water. • Interior applications are not subjected to the same The back of each AMSV should be entirely buttered with 1 fluctuations in temperature and moisture as exterior mortar to a nominal thickness of /2 in. (13 mm). Cover applications. As such, the criteria for clearances used the entire back of the AMSV, not just the perimeter. But- for exterior applications are typically not necessary. tered AMSV should be firmly worked onto the scratch Nevertheless, differential movement between differ- coat and slid slightly back and forth or with a slight ro- ent materials must still be accounted for. tating motion to set the AMSV. Modified mortars, com- plying with ANSI A118.4 or ANSI A118.15, may have a • Flashings, weep screeds, and casing beads are not different "feel" than non-modified mortars. necessary.

12 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Achieve mortar squeeze out in a volume that results in niques may be combined. The resulting thickness of the a full setting bed covering the scratch coat completely. scratch coat and setting bed should be nominally 1 in. As an alternative to the back-butter only method, mortar (25 mm) measured from the outer surface of the WRB to may be troweled onto the scratch coat, completely cov- the back surface of the unit. ering the scratch coat. Or, both mortar application tech- With the proper mortar mix, moisture content and niques may be combined. The resulting thickness of the scratch coat preparation, the installer will feel the mortar scratch coat and setting bed should be nominally 1 in. start to grab within a few seconds of the setting move- (25 mm) measured from the outer surface of the WRB to ment process. At this point, no further movement of that the back surface of the unit. AMSV should be made as the bond will be broken. If the With the proper mortar mix, moisture content, and AMSV is inadvertently moved after initial set has begun, scratch coat preparation, the installer will feel the mortar it should be removed, mortar scraped off the back of the start to grab within a few seconds of the setting move- AMSV and scratch coat, and then reinstalled following ment process. At this point, no further movement of the the application process. unit should be made as the bond will be broken. If the Tight fitted AMSV should be applied from the corners AMSV is inadvertently moved after initial set has begun, toward the middle of a wall, and from the bottom to- it should be removed, mortar scraped off the back of the ward the top of the wall. AMSV and scratch coat, and then reinstalled following the application process. Cold Weather Application Grouting the joints should be completed only after there AMSV applications should be protected from tempera- is sufficient cure time of the installed AMSV units; when tures below 40°F (4°C) during and immediately follow- mild contact with AMSV units will not break the bond to ing installation. The use of anti-freeze admixtures to low- the backup system. Grouting may be done with a grout er the freezing point of the mortar is not recommended. bag, filling joints to the desired depth, ensuring that Accelerating admixtures shall comply with ASTM C1384; mortar is forced into all voids. Grout should be “thumb- accelerating admixtures containing calcium chloride are print hard” before tooling the joints. The curing time not permitted. AMSV pieces containing visible frozen required before the grout is ready will vary significantly moisture shall not be installed. with temperature and humidity. Use a wooden raking stick or pointing tool to tool the joints to the desired The cold weather practices defined in TMS 602 should depth. Extra precaution should be taken while tooling be followed for the installation of AMSV systems. so the surface of the AMSV is not damaged. Clean off Hot Weather Application remaining grout debris on the AMSV surface with a dry, soft-bristled brush. If the environmental conditions during installation ex- To prevent mortar smearing, DO NOT use a wet brush to ceed 90°F (32°C) additional water may be needed on treat uncured mortar joints. the scratch coat surface and the backs of the AMSV be- ing installed. Providing shade and/or frequent misting Tight Fitted Adhered Manufactured of the wall may be required. Consult with mortar man- Stone Veneer Application ufacturer to determine if hot weather mortar mix op- tions are available. The hot weather practices defined Refer to Mortar section for additional guidance regarding in TMS 602 should be followed for the installation of mortar selection. For this installation technique, refer to AMSV systems. the General Mortar Considerations section. The back of the AMSV and the scratch coat should be Cleaning the Adhered Manufactured moistened with the surfaces appearing damp but free of Stone Veneer standing water. Refer to AMSV manufacturer recommendations on The back of each AMSV should be entirely buttered with cleaning and maintenance. Do not use harsh chemicals 1 mortar to a nominal thickness of /2 in. (13 mm). Cover the for cleaning, such as acid, or use abrasive tools such as entire back of the AMSV, not just the perimeter. Buttered wire brushes or power washers. AMSV should be firmly worked onto the scratch coat and slid slightly back and forth to set the AMSV. Coating Adhered Manufactured Stone Veneer Achieve mortar squeeze out in a volume that results in a full setting bed which covers the scratch coat completely. Refer to the AMSV manufacturer for recommendations As an alternative to the back-butter only method, mortar regarding the use of repellant, sealers, or other topically may be troweled onto the scratch coat, completely cov- applied coatings used for water penetration resistance, ering the scratch coat. Or, both mortar application tech- graffiti resistance, or surface sealing.

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 13 Masonry Veneer Manufacturers Association www.masonryveneer.org

Alternative Installation Methods/ rectly spraying on surfaces, pools, and Jacuzzis. Also, Materials downspouts or drainage pipes should be placed so that water is not frequently moistening the AMSV This guide covers common installation practices for units. AMSV systems. Alternative installation materials and methods not included in this guide may be introduced • Do not subject AMSV to contact with de-icing materi- into the marketplace. Example: Exterior installation als, salt, cleaning chemicals, pool chemicals, or other methods using cementitious adhesive mortars with a harsh chemicals. Prolonged exposure to these condi- direct application to a substrate that may include coat- tions may discolor the AMSV or result in surface - ings applied as loadbearing bonded water-proof mem- age. branes. • The installation of AMSV over open stud construction Alternative installation materials and methods along with (no sheathing) is not covered in this Guide. Refer to their test methods and evaluation criteria are being de- recommendations from the AMSV manufacturer. veloped. As a designer, contractor, or installer, you may • Retaining Walls—the details in this Guide only cover wish to utilize these materials and/or methods in lieu of installation of AMSV on retaining walls and required the recommended methods included in this guide. Us- waterproofing for the soil side of the wall (Figure 39). ers should verify that the alternative method(s) will meet Other details of construction of retaining walls, includ- or exceed the recommended installation practices pre- ing water management behind the wall, are outside sented in this guide. the scope of this Guide. Refer to manufacturer's recommendations for additional • Do not use AMSV on exterior stair risers (or similar sit- information regarding the use of alternative installation uations) where exposure to de-icing chemicals, snow methods or materials. and ice removal tools, where standing water is likely to occur, or when appropriate clearances cannot be Cautions maintained. The following precautions should be taken to ensure a • Do not use AMSV in applications with potential expo- successful and durable AMSV installation. sure in direct flame such as return into a firebox of a wood or gas-burning . • Do not subject AMSV to direct or frequent water contact. Examples include avoiding sprinklers di-

14 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 1. Installation Over Wood Framing

INTERIOR GYPSUM BOARD

BATT INSULATION

WOOD FRAMING

EXTERIOR GRADE SHEATHING

(2) LAYERS OF WRB

LATH

LATH FASTENERS - TYPE & SPACING PER ASTM C1063

MORTAR SCRATCH COAT

MORTAR SETTING BED

ADHERED CONCRETE MASONRY VENEER

MORTAR JOINT

WRB LAPPED OVER WEEP SCREED

WEEP SCREED

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 15 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 2. Installation Over Concrete Masonry Units

