Design Considerations for Heat Pump Compressors J

Total Page:16

File Type:pdf, Size:1020Kb

Design Considerations for Heat Pump Compressors J Purdue University Purdue e-Pubs International Compressor Engineering Conference School of Mechanical Engineering 1976 Design Considerations for Heat Pump Compressors J. F. Horn P. H. Scharf Follow this and additional works at: https://docs.lib.purdue.edu/icec Horn, J. F. and Scharf, P. H., "Design Considerations for Heat Pump Compressors" (1976). International Compressor Engineering Conference. Paper 192. https://docs.lib.purdue.edu/icec/192 This document has been made available through Purdue e-Pubs, a service of the Purdue University Libraries. Please contact [email protected] for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html DESIGN CONSIDERATIONS FOR HEAT PUMP COMPRESSORS JAMES HORN, MANAGER HERMETIC COMPRESSOR DESIGN AND PROillCTION ENGINEERING PHILIP SCHARF, MANAGER HERMETIC CCMPRESSOR ENGINEERING COPELAND CORPORATION, SIDNEY, OHIO INTRODUCTION A typical application condition (Figure 4\ would be a 20°F outdoor ambient with an evaporating The increased cost of energy for heating purposes temperature of 5°F. For a compressor isolated in makes the heat pump system more and more attrac­ a separate compartment in the outdoor coil cabinet, tive. The economy of operation of the heat pump the ambient temperature would be about 45°F to 50° will create high demand for this equipment in the F. next few years. This may well be the fastest growing segment of the air conditioning industry. A severe environment condition would be a low evaporating temperature occurring along with a Good system design and use of reliable components high condensing temperature (see Figure 5). This is essential for the success of a heat pump. condition could result from an outdoor ambient Operating conditions are more severe and the temperature of 0° to -l0°F, and restricted air system will be utilized two to three times longer flow over the indoor coil. Here the compressor each year than a conventional air conditioner. could experience evaporating and condensing tempera~ures in the range of -l5°F and ll0°F, With these added requirements in mind we will respect1vely. explore the design of compressors developed especially for heat pump systems. (3) Pressure Ratios HEAT PUMP SYSTEM CONDITIONS The pressure ratio is defined as the absolute discharge pressure divided by the absolute evapora­ (1) Qperating Hours ting pressure. In air conditioning systems, the pressure ratio seldom exceeds 4 to 1. In heat In Northern climates, a heat pump compressor may pumps, the ratio may exceed 8 to 1 as indicated by be required to operate up to seven times longer Figure 6. each year than that required for air conditioning only (see Figure 1). The operating time for a Pressure ratios are a major consideration in heat typical location will be increased by a factor of pump compressor design. As the ratio increases, three. bearing lubrication and discharge valve tempera­ tures may be adversely affected. Figure 7 shows (2) Evaporating and Condensing Temperatures a worn rod-wrist pin bearing. This is a bearing that provides long life when operating on cooling A heat pump compressor must be capable of operating only systems but has a limited life at the higher under a wide range of system conditions - from air pressure ratios experienced under heating conditioning to extreme heat pump conditions. The conditions. Figure 8 shows a valve plate that has standard by which air conditioning compressors been operating at excessive discharge gas tempera­ have been rated for many years (see Figure 2), is ture. The deposits are products of oil breakdown. 130°F condensing temperature and 45°F evaporating Accumulation of such deposits will eventually temperature. prevent proper valve closing and result in loss of performance. At the A.R.I. standard for rating heat pumps (Figure 3), a heat pump system is very effective (4) Liquid Refrigerant Return and yields a high coefficient of performance. Here the condensing and evaporating temperatures are Compressors may be subjected to excessive liquid approximately ll0°F and 30°F respectively. This return during the defrost cycle if the system does condition and the air conditioning standard are not have adequate provision to control liquid flow ideal conditions for the compressor. to the compressor. Liquid flooding is character­ ized by a severe drop in compressor oil sump temperature. 