Theory of Backflow and Backsiphonage

Total Page:16

File Type:pdf, Size:1020Kb

Theory of Backflow and Backsiphonage Chapter Three Pabsolute = Pgage + 14.7psi Water Pressure Theory of Backflow or For an understanding of the Pgage = Pabsolute – 14.7 psi nature of pressure and its and Backsiphonage In essence then, absolute relationship to water depth, pressure is the total pressure. consider the pressure exerted on Gage pressure is simply the the base of a cubic foot of water pressure read on a gage. If there at sea level. (See Fig. 1) The is no pressure on the gage other average weight of a cubic foot than atmospheric, the gage cross-connection1 is the of water is 62.4 pounds per would read zero. Then the link or channel connecting square foot gage. The base may A absolute pressure would be a source of pollution with a be subdivided into 144-square equal to 14.7 psi which is the potable water supply. The inches with each subdivision atmospheric pressure. polluting substance, in most being subjected to a pressure of The term vacuum indicates cases a liquid, tends to enter the 0.433 psig. that the absolute pressure is less potable supply if the net force Suppose another cubic foot than the atmospheric pressure acting upon the liquid acts in of water were placed directly and that the gage pressure is the direction of the potable on top of the first (See Fig. 2). negative. A complete or total supply. Two factors are therefore The pressure on the top surface vacuum would mean a pressure essential for backflow. First, of the first cube which was of 0 psia or -14.7 psig. Since it there must be a link between originally atmospheric, or is impossible to produce a total the two systems. Second, the 0 psig, would now be 0.433 vacuum, the term vacuum, as resultant force must be toward psig as a result of the super- used in the text, will mean all the potable supply. imposed cubic foot of water. degrees of partial vacuum. In a An understanding of the The pressure of the base of partial vacuum, the pressure principles of backflow and the first cube would also be would range from slightly less backsiphonage requires an increased by the same amount than 14.7 psia (0 psig) to understanding of the terms of 0.866 psig, or two times the slightly greater than 0 psia frequently used in their original pressure. (-14.7 psig). discussion. Force, unless com- Backsiphonage1 results in pletely resisted, will produce fluid flow in an undesirable or motion. Weight is a type of reverse direction. It is caused by FIGURE 1. force resulting from the earth’s atmospheric pressure exerted on Pressure exerted by 1 foot of gravitational attraction. water at sea level. a pollutant liquid forcing it Pressure (P) is a force-per-unit toward a potable water supply area, such as pounds per square system that is under a vacuum. inch (psi). Atmospheric pressure is 62.4#/ft3 Backflow, although literally the pressure exerted by the 12" meaning any type of reversed 12" weight of the atmosphere above flow, refers to the flow produced 12" the earth. by the differential pressure Pressure may be referred to existing between two systems using an absolute scale, pounds both of which are at pressures per square inch absolute (psia), greater than atmospheric. Sea level or gage scale, pounds per square inch gage (psig). 0.433 psig Absolute pressure and gage pressure are related. Absolute pressure is equal to the gage pressure plus the atmospheric pressure. At sea level the atmospheric pressure is 14.7 psia. Thus, 1See formal definition in the glossary of the appendix 12 • CROSS-CONNECTION CONTROL MANUAL If this process were Siphon Theory level exactly balances the because of the partial vacuum repeated with a third cubic foot weight of a column of water created by the drop in pressure. of water, the pressures at the Figure 3 depicts the atmo- 33.9 feet in height. The If the faucet were opened, base of each cube would be spheric pressure on a water absolute pressure within the however, the vacuum would be 1,299 psig, 0.866 psig, and surface at sea level. An open column of water in Figure 4 at broken and the water level 0.433 psig, respectively. It is tube is inserted vertically into a height of 11.5 feet is equal to would drop to a height of 77 evident that pressure varies the water; atmospheric pres- 9.7 psia. This is a partial feet above the ground. Thus, with depth below a free water sure, which is 14.7 psia, acts vacuum with an equivalent the atmosphere was supporting surface; in general each foot of equally on the surface of the gage pressure of -5.0 psig. a column of water 23 feet high. elevation change, within a water within the tube and on As a practical example, Figure 5 is a diagram of an liquid, changes the pressure by the outside of the tube. assume the water pressure at a inverted U-tube that has been an amount equal to the weight- closed faucet on the top of a filled with water and placed in per-unit area of 1 foot of the FIGURE 3. 100-foot high building to be 20 two open containers at sea level. Pressure on the free surface of a liquid. The rate of increase for liquid at sea level. psig; the pressure on the If the open containers are water is 0.433 psi per foot of ground floor would then be placed so that the liquid levels depth. 