energies
Article Energy Benefits of Heat Pipe Technology for Achieving 100% Renewable Heating and Cooling for Fifth-Generation, Low-Temperature District Heating Systems
Birol Kılkı¸s 1,2,*, Malik Ça˘glar 3 and Mert ¸Sengül 3
1 Mechanical Engineering Department, Ostim Technical University, Ankara 06374, Turkey 2 Polar Project Technology, Informatics, Architecture, Engineering, Ankara 06640, Turkey 3 Enover Energy, Ankara 06510, Turkey; [email protected] (M.Ç.); [email protected] (M.¸S.) * Correspondence: [email protected]
Abstract: This paper addresses the challenges the policymakers face concerning the EU decarboniza- tion and total electrification roadmaps towards the Paris Agreement set forth to solve the global warming problem within the framework of a 100% renewable heating and cooling target. A new holistic model was developed based on the Rational Exergy Management Model (REMM). This model optimally solves the energy and exergy conflicts between the benefits of using widely available, low-temperature, low-exergy waste and renewable energy sources, like solar energy, and the inability of existing heating equipment, which requires higher exergy to cope with such low temperatures. In recognition of the challenges of retrofitting existing buildings in the EU stock, most of which are more than fifty years old, this study has developed a multi-pronged solution set. The first prong Citation: Kılkı¸s,B.; Ça˘glar, M.; is the development of heating and cooling equipment with heat pipes that may be customized for ¸Sengül,M. Energy Benefits of Heat supply temperatures as low as 35 ◦C in heating and as high as 17 ◦C in cooling, by which equipment Pipe Technology for Achieving 100% oversizing is kept minimal, compared to standard equipment like conventional radiators or fan coils. Renewable Heating and Cooling for It is shown that circulating pump capacity requirements are also minimized, leading to an overall Fifth-Generation, Low-Temperature District Heating Systems. Energies reduction of CO2 emissions responsibility in terms of both direct, avoidable, and embodied terms. In 2021, 14, 5398. https://doi.org/ this respect, a new heat pipe radiator prototype is presented, performance analyses are given, and 10.3390/en14175398 the results are compared with a standard radiator. Comparative results show that such a new heat pipe radiator may be less than half of the weight of the conventional radiator, which needs to be Academic Editors: Hom oversized three times more to operate at 35 ◦C below the rated capacity. The application of heat pipes Bahadur Rijal and Manoj in renewable energy systems with the highest energy efficiency and exergy rationality establishes Kumar Singh the second prong of the paper. A next-generation solar photo-voltaic-thermal (PVT) panel design is aimed to maximize the solar exergy utilization and minimize the exergy destruction taking place Received: 14 May 2021 between the heating equipment. This solar panel design has an optimum power to heat ratio at low Accepted: 29 July 2021 temperatures, perfectly fitting the heat pipe radiator demand. This design eliminates the onboard Published: 30 August 2021 circulation pump, includes a phase-changing material (PCM) layer and thermoelectric generator (TEG) units for additional power generation, all sandwiched in a single panel. As a third prong, the Publisher’s Note: MDPI stays neutral paper introduces an optimum district sizing algorithm for minimum CO emissions responsibility with regard to jurisdictional claims in 2 published maps and institutional affil- for low-temperature heating systems by minimizing the exergy destructions. A solar prosumer house iations. example is given addressing the three prongs with a heat pipe radiator system, next-generation solar PVT panels on the roof, and heat piped on-site thermal energy storage (TES). Results showed
that total CO2 emissions responsibility is reduced by 96.8%. The results are discussed, aiming at recommendations, especially directed to policymakers, to satisfy the Paris Agreement.
Copyright: © 2021 by the authors. Licensee MDPI, Basel, Switzerland. Keywords: exergy rationality; exergy destructions; nearly-avoidable CO2 emissions responsibility; heat This article is an open access article pipe; heat pipe radiator; solar PVT; low-temperature district heating; 100% renewable heating and distributed under the terms and cooling; thermal storage; equipment oversizing; cascaded heat pumps; nearly-zero carbon building conditions of the Creative Commons Attribution (CC BY) license (https:// creativecommons.org/licenses/by/ 4.0/).
Energies 2021, 14, 5398. https://doi.org/10.3390/en14175398 https://www.mdpi.com/journal/energies EnergiesEnergies2021 2021, 14, 14, 5398, x FOR PEER REVIEW 22 of of 54 55
1.1. IntroductionIntroduction and and Literature Literature Survey Survey 1.1.1.1. OverviewOverview TodayToday any any civilizedcivilized action has has a a carbon carbon foot footprint.print. To Toreduce reduce the theglobal global warming warming rate, rate,the legally the legally binding binding Paris Paris Agreement Agreement was wassigned signed by the by World the World Leaders Leaders in December in December 2015, 2015,with withthe primary the primary objective objective to keep to keep the theglob globalal temperature temperature rise rise below below 2 °C 2 ◦ Ccompared compared to ◦ topre-industrial pre-industrial levels levels until until 2100. 2100. A further A further ambition ambition is 1.5 is 1.5°C [1].C[ However,1]. However, Figure Figure 1 indi-1 indicatescates that that these these goals goals will will not notbe achieved. be achieved. According According to the to theOECD OECD Outlook Outlook Baseline Baseline Pro- Projectsjects Report, Report, without without more more ambitious ambitious policie policiess yet yet to to be developed, thethe greenhousegreenhouse gas gas emissionsemissions (GHG) (GHG) would would reach reach almost almost 685 685 parts parts per millionper million (ppm) (ppm) CO2-equivalents CO2-equivalents by 2050. by This2050. concentration This concentration is well is over well the over limit the of limit 450 ppmof 450 (parts ppm per (parts million) per million) to have to at leasthave aat 50%least chance a 50% ofchance meeting of meeting the Paris the Agreement Paris Agreement goals [2 ].goals [2].
Figure 1. Atmospheric CO2 Concentration Predictions for Three Scenarios, including the business-as- usualFigure (BAU) 1. Atmospheric scenario. From CO2 [Concentration3]. Predictions for Three Scenarios, including the business- as-usual (BAU) scenario. From [3].
CO2 never increased more than 30 ppm during the last thousand years, but it did so duringCO2 never the past increased twenty more years than and 30 continuing ppm during [4]. the Despite last thousand serious measures years, but taken it did to so reduceduring thethe COpast2 twentyemissions years and and other continuing particulates, [4]. Despite Figure serious1 reveals measures that there taken must to reduce be a fundamentalthe CO2 emissions flaw in and the other current particulates, theory and Figure applications 1 reveals due that to there a lack must of understandingbe a fundamen- abouttal flaw the in missing the current mechanism theory of and the applications unexplained due CO2 toemissions, a lack of whichunderstanding is either unknown about the ormissing ignored. mechanism In the year of 2020, the theunexplained ‘calculated’ CO global2 emissions, CO2 emissions which is exceeded either unknown 36 billion or tons. ig- Thisnored. calculation In the year was 2020, carried the out ‘calculated’ based on different global CO fractions2 emissions of coal, exceeded oil, gas, and36 billion renewable tons. energyThis calculation sources worldwide, was carried all out of which based have on differ differentent fractions unit content of coal, of CO oil,2. gas, This and result renewa- is an outcomeble energy of suchsources a simplistic worldwide, calculation all of which concerning have different only the unit supply content side. of However, CO2. This no result one asksis an where outcome these of fuels such and a simplistic energy sources calculation are used concerning and how only exergy-rational the supply side. the utilization However, rateno one of their asks usefulwhere workthese potentialfuels and is.energy Exergy sources is the are useful used work and how potential exergy-rational (quality) of the a givenutilization amount rate or of flow their of useful energy work quantity. potential Energy is. mayExergy be storedis the useful and recovered. work potential Exergy (qual- may notity) be of storeda given or amount recovered or flo butw destroyed, of energy quantity. according Energy to the 2ndmay Law be stored of thermodynamics. and recovered. Therefore,Exergy may when not thebe stored term energy or recovered is used, but it isdestroyed, accompanied according by two to vectors,the 2nd namelyLaw of ther- the quantitymodynamics. and quality. Therefore, According when the to theterm ideal energy Carnot is used, Cycle, it is exergy accompanied is always by less two than vectors, the quantitynamely ofthe energy quantity (Exergy and quality. = (1 − T Accordingref/Tsup) times to the the ideal energy Carnot quantity, Cycle, and exergyTref > 0isK). always For example,less than if the natural quantity gas, of which energy has (Exergy a useful = work (1 − T potentialref/Tsup) times of 87% the of energy its energy quantity, content and and Tref ◦ ◦ burns> 0 K). almost For example, at 2000 ifC, natural is simply gas, used which in a has condensing a useful work boiler potential for comfort of 87% heating of its at energy 20 C, thencontent the rationalityand burns ofalmost spending at 2000 such °C, a valuableis simply fuel used only in fora condensing heating on boiler the demand for comfort side
Energies 2021, 14, 5398 3 of 54
is only about 10%, although condensing boilers are generally claimed to be more than 95% efficient. Natural gas, for example, could be used in power generation, industry, and finally, the waste heat could be serviced to the buildings. Otherwise, almost 80% of the useful work potential is destroyed irreversibly in a condensing boiler in buildings. This destruction leads to additional CO2 emission responsibility. This responsibility is the missing part of the strategies for decarbonization and is a simple matter of recognition of the 2nd Law for energy quality, exergy. Someone, somewhere, sometime, and by some means, will need to offset the exergy destructions with additional fuel spending and effort. In other words, we ‘calculate’ the direct emissions but ignore the additional emissions responsibilities, which take place due to mismatches of useful work potential (Exergy Destruction) between the supply and demand. Recognition of the relationships among energy, exergy, exergy destructions, and nearly-avoidable CO2 emissions is critical in emissions control for taking a sustainable position against climate emergencies [5]. Some concerned scientists and engineers have first announced the importance of exergy in the EU by releasing an opinion paper in 2016, with a ‘Think Exergy, not Energy’ [6]. They explained the concept of exergy and its application to energy efficiency, reaching out to policymakers to call for the formation of an International Exergy Panel to specifically address exergy destructions and their implications on the environment. Although this panel did not materialize, it generated enough interest for partial recognition of the importance of the 2nd Law of Thermodynamics. The EU is preparing new roadmaps to mobilize low-exergy (temperature) resources like waste heat, low-temperature solar heat, and low-enthalpy geothermal energy resources. These are widely available but untapped so far. Among various opportunities, buildings, representing almost 40% of the global energy consumption and a similar rate of CO2 emissions, present the largest asset of decarbonization efforts by utilizing such low-exergy sources on the horizon.
