FIXED CDF

CDF 40

Function The CDF 40 is an energy efficient and quiet dehumidifier. It works in accordance with the condensation principle. A draws the humid air into the dehumidi- fier and through an coil. When passing through the evaporator the air is cooled down to below its dew point temperature, and its content of water vapour is condensed into water, which falls into the drip tray and then is led from the drip tray to a drain. The cold, dry air is then passed over the condenser coil where it is re-heated, before leaving the unit at a temperature, which is ap- prox. 5°C higher than at the inlet.

Applications • Archives • Museums • Churches • Changing rooms • Waterworks

FEATURES

Dehumidifier • Built into a strong and robust powder coated hot galvanized sheet metal cabinet • Evaporator and condenser coils are epoxy-coated for high corrosion resistance • Fixed to the wall by means of a wall mounting strip supplied with the unit • Condensate outlet located at the bottom. Outlet stub can be connected to a ¾” hose • Outside connection to mains

Control • Built in electronic hygrostat and • Integrated ON/OFF control of and temperature (electric or coils as accessories) • 0-VOLT connection for alarm • 230 V for control valve, exhaust fan and pump/ • RS 485 gate for BMS (Modbus)

Diodes BLUE: Power connected, standby mode GREEN: ON, deicing YELLOW: Remote pairing mode RED: Errors

Defrosting Active, demand-controlled defrosting is incorporated in the electronic control.

Service For easy service the circuit is supplied with a service valve. The PCB has a USB gate for history data logging for easy fault finding. FIXED DEHUMIDIFIERS CDF

TECHNICAL DATA

Model CDF 40 Operating range – humidity 40 – 100 %RH Operating range – temperature 3 – 32°C Air volume 400 m3/h Power supply 1x230 V/50 Hz Max. ampere consumption 3,4 A Max. power consumption 0,78 kW Refrigerant R407C Quantity of refrigerant 0,7 kg Compressor Rotary Fan CDF 40 Radial Sound level (at 1 metre) 46 dB(A) Weight 56,5 kg Filter 40% 60% 80% G3 PPI 15 Colour3 (Cabinet/Front)0,08 0,13 0,16 gæt RAL 9005/9006 Protection10 0,19class 0,32 0,47 IPX4 Corrosion15 protection0,23 in0,5 accordance1,02 with EN/ISO 12944-2 C4 20 0,3 0,68 1,35 30 0,55 1,25 1,92 gæt CAPACITY32 CURVES0,67 1,45 2,14

capacity CDFcurve 40 for CDF 40 40% Temp. °C 40% RH 60% RH 80% RH 60% 35 80%

30

25

20

15

10

5

0 0 0,5 1 1,5 2 2,5 l/hL/H

Specific energy consumption (SEC): 0,80 kWh/l at 20°C & 60% RH

INSTALLATION

dantherm.com FIXED DEHUMIDIFIERS CDF

DIMENSIONS CDF 40 430,2 327,8 59,1 430,2 56,4 326,1 326,1 699,9 769,2 699,9 769,2 699,9

1010

CDP 40 - 1010 315,6 315,6

CDPCDF40 501010 - 1160 1010 314,5 CDPCDF50 70 - 1495 1160

CDF 70 1495 Drain outlet position

P Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearance according to reference 3

A

DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only entended as a guide. table LZT 142 0001, category 8 R

5

T

P

3

1

Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearanceN according to reference

A

MATERIAL: REV. BY: O

5 DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only intended as a guide. table LZT 142 0001, category 8 R

5

T THICKNESS: WEIGHT: g DATE: 1

1

N

2 MATERIAL: REV. BY: O

5 This Drawing is furnished with the understanding that the REF.: essence there of will not be reproduced in whole or in part THICKNESS: "Thickness@@part1.SLDPRT"mm WEIGHT: 988453.42g DATE: 1 without written authorization by Dantherm Air Handling A/S. CDP Large DATE: All designs originated by Dantherm Air Handling A/S are the 4

property of said Company and will be protected by Patents. R This Drawing is furnished with the understanding that the PART NO REV.: E REF.: bof

V

.

essence there of will not be reproduced in whole or in part CDP Large : without written authorizationSCALE: NOT by Dantherm TO SCALE Air Handling A/S. CDF 50 DATE: 19-08-2017 All designs originated by Dantherm Air Handling A/S are the 351512

property of said Company and will be protected by Patents. R

PART NO REV.: E

V

430,2430,2 .

