Potential for Free-Cooling by Ventilation

Total Page:16

File Type:pdf, Size:1020Kb

Potential for Free-Cooling by Ventilation Solar Energy 80 (2006) 402–413 www.elsevier.com/locate/solener Potential for free-cooling by ventilation Cristian Ghiaus a,b,*,1, Francis Allard a a Laboratoire d’Etude des Phenomenes de Transfert Appliques au Batiment (LEPTAB), Universite´ de La Rochelle, Av. M. Cre´peau, 17000 La Rochelle, France b Technical University of Civil Engineering, Bd. P. Protopopescu, Bucharest, Romania Received 24 November 2004; received in revised form 31 May 2005; accepted 31 May 2005 Available online 29 September 2005 Abstract Natural ventilation is one of the most effective techniques for cooling. Its potential for cooling may be assessed by using a method based on the indoor–outdoor temperature difference of the free-running building, the adaptive comfort criteria and the outdoor temperature. It is demonstrated that the free-running temperature may be used instead of the balance temperature in energy estimation methods. The indoor–outdoor temperature difference of the free-running building becomes a characteristic of the thermal behavior of the building which is decoupled from comfort range and outdoor tem- perature. A measure related to the energy saved and the applicability of free-cooling is given by the probabilistic distribu- tion of the degree-hours as a function of the outdoor temperature and time. Weather data for this method are available in public domain from satellite investigation. The method can be applied when buildings similar to existing ones are con- structed in a new location, when existing buildings are retrofitted or when completely new buildings are designed. The method may be used to interpret the results of building simulation software or of the field measurements. Ó 2005 Elsevier Ltd. All rights reserved. Keywords: Natural ventilation; Energy; Building design; Free-running temperature 1. Introduction Augenbroe, 2002). Building simulation programs are based on first principles and require as inputs The most important decisions that affect the ther- the geometry of the building, the comfort criteria mal performance of buildings are taken in the initial and even the specification of the HVAC technology. stages of design (Holm, 1993; de Wilde et al., 2002). These prerequisites make simulation more adapted Design evaluation may be supported by the results for evaluations in the final stages of design rather of building simulation, by simplified guidelines or than a support for decisions when the building is by expert advice based on experience (deWit and sketched (Clarke, 1985; Shaviv, 1998; Al-Homoud, 2000; Hong et al., 2000; Olsen and Chen, 2003; * Corresponding author. Address: Laboratoire dÕEtude des Clarke et al., 2004). In the initial design, the archi- Phenomenes de Transfert Appliques au Batiment (LEPTAB), tects have many important issues on which the pro- Universite´ de La Rochelle, Av. M. Cre´peau, 17000 La Rochelle, ject is evaluated and investing more in thermal France. Tel.: +33 5 4645 7259; fax: +33 5 4645 8241. E-mail address: [email protected] (C. Ghiaus). design would make them less competitive. The ther- 1 ISES Member. mal analysis is done usually by engineers after the 0038-092X/$ - see front matter Ó 2005 Elsevier Ltd. All rights reserved. doi:10.1016/j.solener.2005.05.019 C. Ghiaus, F. Allard / Solar Energy 80 (2006) 402–413 403 Nomenclature dhc degree-hour for cooling (K h) Qc energy needed for cooling (J) dhfr degree-hour for free-cooling (K h) Tb balance temperature (K) DHc frequency distribution of degree-hour for Tbin temperature interval for a bin (K) cooling Tcl lower limit of comfort temperature (K) DHfc frequency distribution of degree-hour for Tcu upper limit of comfort temperature (K) free-cooling Tdiff temperature difference between indoor DHmc frequency distribution of degree-hour for and outdoor in free-running (K) mechanical cooling Tfr free-running temperature (K) f relative density To outdoor temperature (K) Ktot total cooling loss coefficient of the build- ing (W/K) Greek letters N total number of samples dc condition for cooling (À) Pdf probability distribution dfr condition for free-cooling (À) Pr probability density dmc condition for mechanical cooling (À) qc energy rate needed for cooling (W) qgain total heat gains from sun and internal sources (W) building is designed in order to estimate the heating the thermal mass (Zalba et al., 2003; Khudhair and cooling loads. Energy consumption can be