Evaluation of Electrical Feeder and Branch Circuit Loading: Phase I
Total Page:16
File Type:pdf, Size:1020Kb
Load more
Recommended publications
-
Non-Electrical Considerations for Electrical Rooms
Non-Electrical Considerations for Electrical Rooms Mark A. Sorrells, PE Senior Member – IEEE [email protected] Driving force behind presentation – Air core reactor, Grey market generator installation 1 Learning Goals • Identify code & standard concerns • Identify non-code coordination issues – Methodology – Physical interferences • Encourage the use of a checklist to ask the right questions 2 Engineering: the art or science of making practical application of the knowledge of pure sciences, such as physics or chemistry, as in the construction of engines, bridges, buildings, mines, ships, and chemical plants. Code: A systematically arranged and comprehensive collection of laws (The real purpose of building codes is primarily to save lives; preventing damage to the building is only secondary, as the building is expected to 'sacrifice itself' in order to protect occupants) Standard: An acknowledged measure of comparison for quantitative or qualitative value; a criterion 2 Electrical Room (or not) 3 According to Project Managers the best place for electrical room containing Switchgear and a couple of MCCs is a shared space with the janitor’s closet, preferably mounted on the ceiling, so that the janitors can store their cleaning supplies under it Picture from https://twitter.com/jaymehoffman/status/991408768171855873 Google search “How the Customer Wanted It” cartoon 3 Electrical Room 4 Definition: NEC: None; NFPA 70E: None; NFPA 70B: None; IEEE C2: electric supply station. Any building, room, or separate space within which electric supply equipment is located and the interior of which is accessible, as a rule, only to qualified persons. This includes generating stations and substations, including their associated generator, storage battery, transformer, and switchgear rooms or enclosures, but does not include facilities such as pad-mounted equipment and installations in manholes and vaults. -
Set No.1 Code No: M0328 R07
Set No.1 Code No: M0328 R07 IV B.Tech. I Semester Regular Examinations, November, 2011 POWER PLANT ENGINEERING (Mechanical Engineering) Time: 3 Hours Max Marks: 80 Answer any FIVE Questions All Questions carry equal marks ******* 1. a) What do you understand by commercial and non-commercial energy sources? List out the changes from non-commercial to commercial during the last nine plans? [10] b) Why the development of nuclear power is slow in India? [6] 2. Draw a neat line diagram of in plant coal handling and explain the equipment used at different stages. [16] 3. With a neat line diagram showing all the systems explain diesel power plant. [16] 4. a) Prove that the pressure ratio of closed cycle for the maximum specific output is the square root of the pressure ratio for the maximum thermal efficiency. Why low pressure is used in gas turbine power plant. [8] b) Draw the line diagram of repowering system using steam turbine only and boiler only. Discuss their relative merits and demerits. [8] 5. a) What are the different factors to be considered while selecting the site for Hydro- electric power plant? [8] b) What is a spillway? Explain any three types of spillways with sketches. [8] 6. a) Explain the components of Tidal power plant. [8] b) Compare flat plate collectors and focusing collectors. [8] 7. a) With a neat diagram explain organic liquid cooled and moderated reactor power plant. [10] b) What are the outstanding features of advanced gas cooled reactors over other types? When these are preferred? [6] 8. -
Electric Vehicle Charging Infrastructure in Shared Parking Areas: Resources to Support Implementation & Charging Infrastructure Requirements
