<<

Commercial Rooftop HVAC Energy Savings Research Program Bench Test Report June 2008

Prepared by: Mark Cherniack – Senior Program Manager Howard Reichmuth PE – Senior Engineer

Prepared for: Northwest Power and Conservation Council 851 SW Sixth Avenue, Suite 11100 Portland, Oregon 97204 (503) 222-5161

Acknowledgements Acknowledgements The design and set up of the testing chamber, testing of the components/systems, and initial data assessment was completed by David Robison, P.E., Stellar Processes, Bob Davis, Ecotope and Dennis Landwehr, P.E. under subcontract to New Buildings Institute (NBI). NBI staff is responsible for the final report and conclusions. The following organizations provided funding to make this phase of the ongoing research possible. They responded to an invitation to participate in this opportunity to further the potential for cooperative research partnerships among interested participants nationwide on small commercial HVAC system issues. Their contributions are much appreciated. From the Pacific Northwest through the Northwest Power and Conservation Council Avista Utilities Bonneville Power Administration Eugene (OR) Water and Electric Board Energy Trust of Oregon Idaho Power PacifiCorp (non-Energy Trust area) Puget Sound Energy Snohomish Public Utility District

From the Northeast Cape Light Compact (through Northeast Energy Efficiency Partnership-NEEP) Connecticut Light & Power (NEEP) Long Island Power Authority (NEEP) The United Illuminating Company (NEEP) Western Massachusetts Electric (NEEP) Efficiency Maine Efficiency Vermont National Grid New York State Energy Research and Development Authority NSTAR

The Project Team also acknowledges the responsiveness of Honeywell Product Manager Adrienne Thomle and her engineering staff for making recommendations that strengthened the research, as well as responding with new product designs that will allow economizers to fully function as intended in saving energy. Executive Summary This work has been done as part of the Commercial Rooftop HVAC Energy Savings Research Program which includes four interdependent elements: 1) bench testing of economizer controls, 2) field testing of repair protocols, 3) devising an appropriate measurement and verification (M&V) approach and 4) developing a savings prediction methodology based on prototypical buildings. Taken together, these elements are intended to lead to the development of a reliable field repair protocol with a higher level of confidence in the associated energy savings. This document summarizes the results of only the first of the four elements, the bench testing of economizer controls. This document is also an interim summary of results because the bench testing capability is being retained and will be used further during the project. The bench testing research was applied to the most typical type of dry bulb economizer controller using controlled environmental chambers to determine the environmental and control factors that influence the operation of the economizer. The principal findings are: • The sensors and economizer controller system exhibits an operational pattern (deadband) that can significantly interfere with expected economizer operation by limiting the economizer potential during seasons with warm nights. We refer to this as “hysteresis” in this report. • The sensor and controller components tested exhibited a consistent low bias in . Environmental that are supposed to activate the controller do not correspond to those specified by the manufacturer. The apparent wide sensor and controller tolerance leads to loss of economizer energy savings potential. • The sensors tested appear initially to be more accurate than the dry-bulb sensors tested. However, this stage of research did not measure sensor response over the range of that would be necessary to fully test enthalpy sensors. Some “hysteresis” is present with enthalpy sensors as was exhibited in the dry-bulb sensors tested, but the magnitude of the deadband across a range of conditions is not yet bounded by the available data. Additional testing of the enthalpy sensor is still underway. • A dual differential economizer strategy was tested and compared to the single changeover strategy as a potential improvement. The differential control strategy used in conjunction with a 2-stage has the potential for a more sophisticated control than a simple single change point strategy. However, test results showed only modest improvement from this control strategy. This strategy may be more complex to execute in a simplified and consistent field procedure. It also requires a 2-stage thermostat, which is recommended in any case for effective economizer performance. • A proposed “work-around” solution in the field would substitute an inexpensive contractor’s thermostat (<$10) for the temperature sensor commonly in use. This combination operates with very little hysteresis and is expected to increase the amount of economizer operation. This work around is amenable to a simple and consistent field procedure. • Honeywell personnel provided helpful feedback on the testing protocol. They do not support the proposed work around due to concerns about high feed-in amps to the controller, even though a resistor could be added the circuit.