CDF 50 :

56,4 SCALE: NOT TO SCALE 351514 56,4 430,2 430,2 326,1 59,1 327,8 59,1

RecommendedDETAIL A installation of CDF 40 SCALE 1 : 2 769,2 699,9 Min. 225 Min. Min. 225 699,9 A

CDP 40 - 1010 315,6

CDP 50 - 1160

CDP 70 - 1495

CDF40 1010 727 314,5 727 CDF50 1160

CDF 70 1495

P Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearance according to reference 3

A

DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only entended as a guide. table LZT 142 0001, category 8 R

5

T

1

N

MATERIAL: REV. BY: O

5

THICKNESS: WEIGHT: g DATE: 1 Min. 225 Min.

2 Min. 225

This Drawing is furnished with the understanding that the REF.: essence there of will not be reproduced in whole or in part without written authorization by Dantherm Air Handling A/S. CDP Large DATE: All designs originated by Dantherm Air Handling A/S are the

property of said Company and will be protected by Patents. R

PART NO REV.: E

V

.

P

CDP Large : Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearance according to reference 3 SCALE: NOT TO SCALE A DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only intended as a guide. table LZT 142 0001, category 8 R

351512 5

T

1

N

MATERIAL: REV. BY: O

5

Floor mounting kit THICKNESS: "Thickness@@part1.SLDPRT"mm WEIGHT: 988453.42g DATE: 1

326,1 327,8 4 This Drawing is furnished with the understanding that the REF.: bof essence there of will not be reproduced in whole or in part without written authorization by Dantherm Air Handling A/S. CDF 50 DATE: 19-08-2017 All designs originated by Dantherm Air Handling A/S are the

property of said Company and will be protected by Patents. R

PART NO REV.: E

V

.

CDF 50 : SCALE: NOT TO SCALE 351514

P Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearance according to reference 3

A

DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only entended as a guide. table LZT 142 0001, category 8 R

5

T

1

N

MATERIAL: REV. BY: O

5

THICKNESS: WEIGHT: g DATE: 1

2

This Drawing is furnished with the understanding that the REF.: essence there of will not be reproduced in whole or in part without written authorization by Dantherm Air Handling A/S. CDP Large DATE: All designs originated by Dantherm Air Handling A/S are the

property of said Company and will be protected by Patents. R

PART NO REV.: E

V

.

CDP Large : SCALE: NOT TO SCALE 351512 950,5 913 950,5 Accessories 913 Wireless remote control DRC1 Floor mounting kit Water heating coils Control valve for water heating coils Electric heating coils Exhaust fans

All dimensions are in mm.

dantherm.com

P Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearance according to reference 3

A

DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only intended as a guide. table LZT 142 0001, category 8 R

5

T

1

N

MATERIAL: REV. BY: O

5

THICKNESS: "Thickness@@part1.SLDPRT"mm WEIGHT: 988453.42g DATE: 1

4

This Drawing is furnished with the understanding that the REF.: bof essence there of will not be reproduced in whole or in part without written authorization by Dantherm Air Handling A/S. CDF 50 DATE: 19-08-2017 All designs originated by Dantherm Air Handling A/S are the

property of said Company and will be protected by Patents. R

PART NO REV.: E

V

.

CDF 50 : SCALE: NOT TO SCALE 351514 FIXED DEHUMIDIFIERS CDF

CDF 50 DEHUMIDIFIER

Function The CDF 50 is an energy efficient and quiet dehumidifier. It works in accordance with the condensation principle. A fan draws the humid air into the dehumidi- fier and through an evaporator coil. When passing through the evaporator the air is cooled down to below its dew point temperature, and its content of water vapour is condensed into water, which falls into the drip tray and then is led from the drip tray to a drain. The cold, dry air is then passed over the condenser coil where it is re-heated, before leaving the unit at a temperature, which is ap- prox. 5°C higher than at the inlet.

