<<

2018 IBC Use of & Smoke Separations

Course Description

. This seminar addresses the provisions of the 2018 International Building Code® (IBC®) 2018 IBC Use of Fire and regarding the use of fire and smoke separations. Smoke Separations

Based on the 2018 International Building Code® (IBC®)

2018 IBC Use of Fire and Smoke Separations 2

12

Objectives Course Overview

. Upon completion, you will be better able to: • Module I – Fire and Smoke Protection Concepts 1. Identify the general types of fire and smoke separations. • Module 2 – Types of Fire and Smoke Separations 2. Identify those specific components that make up fire and smoke separations. • Module 3 – Fire and Smoke Separation Components 3. Determine where separations are required. • Module 4 – Fire and Smoke 4. Determine where separations are permitted as Separation Locations alternatives to other requirements.

2018 IBC Use of Fire and Smoke Separations 3 2018 IBC Use of Fire and Smoke Separations 4

34

Copyright 2017 International Code Council 1 2018 IBC Use of Fire & Smoke Separations

Fire and Smoke Protection Concepts . IBC uses fire and smoke assemblies and protectives for a variety of purposes: . Structural integrity maintenance.

Module 1 . Fire spread limitation. . Means of egress protection. Fire and Smoke Protection . Radiant heat (exposure) protection. Concepts . Smoke movement restriction.

2018 IBC Use of Fire and Smoke Separations 6

56

Structural Integrity Structural Fire Resistance

. Larger and/or high-hazard . Structural fire resistance intended to protect buildings require specified fire- structural integrity of building elements during resistance levels for structural . members. . Elements include: . IBC Chapter 6 “Type of Construction.” . Structural frame members. . Bearing walls. . Floor construction. . Roof construction.

2018 IBC Use of Fire and Smoke Separations 7 2018 IBC Use of Fire and Smoke Separations 8

78

Copyright 2017 International Code Council 2 2018 IBC Use of Fire & Smoke Separations

Fire Spread Limitation Egress Protection . Multiple conditions utilize fire-resistant separations . Fire-resistance-rated and/or smoke- to limit fire spread. resistant construction is often mandated. . Complete and partial fire separations either mandated, or provided as an alternative, to address a variety of . “Exit” portion of the means of egress is issues: generally hazardous occupancy or operations. typically where such protection must be afforded. . Vertical and/or horizontal separations typically require opening protectives and other components to achieve . Means of egress fire protection allows full separation. extended travel in large areas or multistory buildings.

2018 IBC Use of Fire and Smoke Separations 9 2018 IBC Use of Fire and Smoke Separations 10

910

Radiant Heat Protection Smoke Movement Restriction

. To prevent building-to- . Smoke-resistant construction often mandated building fire spread due where occupants incapable of self preservation to radiant . and protect-in-place methods are employed. . Institutional . Fire-resistance-rated exterior walls required . Hospitals, nursing homes based on proximity to lot . Prisons, jails, reformatories lines and other buildings on the same site. . Other conditions require separation that includes both . Fire separation distance smoke- and fire-resistance.

2018 IBC Use of Fire and Smoke Separations 11 2018 IBC Use of Fire and Smoke Separations 12

11 12

Copyright 2017 International Code Council 3 2018 IBC Use of Fire & Smoke Separations

Fire Protection Concepts

. List the IBC’s five primary protection concepts for fire- and smoke-resistant construction:

. Structural integrity maintenance. . Fire spread limitation. Module 2 . Means of egress protection. . Radiant heat (exposure) protection. Fire and Smoke Separation . Smoke movement restriction. Types

2018 IBC Use of Fire and Smoke Separations 13

13 14

Fire-resistance-rated Separations Fire-resistance-rated Separations

. IBC has variety of . Fire walls. fire-resistance-rated separation “types”. . Fire barriers. . Each unique . Fire partitions. separation type . Smoke barriers. serves a distinct purpose as . Exterior walls. reflected in its . Horizontal assemblies. design details.

2018 IBC Use of Fire and Smoke Separations 15 2018 IBC Use of Fire and Smoke Separations 16

15 16

Copyright 2017 International Code Council 4 2018 IBC Use of Fire & Smoke Separations

Fire Walls Fire Walls – 706.1.1, Exception 2 . Most complex and protective fire separation. . Typically selected by the designer to provide an alternative solution to code compliance, fire wall creates separate buildings in the same structure. . Oversize buildings . Incompatible use separations . A fire wall at the lot line between two adjacent buildings is permitted where a party wall was once required. . Fire walls required to be 2-, 3- or 4-hour assemblies.

2018 IBC Use of Fire and Smoke Separations 17 2018 IBC Significant Changes 18

17 18

Fire Barriers Fire Partitions . Most common means of separating portions of a . Required where a limited degree of fire and building with fire-resistance-rated construction. smoke protection is warranted. . Used under both mandatory and optional conditions, . Typical in locations where separation is important in fire barriers divide a building into separate areas for a the initial stages of building evacuation. variety of purposes where full separation is desired. . Fire partitions are required to be minimum 1-hour . Are “vertical” assemblies. assemblies

. Fire barriers must be 1-, 2-, 3- or 4-hour assemblies. . Allowances for ½-hour assemblies under specified conditions.

2018 IBC Use of Fire and Smoke Separations 19 2018 IBC Use of Fire and Smoke Separations 20

19 20

Copyright 2017 International Code Council 5 2018 IBC Use of Fire & Smoke Separations

Smoke Barriers Exterior Walls

. Mandated where a high degree of both fire and . Rated exterior walls provide smoke protection is desired. separation from internal or external . Used to create refuge compartments that allow fires. occupants to safely await assistance or rescue. . Also often provide for the protection of outdoor exit travel. . Must be minimum 1-hour assemblies while also providing a high degree of smoke resistance. . Must be minimum 1-, 2- or 3-hour assemblies if within fire separation distance.

2018 IBC Use of Fire and Smoke Separations 21 2018 IBC Use of Fire and Smoke Separations 22

21 22

Horizontal Assemblies Smoke-resistant Separations

. Typically used with fire-resistance-rated wall . In addition to the use of smoke barriers, the IBC assemblies to provide compartmentation in also recognizes smoke partitions as a means to multistory buildings. resist the passage of smoke. . In most cases, the ceiling and floor work together, as . Smoke partitions required where smoke movement of is well as independently, to provide the intended a concern; however, fire is not primary consideration. separation. . Smoke partitions are not required to have a fire- . Required to be minimum ½-, 1-, 2-, 3-, or 4-hour fire- resistance rating. resistance-rated assemblies.

2018 IBC Use of Fire and Smoke Separations 23 2018 IBC Use of Fire and Smoke Separations 24

23 24

Copyright 2017 International Code Council 6 2018 IBC Use of Fire & Smoke Separations

Prescriptive Separations Separation Types

. Mandated where limited degree of separation is 1. Horizontal assemblies required to be minimum ½-, desired. (IBC Table 721.1) 1-, 2-, 3-, or 4-hour fire-resistance-rated assemblies. . Not required to be tested and listed assemblies, these TTRUE or F separation elements adequately serve a specific need. 2. A smoke partition must have a fire resistance rating of 0 hours. . Applications include: . Gypsum board. 3. All exterior walls are required to be minimum 1-, 2- or . Nonrated floor construction. 3-hour fire-resistance-rated assemblies. . Construction capable of restricting smoke migration. TFALSE or F

2018 IBC Use of Fire and Smoke Separations 25 2018 IBC Use of Fire and Smoke Separations 26

25 26

Separation Types

4. Fire walls must have a minimum fire resistance rating of 2 hours.

5. Exterior walls, if within the fire separation distance, must have a rating of __<,1 2 __ or 3 hours. Module 3

6. IBC Table 721.1 allows the use of prescriptive materials in lieu of listed assemblies. Components of Fire and Smoke Separations

2018 IBC Use of Fire and Smoke Separations 27

27 28

Copyright 2017 International Code Council 7 2018 IBC Use of Fire & Smoke Separations

Vertical Elements Vertical Elements . A variety of different walls and partition . Wall assemblies such as fire walls, fire assemblies are established in the IBC to provide barriers, fire partitions, smoke barriers varying degrees of fire and/or smoke separation. and exterior walls must be provided with fire-resistance ratings as . In addition to vertical assemblies that are tested determined in accordance with ASTM and listed as fire-resistance-rated, modified E119 or UL 263, or meet prescriptive assemblies and prescriptive-based separation specifications. elements are selectively addressed throughout . Required fire-resistance ratings vary and are required based on the intended the code. Table 721.1 purpose of the separation.

2018 IBC Use of Fire and Smoke Separations 29 2018 IBC Use of Fire and Smoke Separations 30

29 30

Vertical Elements Horizontal Elements

. Partial assemblies based on listed assemblies . Horizontal assemblies are also tested and listed are also recognized in limited applications, assemblies that resist the spread of fire vertically. typically where the potential hazard is assumed to exist only on one side of the separation . Fire-resistance-rated floors and floor/ceiling element. assemblies can provide varying degrees of fire- resistance. . Prescriptive Control roomsseparation elements are also occasionally Areas ofmandated, Refuge where a specific . Non-rated horizontal elements also provide a material Incidentalis identified spaces as the minimum level of significant level of separation and are regulated separation Shaft required. enclosures under a variety of conditions. (See 714.5 Penetrations and . i.e. 5/8 inch Type X Gyp Board between garage and living space above 717.6.3 Ducts) (Section 406.3.4.1)And more

2018 IBC Use of Fire and Smoke Separations 31 2018 IBC Use of Fire and Smoke Separations 32

31 32

Copyright 2017 International Code Council 8 2018 IBC Use of Fire & Smoke Separations

Vertical/Horizontal Combination Doors . Openings require protection as part of the overall package of fire and/or Apartment . Vertical and horizontal smoke protection. 2-hour Group R-2 elements used to . In most cases, fire-protection-rated door 1-hour completely separate one assemblies are mandated in fire- area from another. separation assemblies. Fire Separation Distance Separation Fire . Table 716.1(2) provides the required Day care Restaurant

None ratings and markings for most Group E Group A-2 conditions.

. In some cases they are also individually identified based on the specific separation. Elevation View: Type IIIA, A/S

2018 IBC Use of Fire and Smoke Separations 33 2018 IBC Use of Fire and Smoke Separations 34

33 34

Doors Windows . In a few cases, a prescriptive means of door protection is mandated. . For example, a solid-wood or honeycomb core doors . Windows are typically regulated in the same of a specified thickness might be established as the manner as doors. minimum required door. . Fire-protection-rated glazing, . At times, the code does not regulate door . Fire-resistance-rated glazing. assemblies in a fire rated assembly. . Fire-resistance-rated glazing is regulated in . The most common examples are: much the same manner as fire-resistance-rated . fire-resistance-rated exterior walls where opening protection is not required wall assemblies . Loadbearing walls protected per Table 601

2018 IBC Use of Fire and Smoke Separations 35 2018 IBC Use of Fire and Smoke Separations 36

35 36

Copyright 2017 International Code Council 9 2018 IBC Use of Fire & Smoke Separations

Windows Windows

Fire-resistance-rated glazing is regulated in much the same manner as fire-resistance-rated wall assemblies, including . There are situations in the code where nonrated testing in accordance with ASTM E 119 or UL 263. glazing is permitted in fire/smoke separation Wall Test walls, such as: FIRE RESISTIVE ASTM E119/NFPA 263 . where security glazing is needed - Group I-3, . where smoke is the only concern - corridor walls in Group I-2, or . where fire-resistance-rated exterior walls are permitted with unprotected openings.

