Part 1 a Simple Approach to Short Circuit Calculations

Total Page:16

File Type:pdf, Size:1020Kb

Part 1 a Simple Approach to Short Circuit Calculations www.stevenengineering.com 9200 - 8 System Distribution Electrical For An Protection Dependable Engineering Outside Local Area: (800) 25 Bussmann 9200 - 8 Part 1 A SimpleApproach Calculations Main Office: (650) 58 6370 - 0 Short Circuit To 230 Ryan Way, South San Francisco, CA, 9408 Bulletin EDP-1 (2004-1) Courtesy of Steven Engineering, Inc. Electrical Distribution System Basic Considerations of Short-Circuit Calculations Why Short-Circuit Calculations Sources of short circuit current that are normally taken Several sections of the National Electrical Code relate under consideration include: to proper overcurrent protection. Safe and reliable - Utility Generation application of overcurrent protective devices based on - Local Generation these sections mandate that a short circuit study and a - Synchronous Motors and www.stevenengineering.com selective coordination study be conducted. - Induction Motors 9200 These sections include, among others: Capacitor discharge currents can normally be - 8 110-9 Interrupting Rating neglected due to their short time duration. Certain IEEE 110-10 Component Protection (Institute of Electrical and Electronic Engineers) publications 230-65 Service Entrance Equipment detail how to calculate these currents if they are substantial. 240-1 Conductor Protection 250-95 Equipment Grounding Conductor Protection Asymmetrical Components 517-17 Health Care Facilities - Selective Coordination Short circuit current normally takes on an asymmetrical characteristic during the first few cycles of duration. That is, Compliance with these code sections can best be it is offset about the zero axis, as indicated in Figure 1. accomplished by conducting a short circuit study and a Outside Local Area: (800) 25 selective coordination study. The protection for an electrical system should not only be safe under all service conditions but, to insure continuity 9200 - 8 of service, it should be selectively coordinated as well. A coordinated system is one where only the faulted circuit is C U isolated without disturbing any other part of the system. R Overcurrent protection devices should also provide short- R TIME circuit as well as overload protection for system E components, such as bus, wire, motor controllers, etc. N T To obtain reliable, coordinated operation and assure Main Office: (650) 58 that system components are protected from damage, it is necessary to first calculate the available fault current at Figure 1 6370 various critical points in the electrical system. - 0 Once the short-circuit levels are determined, the In Figure 2, note that the total short circuit current Ia is engineer can specify proper interrupting rating require- the summation of two components - the symmetrical RMS ments, selectively coordinate the system and provide current IS, and the DC component, IDC. The DC component component protection. is a function of the stored energy within the system at the initiation of the short circuit. It decays to zero after a few General Comments on Short-Circuit Calculations cycles due to I2R losses in the system, at which point the Short Circuit Calculations should be done at all critical short circuit current is symmetrical about the zero axis. The points in the system. RMS value of the symmetrical component may be deter- These would include: mined using Ohm`s Law. To determine the asymmetrical - Service Entrance component, it is necessary to know the X/R ratio of the - Panel Boards system. To obtain the X/R ratio, the total resistance and total - Motor Control Centers reactance of the circuit to the point of fault must be - Motor Starters determined. Maximum thermal and mechanical stress on - Transfer Switches the equipment occurs during these first few cycles. It is - Load Centers important to concentrate on what happens during the first half cycle after the initiation of the fault. 230 Ryan Way, South San Francisco, CA, 9408 Normally, short circuit studies involve calculating a bolted 3-phase fault condition. This can be characterized as all three phases “bolted” together to create a zero impedance connection. This establishes a “worst case” condition, that results in maximum thermal and mechanical stress in the system. From this calculation, other types of fault conditions can be obtained. Courtesy of Steven Engineering, Inc. 3 Electrical Distribution System Basic Considerations of Short-Circuit Calculations To accomplish this, study Figure 2, and refer to Table 8. Interrupting Rating, Interrupting Capacity and Short-Circuit Currents Interrupting Rating can be defined as “the maximum IP = 115,450A Ia short-circuit current that a protective device can safely clear, under specified test conditions.” I = a Interrupting Capacity can be defined as “the actual 66,500A IDC www.stevenengineering.com short circuit current that a protective device has been Is = tested to interrupt.” 