63.3 psig. If the pressure at the in each container are at the Frequently water pressure ground were to drop suddenly same height, a static state will is referred to using the terms due to a heavy fire demand in exist; and the pressure at any “pressure head” or just “head,” the area to 33.3 psig, the specified level in either leg of and is expressed in units of feet pressure at the top would be the U-tube will be the same. of water. One foot of head reduced to -10 psig. If the The equilibrium condition would be equivalent to the building water system were is altered by raising one of the pressure produced at the base airtight, the water would containers so that the liquid of a column of water 1 foot in remain at the level of the faucet level in one container is 5 feet depth. One foot of head or 14.7 14.7 psia psia 1 foot of water is equal to 0.433 FIGURE 5. FIGURE 4. sea level Pressure relationships in a psig. One hundred feet of head Effect of evacuating air from a continuous fluid system at the column. is equal to 43.3 psig. same elevation. FIGURE 2. “Zero” Absolute 4.7 psia Pressure exerted by 2 feet of Pressure water at sea level. If, as shown in Figure 4, the tube is slightly capped and a vacuum pump is used to 0.0 evacuate all the air from the psia sealed tube, a vacuum with a or Vacuum pump -14.7 ' pressure of 0 psia is created psig 10.3 psia 23 within the tube. Because the 24" pressure at any point in a static 0.433 psig fluid is dependent upon the ' height of that point above a 10 ' reference line, such as sea level, 39.9 it follows that the pressure 9.7 within the tube at sea level psia or -5.0 psig 14.7 14.7 must still be 14.7 psia. This is psia psia 0.866 psig equivalent to the pressure at the ' Sea Level base of a column of water 33.9 11.5 feet high and with the column 14.7 14.7 psia or open at the base, water would psia 0.0 psig rise to fill the column to a depth Sea level of 33.9 feet. In other words, the 1See formal definition in the glossary of the appendix weight of the atmosphere at sea CHAPTER THREE • 13 above the level of the other. (See level, since atmosphere cannot shown that as a fluid acceler- FIGURE 9. Dynamically reduced pipe Fig. 6.) Since both containers support a column of water ates, as shown in Figure 8, the pressures. are open to the atmosphere, the greater in height than 33.9 feet. pressure is reduced. As water pressure on the liquid surfaces Figure 7 illustrates how flows through a constriction From pollution To fixture in each container will remain at this siphon principle can be such as a converging section of source 14.7 psia. hazardous in a plumbing pipe, the velocity of the water If it is assumed that a static system. If the supply valve is increases; as a result, the state exists, momentarily, closed, the pressure in the line pressure is reduced. Under such within the system shown in supplying the faucet is less than conditions, negative pressures Figure 6, the pressure in the left the pressure in the supply line may be developed in a pipe. +50 psig tube at any height above the to the bathtub. Flow will occur, The simple aspirator is based free surface in the left container therefore, through siphonage, upon this principle. If this can be calculated. The pressure from the bathtub to the open point of reduced pressure is -10 psig at the corresponding level in the faucet. linked to a source of pollution, right tube above the free surface backsiphonage of the pollutant in the right container may also can occur.
Recommended publications
  • FACT SHEET: BACKFLOW DEVICES 2015 MINNESOTA PLUMBING CODE Minnesota Department of Labor and Industry
    FACT SHEET: BACKFLOW DEVICES 2015 MINNESOTA PLUMBING CODE Minnesota Department of Labor and Industry REQUIREMENTS Refer to the 2015 Minnesota Plumbing Code Parts 603.5.23 through 603.5.23.4 for details about the backflow prevention requirements discussed in this fact sheet. Devices that need to be tested Testing and maintenance The 2015 Minnesota Plumbing Code requires that all • The backflow device must be tested upon initial testable backflow devices be tested upon installation and at installation and at least annually thereafter. least annually thereafter by a certified backflow assembly • Test results must be submitted to the administrative tester. Testable devices include: authority and to the community public water supplier • Reduced pressure principal backflow prevention within 30 days of testing. assemblies, • Reduced pressure detector fire protection backflow Applicability prevention assemblies, • Reduced pressure (RPZ) devices have had testing • Double check backflow prevention assemblies, requirements for many years. New and existing RPZ • Pressure vacuum breaker backflow prevention installations must be tested annually. assemblies, • The testing requirements for testable non-RPZ devices • Double check detector fire protection backflow became effective for installations made on or after prevention assemblies, and Jan. 23, 2016. • Spill resistant pressure vacuum breakers. Tester qualifications Installing the device Testing of backflow prevention devices requires certification • A licensed plumber must perform the installation of a to ASSE Standard 5110. Testing of reduced pressure principal backflow prevention device. devices (RPZs) requires an additional certification by the • The public water supplier must be notified within 30 commissioner of the Minnesota Department of Labor and days following installation of the device on a community Industry.