2018 IBC Use of Fire and Smoke Separations 37 2018 IBC Use of Fire and Smoke Separations 38

37 38

Penetrations Joints . Fire-resistant joint systems are REQUIRED where joints occur in separation walls requiring . Penetrations must typically be protected by opening protection. systems rated to the same level as the element penetrated. . Joint protection is also often required at the voids  Through penetration of Membrane Penetration systems between curtain wall assemblies and: . Nonfire-resistance-rated horizontal assemblies . Prescriptive methods of penetration protection are . Fire-resistance-rated horizontal assemblies also established.  steel pipe penetrations - protect annular space with concrete, grout or

2018 IBC Use of Fire and Smoke Separations 39 2018 IBC Use of Fire and Smoke Separations 40

39 40

Copyright 2017 International Code Council 10 2018 IBC Use of Fire & Smoke Separations

Air Movement Components . Fire dampers, smoke dampers, combination dampers, ceiling radiation dampers and corridor 1. All fire resistive assemblies must be listed in dampers are selectively required in ducts and accordance with ASTM E119 or UL 263. TFALSE or F air openings in separation elements. 2. Horizontal fire resistive elements include all of the . Dampers may be omitted in a variety of following except: situations where their use has been determined a) Floor-ceiling assemblies to be unnecessary. b) Roof-ceiling assemblies . Non-rated floor assemblies may still require c) Floor assemblies protection of penetrations (Section 717.6.3) d) Fire walls .

2018 IBC Use of Fire and Smoke Separations 41 2018 IBC Use of Fire and Smoke Separations 42

41 42

Components

3. Name two circumstances where non-rated glazing may be installed in separation walls.

4.1. where In many security cases, glazing the IBC is needed, uses both vertical and 2. where smoke is the only concern, or 3. wherehorizontal fire-resistance-rated elements in order exterior to completely walls are Module 4 permittedseparate withone unprotectedarea from another. openings. TRUET or F 5. Fire-resistant joint systems are mandated Fire and Smoke Separation where joints occur in separation walls requiring opening protection. TTRUE or F Locations

2018 IBC Use of Fire and Smoke Separations 43

43 44

Copyright 2017 International Code Council 11 2018 IBC Use of Fire & Smoke Separations

Separation Locations

. Building Size, Use and Components . Means of Egress . Fire Limitation Features . Special Building Types . Special Occupancies and Uses . Special Building Features Building Size, Use . Hazardous Uses and Components

2018 IBC Use of Fire and Smoke Separations 45

45 46

Building Height & Area – 503.1 Building Height & Area – 503.1 • Use of fire wall now limited to only the determination of permissible types of construction, based upon Plan View allowable building height and area. • Designer option • Fire wall no longer permitted as means to create separate, smaller buildings for other purposes of the

code (nonsprinklered) (nonsprinklered)

2018 IBC Use of Fire and Smoke Separations 47 2018 IBC Use of Fire and Smoke Separations 48

47 48

Copyright 2017 International Code Council 12 2018 IBC Use of Fire & Smoke Separations

Fire Wall Application for Building Fire Wall Application for Building Height and Area – Example #1 Height and Area – Example #2

Area “A” Area “B” Area “C” Area “C” Area “C” Area “B” Group A-3 Group M Group B Group B Group A-3 Group M 4,000 sq. ft. 10,000 sq. ft. 15,000 sq. ft. 4,000 sq. ft. 10,000 sq. ft. 15,000 sq. ft.

No Fire Barrier Wall

For SI: 1 square foot = 0.0929 m2. For SI: 1 square foot = 0.0929 m2.

2018 IBC Fire & Smoke Protection Features 49 2018 IBC Fire & Smoke Protection Features 50

49 50

706.1.1 Party Walls – Exception #2 Building Height & Area – 706.1.1 . Fire walls nor party walls, are required to be . Required use of a party wall (fire wall) at the lot line used on lot lines dividing a building for between two adjacent buildings where there is joint ownership purposes. service between the buildings is no longer required where: 1. The aggregate height and area of the portions of the building located on both sides of the lot line do not exceed the maximum allowed, and 2. Dedicated easements and contractual agreements that allow either owner access to the other portion of the building to maintain fire and safety systems are provided to the building official.

2018 IBC Significant Changes 51 2018 IBC Significant Changes 52

51 52

Copyright 2017 International Code Council 13 2018 IBC Use of Fire & Smoke Separations

Fire Wall Ratings – Table 706.4 Fire Walls . Rating requirements based on the buildings’ . Provide variety of other construction type(s) and occupancy classification(s). alternative solutions to the designer: . Multiple types of construction. . Reduction/elimination of fire protection features. . In IFC, fire walls may be used to reduce fire flow requirements.

2018 IBC Use of Fire and Smoke Separations 53 2018 IBC Use of Fire and Smoke Separations 54

53 54

Separated Occupancies –Table 508.4 Separated Occupancies – 508.4.4.1 f

. In a mixed-occupancy building, fire barriers and/or horizontal assemblies are utilized under the separated occupancies method.

. Table 508.4 establishes the minimum required fire-resistance for pairs of incompatible

S = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1. occupancies. NS = Buildings not equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1. N= No separation requirement. NP = Not permitted. a. See Section 420. b. The required separation from areas used only for private or pleasure vehicles shall be reduced by 1 hour but not to be less than 1 hour. c. See Section 406.3.2. d. Separation is not required between occupancies of the same classification. e. See Section 422.2 for ambulatory care facilities. f. Occupancy separations that serve to define fire area limits established in Chapter 9 for requiring fire protection systems shall also comply with Section 707.3.10 and Table 707.3.10 in accordance with Section 901.7.

2018 IBC Use of Fire and Smoke Separations 55 2018 IBC Use of Fire and Smoke Separations 56

55 56

Copyright 2017 International Code Council 14 2018 IBC Use of Fire & Smoke Separations

Incidental Uses – 509.4.1 Incidental Uses – Table 509

ROOM OR AREA SEPARATION AND/OR PROTECTION

Furnace room where any piece of equipment is over 400,000 Btu per hour input 1 hour or provide automatic sprinkler system

Rooms with where the largest piece of equipment is over 15 psi and 10 horsepower 1 hour or provide automatic sprinkler system . Where an incidental use as listed on Table 509 machinery room 1 hour or provide automatic sprinkler system 1 hour in Group B, F, m, S and U occupancies Hydrogen fuel gas rooms, not classified as Group H is present, it must selectively be separated from 2 hours in Group A, E, I and R occupancies Incinerator rooms 2 hours and provide automatic sprinkler system other portions of the building by fire barrier Paint shops, not classified as Group H, located in occupancies other than Group H 2 hours; or 1 hour and provide automatic sprinkler system In group E occupancies, laboratories and vocational shops not classified as Group H 1 hour or provide automatic sprinkler system

and/or horizontal assembly as established by In Group I-2 occupancies, laboratories not classified as Group H 1 hour and provide automatic sprinkler system

In ambulatory care facilities, laboratories not classified as Group H 1 hour or provide automatic sprinkler system

Table 509. Laundry rooms over 100 square feet 1 hour or provide automatic sprinkler system

In Group I-2, laundry rooms over 100 square feet 1 hour

Group I-3 cells and Group I-2 patient rooms equipped with padded surfaces 1 hour

In Group I-2, physical plant maintenance shops 1 hour

In ambulatory care facilities or Group I-2 occupancies, wast and linen collection rooms with containers . In some cases, an alternative method of 1 hour that have an aggregate bolume of 10 cubic feet or greater

In other than ambulatory care facilities and Group I-2 occupancies, wast and linen collection rooms 1 hour or provide automatic sprinkler system protection is permitted by the table. over 100 square feet

In ambulatory care facilities or Group I-2 occupancies, storage rooms greater than 100 square feet 1 hour

Stationary storage batter systems having an energy capacity greater than the threshold quantity 1 hour in Group B, F, M, S and U occupancies specified in Table 1206.2 of the International Fire Code 2 hours in Group A, E, I and R occupancies

See Sections 110.26 through 110.34 and Sections 450.8 Electrical installations and transformers through 450.48 of NFPA 70 for protection and separation

2018 IBC Use of Fire and Smoke Separations 2018 IBC Use of Fire and Smoke Separations 57 58

57 58

Incidental Uses – 509.4.2 Incidental Uses – 509.4.2

. Where Table 509 permits sprinkler protection without a fire barrier, incidental uses must be separated by construction capable of resisting the passage of smoke.

Laundry . Doors/air openings regulated for smoke resistance.

2018 IBC Use of Fire and Smoke Separations 59 2018 IBC Use of Fire and Smoke Separations 60

59 60

Copyright 2017 International Code Council 15 2018 IBC Use of Fire & Smoke Separations

Horizontal Building Separation Horizontal Building Separation Section 510.2, #1 Allowance Section 510.2, #1 “Platform” or “Podium” Building . Where separate and distinct buildings are created one above the other, the buildings shall be separated with a minimum 3-hour horizontal Building #2 assembly. -- Podium/platform construction Building #1 Building #2 . When separated and compliant with several other conditions, buildings can be regulated independently for allowable area and number of stories, and fire Building #1 wall continuity.

2018 IBC Use of Fire and Smoke Separations 61 2018 IBC Use of Fire and Smoke Separations 62

61 62

Horizontal Separation- 510.2 Type IIIA Group R-1 and R-2 Buildings – 510.5

4. . Increase to 6 stories and 75 feet 2-hour separations ≤ 3,000 ft2 1. 6.

6 2. Type IA construction 3. Shaft, stair, ramp through horizontal assembly to have not less than 2-hour fire 5. Fully sprinklered rating below horizontal assembly and permitted to be all occupancies except Group H. 3-hour separation Plan View Basement

Elevation View Elevation View

2018 IBC Use of Fire and Smoke Separations 63 2018 IBC Use of Fire and Smoke Separations 64

63 64

Copyright 2017 International Code Council 16 2018 IBC Use of Fire & Smoke Separations

Type IIA Group R-1 and R-2 Buildings - 510.6 Type IIA Group R-1 and R-2 Buildings– 510.6

. Where special height increases are applied for . 9 stories, 100 feet Type IIA Group R-1 and R-2 buildings, minimum 2- hour fire walls are required to segregate the exits. ≥ 50 feet 9 2-hour . Allows nine stories and 100 feet.

