User Guide Rack Power Distribution Unit Metered-by-Outlet AP84XX

990-5571E-001 Publication Date: December June 2017 Schneider Electric IT Corporation Legal Disclaimer The information presented in this manual is not warranted by the Schneider Electric IT Corporation to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan. Therefore, Schneider Electric IT Corporation assumes no liability for damages, violations of codes, improper installation, system failures, or any other problems that could arise based on the use of this Publication. The information contained in this Publication is provided as is and has been prepared solely for the purpose of evaluating data center design and construction. This Publication has been compiled in good faith by Schneider Electric IT Corporation. However, no representation is made or warranty given, either express or implied, as to the completeness or accuracy of the information this Publication contains. IN NO EVENT SHALL SCHNEIDER ELECTRIC IT CORPORATION, OR ANY PARENT, AFFILIATE OR SUBSIDIARY COMPANY OF SCHNEIDER ELECTRIC IT CORPORATION OR THEIR RESPECTIVE OFFICERS, DIRECTORS, OR EMPLOYEES BE LIABLE FOR ANY DIRECT, INDIRECT, CONSEQUENTIAL, PUNITIVE, SPECIAL, OR INCIDENTAL DAMAGES (INCLUDING, WITHOUT LIMITATION, DAMAGES FOR LOSS OF BUSINESS, CONTRACT, REVENUE, DATA, INFORMATION, OR BUSINESS INTERRUPTION) RESULTING FROM, ARISING OUT, OR IN CONNECTION WITH THE USE OF, OR INABILITY TO USE THIS PUBLICATION OR THE CONTENT, EVEN IF SCHNEIDER ELECTRIC IT CORPORATION HAS BEEN EXPRESSLY ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. SCHNEIDER ELECTRIC IT CORPORATION RESERVES THE RIGHT TO CHANGES OR UPDATES WITH RESPECT TO OR IN THE CONTENT OF THE PUBLICATION OR THE THEREOF ANY TIME WITHOUT NOTICE. Copyright, intellectual, and all other proprietary rights in the content (including but not limited to software, audio, video, text, and photographs) rests with Schneider Electric It Corporation or its licensors. All rights in the content not expressly granted herein are reserved. No rights of any kind are licensed or assigned or shall otherwise pass to persons accessing this information. This Publication shall not be for resale in whole or in part. Introduction...... 1 Product Features ...... 1 Types of User Accounts ...... 2 Watchdog Features ...... 3 Overview ...... 3 Network interface watchdog mechanism ...... 3 Resetting the network timer ...... 3 Network Port Sharing (NPS) ...... 4 About the Network Port Sharing Feature ...... 4 Display ID ...... 4 Installation Instructions ...... 4 Specific assignment of Display IDs ...... 4 Firmware Upgrade with NPS ...... 5 RF Tag ...... 5 EnergyWise...... 5 EnergyWise and NPS...... 6 Getting Started ...... 6 Establish Network Settings...... 7 IPv4 initial setup ...... 7 IPv6 initial setup ...... 7 TCP/IP configuration methods ...... 7 .ini utility ...... 7 DHCP and BOOTP configuration ...... 7 Network Management with Other Applications ...... 8 Command Line Interface (CLI) ...... 9 Recovering from a Lost Password ...... 10 Rack PDU Front Panel ...... 11 Network Status LED ...... 13 10/100 LED ...... 13 Load indicator LED ...... 13 Example 1 ...... 14 Example 2 ...... 15 Example 3 ...... 16 Example 4 ...... 17 Command Line Interface...... 18 About the Command Line Interface (CLI) ...... 18 Log on to the CLI ...... 18 Remote access to the command line interface ...... 18 Telnet for basic access ...... 19 SSH for high-security access ...... 19 Local access to the command line interface ...... 19 About the Main Screen ...... 20 Using the CLI ...... 21 Command Syntax...... 22 Command Response Codes ...... 23 Network Management Card Command Descriptions ...... 24

Rack PDU User Guide i ? or ...... 24 about ...... 25 alarmcount ...... 25 boot ...... 26 ...... 27 clrrst ...... 27 console ...... 28 date ...... 29 delete ...... 29 ...... 30 dns ...... 31 email ...... 32 eventlog ...... 33 , quit, or bye ...... 34 firewall ...... 34 format ...... 34 ftp ...... 35 lang ...... 35 lastrst ...... 36 ledblink ...... 36 logzip ...... 36 ...... 37 ntp ...... 37 ping ...... 38 portSpeed ...... 38 prompt ...... 39 ...... 39 radius ...... 40 reboot ...... 41 resetToDef ...... 41 session ...... 42 smtp ...... 42 snmp ...... 43 snmpv3 ...... 44 snmptrap ...... 46 system ...... 47 tcpip ...... 48 tcpip6 ...... 49 user ...... 50 userdflt ...... 51 web ...... 52 ...... 52 xferINI ...... 53 xferStatus ...... 53 Device Command Descriptions ...... 54 Network Port Sharing Commands ...... 54 alarmList ...... 54 bkLowLoad ...... 54 bkNearOver ...... 55 bkOverLoad ...... 55 bkPeakCurr ...... 56

ii Rack PDU User Guide bkReading ...... 56 bkRestrictn ...... 57 devLowLoad ...... 58 devNearOver ...... 58 devOverLoad ...... 58 devPeakLoad ...... 59 devReading ...... 59 dispID ...... 59 energyWise ...... 60 humHyst ...... 62 humLow ...... 62 humMin ...... 63 humReading ...... 63 lcd ...... 63 lcdBlink ...... 64 olAssignUsr ...... 64 olLowLoad ...... 65 olName ...... 66 olNearOver ...... 66 olOverLoad ...... 67 olPeakLoad ...... 68 olReading ...... 69 olUnasgnUsr ...... 69 phLowLoad ...... 70 phNearOver ...... 70 phOverLoad ...... 71 phPeakCurr ...... 71 phReading ...... 72 phRestrictn ...... 73 phTophVolts ...... 73 prodInfo ...... 74 sensorName ...... 75 tempHigh ...... 75 tempHyst ...... 75 tempMax ...... 76 tempReading ...... 76 userAdd ...... 77 userDelete ...... 77 userList ...... 78 userPasswd ...... 79 Web Interface ...... 80 Supported Web Browsers ...... 80 Log On to the Web Interface ...... 80 Overview ...... 80 URL address formats ...... 80 Web Interface Features ...... 81 Tabs ...... 81 Device status icons ...... 82 Quick Links ...... 82 Network Port Sharing (NPS) on the Web User Interface (UI) ...... 83

Rack PDU User Guide iii Group Control using Network Port Sharing ...... 83 About Home ...... 84 The Overview view ...... 84 Status Tab...... 85 About the Status Tab...... 85 View the Load Status and Peak Load ...... 86 View the Network Status ...... 86 Current IPv4 Settings ...... 86 Current IPv6 Settings ...... 86 Domain Name System Status ...... 87 Ethernet Port Speed ...... 87 Control ...... 88 Managing User Sessions ...... 88 Resetting the Network Interface ...... 89 Configuration ...... 90 About the Configuration Tab ...... 90 Configure Load Thresholds ...... 91 To configure load thresholds ...... 91 Configure Rack PDU Name and Location ...... 91 Reset Peak Load and kWh ...... 91 Outlet Settings ...... 92 Configure outlet settings and the outlet name ...... 92 Outlet User Manager ...... 93 Configure an outlet user ...... 93 Outlet Manager and Network Port Sharing ...... 93 Configure Temperature and Humidity Sensors ...... 94 Security...... 95 Session Management screen ...... 95 Ping Response ...... 95 Local Users ...... 95 Remote Users ...... 97 Configure the RADIUS Server ...... 98 Supported RADIUS servers ...... 98 RADIUS and Network Port Sharing ...... 99 Firewall Menus ...... 99 Network Features...... 100 TCP/IP and Communication Settings ...... 100 Port Speed ...... 102 DNS ...... 103 Web ...... 104 Console ...... 105 SNMP ...... 106 SNMPv1 ...... 107 SNMPv3 ...... 108 FTP Server ...... 109 Notifications ...... 110

iv Rack PDU User Guide Event Actions ...... 110 Configure event actions ...... 110 E- notification screens ...... 112 SNMP trap receiver screen ...... 114 SNMP traps screen ...... 114 Remote Monitoring Service ...... 115 General Menu ...... 116 Identification screen ...... 116 Date/Time screen ...... 116 Creating and importing settings with the config file ...... 117 Configure Links ...... 117 Logs in the Configuration Menu ...... 118 Identifying Syslog servers ...... 118 Syslog settings ...... 118 Syslog test and format example ...... 119 Tests Tab...... 120 Setting the Rack PDU LCD or LED Lights to Blink ...... 120 Logs Tab...... 121 Event, Data and Firewall Logs ...... 121 Event log ...... 121 Data log ...... 123 Firewall Logs ...... 125 Use FTP or SCP to retrieve log files ...... 125 About Tab...... 127 About the Rack PDU ...... 128 Support Screen ...... 128 Device IP Configuration Wizard ...... 129 Capabilities, Requirements, and Installation...... 129 How to use the Wizard to configure TCP/IP settings ...... 129 System requirements ...... 129 Installation ...... 129 How to Export Configuration Settings ...... 130 Retrieving and Exporting the .ini File...... 130 Summary of the procedure ...... 130 Contents of the .ini file ...... 130 .ini and Network Port Sharing ...... 130 Detailed procedures ...... 131 The Upload Event and Error Messages ...... 132 The event and its error messages ...... 132 Messages in config.ini ...... 133 Errors generated by overridden values ...... 133 Related Topics ...... 133 File Transfers ...... 134 Upgrading Firmware ...... 134

Rack PDU User Guide Benefits of upgrading firmware ...... 134 Firmware module files (Rack PDU) ...... 134 Firmware File Transfer Methods...... 135 Using the Firmware Upgrade Utility ...... 135 Use FTP or SCP to upgrade one Rack PDU ...... 136 Use XMODEM to upgrade one Rack PDU ...... 137 Use a USB drive to transfer and upgrade the files ...... 137 How to upgrade multiple Rack PDUs ...... 138 Using the Firmware Upgrade Utility for multiple upgrades ...... 138 Updating firmware for Network Port Sharing (NPS) Groups ...... 138 Verifying Upgrades and Updates ...... 139 Verify the success or failure of the transfer ...... 139 Last Transfer Result codes ...... 139 Verify the version numbers of installed firmware...... 139 Troubleshooting...... 140 Rack PDU Access Problems...... 140 SNMP Issues ...... 142 Source Code Copyright Notice...... 143

Rack PDU User Guide Introduction

Product Features The APC by Schneider Electric Metered-by-Outlet Rack Power Distribution Unit (PDU) may be used as a stand-alone, network-manageable power distribution device or up to four devices can be connected together using one network connection. The Rack PDU provides real- remote monitoring of connected loads. User- defined alarms warn of potential circuit overloads. The Rack PDU provides full control over outlets through remote commands and user interface settings. Your Rack PDU comes with a terminator installed in the display In or Out port. In stand-alone operation of Metered-by-Outlet models, one terminator must be installed in the display In or Out port. To use Network Port Sharing between up to four units, a terminator must be installed in the In port at one end of the group and another on the Out port at the other end of the group. You can manage a Rack PDU through its web interface (UI), its command line interface (CLI), StruxureWare, or Simple Network Management Protocol (SNMP). (To use the PowerNet MIB with an SNMP browser, see the PowerNet SNMP Management Information Base (MIB) Reference Guide, available at www.apc.com.) Rack PDUs have these additional features: • Device power, peak power, apparent power, power and energy. • Phase voltage, current, peak current, power, apparent power and power factor. • Bank current and peak current (for models that support breaker banks). • Outlet current, energy, and power monitoring. • Configurable alarm thresholds that provide network and visual alarms to help avoid overloaded circuits. • Various levels of access: Super User, Administrator, Device User, Read-Only, Outlet User, and Network-Only User (These are protected by user name and password requirements). • Multiple user login feature allows up to four users to be logged in simultaneously. • Event and data logging. The event log is accessible by Telnet, Secure (SCP), (FTP), serial connection, or web browser (using HTTPS access with SSL, or using HTTP access). The data log is accessible by web browser, SCP, or FTP. • E-mail notifications for Rack PDU and Network Management Card (NMC) system events. • SNMP traps, Syslog messages, and e-mail notifications based on the severity level or category of the Rack PDU and NMC system event. • Security protocols for authentication and encryption. • Network Port Sharing (NPS). Up to four Rack PDUs of any model can be connected using the In and Out ports so that only one network connection is necessary. • NPS guest firmware auto-update feature allows the NPS to automatically pass a firmware update to its connected guests. This feature will be functional for all guests that have AOS firmware version 6.1.3 or later. • RF Code wireless monitoring support via serial port connection • Cisco EnergyWise certified. NOTE: The Rack PDU does not provide power surge protection. To ensure that the device is protected from power failure or power surges, connect the Rack PDU to a Schneider Electric Uninterruptible Power Supply (UPS).

Rack PDU User Guide 1 Types of User Accounts

The Rack PDU has various levels of access (Super User, Administrator, Device User, Read-Only User, Outlet User, and Network-Only User), which are protected by user name and password requirements. Up to four users are allowed to login to the same Rack PDU simultaneously (available in AOS version 6.1.3 or later). • An Administrator or the Super User can use all of the menus in the UI and all of the commands in the CLI. Administrator user types can be deleted, but the Super User cannot be deleted. The default user name and password for the Super User are both apc. –The Super User or Administrator can manage another Administrator's account (enable, disable, change password, etc). • A Device User has read and access to device-related screens. Administrative functions like session management under the Security menu and Firewall under Logs are grayed out. • A Read-Only User has the following restricted access: – Access to the same menus as a Device User, but without the capability to change configurations, control devices, delete data, or use file transfer options. Links to configuration options are visible but disabled. The event and data logs display no button to the log. • An Outlet User has the following restricted access: – Access through the web interface and command line interface. – Access to the same menus as a Device User, but with limited capability to change configurations, control devices, delete data, or use file transfer options. Links to configuration options are visible but are disabled. The Outlet User has access to the Metered Outlet menu option that allows the user to view only the outlets assigned by the Administrator. Outlet Users cannot clear the event or data logs. The user name and password are defined by the Administrator during the of adding a new Outlet User. • A Network-Only User can only log on using the Web UI and CLI (telnet, not serial). A network- only user has read/right access to the network related menus only.

2 Rack PDU User Guide Watchdog Features Overview To detect internal problems and from unanticipated inputs, the Rack PDU uses internal, system-wide watchdog mechanisms. When it restarts to recover from an internal problem, a Network Interface Restarted event is recorded in the event log. Network interface watchdog mechanism The Rack PDU implements internal watchdog mechanisms to protect itself from becoming inaccessible over the network. For example, if the Rack PDU does not receive any network traffic for 9.5 minutes (either direct traffic, such as SNMP, or broadcast traffic, such as an Address Resolution Protocol [ARP] request), it assumes that there is a problem with its network interface and restarts. The network interface watchdog mechanism is only enabled on a PDU that discovers an active network interface connection at -up. This allows guest PDUs in a Network Port Sharing chain to function normally without rebooting every 9.5 minutes. Resetting the network timer To ensure that the Rack PDU does not restart if the network is quiet for 9.5 minutes, the Rack PDU attempts to contact the every 4.5 minutes. If the gateway is present, it responds to the Rack PDU and the response restarts the 9.5-minute timer. If your application does not require or have a gateway, specify the IP address of a computer that is running on the network and is on the same subnet. The network traffic of that computer will restart the 9.5-minute time frequently enough to prevent the Rack PDU from restarting.

Rack PDU User Guide 3 Network Port Sharing (NPS) About the Network Port Sharing Feature You can use the Network Port Sharing feature to view the status of and configure and manage up to four Rack PDUs using only one network connection. This is made possible by connecting the Rack PDUs via the In and Out ports on the Rack PDU front panel. NOTE: All Rack PDUs in the group must be using the same Rack PDU firmware revision, 5.1.5 or later (excluding v6.0.5 EnergyWise), in order to support the Network Port Sharing Feature. Display ID The display ID is a number, 1 to 4, used to uniquely identify the Rack PDUs in a group. After two or Rack PDUs are connected to one another in an NPS group, they can be identified on the various interfaces by the use of this "Display ID". This Display ID is viewable in the left corner of the display. Alternatively, a larger Display ID “shadow” can be enabled on the LCD by selecting the Display Settings > Display ID > Show option on the LCD keypad. Installation Instructions Connect up to four Rack PDUs via the In and Out ports on the Rack PDU. Insert an RJ45 terminator (included) in the unused In/Out ports on each end of the chain. NOTE: Failure to use terminators may cause a loss of communication on the Rack PDUs. NOTE: To reduce the possibility of communication issues, the maximum total length of cabling connecting Rack PDUs in a group should not exceed 10 meters. All Rack PDUs in a NPS group should reside in the same rack enclosure. Connect the "Network" port of one of the grouped Rack PDUs to a network hub or switch. This unit will be the Host for the Rack PDU group. Guest PDU data will be viewable on the Host PDU. Set up network functionality for this Host Rack PDU as specified in the Establish Network Settings section. The Host will automatically discover any Guest PDUs connected via In/Out ports. The Rack PDU group is now available via the Host's IP address. NOTE: Only one Rack PDU in an NPS group is allowed to be the host. If two host Rack PDUs are connected together, one will automatically be chosen to be the single host for the NPS group. The user also has the option to select a particular guest to be the host as long as that guest has an active network . The host Rack PDU supports many features that are not supported by NPS guests. These include, but are not limited to: • SNMP rPDU2Group OIDs • EnergyWise support • Initiating AOS/App firmware updates for guest Rack PDUs • Time synchronization for guest Rack PDUs • Data logging for the guest Rack PDUs Specific assignment of Display IDs Follow the instructions below before powering up any of the Rack PDUs in the group. If it is desired to have a specific assignment of Display IDs, this can be achieved by powering up the units for the first time in the desired order, 1 to 4. For example, before powering up any of the Rack PDUs connected in a group, determine the Display ID order that you would like. Then, first power up the unit that you would like to have Display ID 1. After that unit has initialized and the LCD has started displaying its screens, power on the unit that you would like to have Display ID 2. Continue in the same way for units 3 and 4, if applicable for your setup. NOTE: The Display ID can be configured from the web interface via the "Configuration > RPDU > Device > Display ID" field. The Display ID can also be configured from the CLI interface via the dispID command.

4 Rack PDU User Guide Firmware Upgrade with NPS

At start-up and routinely during operation, the NPS host compares its own AOS and application versions with the versions found on each guest. In the event of a version difference, the host copies its AOS and then its application to the non-complying guests via the NPS chain. NOTE: Automatic firmware upgrade is only available for Rack PDUs running AOS version v6.1.3 or later as this functionality requires resident firmware support in the NPS host and guests. This functionality requires that any replacement Rack PDUs also be running AOS version v6.1.3 or later to maintain correct operation of the NPS chain. RF Tag

The Rack PDU supports the RF Code sensor tag for Schneider Electric Rack PDUs. The tag enables data center managers to wirelessly monitor power consumption and utilization with the enterprise-class Asset RF Code Zone Manager. The Zone Manager middleware consumes information about power attribute values as reported by the Rack PDU. The RF Code sensor tag for Schneider Electric works in concert with the AP8XXX Rack PDUs with firmware v6.0.9 or later. To implement an RF Code sensor tag solution, plug the tag into the RJ-12 socket labeled Serial Port. Scroll the LCD menu to highlight the RF Code Control entry, press the Select button. Press the select button again to enable. The Rack PDU will immediately reboot and start serial communication with the tag. When an NPS guest RF tag is removed, the NPS host will signal an alarm. In order to clear this alarm, one must the tag and disable the tag in the LCD menu. Then the error will be cleared and the NPS guest will auto reboot. The RF Tag reports per-phase load voltage/amperage/power readings every 10 minutes and device power/ energy use, per-outlet watt-hour/switch state/RMS current, and phase outlet voltages/bank overload state readings every hour. Outlet and bank readings are Rack PDU model dependent as all models do not support monitoring. The complete RF solution requires an RF Code reader, an RF Code Zone Manager, or RF Code Asset Manager. For more information see: www.rfcode.com. EnergyWise

The Rack PDU has the capability of becoming a Cisco EnergyWise Entity. This entity reports power usage and alarms in the EnergyWise Domain. To exercise this capability, plug the Rack PDU network port into a Cisco switch/router that supports the EnergyWise Domain. Log into the web interface of the Rack PDU and navigate to the Configuration/RPDU/ EnergyWise web page. Click on the enable radio button to initiate the task. The task will generate unique parent and children names, default roles, keywords and importance values that comply with EnergyWise requirements. Customization of the aforementioned is supported by clicking on any of the underlined entities to navigate to a configuration web page. The EnergyWise port, domain name and shared secret may also be modified, but must be coordinated with the same parameters in the Cisco gear. The Rack PDU implementation supports a single parent, multiple children hierarchy. The parent may exist as a standalone Rack PDU or as the host Rack PDU for an NPS chain of Rack PDUs. The parent usage reports the power consumed by the Rack PDUs themselves, including any NPS guest Rack PDUs. The children report either inlet power or, in the case of monitored outlets, the power consumed at the outlet. Both parent and children report a usage level (0-10 scale). The parent and inlet usage are always reported as 10 or “On”. When the parent is the host Rack PDU of an NPS chain, the reported parent power is the of the parent and each of the NPS guests. The parent also reports an inlet entity for itself and for each guest as well as an outlet entity for each host outlet and each outlet of every guest. The remaining configurable items are string variables that may be modified as needed and are retained across power cycles or reboots.

Rack PDU User Guide 5 EnergyWise and NPS

The Rack PDUs support Cisco EnergyWise with Rack PDU v6.0.9 firmware or later. The Rack PDU EnergyWise application generates a family at startup. This tree is reported to Cisco hardware during the discovery process. For an initial installation, either establish the NPS chain and enable EnergyWise on the host or enable EnergyWise on the host and then disable and re-enable EnergyWise after the NPS communication is established. Clearly, the first option is simpler. For Rack PDU replacement, the following procedure should be followed. Power down the Rack PDU – any children associated with this Rack PDU will report EW levels and usage as zero. On the Status/Rack PDU/ Group web page, there should be a check box to allow the user to remove the now non-functioning Rack PDU from the NPS chain. Once removed from the chain, any children associated with that Rack PDU will report “.0.” in the display identifier portion of the EW name field. At this time, one can replace the Rack PDU with another of the same model and expect the EnergyWise to function properly again once communication is established. If for some reason the replacement model is different, EnergyWise will have to be disabled and re-enabled after NPS communication is established, to update the family tree and the order of data reported. For more information see: www.cisco.com/en/us/products/ps10195/index.html. Getting Started

To start using the Rack PDU: 1. Install the Rack PDU using the Rack Power Distribution Unit Installation Instructions that were shipped with your Rack PDU. 2. Apply power and connect to your network. Follow the directions in the Rack Power Distribution Unit Installation Instructions. 3. Establish network settings 4. Begin using the Rack PDU by way of one of the following: – “Web Interface” on page 81 – “Command Line Interface” on page 18 – “Rack PDU Front Panel” on page 11

6 Rack PDU User Guide Establish Network Settings IPv4 initial setup You must define three TCP/IP settings for the Rack PDU before it can operate on the network: • The IP address of the Rack PDU • The subnet mask of the Rack PDU • The IP address of the default gateway (only needed if you are going off segment) NOTE: Do NOT use the loopback address (127.0.0.1) as the default gateway. Doing so disables the card. To enable again, you must log on using a serial connection and reset the TCP/IP settings to their defaults. For detailed information on how to use a DHCP server to configure the TCP/IP settings at an Rack PDU, see.“DHCP response options” on page 102 IPv6 initial setup IPv6 network configuration provides flexibility to accommodate your requirements. IPv6 can be used anywhere an IP address is entered on this interface. You can configure manually, automatically, or using DHCP. TCP/IP configuration methods Use one of the following methods to define the TCP/IP settings needed by the Rack PDU: • “Device IP Configuration Wizard” on page 130 • “DHCP and BOOTP configuration” • “Command Line Interface” on page 18 .ini file utility You can use the .ini file export utility to export .ini file settings from configured Rack PDUs to one or more unconfigured Rack PDUs. For more information, see “Creating and importing settings with the config file” on page 118. DHCP and BOOTP configuration The default TCP/IP configuration setting, DHCP, assumes that a properly configured DHCP server is available to provide TCP/IP settings to Rack PDU. You can also configure the setting for BOOTP. A user configuration (INI) file can function as a BOOTP or DHCP boot file. For more information, see “Creating and importing settings with the config file” on page 118. If neither of these servers is available, see “Device IP Configuration Wizard” on page 130 or “Device IP Configuration Wizard” on page 130. BOOTP: For the Rack PDU to use a BOOTP server to configure its TCP/IP settings, it must a properly configured RFC951-compliant BOOTP server. In the BOOTPTAB file of the BOOTP server, enter the Rack PDU’s MAC address, IP address, subnet mask, and default gateway, and, optionally, a bootup file name. Look for the MAC address on the bottom of the Rack PDU or on the Quality Assurance slip included in the package. When the Rack PDU reboots, the BOOTP server provides it with the TCP/IP settings. • If you specified a bootup file name, the Rack PDU attempts to transfer that file from the BOOTP server using TFTP or FTP. The Rack PDU assumes all settings specified in the bootup file. • If you did not specify a bootup file name, you can configure the other settings of the Rack PDU remotely through its “Web Interface” on page 81 or “Command Line Interface” on page 18; the user name and password are both apc, by default. To create a bootup file, see your BOOTP server documentation.

