PRODUCTS NELSON Fire Brick

Product Description Physical Properties Nelson Fire Brick is a soft, pliable, material that is ideal for applications where the Firestop • Color……………….Charcoal Gray application may be required to be re-penetrated. Upon • Weight……………..1.48 lbs. the event of a fire, the brick material expands within the • Dimensions……….. 2” x 5” x 8” opening, forming a solid char that prevents through • Intumescent activation temp. >300°F of the fire. • Asbestos Filler ……None Test Compliance Application • ASTM E-814 and UL1479, Test method for Nelson Fire Brick is an economical, durable, labor through stop fire penetrations. saving firestop material for cable or Testing Data penetrations. Nelson Fire Brick should be installed For specific test criteria, refer to the UL Fire into a clean opening free of grease, dirt or loose Resistance Directory. particles. For general application guidelines, tightly Storage & Handling pack bricks into and around the penetrating item(s) Features Nelson Fire Brick should be stored in dry, covered within the annular space filling all voids. Install brick • Up to 2-Hour Ratings locations. There is no indication of shelf life limitations. centered within opening. Brick may be cut as • Easily Installed necessary to provide a tight fit between opening and Related References • Non-Shrinking penetrating item. Actual installation should be in Underwriters Laboratories Inc. "Fire Resistance • Non-Toxic accordance with the appropriate Nelson application Directory". Application details are available in • Easily Re-penetrable system drawing or applicable system in the UL Fire AutoCAD. format on request. • Excellent Shelf Life Resistance Directory. UL System No. W-L-4061 Availability F Rating 1 or 2 Hr. T Rating 3/4 Hr. AA0834 – 2” x 5” x 8” Brick, 1.48lb. (670 grams) Packaged 6 / Carton

Approvals Underwriters Laboratories Inc., Fill, Void or Cavity Material (XHHW) and (XHHW7)

GENERAL: Areas to be protected must be clean and free of oil, loose dirt or rust. APPLICATION SYSTEM SELECTION: Selection of an WALL ASSEMBLY - Constructed in the manner specified in the U300, appropriate firestop application system design is critical to the U400 or V400 series designs The max. area of opening is 168 sq. in. process. Please consult the Nelson Firestop with a max. dimension of 28". directory and application guide as well as the UL. Fire CABLE TRAY - Max. 24" wide x 4" deep cable tray. The annular space Resistance Directory for additional information. is 0" (point of contact) to 2". FILL MATERIAL: Prior to installation of the Fire Bricks, min. CABLES - Max. 40% aggregate cross-sectional fill of power, control 3/8” thickness of forced into interstices of cables and or communications cable. between cables and cable tray within full depth of the stud A). 1/C-350 kcmil cavity. After installation of the Fire Bricks, min. 3/8” additional B). 200 pair - No. 24awg C). 62.5/125 fiber optic cable putty applied between the interstices of cables, between D). Max. 3/C No.12awg METAL-CLAD cable. cables and cable tray, between the Fire Bricks and cables and NELSON FSP PUTTY - Min. 3/8" depth of putty forced into interstices between cable tray and Fire Brick on both surfaces of the wall of cables and cable tray. assembly. At point of contact location between cable tray and NELSON FIRE BRICKS - For 3-1/2" steel studs, fire bricks installed wall, min. 3/8” thickness of putty applied at the cable tray/wall with 5" dimension projecting through and centered in opening. interface on both surfaces of the wall. For walls larger than 3-1/2" steel studs, fire brick installed with FIRE BRICK: For walls incorporating max. 3-1/2” steel studs, long dim. passing through and centered in opening. fire bricks installed with 5” dimension projecting through and DWG NO. FS-0642 R0 centered in opening. For walls constructed of larger than 3- 1/2” steel studs Fire Brick installed with long dimension UL System No. W-J-4058 passing through and centered in opening. For reinforced F Rating 2 Hr. T Rating 3/4 Hr. concrete and solid filled concrete block wall assemblies, blocks installed centered within depth of opening with the long WALL ASSEMBLY - Min. 6" concrete wall. The max. area dimension placed horizontally. For HOLLOW-CORE block of opening is 168 sq. in. with a max. dimension of 28". walls, Fire Brick installed with long dimension passing through CABLE TRAY - Max. 24" wide x 4" deep cable tray. the opening from surface to surface. Fire Bricks to completely The annular space is 0" (point of contact) to 2". fill the opening. CABLES - Max. 40% aggregate cross-sectional fill of power, control or communications cable. A).1/C-350 kcmil B).200 pair - No. 24awg C).62.5/125 fiber optic D).Max. 3/C No.12awg METAL-CLAD cable. NELSON FSP PUTTY - Min. 3/8" depth of putty forced into interstices of cables and cables tray. NELSON FIRE BRICKS - For concrete and solid filled concrete block wall assemblies, Fire Bricks installed centered within depth of opening with the long dimension placed horizontally. For hollow core block walls, fire bricks installed with long dimension passing through the opening from surface to surface. Fire bricks to completely fill the opening DWG NO. FS-0643 R0

EGS

Electrical Group

L 01 www.afielektrik.com FIRESTOP PRODUCTS CLK™ Silicone

Product Description GENERAL: Nelson Firestop Sealant (CLK™) is a family of one part Areas to be protected must be clean and free of silicone flexible , used to protect from the spread oil, loose dirt or rust. Installation temperatures must be of fire, smoke, gases and water. It is designed for between 40ºF (4ºC) and 90ºF (32ºC). Allow a cure time applications of through stop penetrations and in of less than 2 weeks for a 1/2” thickness. construction joints. It is offered in two forms, a non-sag APPLICATION SYSTEM SELECTION: which can be troweled and a self-leveling grade Selection of an appropriate firestop application system suited for floor applications. design is critical to the fire protection process. Please Application consult the Nelson Firestop directory and application ® CLK™ sealant is ideal for simple penetrations such as guide as well as the UL Fire Resistance Directory for around metallic pipes or conduits and for floor to wall, additional information. floor-to-floor and head of wall applications. Maintains FORMING: the integrity of fire-rated construction. The sealant is Some installations may require forming as either flexible and designed for use in fire-rated control and an integral part of the system or as an option to facilitate isolation joints where expansion and contraction or installation. In systems where forming is required, mineral vibration can occur. wool batts with a minimum nominal density of 4PCF are Availability generally required. Cut forming material oversized to allow AA529 –Non/Sag – 10.3 oz Tube 18.5 in3 (304ml) 12/Ctn for tight . Position forming material to allow for the AA542 - Non/Sag - 2 Gallon Pail 462 in3 (7.6L) proper depth of fill material. AA492 - Non/Sag - 5 Gallon Pail 1155 in3 (19.0L) FILL MATERIAL: AA539 -Self Leveling -10.3 oz Tube 18.5 in3 (304ml) 12/Ctn Nelson Firestop CLK™ may be installed AA552 - Self Leveling - 5 Gallon Pail 1155 in3 (19.0L) by caulking gun or from bulk containers using a bulk loading Approvals caulk gun, or by manually trowelling using a mason’s trowel Underwriters Laboratories Inc. Fill, Void or Cavity or putty knife. For larger applications it can be pumped Material (XHHW) ULC, FM, USN and directly from the pail. Nelson CLK™ S/L (Self-Leveling) is United States Coast Guard fluid and can be poured into place in floor applications. 164.138/3/0 Insure that the sealant makes complete contact with the 164.138/2/0 inside surface of the opening and also the surface of the ABS penetrating item(s). Work sealant into all areas exercising 02-HS261620B-1-PDA care to eliminate voids or seams. The surface of the sealant City of New York, New York, Department of can be smoothed using a putty knife or sponge dipped in MEA 135-00-M water. Adding water to the sealant itself is not MEA 236-87-M Vol. 2 recommended. CLK™ cannot be painted. Features Up to 4 Hour rating Elastomeric (Flexible Cure) UL System No. C-AJ-1203 Silicone Based F Rating 2 Hr. T Rating 0 Hr. Water Resistant Acoustically Tested – Reduces noise transmission DWG NO. FS-0145 R4 Physical Properties Color……………….Brick Red Weight……………..10.75 lbs./ gal. FLOOR or WALL ASSEMBLY - Min. 4-1/2" concrete floor or 5" Consistency..……..Thixotropic wall or CMU block wall. Annular space is 1/2" to 1-1/2". Application Temp…40?F (4?C) to 90?F (32?C) METALLIC or CONDUIT - Max. 24" diam. steel or 4" copper Service Temp..….0?F (-18?C) to 110?F (43?C) FORMING MATERIAL - Tightly pack min. 4pcf, batt Cure Time………...Less than 2 weeks for 1/2" thickness insulation Hazardous Ingredients…..None UL System No. FF-S-1011 STC Rating……………………52 F Rating 4 Hr. Halogen Free Nominal Joint Width - 4” Test Compliance ASTM E 84 Non-Sag Flame spread………….……5 DWG NO. FS-0095 R3 Smoke developed………….40 Self-Leveling Flame spread………….……5 Smoke developed………….35 ASTM E90 Standard Test Method for WALL ASSEMBLY - Constructed in the manner specified in the U300 Laboratory Measurement of Airborne Sound or U400 series design. The max. opening diameter is 5”. Transmission Loss of Partitions and The nom annular space is 1/4”. Elements METALLIC PIPE or CONDUIT - Max. 4” steel, EMT or RMC ASTM E814 and UL1479 Test method for NELSON CLK SEALANT - Min. 5/8” depth through stop fire penetrations. ASTM E1966 and UL2079 Test method for fire FS-0119 DWG NO. R3 resistance of building joint systems. UL System No. C-AJ-3094 Testing Data F Rating 2 Hr. T Rating 1 Hr. For specific test criteria, refer to the UL Fire Resistance Directory. Storage & Handling DWG NO. FS-0131 R2 Nelson CLK™ should be stored at temperatures between 40?F (4?C) and 90?F (32?C). Protect from freezing. Expected shelf life is one year from date of shipment. FLOOR ASSEMBLY - Min. 5-1/2" concrete floor Related References FORMING MATERIAL - Min. 4pcf mineral wool batt insulation Underwriters Laboratories Inc. "Fire Resistance NELSON CLK SEALANT - Min. 1/2" depth Directory". Application details are available in AutoCAD? format on request. FLOOR or WALL ASSEMBLY - Min. 4-1/2" concrete floor or 5” wall or CMU block wall. METALLIC - Max. nominal 6" steel sleeve and extends 2" beyond surfaces. CABLES - Max. 30% fill of 25pr. 24awg or smaller, PVC jacketed telecommunications cable. NELSON CLK SEALANT - Min. 1/2" depth