Applications • Archives • Museums • Churches • Changing rooms • Waterworks

FEATURES

Dehumidifier • Built into a strong and robust powder coated hot galvanized sheet metal cabinet • Evaporator and condenser coils are epoxy-coated for high corrosion resistance • Fixed to the wall by means of a wall mounting strip supplied with the unit • Condensate outlet located at the bottom. Outlet stub can be connected to a ¾” hose • Outside connection to mains

Control • Built in electronic hygrostat and thermostat • Integrated ON/OFF control of humidity and temperature (electric or water heating coils as accessories) • 0-VOLT connection for alarm • 230 V for control valve, exhaust fan and pump/boiler • RS 485 gate for BMS (Modbus)

Diodes BLUE: Power connected, standby mode GREEN: Compressor ON, deicing YELLOW: Remote pairing mode RED: Errors

Defrosting Active, demand-controlled defrosting is incorporated in the electronic control.

Service For easy service the refrigerant circuit is supplied with a service valve. The PCB has a USB gate for history data logging for easy fault finding. FIXED DEHUMIDIFIERS CDF

TECHNICAL DATA

Model CDF 50 Operating range – humidity 40 – 100 %RH Operating range – temperature 3 – 32°C Air volume 680 m3/h Power supply 1x230 V/50 Hz Max. ampere consumption 4,7 A Max. power consumption 1,08 kW Refrigerant R407C Quantity of refrigerant 0,9 kg Compressor Rotary Fan CDF 50 Radial Sound level (at 1 metre) 47 dB(A) Weight 65 kg Filter 40% 60% 80% G3 PPI 15 Colour3 (Cabinet/Front)0,03 0,19 0,45 gæt RAL 9005/9006 Protection10 0,22class 0,54 0,88 IPX4 Corrosion15 protection0,34 0,78 in accordance1,52 with EN/ISO 12944-2 C4 20 0,45 1,45 2,37 30 0,77 2,2 3,3 gæt CAPACITY32 CURVES0,88 2,49 3,67

capacity CDFcurve 50 for CDF 50 40% Temp. °C 40% RH 60% RH 80% RH 60% 35 80%

30

25

20

15

10

5

0 0 0,5 1 1,5 2 2,5 3 3,5 4 l/hL/H

Specific energy consumption (SEC): 0,63 kWh/l at 20°C & 60% RH

INSTALLATION

dantherm.com FIXED DEHUMIDIFIERS CDF

DIMENSIONS CDF 50 430,2 327,8 59,1 430,2 56,4 326,1 326,1 699,9 769,2 699,9 769,2 699,9

1010

CDP 40 - 1010 315,6 315,6

CDPCDF40 116050 - 1160 1010 314,5 CDPCDF50 70 - 1495 1160

CDF 70 1495 Drain outlet position

P Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearance according to reference 3

A

DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only entended as a guide. table LZT 142 0001, category 8 R

5

T

P

3

1

Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearanceN according to reference

A

MATERIAL: REV. BY: O

5 DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only intended as a guide. table LZT 142 0001, category 8 R

5

T THICKNESS: WEIGHT: g DATE: 1

1

N

2 MATERIAL: REV. BY: O

5 This Drawing is furnished with the understanding that the REF.: essence there of will not be reproduced in whole or in part THICKNESS: "Thickness@@part1.SLDPRT"mm WEIGHT: 988453.42g DATE: 1 without written authorization by Dantherm Air Handling A/S. CDP Large DATE: All designs originated by Dantherm Air Handling A/S are the 4

property of said Company and will be protected by Patents. R This Drawing is furnished with the understanding that the PART NO REV.: E REF.: bof

V

.

essence there of will not be reproduced in whole or in part CDP Large : without written authorizationSCALE: NOT by Dantherm TO SCALE Air Handling A/S. CDF 50 DATE: 19-08-2017 All designs originated by Dantherm Air Handling A/S are the 351512

property of said Company and will be protected by Patents. R

PART NO REV.: E

V

430,2430,2 .