1.2. Buildings and the Environment In many EU countries, half of the residential stock comprises buildings, which were built before 1970, when the first thermal efficiency regulations were not in place yet [7]. This situation is almost the same for all other countries with exceptions like Spain and Ireland. Since such existing buildings are still energy-inefficient despite thermal over-insulation retrofits, their thermal loads are still high. They run on old heating equipment like steel or even cast-iron radiators or natural-convection coils, which were designed for high supply temperatures. Therefore, there is a significant conflict between the many old buildings that demand high supply temperatures and the new EU roadmap of utilizing low-temperature thermal sources. Old hydronic heating equipment was designed for at least 70 ◦C of supply design temperature (Teq). Nowadays, the EU is considering moving towards ultra- ◦ low temperature district energy systems with temperatures as low as 35 C(Tsup)[8,9]. In the Framework of International Energy Agency (IEA) Annex 37, a comprehensive compilation of research was carried out by IEA on low-temperature heating and its potential implications and the so-called side effects [10]. They argued that adding passive building systems for better retaining of solar gains and other internal sources, a continuous but lower thermostat settings shave off the peak loads and somehow enhance the utilization of low- temperature heat supplies. They considered floor heating, wall heating, oversized radiators and convectors, and air heating. Their studies were not too conclusive about energy performance, which were limited to the 1st Law of Thermodynamics only, and they did not investigate the effect of district piping and pumping on energy benefits or disadvantages. The potential impacts of low-temperature heating from the perspective of buildings about indoor air quality (IAQ), comfort, and energy have been further investigated by Eijdems, Boerstra, and Veld, without considering the conflict between energy supply temperature and the equipment demand temperature [9]. For public understanding and acceptance, they termed the low-exergy (Low-Temperature) energy as ‘low valued’ energy. They overviewed the impact of low-temperature supply to heating equipment for several types Energies 2021, 14, x FOR PEER REVIEW 4 of 55
Energies 2021, 14, 5398 4 of 54 ing and acceptance, they termed the low-exergy (Low-Temperature) energy as ‘low val- ued’ energy. They overviewed the impact of low-temperature supply to heating equip- ment for several types of equipment, including radiant floor and wall panels, low-tem- ofperature equipment, air heating. including They radiant qualitatively floor and claimed wall panels, that low-temperatureIAQ and sensation air of heating. comfort They im- qualitativelyprove mainly claimed by using that radiant IAQ and panels, sensation which of already comfort permit improve low mainly temperatures by using for radiant opera- panels,tion. However, which already they did permit not lowstudy temperatures how low-temperature for operation. heating However, may they be made did not possible study howby designing low-temperature new equipment heating may and beor madeexisting possible oversizing by designing equipment, new equipmentexcept noting and that or existingheat pump oversizing COP values equipment, may increase except notingdue to reduced that heat temperature pump COP values deficit may between increase the duesup- toply reduced and demand temperature [9]. Figure deficit 2 models between this the conflict supply of and at demandleast 35 °C [9]. of Figure temperature2 models deficit. this ◦ conflictWhen a of low-temperature at least 35 C of temperaturesource is provided deficit. at When Tsup, aFigure low-temperature 2 also shows source that over is provided insula- attionTsup of, Figurethe old2 buildingalso showss may that reduce over insulation the gap. of the old buildings may reduce the gap.
FigureFigure 2.2. ExergyExergy TriangleTriangle with with three three sides sides representing representingε demεdem,,ε εsupsup, and the unit thermal exergy supply,supply, EXH. EXH.
FigureFigure2 2is is a 2-Da 2-D graphical graphical representation representation of theof the exergetic exergetic relationship relationship among among temper- tem- atures,peratures, namely namely∆T, ΔTTref, ,TTrefa,, T anda, andT‘sup T`sup(Exergy (Exergy Triangle). Triangle). The The side side between between points pointsT aT–aT–Trefref representsrepresents thethe unitunit demanddemand exergy.exergy. The The side side ( T‘(T`supsup––TTrefref) represents the unit supply exergy. TheThe sidesideT Ta–a–((T‘T`supsup −− 1/21/2 Δ∆TT) )represents represents the the exergy exergy of a unitunit thermalthermal loadload ((QQ= = 11kW), kW),E EXHXH.. TheThe triangulartriangular area area∆ Δss represents represents the the optimization optimization objective, objective, which which needs needs to be to maximized be maxim- withinized within the given the given temperature temperature constraints constraints and given and given design design temperatures. temperatures. For a For detailed a de- explanationtailed explanation of Figure of 2Figure, please 2, referplease to refer Appendix to AppendixA. A. AccordingAccording toto FigureFigure2 ,2, at at an an indoor indoor comfort comfort temperature temperature of ofT Taa andand thethe ratedrated supplysupply temperaturetemperature requirement requirement of of the the conventional conventional heating heating equipment, equipment,Teq ,T thereeq, there is a is temperature a tempera- deficitture deficit between between the low-temperature the low-temperature district district supply, supply,Tsup, and TTsupeq, .and The T thermaleq. The thermal load, Q, load, may beQ, reducedmay be reduced by additional by additional thermal insulationthermal insulation (Over insulation). (Over insulation). This measure This measure also reduces also Treduceseq to T‘ eqT,eq reducingto T`eq, reducing the temperature the temperature gap between gap between the thermal the thermal supply supply and equipment and equip- requirements.ment requirements. However, However, over insulation over insulation has both has economic both economic and thermophysical and thermophysical limits, andlim- thereforeits, and therefore over insulation over insulation is a weak is tool a weak to resolve tool theto resolve problem. the It problem. is possible It tois determinepossible to andetermine optimum an relation optimum between relation the between over-insulation the over-insulation and equipment and equipment oversizing oversizing by referring by toreferring the Rational to the Exergy Rational Management Exergy Management Efficiency Efficiency (REMM), (REMM),ψR [11]. The ψR [11]. term TheψR isterm the ψ keyR is forthe sustainablykey for sustainably meeting meeting the Paris the Agreement Paris Agre goalsement because goals because it is an indicatorit is an indicator of nearly- of avoidable CO emissions, namely ∆CO , emanating from exergy destructions (ε − ε ). nearly-avoidable2 CO2 emissions, namely2 ΔCO2, emanating from exergy destructionssup dem (εsup Any mismatch is reflected upon ψ . The term ψ has been defined by the ideal Carnot − εdem). Any mismatch is reflectedR upon ψR. TheR term ψR has been defined by the ideal Cycle applied to the unit exergy demand, ε , and the unit exergy supply from source to Carnot Cycle applied to the unit exergy demand,dem εdem, and the unit exergy supply from equipment, εsup. source to equipment, εsup. T 1 − re f ε T𝑇a ψ = dem = 1 − ( − ) R 𝜀 𝑇 Maximize. Exergy Based (1) εsup Tre f Tsup 𝜓 = = (Maximize. Exergy − Based) (1) 𝜀 1 − T + 1 − 0 sup𝑇 Teq𝑇 1 − + 1 − ` 𝑇 𝑇
Energies 2021, 14, 5398 5 of 54
For maximum ψR, the denominator may be minimized if Ta is fixed. By differentiating the denominator concerning Tsup and then equating it to zero:
2 0 Tsup Teq = (For Maximum ψR) (2) Tre f
0 ∆Teq ' 2Tsup∆Tsup 0 ∆T ∆T ≤ eq sup 2Tsup
Tref is the reference environment temperature. A fixed value of 283 K in heating and 273 K in cooling were selected as common bases for all analyses. Then, the exergy- based (Equation (2)) sensitivity for maximum rationality at a given supply temperature is proportional to the uncertainties in the supply temperature, and it is twice as much. Therefore, for a narrow margin of sensitivity required about the maximum ψR at low supply temperatures as desired by the EU roadmaps, uncertainties in the supply temperature must be minimal. This is a critical issue for control systems of 5DE districts with renewables in terms of exergy because Tsup is low, and ∆T‘eq must also be kept minimum, making the condition hard to satisfy. Figure3 shows the trend of variables according to different Tsup ◦ values. Maximum possible exergy rationality, ψR, which is 0.40 is obtained at Tsup = 30 C. At this supply temperature, the insulation must be too heavy that the Q‘ will be about 50% ◦ of the design heating load, which is not practical. If Tsup is 35 C (308 K) and the reference ◦ temperature is 283 K, then T‘eq is 335 K (62 C) for maximum ψR at these temperatures. If ◦ Ta = 24 C (297 K), ψR will be: 1 − 283 K εdem 297 K 0.0471 ψR = = = = 0.291 εsup 283 K 308 K 0.1617 1 − 308 K + 1 − 335 K
The over-insulation rate is implicitly given by Equation (3). (n) is the equipment heating capacity exponent [12]. Tsup0 is the original supply design temperature of the heating equipment, like 70 ◦C.
0 n Q Teq − Ta % = × 100 (3) Q Tsup0 − Ta
Equation (3) provides the energy-based implicit sensitivity of the thermal conditioning load with a change in equipment n, which is a function of changing indoor conditions and the supply temperature as discussed above in Equation (2). If the original heat load coefficient of the building, U0, is known, then the need for over insulation may be estimated from Equation (4). To is the outdoor design temperature. Decreasing U‘ is also an optimality condition for heat pump COP (See Section 2.4.3).
0 0 U Teq − To = (4) U0 Tsup0 − To
◦ For example, if Tsup is 35 C, buildings need to be insulated such that their heating loads are reduced by about 78%. Then the value is locally maximized to 0.29 (29% on the ◦ graph). At Tsup = 39 C, no additional insulation is necessary. This simple exergy-based model shows how the exergy analysis may be effective. For example, now a designer may choose whether to insulate the building more or choose a higher supply temperature mix or blend of waste heat or go deeper in geothermal well if low-enthalpy geothermal energy is to be used. Energies 2021, 14, 5398 6 of 54 Energies 2021, 14, x FOR PEER REVIEW 6 of 55
FigureFigure 3. 3.Variation Variation of of Over Over Insulation Insulation in in Terms Terms of of (Q‘ (Q`/Q/Q),),ψ ψRR,, and andT‘ T`eqeqwith with thethe SupplySupplyTemperature. Temperature.