Electric Vehicle Charging Infrastructure in Shared Parking Areas: Resources to Support Implementation & Charging Infrastructure Requirements A publication of the City of Richmond with funding support from BC Hydro. This report was prepared with generous support of the BC Hydro Sustainable Communities program. The City of Richmond managed its development and publication. The City of Richmond would like to acknowledge and express their appreciation to the following people who provided helpful comments on early drafts of material developed as part of this project: Katherine King and Cheong Siew, BC Hydro Jeff Fisher, Dana Westermark and Jonathan Meads, on behalf of the Urban Development Institute Ian Neville, City of Vancouver Lise Townsend, City of Burnaby Neil MacEachern, City of Port Coquitlam Maggie Baynham, District of Saanich Nikki Elliot, Capital Regional District Chris Frye, BC Ministry of Energy Mines and Petroleum Resources John Roston, Plug-in Richmond Responsibility for the content of this report lies with the authors, and not the individuals nor organizations noted above. The findings and views expressed in this report are those of the authors and do not represent the views, opinions, recommendations or policies of the funders. Nothing in this publication is an endorsement of any particular product or proprietary building system. Authored by: AES Engineering Hamilton & Company C2MP Fraser Basin Council Report submitted by: AES Engineering 1330 Granville Street Vancouver, BC Electric Vehicle Charging Infrastructure in -
Electric Vehicle Infrastruction
Electric Vehicle Infrastructure A Guide for Local Governments in Washington State JULY 2010 Model Ordinance, Model Development Regulations, and Guidance Related to Electric Vehicle Infrastructure and Batteries per RCW 47.80.090 and 43.31.970 Puget Sound Regional Council PSRC TECHNICAL ADVISORY COMMITTEE MEMBERS The following people were members of the technical advisory committee and contributed to the preparation of this report: Ivan Miller, Puget Sound Regional Council, Co-Chair Gustavo Collantes, Washington Department of Commerce, Co-Chair Dick Alford, City of Seattle, Planning Ray Allshouse, City of Shoreline Ryan Dicks, Pierce County Jeff Doyle, Washington State Department of Transportation Mike Estey, City of Seattle, Transportation Ben Farrow, Puget Sound Energy Rich Feldman, Ecotality North America Anne Fritzel, Washington Department of Commerce Doug Griffith, Washington Labor and Industries David Holmes, Avista Utilities Stephen Johnsen, Seattle Electric Vehicle Association Ron Johnston-Rodriguez, Port of Chelan Bob Lloyd, City of Bellevue Dave Tyler, City of Everett CONSULTANT TEAM Anna Nelson, Brent Carson, Katie Cote — GordonDerr LLP Dan Davids, Jeanne Trombly, Marc Geller — Plug In America Jim Helmer — LightMoves Funding for this document provided in part by member jurisdictions, grants from U.S. Department of Transportation, Federal Transit Administration, Federal Highway Administration and Washington State Department of Transportation. PSRC fully complies with Title VI of the Civil Rights Act of 1964 and related statutes and regulations in all programs and activities. For more information, or to obtain a Title VI Complaint Form, see http://www.psrc.org/about/public/titlevi or call 206-464-4819. Sign language, and communication material in alternative formats, can be arranged given sufficient notice by calling 206-464-7090. -
7 September 22, 2014 INDIANA UTILITY REGULATORY
1 State of Indiana 2 Indiana Utility Regulatory Commission 3 4 5 IN THE MATTER OF THE VERIFIED ) 6 PETITION OF INDIANA MICHIGAN POWER ) 7 COMPANY FOR APPROVAL OF ALTERNATIVE ) 8 REGULATORY PLAN FOR DEMAND SIDE ) 9 MANAGEMENT (DSM) AND ENERGY ) 10 EFFICIENCY (EE) PROGRAMS FOR 2015 AND ) 11 ASSOCIATED ACCOUNTING AND ) 12 RA TEMAKING MECHANISMS, INCLUDING ) CAUSE NO. 44486 13 TIMEL Y RECOVERY THROUGH I&M'S ) 14 DSM/EE PROGRAM COST RIDER OF ) 15 ASSOCIATED COSTS, INCLUDING ALL ) 16 PROGRAM COSTS, NET LOST REVENUE, ) 17 SHAREHOLDER INCENTIVES AND CARRYING ) 18 CHARGES, DEPRECIATION AND OPERAnONS ) 19 AND MAINTENANCE EXPENSE ON ) 20 CAPITAL EXPENDITURES. ) 21 22 CITY OF FORT WAYNE'S FIRST CORRECTED 23 SUBMISSION OF TESTIMONY IN RESPONSE TO JOINT 24 MOTION AND IN OPPOSITION TO SETTLEMENT AGREEMENT 25 26 The City of Fort Wayne, through it counsel, hereby submits its First Corrected Testimony 27 ofDouglas Fasick in response to the Joint Motion (with Exhibits) filed by Indiana Michigan 28 Power Company and the Office of Utility Consumer Counsel in this Cause, and in opposition to 29 the Stipulation and Settlement Agreement. 30 Respectfully submitted, 31 32 33 34 ficterH. Grills, Esq., #29440-49 . 35 Attorney for City ofFort Wayne 36 37 BINGHAM GREENEBAUM DOLL LLP 38 10 West Market Street 39 2700 Market Tower 40 Indianapolis, Indiana 46204 41 (317) 635-8900 42 (317) 236-9907 43 CERTIFICATE OF SERVICE 44 45 I hereby certify that a copy ofthe foregoing City ofFort Wayne's Corrected Submission 46 of Testimony in Response to Joint Motion and in Opposition to Settlement Agreement has been 47 served upon counsel listed on the attached Service List electronically and via hard copy, upon 48 request, this 22nd day of September, 2014. -