esti- and Farid, 2004). Putting the problem in this way mated and checked if it is within accepted limits, allows us to assess the potential of architectural ele- complying thus with minimal requirements (Mihala- ments, e.g. sun-space for heating and cooling (Argi- kakou et al., 2002; CSTB, 2003). But these calcula- riou et al., 1994; Mihalakakou, 2002), green roofs tions have practically no influence on the building (Del Barrio, 1998) and pond roofs (Kishore, 1988; design (Ellis and Mathews, 2001). Since the thermal Erell and Etzion, 2000), or methods, such as passive calculations are not done in the initial stages of de- cooling (Belarbi and Allard, 2001). sign, it is essential that the architects are able to take The potential of free-cooling represents a mea- decisions that affect the thermal design. They can sure of the capability of ventilation to ensure indoor use simplified models (Ellis and Mathews, 2001), a comfort without using mechanical cooling systems. combination of simplified models and expert knowl- A way to measure this ability is by using a variant edge (Yezioro and Shaviv, 1996; Shaviv, 1999), or of the bin method in which the annual energy con- just rules of thumb based on acquired experience. sumption is evaluated for different temperature Although these results are not optimal, the heuristic intervals and time periods. The energy consumption rules indicate design solutions for building orienta- is estimated for several values of the outdoor tem- tion, geometry, and thermal mass (Shaviv et al., perature, called bins, and then the total is obtained 1996; Shaviv, 1999). by multiplying by the number of hours in the tem- Another approach would be to consider the perature interval (ASHRAE, 2001a,b). The bin building as a system that should have the potential method employs the balance temperature for calcu- to ensure indoor comfort. The indoor temperature lating the degree-hours in a bin. Balance tempera- is the result of the balance of energy fluxes and accu- ture concept supposes that the indoor temperature mulation. Then, from a thermal point of view, the is constant which implies the use of a heating or aim of the architectural design is to provide the po- air conditioning system. In buildings that use natural tential to implement the control of the energy fluxes ventilation, the indoor temperature varies making through the envelope and to allow energy storage in the concept of balance temperature unsuitable. the building structure. Arguably, the main gains are In order to estimate the relative influence of the solar and internal (Givoni, 1991; Littlefair, 1998), building design, of the comfort criteria and of the the main losses are by advection and conduction climate, it is important to have a method that (Florides et al., 2002), and the energy storage is in decouples these three characteristics. 404 C. Ghiaus, F. Allard / Solar Energy 80 (2006) 402–413 2. Thermal comfort zone Fig. 1 shows a comparison of the comfort zones for the European climatic conditions. The comfort Thermal comfort standards specify the range of range in real HVAC controlled buildings (Fountain conditions or comfort zones where 80% of sedentary et al., 1996) is compared to the ASHRAE comfort or slightly active people feel the environment ther- zone (ASHRAE, 2001a,b) and the standard for nat- mally acceptable. ASHRAE Standard 55 indicates ural ventilation (Brager and de Dear, 2000). The summer and winter comfort zones that correspond approximate parameters of the comfort zones are to typical clothing level of 0.5 and 0.9 clo, respec- given in Table 1. According to the comfort standard tively. ASHRAE comfort range is 3 °C, with a sea- for natural ventilation, the indoor mean tempera- sonal shift of 3 °C(ASHRAE, 2001a,b). Field ture in summer is considered to be 25 °C, corre- studies showed that indoor temperature in fully sponding to the mean monthly temperature of HVAC controlled buildings is maintained in nar- 22 °C(Fig. 2). This comfort standard may be used rower ranges, with the mean temperature of 23 °C, for thermal adaptive control of buildings (McCart- standard deviation of 1–1.5 °C and seasonal shift ney and Nicol, 2002). of 0.5–1 °C(Fountain et al., 1996). But because people adapt themselves to the environment, ther- 3. Balance temperature and the free-running mal comfort in naturally ventilated buildings has temperature larger seasonal ranges than assumed by ISO 7730 and ASHRAE 55 Standards (de Dear et al., 1997; A common way to compare the energy consump- Brager and de