818 S. FLORES ST.  SAN ANTONIO, TEXAS 78204  www.saha.org

Procurement Department

ADDENDUM # 1

To: File 1901-910-23-4878 QQ for: Villa Tranchese Fire Protection Improvements

Please note the following change:

The FA and FS drawings in the solicitation package did not copy correctly. Please replace with the attached drawings.

By: CharlesRBode Date: February 12, 2019 Charles Bode Asst. Director of Procurement

Equal Housing Opportunity  Equal Opportunity Employer SCOPE OF WORK GENERAL NOTES: Abbreviations Applicable Codes Raba Kistner Consultants, Inc.

A Amber Colored Strobe IBC International Building Code 1. 2015 International Existing Building Code 1. THESE DRAWINGS DEPICT GENERAL LOCATIONS OF LIFE SAFETY EQUIPMENT & FIELD DEVICES. EXACT ROUTING OF 12821 West Golden Lane San Antonio, Texas 78249 ADS Acoustically Distinguishable IDC Initiating Device Circut 2. 2015 International Building Code 1. PROVIDE COMPLETE NEW ADDRESSABLE FIRE ALARM/NOTIFICATION COMMUNICATIONS SYSTEM FOR CONDUITS AND WIRE TO BE DETERMINED IN THE FIELD BY THE INSTALLING CONTRACTOR TO SUIT CONDITIONS. ALL www.rkci.com Space IFC International Fire Code 3. 2015 International Fire Code THE FACILITY AS DEPICTED IN THE DOCUMENTS. CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS. AS Automatic Sprinkler Coverage LF Linear Feet 4. 2015 International Plumbing Code P 210 :: 699 :: 9090 2. FIRE ALARM COMMUNICATION SYSTEM SHALL BE OF ONLY NEW EQUIPMENT AND SHALL CONNECT 2. SHOULD ANY CONDITIONS EXIST THAT DIFFER FROM WHAT IS INDICATED ON THESE DRAWINGS WHICH CAUSE MAJOR F 210 :: 699 :: 6426 AHJ Authority Having Jurisdiction NA Not Applicable 5. 2015 International Mechanical Code AMP Amplifier NAC Notification Appliance Circuit TO THE EXISTING BUiLDING'S FIRE ALARM COMMUNICATION SYSTEM. DEVIATIONS IN THE WORK SHOWN, THE CONTRACTOR SHALL CONTACT FIRE PROTECTION CONSULTING GROUP, LLC AND TBPE Firm F-3257 6. 2014 National Electric Code BFP Backflow Preventer NACX Notification Appliance Circuit RABA KISTNER CONSULTANTS, INC. IN A TIMELY MANNER SO AS NOT TO IMPAIR THE CONSTRUCTION SCHEDULE. CA Clean Agent Expander 7. 2013 NFPA 13 3. SHOULD ANY CONDITIONS EXIST THAT DIFFER FROM WHAT IS INDICATED ON THESE DRAWINGS WHICH CAUSE MAJOR DEVIATIONS IN THE WORK SHOWN, THE CONTRACTOR SHALL CONTACT FIRE CMR Code Modification Request NC No Sprinkler Coverage 8. 2013 NFPA 72 3. CONTRACTOR IS RESPONSIBLE FOR MAKING AND OBTAINING APPROVAL FOR ALL NECESSARY ADJUSTMENTS IN PROTECTION CONSULTING GROUP, LLC IN A TIMELY MANNER SO AS NOT TO IMPAIR THE CP Control Panel NFPA National Fire Protection 9. City of San Antonio (COSA) Amendments CIRCUITING AS REQUIRED TO ACCOMMODATE THE RELOCATION OF EQUIPMENT AND/OR DEVICES WHICH ARE AFFECTED CONSTRUCTION SCHEDULE. CU Control Unit Association BY ANY AUTHORIZED CHANGE. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS. NRS Non-Rising Stem dBA Decibel Level 4. DEVICE LOCATION SHOWN ON THIS DRAWING ARE SCHEMATIC IN NATURE. NOT ALL 4. A STAMPED SET OF APPROVED FIRE ALARM DRAWINGS SHALL BE AT THE JOB SITE AND SHALL BE USED FOR DCDA Double Check Detector OS&Y Outside Screw & Yoke Valve APPURTENANCES ARE EXPECTED TO BE SHOWN ON THESE PLANS. THE CONTRACTOR IS INSTALLATION. Assembly PIV Post Indicator Valve RESPONSIBLE FOR DETERMINING FINAL DEVICES AND EQUIPMENT SIZES, DIMENSIONS, LOCATIONS, DL Deluge System PRE Pre-action System AND ELEVATIONS. DS Dry System PS Pressure Switch 5. BUILDING INFORMATION: E Elevator Recall R Releasing; Suppression Sys 5. THE CONTRACTOR SHALL PROVIDE ALL DRAWINGS, CALCULATIONS, AND SUBMITTALS FOR REVIEW 5.1. BUILDING USE: RESIDENTIAL HOUSING EX Existing RTS Remote Alarm Test Switch BY THE OWNER AND ARCHITECT PRIOR TO SUBMITTAL FOR PERMITTING. SUBMITTALS NOT 5.2. OCCUPANCY: R-2 HIGH RISE f2 Square Feet RTI Response Time Index APPROVED BY THE ARCHITECT SHALL NOT BE SUBMITTED FOR PERMITTING BY THE AHJ. THE 5.3. SQFT: 310,860 f3 Cubic Feet RUI Remote Unit Interface CONTRACTOR SHALL BE RESPONSIBLE FOR ALL PERMIT FEES AND SHALL PROVIDE ALL MATERIALS FA Fire Alarm S Shunt Trip AND EFFORT REQUIRED FOR SUBMITTAL OF ANY AND ALL REQUIRED PERMITS. 6. EXISTING FIRE ALARM INFORMATION: FCVA Floor Control Valve SC Strobe Circuit 6.1. FIRE PUMP MONITORING Assembly SF Square Feet 6. ONCE APPROVED BY THE ARCHITECT, THE CONTRACTOR SHALL PROVIDE ALL DOCUMENTS AND 6.2. SPRINKLER SYSTEM MONITORING FDC Fire Department Connection SLC Signal Line Circuit INFORMATION REQUIRED TO OBTAIN A PERMIT FOR THE INSTALLATION OF THIS WORK. THE FH Fire Hydrant VS Valve Supervisory Switch CONTRACTOR SHALL BE RESPONSIBLE FOR ALL PERMIT FEES AND SHALL PROVIDE ALL MATERIALS 7. PROPOSED FIRE PROTECTION INFORMATION: FO Foam System (Tamper) AND EFFORT REQUIRED FOR SUBMITTAL OF ANY AND ALL REQUIRED PERMITS. 7.1. DWELLING UNIT SMOKE DETECTION NOTIFICATION. FP Fire Protection (Sprinklers) W Wall Mounted 7.2. DWELLING UNIT AUDIO VISUAL OCCUPANT NOTIFICATION SYSTEM FPCG Fire Protection Consulting WC Wet Chemical 7. THE CONTRACTOR SHALL MAKE EVERY EFFORT TO MAINTAIN THE INTEGRITY OF THE AESTHETICS 7.3. BUILDING EMERGENCY EVACUATION SYSTEM Group WF Water Flow OF THE SITE AND BUILDING ELEMENTS AFFECTED BY THE THIS WORK. SHOULD ANY DAMAGE TO 7.4. BUILDING SMOKE DETECTION SYSTEM HA Halon WP Weather Proof SITE OR BUILDING FEATURES BE CAUSED BY THE CONTRACTOR AS PART OF THIS WORK, THE HC Horn Circuit WS Wet System CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING OR REPLACING ALL DAMAGED MATERIALS OR 8. ELECTRICAL CONTRACTOR SHALL PROVIDE DEDICATED POWER FOR THE NEW FIRE ALARM PANEL AT THE NEW OTHER ITEMS TO THE SATISFACTION OF THE ARCHITECT AND OWNER. LOCATION.

