TIA-607-B Generic Telecommunications Bonding And

Total Page:16

File Type:pdf, Size:1020Kb

TIA-607-B Generic Telecommunications Bonding And ANSI/TIA-607-B-2011 APPROVED: AUGUST 26, 2011 Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises TIA-607-B September 2011 NOTICE TIA Engineering Standards and Publications are designed to serve the public interest through eliminating misunderstandings between manufacturers and purchasers, facilitating interchangeability and improvement of products, and assisting the purchaser in selecting and obtaining with minimum delay the proper product for their particular need. The existence of such Standards and Publications shall not in any respect preclude any member or non-member of TIA from manufacturing or selling products not conforming to such Standards and Publications. Neither shall the existence of such Standards and Publications preclude their voluntary use by Non-TIA members, either domestically or internationally. Standards and Publications are adopted by TIA in accordance with the American National Standards Institute (ANSI) patent policy. By such action, TIA does not assume any liability to any patent owner, nor does it assume any obligation whatever to parties adopting the Standard or Publication. This Standard does not purport to address all safety problems associated with its use or all applicable regulatory requirements. It is the responsibility of the user of this Standard to establish appropriate safety and health practices and to determine the applicability of regulatory limitations before its use. (From Standard Proposal No. 3-4351-RV2-2, formulated under the cognizance of the TIA TR-42 Telecommunications Cabling Systems, TR-42.16 Subcommittee on Premises Telecommunications Bonding & Grounding). Published by ©TELECOMMUNICATIONS INDUSTRY ASSOCIATION Standards and Technology Department 2500 Wilson Boulevard Arlington, VA 22201 U.S.A. PRICE: Please refer to current Catalog of TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION STANDARDS AND ENGINEERING PUBLICATIONS or call IHS, USA and Canada (1-877-413-5187) International (303-397-2896) or search online at http://www.tiaonline.org/standards/catalog/ All rights reserved Printed in U.S.A. NOTICE OF COPYRIGHT This document is copyrighted by the TIA. Reproduction of these documents either in hard copy or soft copy (including posting on the web) is prohibited without copyright permission. For copyright permission to reproduce portions of this document, please contact the TIA Standards Department or go to the TIA website (www.tiaonline.org) for details on how to request permission. Details are located at: http://www.tiaonline.org/standards/catalog/info.cfm#copyright or Telecommunications Industry Association Technology & Standards Department 2500 Wilson Boulevard, Suite 300 Arlington, VA 22201 USA +1.703.907.7700 Organizations may obtain permission to reproduce a limited number of copies by entering into a license agreement. For information, contact IHS 15 Inverness Way East Englewood, CO 80112-5704 or call USA and Canada (1.800.525.7052) International (303.790.0600) NOTICE OF DISCLAIMER AND LIMITATION OF LIABILITY The document to which this Notice is affixed (the “Document”) has been prepared by one or more Engineering Committees or Formulating Groups of the Telecommunications Industry Association (“TIA”). TIA is not the author of the Document contents, but publishes and claims copyright to the Document pursuant to licenses and permission granted by the authors of the contents. TIA Engineering Committees and Formulating Groups are expected to conduct their affairs in accordance with the TIA Engineering Manual (“Manual”), the current and predecessor versions of which are available at http://www.tiaonline.org/standards/procedures/manuals/TIA’s function is to administer the process, but not the content, of document preparation in accordance with the Manual and, when appropriate, the policies and procedures of the American National Standards Institute (“ANSI”). TIA does not evaluate, test, verify or investigate the information, accuracy, soundness, or credibility of the contents of the Document. In publishing the Document, TIA disclaims any undertaking to perform any duty owed to or for anyone. If the Document is identified or marked as a project number (PN) document, or as a standards proposal (SP) document, persons or parties reading or in any way interested in the Document are cautioned that: (a) the Document is a proposal; (b) there is no assurance that the Document will be approved by any Committee of TIA or any other body in its present or any other form; (c) the Document may be amended, modified or changed in the standards development or any editing process. The use or practice of contents of this Document may involve the use of intellectual property rights (“IPR”), including pending or issued patents, or copyrights, owned by one or more parties. TIA makes no search or investigation for IPR. When IPR consisting of patents and published pending patent applications are claimed and called to TIA’s attention, a statement from the holder thereof is requested, all in accordance with the Manual. TIA takes no position with reference to, and disclaims any obligation to investigate or inquire into, the scope or validity of any claims of IPR. TIA will neither be a party to discussions of any licensing terms or conditions, which are instead left to the parties involved, nor will TIA opine or judge whether proposed licensing terms or conditions are reasonable or non-discriminatory. TIA does not warrant or represent that procedures or practices suggested or provided in the Manual have been complied with as respects the Document or its contents. If the Document contains one or more Normative References to a document published by another organization (“other SSO”) engaged in the formulation, development or publication of standards (whether designated as a standard, specification, recommendation or otherwise), whether such reference consists of mandatory, alternate or optional elements (as defined in the TIA Engineering Manual, 4th edition) then (i) TIA disclaims any duty or obligation to search or investigate the records of any other SSO for IPR or letters of assurance relating to any such Normative Reference; (ii) TIA’s policy of encouragement of voluntary disclosure (see Engineering Manual Section 6.5.1) of Essential Patent(s) and published pending patent applications shall apply; and (iii) Information as to claims of IPR in the records or publications of the other SSO shall not constitute identification to TIA of a claim of Essential Patent(s) or published pending patent applications. TIA does not enforce or monitor compliance with the contents of the Document. TIA does not certify, inspect, test or otherwise investigate products, designs or services or any claims of compliance with the contents of the Document. ALL WARRANTIES, EXPRESS OR IMPLIED, ARE DISCLAIMED, INCLUDING WITHOUT LIMITATION, ANY AND ALL WARRANTIES CONCERNING THE ACCURACY OF THE CONTENTS, ITS FITNESS OR APPROPRIATENESS FOR A PARTICULAR PURPOSE OR USE, ITS MERCHANTABILITY AND ITS NONINFRINGEMENT OF ANY THIRD PARTY’S INTELLECTUAL PROPERTY RIGHTS. TIA EXPRESSLY DISCLAIMS ANY AND ALL RESPONSIBILITIES FOR THE ACCURACY OF THE CONTENTS AND MAKES NO REPRESENTATIONS OR WARRANTIES REGARDING THE CONTENT’S COMPLIANCE WITH ANY APPLICABLE STATUTE, RULE OR REGULATION, OR THE SAFETY OR HEALTH EFFECTS OF THE CONTENTS OR ANY PRODUCT OR SERVICE REFERRED TO IN THE DOCUMENT OR PRODUCED OR RENDERED TO COMPLY WITH THE CONTENTS. TIA SHALL NOT BE LIABLE FOR ANY AND ALL DAMAGES, DIRECT OR INDIRECT, ARISING FROM OR RELATING TO ANY USE OF THE CONTENTS CONTAINED HEREIN, INCLUDING WITHOUT LIMITATION ANY AND ALL INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES (INCLUDING DAMAGES FOR LOSS OF BUSINESS, LOSS OF PROFITS, LITIGATION, OR THE LIKE), WHETHER BASED UPON BREACH OF CONTRACT, BREACH OF WARRANTY, TORT (INCLUDING NEGLIGENCE), PRODUCT LIABILITY OR OTHERWISE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. THE FOREGOING NEGATION OF DAMAGES IS A FUNDAMENTAL ELEMENT OF THE USE OF THE CONTENTS HEREOF, AND THESE CONTENTS WOULD NOT BE PUBLISHED BY TIA WITHOUT SUCH LIMITATIONS. ANSI/TIA-607-B Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises Table of Contents 1 SCOPE ................................................................................................................................................... 1 2 Normative references .......................................................................................................................... 2 3 DEFINITIONS......................................................................................................................................... 3 3.1 General ............................................................................................................................................ 3 3.2 Definition of terms ............................................................................................................................ 3 3.3 Abbreviations and acronyms ........................................................................................................... 5 3.4 Units of measure .............................................................................................................................. 7 4 REGULATORY ...................................................................................................................................... 8 4.1 National requirements .....................................................................................................................
