Valve terminal type 03/05 Electronics Manual Field bus connection FB14
Field bus protocols: CANopen SDS Smart Distributed System
9801A 163959 GB VIFB14 - 03/05
Author: S. Breuer, H. Hohner, H.-J.Drung Editor: H.-J. Drung, M. Holder Translation: Douglas Smith Layout: Festo, Dept. PV-IDM Type setting: DUCOM
Edition: January 1998
(Festo AG & Co., D-73726 Esslingen, 1998)
The copying, distribution and utilization of this document as well as the communication of its contents to others without expressed authoriza- cycled paper cycled tion is prohibited. Offenders will be held liable for the payment of damages. All rights reserved, in particular the right to carry out patent, utility model or ornamental design
printed on 100% re registrations.
9801 A I VIFB14 - 03/05
Part no.: 163 959
Titel: MANUAL
Designation: P.BE-VIFB14-03/05-GB
II 9801 A VIFB14 - 03/05
Contents GENERAL SAFETY INSTRUCTIONS IX Designated use IX Target group X IMPORTANT USER INSTRUCTIONS XI Danger categories XI Pictograms XII Instructions on this manual XIII Service XV
Chapter 1 SYSTEM SUMMARY 1.1 SYSTEM SUMMARY 1-3 System structure 1-3 Type 03: Description of components 1-5 Type 05: Description of components 1-9
Chapter 2 FITTING 2.1 FITTING THE COMPONENTS 2-3 Input/output modules 2-4 End plates 2-6 Hat rail clamping unit (type 03) 2-8 2.2 TYPE 03: FITTING THE VALVE TERMINAL 2-9 Fitting onto a wall (type 03) 2-9 Fitting onto a hat rail (type 03) 2-10 2.3 TYPE 05: FITTING THE VALVE TERMINAL 2-13 Fitting onto a wall (type 05) 2-13
9801 A III VIFB14 - 03/05
Chapter 3 INSTALLATION 3.1 GENERAL CONNECTION TECHNIQUES 3-3 Selecting the field bus cable 3-4 Selecting the operating voltage cable 3-5 Connecting the cables to the plugs/sockets 3-6 3.2 FIELD BUS NODE 3-8 Opening and closing the node 3-8 Configuring the valve terminal 3-11 Setting the station number with CANopen 3-12 Permitted station numbers 3-13 Setting the field bus baud rate 3-19 Setting the field bus protocol 3-20 3.2.1 TYPE 03: CONNECTING THE OPERATING VOLTAGES 3-21 Calculating the current consumption for type 03 3-25 Connection example (type 03) 3-27 3.2.2 TYPE 05: CONNECTING THE OPERATING VOLTAGES 3-29 Calculating the current consumption for type 05 3-33 Connection example (type 05) 3-36 3.2.3 CONNECTING THE FIELD BUS 3-38 Connection instructions for CANopen 3-42 Connecting instructions for the Smart Distributed System 3-43 Terminating resistor 3-44 3.3 CONNECTING THE INPUT MODULES 3-45 Pin assignment 3-47 3.4 CONNECTING THE OUTPUT MODULES 3-48 Pin assignment 3-50
IV 9801 A VIFB14 - 03/05
Chapter 4 COMMISSIONING 4.1 BASIC PRINCIPLES OF CONFIGURATION AND ADDRESSING 4-5 General 4-5 Switching on the operating voltage 4-6 Calculating the configuration data 4-7 Calculating the number of inputs/outputs type 03 4-9 Calculating the number of inputs/outputs type 05 4-10 Address assignment of the valve terminal 4-11 General type 03 and type 05 4-11 Basic rule 1 4-12 Basic rule 2 4-15 Address assignment after extension/conversion 4-16 Addressing example type 03 MIDI/MAXI valves 4-19 Addressing example type 05 ISO valves 4-20 4.2 BASIC PRINCIPLES OF COMMISSIONING AND DIAGNOSIS 4-21 General 4-21 Selecting the inputs/outputs 4-21 General information on CANopen 4-22 Brief summary of scope of function 4-23 Summary of object directory 4-24 Default identifier distribution 4-27 Summary of object directory 4-28 PDO communication parameter record 4-29 PDO communication mapping parameter field 4-31 Digital inputs 4-32 Digital outputs 4-32 Reaction of the digital outputs in the event of a fault 4-33 Definition of emergency object 4-35
9801 A V VIFB14 - 03/05
Addressing inputs and outputs 4-36 Examples: communication process 4-38 Diagnosis of status bits 4-41 Position of the status bits 4-42 4.3 BASIC PRINCIPLES OF THE SMART DISTRIBUTED SYSTEM (HONEYWELL) 4-43 General information 4-43 Commissioning 4-43 Number of inputs and outputs 4-44 Summary of implemented object models 4-45 Summary of actions 4-48 Summary of events 4-49 Assignment of SDS IDs 4-49 Diagnosis 4-50 Diagnosis via status bits 4-51 Setting the transmission mode 4-53 Bus configuration 4-54 4.3.1 CONFIGURING/ADDRESSING THE HONEYWELL SDS PC CONTROL 4-55 General information 4-55 Settings in the Device Editor 4-55 Settings in the Tag Editor 4-58 Setting the transmission types for inputs by means of the programming software 4-60 Setting the Cyclical Timer 4-61 Diagnosis 4-63 Diagnosis via the network manager 4-63 Diagnosis via the SDS user program 4-63 Structure of the SDS diagnostic register 4-65 Diagnosis via the status bits 4-66
VI 9801 A VIFB14 - 03/05
4.3.2 CONFIGURING/ADDRESSING WITH THE GE FANUC SERIES 90/30 4-67 General information 4-67 Bus configuration 4-68 Assigning the I/O addresses 4-68 Diagnosis 4-73 Diagnosis via the SDS interface 4-73 Diagnosis via status bits 4-75
Chapter 5 DIAGNOSIS AND ERROR TREATMENT 5.1 SUMMARY OF DIAGNOSTIC POSSIBILITIES 5-3 5.2 ON-THE-SPOT DIAGNOSIS 5-4 LED display (node) 5-4 Valves 5-8 Input/output modules 5-10 5.3 TESTING THE VALVES 5-11 5.4 STATUS BITS 5-13 5.5 ERROR TREATMENT 5-15 Reaction to faults in the CANopen 5-16 Reaction to faults in the Smart Distributed System 5-17 Short circuit/overload at an output module 5-18
9801 A VII VIFB14 - 03/05
APPENDIX A TECHNICAL APPENDIX TECHNICAL SPECIFICATIONS A-3 CABLE LENGTH AND CROSS SECTION A-7 Calculating with a graph A-8 Calculating with a formula A-10 EXAMPLES OF CIRCUITRY A-12 Operating voltage connection type 03 A-12 Operating voltage connection type 05 A-13 4-input module (PNP) A-14 8-input module (PNP) A-15 4-input module (NPN) A-16 8-input module (NPN) A-17 4-output module (NPN) A-18 ACCESSORIES A-19 Bus connection A-19
APPENDIX B INDEX
VIII 9801 A VIFB14 - 03/05 General safety instructions
GENERAL SAFETY INSTRUCTIONS
Designated use The valve terminal type 03/05 described in this manual is designated exclusively for use as follows: • for controlling pneumatic and electrical actuators (valves and output modules) • for interrogating electrical sensor signals by means of the input modules. Use the valve terminal only as follows: • as designated in the instructions • in technically faultless condition • without any modifications. The specified limit values for pressures, tempe- ratures, electrical data, moments, etc. must be observed when additional commercially- available components such as sensors and actuators are connected.
Please comply also with national and local safety laws and regulations.
9801 A IX VIFB14 - 03/05 General safety instructions
Target group This manual is directed exclusively at technicians who are trained in control and automation technology and who have experien- ce in installing, commissioning, programming and diagnosing programmable logic controllers (PLC) and field bus systems.
X 9801 A VIFB14 - 03/05 General safety instructions
IMPORTANT USER INSTRUCTIONS
Danger categories This manual contains instructions on the possi- ble dangers which can occur when the valve terminals types 03/05 are used.
A distinction is made between the following instructions:
WARNING This means that injury to human beings as well as material damage can occur if these in- structions are not observed.
CAUTION This means that material damage can occur if these instructions are not observed.
PLEASE NOTE This means that this instruction must also be observed.
9801 A XI VIFB14 - 03/05 General safety instructions
Pictograms Pictograms and symbols supplement the dan- ger instructions and draw attention to the consequences of dangers. The following picto- grams are used:
Uncontrolled movements of loose tubing.
Uncontrolled movement of the connected actuators.
High electric voltage or undefined switching states of the electronic components which affect the connected circuits.
Electrostatically vulnerable components which will be destroyed if their contact surfaces are touched.
The ISO valve terminal type 05 is very heavy. Please ensure that it is fastened correctly and see that all operating personnel wear safety shoes.
XII 9801 A VIFB14 - 03/05 General safety instructions
Instructions on this manual The following product-specific abbreviations are used in this manual:
Abbreviation Meaning
Terminal Valve terminal type 03 (MIDI/MAXI) or type 05 (ISO) with/without electrical I/Os
Node Field bus node
Sub-base Pneumatic sub-base for valves
Single sub-base for single solenoid valves type 03 (MIDI/MAXI)
Double sub-base for double solenoid valves or mid-position valves type 03 (MIDI/MAXI)
ISO sub-base Manifold base for 4, 8 or 12 valves type 05 (ISO 5599/I, size 1 or 2)
I Input O Output I/O Input/output
P module Pneumatic module in general
I/O module Module with digital inputs/outputs
Fig. 1: Abbreviations
Valve terminal type 03/05 consists basically of the following components: • the node • pneumatic modules (valve sub-bases with valve and valve bridge or intermediate air supply modules). • electronic modules (4 or 8-input modules, 4-output modules).
9801 A XIII VIFB14 - 03/05 General safety instructions
This electronics manual describes node FB14 and the input/output modules.
PLEASE NOTE All information on the pneumatic modules is to be found in the Pneumatics Manual P.BE-MIDI/MAXI-03-GB or P.BE-ISO-05-GB.
Valve terminals types 03/05 consist of different components:
PLEASE NOTE A valve terminal with four pneumatic valve sub-bases and four input/output modules is used for the diagrams in this manual.
Fig. 2: Standard fitting for the drawings
XIV 9801 A VIFB14 - 03/05 General safety instructions
The valve terminals can be connected to the control systems of various manufacturers. This manual describes the protocols CANopen and SDS and the addressing.
Interface manufacturer Controller Interface Field bus
ESD GmbH VME-System VME-CAN2 Vahrenwalder Str. 205 VME-System VME-CAN2B D-30165 Hannover S5-115U ... 155U CAN-CS515 S5-95U, S5-100U CAN-CS595
Janz Computer AG VME-System VMOD-ICAN2 Im Dörener Feld 8 VME-System VMOD-ICAN3 D-33100 Paderborn CANopen Eberle Controls GmbH PLS vario CAN 21 Postfach 130 153 PLS 514 CAN 41 D-90113 Nürnberg
Selectron System GmbH Selecontrol MAS CBI 751 Schupferstr. 1 IPC/PC PCI 517 D-90482 Nürnberg
Fig. 3: Summary of possible controllers/field bus protocols (extract)
Service If you have any technical problems, please consult your local Festo Service.
9801 A XV VIFB14 - 03/05 General safety instructions
XVI 9801 A VIFB14 - 03/05 1. System summary
1. SYSTEM SUMMARY
9801 A 1-1 VIFB14 - 03/05 1. System summary
Contents
1.1 SYSTEM SUMMARY 1-3 System structure 1-3 Type 03: Description of components 1-5 Type 05: Description of components 1-9
1-2 9801 A VIFB14 - 03/05 1. System summary
1.1 SYSTEM SUMMARY
System structure Festo offers a solution to automation problems at machine level with valve terminals. Valve terminals of types 03 and 05 are constructed on a modular basis and permit combinations of pneumatic and electronic modules such as the
following:
AA AAAAAAAA AAAA AAAA AAAA AAAA AAAA AAAA
AAAA AA AAAA AAAA AAAA AAAA AAAA AAAA AAAA
AAAA AA AAAA AAAA AAAA AAAA AAAA AAAA AAAA
AAAA AA AAAAAAAA AAAA AAAAAAAAAAAAAAAAAAAAAAAAAAAAAA AA AA AA AA AAAA AAAA AAAA AAAA
AAAAAAAAAA AAAAAAAAAAAAAAAAAAAAAAAA AA AA AA AA
A A A A AA AAAAA AAAAA A AAAAAAAAA AA AA AAAAAAA AAAA AAAA AA AA AAAAAAAAAA AA AA AA AA
AAAA AA AA AAAAAAA AAAA AAAA AAAAAAAAAA AAA A A AAAAA AAAAAAAAAAAAAA AA AA AA AA AA
Industrial PC/ AAAA
AAAAAAAAAA AAAA AA AAAAAAAAAAAAAAAAAAAAA AAAAAA AA AA AA AA A A A AA A A A A A
AAAAAAAAAAAAAAAA AAAA AA AAAAAAAAAAAAAAAAAAAAAAAAAAA AAAAAA AAAAAA A A A AA A A A A A AA AA AA
controller AA
AAAAAAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAAAAAAAAA AA AA AA AA
AAAAAAAAAAAAAAAAAAA AA AA AAAAAAA AAAA AAAA A A A A A AA A A A A A AA AA AA AA
AAAAAAAAAAAAAA AAAA AAAA AAAAAAAAAAAAAAAAAAAAAAAA AA AA AA AA
AA AA AAAAAAA AAAA AAAA A AAA AAA AA A AAA A AAA A
AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
Field bus
Valve terminal type 03: MIDI/MAXI valves and electronic modules
Valve terminal type 03: only MAXI valves
Valve terminal type 05: ISO valves and electronic modules
Further field bus slaves
Fig. 1/1: System summary and possible variants of the valve terminals
9801 A 1-3 VIFB14 - 03/05 1. System summary
The valve terminal with field bus connection offers the following advantages: • can be fitted with digital I/Os and pneumatic valves • subsequent extension/conversion possible • small-scale valves • can be connected to various control systems • less wiring due to two-core cables • clarity in system structure due to physical se- paration of controller and machine • valves already fitted • pre-wired (pilot) valve solenoid coils • central compressed air supply • central exhust • device already tested
A field bus system also offers the following advantages: • fewer output modules in the controller • economic data transfer over long distances • high baud rate • a large number of slaves can be connected • error diagnosis is made easier
1-4 9801 A VIFB14 - 03/05 1. System summary
Type 03: Description of components Valve terminal type 03 consists of individual modules. Each module is assigned with diffe- rent functions as well as different connecting, display and operating elements. These are summarized in the diagram below.
3 2 1 4 5 4 5 4 5 4 6
Figure Module 1 Node FB14 2 Electronic modules (input/output modules), fitted with • digital inputs (modules with 4 or 8 inputs) • digital outputs (modules with 4 outputs) 3 End plate left with opening for additional earth/ground connection 4 Pneumatic MIDI, MAXI modules (sub-bases) fitted with S-valves: • 5/2-way solenoid valves • 5/2-way double solenoid valves • 5/3-way mid-position valves (exhausted, pressurized, blocked) • blanking plates S = auxiliary pilot air 5 Pneumatic MIDI, MAXI modules: • pressure supply with integrated exhaust (MIDI) • intermediate pressure supply with integrated exhaust (MIDI) • pressure supply adapter with/without regulator (MIDI – MAXI) • additional pressure supply (MAXI) 6 End plate right, depending on size of last sub-base with either: • common pneumatic tubing and integrated regulator for 5 bar auxiliary pilot air (non-regulated auxiliary pilot air is not permitted) • common pneumatic tubing connections, but without regulator • without common tubing connections (only MAXI) Fig. 1/2: Modules of the valve terminal type 03
9801 A 1-5 VIFB14 - 03/05 1. System summary
The following connecting, display and opera- ting elements are to be found on the electronic modules:
1 2 3 4 5 6 7 8
O4 O4 I4 I8
11 10 9
Figure Meaning 1 Output socket for electrical output 2 Yellow LED (status display per output) 3 Red LED (error display per output) 4 Input socket for one electrical input 5 Green LED (per input) 6 Input socket for two electrical inputs 7 Two green LEDs (one LED per input) 8 Node with LEDs and field bus connection detailed description in chapter "Installation" 9 End plate right 10 Fuse for inputs/sensors 11 Operating voltage connection Fig. 1/3: Display and operating elements on the electronic modules
1-6 9801 A VIFB14 - 03/05 1. System summary
The connecting, display and operating elements shown below are to be found on the pneumatic MIDI modules type 03.
1 234 5
6
9 8 7
Figure Meaning 1 Node with LEDs and field bus connection, detailed description in chapter "Installation" 2 Yellow LEDs 3 Manual override for valve solenoid coils 4 Valve location inscription field 5 Unused valve location with blanking plate 6 Common tubing connections 7 Work connections (per valve) 8 Fuse for inputs/sensors 9 Operating voltage connection Fig. 1/4: Operating, display and connecting elements
9801 A 1-7 VIFB14 - 03/05 1. System summary
The following connecting, display and operating elements are to be found on the pneumatic MAXI modules type 03.
1 2 3 4 5
6
10 9 8 7
Figure Meaning 1 Node with LEDs and field bus connection, detailed description in the chapter "Installation" 2 Yellow LEDs (per valve solenoid coil) 3 Manual override (per valve solenoid coil) 4 Valve location inscription field (designation labels) 5 Unused valve location with blanking plate 6 Common tubing connections 7 Work connections (2 per valve, one above the other) 8 Regulator for limiting the pressure of the auxiliary pilot air 9 Common tubing connection 10 Exhaust connections
Fig. 1/5: Operating, display and connecting elements of the MAXI modules type 03
1-8 9801 A VIFB14 - 03/05 1. System summary
Type 05: Description of components Valve terminal type 05 consists of individual mo- dules. Each module is assigned with different functions as well as different connecting, display and operating elements. These are summarized in the diagram below.
3 2 1 4 5 6
Figure Module 1 Node FB14 2 Electronic modules (input/output modules), fitted with • digital inputs (modules with 4 or 8 inputs) • digital outputs (modules with 4 outputs) 3 End plate left with opening for additional earthing connection 4 Pneumatic modules (manifold sub-bases) fitted with: • Pneumatic valves with hole pattern as per ISO 5599/I - Pneumatic single solenoid valves - Pneumatic double solenoid valves - Pneumatic mid-position valves • Components for vertical linking (pressure regulator intermediate plate, throttle plate, etc.) • Blanking plates 5 Adapter plate for ISO sub-base (manifold sub-bases) as per ISO 5599/I sizes 1 and 2 6 End plate right with fitting holes and thread for M8 ring screws (for transport) Fig. 1/6: Modules of valve terminal type 05
9801 A 1-9 VIFB14 - 03/05 1. System summary
The connecting, display and operating ele- ments shown below are to be found on the pneumatic ISO modules type 05.
1 2 3 4 5 6 7 8
9
12 10 10
9 11
Figure Module 1 Node with LEDs and field bus connection, detailed description in the chapter "Installation" 2 Fuse for inputs/sensors 3 Adapter plate 4 Operating voltage connection for terminal type 05 5 Fuses for valves 6 Valve location inscription field 7 Yellow LEDs (per pilot solenoid coil) 8 Manual override (per pilot solenoid coil, either pushing or locking) 9 External control connection 10 Common pneumatic tubing connections 11 Work connections (per valve) 12 Adapter cable for operating voltage supply to node and I/O modules
Fig. 1/7: Operating, display and connecting elements of ISO modules type 05
The electronic modules have already been de- scribed in the section "Description of compo- nents type 03."