EGS

Electrical Group

L 02 www.afielektrik.com FIRESTOP PRODUCTS CMP™ Firestop Compound

Product Description UL System No. C-AJ-0043 Nelson Compound (CMP™) is a cementitious material that is mixed with water. F Rating 3 Hr. T Rating 2 Hr. It is similar in appearance to and can be troweled to a smooth finish that provides a weather resistant, non-shrinking fire-rated seal. Application CMP™ has been tested for a wide range of penetrants including metallic pipes, cables, cable trays, as well as combustible penetrants such as insulated pipes. It is ideally suited for medium to large openings filled with or without penetrants. Availability AA0476 - 44 lb. Bag - 1000 cu. in. (16.4L) Approvals Underwriters Laboratories Inc., Fill, Void or Cavity Material (XHHW) and (XHHW7), FMCity of New York, New York, Department of Buildings FLOOR or WALL ASSEMBLY - Min. 4-1/2" concrete floor or wall, • MEA 236-87-M Vol. 2 or CMU block wall. The max. size of the opening is 40" x 48". Features NELSON CMP COMPOUND - Install min. 4-1/2" depth • Up to 4-Hour Ratings • Economical DWG NO. FS-0124 R2 • Non-Shrinking UL System No. C-AJ-1040, 8007 • Paintable F Rating 2,3,4 Hr. T Rating 0 or 1/2 Hr. • Water Resistant • Non-Toxic • Excellent Shelf Life • Ideal for Large Openings • Acoustically Tested – Reduces noise transmission Physical Properties • Color……………….Red • Weight……………..44 lbs. per Bag • Yield per bag………1000 cu. in. • Application Temp…40°F (4°C) and above • Set Up Time……….4 hours (approx) • Cure Time………….4 weeks (approx) FLOOR or WALL ASSEMBLY - Min 3-1/4" concrete floor or wall • Hydrostatic Pressure..>30 psi (206kPa) or CMU block wall. The max. size of opening is 10" x 30". • Mix Ratio - Water to CMP compound METALLIC PIPE or CONDUIT - Max. (5) pipes or conduits, max. 1:4.0………420 psi (2895.8 kPa) 6" steel or cast iron, RMC, max. 4" EMT or max. 2" copper pipe. 1:3.5………395 psi (2723.5 kPa) Annular space is 3/4" to 4-3/4". Spacing between pipes or conduits 1:3.0………300 psi (2068.4 kPa) is 3/4" to 1-1/2". 1:2.5………240 psi (1654.7 kPa) PIPE INSULATION (optional), Max. 1" thick FIBERGLASS Test Compliance or MINERAL WOOL. Annular space is 1-1/2" - 3-3/4". • ASTM E119 and UL263, Fire Tests of Building Construction and Materials NELSON CMP COMPOUND - Min. 3-1/4" depth for 2 or 3 hr • ASTM E814 and UL1479, Test method for through stop fire penetrations. F- Rating or 7" depth for 4 hr F- Rating. Testing Data For specific test criteria, refer to the UL Fire Resistance Directory. UL System No. C-AJ-1219 Storage & Handling F Rating 2 Hr. T Rating 0 Hr. Nelson CMP™ should be stored in dry, covered locations. There is no indication of shelf life limitations. Limitations Nelson CMP™ is not a load bearing material. If the area is subject to pedestrian traffic, safety plates must be installed. Related References Underwriters Laboratories Inc. "Fire Resistance Directory". Application details are available in AutoCAD. format on request. GENERAL: Areas to be protected must be clean and free of oil, loose dirt or rust. Installation temperatures must be 40ºF (4ºC) and above. DWG NO. FS-0125 R4 Allow a cure time of 4 weeks. APPLICATION SYSTEM SELECTION: Selection of an appropriate firestop FLOOR or WALL ASSEMBLY - Min. 4-1/2" concrete floor or system design is critical to the fire protection process. Please consult the wall, or CMU block wall. The max. size of opening is 40" x 48". Nelson Firestop directory and application guide as well as the UL. Fire METALLIC PIPE or CONDUIT - Max. 10" steel, 6" RMC, 4" EMT Resistance Directory for additional information. or copper pipe. Annular space is 1" to 37" and between FORMING: Some installations may require forming as either an integral part pipes is 2" to 40". of the system or as an option to facilitate installation. In systems where NELSON CMP COMPOUND - Min. 4-1/2" depth forming is required, plywood or foam insulation boards may be used. In smaller openings, mineral fiber, backer rod or other suitable materials may be used. Recess forming material to a depth which allows for the proper depth of fill material. FILL MATERIAL: Nelson Firestop CMP. may be mixed with water using a UL System No. C-AJ-8049 standard mortar mixer, plastering machine, or mixed by hand in smaller F Rating 2 Hr. T Rating 0 Hr. amounts. CMP™ Compound should be thoroughly mixed with water to achieve a uniform texture. Clean adjacent surfaces of opening prior to installation. For installation without forming, use 1:4 water/compound mix DWG NO. FS-0149 R2 ratio. For quicker installation with forming, use 1:2.5 water/compound ratio. Avoid extreme mix ratios. Material can be pumped, troweled or hand packed into the opening. Floor or wall penetrations with large open areas FLOOR or WALL ASSEMBLY - Min. 4-1/2" concrete floor or wall, or may require some temporary forming. Nelson CMP™ sets up in about four CMU block wall. The max. size of the opening is 40" X 48". hours and cures completely in approximately four weeks. Actual installation The annular space is 1" to 12". should be in accordance with the appropriate Nelson application system METALLIC PIPE or CONDUITS - Max. (2) 10" steel, cast iron. Max. drawing. 6" RMC, 4" copper or EMT. Annular space is 1" to 6-1/2" for pipes and 4" to 12" for trays. CABLES - Max. 30% fill of power, control, or communications cables. NELSON CMP COMPOUND - Min. 4-1/2" depth, flush with the top surface of the floor or both surfaces of the wall.