Plan View

1 ½- hours

Elevation View

2018 IBC Use of Fire and Smoke Separations 65 2018 IBC Use of Fire and Smoke Separations 66

65 66

Open Parking Beneath Groups A, I, B, M Group B or M with Group S-2 Open and R – 510.7.1 Parking Garage – 510.8, #1 and #7

. Where special height and area allowances are . Where a Group B or M occupancy is located permitted for open parking garages below Group above an open parking garage and considered as A, I, B, M and R occupancies, means of egress separate buildings for type of construction for the upper occupancy shall be separated from purposes, in addition to other requirements, the the parking by minimum 2-hour fire barriers. buildings must be separated by a minimum 2-hour horizontal assembly.

2018 IBC Use of Fire and Smoke Separations 67 2018 IBC Use of Fire and Smoke Separations 68

67 68

Copyright 2017 International Code Council 17 2018 IBC Use of Fire & Smoke Separations

Group B or M with Group S-2 Open Parking Garage – 510.8, #1 – #7 Buildings on Same Lot – 503.1.2

7 . Where two or more buildings are located on the same lot, they shall be regulated as separate buildings, or as portions of a single building. 3 6 . If regulated as separate buildings, the opposing exterior walls must be evaluated based on fire separation 5 distance. 2

1 4

Elevation View

2018 IBC Use of Fire and Smoke Separations 69 2018 IBC Use of Fire and Smoke Separations 70

69 70

Buildings on Same Lot – 503.1.2 Exterior Walls – 705.5 Plan View

. For separation purposes, exterior walls near lot lines, or other buildings on the same lot, are required to be fire-resistance-rated as set forth in Table 602.

. The primary concern is radiant heat transfer from one building to another. Assuming nonsprinklered buildings, aggregate area is limited to 9,000 sf and allowable height is limited to 2 stories as both buildings must be regulated as Type VB construction

2018 IBC Use of Fire and Smoke Separations 71 2018 IBC Use of Fire and Smoke Separations 72

71 72

Copyright 2017 International Code Council 18 2018 IBC Use of Fire & Smoke Separations

Exterior Walls – Table 602 Exterior Walls – 705.5 TABLE 602 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCE a, d, g

FIRE SEPARATION TYPE OF OCCUPANCY OCCUPANCY OCCUPANCY DISTANCE = X (feet) CONSTRUCTION GROUP H e GROUP F-1, M, S-1 f GROUP A, B, E, F-2, I, R i, S-2, U h . The required fire-resistance rating of exterior walls X < 5b All 3 2 1 IA 3 2 1 5 < X < 30 with a fire-separation distance of more than 10 Others 2 1 1 IA, IB 2 1 1c feet shall be rated for exposure from fire from the 10 < X < 30 IIB, VB 1 0 0 Others 1 1 1c inside. X > 30 All 0 0 0 . The required fire-resistance rating of exterior walls For SI: 1 foot = 304.8 mm. a. Load-bearing exterior walls shall also comply with the fire-resistance rating of Table 601. b. See Section 706.1.1 for party walls. with a fire-separation distance of less than or c. Open parking garages complying with Section 406 shall hot be required to have a fire-resistance-rating. d. The fire-resistance rating of an exterior wall is determined based upon the fire separation distance of the exterior wall and the story in which the wall is located. e. For special requirements for Group H occupancies, see Section 415.6. equal to 10 feet shall be rated for exposure from f. For special requirements for Group S aircraft hangars, see Section 412.3.1. g. Where Table 705.8 permits nonbearing exterior walls with unlimited area of unprotected openings, the required fire-resistance rating for the exterior walls is0 hours. h. For a building containing only a Group U occupancy private garage or carport, the exterior wall shall not be required to have a fire-resistance rating where the fire fire from both sides. separation distance is 5 feet (1523 mm) or greater.. i. For a Group R-3 building of Type II-B or Type V-B construction, the exterior wall shall not be required to have a fire-resistnace rating where the fire separation distance is 5 feet (1523 mm) or greater.

2018 IBC Use of Fire and Smoke Separations 73 2018 IBC Use of Fire and Smoke Separations 74

73 74

Exterior Walls –705.5 Exterior Walls Section 705.5 . The required fire-resistance rating of exterior walls with a fire separation distance of more than 10 feet shall be rated for exposure from fire from the inside. . Where the fire separation distance is 10 feet or less, the wall shall be rated for exposure to fire from both sides.

2018 IBC Use of Fire and Smoke Separations 75 2018 IBC Use of Fire and Smoke Separations 76

75 76

Copyright 2017 International Code Council 19 2018 IBC Use of Fire & Smoke Separations

Shaft Enclosures – 713 Shaft Enclosure Fire Ratings – 713.4

. Shaft enclosures are a permissible method of . Shaft enclosures shall have a minimum fire- protecting openings and penetrations through resistance rating of: floor/ceiling and roof/ceiling assemblies. . 2 hours where connecting 4 or more stories. . 1 hour where connecting 3 or fewer stories. . Shaft enclosures shall be constructed as fire . 2 hours where penetrating a floor assembly of two or barriers and/or horizontal assemblies. more hours.

2018 IBC Use of Fire and Smoke Separations 77 2018 IBC Use of Fire and Smoke Separations 78

77 78

Chute Access and Discharge Rooms – Hoistway Opening Protection – 713.13.3 and 713.13.4 3006.3, #1 and #2 . waste and linen chutes access . Where elevator lobbies are required, they shall openings must be located in rooms or be constructed with fire partitions. compartments enclosed by not less than 1-hour fire barriers and/or . Where the building is fully sprinklered, smoke horizontal assemblies. partitions may be used to separate the elevator . Discharge rooms shall be separated lobby at each floor. from the remainder of the building by fire barriers and/or horizontal assemblies having a rating equal to the shaft enclosure.

2018 IBC Use of Fire and Smoke Separations 79 2018 IBC Use of Fire and Smoke Separations 80

79 80

Copyright 2017 International Code Council 20 2018 IBC Use of Fire & Smoke Separations

Building Use, Size & Components

1. The required fire-resistance rating of exterior walls with a fire-separation distance of more than 10 feet shall be rated for exposure from fire from the inside and outside. TRUET or F

2. Where special height increases are applied for Type IIA Group R-1 and R-2 buildings to allow Means nine story buildings, minimum 2 -hour fire walls are required to segregate the exits. of Egress

2018 IBC Use of Fire and Smoke Separations 81

81 82

Exit Access Stairways – 1019.3 Exit Access Ramps – 1019.3

. Exit access ramps are required to . Exit access stairways to be enclosed by shaft be enclosed with shaft enclosures (fire barriers) having a minimum fire- enclosures (fire barriers) under resistance ratings in accordance with Section 713: the same conditions as for exit . 2-hour serving 4 stories or more. access stairways. . 1-hour serving 2 or 3 stories. . Due to the limited use of ramps connecting 3 or more stories, the . There are eight exceptions to this requirement! application of this provision is very limited.

2018 IBC Use of Fire and Smoke Separations 83 2018 IBC Use of Fire and Smoke Separations 84

83 84

Copyright 2017 International Code Council 21 2018 IBC Use of Fire & Smoke Separations

Interior Exit Stairways and Extension of Interior Exit Stairways and Ramps – 1023.3.1 Ramps – 1023.2 . A horizontal extension of an interior exit stairway . Enclosures for interior exit stairways and ramps or ramp, where required, shall be by an exit shall be fire barriers and/or horizontal assemblies, passageway constructed with fire barriers and/or with a minimum rating of: horizontal assemblies. . 2 hours where connecting 4 or more stories. . The exit passageway shall have a minimum fire- . 1 hour where connecting 3 or fewer stories. resistance rating equal or greater to that of the . The enclosure shall have a fire-resistance rating connected interior exit stairway or ramp. not less than the floor assembly penetrated, but need not exceed 2 hours. . There shall be a assembly between the exit passageway and exit stairway.

2018 IBC Use of Fire and Smoke Separations 85 2018 IBC Use of Fire and Smoke Separations 86

85 86

Extension of Interior Exit Stairways and Ramps Smokeproof Enclosures and Pressurized Section 1023.3.1 Stairways and Ramps – 1023.11.1 There shall be a fire . Where required for high-rise . A horizontal extension of an door assembly interior exit stairways or ramp, between the exit buildings, underground buildings where required, shall be by an passageway and exit or aircraft-related occupancies, stairway. exit passageway constructed smokeproof enclosures and with fire barriers and/or pressurized stairways may be horizontal assemblies. extended by an exit . The exit passageway shall passageway. have a minimum fire-resistance . Fire barriers and/or horizontal rating equal or greater to that assemblies must have a of the connected interior exit stairway or ramp. minimum 2-hour fire-resistance rating.

2018 IBC Use of Fire and Smoke Separations 87 2018 IBC Use of Fire and Smoke Separations 88

87 88

Copyright 2017 International Code Council 22 2018 IBC Use of Fire & Smoke Separations

Exit Passageways – 1024.3 Horizontal Exits – 1026.2

. Horizontal exits, where provided, shall be . Exit passageways, where provided, shall be constructed with fire walls, or by fire barriers with a enclosed by fire barriers and/or horizontal minimum 2-hour fire-resistance rating. assemblies with a minimum 1-hour fire-resistance . The separation shall extend vertically through the entire rating. building unless floor assemblies have a minimum 2-hour . The rating cannot be less than that required for any fire-resistance rating. connected interior exit stairway or ramp. . A horizontal exit creates refuge areas such that smoke protectives are also required.

2018 IBC Use of Fire and Smoke Separations 89 2018 IBC Use of Fire and Smoke Separations 90

89 90

Horizontal Exits – 1026.4 Exterior Exit Stairways and Ramps – 1027.6

. Exterior exit stairways and ramps shall be separated from the interior of the building consistent with the protection required for interior exit stairways and ramps. . Fire barrier construction is required for those exterior walls adjacent to the exterior stairway or ramp.

2018 IBC Use of Fire and Smoke Separations 91 2018 IBC Use of Fire and Smoke Separations 92

91 92

Copyright 2017 International Code Council 23 2018 IBC Use of Fire & Smoke Separations

Exterior Stairways and Ramps – 1027.6 Spaces under Grandstands and Bleachers – 1029.1.1.1

Rating comes from Rating comes from Rating comes from . Usable spaces must be Section 1023.7 Section 1023.2 Section 1023.7 > 1-hr w/ > 1-hr w/ separated from ¾-hr prot 1-hr or 2-hr w/egress ¾-hr prot grandstands and openings door as only opening openings bleachers above by > 10 ft > 10 ft minimum 1-hour fire

barriers and/or Space used for any purpose other than: horizontal assemblies. • Ticket booths < 100 sf • Toilet rooms • Accessory areas < 1000 sf . Not apply to: and sprinklered . toilet rooms . small ticket booths . Accessory area < 1000 sf.