50,000A 9200 The National Electrical Code requires adequate - C 8 U interrupting ratings in Sections 110-9 and 230-65. R TIME R Is E Section 110-9 Interrupting Rating. Equipment intended to N break current at fault levels shall have an interrupting rating T sufficient for the system voltage and the current which is Ia - Asymmetrical RMS Current available at the line terminals of the equipment. IDC - DC Component Is - Symmetrical RMS Component Section 230-65. Available Short-Circuit Current. Service IP - Instantaneous Peak Current Equipment shall be suitable for the short circuit current Outside Local Area: (800) 25 available at its supply terminals. Figure 2 Low voltage fuses have their interrupting rating 9200 - 8 Figure 2 illustrates a worst case waveform that 1 phase expressed in terms of the symmetrical component of short- of the 3 phase system will assume during the first few circuit current, IS. They are given an RMS symmetrical cycles after the fault initiation. interrupting rating at a specific power factor. This means For this example, assume an RMS symmetrical short that the fuse can interrupt any asymmetrical current circuit value of 50,000 amperes, at a 15% short circuit associated with this rating. Thus only the symmetrical power factor. Locate the 15% P.F. in Table 8. Said another component of short-circuit current need be considered to way, the X/R short circuit ratio of this circuit is 6.5912. determine the necessary interrupting rating of a low voltage Main Office: (650) 58 fuse. For U.L. listed low voltage fuses, interrupting rating The key portions are: equals its interrupting capacity. 6370 - Symmetrical RMS Short Circuit Current = Is Low voltage molded case circuit breakers also have - 0 - Instantaneous Peak Current = Ip their interrupting rating expressed in terms of RMS - Asymmetrical RMS Short Circuit Current symmetrical amperes at a specific power factor. However, (worst case single phase) = Ia it is necessary to determine a molded case circuit breaker’s interrupting capacity in order to safely apply it. The reader From Table 8, note the following relationships. is directed to Buss bulletin PMCB II for an understanding of this concept. Is = Symmetrical RMS Current Ip = Is x Mp (Column 3) Ia = Is x Mm (Column 4) For this example, Figure 2, Is = 50,000 Amperes RMS Symmetrical Ip = 50,000 x 2.309 ( Column 3) = 115,450 Amperes Ia = 50,000 x 1.330 (Column 4) 230 Ryan Way, South San Francisco, CA, 9408 = 66,500 Amperes RMS Asymmetrical With this basic understanding, proceed in the systems analysis. Courtesy of Steven Engineering, Inc. 4 3ø Short-Circuit Current Calculations – Procedures and Methods 3Ø Short-Circuit Current Calculations, To begin the analysis, consider the following system, Procedures and Methods supplied by a 1500 KVA, three phase transformer having a To determine the fault current at any point in the full load current of 1804 amperes at 480 volts. (See System system, first draw a one-line diagram showing all of the A, below) Also, System B, for a double transformation, will sources of short-circuit current feeding into the fault, as well be studied. as the impedances of the circuit components. www.stevenengineering.com To start, obtain the available short-circuit KVA, MVA, or To begin the study, the system components, including SCA from the local utility company. those of the utility system, are represented as impedances 9200 The utility estimates that System A can deliver a short- - 8 in the diagram. circuit of 100,000 MVA at the primary of the transformer. The impedance tables given in the Data Section System B can deliver a short-circuit of 500,000 KVA at the include three phase and single phase transformers, current primary of the first transformer. Since the X/R ratio of the transformers, safety switches, circuit breakers, cable, and utility system is usually quite high, only the reactance need busway. These tables can be used if information from the be considered. manufacturers is not readily available. With this available short-circuit information, begin to It must be understood that short circuit calculations are make the necessary calculations to determine the fault performed without current limiting devices in the system. current at any point in the electrical system. Calculations are done as though these devices are Four basic methods will be presented in this text to replaced with copper bars, to determine the maximum Outside Local Area: (800) 25 instruct the reader on short circuit calculations. “available” short circuit current. This is necessary to These include : project how the system and the current limiting devices will - the ohmic method 9200 - perform. 8 - the per unit method Also, current limiting devices do not operate in series - the TRON® Computer Software method to produce a “compounding” current limiting effect. The - the point to point method downstream, or load side, fuse will operate alone under a short circuit condition if properly coordinated. System A System B 3Ø Single Transformer System Main Office: (650) 58 3Ø Double Transformer System Available Utility Available Utility S.C. MVA 100,000 6370 S.C. KVA 500,000 - 0 1500 KVA Transformer 1000 KVA Transformer, 480Y/277V, 25’ - 500kcmil 480/277 Volts 3Ø 3.5%Z, 3.45%X, .56%R 30’ - 500 kcmil 6 Per Phase 3.45%X, .60%R If.l.
