2015 International Plumbing Code (Amended) Backflow/Cross-Connection Control Requirements

Total Page:16

File Type:pdf, Size:1020Kb

2015 International Plumbing Code (Amended) Backflow/Cross-Connection Control Requirements 2015 International Plumbing Code (amended) Backflow/Cross-Connection Control Requirements AMENDED SECTION NEW SECTION NOTE: Sections highlighted yellow are sections of the 2015 IPC that were amended. The wording in the yellow sections include the amended language (i.e., if you compare Section 312.10.1 below to that of the 2015 IPC, they will be different because the section below contains Louisiana amendments). Sections highlighted green are new sections added (i.e., there is no Section 312.10.3 in the 2015 IPC as there is in this document, it was added to the Louisiana code via Louisiana amendments). 312.10 Installation, inspection and testing of backflow prevention assemblies, barometric loops and air gaps. Installation, inspection and testing shall comply with Sections 312.10.1 through 312.10.3. 312.10.1 Inspections. Annual inspections shall be made of all backflow prevention assemblies, barometric loops and air gaps to determine whether they are operable, properly installed and maintained, and meet testing/code requirements. Inspections of backflow prevention devices including barometric loops and air gaps used to protect high degree of hazard cross connections shall be documented in writing and the report provided to the owner of the backflow prevention device. 312.10.2 Testing. Reduced pressure principle, double check, pressure vacuum breaker, reduced pressure detector fire protection, double check detector fire protection, and spill-resistant vacuum breaker backflow preventer assemblies shall be tested at the time of installation, immediately after repairs or relocation and at least annually. The testing procedure shall be performed in accordance with one of the following standards: ASSE 5013, ASSE 5015, ASSE 5020, ASSE 5047, ASSE 5048, ASSE 5052, ASSE 5056, CSA B64.10.1, USC’s FCCC & HR’s “Manual of Cross-Connection Control”, or UFL’s TREEO’s “Backflow Prevention – Theory and Practice”. Any backflow preventer which is found to be defective shall be repaired. 312.10.3 Owner Responsibilities. The owner of the backflow prevention assemblies shall comply with the following. i. It shall be the duty of the owner of the backflow prevention assembly to see that these tests are made in a timely manner in accord with the frequency of field testing specified in 312.10.2 of this code. ii. The owner shall notify the building official, and/or water supplier (for those devices associated with containment) in advance when the tests are to be undertaken so that the building official and/or water supplier may witness the tests if so desired. iii. Upon completion, the owner shall provide records of such tests, repairs, overhauls, or replacements to the building official or water supplier (for those devices associated with containment). In addition, all records shall be kept by the owner of the backflow prevention device or method for at least 5 years and, upon specific request, shall be made available to the building official or water supplier. iv. All tests, repairs, overhauls or replacements shall be at the expense of the owner of the backflow preventer. 605.3 Water service pipe. Water service pipe shall conform to NSF 61 and shall conform to one of the standards listed in Table 605.3. Water service pipe or tubing, installed underground and outside of the structure, shall have a working pressure rating of not less than 160 psi (1100 kPa) at 73.4ºF (23ºC). Where the water pressure exceeds 160 psi (1100 kPa), piping material shall have a working pressure rating not less than the highest available pressure. Water service piping materials not third-party certified for water distribution shall terminate at or before the full open valve located at the entrance to the structure. All ductile iron water service piping shall be cement mortar lined in accordance with AWWA C104. 