Economizer Applications in Dual-Duct Air-Handling Units

Total Page:16

File Type:pdf, Size:1020Kb

Economizer Applications in Dual-Duct Air-Handling Units ESL-HH-02-05-44 Economizer Applications in Dual-Duct Air-Handling Units Ik-Seong Joo Mingsheng Liu, Ph.D., P.E. Graduate Student Associate Professor Energy Systems Laboratory Energy Systems Laboratory University of Nebraska-Lincoln University of Nebraska-Lincoln ABSTRACT This paper provides analytical tools and Single-Fan, Dual-Duct (SFDD) System engineering methods to evaluate the feasibility of the economizer for dual-duct air-handling units. The The SFDD system (see Figure 1) includes an results show that the economizer decreases cooling economizer, supply and return air fans, a pre-heating energy consumption without heating energy penalties coil, and cooling and heating coils. The terminal for dual-fan, dual-duct air-handling units. The boxes modulate the cold airflow, the hot airflow, or economizer has significant heating energy penalties both to maintain the room air temperature. for single-fan, dual-duct air-handling units. The penalties are higher than the cooling energy savings Exhaust Air Louver when the cold airflow is less than the hot airflow. Exhaust Air Detailed engineering analyses are required to Damper Return Air Fan evaluate the feasibility of the economizer for single- fan, dual-duct systems. Return Air Damper Heating Coil INTRODUCTION The economizer is widely acknowledged as one Cooling Coil Outdoor Air of the popular energy conservation measures. It Supply Air Fan Damper Pre-heat Coil eliminates or reduces mechanical cooling by using Filters free cooling. For a single-duct system, the economizer reduces mechanical cooling with no Terminal Box heating penalties. For a dual-duct system, however, Cold Air Hot Air heating energy penalties may exist. Liu et al. [1997] Suppy Duct Suppy Duct pointed out that the heating energy penalty is often TTZone 1 Zone 2 higher than the cooling energy savings for single-fan, Figure 1. Schematic diagram of the SFDD system dual-duct (SFDD) air-handling units, and they developed an advanced economizer algorithm to The economizer modulates exhaust air, return air solve the economizer operational problems. and outside air dampers accordingly to maintain the However, there are no general guidelines or mixed air temperature at its setpoint. In practice, the recommendations for the economizer design for dual- mixed air temperature setpoint is slightly lower than duct systems. This paper presents economizer the cold air temperature setpoint to avoid the chilled models, performs the energy performance analyses, water valve hunting or frequently opening and and develops the design recommendations. closing. The action of the exhaust and outside air dampers opposes the return air damper. When the outside air damper is fully open, the return air SYSTEM MODELS damper is closed. When the outside air damper is in The dual-duct system supplies both hot and cold the minimum open position, the return air damper is air to each zone, where a terminal box modulates the totally open. total airflow rate and/or the mixing ratio of hot and cold air to maintain the room temperature. The dual The economizer can be activated using either duct-systems are defined as single-fan, dual-duct outside air temperature (temperature economizer) or (SFDD) systems, where a single fan is used to push outside air enthalpy (enthalpy economizer). The air through both hot and cold ducts, and dual-fan, temperature economizer is activated when the outside dual-duct (DFDD) systems, where two fans are used air temperature is within a predefined range. The to push air through cold and hot ducts, respectively. Proceedings of the Thirteenth Symposium on Improving Building Systems in Hot and Humid Climates, Houston, TX, May 20-22, 2002 ESL-HH-02-05-44 enthalpy economizer is activated when the outside air air duct. When the cold airflow rate is smaller than enthalpy is smaller than the return air enthalpy. Both the outside air intake rate, however, a portion of the the temperature and enthalpy economizers use the outside air is supplied to the hot air duct. Figure 4 same control sequence after activation. Figure 2 and and Equation (3) present the economizer schedules. Equation (1) present the economizer schedules. Exhaust Air Louver Exhaust Air Damper b Return Air Fan 1 Return Air Tr Tc,d Damper VSD Heating Coil TTroa VSD Filters Cooling Coil Controller min Outdoor Air Pre-heat Coil Toa Damper PP Te,min Tc,d Te,max Figure 2. Economizer schedules for the SFDD system Terminal Box Cold Air Hot Air Suppy Duct Suppy Duct $ TTO TTZone 1 Zone 2 ' min oa e,max 1 TTT? Figure 3. Schematic diagram of the DFDD system ' c, d oa e,max %TTr c, d (1) b TTT? ' e,min, b oa c, d ' TTr oa o &' min TToa e,min, b 1 o(Tr