2018 IBC Use of Fire and Smoke Separations 93 2018 IBC Use of Fire and Smoke Separations 94

93 94

Corridor Construction – Corridors – 1020.1 Table 1020.1 TABLE 1020.1 CORRIDOR FIRE-RESISTANCE RATING REQUIRED FIRE-RESISTANCE . Corridors shall be fire-resistance rated in OCCUPANT RATING (hours) OCCUPANCY LOAD SERVED Without With accordance with Table 1020.1. BY CORRIDOR sprinkler sprinkler system systemc . Corridor walls are required to be constructed as H-1, H-2, H-3 All Not Permitted 1 H-4, H-5 Greater than 30 Not Permitted 1 fire partitions. A, B, E, F, M, S, U Greater than 30 1 0 . Where interrupted by a lobby, foyer or reception area, R Greater than 30 Not Permitted 0.5c/1d the fire partition protection shall extend behind such I-2a All Not Permitted 0 I-1, I-3 All Not Permitted 1b spaces. I-4 All 1 0

a. For requirements for occupancies in Group I-2, see Sections 407.2 and 407.3. b. For a reduction in the fire-resistance rating for occupancies in Group I-3, see Section 408.8. c. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 where allowed. d. Group R-3 and R-4 building equipped throughout with an automatic sprinkler system in accordance with Section 603.3.1.3. See Section 903.2.8 for occupancies where automatic sprinkler systems are permitted in accordance with Section 903.3.1.3.

2018 IBC Use of Fire and Smoke Separations 95 2018 IBC Use of Fire and Smoke Separations 96

95 96

Copyright 2017 International Code Council 24 2018 IBC Use of Fire & Smoke Separations

Corridor Continuity – 1020.6 Corridor Continuity – 1020.6

Fire resistance continuous from point of entry to an exit and not interrupted by intervening rooms …

Exception: Where interrupted by a lobby, foyer or reception area, the fire partition protection shall extend behind such spaces.

2018 IBC Use of Fire and Smoke Separations 97 2018 IBC Significant Changes 98

97 98

Egress Balconies – 1021.2 Areas of Refuge – 1009.6.4 . Exterior egress balconies shall be separated from the interior of the . Each area of refuge in an accessible means of building by fire partitions and egress shall be separated from the remainder of openings as required for the story by a smoke barrier or horizontal exit. corridors. . Areas of refuge must be designed to minimize the intrusion of smoke. . Separation is not required where two specified conditions are met: . Two available stairways, and, . Dead-ends do not pass unprotected opening

2018 IBC Use of Fire and Smoke Separations 99 2018 IBC Use of Fire and Smoke Separations 100

99 100

Copyright 2017 International Code Council 25 2018 IBC Use of Fire & Smoke Separations

Exterior Area for Assisted Exterior Area for Assisted Rescue – 1009.7.2 Rescue – 1009.7.2 . Exterior walls separating an exterior area for Maneuvering clearance Provide signs - Sections 1009.9 &1009.11 ICC A117.1 assisted rescue from the interior of the building 30” x 48” Wheelchair space Section 1007.6.1 shall have a minimum fire-resistance rating of 1-HR 1-hour, rated for exposure from the interior. fire- resistant construction . Wall rating and opening protectives not required where building fully sprinklered

2018 IBC Use of Fire and Smoke Separations 101 2018 IBC Use of Fire and Smoke Separations 102

101 102

Egress Courts – 1028.4.2 Egress Courts – 1028.4.2

. Exterior walls adjacent to an egress court shall have a minimum 1-hour fire-resistance rating for at least 10 feet above the walking surface where the court is less than 10 feet in width. . Exceptions, Egress court that: . serves an occupant load less than 10, and . serves other than a Group R-3 occupancy.

2018 IBC Use of Fire and Smoke Separations 103 2018 IBC Use of Fire and Smoke Separations 104

103 104

Copyright 2017 International Code Council 26 2018 IBC Use of Fire & Smoke Separations

Enclosures under Enclosures under Interior Residential Interior Stairways Stairways – 1011.7.3 1011.7.3, Exception . Walls and soffits within enclosed usable spaces under . Spaces under stairways enclosed and unenclosed serving an individual Group R-2 or R-3 interior stairways shall be dwelling unit are required, protected by minimum 1-hour at a minimum, to be fire-resistance-rated protected on the enclosed construction, or the rating of side of the stairway with the enclosure, whichever is minimum ½-inch gypsum greater. board.

2018 IBC Use of Fire and Smoke Separations 105 2018 IBC Use of Fire and Smoke Separations 106

105 106

Enclosures under Exterior Interior Exit Discharge – Stairways – 1011.7.4 1028.1, Exception 1.2 . No enclosed usable space is permitted . Where an interior exit stairway is permitted to under an exterior exit egress through a discharge level lobby or similar stairway unless it is space, as one condition the discharge level must completely enclosed be separated from areas below by construction in 1-hour fire- conforming to the fire-resistance rating of the resistance-rated enclosure. construction.

2018 IBC Use of Fire and Smoke Separations 107 2018 IBC Use of Fire and Smoke Separations 108

107 108

Copyright 2017 International Code Council 27 2018 IBC Use of Fire & Smoke Separations

Interior Exit Discharge – Interior Exit Discharge – 1028.1, Exception 1 1028.1, Exception 2.3

Entire area of level shall be 1.4 1.2 separated from areas below by construction equivalent to the stair enclosure. Distance between exit access stair and exit discharge door shall be Egress path from exit stairway to at least 30’ or ¼ length Discharge level must be discharge shall be sprinklered and of overall diagonal of separated from areas all rooms and portions of the level below by construction building, whichever is 1.3 having access to the egress path conforming to the fire- less shall be sprinkled or separated resistance rating of the from the egress path by construction enclosure 1 equivalent to the stair enclosure.

1.1

2018 IBC Use of Fire and Smoke Separations 109 2018 IBC Use of Fire and Smoke Separations 110

109 110

Fire Areas – 901.7

. Many of the sprinkler thresholds are based on size of fire area . Where buildings are divided into fire areas so as not to exceed the limits of Section 903 for requiring an automatic sprinkler system, the fire areas shall be separated by fire barriers and/or horizontal assemblies having a Fire Limitation Features minimum fire-resistance rating as set forth in Table 707.3.10.

2018 IBC Use of Fire and Smoke Separations 112

111 112

Copyright 2017 International Code Council 28 2018 IBC Use of Fire & Smoke Separations

Fire Areas – Fire Areas – 901.7 901.7 . The use of a fire wall to create separate, smaller buildings also creates smaller fire areas as well. . Therefore, fire areas can be established by use of . Fire Wall . Fire Barrier . Horizontal Assembly . Or a combination of the above

2018 IBC Use of Fire and Smoke Separations 113 2018 IBC Use of Fire and Smoke Separations 114

113 114

Smokeproof Enclosures – Stair Pressurization Alternative – 909.20.2 909.20.6.1 . A smokeproof enclosures . Smokeproof enclosure ventilation systems shall shall be separated from Fire door assembly per Section716.2 be isolated from the remainder of the building by the remainder of the (minimum 1 ½- hour building by minimum 2- fire assembly) minimum 2-hour fire barriers and/or horizontal hour fire barriers and/or assemblies. horizontal assemblies. . Protection shall be provided for equipment, control . In addition, the vestibule wiring, power wiring and ductwork. Minimum 20- must be separated from minute smoke- and draft- control door per Section the stairway by minimum 909.20.3.2 2-hour fire barriers and/or horizontal assemblies.

2018 IBC Use of Fire and Smoke Separations 115 2018 IBC Use of Fire and Smoke Separations 116

115 116

Copyright 2017 International Code Council 29 2018 IBC Use of Fire & Smoke Separations

Fire Pump Rooms – Fire Command Center – 911.1.2 913.2.1 . Fire pumps shall be located in rooms separated . Fire command centers, where required, shall be from all other portions of the building by separated from the remainder of the building by minimum 2-hour fire barriers and/or horizontal minimum 1-hour fire barriers and/or horizontal assemblies. assemblies. . In other than high-rise buildings, where the building is fully sprinklered, the fire barriers and/or horizontal assemblies must have a minimum 1-hour fire- resistance rating.

2018 IBC Use of Fire and Smoke Separations 117 2018 IBC Use of Fire and Smoke Separations 118 117 118

Fire Pump Rooms – Fire Alarm Systems in Group R 913.2.1 Occupancies – 907.2.8.1 & 907.2.9.1 . In select Group R occupancies not exceeding 2-stories, an otherwise-mandated fire alarm system may not be required where the units are separated from each other and the public and common areas by minimum 1-hour fire partitions. . Other conditions must also be met.

2018 IBC Use of Fire and Smoke Separations 119 2018 IBC Use of Fire and Smoke Separations 120

119 120

Copyright 2017 International Code Council 30 2018 IBC Use of Fire & Smoke Separations

Smoke Control Systems – 909.5 . Where construction elements are used as a part of a smoke control system, smoke barriers shall be provided. . The maximum allowable leakage area is to be calculated and reviewed for compliance.

Special Building Types

2018 IBC Use of Fire and Smoke Separations 121

121 122

Mall/Anchor Building Separation – Mall/Parking Garage Separation – 402.4.2.2 402.4.2.3 . An anchor building shall be separated from a . An attached parking garage shall be separated covered or open mall building by a fire wall. from a covered mall building, open mall . Where the anchor building is 3 stories or less, building or anchor building by a minimum minimum 2-hour fire barriers are permitted. 2-hour fire barrier and/or horizontal assembly.

2018 IBC Use of Fire and Smoke Separations 123 2018 IBC Use of Fire and Smoke Separations 124

123 124

Copyright 2017 International Code Council 31 2018 IBC Use of Fire & Smoke Separations

Standby Power Protection in High- Mall Tenant Separations – 402.4.2.1 rise Buildings – 403.4.8.1

. If a generator within the building is used for . Each tenant space within a mall building shall standby power in a high-rise building, it shall be separate from other tenant spaces by a fire located in a separate room enclosed with minimum partition. 2-hour fire barriers and/or horizontal assemblies.

. No separation wall is required between the tenant space and the mall.

2018 IBC Use of Fire and Smoke Separations 125 2018 IBC Use of Fire and Smoke Separations 126

125 126

Atrium Sprinkler Protection Atrium Separation – 404.6 Section 404.3, Exception 1 . Atrium spaces shall be separated from . Sprinklers are required throughout a building adjacent spaces by a minimum 1-hour fire containing an atrium. barrier and/or horizontal assembly. . The 1-hour separation is not required under one of EXCEPTION #1: Sprinkler protection is not three exceptions, required for areas adjacent to and above the 1. where glazed enclosure is protected by an automatic atrium space provided that portion is separated sprinkler system, from the atrium by minimum 2-hour fire barriers 2. ¾ hour glass block is utilized, or 3. Open to not more than 3 stories and/or horizontal assemblies.