Rack PDU User Guide 7 DHCP: You can use an RFC2131/RFC2132-compliant DHCP server to configure the TCP/IP settings for the Rack PDU. This section summarizes the Rack PDU’s communication with a DHCP server. For more detail about how a DHCP server can configure the network settings for a Rack PDU, see “DHCP response options” on page 102. 1. The Rack PDU sends out a DHCP request that uses the following to identify itself: – A Vendor Class Identifier (APC by default) – A Client Identifier (by default, the MAC address of the Rack PDU) – A User Class Identifier (by default, the identification of the application firmware installed on the Rack PDU) – A Host Name (by default, apcXXYYZZ with XXYYZZ being the last six digits of the PDU). This is known as DHCP Option 12. 2. A properly configured DHCP server responds with a DHCP offer that includes all the settings that the Rack PDU needs for network communication. The DHCP offer also includes the Vendor Specific Information option (DHCP option 43). The Rack PDU can be configured to ignore DHCP offers that do not encapsulate the APC cookie in DHCP option 43 using the following hexadecimal format. (The Rack PDU does not require this cookie by default.) Option 43 = 01 04 31 41 50 43 Where: – The first byte (01) is the code. – The second byte (04) is the length. – The remaining bytes (31 41 50 43) are the APC cookie. See your DHCP server documentation to add code to the Vendor Specific Information option. NOTE: By selecting the Require vendor specific cookie to accept DHCP Address check box in the web interface, you can require the DHCP server to provide an “APC” cookie, which supplies information to the Rack PDU: Configuration > Network >TCP/IP > IPv4 Settings. Network Management with Other Applications These applications and utilities work with a Rack PDU which is connected to the network. • PowerNet® Management Information Base (MIB) with a standard MIB browser — Perform SNMP SETs and GETs and use SNMP traps • StruxureWare — Provide enterprise-level power management and management of agents, Rack PDUs, and environmental monitors. • Device IP Configuration Utility — Configure the basic settings of one or more Rack PDU over the network, see “Device IP Configuration Utility” • Security Wizard — Create components needed to help with security for the Rack PDUs when you are using Secure Sockets Layer (SSL) and related protocols and encryption routines Access priority for logging on

8 Rack PDU User Guide Command Line Interface (CLI) 1. Log on to the CLI. See “Log on to the CLI” on page 18. 2. Contact your network administrator to obtain the IP address, subnet mask, and default gateway for the Rack PDU. 3. Use these three commands to configure network settings. (Text in italics indicates a variable.) tcpip -i yourIPaddress tcpip -s yourSubnetMask tcpip -g yourDefaultGateway

For each variable, a numeric value that has the format xxx.xxx.xxx.xxx. For example, to set a system IP address of 156.205.14.141, type the following command and press ENTER: tcpip -i 156.205.14.141 4. Type exit. The Rack PDU restarts to apply the changes.

Rack PDU User Guide 9 Recovering from a Lost Password

You can use a local computer (a computer that connects to the Rack PDU or other device through the serial port) to access the command line interface. 1. Select a serial port at the local computer, and disable any service that uses that port. 2. Connect the serial cable (Schneider Electric part number 940-0144A) to the selected port on the computer and to the Serial port at the Rack PDU. 3. Run a terminal program (such as HyperTerminal®) and configure the selected port for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control. 4. Press ENTER, repeatedly if necessary, to display the User Name prompt. If you are unable to display the User Name prompt, verify the following: – The serial port is not in use by another application. – The terminal settings are correct as specified in step 3. – The correct cable is being used as specified in step 2. 5. Press the Reset button. The Status LED will flash alternately orange and green within 5 to 7 seconds of pressing the Reset button. Press the Reset button a second time immediately when the LED begins flashing to reset the user name and password to their defaults temporarily. 6. Press ENTER, repeatedly if necessary, to display the User Name prompt again, then use the default, apc, for the user name and password. (If you take longer than 30 seconds to log on after the User Name prompt is re-displayed, you must repeat step 5 and log on again.) 7. At the command line interface, use the following commands to change the Password setting, which is apc at this stage: user -n -pw

For example, to change the Super User password to XYZ type: user -n apc - apc -pw XYZ 8. Type quit or exit to log off, reconnect any serial cable you disconnected, and restart any service you disabled.

10 Rack PDU User Guide Rack PDU Front Panel

Te m p/ Hu m idi ty Out USB - OK - Warning Select - Overload SELECT

Scroll 0 0 0 Reset

4.37 kW Main Menu 

MAIN x Network In Serial pdu0711a

NOTE: Your Rack PDU is configured so the display backlight turns off after 10 minutes of inactivity. The backlight can be turned on by depressing any button below the display.

Item Function

 Display Shows information about the Rack PDU. In normal operation, input voltage, current, and power refreshes every five seconds. To reverse the text, select Display settings, scroll to Orientation and press Select. apc eieN Device 37.8%RH 24.5ºC 12345678 SELECT SELECT 0 0 ame 24.5ºC 37.8%RH IN IN Device Name Device apc12345678 MA MA pdu0713a pdu0712a

 Main Menu button Press to view the Rack PDU electrical input. SELECT 0 0 IN 1.23 kW MA pdu0724a  Scroll button Press once to display the menu. Press additional times to highlight the desired menu option. SELECT twork se se Ne IN Pha Outlet Current MA Temp/Humidity pdu0714a

 Select button With a menu option highlighted, press the Select button to display Rack PDU information. (Network information is shown SELECT at right.) IN IPv4 Address 10.234.576.89 MA pdu0715a

Rack PDU User Guide 11 Te m p/ Hu m idi ty Out USB - OK - Warning Select - Overload SELECT

Scroll 0 0 0 Reset

Main 4.37 kW Menu 

MAIN x Network In Serial pdu0740b

Item Function

 Load Indicator LEDs Indicates the status of the Rack PDU load. See “Load indicator LED” on page 13.  Temp/Humidity port Port for connecting an optional Schneider Electric Temperature Sensor (AP9335T) or an optional Schneider Electric Temperature/Humidity Sensor (AP9335TH).  In and Out ports For use with the Network Port Sharing feature.  USB port For use with a flash drive for firmware upgrades - 5V @ 100ma.  RJ-12 Serial Port Port for connecting the Rack PDU to a terminal program for local access to the command line interface. Use the supplied serial cable (Schneider Electric part number 940-0144A).  10/100 Base-T Connector Connects the Rack PDU to the network.  Network status LED See “Network Status LED” on page 13.  10/100 LED See “10/100 LED” on page 13.  Reset button Resets the Rack PDU without affecting the outlet status.

12 Rack PDU User Guide Network Status LED

Condition Description

One of the following situations exists: • The Rack PDU is not receiving input power. Off • The Rack PDU is not operating properly. It may need to be repaired or replaced. Contact Customer Support. Solid Green The Rack PDU has valid TCP/IP settings. A hardware failure has been detected in the Rack PDU. Contact Customer Solid Orange Support. Flashing Green The Rack PDU does not have valid TCP/IP settings. Flashing Orange The Rack PDU is making BOOTP requests. Alternately flashing green If the LED is flashing slowly, the Rack PDU is making DHCP2 requests1. and orange If the LED is flashing rapidly, the Rack PDU is starting up. 1. If you do not use a BOOTP or DHCP server, see “Establish Network Settings” on page 7 to configure the TCP/IP settings of the Rack PDU. 2. To use a DHCP server, see “TCP/IP and Communication Settings” on page 101. 10/100 LED

Condition Description

One or more of the following situations exists: • The Rack PDU is not receiving input power. • The cable that connects the Rack PDU to the network is disconnected or Off defective • The device that connects the Rack PDU to the network is turned off. • The Rack PDU itself is not operating properly. It may need to be repaired or replaced. Contact Customer Support. The Rack PDU is connected to a network operating at 10 Megabits per second Solid green (Mbps). Solid orange The Rack PDU is connected to a network operating at 100 Mbps. Flashing green The Rack PDU is receiving or transmitting data packets at 10 Mbps. Flashing orange The Rack PDU is receiving or transmitting data packets at 100 Mbps. Load indicator LED The load indicator LED identifies near-overload (warning) and overload (critical) conditions for the Rack PDU.

Condition Description

Solid Green OK. No near-overload (warning) or overload (critical) alarms are present. Warning. At least one near-overload (warning) alarm is present, but no Solid Yellow overload (critical) alarms are present. Flashing Red Overload. At least one overload (critical) alarm is present.

Rack PDU User Guide 13 Example 1 Main Display Tree Menu

Phase Info Phase NOTE: The Menu Home Screen is restricted to four lines Info per menu page. If there are more than four available Outlet Current Outlet selections, they will appear on multiple pages. “Temp/ Temp/Humidity Current Humidity” only appears when an AP9335T or AP9335TH Network sensor is attached. Software Info T/H SKU/Serial # Display Settings Network RF Code Control

MAIN SELECT SW Info

SKU/SN

Disp Settings

RF Code pdu0708a

No Outlet Current All Outlets Outlet 1 >1 1.2 A bank Bank 1 Outlets Bank 2 Outlets 10 Press “Down” arrow 1 to cycle through the phase Yes outlets.

MAIN SELECT MAIN SELECT

N o

All Outlets Phase 1 L1 Outlets Outlet 1 1.2 A L2 Outlets Press “Down” arrow L3 Outlets 10 W to cycle through the outlets. MAIN SELECT MAIN SELECT pdu0727a

14 Rack PDU User Guide Example 2

Display Tree

T/H SKU/SN SW Info RF Code

Sensor Model AOS RF Code - Console Temp: 45.6ºC AP8XXX 5.0.0 Enabled Hum: 37.8% Serial Number APP Press “Select” ZAxxxxxxxxxx 5.0.0 WILL REBOOT

MAIN SELECT MAIN SELECT MAIN SELECT MAIN SELECT

Network

IPv4 Address IPv6 Address IPv6 Address MAC Address 255.255.255.255 1234:5678:9012 (scrolls through 00 00 00 3456:7890:1234 each IPv6 addr) 00 00 00 5678:9012

MAIN SELECT MAIN SELECT MAIN SELECT MAIN SELECT

Disp. Settings

LCD Contrast LCD Backlight LCD Orientation Network Port Display ID Sharing Group 5 / 9 Auto-On Normal Hide Yes Press “Select” Press “Select” Press “Select” Press “Select” to adjust to switch to switch to switch

MAIN SELECT MAIN SELECT MAIN SELECT MAIN SELECT No pdu0710a

Rack PDU User Guide 15 Example 3

Monitor Status N 1.23 kW o 0 24.5ºC Yes Yes 2 bank 1 Sensor 37.8%RH Device Name

N 2 8 o apc1234567 MAIN SELECT MAIN SELECT

MAIN 1.23 kW Yes 3 bank 1

2 N o 3 MAIN SELECT

1.23 kW

Yes 4 bank 1 3 Main

2 4 Menu

N o MAIN SELECT

1.23 kW Yes 5 bank 1 4

2 5 N o 3 MAIN SELECT

1.23 kW Yes 6 bank 1 4 2 5 3 6 MAIN SELECT

0 0

1.23 kW

MAIN SELECT pdu0720a

16 Rack PDU User Guide Example 4

Monitor Status Indicators

0 0

1.23 kW

MAIN SELECT

Normal Status Device Load Indicator Reading 1.23 kW 1 4 2 5 Bank Load Graphs 3 6 (No Indicator = Normal Status) MAIN SELECT Warning (Near Overload) Indicator 5.67 kW 7.89 kW 1 4 1 4

2 5 2 5 Critical 3 6 3 6 (Overload) MAIN SELECT MAIN SELECT Indicator

Normal Status 0 Indicator 24.5ºC 37.8%RH Device Name apc12345678 MAIN SELECT Critical Sensor Status

Warning High Temp Critical Low Humidity Threshold Threshold 59.0ºC 24.5ºC Violation Violation Indicator 30.0%RH Indicator 10.0%RH Device Name Device Name apc12345678 apc12345678 MAIN SELECT MAIN SELECT pdu0721a

Rack PDU User Guide 17 Command Line Interface

About the Command Line Interface (CLI)

You can use the command line interface to view the status of and configure and manage the Rack PDU (and any connected Rack PDUs, if using the Network Port Sharing Feature). In addition, the command line interface enables you to create scripts for automated operation. You can configure all parameters of a Rack PDU (including those for which there are not specific CLI commands) by using the CLI to transfer an INI file to the Rack PDU. The CLI uses XMODEM to perform the transfer, however, you cannot read the current INI file through XMODEM. Log on to the CLI

To access the command line interface, you can use either a local (serial) connection or a remote (Telnet or SSH) connection with a computer on the same network as the Rack PDU. Remote access to the command line interface You can choose to access the command line interface through Telnet and/or SSH. Telnet is enabled by default. You do not have to enable either. To enable or disable these access methods, use the web interface. On the Configuration tab, select Network from the menu to open the Console Access page. Click to check the desired Enable box. Click Apply to save your changes or Cancel to leave the page.

18 Rack PDU User Guide Telnet for basic access Telnet provides the basic security of authentication by user name and password, but not the high-security benefits of encryption. To use Telnet to access the command line interface: 1. From a computer that has access to the network on which the Rack PDU is installed, at a command prompt, type telnet and the IP address for the Rack PDU (for example, telnet 139.225.6.133, when the Rack PDU uses the default Telnet port of 23), and press ENTER.

If the Rack PDU uses a non-default port number (from 5000 to 32768), you must include a colon or a space, depending on your Telnet client, between the IP address (or DNS name) and the port number. (These are commands for general usage: Some clients do not allow you to specify the port as an argument and some types of might want extra commands). 2. Enter the user name and password (by default, apc and apc for the Super User). If you cannot remember your user name or password, see “Recovering from a Lost Password” on page 10.

SSH for high-security access If you use the high security of SSL for the Web interface, use SSH for access to the command line interface. SSH encrypts user names, passwords, and transmitted data. The interface, user accounts, and user access rights are the same whether you access the command line interface through SSH or Telnet, but to use SSH, you must first configure SSH and have an SSH client program installed on your computer. Local access to the command line interface For local access, use a computer that connects to the Rack PDU through the serial port to access the command line interface: 1. Select a serial port at the computer and disable any service that uses that port. 2. Connect the serial cable (Schneider Electric part number 940-0144A) from the selected serial port on the computer to the Serial port on the Rack PDU. 3. Run a terminal program (e.g., HyperTerminal) and configure the selected port for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control. 4. Press ENTER. At the prompts, enter your user name and password.

Rack PDU User Guide 19 About the Main Screen

Following is an example of the main screen, which is displayed when you log on to the command line interface of a Rack PDU.

APC by Schneider Electric Network Management Card AOS vx.x.x () Copyright 2016 All Rights Reserved RPDU 2g vx.x.x ------Name : Test Lab Date : 6/30/2016 Contact : Don Adams Time : 5:58:30 Location : Building 3 User : Administrator Up Time : 0 Days, 21 Hours, 21 Minutes Stat : P+ N4+ N6+ A+

Type ? For command listing Use tcpip for IP address (-i), subnet (-s), and gateway (-g) APC>

• Two fields identify the (AOS) and application (APP) firmware versions. The application firmware name identifies the type of device that connects to the network. In the example above, the application firmware for the Rack PDU is displayed. Network Management Card AOS vx.x.x RPDU 2g vx.x.x • Three fields identify the system name, contact person, and location of the Rack PDU. Name : Test Lab Contact : Don Adams Location : Building 3 • An Up Time field reports how long the Rack PDU Management Interface has been running since it was last turned on or reset. Up Time: 0 Days, 21 Hours, 21 Minutes • Two fields identify when you logged in, by date and time. Date: 06/30/2016 Time: 5:58:30 • The User field identifies whether you logged in through the Super User, Administrator or account. User: Administrator • A Stat field reports the Rack PDU status. Stat:P+ N4+ N6+ A+

P+ The APC operating system (AOS) is functioning properly.

IPv4 IPv6 IPv4 and Description only only IPv6* N+ N+ N4+ N6+ The network is functioning properly. N? N6? N4? N6? A BOOTP request cycle is in progress. N– N6- N4- N6- The Rack PDU failed to connect to the network. N! N6! N4! N6! Another device is using the Rack PDU IP address.

20 Rack PDU User Guide * The N4 and N6 values can be different from one another: you could, for example, have N4- N6+.

A+ The application is functioning properly. A– The application has a bad checksum. A? The application is initializing. A! The application is not compatible with the AOS.

NOTE: If P+ is not displayed, contact the Schneider Electric Customer Care Center. Using the CLI

At the command line interface, you can use commands to configure the Rack PDU. To use a command, type the command and press ENTER. Commands and arguments are valid in lowercase, uppercase, or mixed case. Options are case-sensitive. While using the command line interface, you can also do the following: • Type ? and press ENTER to view a list of available commands, based on your account type. • To obtain information about the purpose and syntax of a specified command, type the command, a space, and ? or the word help. For example, to view RADIUS configuration options, type: radius ? or radius help • Press the UP arrow key to view the command that was entered most recently in the session. Use the UP and DOWN arrow keys to scroll through a list of up to ten previous commands. • Type at least one letter of a command and press the TAB key to scroll through a list of valid commands that match the text you typed in the command line. • Type exit or quit to close the connection to the command line interface.

Rack PDU User Guide 21 Command Syntax

Item Description

- Options are preceded by a hyphen. Definitions of options are enclosed in angle brackets. For example: < > -dp If a command accepts multiple options or an option accepts mutually [ ] exclusive arguments, the values may be enclosed in brackets. A vertical line between items enclosed in brackets or angle brackets | indicates that the items are mutually exclusive. You must use one of the items.

Example of a command that supports multiple options: ftp [-p ] [-S ] In this example, the ftp command accepts the option -p, which defines the port number, and the option -S, which enables or disables the FTP feature. To change the FTP port number to 5010, and enable FTP: 1. Type the ftp command, the port option, and the argument 5010: ftp -p 5010 2. After the first command succeeds, type the ftp command, the enable/disable option, and the enable selection: ftp -S enable

Example of a command that accepts mutually exclusive arguments for an option: alarmcount -p [all | warning | critical] In this example, the option -p accepts only three arguments: all, warning, or critical. For example, to view the number of active critical alarms, type: alarmcount -p critical The command will fail if you type an argument that is not specified.

22 Rack PDU User Guide Command Response Codes

The command response codes enable scripted operations to detect error conditions reliably without having to match error message text: The CLI reports all command operations with the following format: E [0-9] [0-9] [0-9] : Error message Code Message Code Message E000 Success E200 Input Error E001 Successfully Issued E201 No Response E002 Reboot required for change to take effect E202 User already exists E100 Command failed E203 User does not exist User does not have access to this E101 Command not found E204 command E102 Parameter Error E205 Exceeds Maximum Users E103 Command Line Error E206 Invalid value Outlet Command Error: Device not E104 User Level Denial E207 initialized. Outlet Command Error: Previous command E105 Command Prefill E208 is pending. Outlet Command Error: Database rejected E106 Data Not Available E209 request. Serial communication with the Rack PDU E107 E210 Outlet Command Error: Outlet restricted. has been lost

Rack PDU User Guide 23 Network Management Card Command Descriptions ? or help Access: Super User, Administrator, Device User, Outlet User, Read Only Description: View a list of all the CLI commands available to your account type. To view help text for a specific command, type the command followed by a question mark. Parameters: [] Example 1: apc> ? Network Management Card Commands: ------? about alarmcount boot cd date delete dir eventlog exit format ftp help ping portspeed prompt quit radius reboot resetToDef system tcpip user web xferINI xferStatus

Example 2: apc> help boot Usage: boot -- Configuration Options boot [-b ] (Boot Mode) [-a ] (After IP Assignment) [-o ] (On Retry Fail) [-c ] (Require DHCP Cookie) [-s ] (Note: 0 = never) [-f ] (Note: 0 = never) [-v ] [-i ] [-u ] Error Message: E000, E102

24 Rack PDU User Guide about Access: Super User, Administrator, Device User, Outlet User, Read Only Description: Displays system information (Model Number, Serial Number, Manufacture Dates, etc.) Parameters: None Example: apc> about E000: Success Hardware Factory ------Model Number: AP8XXX Serial Number: ST0913012345 Hardware Revision: HW05 Manufacture Date: 3/4/2016 MAC Address: 00 05 A2 18 00 01 Management : 0 Days 1 Hour 42 Minutes Error Message: E000

alarmcount Access: Super User, Administrator, Device User, Outlet User, Read Only Description: Displays alarms present in the system. Parameters: Option Argument Description View the number of active alarms reported by the Rack PDU. all Information about the alarms is provided in the event log. -p warning View the number of active warning alarms. critical View the number of active critical alarms.

Example: To view all active warning alarms, type: apc> alarmcount E000: Success AlarmCount: 0 Error Message: E000, E102

Rack PDU User Guide 25 boot Access: Super User, Administrator Description: Allows the user to get/set the network startup configuration of the device, such as setting boot mode (DHCP vs BOOTP vs MANUAL). Parameters: Option Argument Description Define how the TCP/IP settings will be configured when -b the Rack PDU turns on, resets, or restarts. See “TCP/IP about each boot mode setting. dhcp and dhcpBootp boot modes only. Enable or disable [] -c the requirement that the DHCP server provide the APC (Require DHCP Cookie) cookie. -v [] Vendor Class is APC The MAC address of the Rack PDU’s NMC, Which -i [] uniquely identifies it on the network. -u [] The name of the application firmware module.

Example: Using a DHCP server to obtain network settings: apc> boot E000: Success Boot Mode: manual Non-Manual Mode Shared Settings ------Vendor class: Client id: XX XX XX XX XX XX User class: After IP assignment: gotoDhcpOrBootp

DHCP Settings ------Retry then stop: 4 DHCP cookie is: enable

BOOTP Settings ------Retry then fail: never On retry failure: prevSettings Error Message: E000, E102

26 Rack PDU User Guide cd Access:Super User, Administrator, Device User, Outlet User, Read Only Description:Allows the user to set the working of the . The is set back to the ‘/’ when the user logs out of the CLI. Parameters: Example: apc> cd logs E000: Success

apc> cd / E000: Success Error Message: E000, E102

clrrst Access: Super User, Administrator Description: Clear reset reason. Example: None Error Message: None

Rack PDU User Guide 27 console Access: Super User, Administrator Description: Define whether users can access the command line interface using Telnet, which is enabled by default, or Secure (SSH), which provides protection by transmitting user names, passwords, and data in encrypted form. You can change the Telnet or SSH port setting for additional security. Alternately, disable network access to the command line interface. Parameters: Option Argument Description Configure access to the command line interface, or use -S disable | telnet | ssh the disable command to prevent access. Enabling SSH enables SCP and disables Telnet. ] -t (telnet) Define the Telnet port used to communicate with the -pt Rack PDU (23 by default). Define the SSH port used to communicate with the Rack - PDU (22 by default). 2400 | 9600 | 19200 | Configure the speed of the serial port connection (9600 -b 38400 bps by default).

Example 1: To enable SSH access to the command line interface, type: console -S ssh Example 2: To change the Telnet port to 5000, type:

apc> console E000: Success Telnet: enabled SSH: disabled Telnet Port: 23 SSH Port: 22 Baud Rate: 9600

Error Message: E000, E102

28 Rack PDU User Guide date Access: Super User, Administrator Definition: Get and set the date and time of the system. To configure an NTP server to define the date and time for the Rack PDU, see “Date/Time screen” on page 117. Parameters: Option Argument Description -d <“datestring”> Set the current date. The format must match the current -f setting. Configure the current time, in hours, minutes, and seconds. Use the -t <00:00:00> 24-hour clock format. mm//yy | Select the numerical format in which to display all dates in this user dd.mm.yyyy | interface. Each letter m (for month), d (for day), and y (for year) -f mmm-dd-yy | represents one digit. Single-digit days and months are displayed with a dd-mmm-yy | leading zero. yyyy-mm-dd

Example 1: To display the date using the format yyyy-mm-dd, type: date -f yyyy-mm-dd Example 2: To define the date as October 30, 2015, using the format configured in the preceding example, type: date -d “2015-10-30” Example 3: To define the time as 5:21:03 p.m., type: date -t 17:21:03 Error Message: E000, E100, E102

delete Access: Super User, Administrator Description: Delete a file in the file system. Parameters: Argument Description Type the name of the file to delete.