Tc,d) When the outside air temperature (T ) is higher o oa Tr Toa than the cold air temperature setpoint (Tc, d ), the economizer uses 100% outside air. When the outside min air temperature is lower than the cold air temperature Toa setpoint, the economizer maintains the mixed air Te,min Tc,d Te,max temperature at the cold air temperature setpoint. When the economizer is off, the system receives the Figure 4. Economizer schedules for the DFDD minimum outside intake. system The minimum economizer temperature,Te,min, b , $ TTO ' min oa e,max varies depending on the minimum outside air intake TTT? ' o c, d oa e,max ratio, min(/)moa ,min md . % o()TT r c, d (3) o TTT? ' e,min, o oa c, d ' TTr oa 1 ' TT ()TT (2) & min TToa e,min, o e,min, b r c, d r min When the outside air temperature is between the The heating and cooling energy consumption maximum economizer temperature (Te,max ) and the depends on economizer cycles, entering air conditions, setpoints of leaving air conditions, and cold air temperature setpoint (Tc, d ), the outside air is cold and hot airflow rates. When these parameters directly supplied into the cold air duct. The cold are given, the heating and cooling energy airflow rate equals the outside airflow rate, and all consumptions can be calculated using energy balance hot air is from the return air. principles [Joo and Liu 2002, under review]. When the outside air temperature is between the cold air temperature setpoint and the minimum Dual-Fan, Dual-Duct (DFDD) System economizer temperature (Te,min, o ), the outside The DFDD system (see Figure 3) has two supply airflow is modulated to maintain the cold deck mixed fans. Outside air is directly introduced into the cold air temperature at the cold deck setpoint. The hot Proceedings of the Thirteenth Symposium on Improving Building Systems in Hot and Humid Climates, Houston, TX, May 20-22, 2002 ESL-HH-02-05-44 deck air is from the return air unless the cold airflow protected if the return and outside air is well mixed ratio ( o ) is smaller than the minimum outside air during the economizer cycle. Therefore, the intake ratio. minimum economizer temperature is selected to be 20°F (-6.7°C). When the outside air temperature is higher than the maximum economizer temperature or lower than The maximum economizer temperature depends the minimum economizer temperature, the primarily on the outside air moisture contents. For a economizer is disabled. When the cold airflow ratio dry climate, such as New Mexico, the maximum is smaller than the minimum outside air intake ratio, economizer temperature can be as high as the return outside air is allowed into the hot deck in any air temperature. For a humid climate, such as schedule. Galveston, TX, the maximum economizer temperature should be limited to 62°F (16.7°C) or is an outside air intake ratio (a ratio of the lower. To consider general conditions, the maximum o economizer temperature is selected to be 65°F outside airflow to the total airflow), which may differ (18.3°C). from the outside air intake ratio of the SFDD system ( b ) because of the dual-fan system’s characteristic The minimum outside air intake depends on the that the outside air is directly supplied to the cold building functions. It often varies from 10% (office deck. buildings) to 30% (hospital buildings). At a low outside air temperature, an office building may The minimum economizer temperature of the require 30% outside air intake due to a reduced total DFDD system, T min,, oe , varies depending on min airflow rate. Therefore, the simulation is conducted and . using minimum outside air intakes of 10%, 20% and o 30%, respectively. TT o TT )( (4) The partial building load can be expressed using e min,, ro , rdc min the cold airflow ratio and the supply air temperature. When the cold airflow ratio is 1, the building is in The energy consumptions can be calculated full cooling. When the cold airflow ratio is 0, the using general energy balance principles. Joo and Liu building is in full heating. provided the detailed models [Joo and Liu 2002, under review]. 0 5 10 15 20 25 30 oC oF 110 oC hot deck temperature 40 ANALYSIS 100 cold deck temperature room temprature C) Economizer performance depends on the o 35 F or 90 following parameters: minimum and maximum o 30 economizer temperatures, minimum outside air 80 intake ratios, cold airflow ratios, room conditions, 25 and deck setpoints. The parameter ranges are 70 selected carefully so that simulation results can be 20 Set-up temperature ( temperature Set-up directly used and serve as a guideline for engineers. 60 15 50 10 The temperature economizer is used in this study 30 40 50 60 70 80 90 o due to the following reasons: (1) it is more popular Outside air temperature (oF or oC) F than the enthalpy economizer, and (2) both Figure 5.