    [Show full text]
  • January 29, 2020 Backflow Protection on an Emergency Eye Wash, Body
    January 29, 2020 Backflow Protection on an Emergency Eye Wash, Body Drench Station, Animal Wash Basins, Mani/Pedicure Bowls near sink Code: 2018 Plumbing Code Section(s): P202, P405.1, P608.5, P608.13, P608.13.2, P608.13.5, P608.13.6, P608.13.7, P608.15.4.1 Question: Do I need to install a AVB, PVB, or an RP on an emergency shower, pull-out style drench hose, Animal wash basin, mani/pedicure bowls and/or eyewash stations at a sink/lavatory/service sink? Answer: Well, it depends. Does the station have continuous water pressure? Will the sink potentially receive waste consisting of chemicals, biohazards, and/or other high hazard applications? Does the station have an integral sprayer? Is there a fixed air gap between the outlet and any nearby sink, pits, and any other areas that would allow the outlet to be submerged? All of these variable and more, come into play when trying to determine what type of backflow protection is required on these types of stations at or near a sink. The type of faucet you use and how it is installed determines the type of backflow preventer that is required. These backflow requirements shall be determined during the CCC plan review process of the Building permit application using the MEP drawings. Compliance will be confirmed during the CO approval process by the CCC Inspector. The following shall be taken into consideration with choosing a system; P202 – Definitions Air Gap (Drainage System). The unobstructed vertical distance through the free atmosphere between the outlet of the waste pipe and the flood level rim of the receptacle into which the waste pipe is discharging.
    [Show full text]
  • Cross-Connection Control Manual and Design Criteria for Cross-Connection Control Plans, Ordinances, and Policies
    CROSS-CONNECTION CONTROL MANUAL AND DESIGN CRITERIA FOR CROSS-CONNECTION CONTROL PLANS, ORDINANCES, AND POLICIES DIVISION OF WATER SUPPLY TENNESSEE DEPARTMENT OF ENVIRONMENT AND CONSERVATION 2008 1. TABLE OF CONTENTS Tennessee Department of Environment and Conservation Guidelines…………..…………….……................. p.1 Definition of Terms............................................................................................................................................p.3 CHAPTER I. Introduction to Backflow Prevention…………………………………………………………..…....…....…..p.6 1.1 Introduction 1.2 Objective 1.3 Causes of Backflow 1.3.1 Backsiphonage 1.3.2 Backpressure II. Responsibility and Authority for Cross-Connection Control…………………………………………….....p.9 2.1 Responsibility 2.1.1 The Water Purveyor 2.1.2 The Customer 2.1.3 Plumbing Inspection Agencies 2.1.4 Installers and Maintenance Personnel 2.1.5 Tennessee Department of Environment and Conservation 2.1.6 Legal Consideration 2.2 Authority 2.2.1 General Discussion 2.2.2 Local Authority 2.2.3 State Wide Authority 2.2.4 Federal Authority III. Developing and Implementing a Cross-Connection Control Program………………………………..….p.14 3.1 Introduction 3.2 Outline of Considerations in Preparing a Plan 3.3 Discussions of Local Cross-Connection Control Plan 3.4 Implementation of the Cross-Connection Control Plan 3.5 Establishing Priorities for Investigation IV. Recommended Practices……………………………………………………………………………………...p.19 4.1 Basic Consideration 4.2 Premises Isolation 4.3 Situations Requiring Maximum Protection 4.4 Establishments
    [Show full text]
  • Cross-Connection Questions, Answers & Illustrations
    50 Cross-Connection Questions, 5Answers & Illustrations0 Relating to Backflow Prevention Products and Protection of Safe Drinking Water Supply watts.com What is backsiphonage? 1 Backsiphonage is the reversal of normal flow in a system caused by a negative pressure (vacuum or partial vacuum) in the supply piping. What factors can cause backsiphonage? 2 Backsiphonage can be created when there is stoppage of the water supply due to nearby firefighting, repairs or breaks in city main, etc. The effect is similar to the sipping of a soda by inhaling through a straw, which induces a flow in the opposite direction. What is backpressure backflow? 3 Backpressure backflow is the reversal of normal flow in a system due to an increase in the downstream pressure above that of the supply pressure. Supply Feed Valve What factors can cause a 4 backpressure backflow condition? Backpressure backflow is created whenever the downstream pressure exceeds the supply pres- sure which is possible in installations such as heating systems, elevated tanks, and pressure-producing systems. An example Return would be a hot water space-heating boiler operating under 15-20 Boiler lbs. pressure coincidental with a reduction of the city water supply below such pressure (or higher in most commercial boilers). As wa- ter tends to flow in the direction of least resistance, a backpressure backflow condition would be created and the contaminated boiler water would flow into the potable water supply. What is a cross-connection? 5 A cross-connection is a direct arrangement of a piping line which allows the potable water supply to be connected to a line which contains a contaminant.
