Installation Manual ROOF SIPs March 2021
ROOF SIPs Installation Manual
Table of Contents Topics General Requirements ...... 3 Materials ...... 3 Electrical Wiring ...... 3 Interior Finish ...... 4 Exterior Cladding ...... 4 Materials Estimation ...... 5
Details Air Barrier Details for Air Barrier Sealants ...... AB-1 Air Barrier Details for Sealing SIP Connections ...... AB-2 Vapour Barrier Details for Vapour Sealing SIP Connections . . . VB-1 Typical Roof Ridge ...... R-1 Roof Ridge Details for 12/12 Pitch Roof ...... R-2 Beam Pocket Detail ...... R-3 SIP Peak Connection (Alternative) ...... R-4 Roof Valley & Intermediate Roof Support ...... R-5 Eave Detail and Roof Support at Exterior Wall ...... R-6 Typical Sloped Roof Assembly ...... R-7 Sloped Roof Assembly with Ridge Beam ...... R-8 Flat Roof Assembly ...... R-9 Skylight Opening & Assembly ...... R-10 Typical Roof Connection Sections (Roof to Wall) ...... R-11 Roofi ng Applied to SIPs ...... R-12 Flat Roofi ng Applied to SIPs ...... R-13 LED Pot Light Installation in Ceiling SIPs ...... R-14 Ceiling Fan Attachment ...... R-15 Electrical Wire Fastened to Roof SIP ...... R-16 Pre-Fabricated Metal Chimney Installation ...... R-17 Screw Fastener Detail for Securing Load to Ceiling Panel . . . . R-18 Roof Overhang Eave Details (Timberframe) ...... R-TF-1 Roof Overhang & Rake (Timberframe) ...... R-TF-2
Roof SIP - Installation Manual 2 March 2021
ROOF SIPs Installation Manual
1. General Requirements 1.1 Scope The basic design and construction requirements for the Thermapan Structural Insulated Panel (SIP) roof system is set forth in this specifi cation. Criteria for materials, environmental control, design loads, and structural design are included. Where requirements are based on internationally recognized standards and specifi cations, these standards and specifi cations are referenced without elaboration.
Installers shall reference engineering design package for fastening arrangements.
2. Materials 2.1 The Thermapan Roof SIP is composed of an expanded polystyrene (EPS) foam core laminated between two layers of oriented strand board (OSB) with a structural adhesive.
2.2 Framing Lumber shall be DOC PS 20 or NLGA No.2 or better.
2.3 Wire nails, ring nails, spikes and staples shall conform to CSA B111 or ANSI/ASME B11.1.
2.4 Wood screws shall conform to ANSI/ASME B18.6.1..
2.5 SIP screws shall conform to ICC-AC233.
2.6 Caulking Compounds shall conform to CAN/CGSB 19.13 or ASTM C 920.
2.7 Polyethylene Sheeting shall conform to CAN/CGSB-37.2, CAN/ CGSB-37.16, or ASTM D 4397.
2.8 Low expansion foam seal shall conform to AAMA 812-04.
2.9 Structural adhesive shall conform to CAN/CGSB 71GP26, APA AFG-01 or ASTM D3498.
3. Electrical Wiring 3.1 An optional furring for electrical passage should be fastened to the underside of the roof SIP between the vapour barrier and the interior fi nish. See details R-1, R-4 and R-5.
Roof SIP - Installation Manual 3 March 2021
4. Interior Finish 4.1 The interior of the roof SIP can be fi nished with any of the common required building code materials. It is recommended that the SIP joints and connections be sealed as per Details AB-1, AB-2 and VB-1.
5. Exterior Roofi ng 5.1 Consult your local building code and refer to details R-11 and R-12 for roofi ng applied to SIPs.
Roof SIP - Installation Manual 4 March 2021
MATERIALS ESTIMATING Roof (Vaulted Ceiling) Estimation Only
Lumber Requirements:
• Perimeter of roof or fascia length
Caulking and Sealant Requirements:
• Every 1200 sqft (111 m2) of SIP equals 1 case of Expandable Foam
• Every 2000 sqft (185 m2) of SIP requires 1 case of Sealant
Fasteners:
• Recommend 2” (50mm) Ring nail or 2” (50mm) screws for connection to panel
• ~ 1.25 times the square footage of SIPs... nailing of spline
• SIP screws use 40% of Roof square footage
Roof SIP - Installation Manual 5 AIR BARRIER RECOMMENDED DETAILS FOR AIR BARRIER SEALANTS
All sealants, FOAM (A) or CAULKING (B), should be applied onto the SIP in a continuous rectangular pattern along the outer most edge of the area to be sealed.