EGS

Electrical Group

L 03 www.afielektrik.com FIRESTOP PRODUCTS CPS™ Composite Sheet

Product Description GENERAL: Areas to be protected must be clean and free of Nelson Composite Sheet (CPS™) is a rigid, elastomeric, oil, loose dirt or rust. fire resistant panel used to seal penetrations and maintain APPLICATION SYSTEM SELECTION: Selection of an the rating of fire rated floors or walls. It consists of a rigid appropriate firestop application system design is critical to the panel, primarily composed of a 5/16” thick elastomeric fire protection process. Please consult the Nelson Firestop sheet, bonded to a 28 gauge galvanized steel sheet on directory and application guide as well as the UL. Fire one side. The composite sheet is reinforced with hexagonal Resistance Directory for additional information. shaped steel wire mesh and bonded with .003" aluminum foil COMPOSITE SHEET: Nelson (CPS™) composite sheet is on the back side. applied to the top side or bottom side of floor or to both sides Application of the wall with the foil side facing the opening. CPS™ is selected according to the size of the opening to be TOPSIDE – Overlap the opening by a min. 2” on all sides. firestopped. A variety of sizes are available. It may be cut Mount with 3/8” diameter x min. 1-7/8” steel masonry anchors for fit over the opening and penetrating items. Nelson CPS™ spaced a max. of 5” on center. is ideally suited for applications for cable tray penetrations, BOTTOMSIDE - Overlap the opening by a min. 3-1/2” on all large floor or wall openings and telecommunications or power sides. Mount with 1/4” diameter x min. 1-1/4” steel masonry cable systems. Actual installation should be in accordance with anchors in conjunction with 1/4” x 1-1/4” diameter steel fender the appropriate Nelson application system drawing. washers spaced a max. of 5” on center. Availability UL System No. C-AJ-0049 AA545 - 5/16” x 24” x 36” F Rating 2 Hr. T Rating 3/4 Hr. AA546 - 5/16” x 36” x 36” AA547 - 5/16” x 36” x 41” AA548 - 5/16” x 16” x 28” AA549 - 5/16” x 12” x 24” Approvals Underwriters Laboratories Inc., Fill, Void or Cavity Material (XHHW) and (XHHW7) Factory Mutual (FM) City of New York, New York , Department of buildings • MEA 236-87-M Vol. 2 FLOOR or WALL ASSEMBLY - Min. 4-1/2" thick lightweight or normal Features weight concrete floor or wall, or CMU block wall. The max. area of the • Up to 2-Hour Ratings opening is 127 sq. inches with a max. dimension of 18". • Unlimited Shelf Life • Easy to Install NELSON CPS COMPOSITE SHEET - Apply to the under side of the • Highly Intumescent floor or to both sides of the wall with the foil side facing the opening. • Easily Fabricated Overlap the opening by a min. of 3-1/2" on all sides. Mount to the floor • Self Supporting Panels or wall with 1/4" x min. 1-1/4" long steel masonry anchors in conjunction Physical Properties with 1/4" x 1-1/4" diameter steel fender washers spaced a max. of 5" OC. • Asbestos Filler ………………None • Solvents ……………………...None SEALANT (optional, not shown) - Apply Nelson CLK sealant around • Hazardous Ingredients ……..None the perimeter of the composite sheet for added smoke seal protection. • Intumescent Expansion Activation Temp……..Initial >250ºF DWG NO. FS-0169 R4 • VOC Content …………………Negligible UL System No. C-AJ-0050 • Volume Increase …………....4 to 10 times F Rating 2 Hr. T Rating 0 Hr. • Material Thickness ………….(0.28" to 0.36") Test Compliance • ASTM E119 and UL263, Fire Tests of Building Construction and Materials • ASTM E814 and UL1479, Test method for through stop fire penetrations. Testing Data For specific test criteria, refer to the UL Fire Resistance Directory. Storage & Handling Nelson CPS™ should be stored in dry, covered locations at no FLOOR or WALL ASSEMBLY - Min. 4-1/2" thick concrete floor or wall, greater temperature than 120ºF (49ºC). There is no indication or CMU wall. The max. area of the opening is 126 sq. in. with a max. of shelf life limitations. dimension of 18". Limitations NELSON CPS COMPOSITE SHEET - Apply to the top side of the floor Nelson CPS™ should not be exposed to harmful chemicals. or to both sides of the wall or HOLLOW-CORE floor, with the foil side Service temperature shall not exceed 180ºF (82ºC). facing the opening. Overlap the opening by a min. 2" on all sides. Mount Related References with 3/8" diameter x min. 1-7/8" steel masonry anchors spaced a max. Underwriters Laboratories Inc. "Fire Resistance of 5" on center. Directory". Application details are available in AutoCAD. format on request. SEALANT (optional, not shown) - Apply CLK sealant around the perimeter of the composite sheet for added smoke seal protection.

DWG NO. FS-0176 R3

EGS

Electrical Group

L 04 www.afielektrik.com FIRESTOP PRODUCTS ES1399™ Elastomeric Sealant

Product Description Nelson Firestop Elastomeric Sealant (ES1399™) is a cost effective, water based acrylic latex, endothermic, fire protective sealant. It is designed for applications of through firestop penetrations and in construction joints. UL System No. C-AJ-2525 Application F Rating 3 Hr. T Rating 2-1/2 Hr. ES1399™ sealant can be applied using a conventional caulk gun, bulk loader or by trowel. For larger applications it can be pumped directly from the pail. ES1399™ is applicable for through firestop penetrations and for floor to wall, floor-to-floor and head of wall FLOOR or WALL ASSEMBLY - Min. 4-1/2" concrete floor or applications. It is flexible and is ideal for applications where joint 5" thick wall or CMU block wall. Max. diameter of opening is 4". expansion and contraction can occur. Apply the required depth METALLIC SLEEVE (optional) - Nom 4" steel sleeve flush of sealant beginning on the edge of the opening (use over various with floor or wall surfaces. backing materials as required). Insure that the sealant makes complete NONMETALLIC PIPE - Max. 2" PVC or SDR17 CPVC or contact with the inside surface of the opening and also the surface of ENT pipe for use in closed (process or supply) the penetrating item(s). On joints, the surfaces should be clean and free The annular space is min. 0" (point of contact) to max. 1-3/4" pipe. of dust, dirt, oil, grease, loose material, rust or other substances. Apply FORMING MATERIAL - Tightly pack min. 4pcf mineral the required thickness in the joint or over the insulation if required. wool batt insulation Availability NELSON ES1399 SEALANT - Min. 1/2" depth AA0870 – Non/Sag-10.3 oz Tube 18.5 in3 (304ml) 12/Ctn. AA0874 - Non/Sag -20.2 oz Foil Pack 36.45 in3 (597 ml) 12/Ctn. AA0890 – Non/Sag - 30 oz Tube 54 in3 (883ml) 10/Ctn. AA0871 – Non/Sag – 5 Gallon Pail 1155 in3 (19.0L) UL System No. W-L-1276 Approvals F Rating 1 or 2 Hr. T Rating 0 Hr. Underwriters Laboratories Inc.Fill, Void or Cavity Material (XHHW) City of New York, New York, Department of Buildings. • MEA 125-04-M DWG NO. FS-0348 R0 Features • Up to 4-Hour ratings • Water-Based Acrylic Latex – Easy clean-up • Economical WALL ASSEMBLY - Constructed in the manner specified • Elastomeric (Flexible Cure) in the U300 or U400 series designs. The annular space is • Paintable 0" (point of contact) to 2". • Water Resistant METALLIC PIPE or CONDUIT - Max. nominal 24" steel, • Acoustically Tested – Reduces noise transmission cast iron pipe, or 6" RMC or 4" EMT. Max. 6" Physical Properties Max. 6" Type L copper pipe or tubing. • Color……………….Red FORMING MATERIAL - Install backer rod within • Weight……………..10.75 lbs. per gallon the annular space, and recess 5/8" from both surfaces of wall. • Consistency...……..Thixotropic NELSON ES1399 SEALANT - Min. 5/8" depth. • Application Temp…40°F (4°C) to 90°F (32°C) UL System No. C-AJ-1414 • STC Rating………………52 F Rating 3 Hr. T Rating 0 Hr. Test Compliance Flame spread……………..0 Smoke developed….……30 • ASTM E90 Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and • ASTM E814 and UL1479 Test method for through stop fire penetrations. • ASTM E1399 Test method for cyclic movement and measuring min. and max. joint • ASTM E1966 and UL2079 Test method for fire resistance of building joint systems. Testing Data DWG NO. FS-0352 R0 For specific test criteria, refer to the UL Fire Resistance Directory. Storage & Handling FLOOR or WALL ASSEMBLY - Min. 4-1/2” concrete floor or wall, Nelson ES1399™ should be stored at temperatures between 40°F (4°C) and or CMU block wall. The annular space may range from 90°F (32°C). Protect from freezing. Expected shelf life is one year from date of 0” (point of contact) to a max. of 1-7/8”. Related References METALLIC SLEEVE (optional) - Max. 8” steel sleeve Underwriters Laboratories Inc. "Fire Resistance Directory". Application details METALLIC PIPE or CONDUIT - Max. 24” steel or cast iron, are available inAutoCAD. format on request. 6” RMC, 4” EMT, or 6” Type L or heavier, copper pipe or tubing. GENERAL: Areas to be protected must be clean and free of oil, loose dirt or rust. FORMING MATERIAL - Tightly pack min. 4pcf mineral wool Installation temperatures must be between 40oF (4oC) and 90oF (32oC). Allow a batt insulation or 1” diameter backer rod cure time of less than 2 weeks for a 1/2” thickness. NELSON ES1399 SEALANT - MIn. 1/2” depth. APPLICATION SYSTEM SELECTION: Selection of an appropriate firestop UL System No. HW-D-0230 application system design is critical to the fire protection process. Please F Rating 2 Hr. consult the Nelson Firestop directory and application guide as well as the UL. Nominal Joint Width - 1" Fire Resistance Directory for additional information. Class II Movement - 25 % Compression FORMING: Some installations may require forming as either an integral part of the system or as an option to facilitate installation. In systems where forming is required, mineral wool batts with a minimum nominal density of 4PCF are generally required. Cut forming material oversized to allow for tight packing. Position forming material to allow for the proper depth of fill material. FILL MATERIAL: Nelson Firestop ES1399™ may be installed by caulking gun or from bulk containers using a bulk loading caulk gun, or by manually trowelling using a mason’s trowel or putty knife. For larger applications it can be pumped directly from the pail. Insure that the sealant makes complete contact with the inside surface FS-0375 RO of the opening and also the surface of the penetrating item(s). Work sealant into DWG NO. all areas exercising care to eliminate voids or seams. The surface of the sealant • FLOOR ASSEMBLY - Min. 3” concrete poured over fluted steel decking. can be smoothed using a putty knife or sponge dipped in water. Adding water to • WALL ASSEMBLY - Min. 8” concrete wall or CMU block wall. the sealant itself is not recommended. ES1399™ can be painted. The max seperation between bottom of floor and top of wall is 1”. • FORMING MATERIAL - Tightly pack min. 4pcf mineral wool batt insulation • NELSON ES1399 SEALANT - Min. 5/8” depth.