Recommended publications
  • Electrical Limiting Factors for Wind Energy Installations
    Electrical limiting factors for wind energy installations Stefan Lundberg ISSN 1401-6184 Institutionen för elteknik Examensarbete 50E Göteborg, Sweden 2000 Abstract In this thesis the electrical limiting factors for installation of wind turbines stated by the Swedish connecting requirements, AMP, have been used to determine which types of power quality problems that will dominate when fix-speed wind turbines are installed. The main limiting factors are static voltage level influence and the flicker emissions. The investigation is based on field measurements on a stall-regulated and on a pitch-regulated wind turbine. It is found that the limiting factor from the power quality point of view is the flicker emissions if one turbine is installed. If three or more turbines are installed it is the static voltage variations that sets the limit, if the summation formula from AMP is used. It is found that the XR-ratio of the grid plays a very large influence on the installation possibility, and a ratio of 1.3-2.8 is the most favourable, depending on the short circuit ratio. The results shown in this thesis can be used to determine if there will be any problem with the static voltage level or the flicker emissions when stall-regulated wind turbines are connected to the network. I II Acknowledgements This work was performed July 2000 – December 2000 at the department of electric Power Engineering at Chalmers University of Technology, Gothenburg. I would like to thank my supervisor Torbjörn Thiringer at Chalmers University of Technology for this valuable advice, linguistic help, support and discussion throughout the work.
    [Show full text]
  • Influencing Factor Analysis of the Short Circuit Ratio on Grid-Connected Photovoltaic Systems 685
    RESEARCH Revista Mexicana de F´ısica 65 (6) 684–689 NOVEMBER-DECEMBER 2019 Influencing factor analysis of the short circuit ratio on grid-connected photovoltaic systems G. Hachemia, R. Dehinia, and F. Brahimb aElectrical Engineering Department; Tahri Mohammed University, B.P. 417, 08000 Bechar, Algeria, e-mail: [email protected] bUniversity Centre of Abdelhafid Boussouf-mila Received 22 September 2018; accepted 11 April 2019 Over the past few years, solar energy conversion technology is sharply developing. An important first step is to make this conversion system more effective and more reliable. The main objective of this paper is to study the influence of the power of the electricity network on the connection of the solar energy source. The photovoltaic source has been examined under the effect of the variation of the parameters of the networks such as the power of short-circuit and the frequency. The results obtained by the simulation have shown that the photovoltaic source has amazing performance if the power system is of high or medium power and with constant parameters. Keywords: Photovoltaic (PV) systems; short circuit power; network impedance. the active power; the reactive power. PACS: 42.79.Wc DOI: https://doi.org/10.31349/RevMexFis.65.684 1. Introduction production of the Photovoltaic installation, the extra charge is provided by the network. Otherwise, energy is supplied to Renewable energies generate little or no waste or polluting the public grid and is used to power consumers. In the past, emissions [1]. They contribute to the fight against the green- distribution networks have behaved like passive elements in house effect and CO2 emissions into the atmosphere, facil- which power flows unidirectional from the source station to itate the reasoned management of local resources, and gen- the end consumers.
