Design Requirement and DC Bias Analysis on HVDC Converter Transformer
Total Page:16
File Type:pdf, Size:1020Kb
Load more
Recommended publications
-
Hvdc Back to Back Connection for Power Exchange Between Electrical Grids
HVDC BACK TO BACK CONNECTION FOR POWER EXCHANGE BETWEEN ELECTRICAL GRIDS by MD. ARIFUR RAHMAN DEPARTMENT OF ELECTRICAL AND ELECTRONIC ENGINEERING DHAKA UNIVERSITY OF ENGINEERING AND TECHNOLOGY GAZIPUR December-2014 HVDC BACK TO BACK CONNECTION FOR POWER EXCHANGE BETWEEN ELECTRICAL GRIDS A Project Report Submitted in partial fulfillment of the requirements for the degree of Master of Electrical and Electronic Engineering By MD. ARIFUR RAHMAN Student No: 022219 Session: 2003-2004 Supervised By Dr. Md. Bashir Uddin Professor DEPARTMENT OF ELECTRICAL AND ELECTRONIC ENGINEERING DHAKA UNIVERSITY OF ENGINEERING AND TECHNOLOGY GAZIPUR December-2014 Declaration It is hereby declared that this project or any part of it has not been submitted elsewhere for the award of any degree or diploma. Candidate’s Signature (Md. ArifurRahman) ii Acknowledgement It is a great pleasure of the author to acknowledge respect and gratitude to the supervisor Dr. Md. Bashir Uddin, Professor, Department of Electrical and Electronic Engineering, DUET, Gazipur, for his kind cooperation, constant encouragement, valuable advice and guidance throughout the project work. Dr. Md. Bashir Uddin provided with information, comments, corrections and criticisms pertaining to the preparation of this project hand note. Without his whole-hearted supervision, this work would not have been possible. I am grateful to Dr. Md. AnowarulAbedin,Professor & Head, Department of Electrical and Electronic Engineering for providing the opportunity of completion of M. Engineering degree through extending my student-ship. I am thankful to Project Director, Manager and Engineer Colleagues of Grid Interconnection Project, Power Grid Company of Bangladesh Ltd. for providing the information against HVDC and Grid Interconnection. -
Analysis of Lightning Arrester Overloading in Future
ANALYSIS OF LIGHTNING ARRESTER OVERLOADING IN FUTURE DISTRIBUTION SYSTEMS WITH DISTRIBUTED GENERATION A Thesis by JONATHAN MICHAEL SNODGRASS Submitted to the Office of Graduate and Professional Studies of Texas A&M University in partial fulfillment of the requirements for the degree of MASTER OF SCIENCE Chair of Committee, Le Xie Committee Members, Miroslav M. Begovic Scott Miller Erick Moreno-Centeno Head of Department, Miroslav M. Begovic August 2016 Major Subject: Electrical Engineering Copyright 2016 Jonathan Snodgrass ABSTRACT The objective of this thesis is to address an issue that arises from the increasing penetration of distributed energy resources in future power systems: the design and analysis of protective devices with more complex topology and power flow patterns. In particular, this thesis investigates lightning arrester overloading and failure from fault- induced overvoltages. Currently, in existing literature and industry practice, there does not exist a readily practical and sufficiently accurate method to determine the magnitude of a fault-induced overvoltage. Thus, the length of time from the fault inception until the lightning arresters fail is unknown, forcing utility companies to assume the worst case scenario and install more costly and complex protection schemes than otherwise needed. In this thesis, the Thevenin Equivalent Impedance method is proposed to analyze a distributed generation (DG) source’s effect on the transformer high side voltage. After examining the voltage transients and determining the magnitude of the overvoltage, an optimal and cost-effective protective relaying strategy is developed and implemented. To complete this study, various types of DG sources were modeled and simulated using two test systems. Finally, the implementation of the suggested solution of intentional islanding operation of the distribution system is discussed. -
High Voltage Direct Current Transmission – Proven Technology for Power Exchange