1-10 9801 A VIFB14 - 03/05 1. System summary
Incoming field bus Continuing field bus
1
Node
4
2 AA
AA 1 = Compressed air
AA AA
AA AA 2 , 4 = Work air
Electrical signal flow
Fig. 1/8: Function summery of valve terminal type 03/05
The node controls the following functions: • connection of the terminal to the field bus module of your control system and to further field bus slaves via the field bus interface • adaption of the field bus baud rate and protocol to the control system • control of data transfer to/from the field bus module of your control system • internal control of the terminal
9801 A 1-11 VIFB14 - 03/05 1. System summary
The input modules process the input signals (e.g. from sensors) and transmit these signals via the field bus to the controller. The output modules are universal electrical outputs and control low current consuming devices, e.g. further valves, lights etc..
The pneumatic modules provide the following: • common channels for supply air and ex- haust • electrical signals from all solenoid valve coils Work connections 2 and 4 have been provided for each valve location on the individual pneumatic modules.
The common channels in the pneumatic end plate or special intermediate supply modules are used to supply the valves with compressed air and to vent the exhaust and pilot exhaust air. Futher modules for intermediate air supply are also available, e.g. in order that different working pressures can be used or that MIDI/MAXI valves or ISO valves can be fitted on a node.
Further information on their use can be found in the pneumatics manual for your valve terminal. Only the electronic modules and the node are described here.
1-12 9801 A VIFB14 - 03/05 2. Fitting
2. FITTING
9801 A 2-1 VIFB14 - 03/05 2. Fitting
Contents
2.1 FITTING THE COMPONENTS 2-3 Input/output modules 2-4 End plates 2-6 Hat rail clamping unit (type 03) 2-8
2.2 TYPE 03: FITTING THE VALVE TERMINAL 2-9 Fitting onto a wall (type 03) 2-9 Fitting onto a hat rail (type 03) 2-10
2.3 TYPE 05: FITTING THE VALVE TERMINAL 2-13 Fitting onto a wall (type 05) 2-13
2-2 9801 A VIFB14 - 03/05 2. Fitting
2.1 FITTING THE COMPONENTS
WARNING Before fitting the components, switch off the following: • the compressed air supply • the power supply for the outputs (pin 2) • the power supply for the electronic components (pin 1)
You can thereby avoid: • uncontrolled movements of loose tubing • undesired movements of the connected actuators • undefined switching states of the electronic components
CAUTION The valve terminal components contain electrostatically vulnerable elements. • Do not therefore touch any contact surfaces on the side plug connectors of the components. • Please observe the instructions for handling elements liable to damage by electrostatic charges.
You thereby avoid destroying the valve termi- nal components.
9801 A 2-3 VIFB14 - 03/05 2. Fitting
PLEASE NOTE Treat all the modules and valve terminal com- ponents with great care. Pay special attention to the following: • Screw connections must not be distorted or subjected to mechanical stress. • The screws must fit exactly (otherwise the threads will be damaged). • The specified torques must be observed. • The modules must be aligned correctly (IP 65). • The contact surfaces must be clean (avoid leaks and faulty connections). • The contacts of type 03-MIDI valve solenoid coils must not be bent (they are not resistant to bending in alternate directions, i.e. they will break off if bent backwards). Please observe also the fitting instructions en- closed with modules and components ordered at a later date.
Input/output modules Before the valve terminal can be extended or converted, it must first be dismantled.
Dismantling (see also following diagram) • Remove completely the screws of the rele- vant modules. The modules are now held to- gether only by the plug connectors. • Pull the modules carefully and without tilting away from the plug connectors. • Replace any seals which are damaged.
2-4 9801 A VIFB14 - 03/05 2. Fitting
Fitting (see also following diagram)
PLEASE NOTE • Modules ordered at a later date should be placed, where possible, after the last module before the end plate. • Do not fit more than 12 electronic modules.
Fit the modules as follows: • Fit a (new) seal on the right-hand contact surface facing the node. • Then fit the module as shown in the diagram below.
Seal
Fastening screws max. 1 Nm
Fig. 2/1: Fitting the electronic I/O modules
9801 A 2-5 VIFB14 - 03/05 2. Fitting
End plates A left-hand and a right-hand end plate are required as a mechanical termination of the valve terminal. These end plates fulfil the following functions: • They comply with protection class IP 65. • They contain connections/contacts for the protective earth cable. • They contain openings for fitting onto walls and onto the hat rail clamping unit.
The right-hand end plate of the ISO terminal is connected conductively via screw connectors and ready fitted spring contacts to the manifold sub-base. It is therefore sufficently earthed.
There are different designs of right-hand end plate for terminal type 03 (MIDI/MAXI). Each design has a ready fitted protective earth cable.
CAUTION Before operating terminal type 03, you must earth the right-hand end plate by means of the protective earth cable. This is to avoid high voltages on the metal surface if there is a technical fault.
2-6 9801 A VIFB14 - 03/05 2. Fitting
Earth the end plates as follows: • Right-hand end plate (type 03) In order to earth the right-hand end plate, connect the cable fitted inside to the appropriate contacts on the pneumatic mo- dules or node (see following diagram). • Left-hand end plate (types 03 and 05) Connect the left-hand end plate conducti- vely to the other components by means of the ready fitted spring contacts. Please note: Instructions on earthing the complete valve terminal are to be found in the chapter "Installation".
The following diagram shows how both end plates are fitted.
Seal Contact for protective earth cable
Seal
Pre-fitted protective Fastening screws earth cable max. 1 Nm
Fig. 2/2: Fitting the end plates (example terminal type 03)
9801 A 2-7 VIFB14 - 03/05 2. Fitting
Hat rail clamping unit (type 03) If the valve terminal is to be fitted onto a hat rail (support rail as per EN 50022), you will require a hat rail clamping unit. The hat rail clamping unit is fastened to the back of the end plates as shown in the diagram below.
Before fitting ensure that: • the fastening surfaces are clean (clean with spirit); • the flat head screws are tightened (6).
After fitting ensure that: • the levers are secured with a locking screw (7).
1 Self adhesive rubber foot 2 Clamping elements 3 Left-hand lever *) 4 Right-hand lever *) 5O-ring 6 Flat head screw 7 Retaining screw
*) Different lever lengths with MIDI and MAXI Fig. 2/3: Fitting the hat rail clamping unit
2-8 9801 A VIFB14 - 03/05 2. Fitting
2.2 TYPE 03: FITTING THE VALVE TERMINAL
Fitting onto a wall (type 03)
WARNING In the case of long terminals, use additional support brackets approx. every 200 mm. You thereby avoid: • overloading the fastening eyes on the end plates • the terminal sagging • natural resonances
Proceed as follows: • Calculate the weight of the terminal (weigh or estimate). General rule:
MIDI MAXI Per pneumatic module 800 g 1200 g per node 1000 g 1000 g Per electronic module 400 g 400 g
• Make sure that the fastening surface can support this weight.
9801 A 2-9 VIFB14 - 03/05 2. Fitting
• Fasten the terminal with four M6 screws as shown below (fitting position as desired). Use spacers if necessary.
7.6 mm
M6
Fig. 2/4: Fitting terminal type 03 on a wall
Fitting onto a hat rail (type 03) The terminal is suitable for fitting onto a hat rail (support rail as per EN 50022). For this purpose there is a guide groove on the rear of all modules for hanging the terminal on the hat rail.
CAUTION • Fitting onto the hat rail without the hat rail clamping unit is not permitted. • If the terminal is fitted in a sloping position or is subjected to vibration, protect it against slipping and use the screws supplied (7) to protect it against unintentional loosening/ opening.
2-10 9801 A VIFB14 - 03/05 2. Fitting
PLEASE NOTE • If the terminal is fitted in a horizontal position and is not subjected to vibration, the fasten- ing of the hat rail clamping unit will be suf- ficient without the screws (7). • If your terminal does not have a hat rail clamping unit, this can be ordered and fitted at a later date. • Whether MIDI or MAXI clamping units are to be used depends on the end plates (MIDI/MAXI).
Proceed as follows: • Calculate the weight of the terminal (weigh or estimate). General rule:
MIDI MAXI
Per pneumatic module 800 g 1200 g
Per node 1000 g 1000 g Per electronic module 400 g 400 g
• Make sure that the fastening surface can support this weight.
9801 A 2-11 VIFB14 - 03/05 2. Fitting
• Fit a hat rail (support rail as per EN 50022 - 35x15; width 35 mm, height 15 mm). • Fasten the hat rail to the fastening surface at least every 100 mm. • Hang the terminal onto the hat rail. Secure the terminal on both sides against tilting or slipping with the hat rail clamping unit (see diagram below). • If the terminal is fitted in a sloping position or is subjected to vibration, use two screws (7) to protect the hat rail clamping unit against unintentional loosening/opening.
Valve terminal type 03
Hat rail clamping unit Locking screw (7)
Fig. 2/5: Fitting terminal type 03 onto a hat rail
2-12 9801 A VIFB14 - 03/05 2. Fitting
2.3 TYPE 05: FITTING THE VALVE TERMINAL
Fitting onto a wall (type 05)
WARNING In the case of long terminals with several I/O modules, use additional support brackets ap- proximately every 200 mm. You thereby avoid: • overloading the fastening eyes on the left-hand end plate • the terminal sagging (I/O side) • natural resonances
• Proceed as follows: • Calculate the weight of the terminal (weigh or estimate). General rule:
ISO ISO Size 1 Size 2
Sub-base *) - 4 valve locations with valves 8 kg 12 kg - 8 valve locations with valves 14 kg 20 kg - 12 valve locations with valves 20 kg 28 kg Per node 1 kg 1 kg
Per electronic module 0.4 kg 0.4 kg
*) Components for vertical linking: For weight see Pneumatics Manual P.BE-ISO-05-GB.
• Make sure that the fastening surface can support this weight.
9801 A 2-13 VIFB14 - 03/05 2. Fitting
Fasten the terminal as follows: • with three M10 screws on the adapter plate and on the right-hand end plate (2); • with two M6 screws on the left-hand end plate (1). If necessary, use the following additional fastening methods: • the opening on the bottom of the right-hand end plate with an M10 thread ("blind hole" 3); • the support bracket for the I/O modules (see fitting instructions with support bracket). The terminal can be fitted in any position. If necessary, use spacers and the thread for an M8 ring screw (transport aid).
Thread for M8 ring screw (for transport) 1 2
3
M6
M10
Fig. 2/6: Fitting an ISO terminal type 05 on wall
2-14 9801 A VIFB14 - 03/05 3. Installation
3. INSTALLATION
9801 A 3-1 VIFB14 - 03/05 3. Installation
Contents
3.1 GENERAL CONNECTION TECHNIQUES 3-3 Selecting the field bus cable 3-4 Selecting the operating voltage cable 3-5 Connecting the cables to the plugs/sockets 3-6
3.2 FIELD BUS NODE 3-8 Opening and closing the node 3-8 Configuring the valve terminal 3-11 Setting the station number with CANopen 3-12 Permitted station numbers: 1; ...; 98 3-13 Setting the field bus baud rate 3-19 Setting the field bus protocol 3-20 3.2.1 Type 03: Connecting the operating voltages 3-21 Calculating the current consumption for type 03 3-25 Connection example (type 03) 3-27 3.2.2 Type 05: Connecting the operating voltages 3-29 Calculating the current consumption for type 05 3-33 Protective earthing 3-35 Connection example (type 05) 3-36 3.2.3 Connecting the field bus 3-38 Connection instructions for CANopen 3-42 Connecting instructions for the Smart Distributed System 3-43 Terminating resistor 3-44
3.3 CONNECTING THE INPUT MODULES 3-45 Pin assignment 3-47
3.4 CONNECTING THE OUTPUT MODULES 3-48 Pin assignment 3-50
3-2 9801 A VIFB14 - 03/05 3. Installation
3.1 GENERAL CONNECTION TECHNIQUES
WARNING Before installation or maintenance work is car- ried out, the following must be switched off: • the compressed air supply • the power supply to the electronic components (pin 1) • the power supply to the outputs/valves (pin 2).
You thereby avoid: • uncontrolled movements of loose tubing • undesired movements of the connected actuators • undefined switching states of the electronic components
9801 A 3-3 VIFB14 - 03/05 3. Installation
Selecting the field bus cable A twisted, screened 4-core cable should be used as the field bus cable.
PLEASE NOTE You must refer to the PLC manual for your controller to see which type of cable you should use. Also take into account the distan- ce and the field bus baud rate selected.
The table below shows the approximate values for the maximum distances depending on the baud rate selected. Precise specifications are to be found in the manuals for your control system.
Baud rate Maximum Max. branch distance length
1000 kBaud 10-40 m 0.3 m
500 kBaud 50-100 m 0.75 m - 3 m
125 kBaud 500 m 3 m
20 kBaud 1000 m 7.5 m
Not all the baud rates named can be used with all PLCs, controllers or PCs/IPCs.
Please note also any restrictions of the maxi- mum branch length.
3-4 9801 A VIFB14 - 03/05 3. Installation
Selecting the operating voltage cable Several parameters must be taken into consi- deration when the operating voltages are connected. Further information can be found in subsequent chapters. • Chapter 3: Installation Section: "Connecting the operating voltages" - Calculating the current consumption - Type of power unit - Cable length and cross section • Chapter 3: Installation Section: "Connecting the field bus" - Calculating the current consumption bus interfaces - Cable length and cross section • Appendix A: Cable length and cross section - Calculating the length and cross section with a table - Calculating with a graph
9801 A 3-5 VIFB14 - 03/05 3. Installation
Connecting the cables to the plugs/sockets
CAUTION The position of the pins is different depending on whether they are in the form of plugs or sockets. • The connections of the input and output modules are in the form of sockets. • The connections of the field bus interface and tf the operating voltage are in the form of plugs. The pin assignment can be found in the chapters which follow.
When you have selected suitable cables, connect them according to steps 1...7. 1. Open the plugs/sockets as follows (see diagram): • Power supply socket Insert the power supply socket into the operating voltage connection on the valve terminal. Unscrew the housing of the socket and remove it. The socket remains inserted in the operating voltage connection. • Sensor plug and field bus socket Unscrew the centre knurled nut. 2. Open the strain relief on the rear part of the housing. Pass the cable through as shown in the diagram below.
3-6 9801 A VIFB14 - 03/05 3. Installation
Cable outer diameter PG7: 4.0 ... 6.0 mm PG9: 6.0 ... 8.0 mm PG13.5: 10.0 ... 12.0 mm Plugs/sockets (straight or angled) power supply socket: PG7, 9 or 13.5 sensor plug: PG7 bus cable socket: PG9
AAAA Cable
AAA A AAAA Strain relief
Housing
AAA
AAA
AA A
A AA
AAAA AAA AAAA AAA
AAA Connecting
AAAAAA AAAAAA A A
AAA AAA AAAAAAA AAAAAAA
AAAA part AAAAAA AAAAAA A A
AAAAAAA AAAAAAA
Socket Plug
Fig. 3/1: Individual plug/socket parts and cable routing
3. Remove 5 mm of insulation from the end of the cable. 4. Fit the strands with cable end sleeves. 5. Connect the ends of the cables. 6. Close the strain relief again and screw the housing back onto the socket. Pull the cable back so that it is not looped inside the hou- sing. 7. Tighten the strain relief.
9801 A 3-7 VIFB14 - 03/05 3. Installation
3.2 FIELD BUS NODE
Opening and closing the node
WARNING Before installation or maintenance work is car- ried out, the following must be switched off: • the compressed air supply • the operating voltage supply to the electronic components (pin 1). • the operating voltage supply to the outputs/valves (pin 2).
You thereby avoid: • uncontrolled movements of loose tubing • undesired movements of the connected actuators • undefined switching states of the electronic components.
3-8 9801 A VIFB14 - 03/05 3. Installation
CAUTION The valve terminal node contains electro- statically vulnerable components. • Do not therefore touch any components. • Observe the regulations for dealing with electrostatically vulnerable components.
In this way the electronic components of the node will not be destroyed.
The following connecting and display elements
are to be found on the cover of the node. AAA
Green LED AAA MOD/NET AAA AAAPOWER
STATUS Red LED
AAA AAA AAA
Green LED BUS AAAERROR AAA POWER AAA Green LED
Plug for BUS field bus cable
Fuse for Operating operating voltage voltage of connection inputs
Fig. 3/2: Cover of node
9801 A 3-9 VIFB14 - 03/05 3. Installation
PLEASE NOTE The cover is connected to the internal printed circuit boards by means of the operating volt- age cable. It cannot, therefore, be removed completely.
• Opening Unscrew and remove the 6 Philips screws in the cover. Carefully lift up the cover. Do not damage the cable through mechanical stress. • Closing Replace the cover. Place the operating voltage cables back into the housing so that they are not clamped. Tighten the Philips screws in the cover in diagonally opposite sequence.
3-10 9801 A VIFB14 - 03/05 3. Installation
Configuring the valve terminal There are four printed circuit boards in the node. Board 2 contains two LEDs and a plug for the field bus cable; board 3 contains two LEDs and switches for setting the configurati-
on.
AA AAA AA
Green LED AAA Green LED
AA
AA AA
AAA AA
Green LED AA Red LED
AAA AA AA AA 8 AA
7 AA
6 9
5 0 1
2 4
3 A Address A
Plug for A
A A
AAA selector
A AA A A A
A AAA A field bus 7 8 A
6 9 A A
A switch
5 0
1
A A 4 2
cables 3
A A
A (station number)
A A
A A A 1
2 AA Baud rate 3 AA 4 AA
AA Protocol
AA AA
Board 1 AA AA AA Board 4
Screening AAA AAA Board 2 Board 3
Flat plug for operating voltage connection
Fig. 3/3: Connecting, display and operating elements of the node
9801 A 3-11 VIFB14 - 03/05 3. Installation
Setting the station number with CANopen You can set the station number of the valve terminal with the two address selector switches on board 3. The switches are numbered from 0 ... 9. The arrow on the address selector switches indicates the tens or units figures of the station number set.
7 8 6 9 Address selector switch 5 0 UNITS figure 4 1 3 2 7 8 6 9 Address selector switch 5 0 TENS figure 4 1 3 2
Fig. 3/4: Address selector switch
PLEASE NOTE • Station numbers may only be assigned once per CANopen interface.
Recommendation Assign the station numbers in ascending order and, if necessary, select them to suit the machine structure of your system.
3-12 9801 A VIFB14 - 03/05 3. Installation
Permitted station numbers: 1; ...; 98
PLEASE NOTE Observe any limitations concerning the station numbers as stipulated by the CAN master and your controller.
Proceed as follows: 1. Switch off the operating voltage. 2. Assign an unused station number to the valve terminal. 3. Use a screwdriver to set the arrow of the rele- vant address selector switch to the units or tens figure of the desired station number.