- 3 - • The test apparatus was successful in providing an inexpensive set of controlled environmental chambers. Taken together these findings cast significant doubt on the capability of existing economizers, specifically with the Honeywell C7450 dry bulb/temperature sensor, to perform according to their potential. Given that economizers have been embodied in building codes on the assumption of performance consistent with their specification, there is an urgency to apply corrective measures. Accordingly, the immediate recommendations are: • A dialog has been opened with Honeywell, the controller/sensor manufacturer, concerning the findings in this report and the proposed work-around. These findings suggest that a significant group of existing economizer controls currently in operating RTUs cannot access the full economizer potential. This is a major functionality problem with significant kWh waste that needs addressing and it is important to continue to access the knowledge of the equipment manufacturer in this regard. • Honeywell, in response to the bench test results that provided important ‘customer’ input to the sensor/controller product manager, has developed a new, advanced dry-bulb sensor that should resolve the field problem. Honeywell has committed to sending several beta stage sensors for bench and field testing in July. If this new sensor works as expected, further discussions about a field retrofit package for utility programs will be held with Honeywell. Commercial availability is expected 3rd quarter of 2008. • Utilities should assess the impacts of identifying the economizer controller sensor equipment described in the report, that may be installed in new RTUs that are receiving financial incentives through current or planned utility energy efficiency/DSM programs. If the particular Honeywell sensor product is present in these new units, a decision must be considered about including a modification to the equipment at installation time so as to not install the problem sensor. A field work-around employing the contractor’s thermostat or snapdisk could be used in lieu of the problematic temperature sensor. The work-around should be based on the single change point control and not use the differential control. The implementation of the work around should be viewed as temporary until the new Honeywell sensor is commercially available. Alternately, utility high efficiency RTU incentive programs could at least flag those systems for a follow up sensor retrofit. • The bench test has been expanded to include Honeywell enthalpy-based economizer controls. It is could be expected that the hysteresis effects observed for dry bulb temperature sensors would not be as significant in the case of enthalpy sensor otherwise, the use of economizing in the more humid eastern US will also be limited relative to its potential. At the time of this report, data is still too sparse from the enthalpy sensor tests for reporting conclusions.

- 4 - Introduction The principal conservation benefit from using an economizer proceeds from using cooler outside air for space cooling instead of air-conditioning when conditions permit. Unfortunately, detailed monitoring revealed that economizing is often ineffective. One cause of this problem is due to a known problem with the economizer control system, referred to here as “hysteresis.” In the typical control mode, the controller must sense a sufficiently cold outdoor temperature before economizing is allowed – this temperature is typically 10ºF cooler than the indoor temperature. This required temperature is referred to as the nominal changeover temperature. Earlier monitoring studies have shown that this “hysteresis” effect prevented economizing during warm summer months in mild climates because the coldest nighttime temperatures were not cold enough to allow economizing. The same problem was not observed in climates with a larger diurnal temperature swing and colder night temperatures. The purpose of the current investigation is to test a typical controller system, identifying the extent to which hysteresis or poor sensor calibration might limit full operation, and to develop and test a “work-around” solution as part of the development of the field service protocol that will be implemented in Phase 3 of the overall project. This preliminary task has been limited to testing the controller apparatus within a set of controlled environmental chambers in order to quantify the problem and verify the potential solution. A future task, and part of the field testing portion of the larger project, will be to implement the proposed solution in the field and to verify the energy impact on HVAC equipment in actual service. This bench testing alone is not sufficient to quantify the full energy impact of economizing because that is a complex function of specific site characteristics and operations. The full energy impact of economizing requires building modeling guided by these lab results and by the field test results. The necessary modeling and field testing are a coordinated part of the larger project. It is usually not necessary to bench test commercial equipment. However, the current status of this type of controller has been shrouded in conflicting anecdotal observations and incomplete knowledge of the inner logic of the control system. In the view of the research project oversight committee, the intended research needed to be based on a precise understanding of the control system performance that could not be assessed from existing research or from the specifications provided by the manufacturer.

This initial report discusses observations regarding the dry-bulb economizer control operations as observed in an indoor test chamber. This type of economizer operation is important in the Pacific Northwest and Rocky Mountain areas where humidity is generally low. Enthalpy controls for economizers will be assessed at a later time as part of the project since they are important for utilities supporting this research in the Northeast, where humidity has a greater impact.