Dear, 1998; Nicol and Humphreys, tion of buildings is by applying the bin method 2002). (ASHRAE, 2001a,b). The estimation of the degree 32 30 c d 28 C) ° 26 b 24 a 22 20 (a) A/C 18 (b) ASHRAE Indoor comfort temperature ( 16 (c) 90% accept. in NV (d) 80% accept. in NV 14 0 51015 20 25 30 3540 Mean monthly temperature (°C) Fig. 1. Comfort range for air conditioning and for natural ventilation: (a) air conditioning; (b) ASHRAE comfort range; (c) natural ventilation, 90% acceptability limits; (d) natural ventilation, 80% acceptability limits (Table 1). Table 1 Comfort zones Mean Winter mean Summer mean Range Seasonal shift (°C) (°C) (°C) (°C) (°C) (a) Air conditioned buildings 23.0 22.5 23.5 1.5 1.0 (b) ASHRAE comfort zone 23.5 22.1 24.9 3.5 2.7 (c) Standard for natural ventilation, 90% acceptability limits 23.9 19.5 25.0 max 28.3 5.0 8.8 (d) Standard for natural ventilation, 80% acceptability limits 23.9 19.5 25.0 max 28.3 7.0 8.9 C.
Recommended publications
  • Page 1 OPTIMAL ENERGY MANAGEMENT of HVAC
    Page 1 OPTIMAL ENERGY MANAGEMENT OF HVAC SYSTEMS BY USING EVOLUTIONARY ALGORITHM Session Number: CIB T2S5 Authors Fong K F, BEng, MSc, CEng, MCIBSE, MHKIE, MASHRAE Hanby V I, BSc, PhD, CEng, MInstE, MCIBSE Chow T T, PhD, CEng, MIMechE, MCIBSE, FHKIE, MASHRAE Abstract The available plant and energy simulation packages become robust and user-friendly, and this is the major reason that they are so popular even in the consultancy fields in these few years. In fact, these plant and energy simulation packages can be widely adopted in studying different alternatives of the operation of HVAC and building services systems. Since there are many parameters involved in different equipment and systems, one of the useful areas of studies is to optimize the essential parameters in order to provide a satisfactory solution for design or operation in terms of efficient and effective facilities management. Therefore in this paper, the simulation-optimization approach is proposed for effective energy management of HVAC systems. Due to the complexity of the HVAC systems, which commonly include the refrigeration, water and air side systems, it is necessary to suggest optimal conditions for different operation according to the dynamic cooling load requirements throughout a year. A simulation-EA coupling suite has been developed by using the metaheuristic skill, and the evolutionary algorithm can be effectively used to handle the discrete, non-linear and highly constrained characteristics of the typical HVAC and building services optimization problems. The effectiveness of this simulation-EA coupling suite has been demonstrated through the establishment of the monthly optimal reset scheme of the chilled water supply temperature of a local central chiller plant.
    [Show full text]
  • Ene04 Low Carbon Design Low and Zero Carbon Technologies
    Ene04 Low carbon design Low and zero carbon technologies Actions: i. Implement LZC (low and zero carbon) technologies in-line with the LZC feasibility study ii. Implement passive design measures and free cooling technologies in line with the previous analysis undertaken Recognised local LZC technologies Technologies eligible to contribute to achieving the criteria must produce energy from renewable sources and meet all other ancillary requirements as defined by Directive 2009/28/EC. Local does not have to mean on site – community schemes near to the site can be used as a way of demonstrating compliance. The following requirements must also be met: 1. There must be a direct supply of energy produced to the building under assessment. 2. Technologies under 50 kWe or 45 kWth must be certified by a Microgeneration Certification Scheme (MCS), or equivalent, and installed by MCS (or equivalent) certified installers. 3. Combined heat and power (CHP) schemes above 50 kWe must be certified under the CHPQA standard. CHP schemes fuelled by mains gas are eligible to contribute to performance against this issue. 4. Heat pumps can only be considered as a renewable technology when used in heating mode. Refer to Annex VI of Directive 2009/28/EC for more detail on accounting for energy from heat pumps. 5. Where MCS or CHPQA certification is not available, the design team must investigate the availability of alternative accreditation schemes in line with the Directives listed above, or an equivalent country or regional directive or standard. Where an accreditation scheme exists, it should be used for the purpose of verifying compliance of the specified LZC technology.
