<<

FOR MORE INFORMATION, VISIT: CASE STUDY HTTP://BUILDEQUINOX.COM/BLACKBOX/

Improved – Needs More Air The subject of this test is a well maintained home occupied by a family of four (two adults and two children). The house is a 2118 square foot, single story ranch home with a , and is well-sealed and insulated for a conventional home. Water condenses on windows throughout the winter, causing the family to operate in order to keep at comfortable levels. All members in the household are on allergy medications.

The home had been the subject of an study in 2006 due to an unvented gas . During that test, the home had an average carbon dioxide level of 1,478 ppm and a measurement of ACH of 0.34 at normal pressure conditions (ACH=), equivalent to an average infiltration rate of 100 cfm flowing through the house.

The homeowner conducted a radon test and found levels exceeding 20 picoCuries per liter in the basement. Carbon dioxide concentrations were also very high while air exchange rates were low relative to the home’s occupancy. VOCs pollutant levels were low, indicating that carbon dioxide generation is the primary pollutant generated by the occupants' activities.

Radon remediation actions were undertaken as this was the primary concern. When high radon levels are found, remediation should occur before altering a home's insulation and infiltration characteristics.

Radon reduction consisted of installing sump pit covers and sealing off floor drains connected to the sump pits. A radon exhaust was added that pulls air from the sumps, a primary source of soil gas. After remediation, a radon concentration of 0.7 picoCuries per liter was measured by the homeowner. The radon trend figure on page 2-2 of the BB IAQ report shows a vertical line that characterizes radon trends. A 0.7 picoCurie per liter radon concentration is a flow rate that is less than 10 picoCurie per second of radioactivity, which is much lower than the 100 picoCuries per second prior to the radon mitigation action.

Air exchange flow of 19 cubic feet per minute per occupant was measured after the installation of the radon mitigation system. The average carbon dioxide level is now 1,082 ppm. This level of carbon dioxide is much lower than the 1,478 ppm measured during the 2006 fireplace study, however, the addition of an air ventilation system with fresh air entering the house from a known source can further improve air quality and provide some level of respiratory relief to the home's occupants. Black Box

Indoor Air Quality Report

Test Number: Black Box Case Study 4 Name: Improved Radon Email address: [email protected] Test Location: Central Illinois Box Location: basement Report Date: 12/10/2012

Overview: This Black Box IAQ™ report provides an assessment of indoor air quality (IAQ) over the tested time period for the designated space. Black Box IAQ™ measures temperature, humidity, carbon dioxide (CO2), and volatile organic compound (VOC) levels. Based on these measurements, the air exchange rate and pollutant generation rates are determined. The report is divided into two sections as follows: Section 1: Test Summary Information Reports the measured and calculated values of temperature, humidity, CO2, VOCs , and air flow rate for the measurement space. A determination is made as to whether the levels are acceptable or not. Unacceptable levels suggest corrective action. Section 2: Recommendations Test results for the measured CO2 and VOC levels are plotted against the calculated air flow rate through the space. Suggested changes to the air exchange rate are given and the impact of changes to the air exchange rate on pollutant levels are provided. Trends in radon gas levels due to changes in air exchange rate are also discussed.

Use our building energy modeling software to design a healthy, comfortable, efficient home. A free version is available at www.buildequinox.com/zeros

CERV: Monitor pollutant levels, get fresh air, and recover energy. Learn more at www.buildequinox.com/products/cerv

* Disclaimer: This test is provided for informational purposes only. Results are dependent on a number of testing conditions. It is vital to appreciate that a test result only gives a “snap-shot” estimate for a single time period and a single location under conditions at the time of testing – how well it represents other locations and times is uncertain since the amounts and types of pollutants and air flow rates in the environment is always changing.

pg. 1-1 www.buildequinox.com ©Build Equinox 2013 Rev 1.9.2, Report # Black Box Case Study 4 1: Test Summary Information Measured Temperature and Humidity Levels: Comfort Chart 100

Slacks & Long Sleeves Comfort

80 Region Shorts & Short Sleeves Comfort 60 Region

40 Room Condition Data Points

20

% Relative Humidity % Relative Average Room Condition

0 60 65 70 75 80 85 Temperature (F) Temperature and relative humidity measured during the test period are shown in the above figure. The two regions represent different comfort levels of clothing for sedentary (eg, office work activity) persons. Room conditions falling mostly within the comfort regions provide confidence that building conditioning systems are operating appropriately. Extended periods of high indoor humidity can be an indirect indicator of mold, a known component of poor indoor air quality. Infiltration or Controlled Ventilation Air Flow Rates: Optimal Air Flow

Low High Air Air Less than 15 15 to 25 Greater than 25 Flow Flow Air Exchange rate per occupant (cfm/person) Air Exchange 18.7 cfm/person

Air flow to the measured space results from either controlled ventilation or uncontrolled infiltration through cracks and inadequate sealing around doors and windows. The Black Box IAQ™ analysis calculates the space air flow rate and is reported in two ways: 1) as cubic feet per minute (cfm) and 2) as cfm per equivalent person (cfm/equiv. person) as shown above. It is important to point out that the calculated equivalent person is not the same as the number of occupants. The equivalent person number is based on typical pollution generation rates per person but can be different from the number of occupants due to occupant activity such as cooking using gas cooktops or actual occupancy time in the tested space. Air flow rates less than 15 cfm/equiv. person contribute to “stale air” and higher levels of indoor pollutants. Air flow rates greater than 25 cfm/equiv. person are higher than needed to maintain adequate indoor air quality and thus increase the heating and cooling energy required to condition the space.

pg. 1-2 www.buildequinox.com ©Build Equinox 2013 Rev 1.9.2, Report # Black Box Case Study 4 Measured CO2 and VOCs Levels:

Optimum Optimum Air Air

Poor Excess Poor Excess Air Air Dilution Quality Air Quality Air

CO2 Level VOC Level

1082. ppm average 551.8 ppm average

Less than 800ppm 800 - 1000 ppm Greater than 1000 Air pollutant ranges

The dial graphs above show the level of measured pollutants during the test period. The table below categorizes the measured levels ranging from “very good” or low pollutant levels to “very poor” or high pollutant levels based on ASHRAE (American Society of Heating, and Engineers) recommended ranges.

