Partial List of Plumbing Hazards Illustrations of Backsiphonage

Total Page:16

File Type:pdf, Size:1020Kb

Partial List of Plumbing Hazards Illustrations of Backsiphonage Appendix A Appendix B Partial List of Illustrations of Plumbing Hazards Backsiphonage Fixtures with Direct Sewer, sanitary The following illustrates typical undersized water service line Connections Sewer, storm plumbing installations where reduces the pressure at the Swimming pool backsiphonage is possible. water closets to atmospheric producing a reversal of the flow. Description C. Suggested Correction: The Backsiphonage water connection at the bedpan Air conditioning, air washer Fixtures with wash sink and the sterilizer Air conditioning, chilled water Submerged Inlets Case I (Fig. 44) should be provided with Air conditioning, condenser A. Contact Point: A rubber properly installed backflow water hose is submerged in a bedpan preventers. Description Air line wash sink. Aspirator, laboratory Baptismal fount B. Causes of Reversed Flow: Aspirator, medical Bathtub (I) A sterilizer connected to the Backsiphonage water supply is allowed to cool Aspirator, weedicide and Bedpan washer, flushing rim Case 2 (Fig. 45) without opening the air vent. fertilizer sprayer Bidet As it cools, the pressure within A. Contact Point: A rubber Autoclave and sterilizer Brine tank the sealed sterilizer drops below hose is submerged in a labora- Auxiliary system, industrial Cooling tower atmospheric producing a tory sink. Auxiliary system, surface water Cuspidor vacuum which draws the B. Cause of Reversed Flow: Auxiliary system, unapproved Drinking fountain polluted water into the sterilizer Two opposite multi-story contaminating its contents. (2) buildings are connected to the well supply Floor drain, flushing rim Boiler system The flushing of several flush same water main, which often Garbage can washer valve toilets on a lower floor lacks adequate pressure. The Chemical feeder, pot-type Ice maker which are connected to an building on the right has Chlorinator Laboratory sink, serrated nozzle installed a booster pump. Coffee urn Laundry machine FIGURE 44. Backsiphonage (Case 1). Cooling system Lavatory FIGURE 45. Backsiphonage (Case 2). Dishwasher Lawn sprinkler system Fire standpipe or sprinkler Photo laboratory sink system B Sewer flushing manhole Fountain, ornamental A Slop sink, flushing rim Hydraulic equipment Slop sink, threaded supply Laboratory equipment A Steam table Lubrication, pump bearings Urinal, siphon jet blowout Photostat equipment Vegetable peeler Plumber’s friend, pneumatic Water closet, flush tank, Pump, pneumatic ejector ball cock Pump, prime line Water closet, flush valve, Pump, water operated ejector siphon jet BB B 38 • CROSS-CONNECTION CONTROL MANUAL When the pressure is inad- Backsiphonage Backsiphonage B. Cause of Reversed Flow: equate in the main, the build- Gasoline may enter the ing booster pump starts Case 4 (Fig. 47) Case 5 (Fig. 48) distribution system by gravity pumping, producing a negative A. Contact Point: The water A. Contact Point: The gasoline or by siphonage in the event of pressure in the main and supply to the dishwasher is not storage tank is maintained full a leak or break in the water causing a reversal of flow in the protected by a vacuum breaker. and under pressure by means of main. opposite building. Also, the dishwasher has a solid a direct connection to the city C. Suggested Correction: A C. Suggested Correction: The waste connection to the sewer. water distribution system. reduced pressure principle laboratory sink water outlet B. Cause of Reversed Flow: backflow preventer should be should be provided with a The undersized main serving installed in the line to the vacuum breaker. The water the building is subject to FIGURE 48. gasoline storage tank or a surge service line to the booster pump reduced pressures, and therefore Backsiphonage (Case 5). tank and pump should be should be equipped with a only the first two floors of the provided in that line. device to cut off the pump building are supplied directly when pressure approaches a with city pressure. The upper negative head or vacuum. floors are served from a booster Backsiphonage pump drawing suction directly Case 6 (Fig. 49) from the water service line. Backsiphonage During periods of low city A. Contact Point: There is a pressure, the booster pump submerged inlet in the second Case 3 (Fig. 46) suction creates negative Gasoline floor bathtub. A A. Contact Point: A chemical