8. THE CONTRACTOR SHALL COORDINATE TESTING AND INSPECTIONS WITH THE OWNER AND 11. SEE ARCHITECTURAL PLANS FOR FIRE-RESISTANCE RATED WALL AND FLOOR/CEILING LOCATIONS. PENETRATIONS ARCHITECT AND IS RESPONSIBLE FOR ALL INSPECTION FEES. TROUGH RATED WALLS AND FLOOR/CEILINGS SHALL BE SEALED WITH A LISTED PENETRATION ASSEMBLY SYSTEM PER ARCHITECTURAL DRAWINGS. 9. THROUGHOUT CONSTRUCTION, THE CONTRACTOR SHALL MAINTAIN ON-SITE A SET OF THE MOST CURRENT WORKING DRAWINGS THAT BEAR THE APPROVAL MARK OF THE AHJ. WHERE FIELD 12. PROVIDE SUPERVISION OF EACH LEVELS FLOOR CONTROL VALVE ASSEMBLIES. MODIFICATIONS ARE MADE TO THE SYSTEM, THEY SHALL BE RECORDED ON THE WORKING DRAWINGS FOR INCORPORATION INTO THE PROJECT AS-BUILT DRAWINGS. THE CONTRACTOR 13. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. SHALL PROVIDE AS-BUILT DRAWINGS AS PART OF THE PROJECT CLOSE-OUT DOCUMENTS AND TRAINING. 14. NOTIFICATION, SUPERVISORY AND MODULES SHOWN ON THIS DOCUMENT ARE SUGGESTED LOCATIONS INTENDED TO 10. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING WITH THE OWNERS MONITORING COMPANY. SHOW SCOPE OF WORK. IT IS THE SELECTED SPRINKLER CONTRACTORS RESPONSIBILITY TO COORDINATE WITH MECHANICAL, STRUCTURAL AND OTHER TRADES DURING CREATION OF SHOP DRAWINGS. QUANTITY OF DEVICES SHOWN ON THIS DOCUMENT NOT INTENDED TO ENCOMPASS ALL REQUIRED TO ACCOMPLISH CODE COMPLIANT NOTIFICATION.

15. THE POWER CIRCUIT TO THE FACP AND TO THE FIRE ALARM POWER SUPPLIES SHALL BE ON A DEDICATED 120V, 20A BRANCH CIRCUIT BREAKER, AND SHALL HAVE A RED MARKING, LOCK-ON PROVISION AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL." THE LOCATION OF THE CIRCUIT DISCONNECT MEANS (CIRCUIT BREAKER) SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT.

16. THE CONTRACTOR WILL MAINTAIN ALL AREAS OF THE BUILDING IN A NEAT AND WORKMAN LIKE MANNER.

17. DO NOT APPLY POWER EXCEPT IN THE PRESENCE OF A FACTORY TRAINED TECHNICAL REPRESENTATIVE. 307 Marshall Street

18. ANY HEAD INSTALLED BEFORE THE BUILDING IS CLEANED AND ACCEPTED SHALL BE COVERED TO San Antonio, Texas PROTECT FROM DUST. ANY FALSE ALARMS DUE TO DIRT CONTAMINATED HEADS SHALL BE THE RESPONSIBILITY OF THE FIRE ALARM INSTALLER. Site Plan and General Notes 19. THE FIRE ALARM INSTALLER WILL MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF

ASSEMBLIES ANY TIME THAT WORK IS NOT ACTIVELY BEING PERFORMED. Villa Tranchese Apartments

20. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND San Antonio Housing Authority NON-POWER LIMITED FIELD WIRING MUST BE INSTALLED WITHIN THE FACP ENCLOSURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND NEC.

21. ALL WIRING SHALL BE INSTALLED ACCORDING TO NFPA 70 (NEC). 21.1. FIRE ALARM CIRCUITS SHALL BE IDENTIFIED IN ACCORDANCE WITH APPROPRIATE SECTION OF NEC 760. MARK ALL FIRE ALARM WIRES IN ACCORDANCE WITH NEC 760 SECTIONS FOR POWER LIMITED AND NON-POWER LIMITED WIRE. 21.2. FIRE ALARM CABLE INSTALLED IN DUCTS, PLENUM, AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP. 21.3. FIRE ALARM CABLE INSTALLED IN THE VERTICAL RUNS AND PENETRATE MORE THAN ONE FLOOR OR CABLES INSTALLED IN VERTICAL RUNS IN SHAFTS SHALL BE TYPE FPLR.

21.4. FIRE ALARM CABLE INSTALLED IN UNDERGROUND CONDUIT OR OTHER WET LOCATIONS SHALL BE UL LISTED PHASE B - Fire Protection Systems & Life Safety Renovations FOR WET LOCATIONS. 21.5. FIRE ALARM CIRCUITS EXTENDING BEYOND ONE BUILDING AND RUN OUTDOOR, OR UNDERGROUND, SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 70 ARTICLES 760, 770, 725 AND 800 WHERE APPLICABLE. 21.6. ALL WIRING, INCLUDING SHIELDS MUST BE DRY AND FREE OF SHORTS AND GROUNDS. 21.7. ALL SHIELDED WIRE MUST HAVE SHIELD CONTINUITY AT FULL LENGTH OF THE WIRE. 21.8. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT. 21.9. 120VAC IS NOT PERMITTED IN THE SAME CONDUIT WITH LOW VOLTAGE WIRING. 21.10. MAINTAIN 40 PERCENT CONDUIT FILL RATIO AS PER NEC REQUIREMENTS.

22. EXISTING CONDUITS MAY BE USED BY THE INSTALLATION CONTRACTOR AS DEEMED NECESSARY, HOWEVER, ANY EXISTING CONDUIT WILL BE USED ONLY IF CONDUITS MEET CURRENT STANDARDS AND CODES. FIRE PROTECTION CONSULTING GROUP, LLC MAKES NO STATEMENTS WRITTEN OR VERBAL AS TO THE CONDITION OF EXISTING CONDUITS.

23. DUCT DETECTORS AND REMOTE INDICATORS TO BE PROVIDED BY FIRE ALARM CONTRACTOR AND INSTALLED BY MECHANICAL CONTRACTOR. DUCT DETECTORS MUST BE INSTALLED IN AN ACCESSIBLE LOCATION FOR SERVICING AND TESTING.

24. VISUAL OR AUDIBLE/VISUAL MOUNTING TO BE 80" TO 96" FROM THE FINISHED FLOOR TO THE BOTTOM OF THE DEVICE PER NFPA 72.

25. AUDIBLE DEVICE MOUNTING TO BE A MINIMUM OF 90" FROM THE FINISHED FLOOR TO THE TOP OF DEVICE AND NO MORE THAN 6" FROM TOP OF DEVICE TO CEILING PER N.F.P.A. 72.

26. MANUAL PULL STATION SHALL BE NOT LESS THAN 3-1/2 FT. (1.1M) AND NOT MORE THAN 4-1/2 FT (1.37M) FROM OPERABLE PART OF DEVICE TO FLOOR LEVEL PER N.F.P.A. 72.

EXISTING R-2 BUILDING UPGRADE TO INCLUDE UNIT SMOKE DETECTION/LOW FREQUENCY NOTIFICATION UPGRADE FIRE ALARM SYSTEM TO INCLUDE BUILDING WIDE VOICE EVACUATION REVISIONS: MONITOR ALL NEW SPRINKLER SYSTEM AND FIRE PUMP DEVICES

These documents and the ideas incorporated herein as instruments of professional service are the property of Raba-Kistner Consultants, Inc. and are not to be used in whole or part without the written authorization of Raba-Kistner Consultants, Inc.