2018 IBC Use of Fire and Smoke Separations 127 2018 IBC Use of Fire and Smoke Separations 128

127 128

Copyright 2017 International Code Council 32 2018 IBC Use of Fire & Smoke Separations

Atrium Separation – 404.6, Underground Building Exception 1 Compartmentation – 405.4 . A building with a floor level more than 60 feet below the lowest discharge level must be divided into at least two compartments, created through the use of smoke barriers. . Elevators that serve more than one compartment shall be provided with an elevator lobby separated from each compartment by a smoke barrier.

2018 IBC Use of Fire and Smoke Separations 129 2018 IBC Use of Fire and Smoke Separations 130

129 130

Private Garage Buildings – 406.3.1

. Multiple 1,000-square-foot private garages are permitted within the same structure where each private garage is separated by minimum 1-hour fire barriers, horizontal assemblies, or both.

Special Occupancies and Uses

2018 IBC Use of Fire and Smoke Separations 132

131 132

Copyright 2017 International Code Council 33 2018 IBC Use of Fire & Smoke Separations

Garage Dwelling Separations – Group I-2 Smoke Compartments – 406.3.4.1 407.5 . Every story in a Group I-2 occupancy* where . A private garage shall be separated from the persons receive care or those having an dwelling unit by minimum ½-inch gypsum board occupant load of 50 or more shall be divided into on the garage side. at least two smoke compartments by smoke . Garages with habitable rooms above shall be barriers. separated by not less than 5/8-inch Type X gypsum board. *24-hour care for 5 or more who are incapable of self-preservation.

2018 IBC Use of Fire and Smoke Separations 133 2018 IBC Use of Fire and Smoke Separations 134

133 134

Group I-2 Corridors – 407.3 Group I-2 Corridors – 407.3

. Corridor walls in a Group I-2 occupancy shall be constructed as smoke partitions.

. Waiting areas and similar spaces constructed as required for corridors are permitted to be open to the corridor. . Doors require no closing device but shall be positive latching and limit smoke

2018 IBC Use of Fire and Smoke Separations 135 2018 IBC Use of Fire and Smoke Separations 136

135 136

Copyright 2017 International Code Council 34 2018 IBC Use of Fire & Smoke Separations

Group I-3 Smoke Compartments – Group I-2 Care Suites – 407.4.4.2 408.6 . Care suites shall be separated from other . Every story in a Group I-3 occupancy shall be portions of the building by smoke partitions. divided into at least two smoke compartments by smoke barriers when:

. used by residents for sleeping or . those stories having an occupant load of 50 or more

*Prisons, jails, correctional facilities where persons are under restraint or security

2018 IBC Use of Fire and Smoke Separations 137 2018 IBC Use of Fire and Smoke Separations 138

137 138

Group I-3 Subdivision of Resident Group I-3 Interior Exit Stairways – Housing Areas – 408.8 408.3.8

. In Occupancy Conditions 3 and 4*, each . One interior exit stairway in each building is sleeping area shall be separated from adjacent permitted to have glazing installed in doors and common spaces by a smoke-tight partition walls at each landing providing access to the where distance of travel from sleeping area to stairway. corridor exceeds 50 feet. . The total glazing is limited to 5,000 square inches per floor level. . Sprinkler protection is required to wet the glazing completely.

*3= free movement in smoke zone, 4 = free movement is restricted but occupants can be released remotely

2018 IBC Use of Fire and Smoke Separations 139 2018 IBC Use of Fire and Smoke Separations 140

139 140

Copyright 2017 International Code Council 35 2018 IBC Use of Fire & Smoke Separations

Aircraft Hangar Fire Areas – Aircraft Hangar Fire Areas – 412.3.6.2 412.3.6.2

. When determining the fire suppression . Support areas, such as offices, shops and requirements for aircraft hangars, established storage rooms, which are separated from the fire areas shall be separated by minimum 2-hour aircraft servicing area by minimum 1-hour fire fire walls. barriers are not required to be included in the determination of fire area size.

2018 IBC Use of Fire and Smoke Separations 141 2018 IBC Use of Fire and Smoke Separations 142

141 142

Aircraft Hangar Heating Aircraft Hangar Fire Areas – 412.3.6.2 Equipment – 412.3.4

. Heating equipment in an aircraft hangar shall be:

 placed in a separate room and separated by minimum 2-hour fire barriers and/or horizontal assemblies.

2018 IBC Use of Fire and Smoke Separations 143 2018 IBC Use of Fire and Smoke Separations 144

143 144

Copyright 2017 International Code Council 36 2018 IBC Use of Fire & Smoke Separations

Residential Aircraft Hangar Residential Unit Wall Separation – 412.4.1 Separations – 420.2 . In Group I-1*, R-1, R-2 and R-3, R-4, walls separating dwelling and sleeping units in the . An aircraft hangar same building, as well as separating such units attached to a dwelling from other occupancies in the building, shall be must be separated by constructed as fire partitions. a minimum 1-hour fire barrier. . Note: If designed as separated mixed-use the separation shall be a fire barrier between occupancies

*Congregate care for more than 16 residents on 24 hour basis: assisted living, group homes, alcohol and drug centers.

2018 IBC Use of Fire and Smoke Separations 145 2018 IBC Use of Fire and Smoke Separations 146

145 146

Residential Unit Floor Ambulatory Care Facilities Separations – 420.3 Separation – 422.2 . In Group I-1, R-1, R-2 and R-3 occupancies, floor assemblies separating dwelling and . Ambulatory care facilities where there are 4 or sleeping units in the same building, as well as more individuals incapable of self-preservation separating such units from other occupancies in shall be separated from adjacent spaces, the building, shall be constructed as horizontal corridors and tenants by fire partitions. assemblies.

2018 IBC Use of Fire and Smoke Separations 147 2018 IBC Use of Fire and Smoke Separations 148

147 148

Copyright 2017 International Code Council 37 2018 IBC Use of Fire & Smoke Separations

Ambulatory Care Facilities Smoke Compartments – 422.3 Ambulatory Care Facilities–422

. Where the aggregate area of one or more ambulatory care facilities exceeds 10,000 square feet, smoke barriers are required to create smoke compartments. . No individual compartment is permitted to exceed 22,500 square feet.

2018 IBC Use of Fire and Smoke Separations 149 2018 IBC Use of Fire and Smoke Separations 150

149 150

1. Which walls are required to have a fire-resistance rating? All walls, except exterior and separating Group A-3 from lobby

2. What minimum type of wall is required? FIRE PARTITION Special Building Features

3. What fire-resistance rating is required? 1

2018 IBC Use of Fire and Smoke Separations 151

151 152

Copyright 2017 International Code Council 38 2018 IBC Use of Fire & Smoke Separations

Stage Proscenium Wall – 410.2.4 Stage Support Areas Separation –

. Where the stage height 410.4.1 exceeds 50 feet, all portions of the stage shall be . The stage shall be separated from support separated from the seating areas, such as dressing rooms, workshops and area by a proscenium wall with a minimum 2-hour storerooms, by fire barriers and/or horizontal rating, extending from the assemblies. foundation to the roof . Minimum 2-hour separation required for stage heights (fundamentally a fire exceeding 50 feet. barrier). . Minimum 1-hour separation required for stage heights . Proscenium opening to be of 50 feet or less. protected by a fire curtain or other acceptable method.

2018 IBC Use of Fire and Smoke Separations 153 2018 IBC Use of Fire and Smoke Separations 154

153 154

Stage Support Areas Separation – Stages 410.5.2 Section 410.4

. Support areas, such as dressing rooms, workshops and storerooms, shall be separated from each other by fire barriers and/or horizontal assemblies. . Minimum 1-hour separation required.

2018 IBC Use of Fire and Smoke Separations 155 2018 IBC Use of Fire and Smoke Separations 156

155 156

Copyright 2017 International Code Council 39 2018 IBC Use of Fire & Smoke Separations

Platform Construction – 410.3 Elevator Machine Rooms – 3005.4

. Where space beneath . Elevator machine rooms and spaces shall be a permanent platform enclosed with fire barriers and/or horizontal is used for storage, or assemblies. any other purpose other than equipment, . The fire-resistance rating shall be not less than the required rating of the hoistway enclosure served by plumbing or wiring, the machinery. the floor assembly shall be at least one- hour construction.

2018 IBC Use of Fire and Smoke Separations 157 2018 IBC Use of Fire and Smoke Separations 158

157 158

Fire Service Access Elevator Occupant Evacuation Elevator Lobby – 3007.6.2 Lobby – 3008.6.2

. In high-rise buildings provided with fire service . In high-rise buildings provided with occupant access elevators, the elevator shall be provided evacuation elevators, the elevator shall be with a lobby enclosed by a smoke barrier. provided with a lobby enclosed by a smoke . Elevator lobbies are not required at the level of exit barrier. discharge. . Elevator lobbies are not required at the level of exit discharge.

2018 IBC Use of Fire and Smoke Separations 159 2018 IBC Use of Fire and Smoke Separations 160

159 160

Copyright 2017 International Code Council 40 2018 IBC Use of Fire & Smoke Separations

Pedestrian Walkways – 3104.5 Tunnels – 3104.10

. Pedestrian walkways shall be separated from the interior of the . Separation between a tunneled walkway and the attached buildings by building to which it is connected shall be not less minimum 2-hour fire than 2-hour fire-resistant construction. barriers and/or horizontal assemblies. . An alternate separation method addresses the walkway/building connections, including the use of a tempered, wired or laminated glass wall.

2018 IBC Use of Fire and Smoke Separations 161 2018 IBC Use of Fire and Smoke Separations 162

161 162

Combustible Storage Section 413 . Attic, under-floor and concealed spaces used for storage of combustible materials shall be:  protected on the storage side as required for 1- hour fire-resistance-rated construction and Openings protected by self-closing non- combustible or 1 ¾” thick solid wood core door EXCEPTIONS: fire-resistance construction nor open Hazardous Uses protectives required in: 1. sprinklered spaces 2. Group R-3 and U occupancies

2018 IBC Use of Fire and Smoke Separations 164

163 164

Copyright 2017 International Code Council 41 2018 IBC Use of Fire & Smoke Separations

Control Areas – 414.2.4 Control Areas - Section 414.2.4

. Where control areas are provided for the use or . Where control areas are provided for the use or storage of hazardous materials, they shall be storage of hazardous materials, they shall be separated by fire barriers in accordance with separated by fire barriers in accordance with Table Table 414.2.2. 414.2.2. (1- or 2-hour) . The floor assemblies separating control areas . The floor assemblies separating control areas shall shall be minimum 2-hour horizontal assemblies. be minimum 2-hour horizontal assemblies. (this . Exception permits 1-hour assemblies under specified includes supporting construction) conditions. . Exception for IIA, IIIA and VA construction permits 1-hour assemblies under specified conditions.