Recommended publications
  • Consider Installing a Condensing Economizer, Energy Tips
    ADVANCED MANUFACTURING OFFICE Energy Tips: STEAM Steam Tip Sheet #26A Consider Installing a Condensing Economizer Suggested Actions The key to a successful waste heat recovery project is optimizing the use of the recovered energy. By installing a condensing economizer, companies can im- ■■ Determine your boiler capacity, prove overall heat recovery and steam system efficiency by up to 10%. Many average steam production, boiler applications can benefit from this additional heat recovery, such as district combustion efficiency, stack gas heating systems, wallboard production facilities, greenhouses, food processing temperature, annual hours of plants, pulp and paper mills, textile plants, and hospitals. Condensing economiz- operation, and annual fuel ers require site-specific engineering and design, and a thorough understanding of consumption. the effect they will have on the existing steam system and water chemistry. ■■ Identify in-plant uses for heated Use this tip sheet and its companion, Considerations When Selecting a water, such as boiler makeup Condensing Economizer, to learn about these efficiency improvements. water heating, preheating, or A conventional feedwater economizer reduces steam boiler fuel requirements domestic hot water or process by transferring heat from the flue gas to the boiler feedwater. For natural gas-fired water heating requirements. boilers, the lowest temperature to which flue gas can be cooled is about 250°F ■■ Determine the thermal to prevent condensation and possible stack or stack liner corrosion. requirements that can be met The condensing economizer improves waste heat recovery by cooling the flue through installation of a gas below its dew point, which is about 135°F for products of combustion of condensing economizer.
    [Show full text]
  • Use Feedwater Economizers for Waste Heat Recovery, Energy Tips
    ADVANCED MANUFACTURING PROGRAM Energy Tips: STEAM Steam Tip Sheet #3 Use Feedwater Economizers for Waste Heat Recovery Suggested Actions ■■ Determine the stack temperature A feedwater economizer reduces steam boiler fuel requirements by transferring after the boiler has been tuned heat from the flue gas to incoming feedwater. Boiler flue gases are often to manufacturer’s specifications. rejected to the stack at temperatures more than 100°F to 150°F higher than The boiler should be operating the temperature of the generated steam. Generally, boiler efficiency can at close-to-optimum excess be increased by 1% for every 40°F reduction in flue gas temperature. By air levels with all heat transfer recovering waste heat, an economizer can often reduce fuel requirements by 5% surfaces clean. to 10% and pay for itself in less than 2 years. The table provides examples of ■■ Determine the minimum the potential for heat recovery. temperature to which stack gases Recoverable Heat from Boiler Flue Gases can be cooled subject to criteria such as dew point, cold-end Recoverable Heat, MMBtu/hr corrosion, and economic heat Initial Stack Gas transfer surface. (See Exhaust Temperature, °F Boiler Thermal Output, MMBtu/hr Gas Temperature Limits.) 25 50 100 200 ■■ Study the cost-effectiveness of installing a feedwater economizer 400 1.3 2.6 5.3 10.6 or air preheater in your boiler. 500 2.3 4.6 9.2 18.4 600 3.3 6.5 13.0 26.1 Based on natural gas fuel, 15% excess air, and a final stack temperature of 250˚F. Example An 80% efficient boiler generates 45,000 pounds per hour (lb/hr) of 150-pounds-per-square-inch-gauge (psig) steam by burning natural gas.