EGS

Electrical Group

L 05 www.afielektrik.com FIRESTOP PRODUCTS FSC3™ Join Coating

Product Description FILL MATERIAL: Apply Nelson Firestop Joint Coating (FSC3™) using an airless sprayer over the mineral wool insulation to a Nelson Firestop Joint Coating (FSC3™) is a water based acrylic latex, elastomeric, nominal 1/8” thick wet applied coating. In joint systems, overlap fire protective coating for use on construction joints. It is designed for labor saving the coating 1/2” onto the wall and floor/roof. In perimeter joints, spray applications onto construction joints and perimeter joint systems overlap the coating 1/2” onto the top surface of the floor and curtain (curtain wall assemblies). wall a min. 1/2”. In through penetrations, overlap the coating 1/2” Application onto the edges of the opening and the penetrant surfaces by a min. FSC3™ coating is spray, brush or trowelled applied over a min. 4” depth of mineral 1/2”.In Wall-to-Wall or Head of Wall joint systems or wall wool insulation packed within the joint width. FSC3™ is specifically for applications through penetrations, the coating is applied to both sides of the wall. in construction joints, wall to wall, floor to wall, floor to floor, head of wall and UL System No. C-AJ-1441 perimeter joint curtain wall applications where thermal expansion and contraction of joints may be encountered. Actual installation may vary according to the type of F Rating 2 Hr. T Rating 0 Hr. joint to be protected. Joint surfaces should be clean and free of dust, dirt, oil, grease, loose material, rust or other substances. A 1/8” wet thickness is applied over the insulation and overlaps the joint surfaces by a minimum 1/2”. Product cures to a nominal 1/16" dry thickness. Availability DWG NO. FS-0458 RO AA0868 - 5 Gallon Pail (19.0L) – 1,155 cu. in. Sprayer Requirements Use a mid-sized commercial pump at minimum. An Airlessco SL810 sprayer with 5 gal suction setup, 50’ x 3/8” airless hose, 007XL spray gun with 0.019 or • FLOOR or WALL ASSAMBLY - Min. 4-1/2” concrete floor or wall, 0.021 tip is a recommendation. or CMU block wall.The max. size of opening is 864 sq. in. with a Approvals max. dimension of 48”. Opening may contain any combination of 24 pipes. • METALLIC PIPES OR CONDUITS - Max. (24) 4” steel, cast iron, Underwriters Laboratories Inc.Fill, Void or Cavity Material (XHHW) Omega Point RMC, EMT or 1-1/2” TYpe L copper tubing. Laboratories Joint Sealant (Category 07920) City of New York, New York, Annular space shall be 5/16” to 2-1/2” between penetrants and 0” Department of Buildings (point of contact) to 2” between periphery of opening and pipes. • MEA 127-04-M Vol. II • FORMING MATERIAL - Tightly pack min. 4pcf mineral wool batt insulation. • MEA 127-04-M • NELSON FSC3 COATING - Apply by spray, trowel, or brush over Features the forming material to a nominal 1/8” thick wet applied coating. • Up to 4-Hour Ratings Overlap the edges of the opening and the penetrant surfaces by a min. 1/2”. • Water-Based Acrylic Latex – Easy clean-up • Elastomeric (Flexible Cure) UL System No. W - L - 7083 • Paintable F Rating 1 or 2 Hr. T Rating 0 Hr. • Water Resistant • Acoustically Tested – Reduces noise transmission Physical Properties • Color……………....Red • Coverage………….65 sq. ft. per 5-gallon pail • Weight……………..10.5 Lbs. Per gallon • Viscosity……………24m cps maximum DWG NO. FS-0400 RO • Application Temp…40°F (4°C) to 90°F (32°C) • Solids…………….…54% • PH…………………..8.0 – 9.0 • STC Rating…………52 Test Compliance • ASTM E84 Flame spread………….…0 • WALL ASSAMBLY - Constructed in the manner specified in the U300 Smoke developed..…..….0 or U400 series designes. The annular space is 0” (point contact) to 2”. • ASTM E90 Standard Test Method for Laboratory Measurement of Airborne • STEEL HVAC - 20” x 20”, No. 24 gauge, steel duct. Sound Transmission Loss of Building Partitions and from date of shipment. • FORMING MATERIAL - Tightly pack min. 4pcf mineral wool batt insulation. Elements ASTM E814 and UL1479 Test method for through-penetration . • NELSON FSC3 COATING - Apply over the forming material to fill the • ASTM E1399 Test method for cyclic movement and measuring min. and max. annular space to a min. 1/8” depth on both sides of the wall. Overlap the joint width. ASTM E1966 and UL2079 Test method for fire resistance of building coating onto the wall and duct a min. 1/2”. joint systems. • METAL FRAME - Min. N›. 22 GA galvanized steel angles sized to lap duct Testing Data a min. of 2” and lap wall surfaces a min. 1-1/2”. For specific test criteria, refer to the UL Fire Resistance Directory and Omega UL System No. HW-D-0308 Point Laboratories Directory. F Rating 2 or 3 Hr. Storage & Handling Nominal Joint Width - 1” Nelson FSC3™ should be stored at temperatures between 40°F (4°C) and Class II Movement - 25% Compr & Ext. 90°F (32°C). Do not dilute. Protect from freezing. Expected shelf life is one year from date of shipment. Cautions Wear eye protection. Do not spray gun at any part of the body. Fluid at high pressure can penetrate the skin and cause internal injury. Observe spray equipment manufacturer’s instructions and warnings. In case of an injury, obtain medical attention immediately. Related References Underwriters Laboratories Inc. "Fire Resistance Directory" and Omega DWG NO. FS-0387 R1 Point Laboratories "Directory of Listed BUILDING PRODUCTS, MATERIALS & • FLOOR ASSEMBLY - Min. 2-1/2” thick concrete floor. ASSEMBLIES". Application details are available in AutoCAD. format on request. • ROOF ASSEMBLY (not shown) - As an alternate to the floor assembly, GENERAL: Areas to be protected must be clean and free of oil, loose dirt or a fire-rated steel deck roof assembly may be used. rust. Installation temperatures must be between 40ºF (4oC) and 90ºF (32ºC). • ROOF INSULATION (not shown) - As specified in the individual P700 APPLICATION SYSTEM SELECTION: Selection of an appropriate firestop series design. application system design is critical to the fire protection process. Please • SPRAY-APPLIED FIRE PROOFING - The steel roof deck shall be sprayed consult the Nelson Firestop directory and application guide as well as the UL. with the thickness of material specified in the individual P700 series Fire Resistance Directory for additional information. design. Also may be used as an alternate to the forming material. FORMING: Tightly pack min. 4pcf mineral wool batt insulation into the annular • WALL ASSEMBLY - Min. 6” thick concrete wall or CMU block wall. The max. seperation between bottom of floor and top of wall is 1”. space. The insulation should be compressed 50% in the nominal joint and • FORMING MATERIAL - Tightly pack min. 4pcf mineral wool batt insulation compressed 33% or 25% (see specific UL system for compressed percentage) into the annular space. into the fluted area and flush with both surfaces of the wall. In perimeter joint • FORMING MATERIAL (Plugs) (not shown) - Mineral wool plugs may be used. systems, the insulation should be compressed 25% in the nominal joint. • NELSON FSC3 COATING - Apply over the or forming material in the joint to a nom 1/8” thick wet applied coating. Overlap the coating 1/2” onto the wall and proctected steel floor or roof deck on both sides of the wall.