(A) A low expansion EXPANDABLE FOAM SEALANT should conform to the AAMA 812-04 standard. Apply a 1/2 inch or a 12.5 mm diameter of a continuous bead of expandable foam sealant onto the SIP:
Expandable Foam Sealant Bead
EPS
(B) A CAULKING SEALANT should conform to ASTM C920-02 and/or CAN/CGSB 19.13-M. Apply a 3/8 inch or a 10 mm diameter continuous bead of caulking onto the lumber spline: CAULKING (CONTINUOUS BEAD)
Caulking Bead
LUMBER STUD OR SPLINE
TITLE PROJECT AIR BARRIER DETAILS FOR AIR BARRIER SEALANTS
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) NOVEMBER 2010 1 AB-1 AIR BARRIER RECOMMENDED DETAILS FOR SEALING SIP CONNECTIONS
(1) Foam to Foam: Use a low expansion foam sealant.
EXPANDABLE FOAM SEALANT
SEE VAPOUR BARRIER DETAIL (VB-1) SIP SPLINE JOINT
(2) Foam to Wood: Use a low expansion foam sealant.
PLATES SECTION LUMBER SPLINES
CAP TOP PLATE EXPANDABLE FOAM SEALANT
EXPANDABLE CAULKING FOAM SEALANT (SEE WOOD LUMBER SPLINE, TO WOOD) END STUD OR JOIST BOTTOM PLATE
(3) Wood to Wood: Use caulking and a low expansion foam sealant.
EXPANDABLE CORNER DETAIL PLAN LUMBER SPLINE FOAM SEALANT
SEE VAPOUR BARRIER EXPANDABLE DETAIL (VB-1) FOAM SEALANT
EXPANDABLE CAULKING FOAM (SEE AB-1) SEALANT CAULKING (SEE AB-1)
TITLE PROJECT AIR BARRIER DETAILS FOR SEALING SIP CONNECTIONS
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) MAY 2020 1 AB-2 VAPOUR BARRIER RECOMMENDED DETAILS FOR VAPOUR SEALING SIP CONNECTIONS
The function of a vapour barrier is to control the entry of water vapour into the building assembly. Vapour barriers should not be confused with an air barrier.
All SIP seams and connections must be VAPOUR SEALED from the INTERIOR. These are recommended vapour barrier methods:
OSB
EXTERIOR
INTERIOR
SEE AIR BARRIER 6 MIL POLY STRIP INTERIOR FINISH FASTENED SEE AIR BARRIER DETAIL (AB-2) CONTINUOUS 6 MIL POLY CAULKED TO OSB DIRECTLY TO SIP DETAIL (AB-2) OVER ENTIRE SIP ASSEMBLY
CONTINUOUS 6 MIL POLY 6 MIL POLY STRIPS & CAULKING RECOMMENDED
EXTERIOR
INTERIOR
SEE AIR BARRIER CAULKING SEE AIR BARRIER DETAIL (AB-2) OSB DETAIL (AB-2) SIP TAPE
SIP TAPE CAULKING
TITLE PROJECT VAPOUR BARRIER DETAILS FOR VAPOUR SEALING SIP CONNECTIONS
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) MAY 2020 2 VB-1 EXPANDABLE FOAM SEALANT SIP SCREW ( SEE FASTENING TABLE)
CHAMFER BLOCKING VAPOUR SEALED (WEDGE) AS PER VB-1
THERMAPAN ROOF PANEL
OPTIONAL FURRING FOR ELECTRICAL PASSAGE
INTERIOR FINISH
STRUCTURAL SUPPORT AS REQUIRED RIDGE SECTION (WITH RIDGE BEAM)
ADJUST FRAMING EXPANDABLE FOAM SEALANT SIP SCREW MEMBER (SEE FASTENING TABLE) AS REQUIRED