605.3.1 Dual check-valve-type backflow preventer. Dual check-valve backflow preventers installed on the water supply system shall comply with ASSE 1024 or CSA B64.6. These devices, which are commonly installed immediately downstream of water meters by water suppliers, are not approved backflow prevention devices and are only allowed to be installed when no cross connections exist downstream of the device or when all downstream cross connections are properly protected by approved backflow prevention devices, assemblies, or methods in accordance with Section 608 of this code. 607.3 Thermal expansion control. Where a storage water heater is supplied with cold water that passes through a check valve, pressure reducing valve or backflow preventer, a thermal expansion tank shall be connected to the water heater cold water supply pipe at a point that is downstream of all check valves, pressure reducing valves and backflow preventers. Thermal expansion tanks shall be sized in accordance with the tank manufacturer’s instructions and shall be sized such that the pressure in the water distribution system shall not exceed that required by Section 604.8. SECTION 608 PROTECTION OF POTABLE WATER SUPPLY 608.1 General. A potable water supply system shall be designed, installed and maintained in such a manner so as to prevent contamination from non-potable liquids, solids or gases being introduced into the potable water supply through cross-connections or any other piping connections to the system. Backflow preventers shall conform to the applicable Standard referenced in Table 608.1. Backflow preventer applications shall conform to Table 608.1, except as specifically stated in Sections 608.2 through 608.16.27 and Sections 608.18 through 608.18.2. TABLE 608.1 APPLICATION OF BACKFLOW PREVENTERS DEGREE OF APPLICABLE DEVICE HAZARDa APPLICATIONb STANDARDS High or low Backsiphonage or Air gap ASME A112.1.2 hazard backpressure High or low Backsiphonage or Air gap fittings for use with plumbing ASME A112.1.3 hazard backpressure fixtures, appliances and appurtenances Antisiphon-type fill valves for gravity ASSE 1002, CSA High hazard Backsiphonage only water closet flush tanks B125.3 Backpressure or Backflow preventer for carbonated Low hazard backsiphonage ASSE 1022 beverage machines 1 3 Sizes /4″ – /8″ Backpressure or Backflow preventer with intermediate Low hazard backsiphonage ASSE 1012, CSA B64.3 atmospheric vents 1 3 Sizes /4″– /4″ High or low Barometric loop Backsiphonage only (See Section 608.13.4) hazard ASSE 1015, AWWA Double check backflow prevention Backpressure or Low hazard C510, CSA B64.5, CSA assembly and double check fire backsiphonage 3 B64.5.1 protection backflow prevention assembly Sizes /8″–16″ Backpressure or Double check detector fire protection backsiphonage Low hazard ASSE 1048 backflow prevention assemblies (Fire sprinkler systems) Sizes 2″–16″ Backpressure or Dual-check-valve-type backflow preventer Low hazard backsiphonage ASSE 1024, CSA B64.6 1 Sizes /4″–1″ Low head backpressure, rated working pressure, ASME A112.21.3, High or low Hose connection backflow preventer backpressure ASSE 1052, CSA hazard or backsiphonage Sizes B64.2.1.1 1 /2″–1″ Low head backpressure or ASME A112.21.3, High or low Hose connection vacuum breaker backsiphonage ASSE 1011, CSA B64.2, hazard 1 3 Sizes /2″, /4″, 1″ CSA B64.2.1 High or low Low head backpressure and Laboratory faucet backflow preventer ASSE 1035, CSA B64.7 hazard backsiphonage Pipe-applied atmospheric-type vacuum High or low Backsiphonage only ASSE 1001, CSA 1 breaker hazard Sizes /4″–4″ B64.1.1 High or low Backsiphonage only ASSE 1020, CSA Pressure vacuum breaker assembly 1 hazard Sizes /2″–2″ B64.1.2 Reduced pressure principle backflow Backpressure or ASSE 1013, AWWA prevention assembly and reduced pressure High or low backsiphonage C511, CSA B64.4, CSA principle fire protection backflow prevention hazard 3 Sizes /8″–16″ B64.4.1 assembly Backsiphonage or Reduced pressure detector fire protection High or low backpressure ASSE 1047 backflow prevention assemblies hazard (Fire sprinkler systems) High or low Backsiphonage only Spill-resistant vacuum breaker assembly 1 ASSE 1056 hazard Sizes /4″–2″ Low head backpressure or ASME A112.21.1, Vacuum breaker wall hydrants, High or low backsiphonage ASSE 1019, CSA frost-resistant, automatic draining type hazard 3 Sizes /4″, 1″ B64.2.2 For SI: 1 inch = 25.4 mm. a. Low hazard—See Pollution (Section 202). High hazard—See Contamination (Section 202). b. See Backpressure (Section 202). See Backpressure, low head (Section 202). See Backsiphonage (Section 202). 608.2 Plumbing fixtures. The supply lines and fittings for plumbing fixtures shall be installed so as to prevent backflow. Plumbing fixture fittings shall provide backflow protection in accordance with ASME A112.18.1/CSA B125.1. 608.3 Devices, appurtenances, appliances and apparatus. Devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softeners, tanks and other appliances and devices that handle or treat potable water shall be protected against contamination. 