    [Show full text]
  • Airflow Simulations Around OA Intake Louver with Electronic Velocity
    Airflow Simulations around OA Intake Louver with Electronic Velocity Sensors Hwataik Han*1, Douglas P. Sullivan2 and William J. Fisk3 1 Professor, Kookmin University, Korea 2 Research Associate, Indoor Environment Department, Lawrence Berkeley National Laboratory, USA 3 Director, Indoor Environment Department, Lawrence Berkeley National Laboratory, USA Abstract It is important to control outdoor airflow rates into HVAC systems in terms of energy conservation and healthy indoor environment. Technologies are being developed to measure outdoor air (OA) flow rates through OA intake louvers on a real time basis. The purpose of this paper is to investigate the airflow characteristics through an OA intake louver numerically in order to provide suggestions for sensor installations. Airflow patterns are simulated with and without electronic air velocity sensors within cylindrical probes installed between louver blades or at the downstream face of the louver. Numerical results show quite good agreements with experimental data, and provide insights regarding measurement system design. The simulations indicate that velocity profiles are more spatially uniform at the louver outlet relative to between louver blades, that pressure drops imposed by the sensor bars are smaller with sensor bars at the louver outlet, and that placement of the sensor bars between louver blades substantially increases air velocities inside the louver. These findings suggest there is an advantage to placing the sensor bars at the louver outlet face. Keywords: ventilation; outdoor
    [Show full text]
  • Energy and Exergy Analysis of Data Center Economizer Systems
    San Jose State University SJSU ScholarWorks Master's Theses Master's Theses and Graduate Research Spring 2011 Energy and Exergy Analysis of Data Center Economizer Systems Michael Elery Meakins San Jose State University Follow this and additional works at: https://scholarworks.sjsu.edu/etd_theses Recommended Citation Meakins, Michael Elery, "Energy and Exergy Analysis of Data Center Economizer Systems" (2011). Master's Theses. 3944. DOI: https://doi.org/10.31979/etd.bf7d-khxd https://scholarworks.sjsu.edu/etd_theses/3944 This Thesis is brought to you for free and open access by the Master's Theses and Graduate Research at SJSU ScholarWorks. It has been accepted for inclusion in Master's Theses by an authorized administrator of SJSU ScholarWorks. For more information, please contact [email protected]. ENERGY AND EXERGY ANALYSIS OF DATA CENTER ECONOMIZER SYSTEMS A Thesis Presented to The Faculty of the Department of Mechanical and Aerospace Engineering San José State University In Partial Fulfillment of the Requirements for the Degree Master of Science By Michael E. Meakins May 2011 © 2011 Michael E. Meakins ALL RIGHTS RESERVED The Designated Thesis Committee Approves the Thesis Titled ENERGY AND EXERGY ANALYSIS OF DATA CENTER ECONOMIZER SYSTEMS by Michael E. Meakins APPROVED FOR THE DEPARTMENT OF MECHANICAL AND AEROSPACE ENGINEERING SAN JOSÉ STATE UNIVERSITY May 2011 Dr. Nicole Okamoto Department of Mechanical and Aerospace Engineering Dr. Jinny Rhee Department of Mechanical and Aerospace Engineering Mr. Cullen Bash Hewlett Packard Labs ABSTRACT ENERGY AND EXERGY ANALYSIS OF DATA CENTER ECONOMIZER SYSTEMS By Michael E. Meakins Electrical consumption for data centers is on the rise as more and more of them are being built.