    [Show full text]
  • Demand-Response Management of a District Cooling Plant of a Mixed Use City Development
    Demand-Response Management of a District Cooling Plant of a Mixed Use City Development Segu Madar Mohamed Rifai Master of Science Thesis KTH - Royal Institute of Technology School of Industrial Engineering and Management Department of Energy Technology SE-100 44 STOCKHOLM Thesis Registration No.: EGI- 2012-011MSC Title: Demand-Response Management of a District Cooling Plant of a Mixed Use City Development. SEGU MADAR MOHAMED RIFAI Student Number: 731222 A-315 Approved Examiner Supervisor at KTH Date: 05/06/2012 Prof. Björn Palm Dr. Samer Sawalha Local Supervisor Dr. Hari Gunasingam Commissioner Contact person i | P a g e Abstract Demand for cooling has been increasing around the world for the last couple of decades due to various reasons, and it will continue to increase in the future particularly in developing countries. Traditionally, cooling demand is met by decentralised electrically driven appliances which affect energy, economy and environment as well. District Cooling Plant (DCP) is an innovative alternative means of providing comfort cooling. DCP is becoming an essential infrastructure in modern city development owning to many benefits compared to decentralized cooling technology. Demand Response Management (DRM) is largely applied for Demand Side management of electrical grid. Demand of electrical energy is closely connected with the demand of alternative form of energy such as heating, cooling and mechanical energy. Therefore, application of DR concept should be applied beyond the electrical grid; in particular, it could be applied to any interconnected district energy systems. District Cooling Plant is one of a potential candidate and Demand Response management solutions can be applied to DCP for sustainable operation.
    [Show full text]
  • Free Cooling – Outside Air Economizer White Paper #11
    FREE COOLING – OUTSIDE AIR ECONOMIZER WHITE PAPER #11 It’s like opening a window when it’s hot inside and cool outside. How much does it save? The easy answer is ‘it depends.’ To really find out, read further. You’ll see there are a lot of factors. Like all heat recovery concepts, a pre-requisite for success is to have the free heat (or free cooling) available at the same location and time as there is a need for it. The free heat in Atlanta has no practical use in Alaska because they are too far apart. Likewise, free cooling from outdoors doesn’t provide any value unless it is warm indoors at that time. Balance Temperature Buildings are like boxes. They have thermal losses and gains through the shell (envelope), and they also have appliances and activities inside that generate heat. See Figure 1. There will be a point where the envelope loss just matches the internal heat gains and neither heating nor cooling is required; above this ‘balance temperature’, cooling will be required. Source: Commercial Energy Auditing Reference Handbook, 3e Doty,S., Fairmont Press. Figure 1. Thermal Balance Temperature FREE COOLING – OUTSIDE AIR ECONOMIZER White Paper What is your building’s balance temperature? A building’s thermal balance temperature can be estimated with a method called regression, but there are also clues. See Table 1. If there is a lot of heat-producing equipment inside, the building becomes self- heating and will include hours in cooling mode when it is cold outside. Opportunity! If the heating and cooling load is mostly from envelope (not a lot of equipment), the balance point will be higher which means it probably won’t be hot inside while it is cold outside.