AsAs depicted depicted in in Figure Figure4 ,4, district district or or central centra comfortl comfort heating heating in in the the industrial industrial era era dates dates backback to to the the 1880s, 1880s, mainly mainly starting starting with with generating generating and and distributing distributing steam steam for for heating heating in in a a ◦ districtdistrict loop loop or or individual individual buildings buildings around around 200 200 C°C (473 (473 K). K). This This step step is is the the first-generation first-generation districtdistrict energy energy system system (1DE (1DE or or 1G). 1G). The The exergyexergyrationality rationalityof ofsteam steam inin heatingheating isis veryvery low.low. ψ comparedcompared toto modern modern systems, systems, as as the the following following equation equation gives, gives, ψRRto to be be 0.117, 0.117, which which is is significantlysignificantly less less than than 0.70, 0.70, which which is is the the limit limit for for green green districts districts [ 11[11]:]: − 283 εdem 1 273.15+28324 ψR = = 1 − = 0.117 (Steam to comfort) (5) 𝜀ε sup 0.406273.15 + 24 (5) 𝜓 = = = 0.117 (Steam to comfort) 𝜀 0.406 where the unit exergy of steam, εs is approximated by the following equation: where the unit exergy of steam, εs is approximated by the following equation: ε ' 0.00198(T − 283 K)(Steam) (6) s s (6) 𝜀 ≃ 0.00198(𝑇 − 283 K) (Steam) AnAn equivalentequivalent (Virtual)(Virtual) Carnot Carnot Cycle-based Cycle-based energy energy source source temperature, temperature,T Tf fmay may be be defineddefined for for steam steam by by simply simply equating equatingε sεsfrom from Equation Equation (6) (6) to to (1 (1− − Trefref//TTf):f): BuildingBuilding insulation insulation plays plays an an important important role role in green in green certification certification programs programs [13]. How- [13]. ever,However, these programsthese programs ignore ignore the connection the connection between between thermal thermal insulation insulation and other and com-other ponentscomponents of agreen of a green building building like alike heat a heat pump. pump. If a heatIf a heat pump pump is used, is used, over over insulation insulation as favorablyas favorably presented presented in Figurein Figure2 may 2 may seem seem economically economically unfeasible unfeasible and and not not worth worth any any furtherfurther greengreen points. points. However,However, whenwhen thethe performanceperformance improvementimprovement ofofthe the heat heat pump pump andand the the positive positive impact impact on on emissions emissions is is considered, considered, the the optimum optimum insulation insulation value value shifts shifts favourably.favourably. TheThe vertical vertical black black line line corresponds corresponds to to the the point point where whereQ‘ Q`,, which which is is seen seen in in shown shown in in FigureFigure3 ,3, is is equal equal to to thethe originaloriginal thermal load, QQ (No(No over over insulation). insulation). This This line line crosses crosses the ◦ theoriginal original equipment equipment supply supply temp temperatureerature requirement requirement (70 °C, (70 noC, oversizing), no oversizing), shows shows a min- aimal minimal ψR ofψ aboutR of about 0.23, 0.23,and indicates and indicates that the that supply the supply temperature temperature may be may less be than less about than ◦ about39 °C 39to allowC to allowfor better for better exergy exergy rationality rationality and give and some give someroom roomfor over for insulation. over insulation. At a superheated steam temperature, T of 488 K at a pressure of 20 bar ε is 0.406 At a superheated steam temperature, TSS of 488 K at a pressure of 20 bar supεsup is 0.406 kW/kW, and T is 476.4 K, which is very close to T in this case. On the other hand, if kW/kW, and Tff is 476.4 K, which is very close to TS S in this case. On the other hand, if moderate-qualitymoderate-quality coalcoal with unit exergy exergy of of 0.75 0.75 kW/kW kW/kW was was used used in ina steam a steam boiler boiler of that of thatera, era,the thesteam steam unit unitexergy exergy output output of 0.4 of06 0.406 kW/kW kW/kW means means an exergy an exergy destruction destruction of (0.75– of (0.75–0.406)0.406) kW/kW kW/kW from fromfuel to fuel steam to steam generation. generation. This, at the same time, means a ∆CO2 emissions responsibility: This, at the same time, means a ΔCO2 emissions responsibility:
𝛥𝐶𝑂 | =0.27×∆(0.75CO2| −1 = 0.4060.27) ×= (0.75 − 0.406) = 0.093 kg CO /kW-h 0.093 kg CO2/kW-h 2 Here the multiplier 0.27 stands for the type of exergy destroyed. Both lignite and Here the multiplier 0.27 stands for the type of exergy destroyed. Both lignite and steam carry on the potential of power generation. Therefore, the exergy destruction from steam carry on the potential of power generation. Therefore, the exergy destruction from lignite to steam is thermal exergy. An electric power generation is still an option. lignite to steam is thermal exergy. An electric power generation is still an option.
Energies 2021, 14, 5398 7 of 54
With such an emissions responsibility in mind at the steam generation step, the second major exergy destruction and emissions responsibility take place at step (4), which concerns the steam heating system in the building. Since the opportunity for electric power generation is missed, the multiplier is 0.63, as exemplified below:
( 273.15 + 24) K ∆CO | = 0.63 × 1 − = 0.208 kg CO /kW-h 2 4 488 K 2
Neglecting other exergy destructions in steps (2) and (3), total ∆CO2 will be the sum of the above two values, which is 0.301 kg CO2/kW-h. A second solution applying the ψR value in Equation (5) (0.117) from coal (εfuel = 0.75 kW/kW) to comfort, estimates exergy destructions in steps (2) and (3): ∆CO2 = 0.63 ε f uel − εdem = 0.63 × ε f uel(1 − ψR) = 0.417 kg CO2/kW-h (7)
The multiplier of 0.63 represents the missed opportunity (exergy mismatch) of gener- ating power upstream of comfort heating (using the waste heat). The difference between the two solutions, namely 0.417 kg CO2/kW-h and 0.301 kg CO2/kW-h, is an estimate about exergy destructions for Step 3, for exergy mismatches between pumping electricity and thermal exergy. ∆CO2 emissions described above exclude direct CO2 emissions yet from a coal boiler, which generates steam. Geothermal energy is often described as a clean and renewable energy source [14]. This statement holds only if, for example, non-condensable gases are captured, stored, utilized, or properly reinjected. Reinjection is also a must for environmental concerns and, simultaneously, to preserve the reservoir exergy. This condition is not completely possible for the original well over the years, and reservoirs need to be expanded. On the other hand, district energy systems are on the rise [15] but without referring to the 2nd Law.
1.3. Evolution of District Energy Systems Figure4 shows the progress of district energy systems, starting from very early local district heating systems based on fossil fuels, mostly coal and lignite. At this 1DE (1G) steam age, the thermal efficiency was low, supply temperatures were high, and the exergy rationality was as low as 0.08. This small number means only 8% of the useful work potential (exergy) of coal could be utilized. The remaining potential application opportunities were irreversibly destroyed according to the 2nd Law of Thermodynamics. This destruction, in turn, translated to additional CO2 emissions in addition to direct emissions from the plant stacks. The supply temperatures were high, and steam heating was popular. The only advantage was the minimization of pumping demand in the district while steam was conveyed. In-situ age (2DE) expanded the district size and introduced the combined heat and power concept at supply temperatures close to 100 ◦C. This generation transformed from steam to hot water. Solar energy, geothermal energy, and biomass were introduced in 3DE. Metered and monitored supply heat at a temperature below 100 ◦C were carried through pre-insulated pipes. Energies 2021, 14, 5398 8 of 54 Energies 2021, 14, x FOR PEER REVIEW 8 of 55
Figure 4. Historical Evolution of District Energy Systems from Steam to 100% Renewables. Developed from [[16].16].
In thethe meantime,meantime, energy energy efficiency efficiency and and exergy exergy rationality rationality significantly significantly increased increased while whilemany many other energyother energy sources sources and industrial and industrial waste heatwaste started heat started to appear to appear in the district in the district energy budget. CO emission responsibilities were also significantly reduced. In the 4DE system, energy budget.2 CO2 emission responsibilities were also significantly reduced. In the 4DE supply temperatures decreased below 60 ◦C, while efficiencies kept increasing. Today, the system, supply temperatures decreased below 60 °C, while efficiencies◦ kept increasing. Today,5DE systems the 5DE keep systems decreasing keep decreasing the supply the temperatures supply temperatures as low as 35as lowC. This as 35 reduction °C. This reductionfacilitates facilitates the achievement the achiev ofement 100% renewableof 100% renewable heating. heating. This very This low-temperature very low-tempera- tar- get, however, goes beyond the economic and technical capability of conventional heating ture target, however, goes beyond the economic and technical capability of conventional systems to satisfy the heating loads resulting in the need for excessive oversizing and tem- heating systems to satisfy the heating loads resulting in the need for excessive oversizing perature peaking. Heat pump temperature peaking defeats the purpose of decarbonization and temperature peaking. Heat pump temperature peaking defeats the purpose of decar- because they are responsible for exergy destructions and nearly-avoidable CO2 emissions in bonization because they are responsible for exergy destructions and nearly-avoidable CO2 addition to the ozone-depleting potential (ODP) of the refrigerants via the relationship with emissions in addition to the ozone-depleting potential (ODP) of the refrigerants via the their still high global warming potential (GWP). ODP and GWB are interrelated. Therefore, relationship with their still high global warming potential (GWP). ODP and GWB are in- a state-of-the-art refrigerant with zero ODP does not guarantee that it is an ozone-free terrelated. Therefore, a state-of-the-art refrigerant with zero ODP does not guarantee that substance because its GWP values are high. it is an ozone-free substance because its GWP values are high. Referencing to a coal (c’ = 0.6 kg CO2/kW-h) burning steam with an efficiency of 0.75: Referencing to a coal (c` = 0.6 kg CO2/kW-h) burning steam with an efficiency of 0.75: c0 0.6 CO = 𝑐` = 0.6 = 0.80 kg CO /kW-h (Energy − based) (8) 𝐶𝑂2 =η =0.75 = 2 (Energy −based) (8) boiler 0.80 kg CO2/kW-h 𝜂 0.75
The total unitunit emissionsemissions rate rate of of 1.217 1.217 kg kg CO CO2/kW-h2/kW-h is is the the sum sum of of Equations Equations (7) (7) and and (8). (8).Therefore, Therefore, district district heating heating systems systems transitioned transitioned away away from from the the steam steam age, age, namely namely from from 2G ◦ 2G(2DE) (2DE) systems systems to temperatures to temperatures below below 100 100C to °C reduce to reduce the exergy the exergy destructions. destructions. This exam- This exampleple shows shows that the that yet the untold, yet untold, unseen, unseen, and unexplained and unexplained nearly nearly avoidable avoidable emissions emissions∆CO2 ΔisCO about2 is about 55% of 55% the of direct the direct CO2 emissions.CO2 emissions. This This means means that that we seewe see the the complete complete problem prob- lembut knowbut know only only half half of the of solutions,the solutions, which which can can only only be revealed be revealed byexergy by exergy rationality. rationality.