Recommended publications
  • How to Choose the Right Cable Category
    How to Choose the Right Cable Category Why do I need a different category of cable? Not too long ago, when local area networks were being designed, each work area outlet typically consisted of one Category 3 circuit for voice and one Category 5e circuit for data. Category 3 cables consisted of four loosely twisted pairs of copper conductor under an overall jacket and were tested to 16 megahertz. Category 5e cables, on the other hand, had its four pairs more tightly twisted than the Category 3 and were tested up to 100 megahertz. The design allowed for voice on one circuit and data on the other. As network equipment data rates increased and more network devices were finding their way onto the network, this design quickly became obsolete. Companies wisely began installing all Category 5e circuits with often three or more circuits per work area outlet. Often, all circuits, including voice, were fed off of patch panels. This design allowed information technology managers to use any circuit as either a voice or a data circuit. Overbuilding the system upfront, though it added costs to the original project, ultimately saved money since future cable additions or cable upgrades would cost significantly more after construction than during the original construction phase. By installing all Category 5e cables, they knew their infrastructure would accommodate all their network needs for a number of years and that they would be ready for the next generation of network technology coming down the road. Though a Category 5e cable infrastructure will safely accommodate the widely used 10 and 100 megabit-per-second (Mbits/sec) Ethernet protocols, 10Base-T and 100Base-T respectively, it may not satisfy the needs of the higher performing Ethernet protocol, gigabit Ethernet (1000 Mbits/sec), also referred to as 1000Base-T.
    [Show full text]
  • CAC, COPPER ALLOY CONDUCTOR in CORROSIVE ENVIRONMENTS Xavier Closa, Overhead Line Electrical Engineer Carme Saez, Strategic Marketing Director
    CAC, Copper Alloy Conductor CAC, COPPER ALLOY CONDUCTOR IN CORROSIVE ENVIRONMENTS Xavier Closa, Overhead Line Electrical Engineer Carme Saez, Strategic Marketing Director ABSTRACT: Copper Alloy Conductors (CAC) transport due to its high electrical and mechanical offer a solution for overhead lines located in corrosive properties. environments, as it has been proved through the experience acquired in a 25 kV line refurbishment in Spain. Historically, the UK has always used copper for small conductors within 10km of the coast due to the heavy salt corrosion of aluminium. Samples of copper and aluminium conductors were collected and further analysed; quantifying the degradation suffered during their service, which in the aluminum case show a significant loss of electrical and mechanical properties. Thanks to the copper microalloy, it can operate at high An economic analysis has also been included, providing temperatures without creeping, thus increasing its an estimation of the necessary investment. capacity. La Farga has designed 5 different copper alloys in order to satisfy different cases, specially the KEY WORDS: Copper, CAC, corrosive most demanding ones: environments, La Farga, overhead lines, a CAC-50-Pica d’Estats-UHC. UHC (Ultra High Conductivity) HC (High Conductivity) STD (Standard) 1. INTRODUCTION HS (High Strength) UHS (Ultra High Strength) La Farga is a copper manufacturer with more than 200 years of history, its large experience covers a wide As well as these characteristics, copper also has the range of copper products used in different sectors: inherent advantage that it does not suffer from railways, tubes, electrical wiring, automotive, etc. vibration fatigue as badly as aluminium. It has a significantly higher EDS (Every Day Stress) limit than The extensive knowledge of copper alloys and the aluminium.
    [Show full text]
  • Technical Information Handbook Wire and Cable
    Technical Information Handbook Wire and Cable Fifth Edition Copyright © 2018 Trademarks and Reference Information The following registered trademarks appear in this handbook: Information in this handbook has been drawn from many Alumel® is a registered trademark of Concept Alloys, LLC publications of the leading wire and cable companies in the industry and authoritative sources in their latest available Chromel® is a registered trademark of Concept Alloys, LLC editions. Some of these include: Copperweld® is a registered trademark of Copperweld Steel Company CSA® is a registered trademark of the Canadian Standards Association • American Society for Testing and Materials (ASTM) CCW® is a registered trademark of General Cable Corporation • Canadian Standards Association (CSA) ® DataTwist is a registered trademark of Belden • Institute of Electrical and Electronics Engineers (IEEE) Duofoil® is a registered trademark of Belden Flamarrest® is a registered trademark of Belden • Insulated Cable Engineers Association (ICEA) Halar® is a registered trademark of Solvay Solexis • International Electrotechnical Commission (IEC) Hypalon® is a registered trademark of E. I. DuPont de Nemours & Company • National Electrical Manufacturers Association (NEMA) Hypot® is a registered trademark of Associated Research, Inc. • National Fire Protection Association (NFPA) IBM® is a registered trademark of International Business Machines Corporation Kapton® is a registered trademark of E. I. DuPont de Nemours & Company • Naval Ship Engineering Center (NAVSEC) Kevlar® is a registered trademark of E. I. DuPont de Nemours & Company • Telecommunications Industry Association (TIA) ® K FIBER is a registered trademark of General Cable Corporation • Underwriters Laboratories (UL). Kynar® is a registered trademark of Arkema, Inc. Loc-Trac® is a registered trademark of Alpha Wire Note: National Electrical Code (NEC) is a registered trademark of the National Fire Protection Association, Quincy, MA.
