Electrical General Notes Abbreviations and Legends
Total Page:16
File Type:pdf, Size:1020Kb
CLIENT GENERAL ELECTRICAL NOTES ELECTRICAL SPECIFICATIONS ELECTRICAL LEGEND ABBREVIATIONS LIGHTING SIGNAL A AMPERE PART I - GENERAL AFF ABOVE FINISHED FLOOR 1. ALL SYMBOLS ARE NOT NECESSARILY USED IN THIS PROJECT. THERMOSTAT OUTLET AT +54" (HVAC UNIT AF ARC FAULT, AMP FUSE 10. CONDUIT PENETRATION THROUGH ROOF SHALL HAVE ROOF FLASHING WITH I. TELEPHONE SYSTEM A. CONDITIONS LINEAR FLUORESCENT FIXTURE DESIGNATION) AFG ABOVE FINISHED GRADE 2. IT IS THE INTENT OF THESE DRAWINGS AND SPECIFICATIONS TO ESTABLISH A STANDARD OF QUALITY. THE CAULK TYPE COUNTER FLASHING SLEEVE. INSTALLATION SHALL BE AIC AMPERE INTERRUPTING CAPACITY ENCLOSED CIRCUIT BREAKER ENGINEER RESERVES THE RIGHT TO ALLOW OTHER METHODS AND MATERIALS NOT REFLECTED HEREIN. 1. FURNISH AND INSTALL A COMPLETELY WIRED AND OPERATIONAL ELECTRICAL WATERTIGHT. 1. TELEPHONE WALL OUTLETS SHALL CONSIST OF STANDARD BOXES MOUNTED 18" SUSPENDED LINEAR FLUORESCENT FIXTURE AL ALUMINUM THE CONTRACTOR SHALL BE RESPONSIBLE TO REQUEST THE ENGINEER WAIVE THE STANDARDS TO ALLOW SYSTEM AS SHOWN ON THE DRAWINGS AND SPECIFIED HEREIN, INCLUDING BUT 11. CONDUITS SHALL BE ROUTED SURFACE ON THE STRUCTURE, PARALLEL AND ABOVE THE FLOOR UNLESS OTHERWISE INDICATED. CONNECT OUTLETS TO ARCH'L ARCHITECTURAL ALTERNATE MEANS AND METHODS PRIOR TO BEGINNING THE PROJECT. CONTRACT DOCUMENT REVISIONS R AS AMP SWITCH NOT LIMITED TO, THESE MAJOR ITEMS. PERPENDICULAR TO THE STRUCTURE. TELEPHONE TERMINAL WITH SEPARATE 3/4" CONDUIT UNLESS OTHERWISE SHOWN FLUORESCENT WALL MOUNT FIXTURE RELAY TO ACCOMMODATE INSTALLED CONDITIONS, WITHOUT PRIOR APPROVAL, WILL RESULT IN ADDITIONAL ON DRAWINGS. PROVIDE A TERMINAL MOUNTING BOARD FOR THE INCOMING AWG AMERICAN WIRE GAUGE DESIGN CHARGES TO THE CONTRACTOR. LINEAR FLUORESCENT STRIP FIXTURE TS TIME SWITCH A. LIGHTING FIXTURES AS INDICATED AND SPECIFIED ON THE PLANS. SERVICE CABLE. BC BARE COPPER 3. ELECTRICAL WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER IN ACCORDANCE WITH THE NECA B. ELECTRICAL PANELS, SERVICE, CONDUIT, WIRING, ETC., FOR ALL OUTLETS AND C. OUTLET, PULL, AND JUNCTION BOXES LIGHT FIXTURE - RECESSED OR SURFACE C BLDG BUILDING INSTALLATION STANDARDS TO THE SATISFACTION OF THE OWNER AND ENGINEER. CONTACTOR EQUIPMENT. L. SHOP DRAWINGS AND APPROVALS PENDANT FIXTURE C. TELEPHONE OUTLETS AND CONDUIT AS INDICATED. 