    [Show full text]
  • Low-Volume Irrigation Systems for Blueberry with Chemigation and Fertigation Suggestions
    Low-Volume Irrigation Systems for Blueberry with Chemigation and Fertigation Suggestions Erick Smith, Department of Horticulture, UGA Tifton campus Wesley Porter, Crop and Soil Sciences, UGA Tifton campus Jonathan Oliver, Department of Plant Pathology, UGA Tifton campus Drip, trickle, microemitters, and subsurface irrigation systems are considered low-volume irrigation. Low-volume irrigation systems are designed to improve irrigation efficiency, delivering water to the crop accurately with minimal water loss. Irrigation efficiency (Table 1) can be categorized into two main concepts: water loss and uniform application. If water loss is significant, or application uniformity is poor, efficiency will be low. Generally, the most significant loss of irrigation water is from overwatering, where the water percolates below the root zone, or from runoff. With good management, losses due to leaks, system drainage, and flushing of filters and lateral lines should not exceed 1%. Low- volume systems have the opportunity to achieve efficiency, and under careful management, will minimize losses from overirrigation. However, using low-volume systems requires increased irrigation frequency and soil moisture monitoring should be used to improve water-use efficiency. Uniformity is desired for each application of water, meaning that the irrigated area receives the same portion of water throughout. A well-designed irrigation system accounts for variability by applying water based on the soil structure (e.g. sandy, silt, loam, clay, and organic matter) and environmental conditions (e.g. wind, temperature, and cloud cover). That said, systems can have losses inherent to the design (Table 1). There may be variability in efficiencies that are noticeable even when comparing low-volume emitters (i.e.
    [Show full text]
  • 3- Ways to Protect from Backflow
    3- WAYS TO PROTECT FROM BACKFLOW Air gap Description: An approved air gap is a method of backflow prevention that means the physical separation between the end of the water supply pipe (example: faucet) and open vessel (example: sink). Installation and testing requirements: The separation must be twice the supply pipe inside diameter but never less than one inch. An air gap or physical disconnection gives the highest degree of protection and shall be used whenever practical in high hazard situations subject to backpressure. Since the application of air gaps is limited, other backflow protection systems can be used Reduced Pressure Zone Backflow Preventer Description: The Reduced Pressure backflow preventer consists of two independent check valves and a differential pressure relief valve, which automatically relieves excess pressure Typical use: The reduced pressure zone backflow preventer controls direct and indirect cross-connections it’s also used to isolate Installation and testing requirements: Due to certain combinations of potable water from non-potable water lines. Used check valve failure and/or system backpressure cause the relief valve to for high hazard risks, the reduced pressure zone discharge, the device must be mounted in a location where the drain will backflow preventer provides the highest level of not become flooded. Annual testing is required. protection. Double check Valve Assembly Description: The Double Check Valve (DC) assembly consists of two single independently acting check valves with water tight valves located at each end of the assembly. Typical use: The double check backflow preventer can only be used in low hazards situations. The use of this type of device is to Installation and testing requirements: The Double check valve (DC) must be protect against back-siphonage or backflow installed in an accessible location for annual testing, this device can be caused by backpressure.