Example
7 8 6 9 UNITS 5 0 4 1 3 2 Setting with 7 8 6 9 field bus address: 05 TENS 5 0 4 1 3 2
7 8 6 9 UNITS 5 0 4 1 Setting with 3 2 7 8 field bus address: 38 6 9 TENS 5 0 4 1 3 2
Fig. 3/5: Examples of address settings
9801 A 3-13 VIFB14 - 03/05 3. Installation
Setting/saving the station number with the Smart Distributed System, Honeywell
PLEASE NOTE • With the Smart Distributed System protocol the station number set must always be an odd number. If the valve terminal detects an even station number when the station number is saved, this will automatically be corrected to the next lower odd number. • Valve terminals which only have inputs cannot be addressed.
The station number can be set with the following devices: • Handheld Activator for Honeywell Smart Distributed System or • a suitable Smart Distributed System Master. With this protocol, it is not necesary to set the station number by means of the address selector switches.
3-14 9801 A VIFB14 - 03/05 3. Installation
The station number (= SDS-ID) is stored in a non-volatile memory in the field bus node of the valve terminal. The station number can be modified at any time. The station number last entered remains stored in the node.
Assigning station numbers with the valve terminal
Valve terminal Assigned station numbers
max. 32 outputs One n = odd (valves/electrical outputs)
max. 28 inputs and Two n = odd max. 32 outputs n + 1 is assigned automatically by valve terminal
Example: Setting and saving the station number with the Honeywell Handheld Activator 1. Supply the valve terminal with 24 V. Connect the bus connection of the valve terminal with the Handheld Activator. 2. Switch on the Activator. Wait until the follo- wing menu appears:
F1 - Select Device F2 - Data / Function F3 - Test F4 - Bus Status
9801 A 3-15 VIFB14 - 03/05 3. Installation
3. Press key F1 - Select Device. The following menu will appear:
Address: NONE F1 - Select Device F2 - Change Address F3 - Options
Press key F1- Address: NONE. The following menu will appear:
-- Select Device -- Address: NONE Enter: STAT Å ì ESC
Press the STAT key. The Activator will now search for the station number of the valve terminal. When you commission the valve terminal for the first time, station number 125 will appear, otherwise the last station number saved. You can transfer the station number found with ENTER. You can continue the search with ↓ ↑.
3-16 9801 A VIFB14 - 03/05 3. Installation
Now enter the new station number.
PLEASE NOTE Always label the field bus node with the last saved station number. You can then be sure that, in the event of the fieldbus node being replaced, the station num- ber is known and can be loaded into the new node.
Protocol Baud rate Max. number of Permitted statíon valve terminals numbers
Honeywell Smart Up to 500 kBaud 64 0; ...; 126 Distributed System Over 500 kBaud 32
Fig. 3/6: Summary of possible station numbers
9801 A 3-17 VIFB14 - 03/05 3. Installation
Besides the address selector switch there is also a DIL switch in the node. The following functions can be set on this DIL switch: • the field bus baud rate • the field bus protocol. The DIL switch consists of four switch elements. These are numbered from 1 to 4.
The position ON is marked.
AA AA
AA AA
AA AA AA AA
AA AA AA AA 7 8 AA 6 9
5 1 0
4 2
3
AA AA
AAA AA AA
AAA AA AA
7 8
AA 6 9 AA
5 1 0
4
2 AA AA
3
AA AA AA
AA AA 1
2 AA
3 AA 4
ON AA
AA
AA
AA
AA
AAA AAA
1 Field bus baud rate 2 3 Field bus protocol 4 ON
Fig. 3/7: Position of the DIL switch
3-18 9801 A VIFB14 - 03/05 3. Installation
Setting the field bus baud rate
PLEASE NOTE Set the field bus baud rate of the valve ter- minal so that it corresponds to that set on the master interface.
Protocol Field bus baud rate [kBaud]
Smart Distributed automatic setting of baud rate System
CANopen 20 kBaud 125 kBaud 500 kBaud 1000 kBaud
1 1 1 1 1 2 2 2 2 2 3 3 3 3 3 4 4 4 4 4 ON
Fig. 3/8: Setting the field bus baud rate
9801 A 3-19 VIFB14 - 03/05 3. Installation
Setting the field bus protocol Set switch elements 3 and 4 to the desired protocol:
Protocol CANopen Smart Reserved Reserved Distributed System
DIL switch settings
1 1 1 1 1 2 2 2 2 2 3 3 3 3 3 4 4 4 4 4 ON ON ON ON ON
Fig. 3/9: Setting the field bus protocol
3-20 9801 A VIFB14 - 03/05 3. Installation
3.2.1 TYPE 03: CONNECTING THE OPERATING VOLTAGES
WARNING Use only power units which guarantee reliable electrical isolation of the operating voltages in accordance with IEC 742/EN 60742 with at least 4 kV isolation resistance. Switch power packs are permitted, providing they guarantee reliable electrical isolation as per EN 60950.
CAUTION The operating voltage supply to the out- puts/valves (pin 2) must be fused externally with max. 10 A. The external fuse prevents the valve terminal from being damaged in the event of a short circuit.
9801 A 3-21 VIFB14 - 03/05 3. Installation
The 24V operating voltages are connected at
the lower left-hand edge of the node. AAA AAA MOD/NET
POWER AAA
AAA STATUS
AAA AAA AAA
BUS AAA ERROR AAA POWERAAA
BUS
Operating voltage connection
Fig. 3/10: Position of the operating voltage connection
3-22 9801 A VIFB14 - 03/05 3. Installation
The following elements of the valve terminal are supplied with + 24 V DC operating voltage via this connection: • the internal electronic components and the inputs of the input modules (pin 1: + 24 V DC, tolerance ± 25%). • the outputs of the valves and the outputs of the output modules (pin 2: + 24 V DC, tolerance ± 10%, external fuse max. 10 A required). Recommendation: Connect the operating voltage for the out- puts/valves via the EMERGENCY STOP circuit.
PLEASE NOTE If there is a common voltage supply for pin 1 (electronic components and inputs) and pin 2 (outputs/valves) the lower tolerance of ±10% for both circuits must be observed.
9801 A 3-23 VIFB14 - 03/05 3. Installation
Check the 24 V operating voltage for the outputs whilst your system is operating. Please ensure that this voltage lies within the permit- ted tolerances even during full operation.
Recommendation • Use a closed loop power unit. • Calculate the complete current consumption in accordance with the following table and then select a suitable power unit and cable cross section. • Avoid long distances between the power unit and the terminal. Calculate the permit- ted distance in accordance with Appendix A. The following general rule applies to type 03:
Supply voltage Cable cross Distance section
Pin 1 = 2.2 A 1.5 mm2 ≤ 8 m Pin 2 = 10 A
2.5 mm2 ≤ 14 m VO = 24 V
3-24 9801 A VIFB14 - 03/05 3. Installation
Calculating the current consumption for type 03 The table below shows how to calculate the total current consumption for terminal type 03. The values quoted have been rounded up. If other valves or modules are used, you should consult the appropriate technical specifications for their current consumption.
Current consumption of electronic components on node type 03 and inputs (pin 1, 24 V ± 25 %) Node 0.200 A Number of simultaneously occupied sensor inputs: ____x0.010 A + ∑ A
Sensor supplies: ____x_____ A + ∑ A (see manufacturer specifications)
Current consumption of electronic components on the node = ∑ A A and inputs (pin 1) max. 2.2 A Current consumption of outputs type 03 (pin 2, 24 V ± 10 %) Number of MIDI valve coils (simultaneously under power): ____ x 0.055 A + ∑ A
Number of MAXI valve coils (simultaneously under power): ____ x 0.100 A + ∑ A
Number of simultaneously activated ∑ electrical outputs: _____x 0.010 A + A
Load current of simultaneously activated electrical outputs: _____x_____ A + ∑ A
∑ ∑ Current consumption outputs (pin 2) max. 10 A = A + A Total current consumption of valve terminal type 03 = ∑ A
Fig. 3/11: Calculating the total current consumption type 03
9801 A 3-25 VIFB14 - 03/05 3. Installation
The following diagram shows the pin as- signment of the operating voltage connection.
24 V supply to 24 V electronic supply to components valves and and inputs outputs
PE (protective 0 V earth connection, incoming contact) Fig. 3/12: Pin assignment of the operating voltage connection (type 03)
Protective earthing The valve terminal has two protective earth connections as follows: • on the operating voltage connection (pin 4 incoming contact) • on the left-hand end plate (M4 thread)
3-26 9801 A VIFB14 - 03/05 3. Installation
PLEASE NOTE Always connect the earth/ground cable to pin 4 of the operating voltage connection. Ensure that the valve terminal housing and the protective earth conductor at pin 4 have the same voltage and that no equalizing currents flow. Connect a protective earth conductor with sufficient cross section to the left-hand end plate if the valve terminal is not fitted on an earthed machine stand.
You can thereby avoid: • interference from electromagnetic sources.
Connection example (type 03) The following diagram shows the connection of a common 24 V supply for pins 1 and 2. Please note that: • the supply to the outputs/valves must be protected against short circuit/overload with an external fuse max. 10 A; • the supply to the electronic components and inputs must be protected against short circuit/overload with an external 3.15 A fuse (recommendation);
9801 A 3-27 VIFB14 - 03/05 3. Installation
• the common tolerance of 24 V DC ± 10 % must be observed; • equalizing currents must be avoided when both earth cables are connected, e.g. by the use of cables with suitable cross section as voltage compensation.
3124 Connecting cable for voltage compensation of earth connections Fuse for inputs to sensors (2 A) 0 V AC 24 V 3,15 A External fuses DC 24V ± 10 A 10% EMERGENCY STOP
Earth cable connection pin 4 designed for 12 A
Fig. 3/13: Example – connecting a common 24V supply and both earth cables (type 03)
3-28 9801 A VIFB14 - 03/05 3. Installation
3.2.2 TYPE 05: CONNECTING THE OPERATING VOLTAGES
WARNING Use only power units which guarantee reliable electrical isolation of the operating voltages in accordance with IEC 742/EN 60742 with at least 4 kV isolation resistance. Switch power packs are permitted, providing they guarantee reliable electrical isolation as per EN 60950.
CAUTION The operating voltage supply to the outputs (pin 2) must be fused externally with max. 10 A. The external fuse prevents the terminal from being damaged in the event of a short circuit.
9801 A 3-29 VIFB14 - 03/05 3. Installation
The 24 V operating voltages are connected on the adapter plate between the node and the valves. The node and the I/O modules are supplied with current via the adapter cable.
Operating voltage connection type 05
Fuses for valves (4 A slow blowing)
Adapter cable
Fig. 3/14: Position of the operating voltage connection type 05
3-30 9801 A VIFB14 - 03/05 3. Installation
The following elements of valve terminal type 05 are supplied with +24 V DC operating voltage via this connection: • the internal electronic components and the inputs of the inputs modules (pin 1: + 24 V DC , tolerance 25 %, external fuse max. 3.15 A recommended). • the outputs of the valves and the outputs of the output modules (pin 2: + 24 V DC , tolerance 10 %, external fuse max. 10 A slow blowing required).
Recommendation Connect the operating voltage for the out- puts/valves via the EMERGENCY STOP circuit or EMERGENCY STOP contacts.
PLEASE NOTE If there is a common voltage supply for pin 1 (electronic components and inputs) and pin 2 (outputs/valves), the lower tolerance of 10% for both circuits must be observed.
9801 A 3-31 VIFB14 - 03/05 3. Installation
Check the 24 V operating voltage of the outputs whilst your system is operating. Please ensure that this voltage lies within the permit- ted tolerances even during full operation.
Recommendation • Use a closed loop power unit. • Calculate the complete current consumption in accordance with the following table and then select a suitable power unit and suitable cable cross section. • Avoid long distances between the power unit and the terminal. Calculate the permit- ted distance in accordance with Appendix A. The following general rule applies to type 05:
Supply Cable Distance max.*) cross section
Pin 1 = 2.2 A 1.5 mm2 ≤ 8 m 2 Pin 2 = 10 A 2.5 mm ≤ 14 m
VO = 24 V
*) Please observe the maximum total current consumption (pins 1 and 2) of max. 12.2 A.
3-32 9801 A VIFB14 - 03/05 3. Installation
Calculating the current consumption for type 05 The table below shows how to calculate the total current consumption for ISO terminal type 05. The values quoted have been rounded up. If other valves or modules are used, you should consult the appropriate technical speci- fications for their current consumption.
Current consumption of electronic components node type 05 and inputs (pin 1, 24 V ± 25 %) Node 0.200 A Number of simultaneously occupied digital sensor inputs: ____ x 0.010 A + ∑ A
Sensor supplies: ____ x _____ A + ∑ A (see manufacturer specifications)
Current consumption of electronic components node and inputs (pin 1) max. 2.2 A∑ A = A
Current consumption of outputs type 05 (pin 2, 24 V ± 10 %) Number of pilot valve solenoids (max. 12 solenoids simultaneously under power): ___ x 0.300 A + ∑ A
Number of simultaneously activated electrical outputs: ___ x 0.010 A + ∑ A Load current of simultaneously activated ∑ electrical outputs: ___ x _____A + A
Current consumption of outputs (pin 2) max. =+∑ A ∑ A 10.0 A Total current consumption of valve terminal type 05 = ∑ A
Fig. 3/15: Calculating the total current consumption type 05
9801 A 3-33 VIFB14 - 03/05 3. Installation
The following diagram shows the pin as- signment of the operating voltage connection on the adapter plate.
24 V supply to 24 V electronic supply to components valves and and inputs outputs
PE (protective 0 V earth connection, incoming contact) Fig. 3/16: Pin assignment of operating voltage connection (type 05)
3-34 9801 A VIFB14 - 03/05 3. Installation
Protective earthing The valve terminal has two protective earth connections as follows: • on the operating voltage connection (pin 4 incoming contact) • on the left-hand end plate (M4 thread).
PLEASE NOTE Always connect the earth/ground cable to pin 4 of the operating voltage connection. Ensure that the valve terminal housing and the protective earth conductor at pin 4 have the same voltage and that no equalizing currents flow. Connect a protective earth conductor with sufficient cross section to the left-hand end plate if the valve terminal is not fitted on an earthed machine stand.
You can thereby avoid: • interference from electromagnetic sources.
9801 A 3-35 VIFB14 - 03/05 3. Installation
Connection example (type 05) The following diagram shows the connection of a common 24 V supply for pins 1 and 2. Please note that: • the outputs must be protected against short circuit/overload with an external slow-blo- wing fuse of max. 10 A; • the electronic components and inputs must be protected against short circuit/overload with an external 3.15 A fuse (recommenda- tion); • the sensors must be additionally protected with the (2 A) fuse fitted; • the valves must be additionally protected with the 4 A slow-blowing fuse fitted; • the common tolerance of 24 V DC ± 10% must be observed; • the node must be supplied with power via the adapter cable; • equalizing currents must be avoided when both earth cables are connected, e.g. by means of cables with suitable cross section as a voltage compensation.
3-36 9801 A VIFB14 - 03/05 3. Installation
Operating voltage connection Fuse for valves (4 A)
Connected adapter cable
Connecting cable for
voltage compensation 312 4 of earth connections
0 V AC 24 V 3.15 A external fuses
DC 24V 10 A ± 10% EMERGENCY STOP
Earth connection pin 4 designed for 12 A
Fig. 3/17: Example – connecting a common 24V supply and both earth cables (type 05)
9801 A 3-37 VIFB14 - 03/05 3. Installation
3.2.3 CONNECTING THE FIELD BUS There is a field bus plug on the node for connecting the valve terminal to the field bus.
The two bus cables, the voltage supply cables (+24V and 0V) for the bus interface and the cable screening are all connected to this plug. The hardware basis of the bus interface is formed by the CAN bus. A typical feature of this bus interface is that it is supplied with voltage via the field bus plug.
The bus should be connected via a branch line by means of a 5-pin M12 socket with PG9 screw connector. These can be ordered from Festo (type FBSD-GD-9-5POL, part no. 18324). Alternatively, you can use the bus cables of other manufacturers (see Appendix A, Acces- sories).
PLEASE NOTE Consult the manual for your PLC to ascertain the T-adapter and the maximum branch line length which are permitted for your controller. Appendix A contains a summary of suitable installation accessories.
The diagram overleaf shows the main bus connection.
3-38 9801 A VIFB14 - 03/05 3. Installation
Voltage supply for Field bus bus interface
Screening
Branch line
AA AAA
AA AAA AA AAA
AA AAA
AA AAA
T-adapter
+24 V
AA AAA
AA AAA AA
0 V AAA
AA AAA
Bus
Fig. 3/18: Structure of bus interface
9801 A 3-39 VIFB14 - 03/05 3. Installation
Current consumption of all bus interfaces
Number of Festo valve terminals ∑ A connected______* 50 mA
Current consumption of the remaining field bus interfaces ∑ A
Current consumption of sensor ∑ A inputs/sensor supply via the bus
Total current consumption of ∑ all bus interfaces A
Avoid long distances between the bus voltage supply and the bus slaves.
If necessary, calculate the permitted distance (see also Appendix A).
PLEASE NOTE Bus slaves of different manufacturers have dif- ferent tolerances in respect of the interface supply. Take this into consideration when planning the bus length. The following applies to FESTO valve terminals: Vmax = 25V Vmin = 11.5V
3-40 9801 A VIFB14 - 03/05 3. Installation
CAUTION • Please observe the correct polarity when connecting the field bus interface. • Connect the screening.
The diagram below shows the pin assignment of the field bus interface. Connect the field bus cables to the terminals of the bus cable socket. Please observe also the connection instructi- ons in the other diagrams as well as the instructions in the PLC manual for your controller.
GND bus +24V bus Data - Data + (CAN_L) (CAN_H) Screening
220 nF 1MΩ internal RC network
Node housing
Fig. 3/19: Pin assignment of the field bus interface
9801 A 3-41 VIFB14 - 03/05 3. Installation
Connection instructions for CANopen
PLEASE NOTE You must check the connection assignment of the CANopen interface in the manual for your controller.
Connect the field bus cable of your control system to the field bus interface of the valve terminal as follows:
PLC/PC/IPC plug assignment Valve terminal pin assignment of the field bus interface
View Pin Signal destination
1 * 2 CAN_L Data-/CAN_L Pin 5 3 CAN_GND GND bus Pin 3 4 * 5 CAN_SHLD Screening Pin 1 6 GND 7 CAN_H Data+/CAN_H Pin 4 8 * 9 CAN_V+ + 24 V bus Pin 2
* nc = Not connected
Fig. 3/20: Pin assignment as per DS102
3-42 9801 A VIFB14 - 03/05 3. Installation
Connecting instructions for the Smart Distributed System
PLEASE NOTE Always check the pin assignment of the Smart Distributed System interface in the manual for your controller.
Connect the field bus cable of your control system to the field bus interface of the valve terminal as follows:
Plug assignment SDS interface Valve terminal pin assignment of the field bus interface
View Pin Signal destination
1 * 2 CAN_L Data-/CAN_L Pin 5 3 GND GND bus Pin 3 4 * 5 * Screening Pin 1 6 * 7 CAN_H Data+/CAN_H Pin 4 8 * 9 V+ + 24 V bus Pin 2
* nc = Not connected
Fig. 3/21: Pin assignment (Honeywell IPC)
9801 A 3-43 VIFB14 - 03/05 3. Installation
Terminating resistor If the valve terminal to be connected is at the end of the field bus line, a terminating resistor (120 Ohm, 0.25 Watt) must be fitted in the socket of the field bus cable. Adaption is necessary.
Fitting the terminating resistor 1. Connect the wires of the resistor together with those of the field bus cable between the wi- res Data + (pin 4) and Data - (pin 5) of the bus cable socket.