194 Excessive liquid refrigerant in the compressor oil starves the pin bearing of oil. The wear shown in sump can have these damaging effects: Figure 7 was induced by operating the compressor in heating mode with the evaporating temperature Slugging - mechanical stress on valves, gaskets, at -l5°F and the oil sump temperature above 250°F. piston-rod assemblies; The bearing surface area must be increased to Loss of oil - violent "boiling" of the refrigerant compensate for less favorable lubrication. We have in the oil sump may carry the oil out in the form found from our development work that wrist pin of foam; bearing areas must be increased 20% to 40% from air conditioning only compressor designs. Dilution of the oil - floodback may dilute the oil to the extent that bearing failure will result; (2) Pistons Piston seizure - rapid change in temperature may A sudden drop in the oil sump temperature may result in loss of piston-to-cylinder clearance and cause the cylinder to "shrink" at a faster rate piston failure. than the piston, resulting in loss of running clearance and piston-to-cylinder seizure. Sudden (5) Low Ambient Temperature Operation temperature drops in the oil result from inadequate liquid control during the defrost cycle. Pistons Low outdoor ambients produce low evaporating with rings have greater running clearance and have pressures and light loads on the compressor. On the ability to survive such thermal shock. single phase motors, light loads impress high voltages on the n.n1 capacitor. (3) Oil Cold starts after a long shut dawn may be damaging The hazards of liquid refrigerant in the heat pump to a compressor if the crankcase heater is not compressor oil sump were listed under "heat pump completely effective. If liquid refrigerant is operating conditions". The oil crnmnonly used in allowed to accumulate in the oil sump it may dilute air conditioning systems mixes readily with liquid the oil and prevent adequate bearing lubrication. refrigerant and can be carried from the compressor If sufficient liquid accumulates it can result in when excessive floodback occurs. The heat pump mechanical damage to valves, gaskets, etc. compressor may frequently be subjected to exces­ sive liquid return, therefore, an oil that is (6) Fault Conditions- easily carried out of the compressor becomes a design concern. Loss of refrigerant - Heat pumps have more complex refrigerant circuitry and more opportunity for ''White oil" (a highly refined mineral oil) has an system leaks to occur. As refrigerant is lost anti-foaming quality that makes it a good candidate from the system, the load on the compressor is for heat pump compressors. System tests with reduced. The reduced load allows the motor to run strategically located sight glasses dramatically at increased speeds which increases the current in demonstrate white oil's ability to stay in the the auxiliary winding and may cause severe over­ compressor oil sump under flooding conditions that heating. This occurs at a time when the motor will carry out standard air conditioning oil. The cooling medium (the refrigerant) is in short compressor experiences less dilution of the oil supply. If the motor protector is responsive to and no loss of lubrication. this condition, it will shut the motor off before the motor temperature reaches a danger point. (4) Motor Protection However, if this condition goes undetected for an extended period of time, the life of the protector Since the heat pump compressor is called on to could be in jeopardy. Since heat pumps have operate three times longer each year and ttnder more auxiliary resistance heaters, which can supply the varied and adverse conditions, the role of the entire heating requirement, a malfunctioning heat motor protection system becomes more significant. pump system may go undetected for an extended A common and successful protection design for air period of time. conditioning systems is a device that senses the combined current of the main and auxiliary motor Blocked condenser - Dirty indoor air filters windings and is located to thermally respond to increase condensing temperature and the pressure high winding temperatures at low currents. ratio that the compressor must operate under. However, to fully protect the compressor at the various heat pump system conditions, additional HEAT PUMP COMPRESSOR DESIGN requirements must be placed on the motor protec­ tion system. (1) Connecting Rod-Wrist Pin Bearing Internal motor protectors are now available that High pressure ratios frequently experienced in can respond to high currents in the main and heat pump operation impose greater requirements on auxiliary windings independently. The protector the wrist pin bearings. The wrist pin is a low has two heaters, one in series with each winding surface velocity bearing that relies on load circuit. A comparison of the two types of motor­ reversal to aid in its lubrication. High pressure protector circuits can be seen in Figure 9. ratios reduce the load reversing action, which 195 The addition of the auxiliary winding heater pro­ (4) Low Ambient Qperation vides these benefits; Typical compressor performance curves with 10° Limits high auxiliary winding temperatures that superheat are shown in Figure 10. Note that these may occur from light loads and high line voltages; curves are cut off at the limit of safe operating temperatures with this amount of superheat. At Protects the compressor motor against sticking low ambient temperatures, the stresses resulting start relay contacts.