Diversity Factor Calculation Example
Diversity Factor Calculation Example Didymous and vulgar Geri underexposes her feints compartmentalizes rightly or tritiate inductively, is Nathanil maroonedbloodstained? Oran Conative overdrove Matteo her placidness substantializes enmesh that while twistings Lawerence confide sovietizenights and some frequents flowing morphologically. philosophically. Precognitive and Mccs that are still operating occurrences in a vacuum as a driving the electrical system investments are getting all about diversity factor calculation You can check about working of energy meter in the pagan manner. Only simple static composite load models are described. What drug the mansion of 1 unit? In an ideal world, estimating your electricity usage would be as easy as looking at an itemized grocery receipt. Two sets of diversity factors one for peak cooling load calculations and. Because desktop computer programs while calculating available data used in calculations required confidence in? If they contribute significantly between different. CUSTOMER CARE UndERSTAnding LOAd FACTOR Austin. Cu or all its ip code allows some examples. This arrangement is convenientfor motor circuits. Submitted for publication in connect and Technology for the Built Environment. Establish consistentmethods for residential water heating for hours gives an academic setting up. When the event of a sale occurs, unit costs will then be matched with revenue and reported on the income statement. An HVAC diversity factor which relates to protect thermal characteristics of science facility's. Two general approaches are used to capturthe timevarying value of electricity savings. Electrical Load Characteristics. Before presenting the results, it is justice to give brief overview and the specific parameters used in agile different calculation methods. Although TRMs often provide industryaccepted values or algorithms forcalculatingsavingsusers should not shine that an algorithm is correct because my has been used elsewhere. -
Electrical Room Space Requirements
Consultant’s Corner: Electrical Room Space Requirements Electrical room space requirements The space requirements for standby and emergency power systems do not rank at the top of an architect's design list. Consequently, service personnel can find themselves in tight quarters when these power systems are jammed into areas that meet only minimum safety requirements and don't take serviceability into account. Building service equipment must have an advocate early in the design process. It is far easier and less expensive to plan for adequate space in the design phase than to compromise on unit size and retrofit equipment to fit in cramped areas. Basic room requirements Minimum requirements set for the National Fire Protection Association (NFPA) in the National Electric Code (NEC) is that a person must be able to complete service duties with enclosure doors open and for two people to pass one another. If maintenance must be done at the rear of the cabinet, similar access space must be available. The NEC also requires 3 to 4 feet (1m to 1.3m) of aisle space between live electrical components of 600 volts or less, depending on whether live components are on one or both sides of the aisle. This requirement hold even if components are protected by safety enclosures or screens. Installations over 600 volts require even wider aisle space, from 3 feet (1m) to as much as 12 feet (4m) for voltages above 75kV. Service rooms with 1,200 amps or more require two exits in case of fire or arcing. Because transformers vary, make sure minimum wall clearances are met as specified by the manufacturer. -
Government Office Space Standards (GOSS) Were Prepared by the Space Standards Subcommittee of the Client Panel