    [Show full text]
  • Potential Plumbing Violations in Food Service Establishments Updated August 2008 Michigan Department of Agriculture, Food and Dairy Division
    Potential Plumbing Violations in Food Service Establishments Updated August 2008 Michigan Department of Agriculture, Food and Dairy Division Protecting the Water Supply Line PROBLEM VIOLATION FC CORRECTION(s) ASSE#’s VALVE AREA (Hazard Section most DOWNSTREAM level) common Toilet Tanks Submerged 5-203.14 Anti-siphon ball cock ASSE 1002 inlet (high) assembly—1” above overflow Hose Bib connection Possible back 5-203.14 Hose bib vacuum ASSE 1011 Not allowed- no back siphon from breaker or 1052 pressure of system hose (high) pressure Water inlet Garbage Submerged 5-203.14 AVB 6” above flood rim ASSE 1001 NO valves-manual or Disposal inlet (high) solenoid- no back pressure of system pressure Overhead Spray rinse When sprayer 5-202.13 Maintain sprayer head ASSE 1020 OK-Sprayer head is with valve head below >1” above flood rim, or ASSE 1056 the valve flood rim (high) PVB 6” unit Sink Faucets Possible 5-202.13 Air-gap between faucet Minimum NA Dipper well water inlet submerged inlet & flood rim at 2X inlet distance 1” diameter Pressure toilet/urinal Submerged 5-203.14 AVB downstream of ASSE 1001 Not allowed- no back inlet (high) valve ASSE 1037 pressure of system pressurized pressure flushing devices Trough Urinal Cross- 5-203.14 AVB downstream of ASSE 1001 No- no back pressure connection valve ASSE 1037 of system pressure (high) pressurized flushing devices Automatic wear/pot Submerged 5-203.14 Provide AVB 6” above ASSE 1001 None downstream of washing machine inlet (high) highest elevation of AVB (AVB must be detergent spray upstream of chemical
    [Show full text]
  • Backflow Prevention Devices
    Examples of Backflow Prevention during Mixing of Agricultural Chemicals 1. What Is Backflow? Backflow occurs when water flows opposite to its normal direction and can lead to contamination of the original water supply. Backflow can occur when collecting water from a source (well, watercourse, etc.) to combine with agricultural chemicals in a sprayer tank. This can cause chemical contamination of the source water. 2. Preventing Backflow The following table describes examples of backflow prevention techniques: Option Description Advantage Disadvantage Costs/Availability Use Use an alternate tank to supply water to Complete Requires an additional step, Variable cost; the alternate separate the sprayer as opposed to filling directly backflow filling the alternate tank tank should be clean water tank from the well, watercourse, etc. Water is prevention before filling the sprayer tank pumped from the source into the water tank and moved to the mixing/ loading area, located an adequate distance from wells and surface water Anti- Install a permanent anti-backflow device Quick solution, Installation may be Price ranges from $100.00 to backflow on the water supply line to prevent the requires no complicated, some types are $800.00; can be purchased device potential for backflow of chemicals from monitoring or susceptible to damage from from plumbing supply stores the sprayer tank. Devices include: double additional debris or freezing or most hardware stores. check valve or hose vacuum break valve steps after installation Maintain an A permanently fixed air gap between the Requires no Requires some monitoring No cost air gap water supply line and the sprayer tank additional can be maintained.
    [Show full text]
  • Water Distribution
    CITY OF LONGMONT WATER DISTRIBUTION TABLE OF CONTENTS 500.00 MINIMUM DESIGN CRITERIA................................................................................... 1 500.01 GENERAL ..................................................................................................................... 1 500.02 DESIGN GUIDELINES................................................................................................. 1 500.03 PIPE SIZES..................................................................................................................... 1 500.04 SERVICE LINES............................................................................................................ 2 500.05 DEPTH ...........................................................................................................................2 500.06 ALIGNMENT ................................................................................................................ 2 500.07 GRADE .......................................................................................................................... 2 500.08 FUTURE CONNECTIONS ........................................................................................... 2 500.09 VALVE SPACING ........................................................................................................ 3 500.10 FIRE HYDRANT LOCATION...................................................................................... 3 500.11 FIRE LINES & FIRE HYDRANT LINES ....................................................................