1. EACH SWITCH, LIGHT. RECEPTACLE OR OTHER OUTLET SHALL BE PROVIDED WITH A C CONDUIT 4. ALL WORK, MATERIALS AND EQUIPMENT SHALL CONFORM TO THE CURRENTLY ACCEPTED EDITION OF ALL T CAB CABINET 1. THE ITEMS SPECIFIED HEREIN AND ON DRAWINGS ARE USED AS A STANDARD WALL MOUNTED LIGHT FIXTURE TRANSFORMER APPLICABLE NATIONAL, STATE AND CITY CODES AND ORDINANCES. CODE GAUGE, GALVANIZED STEEL OUTLET BOX. JUNCTION AND PULL BOXES CAT CATALOG/CATEGORY SHALL BE CODE GAUGE, GALVANIZED STEEL. OUTLET BOXES SHALL BE OF THE OF QUALITY. ANY MATERIALS OF EQUAL QUALITY AND AESTHETIC VALUE WILL BE B. CODES, REGULATIONS, AND STANDARDS ADJUSTABLE RECESSED MOUNTED LIGHT FIXTURE ATS AUTOMATIC TRANSFER SWITCH C/B CIRCUIT BREAKER 5. ALL ELECTRICAL SYSTEM COMPONENTS SHALL BE LISTED OR LABELED BY UL OR OTHER RECOGNIZED ONE PIECE, KNOCKOUT TYPE, IN GENERAL 4" SQUARE WITH PLASTER RING. GIVEN CONSIDERATION AS A SUBSTITUTE FOR THE MATERIALS SPECIFIED. NO CKT CIRCUIT TESTING FACILITY AS ALLOWED BY AUTHORITY HAVING JURISDICTION. 1. THE INSTALLATION SHALL COMPLY WITH APPLICABLE LOCAL AND STATE CODES PLASTER RINGS SHALL BE SET TO PROVIDE NOT MORE THAN 1/8" FROM WALL APPROVAL WILL BE GIVEN TO A SPECIFIC CATALOG NUMBER, MODEL, OR TYPE OF CLG CEILING RECESSED LIGHT FIXTURE TELEPHONE OUTLET AT +18" 6. WHERE AN APPARENT DISCREPANCY EXISTS BETWEEN THE REQUIREMENTS OF THE GENERAL NOTES AND AND ORDINANCES, WITH THE REGULATIONS OF THE CURRENTLY ACCEPTED SURFACE TO RING. IN NO CASE SHALL PLASTER RING PROJECT BEYOND SURFACE EQUIPMENT, PRIOR TO BIDDING. AFTER BIDDING, THE DECISION OF THE ARCHITECT CO, EC CONDUIT ONLY INFORMATION PORTRAYED IN THE ELECTRICAL DRAWINGS, THE CONTRACTOR SHALL INCLUDE IN HIS COST EDITION OF THE NATIONAL ELECTRIC CODE AND WITH THE REQUIREMENTS OF THE OF WALL. SINGLE GANG RINGS SIMILAR TO STEEL CITY 52050 SHALL BE USED FOR AND/OR ENGINEER DETERMINING EQUAL MATERIALS WILL BE FINAL. WALL SCONCE COMM COMMUNICATION CITY OF TORRANCE CU COPPER OF THE GREATER QUALITY OR QUANTITY. POWER, TELEPHONE, AND CATV COMPANIES FURNISHING SERVICES TO THIS 4" BOXES IN UNFINISHED BRICK NUMBER 180 BOXES MAY BE USED FOR UNFINISHED DATA OUTLET AT +18" WALL WASHER 3031 TORRANCE BLVD. INSTALLATION. MASONRY FLUSH WALL OUTLETS. CENTER ALL OUTLET BOXES IN BLOCK COURSE. A 7. ALL ELECTRICAL SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. IF TESTS SHOW THAT WORK IS DEMO DEMOLITION/DEMOLISH 2. THE FOLLOWING INDUSTRY STANDARDS, SPECIFICATIONS, AND CODES ARE LETTER REFERS TO FIXTURE TYPE COMBINATION TELE/COMPUTER OUTLET AT +18" TORRANCE , CA 90503 DEFECTIVE, CONTRACTOR SHALL MAKE ALL NECESSARY CORRECTIONS. 