0 10' 20' 40' 1 SITE PLAN Scale: 1" = 20' SHEET NO. FA 100 UP 1 2 FIRST FLOOR PLAN SCALE: 3/32" = 1'-0" BASEMENT PLAN SCALE: 1/8" = 1'-0" 75 STOR STOR Living/Dining exam room 15 15 RTS RTS 15 75 30 t/r exam room 15 15 15 t/r 15 15 30 x 10 Bedroom interview room LF CONTROL VALVES PUMP CONTROLLERS AND NEW FIRE PUMP/JOCKEY PROVIDE SUPERVISION OF 15 15 15 15 75 G room Bedroom UP LF 30 15 75 15 interview 30 basement chase t/r t/r 75 15 15 15 15 15 mech. conference x 2 rm RTS 15 room FOR NEW WYE STRAINER. NEW ISOLATION VALVES PROVIDE SUPERVISION OF 15 RTS community Office Office 75 room Service Area 15 15 Way 30 Office Office 15 15 15 75

DOWN M.RR STOR MAIL 15 Office pit 15 STOR Waiting 15 15 15 15 TEL JAN Office 30 15 W.RR 15

DOWN 75

UP Rear Foyer vestibule FCVA rear FLOOR CONTROL PROVIDE SUPERVISION VALVES Entry Foyer Elevators vestibule front 75

Stairs FCVA FLOOR CONTROL PROVIDE SUPERVISION OF VALVES 75 Recreation Room 75 15 STOR Kitchen mech. INSTALLATION NOTES: 30 15 15. 14. 13. 17. 16. 12. 11. 10. 1. 6. 8. 7. 5. 9. 3. 2. 4. 190 ° WILL SERVE AS REQUIRED DETECTION AT ELEVATOR LOBBIES IN OPEN CORRIDORS. 17.7.5.5. DUCT WORK IS TO BE PROPERLY IDENTIFIED AT THE LOCATION OF DETECTOR. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND NON-POWER INSTALL CEILING MOUNTED NOTIFICATION APPLIANCES CENTER OF TILES UNLESS NOTED OTHERWISE. VISIBLE AS SHOWN ON FIELD WIRING MUST BE INSTALLED WITHIN THE FACP ENCLOSURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND NEC. DISCONNECT MEANS (CIRCUIT BREAKER) SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT. DUCT DETECTORS SHALL BE PROVIDED. SMOKE DETECTION INSTALLED IN ACCORDANCE WITH NFPA 72, PARAGRAPHS 17.7.5.4.2 AND FASTENING SYSTEMS OR METHODS. PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE SEALED WITH APPROVED RESISTIVE MATERIALS AND/OR ASSEMBLIES. MATERIAL AND RECALL WHETHER SHOWN ON THESE DOCUMENTS OR NOT. PROVIDE ALL NECESSARY MONITOR AND CONTROL MODULES FOR SMOKE DAMPERS, FIRE PUMP, SPRINKLER SYSTEM ELEVATOR POSSIBLE. CONTROL PANELS AND POWER SUPPLY UNITS SHALL BE INSTALLED AS INDICATED OR IN NON-PUBLIC AREAS MAY SURFACE MOUNTED. DEVICES PUBLIC SPACES WHERE BUILDING COMPONENTS ALLOW IT. ROOM. ADDITIONAL SPOT TYPE SMOKE DETECTORS ARE REQUIRED IN THE LOCATION OF ANY FIRE CONTROL ENCLOSURE WHICH SERVES ALARM PROVIDE SUPERVISION OF ALL TAMPER AND WATERFLOW SWITCHES IN ACCORDANCE WITH NFPA 72, PARAGRAPHS 17.12 17.16.1. WHETHER SHOWN ON SUPERVISORY SYSTEM SHALL TRANSMIT EACH OF THE FOLLOWING SIGNALS SEPARATELY. SPEAKERS SHOWN ON PLANS A TO PRODUCE REVERBERANT DBA OF 75 U.N.O. ARE PROVIDE INTELLIGIBILITY PER NFPA 72. TROUBLE SHALL HAVE A RED MARKING, LOCK-ON PROVISION AND BE IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL." THE LOCATION OF SUCH AS WALL MOUNTED VISUAL APPLIANCES, COMBINATION AUDIBLE/VISUAL ETC. SHOULD BE FLUSH WHERE SYSTEM. SPOT TYPE SMOKE DETECTION IS REQUIRED AT THE FACP AND EACH POWER SUPPLY PANEL LOCATION, ELEVATOR LOBBIES EQUIPMENT STROBE CANDELA RATINGS SHALL BE AS INDICATED AND PRESCRIBED PER TABLES 18.5.4.3.1 (A) (B). 3.3. 3.2. 3.1. THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF ASSEMBLIES ANY TIME THAT WORK IS NOT ACTIVELY BEING PERFORMED. WATERFLOW THE POWER CIRCUIT TO FACP AND FIRE ALARM SUPPLIES SHALL BE ON A DEDICATED 120V, 20A BRANCH BREAKER, VERIFY THAT DUCT DETECTORS INSTALLED IN PHASE A ARE COMPATIBLE WITH NEW FIRE PANEL AND REPLACE IF NECESSARY. ADDRESSABLE SYSTEM THESE DRAWINGS OR NOT. THESE DRAWINGS AND IN ACCORDANCE WITH NFPA 72, TABLE 18.5.4.3.1 (B) PARAGRAPH 18.5.4, IFC, SECTION 907.10.1. WIRING: ASSEMBLIES SHALL BE SUITABLE FOR THE HOURLY RATING OF PENETRATED CONSTRUCTION ELEMENT. ALARM AVERAGE AMBIENT SOUND LEVEL DESIGNATION OF 55DBA PER NFPA 72 SECTION 18.4.3, TABLE A.18.4.3. FOR BUSINESS OCCUPANCY. ALL MANUAL FIRE ALARM BOXES, SMOKE DETECTORS, AND NOTIFICATION APPLIANCES SHALL BE FLUSH MOUNT ON RECESSED BACK BOXES WHERE IN ALARMS DUE TO DIRT CONTAMINATED HEADS SHALL BE THE RESPONSIBILITY OF FIRE ALARM INSTALLER. ANY SMOKE DETECTOR HEAD INSTALLED BEFORE THE BUILDING IS CLEANED AND ACCEPTED SHALL BE COVERED TO PROTECT FROM DUST. FALSE ALL EQUIPMENT SHALL BE HELD FIRMLY IN PLACE (E.G., DETECTORS NOT SUPPORTED SOLELY BY SUSPENDED CEILING TILES) WITH APPROVED ALL WIRING SHALL BE INSTALLED IN CONDUIT OR RACEWAYS BUILDING, NO EXPOSED PUBLICLY ACCESSIBLE SPACES. INITIATING DEVICE CIRCUITS SHALL BE CLASS B. NOTIFICATION APPLIANCE CIRCUITS SHALL BE CLASS B. SIGNALING LINE CIRCUITS SHALL BE CLASS A. 15 Meeting rm. Meeting rm. 75 15 NORTH UP THE FIRE ALARM INSTALLER WILL MAINTAIN MANUAL Devices Notification Devices CONTROL DEVICES DETECTORS CONTROL PANELS W 15 LF 15 15 15 RTS Manual Pull Station Addressable Frequency Sounder Base Ceiling Speaker/Strobe Ceiling Strobe Only Weather Proof Heat Detector Wall Smoke Detector with Low Voice/ Hi / Low Frequency Wall Speaker/Strobe Wall Strobe Only Voice/ Hi / Low Frequency 190 deg fixed 135 deg fixed NAC Power Supply Evacuation Control Panel Fire Alarm Emergency Voice Suppresion Module Transient Voltage Surge SMOKE DETECTOR Spot-Type Photoelectric Addressable Input Module Addressable Output Module with Remote Indicator Addressable Duct Smoke Sensor Addressable Smoke Sensor Addressable Heat Detector Addressable Heat Detector ALL as instruments of professional service are the property used in whole or part without the written authorization REVISIONS: These documents and the ideas incorporated herein of Raba-Kistner Consultants, Inc. and are not to be Raba Kistner Consultants, Inc. San Antonio, Texas 78249

