National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6633-NFPA 101-2019 [ Global Comment ]

Throughout Chapter 40 and Chapter 42 and any associated annex material change the term "flammable and combustible liquid" to "ignitable (flammable and combustible) liquid".

Submitter Information Verification

Committee: SAF-IND Submittal Date: Mon Jul 15 10:31:19 EDT 2019

Committee Statement

Committee This correlates the NFPA 101 terminology with changes to NFPA 30 terminology. Since NFPA Statement: 30 is the expert document, NFPA 101 is updating the terminology to match. Response SR-6633-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

30 Eligible Voters 6 Not Returned 23 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Almannai, Ali Birchler, Donald C. Culp, Christopher Johnson, Aaron Jones, Adam C. Richardson, Dennis A.

Affirmative All Cummings, Ryan Cusimano, Alberto Dacus, Sheldon Dale, Stephen E. Dawe, Nicholas A. Desrosier, John Dudley, Jeffry T.

Page 1 of 373

1 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Early, Rob Hanson, Robert E. Humble, Jonathan Klein, Andrew S. Krantz, Sr., Neal W. Laberge, Todd Lozano-Rosales, Roberto McLaughlin, Patrick A. Pierrottie, Jerald Pruett, Scot Sheldon, Steven A. Skinker, Cleveland B. Swiecicki, Bruce J. Tabar, David C. White, Michael S. Wren, Carl D.

Affirmative with Comment Olsen, Brian L. Introduction of the term does little to advance regulatory compliance or improve safety. Significant effort will be required to retrain those within the oil and gas sector and to update terminology use throughout the industry. Voting affirmative with comment as it is important that the terminology between all NFPA codes and standards be harmonized.

Page 2 of 373

2 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6634-NFPA 101-2019 [ Global Comment ]

Update definitions extracted from NFPA 5000 assigned to SAF-IND. See attached word document for changes.

Supplemental Information

File Name Description Approved INDExtracts5000.docx Final. For ballot

Submitter Information Verification

Committee: SAF-IND Submittal Date: Mon Jul 15 11:18:17 EDT 2019

Committee Statement

Committee Statement: Updating extracts to the latest edition of NFPA 5000 Response Message: SR-6634-NFPA 101-2019

Ballot Results

This item has passed ballot

30 Eligible Voters 6 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Almannai, Ali Birchler, Donald C. Culp, Christopher Johnson, Aaron Jones, Adam C. Richardson, Dennis A.

Affirmative All Cummings, Ryan Cusimano, Alberto Dacus, Sheldon Dale, Stephen E. Dawe, Nicholas A.

Page 3 of 373

3 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Desrosier, John Dudley, Jeffry T. Early, Rob Hanson, Robert E. Humble, Jonathan Klein, Andrew S. Krantz, Sr., Neal W. Laberge, Todd Lozano-Rosales, Roberto McLaughlin, Patrick A. Olsen, Brian L. Pierrottie, Jerald Pruett, Scot Sheldon, Steven A. Skinker, Cleveland B. Swiecicki, Bruce J. Tabar, David C. White, Michael S. Wren, Carl D.

Page 4 of 373

4 of 367 10/21/2019, 3:45 PM SAF-IND Definitions Extracted from NFPA 5000

3.3.179.2.1 Health Hazard Material. A chemical or substance classified as a toxic, highly toxic, or corrosive material in accordance with definitions set forth in this code. [5000, 20182021] (SAF-IND)

3.3.179.7 Toxic Material. A material that produces a lethal dose or a lethal concentration within any of the following categories: (1) a chemical or substance that has a median lethal dose (LD50) of more than 50 mg/kg but not more than 500 mg/kg of body weight when administered orally to albino rats weighing between 200 g and 300 g each; (2) a chemical or substance that has a median lethal dose (LD50) of more than 200 mg/kg but not more than 1000 mg/kg of body weight when administered by continuous contact for 24 hours, or less if death occurs within 24 hours, with the bare skin of albino rabbits weighing between 2 kg and 3 kg each, or albino rats weighing 200 g to 300 g each; (3) a chemical or substance that has a median lethal concentration (LC50) in air of more than 200 parts per million but not more than 2000 parts per million by volume of gas or vapor, or more than 2 mg/L but not more than 20 mg/L, of mist, fume, or dust when administered by continuous inhalation for 1 hour, or less if death occurs within 1 hour, to albino rats weighing between 200 g and 300 g each. [5000, 20182021] (SAF-IND)

Page 5 of 373 National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6635-NFPA 101-2019 [ Global Comment ]

Update definitions extracted from NFPA 400 assigned to SAF-IND. See attached word document for changes.