THERMAPAN ROOF PANEL
VAPOUR SEALED AS PER VB-1
CAULK TO PANEL
INTERIOR FINISH
OPTIONAL FURRING FOR ELECTRICAL PASSAGE “RIDGE” SECTION (NO RIDGE BEAM)
NOTE: REFERENCE ROOF PANEL FASTENING TABLE ON CONNECTION DESIGN (CD) SHEET OF ENGINEERED SHOP DRAWINGS
TITLE PROJECT
ROOF RIDGE DETAILS
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) FEBRUARY 2012 5 R-1 SIP SCREWS
THERMAPAN ROOF PANEL
CAULK TO PANEL 6 MIL POLY VAPOUR BARRIER
RIDGE SECTION (TYPICAL RIDGE BEAM)
SIP SCREWS THERMAPAN ROOF PANEL
CAULK TO PANEL
6 MIL POLY RAFTER & BEAM BY OTHERS FOR RAFTER & BEAMS (DESIGNED BY OTHERS)
NOTE: REFER TO AIR BARRIER (AB-2) AND VAPOUR BARRIER (VB-1) DETAILS FOR SEALING SIP CONNECTIONS NOTE: REFERENCE ROOF PANEL FASTENING TABLE ON CONNECTION DESIGN (CD) SHEET OF ENGINEERED SHOP DRAWINGS
TITLE PROJECT SECTIONS - ROOF RIDGE DETAILS FOR 12/12 PITCH ROOF
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) FEBRUARY 2012 R-2 R-2 CHAMFER BLOCKING EXPANDABLE FOAM SEALANT
SIP SCREW SIP SCREW
THERMAPAN ROOF PANEL
VAPOUR SEALED AS PER VB-1
CAULK TO PANEL
TOP PLATES
RIDGE BEAM AS REQUIRED
POST (BUILT-UP OR SOLID)
PANEL JOINT
WALL P ANEL
RIDGE BEAM & POST POCKET
NOTE: REFERENCE ROOF PANEL FASTENING TABLE ON CONNECTION DESIGN (CD) SHEET OF ENGINEERED SHOP DRAWINGS
TITLE PROJECT
BEAM POCKET DETAIL
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) DECEMBER 2010 2 R-3 WEDGE PEAK WITH SIP FILLERS SECURED TO BLOCKING
CONTINUOUS SELF-ADHERING FOAM SEAL WATER RESISTIVE AIR FOAM SEAL BARRIER MEMBRANE (PEEL AND STICK)
SIP SCREW SIP SCREW
THERMAPAN ROOF PANEL
EXPOSED SIP CEILING PANEL
STRUCTURAL SUPPORT AS REQUIRED
TITLE PROJECT SIP PEAK CONNECTION (ALTERNATIVE)
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) FEBRUARY 2019 R-4 EXPANDABLE FOAM SEALANT
SIP SCREW
THERMAPAN ROOF PANEL
CAULK TO PANEL
VAPOUR SEALED OPTIONAL FURRING AS PER VB-1 FOR ELECTRICAL PASSAGE CHAMFER BLOCKING INTERIOR FINISH
STRUCTURAL SUPPORT ROOF VALLEY AS REQUIRED
SIP SCREWS SIP SCREW
THERMAPAN THERMAPAN ROOF PANEL ROOF PANEL
CHAMFER BLOCKING
OPTIONAL FURRING FOR ELECTRICAL PASSAGE
INTERIOR INTERIOR FINISH FINISH WEDGE OR BEAM CHAMFERED STRUCTURAL PANEL JOINT AT TOP PANEL CONTINUES SUPPORT AS REQUIRED AT ROOF SUPPORT OVER ROOF SUPPORT
NOTE: REFERENCE ROOF PANEL FASTENING TABLE ON CONNECTION DESIGN (CD) SHEET OF ENGINEERED SHOP DRAWINGS
TITLE PROJECT
ROOF VALLEY & INTERMEDIATE ROOF SUPPORT
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) JULY 2018 4 R-5 ROOF SUPPORT WITH OVERHANG
CHAMFER BLOCKING (INSERT AFTER ROOF PANELS ARE IN PLACE) THERMAPAN ROOF PANEL
SIP SCREW SEE FASTENING TABLE CAULK TO PANEL