PLEASE NOTE To guarantee reliable contact, we recommend that the wires of the resistor and those of the bus cable be crimped together in common end sleeves.
Ω 4 120
5 2 1
Fig. 3/22: Pin assignment of the field bus interface
2. Fit the bus cable socket to the field bus plug.
3-44 9801 A VIFB14 - 03/05 3. Installation
3.3 CONNECTING THE INPUT MODULES
WARNING Before installation or maintenance work is car- ried out, the following must be switched off: • the compressed air supply • the operating voltage supply to the electronic components (pin 1). • the operating voltage supply to the outputs/valves (pin 2).
You thereby avoid: • uncontrolled movements of loose tubing • undesired movements of the connected actuators • undefined switching states of the electronic components Four or eight inputs are available for the user on the input modules of the valve terminal. The input modules have the following switching logic depending on their type:
Input module type Switching logic INPUT PNP (positive) INPUT-N NPN (negative)
9801 A 3-45 VIFB14 - 03/05 3. Installation
Input module 4 inputs Input module 8 inputs
Socket with one Socket One digital Green with two green input LED digital LED each inputs each each per digital input
Fig. 3/23: Digital input modules (4/8 inputs)
Recommendation for the 8-input modules: Use the Festo DUO cable in order to connect two sensors with one plug.
3-46 9801 A VIFB14 - 03/05 3. Installation
Pin assignment The following diagram shows the pin as- signment of all inputs.
Pin assignment 4 inputs LED Pin assignment 8 inputs LED
free 0 V Input 0 V 2 3 00Ix+1 2 3
1 4 1 4 Input Input 1 + 24 V Ix + 24 V Ix
free 0 V Input 0 V 12Ix+3 2 3 2 3
1 4 1 4 3 Input Input + 24 V Ix+1 + 24 V Ix+2
free 0 V Input 0 V Ix+5 2 3 24 2 3
1 4 1 4 5 Input Input + 24 V Ix+2 + 24 V Ix+4
free 0 V Input 0 V Ix+7 2 3 36 2 3
1 4 1 4 7 Input Input + 24 V Ix+3 + 24 V Ix+6 Fig. 3/24: Input modules: pin assignment (4/8 inputs)
9801 A 3-47 VIFB14 - 03/05 3. Installation
3.4 CONNECTING THE OUTPUT MODULES
WARNING Before installation or maintenance work is carried out, the following must be switched off: • the compressed air supply • the operating voltage for the electronic components (pin 1) • the operating voltage for the outputs/valves (pin 2)
You thereby avoid: • uncontrolled movements of loose tubing • undesired movements of the connected actuators • undefined switching states of the electronic components
3-48 9801 A VIFB14 - 03/05 3. Installation
Four transistor outputs are available for the user on the output modules of the valve terminal. The outputs have positive logic (PNP outputs).
Output module (4-outputs)
Yellow LED per output Red LED per output
Socket with one digital output each
Fig. 3/25: Digital output module (4-outputs)
9801 A 3-49 VIFB14 - 03/05 3. Installation
Pin assignment The diagram below shows the pin assignment of all outputs.
Pin assignment 4 outputs LED
free 0 V 2 3 0
1 4
free Output Ox
free 0 V 1 2 3
1 4
free Output Ox+1
free 0 V 2 2 3
1 4
free Output Ox+2
free 0 V 3 2 3
1 4
free Output Ox+3 Fig. 3/26: Output modules: pin assignment (4 outputs)
3-50 9801 A VIFB14 - 03/05 4. Commissioning
4. COMMISSIONING
9801 A 4-1 VIFB14 - 03/05 4. Commissioning
Contents
4.1 BASIC PRINCIPLES OF CONFIGURATION AND ADDRESSING 4-5 General 4-5 Switching on the operating voltage 4-6 Calculating the configuration data 4-7 Calculating the number of inputs/outputs type 03 4-9 Calculating the number of inputs/outputs type 05 4-10 Address assignment of the valve terminal 4-11 General type 03 and type 05 4-11 Basic rule 1 4-12 Basic rule 2 4-15 Address assignment after extension/conversion 4-16 Addressing example type 03 MIDI/MAXI valves 4-19 Addressing example type 05 ISO valves 4-20
4-2 9801 A VIFB14 - 03/05 4. Commissioning
4.2 BASIC PRINCIPLES OF COMMISSIONING AND DIAGNOSIS 4-21 General 4-21 Selecting the inputs/outputs 4-21 General information on CANopen 4-22 Brief summary of scope of function 4-23 Summary of object directory 4-24 Default identifier distribution 4-27 Summary of object directory 4-28 PDO communication parameter record 4-29 PDO communication mapping parameter field 4-31 Digital inputs 4-32 Digital outputs 4-32 Reaction of the digital outputs in the event of a fault 4-33 Definition of emergency object 4-35 Addressing inputs and outputs 4-36 Examples: communication process 4-38 Diagnosis of status bits 4-41 Position of the status bits 4-42
9801 A 4-3 VIFB14 - 03/05 4. Commissioning
4.3 BASIC PRINCIPLES OF THE SMART DISTRIBUTED SYSTEM (HONEYWELL) 4-43 General information 4-43 Commissioning 4-43 Number of inputs and outputs 4-44 Summary of implemented object models 4-45 Summary of actions 4-48 Summary of events 4-49 Assignment of SDS IDs 4-49 Diagnosis 4-50 Diagnosis via status bits 4-51 Setting the transmission mode 4-53 Bus configuration 4-54 4.3.1 CONFIGURING/ADDRESSING THE HONEYWELL SDS PC CONTROL 4-55 General information 4-55 Settings in the Device Editor 4-55 Settings in the Tag Editor 4-58 Setting the transmission types for inputs by means of the programming software 4-60 Setting the Cyclical Timer 4-61 Diagnosis 4-63 Diagnosis via the network manager 4-63 Diagnosis via the SDS user program 4-63 Structure of the SDS diagnostic register 4-65 Diagnosis via the status bits 4-66 4.3.2 CONFIGURING/ADDRESSING WITH THE GE FANUC SERIES 90/30 4-67 General information 4-67 Bus configuration 4-68 Assigning the I/O addresses 4-68 Diagnosis 4-73 Diagnosis via the SDS interface 4-73 Diagnosis via status bits 4-75
4-4 9801 A VIFB14 - 03/05 4. Commissioning
4.1 BASIC PRINCIPLES OF CONFIGURATION AND ADDRESSING
General Before commissioning or programming, you should first compile a configuration list of all the connected field bus slaves. On the basis of this list you can: • make a comparison between the ACTUAL and NOMINAL configurations in order to ascertain if there are any incorrect connecti- ons. • access these specifications during the syn- tax check of a program, in order to avoid addressing errors. The valve terminal must be configured very accurately, since different configuration specifi- cations may be required for each terminal due to the modular structure. Please observe here also the specifications in the following sections.
9801 A 4-5 VIFB14 - 03/05 4. Commissioning
Switching on the operating voltage
PLEASE NOTE Observe also the switching-on instructions in the PLC manual for your controller.
When the controller is switched on, it automat- ically carries out a comparison between the NOMINAL and ACTUAL configurations. The following points are important for the configura- tion: • The specifications on configuration must be complete and correct. • The power supplies to the PLC and to the field bus slaves must be switched on either simultaneously or in the sequence specified below.
Please observe also the following points when switching on the power supplies: • Common supply. If the control system and all the field bus slaves have a common power supply, they should be switched on with a common central power unit or switch. • Separate supply. If the control system and the field bus slaves have separate power supplies, they should be switched on in the following sequence: 1. first the field bus slaves 2. then the control system.
4-6 9801 A VIFB14 - 03/05 4. Commissioning
Calculating the configuration data Before configuring, calculate the exact number of inputs/outputs available. A modular valve terminal consists of a number of I/Os which differs depending on the type of valve terminal.
PLEASE NOTE • The terminal makes available four status bits for diagnosis via the field bus. These are always assigned automatically within the terminal when there are input modules. • The status bits occupy four additional input addresses.
9801 A 4-7 VIFB14 - 03/05 4. Commissioning
The following table shows the number of I/Os required for each module for configuration.
Module type Number of assigned I/Os *) Single sub-base (type 03) 2O
Double sub-base (type 03) 4O
ISO manifold sub-base (type 05) - 4 valve locations 8O - 8 valve locations 16O - 12 valve locations 24O
Output module (4 digital outputs) 4O
Input module (4 digital inputs) 4I
Input module (8 digital inputs) 8I
Status bits**) 4I *) The I/Os are assigned automatically in the terminal irrespective of whether an input/output is actually used. **) The status bits are assigned automatically in the terminal as soon as there are input modules. Fig. 4/1: Number of assigned I/Os per module
4-8 9801 A VIFB14 - 03/05 4. Commissioning
Calculating the number of inputs/outputs type 03 Copy this table for further calculations and ascertain the number of inputs/outputs.
Table for calculating the inputs/outputs type 03 INPUTS
1. Number of 4-input modules ______⋅ 4 Σ E
+ 2. Number of 8-input modules ______⋅ 8 Σ E
3. The 4 status bits are assigned internally + automatically by the terminal. They must be treated 4E like inputs and added to the intermediate sum.
Total sum of inputs to be configured = Σ E
OUTPUTS
4. Number of single sub-bases type 03 ______⋅ 2 Σ A
5. Number of double sub-bases type 03 ______⋅ 4 + Σ A
Intermediate sum of 4.+ 5. = Σ A
6. Check whether sum of 4 + 5 can be divided without remainder. This check is necessary because of the 4-bit orientated internal addressing of the terminal. Different cases: a) If divisible by 4 without remainder continue with point 7. b) If not round up (+ 2 outputs) + 2A
7. Number of electrical 4-output modules ______⋅ 4 + Σ A
Total sum of outputs to be configured = Σ A
Fig. 4/2: Calculating the number of inputs/outputs type 03
9801 A 4-9 VIFB14 - 03/05 4. Commissioning
Calculating the number of inputs/outputs type 05 Copy this table for further calculations.
Table for calculating the number of inputs/outputs type 05 INPUTS
1. Number of 4-input modules ______⋅ 4 Σ E + Σ E 2. Number of 8-input modules ______⋅ 8
3. The 4 status bits are assigned internally + automatically by the terminal. They must be treated 4E like inputs and added to the intermediate sum.
Total sum of inputs to be configured = Σ E
OUTPUTS
4. ISO manifold sub-base for: • 4 valve locations 8O
• 8 valve locations 16O
• 12 valve locations 24O Σ A
Σ 5. Number of electrical 4-output modules ______⋅ 4 + A
Total sum of outputs to be configured = Σ A
Fig. 4/3: Calculating the number of inputs/outputs type 05
4-10 9801 A VIFB14 - 03/05 4. Commissioning
Address assignment of the valve terminal
General type 03 and type 05 The address assignment of a modular valve terminal depends on the equipment fitted on the terminal. A distinction must be made between the following equipment fitted: • valves and digital I/O modules • valves only • digital I/O modules only The basic rules described overleaf apply to the address assignment of these fitting variants.
PLEASE NOTE If two addresses are assigned for one valve location, the following applies: • Lower-value address ⇒ pilot solenoid 14 • Higher-value address ⇒ pilot solenoid 12
9801 A 4-11 VIFB14 - 03/05 4. Commissioning
Basic rule 1 With mixed fitting, consideration is given to the address assignment of the valves, the digi- tal I/O modules and the status bits. 1. Outputs: The address assignment of the outputs does not depend on the inputs. 1.1 Address assignment of the valves: • Addresses should be assigned in ascending order without gaps. • Counting begins on the node from left to right. • Single sub-bases always occupy two addr. • Double sub-bases always occupy four addr. • ISO valve locations always occupy two addr. • Maximum 26 valve solenoid coils can be addressed. 1.2 Rounding up to 4 bits, different cases: a) If the number of valve addresses can be divided by 4 without remainder, continue with point 1.3. b) If the number of valve addresses cannot be divided by 4 without remainder, the number must be rounded up to 4 bits because of the 4-bit orientated addressing. The 2 bits thus rounded up cannot be used. 1.3 Address assignment of the output modules: The digital outputs are addressed after the (rounded up 4-bit) addresses of the valves. • Addresses should be assigned in ascending order without gaps. • Counting begins on the node from right to left. • Counting on the individual modules is from top to bottom. • Digital output modules always occupy 4 addresses.
4-12 9801 A VIFB14 - 03/05 4. Commissioning
2. Inputs The address assignment of the inputs does not depend on the outputs. 2.1 Address assignment of the input modules: • Addresses should be assigned in ascending order without gaps. • Counting begins on the node from right to left. • Counting on the individual modules is from top to bottom. • 4-input modules occupy 4 addresses. • 8-input modules occupy 8 addresses. 2.2 Status bits The address assignment of the status bits depends on the equipment fitted on the inputs and on the configuration.
The following rule applies: • The status bits are only available when input modules are connected to the terminal and when at least 8 inputs are configured in the PLC. • Addressing. The status bits are transferred to the four highest-value positions of the confi- gured address range.
When the operating voltage is switched on, the valve terminal automatically recognizes all the available pneumatic modules (type 03: max. 13 modules; type 05: 4, 8, 12 valve locations) and digital input/output modules and assigns the ap- propriate addresses. If a valve location is not used (blanking plate) or if a digital input/output is not connected, the relevant address will still be occupied.
9801 A 4-13 VIFB14 - 03/05 4. Commissioning
The diagram below shows the address as- signment with mixed fitting. 4-input module 8-input module 4-output module 8-output module Single sub-base Double sub-base Double sub-base Double sub-base Round up
012 4 6 810 12 14 802016 3 5 7 9 11 13 15 1 9221 17 3
10 4 22 18 5 11 6 23 19 7
Fig. 4/4: Address assignment of a valve terminal with digital I/Os (example type 03)
Remarks on the diagram • If single solenoid valves are fitted onto dou- ble sub-bases, four addresses will be reser- ved for valve solenoid coils; the higher ad- dress in each case then remains unused (see address 3). • If unused valve locations are fitted with blan- king plates, the addresses will still be occu- pied (see addresses 12, 13). • Due to the 4-bit orientated addressing of the modular valve terminal, the address of the last valve location is always rounded up to four full bits (unless the equipment fitted al- ready uses the four full bits). This means that two addresses cannot be used (see ad- dresses 14, 15).
9801 A 4-14 VIFB14 - 03/05 4. Commissioning
Basic rule 2 If only valves are used, the address as- signment will always be as described in basic rule 1.
PLEASE NOTE • Maximum 26 valve solenoid coils can be addressed. • There is no rounding up of the last two positions on the valve side. • Valve terminals without input modules do not require a configuration for inputs. The status bits are not therefore available.
Basic rule 3 If only electrical I/Os are used, the address assignment will always be as described in basic rule 1.
PLEASE NOTE • Counting begins immediately to the left of the node. • There is no rounding up of the last two positions on the valve side.
Please unfold for page 4-14
4-15 9801 A VIFB14 - 03/05 4. Commissioning
Address assignment after extension/ conversion A special feature of the modular valve terminal is its flexibility. If the demands placed on the machine change, then the equipment fitted on the terminal can also be modified.
CAUTION If extensions or conversions are made to the terminal at a later stage, this may result in a shifting of the input/output addresses. This applies in the following cases: • if one or more pneumatic modules is/are fitted/removed at a later stage (type 03). • if a pneumatic module with single valves is replaced by a new module with double valves or vice versa (type 03). • if additional input/output modules are inserted between the node and existing input/output modules. • if existing 4-input modules are replaced by 8-input modules or vice versa.
If the configuration of the inputs is changed, the addresses of the status bits will always be shifted.
4-16 9801 A VIFB14 - 03/05 4. Commissioning
The diagram below shows the modifications to the address assignment if the standard fitting in the previous diagram is extended. 4-input module 4-input 4-output module 4-output module Single sub-base Double sub-base 8-input module Double sub-base Single sub-base notDo round up Double sub-base SUPPLY Double sub-base
012 4 6 8 10 12 14 16 18 19 8 0 24 20 3 5 7 9 11 13 15 17 1 9225 21 3
10 4 26 22 5 11 6 27 23 7
Fig. 4/5: Address assignment of a valve terminal after extension/conversion
Please note: Air supply modules and intermediate air supply modules do not occupy any addresses.
9801 A 4-17 VIFB14 - 03/05 4. Commissioning
Addressing example type 03 MIDI/MAXI valves 4-input module 4-input module 8-input module 4-output 4-output module 4-output sub-base Double sub-base Double Double sub-base Double Double sub-base Double up Round Single sub-base Single Double sub-base Double
Please note: If a valve location occupies two addresses, the following applies: • Lower-value address ⇒ pilot solenoid 14 • Higher-value address ⇒ pilot solenoid 12
Fig. 4/6: Address assignment of a valve terminal type 03 (MIDI/MAXI valves)
9801 A 4-19 VIFB14 - 03/05 4. Commissioning
Addressing example type 05 ISO valves Double valve Double valve Double Double valve Double Double valve Double valve Double valve Double Single valve up round not Do 4-input module 8-input module module 4-output module 4-output Single valve
12 14 12 14 12 1414 12 14 12 14 12 14 14 8 0 20 16 1 9 2 21 17 3 10 4 22 18 1 0 3572 469 8101113 12 15 14 5 11 6 23 19 7
Please note: If a valve location occupies two addresses, the following applies: • Lower-value address ⇒ pilot solenoid 14 • Higher-value address ⇒ pilot solenoid 12
Fig. 4/7: Address assignment of a valve terminal type 05 (ISO valves)
4-20 9801 A VIFB14 - 03/05 4. Commissioning
4.2 BASIC PRINCIPLES OF COMMISSIONING AND DIAGNOSIS
General This chapter describes the configuration and addressing of a valve terminal on a CANopen Interface or CANopen master.
The following standards have been taken into account:
DS 301 Draft Standard 301 concerns the communications profile based on CAL DSP 401 Draft Standard Proposal 401 defines the device profiles for input/output DS 201.. CAN Application Layer CAL DS 207
In order to understand this chapter, the user should be familiar with CANopen and the specifications DS 301 and DSP 401.
Selecting the inputs/outputs
PLEASE NOTE The sum of the input bytes must not exceed 8 bytes (60 inputs + 4 status bits) and 8 out- put bytes (64 outputs).
The number of inputs and outputs is different due to the modular structure of the valve terminal. The number of input bytes and/or output bytes which actually exist on the valve terminal can be read via the appropriate index.
9801 A 4-21 VIFB14 - 03/05 4. Commissioning
General information on CANopen CANopen devices have an object directory which provides access in a standardized man- ner to all important node parameters. You can configure a CANopen system mainly by acces- sing the object directory of the individual nodes. The access mechanism is made available by Service Data Objects (SDOs).
There are two different communication mecha- nisms in a CANopen system.
"Process Data Objects” (PDOs) serves for the fast transfer of processing data and is transmit- ted by simple CAN messages without protocol overhead and in the broadcast procedure. Process Data Objects can be transmitted event-controlled, synchronous to a system time interval or on demand.
Die ”Service Data Objects” (SDO) forms a point-to-point conection and permits access to every entry in the object directory of a node.