Recommended publications
  • Best Practices in Central Heat Pump Water Heating
    MAR 2018 Heat Pumps Are Not Boilers ACEEE – HOT WATER FORUM 2018 | Shawn Oram, PE, LEED AP Director of Engineering & Design ECOTOPE.COM • OVERVIEW • END GAME • WHAT’S AVAILABLE NOW • PROBLEMS WE ARE SEEING • MARKET DEVELOPMENT NEEDS • QUESTIONS AGENDA ECOTOPE.COM 2 Common Space Heat, Seattle 2014 Benchmarking Data 5 DHW Heat, 10 Median EUI (kBtu/SF/yr) Unit Space 1/3 OF THE LOAD IS Heat, 5 TEMPERATURE MAINTAINANCE Lowrise EUI = 32 Unit Non- Common Heat, 10 Non-Heat, Midrise EUI = 36 10 2009 Multifamily EUI (KBTU/Sf/Yr) Highrise EUI = 51 Breakdown By Energy End Use Type MULTIFAMILY ENERGY END USES ECOTOPE.COM 3 “Heat Pumps Move Heat” Optimize storage design to use coldest water possible HEAT PUMP WATER HEATING ECOTOPE.COM 4 R-717 0 BETTER CO2 Variable Capacity | SANDEN, R-744 1 MAYEKAWA, MITSUBISHI Eco-Cute R-1270 2 GWP OF SELECTED REFRIGERANTS R-290 3 (Carbon Dioxide Equivalents, CO2e) R-600a 3 Proposed HFO replacement refrigerant R-1234yf 4 R-1150 4 R-1234ze 6 Refrigerants have 10% of the climate R-170 6 forcing impact of CO2 Emissions R-152a 124 Fixed Capacity| MOST HPWH’s R-32 675 COLMAC, AO SMITH R-134a 1430 R-407C 1744 Variable Capacity | PHNIX, R-22 1810 ALTHERMA, VERSATI R-410A 2088 Fixed Capacity| AERMEC R-125 3500 R-404A 3922 R-502 4657 WORSE R-12 10900 REFRIGERANT TYPES ECOTOPE.COM 5 • No Refrigerant • 20-30% Less Energy • Quiet • GE/Oak Ridge Pilot • Ready for Market -2020 MAGNETO-CALORIC HEAT PUMP ECOTOPE.COM 6 140˚ 120˚ HOT WATER HEAT PUMP HOT WATER HEAT PUMP STORAGE WATER STORAGE WATER HEATER HEATER 50˚ 110˚ Heat the water up to usable Heat the water up 10-15 degrees temp in a single pass.
    [Show full text]
  • The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating
    Solar Calorimetry Laboratory The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating Stephen Harrison Ph.D., P. Eng., Solar Calorimetry Laboratory, Dept. of Mechanical and Materials Engineering, Queen’s University, Kingston, ON, Canada Solar Calorimetry Laboratory Background • As many groups try to improve energy efficiency in residences, hot water heating loads remain a significant energy demand. • Even in heating-dominated climates, energy use for hot water production represents ~ 20% of a building’s annual energy consumption. • Many jurisdictions are imposing, or considering regulations, specifying higher hot water heating efficiencies. – New EU requirements will effectively require the use of either heat pumps or solar heating systems for domestic hot water production – In the USA, for storage systems above (i.e., 208 L) capacity, similar regulations currently apply Canadian residential sector energy consumption (Source: CBEEDAC) Solar Calorimetry Laboratory Solar and HP water heaters • Both solar-thermal and air-source heat pumps can achieve efficiencies above 100% based on their primary energy consumption. • Both technologies are well developed, but have limitations in many climatic regions. • In particular, colder ambient temperatures lower the performance of these units making them less attractive than alternative, more conventional, water heating approaches. Solar Collector • Another drawback relates to the requirement to have an auxiliary heat source to supplement the solar or heat pump unit,
    [Show full text]
  • Refrigerant Selection and Cycle Development for a High Temperature Vapor Compression Heat Pump
    Refrigerant Selection and Cycle Development for a High Temperature Vapor Compression Heat Pump Heinz Moisia*, Renè Riebererb aResearch Assistant, Institute of Thermal Engineering, Graz University of Technology, Inffeldgasse 25/B, 8010 Graz, Austria bAssociate Professor, Institute of Thermal Engineering, Graz University of Technology, Inffeldgasse 25/B, 8010 Graz, Austria Abstract Different technological challenges have to be met in the course of the development of a high temperature vapor compression heat pump. In certain points of operation, high temperature refrigerants can show condensation during the compression which may lead to compressor damage. As a consequence, high suction gas superheat up to 20 K can be necessary. Furthermore high compressor outlet temperatures caused by high heat sink outlet temperatures (approx. 