FASCIA VAPOUR SEALED AS PER EXPANDABLE VB-1 FOAM SEALANT OPTIONAL FURRING FOR INTERIOR ELECTRICAL FINISH PASSAGE
CAULK
EXPANDABLE FOAM SEALANT
FASCIA CAP & PLATE BLOCKING ROOF SUPPORT
SOFFIT FRAMING WITHOUT OVERHANG
OVERHANG (SEE TABLE R-T-3)
THERMAPAN WALL PANEL
NOTE: REFERENCE ROOF PANEL FASTENING TABLE ON CONNECTION DESIGN (CD) SHEET OF ENGINEERED SHOP DRAWINGS
TITLE PROJECT EAVE DETAIL & ROOF SUPPORT AT EXTERIOR WALL
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) MARCH 2020 7 R-6 SECTION A-A
SEE FASTENING TABLE AND DETAIL BELOW
EPS CORE OSB SKIN
VAPOUR SEALED AS PER VB-1
SEE SECTION “B” BELOW A A
SPLINE
BLIND FASCIA (SITE) ROOF ASSEMBLY SIP FASCIA WEDGE FOR PLUMB CUT (SITE) SECTION B SPLINE
NOTE: REFER TO AIR BARRIER (AB-2) AND VAPOUR BARRIER (VB-1) DETAILS FOR SEALING SIP CONNECTIONS. NOTE: REFERENCE ROOF PANEL FASTENING TABLE ON CONNECTION DESIGN (CD) SHEET OF ENGINEERED SHOP DRAWINGS
TITLE PROJECT TYPICAL SLOPED ROOF ASSEMBLY
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) FEBRUARY 2012 6 R-7 SEE DETAIL R-1 OR R-2
A A
SEE DETAIL R-4 OR R-5
BLIND FASCIA (SITE)
FASCIA WEDGE FOR PLUMB CUT (SITE)
ROOF ASSEMBLY SECTION A-A
SIP SPLINE SIP EXPANDABLE SPLINE FOAM LUMBER SPLINE SEALANT
OR
CAULKING (SEE AB-1)
NOTE: REFER TO AIR BARRIER (AB-2) AND VAPOUR BARRIER (VB-1) DETAILS FOR SEALING SIP CONNECTIONS. NOTE: REFERENCE ROOF PANEL FASTENING TABLE ON CONNECTION DESIGN (CD) SHEET OF ENGINEERED SHOP DRAWINGS
TITLE PROJECT SLOPED ROOF ASSEMBLY WITH RIDGE BEAM
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) FEBRUARY 2012 2 R-8 A
A
INSTALL SEE SECTION “B” FASCIA BOARD BELOW ON SITE SPLINE
SECTION SECTION B A-A ISOMETRIC ROOF ASSEMBLY GENERIC DETAIL FOR FLAT ROOF SEE FASTENING EPS 3 “ CORE TABLE FOAM CORE FOAM SPLINE SEAL
CAULK OSB SKIN VAPOUR SEALED AS THERMAPAN PER VB-1 ROOF PANEL VAPOUR SEALED AS PER VB-1
NOTE: REFER TO AIR BARRIER (AB-2) AND VAPOUR BARRIER (VB-1) DETAILS FOR SEALING SIP CONNECTIONS. NOTE: REFERENCE ROOF PANEL FASTENING TABLE ON CONNECTION DESIGN (CD) SHEET OF ENGINEERED SHOP DRAWINGS
TITLE PROJECT FLAT ROOF ASSEMBLY
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) FEBRUARY 2012 2 R-9 ROOF JOISTS ATTACHED BY HANGERS OR SIDE NAILING
OPTIONAL
JOISTS
OPTIONAL
1.5” OR 3” RECESS 1.5” RECESS TYPICAL U.N.O.
SEE SKYLIGHT MANUFACTURER’S DETAIL
HANGER OR NAILS
JOIST DOUBLE SPLINE
TITLE PROJECT SKYLIGHT OPENING & ASSEMBLY
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) FEBRUARY 2012 3 R-10 FLASHING REMOVE FOAM FROM ROOF PANEL AS TO INSTALL SECURE END PLATE NAILER AND LEDGER BOARD TO MATCH WALL BOARD.