Basement and First Level Floor Plan 12821 West Golden Lane FA 200 of Raba-Kistner Consultants, Inc. P 210 :: 699 9090 F 210 :: 699 6426 TBPE Firm F-3257 SHEET NO. San Antonio Housing Authority www.rkci.com PHASE B - Fire Protection Systems & Life Safety Renovations Villa Tranchese Apartments 307 Marshall Street San Antonio, Texas INSTALLATION NOTES:

1. ALL WIRING SHALL BE INSTALLED IN CONDUIT OR IN RACEWAYS IN BUILDING, NO EXPOSED WIRING IN PUBLICLY ACCESSIBLE SPACES. Raba Kistner Consultants, Inc. 2. ALL EQUIPMENT SHALL BE HELD FIRMLY IN PLACE (E.G., DETECTORS SHALL NOT BE SUPPORTED SOLELY BY SUSPENDED CEILING TILES) WITH APPROVED FASTENING SYSTEMS OR METHODS. 12821 West Golden Lane San Antonio, Texas 78249 3. WIRING: 3.1. INITIATING DEVICE CIRCUITS SHALL BE CLASS B. www.rkci.com 3.2. SIGNALING LINE CIRCUITS SHALL BE CLASS A. P 210 :: 699 :: 9090 3.3. NOTIFICATION APPLIANCE CIRCUITS SHALL BE CLASS B. F 210 :: 699 :: 6426 TBPE Firm F-3257 4. INSTALL CEILING MOUNTED NOTIFICATION APPLIANCES CENTER OF TILES UNLESS NOTED OTHERWISE. INSTALL VISIBLE APPLIANCES AS SHOWN ON THESE DRAWINGS AND IN ACCORDANCE WITH NFPA 72, TABLE 18.5.4.3.1 (B) AND PARAGRAPH 18.5.4, AND IN ACCORDANCE WITH IFC, SECTION 907.10.1. STROBE CANDELA RATINGS SHALL BE AS INDICATED AND AS PRESCRIBED PER TABLES 18.5.4.3.1 (A) AND 18.5.4.3.1 (B).

5. PROVIDE SUPERVISION OF ALL TAMPER AND WATERFLOW SWITCHES IN ACCORDANCE WITH NFPA 72, PARAGRAPHS 17.12 AND 17.16.1. WHETHER SHOWN ON THESE DRAWINGS OR NOT.

6. VERIFY THAT DUCT DETECTORS INSTALLED IN PHASE A ARE COMPATIBLE WITH NEW FIRE PANEL AND REPLACE IF NECESSARY. ADDRESSABLE SYSTEM DUCT DETECTORS SHALL BE PROVIDED. DUCT SMOKE DETECTION SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72, PARAGRAPHS 17.7.5.4.2 AND 17.7.5.5. DUCT WORK IS TO BE PROPERLY IDENTIFIED AT THE LOCATION OF THE DETECTOR.

7. SPOT TYPE SMOKE DETECTION IS REQUIRED AT THE FACP AND EACH POWER SUPPLY PANEL LOCATION, ELEVATOR LOBBIES AND ELEVATOR EQUIPMENT ROOM. ADDITIONAL SPOT TYPE SMOKE DETECTORS ARE REQUIRED IN THE LOCATION OF ANY FIRE CONTROL ENCLOSURE WHICH SERVES THE FIRE ALARM SYSTEM.

15 8. ANY SMOKE DETECTOR HEAD INSTALLED BEFORE THE BUILDING IS CLEANED AND ACCEPTED SHALL BE COVERED TO PROTECT FROM DUST. ANY FALSE ALARMS DUE TO DIRT CONTAMINATED HEADS SHALL BE THE RESPONSIBILITY OF THE FIRE ALARM INSTALLER. W LF 9. 190 ° HEAT DETECTOR WILL SERVE AS REQUIRED DETECTION AT ELEVATOR LOBBIES IN OPEN CORRIDORS.

10. ALL MANUAL FIRE ALARM BOXES, SMOKE DETECTORS, AND NOTIFICATION APPLIANCES SHALL BE FLUSH MOUNT ON RECESSED BACK BOXES WHERE IN PUBLIC SPACES WHERE BUILDING COMPONENTS ALLOW IT.

W 11. CONTROL PANELS AND POWER SUPPLY UNITS SHALL BE INSTALLED AS INDICATED OR IN NON-PUBLIC AREAS AND MAY BE SURFACE MOUNTED. DEVICES LF SUCH AS WALL MOUNTED VISUAL APPLIANCES, WALL MOUNTED COMBINATION AUDIBLE/VISUAL APPLIANCES, ETC. SHOULD BE FLUSH MOUNTED WHERE 75 POSSIBLE. 30 W 15 12. THE POWER CIRCUIT TO THE FACP AND TO THE FIRE ALARM POWER SUPPLIES SHALL BE ON A DEDICATED 120V, 20A BRANCH CIRCUIT BREAKER, AND LF SHALL HAVE A RED MARKING, LOCK-ON PROVISION AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL." THE LOCATION OF THE CIRCUIT DISCONNECT MEANS (CIRCUIT BREAKER) SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT.

13. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND NON-POWER LIMITED FIELD WIRING MUST BE INSTALLED WITHIN THE FACP ENCLOSURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND NEC.

14. AVERAGE AMBIENT SOUND LEVEL DESIGNATION OF 55DBA PER NFPA 72 SECTION 18.4.3, TABLE A.18.4.3. FOR BUSINESS OCCUPANCY. ALL SPEAKERS SHOWN ON PLANS A TO PRODUCE A REVERBERANT DBA OF 75 U.N.O. SPEAKERS ARE TO PROVIDE INTELLIGIBILITY PER NFPA 72.

15. SYSTEM SHALL TRANSMIT EACH OF THE FOLLOWING SIGNALS SEPARATELY. 75 75 ALARM WATERFLOW SUPERVISORY TROUBLE UP 16. PROVIDE ALL NECESSARY MONITOR AND CONTROL MODULES FOR SMOKE DAMPERS, FIRE SMOKE DAMPERS, FIRE PUMP, SPRINKLER SYSTEM AND ELEVATOR RECALL WHETHER SHOWN ON THESE DOCUMENTS OR NOT.

17. PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE SEALED WITH APPROVED FIRE RESISTIVE MATERIALS AND/OR ASSEMBLIES. MATERIAL AND ASSEMBLIES SHALL BE SUITABLE FOR THE HOURLY RATING OF THE PENETRATED CONSTRUCTION ELEMENT. THE FIRE ALARM INSTALLER WILL MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF ASSEMBLIES ANY TIME THAT WORK IS NOT ACTIVELY BEING PERFORMED.

Notification Devices 307 Marshall Street San Antonio, Texas Ceiling Strobe Only W LF LF W LF W 15 Ceiling Speaker/Strobe 30 30 30 Voice/ Hi / Low Frequency 15 Villa Tranchese Apartments

Wall Strobe Only San Antonio Housing Authority 15

Wall Speaker/Strobe Voice/ Hi / Low Frequency Typical Upper Level and Enlarged Unit Plan 15

Wall Smoke Detector with Low Frequency Sounder Base W LF

Weather Proof Heat Detector PHASE B - Fire Protection Systems & Life Safety Renovations MANUAL Devices

Addressable ENLARGED UNIT PLAN VIEW Manual Pull Station 2 SCALE: 3/16" = 1'-0"

CONTROL DEVICES

Addressable Output Module

Addressable Input Module

DETECTORS

Addressable Heat Detector 135 deg fixed PROVIDE SUPERVISION OF x 2 HEAT TRACE PANELS

FCVA x 2 Addressable Heat Detector PROVIDE SUPERVISION 190 deg fixed 30 FLOOR CONTROL VALVES

UP Addressable Smoke Sensor Spot-Type Photoelectric

Addressable Duct Smoke Sensor DOWN with Remote Indicator 75 75 75 75 75 75 75 RTS REVISIONS: UP

SMOKE DETECTOR

CONTROL PANELS

These documents and the ideas incorporated herein as instruments of professional service are the property Fire Alarm Emergency Voice of Raba-Kistner Consultants, Inc. and are not to be Evacuation Control Panel used in whole or part without the written authorization of Raba-Kistner Consultants, Inc.