Example: apc> delete /db/prefs.dat E000: Success

Error Messages: E000, E102

Rack PDU User Guide 29 dir Access: Super User, Administrator, Device User, Outlet User, Read Only Description: Displays the content of the working directory. Parameters: None Example: apc> dir E000: Success --wx-wx-wx 1 apc apc 3145728 Mar 3 2015 aos.bin --wx-wx-wx 1 apc apc 3145728 Mar 4 2015 app.bin -rw-rw-rw- 1 apc apc 45000 Mar 6 2015 config.ini drwxrwxrwx 1 apc apc 0 Mar 3 2015 db/ drwxrwxrwx 1 apc apc 0 Mar 3 2015 ssl/ drwxrwxrwx 1 apc apc 0 Mar 3 2015 ssh/ drwxrwxrwx 1 apc apc 0 Mar 3 2015 logs/ drwxrwxrwx 1 apc apc 0 Mar 3 2015 sec/ drwxrwxrwx 1 apc apc 0 Mar 3 2015 dbg/ drwxrwxrwx 1 apc apc 0 Mar 3 2015 pdu/ Error Messages: E000

30 Rack PDU User Guide dns Access: Super User, Administrator Definition: Configure the manual Domain Name System (DNS) settings. Parameters: Parameter Argument Description enable | -OM Override the manual DNS. disable -d Set the domain name. -h Set the host name.

Example: apc> dns E000: Success Active Primary DNS Server: x.x.x.x Active Secondary DNS Server: x.x.x.x

Override Manual DNS Settings: enabled Primary DNS Server: x.x.x.x Secondary DNS Server: x.x.x.x Domain Name: example.com Domain Name IPv6: example.com System Name Sync: Enabled Host Name: ExampleHostName

Error Message: E000, E102

Rack PDU User Guide 31 email Access: Super User, Administrator Description: View email Parameters: Parameters Argument -g[n] (Generation) -t[n] -o[n] (Format) -l[n] -r [n] () Custom Route Option -f[n] -s{n} -p[n] -a[n] (Authentication) -u[n] -w[n] (Encryption) (Required -c[n] Certificate) -i[n] n= Email Recipient Number 1,2,3 or 4)

Example: apc>email E000: Success

Recipient: 1 Generation: enabled Address: [email protected] Format: long Language: enUs - English Route: local

Error Message: E000, E102

32 Rack PDU User Guide eventlog Access: Super User, Administrator, Device User, Outlet User, Read Only Description: View the date and time you retrieved the event log, the status of the Rack PDU, and the status of sensors connected to the Rack PDU. View the most recent device events and the date and time they occurred. Use the following keys to navigate the event log: Parameters: Key Description

ESC Close the event log and return to the command line interface. Update the log display. Use this command to view events that were recorded after you ENTER last retrieved and displayed the log. SPACEBAR View the next page of the event log. View the preceding page of the event log. This command is not available at the main B page of the event log. Delete the event log. Follow the prompts to confirm or deny the deletion. Deleted D events cannot be retrieved.

Example: apc> eventlog ---- Event Log ------Date: 03/06/2016 Time: 13:22:26 ------Metered Rack PDU: Communication Established Date Time Event ------03/06/2016 13:17:22 System: Set Time. 03/06/2016 13:16:57 System: Configuration change. Date format preference. 03/06/2016 13:16:49 System: Set Date. 03/06/2016 13:16:35 System: Configuration change. Date format preference. 03/06/2016 13:16:08 System: Set Date. 03/05/2016 13:15:30 System: Set Time. 03/05/2016 13:15:00 System: Set Time. 03/05/2016 13:13:58 System: Set Date. 03/05/2016 13:12:22 System: Set Date. 03/05/2016 13:12:08 System: Set Date. 03/05/2016 13:11:41 System: Set Date. - Exit, - Refresh, - Next, - Delete Error Message: E000, E100

Rack PDU User Guide 33 exit, quit, or bye Access: Super User, Administrator, Device User, Outlet User, Read Only Description: Exit from the CLI session. The exit, quit, and bye commands all close the CLI session. Parameters: None Example: apc> exit Bye Error Message: None firewall Access: Super User, Administrator Description: Establishes a barrier between a trusted, secure internal network and another network. Parameters: Parameters Argument Description -S Enable or disable the Firewall. Name of the firewall to -f activate. Name of firewall to test and -t duration time in minutes. -fe No argument. List only Shows active file errors. -te No argument. List only Shows test file errors. -c No argument. List only Cancel a firewall test. -r No argument. List only Shows active firewall rules. -l No argument. List only Shows firewall activity log.

Error Message: E000, E102 format Access: Super User, Administrator Description: Allows the user to format the FLASH file system. This will delete all configuration data, event and data logs, certificates and keys. NOTE: The user must confirm by entering “YES” when prompted. Parameters: None Example: apc> format

Format FLASH file system

Warning: This will delete all configuration data, event and data logs, certs and keys.

Enter 'YES' to continue or to cancel: apc> Error Message: None

34 Rack PDU User Guide ftp Access: Super User, Administrator Description: Get/set the ftp configuration data, NOTE: The system will reboot if any configuration is changed. Parameters: Option Argument Definition Define the TCP/IP port that the FTP server uses to communicate with the Rack PDU (21 by default). The FTP -p (valid ranges are: server uses both the specified port and the port one number 21 and 5000-32768) lower than the specified port. -S enable | disable Configure access to the FTP server.

Example:To change the TCP/IP port to 5001, type: apc> ftp -p 5001 E000: Success

apc> ftp E000: Success Service: Enabled Ftp Port: 5001

apc> ftp -p 21 E000: Success Error Message: E000, E102 lang Access: Super User, Administrator, Device User, Outlet User Description: Displays the language in use Parameters: None Example: apc>lang E000: Success

Languages enUs - English

Error Message: None

Rack PDU User Guide 35 lastrst Access: Super User, Administrator Description: Last reset reason Parameters: None Example: apc> lastrst 00 Reset Cleared E000: Success

Error Message: E000, E102 ledblink Access: Super User, Administrator Description: Sets the blink rate to the LED on the Rack Power Distribution Unit. Parameters:

Error Message: E000, E102

36 Rack PDU User Guide netstat Access: Super User, Administrator Description: Displays incoming and outgoing network connections. Parameters: None Example: apc> netstat

Current IP Information:

Family mHome Type IPAddress Status IPv6 4 auto FE80::2C0:B7FF:FE51:F304/64 configured IPv6 0 manual ::1/128 configured IPv4 0 manual 127.0.0.1/32 configured

Error Message: E000, E102 ntp Access: Super User, Administrator Description: Synchronizes the time of a computer client or server. Parameters: Option Argument Definition -OM enable | disable Override the manual settings. -p Specify the primary server. -s Specify the secondary server.

Example 1: To enable the override of manual setting, type: ntp -OM enable

Example 2: To specify the primary NTP server, type: ntp -p 150.250.6.10

Error Message: E000, E102

Rack PDU User Guide 37 ping Access: Super User, Administrator, Device User Description: Perform a network ‘ping’ to any external network device. Parameters: Argument Description Type an IP address with the format xxx.xxx.xxx.xxx, or the DNS name configured by the DNS server.

Example: apc> ping 192.168.1.50 E000: Success Reply from 192.168.1.50: time(ms)= <10 Reply from 192.168.1.50: time(ms)= <10 Reply from 192.168.1.50: time(ms)= <10 Reply from 192.168.1.50: time(ms)= <10 Error Message: E000, E100, E102 portSpeed Access: Super User, Administrator Description: Allows the user to get/set the network port speed. NOTE: The system will reboot if any configuration is changed. Parameters: Option Arguments Description Define the communication speed of the Ethernet port. The auto auto | 10H | command enables the Ethernet devices to negotiate to transmit at -s 10F | 100H | the highest possible speed. See “Port Speed” on page 103 for more 100 F information about the port speed settings. H = Half Duplex 10 = 10 Meg Bits F = Full Duplex 100 = 100 Meg Bits Example: apc> portspeed E000: Success Port Speed: 10 Half_Duplex

apc> portspeed -s 10h E000: Success

apc> portspeed E000: Success Port Speed: 10 Half_Duplex

apc> portspeed -s auto E000: Success

Error Message: E000, E102

38 Rack PDU User Guide prompt Access: Super User, Administrator, Device User Description: Allows the user to change the format of the prompt, either short or long. Parameters: Option Argument Description long The prompt includes the account type of the currently logged-in user. -s short The default setting. The prompt is four characters long: APC> Example: apc> prompt –s long E000: Success

Administrator@apc>prompt –s short E000: Success

Error Message: E000, E102 pwd Access: Super User, Administrator, Device User, Read Only Description: Used to output the of the current working directory. Parameters: None Example: apc> pwd /

apc> cd logs E000: Success

apc> pwd /logs

Error Message: E000, E102

Rack PDU User Guide 39 radius Access:Super User, Administrator Description:View the existing RADIUS settings, enable or disable RADIUS authentication, and configure basic authentication parameters for up to two RADIUS servers. For a summary of RADIUS server configuration and a list of supported RADIUS servers, see “Configure the RADIUS Server” on page 99. Additional authentication parameters for RADIUS servers are available at the Web interface of the Rack PDU. See “RADIUS” on page 98 for more information. For detailed information about configuring your RADIUS server, see the Security Handbook, available at www.apc.com. Parameters: Option Argument Description Configure RADIUS authentication: local—RADIUS is disabled. Local authentication is enabled. local | radiusLocal—RADIUS, then Local Authentication. RADIUS and -a radiusLocal local authentication are enabled. Authentication is requested from the | radius RADIUS server first. If the RADIUS server fails to respond, local authentication is used. radius—RADIUS is enabled. Local authentication is disabled. The server name or IP address of the primary or secondary RADIUS server. -p1 NOTE: RADIUS servers use port 1812 by default to authenticate -p2 users. To use a different port, add a colon followed by the new port number to the end of the RADIUS server name or IP address. The Rack PDU supports ports 1812, 5000 to 32768. -s1 and the Rack PDU . -t1

Example 1: To view the existing RADIUS settings for the Rack PDU, type radius and press ENTER.

Example 2: To enable RADIUS and local authentication, type:

apc> radius -a radiusLocal E000: Success Example 3: To configure a 10-second timeout for a secondary RADIUS server, type:

apc> radius -t2 10 E000: Success Error Message: E000, E102

40 Rack PDU User Guide reboot Access: Super User, Administrator Description: Restart the NMC interface of the Rack PDU only. Forces the network device to reboot. User must confirm this operation by entering a “YES” after the command has been entered. Parameters: None Example: apc> reboot E000: Success Reboot Management Interface Enter 'YES' to continue or to cancel : Rebooting...

Error Message: E000, E100

resetToDef Access: Super User, Administrator Description: Reset all parameters to their default. Parameters: Option Arguments Description all = all configuration data, including the IP address. keepip = all configuration data, except the IP address. -p all | keepip Reset all configuration changes, including event actions, device settings, and, optionally, TCP/IP configuration settings.

Example: To reset all of the configuration changes except the TCP/IP settings for the Rack PDU, type: resetToDef -p keepip Enter 'YES' to continue or to cancel : : all User Names, Passwords. Please ...

Please reboot system for changes to take effect!

Error Message: E000, E100

Rack PDU User Guide 41 session Access: Super User, Administrator Description: Records is logged in, the serial, time and ID. Parameters: Option Arguments -d [-d ] (Delete) -M (Multi-User Enable) -a session User Interface Address Logged In Time ID ------apc Web x.x.x.x 00:00:08 156 apc Telnet x.x.x.x 00:00:02 157 E000: Success

Error Message: E000, E102 smtp Access: Super User, Administrator Description: Internet standard for electronic mail. Parameters: Option Argument -f -p 1 -a (Authentication) -u -w -e (Encryption) -c (Require Certificate) -i 1Port options are 25, 465, 587, 5000 to 32768 Example: apc> smtp E000: Success From: [email protected] Server: mail.example.com Port: 25 Auth: disabled User: User Password: Encryption: none Req. Cert: disabled Cert File: Error Message: E000, E102

42 Rack PDU User Guide snmp Access: Super User, Administrator Description: Enable or disable SNMP 1 or SNMP 3. Parameters: Option Arguments Description -c Identify the group of Rack PDUs -a Set the access level -n The host’s name or address Enable or disable the respective version -S of SNMP, 1 or 3 Example: To enable SNMP version 1, type: apc> snmp E000: Success SNMPv1: enabled

Access Control summary: Access Control #: 1 Community: public Access Type: read Address: 0.0.0.0

Access Control #: 2 Community: private Access Type: write + Address: 0.0.0.0

Access Control #: 3 Community: public2 Access Type: disabled Address: 0.0.0.0

Access Control #: 4 Community: private2 Access Type: disabled Address: 0.0.0.0

Error Message: E000, E102

Rack PDU User Guide 43 snmpv3 Access: Super User, Administrator Description: Enable or disable SNMP 3. Parameters: Option Arguments Description Enable or disable the respective version -S enable | disable of SNMP -u [n] User Name User Name -c [n] Identify the group of Rack PDUs -a [n] Set the access level -n [n] The host’s name or address -ap [n] (Authentication Protocol)] -pp [n] (Privacy Protocol)] -ac [n] (Access) -au [n] ] [n] = Access Control # = 1,2,3, or 4)

Example: apc> snmpv3 E000: Success SNMPv3 Configuration SNMPV3: disabled

SNMPv3 User Profiles

Index: 1 User Name: apc snmp profile1 Authentication: None Encryption: None

Index: 2 User Name: apc snmp profile2 Authentication: None Encryption: None

Index: 3 User Name: apc snmp profile3 Authentication: None Encryption: None

Index: 4 User Name: apc snmp profile4 Authentication: None

Encryption: None

44 Rack PDU User Guide SNMPv3 Access Control

Index: 1 User Name: apc snmp profile1 Access: disabled NMS IP/Host Name: 0.0.0.0

Index: 2 User Name: apc snmp profile2 Access: disabled NMS IP/Host Name: 0.0.0.0

Index: 3 User Name: apc snmp profile3 Access: disabled NMS IP/Host Name: 0.0.0.0

Index: 4 User Name: apc snmp profile4 Access: disabled NMS IP/Host Name: 0.0.0.0

Error Message: E000, E102

Rack PDU User Guide 45 snmptrap Access: Super User, Administrator Description: Enable or disable SNMP trap generation Parameters: Option Arguments -c{n} -r[n] -l[n] [language code] -t[n] [snmpV1 | snmpV3]] -g[n] [enable | disable] -a[n] [enable | disable] -u[n] (User Name) n=Trap reciever # = 1,2,3,4,5 or 6

Example: apc> snmptrap E000: Success

SNMP Trap Configuration

Index: 1 Receiver IP: x.x.x.x Community: public Trap Type: SNMPV1 Generation: disabled Auth Traps: enabled User Name: apc snmp profile1 Language: enUs - English

Error Message: E000, E102

46 Rack PDU User Guide system Access: Super User, Administrator Description: View and set the system name, the contact, the location and view up time as well as the date and time, the logged-on user, and the high-level system status P, N, A (see “About the Main Screen” on page 20 for more information about system status). Parameters: Option Argument Description -n Define the device name, the name of the person responsible for -c the device, and the physical location of the device. NOTE: If you define a value with more than one word, you must enclose the value in quotation marks. -l These values are also used by StruxureWare and the Rack PDU’s SNMP agent. When defined, a custom message will appear on the log on -m screen for all users. Allow the host name to be synchronized with the system name ] so both fields automatically contain the same value. -s (system-hostname NOTE: When enabling this feature, the system name identifier sync) can no longer contain a space character (since it will be synchronized to the host name field).

Example 1: To set the device location as Test Lab, type: apc> system -l “Test Lab” E000: Success Example 2: To view the device name, type: apc> system -n E000: Success Name: : Rack 2 in Room #222 Error Message: E000, E102

Rack PDU User Guide 47 tcpip Access: Super User, Administrator Description: View and manually configure these network settings for the Rack PDU: Parameters: Option Argument Description Type the IP address of the Rack PDU, using the format -i xxx.xxx.xxx.xxx -s Type the subnet mask for the Rack PDU. Type the IP address of the default gateway. Do not use the -g loopback address (127.0.0.1) as the default gateway. -d Type the DNS name configured by the DNS server. -h Type the host name that the Rack PDU will use. -S enable | disable Enable or disable IPv4.

Example 1: To view the network settings of the Rack PDU, type tcpip and press ENTER. apc> tcpip E000: Success IP Address: 192.168.1.50 MAC Address: XX XX XX XX XX XX Subnet Mask: 255.255.255.0 Gateway: 192.168.1.1 Domain Name: example.com Host Name: HostName

Example 2: To view the IP address of the Rack PDU, type: apc> tcpip -i E000: Success IP Address: 192.168.1.50

Example 3: To manually configure an IP address of 192.168.1.49 for the Rack PDU, type: apc> tcpip -i 192.168.1.49 E000: Success Reboot required for change to take effect

Error Message: E000, E102

48 Rack PDU User Guide tcpip6 Access: Super User, Administrator Description: Enable IPv6 and view and manually configure these network settings for the Rack PDU: Parameters: Option Argument Description -S enable | disable Enable or disable IPv6. Enable manual addressing for the IPv6 address of the Rack -man enable | disable PDU. Enable the Rack PDU to automatically configure the IPv6 -auto enable | disable address. -i Set the IPv6 address of the Rack PDU. -g Set the IPv6 address of the default gateway. Set the DHCPv6 mode, with parameters of router controlled, router | statefull statefull (for address and other information, they maintain their -d6 | statelss | never status), stateless (for information other than address, the status is not maintained), never.

Example: To view the network settings of the Rack PDU, type tcpip6 and press ENTER. apc> tcpip6 E000: Success

IPv6: enabled Manual Settings: disabled

IPv6 Address: ::/64 MAC Address: XX XX XX XX XX XX Gateway: :: IPv6 Manual Address: disabled IPv6 Autoconfiguration: enabled DHCPv6 Mode: router controlled

Error Message: E000, E102

Rack PDU User Guide 49 user Access: Super User, Administrator Description: Configure the user name, password, and inactivity timeout for each account type. You can’t edit a user name, you must delete it and then create a new user. For information on the permissions granted to each account type, see “Types of User Accounts” on page 2. Parameters: Option Argument Description -n -pw Specify these options for a user. -pe -d -e enable | disable Enable overall access. Specify how long a session lasts waits before logging off a -st user when the keyboard is idle. Bypass RADIUS by using the serial console (CLI) -sr enable | disable connection, also known as Serial Remote Authentication Override -el enable | disable Indicate the Event Log color coding. -lf tab | csv Indicate the format for exporting a log file. -ts us | metric Indicate the temperature scale, Fahrenheit or Celsius. - - Delete a user. -l Display the current user list.

Example: apc> user -n apc E000: Success Access: Enabled User Name: apc Password: User Permission: Super User User Description: User Description Session Timeout: 3 minutes Serial Remote Authentication Override: Disabled Event Log Color Coding: Enabled Export Log Format: Tab Temperature Scale: Metric Date Format: mm/dd/yyyy Language: English (enUs) Outlets: All Error Message: E000, E102

50 Rack PDU User Guide userdflt Access: Super User, Administrator Description: Complimentary function to “user” establishing default user preferences. There are two main features for the default user settings: Determine the default values to populate in each of the fields when the Super User or Administrator-level account creates a new user. These values can be changed before the settings are applied to the system. For remote users (user accounts not stored in the system that are remotely authenticated such as RADIUS) these are the values used for those that are not provided by the authenticating server. For example, if a RADIUS server does not provide the user with a temperature preference, the value defined in this section will be used. Parameters: Options Argument Description By default, user will be enabled or disabled upon creation. -e (Enable) Remove (Enable) from the end Specify the user's permission level and account type. (user permission) -d Provide a user description. -st minute(s) Provide a default session timeout. Number of incorrect login attempts a user has before the system disables their account. Upon reaching this limit, a message is displayed informing the user the account has been locked. The Super User or an Administrator-level -bl account is needed to re-enable the account to allow the user to log back in. NOTE: A Super User account cannot be locked out, but can be manually disabled if necessary. -el Enable or disable event log color coding. (Event Log Color Coding) -lf Specify the log export format, tab or CSV. (Export Log Format) Specify the user's temperature scale. This setting is also -ts used by the system when a user preference is not (Temperature Scale) available (for example, email notifications). (Date Format) -lg User language -sp Strong password -pp Required password change interval

Rack PDU User Guide 51 Example: apc> userdflt E000: Success Access: Disabled User Permission: Administrator User Description: User Description Session Timeout: 3 minutes Bad Login Attempts: 0 Event Log Color Coding: Enabled Export Log Format: Tab Temperature Scale: Metric Date Format: mm/dd/yyyy Language: English (enUs) Strong Passwords: Disabled Require Password Change: 0 day(s) (Disabled) Error Message: E000, E102

52 Rack PDU User Guide web Access: Super User, Administrator Description: Enable access to the Web interface using HTTP or HTTPS. For additional security, you can change the port setting for HTTP and HTTPS to any unused port from 5000 to 32768. Users must then use a colon (:) in the address field of the browser to specify the port number. For example, for a port number of 5000 and an IP address of 152.214.12.114, type: http://152.214.12.114:5000 Parameters: Option Argument Definition -h enable | disable Enable or disable access to the user interface for HTTP. Enable or disable access to the user interface for HTTPS. -s enable | disable When HTTPS is enabled, data is encrypted during transmission and authenticated by digital certificate. Specify the TCP/IP port used by HTTP to communicate -ph with the Rack PDU (80 by default). The other available range is 5000–32768. Specify the TCP/IP port used by HTTPS to communicate -ps with the Rack PDU (443 by default). The other available range is 5000–32768. -mp Choices are: SSL3.0 | TLS1.0 | TLS1.1 | TLS1.2 Example 1: To prevent all access to the web interface, type: apc> web -h disable -s disable

Example 2: To define the TCP/IP port used by HTTP, type: apc> web E000: Success HttP: enabled Https: disabled Http Port: 80 Https Port: 443 Minimum Protocol: TLS1.1

apc> web -ph 80 E000: Success Error Message: E000, E102

whoami Access: Super User, Administrator, Device Only, Read Only Description: Provides login information on the current user. Parameters: None Example: apc> whoami E000: Success admin Error Message: E000, E102

Rack PDU User Guide 53 xferINI Access: Super User, Administrator Description: Use XMODEM to upload an INI file while you are accessing the command line interface through a serial connection. After the upload completes: • If there are any system or network changes, the command line interface restarts and you must log on again. • If you selected a baud rate for the file transfer that is not the same as the default baud rate for the Rack PDU, you must reset the baud rate to the default to reestablish communication with the Rack PDU. Parameters: None Example: apc> xferINI Enter 'YES' to continue or to cancel : ------File Transfer Baud Rate------1- 2400 2- 9600 3- 19200 4- 38400 > Transferring at current baud rate (9600), press ... > Start XMODEM-CRC Transfer Now! CC 150 bytes have successfully been transmitted.

apc> Error Message: None xferStatus Access: Super User, Administrator Description: View the result of the last file transfer. See “Verifying Upgrades and Updates” on page 140 for descriptions of the transfer result codes. Parameters: None Example: apc> xferStatus E000: Success Result of last file transfer: Failure unknown Error Message: E000

54 Rack PDU User Guide Device Command Descriptions Network Port Sharing Commands The CLI allows commands to be sent to guest Rack PDUs. The user may specify the Display ID of the Rack PDU to be commanded, followed by a colon, before the first argument (or as the first argument, if the command does not normally have arguments). Providing a Display ID is optional, omitting it will simply command the local Rack PDU. For example: [id:]

This will send to the Rack PDU with the Display ID [id:]. [id:] is delimited from with a colon character; do not include any spaces between [id:] , as spaces are used to delimit arguments.

alarmList Access: Super User, Administrator, Device User Description: Displays alarms present on the device (or another device in the group if Network Port Sharing is used.) Parameters: None. Example: To view all active warning alarms, type: apc> alarmList -----Device Alarm Status------1 Critical Alarm Present. ------[Critical] rack PDU 1: Internal power supply #2 fault, under voltage. - Exit, - Refresh Error Message: E102

bkLowLoad Access: Super User, Administrator, Device User Description: Set or view the bank low-load threshold current in amps. You can specify all banks, a single bank, a range, or a comma-separated list of single banks and/or ranges. Parameters: [id#:] [current] bank# = A single number or a range of numbers separated with a dash or a comma; separated list of single bank number and/or number ranges. current = The new bank threshold (Amps) Example 1: To set the low-load threshold for all banks to 1A, type: apc> bkLowLoad all 1 E000: Success Example 2: To view the low-load threshold setting for banks 1 through 3, type: apc> bkLowLoad 1-3 E000: Success 1: 1 A 2: 1 A 3: 1 A Error Messages: E000, E102

Rack PDU User Guide 55 bkNearOver Access: Super User, Administrator, Device User Description: Set or view the bank near-overload threshold current in amps. You can specify all banks, a single bank, a range, or a comma-separated list of single banks and/or ranges. Parameters: [id#:] [current] Example 1: To set the near-overload threshold for all banks to 10A, type: apc> bkNearOver all 10 E000: Success Example 2: To view the near-overload threshold setting for banks 1 through 3, type: apc> bkNearOver 1-3 E000: Success 1: 10 A 2: 10 A 3: 10 A Example 3: To view the near-overload threshold setting for banks 1 and 2 on guest Rack PDU 3, type: apc> bkNearOver 3:1-2 E000: Success 1: 16 A 2: 16 A Error Messages: E000, E102 bkOverLoad Access: Super User, Administrator, Device User Description: Set or view the bank overload threshold current in amps. You can specify all banks, a single bank, a range, or a comma-separated list of single banks and/or ranges. Parameters: [id#:] [current] Example 1: To set the bank overload threshold for all banks to 13A, type: apc> bkOverLoad all 13 E000: Success Example 2: To view the bank overload threshold setting for banks 1 through 3, type: apc> bkOverLoad 1-3 E000: Success 1: 13 A 2: 13 A 3: 13 A Error Messages: E000, E102