608.3.1 Special equipment, water supply protection. The water supply for hospital fixtures shall be protected against backflow with a reduced pressure principle backflow prevention assembly, an atmospheric or spill-resistant vacuum breaker assembly, or an air gap. Vacuum breakers for bedpan washer hoses shall not be located less than 5 feet (1524 mm) above the floor. Vacuum breakers for hose connections in health care or laboratory areas shall not be less than 6 feet (1829 mm) above the floor. 608.4 Water service piping/Containment to protect potable water supplies. Water service piping shall be protected in accordance with Sections 603.2 and 603.2.1. 608.5 Chemicals and other substances. Chemicals and other substances that produce either toxic conditions, taste, odor or discoloration in a potable water system shall not be introduced into, or utilized in, such systems.
Recommended publications
  • FACT SHEET: BACKFLOW DEVICES 2015 MINNESOTA PLUMBING CODE Minnesota Department of Labor and Industry
    FACT SHEET: BACKFLOW DEVICES 2015 MINNESOTA PLUMBING CODE Minnesota Department of Labor and Industry REQUIREMENTS Refer to the 2015 Minnesota Plumbing Code Parts 603.5.23 through 603.5.23.4 for details about the backflow prevention requirements discussed in this fact sheet. Devices that need to be tested Testing and maintenance The 2015 Minnesota Plumbing Code requires that all • The backflow device must be tested upon initial testable backflow devices be tested upon installation and at installation and at least annually thereafter. least annually thereafter by a certified backflow assembly • Test results must be submitted to the administrative tester. Testable devices include: authority and to the community public water supplier • Reduced pressure principal backflow prevention within 30 days of testing. assemblies, • Reduced pressure detector fire protection backflow Applicability prevention assemblies, • Reduced pressure (RPZ) devices have had testing • Double check backflow prevention assemblies, requirements for many years. New and existing RPZ • Pressure vacuum breaker backflow prevention installations must be tested annually. assemblies, • The testing requirements for testable non-RPZ devices • Double check detector fire protection backflow became effective for installations made on or after prevention assemblies, and Jan. 23, 2016. • Spill resistant pressure vacuum breakers. Tester qualifications Installing the device Testing of backflow prevention devices requires certification • A licensed plumber must perform the installation of a to ASSE Standard 5110. Testing of reduced pressure principal backflow prevention device. devices (RPZs) requires an additional certification by the • The public water supplier must be notified within 30 commissioner of the Minnesota Department of Labor and days following installation of the device on a community Industry.
    [Show full text]
  • January 29, 2020 Backflow Protection on an Emergency Eye Wash, Body
    January 29, 2020 Backflow Protection on an Emergency Eye Wash, Body Drench Station, Animal Wash Basins, Mani/Pedicure Bowls near sink Code: 2018 Plumbing Code Section(s): P202, P405.1, P608.5, P608.13, P608.13.2, P608.13.5, P608.13.6, P608.13.7, P608.15.4.1 Question: Do I need to install a AVB, PVB, or an RP on an emergency shower, pull-out style drench hose, Animal wash basin, mani/pedicure bowls and/or eyewash stations at a sink/lavatory/service sink? Answer: Well, it depends. Does the station have continuous water pressure? Will the sink potentially receive waste consisting of chemicals, biohazards, and/or other high hazard applications? Does the station have an integral sprayer? Is there a fixed air gap between the outlet and any nearby sink, pits, and any other areas that would allow the outlet to be submerged? All of these variable and more, come into play when trying to determine what type of backflow protection is required on these types of stations at or near a sink. The type of faucet you use and how it is installed determines the type of backflow preventer that is required. These backflow requirements shall be determined during the CCC plan review process of the Building permit application using the MEP drawings. Compliance will be confirmed during the CO approval process by the CCC Inspector. The following shall be taken into consideration with choosing a system; P202 – Definitions Air Gap (Drainage System). The unobstructed vertical distance through the free atmosphere between the outlet of the waste pipe and the flood level rim of the receptacle into which the waste pipe is discharging.