    [Show full text]
  • Standards/Manuals/ Guidelines for Small Hydro Development
    STANDARDS/MANUALS/ GUIDELINES FOR SMALL HYDRO DEVELOPMENT Electro-Mechanical– 3.2 Selection of Generators and Excitation Systems Sponsor: Lead Organization: Ministry of New and Renewable Energy Alternate Hydro Energy Centre Govt. of India Indian Institute of Technology Roorkee July 2012 Contact: Dr Arun Kumar Alternate Hydro Energy Centre, Indian Institute of Technology Roorkee, Roorkee - 247 667, Uttarakhand, India Phone : Off.(+91 1332) 285821, 285167 Fax : (+91 1332) 273517, 273560 E-mail : [email protected], [email protected] DISCLAIMER The data, information, drawings, charts used in this standard/manual/guideline has been drawn and also obtained from different sources. Every care has been taken to ensure that the data is correct, consistent and complete as far as possible. 3.2 The constraints of time and resources available to this nature of assignment, however do not preclude the possibility of errors, omissions etc. in the data and consequently in the report preparation. Use of the contents of this standard/manual/guideline is voluntarily and can be used freely with the request that a reference may be made as follows: AHEC-IITR, “3.1 Electro-Mechanical– Selection of Turbine and Governing System for Hydroelectric Projects”, standard/manual/guideline with support from Ministry of New and Renewable Energy, Roorkee, June 2012. PREAMBLE There is a series of standards, guidelines and manuals available on electrical, electro-mechanical aspect of moving machines and hydro power related issues by Bureau of Indian Standards (BIS), Rural Electrification Corporation Ltd (REC), Central Electricity Authority (CEA), Central Board of Irrigation & Power (CBIP), International Electromechanical Commission (IEC), International Electrical and Electronics Engineers (IEEE), American Society of Mechanical Engineers (ASME) and others.
    [Show full text]
  • Based Resources Into Low Short Circuit Strength Systems Reliability Guideline
    Integrating Inverter- Based Resources into Low Short Circuit Strength Systems Reliability Guideline December 2017 NERC | Report Title | Report Date I Table of Contents Preface ...................................................................................................................................................................... iv Preamble .................................................................................................................................................................... v Acknowledgements ................................................................................................................................................... vi Executive Summary .................................................................................................................................................. vii Introduction .............................................................................................................................................................. ix Qualitative Description of System Strength ........................................................................................................... x Variable Energy Resources ..................................................................................................................................... x Wind Turbine Generator Technologies ............................................................................................................. xi Solar Photovoltaic Generator Technologies ...................................................................................................
    [Show full text]
  • IEEE Northern Canada & Southern Alberta Sections, PES/IAS Joint Chapter Technical Seminar Series
    IEEE Northern Canada & Southern Alberta Sections, PES/IAS Joint Chapter Technical Seminar Series Designing Electrical Systems for On-Site Power Generation Apr 04th/05th, 2016, Calgary/Edmonton, Alberta, Canada Author: Rich Scroggins, Technical Advisor, Application Engineering Group, Cummins Power Generation Electrical Systems for Onsite Power Generation Systems . Proper generator sizing for motor loads accounting for locked rotor kVA – in “across the line” motor starting applications. – in VFD motor starting applications. Generator short circuit characteristics and their effects on arc flash incident energy. Grounding (system and/or equipment) and ground fault detection of on- site power generation systems: – When to switch the neutral in emergency standby systems – Grounding and ground fault detection schemes for paralleled generator sets in both grid connected and islanded applications Contents . Generator Control Basics . Motor Starting Requirements . Non-Linear Loads and Harmonics . Generator short circuit characteristics . Arc Flash . Generator Grounding – Neutral Switching in Low Voltage Emergency Standby Systems – Grounding of paralleled Systems Basic Generator Set Controls HMI . GC: Genset Control GC – Engine Protection – Start/Stop – Operator Interface (Alarm/Metering) GOV ENGINE . GOV: Governor – Measure Speed/Control Fuel Rate AVR GEN . AVR: Automatic Voltage Regulation – Measure Voltage/Control Excitation CB kVAR= alternator POWER kW = engine TO LOAD Engines produce kW--Fuel Rate Controls Alternators make kVAR--Excitation Controls HMI Parallelling LOAD SHARE DATA GC Load Share Control – Communicates with the load share control on the GOV ENGINE other gensets Load – Adjusts governor set point to share kW equally Share SYNC AVR GEN – Adjusts AVR set point to share kVAR equally – Load share can be Isochronous or Droop CB POWER TO LOAD Sharing kW—Controlled by Fuel (Speed) Sharing kVAR– Controlled by Excitation (Voltage) Excitation System Considerations Self excited generators - Shunt .