56 Rack PDU User Guide bkPeakCurr Access:Super User, Administrator, Device User Description:Display the peak current measurement from a bank(s) Parameters:[id#:] <”all” | bank#> Example: apc> bkPeakCurr 2 E000: Success 2: 0.0 A

apc> bkPeakCurr all E000: Success 1: 0.0 A 2: 0.0 A

Error Messages: E000, E102 bkReading Access: Super User, Administrator, Device User, Read Only Description: View the current reading (measurement) in amps for a bank. You can specify all banks, a single bank, a range, or a comma-separated list of single banks and/or ranges. Parameters: [id#:] [current] Example 1: To view the current reading for bank 3, type: apc> bkReading 3 E000: Success 3: 4.2 A Example 2: To view the current reading for all banks, type: apc> bkReading all E000: Success 1: 6.3 A 2: 5.1 A 3: 4.2 A Error Messages: E000, E102

Rack PDU User Guide 57 bkRestrictn Access: Super User, Administrator, Device User Description: Set or read the overload restriction feature to prevent users from applying power to outlets when an overload threshold is violated. Parameters: [id#:] <“all” | phase#> [<“none” | “near” | “over”> Acceptable arguments are none, near, and over. To specify phases, choose from the following options. Type: all, a single phase, a range, or a comma-separated list of phases. phase# = A single number or a range of numbers separated with a dash or a comma separated list of single phase number and/or number ranges. Example 1: To set the overload restriction for phase three to none, type: apc> bkRestrictn 3 none E000: Success Example 2: To view the overload restrictions for all phases, type: apc> bkRestrictn all E000: Success 1: over 2: near 3: none Example 3: To view the overload restrictions for all phases on guest Rack PDU 2, type: apc> bkRestrictn 2:all E000: Success 1: None 2: None Error Messages: E000, E102 devLowLoad Access: Super User, Administrator, Device User Description: Set or view the low-load threshold in kilowatts for the device. Parameters: [id#:] [threshold] = New power threshold (Kilowatts). Example 1: To view the low-load threshold, type: apc> devLowLoad E000: Success 0.5 kW Example 2: To set the low-load threshold to 1 kW, type: apc> devLowLoad 1.0 E000: Success Error Messages: E000, E102

58 Rack PDU User Guide devNearOver Access:Super User, Administrator, Device User Description:Set or view the near-overload threshold in kilowatts for the device. Parameters: [id#:] [threshold] = New outlet threshold (Kilowatts). Example 1: To view the near-overload threshold, type: apc> devNearOver E000: Success 20.5 kW Example 2: To set the near-overload threshold to 21.3 kW, type: apc> devNearOver 21.3 E000: Success Error Messages: E000, E102 devOverLoad Access:Super User, Administrator, Device User Description: Set or view the overload threshold in kilowatts for the device. Parameters: [id#:] [threshold] = New outlet threshold (Kilowatts). Example 1: To view the overload threshold, type: apc> devOverLoad E000: Success 25.0 kW Example 2: To set the overload threshold to 25.5 kW, type: apc> devOverLoad 25.5 E000: Success Example 3: To view the overload threshold for guest Rack PDU 3, type: apc> devOverLoad 3: E000: Success 5.0 kW Error Messages: E000, E102

Rack PDU User Guide 59 devPeakLoad Access: Super User, Administrator, Device User Description: Display the peak power measurement from the device. Parameters: none Example: apc> devPeakLoad E000: Success 0.0 kW Error Messages: E000, E102 devReading Access: Super User, Administrator, Device User, Read Only Description: View the total power in kilowatts or total energy in kilowatt-hours for the device. Parameters: [id#:] [power | energy | appower | pf] Argument Definition View the total power in kilowatts. View the total energy in kilowatt-hours. View the total apparent power in kVA. View the power factor

Example 1: To view the total power, type: apc> devReading power E000: Success 5.2 kW Example 2: To view the total energy, type: apc> devReading energy E000: Success 200.1 kWh Error Messages: E000, E102 dispID Access: Super User, Administrator Description: Sets or reads the device’s Display ID. Parameters: [id#:] [new_id] = Set the Display ID. Example 1: apc> dispID E000: Success RPDU ID: 1* apc> dispID 2 E000: Success RPDU ID: 2* apc> dispID 3: 2 E000: Success Error Message: E000, E102

60 Rack PDU User Guide energyWise Access: Super User, Administrator, Device User, Outlet User Description: Cisco IOS® software for monitoring, controlling, and reporting the energy use of information technology (IT). Parameters: Option Argument -e ] (Enable) -p -d ] -m ] (Secure Mode) -s -v (Toolkit Version) -n [outlet #] ] (0 for Parent) -r [outlet #] ] (0 for Parent) -k [outlet #] ] (0 for Parent) -i [outlet #] <1-100>] (0 for Parent) (Importance) Example: Enable: Disabled Port: 43440 Domain Name: Secure Mode: Shared Secret Shared Secret: Toolkit Version: (rel2_7)1.2.0 Name (P): apc51F304 Name (C1): apc51F304.1.Outlet1 Name (C2): apc51F304.1.Outlet2 Name (C3): apc51F304.1.Outlet3 Name (C4): apc51F304.1.Outlet4 Name (C5): apc51F304.1.Outlet5 Name (C6): apc51F304.1.Outlet6 Name (C7): apc51F304.1.Outlet7 Name (C8): apc51F304.1.Outlet8 Role (P): Rack Power Distribution Unit Role (C1): Outlet Role (C2): Outlet Role (C3): Outlet Role (C4): Outlet Role (C5): Outlet Role (C6): Outlet Role (C7): Outlet Role (C8): Outlet Keywords (P): apc,pdu,rackpdu Keywords (C1): apc,pdu,rackpdu,outlet Keywords (C2): apc,pdu,rackpdu,outlet Keywords (C3): apc,pdu,rackpdu,outlet Keywords (C4): apc,pdu,rackpdu,outlet Keywords (C5): apc,pdu,rackpdu,outlet

Rack PDU User Guide 61 Keywords (C6): apc,pdu,rackpdu,outlet Keywords (C7): apc,pdu,rackpdu,outlet Keywords (C8): apc,pdu,rackpdu,outlet Importance (P): 1 Importance (C1): 1 Importance (C2): 1 Importance (C3): 1 Importance (C4): 1 Importance (C5): 1 Importance (C6): 1 Importance (C7): 1 Importance (C8): 1 Error Message: None

62 Rack PDU User Guide Temperature/Humidity Sensors Note: You must have installed an optional Schneider Electric Temperature/ Humidity Sensor (AP9335TH) to your Rack PDU in order to use the Humidity related commands. humHyst Access: Super User, Administrator, Device User Description: Sets and reads the humidity threshold hysteresis Parameters: [id#:] [ value ] = new threshold hysteresis value (% RH) Example: apc> humHyst E000: Success 6 %RH apc> humHyst 5 E000: Success Error Message: E000, E102 humLow Access: Super User, Administrator, Device User Description: Set or view the low humidity threshold as a percent of the relative humidity. Parameters: [id#:] [ humidity ] = new low humidity threshold Example 1: To view the low humidity threshold, type: apc> humLow E000: Success 10 %RH Example 2: To set the low humidity threshold, type: apc> humLow 12 E000: Success Example 3: To view the low humidity threshold on guest Rack PDU 3, type: apc> humLow 3: E000: Success 10 %RH Error Message: E000, E102

Rack PDU User Guide 63 humMin Access: Super User, Administrator, Device User Description: Set or view the minimum humidity threshold as a percent of the relative humidity. Parameters: [id#:] [ humidity ] = new minimum humidity threshold. Example 1: To view the minimum humidity threshold, type: apc> humMin E000: Success 6 %RH Example 2: To set the minimum humidity threshold, type: apc> humMin 8 E000: Success Example 3: To set the minimum humidity threshold on guest Rack PDU 3 to 18% RH, type: apc> humMin 3:18 E000: Success Error Message: E000, E102 humReading Access: Super User, Administrator, Device User, Outlet User, Read Only Description: View the humidity value from the sensor. Parameters: [id#:] Example 1: To view the humidity value, type: apc> humReading E000: Success 25 %RH Example 2: To view the humidity value on guest Rack PDU 2, type: apc> humReading 2: E000: Success 48 %RH Error Message: E000, E102, E201 lcd Access: Super User, Administrator, Device User Description: Turn the LCD On/Off Parameters: [id#:] [ on|off ] Example: apc> lcd off E000: Success apc> lcd 1: on E000: Success Error Messages: E000, E100, E102

64 Rack PDU User Guide lcdBlink Access: Super User, Administrator, Device User Description: Blink the LCD Back-light for the specified period Parameters: [id#:] [ time ] = is the number of minutes to blink the display. It can be canceled by pressing a button on the LCD. Valid range is [1-10] Example: apc> lcdBlink E000: Success

Error Messages: E000, E102

olAssignUsr Access: Super User, Administrator Description: Assign control of outlets to an outlet user that exists in the local database. Parameters: [id#:] Argument Definition all All device outlets. The name configured for a specific outlet. (See “olName” on page 67.) A single number or a range of numbers separated with a dash, or a comma- separated list of single outlet numbers and number ranges. A user that exists in the local database. (See “userAdd” on page 78.) Example 1: To assign a user named Bobby to outlets 3, 5 through 7, and 10, type: apc> olAssignUsr 3,5-7,10 bobby E000: Success Example 2: To assign a user named Billy to all outlets, type: apc> olAssignUsr all billy E000: Success Example 3: To assign a user named Billy to all outlets on guest Rack PDU 3, type: apc> olAssignUsr 3:all billy E000: Success Error Message: E000, E102

Rack PDU User Guide 65 olLowLoad Access: Super User, Administrator, Device User Description: Set or view the outlet low-load threshold in kilowatts. To specify an outlet, choose from the following options. Parameters: [id#:] [power] Argument Definition all All device outlets. A single number or a range of numbers separated with a dash, or a comma- separated list of single outlet numbers and number ranges. Example 1: To set the low-load threshold for all outlets to 1 kW, type: apc> olLowLoad all 1 E000: Success Example 2: To view the low-load threshold for outlets 1 through 5, type: apc> olLowLoad 1-5 E000: Success 1: 1 kW 2: 1 kW 3: 1 kW 4: 1 kW 5: 1 kW Example 3: To view the low-load threshold for outlets 1 through 3 on guest Rack PDU 2, type: apc> olLowLoad 2:1-3 E000: Success 1: Outlet 1: 0 W 2: Outlet 2: 0 W 3: Outlet 3: 0 W Error Message: E000, E102, E104

66 Rack PDU User Guide olName Access: Super User, Administrator, Device User, Read Only, and Outlet User, but only for outlets to which the user is assigned. Description: Set or view the name configured for an outlet. Parameters: [id#:] [newname] Argument Definition all All device outlets. A single number or a range of numbers separated with a dash, or a comma- separated list of single outlet numbers and number ranges. The name for a specific outlet. Use only letters and numbers.

Example 1: To configure the name for outlet 3 to BobbysServer, type: apc> olName 3 BobbysServer E000: Success Example 2: To view the names of outlets 3 through 5 on guest Rack PDU 2, type: apc> olName 2:3-5 E000: Success 3: BobbysServer 4: Outlet 4 5: Outlet 5 Error Message: E000, E102, E104

olNearOver Access: Super User, Administrator, Device User Description: Set or view the outlet near-overload threshold in kilowatts. To specify outlets, choose from the following options. Parameters: [id#:] [power] Argument Definition all All device outlets. A single number or a range of numbers separated with a dash, or a comma- separated list of single outlet numbers and number ranges.

Example 1: To set the near-overload threshold for all outlets to 10 kW, type: apc> olNearOver all 10 E000: Success Example 2: To view the near-overload threshold for outlets 1 through 5, type: apc> olNearOver 1-5 E000: Success 1: 10 kW 2: 10 kW 3: 10 kW 4: 10 kW 5: 10 kW Example 3: To set the near-overload threshold for all outlets on guest Rack PDU 3 to 10 kW, type: apc> olNearOver 3:all 10 E000: Success Error Message: E000, E102, E104

Rack PDU User Guide 67 olOverLoad Access: Super User, Administrator, Device User Description: Set or view the outlet overload threshold in kilowatts. To specify outlets, choose from the following options. Parameters: [id#:] [power] Argument Definition all All device outlets. A single number or a range of numbers separated with a dash, or a comma- separated list of single outlet numbers and number ranges. Example 1: To view the overload threshold for outlets 3 and 5 through 7, type: apc> olOverLoad 3,5-7 E000: Success 3: Bobby’s Server: 9 W 5: Billy’s Server: 9 W 6: Joe’s Server: 7 W 7: Jack’s Server: 7 W

Example 2: To set the overload threshold for outlets 3 and 5 through 7 to 8 W on guest Rack PDU 2, type: apc> olOverLoad 3,5-7 8 E000: Success

Example 3: To view the overload threshold you just changed, type: apc> olOverLoad 3,5-7 E000: Success 3: Bobby’s Server: 8 W 5: Billy’s Server: 8 W 6: Joe’s Server: 8 W 7: Jack’s Server: 8 W

Error Message: E000, E102, E104

68 Rack PDU User Guide olPeakLoad Access: Super User, Administrator, Device User Description: Display the peak current measurement from a bank(s). Parameters: [id#:] [] Argument Definition all All device outlets. A single number or a range of numbers separated with a dash, or a comma- separated list of single outlet numbers and number ranges. Example: apc> olPeakLoad 24 E000: Success 24: Outlet 24: 0 W

apc> olPeakLoad 3, 5-7 E000: Success 3: Outlet 3: 0 W 5: Outlet 5: 0 W 6: Outlet 6: 0 W 7: Outlet 7: 0 W Error Message: E000, E102, E104

Rack PDU User Guide 69 olReading Access: Super User, Administrator, Device User, Read Only, and Outlet User, but only for outlets to which the user is assigned. Description: Displays a reading/measurement from an outlet or a group of outlets. Parameters: [id#:] Argument Definition all All device outlets. The name configured for a specific outlet. (See “olName” on page 67.) A single number or a range of numbers separated with a dash, or a comma- separated list of single outlet numbers and number ranges.

Example 1: To view the current readings of outlets 1 through 3, type: apc> olReading 1-3 current E000: Success 1: Outlet 1: 5.1 A 2: Outlet 2: 1.9 A 3: BobbysServer: 2.3 A Example 2: To view the power readings of outlets 1 through 4 on guest Rack PDU 2, type: apc> olReading 2:1-3 power E000: Success 1: Outlet 1: 0 W 2: Outlet 2: 0 W 3: BobbysServer: 0 W Error Message: E000, E102, E104

70 Rack PDU User Guide olUnasgnUsr Access: Super User, Administrator Description: Unassign outlets to a user that exists in the local database. Outlet permissions for RADIUS defined users can only be set at the RADIUS server. This command is only available to the administrator. If an outlet is specified that is not assigned to a user, no error is generated. Parameters: [id#:] Argument Definition all All device outlets. The name configured for a specific outlet. (See “olName” on page 67.) A single number or a range of numbers separated with a dash, or a comma- separated list of single outlet numbers and number ranges. A user that exists in the local database. Example 1: To remove a user named Bobby from control of outlets 3, 5 through 7, and 10, type: apc> olUnasgnUsr 3,5-7,10 bobby E000: Success Example 2: To remove a user named Billy from control of all outlets, type: apc> olUnasgnUsr all billy E000: Success Error Message: E000, E102

phLowLoad Access: Super User, Administrator, Device User Description: Set or view the phase low-load threshold. To specify phases, choose from the following options. Type: all, a single phase, a range, or a comma-separated list of phases. Parameters: [id#:] [current] phase# = A single number or a range of numbers separated with a dash or a comma; separated list of single bank number and/or number ranges. current = The new phase threshold (Amps). Example 1: To set the low-load threshold for all phases to 1 A, type: apc> phLowLoad all 1 E000: Success Example 2: To view the low-load threshold for phases 1 through 3, type: apc> phLowLoad 1-3 E000: Success 1: 1 A 2: 1 A 3: 1 A Error Message: E000, E102

Rack PDU User Guide 71 phNearOver Access: Super User, Administrator, Device User Description: Set or view the phase near-overload threshold. Parameters: [id#:] [current] phase# = A single number or a range of numbers separated with a dash or a comma; separated list of single bank number and/or number ranges. current = The new phase threshold (Amps). Example 1:To set the near-overload threshold for all phases to 10 A, type: apc> phNearOver all 10 E000: Success Example 2:To view the near-overload threshold for phases 1 through 3, type: apc> phNearOver 1-3 E000: Success 1: 10 A 2: 10 A 3: 10 A Error Message: E000, E102 phOverLoad Access: Super User, Administrator, Device User Description: Set or view the phase overload threshold. Parameters: [id#:] [current] phase# = A single number or a range of numbers separated with a dash or a comma; separated list of single bank number and/or number ranges. current = The new phase threshold (Amps). Example 1: To set the overload threshold for all phases to 13 A, type: apc> phOverLoad all 13 E000: Success Example 2: To view the overload threshold for phases 1 through 3, type: apc> phOverLoad 1-3 E000: Success 1: 13 A 2: 13 A 3: 13 A Error Messages: E000, E102

72 Rack PDU User Guide phPeakCurr Access: Super User, Administrator, Device User Description: Display the peak current measurement from a phase(s). Parameters: [id#:] phase# = A single number or a range of numbers separated with a dash or a comma; separated list of single bank number and/or number ranges. Example: apc> phPeakCurr 2 E000: Success 2: 0.0 A

apc> phPeakCurr all E000: Success 1: 0.0 A 2: 0.0 A 3: 0.0 A Error Messages: E000, E102

phReading Access: Super User, Administrator, Device User, Read Only Description: View the current, voltage, or power for a phase. You can specify all phases, a single phase, a range, or a comma-separated list of phases. Parameters: [id#:] < all | phase# > < current | voltage | power | appower | pf > Example 1: To view the measurement for current for phase 3, type: apc> phReading 3 current E000: Success 3: 4 A Example 2: To view the voltage for each phase, type: apc> phReading all voltage E000: Success 1: 120 V 2: 120 V 3: 120 V Example 3: To view the power for phase 2 on guest Rack PDU 3, type: apc> phReading 3:2 power E000: Success 2: 40 W Error Message: E000, E102

Rack PDU User Guide 73 phRestrictn Access: Super User, Administrator Description: Set or view the overload restriction feature to prevent outlets from turning on when the overload alarm threshold is violated. Acceptable arguments are none, near, and over. To specify phases, choose from the following options. Type: all, a single phase, a range, or a comma-separated list of phases. Parameters: [id#:] < all | phase#> [none | near | over] phase# = A single number or a range of numbers separated with a dash or a comma; separated list of single bank number and/or number ranges. Example 1: To set the overload restriction for phase three to none, type: apc> phRestrictn 3 none E000: Success Example 2: To view the overload restrictions for all phases, type: apc> phRestrictn all E000: Success 1: over 2: near 3: none Error Message: E000, E102 phTophVolts Access: Super User, Administrator, Device User, Outlet User, Read Only Description: Read the phase-to-phase voltage on multi-phase devices. Parameters: [id#:] id# = The display identifier of the Rack Power Distribution Unit – normally 1. However, in an NPS environment, the value will be 1 through the number of NPS remotes. Example 1: apc> phTophVolts 1 E000: Success 1: L1-2 208 V 2: L2-3 208 V 3: L3-1 208 V Error Messages: E000, E102

74 Rack PDU User Guide prodInfo Access: Super User, Administrator, Device User, Outlet User, Read Only Description: View information about the Rack PDU. Parameters: [id#: | all] Example: To view the product information for this Rack PDU, type: apc> prodInfo E000: Success RPDU ID: 1* AOS X.X.X Metered-by-Outlet Rack PDU X.X.X Model: AP8XXX Name: room555Main Location: Room 555 Contact: (xxx) 555-1234 Present Outlets: XX Metered Outlets: XX Max Current: XX A Phases: X Banks: X Uptime: 0 Days 0 Hours 0 Minutes NPS Type: Host NPS Status: Active Network Link: Link Active Error Messages: E000

sensorName Access: Super User, Administrator, Device User Description: Set or view the name assigned to the Rack PDU Temp/Humidity port. Parameters: [id#:][newname] Example 1: To set the name for the port to “Sensor1,” type: apc> sensorName Sensor1 E000: Success Example 2: To then view the name for the sensor port, type: apc> sensorName E000: Success Sensor1 Example 3: To set the name for the sensor port on guest Rack PDU 2 to “Sensor1,” type: apc> sensorName 2:Sensor1 E000: Success Error Messages: E000, E102

Temperature Sensor Note: You must have installed an optional Schneider Electric Temperature Sensor (AP9335T) to your Rack PDU in order to use the Temperature related commands.

Rack PDU User Guide 75 tempHigh Access: Super User, Administrator, Device User Description: Set or view the high-temperature threshold in either Fahrenheit or Celsius. Parameters: [id#:] < F | C > [] = New high temperature threshold Example 1: To set the high-temperature threshold to 70º Fahrenheit, type: apc> tempHigh F 70 E000: Success Example 2: To view the high-temperature threshold in Celsius, type: apc> tempHigh C E000: Success 21 C Example 3: To view the high-temperature threshold of guest Rack PDU 2 in Fahrenheit, type: apc> tempHigh 2:F E000: Success 70 F Error Messages: E000, E102 tempHyst Access: Super User, Administrator, Device User Description: Set and displays the temperature threshold hysteresis Parameters: [id#:] < F | C > []= new temperature hysteresis value. Example: apc> tempHyst F 6 E000: Success apc> tempHyst C E000: Success 3 C Error Message: E000, E102

76 Rack PDU User Guide tempMax Access: Super User, Administrator, Device User Description: Set or view the max-temperature threshold in either Fahrenheit or Celsius. Parameters: [id#:] < F | C > []= new max temperature threshold. Example 1: To set the max-temperature threshold to 80º Fahrenheit, type: apc> tempMax F 80 E000: Success Example 2: To view the max-temperature threshold in Celsius, type: apc> tempMax C E000: Success 27 C Example 3: To view the max-temperature threshold of guest Rack PDU 3 in Fahrenheit, type: apc> tempMax 3:F E000: Success 95 F Error Message: E000, E102 tempReading Access: Super User, Administrator, Device User, Outlet User, Read Only Description: View the temperature value in either Fahrenheit or Celsius from the sensor. Parameters: [id#:] < F | C > = temperature Example 1: To view the temperature value in Fahrenheit, type: apc> tempReading F E000: Success 51.1 F Example 2: To view the temperature value of guest Rack PDU 3 in Celsius, type: apc> tempReading 2:C E000: Success 23.5 C Error Message: E000, E102, E201

Rack PDU User Guide 77 userAdd Access: Super User, Administrator Description: Add an outlet user to the local user database. The password for the new user will be the same as the user name. To change the password of the user, use the ‘userPasswd’ command. Parameters: user = A user that does NOT exists in the local database.

Example: To add a user named Bobby, type: apc> userAdd Bobby E000: Success Error Message:E000, E102, E202 userDelete Access: Super User, Administrator Description: Remove an outlet user from the local user database. Parameters: user = A user that exists in the local database.