    [Show full text]
  • Cross Connections
    Cross Connections A cross connection is a direct connection of a non-potable water source with a potable source. Cross connections can result in serious illness and even death. Backflow can be the result of a cross connection, which can affect water quality and create health problems. One of the most notorious incidents of cross connection was the 1969 “Holy Cross Episode,” when many members of the Holy Cross football team developed infectious hepatitis as a result of contact with contaminated water pooled around a sprinkler head. The water supply became contaminated when a partial vacuum in the water distribution system was created due to a nearby fire, which drew contaminated water back into the potable water supply. Another backflow contamination case occurred in Minnesota in 1978 after an herbicide was backsiphoned from a farmer’s tank truck into a city’s water system. The farmer filled his water tank from a hose by the city’s water plant. The water pressure suddenly dropped and the pesticide in the truck was siphoned into the city’s water system. Fortunately, no illness from the contamination occurred, but the city had to limit its water use until the entire system could be flushed and refilled with safe water. BACKFLOW Backflow is defined as undesired, reversed flow of liquid in a piping system. Backflow can be caused by back siphonage, back pressure, or a combination of the two. Back-siphonage backflow occurs when there is a partial vacuum (negative pressures) in a water- supply system, drawing the water from a contaminated source into a potable water supply.
    [Show full text]
  • Backflow Prevention Assembly Installation Standards
    Revised Oct. 06 BACKFLOW PREVENTION ASSEMBLY INSTALLATION STANDARDS All backflow prevention assembly installation shall be in accordance with the following Standards unless otherwise directed or approved by the San Antonio Water System (SAWS). These instructions are general guidelines and are subject to change without notice. Any Inquiries or requests should be directed to the San Antonio Water System’s Backflow Prevention Section, at (210) 233-2421. I. GENERAL INSTRUCTIONS 1. Assemblies will be installed in an accessible location to facilitate maintenance, testing and repair, and should be located no more than five feet above the floor or grade level. The backflow preventer must be installed between the meter and the owner’s first tap or tee (total containment) unless otherwise approved. Internal containment will be approved for car washes, schools, retail laundries, and multiple lease spaces by individual review. In no instances will the assembly be allowed in the same vault with the San Antonio Water System’s water meter. Containment assemblies on fire lines must be located within 100’ (pipe length) of the property line. 2. Vault lids will be constructed in such a manner as to permit easy accessibility at all times by an individual. Vaults deeper than five feet shall be provided with a ladder permanently attached to a side wall. It is the contractor’s and owner’s obligation and responsibility to ensure OSHA regulations are adhered to in the construction of all vaults. Additionally, confined space regulations are to be consulted and followed in the testing and maintenance of the backflow prevention assemblies. 3. Before installing the assembly, pipelines should be thoroughly flushed to remove foreign material.
    [Show full text]
  • Chapter 6 Water Supply and Distribution
    ChaPTer 6 WaTer SuPPlY and diSTribuTion 601.0 hot and Cold Water required. TION: NONPOTABLE GRAY WATER, DO 601.1 general. Except where not deemed necessary for NOT DRINK” in yellow letters (Pantone 108 safety or sanitation by the Authority Having Jurisdiction, or equivalent). each plumbing fixture shall be provided with an adequate (2) Reclaimed (recycled) water systems shall be supply of potable running water piped thereto in an marked in accordance with this section with approved manner, so arranged as to flush and keep it in a the words: “CAUTION: NONPOTABLE clean and sanitary condition without danger of backflow or RECLAIMED (RECYCLED) WATER, DO cross-connection. Water closets and urinals shall be flushed NOT DRINK” in black letters. by means of an approved flush tank or flushometer valve. (3) On-site treated water systems shall be marked Exception: Listed fixtures that do not require water for in accordance with this section with the their operation and are not connected to the water supply. words: “CAUTION: ON-SITE TREATED In occupancies where plumbing fixtures are installed NONPOTABLE WATER, DO NOT DRINK” for private use, hot water shall be required for bathing, in yellow letters (Pantone 108 or equivalent). washing, laundry, cooking purposes, dishwashing or main- (4) Rainwater catchment systems shall be marked tenance. In occupancies where plumbing fixtures are in accordance with this section with the installed for public use, hot water shall be required for words: “CAUTION: NONPOTABLE RAIN- bathing and washing purposes. This requirement shall not WATER WATER, DO NOT DRINK” in yel- supersede the requirements for individual temperature con- low letters (Pantone 108 or equivalent).
    [Show full text]