    [Show full text]
  • Cross-Connection Control Manual and Design Criteria for Cross-Connection Control Plans, Ordinances, and Policies
    CROSS-CONNECTION CONTROL MANUAL AND DESIGN CRITERIA FOR CROSS-CONNECTION CONTROL PLANS, ORDINANCES, AND POLICIES DIVISION OF WATER SUPPLY TENNESSEE DEPARTMENT OF ENVIRONMENT AND CONSERVATION 2008 1. TABLE OF CONTENTS Tennessee Department of Environment and Conservation Guidelines…………..…………….……................. p.1 Definition of Terms............................................................................................................................................p.3 CHAPTER I. Introduction to Backflow Prevention…………………………………………………………..…....…....…..p.6 1.1 Introduction 1.2 Objective 1.3 Causes of Backflow 1.3.1 Backsiphonage 1.3.2 Backpressure II. Responsibility and Authority for Cross-Connection Control…………………………………………….....p.9 2.1 Responsibility 2.1.1 The Water Purveyor 2.1.2 The Customer 2.1.3 Plumbing Inspection Agencies 2.1.4 Installers and Maintenance Personnel 2.1.5 Tennessee Department of Environment and Conservation 2.1.6 Legal Consideration 2.2 Authority 2.2.1 General Discussion 2.2.2 Local Authority 2.2.3 State Wide Authority 2.2.4 Federal Authority III. Developing and Implementing a Cross-Connection Control Program………………………………..….p.14 3.1 Introduction 3.2 Outline of Considerations in Preparing a Plan 3.3 Discussions of Local Cross-Connection Control Plan 3.4 Implementation of the Cross-Connection Control Plan 3.5 Establishing Priorities for Investigation IV. Recommended Practices……………………………………………………………………………………...p.19 4.1 Basic Consideration 4.2 Premises Isolation 4.3 Situations Requiring Maximum Protection 4.4 Establishments
    [Show full text]
  • Cross-Connection Questions, Answers & Illustrations
    50 Cross-Connection Questions, 5Answers & Illustrations0 Relating to Backflow Prevention Products and Protection of Safe Drinking Water Supply watts.com What is backsiphonage? 1 Backsiphonage is the reversal of normal flow in a system caused by a negative pressure (vacuum or partial vacuum) in the supply piping. What factors can cause backsiphonage? 2 Backsiphonage can be created when there is stoppage of the water supply due to nearby firefighting, repairs or breaks in city main, etc. The effect is similar to the sipping of a soda by inhaling through a straw, which induces a flow in the opposite direction. What is backpressure backflow? 3 Backpressure backflow is the reversal of normal flow in a system due to an increase in the downstream pressure above that of the supply pressure. Supply Feed Valve What factors can cause a 4 backpressure backflow condition? Backpressure backflow is created whenever the downstream pressure exceeds the supply pres- sure which is possible in installations such as heating systems, elevated tanks, and pressure-producing systems. An example Return would be a hot water space-heating boiler operating under 15-20 Boiler lbs. pressure coincidental with a reduction of the city water supply below such pressure (or higher in most commercial boilers). As wa- ter tends to flow in the direction of least resistance, a backpressure backflow condition would be created and the contaminated boiler water would flow into the potable water supply. What is a cross-connection? 5 A cross-connection is a direct arrangement of a piping line which allows the potable water supply to be connected to a line which contains a contaminant.