2018 IBC Use of Fire and Smoke Separations 165 2018 IBC Use of Fire and Smoke Separations 166

165 166

Control Areas – Table 414.2.2 Grinding Rooms – 426.1.2

. Rooms used for grinding or other operations that produce combustible dusts shall be enclosed with fire barriers and/or horizontal assemblies. . The required fire-resistance rating is based on the floor area of the room: . 2 hours, where 3,000 square feet or less. . 4 hours, where more than3,000 square feet.

2018 IBC Use of Fire and Smoke Separations 167 2018 IBC Use of Fire and Smoke Separations 168

167 168

Copyright 2017 International Code Council 42 2018 IBC Use of Fire & Smoke Separations

Group H-3 and H-4 Gas Rooms – Highly Toxic Solids and 415.10.2 Liquids – 415.10.4

. Where Group H-3 or H-4 gas rooms are provided, . Where highly toxic solids and liquids are not they shall be separated from other areas by stored in approved hazardous materials storage minimum 1-hour fire barriers and/or horizontal cabinets, they shall be isolated from other assemblies. hazardous material storage by minimum 1-hour fire barriers and/or horizontal assemblies.

2018 IBC Use of Fire and Smoke Separations 169 2018 IBC Use of Fire and Smoke Separations 170

169 170

Group H-5 Fabrication Areas – Flammable Finish Spray 415.11.1.2 Rooms – 416.2

. Fabrication areas in Group H-5 occupancies . In buildings used for the application of shall be separated from: flammable finishes, spray rooms shall be 1. each other, enclosed with minimum 1-hour fire barriers 2. from corridors and and/or horizontal assemblies. 3. from other parts of the building by minimum 1-hour fire barriers and/or horizontal assemblies.

2018 IBC Use of Fire and Smoke Separations 171 2018 IBC Use of Fire and Smoke Separations 172

171 172

Copyright 2017 International Code Council 43 2018 IBC Use of Fire & Smoke Separations

Manufacturing of Organic Final Reflection Coatings – 418

. In buildings used for the manufacture of This slide will help the learner to reflect on the day organic coatings, a variety of fire separations and what they will take back to the job and apply. are required using fire barriers and/or . What? What happened and what was observed horizontal assemblies: in the training? . Storage areas for flammable and combustible liquid tanks: 2 hours . So what? What did you learn? What difference . Nitrocellulose storage rooms: 2 hours did this training make? . Storage rooms for finished products that are . Now what? How will you do things differently flammable or combustible liquids: 2 hours back on the job as a result of this training?

2018 IBC Use of Fire and Smoke Separations 173 2018 IBC Use of Fire and Smoke Separations 174

173 174

Copyright Materials

International Code Council is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA This presentation is protected by US and International members. Certificates of Completion for non-AIA members are available on Copyright laws. Reproduction, distribution, display and use of request. the presentation without written permission of the speaker is prohibited. This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of © International Code Council 2018 construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.

175 176

Copyright 2017 International Code Council 44 2018 IBC Use of Fire & Smoke Separations

Thank you for participating!

To schedule a seminar, contact: The Learning Center™ 1‐888‐ICC‐SAFE (422‐7233) Ext. 33818 or E‐mail: [email protected]

177

177

Copyright 2017 International Code Council 45 2018 IBC Dampers, Penetration and Joint Systems 9/16/2019

Dampers

The requirements of the IBC are duplicated in Section 607 of the IMC Dampers . IBC Section 717 (IMC 607) addresses both ducted and unducted (air transfer openings) IBC Section 717 systems . Provisions of these sections address damper test standards, types of dampers, actuation, access and where the various dampers are required

2015 IBC Dampers, Penetration Firestops and Joint Systems 1 2015 IBC Dampers, Penetration Firestops and Joint Systems 2

12

Five general types of dampers Five types of dampers

Each type of damper has . Fire damper a very specific application . Smoke damper and is tested to show . Combination fire compliance with the and smoke intended application damper . It is important to verify . Corridor damper that the specified and installed damper is the . Ceiling radiation correct damper for that damper application

2015 IBC Dampers, Penetration Firestops and Joint Systems 3 2015 IBC Dampers, Penetration Firestops and Joint Systems 4

34

Copyright 2018 International Code Council 1 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Manufacturer’s Installation Damper test standards Instructions Fire dampers - UL 555 . All dampers are listed . Must be followed for installation (717.2) and must have a label Smoke dampers - UL . Are a requirement of the listing 555S . Must be installed in Ceiling radiation dampers accordance with . Must be available for installation and inspection – UL 555C or tested as a manufacturer’s since variations occur between dampers and part of FR-rated installation instructions manufacturers horizontal assembly . Where smoke and fire . Along with listing, they can help determine damper are required, may use separate orientation and whether damper is allowed in a Combination damper – UL dynamic system 555 and UL 555S dampers or combination damper

2015 IBC Dampers, Penetration Firestops and Joint Systems 5 2015 IBC Dampers, Penetration Firestops and Joint Systems 6

56

Dynamic Dampers Dynamic Dampers

Intended to be installed where air may continue to Are marked with airflow rating and a closing move through the system pressure rating . Tested and labeled for specific airflow and . Airflow in 1,000 fpm increments (2,000 fpm pressure minimum) . Must be capable of closing against the . Closing pressure rating in 2-inch water gage anticipated design conditions (airflow/pressure) increments (4-inch WG minimum) . Are allowed in “static” systems (airflow Installed damper must exceed maximum shutdown) anticipated airflow and pressure – which can vary from normal airflow conditions

2015 IBC Dampers, Penetration Firestops and Joint Systems 7 2015 IBC Dampers, Penetration Firestops and Joint Systems 8

78

Copyright 2018 International Code Council 2 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Static vs. Dynamic Dampers Fire damper ratings TABLE 717.3.2.1 STATIC RATED: Not Tested with Airflow Through Damper FIRE DAMPER RATING (IMC Table 607.3.2.1) Fire dampers shall Fire Damper or FSD MINIMUM Duct TYPE OF DAMPER have the minimum PENETRATION No Airflow RATING (hours) rating specified in Less than 3-hour fire- Table 717.3.2.1 resistance-rated 1.5 DYNAMIC RATED: Tested with Heated Airflow Through Damper assemblies 3-hour or greater fire- resistance-rated 3 Duct Heated Airflow 2000FPM @ 4”w.g. assemblies

2015 IBC Dampers, Penetration Firestops and Joint Systems 9 2015 IBC Dampers, Penetration Firestops and Joint Systems 10

910

Smoke damper ratings Smoke damper ratings Maximum Leakage (CFM/ft2) Class 4 In. WG 6 In. WG 8 In. WG 10 In. WG 12 In. WG . Details are primarily found in UL 555S test I 8.0 9.5 11.0 12.5 14.0

standard II 20.0 24.0 28.0 31.5 35.0

. May be used in static or dynamic systems but III 80.0 96.0 112.0 125.0 140.0 are designed to operate against an airflow and Smoke dampers are tested at elevated temperatures pressure (in order to limit air leakage) and must be labeled with the temperature used to . UL 555S test allows listing of Class III damper determine the leakage ratings but IBC and IMC only allow Class I or Class II • Temperature ratings in increments of 100oF (250oF minimum)  250oF rating is generally adequate, but Section 909.10 may require a higher rating for some smoke control systems

2015 IBC Dampers, Penetration Firestops and Joint Systems 11 2015 IBC Dampers, Penetration Firestops and Joint Systems 12

11 12

Copyright 2018 International Code Council 3 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Fire damper and ceiling radiation Remember, fire dampers and smoke dampers are tested to different standards. damper actuation Done by one of the following: . Operating temperature approximately 50oF above normal temperature in the duct . But not less than 160oF

. Operating temperature up to 350oF allowed for Verify by looking at the label that the smoke control system correct damper is being used.

2015 IBC Dampers, Penetration Firestops and Joint Systems 13 2015 IBC Dampers, Penetration Firestops and Joint Systems 14

13 14

Smoke damper actuation Smoke damper actuation

(716.2.2.1 in 2018)

2015 IBC Dampers, Penetration Firestops and Joint Systems 15 2015 IBC Dampers, Penetration Firestops and Joint Systems 16

15 16

Copyright 2018 International Code Council 4 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Smoke damper actuation Smoke damper actuation

This reduced coverage smoke detection system is only allowed to control the smoke dampers installed within the corridor walls or ceiling.

2015 IBC Dampers, Penetration Firestops and Joint Systems 17 2015 IBC Dampers, Penetration Firestops and Joint Systems 18

17 18

Smoke damper actuation Access and identification Approved means of Where a smoke access must be detection system is provided: provided within all areas served by a duct, the . Large enough to smoke dampers within permit inspection and the protected area are maintenance permitted to be . Shall not reduce fire- controlled by the resistance of system. assembly . Be identified

2015 IBC Dampers, Penetration Firestops and Joint Systems 19 2015 IBC Dampers, Penetration Firestops and Joint Systems 20

19 20

Copyright 2018 International Code Council 5 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Access and identification Access and identification

2015 IBC Dampers, Penetration Firestops and Joint Systems 21 2015 IBC Firestopping, Joint Systems and Dampers

21 22

Access and identification Where dampers are required

. Section 717.5 lists locations where dampers are required for walls and specifies the type of damper required at each location

. Section 717.6 specifies the location and type of damper required for horizontal assemblies

2015 IBC Firestopping, Joint Systems and Dampers 2015 IBC Dampers, Penetration Firestops and Joint Systems 24

23 24

Copyright 2018 International Code Council 6 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Quick reference – Where dampers are required Damper requirements for walls Section Wall type Referenced from Type of damper Plans should specify the location and type of 717.5.1 (IMC 607.5.1) Fire walls 706.11 Fire damper damper to be installed. Inspector should verify 717.5.1.1 Fire wall – Horizontal 706.11 Fire damper, Smoke damper (IMC 607.5.1.1) exits correct type of damper is at each location. 717.5.2 (IMC 607.5.2) Fire barriers 707.10 Fire damper 717.5.2.1 Fire barriers – 707.10 Fire damper, Smoke damper (IMC 607.5.2.1) Horizontal exits . Section 717.5 says: 717.5.3 Shaft enclosures 713.10 Fire damper, Smoke damper (IMC 607.5.5) “where an assembly is required to have both fire 717.5.4 (IMC 607.5.3) Fire partitions 708.9 Fire damper dampers and smoke dampers, combination fire/smoke 717.5.4.1 (IMC Fire partitions ‐ 708.9 Fire damper,Smoke damper 607.5.3 and 607.5.4) Corridors dampers or a fire damper and a smoke damper shall be 717.5.5 (IMC 607.5.4) Smoke barriers 709.8 Smoke damper provided.” 717.5.6 (IMC 607.5.6) Exterior walls 705.10 Fire damper 717.5.7 (IMC 607.5.7) Smoke partitions 710.8 Smoke damper