CDF 50 :

56,4 SCALE: NOT TO SCALE 351514 56,4 430,2 430,2 326,1 59,1 327,8 59,1

RecommendedDETAIL A installation of CDF 50 SCALE 1 : 2 769,2 699,9 Min. 225 Min. Min. 225 699,9 A

CDP 40 - 1010 315,6

CDP 50 - 1160

CDP 70 - 1495

CDF40 1010 727 314,5 727 CDF50 1160

CDF 70 1495

P Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearance according to reference 3

A

DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only entended as a guide. table LZT 142 0001, category 8 R

5

T

1

N

MATERIAL: REV. BY: O

5

THICKNESS: WEIGHT: g DATE: 1 Min. 225 Min.

2 Min. 225

This Drawing is furnished with the understanding that the REF.: essence there of will not be reproduced in whole or in part without written authorization by Dantherm Air Handling A/S. CDP Large DATE: All designs originated by Dantherm Air Handling A/S are the

property of said Company and will be protected by Patents. R

PART NO REV.: E

V

.

P

CDP Large : Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearance according to reference 3 SCALE: NOT TO SCALE A DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only intended as a guide. table LZT 142 0001, category 8 R

351512 5

T

1

N

MATERIAL: REV. BY: O

5

THICKNESS: "Thickness@@part1.SLDPRT"mm WEIGHT: 988453.42g DATE: 1 Floor mounting kit 326,1 327,8 4 This Drawing is furnished with the understanding that the REF.: bof essence there of will not be reproduced in whole or in part without written authorization by Dantherm Air Handling A/S. CDF 50 DATE: 19-08-2017 All designs originated by Dantherm Air Handling A/S are the

property of said Company and will be protected by Patents. R

PART NO REV.: E

V

.

CDF 50 : SCALE: NOT TO SCALE 351514

P Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearance according to reference 3

A

DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only entended as a guide. table LZT 142 0001, category 8 R

5

T

1

N

MATERIAL: REV. BY: O

5

THICKNESS: WEIGHT: g DATE: 1

2

This Drawing is furnished with the understanding that the REF.: essence there of will not be reproduced in whole or in part without written authorization by Dantherm Air Handling A/S. CDP Large DATE: All designs originated by Dantherm Air Handling A/S are the

property of said Company and will be protected by Patents. R

PART NO REV.: E

V

.

CDP Large : SCALE: NOT TO SCALE 351512 950,5 913 950,5 Accessories 913 Wireless remote control DRC1 Floor mounting kit Water heating coils Control valve for water heating coils Electric heating coils Exhaust fans

All dimensions are in mm.

dantherm.com

P Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearance according to reference 3

A

DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only intended as a guide. table LZT 142 0001, category 8 R

5

T

1

N

MATERIAL: REV. BY: O

5

THICKNESS: "Thickness@@part1.SLDPRT"mm WEIGHT: 988453.42g DATE: 1

4

This Drawing is furnished with the understanding that the REF.: bof essence there of will not be reproduced in whole or in part without written authorization by Dantherm Air Handling A/S. CDF 50 DATE: 19-08-2017 All designs originated by Dantherm Air Handling A/S are the

property of said Company and will be protected by Patents. R

PART NO REV.: E

V

.

CDF 50 : SCALE: NOT TO SCALE 351514 FIXED DEHUMIDIFIERS CDF

CDF 70 DEHUMIDIFIER

Function The CDF 70 is an energy efficient and quiet dehumidifier. It works in accordance with the condensation principle. A fan draws the humid air into the dehumidi- fier and through an evaporator coil. When passing through the evaporator the air is cooled down to below its dew point temperature, and its content of water vapour is condensed into water, which falls into the drip tray and then is led from the drip tray to a drain. The cold, dry air is then passed over the condenser coil where it is re-heated, before leaving the unit at a temperature, which is ap- prox. 5°C higher than at the inlet.