    [Show full text]
  • A Study of the Characteristics and Limitations of Various Platings
    A STUDY OF THE CHARACTERISTICS AND LIMITATIONS OF VARIOUS PLATINGS ON CYLINDRICAL ELECTRICAL CONDUCTORS by ROBERT C. SCULLY Presented to the Faculty of the Graduate School of The University of Texas at Arlington in Partial Fulfillment of the Requirements for the Degree of DOCTOR OF PHILOSOPHY THE UNIVERSITY OF TEXAS AT ARLINGTON December 2013 Copyright © by Robert C. Scully 2013 All Rights Reserved ii Acknowledgements This work might never have been completed without the patience and understanding of Dr. Jonathan Bredow, my advisor for it seems too many years to number. His constancy and quiet demeanor gave me the strength and resolve to see this through in spite of life’s adversities and setbacks. I also would like to acknowledge the support of my co-workers and my professional colleagues, without who I would have given up long ago. Last, and certainly not least, I want to mention the love and support from my wife and lifelong companion, Elizabeth, a guiding star through thick and thin, and most importantly in the darkest days of my despair, as I struggled through this process. November 20, 2013 iii Abstract A STUDY OF THE CHARACTERISTICS AND LIMITATIONS OF VARIOUS PLATINGS ON CYLINDRICAL ELECTRICAL CONDUCTORS Robert C. Scully, PhD The University of Texas at Arlington, 2013 Supervising Professor: Jonathan Bredow This work explores the impedance characteristics of copper wires plated with tin, silver, or nickel, the most common type of wiring used in the computer, communications, and aerospace industries. The background of plated wires and a brief review of related research is provided. This is followed by a detailed development of the theory of plated wires, accompanied by a MAPLE code in the appendix that can be used for the numerical analysis of plated wires having two or more plating layers.
    [Show full text]
  • RG-6 Cable Coax Cable
    C51 pg 017 8/4/06 9:10 AM Page 17 Coax Cable Wire and Cable Coaxial Cable Belden New Generation coaxial cable. UL type CM approval. Foam dielectric Plenum Rated and black PVC jacket. 549945 is Siamese Section construction, 1 RG-59/U with 2/18 AWG. 1 Coax Cable 573945 is miniature RG-59/U. Applications: 1 Belden New Generation plenum coaxial cable. UL CCTV and CATV (CATV 5339B5 and 5339Q5 type CMP approval. Foam dielectric and natural only). Key: BC=Bare Copper, CCS= Copper Flamarrest jacket. 649948 is Siamese construction, covered steel, FB= Foil plus braid. 1 RG-59/U with 2/18AWG. Applications: CCTV Ctr./ Wire and Cable and CATV (CATV 633938 and 6339Q8 only). Key: Order # Length RG/U Shield (ea.) (2-4) (5-up) BC=Bare Copper, CCS= Copper covered steel, Antenna Wire . .21 Hook-Up Wire . .24 FB= Foil plus braid. Mfr. #543945 Audio Control Wire 21, 22 Kynar Wire . .24 24-4980 1000' 59 BC/BC $273.00 $252.04$234.66 Audio/Video Cables 25~35 Magnetic Wire . .23 Ctr./ 24-4985 500' 59 BC/BC 152.00 138.88 128.40 Audio Snake Cables . .34 Microphone Cable . .21 Order # Length RG/U Shield (ea.) (2-4) (5-up) Mfr. # 533985 Automotive Wire . .24 Multi-Conductor Mfr. # 643948 24-4990 1000' 6 BC/FB 196.00 180.93 168.45 Cable Management 36~41 Wire . .22, 23 24-4930 1000' 59 BC/BC $859.00 $794.63 $739.83 24-4995 500' 6 BC/FB 109.00 99.70 92.17 Car Audio Wire .