    [Show full text]
  • A Comprehensive Review of Thermal Energy Storage
    sustainability Review A Comprehensive Review of Thermal Energy Storage Ioan Sarbu * ID and Calin Sebarchievici Department of Building Services Engineering, Polytechnic University of Timisoara, Piata Victoriei, No. 2A, 300006 Timisoara, Romania; [email protected] * Correspondence: [email protected]; Tel.: +40-256-403-991; Fax: +40-256-403-987 Received: 7 December 2017; Accepted: 10 January 2018; Published: 14 January 2018 Abstract: Thermal energy storage (TES) is a technology that stocks thermal energy by heating or cooling a storage medium so that the stored energy can be used at a later time for heating and cooling applications and power generation. TES systems are used particularly in buildings and in industrial processes. This paper is focused on TES technologies that provide a way of valorizing solar heat and reducing the energy demand of buildings. The principles of several energy storage methods and calculation of storage capacities are described. Sensible heat storage technologies, including water tank, underground, and packed-bed storage methods, are briefly reviewed. Additionally, latent-heat storage systems associated with phase-change materials for use in solar heating/cooling of buildings, solar water heating, heat-pump systems, and concentrating solar power plants as well as thermo-chemical storage are discussed. Finally, cool thermal energy storage is also briefly reviewed and outstanding information on the performance and costs of TES systems are included. Keywords: storage system; phase-change materials; chemical storage; cold storage; performance 1. Introduction Recent projections predict that the primary energy consumption will rise by 48% in 2040 [1]. On the other hand, the depletion of fossil resources in addition to their negative impact on the environment has accelerated the shift toward sustainable energy sources.
    [Show full text]
  • Hvacwatersystems Waterside Free Cooling.Pdf
    HVAC Water Systems Waterside Free Cooling Summary Free cooling utilizes the evaporative cooling capacity of a cooling tower to indirectly produce chilled water for use in medium temperature loops, such as process cooling loops and sensible cooling loops. Free cooling is best suited for climates that have wetbulb temperatures lower than 55°F for 3,000 or more hours per year. It is most effectively applied to serve process and/or sensible cooling loops that between 50°F–70°F chilled water. Table 1. Free Cooling Application At least 3000 hours per Applicability year where wet bulb temperature is below: 55°F Process cooling water Process cooling, sensible 45°F cooling 35°F All chilled water use 1. Assumes process cooling water is between 60 to 70°F. 2. Assumes sensible cooling water is between 50 to 55°F. Principles • Chilled water systems use chillers that typically operate at 0.5 to 0.7 kW/ton in a partial load regime while free cooling systems typically operate at 0.05 to 0.15 kW/ton. 1 • A flat plate heat exchanger is used to isolate the chilled water loop from the open tower condenser water. With few exceptions, tower water is not reliably clean enough for use directly in the cooling loop. • The approach temperature on a cooling tower is critical for best results. A low approach temperature on the tower is critical to achieve the highest energy savings. • A traditional chiller is used to provide cooling during hot periods and as an always-available emergency backup. For a portion of the year, free cooling offers a non-compressor based backup to the traditional chiller.
    [Show full text]
  • Melink Intelli-Hood Snapshot of 4 Melink Customers a New Standard in Kitchen Ventilation Intelli-Hood Kitchen Ventilation Controls
    ®® Case Studies Melink Intelli-Hood Snapshot of 4 Melink customers A New Standard in Kitchen Ventilation Intelli-Hood Kitchen Ventilation Controls Savings & Benefits Other Intelli-Hood® Advantages Improves Energy Efficiency ® The Intelli-Hood controls improve energy efficiency 1. Eliminate drive losses and belt Supermarket Restaurant Hotel University by reducing the exhaust and make-up fan speeds during maintenance by specifying direct Annual energy savings Annual energy savings Annual energy savings idle periods. Typical annual operating savings are Annual energy savings drive fans. per location per location per location per location $1,500-$3,000 per hood, with a payback of 1-3 years. $2,340 $2,040 $5,500 $5,580 2. Reduce humidity problems associated Improves Kitchen Comfort ® with a negative building pressure. Current payback Current payback Current payback Current payback The Intelli-Hood controls improve kitchen comfort 1.8 years 2.2 years 2.1 years 2.3 years by reducing the supply of hot/humid make-up air during 3. Improve hood and building air idle periods. They also serve as an economizer when balance with variable-speed controls indoor and outdoor conditions are right for free cooling. Finally, the Intelli-Hood® controls reduce hood noise in the (verses belts and pulleys). kitchen up to 90% when the fans slow down. 4. Extend HVAC equipment life by Before-and-After Energy Savings Improves Fire Safety reducing run time and thus wear/tear The Intelli-Hood® controls can improve fire safety by of compressors, motors, heaters, etc. KW with the Intelli-Hood® monitoring the exhaust air temperature. If the temperature Actual reading from a current Intelli-Hood supermarket ® 5.