Supplemental Information

File Name Description Approved INDExtracts400.docx Final. For ballot.

Submitter Information Verification

Committee: SAF-IND Submittal Date: Mon Jul 15 11:26:09 EDT 2019

Committee Statement

Committee Statement: Updating to the latest edition of NFPA 400. Response Message: SR-6635-NFPA 101-2019

Ballot Results

This item has passed ballot

30 Eligible Voters 6 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Almannai, Ali Birchler, Donald C. Culp, Christopher Johnson, Aaron Jones, Adam C. Richardson, Dennis A.

Affirmative All Cummings, Ryan Cusimano, Alberto Dacus, Sheldon Dale, Stephen E. Dawe, Nicholas A.

Page 6 of 373

5 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Desrosier, John Dudley, Jeffry T. Early, Rob Hanson, Robert E. Humble, Jonathan Klein, Andrew S. Krantz, Sr., Neal W. Laberge, Todd Lozano-Rosales, Roberto McLaughlin, Patrick A. Olsen, Brian L. Pierrottie, Jerald Pruett, Scot Sheldon, Steven A. Skinker, Cleveland B. Swiecicki, Bruce J. Tabar, David C. White, Michael S. Wren, Carl D.

Page 7 of 373

6 of 367 10/21/2019, 3:45 PM SAF-IND Definitions Extracted from NFPA 400 3.3.179.2.2 Physical Hazard Material. A chemical or substance classified as a combustible liquid, explosive, flammable cryogen, flammable gas, flammable liquid, flammable solid, organic peroxide, oxidizer, oxidizing cryogen, pyrophoric, unstable (reactive), or water-reactive material. [400, 2019] (SAF-IND)

3.3.179.3 Hazardous Material. A chemical or substance that is classified as a physical hazard material or a health hazard material, whether the chemical or substance is in usable or waste condition. [400, 2019] (SAF-IND)

3.3.179.7.1 Highly Toxic Material. A material that produces a lethal dose or lethal concentration that falls within any of the following categories: (1) a chemical that has a median lethal dose (LD50) of 50 mg/kg or less of body weight when administered orally to albino rats weighing between 200 g and 300 g each; (2) a chemical that has a median lethal dose (LD50) of 200 mg/kg or less of body weight when administered by continuous contact for 24 hours, or less if death occurs within 24 hours, with the bare skin of albino rabbits weighing between 2 kg and 3 kg each or albino rats weighing 200 g to 300 g each; (3) a chemical that has a median lethal concentration (LC50) in air of 200 parts per million by volume or less of gas or vapor, or 2 mg/L or less of mist, fume, or dust, when administered by continuous inhalation for 1 hour, or less if death occurs within 1 hour, to albino rats weighing between 200 g and 300 g each. [400, 2019] (SAF-IND)

Page 8 of 373 National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6563-NFPA 101-2019 [ Detail ]

Updated terminology throughout Chapter 8 to be consistent with terminology used in NFPA 80. - "fire protection rated glazing" to "fire protection glazing" - "fire resistance rated glazing" to "fire resistance glazing" - "fire-rated door" to "fire door" - "fire-rated window" to "fire window" See attached word document for changes.

Supplemental Information

File Name Description Approved 101_Glazing_Terminology.docx Terminology updates for SR-6535. For ballot

Submitter Information Verification

Committee: SAF-FIR Submittal Date: Fri Jun 14 07:40:59 EDT 2019

Committee Statement

Committee This change is to make the use of the terminology consistent with NFPA 80, the reference Statement: document for theses building elements. Response SR-6563-NFPA 101-2019 Message: Public Comment No. 31-NFPA 101-2019 [Section No. 8.3.3.6.10]

Ballot Results

This item has passed ballot

26 Eligible Voters 5 Not Returned 21 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Gould, Jennifer Klein Hall, William J. Jones, Adam C. Richardson, Dennis A. Shino, Gregory K.