LEDGER SECURED TO STUDS
OPTION 1
FLASHING EMBEDDED SECURE ROOF PANEL TO MIN. 1" IN MASONRY NEW STUD WALL WITH SIP SCREWS
WATER RESISTANT MEMBRANE
EXISTING WALL NEW STUD WALL SECURED TO EXISTING STRUCTURAL WALL
OPTION 2 NEW ROOF TO EXISTING WALL
TITLE PROJECT TYPICAL ROOF CONNECTION SECTIONS (ROOF TO WALL)
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) FEBRUARY 2012 3 R-11 THERMAPAN ROOF PANELS (TWO SHOWN) ASPHALT SHINGLES
NON-ADHERING BREATHABLE ROOFING UNDERLAYMENT INSTALLED AS PER MANUFACTURER’S DRIP EDGE INSTRUCTIONS
FASCIA COVER
2X_ FASCIA BOARD
DRIP EDGE STARTER SHINGLE INSTALLED AS PER MANUFACTURER’S FASCIA WEDGE INSTRUCTIONS FASCIA FOR PLUMB CUT BOARD 2X_ BLIND FASCIA FASCIA COVER
THERMAPAN METAL ROOFING OR ROOF PANELS CEDAR SHAKES (TWO SHOWN)
NON-ADHERING BREATHABLE ROOFING UNDERLAYMENT INSTALLED AS PER MANUFACTURER’S DRIP EDGE INSTRUCTIONS
FASCIA COVER FURRING INSTALLED AS PER MANUFACTURER’S 2X_ FASCIA BOARD INSTRUCTIONS
DRIP METAL ROOFING OR EDGE SHAKES INSTALLED AS PER MANUFACTURER’S FASCIA WEDGE INSTRUCTIONS FASCIA FOR PLUMB CUT BOARD 2X_ BLIND FASCIA FASCIA COVER
NOTE: VENTILATION OF SIP ROOF NOT REQUIRED.
TITLE PROJECT ROOFING APPLIED TO SLOPED SIPS
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) AUGUST 2017 2 R-12 NON-ADHERED MEMBRANE (EPDM, PVC, TPO, ETC.)
FASTENERS INTO OSB
PROTECTIVE SHEATHING OR MEMBRANE AS REQUIRED
OSB
EPS
ADHERED ROOFING MEMBRANE
TORCHED ON OR GLUED ON ROOFING MEMBRANE
FASTEN PROTECTIVE SHEATHING LAYER (OSB, PLYWOOD) WITH GLUE, NAILS OR SCREWS
OSB
EPS
NOTES: • SIP SURFACE TO BE DRY. • INSTALL MEMBRANE ACCORDING TO MEMBRANE MANUFACTURER’S DETAILS AND CONFORM TO REQUIREMENTS OF LOCAL BUILDING CODE.
TITLE PROJECT FLAT ROOFING APPLIED TO SIPS
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) NOVEMBER 2011 R-13 DRIVER BOX*
WIRING STRAPPING
LED RECESS CEILING FIXTURE* INTERIOR FINISH
FIXTURE SPECIFICATIONS *FIXTURE TO HAVE AMBIENT OPERATING TEMPERATURE +140F(+40C) MAXIMUM INSTALL AS PER MANUFACTURERS SPECIFICATIONS
TITLE PROJECT LED POT LIGHT INSTALLATION IN CEILING SIPS
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) JANUARY 2017 R-14 WIRING STRAPPING INTERIOR FASTENED FINISH TO OSB 2’ O/C
SHALLOW ELECTRICAL BOX MIN FOUR (4) #8 X 1-1/2” WOOD SCREWS RATED FOR SUPPORT OF WITH WASHERS INTO OSB CEILING FAN (OSB TO RECEIVE FULL SCREW THREAD)
TITLE PROJECT CEILING FAN ATTACHMENT
REFERENCE SCALE
N.T.S. www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) FEBRUARY 2018 R-15 METAL ROOFING OR CEDAR SHAKES
STRAPPING 16” O/C OR AS PER ROOFING SPECIFICATIONS
NON-ADHERING METAL ROOFING BREATHABLE ROOFING (OR SHAKES) INSTALLED UNDERLAYMENT AS PER MANUFACTURER’S INSTALLED AS PER INSTRUCTIONS MANUFACTURER’S INSTRUCTIONS
OSB
EPS
OSB ELECTRICAL WIRE FASTENED TO OSB BENEATH MEMBRANE
TITLE PROJECT ELECTRICAL WIRE FASTENED TO ROOF SIP
REFERENCE SCALE N.T.S.
www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) MARCH 2021 R-16 AIR GAP AS SPECIFIED BY CHIMNEY MANUFACTURER
WEATHER COLLAR AS PER CHIMNEY MANUFACTURER
CHIMNEY SUPPORT BOX AS PER CHIMNEY MANUFACTURER
THERMAPAN ROOF PANEL
INTERIOR WALL FINISH
TRIM COLLAR
2X__ BLOCKING AS PER PANEL THICKNESS AND OPENING SPECIFIED BY CHIMNEY MANUFACTURER
NOTE: ABOVE DETAILS ARE TYPICAL REQUIREMENTS TO INSTALL A PREFABRICATED METAL CHIMNEY IN A THERMAPAN STRUCTURAL INSULATED PANEL. THE CHIMNEY INSTALLATION MUST COMPLY WITH THE CHIMNEY MANUFACTURERS’S SPECIFICATION AND THE APPLICABLE BUILDING CODE.