www.siemens.com/energy/hvdc High Voltage Direct Current Transmission – Proven Technology for Power Exchange Answers for energy. 2 Contents Chapter Theme Page 1 Why High Voltage Direct Current? 4 2 Main Types of HVDC Schemes 6 3 Converter Theory 8 4 Principle Arrangement of an HVDC Transmission Project 11 5 Main Components 14 5.1 Thyristor Valves 14 5.2 Converter Transformer 18 5.3 Smoothing Reactor 20 5.4 Harmonic Filters 22 5.4.1 AC Harmonic Filter 22 5.4.2 DC Harmonic Filter 25 5.4.3 Active Harmonic Filter 26 5.5 Surge Arrester 28 5.6 DC Transmission Circuit 31 5.6.1 DC Transmission Line 31 5.6.2 DC Cable 32 5.6.3 High Speed DC Switches 34 5.6.4 Earth Electrode 36 5.7 Control & Protection 38 6 System Studies, Digital Models, Design Specifications 45 7 Project Management 46 3 1 Why High Voltage Direct Current? 1.1 Highlights from the High Voltage Direct In 1941, the first contract for a commercial HVDC Current (HVDC) History system was signed in Germany: 60 MW were to be supplied to the city of Berlin via an underground The transmission and distribution of electrical energy cable of 115 km length. The system with ±200 kV started with direct current. In 1882, a 50-km-long and 150 A was ready for energizing in 1945. It was 2-kV DC transmission line was built between Miesbach never put into operation. and Munich in Germany. At that time, conversion between reasonable consumer voltages and higher Since then, several large HVDC systems have been DC transmission voltages could only be realized by realized with mercury arc valves. -
Lightning on Transmission Line of the Harm and Prevention Measures
Lightning on transmission lines hazards and Prevention Measures Wang Qinghao, Ge Changxin, Xue Zhicheng, Sun Fengwei, Wu Shaoyong, Li Zhixuan, Shi Dongpeng, Ren Hao, Li Jinye, Ma Hui, Cao Feiyi Fushun Power Supply Company, Liaoning Electric Power Company Limited, State Grid, China, [email protected] Keywords: power transmission line, lightning hazard, prevention measures Abstract. Through the analysis of lightning to the harmfulness of the power transmission line, puts forward the specific measures to prevent lightning accidents, improving insulation, installing controllable discharge lightning rod, reducing the tower grounding resistance, adding coupling ground wire and the proper use of send arrester electrical circuit transmission line. And take on the unit measures nearly were compared, statistics and analysis. Introduction Lightning accident is always an important factor affecting the reliability of the power supply of the electric line to send. Because of the randomness and complexity of lightning activity in the atmosphere, currently the world's research on knowledge transmission line lightning and many unknown elements. Lightning accident of overhead power transmission line is always a problem of safe power supply, lightning accidents accounted for almost all the accidents of 1/2 or more line. Therefore, how to effectively prevent lightning, lightning damage reduced to more and more by transmission line of the relevant personnel to pay attention[1-2]. At present, the measures of lightning protection of transmission line itself mainly rely on the erection of the overhead ground wire of the tower top, its operation and maintenance work is mainly on the detection and reconstruction of tower grounding resistance. Due to its single lightning protection measures, can not well meet the requirements of lightning protection. -
Power Electronics for Distributed Energy Systems and Transmission and Distribution Applications
ORNL/TM-2005/230 POWER ELECTRONICS FOR DISTRIBUTED ENERGY SYSTEMS AND TRANSMISSION AND DISTRIBUTION APPLICATIONS L. M. Tolbert T. J. King B. Ozpineci J. B. Campbell G. Muralidharan D. T. Rizy A. S. Sabau H. Zhang* W. Zhang* Y. Xu* H. F. Huq* H. Liu* December 2005 *The University of Tennessee-Knoxville ORNL/TM-2005/230 Engineering Science and Technology Division POWER ELECTRONICS FOR DISTRIBUTED ENERGY SYSTEMS AND TRANSMISSION AND DISTRIBUTION APPLICATIONS L. M. Tolbert T. J. King B. Ozpineci J. B. Campbell G. Muralidharan D. T. Rizy A. S. Sabau H. Zhang W. Zhang Y. Xu H. F. Huq H. Liu Publication Date: December 2005 Prepared by the OAK RIDGE NATIONAL LABORATORY Oak Ridge, Tennessee 37831 managed by UT-BATTELLE, LLC for the U.S. DEPARTMENT OF ENERGY Under contract DE-AC05-00OR22725 DOCUMENT AVAILABILITY Reports produced after January 1, 1996, are generally available free via the U.S. Department of Energy (DOE) Information Bridge. Web site http://www.osti.gov/bridge Not available externally. Reports are available to DOE employees, DOE contractors, Energy Technology Data Exchange (ETDE) representatives, and International Nuclear Information System (INIS) representatives from the following source. Office of Scientific and Technical Information P.O. Box 62 Oak Ridge, TN 37831 Telephone 865-576-8401 Fax 865-576-5728 E-mail [email protected] Web site http://www.osti.gov/contact.html This report was prepared as an account of work sponsored by an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights. -