Applications • Archives • Museums • Churches • Changing rooms • Waterworks

FEATURES

Dehumidifier • Built into a strong and robust powder coated hot galvanized sheet metal cabinet • Evaporator and condenser coils are epoxy-coated for high corrosion resistance • Fixed to the wall by means of a wall mounting strip supplied with the unit • Condensate outlet located at the bottom. Outlet stub can be connected to a ¾” hose • Outside connection to mains

Control • Built in electronic hygrostat and thermostat • Integrated ON/OFF control of humidity and temperature (electric or water heating coils as accessories) • 0-VOLT connection for alarm • 230 V for control valve, exhaust fan and pump/boiler • RS 485 gate for BMS (Modbus)

Diodes BLUE: Power connected, standby mode GREEN: Compressor ON, deicing YELLOW: Remote pairing mode RED: Errors

Defrosting Active, demand-controlled defrosting is incorporated in the electronic control.

Service For easy service the refrigerant circuit is supplied with a service valve. The PCB has a USB gate for history data logging for easy fault finding. FIXED DEHUMIDIFIERS CDF

TECHNICAL DATA

Model CDF 70 Operating range – humidity 40 – 100 %RH Operating range – temperature 3 – 32°C Air volume 900 m3/h Power supply 1x230 V/50 Hz Max. ampere consumption 6,5 A Max. power consumption 1,5 kW Refrigerant R407C Quantity of refrigerant 1,2 kg Compressor Rotary Fan CDF 70 Radial Sound level (at 1 metre) 50 dB(A) Weight 75,5 kg Filter 40% 60% 80% G3 PPI 15 Colour3 (Cabinet/Front)0,03 0,19 0,4 gæt RAL 9005/9006 Protection10 class0,3 0,6 0,9 IPX4 Corrosion15 protection0,4 0,96 in accordance2,02 with EN/ISO 12944-2 C4 20 0,64 1,77 2,98 30 1,3 2,3 4,2 gæt CAPACITY32 CURVES1,44 2,46 4,5

capacity CDFcurve 70 for CDF 70 40% Temp. °C 40% RH 60% RH 80% RH 60% 35 80%

30

25

20

15

10

5

0 0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 l/hL/H

Specific energy consumption (SEC): 0,58 kWh/l at 20°C & 60% RH

INSTALLATION

dantherm.com FIXED DEHUMIDIFIERS CDF

DIMENSIONS CDF 70 430,2 327,8 59,1 430,2 56,4 326,1 326,1 699,9 769,2 699,9 769,2 699,9

1010

CDP 40 - 1010 315,6 315,6

CDPCDF40 149550 - 1160 1010 314,5 CDPCDF50 70 - 1495 1160

CDF 70 1495 Drain outlet position

P Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearance according to reference 3

A

DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only entended as a guide. table LZT 142 0001, category 8 R

5

T

P

3

1

Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearanceN according to reference

A

MATERIAL: REV. BY: O

5 DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only intended as a guide. table LZT 142 0001, category 8 R

5

T THICKNESS: WEIGHT: g DATE: 1

1

N

2 MATERIAL: REV. BY: O

5 This Drawing is furnished with the understanding that the REF.: essence there of will not be reproduced in whole or in part THICKNESS: "Thickness@@part1.SLDPRT"mm WEIGHT: 988453.42g DATE: 1 without written authorization by Dantherm Air Handling A/S. CDP Large DATE: All designs originated by Dantherm Air Handling A/S are the 4

property of said Company and will be protected by Patents. R This Drawing is furnished with the understanding that the PART NO REV.: E REF.: bof

V

.

essence there of will not be reproduced in whole or in part CDP Large : without written authorizationSCALE: NOT by Dantherm TO SCALE Air Handling A/S. CDF 50 DATE: 19-08-2017 All designs originated by Dantherm Air Handling A/S are the 351512

property of said Company and will be protected by Patents. R

PART NO REV.: E

V

430,2430,2 .