CO2 and VOC Levels: The most common source of indoor CO2 generation is human and correlates with human respiratory activity. Indoor combustion of natural gas, such as from stoves and or improper venting of gas water heaters and , is a large contributor of CO2. Indoor CO2 levels that are unusually high may cause occupants to grow drowsy, get headaches, or function at lower activity levels. The ASHRAE recommended CO2 upper limit is 1,000 parts per million (ppm). VOCs are also emitted from human respiration, but additionally as gases from certain solids or liquids. VOCs include a variety of chemicals, some of which may have short- and long-term adverse health effects. VOCs can be emitted by a wide array of products including carpet, furnishings, paint, cleaning solutions, cosmetics, and building materials among many others. Natural gas combustion and cooking/food preparation are also sources of VOCs. VOCs should also be kept below 1,000 ppm.*

*VOC measurements are correlated to a CO2 reference as the amount of VOCs produced in proportion to human CO2 production.

pg. 1-3 www.buildequinox.com ©Build Equinox 2013 Rev 1.9.2, Report # Black Box Case Study 4 2: Recommendations The interaction between pollutant level and air flow rate to the space is described in more detail in this section. The first table below summarizes the average measured values of CO2 and VOCs during the test period and estimated levels after adjustments are made. The second table summarizes the calculated values of air flow rate to the space during the test period; recommended adjusted level of air flow rate to keep CO2/VOC levels below 1,000 ppm. Controlled ventilation adjustments are based on cfm values.

As air flow rate to the space increases, pollutants are diluted. Conversely, decreases to the air flow rate concentrates pollutants.

Summary Information from Your Test

Average level Estimated level during test period after adjustment CO2 1082.2 (ppm) 1000.0 (ppm) VOC 551.8 (ppm) 533.5 (ppm)

Calculated level Recommended during test period adjusted level Recommended action to achieve adjusted level Space Air 31.8 (cfm) 36.2 (cfm) Add or increase controlled ventilation Flow Rate 18.7 (cfm/equiv. person) 21.2 (cfm/equiv. person)

The following plot provides additional details showing how air exchange flow rate, pollutant generation, and pollutant levels are related. Current pollutant levels and air exchange flow rates are shown with solid symbols for CO2 and VOCs. Also plotted on the figures are lines showing the relative pollution generation rates (equivalent people generation rates for CO2 and VOCs). Hollow symbols show how the suggested air exchange flow rate will impact pollution levels in the space.

The suggested change in ventilation is based on CO2 and VOC levels. Whichever is greater is used to determine the suggested ventilation change. If the concentration level is greater than 1,000 ppm, an increase in room ventilation is suggested. If the concentration level is less than 1,000 ppm, a decrease in room ventilation and/or infiltration is suggested.

A second plot provides guidance related to trends in radon levels due to adjustments in ventilation and/or infiltration levels. Radon testing must be conducted by either certified radon technicians or by individual homeowners using state approved testing methods. The red, horizontal line in the plot marks the maximum recommended level of radon per EPA guidelines. If you have conducted a certified, state approved (where applicable) radon test concurrent with the Black Box IAQ™ test, your radon level should be plotted on the solid vertical line marked "Current Air Exchange Rate". For example, a reading of 4 pCi per liter would be a point located at the intersection of the solid vertical line and the horizontal red line. Increasing fresh air ventilation air flow may reduce radon levels, while decreasing air infiltration air flow may increase radon concentration. The second vertical (dashed) line represents an adjusted air flow rate recommended for maintaining reasonable levels of CO2 and VOCs. The curved lines represent different rates of radon flow into the tested space. Drawing a line that follows the nearest curved line from the current radon level plotted on the solid vertical line to the dashed vertical line shows the expected trend in radon due to air flow adjustments. See our case studies and informational reports for additional guidance. Conducting a second radon test after any changes to the ventilation and infiltration characteristics is recommended. pg. 2-1 www.buildequinox.com ©Build Equinox 2013 Rev 1.9.2, Report # Black Box Case Study 4 Carbon Dioxide (CO2) and Volatile Organic Compounds (VOCs) 0.5 equiv. person CO2 & VOC Characteristics 1 equiv. person 2000 2 equiv. person 4 equiv. person 1800 max CO2 & VOC levels 1600 preferred lower range limit

your space VOC 1400 your space CO2 adjusted VOC 1200 adjusted CO2 1000 Preferred Range 800

600 Carbon Dioxide & VOC (ppm) VOC & CarbonDioxide 400 0 20 40 60 80 100 120 Controlled Ventilation or Infiltrated Air Flow Rate (cfm)

Radon Level Trends versus Air Flow Rate 20 18 10 pCi/sec radioactivity flow 20 pCi/sec radioactivity flow 16 50 pCi/sec radioactivity flow 14 100 pCi/sec radioactivity flow 12 maximum radon level Current Air Exchange Rate 10 Adjusted Air Exchange Rate 8 6

Radon (pCurie/liter) Radon Acceptable Levels 4 2

0 0 20 40 60 80 100 120 Controlled Ventilation or Infiltrated Air Flow Rate (cfm)

pg. 2-2 www.buildequinox.com ©Build Equinox 2013 Rev 1.9.2, Report # Black Box Case Study 4