Application and Analysis for Surge Arrester on Lightning Protection of Distribution Network
MATEC Web of Conferences 40, 007 10 (2016) DOI: 10.1051/matecconf/20164007010 C Owned by the authors, published by EDP Sciences, 2016 Application and Analysis for Surge Arrester on Lightning Protection of Distribution Network Daxing WANG1 , Bin HE 1 ,Wei ZHONG 1,Bo LIN 1, Dong WANG1, Tingbin LI 1 1 SICHUAN TONG YUAN ELECTRIC POWER SCIENCE&TECHNOLOGY CO., LTD, Chengdu,China Abstract. In order to effectively reduce lightning stroke outage rate, effect of lightning protection with surge arrester on transmission line has been generally acknowledged relative to other lightning protection measures. This article introduces in such aspects as the working principle of line surge arrester and effect of lightning protection, and also explores application for lightning arrester of distribution network to achieve difference lightning protection and improve the lightning protection performance of distribution network. Keywords: Surge arrester, lightning protection, distribution network. 1 Introduction According to operational experience at home and abroad, 2 The working principle of surge lightning stroke is the main reason to cause line tripping arrester and service interruption, according to the statistical report of interruption of service in china, 40%~70% of the Surge arrester generally uses the body and air gap, and accident in the power system are caused by lightning surge arrester does not assume system operating voltage, which has brought a great loss to national economy. without considering the long-running voltage electrical In general, the methods which include improving the aging, also the body failure does not affect operation. insulation level of line, decreasing grounding resistance, When a lightning flash directly strikes the tower, part decreasing protection angle and so on have been used in of the lightning current flows through the grounding wire cutting down lightning accidents. -
Basics of HVDC: AC Compared DC
Basics of HVDC: AC compared to DC Dr. Ram Adapa Technical Executive, EPRI [email protected] HVDC Lines and Cables Course June 12, 2017 © 2017 Electric Power Research Institute, Inc. All rights reserved. Increased Benefits of Long Distance Transmission .Carrying energy from cheap generation sources which are far away from the load centers. .Long distance transmission increases competition in new wholesale electricity markets . Long distance electricity trade could include across nations or multiple areas within a nation and allows arbitrage of price differences .Long distance transmission allows interconnection of networks and thus reducing the reserve margins across all networks. .More stable long distance transmission is needed to meet contractual obligations 2 © 2017 Electric Power Research Institute, Inc. All rights reserved. Transmitting Fuel versus Transmitting Energy .Load centers can be served by: – Long distance transmission with remote generation – Transmitting fuel to the local generation facilities .Bottom line is Economics to see which option is better .Depends on many factors – Type of fuel – coal can be transported, hydro can’t – Cost of transporting fuel to local generators – Availability of generation facilities close to load centers – Allowable pollution levels at the local gen. facilities 3 © 2017 Electric Power Research Institute, Inc. All rights reserved. Long Distance Transmission – AC versus DC .AC versus DC debate goes back to beginnings of Electricity – DC was first (Thomas Edison) – AC came later (Tesla / Westinghouse) .AC became popular due to transformers and other AC equipment .Long Distance Transmission – AC versus DC - based on economics and technical requirements 4 © 2017 Electric Power Research Institute, Inc. All rights reserved. 5 5 © 2017 Electric Power Research Institute, Inc. -
Lightning Performance of Medium Voltage Transmission