CDF 50 :

56,4 SCALE: NOT TO SCALE 351514 56,4 430,2 430,2 326,1 59,1 327,8 59,1

RecommendedDETAIL A installation of CDF 70 SCALE 1 : 2 769,2 699,9 Min. 225 Min. Min. 225 699,9 A

CDP 40 - 1010 315,6

CDP 50 - 1160

CDP 70 - 1495

CDF40 1010 727 314,5 727 CDF50 1160

CDF 70 1495

P Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearance according to reference 3

A

DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only entended as a guide. table LZT 142 0001, category 8 R

5

T

1

N

MATERIAL: REV. BY: O

5

THICKNESS: WEIGHT: g DATE: 1 Min. 225 Min.

2 Min. 225

This Drawing is furnished with the understanding that the REF.: essence there of will not be reproduced in whole or in part without written authorization by Dantherm Air Handling A/S. CDP Large DATE: All designs originated by Dantherm Air Handling A/S are the

property of said Company and will be protected by Patents. R

PART NO REV.: E

V

.

P

CDP Large : Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearance according to reference 3 SCALE: NOT TO SCALE A DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only intended as a guide. table LZT 142 0001, category 8 R

351512 5

T

1

N

MATERIAL: REV. BY: O

5

THICKNESS: "Thickness@@part1.SLDPRT"mm WEIGHT: 988453.42g DATE: 1 Floor mounting kit 326,1 327,8 4 This Drawing is furnished with the understanding that the REF.: bof essence there of will not be reproduced in whole or in part without written authorization by Dantherm Air Handling A/S. CDF 50 DATE: 19-08-2017 All designs originated by Dantherm Air Handling A/S are the

property of said Company and will be protected by Patents. R

PART NO REV.: E

V

.

CDF 50 : SCALE: NOT TO SCALE 351514

P Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearance according to reference 3

A

DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only entended as a guide. table LZT 142 0001, category 8 R

5

T

1

N

MATERIAL: REV. BY: O

5

THICKNESS: WEIGHT: g DATE: 1

2

This Drawing is furnished with the understanding that the REF.: essence there of will not be reproduced in whole or in part without written authorization by Dantherm Air Handling A/S. CDP Large DATE: All designs originated by Dantherm Air Handling A/S are the

property of said Company and will be protected by Patents. R

PART NO REV.: E

V

.

CDP Large : SCALE: NOT TO SCALE 351512 950,5 913 950,5 Accessories 913 Wireless remote control DRC1 Floor mounting kit Water heating coils Control valve for water heating coils Electric heating coils Exhaust fans

All dimensions are in mm.

dantherm.com

P Linear dimensions without tolerances according to Sheetmetal flatstate is based on Dantherm Air Handling A/S Surface appearance according to reference 3

A

DS/EN 22768-1 medium. Angular dimensions without tolerances: ± 1° process equipment and is only intended as a guide. table LZT 142 0001, category 8 R

5

T

1

N

MATERIAL: REV. BY: O

5

THICKNESS: "Thickness@@part1.SLDPRT"mm WEIGHT: 988453.42g DATE: 1

4

This Drawing is furnished with the understanding that the REF.: bof essence there of will not be reproduced in whole or in part without written authorization by Dantherm Air Handling A/S. CDF 50 DATE: 19-08-2017 All designs originated by Dantherm Air Handling A/S are the

property of said Company and will be protected by Patents. R

PART NO REV.: E

V

.

CDF 50 : SCALE: NOT TO SCALE 351514 FIXED DEHUMIDIFIERS CDF

ACCESSORIES CDPCDF 1035 – CDFCDP 4045 –– CDFCDP 5065 –– CDFCDP 70 35T – CDP 45T – CDP 65T

Illustration Accessory Description CDF-type Dantherm No.