4-22 9801 A VIFB14 - 03/05 4. Commissioning
Brief summary of scope of function • Module states and boot up after communi- cation profile DS 301 • All the entries in the communication part of the object directory are included • A service data object for read/write access to the object directory • A process data object for access to digital input/outputs • PDO-COB identifier for read/write access can be selected individually • PDO transmission types for read/write ac- cess can be set separately as asynchro- nous (255), synchronous cyclic (1-240), synchronous acyclic (0) as per DS 301 • PDO emergency telegram for error message to the master • Synchronous mode • Node guarding • All COB-IDs of the implemented functions (except for SDO) can be selected separa- tely in the object directory via SDO transfer, both for sending and for receiving • Default setting of all identifiers as per DS 301 and the node address
9801 A 4-23 VIFB14 - 03/05 4. Commissioning
Summary of object directory The following table shows the implemented objects of the Festo valve terminal. The table is based on DS 301 (Draft Standard Proposal):
Index (hex) Objects 1000-100E Communication part of the object directories 1400 Communication parameter for receive PDO 1600 Mapping parameter for receive PDO (variable mapping not implemented) 1800 Communication parameter for send PDO 1803 Communication parameter for emergency PDO 1A00 Mapping parameter for send PDO (variable mapping not implemented) 1A03 Mapping parameter for emergency PDO (variable mapping not implemented) 6000 Input array 6200 Output array 6206 Fault mode array for the output lines 6207 Fault state array for the output lines
4-24 9801 A VIFB14 - 03/05 4. Commissioning
COB identifier The Festo valve terminal with CANopen repre- sents a "minimum capability device" (minimum device). The PDO-COB identifier can be se- lected individually for read and write access.
Bit 10 Bit 7 Bit 6 Bit 0
Function code Module-ID
Fig. 4/9: Structure of COB identifier
Max. 127 slaves can be controlled with the module-ID. Addresses from 1 ... 98 can be set with the address selector switches of the valve terminal. Address 99 is reserved for the self test. Address 00 is not valid. The address is also referred to as station number, MAC-ID or "MESSAGE-ID."
Example: COB-ID for valve terminal. Set address (rotary switch): 10D.
Bit 10 Bit 7 Bit 6 Bit 0 0 0 0 1 0 1 0
Function code Module-ID
Fig. 4/10: Structure of COB identifier for valve terminal no. 10
9801 A 4-25 VIFB14 - 03/05 4. Commissioning
Switch-on reaction of the valve terminal Status diagram of the Festo valve terminal
Switch on
Hardware initialization 1
Communication initialization 1 4 5 Pre-Operational [cs=82H] [cs=81H]
[cs=80H] 3 2 [cs=01H] 4 5 Operational [cs=82H] [cs=81H]
Fig. 4/11: Status diagram of the valve terminal
Description of the status transfers
Status Designation Command Function transfer specifier (CS) 1 Automatic initialization after switching on
2 Start_remote_Node_Indication 01H – Start valve terminal – Release outputs – Start PDO transmission
3 Enter_Pre_Operation_ State 80H Stops PDO transmission; SDO remains active
4 Reset_Communication_ 82H Reset communication Indication functions
5 Reset_Node_Indication 81H Reset module including application
4-26 9801 A VIFB14 - 03/05 4. Commissioning
Default identifier distribution The following table shows the identifier distri- bution.
Peer-to-Peer Objects Object Object Function CMS Value range of Name designation code priority COB identifier (binary) group with Festo valve terminals
SYNC 0001 0 128D 80H
EMER- For high-priority 0001 0, 1 129D to 226D GENCY processes 081H 0E2H e.g. voltage failure
Send 0011 1, 2 385D to 482D PDO 181H 1E2H
Receive 0100 2 513D to 610D PDO 201H 262H
Send 1011 6 1409D to 1506D SDO 581H 5E2H
Receive 1100 6, 7 1537D to 1634D SDO 601H 662H
Node 1110 7 1793D to 1890D guarding 701H 762H
9801 A 4-27 VIFB14 - 03/05 4. Commissioning
Summary of object directory The communication part of the objects contains the following objects. Values and examples refer to module-ID = 1.
Communication profile Index Object name Object Object Object Values/ Explanation of values (hex) symbolic designation type attributes subindex 1000 VAR Device type U32 ro 91 01 03 00 0191 = Device profile for I/O module x: 0300 = Digital inputs and digital outputs exist 1001 VAR Manufacturer U8 ro xx 00 = No error error field 81 = Generic manufacturer error 1002 VAR Predef_status U32 ro 00 00 00 00 Not defined 1003 ARRAY Predef_error U16 ro "0"= 0x xx Number of errors field [2] "1"= xx xx Standard error field 2023 = Short circuit/ overload 2033 = Valve voltage < 21.6 V 3033 = Valve voltage > 10 V 2031 = Sensor voltage < 10 V 1004 ARRAY No. of PDOs [3] U32 ro "0"= 02 01 No. of transmit PDOs supported 01 00 No. of receive PDOs "1"= 01 00 No. of syn. transmit PDOs 01 00 No. of syn. receive PDOs "2"= 02 00 No. of asyn transmit PDOs 01 00 No. of asyn. receive PDOs 1005 VAR COB Id U32 rw 80 00 00 80 8000 = Device supports SYNC SYNC message. message Does not generate SYNC message. 0080 = Default COB-ID 80 1006 VAR Communication U32 rw 80 96 98 00 = 10 sec cycle period U = unsigned, ro = read only, rw = read write Table continued on next page
4-28 9801 A VIFB14 - 03/05 4. Commissioning
Table continued Communication profile Index Object name Object Object Object Values/ Explanation of values (hex) symbolic designation type attributes subindex 1007 VAR Synchronous U32 rw 00 00 00 00 Without function window length 1008 ARRAY Manufacturer String 46 42 31 34 FB14 device name 1009 ARRAY Manufacturer String 30 38 39 36 min. 0896 hardware version 100A ARRAY Manufacturer String 56 31 2E 31 V1.1 software version 100B VAR Node-ID U32 ro 01 00 00 00 Node address 100C VAR Guard time U16 rw E8 03 e.g. 1000 ms 100D VAR Lifetime factor U8 rw 03 Life time for the node guarding protocol 100E VAR Nodeguard_id U32 rw 01 07 00 80 Nodeguard identifier U = unsigned, ro = read only, rw = read write
PDO communication parameter record The following object directory is defined in the "Receive" PDO communication parameter. Va- lues and examples refer to module-ID = 1.
Communication profile Index Object name Object Object Object Values/ Explanation of (hex) symbolic designation type attributes subindex values 1400 RECORD Communication PDOComm rw "0"=02 = No. of entries parameter for parameter "1"=01 02 00 00 = COB-ID 200 + receive PDO module-ID "2"=xx = transmission type Default = FF 01 = async. FF= acyc. async.
9801 A 4-29 VIFB14 - 03/05 4. Commissioning
The following object directory is defined in the "Transmit" PDO communication parameter. Va- lues and examples refer to module-ID = 1.
PLEASE NOTE With transmission type "synchronous", the parameter (01...F0) specifies the number of SYNC messages which must be received until the send PDO is transmitted.
Communication profile Index Object name Object Object Object Values/ Explanation of (hex) symbolic designation type attributes subindex values 1800 1. Communication PDOComm rw "0"=02 = No. of entries parameter for parameter "1"=01 81 00 00 = COB-ID 180 + send PDO module-ID "2"=xx transm. type Default = FF 00 = acyclic synch. 01-F0 = synch. FF = acyclic asynch. 1803 RECORD 4. Communication PDOComm rw "0"=02 = No. of entries parameter for parameter "1"=81 00 00 00 = COB-ID 80 + send PDO module-ID "2"=FE = transmission type asynch. (not changeable)
4-30 9801 A VIFB14 - 03/05 4. Commissioning
PDO communication mapping parameter field
PLEASE NOTE Variables mapping is not supported.
"Receive" PDO mapping parameter:
Communication profile Index Object name Object Object Object Values/ Explanation of (hex) symbolic designation type attributes subindex values 1600 ARRAY Mapping PDOComm ro "0"= 0x = No. of available parameter for parameter output bytes receive PDO "1"= 08 01 00 62 = O 0.0 - O 0.7 "2"= 08 02 00 62 = O 1.0 - O 1.7 "3"= 08 03 00 62 = O 2.0 - O 2.7 "4"= 08 04 00 62 = O 3.0 - O 3.7 "5"= 08 05 00 62 = O 4.0 - O 4.7 "6"= 08 06 00 62 = O 5.0 - O 5.7 "7"= 08 07 00 62 = O 6.0 - O 6.7 "8"= 08 08 00 62 = O 7.0 - O 7.7
"Transmit" PDO mapping parameter:
Communication profile Index Object name Object Object Object Values/ Explanation of (hex) symbolic designation type attributes subindex values 1A00 ARRAY Mapping PDOComm ro "0"= 0x = No. of available parameter for parameter input bytes send PDO "1"= 08 01 00 60 = I 0.0 - I 0.7 "2"= 08 02 00 60 = I 1.0 - I 1.7 "3"= 08 03 00 60 = I 2.0 - I 2.7 "4"= 08 04 00 60 = I 3.0 - I 3.7 "5"= 08 05 00 60 = I 4.0 - I 4.7 "6"= 08 06 00 60 = I 5.0 - I 5.7 "7"= 08 07 00 60 = I 6.0 - I 6.7 "8"= 08 08 00 60 = I 7.0 - I 7.7 1A03 ARRAY Mapping PDOComm ro ”0”=07 = No. of bytes parameter for Parameter ”1”=10 01 03 10 = Manufacturer emergency error field PDO Emergency error code ”2”...”7” = Reserved
9801 A 4-31 VIFB14 - 03/05 4. Commissioning
Digital inputs Festo supports the "INPUT ARRAY" and "OUTPUT ARRAY" for the 8-bit commands. The following tables apply:
Communication profile Index Object name Object Object Object Values/ Explanation of (hex) symbolic designation type attributes subindex values 6000 ARRAY Read state 8 Unsigned 8 ro ”0”= 0x = No. of available input lines[9] input bytes "1" =xx = I 0.0 - I 0.7 "2" =xx = I 1.0 - I 1.7 "3" =xx = I 2.0 - I 2.7 "4" =xx = I 3.0 - I 3.7 "5" =xx = I 4.0 - I 4.7 "6" =xx = I 5.0 - I 5.7 "7" =xx = I 6.0 - I 6.7 "8" =xx I 7.0 - I 7.7
Digital outputs
Communication profile Index Object name Object Object Object Values/ Explanation of (hex) symbolic designation type attributes subindex values 6200 ARRAY Write state 8 Unsigned 8 rw ”0”= 0x = No. of available output lines[9] output bytes "1" = xx = O 0.0 - O 0.7 "2" = xx = O 1.0 - O 1.7 "3" = xx = O 2.0 - O 2.7 "4" = xx = O 3.0 - O 3.7 "5" = xx = O 4.0 - O 4.7 "6" = xx = O 5.0 - O 5.7 "7" = xx = O 6.0 - O 6.7 "8" = xx = O 7.0 - O 7.7
4-32 9801 A VIFB14 - 03/05 4. Commissioning
Reaction of the digital outputs in the event of a fault Festo supports the "FAULT MODE ARRAY" for the 8-bit commands. The following tables apply:
Communication profile Index Object name Object Object Object Values/ Explanation of values (hex) symbolic designation type attributes subindex 6206 ARRAY Fault mode Unsigned 8 rw "0"= 0x = No. of available 8 output output bytes lines[9]. "1" = xx = Masking Define masking O 0.0 - O 0.7 "2" = xx = Masking O 1.0 - O 1.7 "3" = xx = Masking O 2.0 - O 2.7 "4" = xx = Masking O 3.0 - O 3.7 "5" = xx = Masking O 4.0 - O 4.7 "6" = xx = Masking O 5.0 - O 5.7 "7" = xx = Masking O 6.0 - O 6.7 "8" = xx = Masking O 7.0 - O 7.7 Default value: FF
9801 A 4-33 VIFB14 - 03/05 4. Commissioning
Festo supports the "FAULT STATE ARRAY" for the 8-bit commands. The following tables apply:
Communication profile Index Object name Object Object Object Values/ Explanation of (hex) symbolic designation type attributes subindex values
6207 ARRAY Fault state Unsigned 8 rw "0"= 0x = No. of available 8 output output bytes lines[9] "1" = xx = Fault state Set masking O 0.0 - O 0.7 "2" = xx = Fault state O 1.0 - O 1.7 "3" = xx = Fault state O 2.0 - O 2.7 "4" = xx = Fault state O 3.0 - O 3.7 "5" = xx = Fault state O 4.0 - O 4.7 "6" = xx = Fault state O 5.0 - O 5.7 "7" = xx = Fault state O 6.0 - O 6.7 "8" = xx = Fault state O 7.0 - O 7.7 Default value: 00
PLEASE NOTE With index 6206, you can determine the out- puts which are to assume a default status in the event of an error. With index 6207, you can determine the status which the outputs are to assume in the event of an error.
4-34 9801 A VIFB14 - 03/05 4. Commissioning
Definition of emergency object Festo supports a "PDO Emergency Object" as per DS 401 (see diagram). The PDO object is sent by the valve terminal in the following cases: • undervoltage at valves and outputs < 21.6 V • undervoltage at valves and outputs < 10 V • short circuit/overload at an output
• undervoltage at sensor supply < 10 V The emergency PDO is sent when a fault occurs and when the fault has been eliminated.
Byte Byte 0 1234567
Emergency Error code 2320 = SC/O 3320 = Vval < 21,6 V 3330 = Voff < 10 V 3120 = Vsen > 10 V
Error register 00 = no error 81 = Generic and Manufacturer error
Manufacturer specific error field (reserved)
Fig. 4/12: Definition of Emergency Object
9801 A 4-35 VIFB14 - 03/05 4. Commissioning
Addressing inputs and outputs
PLAESE NOTE Observe also the basic addressing rules at the beginning of the chapter. rounding) I 3.4 ... I 3.7 ... I 3.4 I 3.3 ... I 3.0 I 2.7 ... I 2.0 I 1.7 ... I 1.0 I 0.7 ... I 0.0 O 1.4; 1.7 O O 0.0 O 0.1 O 0.3; 0.2 O O 0.5; 0.4 O O 0.7; 0.6 O O 1.1; 1.0 O (free due to due (free
Fig. 4/13: Assignment of inputs/outputs
The following table shows the assignment of all the inputs and outputs:
4-36 9801 A VIFB14 - 03/05 4. Commissioning
Valve terminal inputs
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0 Byte 0 I0.7 I0.6 I0.5 I0.4 I0.3 I0.2 I0.1 I0.0 Byte 1 I1.7 I1.6 I1.5 I1.4 I1.3 I1.2 I1.1 I1.0 Byte 2 I2.7 I2.6 I2.5 I2.4 I2.3 I2.2 I2.1 I2.0 Byte 3 I3.7 I3.6 I3.5 I3.4 I3.3 I3.2 I3.1 I3.0 Byte 4 I4.7 I4.6 I4.5 I4.4 I4.3 I4.2 I4.1 I4.0 Byte 5 I5.7 I5.6 I5.5 I5.4 I5.3 I5.2 I5.1 I5.0 Byte 6 I6.7 I6.6 I6.5 I6.4 I6.3 I6.2 I6.1 I6.0 Byte 7 I7.7 I7.6 I7.5 I7.4 I7.3 I7.2 I7.1 I7.0
Valve terminal outputs
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0 Byte 0O0.7O0.6O0.5O0.4O0.3O0.2O0.1O0.0 Byte 1O1.7O1.6O1.5O1.4O1.3O1.2O1.1O1.0 Byte 2O2.7O2.6O2.5O2.4O2.3O2.2O2.1O2.0 Byte 3O3.7O3.6O3.5O3.4O3.3O3.2O3.1O3.0 Byte 4O4.7O4.6O4.5O4.4O4.3O4.2O4.1O4.0 Byte 5O5.7O5.6O5.5O5.4O5.3O5.2O5.1O5.0 Byte 6O6.7O6.6O6.5O6.4O6.3O6.2O6.1O6.0 Byte 7O7.7O7.6O7.5O7.4O7.3O7.2O7.1O7.0
Fig. 4/14: Assignment of inputs/outputs
9801 A 4-37 VIFB14 - 03/05 4. Commissioning
Examples: communication process All the examples refer to module-ID = 1, i.e. the set valve terminal address 1.
Example 1: Signal change 0 → 1 input 0
COB-ID Data PLC PC 181 01 00 00 00 00 00 00 00 IPC
values in hex
Fig. 4/15: Signal change at input 0
When there is a signal change, the valve terminal automatically sends the status of the inputs (send PDO). In the example only input 0 is at "log. 1."
Example 2: Set output 0 of the valve terminal
COB-ID Data PLC PC 201 IPC 01 00 00 00 00 00 00 00
values in hex
Fig. 4/16: Output 0 (set 1st. valve)
In order to set valves and outputs on the valve terminal, the receive PDO must be sent by the master. In the example only output 0 is set. Any outputs already set will be reset.
4-38 9801 A VIFB14 - 03/05 4. Commissioning
Example 3: Read object 1000H, subindex 0 (device type: device profile, device equipping).
COB-ID Index Sub-Index *) Data Initiate DomainInitiate Upload Request
601 40 00 10 00 00 00 00 00 PLC PC IPC 581 43 00 10 00 91 01 03 00
Values in hex *) with 4 data bytes Initiate Domain Initiate Upload Response Index Sub-Index Data*)
Fig. 4/17: Read object 1000H
In order to read objects of a valve terminal, the send SDO must be loaded with the Upload command, the index and the subindex. The valve terminal then sends the number of data bytes, the index, the subindex and the data bytes.
9801 A 4-39 VIFB14 - 03/05 4. Commissioning
Example 4: Write object 100CH, subindex 0 (Guard time).
COB-ID Index Sub-Index *) Data Initiate DomainInitiate Download Request 601 PLC 2B 0C 10 00 04 7F 00 00 PC IPC 581 60 0C 10 00 xx xx xx xx
Values in hex *) with 2 data bytes xx = Value not defined Initiate Domain Initiate Upload Response Index Sub-Index Data*)
Fig. 4/18: Write object 100CH
In order to write objects of a valve terminal, the receive SDO must be loaded with the Download command, the index, the subindex and the value. The valve terminal then sends as acknowlegement the index, the subindex and a data byte.
4-40 9801 A VIFB14 - 03/05 4. Commissioning
Diagnosis of status bits The status bits signalize internal errors in the valve terminal. The following errors are reco- gnized: • Undervoltage at valves/outputs < 21.6V • Undervoltage at valves/outputs < 10V • Short circuit/overload of an electrical output • Undervoltage in sensor supply < 10V Further information can be found in chapter 5 "Diagnosis and error treatment" (chapter 5.3 Status bits).
The status bits are treated and transferred like inputs. They always occupy the four highest- value addresses/bits of the available address range. If the inputs of the input addresses/bits thereunder are not used, the valve terminal will set them to "logic zero."
PLEASE NOTE The status bits always increase the number of inputs by 4 and, therefore, also the sum of any input bytes.
Example: Valve terminal fitted with 32 inputs. The number of available input bytes is then: 5 input bytes (28 inputs + 4 status bits).