    [Show full text]
  • Performance Measurements of a Unique Louver
    Performance Measurements Grant O. Musgrove Southwest Research Institute, of a Unique Louver Particle San Antonio, TX 78238 e-mail: [email protected] Separator for Gas Turbine Engines Karen A. Thole Mechanical and Nuclear Engineering Department, Solid particles, such as sand, ingested into gas turbine engines, reduce the coolant flow The Pennsylvania State University, in the turbine by blocking cooling channels in the secondary flow path. One method to University Park, PA 16802 remove solid particles from the secondary flow path is to use an inertial particle separa- tor because of its ability to incur minimal pressure losses in high flow rate applications. In this paper, an inertial separator is presented that is made up of an array of louvers Eric Grover followed by a static collector. The performance of two inertial separator configurations was measured in a unique test facility. Performance measurements included pressure Joseph Barker loss and collection efficiency for a range of Reynolds numbers and sand sizes. To comple- ment the measurements, both two-dimensional and three-dimensional computational United Technologies Corporation – results are presented for comparison. Computational predictions of pressure loss agreed Pratt & Whitney, with measurements at high Reynolds numbers, whereas predictions of sand collection East Hartford, CT 06108 efficiency for a sand size range 0–200lm agreed within 10% of experimental measure- ments over the range of Reynolds numbers. Collection efficiency values were measured to be as high as 35%, and pressure loss measurements were equivalent to less than 1% pres- sure loss in an engine application. [DOI: 10.1115/1.4007568] Introduction operating principle of inertial separators is to cause the particle- laden flow to abruptly change trajectory, whereby the particles do Aircraft gas turbines ingest solid particles during takeoff, land- not react to the change in flow direction due to their larger inertia ing, and while flying in dusty environments.
    [Show full text]
  • High Performance House Best Practices Guide
    New York State Energy Research & Development Authority High Performance House Best Practices Guide Design Intelligence for Energy Performance in Single Family Homes TABLE OF CON T EN T S High Performance House 1.1 Initial Work................................... 3 1.2 Process.......................................... 4 1.3 Testing........................................... 4 1.3.1 Building Construction.............................. 4 1.3.2 Building Form and Siting......................... 5 1.3.3 Passive Sustainable Strategies................ 6 1.3.4 Active Sustainable Strategies................... 14 1.4 Conclusions................................... 14 1.4.1 Additional Recommendations.................. 15 2 1.1 INitiAL WORK 1.1 Initial Work ON cti Preliminary analysis looked purely at geometric implications on energy use. This theoretical investigation tested a variety of building forms and found two general guidelines that govern performance. Across all building manipulations, results showed that forms minimizing volume and RODU T maximizing southern exposure perform best. This lines with rational thought; increased volume N increases the volume of required conditioned space, while maximizing southern exposure allows I for greatest winter solar gains and daylighting. Following this study, energy analysis was given for three, previously conceived housing designs – “Slope House”, “Underground House” and “X House”. In all cases, formal design (siting, building form, orientation) were given, fixed parameters. This proved a challenge to the energy optimization of the house. For the “Slope House”, building volume opens to the west without the benefit of southern expo- sure on the open face. Passive solar gains were minimal, with excessive shading on south facing windows. The majority of glazing is to the north, which effectively cuts the building’s thermal resistance/storage without the offsetting solar gains received on southern exposures.
    [Show full text]
  • Thermal Optimization of Solar Biomass Hybrid Cogeneration Plants
    Journal of Scientific & Industrial Research Vol. 65 April 2006, pp. 355-363 Thermal optimization of solar biomass hybrid cogeneration plants Anuradha Mishra 1, M N Chakravarty 2 and N D Kaushika 2, * 1IEC College of Engineering and Technology, Greater Noida 2School of Research and Development, Bharati Vidyapeeth College of Engineering, Paschim Vihar, New Delhi Received 10 February 2005; accepted 25 January 2006 Thermal optimization and performance matching of subsystems in solar biomass hybrid plant are investigated. The plant incorporates solar collector field, multiple fuel boiler, steam turbine, deaerator and economizer units. The solar field consists of line focus parabolic trough collectors. The thermal model is used for comparative study of various variations of parabolic trough collectors; LS3, Euro Trough (ET) and Duke solar excel over others. The matching of the output heat Qu and the temperature to the feed water conditions indicate that ET is the most suitable for the application; its inlet temperature requirement also matches the energy balance of the deaerator. Keywords : Biogas, Cogeneration, Hybrid power plant, Parabolic trough collector Introduction Cogeneration Plant Configuration India produces abundant quantities of agro residues A solar biomass hybrid plant would incorporate (rice husk, coffee husk, cashew shells, groundnut solar collector field, multiple fuel boiler, steam shells) and wastes (distillery waste). Co-generation of turbine, deaerator and economizer units (Fig. 1). The process heat and power is an important energy saving solar field consists of concentrating collectors. Three approach. It is particularly suitable for paper, solar thermal collector technologies (parabolic trough, chemicals, textiles, food and petroleum refining parabolic dish and solar tower) have reached the stage industries.