pressures in the low system, B. Cause of Reversed Flow: tank has a submerged inlet. thereby reversing the flow. Water An automobile breaks a nearby B. Cause of Reversed Flow: C. Suggested Correction: The fire hydrant causing a rush of The plant fire pump draws dishwasher hot and cold water Main water and a negative pressure in suction directly from the city should be supplied through an B the service line to the house, water supply line which is air gap and the waste from the sucking dirty water out of the insufficient to serve normal dishwasher should discharge bathtub. plant requirements and a major through an indirect waste. The C. Suggested Correction: The fire at the same time. During a booster pump should be hot and cold water inlets to the fire emergency, reversed flow equipped with a low-pressure FIGURE 49. bathtub should be above the may occur within the plant. cutoff device. Backsiphonage (Case 6). rim of the tub. C. Suggested Correction: The water service to the chemical FIGURE 47. tank should be provided Backsiphonage (Case 4). through an air gap. A FIGURE 46. Backsiphonage (Case 3). CHEMICALS INC. B A Dishwasher A Sewer High service Low service B B Main APPENDIX B • 39 Appendix C C. Suggested Correction: Illustrations of Each pier water outlet should be protected against backflow. The main water service to the Backpressure pier should also be protected against backflow by an air gap The following presents FIGURE 51. or reduced pressure principle illustrations of typical plumbing Backflow (Case 2). backflow preventer. installations where backflow resulting from backpressure is possible. Backflow B Case 4 (Fig. 53) Backflow A A. Contact Point: A single- valved connection exists Case I (Fig. 50) between the public, potable A. Contact Point: A direct Backflow water supply and the fire- connection from the city supply Case 2 (Fig. 51) sprinkler system of a mill. to the boiler exists as a safety B. Cause of Reversed Flow: measure and for filling the A. Contact Point: Sewage The sprinkler system is nor- system. The boiler water system seeping from a residential mally supplied from a nearby is chemically treated for scale cesspool pollutes the private Backflow lake through a high-pressure prevention and corrosion well which is used for lawn Case 3 (Fig. 52) pump. About the lake are large control. sprinkling. The domestic water numbers of overflowing septic B. Cause of Reversed Flow: system, which is served from a A. Contact Point: A valve tanks. When the valve is left The boiler water recirculation city main, is connected to the connection exists between the open, contaminated lake water pump discharge pressure or well supply by means of a valve. potable and the non potable can be pumped to the public backpressure from the boiler The purpose of the connection systems aboard the ship. supply. may be to prime the well exceeds the city water pressure B. Cause of Reversed Flow: supply for emergency domestic C. Suggested Correction: The and the chemically treated While the ship is connected to use. potable water supply to the fire water is pumped into the the city water supply system system should be through an air domestic system through an B. Cause of Reversed Flow: for the purpose of taking on gap or a reduced pressure open or leaky valve. During periods of low city water for the potable system, principle backflow preventer C. Suggested Correction: As water pressure, possibly when the valve between the potable should be used. minimum protection two check lawn sprinkling is at its peak, and nonpotable systems is valves in series should be the well pump discharge opened, permitting contami- FIGURE 53. provided in the makeup pressure exceeds that of the city nated water to be pumped into Backflow (Case 4). waterline to the boiler system. main and well water is pumped the municipal supply. An air gap separation or into the city supply through an ACME MILLS reduced pressure principle open or leaky valve. FIGURE 52. backflow preventer is better. C. Suggested Correction: The Backflow (Case 3). connection between the well Sprinkler FIGURE 50. water and city water should be System Backflow (Case 1). broken City main A A B Pump B To potable A system B Chemical feeder 40 • CROSS-CONNECTION CONTROL MANUAL Appendix D Appendix E Illustrations of Illustrations of Air Gaps Vacuum Breakers The following illustrations describe methods of providing an FIGURE 57. air gap discharge to a waste line which may be occasionally or Vacuum