Example: To remove a user named Bobby, type: apc> userDelete Bobby E000: Success

Error Message: E000, E102, E202

78 Rack PDU User Guide userList Access: Super User, Administrator, Device User, Read Only, and Outlet User, but only for outlets to which the user is assigned. Description: List the users and the outlets assigned to them. When used by the administrator, it lists the users in the local database and the outlet numbers assigned to them. When used by an outlet user, it lists only that user and their outlets. If the active user was authenticated via RADIUS, then the user and the outlet permissions are displayed based on logged user type. When multiple Rack PDUs are connected via the In/Out ports, the outlets will be listed as: [];[];[];[] is the display ID of the Rack PDU, and the list of owned outlets is contained within square brackets that follow. A semi-colon is used to delimit one Rack PDU device from the next. Parameters: None Example 1: When logged in as the Administrator, type: apc> userList E000: Success Name User Type Status Outlets ------apc Super ****** 1-24 device Device Enabled 1-24 readonly ReadOnly Enabled 1-24 network NetworkOnly Enabled 1-24 dobby Outlet Enabled 1-12

Example 2: If outlet user ‘dobby’ is logged in: apc> userList E000: Success Name User Type Status Outlets ------dobby Outlet Enabled 1-12

Example 3: If a radius outlet user ‘RadOutlet’ is logged in: apc> userList E000: Success Name User Type Status Outlets ------RadOutlet Outlet(Radius) ****** 1[1,3,5]

Example 4: If a radius device user ‘RadDevice’ is logged in: apc> userList E000: Success Name User Type Status Outlets ------raddev Device(Radius) ****** 1-24 readonly ReadOnly Enabled 1-24 network NetworkOnly Enabled 1-24 dobby Outlet Enabled 1-12

Rack PDU User Guide 79 Example 5: If an Admin user is logged in, and multiple Rack PDUs are present on the In/Out ports: apc> userList E000: Success Name User Type Status Outlets ------apc Super ****** 1[1-24]; 2[1-24]; 3[1-24]; 4[1-24] administrator Admin Enabled 1[1-24]; 2[1-24]; 3[1-24]; 4[1-24] device Device Enabled 1[1-24]; 2[1-24]; 3[1-24]; 4[1-24] readonly ReadOnly Enabled 1[1-24]; 2[1-24]; 3[1-24]; 4[1-24] network NetworkOnly Enabled 1[1-24]; 2[1-24]; 3[1-24]; 4[1-24] dobby Outlet Enabled 1[1]; 3[3]; 4[4]

Error Message: E000 userPasswd Access: Super User, Administrator. Description: Set an outlet User password.The administrator user can change passwords for all users. Parameters: = User name that will have its password changed. Password 2 is a confirmation and must be identical to password 1. Example: To set dobby’s password to “riddle” type: apc> userPasswd dobby riddle riddle E000: Success Error Messages:E000, E102, E104

80 Rack PDU User Guide Web Interface

Supported Web Browsers

You can use ® Internet Explorer® (IE) 7.x and higher (on Windows® operating systems only) or Mozilla® Firefox® 3.0.6 or higher (on all operating systems) to access the Rack PDU through its Web interface. Other commonly available browsers may work but have not been fully tested by APC. The Rack PDU cannot work with a proxy server. Before you can use a Web browser to access the Web interface of the Rack PDU, you must do one of the following: • Configure the Web browser to disable the use of a proxy server for the Rack PDU. • Configure the proxy server so that it does not proxy the specific IP address of the Rack PDU.

Log On to the Web Interface

Overview You can use the DNS name or System IP address of the Rack PDU for the URL address of the Web interface. Use your case-sensitive user name and password to log on. The default user name and password for the Super User are both apc. For all other user types, there is no default user name or password. The Super User or an Administrator created by the Super User, must define the user name and password and other account characteristics for these users. NOTE: If you are using HTTPS (SSL/TLS) as your access protocol, your login credentials are compared with information in a server certificate. If the certificate was created with the Security Wizard, and an IP address was specified as the common name in the certificate, you must use an IP address to log on to the Rack PDU. If a DNS name was specified as the common name on the certificate, you must use a DNS name to log on.

URL address formats

Type the DNS name or IP address of the Rack PDU in the Web browser’s URL address field and press ENTER. When you specify a non-default Web server port in Internet Explorer, you must include http:// or https:// in the URL.

Common browser error messages at log-on

Error Message Browser Cause of the Error

“This page cannot be displayed.” Internet Explorer Web access is disabled, or the URL was not correct. “Unable to connect.” Firefox

Rack PDU User Guide 81 URL format examples • For a DNS name of Web1:

– http://Web1 if HTTP is your access mode – https://Web1 if HTTPS (HTTP with SSL) is your access mode • For a System IP address of 139.225.6.133 and the default Web server port (80):

– http://139.225.6.133 if HTTP is your access mode – https//139.225.6.133 if HTTPS (HTTP with SSL) is your access mode • For a System IP address of 139.225.6.133 and a non-default Web server port (5000):

– http://139.225.6.133:5000 if HTTP is your access mode – https://139.225.6.133:5000 if HTTPS (HTTP with SSL) is your access mode • For a System IPv6 address of 2001:db8:1::2c0:b7ff:fe00:1100 and a non-default Web server port (5000): http://[2001:db8:1::2c0:b7ff:fe00:1100]:5000 if HTTP is your access mode Web Interface Features

Read the following to familiarize yourself with basic Web interface features for your Rack PDU.

Tabs The following tabs are available: • Home: Appears when you log on (This is the default tab when you log on. To change the login page to a different page, click on the green pushpin at the top right side of the browser window while on the desired page). View active alarms, the load status of the Rack PDU, and the most recent Rack PDU events. For more information, see “About Home” on page 85. • Status: Gives the user the status of the Rack PDU and Network. The RPDU tab covers the status of alarms, groups, device, phase, bank, and environment. Network tab covers just the network. See “Status Tab” on page 86. • Control: The Control tab covers three topics: RPDU, Security and Network. Much more information is covered under each of these tabs and will be described in the Control tab section. • Configuration: The Configuration tab covers RPDU, Security, Network, Notification, General and Logs. Much more information is covered under each of these tabs and will be described in the Configuration tab section. • Tests: The Tests tab covers RPDU and Network. The RPDU tab covers LCD Blink and the Network tab covers LED Blink. Both will be further described later in the Tests section of the document. • Logs: The Logs section covers: Event, Data and Firewall. The Event and Data tabs cover more information which will be further discussed later in the Logs section of the document. • About: The About section covers RPDU and Network, which will be further discussed later in the About section of the document.

82 Rack PDU User Guide Device status icons One or more icons and accompanying text indicate the current operating status of the Rack PDU: Symbol Description

Critical: A critical alarm exists, which requires immediate action.

Warning: An alarm condition requires attention and could jeopardize your data or equipment if its cause is not addressed.

No Alarms: No alarms are present, and the Rack PDU and NMC are operating normally.

At the upper right corner of every page, the web interface displays the same icons currently displayed on the Home page to report Rack PDU status: • The No Alarms icon if no alarms exist. • One or both of the other icons (Critical and Warning) if any alarms exist, and after each icon, the number of active alarms of that severity.

Quick Links At the lower left on each page of the interface, there are three configurable links. By default, the links access the URLs for these Web pages: • Link 1: The home page of the APC by Schneider Electric website • Link 2: Demonstrations of APC by Schneider Electric web-enabled products • Link 3: Information on APC by Schneider Electric Remote Monitoring Service

Located in the upper right hand corner of each page: • User name (click to change user preferences) • Language (if available, click to change language preference) • Log Off (click to log the current user off of the web interface) • Help (click to view help contents) • (click to set the current web page to be the log in home page) Example: Log In Home: To make any screen the “home” screen (i.e., the screen that displays first when you log on), go to that screen, and click the icon in the top right corner. Click to revert to displaying the Home screen when you log on.

Rack PDU User Guide 83 Network Port Sharing (NPS) on the Web User Interface (UI) Group Control using Network Port Sharing The web interface of the Rack PDU will have additional capabilities if the Rack PDU is part of an NPS group. This includes an NPS Group Status web page and an NPS Group Configuration page. In addition, for web pages that support NPS Rack PDUs, the user can select a different Rack PDU in the group to view by selecting the Rack PDU Display ID of the unit he or she would like to view. Each Rack PDU in the NPS group is denoted with a Rack PDU icon followed by its Display ID (1 to 4). The Rack PDU that the user is logged into is displayed with an additional asterisk (*) following the Display ID. NOTE: The Reset/Reboot web page has many additional reset/reboot options for Rack PDU groups. These include individual Rack PDU reset to defaults, individual Rack PDU rebooting, and clearing of guest PDU lost communication alarms by removing the guests from the group.

84 Rack PDU User Guide About Home

The Home page contains the following information: Active Alarms, Load Status and Recent Device Events. Active Alarms will show if any alarms exist. If no alarms exist, a green check mark with the words ”No Alarms Present” will show. The Load Status shows a colored bar demonstrating the level of the Bank, Phase and Device loads. To see the Device Status select the More link at the bottom of the list.The Recent Device Events box will list the five most recent device Events by the device by Date, Time and Event.

The Overview view In the Load Status area, view the load for the device in kW and for the phases and banks in amps, as applicable. The green, yellow, and red meter shows the current load status: normal, near overload, or overload. NOTE: If a low load threshold was configured the meter will also include a blue segment to the left of the green.

In the Rack PDU Parameters box the reader will find the Name, Location, Contact, Model Number, Rating, User (type of user account accessing the Rack PDU) and Uptime (the amount of time the Rack PDU has been operating since the last reboot from either a power cycle or a reboot of the Management Interface). In the Recent Device Events box are the Events which have occurred most recently and the dates and times they occurred. A maximum of five Events are shown at one time. Click More Events to go to the Logs tab to view the entire event log.

Rack PDU User Guide 85 Status Tab

About the Status Tab Use the Status tab to: • View the load status for the Rack PDU and Network Status • Under the Rack PDU tab readers can scroll and access: Alarms, Device, Phase, Bank, Outlets and Environment. • Manage outlets • Select Network from the menu, to view the current IPv4 and IPv6 settings.

86 Rack PDU User Guide View the Load Status and Peak Load Path: Status > RPDU

Alarms: Lists Device Alarm Status. Group: Network Port sharing Group Status. List the Properties, Metering and firmware version information. Change Host Rack PDU can be accessed from its link at the bottom of the page. Device: Shows status of device. Lists Status, Properties and Configuration information. Phase: Shows Phase Status. The phase settings can also be configured via a Configure Phase Settings link at the bottom of the page. Configuration can be changed as well. Bank: Shows bank status (only on units with this feature). List current size and demonstrates range on a colored red, green and yellow sliding bar. The bank settings can be changed via a Configure Bank status link at the bottom of the page. Outlet: Shows: Outlet Name, Phase, State and Outlet Load Environment: Shows Alarm Status, Temperature, Humidity and can configure Temperature and Humidity Configuration after pressing the Configure link.

View the Network Status Path: Status > Network

The Network screen displays information about your network.

Current IPv4 Settings System IP: The IP address of the unit. Subnet Mask: The IP address of the sub-network. Default Gateway: The IP address of the router used to connect to the network. MAC Address: The MAC address of the unit. Mode: How the IPv4 settings are assigned: Manual, DHCP, or BOOTP. DHCP Server: The IP address of the DHCP server. This is only displayed if Mode is DHCP. Lease Acquired: The date/time that the IP address was accepted from the DHCP server. Lease Expires: The date/time that the IP address accepted from the DHCP server expires and will need to be renewed.

Current IPv6 Settings Type: How the IPv6 settings are assigned.

IP Address: The IP address of the unit.

Prefix Length: The range of addresses for the sub-network.

Rack PDU User Guide 87 Domain Name System Status Active Primary DNS Server: The IP address of the primary DNS server.

Active Secondary DNS Server: The IP address of the secondary DNS server.

Active Host Name: The host name of the active DNS server.

Active Domain Name (IPv4/IPv6): The IPv4/IPv6 domain name that is currently in use.

Active Domain Name (IPv6): The IPv6 domain name that is currently in use. Ethernet Port Speed Current Speed: The current speed assigned to the Ethernet port.

88 Rack PDU User Guide Control

The Control menu options enable you to take immediate actions affecting active user management and the security of your network.

Managing User Sessions Path: Control > Security > Session Management

The Session Management menu displays all active users currently connected to the Rack PDU. To view Information about a given user, click their user name. The Session Details screen displays basic information about the user including what interface they are logged-in to, their IP address, and user authentication. There is also an option to Terminate Session for the user.

Rack PDU User Guide 89 Resetting the Network Interface Path: Control > Network > Reset/Reboot

This menu gives you the option to reset and reboot various components of the network interface. Users have the option to Reboot Management Interface, NOTE: Rebooting the Management Interface only restarts the Rack PDU’s Network Management Interface. It does not affect the outlet ON/OFF status.

Reset All: Clear the Exclude TCP/IP checkbox to reset all configuration values; mark the Exclude TCP/IP checkbox to reset all values except TCP/IP. Reset Only: (Resetting may take up to a minute) Options include: • TCP/IP settings: Set TCP/IP Configuration to DHCP & BOOTP, its default setting, request requiring that the Rack PDU receive its TCP/IP settings from a DHCP or BOOTP server. See “View the result of the test DNS in the Last Query Response field.” • Event configuration: Reset all changes to event configuration, by event and by group, to their default settings. • Guest PDU lost communication alarms by removing corresponding guest Rack PDUs. • Host Display ID and Remove all Guest Rack PDUs. • RPDU to Defaults. • For NPS groups: Guest PDU lost Communication alarms by removing corresponding guest Rack PDUs. Host Display ID and remove all guest Rack PDUs Host to Defaults Guest to Defaults Guest Management Interface (Reboot)

90 Rack PDU User Guide Configuration

About the Configuration Tab

Under the Configuration tab, several menu options are available to make changes to the Rack PDUs: • View the load status for the Rack PDU • Configure load thresholds for all connected devices, phases, banks, and outlets. • Manage and control outlets • Configure a name and location for the Rack PDU • View and manage the peak load measurement • Click user-configurable links to open web pages for specific devices connected to the Rack PDU

Rack PDU User Guide 91 Configure Load Thresholds

Path: Configuration > RPDU

View the load for the device, phases, banks, and outlets. The indicator in the green, yellow, and red meter shows the current load status: normal, near overload, or overload. If a low load threshold was configured, the meter will include a blue segment to the left of the green. When viewing the Device Load, the triangle above the meter indicates peak load. NOTE: The Rack PDU generates an alarm when any bank exceeds its configured value. However, if a circuit breaker trips, there is no definitive indication that the circuit breaker is open, other than that the current for that bank will drop. Set the Low Load Warning to 1 amp for these reasons: • The default setting for the Low Load Warning is 0 amps. This effectively disables the warning. With a setting of 0 amps for the Low Load Warning, the web interface will not indicate that a circuit breaker may have tripped. • A 1 amp detection threshold for the Low Load Warning for Bank Load Management will help to indicate that a circuit breaker may have tripped. To configure load thresholds 1. To configure load thresholds for the device, phases, or banks, make a selection from the Configuration > RPDU > Device and Phase and Bank drop-down menu. To configure load thresholds for outlets, click Configuration and then click an outlet. 2. Set Overload Alarm, Near Overload Warning, and Low Load Warning thresholds. 3. Click Apply to save your settings. Configure Rack PDU Name and Location

Path: Configuration > RPDU > Device

The name and location you enter will appear on the Home tab. 1. Enter a name and location and contact. 2. Click Apply to save. Reset Peak Load and kWh

Path: Configuration > RPDU > Device

3. Click the Configuration tab, then RPDU, then Device. 4. Click the Peak Load and Kilowatt-Hours check boxes as desired. 5. Click Apply.

92 Rack PDU User Guide Outlet Settings

Select From the options to control the outlets on your Rack PDU. Path: Configuration > RPDU > Metered Outlet > Configuration

Configure outlet settings and the outlet name The following settings are available: Setting Description Set the name for one or more outlets. The name is displayed next to the Name outlet number on status screens. Define an HTTP or HTTPS link to a web site or IP address. The external device web link can be set to the IP address of the external device plugged into the outlet (if applicable). Alternatively, it can be set to External Link the device's manufacturer web page in order to more easily view user manuals, etc. Clicking the link on the Outlet Links page will open a new browser window to the link. Phase L1-N - View Only Bank 1 - View Only Outlet Type (Rating) C13 (2500 W) - View Only Current 0.0 A - View Only Energy 0.0 kWh (last reset xx/XX/XXX 00:00:00) - View Only Power 0.0 W (Normal Load) 0.0 kWh at XX/XX/XXXX 00:00:00 (last reset XX/XX/XXXX 00:00:00 - View Peak Power Only Power Color Bar Graph - View Only Overload Alarm New Value in W (0 to 2750) Near Overload Warning View value in W (0 to 2750) Low Load Warning View value in W (0 to 2750)

Path: Configuration > RPDU > Metered Outlet > Configuration

Click the Configure Multiple Outlets button in the Outlet Configuration section or click the outlet name. • Configure outlet settings for multiple outlets: – Select the checkboxes next to the numbers of the outlets you want to modify, or select the All Outlets checkbox. – Enter values for Name and Link, and click the Apply button immediately below the list. • Configure outlet settings for a single outlet: – Enter values for Name and Link, and click the Apply button immediately below the list.

Rack PDU User Guide 93 Outlet User Manager The Outlet User Management web page allows a user with administrative rights to view existing outlet user information and to add new users. Individual outlets can be assigned to each outlet user. When an outlet user logs into the Rack PDU, he or she will only be able to view or control outlets that have been assigned to the outlet user. To modify an existing outlet user's assigned outlets, click on the outlet listing under the desired Rack PDU icon. To modify an existing outlet user's properties, click on the desired user name. To create a new outlet user account, click the Add User button on the web page. This will take you to the new user configuration web page. Be sure to select Outlet in the User Type field. After filling out all of the fields, click Next >> to continue to the next page which allows you to select the desired outlets for the outlet user.

Configure an outlet user Path: Configuration > RPDU > Outlet User

1. Click the Add New User button. 2. Type in the information for the following options and click Apply to confirm the changes. Option Description Set the outlet user name. "New User" is reserved and is not allowed. User Name NOTE: A user name in orange indicates the user account has been disabled. Password Set the outlet user password. User Description Set identification/description of outlet user. Account Status Enable, disable, or delete outlet user's account. Device outlet access Select the outlets the user can access.

Outlet Manager and Network Port Sharing Outlet users can be assigned outlets on any Rack PDU in a group with metered outlets. The outlet users will be stored on the Host PDU. In the web interface, you can view outlets assigned to a particular Rack PDU by clicking on its Display ID in the window.

94 Rack PDU User Guide Configure Temperature and Humidity Sensors Path: Configuration > RPDU > Environment

NOTE: To use this feature, you must have installed an optional Schneider Electric Temperature Sensor (AP9335T) or Schneider Electric Temperature/Humidity Sensor (AP9335TH) to your Rack PDU. For temperature: • If the high temperature threshold is reached, the system generates a Warning alarm. • If the maximum temperature threshold is reached, the system generates a Critical alarm. Similarly, for humidity: • If the low humidity threshold is reached, the system generates a Warning alarm. • If the minimum humidity threshold is reached, the system generates a Critical alarm. • NOTE: Click the thermometer symbol in the upper right corner to toggle between Fahrenheit and Celsius. To configure temperature and humidity sensors:

1. Enter values for minimum, maximum, high, and low thresholds. 2. Enter Hysteresis values. 3. Enable alarm generation as desired. 4. Click Apply. Hysteresis: This value specifies how far past a threshold the temperature or humidity must return to clear a threshold violation. • For Maximum and High temperature threshold violations, the clearing point is the threshold minus the hysteresis. • For Minimum and Low humidity threshold violations, the clearing point is the threshold plus the hysteresis. Increase the value for Temperature Hysteresis or Humidity Hysteresis to avoid multiple alarms if temperature or humidity that has caused a violation then wavers slightly up and down. If the hysteresis value is too low, such wavering can cause and clear a threshold violation repeatedly. Example of rising but wavering temperature: The maximum temperature threshold is 85°F, and the temperature hysteresis is 3°F. The temperature rises above 85°F, violating the threshold. It then wavers down to 84°F and then up to 86°F repeatedly, but no clearing event and no new violation occur. For the existing violation to clear, the temperature would have to drop to 82°F (3°F below the threshold). Example of falling but wavering humidity: The minimum humidity threshold is 18%, and the humidity hysteresis is 8%. The humidity falls below 18%, violating the threshold. It then wavers up to 24% and down to 13% repeatedly, but no clearing event and no new violation occur. For the existing violation to clear, the humidity would have to rise to above 26% (8% past the threshold).

Rack PDU User Guide 95 Security Session Management screen Path: Configuration > Security > Session Management

Enabling Allow Concurrent Logins means that two or more users can log on at the same time. Each user has equal access and each interface (HTTP, FTP, telnet console, serial console (CLI), etc.) counts as a logged-in user. Remote Authentication Override: The Rack PDU supports Radius storage of passwords on a server. However, if you enable this override, the Rack PDU will allow a local user to log on using the password for the Rack PDU that is stored locally on the Rack PDU. See also “Local Users” and “Remote Users authentication”. Ping Response Path: Configuration > Security > Ping Response

Select the Enable check box for IPv4 Ping Response to allow the Rack PDU to respond to network pings. Clear the check box to disable an Rack PDU response. This does not apply to IPv6. Local Users Use These menu options to view, and to set up access and individual preferences (like displayed date format), to the Rack PDU user interfaces. This applies to users as defined by their logon name. Path: Configuration > Security > Local Users > Management

Setting user accessWith this option an Administrator or Super User can list and configure the users allowed access to the UI. The Super User user account always has access to the Rack PDU. Click on Add User to add a user. On the resulting User Configuration screen, you can add a user and withhold access by clearing the Access check box. User names and passwords are case-sensitive. The maximum length for both the name and password is 64 bytes, with for multi-byte characters. You have to enter a password. Blank passwords, (passwords with no characters) are not allowed. NOTE: Values greater than 64 bytes in Name and Password might get truncated. To change an Administrator/ Super User setting, you must enter all three password fields. Use Session Timeout to configure the time (3 minutes by default) that the UI waits before logging off an inactive user. If you change this value, you must log off for the change to take effect. NOTE: This timer continues to run if a user closes the browser window without first logging Off by clicking Log Off at the upper right.Because that user is still considered to be logged on, no user can log on until the time specified as Minutes of Inactivity expires. For example, with the default value for Minutes of Inactivity, if a user closes the browser window without logging off, no user can log on for 3 minutes. Serial Remote Authentication OverrideBy selecting this option, you can bypass RADIUS by using the serial console (CLI) connection. This screen enables it for the selected user, but it must also be enabled globally to work, (through the “Session Management” screen). Default settingsDetermine the default values to populate in each of the fields when the Super User or Administrator-level account creates a new user. These values can be changed before the settings are applied to the system. • Access: Put a check in the Enable box to allow access. • User Type: Select the user type from the dropdown menu. • User Description: Type the user Description in the box. • Session Timeout: Select from 1 to 60 seconds. • Bad Login Attempts. Set the number of failed login attempts the user can have. Select from 0 to 99 attempts. 0= unlimited.

96 Rack PDU User Guide User PreferencesThis option is enabled by default. • Event Log Color Coding: Mark the checkbox to enable color-coding of alarm text recorded in the event log. System event entries and configuration change entries do not change color. Text Color Alarm Severity

Red Critical: A critical alarm exists, which requires immediate action. Warning: An alarm condition requires attention and could jeopardize Orange your data or equipment if its cause is not addressed. Green Alarm Cleared: The conditions that caused the alarm have improved. Normal: No alarms are present. The Rack PDU and all connected Black devices are operating normally. • Change the default temperature scale: Select the temperature scale, US Customary (Fahrenheit) or Metric (Celsius), in which to display all temperature measurements in this user interface. • Export Log Format: Configure which format the event log should be displayed in when exported (downloaded). Tab (default) allows fields to be tab-delimited whereas CSV is comma-separated. • Date Format: Select the numerical format in which to display all dates in this user interface. In the selections, each letter m (for month), d (for day), and y (for year) represents one digit. Single-digit days and months are displayed with a leading zero. • Language: Select the user interface display languages from the drop-down box.

Password Requirements • Strong Passwords: Configure whether new passwords created for user accounts will require additional rules such as at least one lowercase character, one uppercase character, one number, and one symbol. • Password Policy: Select the duration (in days) to which the user will be required to change their password. A value of 0 days disables this feature (by default).

Rack PDU User Guide 97 Remote Users Authentication Specify how you want users to be authenticated at logon. Path: Configuration > Security > Remote Users > Authentication

For information about local authentication (not using the centralized authentication of a RADIUS server), see the Security Handbook, available at www.apc.com. The authentication and authorization functions of RADIUS (Remote Authentication Dial-In User Service) is supported. • When a user accesses the Rack PDU or other network-enabled device that has RADIUS enabled, an authentication request is sent to the RADIUS server to determine the User permission level. • RADIUS user names used with the Rack PDU are limited to 32 characters. Select one of the following: • Local Authentication Only: RADIUS is disabled. Local authentication is enabled. • RADIUS, then Local Authentication: RADIUS and local authentication are enabled. Authentication is requested from the RADIUS server first. If the RADIUS server fails to respond, local authentication is used. • RADIUS Only: RADIUS is enabled. Local authentication is disabled. • NOTE: If RADIUS Only is selected, and the RADIUS server is unavailable, or improperly configured, remote access is unavailable to all users. You must use a serial connection to the command line interface and change the access setting to local or radiusLocal to regain access. For example, the command to change the access setting to local would be: radius -a local

RADIUS Path: Configuration > Security > Remote Users > RADIUS

Use this option to do the following: • List the RADIUS servers (a maximum of two) available to the Rack PDU and the time-out period for each. • Click on a link, and configure the parameters for authentication by a new RADIUS server. • Click a listed RADIUS server to display and modify its parameters. RADIUS Setting Definition The server name or IP address (IPv4 or IPv6) of the RADIUS server. Click on a link to configure the server. RADIUS Server NOTE: RADIUS servers use port 1812 by default to authenticate users. The Rack PDU supports ports 1812, 5000 to 32768. Secret The shared secret between the RADIUS server and the Rack PDU. The time in seconds that the Rack PDU waits for a response from the Reply Timeout RADIUS server. Enter the Administrator user name and password to test the RADIUS Test Settings server path that you have configured. Skip Test and Apply Do not test the RADIUS server path. (Not recommended)

98 Rack PDU User Guide Configure the RADIUS Server Summary of the configuration procedure You must configure your RADIUS server to work with the Rack PDU. For examples of the RADIUS users file with Vendor Specific Attributes (VSAs) and an example of an entry in the dictionary file on the RADIUS server, see the Security Handbook. 1. Add the IP address of the Rack PDU to the RADIUS server client list (file). 2. Users must be configured with Service-Type attributes unless Vendor Specific Attributes (VSAs) are defined. If no Service-Type attributes are configured, users will have read-only access (on the Web interface only). See your RADIUS server documentation for information about the RADIUS users file, and see the Security Handbook for an example.