INTERIOR GYPSUM BOARD

FURRING OR CHANNEL

RIGID INSULATION

JOINT REINFORCEMENT

CMU BACKUP

LATH (OPTIONAL)

LATH FASTENER - TYPE & SPACING PER ASTM C1063

MORTAR SCRATCH COAT

MORTAR SETTING BED

ADHERED CONCRETE MASONRY VENEER

MORTARJOINT

WEEP SCREED (OPTIONAL)

16 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 3. Wall Assembly Transition

EXTERIOR FINISH (STUCCO SHOWN)

LAYERS OF WRB PER CLADDING CODE REQUIREMENTS

LAP WRB OVER SCREED/FLASHING

WEEP SCREED OR CASING BEAD (VARIES BY CLADDING TYPE)

EXTEND WRB FROM WALL BELOW 6 IN. (152 mm) MIN. ABOVE STONE CLADDING

FLASHING

BEDDING SEALANT UNDER 6 in. FLASHING (152 mm) MIN. SCRATCH COAT

MORTAR SETTING BED

ADHERED MANUFACTURED STONE VENEER

MORTAR JOINT (WHERE USED)

(2) LAYERS WRB

FASTENER

LATH

SHEATHING

BLOCKING (WHERE REQUIRED)

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 17 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 4a. Typical Frame Wall Section

WALL SYSTEM WALL SYSTEM SHEATHING USE OF LATH AND SHEATHING MORTAR SCRATCH (2) LAYERS WRB COAT (2) LAYERS WRB (OPTIONAL) LATH LATH MORTAR MORTAR SCRATCH COAT SCRATCH COAT MORTAR SETTING BED MORTAR SETTING BED ADHERED ADHERED MANUFACTURED MANUFACTURED STONE VENEER STONE VENEER MORTAR JOINT MORTAR JOINT (WHERE USED) (WHERE USED) INTERIOR EXTERIOR

WALL SYSTEM WALL SYSTEM

SHEATHING SHEATHING USE OF CEMENT BOARD (2) LAYERS WRB (2) LAYERS (OPTIONAL) WRB

CEMENT BOARD CEMENT BOARD

MORTAR MORTAR SETTING BED SETTING BED

ADHERED ADHERED MANUFACTURED MANUFACTURED STONE VENEER STONE VENEER

MORTAR JOINT MORTAR JOINT (WHERE USED) (WHERE USED)

INTERIOR EXTERIOR

18 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 4b. Typical Wall Frame Section with Continuous Rigid Insulation

SHEATHING SHEATHING USE OF LATH AND MORTAR SCRATCH COAT (2) LAYERS WRB (2) LAYERS WRB (OPTIONAL) LATH LATH

MORTAR SCRATCH MORTAR SCRATCH COAT COAT MORTAR SETTING MORTAR SETTING BED BED CONTINUOUS CONTINUOUS INSULATION INSULATION*

ADHERED ADHERED MANUFACTURED MANUFACTURED STONE VENEER STONE VENEER

MORTAR JOINT MORTAR JOINT (WHERE USED) (WHERE USED) INTERIOR EXTERIOR

USE OF CEMENT SHEATHING SHEATHING BOARD

(2) LAYERS WRB (2) LAYERS WRB (OPTIONAL)

CEMENT CEMENT BOARD BOARD

MORTAR MORTAR SETTING SETTING BED BED CONTINUOUS *SEE TABLES 3 and CONTINUOUS INSULATION* 4 FOR FASTENER INSULATION ADHERED REQUIREMENTS ADHERED MANUFACTURED OVER CONTINU- MANUFACTURED STONE VENEER OUS INSULATION STONE VENEER

MORTAR JOINT MORTAR JOINT (WHERE USED) (WHERE USED) INTERIOR EXTERIOR

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 19 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 5a. Foundation Wall Base

SHEATHING

(2) LAYERS WRB

LATH

MORTAR SCRATCH COAT

MORTAR SETTING BED

ADHERED MANUFACTURED STONE VENEER

MORTAR JOINT (WHERE USED)

FLOOR FRAMING

LAP WRB OVER WEEP SCREED FLANGE

FOUNDATION WEEP SCREED EXTEND ADHERED MANUFACTURED STONE VENEER MIN. 1 IN. (25 mm) BELOW TOP OF FOUNDATION

2 IN. (51 mm) AT PAVING (CAN BE REDUCED TO 0.5 IN. (13 mm) AT PAVING WHEN PAVING IS SUPPORTED BY SAME FOUNDATION AS WALL)

4 IN. (102 mm) AT GRADE

SLOPE GRADE 2% MIN.

20 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 5b. Foundation Wall Base Over Continuous Rigid Insulation

*SEE TABLES 3 and SHEATHING 4 FOR FASTENER LAYERS WRB REQUIREMENTS OVER CONTINU- CONTINUOUS INSULATION* OUS INSULATION LATH

MORTAR SCRATCH COAT

MORTAR SETTING BED

ADHERED MANUFACTURED STONE VENEER

MORTAR OINT WHERE USED

FLOOR FRAMING

LAP WRB OVER WEEP SCREED FLANGE

FOUNDATION WEEP SCREED

ETEND ADHERED MANUFACTURED STONE VENEER MIN. IN. BELOW TOP OF FOUNDATION

IN. AT PAVING CAN BE REDUCED TO . IN. 3 AT PAVING WHEN PAVING IS SUPPORTED BY SAME FOUNDATION AS WALL

4 IN. AT GRADE

SLOPE GRADE MIN.

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 21 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 6. Foundation Wall Base – AMSV Overlapping Foundation

SHEATHING NOTE 1: FOR CONTINUOUS INSULATION APPLICATIONS, REFER TO FIGURE 5b. (2) LAYERS WRB

LATH NOTE 2: REFER TO FIGURE 7 FOR AN ALTERNATIVE MORTAR SCRATCH COAT DETAIL FOR ACCOMMODAT- ING DIFFERENTIAL MOVE- MORTAR SETTING BED MENT THAT MAY BE PRES- ENT WHEN TRANSITIONING BETWEEN FOUNDATION AND ABOVE GRADE WALLS. ADHERED MANUFACTURED STONE VENEER

MORTAR JOINT (WHERE USED)

(2) LAYERS WRB

FLASHING 6 IN. (152 mm)

FLOOR LINE OR FOUNDATION

(2) LAYERS WRB CONTINUED (WHERE REQ'D)

FLASHING 6 IN. (152 mm) LAP WRB OVER WEEP SCREED FLANGE FOUNDATION WEEP SCREED

22 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 7. Foundation Wall – Transition to AMSV Continuing Down Foundation