ISSN 2319-8885 Vol.03,Issue.16 July-2014, Pages:3362-3367 www.semargroup.org, www.ijsetr.com Lightning Performance of Medium Voltage Transmission Line Protected by Surge Arresters 1 2 NANG KYU KYU THIN , KHIN THUZAR SOE 1Dept of Electrical Power Engineering, Mandalay Technological University, Mandalay, Myanmnar, E-mail: [email protected]. 2Assoc Prof, Dept of Electrical Power Engineering, Mandalay Technological University, Mandalay, Myanmnar, E-mail: [email protected]. Abstract: Lightning strikes to overhead transmission lines are a usual reason for unscheduled supply interruption in the modern power system, In an effort to maintain failure rates in a low level, providing high power quality and avoiding damages and disturbances, plenty of lightning performance estimation studies have been conducted and several design methodologies have been proposed. The protection of overhead transmission lines is achieved using shield wires and surge arresters. Surge arresters should be insulators at any voltage below the protected voltage, and good conductor at ant voltage above. to pass the energy of the lightning strike to ground. In this work an analysis of the lightning performance of 33 kV Aung Pin Lae - Myoma transmission line. The line is protected with only surge arresters and the current simulation of surge arrester is implemented on the sending end and receiving end of the network. By increasing the tower footing resistance, the lightning failure rate become greater. Smaller arresters intervals decerase the failure rate. The results of the current work could be useful for the maintenance and the design of Aung Pin Lae - Myoma 33 kV transmission line. Keywords: Shield Wire, Surge Arrester, Tower Footing Resistance, Transmission Line. -
HVDC Transmission PDF
High Voltage Direct Current Transmission – Proven Technology for Power Exchange 2 Contents Chapter Theme Page Contents 3 1Why High Voltage Direct Current? 4 2 Main Types of HVDC Schemes 6 3 Converter Theory 8 4Principle Arrangement of an 11 HVDC Transmission Project 5 Main Components 14 5.1 Thyristor Valves 15 5.2 Converter Transformer 18 5.3 Smoothing Reactor 21 5.4 Harmonic Filters22 5.4.1 AC Harmonic Filter 23 5.4.2 DC Harmonic Filter 25 5.4.3 Active Harmonic Filter 26 5.5 Surge Arrester 28 5.6 DC Transmission Circuit 5.6.1 DC Transmission Line 31 5.6.2 DC Cable 33 5.6.3 High Speed DC Switches 34 5.6.4 Earth Electrode 36 5.7 Control & Protection 38 6System Studies, Digital Models, 45 Design Specifications 7Project Management 46 3 1 Why High Voltage Direct Current ? 1.1 Highlights from the High Line-Commutated Current Sourced Self-Commutated Voltage Sourced Voltage Direct Current (HVDC) History Converters Converters The transmission and distribution of The invention of mercury arc rectifiers in Voltage sourced converters require electrical energy started with direct the nineteen-thirties made the design of semiconductor devices with turn-off current. In 1882, a 50-km-long 2-kV DC line-commutated current sourced capability. The development of Insulated transmission line was built between converters possible. Gate Bipolar Transistors (IGBT) with high Miesbach and Munich in Germany. voltage ratings have accelerated the At that time, conversion between In 1941, the first contract for a commer- development of voltage sourced reasonable consumer voltages and cial HVDC system was signed in converters for HVDC applications in the higher DC transmission voltages could Germany: 60 MW were to be supplied lower power range. -
Operational Strategies for HVDC Transmission in Smart Grids: the Security Versus Markets Dilemma
Operational strategies for HVDC transmission in smart grids: the security versus markets dilemma Master Thesis Chanpreet Kaur Talwar Technische Universiteit Delft OPERATIONAL STRATEGIES FOR HVDC TRANSMISSION IN SMART GRIDS: THE SECURITY VERSUS MARKETS DILEMMA MASTER THESIS by Chanpreet Kaur Talwar in partial fulfillment of the requirements for the degree of Master of Science in Electrical Engineering and Computer Science (Intelligent Electrical Power Grids) at the Delft University of Technology, to be defended publicly on Monday August 28, 2017 at 10:00 AM. Supervisors: Prof. dr. Peter Palensky, TU Delft Dr. ir. Georgios Papaefthymiou, Elia Grid International, Germany Ir. Martijn de Jong, TU Delft Thesis committee: Prof. dr. Peter Palensky, TU Delft Dr. ir. Jose Luis Rueda Torres, TU Delft Dr. Domenico Lahaye, TU Delft Ir. Martijn de Jong, TU Delft An