- 5 - Previous investigations have attempted to quantify the savings from repair of existing packaged HVAC units1. These HVAC units are numerous in small commercial buildings, but conservation options have been difficult to justify due to the costs necessary to reach these small customers. Demonstration of cost and benefits will assist agencies in designing conservation outreach programs. Background A preliminary task to the bench test effort was to review available field experience to identify the most commonly used control items for test. Accordingly, we reviewed available characteristics data collected as part of Puget Sound Energy (PSE) Premium Service Rooftop program. To be eligible for the program, an RTU must have an economizer. This represented a fairly large set of data expected to be typical of installations in the Northwest. Out of 223 systems with economizers, the following characteristics were noted: • 70% had the controller that we are testing • 41% used enthalpy sensors with unknown drift and calibration, although only dry- bulb sensing is necessary in our climate. • 56% had only a single stage of cooling wired, which significantly curtailed economizer use. • 73% used single changeover point (one outdoor sensor and no return air sensor), 27% used a differential changeover strategy. Taken together these statistics suggest that about 60% of the units were operating below par. The main reason is the predominant use of single stage control. A secondary reason is the unnecessary use of enthalpy sensors in this climate. One manufacturer (Honeywell) has provided the basic controller (W7459) used throughout the last several decades by most HVAC manufacturers – with about 85% market share. Recently, other companies have developed their own products. However, this particular controller is ubiquitous among existing installations that would be candidates for retrofit repairs. For that reason, we targeted this particular controller as the subject of study. The particular items bench tested are itemized below.

Item/Function Manufacturer Model /Part # Economizer Controller Honeywell W 7459 Dry bulb Temperature Sensor Honeywell C 7650 Contractor’s Thermostat, Temp-Stat TS-65 (<$10) Snap Disc Thermostat (~$25) Service First SEN00235A Model 20602L4-B74

Table 1 – Items Tested

1 Small Commercial HVAC Pilot Program Market Progress Evaluation Report, No. 1, http://www.nwalliance.org/research/reports/135.pdf

- 6 - The initial understanding of the particular control logic was somewhat general and informed principally by the manufacturer’s product cut sheets and application guide. At the outset, controller operation is generally understood as follows: The important part of the controller is a potentiometer that compares conditions and modulates the economizer dampers in response to control parameters. Those parameters include 1) installer-adjusted set points for the outside air temperature which triggers economizer operation (A, B, C, D settings), 2) a reference condition that is usually a set resistor, but an indoor temperature sensor is used for differential control, and a 3) a sequence to assure that supply temperature is not overly cold. When there is a call for cooling and economizing is possible, the controller sends 24 volt current to the motor, which simultaneously opens the outside air dampers and closes the return air dampers. An LED light indicates this condition. When there is no current, the LED turns off and the motor resets by spring action to a minimum amount of outside air needed to meet guidelines. This example can be described as a single changeover strategy since operation change is controlled by a single outside air sensor referenced to the controller set points. Notice that this idealized description of the control logic does not mention any hysteresis effect in the cut sheets, though it is mentioned in a note in the applications guide. After the detailed testing conducted here, a precise apparent control logic diagram was devised and is shown in Figure 3 (pg.9). Component Testing Results The bench testing was done in a testing facility, described in Appendix A, set up specifically for this purpose. The initial bench tests were intended to reveal the specific operation of the control system on a limited number of controllers and sensors, hence the results are essentially anecdotal and are not intended to be statistically rigorous samples. Two controllers and four temperature sensors were purchased for testing purposes. Eugene Water and Electric Board (EWEB) staff also provided a number of working but used sensors retrieved from various repair jobs. The test equipment recorded the position of the economizer actuator arm and the status of the LED indication light. Both are conditions that indicate the controller is operating in economizer mode. Both of these conditions agreed closely with each other – typically the actuator arm moved within a few seconds of the indicator light. The manufacturer’s cut sheet for sensors2 indicates that control operations and sensor ma output are expected to follow a linear response to outdoor temperature. This manufacturer’s specification is referred in this report as the “reference”. Of course, the reference range of operation also depends on the installer-adjusted set points (A, B, C, D settings). Initial tests of sensors and controllers were directed at the electrical properties of the components compared to temperature. These initial tests revealed that the controller and temperature sensors were biased toward low temperature readings. That is, sensors activated operation at temperatures lower than actual temperature. The tests also showed that the temperature sensor output exhibits sensitivity to the excitation voltage. However, measurements on the individual components, such as current versus temperature in the temperature sensors, led to inconclusive results due to lack of knowledge of the electronic details of the control approach. Accordingly, an overall control test protocol was devised that treated the sensor and controllers as a single component. This overall control test protocol is described and discussed in Appendix B.