2. THE CONTRACTOR SHALL SUBMIT SEVEN (7) IDENTICAL BOUND SETS OF SHOP DISC. DISCONNECT MINIMUM REQUIREMENTS: 2. BOXES INSTALLED IN POURED CEMENT FLOORS SHALL BE FLUSH TYPE CAST IRON DRAWINGS ON THE FOLLOWING NEW ITEMS WHERE SPECIFIED ON PLANS: DN DOWN 8. CONTRACTOR SHALL GUARANTEE ALL WORK AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP WHICH OR STEEL WITH WATERTIGHT GASKETED COVERS. WHERE BOXES ARE MONO-POINT LIGHT FIXTURE TELEPHONE OUTLET ABOVE COUNTER DWG DRAWING PROJECT NAME MAY OCCUR UNDER NORMAL USE FOR A PERIOD OF ONE YEAR AFTER OWNER'S ACCEPTANCE. ALL DEFECTS A. THE NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION STANDARDS. INSTALLED IN FLOORS WITH TILE OR CARPET FLOOR COVERING, COVERS SHALL A. LIGHTING FIXTURE CUTS AND PERFORMANCE DATA. EA EACH SHALL BE PROMPTLY CORRECTED BY CONTRACTOR. B. THE NATIONAL ELECTRICAL CODE, INCLUDING LOCAL AMENDMENTS. BE OF THE RECESSED TYPE TO ACCOMMODATE THE FLOOR COVERING. TRACK LIGHT FIXTURE TELE/DATA OUTLET ABOVE COUNTER B. OUTLINE DRAWINGS & DATA SHEETS OF EACH PANELBOARD & ELECT. ELECTRICAL C. UNDERWRITER LABORATORIES INCORPORATED STANDARDS. 9. THE ELECTRICAL CONTRACTOR SHALL MAINTAIN A SET OF DRAWINGS AT THE JOB SITE FOR THE EXCLUSIVE SWITCHBOARD. PARKING LOT POLE MOUNTED LIGHT FIXTURE DATA OUTLET ABOVE COUNTER ELEV ELEVATOR PURPOSE OF MAINTAINING A RECORD OF ALL WORK INSTALLED AND TO SHOW ANY DEVIATIONS FROM D. AMERICAN NATIONAL STANDARDS INSTITUTE. 3. BOXES INSTALLED FOR THE ALARM, COMPUTER, AND SECURITY SYSTEM SHALL BE C. OUTLINE DRAWINGS OF ALL SWITCHGEAR. EM EMERGENCY THE WORK INDICATED ON THE DRAWINGS PROVIDED WITH APPROPRIATE COVER PLATES. EMT ELECTRICAL METALLIC TUBING FIRE STATION NO.1 BOLLARD LIGHT FIXTURE FLUSH FLOOR BOX W \ COMBINATION TELE/DATA 3. SUBMIT ITEMS AT ONE TIME IN A NEAT AND ORDERLY MANNER WITHIN 15 DAYS OF EMT EQUIPMENT EQUIP 10. DO NOT SCALE ELECTRICAL DRAWINGS. VERIFY EXACT LOCATION OF ALL DEVICES, JUNCTION BOXES, C. INSPECTION OF SITE OUTLET (E), EXIST EXISTING 4. BOXES FOR TELEPHONE, COMPUTER, T.V., FIRE ALARM, SECURITY, AND SIMILAR AWARD OF CONTRACT. PARTIAL SUBMITTALS WILL NOT BE ACCEPTABLE. LIGHTING FIXTURES, ETC. WITH ARCHITECTURAL AND INTERIOR DESIGN DRAWINGS PRIOR TO 1. PRIOR TO SUBMITTING A BID FOR ELECTRICAL WORK, THE CONTRACTOR SHALL SYSTEMS SHALL BE