SHEATHING NOTE : FOR CONTINUOUS INSULATION APPLICATIONS, REFER TO FIGURE 5b. LAYERS WRB LATH

MORTAR SCRATCH COAT

MORTAR SETTING BED

ADHERED MANUFACTURED STONE VENEER

MORTAR OINT WHERE USED LAP WRB OVER FLASHING SILL SCREED FLANGE WEEP SCREED, DRIP SCREED, OR CASING BEAD OPTIONAL FLASHING TRANSITION ETEND MIN. IN. BELOW TOP OF FOUNDATION FLASHING SLOPED TO ETERIOR BEDDING SEAL UNDER FLASHING WITH DRIP EDGE

IN. LATH WHERE REQD MORTAR SETTING BED OVER MORTAR SCRATCH COAT FLOOR LINE OR FOUNDATION

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 23 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 8a. Cladding Transition

NOTE: OTHER FINISHES MAY BE USED

EXTERIOR CLADDING ( SHOWN)

LAYERS OF WRB PER CLADDING CODE REQUIREMENTS

EXTEND WRB FROM WALL BELOW 6 IN. (152 mm) MIN. ABOVE CLADDING TRANSITION

FLASHING WITH DRIP EDGE

BLOCKING (OPTIONAL)

BEDDING SEAL UNDER FLASHING 6 IN. (152 mm) LAP LATH FASTENER

ADHERED MANUFACTURED STONE VENEER SUPPORT ANGLE -- INSTALL IF REQUIRED PER THE STONE MANUFACTURER'S INSTRUCTIONS ADHERED MANUFACTURED STONE VENEER

MORTAR SETTING BED MORTAR SCRATCH COAT

(2) LAYERS WRB LATH MORTAR JOINT (WHERE USED) SHEATHING

Flashing should be installed prior to the adhered manufactured stone. Water resistive barrier laps over the vertical leg of flashing for positive drainage. Optional support angle shown. Verify installation requirements with adhered manufactured stone veneer manufacturer.

24 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 8b. Cladding Transition Over Continuous Rigid Insulation

NOTE: OTHER FINISHES MAY BE USED EXTERIOR CLADDING (SIDING SHOWN)

LAYERS OF WRB PER CLADDING CODE REQUIREMENTS

EXTEND WRB FROM WALL BELOW 6 IN. (152 mm) MIN. ABOVE CLADDING TRANSITION

FLASHING WITH DRIP EDGE

BLOCKING (OPTIONAL)

BEDDING SEAL UNDER FLASHING 6 IN. (152 mm) LAP LATH FASTENER

ADHERED MANUFACTURED STONE VENEER SUPPORT ANGLE -- INSTALL IF REQUIRED PER THE STONE MANUFACTURER'S INSTRUCTIONS ADHERED MANUFACTURED STONE VENEER

MORTAR SETTING BED MORTAR SCRATCH COAT

(2) LAYERS WRB LATH MORTAR JOINT (WHERE USED) SHEATHING CONTINUOUS INSULATION

Flashing should be installed prior to the adhered manufactured stone. Water resistive barrier laps over the vertical leg of flashing for positive drainage. Optional support angle shown. Verify installation requirements with adhered manufactured stone veneer manufacturer.

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 25 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 9a. Outside Corner

SHEATHING

BATT INSULATION (2) LAYERS WRB

LATH -- WRAP LATH AROUND CORNER MIN. 12 IN. (305 MM)TO NEXT FRAMING MEMBER AND LAP AT FRAMING MEMBER

MORTAR SCRATCH COAT

MORTAR SETTING BED

ADHERED MANUFACTURED STONE VENEER MORTAR JOINT (WHERE USED)

EXTEND AT LEAST ONE LAYER OF WRB FROM EACH DIRECTION AROUND CORNER 12 IN. (305 MM) MIN.

WALL SYSTEM AT CORNER

ADHERED MANUFACTURED STONE VENEER ALTERNATE SHORT END RETURNS ABOVE AND BELOW AT CORNER

26 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 9b. Outside Corner Over Continuous Insulation

SHEATHING

BATT INSULATION (2) LAYERS WRB

LATH -- WRAP LATH AROUND CORNER MIN. 12 IN. (305 mm) TO NEXT FRAMING MEMBER AND LAP AT FRAMING MEMBER

CONTINUOUS INSULATION

MORTAR SCRATCH COAT MORTAR SETTING BED

ADHERED MANUFACTURED STONE VENEER MORTAR JOINT (WHERE USED) EXTEND AT LEAST ONE LAYER OF WRB FROM EACH DIRECTION AROUND CORNER 12 IN. (305 mm) MIN.

WALL SYSTEM AT CORNER

ADHERED MANUFACTURED STONE VENEER ALTERNATE SHORT END RETURNS ABOVE AND BELOW AT CORNER

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 27 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 10a. Inside Corner

ADHERED MANUFACTURED STONE VENEER ALTERNATE ENDS ABOVE AND BELOW TO INTERWEAVE CORNER

EXTEND AT LEAST ONE LAYER OF WRB FROM EACH DIRECTION AROUND CORNER 12 IN. (305 mm) MIN.

LATH - WRAP LATH AROUND CORNER 12 IN. (305 mm) MIN.TO NEXT FRAMING MEMBER AND LAP LATH AT FRAMING MEMBER

ADHERED MANUFACTURED STONE VENEER

MORTAR JOINT (WHERE USED) MORTAR SCRATCH COAT

MORTAR SETTING BED

LATH

(2) LAYERS WRB

SHEATHING

28 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 10b. Inside Corner Over Continuous Insulation

ADHERED MANUFACTURED STONE VENEER ALTERNATE ENDS ABOVE AND BELOW TO INTERWEAVE CORNER

EXTEND AT LEAST ONE LAYER OF WRB FROM EACH DIRECTION AROUND CORNER 12 IN. (305 mm) MIN.

LATH - WRAP LATH AROUND CORNER MIN. 12 IN. (305 mm) TO NEXT FRAMING MEMBER AND LAP LATH AT FRAMING MEMBER

ADHERED MANUFACTURED STONE VENEER

MORTAR JOINT (WHERE USED) MORTAR SCRATCH COAT

MORTAR SETTING BED

LATH

(2) LAYERS WRB

SHEATHING

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 29 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 11a. Horizontal Transition

NOTE: OTHER FINISHES MAY BE USED

EXTERIOR SHEATHING (SIDING SHOWN)

LAYERS OF WRB PER CLADDING CODE REQUIREMENTS FLASHING - PROVIDE END DAM AT FLASHING TERMINATION

HORIZONTAL WOOD TRIM

STRIP OF FLASHING - LAP OVER FLASHING BELOW BLOCKING FOR LATH EDGE AND FLASHING

FLASHING - PROVIDE END DAM AT FLASHING TERMINATION ABOVE FLASHING BEDDING SEAL UNDER FLASHING EXTEND WRB 6 IN. (152 mm) CASING BEAD (OPTIONAL) OVER WRB

ADHERED MANUFACTURED STONE VENEER

MORTAR SETTING BED MORTAR SCRATCH COAT

LATH (2) LAYERS WRB MORTAR JOINT (WHERE USED)

SHEATHING

30 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 11b. Horizontal Transition Over Continuous Insulation

NOTE: OTHER FINISHES MY BE USED

EXTERIOR SHEATHING (SIDING SHOWN)