breakers. continuously subject to backpressure. Vaccum closes gate FIGURE 54. Brass inset Air gap to sewer subject to backpressure—force main. Air enters here Air preventing rise of D Rubber sleeve contaminated liquids Ball check in fixtures 2xD Air vent Waste line Flush connection Pump Cowl nut FIGURE 55. Air gap to sewer subject to backpressure—gravity drain. D FIGURE 58. Vacuum breaker arrangement for 2xD an outside hose hydrant. Indirect waste “A” “A” Ball check Plan Support vanes Horizontal waste 1" sleeve, sch. 40. FIGURE 56. ½" or ¾" Fire system makeup tank for a Hand wheel gate valve dual water system. Exterior " " ½ or ¾ building wall I.P.S. hose adapter sch. 40. galv. ½" or ¾" vacuum breaker " " Coupling M.I. galv. Nonpotable supply Float valves
Recommended publications
  • FACT SHEET: BACKFLOW DEVICES 2015 MINNESOTA PLUMBING CODE Minnesota Department of Labor and Industry
    FACT SHEET: BACKFLOW DEVICES 2015 MINNESOTA PLUMBING CODE Minnesota Department of Labor and Industry REQUIREMENTS Refer to the 2015 Minnesota Plumbing Code Parts 603.5.23 through 603.5.23.4 for details about the backflow prevention requirements discussed in this fact sheet. Devices that need to be tested Testing and maintenance The 2015 Minnesota Plumbing Code requires that all • The backflow device must be tested upon initial testable backflow devices be tested upon installation and at installation and at least annually thereafter. least annually thereafter by a certified backflow assembly • Test results must be submitted to the administrative tester. Testable devices include: authority and to the community public water supplier • Reduced pressure principal backflow prevention within 30 days of testing. assemblies, • Reduced pressure detector fire protection backflow Applicability prevention assemblies, • Reduced pressure (RPZ) devices have had testing • Double check backflow prevention assemblies, requirements for many years. New and existing RPZ • Pressure vacuum breaker backflow prevention installations must be tested annually. assemblies, • The testing requirements for testable non-RPZ devices • Double check detector fire protection backflow became effective for installations made on or after prevention assemblies, and Jan. 23, 2016. • Spill resistant pressure vacuum breakers. Tester qualifications Installing the device Testing of backflow prevention devices requires certification • A licensed plumber must perform the installation of a to ASSE Standard 5110. Testing of reduced pressure principal backflow prevention device. devices (RPZs) requires an additional certification by the • The public water supplier must be notified within 30 commissioner of the Minnesota Department of Labor and days following installation of the device on a community Industry.
    [Show full text]
  • January 29, 2020 Backflow Protection on an Emergency Eye Wash, Body
    January 29, 2020 Backflow Protection on an Emergency Eye Wash, Body Drench Station, Animal Wash Basins, Mani/Pedicure Bowls near sink Code: 2018 Plumbing Code Section(s): P202, P405.1, P608.5, P608.13, P608.13.2, P608.13.5, P608.13.6, P608.13.7, P608.15.4.1 Question: Do I need to install a AVB, PVB, or an RP on an emergency shower, pull-out style drench hose, Animal wash basin, mani/pedicure bowls and/or eyewash stations at a sink/lavatory/service sink? Answer: Well, it depends. Does the station have continuous water pressure? Will the sink potentially receive waste consisting of chemicals, biohazards, and/or other high hazard applications? Does the station have an integral sprayer? Is there a fixed air gap between the outlet and any nearby sink, pits, and any other areas that would allow the outlet to be submerged? All of these variable and more, come into play when trying to determine what type of backflow protection is required on these types of stations at or near a sink. The type of faucet you use and how it is installed determines the type of backflow preventer that is required. These backflow requirements shall be determined during the CCC plan review process of the Building permit application using the MEP drawings. Compliance will be confirmed during the CO approval process by the CCC Inspector. The following shall be taken into consideration with choosing a system; P202 – Definitions Air Gap (Drainage System). The unobstructed vertical distance through the free atmosphere between the outlet of the waste pipe and the flood level rim of the receptacle into which the waste pipe is discharging.