Affirmative All Alday, Eddie Dewayne Page 9 of 373

7 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Cahanin, Gregory J. Cook, David Dawe, Nicholas A. Devlin, John F. Dudley, Jeffry T. Goldhammer, Edward S. Graupmann, Joseph Gump, Jack A. Higgins, Joseph Patrick Hopper, Howard Hugo, Jeffrey M. Humble, Jonathan Jackson, Waymon Koffel, William E. McHugh, Jr., William J. Morris, Jeramie W. Roeper, Kurt A. Stashak, Catherine L. Wittasek, Nathan B. Zivnuska, Alexander Frederick

Page 10 of 373

8 of 367 10/21/2019, 3:45 PM 8.3.2.1.1* fire resistance glazing tested in accordance with ASTM E119, Standard Test Methods for Fire Tests of Building Construction and Materials, or UL 263, Fire Tests of Building Construction and Materials, shall be permitted.

Table 8.3.3.2.2 Minimum Fire Ratings for Opening Protectives in Fire-Resistance-Rated Assemblies and Fire-Rated Glazing Markings Fire- Fire-Rated Minimum Side Rated Glazing Minimum Fire Light/Transom Fire Window Glazi Marking Side Window Walls Assembly Marking Fire Door ng Light/Transom Ratinga,b (hr) and Rating (hr) Door Vision Marki Panel Partiti Assemb Panel ng ons lies (hr) Maxim Door Fire Fire Fire Fire Fire Fire Fire Fire Compon (hr) um Visio Protect Resista Protect Resista Protect Resista Protect Resista ent Size n ion nce ion nce ion nce ion nce (in.2) Panel D-H- Elevator 155 90 or D-H-W- hoistway 2 11⁄2 NP 2 NP NP 2 NP W-120 in.2 c D-H- 120 s W-90 D-H- 155 60 or D-H-W- 1 1 NP 1 NP NP 1 NP W-60 in.2 c D-H- 60 W-60 D-20 85 in.2 D-W- 1⁄2 1⁄3 or D- 1⁄3 1⁄3 D-H-20 1⁄3 1⁄3 OH-20 W-30 d 20 W-20 ≤100 Elevator in.2, lobby D-H- 100 D-H-W- (per 1 1 T-60 NP 1 NP NP 1 NP W-60 in.2 a 60 7.2.13.4 or D- ) H-W- 60 >100 in.2,

D-H- W-60 Vertical shafts (includin Maxim D-H- g um 90 or D-H-W- stairway 2 11⁄2 NP 2 NP NP 2 NP W-120 size D-H- 120 s, exits, tested W-90 and refuse chutes) Maxim D-H- um 60 or D-H-W- 1 1 NP 1 NP NP 1 NP W-60 size D-H- 60 tested W-60 Replace ment Maxim D-20 panels in um D-W- 1⁄2 1⁄3 or D- 1⁄3 1⁄3 D-H-20 1⁄3 1⁄3 OH-20 W-30 existing size 20 W-20 vertical tested shafts Horizont Maxim D-H- D-H-W- 2 11⁄2 NP 2 NP NP 2 NP W-120 al exits um 90 or 120