LAYERS OF WRB PER CLADDING CODE REQUIREMENTS FLASHING - PROVIDE END DAM AT FLASHING TERMINATION

HORIZONTAL WOOD TRIM

STRIP OF FLASHING - LAP OVER FLASHING BELOW BLOCKING FOR LATH EDGE AND FLASHING

FLASHING - PROVIDE END DAM AT FLASHING TERMINATION

BEDDING SEAL UNDER FLASHING ABOVE FLASHING

EXTEND WRB 6 IN. (152 mm) CASING BEAD (OPTIONAL) OVER WRB

ADHERED MANUFACTURED STONE VENEER

MORTAR SETTING BED MORTAR SCRATCH COAT

LATH (2) LAYERS WRB MORTAR JOINT (WHERE USED) CONTINUOUS INSULATION SHEATHING

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 31 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 12a. Vertical Transition

BLOCKING AT LATH EDGE BACKER ROD AND SEALANT FLASHING BEHIND TRIM - CASING BEAD AT SEALANT JOINT (OPTIONAL) EXTEND UNDER ADJACENT FINISH AS REQUIRED FLASHING ADJACENT FINISH (2) LAYERS WRB - (1) LAYER UNDER FLASHING VARIES LAP (1) LAYER OVER FLASHING AND CASING BEAD

SHEATHING LATH WOOD TRIM (PRIMED) SIZE AND PROFILE MORTAR SCRATCH COAT MAY VARY 3 8 IN. (10 mm) LAP FLASHING MORTAR SETTING BED JOINT ADHERED MANUFACTURED OVER CASHING BEAD STONE VENEER 6 IN. (152 mm) MIN. MORTAR JOINT (WHERE USED)

32 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 12b. Vertical Transition Over Continuous Insulation

BLOCKING AT LATH EDGE BACKER ROD AND SEALANT FLASHING BEHIND TRIM - CASING BEAD AT SEALANT JOINT (OPTIONAL) EXTEND UNDER ADJACENT FINISH AS REQUIRED FLASHING ADJACENT FINISH (2) LAYERS WRB - (1) LAYER UNDER FLASHING VARIES LAP (1) LAYER OVER FLASHING AND CASING BEAD

SHEATHING CONTINUOUS INSULATION WOOD TRIM (PRIMED) LATH SIZE AND 3 8 IN. (10 mm) MORTAR SCRATCH COAT PROFILE MAY VARY JOINT LAP FLASHING MORTAR SETTING BED OVER CASHING BEAD ADHERED MANUFACTURED 6 IN. (152 mm) MIN. STONE VENEER

MORTAR JOINT (WHERE USED)

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 33 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 13a. Open Eave - Overhang

ADHERED MANUFACTURED STONE VENEER

MORTAR SETTING BED

MORTAR SCRATCH COAT

MORTAR JOINT (WHERE USED) FLASHING OVER WRB 6 IN. (152 mm) MIN. LAP

LATH

(2) LAYERS WRB SHEATHING

Water resistive barrier should be in place prior to soffit installation followed by adhered manufactured stone veneer.

34 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 13b. Open Eave - Overhang Over Continuous Insulation

ADHERED MANUFACTURED STONE VENEER MORTAR SETTING BED

MORTAR SCRATCH COAT MORTAR JOINT (WHERE USED) LATH FLASHING OVER WRB 6 IN. (152 mm) MIN. LAP CONTINUOUS INSULATION

(2) LAYERS WRB SHEATHING

Water resistive barrier should be in place prior to soffit installation followed by adhered manufactured stone veneer.

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 35 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 14. Open Eave - Flush

NOTE:FOR CONTINUOUS INSULATION APPLICATIONS, REFER TO FIGURE 13b.

WRB OR FLASHING

USE WOOD STOP OR 1X FILLER BEHIND FASCIA OPTION: CASING BEAD OVER FLASHING 1 IN. (25 mm) MIN. LAP OVER TOP OF ADHERED MANUFACTURED STONE VENEER ADHERED MANUFACTURED STONE VENEER

MORTAR SETTING BED MORTAR SCRATCH COAT

MORTAR JOINT (WHERE USED)

LATH FLASHING OVER WRB 6 IN. (152 mm) MIN. LAP (2) LAYERS WRB

SHEATHING

Water resistive barrier should be in place prior to soffit installation followed by adhered manufactured stone veneer.

36 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 15. Rake - Overhang

NOTE:FOR CONTINUOUS INSULATION APPLICATIONS, REFER TO FIGURE 13b.

FLASHING OR WRB STRIP BEHIND TRIM - LAP OVER (2) LAYERS WRB AT WALL

BACKER ROD AND SEALANT CASING BEAD (OPTIONAL) ADHERED MANUFACTURED STONE VENEER MORTAR JOINT (WHERE USED) MORTAR SETTING BED FLASHING OVER WRB

4 IN. (102 mm) MIN. LAP MORTAR SCRATCH COAT LATH (2) LAYERS WRB SHEATHING

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 37 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 16. Rake - Flush

NOTE:FOR CONTINUOUS INSULATION APPLICATIONS, REFER TO FIGURE 13b.

FLASHING OR WRB STRIP BEHIND TRIM LAP OVER WRB AT WALL

BACKER ROD AND SEALANT

1 IN. (25 mm) MIN. LAP OVER TOP OF ADHERED MANUFACTURED STONE VENEER

CASING BEAD OVER (OPTIONAL) (2) LAYERS WRB - OPTION: USE WOOD STOP OR 1X FILLER BEHIND SUB-FASCIA ADHERED MANUFACTURED STONE VENEER

MORTAR JOINT (WHERE USED)

MORTAR SETTING BED MORTAR SCRATCH COAT FLASHING OVER WRB 4 IN. (102 mm) MIN. LAP LATH (2) LAYERS WRB SHEATHING

38 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 17a. Side Wall – Composition Shingles

ADHERED MANUFACTURED STONE VENEER MORTAR SETTING BED

MORTAR SCRATCH COAT

MORTAR OINT WHERE USED LATH

BLOCING FOR LATH EDGE AND FLASHING LAYERS WRB LAP OVER STEP FLASHING AND WEEP SCREED

STEP FLASHING AT RAE PER ROOF MANUFACTURERS RECOMMENDATIONS

WEEP SCREED - LAP OVER STEP FLASHING IN. MIN. ROOF TYPE MAY VARY - IN. MIN. COMPOSTION SHINGLE ROOF SHOWN

ROOF UNDERLAYMENT - TURN UP AT SIDE WALL

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 39 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 17b. Side Wall – Composition Shingles Over Continuous Insulation

CONTINUOUS INSULATION ADHERED MANUFACTURED STONE VENEER MORTAR SETTING BED

MORTAR SCRATCH COAT

MORTAR OINT WHERE USED LATH

BLOCING FOR LATH EDGE AND FLASHING LAYERS WRB LAP OVER STEP FLASHING AND WEEP SCREED

STEP FLASHING AT RAE PER ROOF MANUFACTURERS RECOMMENDATIONS

WEEP SCREED - LAP OVER STEP FLASHING IN. MIN. ROOF TYPE MAY VARY - IN. MIN. COMPOSTION SHINGLE ROOF SHOWN

ROOF UNDERLAYMENT - TURN UP AT SIDE WALL

40 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 18. Side Wall – Composition Shingles Curbing

NOTE:FOR CONTINUOUS INSULATION APPLICATIONS, REFER TO FIGURE 17b. ADHERED MANUFACTURED STONE VENEER

(2) LAYERS WRB LAP OVER WEEP SCREED AND COUNTERFLASHING

BLOCKING FOR LATH EDGE AND FLASHING

WEEP SCREED

MIN. COUNTERFLASHING 2 IN. (51 mm)

STEP FLASHING AT RAKE PER ROOF MANUFACTURER'S RECOMMENDATION 2 IN. MIN. (51 mm)

ROOF TYPE MAY VARY - COMPOSTION SHINGLE 2 IN. MIN.