2 Figure 3. C7650 Temperature Sensor Output Current of C7650 Sensor Manual 63-2499-1, 1996.

- 7 - Implied Controller Temperature Points 100 90

80 Reference 70

60 7650 Test DegF 50 Result 40 30 20 D C B/C B

Figure 1 - Test of Controller Settings

Reference Observed Deg F Deg F D ON 45.0 39.1 OFF 54.6 48.1 C ON 59.1 51.0 OFF 68.7 60.5 B/C ON 65.5 59.2 OFF 74.8 70.1 B ON 71.9 61.5 OFF 80.9 71.0

Table 2 - Reference and Observed Change Points

Figure 1 and Table 2 show the response of one typical sensor at different controller set points under the testing protocol as described in Appendix B. For this sensor, all the tests results are biased lower than the specified reference. For example, at setting B/C, economizing is expected to occur within the range of 65 to 75ºF ambient temperature. In fact, the operation occurred within a range of 59 to 70ºF. The result is a constraint on economizing operation. Using this example at setting B/C, night temperatures will have to fall to below 59ºF so that economizing will take place the next day. Obviously, this rules out economizing during much of the summer in a mild climate. Thus, even such a small error can result in a serious reduction of economizing. The test results agree with previous field monitoring that showed ineffective economizing in locations with warm night temperatures. An evident difficulty is that the installer, relying on the manufacturer’s reference documentation, will not be able to select an appropriate setpoint due to the undocumented bias of the components, which appears to be variable among sensors.

- 8 - Previous studies have observed that the controllers are typically shipped from the factory set at setting D. Figure 1 demonstrates that this setting assures little or no economizing. As a result, the repair programs have recommended that installers change the setting to B or C. Based on PSE program data, installers are following that recommendation and typically adjust the setting to midway between B and C. Accordingly, B/C was used as the typical setting for subsequent testing.

Example of Controller Operation

90

80

70 On 60 Off

50 Temperature, degF 40

40 40 20 00 8:20 1:00 4: 7:40 11: 15:00 18:20 21: 11: Time

Figure 2 - Example of Controller Operation Figure 2 shows an example of typical test runs that illustrate the hysteresis effect. In this first part of the example, the chamber starts at a temperature near 70ºF, so the controller quickly turns economizing “off”. Economizing remains “off” until the temperature falls to 60ºF; then it turns “on” again. As the temperature rises, economizing remains on until the temperature reaches about 70ºF. The important point is that the controller does not initiate operation until the temperature falls to the “reset” point of about 60ºF. Then, economizing continues until the temperature rises again to the high limit. At that point, economizing is halted until the “reset” temperature is again experienced. This operation continues through any number of similar cycles. This example duplicates the problem observed in the field – economizing will not occur unless night time temperatures fall to the low set point, which may not happen under milder nighttime conditions. There was concern that the installer may not do A, B, C, D settings consistently. The set potentiometer is small and difficult to read in the field, and the potentiometer is continuously variable, with no physical ratchet for the A, B, C, D points. So one question tested was: how reproducible are the settings? Multiple attempts to set at the A, B, C, D settings were fairly repeatable.

- 9 -

APPARENT ECONOMIZER LOGIC

Set reference temps, ref low and ref high, with ABCD potentiometer

Is OSA yes no less than ref low?

Turn on reset Is OSA yes no indicator less than ref high?

Is reset no yes indicator Turn off reset on? indicator

Is supply yes temp no greater than 55°?

No voltage to actuator, LED is off 24 volts to actuator LED and damper returns is on, damper is opened by spring to minimum full or controlled to setting maintain 55F supply Figure 3 - Control Logic Diagram Based on these observations, Figure 3 shows a diagram of the control logic as determined from the bench test results. Of course, the controller is only operational when there is a call for cooling. Both controllers tested performed identically. This suggests that it might be possible to set the controller at a setpoint to compensate for the observed temperature bias in the sensors. However, the sensors exhibited some variability in the amount of bias. Figure 4 and Table 3 show how several sensors performed with the controller at the same B/C setting each time. Such variability makes it difficult to define a standard offset that would compensate for the biased measurements. More important, this compensation approach does not solve the hysteresis problem. Figure 4 and Table 3, show the performance of the four new C7650 sensors and six older C7650 sensors. Initially, we were concerned that older sensors might drift off calibration and be less accurate. Disassembly of the sensors in Figure 5 shows that, although the model number has not changed, the manufacturing design has changed. The new sensors utilize different internal components than the old ones. While our sample is small, it suggests that there is little difference in performance between new and older sensors.