Page 11 of 373 Fire- Fire-Rated Minimum Side Rated Glazing Minimum Fire Light/Transom Fire Window Glazi Marking Side Window Walls Assembly Marking Fire Door ng Light/Transom Ratinga,b (hr) and Rating (hr) Door Vision Marki Panel Partiti Assemb Panel ng ons lies (hr) Maxim Door Fire Fire Fire Fire Fire Fire Fire Fire Compon (hr) um Visio Protect Resista Protect Resista Protect Resista Protect Resista ent Size n ion nce ion nce ion nce ion nce (in.2) Panel size D-H- tested W-90 Horizont al exits Maxim D-H- served um 45 or e e D-H-W- by 2 3⁄4 size 3⁄4 3⁄4 D-H-45 3⁄4 3⁄4 OH-45 W-120 D-H- 45 bridges tested W-45 between e buildings Exit Maxim D-20 access um D-H-W- 1 1⁄3 or D- 3⁄4 3⁄4 D-H-45 3⁄4 3⁄4 OH-45 W-60 corridors size 45 W-20 f tested Maxim D-20 um D-H-W- 1⁄2 1⁄3 or D- 1⁄3 1⁄3 D-H-20 1⁄3 1⁄3 OH-20 W-30 size 20 W-20 tested ≤100 in.2, Other D-H- 100 D-H-W- fire 3 3 180 NP 3 NP NP 3 NP W-180 in.2 a 180 barriers or D- H-W- 180 >100 in.2, D-H- W- 180 Maxim D-H- um 90 or D-H-W- 2 11⁄2 NP 2 NP NP 2 NP W-120 size D-H- 120 tested W-90 Maxim D-H- um 45 or e e D-H-W- 1 3⁄4 size 3⁄4 3⁄4 D-H-45 3⁄4 3⁄4 OH-45 W-60 D-H- 45 tested W-45 e Maxim D-20 um D-H-W- 1⁄2 1⁄3 or D- 1⁄3 1⁄3 D-H-20 1⁄3 1⁄3 OH-20 W-30 size 20 W-20 tested Maxim D-20 Smoke um D-H-W- 1 1⁄3 or D- 3⁄4 3⁄4 D-H-45 3⁄4 3⁄4 OH-45 W-60 barriersf size 45 W-20 tested D-20 Maxim D-H-W- 1⁄2 1⁄3 or D- 1⁄3 1⁄3 D-H-20 1⁄3 1⁄3 OH-20 W-30 um 20 W-20

Page 12 of 373 Fire- Fire-Rated Minimum Side Rated Glazing Minimum Fire Light/Transom Fire Window Glazi Marking Side Window Walls Assembly Marking Fire Door ng Light/Transom Ratinga,b (hr) and Rating (hr) Door Vision Marki Panel Partiti Assemb Panel ng ons lies (hr) Maxim Door Fire Fire Fire Fire Fire Fire Fire Fire Compon (hr) um Visio Protect Resista Protect Resista Protect Resista Protect Resista ent Size n ion nce ion nce ion nce ion nce (in.2) Panel size tested Maxim Smoke D-20 um D-H-W- partition 1 1⁄3 or D- 3⁄4 3⁄4 D-H-45 3⁄4 3⁄4 OH-45 W-60 size 45 sf,g W-20 tested Maxim D-20 um D-H-W- 1⁄2 1⁄3 or D- 1⁄3 1⁄3 D-H-20 1⁄3 1⁄3 OH-20 W-30 size 20 W-20 tested

For SI units, 1 in.2 = 0.00064516 m2. NP: Not permitted. afire resistance glazing tested to ASTM E119, Standard Test Methods for Fire Tests of Building Construction and Materials, or UL 263, Fire Tests of Building Construction and Materials, shall be permitted in the maximum size tested (see 8.3.3.6.8). bFire-rated glazing in exterior windows shall be marked in accordance with Table 8.3.3.6.3. cSee ASME A17.1/CSA B44, Safety Code for Elevators and Escalators, for additional information. dSee ASME A17.3, Safety Code for Existing Elevators and Escalators, for additional information. eMaximum area of individual exposed lights shall be 1296 in.2 (0.84 m2), with no dimension exceeding 54 in. (1.37 m) unless otherwise tested. [80:Table 4.4.5 Note b and 80:4.4.5.1] fFire doors are not required to have a hose stream test per UL 10B, Fire Tests of Door Assemblies, or UL 10C, Positive Pressure Fire Tests of Door Assemblies. gFor residential board and care, see 32.2.3.1 and 33.2.3.1.

8.3.3.6.3 New fire protection glazing shall be marked in accordance with Table 8.3.3.6.3 and

8.3.3.6.4 New fire resistance glazing shall be marked in accordance with Table 8.3.3.6.3 and Table 8.3.3.2.2, and such marking shall be permanently affixed.