(51 mm) ROOF SHOWN

ROOF UNDERLAYMENT - TURN UP AT SIDE WALL 1X FILLER - SLOPE TOP

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 41 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 19. Side Wall – Tile Roofing

NOTE:FOR CONTINUOUS INSULATION APPLICATIONS, REFER TO FIGURE 17b.

ADHERED MANUFACTURED STONE VENEER

MORTAR SETTING BED

MORTAR SCRATCH COAT

LATH

BLOCKING FOR LATH EDGE AND FLASHING (2) LAYERS WRB LAP OVER WEEP SCREED

WEEP SCREED OR DRIP SCREED LAP OVER RAKE WALL FLASHING 2 IN. (51 mm) MIN.

SIDE WALL FLASHING PER ROOF MANUFACTURER'S 2 IN. MIN.

(51 mm) RECOMMENDATION

ROOF TYPE MAY VARY - TILE ROOF SHOWN ROOF UNDERLAYMENT - TURN UP AT SIDE WALL

42 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 20. Side Wall – Tile Roofing Curbing

NOTE:FOR CONTINUOUS INSULATION APPLICATIONS, REFER TO FIGURE 17b.

ADHERED MANUFACTURED STONE VENEER

(2) LAYERS WRB - LAP OVER WEEP SCREED AND FLASHING

SCREED OR DRIP SCREED BLOCKING FOR LATH EDGE AND FLASHING

COUNTERFLASHING

1X FILLER MIN. LAP 2 IN. (51 mm) SIDE WALL FLASHING PER ROOF 2 IN. MIN. MANUFACTURER'S

(51 mm) RECOMMENDATION

ROOF TYPE MAY VARY - TILE ROOF SHOWN ROOF UNDERLAYMENT - TURN UP AT SIDE WALL

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 43 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 21a. Window Sill

WINDOW FRAME PROFILE MAY VARY - REFER TO WINDOW MANUFACTURERS DETAILS FOR INSTALLATION AND FLASHING

BEDDING SEALANT UNDER WINDOW FIN IF REQUIRED PER WINDOW MANUFACTURERS INSTRUCTIONS

AIR SEAL BACER ROD AND SEALANT

CASING BEAD OPTIONAL

3 IN.

SILL FLASHING UNDER WINDOW FIN LAP OVER WRB 4 IN. MIN. ADHERED MANUFACTURED STONE VENEER WITH SLOPED TOP MORTAR SETTING BED

MORTAR OINT WHERE USED

ADHERED MANUFACTURED STONE VENEER MORTAR SCRATCH COAT

LATH

LAYERS WRB UNDER SILL FLASHING SHEATHING

Rough openings must be properly flashed prior to window installation. Tuck water resistive barrier under flashing at sill. Sill flashing should drain to the exterior of the primary WRB or to exterior of adhered manu- factured stone veneer.

44 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 21b. Window Sill Over Continuous Insulation

WINDOW FRAME PROFILE MAY VARY - REFER TO WINDOW MANUFACTURERS DETAILS FOR INSTALLATION AND FLASHING BEDDING SEALANT UNDER WINDOW FIN IF REQUIRED PER WINDOW MANUFACTURERS INSTRUCTIONS

BACER ROD AND SEALANT AIR SEAL CASING BEAD OPTIONAL

3 IN. FLASHING

SILL FLASHING UNDER WINDOW FIN LAP OVER WRB 4 IN. MIN. ADHERED MANUFACTURED STONE VENEER WITH SLOPED TOP MORTAR SETTING BED MORTAR OINT WHERE USED ADHERED MANUFACTURED STONE VENEER MORTAR SCRATCH COAT

CONTINUOUS INSULATION LATH

LAYERS WRB UNDER SILL FLASHING SHEATHING

Rough openings must be properly flashed prior to window installation. Tuck water resistive barrier under flashing at sill. Sill flashing should drain to the exterior of the primary WRB or to exterior of adhered manu- factured stone veneer.

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 45 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 22. Window Jamb

NOTE:FOR CONTINUOUS INSULATION APPLICATIONS, REFER TO FIGURE 21b.

WINDOW FRAME PROFILE MAY VARY - REFER TO WINDOW MANUFACTURER'S DETAILS FOR INSTALLATION AND FLASHING JAMB FLASHING UNDER WINDOW FIN

BEDDING SEALANT UNDER WINDOW FIN SHEATHING (2) LAYERS WRB SEAL EDGE TO FIN LATH MORTAR SCRATCH COAT

3 8 IN. MORTAR SETTING BED (10 mm) MORTAR JOINT (WHERE USED) ADHERED MANUFACTURED STONE VENEER BEDDING SEALANT UNDER WRB LAPPED OVER CASING BEAD

CASING BEAD (OPTIONAL) LAP FLASHING OVER LEG BACKER ROD AND SEALANT

Rough openings must be properly flashed prior to window installation. Backer rod and sealant between the window frame and the adhered manufactured stone veneer allows for movement between the dis- similar materials.

46 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 23. Window Head

NOTE:FOR CONTINUOUS INSULATION APPLICATIONS, REFER TO FIGURE 21b.

SHEATHING

(2) LAYERS WRB LATH MORTAR SCRATCH COAT MORTAR SETTING BED

ADHERED MANUFACTURED STONE VENEER MORTAR JOINT (WHERE USED) ADHERED MANUFACTURED STONE VENEER KEY OR TRIM (WHERE OCCURS)

LAP WRB OVER HEAD FLASHING AND SEAL EDGE

OVER HEAD FIN DRIP SCREED OR CASING BEAD

9 IN. (229 mm) MIN. FLASHING 3 8 IN. (10 mm) HEAD FLASHING SET IN SEALANT (WIDTH TO COVER JAMB TREATMENT)

OPTIONAL BACKER ROD AND SEALANT

BEDDING SEALANT UNDER WINDOW FIN

WINDOW FRAME PROFILE MAY VARY - REFER TO WINDOW MANUFACTURER'S DETAILS FOR INSTALLATION AND FLASHING

Flashing and WRB installed shingle fashion may be complimented with self-adhered flashing (SAF) to seal WRB to window frame.