    [Show full text]
  • Low-Volume Irrigation Systems for Blueberry with Chemigation and Fertigation Suggestions
    Low-Volume Irrigation Systems for Blueberry with Chemigation and Fertigation Suggestions Erick Smith, Department of Horticulture, UGA Tifton campus Wesley Porter, Crop and Soil Sciences, UGA Tifton campus Jonathan Oliver, Department of Plant Pathology, UGA Tifton campus Drip, trickle, microemitters, and subsurface irrigation systems are considered low-volume irrigation. Low-volume irrigation systems are designed to improve irrigation efficiency, delivering water to the crop accurately with minimal water loss. Irrigation efficiency (Table 1) can be categorized into two main concepts: water loss and uniform application. If water loss is significant, or application uniformity is poor, efficiency will be low. Generally, the most significant loss of irrigation water is from overwatering, where the water percolates below the root zone, or from runoff. With good management, losses due to leaks, system drainage, and flushing of filters and lateral lines should not exceed 1%. Low- volume systems have the opportunity to achieve efficiency, and under careful management, will minimize losses from overirrigation. However, using low-volume systems requires increased irrigation frequency and soil moisture monitoring should be used to improve water-use efficiency. Uniformity is desired for each application of water, meaning that the irrigated area receives the same portion of water throughout. A well-designed irrigation system accounts for variability by applying water based on the soil structure (e.g. sandy, silt, loam, clay, and organic matter) and environmental conditions (e.g. wind, temperature, and cloud cover). That said, systems can have losses inherent to the design (Table 1). There may be variability in efficiencies that are noticeable even when comparing low-volume emitters (i.e.
    [Show full text]
  • 3- Ways to Protect from Backflow
    3- WAYS TO PROTECT FROM BACKFLOW Air gap Description: An approved air gap is a method of backflow prevention that means the physical separation between the end of the water supply pipe (example: faucet) and open vessel (example: sink). Installation and testing requirements: The separation must be twice the supply pipe inside diameter but never less than one inch. An air gap or physical disconnection gives the highest degree of protection and shall be used whenever practical in high hazard situations subject to backpressure. Since the application of air gaps is limited, other backflow protection systems can be used Reduced Pressure Zone Backflow Preventer Description: The Reduced Pressure backflow preventer consists of two independent check valves and a differential pressure relief valve, which automatically relieves excess pressure Typical use: The reduced pressure zone backflow preventer controls direct and indirect cross-connections it’s also used to isolate Installation and testing requirements: Due to certain combinations of potable water from non-potable water lines. Used check valve failure and/or system backpressure cause the relief valve to for high hazard risks, the reduced pressure zone discharge, the device must be mounted in a location where the drain will backflow preventer provides the highest level of not become flooded. Annual testing is required. protection. Double check Valve Assembly Description: The Double Check Valve (DC) assembly consists of two single independently acting check valves with water tight valves located at each end of the assembly. Typical use: The double check backflow preventer can only be used in low hazards situations. The use of this type of device is to Installation and testing requirements: The Double check valve (DC) must be protect against back-siphonage or backflow installed in an accessible location for annual testing, this device can be caused by backpressure.