EnergiesEnergies2021 2021, 14, 14, 5398, x FOR PEER REVIEW 99 of of 54 55
ThisThis ratio ratio also also shows shows why why in in the the following following generations generations of districtof district energy, energy, steam steam heating heat- hasing been has graduallybeen gradually abandoned. abandoned. Figure Figure5 reveals 5 reveals this trend, this which trend, shows which the shows steady the decline steady ofdecline steam of piping steam in piping district in energydistrict from energy 1950 from to 20001950 andto 2000 the and more the recent more days. recent This days. trend This hastrend the has apparent the apparent objective objective of increasing of increasing the exergy therationality, exergy rationality,ψR, by decreasing ψR, by decreasing the supply the temperatures.supply temperatures. However, However, steam and steam hot waterand hot district water heating district systemsheating stillsystems exist still despite exist thedespite obvious the exergeticobvious exergetic disadvantages. disadvantages. For example, For example, 500,000 Copenhageners 500,000 Copenhageners are still district are still heateddistrict with heated 500 MWwith steam500 MW and steam 1000 MWand hot1000 water MW [hot17]. water Termis [17].® is Termis a commercial® is a commercial hydraulic modelinghydraulic tool, modeling which tool, simulates which thesimulates flows, pressure,the flows, and pressure, thermal and conditions thermal conditions in a district in networka district [18 network,19]. On [18,19]. the contrary, On the one contrary of the, earlierone of computer-basedthe earlier computer-based modeling tools modeling was atools computer was a code-namedcomputer code-named HEATMAP, HEATMAP, designed fordesigned low-temperature for low-temperature geothermal geothermal energy districtenergy energydistrict systemsenergy systems [20]. They [20]. argued They thatargu whereed that geothermal where geothermal waters arewaters not warmare not enoughwarm enough to use directly, to use directly, water-source water-source heat pumps heat pumps can be usedcan be to used peak to the peak temperature the tempera- to requiredture to required levels, such levels, as in such Lund, as Sweden; in Lund, Chateauroux, Sweden; Chateauroux, France; and Ephrata,France; Washington,and Ephrata, USAWashington, [21–24]. USA [21–24].
FigureFigure 5. 5.Length Length of of Steam Steam Pipes Pipes of of Different Different Diameters Diameters in in District District Energy Energy Systems SystemsOver Overthe theYears. Years. FromFrom [17 [17].]. This This figure figure shows shows that that district district loop loop lengths lengths (in meters) (in meters) composed composed of steam of steam pipes havepipes been have significantlybeen significantly reduced reduced since the since 1950–1954 the 1950–1954 period. period. First, this First, results this fromresults the from transition the transition from steam from steam to hot water, and second the recognition of the fact that pumping power demand-related to hot water, and second the recognition of the fact that pumping power demand-related emissions emissions versus embodied emissions of large pipe diameters have an optimum point, which gen- versus embodied emissions of large pipe diameters have an optimum point, which generally calls for erally calls for shorter distances and moderately-sized pipe diameters. That is why larger pipes like shorterDN350 distances pipes are andnot moderately-sizedused anymore. pipe diameters. That is why larger pipes like DN350 pipes are not used anymore.
1.4.1.4. District District and and Heat Heat Pumps Pumps AsAs discussed discussed in in later later sections sections of of this this paper, paper, electrically electrically operated operated heat heat pumps pumps are are not not necessarilynecessarily exergy-rational. exergy-rational. Instead,Instead, anan optimumoptimum mixmix of of equipment equipment oversizing oversizing to to retain retain theirtheir rated rated capacities capacities at at low low temperatures temperatures with with or or without without heat heat pumps pumps is is necessary necessary (See (See SectionSection2 ).2). Today‘sToday`s strategies strategies have have started started to to involve involve low-temperature low-temperature waste waste heat heat resources resources and and renewablerenewable energy energy resources resources in in low-temperature low-temperature district district energy energy systems systems along along with with solar solar prosumersprosumers in in an an optimum optimum resource resource blending. blending. Following Following thisthis trend,trend, thethe third third and and fourth- fourth- generationgeneration district district systems systems have have started started to to involve involve much much lower lower temperatures temperatures to to utilize utilize the the wastewaste heat heat and and low-enthalpy low-enthalpy geothermal geothermal energy, energy, which which is is also also abundant. abundant. However, However, the the conventionalconventional heating heating systems systems werewere only only able able to to cope cope with with lower lower temperatures temperatures down down to to aboutabout 60 60◦ C.°C. Below Below this this supply supply temperature, temperature, the the district district system system requires requires new new equipment equipment technologiestechnologies andand betterbetter waysways ofof harnessing harnessingon-site on-site solarsolar energyenergy toto supply supply heat heat to to new new
Energies 2021, 14, 5398 10 of 54
equipment. Another option is to use heat pumps to peak the supply temperatures to either eliminate or minimize the oversizing of standard heating equipment or reducing the need for new technologies in the short term. However, current heat pump technology has unique challenges regarding the exergy mismatch between its electrical power demand and the peaking thermal exergy (Inset in Figure4). ! εsup TUL εdes = − 1 − ≥ 0 (Exergy − based) (9) COP Tpeak
In this respect, a heat pump with COP = 5 destroys exergy due to the unit exergy mismatch between electric power (0.95 kW/kW) and thermal peaking power between 35 ◦C (308 K) and 65 ◦C (338 K): For example, if 35 ◦C (308 K) district supply at 35 ◦C (308 K) is peaked to 65 ◦C (338 K):
0.95 308 K ε = − 1 − = 0.10 kW/kW des 5 338 K
If an on-site natural gas boiler (εsup: 0.87 kW/kW) replaces the heat pump, COP is replaced by its thermal efficiency, like ηI = 0.85, then εdes will be much higher (0.93 kW/kW). In the heat pump case, the high-exergy electrical power (0.95 kW/kW) is generated first at the origin of the fuel-to-power phase. This electrical power is finally converted to thermal power just for low-exergy comfort heating. This process chain using electrical power through the heat pump could be accomplished by low-exergy sources like waste heat or solar thermal energy. Therefore, the heat pump destroys the opportunity of utilizing the high-exergy electrical power in better ways with high-exergy demanding applications like industry or electrical mobility. The destroyed unit exergy is responsible for the so- called nearly-avoidable CO2 emissions ∆CO2. It is avoidable because it could be largely eliminated by removing the need for temperature peaking with low-temperature heating equipment. It is nearly avoidable because there will always be some exergy destruction inevitably present in any process. The exergy loss of electrical power input to the heat pump and then to the thermal exergy supply at 65 ◦C needs to be offset, most likely by consuming fossil fuels somewhere by someone and by some means. Referencing this offset amount of unit exergy to an on-site power generator with natural gas, Equation (10) gives the emission responsibility due to exergy destruction for power.
∆CO2 = +0.63εdes = +0.63 × 0.10 = +0.063 kg CO2/kW-h > 0 {Exergy − based} (10)
Equation (10) holds irrespective of the power generation technology at the origin even no fossil fuels are involved, like solar power systems, because the solar power generated could be allocated to higher exergy demands or fed to the grid to reduce its load. The exergy-based multiplier 0.63 in Equation (10) corresponds to a reference case of on-site power generation efficiency of 0.36 with natural gas (0.2 kg CO2/kW-h, 0.87 kW/kW), or grid power on natural gas and the primary energy factor (PEF) of 2.75: 0.2/0.87 × 2.75 = 0.63. This positive emissions responsibility adds to the direct emissions depending upon where and how the electrical power is generated and transmitted: Therefore, the use of heat pumps for temperature peaking does not sequester carbon. This example shows that temperature peaking with heat pumps or other means defeat the decarbonization roadmap for total electrification by wide-scale application of heat pumps. Even if heat pumps are not used, consider indoor electric resistance heating using electricity generated by on-site, roof-mounted PV panels. Let the unit exergy demand for indoor heating at a Dry-Bulb (DB) comfort air temperature of 293 K (20 ◦C) in reference to 283 K (10 ◦C) environment temperature. Then the unit exergy demand, εdem, will be (1 − 283 K/293 K) = 0.034 kW/kW. Comparing this small thermal exergy demand with high unit exergy of electric power of 0.95 kW/kW, the rational exergy management efficiency from solar energy to comfort heat using PV electricity will be (See Equation (5)): ψR = εdem/(0.95/ηPV) = 0.007, which Energies 2021, 14, 5398 11 of 54
renders solar PV installation useless. Here ηPV is 0.20. If solar heating is the only aim, then a domestic hot-water collector would have better rationality. If a heat pump is installed between the solar PV system and the indoor electric heater with a given COP, ψR will be raised only by a factor of COP. To be even with the unit exergies of the input (solar electricity) and the output (heat) in the above calculation, the necessary COP value (1/0.006) is impossible when compared with the theoretical Carnot-Cycle limit for heat pumps, even if a case of infinitely cascaded heat pumps in parallel is considered [25]. The theoretical ideal limit is the ratio of Tpeak/(Tpeak − Tsup). For example, if a heat pump peaks the low-temperature thermal supply (Source Temperature) at 308 K to 350 K (Peaked Temperature), the theoretical limit for COP is 8.3. Instead, series cascading of smaller heat pumps may keep increasing the peaking temperature. For example, two smaller heat pumps in series stepping up the temperature towards the final peaking temperature in two equal steps (42 K/2 = 21 K, each) relax the ideal COP limits. The first heat pump has a theoretical COP limit of (308 + 21)/21 = 15.66. The second heat pump has a theoretical COP limit of 350/21 = 16.66. Nevertheless, cascading multiple heat pumps means more investment and main- tenance cost, additional space, maintenance and controls, and material embodiments. Therefore, from an exergetic point of view, it is understood that the EU dream of total electrification of heating and cooling with or without heat pumps with 100% renewables (or not) may not come true unless heat pump technology is further developed by improv- ing their heating COP value to around 8 or 10, in a series formation at additional costs. These sample results conclude that the sustainable solution for decarbonization with low and ultra-low district energy supply temperatures lies on the demand side by low-exergy heating and cooling equipment without requiring temperature peaking of any kind, i.e., electrical or non-electrical. As an interim solution, Ding et al. have proposed a heat pump-heat pipe ‘composite’ system as shown in their illustration as given in Figure6[ 26]. In this system, the condenser side of the heat pump is directly connected through its condenser side with the indoor heat pipe radiator unit(s). Thus, the heat of condensation at 35 ◦C is utilized for space heating at a low-temperature supply. A typical application reaches indoor steady-state conditions in about 30 min. They also claimed that the radiator surface temperature is more uniform compared to other types of standard radiators. They tested R22, R32, R134a, and R410A refrigerants at different fill rates and heat pipe pressures and achieved COP values up to 4.5 in cold climatic conditions in their test chamber (5 ◦C). Their COP values are still not sufficient. Although their experimental COP values are not sufficiently high from the exergy point of view (COP < 7~10), such a novel composition of heat pump and heat pipe technology is a potent reminder about the necessity of concentrating on heat pipe technology towards sustainable decarbonization rather than trying to tweak existing technologies with narrow ranges of optimization chances to fit into the low-temperature heating targets with total electrification. As another solution, some authors recommend large temperature differences between the supply and return temperatures, ∆T, like 55 ◦C supply and 25 ◦C return in the equip- ment (∆T = 30 ◦C), expecting that the need for oversizing may be reduced [27]. This approach has rapidly diminishing returns, as shown in Figure7[ 28,29], especially for single-pipe systems, which were favoured between the 1960 and 1980 period, mainly for the economy and design simplicity reasons. Much older buildings, as a remnant of the steam age, have double pipe systems as do today’s buildings. Unfortunately, these types of buildings are in the majority of the existing building stock in many countries. Higher the ∆T (>20 ◦C), the need for equipment addition in series (Oversizing) increases at any given supply temperature. EnergiesEnergies2021 2021, 14, 14, 5398, x FOR PEER REVIEW 1212 of of 54 55
FigureFigure 6.6. Heat Pump/Heat Pipe Pipe Composite Composite System. System. From From [6,26]. [6,26 In]. this In thissystem system,, the heat-pipe the heat-pipe radi- radiatorator acts actsas a ascondenser a condenser for the for heat the pump heat pump while whileheats the heats indoor the indoor space at space low temperature at low temperature through the heat pipes. through the heat pipes.