Watertank White or grey CDF 10 351615

DRC1 is a wireless RH and temperature controller Frequency: 433 mhz Range up to 50 m depending on the conditions CDF 40 Remote control, DRC1 Protection class: IP 20 CDF 50 093455 CDF 70 Functionalities: • Reading and setting of RH and temperature, alarms and service information • Locking of settings

Each bracket to be mounted CDF 40 Floor mounting kit, on each side of the dehumi- CDF 50 094332 2 pcs.- black difier CDF 70

Water heating coil Comprises water heating CDF 40 094333 3,2 kW*) coil, flexible hose, fittings and gasket Water heating coil *at 80/60° C CDF 50 094334 5,1 kW*) (See technical specifications Water heating coil for water heating coils on CDF 70 094335 7,4 kW*) separate page)

Comprises valve and actuator DN 10 control valve 230 V, ON/OFF (180 seconds CDF 40 and actuator for from closed to fully open), CDF 50 094340 water heating coils incl. union nut for Ø 12 cu CDF 70 tube

dantherm.com FIXED DEHUMIDIFIERS CDF

ACCESSORIES CDPCDF 1035 – CDFCDP 4045 –– CDFCDP 5065 –– CDFCDP 70 35T – CDP 45T – CDP 65T

Illustration Accessory Description CDF-type Dantherm No.

Electric heating coil CDF 40 094336 2 kW

Electric heating coil Comprises electric heating 094337 3,5 kW coil, relays and electric CDF 50

Electric heating coil CDF 70 094338 5 kW

CDF 40 Exhaust fan, The exhaust fan can be used 094339 CDF 50 Q = 97 m3/h in combination with the CDF CDF 70 to either increase dehumidi- fication capacity or establish outdoor air supply.

CDF 40 Exhaust fan, Relay and electric are included. CDF 50 094341 Q = 185 m3/h CDF 70

dantherm.com FIXED DEHUMIDIFIERS CDF

ACCESSORIES CDF 40 - CDF 50 - CDF 70

Water heating coils - calculations at = 20°C; 50% RH

CDF 40 Q=400 m3/h Water temperature °C 82/71 80/60 70/35 90/70 60/40 55/45 Capacity kW 3,85 3,19 1,16 3,94 1,64 1,91 Water flow rate l/sec. 0,09 0,04 0,01 0,05 0,02 0,05 Water pressure drop kPa 15,5 3,9 0,3 5,5 1,3 5,7 Water velocity m/sec. 1,22 0,56 0,11 0,69 0,28 0,66 Air flow rate m3/sec. 0,11 0,11 0,11 0,11 0,11 0,11 Inlet temperature °C 82 80 70 90 60 55 Outlet temperature °C 71 60 35 70 40 45 Air pressure drop Pa 8 8 8 8 8 8 Connection tube mm 12 12 12 12 12 12

CDF 50 Q=680 m3/h Water temperature °C 82/71 80/60 70/35 90/70 60/40 55/45 Capacity kW 6,11 5,12 2,42 6,29 2,75 3,08 Water flow rate l/sec. 0,14 0,06 0,02 0,08 0,03 0,08 Water pressure drop kPa 42,2 10,6 1,1 14,9 3,8 15,6 Water velocity m/sec. 1,94 0,06 0,24 1,1 0,48 1,07 Air flow rate m3/sec. 0,19 0,19 0,19 0,19 0,19 0,19 Inlet temperature °C 82 80 70 90 60 55 Outlet temperature °C 71 60 35 70 40 45 Air pressure drop Pa 10 10 10 10 10 10 Connection tube mm 12 12 12 12 12 12

CDF 70 Q=900 m3/h Water temperature °C 82/71 80/60 70/35 90/70 60/40 55/45 Capacity kW 8,74 7,43 3,86 9,07 4,12 4,47 Water flow rate l/sec. 0,19 0,09 0,03 0,11 0,05 0,11 Water pressure drop kPa 108,1 27,7 3,4 38,7 10,3 40,7 Water velocity m/sec. 2,78 1,3 0,38 1,59 0,71 1,55 Air flow rate m3/sec. 0,25 0,25 0,25 0,25 0,25 0,25 Inlet temperature °C 82 80 70 90 60 55 Outlet temperature °C 71 60 35 70 40 45 Air pressure drop Pa 8 8 8 8 8 8 Connection tube mm 12 12 12 12 12 12

dantherm.com