electronic version of this thesis is available at http://repository.tudelft.nl/. Preface First of all, I wish to thank my responsible supervisor, prof. Peter Palensky for guiding me in pursuing my thesis under his kind patronage, and allowing me to be a part of the Intelligent Electrical Power Grid (IEPG) research group in the Netherlands. Second and foremost, I am highly thankful to my daily su- pervisor Martijn De Jong for his monetary and moral support during the course of thesis studies. Words cannot express my sincere appreciation, but all I can say is that I shall always remain highly obliged and grateful to you for supervising my work, and finding time for me from your busy schedule to clarify all my queries and doubts in the best possible way. -
"Lightning" Arrester
SECONDARY HE900 SURGE 480VAC "LIGHTNING" 3∅, 3W FEATURES ARRESTER • Industrial/Commercial Version • MOV Circuit Design • Made in America utilizing American Components • Cost Effective • Reliable Solid-State Protection • Maintenance Free • Molded Plastic Case • Threaded 1/2" NPT conduit nipple with locknut • 18 " Stranded 12 AWG color coded leads • Suitable for indoor or outdoor installation • Automatic Recovery, Self Restoring DESCRIPTION The HE900 is a MOV (Metal Oxide Varistor) based hardwired Secondary Surge Arrester, often referred to as a Lightning Arrester. The device is designed to protect electrical equipment from damaging effects of Spikes (+) and Notches (-) caused by lightning, utility switching, insulation arcing, electrical motor cycling, and other large or sudden changes in electrical power flow on incoming AC power lines. The HE900 is a three phase, three wire arrester intended to protect 480 VAC systems. The epoxy encapsulated arrester is designed to be easily installed in any position indoors or outdoors utilizing the integral 1/2" threaded nipple and supplied metal lock nut. The housing is molded from flame retardant plastic that is both weather and UV resistant, and complies with the UL standard for strength and flame resistance properties. The arrester is sealed with UL component recognized epoxy potting compound. The HE900 has three 18" long, 12 AWG multi-stranded leads that are color coded for ease of installation. The HVPSI HE900 is ideal protection for outdoor lighting and pole lamps, panelboards, oilfield pumps, workshops, irrigation and sump pumps, refrigeration systems, farm equipment including milking machines and poultry processing equipment, electric motors and controls, heat pumps and air conditioning equipment and many other electrical devices. -
Holistic Approach to Offshore Transmission Planning in Great Britain
OFFSHORE COORDINATION Holistic Approach to Offshore Transmission Planning in Great Britain National Grid ESO Report No.: 20-1256, Rev. 2 Date: 14-09-2020 Project name: Offshore Coordination DNV GL - Energy Report title: Holistic Approach to Offshore Transmission P.O. Box 9035, Planning in Great Britain 6800 ET Arnhem, Customer: National Grid ESO The Netherlands Tel: +31 26 356 2370 Customer contact: Luke Wainwright National HVDC Centre 11 Auchindoun Way Wardpark, Cumbernauld, G68 Date of issue: 14-09-2020 0FQ Project No.: 10245682 EPNC Report No.: 20-1256 2 7 Torriano Mews, Kentish Town, London NW5 2RZ Objective: Analysis of technical aspects of the coordinated approach to offshore transmission grid development in Great Britain. Overview of technology readiness, technical barriers to integration, proposals to overcome barriers, development of conceptual network designs, power system analysis and unit costs collection. Prepared by: Prepared by: Verified by: Jiayang Wu Ian Cowan Yongtao Yang Riaan Marshall Bridget Morgan Maksym Semenyuk Edgar Goddard Benjamin Marshall Leigh Williams Oluwole Daniel Adeuyi Víctor García Marie Jonette Rustad Yalin Huang DNV GL – Report No. 20-1256, Rev. 2 – www.dnvgl.com Page i Copyright © DNV GL 2020. All rights reserved. Unless otherwise agreed in writing: (i) This publication or parts thereof may not be copied, reproduced or transmitted in any form, or by any means, whether digitally or otherwise; (ii) The content of this publication shall be kept confidential by the customer; (iii) No third party may rely on its contents; and (iv) DNV GL undertakes no duty of care toward any third party. Reference to part of this publication which may lead to misinterpretation is prohibited.