110 °C) and high pressure ratios can lead to problems with the compressor lubricant. In order to meet these challenges different refrigerant and cycle configurations have been investigated by means of simulation. Thermodynamic properties as well as legal and availability aspects have been considered for the refrigerant selection. The focus of the cycle configurations has been set on the realization of the required suction gas superheat. Therefore the possibility of an internal heat exchanger and a suction gas cooled compressor has been investigated. The simulation results showed a COP increase of up to +11 % due to the fact that the main part of the suction gas superheat has not been provided in the evaporator. Furthermore, the effect of increased subcooling has been investigated for a single stage cycle with internal heat exchanger. The results showed a COP of 3.4 with a subcooling of 25 K at a temperature lift of approximately 60 K for the refrigerant R600 (n-butane).
    [Show full text]
  • High Temperature Heat Pump Using HFO and HCFO Refrigerants
    Purdue University Purdue e-Pubs International Refrigeration and Air Conditioning School of Mechanical Engineering Conference 2018 High temperature heat pump using HFO and HCFO refrigerants - System design, simulation, and first experimental results Cordin Arpagaus NTB University of Applied Sciences of Technology Buchs, Switzerland, [email protected] Frédéric Bless NTB University of Applied Sciences of Technology Buchs, Institute for Energy Systems, Werdenbergstrasse 4, 9471 Buchs, Switzerland, [email protected] Michael Uhlmann NTB University of Applied Sciences in Buchs, Switzerland, [email protected] Elias Büchel NTB University of Applied Sciences of Technology Buchs, Institute for Energy Systems, Werdenbergstrasse 4, 9471 Buchs, Switzerland, [email protected] Stefan Frei NTB University of Applied Sciences of Technology Buchs, Institute for Energy Systems, Werdenbergstrasse 4, 9471 Buchs, Switzerland, [email protected] See next page for additional authors Follow this and additional works at: https://docs.lib.purdue.edu/iracc Arpagaus, Cordin; Bless, Frédéric; Uhlmann, Michael; Büchel, Elias; Frei, Stefan; Schiffmann, Jürg; and Bertsch, Stefan, "High temperature heat pump using HFO and HCFO refrigerants - System design, simulation, and first experimental results" (2018). International Refrigeration and Air Conditioning Conference. Paper 1875. https://docs.lib.purdue.edu/iracc/1875 This document has been made available through Purdue e-Pubs, a service of the Purdue University Libraries. Please contact [email protected]
    [Show full text]
  • Performance of a Heat Pump Water Heater in the Hot-Humid Climate, Windermere, Florida
    BUILDING TECHNOLOGIES OFFICE Building America Case Study Technology Solutions for New and Existing Homes Performance of a Heat Pump Water Heater in the Hot-Humid Climate Windermere, Florida Over recent years, heat pump water heaters (HPWHs) have become more read- PROJECT INFORMATION ily available and more widely adopted in the marketplace. A key feature of an Project Name: Systems Evaluation at HPWH unit is that it is a hybrid system. When conditions are favorable, the unit the Cool Energy House will operate in heat pump mode (using a vapor compression system that extracts Location: Windermere, FL heat from the surrounding air) to efficiently provide domestic hot water (DHW). Partners: Homeowners need not adjust their behavior to conform to the heat pump’s Southern Traditions Development capabilities. If a heat pump cannot meet a higher water draw demand, the heater http://southerntraditionsdev.com/ will switch to electric resistance to provide a higher heating rate. This flexibility Consortium for Advanced provides the energy savings of heat pump mode (when possible) while perform- Residential Buildings www.carb-swa.com ing as an electric resistance water heater (ERWH) during periods of high DHW demand. Furthermore, an HPWH’s operational byproduct is cooling and dehu- Building Component: Domestic hot water midification, which can be particularly beneficial in hot-humid climates. Application: Retrofit, single family For a 6-month period, the Consortium for Advanced Residential Buildings, a Year Tested: 2012 U.S. Department of Energy Building America team, monitored the performance Applicable Climate Zone(s): Hot-humid of a GE Geospring HPWH in Windermere, Florida. The study included hourly energy simulation analysis using the National Renewable Energy Laboratory’s PERFORMANCE DATA Building Energy Optimization-Energy Plus (BEopt) v1.3 software.