EGS

Electrical Group

L 06 www.afielektrik.com FIRESTOP PRODUCTS FSC™ Cable Coating

Product Description Nelson Firestop Fire Protective Cable Coating (FSC™) is water based, intumescent, fire protective coating designed to enhance the fire resistance of electrical power, communications and control cables. Physical Properties It is commonly applied to continuous cable runs to • Color……………....Off White prevent the propagation of fire. It is designed for • Coverage………….14 sq. ft. per gallon labor saving spray applications on cables. • Weight……………..9.9 Lbs. per gallon Application • Viscosity……………60m cps maximum FSC™ is spray or brush applied onto cables. Apply • Application Temp…40°F(4°C) to 110°F(44°C) 1/8” wet thickness, which dries to 1/16” thick film. For • VOC Content………Negligible optimal performance the surfaces should be clean • Intumescent Expansion…...600% and free of dust, dirt, oil, grease, loose material, rust • Drying Time…………To touch – 2 hrs. or other substances. FSC™ adheres well to all Complete- 24-48 hrs construction materials and cables allowing for vertical or overhead applications. When applying by a spray method, it is best applied using an airless spray unit Test Compliance with the following specifications: • ASTM E 84 Flame spread………….…15 Pump…………………..min. 3000psi Smoke developed..…..….45 Hose……………………50' x 1/2" (use 3/4" over 50') • ASTM E 162 Specific Flammability of Gun……………………Hydra-Mastic (Filter Removed) Materials using a Radiant Heat Energy Source. Tip……………………..min. 0.037" reversible tip • IEEE 383 Vertical Flame Spread on .………….min. 150 CFM min. Grouped Cables Availability AA0671 – 5 Gallon Pail – (19.0L) 1,155 cu. in. Uses Approvals FSC™ is specifically for applications to provide Factory Mutual Approved “Fire Protective Coatings” enhanced fire resistance to electrical power, For Grouped Electrical Cables. communications and control cables. FSC™ provides Testing Data superior performance on horizontal and vertical cable For specific test criteria, refer to the FM Approval Guide. tray systems. No maintenance is required. When Storage & Handling adding or removing cables, re-coat exposed area with Nelson FSC™ should be stored at temperatures FSC™ as required. between 35°F (2°C) and 120°F (49°C). Do not dilute. Features Protect from freezing. Expected shelf life is one year • Water-Based Acrylic Latex – Easy clean-up from date of shipment. • Intumescent • No Cable De-rating Cautions • Elastomeric (Flexible Cure) Wear eye protection. Do not spray gun at any part of • Paintable the body. Fluid at high pressure can penetrate the • Water Resistant skin and cause internal injury. Do not spray on or near live electrical circuitry, as material may be conductive when wet. Observe spray equipment manufacturer’s instructions and warnings. In case of an injury, obtain medical attention immediately. Related References Factory Mutual Research Approval Guide

EGS

Electrical Group

L 07 www.afielektrik.com FIRESTOP PRODUCTS FSP™ Firestop Putty

Product Description FILL MATERIAL: Nelson Firestop FSP™ putty is suggested to Nelson Firestop Putty (FSP™) is a completely premixed and ready-to-use formula be installed by hand. The putty should be installed no thinner that can be hand pressed into place forming an immediate fire seal.When exposed than 3/4”. FSP™ is normally installed from one side on floor to fire the intumescent material expands to seal voids created from fire exposure on penetrations and from both sides of a wall penetration. The deteriorating penetrating items. FSP™ is a blend of organic and inorganic materials putty should be packed from the bottom of the opening, that is hand moldable.FSP™ is reusable when adding or changing penetrating items starting at the back and working forward. FSP™ should be since the material remains pliableand does not set up. pushed into all voids. A minimum of 1/2” of FSP™ should Application surround each penetrating item (annular space). When this is Nelson FSP™ requires no special skills or tools to install. To ensure adequate adhesion, not possible (such as a cable tray), a crown shall be built up all surfaces should be clean and free of dust, grease, oil, loose materials, rust or other around the bundle of penetrating items, using a second layer substances. Apply the required depth of FSP™ over various backing materials as of putty. The crown should have a 30º slope with the wall or required. Ensure that the FSP™ makes complete contact with the inside surface of the floor surface. Wall openings should not have an unsupported opening and also the surface of each penetrating item. FSP™ is ideal for metallic space of putty greater than 4”. Floor openings should not have and non-metallic pipes, insulated pipes, cables and ductwork in a variety of fire rated unsupported spaces of putty greater than 1-1/2”. floor or wall constructions. It is especially applicable for applications where re-pene Installation of FSP™ putty pads is determined by construction trating the opening is needed after initial installation. Actual installation may vary of wall “F” rating and size of electrical box to be covered. according to the type of firestop application. Using gloves, remove pad from plastic film. Apply pad onto Availability electrical box by forming over backside of electrical box to Bar AA445 – 1” x 3” x 12” (36.0 cu. in.) – 10/Ctn. completely cover exposed surfaces. It is not necessary to Bulk AA0439 – 20 Lbs. (432 cu. in.) cover the side of the box against the stud to which it is Pads AA458 – 1/8” x 6” x 7” – 20/Ctn. mounted. An additional 1/4” thickness of putty to be formed AA452 – 1/4” x 6” x 7” – 20/Ctn. around the connector securing the end of each electrical AA447 – 1/4” x 4” x 8” – 20/Ctn. metallic tube or conduit to the box. Approvals The horizontal separation between protected outlet boxes on Underwriters Laboratories Inc. "Fill, Void or Cavity Material (XHHW)", FM, ABS and opposite sides of the wall may be less than 24” provided that USCG. City of New York, New York, Department of Buildings the boxes are not installed back-to-back. • MEA 135-00-M Wall Openings Protective • MEA 196-84-M Vol. 3 Materials (CLIV) Features UL File R10764 • Intumescent F Rating 2 Hr. • Up to a 3-Hour Rating • Reusable for Convenient Retrofit • Smoke and Gas Tight • Weather Resistant • Excellent Shelf Life • Acoustically Tested – Reduces noise transmission Physical Properties • Color……………….Tan • Density……………..0.049 lbs/cu. in. • Consistency...……..7.00mm (Penetrometer) • Activation Temp.….500ºF (260ºC) Max. • Application Temp…40°F (4°C) to 110°F (43°C) DWG NO. FS-0210 R3 • Dielectric strength…>356v/mil. • WALL ASSEMBLY - Constructed in the manner specified in the • STC Rating………………….54 U400 series designs. Test Compliance • STEEL OUTLET BOX - Max. 4” X 4” steel outlet box installed in • ASTM E84 Flame spread…………5 accordance with NFPA 70 regulations. The box can be installed Smoke developed……10 within the same stud cavitiy, provided they are not installed back-to-back. • ASTM E90 Standard Test Method for Laboratory Measurement of Airborne • NELSON FSP PUTTY PADS - Min. 1/4” thickness Putty pad. Sound Transmission Loss of Building Partitions and Elements Putty pads are to be installed to completely cover the exterior • ASTM E814 and UL1479 - Test method for through stop fire penetrations. surfaces of the outlet box (except for the side of side of the outlet • ANSI/UL 263, "Fire Tests of Building Construction and Materials." box against the stud) and completely seal against the stud within • NFPA 70 "Wall Opening Protective Materials" the stud cavity. Testing Data UL System No. W-L-3190 For specific test criteria, refer to the UL Fire Resistance Directory. F Rating 1 or 2 Hr. T Rating 0 Hr. Storage & Handling Nelson FSP™ should be stored indoors. Long term storage temperature: 140ºF (60ºC) maximum. There is no indication of shelf-life limitations. Partially used bars should be re-wrapped in their original packaging before being stored. Related References Underwriters Laboratories Inc. "Fire Resistance Directory". Application details are available inAutoCAD. format on request. GENERAL: Areas to be protected must be clean and free of oil, loose dirt or rust. Installation temperatures must be between 40oF (4oC) and 110oF (43oC). APPLICATION SYSTEM SELECTION: Selection of an DWG NO. FS - 0382 RO appropriate firestop application system design is critical to the fire protection process. Please consult the Nelson Firestop WALL ASSEMBLY - Construct as specified in the U300 or U400 directory and application guide as well as the UL. Fire series designs. The max. diam. of the opening is 4". Annular space Resistance Directory for additional information. is 1/2" to 1” METALLIC SLEEVE - Max. nominal 4" diameter min. FORMING: Some installations may require forming as either 28 GA steel sleeve having a min. 2" lap. Sleeve installed by coiling an integral part of the system or as an option to facilitate the sheet steel to a diameter smaller than the opening and releasing installation. In systems where forming is required, mineral the coil to let it uncoil against the periphery of the opening. Sleeve wool batts with a minimum nominal density of 4PCF are will extend a nominal 2" beyond each surface of the wall. generally required. Cut forming material oversized to allow for CABLES - Max. 40% fill of 100pr. #24awg., or smaller PVC jacketed tight packing. Position forming material to allow for the proper telecommunications cables. depth of fill material. FORMING MATERIAL - Tightly pack min. 4pcf mineral wool into the sleeve to the full depth. NELSON FSP PUTTY - Apply over the forming material to a min. 1-1/2" depth, flush with both ends of the sleeve.