- 10 - Implied Controller Temperature Points, Setting B/C 90 85 Reference 80 New 75 Sensors 70 Used 65 Sensors DegF 60 Contractor 55 Tstat 50 Snapdisk 45 40

Figure 4 - Comparison of Sensors

New Sensors Used Sensors DegF DegF DegF ON B/C 65.5 #2 59.2 E#1 64.1 Reference

OFF 74.8 70.1 72.7 ON #1 61.6 E#3 63.6 OFF 71.3 72.0 ON T-statA 63.3 #3 60.7 E#4 63.7 OFF 65.3 70.3 73.6 ON T-statB 64.2 #4 59.3 E#6 61.1 OFF 65.9 69.8 71.0 ON SnapdiskA 64.5 E#7 60.7

OFF 75.7 69.9 ON SnapdiskB 66.6 E#2 62.1

OFF 77.2 70.3

Table 3 - Observed Change Points by Sensor

- 11 -

Figure 5 – New (not the 2008 replacement model) and Older Sensors The C7650 sensors output a current signal in milliamps (mA) to the controller. This is an advantage in control applications since resistance in a long wiring run has less effect on current based sensor than a resistance based one. The internal components of the sensor are necessary to generate the required current signal. It was suggested that there may be a field measurement of resistance that installers could make to verify sensor accuracy. However, measurements found that the sensors exhibit no measurable resistance. That is, the internal electronic components do not pass current without the excitation voltage. Recognizing that the built-in hysteresis (deadband) limits operation, testing focused on finding and testing a work-around solution. The research team investigated the use of a simple thermostat (close-on-fall thermostat) to substitute for the outdoor temperature sensor. Replacing the usual sensor with an on/off closure has the effect of providing a satisfying temperature input that overrides any control constraints. The closure switch is a possible workaround for the imprecision of the controller and sensors. Essentially, it bypasses the A, B, C, D settings and provides an on/off control instead. We tested two snapdisks (cost ~ $25) and found them to be highly repeatable and close to specifications. However, these are relatively expensive, and they still show a significant 10 degrees of hysteresis deadband. Two low-cost “contractor’s ” (cost <$10) were tested and found to be equally accurate and repeatable. These thermostats are connected in place of the sensor and then bypass the changeover logic. Figure 5 shows the temperature control points for these options as well. Either the snapdisk or the thermostat provides a solution to the sensor temperature accuracy problem. But the preferred choice is the contractor’s thermostat because it has a narrow

- 12 - deadband and it is relatively inexpensive. It permits economizing when temperatures are 63ºF and below and continues until temperatures rise to 65ºF – the narrow deadband of this thermostat is preferred because it will increase the use of economizing. This thermostat is also available in other temperature ranges. Figure 6 shows the snap disc on the left and contractors thermostat, right, that were tested.

Figure 6. Snapdisk and Contactor's Thermostat

It was suggested by the manufacturer that enthalpy sensors are more accurate than the dry-bulb sensors tested. We briefly checked an economizer using an enthalpy sensor with a single changeover strategy (i.e. with the reference resistor in place instead of an enthalpy sensor in the return air). Air in the environmental chamber was quite dry and it was necessary to apply control setting D in order to have any control response at all from the enthalpy sensor. As shown in Figure 7, this particular sensor demonstrated a better response -- with operation for outdoor air Temperature at a range of 67 to 77ºF. This suggests the enthalpy sensor tested may have better accuracy than the dry-bulb sensors tested. However, the same deadband hysteresis still occurs with the enthalpy sensors. Also it is known that this sensor is responsive to humidity as well as temperature, and we are reluctant to extrapolate this performance to field conditions without a more thorough test of response to a wider variety of temperature/humidity conditions. Ongoing, limited testing of the C7400 enthalpy sensor is continuing until there is sufficient test point data to assess and report on.

- 13 - Enthaply System, Setting D (dry air)

90 85 80 75 70 LED On 65 LED OFF 60 OAT, degF OAT, 55 50 45 40

Figure 7 - Operation with Enthalpy Sensor

Differential Control Strategy A dual differential control was also tested. Under this strategy, the controller is set up to compare outdoor air temperature (OAT) to the return air temperature (RAT). This strategy is expected to provide for more economizer operation when the indoor temperature is warmer than the temperature implied by the reference resistor. This strategy requires that the controller be set to the D setting. A test of the differential control requires that the two control parameters, outside air temperature, and return air temperature, be varied in an orderly way to test the control system under its full range of conditions. For this test, we cycled the outdoor temperature repeatedly while maintaining the return air temperature at a specific point. The test was then repeated with a different temperature set for the return air sensor. Results are shown in Figure 8.

Implied Differential Controller Temperature Points 100 90 80

70 7650 Test 60 Result DegF 50 40 30 20 65 72 75 79

Figure 8 - Differential Control Results In general, one observes that the initiation temperature or “turn-on” point increases when return air is warmer. This is consistent with allowing economizing to continue longer since the building

- 14 - can benefit from cooling even at higher outdoor temperatures. However, the high limit of “turn- off” temperature does not appear to be affected. Test results in Figure 8 are somewhat variable due to noise in the experimental measurements. The results of these tests are simplified in Figure 9 showing generalized economizer “turn-on” and “turn-off” temperatures as a function of return air temperature.