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 47 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 24. Kick-Out Flashing

ADHERED MANUFACTURED STONE VENEER

ROOFING MATERIAL

(2) LAYERS WRB LAP OVER SCREED AND STEP FLASHING

WEEP SCREED

STEP FLASHING AT ROOFING LAP OVER KICK-OUT FLASHING

KICK-OUT FLASHING - SEAL OVER EAVE FLASHING

SHINGLE LAP ALL WALL FLASHING PIECES WITH WRB UNDERLAYMENT PER ROOF MANUFACTURER

EAVE DRIP EDGE FLASHING

GUTTER

WRB STRIP BEHIND TRIM LAP OVER WRB AT WALL

48 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 25. Cricket

EXTEND CRICKET MIN. 2 IN. (51 mm) BEYOND CHASE

TYPICAL CRICKET PER ROOF MANUFACTURER'S RECOMMENDATIONS DETAIL 25.2 (2) LAYERS WRB

WEEP SCREED

COUNTERFLASHING

ADHERED MANUFACTURED STONE VENEER OVER FRAMED WALL OR CHASE DETAIL 25.3

(2) LAYERS WRB

EXTEND FLASHING 2 IN. (51 mm) BEYOND CHASE - EACH SIDE TO ACCOMODATE INSTALLATION OF ADHERED MANUFACTURED STONE VENEER SEE DETAIL 23.3 2 IN. (51 mm) MIN.

COMPOSITION SHINGLE ROOFING (OTHER ROOFING SIMILAR) UNDERLAYMENT OVER ROOF SUBSTRATE - LAP OVER CRICKET FLANGE CRICKET - PROVIDE SHEATHING AND FRAMING SUPPORT AS NEEDED

DETAIL 25.1

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 49 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 26. Chimney Chase

METAL CHIMNEY CAP PER PLAN SOLID SUBSTRATE - SLOPE 4:, MIN. ROOFING UNDERLAYMENT IN. WIDE FLASHING OR WRB STRIP LAP OVER WRB AT WALL

SHIM AS REQUIRED OR BLOCING AS REQUIRED

3 4 IN. STUCCO EY OPTION: USE WOOD STOP OR CASING BEAD OVER FLASHING TRIM

IN. MIN. LAP OVER TOP OF ADHERED MANUFACTURED CHIMNEY CHASE NOTE: STONE VENEER MAINTAIN MINIMUM CLEARANCE OF DIMENSION TO CLEAR TOP COMBUSTIBLE OF A.C.M.V. MATERIALS PER ADHERED MANUFACTURED CHIMNEY STONE VENEER MANUFACTURERS RECOMMENDATIONS MORTAR OINT WHERE USED MORTAR SETTING BED MORTAR SCRATCH COAT LATH LAYERS WRB SHEATHING

50 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 27. Column Base

LATH

MORTAR SCRATCH COAT

MORTAR JOINT (2) LAYERS WRB

EXTERIOR GRADE SHEATHING - MAINTAIN 1 IN. (25 mm) MIN. ABOVE CONCRETE FRAMED WALL SYSTEM

WEEP SCREED OR DRIP SCREED

BEDDING SEAL UNDER FLAHSING

1 2 IN. (13 mm) MIN.

A minimum one half inch (13 mm) clearance should be maintained at all sides of the base. All column materi- als to be exterior grade. Do not extend flashing past edge of AMSV for safety reasons.

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 51 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 28. Penetration, Flanged

CUT WRB DIAGONALLY FROM TOP CORNERS PENETRATION FLANGE (1) LAYER WRB

APPLY (1) LAYER SELF-ADHERED FLASHING (SAF) OVER WRB UNDER PENETRATION FLANGE

STEP 1

SEAL DIAGONAL CUTS IN WRB WITH (1) LAYER SAF

SEAL TOP FLAP OF WRB APPLY (1) LAYER SAF OVER TOP FLAP

APPLY (1) LAYER SAF OVER WRB EACH SIDE AND UNDER TOP FLAP OF CUT WRB

NOTE: 2ND LAYER OF WRB (OUTER LAYER) TO BE APPLIED OVER FLANGE AND FLASHING OF PENETRATION

STEP 2

Penetration with flanges can be incorporated into the wall system by applying WRB in a watershed fashion and sealing cuts in the WRB with self-adhered flashing. Drawing illustrates installation with housewrap WRB. Installation with building paper WRB would be similar but instead of 45 degree cuts, fit last piece of WRB on top of flanges and tuck under WRB course above penetration.

52 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 29. Penetration Non-Flanged, with Building Paper WRB

UPPER COURSE WRB LAPPED MIN. 2 IN. (51 mm)

(1) LAYER WRB TRIM TO FIT AROUND PENETRATION

APPLY FLEXIBLE SELF-ADHERED FLASHING (SAF) AND SEALANT AROUND PENETRATION NON-FLANGED PENETRATION

LOWER COURSE WRB (BUILDING PAPER) STEP 1

TUCK UNDER UPPER COURSE OF WRB MIN. 2 IN. (51 mm)

(1) LAYER WRB

NON-FLANGED PENETRATION

(1) LAYER WRB - APPLY OUTER LAYER WRB OVER FLASHING AT PENETRATION AND TRIM TO FIT AROUND PENETRATION

STEP 2

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 53 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 30. Penetration Non-Flanged, with Housewrap WRB

WRB CUT AT APPROIMATELY 4 ANGLE UP FROM PENETRATION HOLD FLAP UP AND AWAY FOR FLEIBLE SELF-ADHERED FLASHING SAF TO BE SEALED AT PENETRATION

SHEATHING BEHIND

LAYER WRB TRIM TO FIT AROUND PENETRATION

APPLY FLEIBLE SAF AND OR SEALANT AROUND PENETRATION

NON-FLANGED PENETRATION

LAYER WRB

FLAP OF WRB FOLDED UP

STEP FLEIBLE SAF

NON-FLANGED PENETRATION

PLACE FLAP OF WRB ON ETERIOR SIDE OF FLEIBLE SAF - SEAL CUTS IN WRB WITH SAF

LAYER WRB

APPLY FLEIBLE SAF SEALING TO PENETRATION AND WRB

NON-FLANGED PENETRATION FLAP OF WRB FOLDED DOWN ON TOP OF SAF AROUND PIPE

FLEIBLE SAF SEALING STEP CUTS IN WRB NOTE: NON-FLANGED APPLY LAYER OF WRB OUTER LAYER PENETRATION OVER FLASHING AT PENETRATION AND FLEIBLE SAF TRIMMED TO FIT AROUND PENETRATION

54 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 31. Penetration, Fixture

INSULATION WALL SYSTEM SHEATHING (2) LAYERS WRB*

LATH

BED EXTERIOR FLANGE IN SEALANT PLASTER RING

MORTAR SETTING BED

ADHERED MANUFACTURED STONE VENEER

MORTAR SCRATCH COAT

(2) LAYERS WRB

MORTAR JOINT (WHERE USED)

LATH INTERIOR EXTERIOR

*SEE FIGURES 29, 30, AND 31 FOR FLASHING OPTIONS.

Plaster rings should be affixed over the service box to bring the face of the box flush with the adhered manu- factured stone veneer. Bed the exterior flange in sealant. Water resistive barrier should be installed snugly around the plaster ring flange.