9801 A 4-41 VIFB14 - 03/05 4. Commissioning
Position of the status bits The addresses of the status bits in the address range of a valve terminal (depending on the extent to which the valve terminal is equipped) are shown in the following table:
Valve terminal Available address Addresses of equipment range the status bits None No address No status bits range for inputs available up to 4 inputs I 0.0 - I 0.3 I 0.4 - I 0.7 up to 12 inputs I 0.0 - I 1.3 I 1.4 - I 1.7 up to 20 inputs I 0.0 - I 2.3 I 2.4 - I 2.7 up to 28 inputs I 0.0 - I 3.3 I 3.4 - I 3.7 up to 36 inputs I 0.0 - I 4.3 I 4.4 - I 4.7 up to 44 inputs I 0.0 - I 5.3 I 5.4 - I 5.7 up to 52 inputs I 0.0 - I 6.3 I 6.4 - I 6.7 up to 60 inputs I 0.0 - I 7.3 I 7.4 - I 7.7
4-42 9801 A VIFB14 - 03/05 4. Commissioning
4.3 BASIC PRINCIPLES OF THE SMART DISTRIBUTED SYSTEM (HONEYWELL)
General information
PLEASE NOTE When using the valve terminal on the Ho- neywell Smart Distributed System (SDS), ob- serve the instructions on setting the station number (see chapter 3).
Commissioning Carry out the following steps in order to commission the system:
Step Activity 1 Setting the protocol • Remove the cover of the node • Set the protocol (Smart Distributed System) • Replace the node cover and screw it tight 2 Setting the station number • Connect the Handheld Activator to the valve terminal • Apply 24 V DC to the valve terminal • Switch on the Handheld Activator • Select the menu
Fig. 4/19: Commissioning steps
9801 A 4-43 VIFB14 - 03/05 4. Commissioning
Number of inputs and outputs
PLEASE NOTE The maximum equipment fitted onto the valve terminal with the SDS protocol is: – max. 4 bytes outputs (32 valve coils and/or electrical outputs). – max. 4 bytes inputs (28 electrical inputs + 4 status bits)
The following equipment can be fitted:
Valve terminal System configuration equipment *) Outputs Inputs Up to 8 outputs 8 – Up to 16 outputs 16 – Up to 32 outputs 32 – Up to 8 outputs and 8 8 4 inputs Up to 16 outputs and 16 16 up to 12 inputs Up to 32 outputs and 32 32 up to 28 inputs *) further variants of equipment are possible
Fig. 4/20: Examples: Variants of equipment
4-44 9801 A VIFB14 - 03/05 4. Commissioning
Summary of implemented object models The table below shows all the implemented attributes of the input object of the valve terminal (as per ”Multiple Binary Input Object” profile = station address n+1).
Attribute Function Variable Size Num- Read/ Value ID type ber Write 0Network Data UByte3r18 Descriptor 1 7 (15, 31)1) 1 Baud rate U Byte 1 r 0 2 Object type U Byte 2 r 1 5 3 3 Partner ID no. U Word 1 r 113 4 Logical address U Byte ? r SDS-ID -12) list 5 Unused – – – – – 6 Un/solicited mode – Byte 1 rw 1 (default) 7 Software version ASCII Undefined 12 r V2.0 (or higher) 8 Diagnostic error UByte1r– counter 9 Diagnostic error U Long Word 1 r – register U = unsigned; r = read only; rw = read/write 1) Depends on equipment fitted on valve terminal. The valve terminal selects the number automatically. 2) Related to station number n+1
Fig. 4/21: Summary of implemented attributes (input model)
9801 A 4-45 VIFB14 - 03/05 4. Commissioning
Attribute Function Variable Size Num- Read/ Value ID type ber Write 10 Cyclic timer U Word 1 rw 0 11 Serial number U Long 1 r Individual 12 Data Code ASCII Undefined 4 r 3497 (or higher) 13 Catalog listing ASCII Undefined 32 r IFB-14 14 Partner name ASCII Undefined 32 r FESTO 15 Component tag ASCII Undefined 32 rw VALVE name TERMINAL 16 Unused – – – – – 17 Unused – – – – – 18 Input variable Boolean Undefined 81 r Status of [16] inputs [32] U = unsigned; r = read only; rw = read/write 1) Depends on equipment fitted on valve terminal. The valve terminal selects the number automatically. 2) Related to station number n+1
Fig. 4/21a: Summary of implemented attributes (input model) – Continued
The following table shows all the implemented attributes of the output object of the valve terminal (as per ”Multiple Binary Output Object” profile = station address n).
4-46 9801 A VIFB14 - 03/05 4. Commissioning
Attribute Function Variable Size Num- Read/ Value ID type ber Write 0 Network Data UByte3r19 Descriptor 129 7 (15, 31)1) 1 Baud rate U Byte 1 r 0 2 Object type U Byte 2 r 1 6 8 3 Partner ID no. U Word 1 r 113 4 Logical address U Byte ? r SDS-ID -12) list 5Unused – – – –– 6Unused – – – –– 7 Software version ASCII Undefined 12 r V2.0 (or higher) 8 Diagnostic error UByte1r– counter 9 Diagnostic error U Long Word 1 r – register 10 Unused – – – – – 11 Serial number U Long 1 r Individual 12 Data code ASCII Undefined 4 r 3497 (or higher) 13 Catalog listing ASCII Undefined 32 r IFB-14 14 Partner name ASCII Undefined 32 r FESTO 15 Component tag ASCII Undefined 32 rw VALVE name TERMINAL 16 Unused – – – – – 17 Unused – – – – – 18 Output variable Boolean Undefined 81 r Status of [16] outputs [32] U = unsigned; r = read only; rw = read/write 1) Depends on equipment fitted on valve terminal. The valve terminal selects the number automatically. 2) Related to station number n Fig. 4/22: Summary of implemented attributes (output model)
9801 A 4-47 VIFB14 - 03/05 4. Commissioning
Summary of actions The table below shows all the implemented actions of the valve terminal (as per ”Multiple Binary Input or Output Object” profile).
Action Function Request Data Request Response Response ID parameters Data Data Data parameter parameters parameter type type 0 No operation None None – 1 Change New address U 8 None – address device ID U 8 partner ID U 16 serial no. U 32 2 Self test None – None – 6 Clear all errors None – None – 8 Enroll logical None – Serial no. U 16 device partner ID U 32 53 Read primitive Attribute ID U 8 Attribute ID U 8 tag primitive U 32 tag 57 Password Password U 8*N None – code U = unsigned; r = read only; rw = read/write Fig. 4/23: Summary of implemented actions
4-48 9801 A VIFB14 - 03/05 4. Commissioning
Summary of events The table below shows all the implemented events of the valve terminal (as per ”Multiple Binary Input or Output Object” profile).
Event Function Output Data Output Data ID parameters parameter type 0 Diagnostic Counter value U 8 event counter 6 Update input Attribute ID U 8 state 1) data U 8 7 Noop 1) –– U = unsigned 1) Only valve terminal with inputs and outputs Fig. 4/24: Summary of implemented events
Assignment of SDS IDs The table below shows the assignment of the object IDs and attribute IDs to the SDS IDs:
Valve terminal Output Input equipment Only outputs SDS ID n*) – object ID 0 attribute ID 19 max. 28 inputs SDS ID n*) SDS ID n+1*) and object ID 0 object ID 0 max. 32 outputs attribute ID 19 attribute ID 18 Only inputs – Not possible *) SDS ID n stands for the stored station number in the valve terminal. Fig. 4/25: Assignment of the SDS IDs
9801 A 4-49 VIFB14 - 03/05 4. Commissioning
Diagnosis
PLEASE NOTE The controllers offer very different diagnostic possibilities. Details can be found in the ma- nual for your interface or control system and in the following chapter.
The Festo valve terminal supports the following functions:
- Diagnostic error counter - Diagnostic error register.
The number of set bits in the error register is shown in the error counter. In addition to the SDS-typical error codes, the error register also contains valve terminal specific error messages.
4-50 9801 A VIFB14 - 03/05 4. Commissioning
The table below shows the assignment of the valve terminal specific bits in byte 2 of the diagnostic error register. Bytes 3 and 4 are not assigned.
Bit Function Meaning 0Reserved 1Reserved 2 Short circuit/ Short circuit/overload of an over load electrical output 3Reserved
4VSen Undervoltage in sensor supply (< 10 V)
5VVal Undervoltage in valve supply (< 21.6 V)
6Voff Undervoltage in valve supply (< 10 V) 7Reserved Fig. 4/26: Valve terminal specific error messages
In addition, the Festo valve terminal provides status bits for diagnostic purposes, irrespective of the control system used.
Diagnosis via status bits
PLEASE NOTE The status bits are only available if inputs are fitted.
9801 A 4-51 VIFB14 - 03/05 4. Commissioning
The status bits signalize internal errors of the valve terminal. The following errors are reco- gnized: • undervoltage at valves/outputs < 21.6 V • undervoltage at valves/outputs < 10 V • short circuit/overload at an electrical output • undervoltage in sensor supply < 10 V Further details can be found in chapter 5.4, Status bits.
PLEASE NOTE The status bits are treated and transferred like inputs. They always occupy the four highest value addresses/bits of the configured address range. If the inputs of the input addresses/bits thereunder are not used, the valve terminal will set them to ”logic zero."
The status bits occupy the following address range depending on the equipment fitted on the valve terminal:
Valve terminal Configured address Available input Addresses of equipment range addresses the status bits No inputs – – – Up to 4 inputs 1 byte / 8 inputs 0 ... 3 4 ... 7 Up to 12 inputs 2 bytes / 16 inputs 0 ... 11 12 ... 15 Up to 28 inputs 4 bytes / 32 inputs 0 ... 27 28 ... 31 Fig. 4/27: Position of status bits
4-52 9801 A VIFB14 - 03/05 4. Commissioning
Setting the transmission mode
PLEASE NOTE • Undertake all settings via the user program. In this way you can be sure that a new node will automatically be set correctly after servicing. The Festo valve terminal is set at the factory as follows: Unsolicited mode (attribute ID 6 = 1). Cyclical timer = 0 (attribute ID 10 = 0)
The following transmission modes of the valve terminal inputs can be set with the Handheld Activator: • Solicited mode: inputs are interrogated by the master • Unsolicited mode: event-controlled transmission of status mo- difications • Cyclic mode: cyclic transmission of the valve terminal inputs. The repetition time results from: (set value) * 10 ms. The value 0 deactivates this mode. All three transmission modes can be com- bined. Further information can be found in the documentation for your control system.
9801 A 4-53 VIFB14 - 03/05 4. Commissioning
Set the transmission mode with the Handheld Activator as follows: 1. Connect the Activator to the valve terminal. 2. Activate function F1 - Select Device (2x). Se- lect the valve terminal. Enter the address of the input object to be modified. Transfer this with ENT. 3. Press ESC (= return to input starting menu). 4. Activate F2 - Data / Function. 5. Activate F3 - Direct Access 6. Enter 6. 7. The set Un/Solicited mode will appear, e.g. 1. 8. Press the PROG key. Set the desired mode: 0 = Solicited mode 1 = Unsolicited mode 9. Transfer the mode with ENT. 10. Press ESC (= return to main menu). The Cyclical timer is set accordingly. Select attribute 10 (instead of attribute 6).
Bus configuration The SDS bus configuration is different for each system. The following examples show two bus configurations for the most common SDS control systems.
4-54 9801 A VIFB14 - 03/05 4. Commissioning
4.3.1 CONFIGURING/ADDRESSING THE HONEYWELL SDS PC CONTROL
General information
PLEASE NOTE The following information refers to the special settings required when the Honeywell SDS PC is used in conjunction with a Festo valve ter- minal.
Configuration must be made with a special Honeywell program. Details on installing and operating this program can be found in the relevant Honeywell documentation.
The SDS device address (SDS-ID) must be the same as the station number stored in the valve terminal.
Settings in the Device Editor
PLEASE NOTE If certain device types are not available in your control system, contact your control system supplier. He will supply you with the necessary updates.
9801 A 4-55 VIFB14 - 03/05 4. Commissioning
Enter the following with the Device Editor: • Device name • Device type • SDS device address.
1
2
1 Festo valve terminals require specific entries both for outputs and inputs 2 Configuring Festo valve terminals as: - 8; 16 or 32 input bits and - 8; 16 or 32 output bits Fig. 4/28: Select device and device type for Festo valve terminals
4-56 9801 A VIFB14 - 03/05 4. Commissioning
Activate the button "Configure". Then assign an SDS device address (SDS-ID) to each device (see also chapter 3).
1
2
1 )Valve terminals with outputs occupy one SDS Device Address (n = odd number) 2 Valve terminals with outputs and inputs occupy two SDS Device Addresses (n and n+1) Fig. 4/29: Assigning the SDS device address
The assignment of device, device type and SDS device address is then concluded.
9801 A 4-57 VIFB14 - 03/05 4. Commissioning
Settings in the Tag Editor
PLEASE NOTE Declare the inputs and outputs of the valve terminal in bits. In this way, the valve coils and the return messages from the sensors can be addressed more easily in the sequence pro- gram.
Enter symbolic names for the inputs or outputs of the valve terminal as follows: 1. ”Device”: select the SDS-ID for the valve ter- minal to be configured. 2. "Type": select "Input bit" 3. "Tag”: enter a symbolic name for each I/O listed under "Point".
4-58 9801 A VIFB14 - 03/05 4. Commissioning
The example shows the configuration of the valve terminal inputs. The outputs must be configured in the same way.
1
1 Symbolic name for each bit Fig. 4/30: Entries in the Tag Editor
9801 A 4-59 VIFB14 - 03/05 4. Commissioning
Setting the transmission types for inputs by means of the programming software You can set the transmission type for inputs with the function ”Attribute Editor” during the network test.
Example:
1
2
1 SDS ID of the valve terminal 2 Mode selcetion: 0 = Solicited Mode 1 = Unsolicited Mode Fig. 4/31: Setting the Un/Solicited Mode
4-60 9801 A VIFB14 - 03/05 4. Commissioning
Setting the Cyclical Timer
1
2
1 SDS ID of the inputs of the valve terminal 2 Refresh time of inputs: 0 = Inactive n = Refresh time n * 10 ms Fig. 4/32: Setting the Cyclical Timer
Settings can also be made via the user program (function ”I/O Special Function Se- lection” or ”SDS Attribute Write”, see appro- priate documentation).
9801 A 4-61 VIFB14 - 03/05 4. Commissioning
Recommendation: Enter the necessary settings via the user program. During servicing, these settings will be trans- ferred automatically.
Example:
1
2 3
4
5
1 Activate SDS driver 2 Activate Write Device 3 Select SDS ID of the inputs of the valve terminal 4 Attribute 6: Un/Solicited Mode 5 Mode 0 or 1 via variable Fig. 4/33: Setting the Un/Solicited Mode via the user program
4-62 9801 A VIFB14 - 03/05 4. Commissioning
Diagnosis The following possibilities of diagnosis are available: • Diagnosis via the network manager • Diagnosis via the SDS user program • Diagnosis via the status bits
Diagnosis via the network manager Faulty slaves can be localized with the function ”Network Status and Diagnostics” in the net- work manager.
To improve diagnosis you should make a list of all the attributes. Attribute 9 (SDS ”Diagnostic Register”) contains valve terminal specific error messages in addition to SDS specific error messages.
Diagnosis via the SDS user program The SDS ”Diagnostic Error Counter” (attribute 8) and the SDS ”Diagnostic Error Register” (attribute 9) can be downloaded from the user program with the function ”I/O Special Function Selection.”
9801 A 4-63 VIFB14 - 03/05 4. Commissioning
Example:
1
2 3
4
5
1 Activate SDS driver 2 Activate Device Diagnostic 3 Select SDS ID 4 Diagnostic bytes 0 and 1 5 Diagnostic bytes 2 and 3 Fig. 4/34: Download SDS diagnostic register
The low and high integer variables contain valve terminal specific error mesages in additi- on to SDS specific error messages.
4-64 9801 A VIFB14 - 03/05 4. Commissioning
Structure of the SDS diagnostic register You can find the valve terminal specific error messages in byte 1 of the diagnostic register or in the low integer variable. Further details on the causes of faults can be found in chapter 5 ”Diagnostics and error treatment.”
Diagnostic register: Byte 0, 1, 2, 3
Byte 0 Byte 1
Specific error code for valve terminals
27 26 25 24 23 22 21 20 27 26 25 24 23 22 21 20
R 654R 2 RR SDS
Byte 2 Byte 3
27 26 25 24 23 22 21 20 27 26 25 24 23 22 21 20
R R
2 Short circuit/overload 6 Voff < 10 V 4 VSen < 10 V R reserved 5 VVal < 21.6 V SDS SDS specific error code
Fig. 4/35: Assignment of the SDS diagnostic register
Please refer to the Honeywell programming software manual for a description of the error code.
9801 A 4-65 VIFB14 - 03/05 4. Commissioning
Diagnosis via the status bits The status bits signalize internal errors of the valve terminal. The following errors are reco- gnized: • undervoltage at valves/outputs < 21.6 V • undervoltage at valves/outputs < 10 V • short circuit/overload at an electrical output • undervoltage in sensor supply < 10 V Further details can be found in chapter 5.4.
PLEASE NOTE The status bits are treated and transferred like inputs. They always occupy the four highest value addresses/bits of the configured address range. If the inputs of the input addresses/bits thereunder are not used, the valve terminal will set them to ”logic zero”.
The status bits occupy the following address range, depending on the equipment fitted on the valve terminal:
Valve terminal Available input Addresses of equipment addresses the status bits No inputs – – Up to 4 inputs 0 ... 3 4 ... 7 Up to 12 inputs 0 ... 11 12 ... 15 Up to 28 inputs 0 ... 27 28 ... 31
Fig. 4/36: Position of the status bits
4-66 9801 A VIFB14 - 03/05 4. Commissioning
4.3.2 CONFIGURING/ADDRESSING WITH THE GE FANUC SERIES 90/30
General information
PLEASE NOTE The following information refers to the SDS In- terface from Horner Electric in conjunction with the GE Fanuc Series 90/30.
With this control system, the bus configuration is carried out with the configuration program SDS Interface Configuration Utility (SDSCFG.EXE) from Horner Electric. Details on installing and operating this program can be found in the documentation for the interface module. General SDS information can also be found in previous pages.
Festo valve terminals are configured like SDS modules.
9801 A 4-67 VIFB14 - 03/05 4. Commissioning
Bus configuration Carry out the bus configuration as indicated in the following steps: 1. Select the slave to be configured. 2. Assign the I/O addresses: - input addresses before - output addresses.
Assigning the I/O addresses
PLEASE NOTE • Depending on the equipment fitted, the Festo valve terminal occupies one or two station numbers (SDS IDs). • The number of inputs/outputs (rounded up to 8, 16 or 32 inputs/outputs) must correspond to the equipment fitted on the valve terminal. You must not configure additional inputs or outputs as reserves.
Valve terminal SDS ID SDS ID equipment for outputs for inputs Only inputs – –
Only outputs n *) – Inputs and outputs n *) n+1
*) SDS ID n stands for the station number stored in the valve terminal.
Fig. 4/32: Assignment of station numbers to the valve terminal equipment
4-68 9801 A VIFB14 - 03/05 4. Commissioning
Sequence of the input assignment: 1. Enter the PLC starting address of the valve terminal inputs. 2. Enter the number of valve terminal inputs in- cluding 4 status bits. The number of inputs and outputs depends on the equipment fitted on the valve terminal.