ThisThis relationshiprelationship was formulated with with the the principles principles presented presented earlier earlier by by Kilkis, Kilkis, B. B.[12,28]. [12,28 ].This This formulation formulation is isgiven given in in Equation Equation (11) (11) and and sh shownown in inFigure Figure 7.7 . ( ∆T 0) K e 20e K (11) OversizingOversizing= 1=+ 1 + (11) l 𝑙 The term (l) in Equation (11) is a constant depending upon the equipment properties, The term (l) in Equation (11) is a constant depending upon the equipment properties, indoor air temperature, and heat load. indoor air temperature, and heat load. Figure 7 shows that the oversizing requirement becomes excessive by choosing ΔT Figure7 shows that the oversizing requirement becomes excessive by choosing ∆T above 30 °C, contrary to what was proposed in a research thesis [27]. above 30 ◦C, contrary to what was proposed in a research thesis [27]. . 𝑄 𝛥𝑇 10 1.33 (12) Q = (𝑇 ∆−T − 20)/(𝑇 − 10 − 20) × Oversizing =𝑄 Tsup − 2− 20 / Tsup − 2 − 20 × Oversizing (12) Qo 2 2 Here, the number 1.33 is the exponent of the heating capacity equation of a standard radiator.Here, Here, the number ΔT is referenced 1.33 is the to exponent 10 K. Figure of the 8 heatingshows that capacity at relatively equation low of supply a standard tem- radiator.peratures, Here, oversizing∆T is has referenced diminishing to 10 returns K. Figure in terms8 shows of increased that at relatively ΔT values low above supply 30 K. temperatures,For lower supply oversizing temperatures has diminishing such as 35 returns °C, as intargeted terms of by increased the EU goals∆T values of ultra-low above 30district K. For heating, lower supply namely temperatures 5DE, ΔT must such be asaround 35 ◦C, 10 as K, targeted in some by cases, the EU as goalslow as of 5 ultra-lowK to have districtsome positive heating, heating namely capacity 5DE, ∆ Tgainmust by be series around oversizing. 10 K, in Otherwise, some cases, irrespective as low as 5 of K the to havedegree some of oversizing, positive heating the heating capacity capacity gain byof seriesthe original oversizing. equipment Otherwise, cannotirrespective be restored. ofSuch the small degree ΔT of values, oversizing, of course, theheating strain the capacity piping ofand the pumping original costs equipment and material cannot em- be restored.bodiments Such besides small related∆T values, CO2 embodiments of course, strainand operating the piping emissions. and pumping Another costs solution, and materialwhich seems embodiments to be already besides available, related COis to2 embodimentsuse radiant panels, and operating which may emissions. be made Another readily solution,compatible which with seems 5DE tosystems. be already However, available, thes ise to systems use radiant carry panels, the same which problems may be madeof the readilyadditional compatible expense withof more 5DE tubi systems.ng (less However, tube spacing these on systems centers) carry and ancillaries the same problemsaccording ofto thetheir additional material, expenseenergy, and of more CO2 tubingembodiments (less tube and spacing pumping on demand, centers) andplusancillaries their diffi- accordingculty to retrofit to their existing material, buildings. energy, All and these CO 2challengesembodiments call for and new pumping heat pipe demand, technologies plus theirin space difficulty heating to and retrofit coolin existingg at low-exergy buildings. systems. All these challenges call for new heat pipe technologiesAnother in difficulty space heating is the andelectrical cooling power at low-exergy demand of systems. pumping stations, especially at ΔT valuesAnother less difficulty than 10 isKthe on electricalthe main powerdistrict demand heating ofloop. pumping In this stations, case, a main especially parallel at ∆pipingT values alternative less than may 10 Kbe on considered the main districtbecause heatingthe pressure loop. head In this in case,the piping a main system parallel re- piping alternative may be considered because the pressure head in the piping system duces by a factor of (1/Np) [12]. reduces by a factor of (1/Np)[12].
EnergiesEnergies 20212021, 14, 14, x, FOR 5398 PEER REVIEW 13 13of of55 54 Energies 2021, 14, x FOR PEER REVIEW 13 of 55
FigureFigure 7. 7.ChangeChange of ofSeries-Oversizing Series-Oversizing Rates Rates with with ΔT∆. TReference. Reference ΔT∆ isT istaken taken 20 20 K Kat atNo-Oversizing No-Oversizing Figure 7. Change of Series-Oversizing Rates with ΔT. Reference◦ ΔT is taken 20 K at No-Oversizing ConditionCondition (Oversizing: (Oversizing: 1). 1).Indoor Indoor Air Air Temperature Temperature Ta T=a 20= 20°C. C.This This figure figure shows shows that that equipment equipment Condition (Oversizing: 1). Indoor Air Temperature Ta = 20 °C. This figure shows that equipment oversizingoversizing increases increases while while ΔT ∆throughT through the theequipment equipment is increased. is increased. The corresponding The corresponding ΔT for∆ no-T for oversizing increases while ΔT through the equipment is increased. The corresponding ΔT for no- oversizingno-oversizing is 10 K. is The 10 K. point The representing point representing Reference Reference 27 shown 27 shownon the same on the curve same calls curve for calls an over- for an oversizing is 10 K. The point representing Reference 27 shown on the same curve calls for an over- sizingoversizing multiplier multiplier of 2. Large of 2. Δ LargeT values∆T valuesare limited are limited due to dueaeration to aeration problems problems in hydronic in hydronic circuits circuits and sizing multiplier of 2. Large ΔT values are limited due to aeration problems in hydronic circuits and reductionand reduction in heating in heating equipment equipment capacity. capacity. reduction in heating equipment capacity. MostMost importantly, importantly, if iftemperatures temperatures need need to tobe be peaked peaked by by heat heat pumps, pumps, ΔT∆ Tmustmust be be Most importantly, if temperatures need to be peaked by heat pumps, ΔT must be smallsmall to to increase increase their their COPCOP values.values. Although Although the the pumping pumping power power demand demand increases, increases, which small to increase their COP values. Although the pumping power demand increases, whichlarge large pipe pipe diameters diameters may limitmay limit (at the (at cost the of cost material of material embodiment), embodiment), a ∆T ofa Δ 10T Kofis 10 ideal. K which large pipe diameters may limit (at the cost of material embodiment), a ΔT of 10 K is Seeideal. Figure See 8Figure. On the 8. otherOn the hand, other any hand temperature, any temperature drop below drop 10 below K has disadvantages,10 K has disad- as is ideal. See Figure 8. On the other hand, any temperature drop below 10 K has disad- vantages,shown inas Figure shown8 .in Figure 8. vantages, as shown in Figure 8.
Figure 8. Temperature Profiles of the Fluid Flow in Series Oversizing of the Equipment at Different Figure 8. Temperature Profiles of the Fluid Flow in Series Oversizing of the Equipment at Different Figure∆T and 8. Temperature Supply Temperatures, Profiles ofT thesup. Fluid Flow in Series Oversizing of the Equipment at Different ΔT and Supply Temperatures, Tsup. ΔT and Supply Temperatures, Tsup. Figure8 shows the 5DE curve (Green line), which corresponds to the target of Tsup = 35Figure◦C, such 8 shows that atthe this 5DE supply curve temperature,(Green line), which about 18%corresponds more heat to atthe∆ Ttargetof 5 Kof mayTsup = be Figure 8 shows the 5DE curve (Green line), which corresponds to the target of Tsup = 35 °C, such that at this supply temperature, about 18% more heat at ΔT of 5 K may be 35generated °C, such (thatQ/Q ato =this 1.18). supply The practicaltemperature, range about is 15 K18% and more below. heat About at Δ 10T Kofis 5 theK may common be
Energies 2021, 14, 5398 14 of 54
point for all supply temperatures for Q/Qo = 1 base (See Figure7). Below 10 K, this ratio particularly increases above one for 5DE systems. Therefore 10 K is the lower bound. In the same token, the upper bound is 15 K if the Q/Qo is permitted only down to 80%. The term Np is the number of parallel circuits instead of a single main district piping system. This approach may be helpful provided that Np is optimized in terms of cost, energy, all associated embodiments, physical constraints, and terrain.