    [Show full text]
  • Minimum Short Circuit Ratio Requirement for MMC-HVDC Systems Based on Small-Signal Stability Analysis
    energies Article Minimum Short Circuit Ratio Requirement for MMC-HVDC Systems Based on Small-Signal Stability Analysis Zheren Zhang 1, Liang Xiao 2 , Guoteng Wang 1, Jian Yang 1 and Zheng Xu 1,* 1 College of Electrical Engineering, Zhejiang University, Hangzhou 310027, China 2 China Southern Grid Power Dispatching and Control Center, Guangzhou, Guangdong 510700, China * Correspondence: [email protected]; Tel.: +86-0571-8795-2074 Received: 26 June 2019; Accepted: 18 August 2019; Published: 26 August 2019 Abstract: This paper determines the minimum short circuit ratio (SCR) requirement for a modular multilevel converter based high-voltage direct current (MMC-HVDC) transmission systems. Firstly, a simplified model of MMC is introduced; the MMC is represented by its AC and DC side equivalent circuit. Next, by linearizing the MMC subsystem and the DC network subsystem, the deduction of the small-signal models of MMC subsystem, the small-signal model of the DC network and MMC-HVDC are carried out successively. Thirdly, the procedure for determining the minimum SCR requirement of MMC-HVDC is described. Finally, case studies are performed on a two-terminal MMC-HVDC system under four typical control schemes. The results show that the restraint factors for the rectifier MMC is predominantly the voltage safety limit constraint, and the restraint factors for the inverter MMC are mainly the phase locked loop (PLL) or the outer reactive power controller. It is suggested that the minimum SCR requirement for the sending and the receiving systems should be 2.0 and 1.5 in the planning stage. Keywords: modular multilevel converter (MMC-HVDC); small signal stability; minimum SCR; control scheme 1.
    [Show full text]
  • Allocation of Synchronous Condensers for Restoration of System Short-Circuit Power
    Downloaded from orbit.dtu.dk on: Dec 20, 2017 Allocation of synchronous condensers for restoration of system short-circuit power Marrazi, Emanuel; Yang, Guangya; Weinreich-Jensen, Peter Published in: Journal of Modern Power Systems and Clean Energy Link to article, DOI: 10.1007/s40565-017-0346-4 Publication date: 2017 Document Version Peer reviewed version Link back to DTU Orbit Citation (APA): Marrazi, E., Yang, G., & Weinreich-Jensen, P. (2017). Allocation of synchronous condensers for restoration of system short-circuit power. Journal of Modern Power Systems and Clean Energy. DOI: 10.1007/s40565-017- 0346-4 General rights Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights. • Users may download and print one copy of any publication from the public portal for the purpose of private study or research. • You may not further distribute the material or use it for any profit-making activity or commercial gain • You may freely distribute the URL identifying the publication in the public portal If you believe that this document breaches copyright please contact us providing details, and we will remove access to the work immediately and investigate your claim. 21/11/2017 e.Proofing Allocation of synchronous condensers for restoration of system Emanuel MARRAZI et al. short-circuit power Allocation of synchronous condensers for restoration of system short-circuit power Open AccessThis article is distributed under the terms of the Creative Commons Attribution 4.0 International License (http://creativecommons.org/licenses/by/4.0/), which permits unrestricted use, distribution, and reproduction in any medium, provided you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons license, and indicate if changes were made.