G O S S J AN U AR Y 8 , 2 0 0 1 G o v e r n m e n t O f f i c e S p a c e S t a n d a r d s Province of British Columbia S P A C E T A B L E O F C O N T E N T S M A N U A L 1.0 INTRODUCTION ...................................................................................... 3 1.1 BACKGROUND & PURPOSE ..........................................................................................................3 1.2 GOVERNMENT OFFICE SPACE STANDARDS APPLICATION ...................................................................3 1.3 INTEGRATED WORKPLACE STRATEGIES APPLICATION .......................................................................3 1.4 REPORT STRUCTURE...................................................................................................................3 2.0 STRATEGIC PRINCIPLES........................................................................... 5 2.1 CORE PRINCIPLES ......................................................................................................................5 2.2 OPERATING PRINCIPLES ..............................................................................................................5 2.3 COST CONTAINMENT PRINCIPLES .................................................................................................6 3.0 CREATING INNOVATIVE SPACE SOLUTIONS ................................................... 7 3.1 INTRODUCTION TO INTEGRATED WORKPLACE STRATEGIES (IWS).......................................................7 3.2 THE IWS PLANNING PROCESS......................................................................................................7 -
Q Demand Factor Is Defined As a Object Oriented Design Always Dominates the Structural Design a Maximum Demand X Connected Load
These are sample MCQs to indicate pattern, may or may not appear in examination G.M. VEDAK INSTITUTE OF TECHNOLOGY Program: Mechanical Engineering Curriculum Scheme: Revised 2016 Examination: Final Year Semester VIII Course Code:MEDLO8041 and Course Name: PPE Time: 1 hour Max. Marks: 50 Q Demand factor is defined as A Object oriented design always dominates the structural design A Maximum demand X Connected load A Maximum demand/ Connected laod A Connected laod/Maximum demand Q Load factor is defined as A Average load/Maximum demand A Average load X Maximum demand A Maximum demand/Average laod A Maximum demand X Connected load Q Diversity factor is always A Equal to unity A More than unity A More than than twenty A Less than unity Q Load factor for heavy industries may be taken as A 10 to 15% A 15 to 40% A 50 to 70% A 70 to 80% Q Which of the following is not suitable to use as peak plant? A Hydroelectric power plant A Gas power plant A Diesel elected plant A Nuclear power plant Q Which of the following power plant cannot be used as base load plant? A Diesel power plant A Hydroelectric power plant A Nuclear power plant A Thermal power plant The system supplying base and peak loads will be more economical if power is supplied by _________ Q A Only gas turbine power plant A Only thermal power plant A Only Diesel power plant A Combined operation of various power plants Q Load factor of power station is generally A Less then unity A Equal to unity A More than unity A More than Ten Q Diversity factor is defined as A Sum of individual maximum demands/Maximum demand of entire group A Maximum demand of entire group/Sum of individual maximum demands A Maximum demand of entire group X Sum of individual maximum demands A Maximum demand of entire group + Sum of individual maximum demands Q In order to have lower cost of electrical energy generation A The load factor and diversity factor should be low. -
Electrical Equipment Room Design Considerations Atlanta Chapter
Atlanta Chapter – IEEE Industry Applications Society Electrical Equipment Room Design Considerations presented at the Sheraton Buckhead Hotel Atlanta, Georgia November 20, 2006 Outline 1. Definitions 2. Power Distribution Configurations 3. Selection of Transformer 4. Installation and Location of Transformer 5. Service Entrance Equipment 6. Selection of Circuit Breaker 7. Electrical Equipment Room Construction (New) 8. Electrical Equipment Room Construction (Existing) 9. Maximum Impedance in a Ground Return Loop to Operate an Overcurrent Protective Device 10. 2005 NEC Requirements Outline 11. Ground Fault Sensing 12. Zero Sequence Sensing vs. Residual Sequence Sensing 13. Power Distribution Systems with Multiple Sources 14. Modified Differential Ground Fault (MDGF) Protection Systems 15. Designing a MDGF Protection System 16. Reported Ground Fault Losses 1. Definitions System Configuration •The system configuration of any Power Distribution System is based strictly on how the secondary windings of the Power Class Transformer, or generator, supplying the Service Entrance Main or loads, are configured. (This includes whether or not the windings are referenced to earth.) • The system configuration is not based on how any specific load or equipment is connected to a particular power distribution system. 