    [Show full text]
  • Damper Application Guide 1.” 1 Common 2 2 + Hot
    Control of Dampers ®® INDEX I. INTRODUCTION A. Economizer Systems ............................................................................................................ 3 B. Indoor Air Quality ...................................................................................................................3 C. Damper Selection ..................................................................................................................3 II. DAMPER SELECTION A. Opposed and Parallel Blade Dampers ..................................................................................3 B. Flow Characteristics...............................................................................................................4 C. Damper Authority ..................................................................................................................4 D. Combined Flow ......................................................................................................................6 III. ADDITIONAL CONSIDERATIONS A. Economizer Systems .............................................................................................................6 B. Building Pressure ...................................................................................................................8 C. Mixed Air Temperature Control ..............................................................................................8 D. Actuators - General ................................................................................................................8
    [Show full text]
  • IAQ Economizer LOGIC BOX
    IAQ Economizer LOGIC BOX Split-system Economizing/Indoor Air Quality/CO Alarm Activated Works on forced air systems, with or without air conditioning installed Enables cost saving cooling strategy: Expensive mechanical cooling can be set at a higher temperature Fresh Air Cooling can be set at a lower temperature Supports a variety Indoor Air Quality configurations: Continuous introduction Timed introduction CO2 or VOC sensor activated introduction Provides alarm activated fresh air introduction supporting CO or other alarm installations Occupant interface provides easy override, along with readiness, damper and fault status, (continuous fault detection) Operational tests can be conducted from within the conditioned space Quick connect wiring harnesses provide fast, correct termination FRESH AIR MANUFACTURING CO. FAMCO IAQ Economizer Famcoiaq.com 649 N. Ralstin St., Meridian, ID 83642 * (208)884-8931 * (800)-234-1903 * FAX: (208)884-8943 IAQ Economizer ECONOMIZER SYSTEM Damper Actuator Exhaust Damper Transformer Thermostat Logic Literature Box Cables Damper Box Actuator – Honeywell MS8105A1030, 24 VAC, 44 lb-in torque Outdoor thermostat- Dayton RLZ94A Nema 4X, Range 30º-110º F Transformer – RIB Functional Devices, Inc. TR50VA005 , 50VA All required System Cables are provided: • Power 40’ • Furnace 40’, plenum rated, HVAC industry standard color coding for furnace board termination • Damper Box 50’, plenum rated • Outdoor thermostat, 70’ , shielded, non polarity sensitive FRESH AIR MANUFACTURING CO. FAMCO IAQ Economizer
    [Show full text]
  • Building Applications, Opportunities and Challenges of Active Shading Systems: a State-Of-The-Art Review
    energies Review Building Applications, Opportunities and Challenges of Active Shading Systems: A State-Of-The-Art Review Joud Al Dakheel and Kheira Tabet Aoul * ID Architectural Engineering Department, United Arab Emirates University, P.O. Box 15551 Al Ain, UAE; [email protected] * Correspondence: [email protected]; Tel.: +971-566-433-648 Academic Editor: Arman Hashemi Received: 28 June 2017; Accepted: 4 August 2017; Published: 23 October 2017 Abstract: Active shading systems in buildings have emerged as a high performing shading solution that selectively and optimally controls daylight and heat gains. Active shading systems are increasingly used in buildings, due to their ability to mainly improve the building environment, reduce energy consumption and in some cases generate energy. They may be categorized into three classes: smart glazing, kinetic shading and integrated renewable energy shading. This paper reviews the current status of the different types in terms of design principle and working mechanism of the systems, performance, control strategies and building applications. Challenges, limitations and future opportunities of the systems are then discussed. The review highlights that despite its high initial cost, the electrochromic (EC) glazing is the most applied smart glazing due to the extensive use of glass in buildings under all climatic conditions. In terms of external shadings, the rotating shading type is the predominantly used one in buildings due to its low initial cost. Algae façades and folding shading systems are still emerging types, with high initial and maintenance costs and requiring specialist installers. The algae façade systems and PV integrated shading systems are a promising solution due to their dual benefits of providing shading and generating electricity.