NAC Power Supply

Transient Voltage Surge Suppresion Module

SHEET NO. 1 PLAN LEVEL 2 THRU 11 SCALE: 3/32" = 1'-0" FA 201 Raba Kistner Consultants, Inc. 12821 West Golden Lane San Antonio, Texas 78249 www.rkci.com P 210 :: 699 :: 9090 F 210 :: 699 :: 6426 FIRE ALARM PANEL SEQUENCE OF OPERATION TBPE Firm F-3257 CONTROL UNIT ANNUNCIATION NOTIFICATION LIFE SAFETY INTERFACE

**FLOOR ABOVE/FLOOR BELOW

ACTUATE COMMONACTUATE ALARM AUDIBLEACTUATE SIGNAL ALARM COMMONACTUATE SIGNAL SUPERVISORY AUDIBLEACTUATE SUPERVISORY COMMONSIGNALACTUATE TROUBLE SIGNALAUDIBLEDISPLAY SIGNAL TROUBLE DEVICE STATUSSIGNALACTUATE BUILDINGACTUATE AUDIBLE BUILDING EVACUATION** VISIBLEACTUATE EVAC ALL DEVICES**ACTUATE AUDIBLE SLEEPING DEVICES UNITTEMPORALTRANSMIT AUDIBLE 4 ALARMLOWTRANSMIT FREQUENCY TO RECEIVINGSUPERVISORYTRANSMIT STATION TROUBLE TO RECEIVING TO RECEIVING STATN STATION ASSOCIATEDELEVATOR AIR HANDLER RECALL SHUTDOWN COMMENTS

ADDRESSABLE PULL STATION

ADDRRESSABLE SMOKE DETECTOR

ADDRESSABLE HEAT DETECTOR

ADDRESSABLE DUCT DETECTOR

SMOKE DETECTOR SOUNDER BASE

SPRINKLER WATERFLOW

SPRINKLER TAMPER

KITCHEN HOOD

AC LOSS TO FACP OR NAC

24VDC LOSS TO SOUNDER BASES

OPEN/SHORT CIRCUIT OR GROUND FLT

DISABLED DEVICES

BATTERY FAULT 307 Marshall Street San Antonio, Texas Sequence of Operations

FIRE PUMP PHASE REVERSAL

FIRE PUMP POWER LOSS Villa Tranchese Apartments San Antonio Housing Authority PUMP RUN ON

EMERGENCY GENERATOR ON

PUMP CONTROLLER BATTERY FAULT

HEAT TRACE POWER LOSS

HEAT TRACE GROUND FAULT PHASE B - Fire Protection Systems & Life Safety Renovations

SEQUENCE OF OPERATIONS 2 SCALE: NTS

FIRE ALARM RISER - DIAGRAMMATIC PURPOSES ONLY

REVISIONS:

These documents and the ideas incorporated herein as instruments of professional service are the property of Raba-Kistner Consultants, Inc. and are not to be used in whole or part without the written authorization of Raba-Kistner Consultants, Inc.

ONE - LINE DIAGRAM 1 SCALE: NTS SHEET NO. FA 300 SCOPE OF WORK Abbreviations Applicable Codes GENERAL NOTES: Raba Kistner Consultants, Inc.