1.5. Low-Temperature District Energy Systems Studies on low-temperature district energy systems are not entirely new. Kilkis, B. has developed new metrics to guide the designers and practitioners to tackle the temperature incompatibility problem between the low-temperature supply from the district and the high-temperature demand of existing heating equipment. He analyzed two options, namely temperature peaking of the supply temperature and equipment oversizing. Results show that both have diminishing returns, and an optimal solution is difficult to obtain [28]. He suggested developing new terminal equipment, which is readily temperature-compatible with low-temperature district energy systems. In his other research, Kilkis, B. developed an analytical optimization tool for cases where low-temperature energy sources in heating and high-temperature waste cold energy sources are used for indoor space cooling [29]. This research involved three steps. The first step concerns heat pump retrofit of old buildings, replacing conventional energy conversion systems like boilers, while conventional heating equipment is retained for minimum life cycle cost. The second step concerns new buildings where heat pumps are coupled with radiant panel systems, increasing the COP of heat pumps. The third step involves a hybrid form of heating ventilating and air conditioning (HVAC) system, which optimally combines forced-air heating and cooling with hydronic equipment. Results showed that when heat pumps are considered to be used in buildings, whether old or new, the main challenge is the conflict between the heat pump COP and the supply temperature demand of various equipment unless low-exergy equipment is developed. Li and Svend have also focused on low-temperature district heating by carrying out energy and exergy analyses [30]. They have set a supply-return temperature of 55 ◦C supply and 25 ◦C return and argued that such a temperature difference of 30 ◦C is practical, as observed in a Danish project. Their analysis was based on a low-temperature heating system, namely floor heating and low-temperature radiators. Nevertheless, no details about the equipment were given. A district heating network design and simulation code was also developed to incorporate the network optimization procedure. Wheatcroft, E. et al. have investigated the impact of low-temperature waste heat use to achieve the 2050 goals for decarbonization [31]. They have reminded that heat from data centers, metro systems, public sector buildings, and wastewater treatment plants may be recovered to satisfy 10% of the overall heat demand in the EU countries. They gave practical examples from countries like Denmark, Sweden, and Germany but did not consider the exergy mismatches between the thermal power circulated and the electrical power exergy used in pump stations. In particular, the recent pandemic has forced online communications and increased cloud applications, increasing the low-exergy waste heat from data centers [32]. The waste heat may be utilized more effectively in 5DE districts. Grassi, P. et al. have investigated the potential impact of low supply temperatures on the indoor human thermal comfort sensation [33]. Their simulations for different building typologies in Italy showed that the most severe discomfort situations are experienced in buildings built before 1990. They have also recognized that the same may be true for new buildings because of the poor output of radiators when working at very low temperatures. They explained the reason but could not provide sustainable solutions, except noting that radiators were already oversized in many cases in existing buildings. Zyczy´nska,A.˙ et al. have investigated the impact of thermal retrofitting in Polish buildings on their annual energy budget [34]. They concluded that the thermal retrofitting in multi-family apartments that they have investigated reduced their heating demand up to 43%. This conclusion is essential from the energy and exergy point of view that by lowering the heating load, the supply temperatures Energies 2021, 14, 5398 15 of 54
required by the heating equipment also decrease, as will be shown in Equations (47) and (59) in the following sections of this paper. Reduction in thermal loads also reduces the need for equipment oversizing, which is especially critical in the retrofit of old buildings, unless the heating equipment is replaced by newly designed low-exergy equipment, like radiators with heat pipes. Young et al. have investigated the optimality conditions in considering electrical power and thermal power distribution systems together. This approach is vital for establishing a holistic optimization model about the power-heat energy flow in a district. Their objective was to minimize the heat losses and active power losses within certain constraints by developing a new model, namely, Optimal Heat-Power Flow. Although the Authors did not mention it, the unit exergy mismatch between electric power and thermal power, especially in low-temperature district heating systems, is significant. Therefore, an exergy balance also becomes more critical in optimizing the flows [35]. Suna et al. devised an experimental radiator with flat heat pipes to form a better radiant surface on both sides with enhanced heat transfer between the heat pipes and the front and back panels [36]. Without considering the exergy balance between the additional thermal capacity gained (∆QFC) and the fan power (P) required, they also proposed that small electric fans on the top surface of the radiator increase the thermal capacity by forced convection. The authors did not report the fan power demand in their experimental setup. The exergy balance may probably be negative in cases where the fan power demand is high. To avoid such a case (Exergy destruction), it would be prudent to check the following non-negativity condition, which compares the thermal exergy and the pumping power exergy: Ta ∆EX = ∆QFC 1 − − 0.95P > 0 (Exergy − based) (13) Ts
Here, Ta is the indoor DB air temperature, and Ts is the average panel surface tem- ◦ ◦ perature. For example, if ∆QFC is 400 W, Ta is 293 K (20 C), and Ts is 304 K (31 C), the fan power must not exceed 15.2 W. Otherwise, the exergy benefit of enhancing thermal power by forced convection will be negative. Furthermore, there will be CO2 responsibility of the electrical energy consumed, depending upon how and where the electric power is generated and transmitted minus the CO2 emissions savings from the thermal gain by an amount of ∆QFC.
1.6. Objectives The main objective of this research paper is to provide new insight into the benefits of the 2nd Law in sustainably responding to the climate emergency. To many, exergy remains in the textbooks without much translation to the practical needs of today and tomorrow for the environment. In order to overcome this conceptual difficulty, the objective is to equip researchers, engineers, and policymakers to simultaneously look at the two sides of the global warming problem, namely the quality of the energy sources on the demand side and the quality of energy on the demand side. Therefore, the aim is to let them recognize that exergy is not something difficult but more or less a matter of wisdom to match the exergy of supply and demand in every application such that resulting emissions due to mismatches are minimized.
2. Material and the Method of the Exergy-Based Model and Research An exergy-based model was developed to cover the four steps of district heating, namely the 5DE generation phase (Step 1), the district loop (Step 2), supply temperature peaking with heat pumps (not preferable unless COPH > 10, Step 3, either at the district plant or individually at the buildings), solar prosumers (Step 4) with conventional or new heat pipe types of heating equipment. The main aspects central to the problem were addressed first by the following hy- potheses: • Decarbonizing the built environment is possible by tapping into the widely available low-temperature renewable and waste heat sources. Energies 2021, 14, 5398 16 of 54
• District energy systems may be helpful to achieve this goal. • However, low-Temperature district energy systems can be successfully applied pro- vided that: (a) District circuit loop length is optimal concerning pumping exergy spending and thermal exergy distribution. This issue has already been answered (Refer to Reference [37]) (b) The temperature difference between the supply and return piping must be small at low supply temperatures (c) New low-temperature heating equipment must be developed to minimize or eliminate the necessity for equipment oversizing and temperature peaking. (d) Temperature peaking with heat pumps defeats the decarbonization objective unless the COP approaches 10. Such a high value may be achieved by cascading heat pumps and de-centralizing. (e) Heat pipes, wherever they may replace pumps or fans, reduce the CO2 emis- sions responsibilities economically. • District size with the number and capacity of the interconnected solar prosuming buildings must be small due to low solar heat temperatures being shared in the circuit. In this respect, sometimes detached solar buildings may be more rational • Especially in low-temperature applications, exergy rationality must be prioritized.
2.1. Research Design The main method of the research is based on the Rational Exergy Management Model (REMM) as an analytical tool to investigate the problem and verify the hypotheses. This method employs the exergy methods derived and based on the ideal Carnot efficiency and with derived metrics. The primary research method also aims for an easy-to-comprehend algorithm of met- rics and design equations that may also be understood and implemented by policymakers and comprehended by the public besides scientists and engineers. Thus, the ease of ac- knowledging the effect of nearly-avoidable CO2 emissions due to exergy destructions will be established and facilitated. In this token, this research plan was based on the need for sustainable decarbonization. Based on this need, exergy destructions, which become more dominant in low- temperature applications, like district energy systems with solar and waste heat as low as ◦ 35 C, are linked to the nearly-avoidable (additional) CO2 emissions. The hypotheses were verified and supported by analytical methods and derivations rather than experimentation due to the complexity and difficulties to implement the methodology to district energy systems. Mathematical tools supplemented by new veri- fication metrics have shown that hypotheses made are accurate and correct. REMM has successfully addressed all aspects of the problem of global warming. In addition, certified tests for heat pipe radiators were conducted in line with ANSI/ASHRAE SPC 138 test chamber principles. To quantify the importance of the exergy rationality approach, three impossible cases are exemplified first.
2.2. Impossible Cases with Existing Comfort Heating Equipment 2.2.1. Case 1 Figure9 shows the basic case for utilizing low-temperature thermal sources like solar thermal or waste heat (Step 1) in a district energy system. In this case, the standard heating equipment in the buildings (Step 4) is not oversized. Instead, the district supply temperature, Tsup is peaked at the central plant by heat pumps (HP, Step 3). Temperature- peaked thermal power is distributed in the district (Step 2) by circulation pump stations, demanding a total electrical power of P. Assuming that more recent models of hydronic heating equipment are used in the buildings, such that the supply temperature is 65 ◦C. The return temperature is 55 ◦C(∆T = 10 ◦C), just after one tour of thermal power distribution in the district, the waste heat or centralized solar thermal power field will become useless Energies 2021, 14, x FOR PEER REVIEW 17 of 55
equipment in the buildings (Step 4) is not oversized. Instead, the district supply tempera- ture, Tsup is peaked at the central plant by heat pumps (HP, Step 3). Temperature-peaked thermal power is distributed in the district (Step 2) by circulation pump stations, demand- ing a total electrical power of P. Assuming that more recent models of hydronic heating equipment are used in the buildings, such that the supply temperature is 65 °C. The return Energies 2021, 14, 5398 temperature is 55 °C (ΔT = 10 °C), just after one tour of thermal power distribution17 in of the 54 district, the waste heat or centralized solar thermal power field will become useless be- cause the return temperature to the heat exchanger (55 °C) will be higher than the input temperature of 35 °C. This result defeats the purpose of using low-temperature thermal ◦ becausesources for the decarbonization, return temperature while to the exergy heat exchangerdestructions (55 of C)the will following be higher amounts than the will input oc- temperature of 35 ◦C. This result defeats the purpose of using low-temperature thermal cur, with non-zero unit exergy destructions and DCO2 amounts as shown in the following sourcescalculations for decarbonization, These results ultimate while exergyly end destructionsthe operation of of the Case following 1. amounts will occur, with non-zero unit exergy destructions and DCO2 amounts as shown in the following calculations𝜀 =1−[( These273.15 results+ 35) K/ ultimately(273.15 + 55 end) K the] = operation0.061 kW/kW of Case 1.
𝛥𝐶𝑂 = 0.27 × 0.061 = εdes = 1 −0.0165[(273.15 kg+ CO35 )/kW-hK/(273.15 + 55) K] = 0.061 kW/kW The condition worsens for 90 °C/70 °C regime: ∆CO2 = 0.27 × 0.061 = 0.0165 kg CO2/kW-h The condition worsens for 90 ◦C/70 ◦C regime : 𝜀 =1−[( ) ( ) ] = 273.15 + 35 K/ 273.15 + 90 K 0.102 kW/kW (ΔT = 20 °C) ◦ εdes = 1 − [(273.15 + 35) K/(273.15 + 90) K] = 0.102 kW/kW (∆T = 20 C)
𝛥𝐶𝑂 = 0.27 × 0.102 = 0.0275 kg CO /kW-h ∆CO2 = 0.27 × 0.102 = 0.0275 kg CO2/kW-h Figure9 9 further further showsshows thatthat decarbonizationdecarbonization goalsgoals areare defeateddefeated byby directdirect andand nearly-nearly- 2 avoidable CO2 emissionsemissions of of the the heat pump(s) power supply sources delivering electricity to thethe heatheat pumpspumps andand circulationcirculation pumps.pumps. SuchSuch positivepositive exergyexergy destructionsdestructions renderrender thisthis application to be impossible right at the beginningbeginning of thethe processprocess byby notnot permittingpermitting thethe use of low-temperature thermal sources, as EU countries target for, thusthus alsoalso defeatsdefeats thethe strategy of using widely available low-temperature thermalthermal resources.resources. InIn general,general, toto make this solution workable, the returnreturn temperaturetemperature mustmust satisfysatisfy EquationEquation (14),(14), whichwhich showsshows that either equipment oversizing and or partialpartial temperaturetemperature peakingpeaking isis necessarynecessary forfor thethe building.