2015 IBC Dampers, Penetration Firestops and Joint Systems 25 2015 IBC Firestopping, Joint Systems and Dampers

25 26

Ceiling radiation dampers Ceiling radiation dampers

Ceiling radiation dampers Since CRD limits amount (CRD) used to limit of heat through them, passage of fire and heat cannot substitute a fire through opening in ceiling damper at this location membrane of a fire- . CRDs don’t have hourly resistive assembly rating . Test details in 717.3.1 . Tested for use in specific . Test to UL 555C, or assemblies, or are . As part of the full . Tested as alternate to a horizontal assembly test hinged door damper from assembly test

2015 IBC Dampers, Penetration Firestops and Joint Systems 27 2015 IBC Dampers, Penetration Firestops and Joint Systems 28

27 28

Copyright 2018 International Code Council 7 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

UL 263 Duct outlet protection Ceiling radiation dampers systems - Another way to eliminate a CRD . Three items allow System A: CRD to be exempted . Only permitted when . Tested to ASTM E 119 specified within the or UL 263 showing individual horizontal CRD not required assembly’s design . Exhaust duct penetration within wall cavity and complying with Section 714.5.2 . Use of duct outlet protection system

2015 IBC Dampers, Penetration Firestops and Joint Systems 29 2015 IBC Dampers, Penetration Firestops and Joint Systems 30

29 30

UL 263 Duct outlet protection systems - Another way to eliminate a CRD System B: . May be used in any design that contains a steel duct protected by a hinged door damper in the test . Limited to equal or smaller size outlet than was tested with a hinged door damper

2015 IBC Dampers, Penetration Firestops and Joint Systems 31 2015 IBC Firestopping, Joint Systems and Dampers

31 32

Copyright 2018 International Code Council 8 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Damper installation Damper installation Four aspects usually only addressed within the Installation instructions installation instructions are: will provide minimum 1. The space around a damper when it is installed in annular space around the opening. damper 2. The requirement for a sleeve if the damper is . Space is required to allow expansion and installed within a duct. movement 3. The attachment and potential break-away feature . Example: May require for any duct attached to the damper or sleeve. 1/8 inch per foot of damper on all sides 4. Whether the opening through the assembly must . Gap is OK. It is tested be lined with some material such as gypsum board this way . Filling required gap or may leave the framing members exposed. would void listing

2015 IBC Dampers, Penetration Firestops and Joint Systems 33 2015 IBC Dampers, Penetration Firestops and Joint Systems 34

33 34

Damper installation Damper installation

Retaining angles: Do not place sealants . Generally cover annular around/between retaining space or gap angles and assembly or . Hold damper or sleeve in damper unless indicated opening but allow for in listing or installation movement – if attached to instructions wall they may void listing . Sealants could void . Generally overlap wall by listing 1 inch minimum . Could restrict damper . Attachment is covered by movement item 7 of SMACNA table . Always check listing if sealant is used/desired

2015 IBC Dampers, Penetration Firestops and Joint Systems 35 2015 IBC Dampers, Penetration Firestops and Joint Systems 36

35 36

Copyright 2018 International Code Council 9 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Sleeve for damper Breakaway connections

Use of a sleeve is not a . Thickness of sleeve Connection to damper or specific code requirement generally increases damper sleeve must allow . Simplifies installation based on duct size and ductwork to breakaway and ductwork type of connection to and not pull damper from attachment duct the opening . May come from factory . Manufacturer’s . Types of connections or be field constructed instructions should and locations are . Manufacturer’s show specified in installation installation instructions . Thickness instructions will address. See items . Minimum extension . UL 555 shows various 4, 5 and 6 from . Details of how it is held types of connections SMACNA table into the opening . Test is required by UL Verify with listing. For example a flat 555 drive may not be permitted, or may only be allowed on vertical sides of duct

2015 IBC Dampers, Penetration Firestops and Joint Systems 37 2015 IBC Dampers, Penetration Firestops and Joint Systems 38

37 38

Breakaway test – UL 555 Preparation of opening

Damper remains in the rated wall after Listing and . Verify with duct “breaks” away from the sleeve manufacturer’s manufacturer’s instructions will include installation instructions details regarding . As a general rule of preparation of opening thumb: . Information is from item . Many wood assemblies 13 of SMACNA table will require a layer of and dependent on fire-resistive protection in testing the opening . Metal frame assemblies . No general code may not require Weight of sand in barrel varies. 220 requirement either pounds if duct 24 inches or less protection 440 pounds if duct > 24 inches exempting or requiring

2015 IBC Dampers, Penetration Firestops and Joint Systems 39 2015 IBC Dampers, Penetration Firestops and Joint Systems 40

39 40

Copyright 2018 International Code Council 10 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Preparation of openings - Examples Maintenance and inspections Noncombustible framing Combustible framing Once installed, dampers . IFC references NFPA must be maintained to 80 and NFPA 105 ensure they continue to standards function . These are “referenced . IMC 102.3 requires standards” and “considered part of the maintenance and does requirements of this reference IFC code.” (IFC 102.7, IBC . Similar provision from 102.4 and IMC 102.8) 2012 IBC 3401.2 lost in . NFPA 80 – Fire switch to IEBC . NFPA 105 – Smoke . IFC 108, 701.5, 706.1 and 706.2 provide details

2015 IBC Dampers, Penetration Firestops and Joint Systems 41 2015 IBC Dampers, Penetration Firestops and Joint Systems 42

41 42

Maintenance and inspection

IFC Sections 108, 706.1 and 706.2 Penetrations IBC Section 714

2015 IBC Dampers, Penetration Firestops and Joint Systems 43

43 44

Copyright 2018 International Code Council 11 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Penetrations Penetrations

Penetrations in fire-resistance-rated and/or smoke- No single item will work for . Size and configuration of every situation. Required the opening (the annular resistant assemblies create breaches and potential space between penetrant systems depend on: and periphery of opening) weak points that could reduce the assembly’s’ . Type and rating of base effectiveness if not properly protected. assembly . Type, size and material of Systems also vary between . Penetrations and the materials used to protect penetrant different manufacturers and them must not reduce the assembly rating . Type and thickness of any within individual product insulation on penetrant lines . Section 714 regulates both rated assemblies, . Material type and thickness . So don’t get complacent and nonfire-resistance-rated horizontal of any sleeve and assume all systems . Type of firestopping are equal or installed in assemblies material used in firestop similar manner system

2015 IBC Dampers, Penetration Firestops and Joint Systems 45 2015 IBC Dampers, Penetration Firestops and Joint Systems 46

45 46

Topics covered in Section 714 Definition – Annular space

. Fire-resistance-rated walls – Section 714.4 Important to understand . Fire-resistance-rated horizontal assemblies – terminology and test Section 714.5 methods . Smoke barriers – Section 714.5.4 (applies to . Annular space both walls and horizontal assemblies) . “The opening around the penetrating item” . Nonfire-resistance-rated horizontal assemblies – . Many assemblies Section 714.6 include a minimum and maximum dimension

2015 IBC Dampers, Penetration Firestops and Joint Systems 47 2015 IBC Dampers, Penetration Firestops and Joint Systems 48

47 48

Copyright 2018 International Code Council 12 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Annular space can vary Definition Membrane penetration Through penetration

2015 IBC Dampers, Penetration Firestops and Joint Systems 49 2015 IBC Dampers, Penetration Firestops and Joint Systems 50

49 50

Definition Definitions

There are a number of . Through-penetration other definitions that firestop system code users should be . L Rating familiar with: . Mineral fiber . Penetration firestop . Mineral wool . Membrane- penetration firestop Just be certain to look . Membrane- at Chapter two when a penetration firestop term is shown in italics system within the code

2015 IBC Dampers, Penetration Firestops and Joint Systems 51 2015 IBC Dampers, Penetration Firestops and Joint Systems 52

51 52

Copyright 2018 International Code Council 13 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Firestopping vs. Test standards fireblocking or draftstopping Code provides two basic . First option is seldom . Section 714: methods to evaluate the used firestopping for performance of . Second option penetration firestop evaluates resistance to: penetrations systems: . Development of through . Section 718: . Test as part of overall openings assembly (ASTM E 119 . Flaming on unexposed fireblocking and or UL 263), or surface, and draftstopping . Test penetration . Ability to limit thermal transmission through the separately (ASTM E penetration 814 or UL 1479) . All four tests require hose stream test

2015 IBC Dampers, Penetration Firestops and Joint Systems 53 2015 IBC Dampers, Penetration Firestops and Joint Systems 54

53 54

Firestopping vs. Where penetration protection fireblocking or draftstopping is required 718 fireblocking or 714 Penetration firestops draftstopping Primary requirements are found in: . Protects penetrations . Limits spread of fire . 714.4 (Fire-resistance-rated walls) into rated assemblies within concealed spaces . 714.5 (Horizontal assemblies) . Applies to both . May be rated or non- . 714.6 (Nonfire-resistance-rated horizontal combustible and rated construction assemblies) noncombustible . Applies to combustible . 714.5.4 (Smoke barriers) construction concealed locations . Not tested, but use . Typically a tested system specific Those code sections address not only the type of prescriptive/generic penetrations required to be protected but also the products that are deemed to be acceptable acceptable methods of protection

2015 IBC Dampers, Penetration Firestops and Joint Systems 55 2015 IBC Dampers, Penetration Firestops and Joint Systems 56

55 56

Copyright 2018 International Code Council 14 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Where penetration protection Penetration of is required fire-resistance-rated walls Section 714 is referenced Best to look at specific Section 714.4 is the Sections 714.4.1.1 and from a number of assembly section before starting point 714.4.1.2 allow: locations looking at 714 . Primary sections are . Test penetration as part . Sections 706.9 and . Sections 707.7.1 and . 714.4.1 (through of overall assembly penetrations) (ASTM E 119 or UL 707.7 are examples – 710.6 are examples 263), or from fire wall and fire . 707.7 does reference . 714.4.2 (membrane penetrations) . Test penetration barrier provisions 714 but 707.7.1 prohibits separately (ASTM E 814 . Section 712.1.4 – from certain penetrations or . Both contain or UL 1479) allows them in specific exceptions the vertical openings locations . An F rating is required provisions . 710.6 does not reference . Both ultimately point for systems 714 for penetrations in back to 714.4.1.1 and smoke partitions 714.4.1.2

2015 IBC Dampers, Penetration Firestops and Joint Systems 57 2015 IBC Dampers, Penetration Firestops and Joint Systems 58

57 58

Penetration firestop systems Through penetrations – 714.4

Are tested and listed systems General requirement is for . Should be installed as tested and described in tested system product directory and manufacturer’s instructions . Exception limited to . Deviations can impact performance steel, ferrous or copper pipes, tubes or conduits Tested systems help . Offers two methods of protection . Demonstrate compliance with code requirements . Focuses on protection of . Provide installer with detailed installation annular space requirements . Item 1 limited to . Provide inspector with document to use for inspection concrete or masonry of the installation walls