    [Show full text]
  • Potential Plumbing Violations in Food Service Establishments Updated August 2008 Michigan Department of Agriculture, Food and Dairy Division
    Potential Plumbing Violations in Food Service Establishments Updated August 2008 Michigan Department of Agriculture, Food and Dairy Division Protecting the Water Supply Line PROBLEM VIOLATION FC CORRECTION(s) ASSE#’s VALVE AREA (Hazard Section most DOWNSTREAM level) common Toilet Tanks Submerged 5-203.14 Anti-siphon ball cock ASSE 1002 inlet (high) assembly—1” above overflow Hose Bib connection Possible back 5-203.14 Hose bib vacuum ASSE 1011 Not allowed- no back siphon from breaker or 1052 pressure of system hose (high) pressure Water inlet Garbage Submerged 5-203.14 AVB 6” above flood rim ASSE 1001 NO valves-manual or Disposal inlet (high) solenoid- no back pressure of system pressure Overhead Spray rinse When sprayer 5-202.13 Maintain sprayer head ASSE 1020 OK-Sprayer head is with valve head below >1” above flood rim, or ASSE 1056 the valve flood rim (high) PVB 6” unit Sink Faucets Possible 5-202.13 Air-gap between faucet Minimum NA Dipper well water inlet submerged inlet & flood rim at 2X inlet distance 1” diameter Pressure toilet/urinal Submerged 5-203.14 AVB downstream of ASSE 1001 Not allowed- no back inlet (high) valve ASSE 1037 pressure of system pressurized pressure flushing devices Trough Urinal Cross- 5-203.14 AVB downstream of ASSE 1001 No- no back pressure connection valve ASSE 1037 of system pressure (high) pressurized flushing devices Automatic wear/pot Submerged 5-203.14 Provide AVB 6” above ASSE 1001 None downstream of washing machine inlet (high) highest elevation of AVB (AVB must be detergent spray upstream of chemical
    [Show full text]
  • Backflow Prevention Devices
    Examples of Backflow Prevention during Mixing of Agricultural Chemicals 1. What Is Backflow? Backflow occurs when water flows opposite to its normal direction and can lead to contamination of the original water supply. Backflow can occur when collecting water from a source (well, watercourse, etc.) to combine with agricultural chemicals in a sprayer tank. This can cause chemical contamination of the source water. 2. Preventing Backflow The following table describes examples of backflow prevention techniques: Option Description Advantage Disadvantage Costs/Availability Use Use an alternate tank to supply water to Complete Requires an additional step, Variable cost; the alternate separate the sprayer as opposed to filling directly backflow filling the alternate tank tank should be clean water tank from the well, watercourse, etc. Water is prevention before filling the sprayer tank pumped from the source into the water tank and moved to the mixing/ loading area, located an adequate distance from wells and surface water Anti- Install a permanent anti-backflow device Quick solution, Installation may be Price ranges from $100.00 to backflow on the water supply line to prevent the requires no complicated, some types are $800.00; can be purchased device potential for backflow of chemicals from monitoring or susceptible to damage from from plumbing supply stores the sprayer tank. Devices include: double additional debris or freezing or most hardware stores. check valve or hose vacuum break valve steps after installation Maintain an A permanently fixed air gap between the Requires no Requires some monitoring No cost air gap water supply line and the sprayer tank additional can be maintained.
    [Show full text]
  • Water Distribution
    CITY OF LONGMONT WATER DISTRIBUTION TABLE OF CONTENTS 500.00 MINIMUM DESIGN CRITERIA................................................................................... 1 500.01 GENERAL ..................................................................................................................... 1 500.02 DESIGN GUIDELINES................................................................................................. 1 500.03 PIPE SIZES..................................................................................................................... 1 500.04 SERVICE LINES............................................................................................................ 2 500.05 DEPTH ...........................................................................................................................2 500.06 ALIGNMENT ................................................................................................................ 2 500.07 GRADE .......................................................................................................................... 2 500.08 FUTURE CONNECTIONS ........................................................................................... 2 500.09 VALVE SPACING ........................................................................................................ 3 500.10 FIRE HYDRANT LOCATION...................................................................................... 3 500.11 FIRE LINES & FIRE HYDRANT LINES ....................................................................