MINIMUM 4" SQUARE AND 2-1/8" DEEP. EXIT SIGN - CEILING MOUNTED TELEVISION OUTLET (ER) EXISTING TO BE RELOCATED INSTALLATION. CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF ALL MECHANICAL EQUIPMENT AND VISIT THE SITE OF THE PROPOSED CONSTRUCTION AND SHALL THOROUGHLY HVAC REPLACEMENT OTHER EQUIPMENT REQUIRING ELECTRICAL CONNECTION PRIOR TO ROUGH-IN. EVERY OUTLET HEIGHT M. RECORD AND AS-BUILT DRAWINGS EXIT SIGN - WALL MOUNTED C TELEVISION CAMERA (CCTV) FBO FURNISHED BY OTHERS SHALL BE VERIFIED ON EACH WALL WITH THE INTERIOR PLANNING AND DESIGN DRAWINGS. COORDINATE ACQUAINT HIMSELF WITH EXISTING UTILITIES, AND WORKING CONDITIONS TO BE D. PANEL BOARDS FF FINISHED FLOOR ENCOUNTERED, ETC. ALLOWANCE WILL NOT BE MADE FOR NONCOMPLIANCE WITH 1. THE ELECTRICAL CONTRACTOR SHALL MAINTAIN A SET OF DRAWINGS AT THE JOB FIXT FIXTURE PROJECT (606) WITH CABINET SHOP DRAWINGS TO ENSURE PROPER HEIGHT AND LOCATION WITH RESPECT TO EXIT SIGN - W/ARROWS INDICATE DIRECTION FIRE ALARM HORN/STROBE MILLWORK, EQUIPMENT, ETC. THIS CONDITION AFTER BIDDING. 1. CIRCUIT BREAKER TYPE AS INDICATED ON DRAWINGS. UNLESS INDICATED SITE FOR THE EXCLUSIVE PURPOSE OF MAINTAINING A RECORD OF ALL WORK FLEX FLEXIBLE METALLIC CONDUIT (STEEL) 1701 CRENSHAW BLVD. OTHERWISE, ALL PANELS SHALL HAVE PANEL BOARD TYPE CONSTRUCTION WITH INSTALLED AND TO SHOW ANY DEVIATIONS FROM THE WORK INDICATED ON THE CR 11. THESE DRAWINGS INDICATE THE FINISHED REQUIREMENTS FOR THE ELECTRICAL SYSTEMS, EQUIPMENT, 2. ELECTRICAL INSTALLATION SHALL MEET THE EXISTING CONDITIONS. BOLT-ON CIRCUIT BREAKERS FOR 3∅ PANELS. MANUFACTURERS SHALL BE EMERGENCY BATTERY UNIT WITH HEADS CARD READER FLUOR FLUORESCENT DRAWINGS. FT FEET OR FOOT TORRANCE, CALIFORNIA LIGHTING FIXTURES, OUTLETS AND DEVICES. DUE TO STRUCTURAL CONDITIONS, MECHANICAL DUCT, GENERAL ELECTRIC, SQUARE D, SIEMENS, CUTLER-HAMMER OR EQUAL WITH PIPING CONFLICTS, OR OTHER LEGITIMATE REASONS, THE CONTRACTOR MAY DESIRE TO INSTALL THE FIXTURE w/ EMERGENCY BATTERY OR GENERATOR FLOW SWITCH VOLTAGE, SIZES, AND RATINGS AS INDICATED ON DRAWINGS. GFA GROUND FAULT ALARM WORK INDICATED IN A MANNER DIFFERENT FROM THAT SHOWN. SUCH CHANGES SHALL BE PRESENTED TO D. STORAGE AND HANDLING OF MATERIAL J. LIGHTING CONTROL GFCI GROUND FAULT CIRCUIT CONSULTANT THE ENGINEER FOR REVIEW AND APPROVAL PRIOR TO PROCEEDING. UPON APPROVAL, THE WORK SHALL 1. DELIVER MATERIALS AND EQUIPMENT TO THE PROJECT IN THE MANUFACTURER'S 2. THE CIRCUIT