    [Show full text]
  • Low Short Circuit Ratio Connection of Wind Power Plants
    Low Short Circuit Ratio Connection of Wind Power Plants Master of Science Thesis Author: Anna Golieva Supervisors: Prof. Peter Palensky TU Delft - Chairman Dr. Ir. Jose Luis Rueda Torres TU Delft Prof. Trond Toftevaag NTNU Prof. Poul Ejnar Sørensen DTU Ömer Göksu DTU John Bech Siemens Wind Power Abstract Primary factor for the site selection during the planning process of the large modern wind farms is the wind climate, which is usually favorable at remote and offshore locations where the public grid is not particularly strong. Among the consequences of this solution is the necessity to connect wind farms to weak points of the grid and the necessity to reach this point by the means of long connection lines. All the mentioned factors result in a low short circuit ratio connection of wind farms becoming a frequent condition to deal with. Wind turbine manufacturers and wind farm operators have already faced various engineering prob- lems concerning the wind farms, operating in weak grids. One of them is inability to transfer the desired amount of the active power along the needed distance due to the lack of transmission capa- bility. Besides that the system has to operate at the tip of its PV curve, which makes it vulnerable to voltage instability in case of sudden changes in a system, for instance a load connection or a short circuit. Furthermore, all the modern wind farms are using power electronic converter based drivetrain system, which has numerous advantages in terms of controllability but also demonstrates much lower short circuit current capabilities, compared to the previously used synchronous genera- tor technology.
    [Show full text]
  • Guideline Notes for Generators - Submission of Grid Code Data
    GUIDELINE NOTES FOR GENERATORS - SUBMISSION OF GRID CODE DATA GUIDELINE NOTES FOR GENERATORS SUBMISSION OF GRID CODE DATA (Prepared by National Grid plc) Issue 27 Feng Xue System Technical Performance April 2008 GUIDELINE NOTES FOR GENERATORS - SUBMISSION OF GRID CODE DATA NOTES These notes of guidance have been prepared by National Grid with the aim of assisting Users in completing the relevant Schedules of the Grid Code (GC). The guidance notes do not form part of the GC, and if there is any conflict between the Guidance Notes and the GC, or any other agreement, then that agreement shall take precedence. DOCUMENT CHANGE CONTROL DETAILS ISSUE No. PUBLISHED CHANGES MADE APPROVED Issue 22 February 2001 Page 5 (User System demand) text amplified. P T Manning Issue 23 April 2001 Page 16 Governor Time Constant explanation added. Part II (Pages 19-23) : Amended to take account of NETA changes Part IV (Fault Infeeds): additional clarification provided. Issue 24 March 2004 Revision to comply with Issue 2 – Rev.14 of the GC D. Balasingam Issue 25 April 2006 Update in accordance with Grid Code Issue 3 Revision 15 K.F. Dan Issue 26 April 2007 Updates to reflect data requirement for data relating to K.F. Dan renewable generation. Contact details added. Issue 27 April 2008 Updates to reflect the changes of data requirement for data F. Xue relating to Power Park Module/Unit. Page 2 of 35 GUIDELINE NOTES FOR GENERATORS - SUBMISSION OF GRID CODE DATA INTRODUCTION..................................................................................................................................................... 5 1. CHANGES IN REGISTERED CAPACITY....................................................................................... 6 PART I .................................................................................................................................................................... 7 GUIDANCE NOTES ON DATA REGISTRATION CODE SCHEDULE 1...............................................................