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 55 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 32. Penetration, Dryer Vent

NOTE: SEAL AROUND ANNULAR SPACE OF ADHERED MANUFACTURED PENETRATION. STONE VENEER

MORTAR JOINT (WHERE USED)

MORTAR SETTING BED

MORTAR SCRATCH COAT

BED EXTERIOR FLANGE IN SEALANT

EXTERIOR DRYER VENT

LATH

(2) LAYERS WRB*

SHEATHING

WALL SYSTEM

INTERIOR EXTERIOR

*SEE FIGURES 29, 30, AND 31 FOR FLASHING OPTIONS

56 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 33. Deck Termination

SHEATHING

LATH MORTAR SCRATCH COAT

MORTAR SETTING BED ADHERED MANUFACTURED STONE VENEER

MORTAR OINT WHERE USED

LAYERS WRB

LAP WRB OVER WEEP SCREED OR FLASHING

FLASHING OR WEEP SCREED

MIN. FLOOR FRAMING IN.

LEDGER

DEC FRAMING

ADHERED MANUFACTURED STONE VENEER

FLASHING

MORTAR SETTING BED

MORTAR SCRATCH COAT

LAYERS WRB

LATH SHEATHING

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 57 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 34. Wall Cap

ADHERED MANUFACTURED STONE VENEER CAP IN MORTAR SETTING BED

LEVEL SCRATCH COAT AT TOP OF WALL

LATH OVER TOP OF WALL - LAP OVER WALL LATH 4 IN. (102 mm) MIN. FASTEN LATH AT VERTICAL WALL FACES ONLY

FLASHING OVER TOP OF WALL CONSTRUCTION. LAP OVER WRB 1 IN. (25 mm) SLOPING SOLID SHIM MIN. (e.g. BEVELED SIDING)

ADHERED MANUFACTURED STONE VENEER

MORTAR SETTING BED

MORTAR JOINT (WHERE REQUIRED)

MORTAR SCRATCH COAT

WRB (WHERE REQUIRED)

SHEATHING WALL SYSTEM

WEEP SCREED OR DRIP SCREED

BEDDING SEAL UNDER FLASHING MIN. 2 IN. (51 mm)

58 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 35. Wall Assembly – Rainscreen System – Membrane System

NOTE: WHERE PERMITTED, RAINSCREEN MAY REPLACE (1) LAYER OF WRB

ADHERED MANUFACTURED STONE VENEER MORTAR SETTING BED

MORTAR SCRATCH COAT LATH

(1) LAYER WRB OR MORTAR SCREEN DRAINAGE MEDIUM

(1) LAYER WRB SHEATHING

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 59 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 36. Wall Assembly – Rainscreen System – Strapped

NOTE: WHERE PERMITTED, RAINSCREEN MAY REPLACE (1) LAYER OF WRB

ADHERED MANUFACTURED STONE VENEER MORTAR SETTING BED

MORTAR SCRATCH COAT PRESSURE TREATED FURRING* 8 IN. (203 mm) O.C. LATH

(1) LAYER WRB OR MORTAR SCREEN

(1) LAYER WRB SHEATHING

60 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 37. Foundation Wall Base – Rainscreen System

NOTE: WHERE PERMITTED, RAINSCREEN MAY REPLACE (1) LAYER OF WRB SHEATHING

WRB DRAINAGE MEDIUM

MORTAR SCREEN / WRB

LATH

MORTAR SCRATCH COAT

MORTAR SETTING BED

ADHERED MANUFACTURED STONE VENEER MORTAR JOINT (WHERE USED) FLOOR FRAMING LAP WRB OVER WEEP SCREED FLANGE

WEEP SCREED, DRIP SCREED, OR CASING BEAD

FOUNDATION WEEP SCREED OR WEEP SCREED

EXTEND ADHERED MANUFACTURED STONE VENEER MIN. 1 IN. (25 mm) BELOW TOP OF FOUNDATION 2 IN. (51 mm) MIN. AT PAVING (CAN BE REDUCED TO 0.5 IN. (13mm) AT PAVING WHEN PAVING IS SUPPORTED BY SAME FOUNDATION AS WALL)

4 IN. (102 mm) MIN. AT GRADE

SLOPE GRADE 2% MIN.

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 61 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 38. Typical Wall Section – Rainscreen System

NOTE: WHERE PERMITTED, RAINSCREEN MAY REPLACE (1) LAYER OF WRB WALL SYSTEM

SHEATHING

WRB

DRAINAGE MEDIUM

MORTAR SCREENWRB LATH

MORTAR SCRATCH COAT

MORTAR SETTING BED

ADHERED MANUFACTURED STONE VENEER

MORTAR OINT WHERE USED

INTERIOR ETERIOR

62 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 39. Retaining Wall (CMU)

APPLIED LIQUID WATERPROOF COATING

GRAVEL BACKFILL APPROXIMATELY 2 IN. (51 mm) MIN. AT GRADE 6 IN. (152 mm) WIDE PROVIDE DRAINAGE AT FOOTING 1 2 IN. (13 mm) MIN. AT PAVING LANDSCAPE CLOTH (OPTIONAL)

ADHERED MANUFACTURED STONE VENEER CAP IN MORTAR SETTING BED

1 IN. (25 mm) MIN.

LEVEL SCRATCH COAT AT TOP OF WALL

ADHERED MANUFACTURED STONE VENEER MORTAR SETTING BED

MORTAR JOINT (WHERE USED)

CMU WALL SYSTEM WATERPROOFING (WHEN REQUIRED)

NOTE: THIS 1 2 IN. (13 mm) MIN. AT PAVING DETAIL COVERS ONLY INSTALLATION OF 2 IN. (51 mm) MIN. AT GRADE AMSV ON THE SOIL SIDE OF THE WALL. OTHER DETAILS OF CONSTRUCTION OF RETAINING WALLS, INCLUDING WATER MANAGEMENT BEHIND THE WALL ARE OUTSIDE OF THE SCOPE OF THIS GUIDE. GRADE

SECTION VIEW

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 63 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 40. Stone Wrap Under Straight Overhang

IF INSIDE CORNER IS NOT COVERED BY ROOF, PERFORM SAME DETAIL AS THE FRONT

1ST LAYERS WRB

2ND LAYERS WRB

WIRE LATH

FRAMING MORTAR SCRATCH COAT

COVERED ROOF SOFFIT MORTAR SETTING BED

EXTERIOR SHEATHING

SELF-ADHERED FLASHING (SAF) AT CORNERS

(2) LAYERS WRB (1) LAYER TO EXTENDS UP BEHIND SOFFIT ADHERED MANUFACTURED STONE WEEP SCREED

MORTAR SETTING BED MORTAR SCRATCH COAT

ADHERED MANUFACTURED STONE SEE TABLE 2 FOR RECOMMENDATIONS ON SETTING BED MORTAR FOR NON-VERTICAL APPLICATION.