A Amber Colored Strobe IBC International Building Code 1. 2015 International Existing Building Code 1. PROVIDE COMPLETE NEW WET-PIPE AUTOMATIC SPRINKLER AND STANDPIPE SYSTEM TO FULLY PROTECT THE EXISTING BUILDING AS DEPICTED IN 1. PROVIDE COMPLETE NEW WET-PIPE AUTOMATIC SPRINKLER SYSTEM TO FULLY PROTECT THE BUILDING AS DEPICTED IN THESE 12821 West Golden Lane THESE CONSTRUCTION DOCUMENTS AND SPECIFICATIONS. San Antonio, Texas 78249 ADS Acoustically Distinguishable IDC Initiating Device Circut 2. 2015 International Building Code DOCUMENTS. www.rkci.com Space IFC International Fire Code 3. 2015 International Fire Code 2. ALL DESIGN, FABRICATION. MATERIAL, AND INSTALLATION SHALL CONFORM TO NFPA 13, NFPA 14, NFPA 24, NFPA 72 AND ALL STATE AND LOCAL AS Automatic Sprinkler Coverage LF Linear Feet CODES PER THE 2015 EDITIONS OF THE IBC AND IFC INCLUDING CITY OF SAN ANTONIO ADOPTED AMENDMENTS. 2. PROVIDE EACH LEVEL WITH FLOOR CONTROL VALVE ASSEMBLIES. CONNECTION TO BY-OTHER. P 210 :: 699 :: 9090 4. 2015 International Plumbing Code F 210 :: 699 :: 6426 AHJ Authority Having Jurisdiction NA Not Applicable 5. 2015 International Mechanical Code AMP Amplifier NAC Notification Appliance Circuit 3. BUILDING INFORMATION: TBPE Firm F-3257 6. 2014 National Electric Code 3. THE CONTRACTOR SHALL PROVIDE ALL DRAWINGS, CALCULATIONS, AND SUBMITTALS FOR REVIEW BY THE OWNER AND ARCHITECT BFP Backflow Preventer NACX Notification Appliance Circuit 3.1. BUILDING USE: RESIDENTIAL HOUSING 7. 2013 NFPA 13 3.2. OCCUPANCY: R-2 HIGH RISE PRIOR TO SUBMITTAL FOR PERMITTING. SUBMITTALS NOT APPROVED BY THE ARCHITECT SHALL NOT BE SUBMITTED FOR PERMITTING CA Clean Agent Expander 3.3. SQFT: 310,860 CMR Code Modification Request NC No Sprinkler Coverage 8. 2013 NFPA 72 BY THE AHJ. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL PERMIT FEES AND SHALL PROVIDE ALL MATERIALS AND EFFORT CP Control Panel NFPA National Fire Protection 9. City of San Antonio (COSA) Amendments 4. EXISTING FIRE PROTECTION INFORMATION: REQUIRED FOR SUBMITTAL OF ANY AND ALL REQUIRED PERMITS. CU Control Unit Association 4.1. CLASS II STANDPIPE SYSTEM 4.2. SPRINKLERED BASEMENT dBA Decibel Level NRS Non-Rising Stem 4. IF A CURRENT FIRE FLOW TEST IS NOT OTHERWISE PROVIDED BY THE ENGINEER, THE CONTRACTOR SHALL PROVIDE A FIRE FLOW TEST 4.3. STANDPIPE FIRE PUMP DCDA Double Check Detector OS&Y Outside Screw & Yoke Valve 4.4. REMAINING OCCUPIED SPACES NOT SPRINKLERED TO SUPPORT DESIGN OF THE SPRINKLER SYSTEM WORK. IF THE ENGINEER'S FLOW TEST HAS BEEN CONDUCTED MORE THAN ONE YEAR Assembly PIV Post Indicator Valve PRIOR TO THE DATE OF SUBMITTAL FOR SPRINKLER PERMIT, THE CONTRACTOR SHALL CONDUCT A NEW TEST TO BE INCLUDED WITH DL Deluge System PRE Pre-action System 5. PROPOSED FIRE PROTECTION INFORMATION: DS Dry System PS Pressure Switch 5.1. NEW WET SPRINKLER STANDPIPE WITH INDIVIDUAL FLOOR CONTROL VALVES LOCATED IN CENTRAL STAIR. THE SUBMITTAL TO THE ARCHITECT AND TO THE AHJ FOR PERMITTING. E Elevator Recall R Releasing; Suppression Sys 5.2. NEW FIRE PUMP TO SERVE BOTH THE STANDPIPE AND BUILDING SPRINKLER SYSTEM. 5.3. NEW CLASS I STANDPIPE SYSTEM REPLACING THE EXISTING STANDPIPE AND THEIR EXISTING HOSE LINES AND CONNECTIONS. 5. THE CONTRACTOR SHALL MAKE EVERY EFFORT TO MAINTAIN THE INTEGRITY OF THE AESTHETICS OF THE SITE AND BUILDING EX Existing RTS Remote Alarm Test Switch 5.4. PROVIDE A FULLY SPRINKLERED BUILDING. f2 Square Feet RTI Response Time Index ELEMENTS AFFECTED BY THE THIS WORK. SHOULD ANY DAMAGE TO SITE OR BUILDING FEATURES BE CAUSED BY THE CONTRACTOR AS f3 Cubic Feet RUI Remote Unit Interface 6. THE OWNER SHALL BE RESPONSIBLE FOR MAINTAINING HEAT IN THE AREAS SHOWN ON PLANS TO INCLUDE CENTRAL STAIRWELL, OCCUPIED AND PART OF THIS WORK, THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING OR REPLACING ALL DAMAGED MATERIALS, FA Fire Alarm S Shunt Trip UNOCCUPIED UNITS, BASEMENT AND ENTIRE FIRST FLOOR. MAINTAIN A MINIMUM TEMPERATURE OF 40 DEGREES F AT ALL TIMES. REFER TO ME FCVA Floor Control Valve SC Strobe Circuit SHEETS FOR AREA HEATER LOCATIONS. LANDSCAPING, OR OTHER ITEMS TO THE SATISFACTION OF THE ARCHITECT AND OWNER. Assembly SF Square Feet 7. WET SPRINKLER MAIN PIPE CROSSING EXTERIOR CORRIDORS SHALL BE PROTECTED BY A LISTED HEAT TRACE SYSTEM AND MONITORED BY THE 6. THE CONTRACTOR SHALL COORDINATE TESTING AND INSPECTIONS WITH THE OWNER AND ARCHITECT AND IS RESPONSIBLE FOR ALL FDC Fire Department Connection SLC Signal Line Circuit FIRE ALARM SYSTEM. ALL SPRINKLER PIPE INCLUDING CONCEALMENT SOFFITS AND HANGERS SHALL MAINTAIN A CLEAR HEAD SPACE OF 7'-6" FH Fire Hydrant VS Valve Supervisory Switch MINIMUM. INSPECTION FEES. FO Foam System (Tamper) 8. THE ELECTRICAL CONTRACTOR SHALL PROVIDE DEDICATED POWER FOR THE NEW FIRE PUMP AT NEW LOCATION. REFER TO ME DRAWINGS. FP Fire Protection (Sprinklers) W Wall Mounted 7. THROUGHOUT CONSTRUCTION, THE CONTRACTOR SHALL MAINTAIN ON-SITE A SET OF THE MOST CURRENT WORKING DRAWINGS THAT FPCG Fire Protection Consulting WC Wet Chemical 9. STORAGE IN SPRINKLERED AREAS SHALL BE MAINTAINED A MINIMUM OF 18 INCHES BELOW THE SPRINKLER DEFLECTORS AND A MAXIMUM OF 8 BEAR THE APPROVAL MARK OF THE AHJ. WHERE FIELD MODIFICATIONS ARE MADE TO THE SYSTEM, THEY SHALL BE RECORDED ON Group WF Water Flow FEET AFF. HA Halon WP Weather Proof THE WORKING DRAWINGS FOR INCORPORATION INTO THE PROJECT AS-BUILT DRAWINGS. THE CONTRACTOR SHALL PROVIDE AS-BUILT HC Horn Circuit WS Wet System 10. NO HAZARDOUS MATERIALS STORAGE WILL BE PERMITTED IN THIS BUILDING. DRAWINGS AS PART OF THE PROJECT CLOSE-OUT DOCUMENTS AND TRAINING.

11. SEE ARCHITECTURAL PLANS FOR FIRE-RESISTANCE RATED WALL AND FLOOR/CEILING LOCATIONS. PENETRATIONS TROUGH RATED WALLS AND FLOOR/CEILINGS SHALL BE SEALED WITH A LISTED PENETRATION ASSEMBLY SYSTEM PER ARCHITECTURAL DRAWINGS.

12. PROVIDE EACH LEVEL WITH FLOOR CONTROL VALVE ASSEMBLIES. CONNECTION TO FIRE ALARM CONTROL PANEL BY-OTHER.

13. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

14. SPRINKLER PIPE AND HEAD LOCATIONS SHOWN ON THIS DOCUMENT ARE SUGGESTED LOCATIONS INTENDED TO SHOW SCOPE OF WORK. IT IS THE SELECTED SPRINKLER CONTRACTORS RESPONSIBILITY TO COORDINATE WITH MECHANICAL, STRUCTURAL AND OTHER TRADES DURING CREATION OF SHOP DRAWINGS. QUANTITY OF HEADS SHOWN ON THIS DOCUMENT NOT INTENDED TO ENCOMPASS ALL HEADS REQUIRED TO ACCOMPLISH CODE COMPLIANT COVERAGE.

NEW DOUBLE CHECK BACKFLOW PREVENTER IN NEW VAULT. EXISTING 6" FIRE RE DETAIL 2 THIS SHEET WATER LINE 307 Marshall Street San Antonio, Texas Site Plan and General Notes Villa Tranchese Apartments San Antonio Housing Authority

EXISTING R-2 BUILDING 24"x32" HINGED MANWAY UPGRADE SPRINKLER SYSTEM TO INCLUDE BUILDING WIDE SPRINKLER PROTECTION.

PROVIDE NEW SPRINKLER STANDPIPE IN CENTRAL STAIRWELL AND IN EXISTING STANDPIPE RISER CHASES ADJACENT TO PHASE B - Fire Protection Systems & Life Safety Renovations STAIRWELLS, INCLUDING FLOOR CONTROL VALVES. PROVIDE NEW FIRE PUMP TO SUPPLY SYSTEMS.

18"

FLOW FLOW

3/4" DETECTOR METER w/ 2 SHUT-OFFS VALVES AND BACKFLOW PREVENTER GALVANIZED ALL-THREAD RETAINER ROD (TYP.)

1/4" THICK CHECKER PLATE FRAME AND WEIGHT COVER. PRIMERED AND PAINTED WITH (1) LBS COAT OF INDUSTRIAL BLACK ENAMEL PAINT.

EXISTING PUBLIC WATER MAIN OS&Y GATE VALVE (TYP.) REVISIONS: PRECAST CONCRETE VAULT

DUCTILE IRON OR C-900 STUB-OUT

FLOW

These documents and the ideas incorporated herein as instruments of professional service are the property UNI-FLANGE of Raba-Kistner Consultants, Inc. and are not to be (TYP.) used in whole or part without the written authorization of Raba-Kistner Consultants, Inc.