    [Show full text]
  • Design of a Heat Pump Assisted Solar Thermal System Kyle G
    Purdue University Purdue e-Pubs International High Performance Buildings School of Mechanical Engineering Conference 2014 Design of a Heat Pump Assisted Solar Thermal System Kyle G. Krockenberger Purdue University, United States of America / Department of Mechanical Engineering Technology, [email protected] John M. DeGrove [email protected] William J. Hutzel [email protected] J. Christopher Foreman [email protected] Follow this and additional works at: http://docs.lib.purdue.edu/ihpbc Krockenberger, Kyle G.; DeGrove, John M.; Hutzel, William J.; and Foreman, J. Christopher, "Design of a Heat Pump Assisted Solar Thermal System" (2014). International High Performance Buildings Conference. Paper 146. http://docs.lib.purdue.edu/ihpbc/146 This document has been made available through Purdue e-Pubs, a service of the Purdue University Libraries. Please contact [email protected] for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html 3572 , Page 1 Design of a Heat Pump Assisted Solar Thermal System Kyle G. KROCKENBERGER 1*, John M. DEGROVE 1*, William J. HUTZEL 1, J. Chris FOREMAN 2 1Department of Mechanical Engineering Technology, Purdue University, West Lafayette, Indiana, United States. [email protected], [email protected], [email protected] 2Department of Electrical and Computer Engineering Technology, Purdue University, West Lafayette, Indiana, United States. [email protected] * Corresponding Author ABSTRACT This paper outlines the design of an active solar thermal loop system that will be integrated with an air source heat pump hot water heater to provide highly efficient heating of a water/propylene glycol mixture.
    [Show full text]
  • Refined Comfort
    REFINED COMFort Dehumidification Systems FOR COMMERCIAL ROOFTOP UNITS AND SPLIT SYSTEMS Superior humidity and temperature control every day of the year With the Humiditrol® dehumidification system from Lennox, you can easily reduce humidity levels regardless of room temperature. The unique dehumidification-on-demand design removes moisture based on relative humidity levels—not the temperature—so it’s easy and efficient to create a better indoor environment. Why the Humiditrol® dehumidification system is more effective The Humiditrol dehumidification system is different from standard dehumidification HUMIDITROL® products that use cooling to remove moisture. That method can backfire by overcooling DEHUMIDIFICATION the space and leading to condensation and mold growth, even damaging building AT A GLANCE: materials. The Humiditrol system removes moisture with minimal effect on temperature, avoiding problems with overcooling. Integrated dehumidification system that controls humidity independent of room temperature Reduced humidity is better for business Available on rooftop units and small split systems High humidity levels can make Indoor air quality people feel sticky and may create productivity costs Efficiently improves indoor air a breeding ground for mold, quality (IAQ) and comfort mildew, dust mites and bacteria. Estimated number of employees 65 This environment not only affects Salary cost (per average employee) $30,000 Reduces spread of allergens such as customer comfort, but can also mold, mildew and dust mites Total staff (yearly) $1,950,000 compromise the integrity of Productivity losses due to poor computers and electronics, building thermal comfort, absenteeism, 3% Helps control mold-related repair comfort, etc. (average %) and maintenance costs materials and stocked items. Total lost productivity $58,500 Maintaining relative humidity Rooftop unit system removes up to Information from “Humidity Control, IAQ and You” Engineered Systems magazine, January 2001.