    [Show full text]
  • Backflow Prevention Devices
    Examples of Backflow Prevention during Mixing of Agricultural Chemicals 1. What Is Backflow? Backflow occurs when water flows opposite to its normal direction and can lead to contamination of the original water supply. Backflow can occur when collecting water from a source (well, watercourse, etc.) to combine with agricultural chemicals in a sprayer tank. This can cause chemical contamination of the source water. 2. Preventing Backflow The following table describes examples of backflow prevention techniques: Option Description Advantage Disadvantage Costs/Availability Use Use an alternate tank to supply water to Complete Requires an additional step, Variable cost; the alternate separate the sprayer as opposed to filling directly backflow filling the alternate tank tank should be clean water tank from the well, watercourse, etc. Water is prevention before filling the sprayer tank pumped from the source into the water tank and moved to the mixing/ loading area, located an adequate distance from wells and surface water Anti- Install a permanent anti-backflow device Quick solution, Installation may be Price ranges from $100.00 to backflow on the water supply line to prevent the requires no complicated, some types are $800.00; can be purchased device potential for backflow of chemicals from monitoring or susceptible to damage from from plumbing supply stores the sprayer tank. Devices include: double additional debris or freezing or most hardware stores. check valve or hose vacuum break valve steps after installation Maintain an A permanently fixed air gap between the Requires no Requires some monitoring No cost air gap water supply line and the sprayer tank additional can be maintained.
    [Show full text]
  • Methods and Devices for the Prevention of Backflow and Back
    Chapter Four Air Gap (2) The air gap may be easily Methods and Devices defeated in the event that the Air gaps are non-mechanical “2D” requirement was purposely backflow preventers that are or inadvertently compromised. for the Prevention of very effective devices to be used Excessive splash may be encoun- where either backsiphonage or tered in the event that higher Backflow and backpressure conditions may than anticipated pressures or exist. Their use is as old as flows occur. The splash may be a Back-Siphonage piping and plumbing itself, but cosmetic or true potential only relatively recently have hazard—the simple solution standards been issued that being to reduce the “2D” wide choice of devices standardize their design. In dimension by thrusting the Aexists that can be used to general, the air gap must be supply pipe into the receiving prevent backsiphonage and twice the supply pipe diameter funnel. By so doing, the air gap backpressure from adding but never less than one inch. is defeated. contaminated fluids or gases See Figure 12. into a potable water supply (3) At an air gap, we expose the system. Generally, the selection water to the surrounding air FIGURE 12. with its inherent bacteria, dust of the proper device to use is Air gap. based upon the degree of hazard particles, and other airborne posed by the cross-connection. pollutants or contaminants. In addition, the aspiration effect of Additional considerations are Diameter based upon piping size, location, “D” the flowing water can drag down and the potential need to surrounding pollutants into the periodically test the devices to “2D” reservoir or holding tank.
    [Show full text]
  • Atmospheric Vacuum Breaker Back-Siphon Prevention Assembly; NO VALVES Are Allowed Downstream of an A.V.B
    ATMOSPHERIC and PRESSURE VACUUM BREAKER INSTALLATION STANDARDS: Atmospheric Vacuum Breaker Back-siphon Prevention Assembly; NO VALVES are allowed downstream of an A.V.B. Minimum elevation requirement of six inches (6”) above highest point in system must be met. Shall not be subjected to operating pressure for more than twelve (12) hours in any twenty-four (24) hour period. Assembly is designed to protect against a back-siphon condition only. Pressure Vacuum Breaker Back-siphon Prevention Assembly; Valves are allowed downstream of a P.V.B. Minimum elevation requirement of twelve inches (12”) above highest point in system must be met. Assembly is designed to protect against a back-siphon condition only. A. A. V. B. s / P. V. B. s, shall only be used on systems that are not subject to back- pressure. If back-pressure is present or possible a D. C. V. A. or R. P. B. A. is required. Annual backflow assembly testing of an A. V. B .is not required, although inspections have indicated a high rate of improperly installed A. V. B. s due to valves or electronic stations present downstream of assembly, or failure to meet the six- inch (6”) minimum elevation requirement. The City of Post Falls Water Division inspects all A. V. B. installations annually, there are no fees associated with this inspection. B. A. V. B. s / P. V. B. s shall never be exposed to compressed air and must be removed if compressed air is used to winterize the irrigation system. Note: Manufacturer freeze protection guidelines recommend assemblies be removed and stored indoors in areas where freezing temperatures may occur.