Generalized Differential Operation

80

70 On

degF Off 60

50 Outdoor Temperature,Outdoor 65 70 75 80 Return Temperature, degF

Figure 9 - Generalized Differential Operation Benefits from differential control are likely to be modest. First, because the decrease in the “hysteresis” deadband is modest. Second, because the amount of economizer cooling from outdoor air will be small when outdoor temperature is close to indoor temperature.

Note that the “single changeover” operation described earlier is a special case of the differential control. With single changeover, the reference resistor results in a mA signal that would be the equivalent of the RAT sensor reading a high indoor temperature. Thus, the constraints related to RAT are “locked in.”

Progress with Honeywell In 2006, prior to the start of the project’s research phase, NBI staff had communicated the potential deadband problem that researchers in the Northwest had identified earlier to Honeywell’s product manager for the economizer controller and sensor of interest. In response, the product manager noted that the C7650 does indeed act as described and was not recommended for use for dry bulb applications. It was suggested that the utility service programs could simply replace the C7650 with the C7400 enthalpy sensor. This recommendation to substitute enthalpy sensors was rejected by the research team for two reasons: 1) a sensor based on humidity measurement is not compatible with the generally lower humidity levels in the Northwest, and 2) there is anecdotal evidence indicating that enthalpy sensors are not particularly accurate and may suffer from drift and/or calibration problems. A study of humidity sensors conducted by the Iowa Energy Center indicated widespread low accuracy in the sensors currently available in the market. Honeywell staff noted that new automated calibration techniques will be instituted for enthalpy sensor production that will result in higher accuracy sensors.

- 15 - Naturally, there was interest from the research team as to how this sensor came to be so widely used if the manufacturer now does not recommend its use. As was learned, Honeywell had designed the controller to be paired with an enthalpy sensor. In responding to its customers, the HVAC manufacturers, to provide a lower cost sensor solution, the enthalpy sensor was replaced with the C7650 sensor. The unfortunate result has been a limitation on the availability of economizer cooling in the Pacific Northwest and elsewhere in the country under temperature conditions where nighttime summer temperatures are elevated and the deadband limits the changeover point to activate the economizer damper. There is no estimate possible of the kWh savings lost from the use of this sensor with the W7459 controller and potentially other controllers across tens of thousands of rooftop units. As a result of the developing relationship and ongoing communications with the Honeywell, the research team was asked to provide recommendations to Honeywell on the parameters of a more effective temperature sensor and economizer controller. Some of the recommendations referenced the features defined in the California Energy Commission’s Public Interest Energy Research project for the Advanced Rooftop Unit (ARTU). One of the ARTU features was a controller sensor with a 2°F deadband. The recommendations of the research team provided support to the Honeywell product manager internally to accelerate the development of a new dry-bulb sensor and updated economizer controller. A new controller design will include DCV input capability, a startup check test sequence for the installer and other features that have not been disclosed. In late May 2007, research team members including representatives from the Bonneville Power Administration, Ecotope, New Buildings Institute, Northwest Energy Efficiency Alliance Northwest Power and Conservation Council, Portland Energy Conservation, Inc., and Stellar Processes, met with the product manager and engineering staff in Portland, OR to discuss the design and features of the new sensor. The sensor is field retrofittable having the same form factor of the C7650 and is connected by the existing wiring leads. The new sensor that was presented had six optional temperature ranges, from 48°F to 78°F. The lowest temperature level addresses market needs for providing adequate cooling for data centers/rooms. The settings are activated by dipswitches. This setup provides the HVAC installer with a positive signal that they have set the unit’s changeover range where they meant to. The sensor has onboard logic and will actually control the controller. The A-B-C-D setting ‘pot’ in the W7459 will be inoperative. Team members recommended 63°F for the factory default setting. Honeywell will be sending beta samples of the sensor for the research team to bench and field test. There was also a discussion of the development and potential large-scale field deployment of a retrofit package in the Northwest. Detailed discussions will take place once commercial availability and pricing is known. The research team will stay fully in touch with the Northeast project partners on this developing activity. Honeywell expects to obsolete the C7650 sensor as the means of removing it from market availability and expects a commercial launch of the new sensor in October 2008. No information has been provided yet on sensor pricing. Significantly, the utilities are now being viewed by this Honeywell product manager, as an important customer group that has specific product functionality needs, in addition to the traditional Honeywell customer base consisting primarily of the HVAC manufacturers, whose product value needs are not necessarily consistent with utility and ratepayer needs. This is a significant opening for utilities and energy efficiency organizations to be involved with

- 16 - fundamental energy efficiency-related product development and design. This relationship with Honeywell needs to be actively maintained and supported further as appropriate. There are other energy performance and hardware-related opportunities that must be explored with the HVAC manufactures directly. These will be further elaborated to the utility partners involved in this project.