Figure 9.9. ImpossibleImpossible Case Case 1. Low-Temperature1. Low-Temperature Source Source is Peaked is Peaked at the Districtat the District Plant by Plant Heat Pump(s).by Heat ◦ ◦ SupplyPump(s). temperature Supply temperature is 65 C, up is to65 90°C,C. up This to 90 case °C. enables This case the enables retention the of retention the standard of the equipment standard withoutequipment any without need to any oversize. need to However, oversize. moreHowever, pipe insulationmore pipe isinsulation required is to required eliminate to additional eliminate heatadditional losses. heat The losses.COP of The the COP central of the heat central pump heat station pump is notstation high is duenot high to the due temperature to the temperature peaking requirementpeaking requirement from 35 ◦ fromC to 6535 ◦°CC andto 65 higher. °C and higher.
◦ o ∆T𝛥𝑇 Tret𝑇 <<3535C C− − (14)(14) 2 2 There are additional constraints, such as the COP of the heat pumps will be reduced in a peaking process to higher temperatures, the district loop pipe insulation must be thicker to avoid excessive thermal losses at high supply temperatures, increased power consumption of the heat pumps leading to more CO2 emissions responsibilities as well as ozone-depleting emissions with positive ODP (Ozone-Depleting Potential) of the refrigerant). Although at a higher ∆T pumping power, demand will be smaller. Case 2 shows equipment oversizing, which eliminated temperature peaking. Electric power for the heat pump and the district loop pump(s) come with direct and nearly-avoidable CO2 emissions. Energies 2021, 14, x FOR PEER REVIEW 18 of 55
There are additional constraints, such as the COP of the heat pumps will be reduced in a peaking process to higher temperatures, the district loop pipe insulation must be thicker to avoid excessive thermal losses at high supply temperatures, increased power consumption of the heat pumps leading to more CO2 emissions responsibilities as well as ozone-depleting emissions with positive ODP (Ozone-Depleting Potential) of the refrig- erant). Although at a higher ΔT pumping power, demand will be smaller. Case 2 shows equipment oversizing, which eliminated temperature peaking. Electric power for the heat Energies 2021, 14, 5398 18 of 54 pump and the district loop pump(s) come with direct and nearly-avoidable CO2 emis- sions.
2.2.2.2.2.2. Case Case 2 2 ThisThis case case in in Figure Figure 10 10 replacesreplaces centralcentral heat pumps with with individual individual heat heat pumps pumps to to be beinstalled installed in ineach each building building in inthe the district. district. Indoor Indoor comfort comfort heating heating equipment equipment is the is same the samewithout without any anyoversizing, oversizing, accommodating accommodating lowe lowerr supply supply temperatures temperatures forfor givengiven indoor indoor heatingheating loads. loads. Thermal input input is is distributed distributed in in the the district district loop loop at about at about 35 °C 35 to◦ Cthe to build- the buildingsings and andthen then locally locally peaked peaked to 65 to °C 65 by◦ Cindi byvidual individual heat pumps heat pumps to suit to the suit existing the existing equip- equipment.ment. Nothing Nothing seems seems to be todifferent be different in terms in termsof mission of mission impossible, impossible, except exceptthat thermal that thermalinsulation insulation in the inloop the looppipes pipes may may be besmaller smaller due due to to low low temperatures temperatures atat thethe supply supply branchesbranches of of thethe districtdistrict loop. Therefore, Therefore, th thee low-temperature low-temperature district district energy energy systems systems may maybring bring a new a new understanding understanding to urban to urban life and life andstrategy strategy to city to planners city planners by optimally by optimally using usingheat heatpumps, pumps, equipment equipment oversizing, oversizing, and andadditional additional low-temperature low-temperature applications applications inte- integratedgrated into into the the district. district. Thermal Thermal storage storage is is also also an essentialessential optimizationoptimization parameter parameter by by offeringoffering peak peak load load shaving, shaving, thus thus reducing reducing peak peak temperature temperature demands demands leading leading to reduction to reduc- oftion the of need the forneed equipment for equipment oversizing. oversizing.
FigureFigure 10. 10.Impossible Impossible Case Case 2. 2. Removal Removal of of Central Central Heat Heat Pumps Pumps (Case (Case 1) 1) with with Individual Individual Heat Heat Pumps Pumps inin the the Buildings. Buildings. Standard Standard Equipment Equipment Without Without Oversizing. Oversizing. In In this this case, case, each each building building is is equipped equipped withwith individual individual heat heat pumps. pumps. The main district district supply supply line line has has a alower lower temperature, temperature, thus thus does does not require additional insulation. However, because the return temperature will be higher (55 °C) than not require additional insulation. However, because the return temperature will be higher (55 ◦C) the temperature of the solar/waste heat (35 °C), this option defeats the purpose of utilizing low- than the temperature of the solar/waste heat (35 ◦C), this option defeats the purpose of utilizing temperature thermal sources. At the same time, the district return piping needs to be additionally low-temperatureinsulated. thermal sources. At the same time, the district return piping needs to be additionally insulated.
2.2.3.2.2.3. Case Case 3 3 InIn this this case case (Figure (Figure 11 11),), standard standard equipment equipment is is retrofitted retrofitted by by simply simply oversizing oversizing or or addingadding more more heating heating equipment equipment indoors indoors to accommodateto accommodate the the supply supply temperature temperature at 35 at◦C 35 directly°C directly without without temperature temperature peaking. peaking. In this In case, this however,case, however, the heating the heating equipment equipment over- sizingoversizing ratio, ratio,F‘ in termsF` in terms of equipment of equipment length length and width and product,width product, may be may seven be orseven even or moreeven (See more Section (See Section 3.1). Such 3.1). an Such oversizing an oversizi addsng material adds material weight, weig highht, cost, high manufacturing cost, manufac- embodiments,turing embodiments, and more and heat more transfer heat fluidtransfer to the fluid system. to the The system. latter The means latter higher means start-up higher pumping power requirement in on-off controls unless multi-cascade pumps are used. For single-speed pumps, this means oversizing the pump and reduced efficiency. Therefore, such a large amount of oversizing is almost impossible, especially in old buildings, to be
retrofitted. In the EU countries, more than half of the buildings are older than 50 years. The only rational option is radiant panel heating systems solar PVT panels with little over- sizing [38–40], which is also material, pumping energy-intensive, and almost impossible to retrofit the floors or ceilings in old buildings [40]. In this case, because ∆T needs to be small at such low temperatures in the entire district loop, pumping power in the district will be higher. Energies 2021, 14, x FOR PEER REVIEW 19 of 55
start-up pumping power requirement in on-off controls unless multi-cascade pumps are used. For single-speed pumps, this means oversizing the pump and reduced efficiency. Therefore, such a large amount of oversizing is almost impossible, especially in old build- ings, to be retrofitted. In the EU countries, more than half of the buildings are older than 50 years. The only rational option is radiant panel heating systems solar PVT panels with little oversizing [38–40], which is also material, pumping energy-intensive, and almost Energies 2021, 14, 5398 impossible to retrofit the floors or ceilings in old buildings [40]. In this case, because19 of Δ 54T needs to be small at such low temperatures in the entire district loop, pumping power in the district will be higher. TheThe aboveabove threethree casescases showshow thethe impossibilityimpossibility ofof utilizing utilizinglow-temperature low-temperaturethermal thermal sourcessources withwith existingexisting heatingheating equipmentequipment inin buildingsbuildings connectedconnected totothe the grid. grid.The The feasible feasible resolutionresolution ofof thethe conflictconflict betweenbetween low-temperaturelow-temperature thermalthermal sourcessources andand high-temperaturehigh-temperature equipmentequipment lies lies on on the the demand demand side, side, namely namely buildings buildings with newwithheating new heating equipment, equipment, which needwhich little need or little no oversizing or no oversizing at low supplyat low supply temperatures, temperatures, and without and without any performance any perfor- compromise.mance compromise. One such One viable such solution viable solution is to use is heat to use pipes heat in pipes new equipmentin new equipment designs de- to obtainsigns to more obtain favourable more favourable performance performanc characteristics.e characteristics. In 1963, Los In Alamos1963, Los physicist Alamos George physi- Grovercist George successfully Grover successfully demonstrated demonstrated his invention his of invention the heat pipe. of the Grover’s heat pipe. inspiration Grover’s for in- thespiration heat pipe for the came heat from pipe rudimentary came from heat-conductingrudimentary heat-conducting pipes used by pi Britishpes used bakers by British more thanbakers 170 more years than ago. 170 A heatyears pipe ago. is A a heat heat-transfer pipe is a deviceheat-transfer that combines device that the principlescombines the of bothprinciples thermal of both conductivity thermal conductivity and phase transition and phase to transition transfer heatto transfer between heat two between points two at differentpoints at temperatures different temperatures effectively. effectively. They have veryThey high have effective very high thermal effective conductivity thermal andcon- provideductivity a fastand responseprovide a to fast operational response changes.to operational changes.
Figure 11. Case 3: Utilization of Low-Temperature Sources with Oversized, Standard Equipment. Figure 11. Case 3: Utilization of Low-Temperature Sources with Oversized, Standard Equipment. In In this case, the district loop is at a low temperature. No temperature peaking is necessary because this case, the district loop is at a low temperature. No temperature peaking is necessary because the the standard equipment is oversized, and ΔT must be lowest (5 K). This case increases pumping standard equipment is oversized, and ∆T must be lowest (5 K). This case increases pumping power power demand and embodied costs of equipment oversizing. demand and embodied costs of equipment oversizing.