    [Show full text]
  • Evaluation of Backflow Prevention Devices: a State-Of-The-Art Report
    NBSIR 76-1070 Evaluation of Backflow Prevention Devices: A State-of-the-Art Report Grover C. Sherlin Robert W. Beausoliel Center for Building Technology Institute for Applied Technology National Bureau of Standards Washington, D. C. 20234 June 1976 Final Report Prepared for Water Supply Division Environmental Protection Agency Washington, D. C. 20460 NBSIR 76-1070 EVALUATION OF BACKFLOW PREVENTION DEVICES: A STATE-OF-THE-ART REPORT Grover C. Sherlin Robert W. Beausoliel Center for Building Technology Institute for Applied Technology National Bureau of Standards Washington, D. C. 20234 June 1976 Final Report Prepared for Water Supply Division Environmental Protection Agency Washington, D. C. 20460 U.S. DEPARTMENT OF COMMERCE, Elliot L. Richardson, Secretary Edward O. Vetter, Under Secretary Dr. Betsy Ancker-Johnson. Assistant Secretary for Science and Technology NATIONAL BUREAU OF STANDARDS, Ernest Ambler, Acting Director CONTENTS Abstract 1 1. Introduction 2 1.1 Purpose and Scope 2 1.2 Fundamentals of Backflow 3 2. Background Information 7 2.1 Historical Background and Recorded Incidents of Backflow through Backflow Connection and Cross-Connections 7 2.2 Navy Study of FCCCR Certification Procedures 9 2.3 A.S.S.E. Concern for Backflow Problems 10 2.4 Backflow Prevention Devices and Piping Arrangements 12 3. Elements in the Evaluation of Backflow Prevention Devices... 18 3.1 The Product Standards 18 3.2 The Plumbing Codes 19 3.3 The Manufacturers of Backflow Prevention Devices 23 3.4 Testing Laboratories 23 3.5 A Conceptual Model Cross-Connection Control Program 36 / 4. Evaluation of Devices 39 4.1 Design Considerations that Affect Reliability 39 4.2 Methods that Test Appropriate Attributes 45 5.
    [Show full text]
  • Hose Bibb Vacuum Backflow Preventer with Double Check Valve Breaker Atmospheric Vent (Continuous Pressure)
    CROSS CONNECTION: A cross connection is any actual or potential physical connection between a potable water supply line and any pipe, vessel, or machine containing a non potable fluid or has the possibility of containing a non potable fluid, solid or gas, such that it is possible for the non potable fluid, solid or gas to enter the water system by backflow. A cross connection could be any physical arrangement whereby a potable water supply is connected, directly or indirectly, with any non potable or unapproved water supply system, sewer, drain, conduit, pool, storage reservoir, plumbing fixture, or any other device which contains, or may contain, contaminated water, liquid, gases, sewage, or other waste of unknown or unsafe quality which may be capable of imparting contamination to the potable water supply as a result of backflow. ** BACKFLOW: Backflow is a flow in reverse from the normal direction of flow in a piping system. It occurs due to a differential pressure existing between two different points within a continuous fluid system; fluids of higher pressure flowing to a fluid of lower pressure. Backflow may occur due to either backsiphonage or backpressure. ** BACKSIPHONAGE: Backsiphonage is caused by negative pressure in the supply piping. Some common causes of backsiphonage are: (1) high velocity pipe lines; (2) line repair or break that is lower than a service point; (3) lowered main pressure due to high water withdrawal rate such as fire fighting or water main flushing; or (4) reduced supply pressure on the suction side of the booster pump. CONTINUOUS PRESSURE: An installation in which the pressure is being supplied continuously to a backflow prevention device for periods over 12 hours at a time.