Valve terminal System configuration equipment Outputs Inputs
Up to 8 outputs 8 –
Up to 16 outputs 16 – Up to 32 outputs 32 –
Up to 8 outputs and 88 4 inputs
Up to 16 outputs and 16 16 up to 12 inputs Up to 32 outputs and 32 32 up to 28 inputs
Fig. 4/33: System configuration dependent on equipment fitted on the valve terminal
Sequence of the output assignment: 1. Enter the PLC starting address of the valve terminal outputs. 2. Enter the number of valve terminal outputs (spools and electrical outputs). See also pre- vious table.
9801 A 4-69 VIFB14 - 03/05 4. Commissioning
Examples: Configuration of a valve terminal with 28 inputs (+ 4 status bits) and 24 outputs, station number (SDS-ID) = 45.
45
236 32 2
1 45 46
1 Slave configuration (inputs) 2 Slave selection: inputs of the valve terminal Fig. 4/39: Example – configuration of the inputs (SDS ID 46)
4-70 9801 A VIFB14 - 03/05 4. Commissioning
45
2 236 32
1 45 46
1 Slave configuration (outputs) 2 Slave selection: outputs of the valve terminal Fig. 4/40: Example – configuration of the outputs (SDS ID 45)
9801 A 4-71 VIFB14 - 03/05 4. Commissioning
The following I/O assignment results from the configuration shown: S
* unused
Program:
S = Statusbits Fig. 4/36: Example – I/O assignment of the valve terminal with SDS interface and GE 90-30
4-72 9801 A VIFB14 - 03/05 4. Commissioning
Diagnosis The following possibilities for diagnosis are available: • diagnosis via the SDS interface • diagnosis via the status bits
Diagnosis via the SDS interface When configuring the Horner SDS interface you can set the following for diagnosis: • one (1) or three (3) analogue input words and • one (1) analogue output word. Further details on the causes of faults can be found in chapter 5 ”Diagnostics and error treatment.”
9801 A 4-73 VIFB14 - 03/05 4. Commissioning
Valve terminal specific data with three (3) analogue input words (high byte of word n+1):
Register High-Byte Low-Byte
Specific error code for valve terminals
%Aln 27 26 25 24 23 22 21 20 27 26 25 24 23 22 21 20
E D
%Aln+1 27 26 25 24 23 22 21 20 27 26 25 24 23 22 21 20
R 6 54 R 2 RR E
%Aln+2 27 26 25 24 23 22 21 20 27 26 25 24 23 22 21 20
2 Short circuit/overload D Device number 4 VSen < 10 V E Error code 5 VVal < 21.6 V R reserved 6 VOut < 10 V
Fig. 4/37: Valve terminal specific assignment of high byte of %AIn+1)
The description of the error code can be found in the documentation for your SDS interface.
4-74 9801 A VIFB14 - 03/05 4. Commissioning
Diagnosis via status bits
PLEASE NOTE The status bits are only available if inputs are fitted on the valve terminal.
The status bits signalize internal faults in the valve terminal. The following faults are recogni- zed: • undervoltage at valves/outputs < 21.6 V • undervoltage at valves/outputs < 10 V • short circuit/overload at an electrical output
• undervoltage in sensor supply < 10 V Further details can be found in chapter 5.4, Status bits.
PLEASE NOTE The status bits are treated and transferred like inputs. They always occupy the four highest value addresses/bits of the configured address range. If the inputs of the input addresses/bits thereunder are not used, the terminal will set them to ”logic zero.”
9801 A 4-75 VIFB14 - 03/05 4. Commissioning
The status bits occupy the following address range depending on the equipment fitted on the valve terminal:
Valve terminal Configured Available address Addresses of the equipment address range range status bits No inputs Up to 4 inputs %I Size = 8 0 ... 3 %In+4 ...+7 Up to 12 inputs %I Size = 16 0 ... 11 %In+12 ...+15 Up to 28 inputs %I Size = 32 0 ... 27 %In+28 ...+31 n = Configured starting address of the inputs
Fig. 4/43: Position of the status bits
4-76 9801 A VIFB14 - 03/05 5. Diagnosis and error treatment
5. DIAGNOSIS AND ERROR TREATMENT
9801 A 5-1 VIFB14 - 03/05 5. Diagnosis and error treatment
Contents
5.1 SUMMARY OF DIAGNOSTIC POSSIBILITIES 5-3
5.2 ON-THE-SPOT DIAGNOSIS 5-4 LED display (node) 5-4 Valves 5-8 Input/output modules 5-10
5.3 TESTING THE VALVES 5-11
5.4 STATUS BITS 5-13
5.5 ERROR TREATMENT 5-15 Reaction to faults in the CANopen 5-16 Reaction to faults in the Smart Distributed System 5-17 Short circuit/overload at an output module 5-18
5-2 9801 A VIFB14 - 03/05 5. Diagnosis and error treatment
5.1 SUMMARY OF DIAGNOSTIC POSSIBILITIES The modular valve terminal offers comprehen- sive and user-friendly possibilities for diagnosis and error treatment. The following possibilities are available depending on the equipment fitted on the terminal.
Equipment fitted on the valve terminal Input modules FB14 (electrical inputs) Diagnostic Status bits LEDs possibilities Status bits Meaning
AA MOD/NET
POWER AA
Bit Bit Bit Bit AA STATUS
AA AA AA
BUS AAERROR AA 7 6 5 4 POWERAA 0 0 0 0 No error BUS X 0 1 X S.C./O X 1 0 X Vval < 21.6V X 1 1 X Vout < 10 V 1 X X X Vsen < 10 V
X = not relevant Brief The four status bits are The LEDs show directly description transferred cyclically to the configuration errors, hardware field bus module as "inputs" errors and bus errors. together with the normal inputs. Advantage Fast access to error messages Fast "on-the-spot" error recognition Detailed Chapter 5.4 Chapter 5.2 description Fig. 5/1: Possibilities of diagnosis and error treatment
9801 A 5-3 VIFB14 - 03/05 5. Diagnosis and error treatment
5.2 ON-THE-SPOT DIAGNOSIS
LED display (node) The LEDs on the cover of the node supply information on the operating status of the valve terminal.
Green LED Green LED (display for (display
voltage node OK) AAA
AAAAPOWER MOD/NET AAA
AAAA STATUS AAA
supply) AAAA
AAAA AAA AAAA
BUS AAA ERROR
AAAA AAA
AAAA POWER AAA
Green LED Red LED (display for (error display) bus voltage BUS supply)
Fig. 5/2: LEDs on the node
The following tables show the various opera- ting states indicated by the LEDs.
LED Meaning
LED is out
LED lights up
LED flashes
5-4 9801 A VIFB14 - 03/05 5. Diagnosis and error treatment
LED displays of the CANopen
Reaction Sequence Operating status Error treatment
POWER LED
Operating voltage applied None ON OFF
ON Operating voltage not Check operating voltage OFF applied connection for electronic components (pin 1).
BUS POWER LED
ON Operating voltage of bus None interface applied OFF
ON Operating voltage of bus Check bus operating OFF interface not applied voltage connection (bus plugs pins 2 and 3)
MOD/NET STATUS LED Operating status normal None ON or OFF operating status normal, Check the ... but valves do not switch. Possible causes: • compressed air supply • compressed air supply not correct • pilot exhaust blocked • pilot exhaust channels
Flashes once when the None bus supply (BUS POWER) is switched on (LED test)
• Pre-operational mode • None • Too many transmission • Check cables/plug errors connectors, switch (error counter overflow) valve terminal on again; reduce baud rate or bus length
Fig. 5/3: LED display of operating status
9801 A 5-5 VIFB14 - 03/05 5. Diagnosis and error treatment
Reaction Sequence Operating status Error treatment
ERROR LED
No internal terminal error, None ON No fitting error OFF
• Non-permitted station • Correct station no. number set, station no. assigned twice or max. value exceeded
• Flashes once when None switched on (LED test)
Modules not fitted Reduce the ... ON correctly: OFF • more than 12 I/O • number of I/O modules modules fitted • max. permitted number • number of input of inputs exceeded modules • max. permitted number • number of output of outputs exceeded modules
Hardware error Servicing required ON OFF
Internal terminal fault See chapter 5.3 ON (only CANopen) Status bits OFF
Fig. 5/3a: LED display of operating status (continued)
5-6 9801 A VIFB14 - 03/05 5. Diagnosis and error treatment
LED displays of the Smart Distributed System
Reaction Sequence Operating status Error treatment
POWER LED Operating voltage applied None ON OFF
Operating voltage not Check operating voltage ON applied connection for electronics OFF (pin 1)
ERROR LED Operating voltage of the None ON bus interface applied OFF
ON Operating voltage of the Check connection for bus bus interface not applied operating voltage (bus OFF plug pin 2 and pin 3)
MOD/NET STATUS-LED Operating status normal, None data exchange runs or operating voltage normal, Check the ... but valves do not switch. Possible causes: • compressed air supply • compressed air supply not correct • pilot exhaust blocked • pilot exhaust channels
Field bus node has started. Start communication ON Communication from OFF master has not yet started.
Communication to master • Check cables/plug ON interrupted connectors OFF • If necessary, reduce baud rate or bus length Flashes once when the None bus voltage supply is switched on (LED test) (BUS POWER).
Fig. 5/4: LED display SDS
9801 A 5-7 VIFB14 - 03/05 5. Diagnosis and error treatment
Valves There is a yellow LED for every valve solenoid coil. This LED shows the switching state of the valve solenoid coil.
Yellow LEDs
LED Switch position of Meaning valve solenoid coil Yellow out Basic position Logic 0 (no signal) Yellow alight • Switch position Logic 1 (signal present) or • basic position Logic 1 but: • operating voltage of outputs is below permitted tolerance range (< DC 21.6V) or • compressed air supply not correct or • pilot exhaust blocked or • Servicing required
Fig. 5/5: LED display – switching status of valve solenoid coil
5-8 9801 A VIFB14 - 03/05 5. Diagnosis and error treatment
There is a yellow LED for every pilot solenoid on the ISO terminal. This LED shows the switching status of the valve solenoid coil.
Yellow LEDs
LED Switch position of Meaning pilot solenoid Yellow out Basic position Logic 0 (no signal) Yellow alight • switch position logic 1 (signal present) or • basic position Logic 1 but: • operating voltage of outputs is below permitted tolerance range (< DC 21.6V) or • compressed air supply not correct or • pilot exhaust blocked or • servicing required
Fig. 5/6: LED display – switching status of ISO pilot solenoids
9801 A 5-9 VIFB14 - 03/05 5. Diagnosis and error treatment
Input/output modules In addition to the relevant connections, there are one or two LEDs (status displays) on the input/output modules. These LEDs have the colours: • green (status display of the digital inputs) • yellow (status display of the digital outputs) • red (error display of the digital outputs)
The current signal at the relevant input or output is shown by means of the yellow and green LEDs. The red LEDs of the outputs indicate a short ciruit or overload at the appropriate output.
Green LEDs Red LEDs (short circuit/ Yellow LEDs (Switching status overload display of outputs) (Switching status display of inputs) display of outputs)
I8 I8 I4 O8
LED Status Yellow out Logic 0 or (no signal) green out Yellow alight Logic 1 or (signal present) green alight Red out Output without short circuit/overload Red alight Short circuit/overload at relevant output
Fig. 5/7: LED displays of input/output modules
5-10 9801 A VIFB14 - 03/05 5. Diagnosis and error treatment
5.3 TESTING THE VALVES
WARNING Before starting the test, switch off the com- pressed air supply to the valves.
In this way you can avoid undesired or dangerous movements of the actuators.
CAUTION • This test function runs automatically within the terminal. All the valves are switched on and off cyclically. • None of the programmed lockings or further switching conditions will be taken into account.
The terminal makes the following test routines available with which all the valves are switched on and off cyclically:
Testroutine Meaning Parallel All outputs are switched on and off simultaneously at 1 s intervals. Serial All outputs are switched on and off one after the other at 1 s intervals. Fig. 5/8: Test routines
9801 A 5-11 VIFB14 - 03/05 5. Diagnosis and error treatment
Starting the test routine 1. Switch off the operating voltage supplies (pins 1 and 2). 2. Open the node. 3. Note the position of the address selector switch and of the DIL switch elements. 4. Set address 99 and set DIL switch elements 1 and 2 to OFF, and 3 and 4 to ON. 5. Switch on the operating voltage supplies (pins 1 and 2). 6. Set the desired test routine on the address selector switches as follows:
Test routine Address to be set
Parallel 0, 1 or 2
Serial 3 Fig 5/9: Setting the test routines
7. Start: set DIL switch elements 1 and 2 to ON.
If errors occur when the test routine is started, the red LED on the node will flash quickly. The procedure must then be repeated.
Stopping the test routine 1. Switch off the operating voltage supply to the terminal (pins 1 and 2). 2. Reset the address selector switch and DIL switch elements to their original positions.
5-12 9801 A VIFB14 - 03/05 5. Diagnosis and error treatment
5.4 STATUS BITS The modular valve terminal makes available 4 status bits for diagnostic purposes, irrespective of the protocol set.
PLEASE NOTE The four status bits of the valve terminal are only available when the terminal is fitted with input modules.
The status bits are configured like inputs and always occupy the four highest-value ad- dresses in the available address range.
The status bits are made available at these addresses as soon as there are inputs. If the inputs of the addresses thereunder are not used, the terminal will set them at "logic zero". See also chapter 4.2 Basic principles of commissioning and diagnosis.
9801 A 5-13 VIFB14 - 03/05 5. Diagnosis and error treatment
The four status bits supply coded diagnostic information with the following meaning:
Status bits*) Diagnostic information
27 26 25 24
0000No error
X 0 1 X Short circuit overload at output
X10XVvalves < 21.6 V
X11XVoutputs < 10 V
1XXXVsensor < 10 V
X = not relevant *) The status bits can always be addresed by the four highest-value addresses of the configured address range Fig. 5/10: Coded diagnostic information of the four status bits
Diagnostic Description Function information
Short Output short-circuited or Monitors the electrical circuit/overload overloaded outputs of the output at output modules.
Vvalves < 21.6 V Operating voltage at pin 2 Monitors the tolerance of (valves and outputs) of the the operating voltage for operating voltage connection valves and electrical < 21.6V outputs.
Voutputs < 10 V Operating voltage at pin 2 Monitors the operating (valves and outputs) of the voltage for valves and operating voltage connection electrical outputs (no < 10V voltage, e.g. EMERGENCY STOP).
Vsensor < 10 V Operating voltage at pin 1 Monitors the supply (electronic components and voltage for inputs inputs) of the operating voltage (sensors). Indicates connection < 10 V whether internal fuse has been triggered.
Fig. 5/11: Diagnostic information
5-14 9801 A VIFB14 - 03/05 5. Diagnosis and error treatment
5.5 ERROR TREATMENT
PLEASE NOTE If all outputs are reset after a PLC stop or if there is an interruption or fault in the field bus, the following "pneumatic rules" must be observed: • unilaterally actuated valves assume the basic position • double solenoid valves remain in their current position • mid-position valves assume the mid- position and (depending on valve type) are pressurized, exhausted or blocked.
9801 A 5-15 VIFB14 - 03/05 5. Diagnosis and error treatment
Reaction to faults in the CANopen The reaction of the outputs when there is a fault varies. A distinction is made between: • reset by the master • communication failure
Fault Reaction
Reset by master Outputs are reset immediately
Communication failure When the defined time has (bus interface is still expired (guardtime * lifetime supplied with 24 V) factor) the outputs assume default status (index 100 C and 100 D). The default status is determined by index 6206 and 6207.
Communication failure Outputs are reset (bus interace is no immediately longer supplied with 24 V) Fig. 5/12: Reaction of the valve terminal to faults in the CANopen
5-16 9801 A VIFB14 - 03/05 5. Diagnosis and error treatment
Reaction to faults in the Smart Distributed System
CAUTION The reaction of the outputs to a PLC/IPC stop can be determined for each controller. E.g. Honeywell SDS programming software: with the function "Softing SDS Driver" you can select either ”Hold Last State” or ”Zero Out- puts”. Check which of these settings is suitable for your application.
The reaction of the outputs to faults varies. A distinction is made between the following cases:
Fault Reaction
PLC/IPC stop Outputs are reset immediately. In the case of a programmed ”Hold Last State” the outputs remain set.
Communication failure (bus plug In each case the outputs are reset disconnected or bus interface is no immediately. longer supplied with 24 V)
Communication failure (controller Outputs will be reset when timeout switched off or connection to time (2.5 s) has expired. controller interrupted, but bus interface is still supplied with 24 V) Fig. 5/13: Reaction of the valve terminal to faults in the Smart Distributed System
9801 A 5-17 VIFB14 - 03/05 5. Diagnosis and error treatment
Short circuit/overload at an output module If there is a short circuit or overload: • the digital output will be switched off, • the red LED will light up, • the error code "short circuit overload" will be entered in the four status bits.
In order to reactivate the output, proceed as follows:
Step Explanation
Eliminate short circuit or overload
Set output to 0 (RESET) • Manual in on-line mode • Automatic in PLC program Fig. 5/12: Eliminating short circuit/overload
The output can then be reset to "logic". If the short circuit still exists, the output will be switched off again.
5-18 9801 A VIFB14 - 03/05 Appendix A
TECHNICAL APPENDIX
9801 A A-1 VIFB14 - 03/05 Appendix A
Contents TECHNICAL SPECIFICATIONS A-3 General A-3 Operating voltage for electronic components and inputs A-4 Operating voltage for outputs/valves A-4 Operating voltage for bus interface A-5 Electrical input modules A-5 Electrical output modules A-5 Field bus A-6 Electromagnetic compatibility (EMC) A-6
CABLE LENGTH AND CROSS SECTION A-7 Calculating with a graph A-8 Calculating with a formula A-10
EXAMPLES OF CIRCUITRY A-12 Operating voltage connection type 03 A-12 Operating voltage connection type 05 A-13 4-input modules (PNP) A-14 8-input modules (PNP) A-15 4-input modules (NPN) A-16 8-input modules (NPN) A-17 4-output modules A-18
ACCESSORIES A-19 Bus connection A-19
A-2 9801 A VIFB14 - 03/05 Appendix A
TECHNICAL SPECIFICATIONS
General Protection class IP 65 (as per DIN 40050)
Temperature during • operation + 5oC ... +50oC • storage/transport -20oC ... +60oC Oscillation (as per DIN/IEC 68 parts 2-6 and as per IEC 721/parts 2-3) 3.5 mm path • Transport at 2-8 Hz 1 g acceleration at 8-25 Hz
• Operation 3.5 mm path at 25-57 Hz 5 g acceleration at 57-150 Hz and 1 g acceleration at 150-200 Hz Shock (as per DIN/IEC 68 parts 2-27 und IEC 721) 30 g at 11 ms duration
9801 A A-3 VIFB14 - 03/05 Appendix A
Operating voltage electronic components and inputs (Pin 1 – operating voltage connection) • Rated value DC 24 V (protected against incorrect polarity) • Tolerance ± 25 % (DC18 V ... 30 V) • Residual ripple 4Vpp • Current consumption 200 mA + sum of (at 24 V) current consumption of electrical inputs
• Fuse for supply to internal 2 A, slow inputs/sensors blowing
Power consumption (P) • Calculation P[W] = (0.2 A + ∑ I inputs) ⋅ 24 V Bridging time if logic min. 20 ms voltage drops
Operating voltage outputs/valves (Pin 2 – operating external fuse voltage connection) required • Rated value DC 24 V (typ. 10 A) (protected against incorrect polarity) • Tolerance ± 10 % (DC 21.6 V ... 26.4 V) • Residual ripple 4 Vpp • Current consumption 10 mA (at 24 V) +sum of current consumption of electrical outputs +sum of current consumption of switched valve solenoid coils (e.g. per MIDI valve solenoid coil 55 mA)
Power consumption (P) P[W] = (0.01 A + • Calculation ∑ Ielectrical outputs + ∑ Isolenoid coil) ⋅ 24 V
A-4 9801 A VIFB14 - 03/05 Appendix A
Operating voltage of bus interface (PIN 2, 3 - bus interface) external fuse required
• Rated value DC 24V • Not protected against short circuit • Tolerance + 4% - 52% (Vmax 25V, Vmin 11.5V) • Current consumption 50 mA (at 24 V)
Electrical input modules (PNP/NPN) Input voltage range DC 0 ... 30 V
Logic level PNP • ON ≥ 12.5 V • OFF ≤ 7 V Logic level NPN • ON ≤ 5 V • OFF ≥ 11 V Current consumption (at typ. 9 mA 24V) (input current from sensor to input at "logic 1")
Response delay typ. 5 ms (at 24 V)
Common fuse for 2 A, slow blowing operating voltage supply to sensors
Electrical isolation None
Electrical output modules (PNP) Loading • per digital output max. 0.5 A (bulbs max. 10 W because of PTC effect Current consumption (at 24 V) • Internal consumption typ. 9 mA at "logic 1" Electronic fuse (short circuit overload) • Trigger current max. 1.5 A • Response time max. 1 s (short circuit)
Electrical isolation None
9801 A A-5 VIFB14 - 03/05 Appendix A
Field bus Design ISO 11898 Transmission type serial asynchronous, half- duplex Protocol CANopen Baud rate depends on protocol Cable length (depending on 1000 m baud rate and cable type) Cable type (depending on see controller manual cable length and field bus baud rate set)
Electromagnetic compatibility (EMC) Interference radiated limit class B • tested as per EN 55011,
Resistance to interference • tested as per EN 50082-2
Please refer to the Pneumatics Manual for technical specifications on the pneumatic compo- nents and valves.