EGS

Electrical Group

L 08 www.afielektrik.com FIRESTOP PRODUCTS FSP™ Firestop Putty

UL System No. C-AJ-5288 Product Description Nelson Firestop Sealant (LBS3™) is an elastomeric, water based, intumescent, fire protective sealant. It is designed for applications of through firestop penetrations and construction joints. It is used to seal against the spread of DWG NO. FS-0648 RO fire, smoke, gasses and water. Application LBS3™ is ideally suited for through firestop penetrations of non-combustible pipe, insulated pipe and combustible pipe such as PVC, PEX, CPVC and ABS, in floors or walls. LBS3™ sealant can be applied using a conventional • FLOOR or WALL ASSEMBLY - Min. 4-1/2” thick lightweight or normal weight caulk gun, bulk loader or by trowel. For larger applications it can be pumped concrete floor or min. 5” thick wall, or CMU block wall. Max. diameter of opening is 30”. directly from the pail. Actual installation of Nelson LBS3™, may vary • METALLIC SLEEVE (optional) - Max. 30” diameter steel sleeve cast or grouted according to the type of firestop application. Apply the required depth of into floor or wall assembly, flush with floor or wall surfaces. sealant beginning on the edge of the opening (use over various backing • METALLIC PIPE - Max. nominal 24”, or smaller, Sch. 20 or heavier steel or cast materials as required). Insure that the sealant makes complete contact with iron pipe. Max. nominal 6” diameter or smaller Type L or heavier copper pipe or tubing. the inside surface of the opening and also the surface of the penetrating • PIPE INSULATION - Nominal 2” thick, or thinner, FIBERGLASS pipe insulation. item(s). The annular space is 5/16” to 1-1/4”. Availability • FORMING MATERIAL - Tightly pack min. 4” thickness of min. 4pcf mineral wool AA0892 – 10.3 oz Tube 18.5 in3 (304ml) 12/Ctn. batt insulation to fill the annular space. AA0893 – 20.2 oz Foil Pack 36.45 in3 (597 ml) 12/Ctn. • NELSON ES1399/LBS3 SEALANT - Apply sealant over the forming material to a AA0894 – 30 oz Tube 54 in3 (883ml) 10/Ctn. min. 1/2” depth, flush with the topside of the floor or with both sides of the wall. AA0895 – 5 Gallon Pail 1155 in3 (19.0L) UL System No. C-AJ-1487 Approvals T Rating 0 Hr. Underwriters Laboratories Inc., Fill, Void or Cavity Material (XHHW), F Rating 2 Hr. Underwriters Laboratories Inc., Fill, Void or Cavity Materials certified for Canada (XHHW7) City of New York, New York, Department of Buildings • MEA 126-04-M Features • Up to 3-hour Fire Rating DWG NO. FS-0526 RO • Water-Based – Easy clean-up • Elastomeric, Flexible cure • FLOOR or WALL ASSEMBLY - Min. 2-1/2" thick concrete floor or • Highly Intumescent wall, or CMU block wall. Max. diameter of opening is 24-7/8" • Paintable • METALLIC PIPE or CONDUIT - Nominal 24" diameter, steel or cast iron, • Water Resistant max. 6" RMC, or 4" EMT or max. 6" Type L copper pipe or tubing. • No solvents, silicones or The annular space is 0" (point of contact) to 7/8". • Acoustically Tested – Reduces noise transmission • FORMING MATERIAL - Install backer rod into the opening and recess Physical Properties 1/2" from top surface of the floor or both surfaces of the wall. • Color ...... Red • NELSON LBS3 SEALANT - Min. 1/2" depth over the forming material. • Cure Time (skin over) ...... Approx. 2 hr. UL System No. C-AJ-2462 (full cure) ...... 3 to 4 weeks • Asbestos Fillers...... None F Rating 2 Hr. T Rating 1/2 Hr. • Solvents ...... None • Density ...... 10.0 Ibs./gallon • VOC Content...... 10.86 g/l • Application Temp...... 40º (4ºC) to 90ºF (32ºC) • Activation Temp...... Exp, begins @ 250º • STC Rating...... 52

Test Compliance FS-0530 RO • ASTM E84 and UL 723 DWG NO. Flame spread...... 0 • FLOOR or WALL ASSEMBLY - Min. 4-1/2" thick concrete floor or wall, or CMU block wall. Max. diameter of opening is 4-1/4" Smoke developed...... 5 • METALLIC SLEEVE (optional) - Nom 4" steel pipe • ASTM E90 Standard Test Method for Laboratory Measurement of Airborne • NONMETALLIC PIPE- Max, 2” Sch. 40 PVC pipe for use in closed Sound Transmission Loss of Building Partiitions and Elements (process or supply) piping systems.The nominal annular space range is 9/16” to 1-3/8”. • ASTM E814 and UL1479 Test method for through stop fire penetrations. • FORMING MATERIAL - Tightly pack min. 4pcf mineral wool batt insulation. • ASTM E1966 and UL2079 Test method for fire resistance of building joint • NELSON LBS3 SEALANT - Min. 1" depth over the forming material. systems. UL System No. W-L-3242 • ASTM C719 Adhesion and Cohesion of Elastomeric Joint Sealants Under Cyclic Movement. F Rating 1 or 2 Hr. T Rating 0 Hr. Testing Data For specific test criteria, refer to the UL Fire Resistance Directory. Storage & Handling Nelson LBS3™ should be stored at temperatures between 40ºF (4ºC) and 90ºF (32ºC). Protect from freezing. Expected shelf life is one year from date of shipment. Related References DWG NO. FS-0600 RO Underwriters Laboratories Inc. “Fire Resistance Directory”. ® Application details are available in AutoCad format on request. • WALL ASSEMBLY - Construct as specified in the U300 or U400 series designs per UL Fire Resistance Directory. The max. diameter of the opening is 4”. • CABLES - Max. 41 % fill of max. 2/C #12awg Type CATV copper conductor cable (12-2 ROMEX), max. RG/6#18awg Type CATV copper conductor coaxial cable, max. 1/C 350 kcmil cable, max. 400pr#24awg copper telephone cables all with polyvinly chloride (PVC) insulation and jacket, max. 1/C 350 kcmil cable with cross-linked polyethylene insulation and jacket or max. 4/C#2/0 aluminum or copper conductor, aluminum or steel jecketed METAL CLAD or ARMORED CLAD cable. The annular space between the cable bundle and the periphery of opening shall be a min. 0” (point of contact) to max. 1-1/4”. • NELSON LBS3 SEALANT - Min. 5/8" depth. EGS

Electrical Group

L 09 www.afielektrik.com FIRESTOP PRODUCTS PCS™ Pipe Choke System

Product Description UL System No. C-AJ-2086 Nelson pipe choke system (PCS™) is a prefabricated device used to seal F Rating 2 or 3 Hr. T Rating 0,1-1/2, or 2 Hr. penetrations and maintain the rating of fire rated floors and walls. The pipe choke is designed for penetrations of non-metallic pipes. When exposed to fire, the intumescent material expands to seal voids created from fire exposure on deteriorating penetrating items. The PCS™ consists of a heavy gauge metallic collar filled with a highly intumescent, pliable material. Application Nelson PCS™ is intended for use on combustible pipe firestopping penetration applications for pipe sizes up to 4 inches outside diameter. PCS™ requires no special skills or tools for installation. Choose the appropriate size of PCS™ to fit the penetrating pipe O.D. Flush mount to FLOOR or WALL ASSEMBLY - Min. 4-1/2" thick concrete floor or wall, the wall or floor surface using the mounting ears on the device. Actual or CMU block wall. The max. annular space is 1/4". Max. diameter of installation should be in accordance with the appropriate Nelson application opening is 5". system drawing. NONMETALLIC PIPE or CONDUIT - Nominal 4" diameter, Sch 40 PVC Availability solid core SDR11 Polybutylene(PB) or SDR17 CPVC pipe. PCS 1.5 ………… 1-1/2" nominal O.D.Pipe NELSON PCS PIPECHOKE - Apply the appropriate sized pipechoke PCS 2 ……………….. 2" nominal O.D.Pipe around the pipe on the underside of the floor, or on both sides of the wall. Secure to the concrete with steel masonry anchors and fender washers. PCS 3 ……………..… 3" nominal O.D.Pipe DWG NO. FS-0111 R8 PCS 4 ……………….. 4" nominal O.D.Pipe Approvals UL System No. W-L-2071 Underwriters Laboratories Inc., Firestop Device For Use in Through- F Rating 1 or 2 Hr. T Rating 1/2, 1 or 2 Hr. Penetration Firestop Systems (XHJI) , Factory Mutual (FM), City of New York, New York, Department of Buildings • MEA 173-99-M • MEA 196-84-M Vol. 3 • MEA 236-87-M Vol. 2 Features • Up to 3-Hour Ratings • Unlimited Shelf Life • Easy to Install • Highly Intumescent WALL ASSEMBLY - Constructed in the manner specified in the U300 • VOC Compliant or U400 series designs as shown in the UL Fire Resistance Directory. • Non Toxic The nom annular space is 1/4" to 5/16" for 2" diameter or less pipes • Retrofitable or conduits and the annular space is 1/4" for pipes or conduits greater • Does not Require Additional Caulking than 2". Physical Properties NONMETALLIC PIPE - Nominal 4" diameter, or smaller, Sch. 40 PVC • Color ………………………Silver or RNC pipe for use in closed (process or supply) or vented (drain, waste • Asbestos Filler ……………None or vent) piping systems or SDR13.5 CPVC pipe for use in closed piping • Solvents ……………………None systems. F and T ratings are as follows: • Hazardous Ingredients …..None Pipe Size F Rating (Hr.) T Rating (Hr.) • Intumescent Expansion Activation Temp. …………..Initial 300ºF • VOC Content ………………Negligible 4” 1 1 • Volume Increase …………..> 300% 4” 2 2 • Density………………………1.4 lbs / cu. in. • Application Temp…40°F (4°C) to 90°F (32°C) Test Compliance 3” 1 1 • ASTM E119 and UL263, Fire Tests of Building Construction and Materials 3” 2 2 • ASTM E814 and UL1479, Test method for through stop fire penetrations. 2” 1 1/2 Testing Data 2” 2 2 For specific test criteria, refer to the UL Fire Resistance Directory. Limitations NELSON PCS PIPECHOKE - Install the appropriate sized pipechoke Nelson PCS™ should not be heavily exposed or come in direct contact around the pipe on both sides of the wall and secure the choke to the with chemicals. Service temperature shall not exceed 180ºF (82ºC). wall with 1/8" diameter by 1-3/4" toggle bolts in conjunction with 1/4" Related References by 3/4" diameter and 1/4" by 1-1/4" diameter steel fender washers. Underwriters Laboratories Inc. “Fire Resistance Directory”. Application DWG NO. FS-0110 R4 details are available in AutoCAD. format on request. UL System No. F-C-2031 GENERAL: Areas to be protected must be clean and free of oil, loose dirt F Rating 2 Hr. T Rating 0 Hr. or rust. Installation temperatures must be 40oF (4oC) and above. APPLICATION SYSTEM SELECTION: Selection of an appropriate firestop system design is critical to the fire protection process. Please consult the Nelson Firestop directory and application guide as well as the UL. Fire Resistance Directory for additional information. INSPECTION: Determine if the PCS will fit the pipe application and determine the number of required anchors. Determine if the annular space between the pipe and the edge of the opening is between 1/8” and 1/4”. The annular space must be 1/8” minimum to allow the PCS to slide through. If the annular space is greater than 5/16”, the PCS cannot be used. INSTALLATION: PCS device incorporates anchor tabs for securement to both surfaces of gypsum wall by means of 1/8” diameter by 1-3/4” long steel toggle bolts in conjunction with 1/4” by 3/4” diameter and 1/4” by 1-1/4” diameter steel fender washers. PCS device incorporates anchor tabs for securement to bottom surface of concrete floor or both surfaces of concrete wall by means of 1/4” diameter by 1-3/4” long steel sleeved concrete anchors in conjunction with 1/4” by 3/4” diameter and 1/4” by 1-1/4” diameter steel washers. PCS device incorporates anchor tabs for securement to finished gypsum wallboard ceiling by means of 1/8” diameter by 3” long toggle bolts in conjunction with 1/4” by 1” diameter steel fender washers. DWG NO. FS-0137 R2