3. VSAs can be used instead of the Service-Type attributes provided by the RADIUS server. VSAs require a dictionary entry and a RADIUS users file. In the dictionary file, define the names for the ATTRIBUTE and VALUE keywords, but not for the numeric values. If you change numeric values, RADIUS authentication and authorization will fail. VSAs take precedence over standard RADIUS attributes.

Configuring a RADIUS server on UNIX® with shadow passwords If UNIX shadow password files are used (/etc/) with the RADIUS dictionary files, the following two methods can be used to authenticate users: • If all UNIX users have administrative privileges, add the following to the RADIUS “user” file. To allow only Device Users, change the APC-Service-Type to Device. DEFAULT Auth-Type = System APC-Service-Type = Admin • Add user names and attributes to the RADIUS “user” file, and verify the password against /etc/ passwd. The following example is for users bconners and thawk: bconners Auth-Type = System APC-Service-Type = Admin thawk Auth-Type = System APC-Service-Type = Device Supported RADIUS servers FreeRADIUS and Microsoft IAS 2003 are supported. Other commonly available RADIUS applications may work but have not been fully tested.

Rack PDU User Guide 99 RADIUS and Network Port Sharing NOTE: See the Security Handbook for Network Management Cards for more information on using RADIUS. For RADIUS users file with VSAs, outlets on guest Rack PDUs can be associated to RADIUS users by using the method in the following example: # give user access to outlets 1, 2, and 3 on unit 1, # outlet 7 on unit 2, outlets 1 through 6 # on unit 3, and outlets 1,2,4 through 6, 7 through 10, # and 20 on unit 4 newOutletUser Auth-Type = Local, User-Password = "newoutlets" APC-Service-Type = Outlet, APC-Outlets = "1[1,2,3];2[7];3[1-6];4[1,2,4-6,7-10,20];"

Firewall Menus Path: Configuration > Security > Firewall

Configuration: Enable or disable the overall firewall functionality. Any configured policy is also listed, even if the firewall is disabled. Active Policy: Select an active policy from the available firewall policies. The validity of policy is also listed here. Active Rules: When a firewall is enabled, this lists the individual rules that are being enforced by a current active policy. You can edit existing rules and add or delete new rules here. Create/Edit Policy: Create a new policy or edit an existing one. Load Policy: Load a policy (with .fwl suffix) from a source external to this device. Test: Temporarily enforce the rules of a chosen policy for a time that you specify.

100 Rack PDU User Guide Network Features TCP/IP and Communication Settings

TCP/IP Path: Configuration > Network > TCP/IP

The TCP/IP option on the left navigation menu, selected by default when you choose Network on the top menu bar, displays the current IPv4 address, subnet mask, default gateway, MAC address, and boot mode of the Rack PDU. For information on DHCP and DHCP options, see RFC2131 and RFC2132.

Setting Description Enable Enable or disable IPv4 with this check box. Manual Configure IPv4 manually by entering the IP address, subnet mask, and default gateway. A BOOTP server provides the TCP/IP settings. At 32-second intervals, the Rack PDU requests network assignment from any BOOTP server: • If the Rack PDU receives a valid response, it starts the network services. • If the Rack PDU finds a BOOTP server, but a request to that server fails or times out, the Rack PDU stops requesting network settings until it is restarted. • By default, if previously configured network settings exist, and the Rack PDU receives BOOTP no valid response to five requests (the original and four retries), it uses the previously configured settings so that it remains accessible. Click Next>> to access the BOOTP Configuration page to change the number of retries or the action to take if all retries fail :1 • Maximum retries: Enter the number of retries that will occur when no valid response is received, or zero (0) for an unlimited number of retries. • If retries fail: Select Use prior settings (the default) or Stop BOOTP request. The default setting. At 32-second intervals, the Rack PDU requests network assignment from any DHCP server. • If the Rack PDU receives a valid response, it does not (as previously) require the APC cookie from the DHCP server in order to accept the lease and start the network services. DHCP • If the Rack PDU finds a DHCP server, but the request to that server fails or times out, it stops requesting network settings until it is restarted.1 • Require vendor specific cookie to accept DHCP Address: By selecting this check box, you can require the DHCP server to provide a cookie which supplies information to the Rack PDU. 1. The default values for these three settings on the configuration pages generally do not need to be changed: •Vendor Class: APC •Client ID: The MAC address of the Rack PDU, which uniquely identifies it on the local area network (LAN) •User Class: The name of the application firmware module

Rack PDU User Guide 101 DHCP response options Each valid DHCP response contains options that provide the TCP/IP settings that the Rack PDU needs to operate on a network, and other information that affects the operation of the Rack PDU. Vendor Specific Information (option 43)The Rack PDU uses this option in a DHCP response to determine whether the DHCP response is valid. This option contains an APC-specific option in a TAG/LEN/DATA format, called the APC Cookie. This is disabled by default. • APC Cookie. Tag 1, Len 4, Data “1APC” Option 43 communicates to the Rack PDU that a DHCP server is configured to service devices. Following, in hexadecimal format, is an example of a Vendor Specific Information option that contains the APC cookie: Option 43 = 0x01 0x04 0x31 0x41 0x50 0x43

TCP/IP optionsThe Rack PDU uses the following options within a valid DHCP response to define its TCP/IP settings. All of these options except the first are described in RFC2132. • IP Address (from the yiaddr field of the DHCP response, described in RFC2131): The IP address that the DHCP server is leasing to the Rack PDU. • Subnet Mask (option 1): The Subnet Mask value that the Rack PDU needs to operate on the network. • Router, i.e., Default Gateway (option 3): The default gateway address that the Rack PDU needs to operate on the network. • IP Address Lease Time (option 51): The time duration for the lease of the IP Address to the Rack PDU. • Renewal Time, T1 (option 58): The time that the Rack PDU must wait after an IP address lease is assigned before it can request a renewal of that lease. • Rebinding Time, T2 (option 59): The time that the Rack PDU must wait after an IP address lease is assigned before it can seek to rebind that lease.

Other optionsThe Rack PDU also uses these options within a valid DHCP response. All of these options except the last are described in RFC2132. • Network Time Protocol Servers (option 42): Up to two NTP servers (primary and secondary) that the Rack PDU can use. • Time Offset (option 2): The offset of the Rack PDU's subnet, in seconds, from Coordinated Universal Time (UTC). • Domain Name Server (option 6): Up to two Domain Name System (DNS) servers (primary and secondary) that the Rack PDU can use. • Host Name (option 12): The host name that the Rack PDU will use (32-character maximum length). • Domain Name (option 15): The domain name that the Rack PDU will use (64-character maximum length). • Boot File Name (from the file field of the DHCP response, described in RFC2131): The fully qualified directory-path to a user configuration file (.ini file) to download. The siaddr field of the DHCP response specifies the IP address of the server from which the Rack PDU will download the .ini file. After the download, the .ini file is used as a boot file to reconfigure the settings.

102 Rack PDU User Guide Path: Configuration > Network > TCP/IP > IPv6 settings

Setting Description

Enable Enable or disable IPv6 with this check box. Manual Configure IPv6 manually by entering the IP address and the default gateway. When the Auto Configuration check box is selected, the system obtains addressing Auto prefixes from the router (if available). It uses those prefixes to automatically configure Configuration IPv6 addresses. Router Controlled: Selecting this option means that DHCPv6 is controlled by the Managed(M) and Other(O) flags received in IPv6 router advertisements. When a router advertisement is received, the Rack PDU checks whether the M or the O flag is set. The Rack PDU interprets the state of the M (Managed Address Configuration Flag) and O (Other Stateful Configuration Flag) "bits" for the following cases: • Neither is set: Indicates the local network has no DHCPv6 infrastructure. The Rack PDU uses router advertisements and manual configuration to get addresses that are not link-local and other settings. • M, or M and O are set: In this situation, full DHCPv6 address configuration occurs. DHCPv6 is used to obtain addresses AND other configuration settings. This is known as DHCPv6 stateful. Once the M flag has been received, the DHCPv6 address configuration stays in effect until the interface in question has been closed. This is true even if subsequent router advertisement packets are received in which DHCPv6 the M flag is not set. Mode If an O flag is received first, then an M flag is received subsequently, the Rack PDU performs full address configuration upon receipt of the M flag • Only O is set: In this situation, the Rack PDU sends a DHCPv6 Info-Request packet. DHCPv6 will be used to configure “other” settings (such as location of DNS servers), but NOT to provide addresses. This is known as DHCPv6 stateless. Address and Other Information: With this radio box selected, DHCPv6 is used to obtain addresses AND other configuration settings. This is known as DHCPv6 stateful. Non-Address Information Only: With this radio box selected, DHCPv6 will be used to configure "other" settings (such as location of DNS servers), but NOT to provide addresses. This is known as DHCPv6 stateless. Never: Select this to disable DHCPv6.

Port Speed Path: Configuration > Network > Port Speed

The Port Speed setting defines the communication speed of the TCP/IP port. • For Auto-negotiation (the default), Ethernet devices negotiate to transmit at the highest possible speed, but if the supported speeds of two devices are unmatched, the slower speed is used. • Alternatively, you can choose 10 Mbps or 100 Mbps, each with the option of half-duplex (communication in only one direction at a time) or full-duplex (communication in both directions on the same channel simultaneously).

Rack PDU User Guide 103 DNS Path: Configuration > Network > DNS > Configuration

Use the options under Configuration to configure and test the Domain Name System (DNS): • Override Manual DNS Settings: Selection of Override Manual DNS Settings will result in configuration data from other sources (typically DHCP) taking precedence over the manual configurations set here. • Select Primary DNS Server or Secondary DNS Server to specify the IPv4 or IPv6 addresses of the primary and optional secondary DNS server. For the Rack PDU to send e-mail, you must at least define the IP address of the primary DNS server. – The Rack PDU waits up to 15 seconds for a response from the primary DNS server or secondary DNS server (if specified). If the Rack PDU does not receive a response within that time, e-mail cannot be sent. Use DNS servers on the same segment as the Rack PDU or on a nearby segment (but not across a wide-area network [WAN]). – Define the IP addresses of the DNS servers then enter the DNS name of a computer on your network to look up the IP address for that computer to verify correct operation. • System Name Synchronization: Allow the system name to be synchronized with the host name so both fields automatically contain the same value. NOTE: When enabling this feature, the system name identifier can no longer contain a space character (since it will be synchronized to the host name field). • Host Name: Configure a host name here and a domain name in the Domain Name field then users can enter a host name in any field in the Rack PDU interface (except e-mail addresses) that accepts a domain name. • Domain Name (IPv4/IPv6): Configure the domain name here only. In all other fields in the Rack PDU interface (except e-mail addresses) that accept domain names, the Rack PDU adds this domain name when only a host name is entered. – To override all instances of the expansion of a specified host name by the addition of the domain name, set the domain name field to its default, somedomain.com, or to 0.0.0.0. – To override the expansion of a specific host name entry, include a trailing period. The Rack PDU recognizes a host name with a trailing period (such as mySnmpServer.) as if it were a fully-qualified domain name and does not append the domain name. • Domain Name (IPv6): Specify the IPv6 domain name here. Test Path: Configuration > Network > DNS > Test

Use this option to send a DNS query that tests the setup of your DNS servers by looking up the IP address. View the result of a test in the Last Query Response field. • Select test to send a DNS query that tests the setup of your DNS servers: –As Query Question, identify the value to be used for the selected query type: Query Type Selected Query Question to Use

by Host The URL by FQDN The fully qualified domain name, my_server.my_domain by IP The IP address by MX The Mail Exchange address

104 Rack PDU User Guide Web Path: Configuration > Network > Web > Configuration

Option Description

To activate changes to any of these selections, log off from the Rack PDU: • Disable: Disables access to the Web interface. (To re-enable access, log in to the command line interface, then type the command http -S enable. For HTTPS access, type https -S enable.) • Enable HTTP (the default): Enables Hypertext Transfer Protocol (HTTP), which provides Web access by user name and password, but does not encrypt user names, passwords, and data during transmission. • Enable HTTPS: Enables Hypertext Transfer Protocol (HTTPS) over Secure Sockets Layer (SSL). SSL encrypts user names, passwords, and data during transmission, and authenticates the Rack PDU by digital certificate. When HTTPS is enabled, your browser displays a small lock icon.

access See “Creating and Installing Digital Certificates” in the Security Handbook, available at www.apc.com.

HTTP Port: The TCP/IP port (80 by default) used to communicate by HTTP with the Rack PDU.

HTTPS Port: The TCP/IP port (443 by default) used to communicate by HTTPS with the Rack PDU. For either of these ports, you can change the port setting to any unused port from 5000 to 32768 for additional security. Users must then use a colon (:) in the address field of the browser to specify the port number. For example, for a port number of 5000 and an IP address of 152.214.12.114: http://152.214.12.114:5000 https://152.214.12.114:5000 Add, replace, or remove a security certificate.

Status: • Not installed: A certificate is not installed, or was installed by FTP or SCP to an incorrect location. Using Add or Replace Certificate File installs the certificate to the correct location, /ssl on the Rack PDU. • Generating: The Rack PDU is generating a certificate because no valid certificate was found. • Loading: A certificate is being activated on the Rack PDU. • Valid certificate: A valid certificate was installed or was generated by the Rack PDU. ssl Click on this link to view the contents of the certificate. certificate If you install an invalid certificate, or if no certificate is loaded when you enable SSL, the Rack PDU generates a default certificate, a process which delays access to the interface for up to one minute. You can use the default certificate for basic encryption-based security, but a security alert message displays whenever you log on.

Add or Replace Certificate File: Enter or browse to the certificate file created with the Security Wizard.

See “Creating and Installing Digital Certificates” in the Security Handbook, available at www.apc.com, to choose a method for using digital certificates created by the Security Wizard or generated by the Rack PDU.

Remove: Delete the current certificate.

Rack PDU User Guide 105 Console Path: Configuration > Network > Console > options

Option Description

• Disable: Disables all access to the command line interface. • Enable Telnet (the default): Telnet transmits user names, passwords, and data without encryption. • Enable SSH: SSH transmits user names, passwords, and data in encrypted form, providing protection from attempts to intercept, forge, or alter data during transmission. Configure the ports to be used by these protocols: • Telnet Port: The Telnet port used to communicate with the Rack PDU (23 by default). You can change the port setting to any unused port from 5000 to 32768 for additional access security. Users must then use a colon (:) or a space, as required by your Telnet client program, to specify the non-default port. For example, for port 5000 and an IP address of 152.214.12.114, your Telnet client requires one of the these commands: telnet 152.214.12.114:5000 telnet 152.214.12.114 5000 • SSH Port: The SSH port used to communicate with the Rack PDU (22 by default). You can change the port setting to any unused port from 5000 to 32768 for additional security. See the documentation for your SSH client for the command line format required to specify a non-default port. Status indicates the status of the host key (private key): • SSH Disabled: No host key in use: When disabled, SSH cannot use a host key. • Generating: The Rack PDU is creating a host key because no valid host key was found. • Loading: A host key is being activated on the Rack PDU. • Valid: One of the following valid host keys is in the /ssh directory (the required location on the Rack PDU): •A 1024-bit or 2048-bit host key created by the Security Wizard ssh host •A 2048-bit RSA host key generated by the Rack PDU key Add or Replace: Browse to and upload a host key file created by the Security Wizard.

To use the Security Wizard, see the Security Handbook, available at www.apc.com.

NOTE: To reduce the time required to enable SSH, create and upload a host key in advance. If you enable SSH with no host key loaded, the Rack PDU takes up to one minute to create a host key, and the SSH server is not accessible during that time.

Remove: Remove the current host key.

NOTE: To use SSH, you must have an SSH client installed. Most Linux and other UNIX platforms include an SSH client, but operating systems do not. Clients are available from various vendors.

106 Rack PDU User Guide SNMP All user names, passwords, and community names for SNMP are transferred over the network as plain text. If your network requires the high security of encryption, disable SNMP access or set the access for each community to Read. (A community with Read access can receive status information and use SNMP traps.) When using StruxureWare to manage a Rack PDU on the public network, you must have SNMP enabled in the Rack PDU interface. Read access will allow the StruxureWare to receive traps from the Rack PDU, but Write access is required while you use the interface of the Rack PDU to set the StruxureWare as a trap receiver. For detailed information on enhancing and managing the security of your system, see the Security Handbook, available at www.apc.com.

Network Port Sharing All Rack PDUs in a group can be accessed through the Host Rack PDU via SNMP "rPDU2" OIDs available in our PowerNet-MIB. The full path to these OIDs is: iso(1).org(3).dod(6).internet(1).private(4).enterprises(1).apc(318).products(1). hardware(1).rPDU2(26) Individual Rack PDUs can be identified in the SNMP MIB tables by viewing the corresponding "Module" OIDs in each table. These Module OIDs will return the Display ID of the Rack PDU. Example Module OIDs: rPDU2IdentModule, rPDU2DeviceConfigModule, rPDU2SensorTempHumidityConfigModule In order to be backwards compatible with previous versions, the Host Rack PDU will always be the first index in any table that supports multiple Rack PDUs. In addition, after the Rack PDU group is set up, the index order of guest Rack PDUs should not change even if the Display ID is changed or a PDU temporarily loses communication. The index order should only change if you manually remove a Rack PDU from the group. A MIB table walk should skip the indexes associated with a Rack PDU that has temporarily lost communication.

Rack PDU User Guide 107 SNMPv1 Path: Configuration > Network > SNMPv1 > options

Option Description

Enable SNMPv1 Access: Enables SNMP version 1 as a method of communication with access this device. You can configure up to four access control entries to specify which Network Management Systems (NMSs) have access to this device. The opening page for access control, by default, assigns one entry to each of the four available SNMPv1 communities, but you can edit these settings to apply more than one entry to any community to grant access by several specific IPv4 and IPv6 addresses, host names, or IP address masks. To edit the access control settings for a community, click its community name. • If you leave the default access control entry unchanged for a community, that community has access to this device from any location on the network. • If you configure multiple access control entries for one community name, the limit of four entries requires that one or more of the other communities must have no access control entry. If no access control entry is listed for a community, that community has no access to this device. Community Name: The name that an NMS must use to access the community. The maximum length is 15 ASCII characters, and the default community names for the four communities are public, private, public2, and private2. access NMS IP/Host Name: The IPv4 or IPv6 address, IP address mask, or host name that control controls access by NMSs. A host name or a specific IP address (such as 149.225.12.1) allows access only by the NMS at that location. IP addresses that contain 255 restrict access as follows: • 149.225.12.255: Access only by an NMS on the 149.225.12 segment. • 149.225.255.255: Access only by an NMS on the 149.225 segment. • 149.255.255.255: Access only by an NMS on the 149 segment. • 0.0.0.0 (the default setting) which can also be expressed as 255.255.255.255: Access by any NMS on any segment. Access Type: The actions an NMS can perform through the community. • Read: GETS only, at any time • Write: GETS at any time, and SETS when no user is logged onto the Web interface or command line interface. • Write+: GETS and SETS at any time. • Disable: No GETS or SETS at any time.

108 Rack PDU User Guide SNMPv3 Path: Configuration > Network > SNMPv3 > options

For SNMP GETs, SETs, and trap receivers, SNMPv3 uses a system of user profiles to identify users. An SNMPv3 user must have a user profile assigned in the MIB software program to perform GETs and SETs, browse the MIB, and receive traps. NOTE: To use SNMPv3, you must have a MIB program that supports SNMPv3. The Rack PDU supports SHA or MD5 authentication and AES or DES encryption.

Option Description

access SNMPv3 Access: Enables SNMPv3 as a method of communication with this device. By default, lists the settings of four user profiles, configured with the user names apc snmp profile1 through apc snmp profile4, and no authentication and no privacy (no encryption). To edit the following settings for a user profile, click a user name in the list.

User Name: The identifier of the user profile. SNMP version 3 maps GETs, SETs, and traps to a user profile by matching the user name of the profile to the user name in the data packet being transmitted. A user name can have up to 32 ASCII characters.

Authentication Passphrase: A phrase of 15 to 32 ASCII characters (apc auth passphrase, by default) that verifies that the NMS communicating with this device through SNMPv3 is the NMS it claims to be, that the message has not been changed during transmission, and that the message was communicated in a timely manner, indicating that it was not delayed and that it was not copied and sent again later at an inappropriate time. user profiles Privacy Passphrase: A phrase of 15 to 32 ASCII characters (apc crypt passphrase, by default) that ensures the privacy of the data (by means of encryption) that an NMS is sending to this device or receiving from this device through SNMPv3.

Authentication Protocol: The Schneider Electric implementation of SNMPv3 supports SHA and MD5 authentication. Authentication will not occur unless an authentication protocol is selected.

Privacy Protocol: The implementation of SNMPv3 supports AES and DES as the protocols for encrypting and decrypting data. Privacy of transmitted data requires that a privacy protocol is selected and that a privacy passphrase is provided in the request from the NMS. When a privacy protocol is enabled but the NMS does not provide a privacy passphrase, the SNMP request is not encrypted.

NOTE: You cannot select the privacy protocol if no authentication protocol is selected.

Rack PDU User Guide 109 Option Description

You can configure up to four access control entries to specify which NMSs have access to this device. The opening page for access control, by default, assigns one entry to each of the four user profiles, but you can edit these settings to apply more than one entry to any user profile to grant access by several specific IP addresses, host names, or IP address masks. • If you leave the default access control entry unchanged for a user profile, all NMSs that use that profile have access to this device. • If you configure multiple access entries for one user profile, the limit of four entries requires that one or more of the other user profiles must have no access control entry. If no access control entry is listed for a user profile, no NMS that uses that profile has any access to this device.

To edit the access control settings for a user profile, click its user name.

access Access: Mark the Enable checkbox to activate the access control specified by the control parameters in this access control entry. User Name: From the drop-down list, select the user profile to which this access control entry will apply. The choices available are the four user names that you configure through the user profiles option on the left navigation menu.

NMS IP/Host Name: The IP address, IP address mask, or host name that controls access by the NMS. A host name or a specific IP address (such as 149.225.12.1) allows access only by the NMS at that location. An IP address mask that contains 255 restricts access as follows: • 149.225.12.255: Access only by an NMS on the 149.225.12 segment. • 149.225.255.255: Access only by an NMS on the 149.225 segment. •149.255.255.255: Access only by an NMS on the 149 segment. • 0.0.0.0 (the default setting) which can also be expressed as 255.255.255.255: Access by any NMS on any segment.

FTP Server Path: Configuration > Network > FTP Server

The FTP Server settings enable (by default) or disable access to the FTP server and specify the TCP/IP port (21 by default) that the FTP server uses to communicate with the Rack PDU. The FTP server uses both the specified port and the port one number lower than the specified port. You can change the Port setting to the number of any unused port from 5001 to 32768 for added security. Users must then use a colon (:) to specify the non-default port number. For example, for port 5001 and IP address 152.214.12.114, the command would be ftp 152.214.12.114:5001. NOTE: FTP transfers files without encryption. For higher security, disable the FTP server, and transfer files with SCP. Selecting and configuring Secure SHell (SSH) enables SCP automatically. At any time that you want a Rack PDU to be accessible for management by StruxureWare, FTP Server must be enabled in the Rack PDU interface. For detailed information on enhancing and managing the security of your system, see the Security Handbook, available at www.apc.com.

110 Rack PDU User Guide Notifications Event Actions Path: Configuration > Notification

Types of notification You can configure event actions to occur in response to an event or group of events. These actions notify users of the event in any of several ways: • Active, automatic notification. The specified users or monitoring devices are contacted directly. – E-mail notification –SNMP traps – Remote Monitoring Service – Syslog notification • Indirect notification – Event log. If no direct notification is configured, users must check the log to determine which events have occurred You can also log system performance data to use for device monitoring. See “Logs in the Configuration Menu” on page 119 for information on how to configure and use this data logging option. – Queries (SNMP GETs) For more information, see “SNMP” on page 107. SNMP enables an NMS to perform informational queries. For SNMPv1, which does not encrypt data before transmission, configuring the most restrictive SNMP access type (READ) enables informational queries without the risk of allowing remote configuration changes.

Configure event actions Path: Configuration > Notification > Event Actions > By Event

By default, logging an event is selected for all events. To define event actions for an individual event: 1. To find an event, click on a column heading to see the lists under the Device Events or System Events categories. Or you can click on a sub-category under these headings, like Security or Temperature. 2. Click on the event name to view or change the current configuration, such as recipients to be notified by e-mail, or Network Management Systems (NMSs) to be notified by SNMP traps. If no Syslog server is configured, items related to Syslog configuration are not displayed.