TITLE PROJECT PRE-FABRICATED METAL CHIMNEY - ROOF INSTALLATION
REFERENCE SCALE
N.T.S.
www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) FEBRUARY 2019 R-17 TYPICAL SIP ROOF SECTION
ELECTRICAL BOX (OPTIONAL) THERMAPAN PANEL
THERMAPAN PANEL EPS THERMAPAN CEILING OSB SKIN
SEE DETAIL A
FIXTURE FINISH CAP
FIXTURE FASTENING PLATE LOAD
CEILING FINISH (DRYWALL OR WOOD PANELLING)
CEILING LOAD RESISTANCE CAN BE ACHIEVED WITH NUMBER 10 SHEET METAL SCREWS INSTALLED TO A SIP CEILING FINISH AS PANEL EPS LAYER DETAILED OR TO THE SIP SKIN DIRECTLY.
EACH SCREW CAN RESIST A PULL OUT OF PANEL OSB SKIN 90 POUNDS IN 7/16" OSB. CONTRACTOR TO CONFIRM LOAD TO BE SECURED AND NUMBER OF FASTENERS REQUIRED. MINIMUM 4 SCREWS CEILING FINISH PER FIXTURES. FULL THICKNESS OF OSB TO RECEIVE SCREW THREAD ON ANGLE AS DETAILED
DETAIL A
TITLE PROJECT SCREW FASTENER DETAIL FOR SECURING LOAD TO THERMAPAN CEILING PANEL
REFERENCE SCALE
N.T.S.
www.thermapan.com DATE REVISION DWG. No. 1-877-443-WALL (9255) FEBRUARY 2020 R-18 UNFINISHED EAVE DETAIL FOR LEVEL SOFFIT
ROOF PANEL
RAFTER 1/2” DRYWALL RECESS CAULK TO PANEL FOR INLAY VAPOUR SEALED AS PER VB-1 EXPANDABLE FOAM SEALANT 2” NAIL INTO TIMBERFRAME WALL PANEL POST
FINISHED EAVE DETAIL WITH LEVEL SOFFIT
ROOF PANEL
RAFTER TAIL AND INLAY INSTALLED ON GROUND - SCREWED FROM TOP AND BOTTOM
RAFTER TAILS RAFTER @ 16" O/C 1/2 " DRY WALL
CAULK TO PANEL VAPOUR SEALED FINISHED AS PER VB-1 FASCIA INSULATION SUGGESTED
KICKER POST
FINISHED SOFFIT
LEDGER
WALL PANEL
NOTE: REFER TO AIR BARRIER (AB-2) AND VAPOUR BARRIER (VB-1) DETAILS FOR SEALING SIP CONNECTIONS.
TITLE PROJECT ROOF OVERHANG EAVE DETAILS (TIMBERFRAME)
REFERENCE SCALE
8020 N.T.S. DATE REVISION DWG. No. www.thermapan.com 1-877-443-WALL (9255) FEBRUARY 2012 3 R-TF-1 HURRICANE STRAP
OSB "TIE"
EXPANDABLE CONVENTIONAL FOAM SEALANT LADDER ROOF PANEL
BEAM / RAFTER
VAPOUR SEALED AS PER VB-1
BUILT OUT OPTION POPULAR FOR ROOFS WALL PANEL WITH COMMON RAFTER SYSTEMS AND PANEL ORIENTED VERTICALLY
NOTE: SCREW AND GLUE LADDER TO WALL PANEL
FOAM HELD BACK FOR RAKE BLOCKING
2X_ INLAY RAKE BLOCKING
ROOF PANEL EXPANDABLE FOAM SEALANT RAFTER / BEAM
VAPOUR SEALED AS PER VB-1
WALL PANEL RUN-BY OPTION, POPULAR FOR ROOFS WITH PRINCIPAL RAFTERS AND PURLINS AND PANELS ORIENTED HORIZONTALLY
NOTE: REFER TO AIR BARRIER (AB-2) AND VAPOUR BARRIER (VB-1) DETAILS FOR SEALING SIP CONNECTIONS.
TITLE PROJECT ROOF OVERHANG & RAKE (TIMBERFRAME)
REFERENCE SCALE
8020 N.T.S. DATE REVISION DWG. No. www.thermapan.com 1-877-443-WALL (9255) MAY 2009 2 R-TF-2