    [Show full text]
  • Protect Your Drinking Water
    Action You Can Take Prior to Inspection: Protect Your *Read and understand this brochure. *Review each of the diagrams and Drinking Water review your bathroom and kitchen set- up to ensure you are protected. *Call a plumber with questions on backflow prevention for boiler or plumbing fixtures and appliances. *Inspect hose connections on your house for proper backflow prevention (ex. outside hose facet and utility sinks). Remember, only you can prevent cross connections from occurring where you live. Follow these tips and you will be eliminating the chances of contaminating your family’s drinking water. Provided by the Fall River Utility Cross Connection Consultant: Tips: Keep the ends of hoses clear of all possible contaminants. Ø Don’t submerge hoses in buckets, pools, tubs, sinks, or ponds. Make sure dishwashers are installed General Engineering Cross Connection and with air gap device. Company Ø Don’t use spray attachments without 916 Silver Lake Drive Phone: 608-742-2169 Backflow Prevention Guide a backflow prevention device. P.O. Box 340 Fax: 608-742-2592 for Residential Users Verify and install a simple hose bibb Portage, WI 53901 Website: vacuum breaker on all threaded faucets www.generalengineering.net around your home. Have a minimum of an 1" air gap on all water treatment devices. What is a Cross Connection? A “Cross Connection” means a connection or potential connection between ay part of the municipal water supply IN THE KITCHEN Hoses and water treatment devices may create a system and another environment containing substances in a manner that, under any circumstances, would allow potential backflow hazard if not properly isolated the substances to enter the water supply system by means of back-siphonage or back pressure.
    [Show full text]
  • Backflow Prevention Products Condensed Catalog
    Water Safety Water Safety, Flow Control and Backflow Prevention Products Condensed Catalog watts.com Index Model/Series - - - - - - - - - Page Model/Series - - - - - - - - - Page Model/Series - - - - - - - - -Page Model/Series - - - - - - - - - Page Numerical 1L/1XL - - - - - - - - - - - - - - - - - - - - 25 800MQT - - - - - - - - - - - - - - - - - - - 61 Elbows - - - - - - - - - - - - - - - - - - - - 59 PVS-1000 - - - - - - - - - - - - - - - - - - 39 2-M2 - - - - - - - - - - - - - - - - - - - - - 115 909 - - - - - - - - - - - - - - - - - - - - 52-53 EMVII-6400SS- - - - - - - - - - - - - - - - 70 PX, P1-P16 - - - - - - - - - - - - - - - - 120 3L- - - - - - - - - - - - - - - - - - - - - - - - 28 909RPDA- - - - - - - - - - - - - - - - - - - 58 ENS-20 - - - - - - - - - - - - - - - - - - - - 30 QF - - - - - - - - - - - - - - - - - - - - - - 103 05- - - - - - - - - - - - - - - - - - - - - - - 113 911- - - - - - - - - - - - - - - - - - - - - - - 95 ETA- - - - - - - - - - - - - - - - - - - - - - - 96 R-24, R-26, R-30 - - - - - - - - - - - - - 30 6 - - - - - - - - - - - - - - - - - - - - - - - - 79 912HP- - - - - - - - - - - - - - - - - - - - - 60 ET-RA - - - - - - - - - - - - - - - - - - - - - 96 RA - - - - - - - - - - - - - - - - - - - - - - 105 007- - - - - - - - - - - - - - - - - - - - - - - 43 919- - - - - - - - - - - - - - - - - - - - - - - 55 ETX, ETSX - - - - - - - - - - - - - - - - - - 97 * RBFF- - - - - - - - - - - - - - - - - - - - - - 99 007DCDA - - - - - - - - - - - - - - - - - - 48 957/957N/957Z - - - - - - - - - - - - - - 49 F127W
    [Show full text]
  • Backflow Prevention FAQ
    Backflow Prevention FAQ What is a cross-connection? A cross connection is any physical or potential connection between a potable water supply and any potential hazardous material. This connection can be created when plumbing is incorrectly installed or even by simply attaching a hose to a faucet. Cross connections are not easy to discover, but can pose a serious threat to water quality. Federal and State regulations provide that no such connection is permissible without the installation of an approved backflow prevention assembly in accordance to the degree of hazard of the substance involved. What is potable water? Potable water is water which is safe for human consumption, free from harmful microbiological or chemical substances as described by federal and State drinking water regulations. What is backflow? Backflow is an undesirable reversal of flow of non-potable water or other substances through a cross-connection and into the piping of a public water system or consumer's potable water system. There are two types of backflow—back pressure and backsiphonage. What is back pressure backflow? Back pressure backflow is backflow caused by a downstream pressure that is greater than the upstream or supply pressure in a public water system or consumer's potable water system. Back pressure can result from an increase in downstream pressure, a reduction in the potable water supply pressure, or a combination of both. Increases in downstream pressure can be created by pumps, temperature increases in boilers, etc. Reductions in potable water supply pressure occur whenever the amount of water being used exceeds that amount of water being supplied, such as during hydrant flushing, fire fighting, or water main breaks.