NOTE: When viewing details of an event configuration, you can enable or disable event logging or Syslog, or disable notification for specific e-mail recipients or trap receivers, but you cannot add or remove recipients or receivers. To add or remove recipients or receivers, see the following: • “Identifying Syslog servers” on page 119 • “Configuration > Notification > E-mail > Recipients” on page 114 • “SNMP trap receiver screen” on page 115

Rack PDU User Guide 111 Path: Configuration > Notification > Event Actions > By Group

To configure a group of events simultaneously:

1. Select how to group events for configuration:

–Select Events by Severity, and then select one or more severity levels. You cannot change the severity of an event.

–Select Events by Category, and then select all events in one or more pre-defined categories.

2. Click Next to to the next screen to do the following: – Select event actions for the group of events.

• To select any action except Logging (the default), you must first have at least one relevant recipient or receiver configured.

• If you selected Logging and have configured a Syslog server, select Event Log or Syslog on the next screen. See “Logs in the Configuration Menu” on page 119

3. Click Next to move to the next screen to do the following: – If you selected Logging on the previous screen, select Enable Notifications or Disable Notification. – If you selected Email Recipients on the previous screen, select the e-mail recipients to configure. – If you selected Trap Receivers on the previous screen, select the trap receiver to configure.

4. Click Next to move to the next screen to do the following: – If you are configuring Logging settings, view the pending actions and click Apply to accept the changes or click Cancel to revert to the previous settings. – If you are configuring Email Recipients or Trap Receivers, select Enable Notifications or Disable Notification and set the notification timing settings (see “Notification parameters:” on page 113 for more information on these settings).

5. Click Next to move to the next screen to do the following: – View the pending actions and click Apply to accept the changes or click Cancel to revert to the previous settings.

112 Rack PDU User Guide Notification parameters: These configuration fields define e-mail parameters for sending notifications of events. They are usually accessed by clicking the receiver or recipient name. Field Description

Delay n time before If the event persists for the specified time, the notification is sent. If the sending condition clears before the time expires, no notification is sent. The notification is sent repeatedly at the specified interval (the default is Repeat at an interval of n every 2 minutes until the condition clears). Up to n times During an active event, the notification repeats for this number of times. or The notification is sent repeatedly until the condition clears or is Until condition clears resolved.

NOTE: For events that have an associated clearing event, you can also set these parameters.

E-mail notification screens

Use Simple Mail Transfer Protocol (SMTP) to send e-mail to up to four recipients when an event occurs. To use the e-mail feature, you must define the following settings: • The IP addresses of the primary and, optionally, the secondary Domain Name System (DNS) servers. • The IP address or DNS name for the SMTP Server and From Address. • The e-mail addresses for a maximum of four recipients. • You can use the To Address setting of the recipients option to send e-mail to a text-based screen. Path: Configuration > Notification > E-mail > Server

This screen lists your primary and secondary DNS servers and displays the following fields: From Address: The contents of the From field in e-mail messages sent by the Rack PDU: • In the format user@ [IP_address] (if an IP address is specified as Local SMTP Server) • In the format user@domain (if DNS is configured and the DNS name is specified as Local SMTP Server) in the e-mail messages. NOTE: The local SMTP server may require that you use a valid user account on the server for this setting. See the server documentation. SMTP Server: The IPv4/ IPv6 address or DNS name of the local SMTP server. NOTE: This definition is required only when the SMTP server is set to Local. Authentication: Enable this if the SMTP server requires authentication. Port: The SMTP port number, with a default of 25. The range is 25, 465, 587, 5000 to 32768. User Name, Password, and Confirm Password: If your mail server requires authentication, enter your user name and password here. This performs a simple authentication, not SSL. Use SSL/TLS: Select when encryption is used. • Never: The SMTP server does not require nor support encryption. • If Supported: The SMTP server advertises support for STARTTLS but doesn't require the connection to be encrypted. The STARTTLS command is sent after the advertisement is given. • Always: The SMTP server requires the STARTTLS command to be sent on connection to it. • Implicitly: The SMTP server only accepts connections that begin encrypted. No STARTTLS message is sent to the server.

Rack PDU User Guide 113 Require CA Root Certificate: This should only be enabled if the security policy of your organization does not allow for implicit trust of SSL connections. If this is enabled, a valid root CA certificate must be loaded onto the Rack PDU for encrypted e-mails to be sent. File Name: This field is dependent on the root CA certificates installed on the Rack PDU and whether or not a root CA certificate is required. Path: Configuration > Notification > E-mail > Recipients

Specify up to four e-mail recipients. Click on a name to configure the settings. Generation: Enables (default) or disables sending e-mail to the recipient. To Address: The user and domain names of the recipient. To use e-mail for paging, use the e-mail address for the recipient’s pager gateway account (for example, [email protected]). The pager gateway will generate the page.

To bypass the DNS lookup of the IP address of the mail server, use the IP address in brackets instead of the e- mail domain name, e.g., use jsmith@[xxx.xxx.x.xxx] instead of [email protected]. This is useful when DNS lookups are not working correctly. Language: The language which the e-mail notification will be sent in. This is dependent on the installed language pack (if applicable). Port: The SMTP port number, with a default of 25. The range is 25, 465, 587, 5000 to 32768. Format: The long format contains name, location, contact, IP address, serial number of the device, date and time, event code, and event description. The short format provides only the event description. Server: Select one of the following methods for routing e-mail: • Local: This is through the site-local SMTP server. This recommended setting ensures that the e- mail is sent using the site-local SMTP server. Choosing this setting limits delays and network outages and retries sending e-mail for many hours. When choosing the Local setting you must also enable forwarding at the SMTP server of your device and set up a special external e-mail account to receive the forwarded e-mail. Check with your SMTP server administrator before making these changes. • Recipient: This is the SMTP server of the recipient. The Rack PDU performs an MX record look- up on the recipients e-mail address and uses that as its SMTP server. The e-mail is only sent once so it could easily be lost. • Custom: This setting enables each e-mail recipient to have its own server settings. These settings are independent of the settings given under “SMTP Server” above. Path: Configuration > Notification > E-mail > SSL Certificates

Load a mail SSL certificate on the Rack PDU for greater security. The file must have an extension of .crt or .cer. Up to five files can be loaded at any given time. When installed, the certificate details also display here. An invalid certificate will display “n/a” for all fields except File Name. Certificates can be deleted using this screen. Any e-mail recipients using the certificate should be manually modified to remove reference to this certificate. Path: Configuration > Notification > E-mail > Test

Send a test message to a configured recipient.

114 Rack PDU User Guide SNMP trap receiver screen

Path: Configuration > Notification > SNMP Traps > Trap Receivers

With Simple Network Management Protocol (SNMP) traps, you can automatically get notifications for significant Rack PDU events. They are a useful tool for monitoring devices on your network. The trap receivers are displayed by NMS IP/Host Name, where NMS stands for Network Management System. You can configure up to six trap receivers. To configure a new trap receiver, click Add Trap Receiver. To edit (or delete) one, click its IP address/host name. Trap Generation: Enable (the default) or disable trap generation for this trap receiver. NMS IP/Host Name: The IPv4/ IPv6 address or host name of this trap receiver. The default, 0.0.0.0, leaves the trap receiver undefined. Language: Select a language from the drop-down list. This can differ from the UI and from other trap receivers. Select either the SNMPv1 or SNMPv3 radio button to specify the trap type. For an NMS to receive both types of traps, you must separately configure two trap receivers for that NMS, one for each trap type. SNMPv1: Settings for SNMPv1. • Community Name: The name (“public” by default) used as an identifier when SNMPv1 traps are sent to this trap receiver. • Authenticate Traps: When this option is enabled (the default), the NMS identified by the NMS IP/ Host Name setting will receive authentication traps (traps generated by invalid attempts to log on to this device). SNMPv3: Settings for SNMPv3. • User Name: Select the identifier of the user profile for this trap receiver. If you delete a trap receiver, all notification settings configured under “Configuring event actions” for the deleted trap receiver are set to their default values. SNMP traps test screen Path: Configuration > Notification > SNMP Traps > Test

Last Test Result: The result of the most recent SNMP trap test. A successful SNMP trap test verifies only that a trap was sent; it does not verify that the trap was received by the selected trap receiver. A trap test succeeds if all of the following are true: • The SNMP version (SNMPv1 or SNMPv3) configured for the selected trap receiver is enabled on this device. • The trap receiver itself is enabled. • If a host name is selected for the To address, that host name can be mapped to a valid IP address. To: Select the IP address or host name to which a test SNMP trap will be sent. If no trap receiver is configured, a link to the Trap Receiver configuration screen is displayed.

Rack PDU User Guide 115 Remote Monitoring Service Path: Configuration > Notification > Remote Monitoring

The remote monitoring service (RMS) is an optional service from APC by Schneider Electric that monitors your system from a remote operation center 24 hours a day, 7 days a week, and notifies you of device and system events. To purchase the RMS service, contact your vendor or click on the link on the top part of this screen: APC by Schneider Electric RMS Web site.

Registration.To activate APC by Schneider Electric RMS for the Rack PDU, select Enable Remote Monitoring Service., choose between Register Company and Device and Register Device Only, complete the form, and click Send APC RMS Registration. Use the Reset Remote Monitoring Service Registration check box to discontinue the service, whether permanently or temporarily (for example, if you are moving a Rack PDU).

116 Rack PDU User Guide General Menu This menu contains miscellaneous configuration items including device identification, date and time, exporting and importing your Rack PDU configuration options, the three links at the bottom left of the screen, and consolidating data for troubleshooting purposes.

Identification screen Path: Configuration > General > Identification

Define the Name, the Location (the physical location), and the Contact (the person responsible for the device) used by: • the SNMP agent of the Rack PDU and • StruxureWare Specifically, the name field is used by the sysName, sysContact, and sysLocation object identifiers (OIDs) in the SNMP agent of the Rack PDU. For more information about MIB-II OIDs, see the PowerNet® SNMP Management Information Base (MIB) Reference Guide, available at www.apc.com. The Name and Location fields also identify the device when you register for the Remote Monitoring Service. Host Name Synchronization allows the host name to be synchronized with the system name so both fields automatically contain the same value. NOTE: When enabling this feature, the system name identifier can no longer contain a space character (since it will be synchronized to the host name field).

System Message: When defined, a custom message will appear on the log on screen for all users.

Date/Time screen Path: Configuration > General > Date/Time > Mode

Set the time and date used by the Rack PDU. You can change the current settings manually or through a Network Time Protocol (NTP) Server: With both, you select the Time Zone. This is your local time difference with Coordinated Universal Time (UTC), also known as Greenwich Mean Time (GMT). Manual Mode: Do one of the following: • Enter the date and time for the Rack PDU • Select the check box Apply Local Computer Time to apply the date and time settings of the computer you are using Synchronize with NTP Server: Have an NTP (Network Time Protocol) Server define the date and time for the Rack PDU. By default, any Rack PDU on the private side of a StruxureWare obtains its time settings by using StruxureWare as an NTP server. • Override Manual NTP Settings: If you select this, data from other sources (typically DHCP) take precedence over the NTP configurations you set here. • Primary NTP Server: Enter the IP address or domain name of the primary NTP server. • Secondary NTP Server: Enter the IP address or domain name of the secondary NTP server, when a secondary server is available. • Update Interval: Define, in hours, how often the Rack PDU accesses the NTP Server for an update. Minimum: 1; Maximum: 8760 (1 year). • Update Using NTP Now: Initiate an immediate update of the date and time by the NTP Server.

Rack PDU User Guide 117 Daylight Saving Path: Configuration > General > Date /Time > Daylight Saving

Daylight Saving Time (DST) is disabled by default. You can enable traditional United States DST, or enable and configure a customized daylight saving time to match how Daylight Saving Time is implemented in your local area. When customizing DST, the system puts the clock forward by an hour when the time and date you specify under Start is reached and puts the clock back an hour when the time and date you specify under End is reached. • If your local DST always starts or ends on the fourth occurrence of a specific weekday of a month (e.g., the fourth Sunday), choose Fourth/Last. If a fifth Sunday occurs in that month, you should still choose Fourth/Last. • If your local DST always starts or ends on the last occurrence of a specific weekday of a month, whether it is the fourth or the fifth occurrence, choose Fifth/Last. Creating and importing settings with the config file Path: Configuration > General > User Config File

Use the settings from one Rack PDU to configure another. Retrieve the config.ini file from the configured Rack PDU, customize that file (e.g., change the IP address), and upload the customized file to the new Rack PDU. The file name can be up to 64 characters, and must have the.ini suffix. Reports the progress of the upload. The upload succeeds even if the file contains errors, Status but a system event reports the errors in the event log. Browse to the customized file and upload it so that the current Rack PDU can use it to set Upload its own configuration. Allows the download of the Configuration File (config.ini) file directly through the web Download browser to the user's computer.

To retrieve and customize the file of a configured Rack PDU, see “How to Export Configuration Settings” on page 131. Instead of uploading the file to one Rack PDU, you can export the file to multiple Rack PDUs by using an FTP or SCP script.

Configure Links Path: Configuration > General > Quick Links

Select Configuration > General > Quick Links to view and change the URL links displayed at the bottom left of each page of the interface. By default, these links access the following Web pages: • Link 1: The home page of the APC by Schneider Electric website • Link 2: Demonstrations of APC by Schneider Electric web-enabled products • Link 3: Information on APC by Schneider Electric Remote Monitoring Service

118 Rack PDU User Guide Logs in the Configuration Menu

Identifying Syslog servers Path: Configuration > Logs > Syslog > Servers

Click Add Server to configure a new Syslog server.

Syslog Server: Uses IPv4/ IPv6 addresses or host names to identify from one to four servers to receive Syslog messages sent by the Rack PDU.

Port: The port that the Rack PDU will use to send Syslog messages. The default UDP port assigned to Syslog is 514.

Language: Select the language for any Syslog messages.

Protocol: Select either UDP or TCP.

Syslog settings Path: Configuration > Logs > Syslog > Settings

Message Generation: Enable the generation and the logging of Syslog messages for events that have Syslog configured as a notification method.

Facility Code: Selects the facility code assigned to the Syslog messages of the Rack PDU (User, by default). NOTE: User best defines the Syslog messages sent by the Rack PDU. Do not change this selection unless advised to do so by the Syslog network or system administrator.

Severity Mapping: This section maps each severity level of the Rack PDU or environment events to available Syslog priorities. The local options are Critical, Warning, and Informational. You should not need to change the mappings. • Emergency: The system is unusable • Alert: Action must be taken immediately • Critical: Critical conditions • Error: Error conditions • Warning: Warning conditions • Notice: Normal but significant conditions • Informational: Informational messages • : Debug-level messages The following are the default settings for the Local Priority settings: • Critical is mapped to Critical • Warning is mapped to Warning • Informational is mapped to Info

Rack PDU User Guide 119 Syslog test and format example Path: Configuration > Logs > Syslog > Test

Send a test message to the Syslog servers (configured through the “Identifying Syslog servers” option above). The result will be sent to all configured Syslog servers. Select a severity to assign to the test message and then define the test message. Format the message to consist of the event type (for example, APC, System, or Device) followed by a colon, a space, and the event text. The message can have a maximum of 50 characters. • The priority (PRI): the Syslog priority assigned to the message event, and the facility code of messages sent by the Rack PDU. • The Header: a time stamp and the IP address of the Rack PDU. • The message (MSG) part: • The TAG field, followed by a colon and space, identifies the event type. • The CONTENT field is the event text, followed (optionally) by a space and the event code. Example: APC: Test Syslog is valid.

120 Rack PDU User Guide Tests Tab

Setting the Rack PDU LCD or LED Lights to Blink

Path: Tests > Network > LED Blink

If you are having trouble finding your Rack PDU, enter a number of minutes in the LED Blink Duration field, click Apply, and the Status and Link LED lights on the display will blink.

Path: Tests > RPDU > LCD Blink

Under this menu, you can enter a number of minutes in the LCD Blink Duration field, click Apply and the LCD backlight will begin blinking.

Rack PDU User Guide 121 Logs Tab

Event, Data and Firewall Logs

Event log Path: Logs > Events

By default, the log displays all events recorded during the last two days, starting with the latest events. Additionally, the log records any event that sends an SNMP trap, except SNMP authentication failures, and abnormal internal system events. You can enable color coding for events on the Configuration > Security > Local Users Management screen.

122 Rack PDU User Guide Path: Logs > Events > Log

By default, the event log displays the most recent events first. To see the events listed together on a Web page, click Launch Log in New Window. To open the log in a text file or to save the log to disk, click on the floppy disk icon( ) on the same line as the Event Log heading. You can also use FTP or Secure CoPy (SCP) to view the event log. See “Use FTP or SCP to retrieve log files” on page 126.

Filtering event logs: Use filtering to omit information you don’t want to display. • Filtering the log by date or time: Use the Last or From radio buttons. (The filter configuration is saved until the Rack PDU restarts.) • Filtering the log by event severity or category: – Click Filter Log. – Clear a check box to remove it from view. – After you click Apply, text at the upper right corner of the Event Log page indicates that a filter is active. The filter is active until you clear it or until the Rack PDU restarts. • Removing an active filter: – Click Filter Log. – Click Clear Filter (Show All). – As Administrator, click Save As Default to save this filter as the new default log view for all users. Important points on filtering: • Events are processed through the filter using OR logic. If you apply a filter, it works regardless of the other filters. • Events that you cleared in the Filter By Severity list never display in the filtered Event Log, even if selected in the Filter by Category list. • Similarly, events that you clear in the Filter by Category list never display in the filtered Event Log.

Deleting event logs: To delete all events, click Clear Log. Deleted events cannot be retrieved. To disable the logging of events based on their assigned severity level or their event category, see “Configure event actions” on page 111 Path: Logs > Events > Reverse Lookup

With reverse lookup enabled, when a network-related event occurs, both the IP address and the domain name for the networked device with the event are logged in the event log. If no domain name entry exists for the device, only its IP address is logged with the event. Since domain names generally change less frequently than IP addresses, enabling reverse lookup can improve the ability to identify addresses of networked devices that are causing events. Reverse lookup is disabled by default. You should not need to enable it if you have no DNS server configured or have poor network performance because of heavy network traffic.

Rack PDU User Guide 123 Path: Logs > Events > Size

Use Event Log Size to specify the maximum number of log entries. NOTE: When you resize the event log in order to specify a maximum size, all existing log entries are deleted. When the log subsequently reaches the maximum size, the older entries are deleted. Network Port Sharing event logs and traps Rack PDU events from guest Rack PDUs are sent to the host Rack PDU for inclusion into its log. The log entry will include the Display ID of the unit that the event occurred on. These events are then handled the same as local events from the host PDU. Therefore alarms, SNMP traps, e- mails, Syslog, etc will support Rack PDU events and alarms from all Rack PDUs in a group. Example event log: Rack PDU 4: Device low load. NOTE: System events will only be logged for the host Rack PDU. System events from guest Rack PDUs will not be logged on the host PDU.

Data log Use the data log to display measurements about the Rack PDU, the power input to the Rack PDU, and the ambient temperature of the Rack PDU. The steps to display and resize the data log are the same as for the event log, except that you use menu options under Data instead of Events. Path: Logs > Data > Log

Filtering data logs: Use filtering to omit information you don’t want to display. Using the Network Port Sharing Data Log, the host Rack PDU will poll data from guest Rack PDUs so that data from all Rack PDUs in a group are available. To view data from a different Rack PDU in a group, select the desired Rack PDU from the "Filter Log" pull-down list. Similarly for data log graphing, you can select a different Rack PDU by clicking on the Change Data Filter button. • Filtering the log by date or time: Use the Last or From radio buttons. (The filter configuration is saved until the Rack PDU restarts.) • Filtering the log by event severity or category: – Click Filter Log. – Clear a check box to remove it from view. – After you click Apply, text at the upper right corner of the Data Log page indicates that a filter is active. The filter is active until you clear it or until the Rack PDU restarts. • Removing an active filter: – Click Filter Log. – Click Clear Filter (Show All). – As Administrator, click Save As Default to save this filter as the new default log view for all users.

Deleting data logs: To delete all data log records, click Clear Data Log. Deleted data log records cannot be retrieved. Path: Logs > Data > Interval

Define, in the Log Interval setting, how frequently data is searched for and stored in the data log. When you click Apply, the number of possible storage days is recalculated and display at the top of the screen. When the log is full, the oldest entries are deleted. NOTE: Because the interval specifies how often the data is recorded, the smaller the interval, the more times the data is recorded and the larger the log file.

124 Rack PDU User Guide Path: Logs > Data > Graphing

Data log graphing provides a graphical display of logged data and is an enhancement of the existing data log feature. How the graphing enhancement displays data and how efficiently it performs will vary depending on your computer hardware, computer operating system, and the Web browser you use to access the interface of the unit. NOTE: JavaScript® must be enabled in your browser to use the graphing feature. Alternatively, you can use FTP or SCP to import the data log into a spreadsheet application, and graph data in the spreadsheet Graph Data: Select the data items that correspond to the abbreviated column headings in the data log to graph multiple data items. Hold down CTRL to select multiple items.

Graph Time: Select Last to graph all records or to change the number of hours, days, or weeks for which data log information is graphed. Select a time option from the drop-down menu. Select From to graph data logged during a specific time period. NOTE: Enter time using the 24-hour clock format. Apply: Click Apply to graph the data.

Launch Graph in New Window: Click Launch Graph in New Window to launch the data log graph in a new browser window that provides a larger view of the graph. Path: Logs > Data > Rotation

Rotation causes the contents of the data log to be appended to the file you specify by name and location. Use this option to set up password-protection and other parameters. • FTP Server: The IP address or host name of the server where the file will reside. • User Name/Password: The user name with password required to send data to the repository file. This user must also be configured to have read and write access to the data repository file and the directory (folder) in which it is stored. • File Path: The path to the repository file. • Filename: The name of the repository file (an ASCII text file), e.g. datalog.txt. Any new data is appended to this file: it does not overwrite it. • Unique Filename: Select this check box to save the log as mmddyyyy_.txt, where filename is what you specified in the Filename field above. Any new data is appended to the file but each day has its own file. • Delay n hours between uploads: The number of hours between uploads of data to the file (max. 24 hours). • Upon failure, try uploading every n minutes: The number of minutes between attempts to upload data to the file after a failed upload. – Up to n times: The maximum number of times the upload will be attempted after it fails initially. – Until upload succeeds: Attempt to upload the file until the transfer is completed. Path: Logs > Data > Size

Use Data Log Size to specify the maximum number of log entries. NOTE: When you resize the data log in order to specify a maximum size, all existing log entries are deleted. When the log subsequently reaches the maximum size, the older entries are deleted.

Rack PDU User Guide 125 Firewall Logs Path: Logs > Firewall

If you create a firewall policy, firewall events will be logged here. The information in the log can be useful to help the technical support team solve problems. Log entries contain information about the traffic and the rules action (allowed, discarded). When logged here, these events are not logged in the main Event Log (see “Event log” on page 122). A firewall log contains up to 50 of the most recent events. The firewall log is cleared when the management interface reboots.

Use FTP or SCP to retrieve log files An Administrator or Device User can use FTP or SCP to retrieve a tab-delineated event log file (event.txt) or data log file (data.txt) and import it into a spreadsheet. • The file reports all events or data recorded since the log was last deleted or (for the data log) truncated because it reached maximum size. • The file includes information that the event log or data log does not display.

– The version of the file format (first field)

– The date and time the file was retrieved

–The Name, Contact, and Location values and IP address of the Rack PDU

– The unique Event Code for each recorded event (event.txt file only)

NOTE: The Rack PDU uses a four-digit year for log entries. You may need to select a four- digit date format in your spreadsheet application to display all four digits. If you are using the encryption-based security protocols for your system, use SCP to retrieve the log file. If you are using unencrypted authentication methods for the security of your system, use FTP to retrieve the log file. See the Security Handbook, available at www.apc.com, for information on available protocols and methods for setting up the type of security you need.

To use SCP to retrieve the files To retrieve the event.txt file, use the following command: scp username@hostname_or_ip_address:event.txt ./event.txt To use SCP to retrieve the data.txt file, use the following command: scp username@hostname_or_ip_address:data.txt ./data.txt

126 Rack PDU User Guide To use FTP to retrieve the event.txt or data.txt files

1. At a command prompt, type ftp and the IP address of the Rack PDU, and press ENTER. If the Port setting for the FTP Server option (set through the Network menu of the Administration tab) has been changed from its default (21), you must use the non-default value in the FTP command. For Windows FTP clients, use the following command, including spaces. (For some FTP clients, you must use a colon instead of a space between the IP address and the port number.) ftp>open ip_address port_number To set a non-default port value to enhance security for the FTP Server, see “FTP Server” on page 110. You can specify any port from 5001 to 32768.

2. Use the case-sensitive User Name and Password for Administrator or Device User to log on. For Administrator, apc is the default for User Name and Password. For the Device User, the defaults are device for User Name and apc for Password.