2015 IBC Dampers, Penetration Firestops and Joint Systems 59 2015 IBC Dampers, Penetration Firestops and Joint Systems 60

59 60

Copyright 2018 International Code Council 15 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Through penetrations Membrane penetrations Section 714.4.1 Exception Item 2 provides a number of options General requirement is for membrane penetrations . Can allow virtually any material to fill annular space (if to comply with through penetration provisions tested) . Six exceptions . Type of wall is not limited to concrete or masonry . Four applicable to electrical boxes . Size of penetration is not limited . One for boxes other than electrical . Type of penetration is still limited (e.g. washing machine hose connection boxes, hose cabinets, manual fire alarm pull boxes, dryer . Not easy to comply with since it basically exhaust boxes, electrical panel boards, etc.) requires testing and these are not listed . One for sprinkler penetrations products – test information often not available

2015 IBC Dampers, Penetration Firestops and Joint Systems 61 2015 IBC Dampers, Penetration Firestops and Joint Systems 62

61 62

Back-to-back membrane Membrane penetrations penetrations Three means of Membrane penetrations are different than through complying . Tested as part of overall penetrations assembly (714.4.1.1) . Generally code does not address how to deal . Tested separately for F rating (714.4.1.2) with back-to-back penetrations . Comply with an . Exceptions 1 and 2 for outlet boxes do address this exception (There are 6 in 714.4.2 or 2 in . Membrane penetration not covered by one of 714.4.1) the exceptions will essentially require same . Electrical boxes are one of the most protection as through penetration common membrane . Consult manufacturer & listing if concerned with back- penetrations to-back items to see if added protection is needed

2015 IBC Dampers, Penetration Firestops and Joint Systems 63 2015 IBC Dampers, Penetration Firestops and Joint Systems 64

63 64

Copyright 2018 International Code Council 16 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Penetrations of horizontal Penetration of horizontal assemblies assemblies IBC looks at horizontal assemblies as a means of Protection requirements depend on type and compartmenting a building to minimize vertical location of the assembly spread of smoke or fire . Horizontal assemblies may be a floor or a roof . May rely on some type of specific ceiling Penetration protection requirements apply to: construction as integral part of rating . Fire-resistance-rated assemblies (714.5.1 to . Important to protect penetrations through any part 714.5.4) integral to the fire-resistance rating – whether floor, roof or the ceiling membrane beneath them . Nonfire-resistance-rated assemblies (714.6) . Sections 714.5 and 712.1.15 allow unprotected openings through roof deck/slab if not affecting structural integrity

2015 IBC Dampers, Penetration Firestops and Joint Systems 65 2015 IBC Dampers, Penetration Firestops and Joint Systems 66

65 66

Fire-resistance-rated assemblies Horizontal assemblies – Through Scoping penetrations Section 714.5 is horizontal assembly’s equivalent Section 714.5.1 provides two basic methods for of Section 714.4 for walls evaluating through penetrations . Due to exclusions in Sections 714.5. and . Test as part of overall assembly (ASTM E 119 or UL 712.1.15, it does not include the roof of a 263), or roof/ceiling assembly or to a roof which is rated . Test penetration separately (ASTM E 814 or UL 1479) by itself These options were covered previously in Test Standard section and are the same as allowed for walls in 714.4.1 . First option is seldom used

2015 IBC Dampers, Penetration Firestops and Joint Systems 67 2015 IBC Dampers, Penetration Firestops and Joint Systems 68

67 68

Copyright 2018 International Code Council 17 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Horizontal assemblies – Through Through penetration firestop penetrations systems – 714.5.1.2 In lieu of general . Limited to steel, Testing firestop systems in horizontal assemblies options, can use one of ferrous or copper to ASTM E 814 or UL 1479 differs from wall three exceptions conduits, pipes, tubes provisions since testing requires both an F and a T or vents; or to rating . Exception 1 is similar concrete or masonry . T rating is a higher performance criteria and to Item 2 in Exception items more difficult to achieve than F rating for walls in 714.4.1 . Limited to a single . T rating limits temperature increase through the floor penetrant and the firestop system; and does not . Testing per ASTM lessen original assembly performance E119 or UL 263

2015 IBC Dampers, Penetration Firestops and Joint Systems 69 2015 IBC Dampers, Penetration Firestops and Joint Systems 70

69 70

Through penetration firestop Through penetration firestop systems – 714.4.1.2 systems – T Rating exceptions Obtaining T rating Three options to generally requires eliminate T rating insulation of penetrant requirement above and/or below to . Exception 1 relies on limit heat transmission “insulation” protection . Details are described that the wall provides in listing and . Allowed whether wall manufacturer’s is rated or not installation instructions . If wall beneath, must extend to floor – to contain penetrant

2015 IBC Dampers, Penetration Firestops and Joint Systems 71 2015 IBC Dampers, Penetration Firestops and Joint Systems 72

71 72

Copyright 2018 International Code Council 18 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Through penetration firestop Exception 2 – systems – T rating exceptions Eliminating T rating Exception 2 applies to Was added into code because it is conceptually floor drains, tub drains similar to Exception 1 and ceiling helps shield and shower drains penetrant . Must be contained . Should only be used for horizontal assembly and located within where ceiling is part of protection and rating concealed space of . Only applicable to the three specific drains. horizontal assembly Should not use for other penetrants. . Exceptions only eliminate T rating (Not F rating)

2015 IBC Dampers, Penetration Firestops and Joint Systems 73 2015 IBC Dampers, Penetration Firestops and Joint Systems 74

73 74

Through penetration firestop Membrane penetrations systems – T rating exception Exception 3 limited to As general requirement, membrane penetrations use with metal-enclosed are protected the same as through penetrations electrical switchgear . Tested as part of overall assembly, or . 4” maximum diameter . Tested to ASTM E 814 or UL 1479 as firestop system metal penetrant . Eight exceptions permitted in lieu of general . Must go “directly” into provisions enclosure - REQUIRES F-RATING OR COMPLIANCE WITH EXCEPTION 1 OR 2 FROM SECTION 714.5.1 . Eliminates T rating – Code uses through penetration provisions even Still needs F rating or though these are membrane penetrations other exception

2015 Template 75 2015 IBC Dampers, Penetration Firestops and Joint Systems 76

75 76

Copyright 2018 International Code Council 19 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Smoke barriers – 714.5.4 Smoke barrier penetrations

Smoke barrier provisions of Section 709 are Penetrations must be tested to UL 1479 and obtain referenced by a number of other code sections an L rating . Generally used where occupants are unable to . L rating provides quantitative indication of evacuate (hospitals, jails, ambulatory care system’s ability to resist passage of smoke facility), or to compartment building for smoke control system . System must be tested and listed to have an L . May be either walls or horizontal assemblies rating – don’t assume something complies . Both 714.4 and 714.5 reference 714.5.4 . Air leakage test is an optional test under UL 1479 . Generally require a 1-hour rating for barrier . ASTM E 814 test does not contain L rating test protocol

2015 IBC Dampers, Penetration Firestops and Joint Systems 77 2015 IBC Dampers, Penetration Firestops and Joint Systems 78

77 78

Marking and identification Smoke barrier penetrations Section 703.7 Air leakage (L rating) cannot exceed . 5.0 cfm per square foot of penetration opening for each system, or . A total leakage of 50 cfm for any 100 square feet of wall or floor area.

. L rating provides measurable criteria versus subjective provisions (limit, restrict, resist) . L rating determined at both ambient temperature and at elevated temperature

2015 IBC Dampers, Penetration Firestops and Joint Systems 79 2015 IBC Dampers, Penetration Firestops and Joint Systems 80

79 80

Copyright 2018 International Code Council 20 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Maintenance – IFC 703.1 and 704.1 Requires fire-resistance rating of construction “including…firestops…and fire-resistant joint systems” to be maintained. Fire-resistant joint systems . Requires visual inspection by owner on annual basis (IFC 701.5 and 701.6) Section 715 . Not required for inaccessible concealed areas . Repair or replaced if damaged or altered; protected if new penetration . Same intent as 2012 IBC 3401.2 and 3404.1 (lost these sections in 2015 IBC and IEBC)

2015 IBC Dampers, Penetration Firestops and Joint Systems 81 2015 IBC Dampers, Penetration Firestops and Joint Systems 82

81 82

Joint - Definition Joints – Locations & examples Examples: IBC defines a joint as “the opening in or between . Gap between adjacent assemblies that is created due to building adjacent concrete tilt- tolerances, or is designed to allow independent up panels movement of the building in any plane caused by thermal, seismic, wind or any other loading.” . Head of wall/top of wall . Put another way, the joint is the breach or opening in or between adjacent assemblies . Floor and exterior curtain wall . A joint system is used to fill the opening or breach . Expansion joint in floor

2015 IBC Dampers, Penetration Firestops and Joint Systems 83 2015 IBC Dampers, Penetration Firestops and Joint Systems 84

83 84

Copyright 2018 International Code Council 21 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Joints – Locations & examples Joint firestop systems

Test joint systems using Compliant systems ASTM E 1966 or UL . Accommodate cyclical movement of adjacent 2079 assemblies . Neither ASTM E119 . Prevent the passage of flame and hot gases nor UL 263 evaluate sufficient to ignited cotton waste on unexposed performance where side of the assembly wall and floor . Will remain in place when subjected to the hose assemblies connect stream test . ASTM E 2307 used for floor/curtain wall

2015 IBC Dampers, Penetration Firestops and Joint Systems 85 2015 IBC Dampers, Penetration Firestops and Joint Systems 86

85 86

Test criteria – Section 715.3 Where required ASTM E 1966 and UL Section 715.1 states joints “in or between fire- 2079 are essentially resistance-rated” walls or horizontal assemblies equivalent Nonsymmetrical wall joint are required to be protected by approved systems . Both focus on joint systems must be tested from both sides, or from . Most locations are covered by this general and ability to go least fire-resistant side requirement or the exception in 715.1 through movement (similar to 703.2.1 wall test) . There are ten exempt locations in 715.1 cycles . Sections 715.4 through 715.6 contain specific . ASTM E 1966 does • Exception for exterior not evaluate smoke walls with fire separation requirements for certain locations leakage so must use distance greater than 10 UL 2079 for L rating feet.

2015 IBC Dampers, Penetration Firestops and Joint Systems 87 2015 IBC Dampers, Penetration Firestops and Joint Systems 88

87 88

Copyright 2018 International Code Council 22 2018 IBC Dampers, Penetration Firestops and Joint Systems 9/16/2019

Exception from 715.1

The exception in 715.1 list ten locations where joint systems are not required to be installed . Most eliminate joint protection due to fact that some other code provision would allow a fire to circumvent the joint system . Therefore code cannot justify requiring a joint system where the fire can bypass it by another route

2015 IBC Dampers, Penetration Firestops and Joint Systems 89

89

Copyright 2018 International Code Council 23