    [Show full text]
  • Echnica L Ssista Nce Tu Dy Umass Memorial Medical Center
    UMASS MEMORIAL MEDICAL CENTER POWER PLANT 55 LAKE AVENUE NORTH WORCESTER, MA T ECHNICAL ECHNICAL A SSISTANCE SSISTANCE PREPARED FOR S TUDY DCAMM Prepared by B2Q Associates, Inc. Andover, MA Revision Date 12/21/2015 TECHNICAL ASSISTANCE STUDY - WATERSIDE ECONOMIZER UMASS MEMORIAL MEDICAL CENTER - POWER PLANT Introduction .................................................................................................................................... 3 Contacts .......................................................................................................................................... 5 Approach & Modeling Methodology .............................................................................................. 6 Executive Summary Table ............................................................................................................... 7 Facility & Process Description ......................................................................................................... 8 Annual Chilled Water Load Profile ................................................................................................ 11 Energy Modeling Methodology .................................................................................................... 15 Baseline Chiller Plant Modeling ................................................................................................ 15 Power Plant Modeling............................................................................................................... 17 Energy Conservation
    [Show full text]
  • "Free" Cooling Using Water Economizers
    engineers newsletter volume 37–3 • providing insights for today’s hvac system designer "free" cooling using Standard 90.1 requirements Water Economizers The following sections of the Standard 90.1 prescriptive path are relevant for water economizers.[4] from the editor … Why economize? In past newsletters, we addressed the ability to accomplish "free" cooling by There are times of the year when a Section 6.5.1 Economizers. "Each artfully rearranging traditional cooling cooling system…" over the size equipment [1] and other ways to achieve system can use outdoor conditions to byproduct cooling virtually for free.[2] cool the building or process using the thresholds shown below "that has a fan We’ve also provided newsletters that standard cooling components to shall include either an air or water discussed air economizers and energy distribute its cooling effect. economizer." There are nine exceptions: code requirements.[3] small individual fan cooling units, In this EN, Susanna Hanson (Trane The most prevalent technique is an air spaces humidified above 35°F (2ºC) applications engineer) focuses on the economizer. When the temperature, or dew point for processes, systems with traditional methods of water-side enthalpy, of the outdoor air is low, condenser heat recovery, some economizing and associated energy code requirements. cooler outdoor air is used to reduce the residential applications, and systems temperature (or enthalpy) of air entering with minimal hours or cooling loads. the cooling coil. This can reduce or There is also an option to use higher eliminate mechanical cooling for much Let’s start with some definitions. efficiency equipment in lieu of an of the year in many climates.
    [Show full text]
  • Investigation of Separated Two-Phase Thermosiphon Loop for Relieving the Air-Conditioning Loading in Datacenter
    energies Article Investigation of Separated Two-Phase Thermosiphon Loop for Relieving the Air-Conditioning Loading in Datacenter Hafiz M. Daraghmeh 1 , Mohammed W. Sulaiman 1 , Kai-Shing Yang 2 and Chi-Chuan Wang 1,* 1 Department of Mechanical Engineering, National Chiao Tung University, Hsinchu 300, Taiwan; hafi[email protected] (H.M.D.); [email protected] (M.W.S.) 2 Green Energy & Environment Research Laboratories, Industrial Technology Research Institute, Hsinchu 300, Taiwan; [email protected] * Correspondence: [email protected]; Tel.: +886-3-5712121 Received: 28 November 2018; Accepted: 24 December 2018; Published: 29 December 2018 Abstract: This study investigates the feasibility of using R-134a filled separated two-phase thermosiphon loop (STPTL) as a free cooling technique in datacenters. Two data center racks one of them is attached with fin and tube thermosiphon were cooled by CRAC unit (computer room air conditioning unit) individually. Thermosiphon can help to partially eliminate the compressor loading of the CRAC; thus, energy saving potential of thermosiphon loop was investigated. The condenser is a water-cooled design and perfluoroalkoxy pipes were used as adiabatic riser/downcomer for easier installation and mobile capability. Tests were conducted with filling ratio ranging from 0 to 90%. The test results indicate that the energy saving increases with the rise of filling ratio and an optimum energy savings of 38.7% can be achieved at filling ratios of 70%, a further increase of filling ratio leads to a reduction in energy saving. At a low filling ratio like 10%, the evaporator starves for refrigerant and a very uneven air temperature distribution occurring at the exit of data rack.