A-6 9801 A VIFB14 - 03/05 Appendix A
CABLE LENGTH AND CROSS SECTION
PLEASE NOTE The following information is for the exclusive use of personnel trained in electrotechnology and who are already familiar with the contents of the chapters on "Installation" in this manual.
A load-dependent drop in voltage occurs on all three cables for the operating voltage supply to a valve terminal. This can cause the voltage at pin 1 or 2 of the operating voltage connection to be outside the permitted tolerances.
Recommendation • Avoid long distances between the power unit and the terminal. • Calculate suitable cable lengths and cross sections in accordance with the following graph or formulae. Please note that: – the graph supplies approximate values for the cross sections 1.5 and 2.5 mm2. – the formulae supply exact values for any cross section.
PLEASE NOTE The following graphs and formulae require that the cross sections of the operating voltage supply cables (pins 1, 2 and 3) are the same.
9801 A A-7 VIFB14 - 03/05 Appendix A
Calculating with a graph Proceed as follows: 1. Calculate the maximum current consumption of the output/valves (I2). 2. Calculate the lowest voltage to be expected on the power unit during operation (VOmin). Take into consideration: • the influence of load variation on the power unit • the fluctuations in the primary mains voltage. 3. Read the permitted length of cable in the ta- ble for the relevant cross section. Example for 1.5 mm2: VOmin = 22.8 V, I2 = 2 A; Lmax = 25 m
A-8 9801 A VIFB14 - 03/05 Appendix A
VOmin in volt V Current I2 in ampere
14A 12A 10A8A 6A 4A +10% 26.4 26
3A 25
2A 24
23
22 Cross section 1.5 mm2 -10% 21.6
0 10 20 30 40 50 m
Cable length in metres
VOmin in volt V Current I2 in ampere
14A 12A 10A 8A +10% 26.4 26 6A
25 4A
24 3A
2A 23
22 Cross section 2.5 mm2 -10% 21.6
0 10 20 30 40 50 m Cable length in metres
9801 A A-9 VIFB14 - 03/05 Appendix A
Calculating with a formula Proceed as follows: 1. Calculate the maximum current consumption of the inputs and electronic components (I1) as well as of the outputs/valves (I2). 2. Calculate the lowest voltage to be expected on the power unit during operation (VOmin). Take into consideration: • the influence of load variation on the power unit • the fluctuations in the primary mains voltage. 3. Enter the values in the appropriate formula. The equivalent circuit diagram and the ex- ample explain the relations.
Operating voltage supply Equivalent circuit
Cable VO resistance (outgoing)
VL1 RL1 RL2 VL2 Valve terminal VO 3.15 AT l1 AC Pin 1 l2 10 AT Pin 2 Rl1 Rl2 VTERMINAL *) DC l0 Pin 3
Distance (cable length) L
VL2 + VL1 RL0 cable resistance (returning) 0 V *) EMERGENCY STOP
Fig. A/3: Cable length (L) and cable resistance (RL)
A-10 9801 A VIFB14 - 03/05 Appendix A
Formula for calculating cable lengths
(VOmin − VTERMINALmin) ⋅ A ⋅ κCu L ≤ 2 ⋅ I2 + I1
This means:
• VTERMINAL = 24 V ± 10%, minimum: VTERMINALmin ≥ 21.6 V
• VOmin = minimum operating voltage supply (at power unit)
• Current I1 = Current for electronic compo- nents and inputs
• Current I2 = Current for outputs/valves • A = Cable cross section (uniform e.g. 1.5 mm2) • κ = Conductivity value of cables m (uniform e.g. κCu = 56 ) mm 2 ⋅ Ω
Example I1 =1 A; I2 = 5 A; VOmin = 24 V; VTERMINALmin = 21.6 V ; m κCu = 56 ; mm 2 ⋅ Ω Result L ≤ 18 m for A = 1.5 mm2 L ≤ 30 m for A = 2.5 mm2
9801 A A-11 VIFB14 - 03/05 Appendix A
EXAMPLES OF CIRCUITRY
Operating voltage connection type 03
Pin assignment 1: 24 V supply (node) electronic 2: 24 V supply to components outputs/valves
4: PE 3: 0 V Circuitry example and internal Electrical outputs Valves (must be fused structure 2 A externally) Electrical 24 V electronic inputs/ components sensors without internal (fused fuse internally) Operating voltage connection for valve terminal
1 4 2 3 Power unit (central voltage supply) Further bus slaves 3.15 A AC 24 V ± 10 % 230 V 24 V ± 10 % 10 A DC 0 V *) PE
*) EMERGENCY STOP
Fig. A/4a: Circuitry example – operating voltage type 03
A-12 9801 A VIFB14 - 03/05 Appendix A
Operating voltage connection type 05
Pin assignment 1: 24 V supply 2: 24 V supply to (adapter electronic outputs/valves plate) components and inputs
4: PE 3: 0 V
Circuitry Electrical outputs example and (must be internal fused externally) Adapter cable structure Electrical 2 A inputs/sensors (fused internally) 4 A 24 V electronic Valves max. 50% components simultaneity (fused internally)
1 4 2 3 Power unit Operating voltage (central connection for valve voltage terminal supply) 3.15 A AC 24 V ± 10 % 230 V 24 V ± 10 % 10 A DC 0 V *) PE
*) EMERGENCY STOP
Fig. A/4b: Circuitry example – operating voltage type 05
9801 A A-13 VIFB14 - 03/05 Appendix A
4-input module (PNP)
Internal Pin 24 V ± 25 % structure 1
free 2
PLC/I-PC Logic Ex recognition 4 (via Ix field bus) Green LED Ix
0 V 3
Pin 2: free 3: 0 V assignment
1: + 24 V 4: input Ix
Circuitry examples
positive positive
AAAA AAAA A
AAAA AAA A
A switching switching
AAAA AAAA A
AAAA AAA A A
AAAA AAAA A
AAAA AAA A A
AAAA AAAA A
AAAA AAAA A
Three-wire Two-wire Contact sensor sensor
Fig. A/5: Circuitry examples – 4-input modules (PNP)
A-14 9801 A VIFB14 - 03/05 Appendix A
8-input module (PNP)
Internal Pin 24 V ± 25 % structure 1 PLC/I-PC Logic Ex+1 recognition 2 (via field Ix + 1 PLC/I-PC bus) Logic E Green x recognition 4 (via field LED Ix bus) Ix+1 Green LED Ix
3 0 V
Pin 2: input Ix+1 3: 0 V assignment
1: + 24 V 4: input Ix
Circuitry example Twin distributor (T-piece, e.g. ,
Festo Duo-cable)
A A AAAA AAAA
A A AAAA AAAA
A A AAAA AAAA
A A AAAA AAAA
A A AAAA AAAA
A A AAAA AAAA
A A A A AAA AAA
AAAAA AAAAA
Sensor 2 (Ix+1) Sensor 1 (Ix)
Fig. A/6: Circuitry examples – 8-input modules (PNP)
9801 A A-15 VIFB14 - 03/05 Appendix A
4-input module (NPN)
Internal Pin structure 3 0 V not 2 connected
PLC/I-PC Logic- Ex recognition 4 Ix green LED Ix
24 V ± 25 % 1
Pin 2: not 3: 0 V assignment connected
1: + 24 V 4: Input Ix
Circuitry example
negative positive
A AAAA AAAA A
A AAAA AAAA A
A AAAA AAAA
switching A switching
A AAAA AAAA A
A AAAA AAAA A
A AAAA AAAA A
A A AAA AAAA A
AAAAA AAA A A
AAAAA
Fig. A/7: Circuitry example – 4-input module NPN
A-16 9801 A VIFB14 - 03/05 Appendix A
8-input module (NPN)
Internal 0 V Pin structure 3 PLC/I-PC Logic Ex+1 recognition 2 Ix + 1
Green PLC/I-PC Logic recognition LED Ex 4 Ix + 1 Ix Green LED Ix
24 V ± 25 % 1
Pin 2: Input Ix+1 3: 0 V assignment
1: + 24 V 4:Input Ix Circuitry example Twin distributor T-piece, e.g.
Festo DUO-cable)
AAAA A
AAAA AAAA A A
AAAA AAAA A A
AAAA AAAA A A
AAAA AAAA A A
AAAA AAAA A A
AAAA AAAA A A
AAA AAA A A A A
AAAAA AAAA A
Sensor 2 (Ix+1) Sensor 1 (Ix)
Fig. A/8: Circurity example – 8-input module NPN
9801 A A-17 VIFB14 - 03/05 Appendix A
4-output module (NPN)
Internal ± Pin structure 24 V 10 % free 1 2 PLC/I-PC free Output A 4 x driver (via field bus)
Diagnosis - output status - overload Yellow Red LED 0 V LED 3
Pin assignment 2: not 3: 0 V connected
1: not 4: output Ox connected
Circuitry ex- Example 1 Example 2 NOT + 24 V amples PERMITTED
Fig. A/9: Circuitry examples – 4-output modules
A-18 9801 A VIFB14 - 03/05 Appendix A
ACCESSORIES This section gives a summary of the acces- sories required.
PLEASE NOTE The following summaries do not claim to be complete. The addresses of the suppliers named can be found at the end of the section.
Bus connection The bus must be connected via a branch line by means of a 5-pin M12 socket with PG9 screw connector. These connectors can be ordered from Festo (type: FBSD-GD-9-5POL, part no. 18324).
Alternatively, you can use bus cables (drop cable, M12 / 7/8") from the following manu- facturers:
Manufacturer Type Length Lumberg RS50 RKT5-614/1.5F 1.5 F RS50 RKT5-614/3F 3.0 F RS50 RKT5-614/6F 6.0 F RS50 RKT5-614/9F 9.0 F Turck RSM 572-*M-RKC 4.5T/S633 x m RSM 572-*M-RKC 4.5T/S630 x m *) Length in metres
9801 A A-19 VIFB14 - 03/05 Appendix A
The branch line can be connected to the bus by means of a T-adapter (T-tap). The following T-taps are available to suit the bus cables named.
Manufacturer Type Lumberg TAP 50-RK Turck RSM-2RKM 57 Woodhead DN 3000
The following manufacturers offer T-adapters with screw terminals.
Manufacturer Type Phillips BR50 Selectron CTA 701
Addresses:
Manufacturer Addresses Woodhead United States Industries Inc. Daniel Woodhead 3411 Woodhead Drive Northbrook, Illinois 60062 Canada Woodhead Canada Ltd. Company 1090 Brevik Place Mississauga, Ontario Canada L4W 3Y5 United Kingdom Aero-Motive (U.K.) Ltd. 9. Rassau Industrial Estate Ebbw Vale, Gwent, NP3 5SD, U.K Germany H. F. Vogel GmbH Tullastrasse 9 75196 Remchingen
A-20 9801 A VIFB14 - 03/05 Appendix A
Manufacturer Addresses Lumberg United States Lumberg Inc. 11351 Business Center Drive USA-Richmond, VA 23236 United Kingdom Lumberg (U.K.) Ltd. The Mount, Highclere Newbury, Berkshire, RG 20 9QZ Germany Lumberg GmbH & Co. Hälverstraße 94 D-58579 Schalksmühle Turck United States TURCK Inc. 3000 Campus Drive USA-Plymouth, MN 55441-2656 United Kingdom MTE TURCK Ltd. Stephenson Road Leigh-on-Sea, Essex SS9 5LS Germany Hans Turck Gmbh & Co.KG Witzlebenstraße 7 D-45472 Mülheim an der Ruhr Philips Netherlands PMA Nederland Gebouw TQIII-4 Postbus 80025 NL-5600 JZ Eindhoven Germany Philips Industrial Electrionics Deutschland Miramstraße 87 D-34123 Kassel Selectron Switzerland Selectron Lyss AG Industrielle Elektronik Bernstrasse 70 CH-3250 Lyss Germany Selectron System GmbH Schupfer Strasse 1 Postfach 31 02 62 D-90202 Nürnberg
9801 A A-21 VIFB14 - 03/05 Appendix A
A-22 9801 A VIFB14 - 03/05 Appendix B
INDEX
9801 A B-1 VIFB14 - 03/05 Appendix B
B-2 9801 A VIFB14 - 03/05 Appendix B
PLEASE NOTE The index is based on key words. It therefore supplements the contents which are based on a function/action-orientated grouping.
In the index you will not therefore find "Con- necting the operating voltage", but the separa- te entries "Connections" and "Voltage".
A Abbreviations ...... XIII Accessories Manufacturer ...... A-20 Addressing basic rule 1...... 4-12 basic rule 2...... 4-15 basic rule 3...... 4-15
C Cable connecting to plugs/sockets...... 3-6 field bus ...... 3-4, 3-38 operating voltage ...... 3-4, 3-32, A-7 selecting ...... 3-4, A-7 Calculating the weight ...... 2-11
9801 A B-3 VIFB14 - 03/05 Appendix B
CANopen addressing inputs and outputs...... 4-36 COB identifier...... 4-25 default identifier distribution ...... 4-27 diagnosis of status bits ...... 4-41 DS 301 (Draft Standard) ...... 4-21 DSP (Draft Standard Prosal) ...... 4-21 examples communication process...... 4-38 FAULT MODE ARRAY ...... 4-33 FAULT STATE ARRAY ...... 4-34 general ...... 4-21 - 4-22 INPUT ARRAY...... 4-32 MESSAGE-ID...... 4-25 minimum capability device ...... 4-25 OUTPUT ARRAY...... 4-32 PDO communication mapping parameter field ...... 4-31 PDO communication parameter record . . 4-29 Process Data Objects ...... 4-22 receive PDO mapping parameter ...... 4-31 Service Data Objects ...... 4-22 setting the station number ...... 3-12 summary...... 4-24 transmit PDO mapping parameter ...... 4-31 COB identifier ...... 4-25 Connections inputs ...... 3-45 outputs ...... 3-48 valves ...... 1-7 Connections, valves ...... 1-5, 1-9 Current calculating for type 03 ...... 3-25 fuses...... 3-21, 3-27, 3-37, A-12 selecting the cable ...... 3-32, A-7 Current consumption ...... 3-25
B-4 9801 A VIFB14 - 03/05 Appendix B
D Data transmission interface ...... 3-38, 3-41 Diagnosis diagnostic word ...... 5-13 LEDs...... 5-4 status bits ...... 5-13 Diagnostic possibilities...... 5-3 Digital outputs of valve terminal ...... 4-33
E Earthing components ...... 2-7 valve terminal . . . . 3-2, 3-26, 3-28, 3-35, 3-37 EMERGENCY STOP. . . . 3-23, 3-28, 3-37, A-10 Error short circuit output module...... 5-18 treatment ...... 5-3
F Fastening eyes ...... 2-9, 2-13 Field bus interface ...... 3-38 module ...... XV node ...... 1-11 station number ...... 3-12 Function node ...... 1-8, 1-11, 3-9 valve terminal ...... 1-3, 1-8 Fuses external...... 3-27, 3-37, A-12 internal ...... 3-9, A-12
H Hat rail clamping unit ...... 2-10
9801 A B-5 VIFB14 - 03/05 Appendix B
I Switching status...... 5-10
L LED display inputs ...... 3-46 node ...... 3-11 outputs ...... 3-49 valves ...... 5-8
M MAC-ID ...... 4-25
N Node ...... 1-11
O Operating voltage selecting the cable ...... 3-5 Switching status...... 5-10
P PDO communication mapping ...... 4-31 communication parameter record ...... 4-29 definition of emergency object ...... 4-35 digital inputs of valve terminal ...... 4-32 digital outputs - reaction to faults...... 4-33 parameter field ...... 4-31 Pin assignment ...... 3-47, 3-50 operating voltage ...... 3-26 Protective earth cable components ...... 2-6
B-6 9801 A VIFB14 - 03/05 Appendix B
S Screening field bus ...... 3-41 SDS assignment of SDS IDs ...... 4-49 basic principles...... 4-43 commissioning ...... 4-43 configuring with GE Fanuc 90/30 ...... 4-67 configuring with Honeywell PC control . . 4-55 connecting instructions...... 3-43 diagnosis ...... 4-50 diagnosis via status bits...... 4-51 GE Fanuc, diagnosis via status bits . . . . 4-75 GE Fanuc,diagnosis...... 4-73 Honeywell Device Editor ...... 4-55 Honeywell Tag Editor...... 4-58 Honeywell, diagnosis ...... 4-63 Honeywell, diagnosis via the status bits . 4-66 Honeywell, diagnostic register ...... 4-65 Honeywell, setting the cyclical timer . . . . 4-61 Honeywell, setting the transmission types 4-60 LED displays ...... 5-7 number of inputs and outputs ...... 4-44 reaction, of the valve terminal ...... 5-17 reaction, to faults ...... 5-17 saving the station number ...... 3-14 setting the transmission mode ...... 4-53 summary of actions ...... 4-48 summary of events...... 4-49 summary of implemented object modules 4-45
9801 A B-7 VIFB14 - 03/05 Appendix B
Short circuit eliminate ...... 5-18 fuses...... 3-27, A-12 fusing ...... 3-28 Status bits diagnostic information ...... 5-13 System structure ...... 1-3
T Technical specifications...... A-3
V Voltage connecting ...... 3-21, 3-26 connecting the field bus ...... 3-41, 3-44 connecting type 05...... 3-29, 3-34, 3-37 selecting the cable ...... 3-24, 3-32 selecting the power unit . . . . 3-24, 3-32 - 3-33 switching on ...... 4-6
B-8 9801 A