    [Show full text]
  • Review of Temperature and Humidity Control Technology for Heat Pump and Air Conditioning Systems
    Purdue University Purdue e-Pubs International Refrigeration and Air Conditioning School of Mechanical Engineering Conference 2016 Review of Temperature and Humidity Control Technology for Heat Pump and Air Conditioning Systems Xiaojie Lin University Of Maryland, United States of America, [email protected] Yunho Hwang University Of Maryland, United States of America, [email protected] Reinhard Radermacher University Of Maryland, United States of America, [email protected] Saikee Oh University Of Maryland, United States of America, [email protected] Follow this and additional works at: http://docs.lib.purdue.edu/iracc Lin, Xiaojie; Hwang, Yunho; Radermacher, Reinhard; and Oh, Saikee, "Review of Temperature and Humidity Control Technology for Heat Pump and Air Conditioning Systems" (2016). International Refrigeration and Air Conditioning Conference. Paper 1727. http://docs.lib.purdue.edu/iracc/1727 This document has been made available through Purdue e-Pubs, a service of the Purdue University Libraries. Please contact [email protected] for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html 2386, Page 1 Review of Temperature and Humidity Control Technology for Heat Pump and Air Conditioning Systems Xiaojie LIN1, Yunho HWANG1*, Reinhard RADERMACHER1, Saikee OH2 1Center for Environmental Energy Engineering, University of Maryland, 4164 Glenn L. Martin Hall Bldg., College Park, MD 20742, USA 2System Air Conditioning Laboratory, LG Electronics, 327-23, Gasan-Dong, Geumcheon-gu, Seoul, 153-802, Republic of Korea *: Corresponding Author, Tel: (301) 405-5247, E-mail: [email protected] ABSTRACT Indoor temperature and humidity are the two most significant factors to occupants’ thermal comfort.
    [Show full text]
  • Comfort, Indoor Air Quality, and Energy Consumption in Low Energy Homes
    Comfort, Indoor Air Quality, and Energy Consumption in Low Energy Homes P. Engelmann, K. Roth, and V. Tiefenbeck Fraunhofer Center for Sustainable Energy Systems January 2013 NOTICE This report was prepared as an account of work sponsored by an agency of the United States government. Neither the United States government nor any agency thereof, nor any of their employees, subcontractors, or affiliated partners makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights.Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States government or any agency thereof.The views and opinions of authors expressed herein do not necessarily state or reflect those of the United States government or any agency thereof. Available electronically at http://www.osti.gov/bridge Available for a processing fee to U.S. Department of Energy and its contractors, in paper, from: U.S. Department of Energy Office of Scientific and Technical Information P.O. Box 62 Oak Ridge, TN 37831-0062 phone: 865.576.8401 fax: 865.576.5728 email:mailto:[email protected] Available for sale to the public, in paper, from: U.S. Department of Commerce National Technical Information Service 5285 Port Royal Road Springfield, VA 22161 phone: 800.553.6847 fax: 703.605.6900 email: [email protected] online ordering: http://www.ntis.gov/ordering.htm Printed on paper containing at least 50% wastepaper, including 20% postconsumer waste Comfort, Indoor Air Quality, and Energy Consumption in Low Energy Homes Prepared for: The National Renewable Energy Laboratory On behalf of the U.S.
    [Show full text]
  • Switch to an Energy Efficient Heat Pump Hvac System
    SWITCH TO AN ENERGY Benefits Types of Heat Pump Systems EFFICIENT HEAT PUMP Two-For-One: heat pumps are capable of both More comfortable: in contrast to the hot and Ducted heat pumps are ideal for homes with HVAC SYSTEM heating in the winter and cooling in the summer. dry air of a furnace, heat pumps circulate air that’s ductwork currently in place. A ducted heat pump has an You only have to buy, install, maintain, and repair naturally humid. outdoor unit that replaces your air conditioner’s outdoor one system. unit. HIGH PERFORMANCE WITH LOW EMISSIONS More energy-efficient and Climate AND ELIGIBLE FOR REBATES Better indoor air quality: switching from Smart: heat pumps can reduce your electricity Ductless mini-split heat pumps are best a gas furnace to a heat pump HVAC can remove use for heating by 50% compared to furnaces and suited to homes that have electric heating in each harmful air contaminants, such as carbon monoxide and baseboard heaters. Using energy-efficient appliances room or may provide a lower cost alternative to a nitrogen oxide, from homes. reduces electric bills and greenhouse gas emissions. ducted system. Mini-split systems don’t require duct work and they have an air delivery unit in each room that keeps temperatures at a comfortable level. How it Works BayREN Home+ Program Energy Efficiency and Electrification Rebates Frequently Asked Questions BayREN implements energy savings programs in collaboration with the nine bay area counties. Get up to $1,000 from BayREN Home+ to upgrade a central What’s the difference between an air natural gas furnace and air conditioner system to a conditioner and heat pump? Heat pumps high-efficiency heat pump HVAC system.