GALVANIZED ANGLE 12"x12" SUMP WITH SUPPORT (TYP) CAST IRON GRATE

0 10' 20' 40' SHEET NO. 1 OVERALL SITE PLAN 2 PROPOSED NEW BACKFLOW PREVENTER Scale: 1" = 20' NORTH SCALE:3/16" = 1'-0" FS 100 UP 1 FIRST FLOOR PLAN SCALE: 3/32" = 1'-0" STOR STOR exam room Living/Dining exam room t/r t/r interview room Bedroom 2 room provide new 60htz electric basement BASEMENT PLAN SCALE: 1/8" = 1'-0" chase PROVIDE FIRE-RATED PATCH and all associated 1000gpm at 150psi Bedroom REMOVE WINDOW AND interview appurtenances WITH NEW. REPLACE RISER AND REPLACE EXISTING STANPIPE DEMO EXISTING STANDPIPE REPLACE WITH NEW RISER AND FEED LINE HOSE VALVES ON CABINET. DEMO EXISTING HOSE fire pump EACH LEVEL. basement chase t/r t/r DISCHARGE LINE TO NEW PUMP ROOM NEW FIRE TIE-IN NEW PUMP STANDPIPE FEED FS 201 1 conference 3 room mech. rm DISCONNECT AND REMOVE header pump test New fire ONCE NEW FIRE PUMP IS Office Office EXISTING FIRE PUMP Service Area G Way COMMISSIONED community LOCATION UP Office room Office Existing Alarm Bell Existing Area Drain

DOWN TAP EXISTING SUPPLY FOR STOR MAIL M.RR Office pit NEW FIRE PUMP STOR Waiting JAN DEMO EXISTING STANDPIPE (REMOVED) 1 1 TEL. Office W.RR 2 Rear Foyer vestibule rear DEMO EXISTING 6" SUCTION LINE Entry Foyer RISER AND CABINET. DEMO EXISTING STANDPIPE WITH FLOOR CONTROL VALVES AT EACH BUILDING LEVEL AND HOSE NEW SPRINKLER AND STANDPIPE Elevators vestibule front VALVES ON INTERMEDIATE LANDINGS. FS 202 3

Stairs FCVA NEW FEED TO EAST DROPPED CEILING

STANDPIPE IN DOWN

UP FCVA Recreation Room RISER NEW STANDPIPE SPRINKLER SYSTEM STOR Kitchen WITH NEW. REPLACE RISER AND REPLACE EXISTING STANPIPE HOSE VALVES ON CABINET. DEMO EXISTING HOSE EACH LEVEL. mech. 1. 2. KEY NOTES: CONNECTION TO EXISTING WATER MAIN. ISOLATION VALVES SHALL BE EQUIPPED WITH TAMPER PROVIDE NEW 6 INCH WYE STRAINER WITH TWO ISOLATION VALVES ON PUMP SUCTION LINE AT SWITCHES. TRACING CIRCUITS ON EACH FLOOR. RAYCHEM ACS-30 OR EQUIVALENT. ADD NEW MULTIPOINT HEAT TRACING MAIN CONTROL PANEL TO SUB PANELS FOR Meeting rm. Meeting rm. NORTH UP # as instruments of professional service are the property used in whole or part without the written authorization REVISIONS: These documents and the ideas incorporated herein of Raba-Kistner Consultants, Inc. and are not to be Raba Kistner Consultants, Inc. San Antonio, Texas 78249 Basement and First Level Plans 12821 West Golden Lane FS 200 of Raba-Kistner Consultants, Inc. P 210 :: 699 9090 F 210 :: 699 6426 TBPE Firm F-3257 SHEET NO. San Antonio Housing Authority www.rkci.com PHASE B - Fire Protection Systems & Life Safety Renovations Villa Tranchese Apartments 307 Marshall Street San Antonio, Texas KEY NOTES: #

1. COORDINATE PIPE AND SPRINKLER LOCATION WITH EXISTING MECHANICAL. 2. RESTROOM NOT REQUIRING SPRINKLER PROTECTION Raba Kistner Consultants, Inc. 3. NON ACCESSIBLE CONCEALED SPACE 4. FREE STANDING CLOSET 12821 West Golden Lane 5. PIPE AND INSULATION MUST BE WITHIN 6 INCHES OF CEILING. USE LOW PROFILE HANGER TO BRING San Antonio, Texas 78249 INSULATED PIPE AS CLOSE TO CEILING AS POSSIBLE. 6. ADD NEW HEAT TRACING CONTROL PANEL FOR HEAT TRACING CIRCUITS ON EACH FLOOR. RAYCHEM www.rkci.com ACS-PCM-5 OR EQUIVALENT. P 210 :: 699 :: 9090 7. LOCATE PIPING IN UNITS AS CLOSE TO WALLS AS POSSIBLE. USE LOW PROFILE HANGER TO BRING F 210 :: 699 :: 6426 PIPE AS CLOSE TO CEILING AS POSSIBLE. TBPE Firm F-3257

DOORS TO CEILING TYP 5 PROVIDE DOOR STOP TO EXISTING HOSE CABINET. DEMO EXISTING UP PROTECT PIPE STANPIPE RISER AND REPLACE WITH NEW. REPLACE HOSE VALVES ON EACH LEVEL.

1 307 Marshall Street

3 San Antonio, Texas 3

1 Villa Tranchese Apartments 4 Upper Level and Enlarged Unit Plan San Antonio Housing Authority 2

2 7 PHASE B - Fire Protection Systems & Life Safety Renovations ENLARGED UNIT PLAN VIEW PARTIAL BUILDING SECTION 2 SCALE: 3/16" = 1'-0" 3 SCALE: 1/4" = 1'-0"

RUBBISH CHUTE REQUIRES SPRINKLER PROTECTION PER IBC/IFC INSTALL PIPE IN 903.2.11.2 AND IEBC 904.2 SOFFIT SYSTEM WITH PROVIDE SPRINKLERS AT THE TOP MOST CHUTE, TERMINATION FULLY CONCEALED POINT OF CHUTE AND AT INTERMEDIATE LEVELS. SPRINKLER HEADS

Jan.Clos. 6

FCVA Laundry Rm PROVIDE SPRINKLER AT TOP OF STAIRWELL AND BENEATH BOTTOM LANDING.

Stairs UP

DEMO EXISTING STANDPIPE Elevators

DOWN DOORS TO CEILING TYP EXISTING HOSE CABINET. DEMO EXISTING CHASE OR PIPE ENCLOSURE. PROVIDE DOOR STOP TO EXISTING HOSE CABINET. DEMO EXISTING STANPIPE RISER AND REPLACE WITH NEW. PROVIDE HEAT TRACING TO PROTECT UP PROTECT PIPE STANPIPE RISER AND REPLACE WITH NEW. CHASE OR PIPE ENCLOSURE. REPLACE HOSE VALVES ON EACH LEVEL. PIPE FROM FREEZING REPLACE HOSE VALVES ON EACH LEVEL. PROVIDE HEAT TRACING TO REVISIONS: PROTECT PIPE FROM FREEZING

These documents and the ideas incorporated herein as instruments of professional service are the property of Raba-Kistner Consultants, Inc. and are not to be used in whole or part without the written authorization of Raba-Kistner Consultants, Inc.