    [Show full text]
  • A Comparison of Aluminum Vs. Copper As Used in Electrical Equipment
    A COMPARISON OF ALUMINUM VS. COPPER AS USED IN ELECTRICAL EQUIPMENT Larry Pryor, P.E. – Sr. Specification Engineer, GE Consumer & Industrial Rick Schlobohm, P.E. – Sr. Specification Engineer, GE Consumer & Industrial Bill Brownell, P.E – Specification Engineer, GE Consumer & Industrial ABSTRACT strength limits its use to special applications The debate over the pros and cons of aluminum vs. such as joint plating and sliding contact surfaces. copper conductors has been discussed for many years. Many of the concerns are based on old For the purposes of this paper, the areas of information and also misinformation. These discussion are: concerns center on the very different properties of the two materials and their suitability for - Current Carrying Capacity, Conductivity application within the Electrical Equipment - Physical Properties Industry. Reliable performance from the a. Expansion conductors, the joints and terminations of the b. Weight conductors is essential to the operation of the c. Tensile Strength electrical system. With the recent increases in the - Connections and Terminations cost of copper, customers are seeing these - Plating and Environmental Concerns increases passed on to them by the equipment - Product Offerings manufacturer. The variance in cost between - Cost Comparison equipment with copper versus aluminum - Impact on Various Pieces of Equipment conductors is now affecting the customer’s buying decision. CURRENT CARRYING CAPACITY This paper provides a comparison of the The electrical and mechanical properties of a mechanical and electrical properties of copper (Cu) material are dependent on its alloy. For the and aluminum (Al) and their relevance as applied to comparison between copper and aluminum in electrical distribution products.
    [Show full text]
  • Fields of Application of Nickel Plated Copper Conductor
    Fields of application of nickel plated copper conductor By Selcuk Harput Sarkuysan Electrolytic Copper Co. Turkey Abstract: Increasing experience in nickel coating techniques on copper wire has been an important factor encouraging its use in the form of cables for high temperature applications. Unfortunately, the expected amendments in related standards lagged behind, or simply neglected, are essential for correct material selection for cable producers and end users. To compare the properties of nickel plated copper wire to those of tin and silver plated copper wires and highlight the outstanding properties gained by nickel plating in regard to their high temperature applications are the aims of this paper. The main topics taken under consideration are physical, electrical and thermal properties of nickel coated copper wire, its standard specifications and wire geometries, its comparison with other coating metals (i.e. tin and silver) and giving information about special thermally resistant insulation materials, and the bases of selection for best wiring material under different environmental conditions at certain temperatures. Selcuk Harput is R&D Manager in Sarkuysan Electrolytic Copper Co., Turkey. He is responsible for all research and development activities of Sarkuysan. He joined Sarkuysan in 1988. He was previously primary aluminium production superintendent in Etibank Aluminum Plant, Turkey. He holds a diploma in metallurgical engineering from The Middle East Technical University, Ankara, Turkey. He is a member of WAI, AESF and Chamber of Metallurgical Engineers in Turkey. Nickel plating: a short history Nickel can be expressed as good high and low temperature strength, high oxidation resistance, corrosion resistant, highly desirable material. Nickel was discovered in 1751 by Cronsted in Sweden.