3. Use the get command to transmit the text of a log to your local drive. ftp>get event.txt or ftp>get data.txt

4. Type quit at the ftp> prompt to exit from FTP.

Rack PDU User Guide 127 About Tab

128 Rack PDU User Guide About the Rack PDU Path: About > RPDU/Network

The hardware information is useful to Schneider Electric Customer Support for troubleshooting problems with the Rack PDU. The serial number and MAC address are also available on the Rack PDU itself. Firmware information for the Application Module, APC OS (AOS), and APC Boot Monitor indicates the name, the firmware version, and the date and time each firmware module was created. This information is also useful in troubleshooting and enables you to determine if updated firmware is available at the web site, www.apc.com. Management Uptime is the length of time the network management interface has been running continuously. Support Screen Path: About > Support

With this option, you can consolidate various data in this interface into a single zipped file for troubleshooting purposes and customer support. The data includes the event and data logs, the configuration file and complex debugging information. Click Generate Logs to create the file and then Download. You will be asked whether you want to view or save the zipped file.

Rack PDU User Guide 129 Device IP Configuration Wizard

Capabilities, Requirements, and Installation How to use the Wizard to configure TCP/IP settings The Device IP Configuration Wizard can discover Rack PDUs that do not have an IP address assigned. Once discovered, you can configure the IP address settings for the cards. You can also search for devices already on the network by entering an IP range to define the search. The Utility scans the IP addresses in the defined range and discovers Rack PDUs that already have a DHCP- assigned IP address. NOTE: For detailed information on the Utility, see the Knowledge Base on the support page of the www.apc.com website and search for FA156064 (the ID of the relevant article). NOTE: To use the DHCP Option 12 (AOS 5.1.5 or higher), see Knowledge Base ID FA156110. System requirements

The Device IP Configuration Wizard runs on Microsoft® Windows® 2000, Windows Server® 2003, Windows Server® 2012, and on 32- and 64-bit versions of Windows XP, , Windows 2008, , and operating systems. The Device IP Configuration Wizard supports cards that have firmware version 3.0.x or higher and is for IPv4 only. Installation

To install the Device IP Configuration Wizard from a downloaded executable file 1. Go to www.apc.com 2. Download the Device IP Configuration Wizard. 3. Run the downloaded executable file. When installed, the Device IP Configuration Wizard is available through the Windows Start menu options.

130 Rack PDU User Guide How to Export Configuration Settings

Retrieving and Exporting the .ini File Summary of the procedure

A Super User/Administrator can retrieve the .ini file of a Rack PDU and export it to another Rack PDU or to multiple Rack PDUs. The steps are below; see details in the sections following.

1. Configure a Rack PDU with the desired settings and export them.

2. Retrieve the .ini file from that Rack PDU.

3. Customize the file to change the TCP/IP settings at least.

4. Use a file transfer protocol supported by the Rack PDU to transfer a copy to one or more other Rack PDUs. For a transfer to multiple Rack PDUs, use an FTP or SCP script or the .ini file utility. Each receiving Rack PDU uses the file to reconfigure its own settings and then deletes it. NOTE: Managing Users via the config.ini - Users are no longer managed via the config.ini in any form. Users are now managed via a separate file with the .csf extension. For further information on this topic, refer to article ID FA176542 in the Knowledge Base at www.apc.com.

Contents of the .ini file

The config.ini file you retrieve from a Rack PDU contains the following: • Section headings and keywords (only those supported for the particular device from which you retrieve the file): Section headings are category names enclosed in brackets ([ ]). Keywords, under each section heading, are labels describing specific Rack PDU settings. Each keyword is followed by an equals sign and a value (either the default or a configured value). • The Override keyword: With its default value, this keyword prevents the exporting of one or more keywords and their device-specific values. For example, in the [NetworkTCP/IP] section, the default value for Override (the MAC address of the Rack PDU) blocks the exporting of values for the SystemIP, SubnetMask, DefaultGateway, and BootMode.

.ini and Network Port Sharing The .ini configuration utility is able to get and set values for all Rack PDUs in a group. In order to be backwards compatible, the host Rack PDU will always be designated as first, "PDU_A". Any guest Rack PDUs are then designated "PDU_B", "PDU_C", and "PDU_D" based on their Display ID in ascending order. Therefore, "PDU_A" will not necessarily correlate to Display ID 1, and so on. NOTE: Because of the large number of configuration values possible in a Rack PDU group, it may take a very long time to process an INI file set. For example, a Rack PDU group of 4 units with all values changing may take 30 minutes to complete processing.

Rack PDU User Guide 131 Detailed procedures

Retrieving: To set up and retrieve an .ini file to export: 1. If possible, use the interface of a Rack PDU to configure it with the settings to export. (Directly editing the .ini file risks introducing errors).

2. To use FTP to retrieve config.ini from the configured Rack PDU: – Open a connection to the Rack PDU using its IP address:

ftp> open ip_address – Log on using the Super User/Administrator user name and password. – Retrieve the config.ini file containing the settings of the Rack PDU:

ftp> get config.ini The file is written to the folder from which you launched the FTP.

To retrieve configuration settings from multiple Rack PDUs and export them to other Rack PDUs, see Release Notes: ini File Utility, version 2.0, available at www.apc.com.

Customizing: You must customize the file before you export it.

1. Use a text editor to customize the file.

– Section headings, keywords, and pre-defined values are not case-sensitive, but string values that you define are case-sensitive.

– Use adjacent quotation marks to indicate no value. For example, LinkURL1="" indicates that the URL is intentionally undefined.

– Enclose in quotation marks any values that contain leading or trailing spaces or are already enclosed in quotation marks.

– To export scheduled events, configure the values directly in the .ini file.

– To export a with the greatest accuracy, if the receiving Rack PDUs can access a Network Time Protocol server, configure enabled for NTPEnable:

NTPEnable=enabled

Alternatively, reduce transmission time by exporting the [SystemDate/Time] section as a separate .ini file.

– To add comments, start each comment line with a semicolon (;). 2. Copy the customized file to another file name in the same folder:

– The file name can have up to 64 characters and must have the .ini suffix.

– Retain the original customized file for future use. The file that you retain is the only record of your comments.

132 Rack PDU User Guide Transferring the file to a single Rack PDU: To transfer the .ini file to another Rack PDU, do either of the following: • From the Web UI of the receiving Rack PDU, select Configuration > General > User Config File. Enter the full path of the file, or use Browse on your local PC. • Use any file transfer protocol supported by Rack PDUs, i.e., FTP, FTP Client, SCP, or TFTP. The following example uses FTP: – From the folder containing the copy of the customized .ini file, use FTP to log in to the Rack PDU to which you are exporting the .ini file:

ftp> open ip_address

– Export the copy of the customized .ini file to the root directory of the receiving Rack PDU:

ftp> put filename.ini

Exporting the file to multiple Rack PDUs: To export the .ini file to multiple Rack PDUs: • Use FTP or SCP, but write a script that incorporates and repeats the steps used for exporting the file to a single Rack PDU. • Use a batch processing file and the .ini file utility. • To create the and use the utility, see Release Notes: ini File Utility, version 2.0, available at www.apc.com. The Upload Event and Error Messages The event and its error messages The following event occurs when the receiving Rack PDU completes using the .ini file to update its settings. Configuration file upload complete, with number valid values If a keyword, section name, or value is invalid, the upload by the receiving Rack PDU succeeds, and additional event text states the error.

Event text Description

Configuration file warning: Invalid keyword on line number. A line with an invalid keyword or value is ignored. Configuration file warning: Invalid value on line number. Configuration file warning: Invalid section If a section name is invalid, all keyword/value pairs in that on line number. section are ignored. Configuration file warning: Keyword found A keyword entered at the beginning of the file (i.e., before outside of a section on line number. any section headings) is ignored. If the file is too large, an incomplete upload occurs. Reduce Configuration file warning: Configuration file the size of the file, or divide it into two files, and try exceeds maximum size. uploading again.

Rack PDU User Guide 133 Messages in config.ini A Rack PDU from which you download the config.ini file must be discovered successfully in order for its configuration to be included. If the Rack PDU is not present or is not discovered, the config.ini file contains a message under the appropriate section name, instead of keywords and values. For example: Rack PDU not discovered If you did not intend to export the Rack PDU configuration as part of the .ini file import, ignore these messages.

Errors generated by overridden values The Override keyword and its value will generate error messages in the event log when it blocks the exporting of values. See “Contents of the .ini file” on page 131 for information about which values are overridden. Because the overridden values are device-specific and not appropriate to export to other Rack PDUs, ignore these error messages. To prevent these error messages, delete the lines that contain the Override keyword and the lines that contain the values that they override. Do not delete or change the line containing the section heading.

Related Topics On Windows operating systems, instead of transferring .ini files, you can use the Device IP Configuration Wizard to update the basic TCP/IP settings of the Rack PDU and configure other settings through its user interface. See “Device IP Configuration Wizard” on page 130.

134 Rack PDU User Guide File Transfers

Upgrading Firmware Benefits of upgrading firmware When you upgrade the firmware on the Rack PDU: • You obtain the latest bug fixes and performance improvements. • New features become available for immediate use. Keeping the firmware versions consistent across your network ensures that all Rack PDUs support the same features in the same manner. Upgrading here means simply placing the module files on the Rack PDU; there is no installation required. Check regularly on www.apc.com for any new upgrades. Firmware module files (Rack PDU) A firmware release has three modules, and they must be upgraded (that is, placed on the Rack PDU) in the same order as shown in the table below. NOTE: It is possible to skip upgrading the bootmon file if it is already the same version as the file located on the card.

Order Module Description 1 Boot Monitor (bootmon) Roughly equivalent to the BIOS of a PC American Power Conversion Operating System Can be considered the operating system of 2 (AOS) the Rack PDU 3 Application Specific to the Rack PDU device type

(Each module contains one or more Cyclical Redundancy Checks (CRCs) to protect its data from corruption). The boot monitor module, the AOS, and the application file names share the same basic format: apc_hardware-version_type_firmware-version.bin • apc: Indicates the context. • hardware-version: hw0n where n identifies the hardware version on which you can use this file. • type: Identifies which module. • version: The version number of the file. • bin: Indicates that this is a binary file.

Rack PDU User Guide 135 Firmware File Transfer Methods

NOTE: Upgrade the bootmon module first, then the AOS module, and finally, the application module by placing them on the Rack PDU in that order. Obtain the free, latest firmware version from the APC by Schneider Electric web site. To upgrade the firmware of one or more Rack PDUs, use 1 of these 5 methods: • On a Windows operating system, use the Firmware Upgrade Utility downloaded from the web site www.apc.com. • On any supported operating system, use FTP or SCP to transfer the individual AOS and application firmware modules. • For a Rack PDU that is NOT on your network, use XMODEM through a serial connection to transfer the individual firmware modules from your computer to the Rack PDU. • Use a USB drive to transfer the individual firmware modules from your computer. See “How to upgrade multiple Rack PDUs” on page 139. • For upgrades to multiple Rack PDUs, see “Upgrading the firmware on multiple Rack PDUs” and “Using the Firmware Upgrade Utility for multiple upgrades on Windows”.

Using the Firmware Upgrade Utility This Firmware Upgrade Utility is part of the firmware upgrade package available on the www.apc.com website. (Never use an Upgrade Utility designated for one product to upgrade the firmware of another product).

Using the Utility for upgrades on Windows-based systems: On any supported Windows operating system, the Firmware Upgrade Utility automates the transferring of the firmware modules, in the correct module order. Unzip the downloaded firmware upgrade file and double-click the .exe file. Then enter the IP address, the user name, and the password in the dialog fields and click Upgrade Now. You can use the Ping button to test your entered details. See “How to upgrade multiple Rack PDUs” on page 139.

Using the Utility for manual upgrades, primarily on Linux: On non-Windows operating systems, the Firmware Upgrade Utility extracts the individual firmware modules, but does not upgrade the Rack PDU. See “Firmware File Transfer Methods” on page 136 for the different upgrade methods after extraction. To extract the firmware files:

1. After extracting files from the downloaded firmware upgrade file, run the Firmware Upgrade Utility (the .exe file).

2. At the prompts, click Next>, and then specify the directory location to which the files will be extracted.

3. When the Extraction Complete message displays, close the dialog box.

136 Rack PDU User Guide Use FTP or SCP to upgrade one Rack PDU FTP: To use FTP to upgrade a Rack PDU over the network: • The Rack PDU must be on the network, with its system IP, subnet mask, and default gateway configured. • The FTP server must be enabled at the Rack PDU, see “FTP Server” on page 110. To transfer the files (this procedure assumes bootmon does not need upgrading, it is always necessary to upgrade the other two, though):

1. The firmware module files must be extracted, see “To extract the firmware files:”.

2. At a computer on the network, open a command prompt window. Go to the directory that contains the firmware files, and list the files: C:\>cd apc C:\apc>dir 3. Open an FTP client session: C:\apc>ftp

4. Type open with the IP address of the Rack PDU, and press ENTER. If the port setting for the FTP Server has changed from its default of 21, you must use the non-default value in the FTP command.

• For Windows FTP clients, separate a non-default port number from the IP address by a space. For example (showing a space before 21000): ftp> open 150.250.6.10 21000 • Some FTP clients require a colon instead before the port number.

5. Log on as Administrator (apc is the default user name and password). 6. Upgrade the AOS. (Always upgrade the AOS before the application module). ftp> bin ftp> put apc_hw05_aos_nnn.bin (where nnn is the firmware version number)

7. When FTP confirms the transfer, type quit to close the session. 8. After 20 seconds, repeat step 3 through step 7, using the application module file name at step 6,

SCP: To use Secure CoPy (SCP) to upgrade firmware for the Rack PDU, follow these steps (this procedure assumes bootmon does not need upgrading, it is always necessary to upgrade the other two though):

1. the firmware modules, see “Using the Utility for manual upgrades, primarily on Linux:” on page 136.

2. Use an SCP command line to transfer the AOS firmware module to the Rack PDU. The following example uses nnn to represent the version number of the AOS module: scp apc_hw05_aos_nnn.bin [email protected]:apc_hw05_aos_nnn.bin 3. Use a similar SCP command line, with the name of the application module, to transfer the application firmware module to the Rack PDU. (Always upgrade the AOS before the application module).

Rack PDU User Guide 137 Use XMODEM to upgrade one Rack PDU To use XMODEM to upgrade one Rack PDU that is not on the network, you must extract the firmware files from the Firmware Upgrade Utility (see “To extract the firmware files:”). To transfer the files (this procedure assumes bootmon does not need upgrading, it is always necessary to upgrade the other two though):

1. Select a serial port at the local computer and disable any service that uses the port.

2. Connect the provided serial configuration cable (part number 940-0144A) to the selected port and to the RJ-12 style serial port at the Rack PDU.

3. Run a terminal program such as HyperTerminal, and configure the selected port for 57600 bps, 8 data bits, no parity, 1 stop bit, and no flow control.

4. Press the Reset button on the Rack PDU, then immediately press the Enter key twice, or until the Boot Monitor prompt displays: BM>

5. Type XMODEM, then press ENTER. 6. From the terminal program’s menu, select XMODEM, then select the binary AOS firmware file to transfer using XMODEM. After the XMODEM transfer is complete, the Boot Monitor prompt returns. (Always upgrade the AOS before the application module).

7. To install the application module, repeat step 5 and step 6. In step 6, use the application module file name.

8. Type reset or press the Reset button to restart the Rack PDU’s management interface.

Use a USB drive to transfer and upgrade the files Use a USB drive to transfer and upgrade the files. Before starting the transfer, make sure the USB drive is formatted in FAT32. 1. Download the firmware upgrade files and unzip them. 2. Create a folder named apcfirm on the USB flash drive. 3. Place the extracted module files in the apcfirm directory. 4. Use a text editor to create a file named upload.rcf. (The file extension must be .rcf, not .txt for example.) 5. In upload.rcf, add a line for each firmware module that you want to upgrade. For example, to upgrade to bootmon version 1.0.5, AOS v6.0.9, and RPDU2g application version v6.0.9, type: BM=apc_hw05_bootmon_105.bin AOS=apc_hw05_aos_609.bin APP=apc_hw05_rpdu2g_609.bin 6. Place upload.rcf in the apcfirm folder on the flash drive. 7. Insert the flash drive into a USB port on your Rack PDU. 8. Press the display Reset button and wait for the card to reboot fully. 9. Check that the upgrade was completed successfully using the procedures in “Verifying Upgrades”.

138 Rack PDU User Guide How to upgrade multiple Rack PDUs Use one of these three methods: • Firmware Upgrade Utility: Use this for multiple firmware updates in IPv4 if you have Windows. The utility records all upgrade steps in a log as a good reference to validate the upgrade. • Export configuration settings: You can create batch files and use a utility to retrieve configuration settings from multiple Rack PDUs and export them to other Rack PDUs. See Release Notes: ini File Utility, version 2.0, available in the Knowledge Base at www.apc.com • Use FTP or SCP to upgrade multiple Rack PDUs: To upgrade multiple Rack PDUs using an FTP client or using SCP, write a script which automatically performs the procedure. NOTE: Utility is available from the Knowledge Base: www.apc.com/support

Using the Firmware Upgrade Utility for multiple upgrades After downloading the Upgrade Utility, double click on the .exe file to run the utility (which ONLY works with IPv4) and follow these steps to upgrade your Rack PDU firmware:

1. Type in an IP address, a user name, and a password, and choose the Ping button if you need to verify an IP address.

2. Choose the Device List button to open the iplist.txt file. This should list any device IP, user name, and password. For example, SystemIP=192.168.0.1 SystemUserName=apc SystemPassword=apc

You can use an existing iplist.txt file if it already exists.

3. Select the Upgrade From Device List check box to use the iplist.txt file. 4. Choose the Upgrade Now button to start the firmware version update(s).

5. Choose View Log to verify any upgrade.

Updating firmware for Network Port Sharing (NPS) Groups For an NPS Group, all Rack PDUs in the group should have the same firmware version. If all Rack PDUs in the group have AOS v6.0.9 or later, simply update the host Rack PDU and it will update all guest Rack PDUs automatically. This may take up to 10 minutes. For any Rack PDUs in the group that do not have AOS v6.0.9 or later, they will need to be updated manually by any of the methods detailed previously.

Rack PDU User Guide 139 Verifying Upgrades and Updates Verify the success or failure of the transfer To verify whether a firmware upgrade succeeded, use the xferStatus command in the command line interface to view the last transfer result, or use an SNMP GET to the mfiletransferStatusLastTransferResult OID.

Last Transfer Result codes Possible transfer errors include the TFTP or FTP server not being found, or the server refusing access, the server not finding or not recognizing the transfer file, or a corrupt transfer file.

Code Description

Successful The file transfer was successful. Result not There are no recorded file transfers. available Failure unknown The last file transfer failed for an unknown reason. Server The TFTP or FTP server could not be found on the network. inaccessible Server access The TFTP or FTP server denied access. denied File not found The TFTP or FTP server could not locate the requested file. File type unknown The file was downloaded but the contents were not recognized. The file was downloaded but at least one Cyclical Redundancy Check (CRC) File corrupt failed.

Verify the version numbers of installed firmware. Path: About > Network

Use the Web UI to verify the versions of the upgraded firmware modules. You could also use an SNMP GET to the MIB II sysDescr OID. In the command line interface, use the about command.

140 Rack PDU User Guide Troubleshooting

Rack PDU Access Problems

For problems that persist or are not described here, contact APC by Schneider Electric Customer Care at www.apc.com.

Problem Solution After a Network Port Sharing host is updated to new This can be solved by manually updating the affected guest Rack PDUs by firmware, the guest Rack one of the firmware update methods. For example, see Using a USB flash PDUs show a "firmware drive to upgrade one Rack PDU section. version does not match" alarm. Cannot enable EnergyWise on User is allowed to have a redundant network in a NPS chain. However, only a guest Rack PDU in a NPS one Rack PDU, the host, will communicate to EnergyWise. group. (A) It is possible to receive an incorrect tag: 1. Verify you have the correct tag from the RF code. Go to: www.rfcode.com 2. Verify you are in correct mode (RF Code active screen on LCD). a. Select the Scroll button on the Rack PDU device. b. On the second screen press Select to active the RF Code Control RF Code Issues (A) screen. Unable to clear RF Tag c. The screen will say: Rf-Code Console Disabled/Enabled Press Communications Lost “Select” Will Reboot. alarm(B): 3. Check serial communication is OK: Connect serial cord provided with the unit to the unit Serial port and a serial port located on the computer. Access the Command Line Interface to verify signals are being received and sent from the computer to the unit. Only valid if RF is disabled. (B) Ensure tag is installed in the serial port, then disable the RF feature through the LCD display. The RF Tag can then be safely removed. If the Rack PDU’s Network Status LED is green, try to ping another node on the same network segment as the Rack PDU. If that fails, it is not a problem with the Rack PDU. If the Network Status LED is not green, or if the ping test succeeds, perform the following checks: Unable to ping the Rack PDU • Verify all network connections. • Verify the IP addresses of the Rack PDU and the NMS. • If the NMS is on a different physical network (or subnetwork) from the Rack PDU, verify the IP address of the default gateway (or router). • Verify the number of subnet bits for the Rack PDU’s subnet mask. Cannot allocate the Before you can use a terminal program to configure the Rack PDU, you communications port through a must shut down any application, service, or program using the terminal program communications port. Cannot access the command Make sure that you did not change the baud rate. Try 2400, 9600, 19200, or line interface through a serial 38400. connection

Rack PDU User Guide 141 Problem Solution • Make sure you are using the correct access method, Telnet or Secure SHell (SSH). These can be enabled or disable independently. The Super User or an Administrator can enable these access methods. By default, Cannot access the command Telnet is enabled.. line interface remotely • For SSH, the Rack PDU may be creating a host key. The Rack PDU can take up to one minute to create the host key, and SSH is inaccessible for that time. • Verify that HTTP or HTTPS access is enabled. • Make sure you are specifying the correct URL — one that is consistent with the security system used by the Rack PDU. SSL requires https, not http, at the beginning of the URL. • Verify that you can ping the Rack PDU. Cannot access the web interface • Verify that you are using a Web browser supported for the Rack PDU. See “Supported Web Browsers” on page 81. • If the Rack PDU has just restarted and SSL security is being set up, the Rack PDU may be generating a server certificate. The Rack PDU can take up to one minute to create this certificate, and the SSL server is not available during that time. • If you are having communications problems with Network Port Sharing, check that the total length of network cable between up to four units is not more than 10 meters. • If you are having communications problems with Network Port Sharing, Cannot communicate using check that a terminator is installed at both ends of up to four units that Network Port Sharing (NPS) can be grouped together. • If you are using Network Port Sharing and do not see one or more of the units in the group, check that all units in the group are using the same firmware revision. You can download appropriate firmware revisions from the APC by Schneider Electric website. The Rack PDU reports “Component communications Refer to Knowledge Base FA168022 at www.apc.com. lost with Phase Meter” and/or “Communication lost” alarms The Rack PDU reports “CAN Refer to Knowledge Base FA173637 at www.apc.com. bus off” alarm

142 Rack PDU User Guide SNMP Issues

Problem Solution • Verify the read (GET) community name (SNMPv1) or the user profile configuration (SNMPv3). Unable to perform a GET • Use the command line interface or UI to ensure that the NMS has access. See “SNMP” on page 107 • Verify the read/write (SET) community name (SNMPv1) or the user profile configuration (SNMPv3). Unable to perform a SET • Use the command line interface or UI to ensure that the NMS has write (SET) access (SNMPv1) or is granted access to the target IP address through the access control list (SNMPv3). See “SNMP” on page 107. • Make sure the trap type (SNMPv1 or SNMPv3) is correctly configured for the NMS as a trap receiver. • For SNMP v1, query the mconfigTrapReceiverTable MIB OID to verify that the NMS IP address is listed correctly and that the community name defined for the NMS matches the community name in the table. If either is not correct, use Unable to receive traps at SETs to the mconfigTrapReceiverTable OIDs, or use the command line the NMS interface or UI to correct the trap receiver definition. • For SNMPv3, check the user profile configuration for the NMS, and run a trap test. See “SNMP” on page 107, “SNMP trap receiver screen” on page 115, and “SNMP traps test screen” on page 115. Traps received at an See your NMS documentation to verify that the traps are properly integrated in the NMS are not identified alarm/trap database.

Rack PDU User Guide 143 Source Code Copyright Notice cryptlib copyright Digital Data Security New Zealand Ltd 1998. Copyright © 1990, 1993, 1994 The Regents of the University of California. All rights reserved. This code is derived from software contributed to Berkeley by Mike Olson. Redistribution and use in source and binary forms, with or without modification, are permitted provided that the following conditions are met: 1. Redistributions of source code must retain the above copyright notice, this list of conditions and the following disclaimer. 2. Redistributions in binary form must reproduce the above copyright notice, this list of conditions and the following disclaimer in the documentation and/or other materials provided with the distribution. 3. All advertising materials mentioning features or use of this software must display the following acknowledgment: This product includes software developed by the University of California, Berkeley and its contributors. 4. Neither the name of the University nor the names of its contributors may be used to endorse or promote products derived from this software without specific prior written permission. THIS SOFTWARE IS PROVIDED BY THE REGENTS AND CONTRIBUTORS “AS IS” AND ANY EXPRESS OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE REGENTS OR CONTRIBUTORS BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.

144 Rack PDU User Guide

Worldwide Customer Support

For more information contact Customer Support at www.apc.com/support.

© 2016 Schneider Electric. APC, StruxureWare and PowerNet are owned by Schneider Electric Industries S.A.S. All other trademarks are property of their respective owners.

990-5571E-001 7/2017