1 PLAN LEVEL 2 THRU 11 SHEET NO. SCALE: 3/32" = 1'-0" TEN (10) FS 201 1 PENTHOUSE PLANS SCALE: 1/4" = 1'-0" 3 BUILDING SECTION SCALE: 3/16" = 1'-0" ROOF MANIFOLD MAY BE REQUIRED HERE PENTHOUSE FEED

1 9'-22" BASEMENT FEED 1ST FLOOR FEED MACH.RM. FEED

6'-0" FCVA FCVA 1ST FLOOR CONTROL BASEMENT CONTROL

6'-0" FCVA FCVA FCVA FCVA FLOOR CONTROL EACH LEVEL 2ND FLOOR CONTROL FIRE PUMP FROM NEW 10TH FLOOR FEED MAIN 11TH FLOOR FEED MAIN 2ND FLOOR FEED MAIN TYPICAL EACH FLOOR NEW WET SPRINKLER CONTROL VALVES STANDPIPE WITH FLOOR FIRE MAIN EXISTING 6"

FCVA 2 PENTHOUSE PLANS SCALE: 1/4" = 1'-0" FCVA as instruments of professional service are the property used in whole or part without the written authorization REVISIONS: These documents and the ideas incorporated herein of Raba-Kistner Consultants, Inc. and are not to be Raba Kistner Consultants, Inc. San Antonio, Texas 78249

Penthouse Plan and Building Section 12821 West Golden Lane FS 202 of Raba-Kistner Consultants, Inc. P 210 :: 699 9090 F 210 :: 699 6426 TBPE Firm F-3257 SHEET NO. San Antonio Housing Authority www.rkci.com PHASE B - Fire Protection Systems & Life Safety Renovations Villa Tranchese Apartments 307 Marshall Street San Antonio, Texas Raba Kistner Consultants, Inc. 12821 West Golden Lane San Antonio, Texas 78249 www.rkci.com P 210 :: 699 :: 9090 F 210 :: 699 :: 6426 TBPE Firm F-3257

DISCHARGE SUPPLY SUPPLY DISCHARGE TEST HEADER

BY-PASS BYPASS

TO TEST HEADER

1 2'-02"

PUMP ROOM SECTION PUMP ROOM SECTION 2 SCALE: 1/2" = 1'-0" 1 SCALE: 1/2" = 1'-0"

2'-6"

TO FIRE PUMP 1'-61" TEST HEADER 2 307 Marshall Street 2 San Antonio, Texas

PIPE TO EXISTING AREA DRAIN

1 1 Villa Tranchese Apartments 1'-92" 4'-32" Pump Room and Sprinkler Details San Antonio Housing Authority

6X4 CONCENTRIC 6" PUMP REDUCER DISCHARGE PHASE B - Fire Protection Systems & Life Safety Renovations 2'-6"

6" PUMP INLET 1

JOCKEY PUMP

SKID MOUNTED FIRE PUMP SINGLE STAGE HORIZONTAL SPLIT CASE 60 HZ ELECTRIC MOTOR DRIVEN ELECTRIC MOTOR 1000 GPM, 150PSI 125Hp

REVISIONS: FIRE PUMP AND JOCKEY PUMP CONTROLLERS

FLOOR CONTROL VALVE ASSEMBLY Sprinkler Riser, provide pressure gauge at top

2" Drain Riser These documents and the ideas incorporated herein as instruments of professional service are the property Grooved Butterfly Valve of Raba-Kistner Consultants, Inc. and are not to be used in whole or part without the written authorization Grooved Check Valve of Raba-Kistner Consultants, Inc. Riser Manifold Flow Switch Water Gauge Combination Inspectors Test and Drain Valve To Sprinklers SHEET NO.

1 TYPICAL FLOOR CONTROL VALVE ASSEMBLY 2 ENLARGED PUMP ROOM PLAN NTS SCALE: 1"=1'-0" FS 300 Raba Kistner Consultants, Inc. 12821 West Golden Lane San Antonio, Texas 78249 www.rkci.com P 210 :: 699 :: 9090 F 210 :: 699 :: 6426 TBPE Firm F-3257

HEAT TRACE PIPE SECTION HEAT TRACE POWER CONNECTION HEAT TRACE DETAIL 10 NTS 10 NTS 10 NTS

GROOVED TEE WITH RIGID Primary and OR FIRELOCK GROOVED Secondary Air Vent COUPLINGS Air Discharge Orifice 1" Arm Over Valves

Connection to Air Ejector Device

WET-PIPE SPRINKLER LESS THAN 36" Highest Remote Wet SYSTEM BRANCH LENGTH OF RISER STEEL PIPE RISER NIPPLE LINE THREADED NIPPLE Pressure Guage Sprinkler Main REDUCING COUPLING RIGID OR FIRELOCK GROOVED COUPLING ON WELD GROOVED OUTLET CEILING TILE OR STANDARD STYLE GYP BOARD RECESSED OR CROSS MAIN CEILING CONCEALED SPRINKLER

ARMOVER DETAIL RISER DETAIL AIR EJECTOR DETAIL 307 Marshall Street San Antonio, Texas 10 NTS 11 NTS 12 NTS Sprinkler System Details Villa Tranchese Apartments San Antonio Housing Authority

EXISTING BRICK

BRANCH LINE BRANCH LINE 1" DROP SOFI-SEAL OR SIMILAR 1" OUTLET 48" OR WIDER DUCT OR UL/FM APPROVED OBSTRUCTION 1"x0'-2" NIPPLE CONCEALMENT SYSTEM

DRY HORIZONTAL PHASE B - Fire Protection Systems & Life Safety Renovations 1" x ½" CAST IRON REDUCING 90° 1" CAST IRON 90° EL SIDEWALL WITH LOW PROFILE UPRIGHT SPRINKLER - 1" ARM OVER CONCEALED ESCUTCHEON DEFLECTOR 1" CAST IRON TEE CORE DRILL THRU MIDDLE THIRD OF 1" to 6" BELOW DUCT and 6" CONCRETE BEAM. VERIFY LOCATION FROM SIDE OF OBSTRUCTION 1" DROP OF REBAR REINFORCEMENT PRIOR TO PENETRATING. CONTRACTOR 1"x½" REDUCER COUPLING SHALL ENSURE CORRECT INSTALLATION TO PREVENT PIPES RECESSED PENDENT FROM FREEZING. UPRIGHT SPRINKLER

ARMOVER DETAIL ARMOVER DETAIL HANGER DETAIL DRY SIDEWALL INSTALLATION DETAIL 7 NTS 8 NTS 8 NTS 8 NTS

LC 150 SEALANT OPTIONAL BACKER ROD USED AS FORMING CONCRETE OR MATERIAL CONCRETE BLOCK WALL

CONCRETE TEE CONCRETE TEE CONSTRUCTION CONSTRUCTION REVISIONS: LC150 Sealant SAMMY EXPRESS SIDEWINDER Mod. No. SWC20 STEEL SPRINKLER PIPE STEEL, IRON, AND COPPER PLACE IN MIDDLE 3RD OF SAMMY EXPRESS SIDEWINDER PIPE OR CONDUIT MINERAL WOOL BATT, NOM. 4 PCF, TO ANNULUS RANGING FROM FILL THICKNESS RECESSED FROM BOTH BEAM ONLY Mod. No. SWC20 POINT CONTACT TO 1/2" SIDES TO ACCOMMODATE FILL MATERIAL 3/8" ZINC PLATED MAX. PLACE IN MIDDLE 3RD OF ALL THREAD ROD BEAM ONLY RATED GYPSUM WALL BOARD PENETRANT MAXIMUM SEALANT MINERAL ANNULUS ASSEMBLY TRADE SIZE DEPTH WOOL MINIMUM MAXIMUM 3/8" ZINC PLATED ROD STEEL OR IRON 24" 1/2" 3" POINT CONTACT 2" STEEL OR IRON 4" 1" N/A POINT CONTACT 1-1/2" PIPE (OR ANGLE) WITH END 3/8" ZINC ALL THREAD COPPER 4" 1/2" 3" POINT CONTACT 2" CAP OR SLIP STOP CLAMP These documents and the ideas incorporated herein PLATED ROD as instruments of professional service are the property ADJUSTABLE RING HANGER of Raba-Kistner Consultants, Inc. and are not to be used in whole or part without the written authorization 1 OR 2 HOUR RATED FIRESTOP FOR METALLIC PIPING 3 HOUR RATED FIRESTOP FOR METALLIC PIPING of Raba-Kistner Consultants, Inc. THROUGH GYPSUM BOARD WALLS USING LC150 THROUGH CONCRETE WALLS USING LC150 SEALANT ADJUSTABLE RING HANGER SEALANT SYSTEM: WL-1090 OR APPROVED EQUAL SYSTEM: C-AJ-1213 OR APPROVED EQUAL

FIRE STOP DETAILS HANGER DETAIL IN BASEMENT HANGER DETAIL IN BASEMENT 14 NTS 6 NTS 5 NTS

SHEET NO. FS 301