1. Definitions Ground Fault Protection System •A designed, coordinated, functional, and properly installed system that provides protection from electrical faults or short circuit conditions that result from any unintentional, electrically conducting connection between an ungrounded conductor of an electrical circuit and the normally non–current-carrying conductors, metallic enclosures, metallic raceways, metallic equipment, or earth. 1. Definitions Ground Fault Protection of Equipment (Per Article 100 in the 2005 NEC) • “A system intended to provide protection of equipment from damaging line-to-ground fault currents by operating to cause a disconnecting means to open all ungrounded conductors of the faulted circuit. -
Electrical Redesign for Greenwich Academy Upper School
| Greenwich Academy Upper School Matthew Fracassini | | Senior Thesis 2004 PSU AE | Electrical Redesign for Greenwich Academy Upper School general description: Power is supplied to the Upper School by an existing 13.2 kV connection located on the exterior of the adjacent building, Ruth West Campbell Hall. A new 750 kVA transformer was added during construction to step the voltage down 208Y/120 V. The transformer is located in a vault beneath the exterior stairway closest to the Gym Building. A 4” conduit bank consisting of three (3) #2 (15kV rated) cables feeds the 3000 A Main Distribution Panel (MDP) located in the basement. This switchboard provides 3-phase power to all of the panels in the building. emergency power: A 200 kW Generator, located in the same vault as the transformer, provides 3- phase power at 208/120 Volts. The generator is connected by 2 sets of 4 500MCM THHN conductors to an 800 A Automatic Transfer Switch in order to ensure safe shifting of the loads in the event of a power fault. The emergency switchboard supplies the emergency lighting system and emergency receptacles, as well as the hydraulic elevator with 208/120 V power. overcurrent devices: The overcurrent protection devices are all located on the Main Distribution Panel (MDP) or the emergency distribution panel (MDP-EM) in the Electrical Room. At this switchboard, all of the panels are protected from overload and ground faults by 3-pole circuit breakers of various capacities. Fused disconnect switches are used to protect from high-level short-circuits. The panels themselves are protected by a 3000 A 3-pole breaker and a 2500A fused disconnect switch. -
Electrical Engineering
Electrical Engineering 6 6 6.0 TABLE OF CONTENTS 6.1 General Approach 6.13 Uninterruptible Power Systems 6.2 Codes and Standards 6.14 Computer Center Power Distribution 183 Electrical Design Standards 6.15 Lighting 6.3 Commissioning 204 Interior Lighting 204 General Lighting Fixture Criteria 6.4 Placing Electrical Systems and 208 Lighting Criteria for Building Spaces Communications Systems in Buildings 208 Lobbies, Atria, Tunnels and Public Corridors 208 Mechanical and Electrical Spaces 6.5 General Design Criteria 208 Dining Areas and Serveries 209 Lighting Controls 6.6 Electrical Load Analysis 210 Exterior Lighting 188 Standards for Sizing Equipment and Systems 6.16 Raceway System for Communications 6.7 Utility Coordination and Site Considerations 212 Communications Raceways 6.8 Site Distribution 6.17 Layout of Main Electrical Rooms 6.9 Primary Distribution 6.18 Alterations in Existing Buildings 193 Transformers and Historic Structures 6 215 Placing Electrical and Communications 6.10 Secondary Distribution Systems in Renovated Buildings 194 Secondary Distribution Systems 216 Building Service 216 Secondary Power Distribution 6.11 Wiring Devices 216 Computer Center Power 197 Placement of Receptacles 216 Lighting 218 Communications Distribution 6.12 Emergency Power Systems 199 Batteries 199 Generator Systems Harry S. Truman Presidential Library and Museum Addition and Renovation Architect: Gould Evans GSA Project Manager: Ann Marie Sweet-Abshire Photo: Mike Sinclair 180 FACILITIES STANDARDS FOR THE PUBLIC BUILDINGS SERVICE 6.0 Table of Contents Revised March 2003 – PBS-P100 It is GSA’s goal to build facilities equipped with the latest 6.1 General Approach advances in office technology and communication.