    [Show full text]
  • Cross Connections
    Cross Connections A cross connection is a direct connection of a non-potable water source with a potable source. Cross connections can result in serious illness and even death. Backflow can be the result of a cross connection, which can affect water quality and create health problems. One of the most notorious incidents of cross connection was the 1969 “Holy Cross Episode,” when many members of the Holy Cross football team developed infectious hepatitis as a result of contact with contaminated water pooled around a sprinkler head. The water supply became contaminated when a partial vacuum in the water distribution system was created due to a nearby fire, which drew contaminated water back into the potable water supply. Another backflow contamination case occurred in Minnesota in 1978 after an herbicide was backsiphoned from a farmer’s tank truck into a city’s water system. The farmer filled his water tank from a hose by the city’s water plant. The water pressure suddenly dropped and the pesticide in the truck was siphoned into the city’s water system. Fortunately, no illness from the contamination occurred, but the city had to limit its water use until the entire system could be flushed and refilled with safe water. BACKFLOW Backflow is defined as undesired, reversed flow of liquid in a piping system. Backflow can be caused by back siphonage, back pressure, or a combination of the two. Back-siphonage backflow occurs when there is a partial vacuum (negative pressures) in a water- supply system, drawing the water from a contaminated source into a potable water supply.
    [Show full text]
  • Backflow Prevention Assembly Installation Standards
    Revised Oct. 06 BACKFLOW PREVENTION ASSEMBLY INSTALLATION STANDARDS All backflow prevention assembly installation shall be in accordance with the following Standards unless otherwise directed or approved by the San Antonio Water System (SAWS). These instructions are general guidelines and are subject to change without notice. Any Inquiries or requests should be directed to the San Antonio Water System’s Backflow Prevention Section, at (210) 233-2421. I. GENERAL INSTRUCTIONS 1. Assemblies will be installed in an accessible location to facilitate maintenance, testing and repair, and should be located no more than five feet above the floor or grade level. The backflow preventer must be installed between the meter and the owner’s first tap or tee (total containment) unless otherwise approved. Internal containment will be approved for car washes, schools, retail laundries, and multiple lease spaces by individual review. In no instances will the assembly be allowed in the same vault with the San Antonio Water System’s water meter. Containment assemblies on fire lines must be located within 100’ (pipe length) of the property line. 2. Vault lids will be constructed in such a manner as to permit easy accessibility at all times by an individual. Vaults deeper than five feet shall be provided with a ladder permanently attached to a side wall. It is the contractor’s and owner’s obligation and responsibility to ensure OSHA regulations are adhered to in the construction of all vaults. Additionally, confined space regulations are to be consulted and followed in the testing and maintenance of the backflow prevention assemblies. 3. Before installing the assembly, pipelines should be thoroughly flushed to remove foreign material.
    [Show full text]
  • Chapter 6 Water Supply and Distribution
    ChaPTer 6 WaTer SuPPlY and diSTribuTion 601.0 hot and Cold Water required. TION: NONPOTABLE GRAY WATER, DO 601.1 general. Except where not deemed necessary for NOT DRINK” in yellow letters (Pantone 108 safety or sanitation by the Authority Having Jurisdiction, or equivalent). each plumbing fixture shall be provided with an adequate (2) Reclaimed (recycled) water systems shall be supply of potable running water piped thereto in an marked in accordance with this section with approved manner, so arranged as to flush and keep it in a the words: “CAUTION: NONPOTABLE clean and sanitary condition without danger of backflow or RECLAIMED (RECYCLED) WATER, DO cross-connection. Water closets and urinals shall be flushed NOT DRINK” in black letters. by means of an approved flush tank or flushometer valve. (3) On-site treated water systems shall be marked Exception: Listed fixtures that do not require water for in accordance with this section with the their operation and are not connected to the water supply. words: “CAUTION: ON-SITE TREATED In occupancies where plumbing fixtures are installed NONPOTABLE WATER, DO NOT DRINK” for private use, hot water shall be required for bathing, in yellow letters (Pantone 108 or equivalent). washing, laundry, cooking purposes, dishwashing or main- (4) Rainwater catchment systems shall be marked tenance. In occupancies where plumbing fixtures are in accordance with this section with the installed for public use, hot water shall be required for words: “CAUTION: NONPOTABLE RAIN- bathing and washing purposes. This requirement shall not WATER WATER, DO NOT DRINK” in yel- supersede the requirements for individual temperature con- low letters (Pantone 108 or equivalent).
    [Show full text]