    [Show full text]
  • THWN Or THHN PVC Insulation, Nylon Jacket, 600 Volts
    THWN or THHN PVC Insulation, Nylon Jacket, 600 Volts APPLICATION: General purpose wiring in accordance with the National Electrical Code, maximum conductor temperature of 90°C in dry locations and 75°C in wet locations, 600 volts, for installation in conduit or other recognized raceway. Also used for wiring of machine tools (stranded), ap- pliances, and control circuits not exceeding 600 volts. STANDARDS: 1. Listed by UL as Type THHN or THWN per Standard 83, and as Type MTW per Standard 1063 (stranded items). 2. Listed by UL as Gasoline and Oil Resistant 11. 3. Listed by UL as Sunlight Resistant (1/0 AWG and larger, black only). 4. 1/0 AWG and larger pass UL and IEEE-383 ribbon burner flame test and are listed For CT Use. 5. Listed by UL as 105°C Appliance Wiring Material, 60°C where exposed to oil (stranded items only). 6. C(UL) listed as Type T90 Nylon or TWN75, FT1. 7. Conforms to Federal Specification J-C-30B. CONSTRUCTION: Annealed uncoated copper conductor, PVC insulation, nylon jacket, surface printed. Thickness Approx. Wt. NEC Ampacity* Size in Mils Nom- lbs/1000 ft AWG PVC final USAWC or No. of Insula- Nylon Diam. 75°C 90°C Part # kcmil Strands tion Jacket Inches THWN THHN Net Copper Solid (THWN or THHN) 14-01SOLTHHN 14 Solid 15 4 .105 20 25 16 12 12-01SOLTHHN 12 Solid 15 4 .122 25 30 24 20 10-01SOLTHHN 10 Solid 20 4 .153 35 40 38 31 Stranded (MTW or THWN or THHN) 14-01THHN 14 19 15 4 .112 20 25 16 12 12-01THHN 12 19 15 4 .130 25 30 24 18 10-01THHN 10 19 20 4 .164 35 40 38 32 8-01THHN 8 19 30 5 .220 50 55 64 51 6-01THHN 6 19
    [Show full text]
  • All Aluminum Conductor, Bare 800-238-7514
    AAC All Aluminum Conductor, Bare Construction Aluminum alloy 1350-H19 wires, concentrically stranded. Specifications Meets or exceeds the following ASTM specifications: • B-230 Aluminum Wire, 1350-H19 for Electrical Purposes • B-231 Aluminum Conductors, Concentric-Lay-Stranded See referenced page in the Applications Hardware & Supplies section: Classes* AA and A are used primarily for overhead transmission and Suggested Prep Tool primary and secondary distribution where ampacity must be maintained • Cable End Strippers and a lighter conductor (compared to ACSR) is desired, when conductor 2x2, 4x4 - I-9 strength is not a critical factor. Classes B and C are used primarily as bus, apparatus connectors and jumpers where additional flexibility is required. *Classes refer to stranding and are an indication of relative conductor flexibility, AA being the least flexible, C the most flexible. Resistance Stranding (Ohms/M-ft) Size (AWG Individual Complete Allowable Ampacity Code Word or kcmils) No. of Wires Class Wire Dia. (in) Cable Dia. (in) DC @ 20˚C AC @ 20˚C (amps) Iris 2 7 AA, A .0974 .292 .26000 .31800 185 Poppy 1/0 7 AA, A .1228 .368 .16400 .20000 247 Aster 2/0 7 AA, A .1379 .414 .13000 .15900 286 Phlox 3/0 7 AA, A .1548 .464 .10300 .12600 331 Oxlip 4/0 7 AA, A .1739 .522 .08170 .09990 383 Laurel 266.8 19 A .1185 .592 .06480 .07930 444 Tulip 336.4 19 A .1331 .665 .05140 .06300 513 Daffodil 350 19 A .1357 .679 .04940 .06050 526 Canna 397.5 19 AA, A .1446 .723 .04350 .05340 570 Cosmos 477 19 AA .1584 .792 .03620 .04450 639 Dahlia 556.5 19 AA .1711
    [Show full text]
  • C102/C110 Copper Conductor Wire
    C102/C110 Copper Conductor Wire Copper is the “standard” metal used for electrical conductors. Copper has extremely high electrical conductivity, surpassed only by pure silver and it has excellent tensile, solderability and corrosion characteristics. C102 is an oxygen free (OF) copper that has better drawing and resistance to hydrogen embrittlement than C110 (ETP). OF copper contains less dissolved oxygen than ETP, which gives OF its performance advantage. In most applications, ETP is an acceptable conductor material and is more economical than OF copper. Both OF and ETP copper conductors are available bare or plated with silver, nickel or tin. Physical Properties SOFT Tensile 32 ksi Elongation 10 - 20% Electrical Conductivity 100% IACS* @ 68°F Electrical Resistivity 10.37 cir mil ohm/ft @ 68°F Melting Point 1981°F Density 0.323 lbs/in³ Thermal Coefficient of Resistance 0.00218 Per °F 19-Strand Unilay Constructions NICKEL PLATED COPPER - SOFT (50 MICRO-INCH NICKEL THICKNESS) DIAMETER (inch) RESIST WEIGHT AWG CONST (Ω/mft) (lb/mft) MIN MAX MAX MAX 18 19/30 0.0462 0.0480 5.97 5.94 20 19/32 0.0368 0.0387 9.52 3.86 22 19/34 0.0289 0.307 15.4 2.43 24 19/36 0.0228 0.0247 24.7 1.57 26 19/38 0.0182 0.0200 40.0 1.037 28 19/40 0.0140 0.0159 67.5 0.648 SILVER PLATED COPPER - SOFT (40 MICRO-INCH SILVER THICKNESS) DIAMETER (inch) RESIST WEIGHT AWG CONST (Ω/mft) (lb/mft) MIN MAX MAX MAX 18 19/30 0.0462 0.0471 5.79 5.73 20 19/32 0.0368 0.0377 9.19 3.69 22 19/34 0.0289 0.0298 15.0 2.32 24 19/36 0.0228 0.0238 23.9 1.46 26 19/38 0.0182 0.0191 37.7 0.948 28 19/40 0.0140 0.0149 63.7 0.578 30 19/42 0.0112 0.0121 99.0 0.381 32 19/44(1) 0.0094 0.0104 154.2 0.257 (1) True Concentric Custom constructions are available, please contact the sales department The information provided on this page is for reference purposes only.