    [Show full text]
  • A Solar Heating and Cooling System in a Nearly Zero-Energy Building: a Case Study in China
    Hindawi International Journal of Photoenergy Volume 2017, Article ID 2053146, 11 pages https://doi.org/10.1155/2017/2053146 Research Article A Solar Heating and Cooling System in a Nearly Zero-Energy Building: A Case Study in China 1,2 1 2 2 2 2 2 Zhifeng Sun, Yaohua Zhao, Wei Xu, Xinyu Zhang, Huai Li, Min Wang, Tao He, and 2 Dongxu Wang 1College of Architecture and Civil Engineering, Beijing University of Technology, Beijing 100124, China 2Institute of Building Environment and Energy, China Academy of Building Research, Beijing 100013, China Correspondence should be addressed to Xinyu Zhang; [email protected] Received 5 January 2017; Revised 21 April 2017; Accepted 18 May 2017; Published 18 July 2017 Academic Editor: Michel Feidt Copyright © 2017 Zhifeng Sun et al. This is an open access article distributed under the Creative Commons Attribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited. The building sector accounts for more than 40% of the global energy consumption. This consumption may be lowered by reducing building energy requirements and using renewable energy in building energy supply systems. Therefore, a nearly zero-energy building, incorporating a solar heating and cooling system, was designed and built in Beijing, China. The system included a 35.17 kW cooling (10-RT) absorption chiller, an evacuated tube solar collector with an aperture area of 320.6 m2, two hot-water storage tanks (with capacities of 10 m3 and 30 m3, respectively), two cold-water storage tanks (both with a capacity of 10 m3), and a 281 kW cooling tower.
    [Show full text]
  • Performance Analysis and Control Strategies to Enhance Free Cooling
    ________________________________________________________________________________________________ Performance Analysis and Control Strategies to Enhance Free Cooling with an Active PCM-Heat Exchanger Navid Morovat1, José Agustín Candanedo2, Andreas K Athienitis1 1Concordia university, Montreal, Canada 2CanmetENERGY, Montreal, Canada free cooling Abstract peak load shifting This paper presents a simulation case study of an active active building systems thermal energy storage device with phase-change passive building systems materials (PCM) for free-cooling purposes. The charging/discharging of the PCM, arranged in layers in a In passive applications, PCMs are integrated into the heat exchanger, is done through a controlled air stream building envelopes to increase the effective thermal passing through these layers. First, the effect of airflow storage capacity in order to better energy saving and rate on charging/discharging time is investigated. Then, temperature regulation. The main problem with different control strategies targeting reduction in peak incorporating PCMs in the building envelope is the demand and HVAC system sizing are evaluated. Results difficulty of exchanging a high rate of heat between the show that for the present case-study 14% reduction in air and the PCM. Passive ways for cooling may also not energy consumption and 10% enhanced energy flexibility be as effective in extreme climate conditions. This is could be achieved using the PCM heat exchanger mainly because the outdoor ambient air temperature does (PCM-HX) for free cooling. not decrease sufficiently at night. Stetiu and Feustel (1998) found that for climates with relatively high Introduction ambient temperatures (above 17 °C) during the night, it The role of buildings as flexible loads is becoming more would be beneficial to force the supply air along the important; they can act as energy generators, energy storage surfaces to facilitate good heat exchange.
    [Show full text]