EGS

Electrical Group

L 10 www.afielektrik.com FIRESTOP PRODUCTS WRS3™ Wrap Strip

Product Description UL System No. W - L - 2388 Nelson Wrap Strip (WRS3™) is a highly intumescent firestop wrap system. F Rating 1 or 2 Hr. T Rating 0,1 or 1-1/2 Hr. When exposed to fire, the wrap strip expands and forms a hard char to seal off the penetrating item and preventing the passage of fire and hot gasses. Application Nelson WRS3™ is designed for combustible pipe and insulated pipe through stop penetrations in fire rated floors and walls. WRS3™ is easily installed by following the appropriate firestop system design detail. The Wrap Strip is cut to length to fit the circumference of the pipe. Depending on the system requirements, additional layers may be required and will be cut to fit over layer. A metal restraining collar is available where required previous which is a mechanical device designed to hold the wrap strip in place. Restraining WALL ASSEMBLY - Constructed in the manner specified in the U300 collar is easily cut to fit and no special skills or tools are required to install. or U400 series designs as shown in the UL Fire Resistance Directory. Availability NONMETALLIC PIPE or CONDUIT - Max. 4" nominal diameter, Sch. 40 AA0896 – 1" x 1/4" x 12' roll (25.4mm x 6mm x 3.65m) PVC ABS or RNC pipe for use in closed (process or supply) or vented AA0897 – 11/2" x 1/4" x 12' roll (38mm x 6mm x 3.65m) (drain, waste or vent) piping systems. Max. 4" diameter or smaller AA0659D - 1" to 11/2" x 25' Restraining Collar SDR13.5 CPVC pipe for use in closed piping systems. The annular (25.4mm to 38mm x 7.62m) space between pipe, conduit or tubing and periphery of opening shall Approvals be 0" (point of contact) to 1/2". Underwriters Laboratories Inc., Fill, Void or Cavity Material (XHHW) NELSON LBS3 SEALANT - Apply LBS3 within the annular space to a City of New York, New York, Department of Buildings min. 5/8" depth, flush with both wall surfaces. At point of contact, a min. • MEA 128-04-M 3/8" diameter bead of sealant shall be applied at the gypsum/pipe Features interface on both surfaces of wall. • Up to 3-Hour Rating NELSON WRS3 WRAPSTRIP - Apply 1" wide WRS3 around the pipe • Ease of installation on both sides of the wall in accordance with the schedule shown in the • Highly Intumescent table below. • Excellent Freeze-Thaw Pipe Type Max.Pipe Size Nos.of Layers F Rating (Hr.) T Rating (Hr.) • Asbestos Free PVC,CPVC or RNC 4 2 2 0 • Solvent Free ABS 4 3 2 1-1/2 • No hazardous ingredients PVC,CPVC or RNC 4 3 2 1 • Cost Effective PVC,CPVC or RNC 3 2 2 1 • Water Resistant Physical Properties ABS 3 2 2 1-1/2 • Color………………..Red PVC,CPVC or RNC 2 1 2 1 • Intumescent Expansion Activation –250ºF (121ºC) ABS 2 1 2 1-1/2 • Service Temperature 40ºF (4ºC) and 90ºF (32ºC). Test Compliance PVC,CPVC,ABS or RNC 4 3 1 0 • ASTM E814 (UL1479) PVC,CPVC or RNC 4 2 1 0 Testing Data PVC,CPVC,ABS or RNC 3 2 1 0 PVC,CPVC,ABS or RNC 2 1 1 0 For specific test criteria, refer to the UL Fire Resistance Directory. Storage & Handling STEEL RESTRAINING COLLAR - Apply nominal 28 gauge prefabricated Nelson WRS3™ should be stored between temperatures of 40ºF galvanized steel collar around the wrapstrip. Overlap the collar and (4ºC) and 90ºF (32ºC). secure with 1/2” wide by 0.028” thick stainless steel hose clamp. Collar Related References secured to the wall with 1/8” diameter by min. 2-3/4” long steel molly Underwriters Laboratories Inc. “Fire Resistance Directory”. Application bolts in cojunction with 1/4” by 1-1/4” diameter steel fender washers. details are available in AutoCAD. format on request. DWG NO. FS-0632 R0 GENERAL: Areas to be protected must be clean and free of oil, loose UL System No. C - AJ - 2489 dirt or rust. Installation temperatures must be 40ºF (4ºC) and above. F Rating 2 or 3 Hr. T Rating 1-1/2 or 2 Hr. APPLICATION SYSTEM SELECTION: Selection of an appropriate firestop system design is critical to the fire protection process. Please consult the Nelson Firestop directory and application guide as well as the UL. Fire Resistance Directory for additional information. WRAPSTRIP: Nom 1/4” thick intumescent material faced on both sides with a plastic film, supplied in 1” or 1-1/2” wide strips. The layers of wrapstrips are individually wrapped around the through penetrant with ends butted and held in place with masking tape. Butted ends in successive layers shall be offset. The edge of the wrapstrip shall abut the surface of the wall or floor. The layers of wrapstrips are installed on each side of the gypsum or concrete wall or bottom side of the concrete floor. The number of layers and width of wrapstrip is dependent on the diameter of the through-penetrant and annular space within the firestop system. FILL MATERIAL: Nelson Firestop Sealant (LBS3™) ranging from 1/4” thickness to 3/4” thickness is applied within the , flush with top surface of the floor or with both surfaces of the wall. Please refer to the UL. Fire Resistance Directory for the appropriate thickness. STEEL COLLAR: Collar fabricated from coils of precut 0.019 in.(No. 28 MSG) galvanized sheet steel by 1” deep and with min. five 1-1/4”wide by 2” long anchor tabs for securement to the concrete floor or wall. Min. four 1-1/4” wide by 2” long anchor tabs for securement to gypsum wall. Retainer tabs, Pipe Type Max.Pipe Size Annular Space(In) Nos.of Layers Useof Layers F Rating (Hr.) T Rating (Hr.) 3/4” wide tapering down to 1/4” wide and located opposite the anchor tabs, PVC,CPVC,RNC 4 10 5 0-38 3 Not Permitted 2 0 PVC,CPVC,RNC 3 0-38 2 Not Permitted 2 0 are folded 90 degrees towards through-penetrant and to retain the wrapstrips. PVC,CPVC,RNC 1-1/2 to 2 0-38 1 Not Permitted 2 2 Steel collar wrapped around wrapstrips and through penetrant with a 1”wide PVC,CPVC,RNC 4 0-34 3 Permitted 2 1-1/2 PVC,CPVC,RNC 3 0-34 2 Permitted 2 2 overlap along its perimeter joint. Steel collar tightened around wrapstrips and PVC,CPVC,RNC 1-1/2 to 2 0-34 1 Permitted 2 2 ABS 4 0-34 3 Permitted 3 3 through penetrant using min. 1/2” wide by 0.028in. thick stainless steel hose ABS 3 0-34 2 Permitted 2 2 clamp installed at mid-height of the collar. Collar secured to concrete surface ABS 1-1/2 to 2 0-34 1 Permitted 3 3 with 1/4” diameter by min. 2-1/4”long steel concrete anchors in conjunction with min. 1/4” by 1-1/4” diameter steel fender washers. Collar secured to gypsum wall with 1/8” diameter by min. 2-3/4” long steel molly bolts in conjunction with min. 1/4” by 1-1/4” diameter steel fender washers. Collars are installed on both sides of wall. DWG NO. FS-0638 R1 EGS