    [Show full text]
  • Analysis of System Improvements in Solar Thermal and Air Source Heat
    Analysis of system improvements in solar thermal and air source heat pump combisystems Stefano Poppi, Chris Bales, Andreas Heinz, Franz Hengel, David Chèze, Igor Mojic, Catia Cialani To cite this version: Stefano Poppi, Chris Bales, Andreas Heinz, Franz Hengel, David Chèze, et al.. Analysis of system improvements in solar thermal and air source heat pump combisystems. Applied Energy, Elsevier, 2016, 173 (1), pp.606-623. 10.1016/j.apenergy.2016.04.048. cea-01310230 HAL Id: cea-01310230 https://hal-cea.archives-ouvertes.fr/cea-01310230 Submitted on 2 May 2016 HAL is a multi-disciplinary open access L’archive ouverte pluridisciplinaire HAL, est archive for the deposit and dissemination of sci- destinée au dépôt et à la diffusion de documents entific research documents, whether they are pub- scientifiques de niveau recherche, publiés ou non, lished or not. The documents may come from émanant des établissements d’enseignement et de teaching and research institutions in France or recherche français ou étrangers, des laboratoires abroad, or from public or private research centers. publics ou privés. Analysis of system improvements in solar thermal and air source heat pump combisystems. Stefano Poppi*1,2, Chris Bales1, Andreas Heinz4, Franz Hengel4, David Chèze6, Igor Mojic5, Catia Cialani3 1Solar Energy Research Center (SERC), Dalarna University College, S-79188 Falun, Sweden 2Department of Energy Technology, KTH, SE-100 44 Stockholm, Sweden 3Department of Economics, Dalarna University College, S-79188 Falun, Sweden 4Institute of Thermal Engineering, Graz University of Technology, Inffeldgasse 25b, A-8010 Graz, Austria 5Institut für Solartechnik SPF, University of Applied Sciences HSR, Oberseestr. 10, 8640 Rapperswil, Switzerland 6CEA, LITEN, Department of Solar Technologies, F-73375 Le Bourget du Lac, France *Corresponding author.
    [Show full text]
  • The Energize Denver Renewable Heating and Cooling Plan Resilient Existing Buildings and Homes
    The Energize Denver Renewable Heating and Cooling Plan Resilient Existing Buildings and Homes CONTRIBUTORS The following City and County of Denver Office of Climate Action, Sustainability, and Resiliency (CASR) staff co-developed and contributed to this plan development: • Jan Keleher, Building Electrification Lead • Katrina Managan, Buildings Team Lead • Elizabeth Babcock, Climate Team Manager • Grace Rink, Chief Climate Officer • Jarrett Vigil, Graduate Level Intern Lotus Engineering and Sustainability, LLC (Lotus) co-led the development of the plan with four project partners: NORESCO, Energy and Environmental Economics (E3), AECOM, and Energy Outreach Colorado (EOC). The report was designed by Adrian Newman, Creative Professional. Tyler Poulson and Laura Tajima with the Building Electrification Institute served as Denver’s strategic advisors. CONTACT INFORMATION City and County of Denver Lotus Engineering and Sustainability, LLC Jan Keleher Emily Artale, Founder, Principal Engineer Building Electrification Lead and Co-Owner Office of Climate Action, Sustainability, 1627 Vine Street, Denver, Colorado 80206 Resiliency P: 303.709.9948 P: 720.865.5388 E: [email protected] E: [email protected] ACKNOWLEDGMENTS The completion of this work would not have been possible without the support and input of the following individuals, to whom the City and County of Denver is grateful. Over 100 individuals helped guide the process through their participation in the Building Electrification Advisory Groups and Workforce Roundtables.
    [Show full text]