- 17 -

Appendix A– Description of Test Facility The test apparatus was required to meet the following specifications: • Three independent temperature controlled test chambers. o Dry bulb temperature controllable in the range 40-80 ºF. • Equipment test bench o Log on/off status of at least 8 digital variables. o Log 8 analog sensor outputs, 0-5 V, and 4-20 mA, o Log economizer actuator output signal. • Communication system integration sufficient to store and archive test results both analog data and digital data as appropriate. o Log test conditions for dry bulb temperature and relative humidity The chambers consist of three insulated boxed installed in a residential freezer as shown in Figure 10.

Figure 10 - Environmental Chambers Each box contains a small air circulation to maintain a uniform temperature. A computer control system senses the temperature in each box and adds (by turning on a small light bulb) as needed to maintain the specified temperature regime, as shown in Figure 10. Each box can be programmed for a specified temperature regime, such as a specified change rate and temperature range. For example, Figure 12 shows a program that varies temperature from about 44 to 72 ºF and back at a rate of about 1 degree per minute. This is a typical program to represent the “outdoor” temperature range or OAT. While there is some fluctuation in the controller temperature, the system can maintains an average temperature within about 0.1 ºF.

- 18 -

Figure 11 - Inside of Chamber The test protocol alluded to in this report consisted of following a sensor/controller system through a range of OAT temperature changes similar to that shown in Figure 12. We then recorded the temperature points at which the controller operation changed to either economize or not economize. These control points represent the “turn on” or “turn off” points described in the report such as in Figure 1 and Figure 8.

Temperature in Chamber

75 70 65 60 55 DegF 50 45 40 0 0 00 00 00 6: 1: 1: 1: 5 :1 :1 :1 2: 12:26:0012:41:001 13 13:26:0013:41:0013:56:0014 14:26:0014:41:0014:56:0015 15:26:00

Figure 12 - Example of Environmental Chamber Temperatures

- 19 - With multiple chambers, it is possible to investigate alternative strategies. For example, we test the differential strategy by programming one chamber to represent the “return air” temperature while another chamber represented the “outdoor” one. In this case, the test protocol specifies that the chamber that represents OAT to follow a similar program to that shown in as described earlier. At the same time, another chamber that represents RAT operates through a temperature range that would vary between something like 65 to 75 ºF. We then record the temperature points at which the controller operation changed to either economize or not economize. This protocol then allows documentation of the conditions when economizer operations start and stop as shown in Figure 1. We built the apparatus with capability to measure other parameters, such as the mA sensor output. That is because, at the onset, we were not sure what measured parameters might turn out to be important. While we recorded mA outputs, it turned out that the controller operations could be easily described using temperature measurements. The equipment is also capable of measuring relative humidity although current work has focused only on dry-bulb controls. Future work will investigate enthalpy controls. Figure 13 shows a schematic of the test apparatus. The three environmental chambers are indicated by different colors.

NBI ECONOMIZER TESTING SET-UP TEST CHAMBERS

USB DS Adapter Hub To U’s 25W

MCC USB – 1208FS AC Relay To Bulbs U - DS 18B20 Sensor x 4 Laptop w/Energy - AD 590 Sensor Answer A/D *4 Port A Digital 1/0 Outputs *16 Honeywell W7459 Analog Port B Controller 24V AC Inputs Outputs

24vac To W 7459 To 10V Input 1 U 0 1 2 3 Multiplexer DC 1 4 x 8 input Inputs Honeywell 24v Digital 0A – 0H 1A – 1N 2A – 2H 3A – 3H 7650 AC DC Volt DC-MA ‘Digital’ AD590 sensor Relay Input 2 Inputs Inputs Inputs Sensors To MA Input LED To ’s

50

Photo To Diode 10 V 24 V 20 V To 3 AC MA Input DC AC DC Relays

On U W7415 120V Plug Strip Actuator Off Arm 1 120 V U Freezer Ambient

Figure 13 - Test Apparatus Schematic Diagram

- 20 - Appendix B - Overall Economizer Control Test Description and Discussion

Purpose - This test is intended to establish the outside air temperatures associated with economizer open and close points. This test is intended to be used with dry bulb temperature sensors. In general, the economizer control may have several components (temperature sensors, controller, actuator) that interact in the overall control function. Measurements on the individual components, such as mA vs. temperature for the temperature sensors, lead to inconclusive results due to lack of knowledge of the electronic details of the control approach. Regardless of the electronic specifics of the controls, (or any sub component), all economizer controls ultimately do the same thing: they open and close dampers at certain outside air, return air, and supply air temperatures. This test seeks to quantify the performance of the economizer control system as a whole.