64 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 41a. Forward Mounted Commercial Window

(2) LAYERS WRB WRAPPED INTO ROUGH OPENING

CORNER UNIT

OPTIONAL CASING BEAD (NOT SHOWN) BACKER ROD, SEALANT WINDOW JAMB

JAMB DETAIL

(2) LAYERS WRB WRAPPED INTO ROUGH OPENING

SELF ADHERED FLASHING MEMBRANE

LATH

FIELD FAB CUSTOM DRIP CAP

BACKER ROD, SEALANT

OPTIONAL CASING BEAD (NOT SHOWN) PAN FLASHING

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 65 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 41b. Forward Mounted Commercial Window Over Continuous Insulation

(2) LAYERS WRB WRAPPED INTO ROUGH OPENING

CONTINUOUS INSULATION

CORNER UNIT

OPTIONAL CASING BEAD (NOT SHOWN) BACKER ROD, SEALANT WINDOW JAMB

JAMB DETAIL (2) LAYERS WRB WRAPPED INTO ROUGH OPENING

CONTINUOUS INSULATION

SELF ADHERED FLASHING MEMBRANE LATH FIELD FAB CUSTOM DRIP CAP

BACKER ROD, SEALANT

OPTIONAL CASING BEAD (NOT SHOWN) PAN FLASHING LATH CONTINUOUS INSULATION

66 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 42. Forward Mounted Commercial Window— Top View

NOTE:FOR CONTINUOUS INSULATION APPLICATIONS, REFER TO FIGURE 41b.

(2) LAYERS WRB WRAPPED INTO ROUGH OPENING

CORNER UNIT

BACKER ROD, SEALANT

WINDOW JAMB

OPTIONAL CASING BEAD (NOT SHOWN)

SECTION VIEW

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 67 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 43. Commercial Storefront Window—Top View

NOTE:FOR CONTINUOUS INSULATION APPLICATIONS, REFER TO FIGURE 41b.

(2) LAYERS WRB WRAPPED INTO ROUGH OPENING

TRIM MATERIALS SPECIFIED BY OTHERS

WINDOW JAMB

CASING BEAD OPTIONAL (NOT SHOWN)

BACKING ROD, SEALANT

68 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 44. Commercial Storefront Window

NOTE:FOR CONTINUOUS INSULATION APPLICATIONS, REFER TO FIGURE 41b. (2) LAYERS WRB WRAPPED INTO ROUGH OPENING OPTIONAL CASING BEAD (NOT SHOWN)

BACKER ROD, SEALANT

TRIM MATERIALS SPECIFIED BY OTHERS WINDOW JAMB

JAMB DETAIL

(2) LAYERS WRB WRAPPED INTO ROUGH OPENING SELF ADHERED FLASHING MEMBRANE DRIP CAP

BEDDING SEAL

TRIM MATERIALS SPECIFIED BY OTHERS

SLOPPED SILL SPECIFIED BY OTHERS OPTIONAL CASING BEAD (NOT SHOWN)

PAN FLASHING

BACKER ROD, SEALANT

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 69 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 45. Wall—Section Multi-Floor Joint Detail

NOTE:FOR CONTINUOUS INSULATION APPLICATIONS, REFER TO FIGURE 41b. LAP WRB OVER FLASHING SILL SCREED FLANGE

WRB

WEEP SCREED, DRIP SCREED, OR WEEP CASING BEAD

BEDDING SEAL UNDER

FLASHING WITH DRIP EDGE SIZED PER THICKEST STONE

FLASHING

DETAIL

SHEATHING

MORTAR SCRATCH COAT

MORTAR SETTING BED

ADHERED MANUFACTURED STONE VENEER

1 IN. (25 mm) MIN. SEE DETAIL ABOVE

(2) LAYERS WRB

MORTAR JOINT (WHERE USED)

LATH

WALL SYSTEM

70 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 46a. Wall—Section CMU

MASONRY WALL SYSTEM (CMU SHOWN)

WRB (OPTIONAL)

LATH (OPTIONAL)

MORTAR SCRATCH COAT (USED WITH LATH)

MORTAR SETTING BED

ADHERED MANUFACTURED STONE VENEER

LATH FASTENER

MORTAR JOINT (WHERE USED)

INTERIOR EXTERIOR

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 71 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 46b. Wall—Section Over Continuous Rigid Insulation

MASONRY WALL SYSTEM (CMU SHOWN)

WRB (OPTIONAL)

LATH

MORTAR SCRATCH COAT (USED WITH LATH)

MORTAR SETTING BED

CONTINUOUS INSULATION

ADHERED MANUFACTURED STONE VENEER

LATH FASTENER

MORTAR JOINT (WHERE USED)

INTERIOR EXTERIOR

72 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 47. Wall-Section Parapet with Stone Cap

LATH OVER TOP OF WALL - LAP OVER WALL LATH 4 IN. (102 mm) MIN. FASTEN ADHERED MANUFACTURED LATH AT VERTICAL WALL STONE VENEER CAP IN FACES ONLY MORTAR SETTING BED

KERF* LEVEL SCRATCH COAT AT BACKER ROD & SEALANT TOP OF WALL

1IN. (25 mm) MIN. SLOPING SOLID SHIM (e.g. BEVELED SIDING)

FLASHING OVER TOP OF WALL CONSTRUCTION. LAP OVER WRB MORTAR SETTING BED

SHEATHING

SCRATCH COAT SCUPPER LATH 1X FILLER - SLOPE TOP

ADHERED MANUFACTURED STONE VENEER ROOF UNDERLAYMENT - TURN UP AT SIDE WALL MORTAR JOINT (WHERE USED)

(2) LAYERS WRB

CONTINUOUS INSULATION

*Kerfs are typically not a molded feature of manufactured stone units, but instead are field-cut features where desired.

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 73 Masonry Veneer Manufacturers Association www.masonryveneer.org

Figure 48. Wall-Section Parapet with Steel Cap

1 IN. (25 mm)

SLOPED METAL COPING SYSTEM

PRESSURE TREATED BLOCKING

MEMBRANE FLASHING EXTEND OVER TOP OF PARAPET STYLE PER ARCH.

SEALANT, TYPICAL DRIP EDGE PER ARCH. SHEATHING

MORTAR SETTING BED SCUPPER

SCRATCH COAT ROOF SYSTEM PER ARCH. LATH

ADHERED MANUFACTURED STONE VENEER

MORTAR JOINT (WHERE USED)

(2) LAYERS WRB

CONTINUOUS INSULATION

74 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org

Notes:

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 75 Masonry Veneer Manufacturers Association www.masonryveneer.org

Notes:

76 March 2018 Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing Masonry Veneer Manufacturers Association www.masonryveneer.org Masonry Veneer Manufacturers Association Associate Members

BASF www.basf.com

ClarkDietrich Building Systems www.clarkdietrich.com

Laticrete International Inc. https://laticrete.com

PermaBase Cement Board (National Gypsum) www.nationalgypsum.com

Plastic Components Inc. http://plasticomponents.com/

Smooth-On, Inc. www.smooth-on.com/

SPEC MIX, Inc. www.specmix.com/

Installation Guide for Adhered Manufactured Stone Veneer, 5th Edition, 2nd Printing March 2018 77 Masonry Veneer Manufacturers Association

For additional information or questions on the items contained here, please contact NCMA at: (703) 713-1900 Copyright © 2017 NCMA All Rights Reserved. NCMA and its respective logos are trademarks of NCMA. In the United States and other countries.