    [Show full text]
  • 2015 International Plumbing Code (Amended) Backflow/Cross-Connection Control Requirements
    2015 International Plumbing Code (amended) Backflow/Cross-Connection Control Requirements AMENDED SECTION NEW SECTION NOTE: Sections highlighted yellow are sections of the 2015 IPC that were amended. The wording in the yellow sections include the amended language (i.e., if you compare Section 312.10.1 below to that of the 2015 IPC, they will be different because the section below contains Louisiana amendments). Sections highlighted green are new sections added (i.e., there is no Section 312.10.3 in the 2015 IPC as there is in this document, it was added to the Louisiana code via Louisiana amendments). 312.10 Installation, inspection and testing of backflow prevention assemblies, barometric loops and air gaps. Installation, inspection and testing shall comply with Sections 312.10.1 through 312.10.3. 312.10.1 Inspections. Annual inspections shall be made of all backflow prevention assemblies, barometric loops and air gaps to determine whether they are operable, properly installed and maintained, and meet testing/code requirements. Inspections of backflow prevention devices including barometric loops and air gaps used to protect high degree of hazard cross connections shall be documented in writing and the report provided to the owner of the backflow prevention device. 312.10.2 Testing. Reduced pressure principle, double check, pressure vacuum breaker, reduced pressure detector fire protection, double check detector fire protection, and spill-resistant vacuum breaker backflow preventer assemblies shall be tested at the time of installation, immediately after repairs or relocation and at least annually. The testing procedure shall be performed in accordance with one of the following standards: ASSE 5013, ASSE 5015, ASSE 5020, ASSE 5047, ASSE 5048, ASSE 5052, ASSE 5056, CSA B64.10.1, USC’s FCCC & HR’s “Manual of Cross-Connection Control”, or UFL’s TREEO’s “Backflow Prevention – Theory and Practice”.
    [Show full text]
  • Cross Connection and Backflow Prevention Control Program
    CROSS CONNECTION AND BACKFLOW PREVENTION CONTROL PROGRAM REVISED March 2021 ORDINANCE NO: 2009-O-012 ORDINANCE NO: 2016-O-XXX TOWN OF LEESBURG CROSS CONNECTION AND BACKFLOW PREVENTION CONTROL PROGRAM I. Purpose and applicability 1. Purpose. The purpose of this program, adopted by ordinance, is to abate or control actual or potential cross connections and protect the public health. The ordinance provides for establishment and enforcement of a cross connection control and backflow prevention program in accordance with the Commonwealth of Virginia, State Board of Health, Waterworks Regulations 1995, or as amended. THIS PROGRAM IS DIRECTED AT SERVICE LINE PROTECTION (CONTAINMENT). 2. Applicability. The provisions of this program will apply to all premises connected to Town’s water system. II. Definitions Air Gap — means the unobstructed vertical distance through the free atmosphere between the lowest point of the potable water outlet and the rim of the receiving vessel. ASSE – means the American Society of Sanitary Engineering. Atmospheric Vacuum Breaker (AVB) – means a backflow prevention device consisting of a float check, a check seat, and an air inlet port. The device is designed to allow atmospheric pressure to enter the air–inlet port thus breaking the vacuum and preventing backsiphonage. The device must be installed at least six inches above the highest outlet and may never be subjected to a back pressure condition or have a downstream shutoff valve, or be installed where it will be subject to continuous pressure for more than 12 hours. Auxiliary Water System — means any water system on or available to the premises other than the waterworks.
    [Show full text]