A principal complexity of existing economizer controls is that the control points may depend on the direction of change of the outside air temperature, increasing or decreasing. The control also differs depending on whether or not the outside temperature has reached a sufficiently low temperature trigger point. This dependency on a low temperature trigger point is referred to as control hysteresis. The control test must be capable of identifying the circumstances leading to the control points.

General Method - In general, the testing method seeks to vary the principal control parameters in an orderly way, sufficient to exercise and observe the control system over the full range of control conditions it can be expected to encounter. Here this is referred to as traversing the control domain.

Single outdoor dry bulb sensor control - The simplest case involves a single dry bulb outdoor temperature control. In this case, traversing the control domain consists only of varying the outdoor temperature in both directions between upper and lower limits. This test uses a test setup with a temperature controlled test chamber. The outside air temperature is simulated in the test chamber, enclosing the outside air temperature sensor. This simulated outside air temperature will be cycled from a high temperature, higher than the highest control temperature for the subject control (usually 80-90ºF), to a low temperature, lower than the lowest control temperature (usually about 45ºF). As the outside air temperature is cycled, the status of the control output is recorded, open dampers (LED on), or close dampers (LED off).

- 21 - Thermal Delay in Sensors

66 Environment 65 Temperature Program 64

63 Sensor Response Temperature, degF 62 62.80 3 9 5 1 7 3 9 5 5 1 2 2 17: 17: 18:0 18:1 18: 18: 18:

Figure 14 - Thermal Delay in Sensor Response We found that the sensors exhibit a large time response in responding to temperature changes. Figure 14 exhibits an example. The test is programmed for step temperature change as shown by the black line. The actual temperature in the environment boxes follows closely as shown by the green data points. However, the response from the sensor, shown by the red line, exhibits a long thermal decay response in adjusting to the temperature change. (The sensor output is actually in mA but has been calibrated here to match the temperature units shown.) In this example, it takes about 12 minutes for the sensor to fully equilibrate to a 1ºF temperature change. Given this long delay, we elected to operate the tests with a full hour to allow for thermal equilibrium. Our initial tests failed to recognize the importance of allowing for full thermal equilibrium. Note that a long response is not necessarily an error in controls – it avoids control “chatter” if there is rapid temperature cycling around the control point.

Economizer Response Test - differential control

75

r 70

65

60

55 perature, deg F deg perature, 50 Tem 45 Outside Air or Return Ai

40 0 60 120 180 240 300 360 420 480 540 600 660 720 780 840 Increasing Time, minutes

ON OFF

Figure 15 - Economizer Response Test

- 22 - The real problem in testing a control system is that there is often a very wide range of control possibilities and the purpose of the controls test is to examine a broad enough range of control possibilities that the full operation of the control is well understood. The challenge is to find simple ways of presenting the multiple test results.

For the simple case of a single outdoor dry bulb temperature control, the test results are worked into a graphical format such as Figure 15. The advantage of Figure 15 is that it maps the results of an automatic test sequence consisting of hundreds of individual tests conducted in an orderly sequence and range of conditions. For example, this figure shows that the dampers open whenever the temperature is below about 56ºF. It also shows that the dampers are open at outside air temperatures of 56 to 72ºF, but only if the temperature has been increasing from a temperature below 55 ºF. It also shows that the dampers close at about 72ºF, and that the dampers will remain closed in the range of 56 to 72ºF until the temperature again reaches 55ºF or below. For the simple single sensor test, there need be only a few temperature cycles, not the many cycles shown in Figure 12.

The operationally useful outputs from Figure 15 are the low ON control point (about 56ºF), the high OFF control point (about 72ºF), and the recognition of the hysteresis pattern such that a temperature of 55ºF or lower must be encountered in order for the dampers to open.

Figure 15 shows a simple single change point situation. Ideally, the outside air temperature should have been cycled to a higher temperature to show operation of the control at temperatures above the upper control point. In early tests, to limit duration of the test, the test control limited the upper outside air test points to the high control point.

Enthalpy Sensor Control – This is a potentially complex control system to test because it involves varying the humidity as well as the dry bulb temperature. Traversing the control domain for this situation will involve traversing the psychrometric chart in a manner that is experimentally achievable to establish a performance surface. The resulting data will then need to be interpolated and reassembled to express the control system performance compared with the parameters of interest.

- 23 -