    [Show full text]
  • Impact of Short-Circuit Ratio on Grid Integration of Wind Farms - a New Zealand Perspective
    2nd Int'l Conference on Large-Scale Grid Integration of Renewable Energy in India| New Delhi, India | 4-6 Sep 2019 Impact of Short-circuit Ratio on Grid Integration of Wind Farms - A New Zealand Perspective Raghavender D. Goud and Ramesh Rayudu Vikash Mantha Ciaran P. Moore School of Engineering and Electrical Design Engineer Department of Electrical and Computer Science UK Power Networks Computer Engineering Victoria University of wellington Bury St Edmunds, UK University of Canterbury Wellington, New Zealand Christchurch, New Zealand Email: [email protected] Abstract—The high wind energy potential sites are increas- ingly remote from the load centers which create problems in integrating wind power plants into power grids. One of the major issues is the short-circuit ratio (SSR) at the point of common coupling. A lower short-circuit ratio will lead to a weaker grid which in turn creates power system stability problems. The definition of a weak grid depends on short- circuit ratio values. In New Zealand, it is often noted that the definition of a weak grid, based on SSR,is different from that of standard values (of SSR) due to several reasons. New Zealands grid is long and slender with arguably major generation at one end and load centers at the other side. Close to 80% of daily consumption of electricity is generated from renewables with 5-8% contributed by Wind generation. Wind farm locations in New Zealand share the same difficulties as shared by many nations in terms of remote locations, far away from load centers and wind variability.
    [Show full text]
  • Synchronous Generators -- Odds and Ends -- a Ca Bine T O F Cur Ios Ities
    Synchronous Generators -- Odds and Ends -- a Ca bine t o f Cur ios ities Presenter - Allen Windhorn Support - [email protected] IEEE Houston CED Seminar – January 9 & 10, 2018 By LoKiLeCh - Own work, CC BY 3.0, https://commons.wikimedia.org/w/index.php?curid=12879005 Contents: 1. Arc-Flash Energy 2. Leading Power Factor, Harmonics, and UPS Loads 3. Grid Codes 4. Power Systems – Symmetrical Components and Per-Unit 5. Reference Frame Theory: Generator Models and Park’s Equations 6. Excitation System Models and Exciter Response 7. Decrement Curves 8. Synchronization and Paralleling 9. Ten Common Questions for Specifying Generators 1 1. Arc-Flash Energy 2 Key Messages • IEEE Std 1584-2002 does not address the special nature of arc flash energy from synchronous generation sources. It is based on electrical sources having fixed impedance, hence constant arc current. • Because the arc current from a synchronous generator changes with time, circuit protective devices may clear the fault earlier or later than expected. Calculations based on constant arc current may overestimate or underestimate the incident energy, leading to unforeseen hazards. • Ship power is nearly all provided by synchronous generators, so no method to calculate arc energy • A tentative method is presented to account for the changing current, based on methods in IEEE Std 242 to estimate fault current vs. time. We recommend the incorporation of some such similar method in IEEE 1584. 3 Fault Currents of a Synchronous Machine • IEEE Std 242 provides a simplified method
    [Show full text]
  • Matching Generators to Power Systems
    Matching Generators to Power Systems Allen Windhorn <[email protected]> 24 October 2019 Contents: 1. Ratings and General Considerations 2. Generator Construction 3. Reactances and Fault Currents/Decrement Curves 4. Grid Codes and Effect on Generators 5. Synchronization and Paralleling 6. Reference Frame Theory (Short Version) 7. Excitation System Models and Exciter Response 8. Synchronous Condensers (Compensators) 1 1. Ratings and General Considerations 2 Frequency, Voltage, Current, & Power • Rated frequency: determined by locale or application (usually 50 or 60 Hz but 400 Hz for aircraft ground power, other special) – Frequency variation: determined by governor and engine characteristics – Frequency is determined by RPM and poles: × • = × • RPM = 120 120 – 120: 60 seconds/minute, 2 pole pairs/cycle 3 Frequency, Voltage, Current, & Power • Rated voltage (=>flux density) affected by: – Saturation flux density of steel, geometry – Frequency – Number of stator coils (i.e. number of slots) – Number of turns in each coil – Pitch of the coils (i.e. number of slots span) – Stator parallel connections and hookup – Length and diameter of the stator lamination stack • = , is total series turns, is flux ∅ 4 ∅ Frequency, Voltage, Current, & Power • Most of the adjustable parameters (e.g. turns, parallels, slots) have discrete values (we can’t design to an exact voltage, so there are tradeoffs) • Others may be determined by specifications, physics, or economic considerations (e.g. pitch, steel characteristics) 5 Frequency, Voltage,
    [Show full text]