    [Show full text]
  • Impacts of Commercial Building Controls on Energy Savings and Peak Load Reduction May 2017
    PNNL-25985 Impacts of Commercial Building Controls on Energy Savings and Peak Load Reduction May 2017 N Fernandez Y Xie S Katipamula M Zhao W Wang C Corbin Prepared for the U.S. Department of Energy under Contract DE-AC05-76RL01830 PNNL-25985 Impacts of Commercial Building Controls on Energy Savings and Peak Load Reduction N Fernandez Y Xie S Katipamula M Zhao W Wang C Corbin May 2017 Prepared for the U.S. Department of Energy under Contract DE-AC05-76RL01830 Pacific Northwest National Laboratory Richland, Washington 99352 Summary Background Commercial buildings in the United States consume approximately 18 quadrillion British thermal units (quads) of primary energy annually (EIA 2016). Inadequate building operations leads to preventable excess energy consumption along with failure to maintain acceptable occupant comfort. Studies have shown that as much as 30% of building energy consumption can be eliminated through more accurate sensing, more effective use of existing controls, and deployment of advanced controls (Fernandez et al. 2012; Fernandez et al. 2014; AEDG 2008). Studies also have shown that 10% to 20% of the commercial building peak load can be temporarily managed or curtailed to provide grid services (Kiliccote et al. 2016; Piette et al. 2007). Although many studies have indicated significant potential for energy savings in commercial buildings by deploying sensors and controls, very few have documented the actual measured savings (Mills 2009; Katipamula and Brambley 2008). Furthermore, previous studies only provided savings at the whole-building level (Mills 2009), making it difficult to assess the savings potential of each individual measure deployed. Purpose Pacific Northwest National Laboratory (PNNL) conducted this study to systematically estimate and document the potential energy savings from Re-tuning™ commercial buildings using the U.S.
    [Show full text]
  • BIM Handbook
    BIM Handbook A Guide to Building Information Modeling for Owners, Managers, Designers, Engineers, and Contractors Chuck Eastman Paul Teicholz Rafael Sacks Kathleen Liston John Wiley & Sons, Inc. BIM Handbook: A Guide to Building InformationModeling for Owners, Managers,Designers, Engineers, and Contractors. Chuck Eastman, Paul Teicholz, Rafael Sacks and Kathleen Liston Copyright © 2008 John Wiley & Sons, Inc. ffirs.indd i 1/3/08 12:32:13 PM This book is printed on acid-free paper. ϱ Copyright © 2008 by John Wiley & Sons, Inc. All rights reserved Published by John Wiley & Sons, Inc., Hoboken, New Jersey Published simultaneously in Canada No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical, photocopying, recording, scanning, or otherwise, except as permitted under Section 107 or 108 of the 1976 United States Copyright Act, without either the prior written permission of the Publisher, or authorization through payment of the appropriate per-copy fee to the Copyright Clearance Center, 222 Rosewood Drive, Danvers, MA 01923, (978) 750-8400, fax (978) 646-8600, or on the web at www.copyright.com. Requests to the Publisher for permission should be addressed to the Permissions Department, John Wiley & Sons, Inc., 111 River Street, Hoboken, NJ 07030, (201) 748-6011, fax (201) 748-6008, or online at www.wiley.com/go/permissions. Limit of Liability/Disclaimer of Warranty: While the publisher and the author have used their best efforts in preparing this book, they make no representations or warranties with respect to the accuracy or completeness of the contents of this book and specifi cally disclaim any implied warranties of merchantability or fi tness for a particular purpose.
    [Show full text]