Electrical Group

L 11 www.afielektrik.com FIRESTOP PRODUCTS PLW™ Firestop Pillows

Product Description Nelson (PLW™) is a compressible firestop device that is UL System No. W - L - 4003 F Rating 1 or 2 Hr. T Rating 1/2 Hr. well suited for installations where frequent changes may be required. PLW™ consists of a mineral fiber treated with a highly intumescent material enclosed in a strong polyethylene bag. When exposed to fire, the pillows expand to lock the seal in place. Even though PLW™ is classified as a permanent firestop system for several applications including steel and aluminum cable trays, PLW™ also is an excellent temporary seal. Application Nelson Firestop Pillow (PLW™) is ideally suited for applications for cable tray penetrations or temporary closures requiring fire rating integrity. Install Nelson PLW™ into areas where the surfaces are clean and free of dust, grease, oil, loose materials, rust or other substances. Pillows may be coated with cable pulling lubricant for ease of installation. Tightly pack the pillows and insert lengthwise into openings. Actual installation should be in accordance with the appropriate Nelson application system drawing. WALL ASSEMBLY - Constructed in the manner specified in the U300 Availability or U400 series designs as showing the UL Fire Resistance Directory. AA0478 – 9.6” x 4” x 3” 20/Ctn. The max. area of opening is 160 sq. in. with a max. dimension of 20". AA0479 – 9.6” x 8” x 3” 10/Ctn. The annular space between the cable tray and top and bottom of the Approvals opening shall range from 0" (point of contact) to 2". Underwriters Laboratories Inc., Fill, Void or Cavity Material (XHHW) and CABLE TRAY - Max. 18" wide x 4" deep aluminum or 18" x 6" steel, (XHHW7), Factory Mutual (FM) open ladder type cable tray. The annular space is 1". Features CABLES - Max. 18-30% aggregate cross-sectional fill of power, control • Up to 3-Hour Ratings or communications cable (300 MCM), 7C-12 awg and 100 pr. 24 awg. • Unlimited Shelf Life STEEL CHANNEL - Fabricated from 30 ga. galv. steel. Channel is to • Easy to Install bridge the stud cavity on both sides of the opening with a min. 3" flange • Highly Intumescent on both sides of wall. • Highly Compressible NELSON PLW PILLOWS - Pillows to be installed horizontally through • No Disagreeable Toxic or Hazardous Fumes the wall and centered within the opening of the wall. • Easily Repenetrated NELSON FSP PUTTY - After installation of the pillows, apply FSP putty Physical Properties to seal any voids between the cables, cable tray and the pillows • Color ……………………....Safety Orange WIRE LATH - Nominal 2", 19awg. galv. steel wire lath, cut to fit the • Asbestos Filler ……….…..None contour of the opening with a min. 3" lap beyond the periphery of the • Solvents …………………..None opening. • Hazardous Ingredients ….None DWG NO. FS-0097 R4 • Activation Temp.……....Initial >275ºF (135ºC) • k - Value ………….0.25 BTU in./hr. sq. ft. ºF • Polyethylene Thickness …4 mils Test Compliance • ASTM E119 and UL263, Fire Tests of Building Construction and Materials UL System No. C -AJ - 4032 • ASTM E814 and UL1479, Test method for through stop fire penetrations. F Rating 2 Hr. T Rating 0 Hr. Testting Data For specific test criteria, refer to the UL Fire Resistance Directory. Storage & Handling Nelson PLW™ should be stored in dry, covered locations at no greater temperature than 120ºF (49ºC). There is no indication of shelf life limitations. Limitations Nelson PLW™ should not be exposed to chemicals harmful to polyethylene. Service temperature shall not exceed 275ºF (135ºC). Related References Underwriters Laboratories Inc. "Fire Resistance Directory". Application details are available in AutoCAD. format on request. GENERAL: Areas to be protected must be clean and free of oil, loose dirt or rust. APPLICATION SYSTEM SELECTION: Selection of an appropriate firestop application system design is critical to the fire protection process. Please consult the Nelson Firestop directory and application guide as well as the UL. Fire Resistance Directory for additional information. PILLOW: Install Nelson Firestop Pillows (PLW™) so the 9.6” dimension travels through the wall, or floor. Start with the bottom corners and tightly pack pillows vertically so that the large faces of the pillows are facing the framing. Install tightly packed pillows horizontally in rows between the space of vertically installed pillows. Apply a min. depth of 1” of (FSP™) putty in all four corners between the vertical pillows and framing. Any voids between pillows and pillows and penetrating items must be filled with (FSP™) putty at a min. depth of 1”. WIRE LATH: Nominal 2”, 19awg galv steel wire lath, cut to fit the contour of the opening with a min. 3” lap (2” lap for concrete) beyond the periphery of the opening. Wire lath secured to both surfaces of gypsum wall assembly with 2-1/4” long Type S self drilling, self tapping bugle head steel screws and 1/4" by 1-1/2” diameter steel fender washers, spaced 6” OC. Wire lath secured to both surfaces of concrete floor or wall assembly with 1/4” diameter by 1-3/4” long concrete anchors in conjunction with 1/4" by 1-1/2” diameter steel fender washers, spaced 6” OC. CALCULATION: Measure the opening, in inches, and multiply length by width, which gives you the total area in sq. in. (TA). Estimate the penetrating item DWG NO. FS-0147 R3 area and subtract it from the total area of the opening (TA) to get the area to be firestopped (FA). Take the area of the pillows and divide into the firestopped area (FA) to get number of pillows needed. Example: Opening size is 8” x 40” (320 sq. in.) (Total area) (TA). Cable tray is 36” x 6” @ 40% cable fill. Total Area(TA) is 320 sq. in. and penetrating item area is .4” x 6” x 36” (86.4) sq. in. Take total area (TA) and subtract penetrating EGS item area to get firestopped area (FA) (320 – 86.4 = 233.6 sq. in.). Area of pillows (PA) is 3” x 4” x 20% compression or 3” x 8” x 20% compression. Electrical Group Take (FA)/(PA) = number of pillows needed.

L 12 www.afielektrik.com FIRESTOP PRODUCTS MCT™/ MPS™ System TECRON/FLEXRON

Product Description Physical Properties Nelson MCT™ modules are a molded, neoprene based • Boiling Point Not established product, which form an airtight/watertight seal and • Specific Gravity @ 68ºF 1.7 – 1.9 provide maximum fire protection of cables passing • Vapor Pressure (mmHg) and Temperature Solid through fire rated walls, floors, decks, or bulkheads. • Melting Point >1000ºC Application • Vapor Density (Air =1) Solid Modules are selected to coordinate with cable • Evaporation Rate Solid diameters passing through the wall, floor, bulkhead or • Appearance Brick Red deck being penetrated. A variety of welded metal • Odor None frames are utilized to house the modules. Blank • Durometer Tecron 68 – 75 modules are used to fill unused spaces. The finished • Flexron 45 - 55 frame assembly will be completely filled using Test Compliance modules and related stay plates, compression plate • MIL-S-901C Shock Test and end packing such that a compression fit is • MIL-STD-167-1 Vibration Test applied to all modules within the frame • MIL-P-24705 QPL 2000ºF Availability • IMO A. 754 (18) A. III & A. IV Most modules, strips and accessory items are in • ASTM E-814 and UL1479 – Test stock. Please contact a distributor or Customer method for through stop fire penetrations. Service for more information. Approvals Uses • Underwriters Laboratories, Inc. Firestop device for use in fire rated walls or floors in • U. S. Navy construction applications and in marine vessel decks • U. S. Coast Guard and bulkheads. • American Bureau of Shipping (ABS) Features • Det Norske Veritas (DNV) • Neoprene based – good resistance to acids, • Lloyds Register gasoline, lube oils, animal and vegetable oils, Testing Data oxidation, ozone and weather. Available upon request. For UL approval see • Good dielectric strength. Underwriters Laboratories “Fire Resistance Directory”. • High tensile strength, tear resistance, Storage & Handling abrasion resistance. Tecron & Flexron modules should be stored indoors • Good rebound characteristics. between 40ºF (4ºC) & 90ºF (32ºC). • Up to 4 hour fire rating. Related References Underwriters Laboratories Inc. "Fire Resistance Directory". Application details are available in AutoCAD. format on request.

EGS

Electrical Group

L 13 www.afielektrik.com