2.3.2.3. PossiblePossible Case:Case: NewNewHeating Heating Equipment Equipment without without or or Little Little Support Support from from Cascaded Cascaded Heat Heat Pumps CasePumps 4 CaseIn 4 this technically and economically viable case (Figure 12), new equipment designed with heatIn this pipes technically with little and water economically content and viable better case thermo-mechano-hydraulic (Figure 12), new equipment properties designed iswith much heat lighter pipes andwith requires little water little content oversizing. and better If temperature thermo-mechano-hydraulic peaking is necessary, properties heat pumpsis much must lighter be cascadedand requires to improve little oversizing the overall. If temperatureCOP equal to peaking above 10is necessary, [41]. The only heat remainingpumps must sustainability be cascaded challenge to improve for achievingthe overall the COP goals equal of EUto above for 5DE 10 systems[41]. The is only the highremaining preciseness sustainability and accuracy challenge required for achieving to control the the goals system of atEU such for 5DE low temperatures.systems is the Thehigh sensitivity preciseness in matchingand accuracy the low-quality required to exergy control of the such system widely at availablesuch low resources temperatures. with theThe demand sensitivity is critical.in matching This the condition low-quality is depicted exergy of in such Figure widely 13 and available Equation resources (15). Anywith perturbation in the temperature affects the sensitivity of exergy in terms of ∆T by its square. ∆ε Tre f = (15) ∆T T2
Energies 2021, 14, x FOR PEER REVIEW 20 of 55 Energies 2021, 14, x FOR PEER REVIEW 20 of 55
the demand is critical. This condition is depicted in Figure 13 and Equation (15). Any per- theturbation demand in is the critical. temperature This condition affects isth depictede sensitivity in Figure of exergy 13 and in terms Equation of Δ T(15). by Anyits square. per- turbation in the temperature affects the sensitivity of exergy in terms of ΔT by its square. 𝛥𝜀 𝑇 (15) 𝛥𝜀 =𝑇 𝛥𝑇 = 𝑇 (15) 𝛥𝑇 𝑇 The challenge of sensitivity-if resolved (System Management Difficulty), will pay off by theThe ability challenge to utilize of sensitivity-if widely available resolved low-temperature (System Management thermal Difficulty), sources for will and pay decar- off bybonization. the ability Besides,to utilize less widely power available is consumed low-temperature by heat pumps thermal (or sources no heat for pumps: and decar- zero bonization.power), negligible Besides, ozoneless power depletion is consumed effect due by to heat reduced pumps refrigerants (or no heat in heatpumps: pumps, zero if power),used, minus negligible more ozone power depletion demand effectby the due district to reduced main loop refrigerants pumps. Despitein heat pumps,several ad-if used,vantages minus and more potential power contributions demand by theto the district 5DE low-temperaturemain loop pumps. and Despite ultra-low several tempera- ad- Energies 2021, 14, 5398 20 of 54 vantagesture district and heatingpotential and contributions individual buildingto the 5DE heating low-temperature sector, heat-pipe and ultra-low radiator technologytempera- tureis not district commercially heating and mature individual yet, except building for someheating experimental sector, heat-pipe studies. radiator technology is not commercially mature yet, except for some experimental studies.
FigureFigure 12. 12. Case 4. Ultimate Ultimate Solution Solution for for 5DE 5DE District District He Heatingating with with Heat Heat Pipe Pipe Radiators Radiators (HPR). (HPR). Heat Figure 12. Case 4. Ultimate Solution for 5DE District Heating with Heat Pipe Radiators (HPR). Heat Heatpipe piperadiators radiators are more are moreadjustable adjustable to low-temper to low-temperatureature supply supply and require and require less oversizing. less oversizing. Optimi- pipezation radiators with small are more heat adjustablepumps will to be low-temper more feasibleature if supplytemperature and require peaking less is necessary.oversizing. Optimi- zationOptimization with small with heat small pumps heat will pumps be more will be feasible more feasibleif temperature if temperature peaking peaking is necessary. is necessary. Abundance Managing Abundancein the NatureManagingDifficulty 0.38 in the Nature Difficulty 0.38
0.36 0.36
0.34 0.34
0.32 0.322 2 0.3 0.3 LOW 0.28 LOW 0.28 TEMPERATURE
Sensivity 10 x TEMPERATURE 0.26 Sensivity 10 x 0.26 MEDIUM 0.24 MEDIUM 0.24 ULTRA-LOW TEMPERATURE TEMPERATURE ULTRA-LOW ULTRA-LOW TEMPERATURE 0.22 HIGH
TEMPERATURE HIGH 0.22 TEMPERATURE
0.2 TEMPERATURE 0.2 280 285 290 295 300 305 310 315 320 325 330 335 340 345 350 355 360 365 370 280 285 290 295 300 305 310 315 320 325 330 335 340 345 350 355 360 365 370 ΣCO =ΔCO +CO Source Temperature, K ΣCO =ΔCO2 +CO2 2 Source Temperature, K 2 2 2
FigureFigure 13. 13.Change Change of of Sensitivity Sensitivity with with Low Low District District Temperatures. Temperatures. Moving Moving to low to sourcelow source temperatures tempera- Figure 13. Change of Sensitivity with Low District Temperatures. Moving to low source tempera- increasestures increases the sensitivity the sensitivity of the thermal of the thermal response resp andonse leads and to leads control to issues,control although issues, although lower supply lower turessupply increases temperatures the sensitivity enable theof the broade thermalr use resp of low-temperatureonse and leads to resources. control issues, although lower supplytemperatures temperatures enable enable the broader the broade use ofr low-temperatureuse of low-temperature resources. resources. Kerrighan et al. provided useful information about the advantages of the heat-pipe KerrighanThe challenge et al. ofprovided sensitivity-if useful resolved information (System about Management the advantages Difficulty), of the heat-pipe will pay offradiator by the concept ability tofollowing utilize widelytheir early available demons low-temperaturetrative tests on a thermal bench scale sources with for partial and radiator concept following their early demonstrative tests on a bench scale with partial decarbonization. Besides, less power is consumed by heat pumps (or no heat pumps: zero power), negligible ozone depletion effect due to reduced refrigerants in heat pumps, if used, minus more power demand by the district main loop pumps. Despite several advan- tages and potential contributions to the 5DE low-temperature and ultra-low temperature district heating and individual building heating sector, heat-pipe radiator technology is not commercially mature yet, except for some experimental studies. Kerrighan et al. provided useful information about the advantages of the heat-pipe radiator concept following their early demonstrative tests on a bench scale with partial support from the EU and under the Ireland Grant CFTD-07-IT-307 [42]. Figure 14 shows the so-called heat-pipe natural convector. Energies 2021, 14, x FOR PEER REVIEW 21 of 55 Energies 2021, 14, x FOR PEER REVIEW 21 of 55
Energies 2021, 14, 5398 21 of 54 support from the EU and under the Ireland Grant CFTD-07-IT-307 [42]. Figure 14 shows thesupport so-called from heat-pipe the EU and natural under convector. the Ireland Grant CFTD-07-IT-307 [42]. Figure 14 shows the so-called heat-pipe natural convector.
FigureFigure 14. 14.Experimental Experimental Heat-PipeHeat-Pipe NaturalNatural Convector.Convector. FinsFins areare attachedattached toto horizontalhorizontal heatheat pipes.pipes. ReprintedFigure 14. withExperimental permission, Heat-Pipe Elsevier, Natural 2021 [42]. Convector. Fins are attached to horizontal heat pipes. ReprintedReprinted with with permission, permission, Elsevier, Elsevier, 2021 2021 [ 42[42].]. TheThe first first commercial commercial product, product, Enover Enover Heat-Pipe Heat-Pipe Radiator Radiator (HPR) (HPR) with with 3-phase 3-phase refrigerant- refrig- The first commercial product, Enover Heat-Pipe Radiator (HPR) with 3-phase refrig- fillederant-filled wickless wickless heat pipes, heat pipes, EHP, is EHP, shown is shown in Figure in 15Figure[ 43]. 15 The [43]. full-size The full-size experimental experi- erant-filled wickless heat pipes, EHP, is shown in Figure 15 [43]. The full-size experi- prototypemental prototype is shown is in shown Figure in 15 Figure. 15. mental prototype is shown in Figure 15.
Figure 15. Photo of the Prototype Enover Heat-Pipe Radiator (HPR). This prototype was tested in FigurecertifiedFigure 15. 15. labs.Photo Photo of of the the Prototype Prototype Enover Enover Heat-Pipe Heat-Pipe Radiator Radiator (HPR). (HPR). This This prototype prototype was was tested tested in in certified labs. certified labs. 2.4. Models of Each Step (1 to 4) 2.4.2.4. Models Models of of Each Each Step Step (1 (1 to to 4) 4) Step 1. Supply: Central District Plant and the Next-Generation PVT Systems of the StepProsumers.Step 1. 1. Supply:Supply: Central District Plant an andd the the Next-Generation Next-Generation PVT PVT Systems Systems of of the the Pro- sumers.Prosumers. Supply is both from the district central plant and the prosumers circulated on the mainSupplySupply district is isloop. bothboth The fromfrom primary the the district district source central central at the plant plant district and and central the the prosumers prosumers and prosumer circulated circulated scales on on is the the mainsolarmain district PVTdistrict system. loop.loop. The The primarythermalprimary sourcesupplysource at atneeds thethe district districtto be at central central low temperatures, and and prosumer prosumer which scales scales can is is the thebe solarreadilysolar PVTPVT accommodated system.system. TheThe thermalwiththermal heat supplysupply pipe radiators needsneeds toto with bebe at littleat low low oversizing temperatures, temperatures, and generally which which can can with- be be readilyoutreadily temperature accommodated accommodated peaking, with with heatto heat maintain pipe pipe radiators radiators the ra withted with PV little little efficiency oversizing oversizing with and and active generally generally cooling. without with- To temperatureachieveout temperature this peaking,condition, peaking, to however, maintain to maintain the the heat rated the transfer PVrated efficiency fluidPV efficiency must with be active circulatedwith cooling. active fast, Tocooling. which achieve re-To thisquiresachieve condition, more this electriccondition, however, pump however, the or heatfan power.the transfer heat In transfer fluidthis respect, must fluid be controlmust circulated be caution circulated fast, must which fast, be paidwhich requires such re- morethatquires the electric more electrical electric pump power orpump fan demand power.or fan power. Infor this the In respect, coolant this respect, control circulation control caution must caution must be belessmust paid than be such paid the thatsuchtotal theexergythat electrical the supplied electrical power by power demandPVT (Figure demand for the16). for coolant the coolant circulation circulation must be must less thanbe less the than total the exergy total suppliedexergy supplied by PVT (Figureby PVT 16(Figure). 16).
Energies 2021, 14, 5398 22 of 54 Energies 2021, 14, x FOR PEER REVIEW 22 of 55
FigureFigure 16. 16. SimplifiedSimplified PVT PVT Thermal Thermal and and Electric Electric Power Power Diagram Diagram with with a a Pump, Pump, including including the the heat heat exchanger, main pump, and the thermal energy storage. PMPPT: Direct Power MPPT (Maximum exchanger, main pump, and the thermal energy storage. PMPPT: Direct Power MPPT (Maximum Power Point Tracking). P ~ 0 if heat pipes are used. Power Point Tracking). P ~ 0 if heat pipes are used.
2.4.1.2.4.1. Optimum Optimum Pump Pump Control Control in in PVT PVT Panel Panel
FromFrom Equation Equation (16), (16), TToutout isis solved solved for for give give solar solar insolation insolation and and operating operating conditions. conditions.
𝑄=𝐼 𝐴 𝜂 𝑉. =𝜌(𝑇 )𝑉. 𝐶 (𝑇 )(𝑇 −𝑇 ) (16) Q = In ApηHE V = ρ(Tm)VCp(Tm)(Tout − Tin) (16)