    [Show full text]
  • Aluminum Building Wire Installation and Terminations
    ALUMINUM BUILDING WIRE INSTALLATION AND TERMINATIONS Aluminum Building Wire Installation and Terminations by Christel Hunter 78 IAEI NEWS January.February 2006 www.iaei.orwww.iaei.orgg ALUMINUM BUILDING WIRE INSTALLATION AND TERMINATIONS Welcome to the 21st Century! n my experiences as a field engineer with Alcan Cable, I’m often asked about the right way to install aluminum building wire. Quite often I’m told that aluminum wiring is fine, as long as the installer is careful. The implication is that install- Iing aluminum building wire is in some way trickier than installing copper building wire. Although this might have been true with pre- 1972 aluminum wire, conductor and connector changes have made installing aluminum building wire as simple as installing copper. History of Aluminum Wire Electricity is transmitted from the utility generating station to in- dividual meters using almost exclusively aluminum wiring. In the U.S., utilities have used aluminum wire for over 100 years. It takes only one pound of aluminum to equal the current-carrying capac- ity of two pounds of copper. The lightweight conductors enable the utility to run transmission lines with half the number of supporting structures. The utility system is designed for aluminum conductors, and utility installers are familiar with installation techniques for the types of aluminum conductors used in utility applications. Feeder and branch-circuit wiring systems were designed primar- ily for copper conductors. Aluminum wiring was evaluated and listed by Underwriter’s Laboratories for interior wiring applications in 1946; however, it was not used heavily until 1965. At that time, www.iaei.org January.February 2006 IAEI NEWS 79 ALUMINUM BUILDING WIRE INSTALLATION AND TERMINATIONS copper shortages and high prices made the installation The most likely and often identified culprits were: work- of aluminum branch-circuit conductors a very attractive manship, thermal expansion differences and creep.
    [Show full text]
  • Nasa Tech Brief
    https://ntrs.nasa.gov/search.jsp?R=19670000122 2020-03-11T20:45:32+00:00Z View metadata, citation and similar papers at core.ac.uk brought to you by CORE provided by NASA Technical Reports Server May 1967 Brief 67-10122 NASA TECH BRIEF NASA Tech Briefs are issued to summarize specific innovations derived from the U.S. space program, to encourage their commercial application. Copies are available to the public at 15 cents each from the Clearinghouse for Federal Scientific and Technical Information, Springfield, Virginia 22151. Evaluation of High Temperature Stranded Hookup Wire In the selection of wire and insulation materials for for most high temperature uses and will withstand electronic space assemblies, proper consideration must temperatures well above the normal 100°C applica- be given to design criteria and end use requirements. tions. Knowledge of the advantages and limitations of these The use of Teflon extruded insulation is limited by materials will prevent overspecifications and should the inability of tin coated applications to withstand the result in direct cost savings. Teflon extrusion temperatures which range up to To aid in the selection of these materials, tests 540°C. In space system applications using Teflon were performed to determine primary wire charac- insulated wires, the copper conductors are plated with teristics in the areas of tensile strength, flexibility, nickel or silver. The silver plating results in cuprous conductivity, and general workability. Supplemen- oxide or "red plague", a condition generally recog- tary sampling tests were included to supply additional nized throughout the space industry. The silver over information usually required by procurement specifi- nickel over copper conductor was intended to over- cations.
    [Show full text]