8.3.3.6.5 Fire protection glazing shall be permitted in fire barriers having a required fire resistance rating of 1 hour or less and shall be of an approved type with the appropriate fire protection rating for the location in which the barriers are installed.

8.3.3.6.7 Fire protection glazing in fire door assemblies, other than in existing fire-rated door assemblies, shall be of a design that has been tested to meet the conditions of acceptance of NFPA 252, UL 10B, Fire Tests of Door Assemblies, or UL 10C, Positive Pressure Fire Tests of Door Assemblies.

8.3.3.6.8 Fire resistance glazing tested in accordance with ASTM E119, Standard Test Methods for Fire Tests of Building Construction and Materials, or UL 263, Fire Tests of Building Construction and Materials, shall be permitted in fire doors and fire window assemblies in accordance with their listings.

8.3.3.6.9 Nonsymmetrical fire protection glazing systems shall be tested with each face exposed to the furnace, and the assigned fire protection rating shall be the shortest duration obtained from the two tests conducted in compliance with NFPA 257 or UL 9, Fire Tests of Window Assemblies.

8.3.3.6.10

Page 13 of 373 The total combined area of fire protection glazing in fire window assemblies and fire door assemblies used in fire barriers shall not exceed 25 percent of the area of the fire barrier that is common with any room, unless the installation meets one of the following criteria:

(1) The installation is an existing fire window installation of wired glass and other fire-rated glazing materials in approved frames.

(2) The fire protection glazing material is installed in approved existing frames.

Page 14 of 373 National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6581-NFPA 101-2019 [ Detail ]

Revised Wording: 31.3.5.12.1* All high-rise buildings, other than those meeting 31.3.5.12.2 shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with 31.3.5.2within 12 years of the adoption of this Codeby January 1, 2033.

Submitter Information Verification

Committee: SAF-RES Submittal Date: Mon Jul 08 18:54:02 EDT 2019

Committee Statement

Committee This revision is to clarify the 12 year time requirement for sprinkler retrofit in existing high- Statement: rise buildings. Response Message: SR-6581-NFPA 101-2019

Ballot Results

This item has passed ballot

31 Eligible Voters 6 Not Returned 25 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Boyd, H. Wayne Damron, Donald P. Gould, Jennifer Klein Hall, William J. Sharry, John A. Zwirn, Jeffrey D.

Affirmative All Almannai, Ali Asp, Roland A. Bradley, Harry L. Buuck, Daniel Coats, Paul D. Cook, David

Page 15 of 373

9 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Cotter, Patrick B. Cronin, Bradford T. Dawe, Nicholas A. Finnegan, Daniel P. Haidar, Abir Isman, Kenneth E. Lambert, Josh Larson, Mark Lathrop, James K. Longhitano, Alfred J. Mayl, Eric N. Noble, Thomas William Paszczuk, Henry Pauls, Jake Pullen, William Davison Roberts, Richard Jay Spangler, Kevin Versteeg, Joseph H. Zubair Sarwar, Muhammad Ahmad

Page 16 of 373

10 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6658-NFPA 101-2019 [ Detail ]

18.3.7.1 Buildings containing health care facilities shall be subdivided by smoke barriers (see 18.2.4.3), unless otherwise permitted by 18.3.7.2 and 18.3.7.3, as follows:

(1) To divide every story used by inpatients for sleeping or treatment into not less than two smoke compartments

(2) To divide every story having an occupant load of 50 or more persons, regardless of use, into not less than two smoke compartments

(3) To limit the size of each smoke compartment required by 18.3.7.1(1) and 18.3.7.1(2) to an area not exceeding one of the following:

(a) 22,500 ft2 (2100 m2) gross in hospital smoke compartments where any patient sleeping room is configured for two or more patients

(b) 40,000 ft2 (3720 m2) gross in hospital smoke compartments where all patient sleeping rooms are configured for only one patient, in which case suites in accordance with 18.2.5.7 shall be permitted where every occupiable sleeping room within the suite is configured for only one patient

(c) 40,000 ft2 (3720 m2) gross in hospital smoke compartments that contain no patient sleeping rooms

(d) 22,500 ft2 (2100 m2) gross in nursing homes and limited care facilities

(4) To separate atriums in accordance with 8.6.718.3.7.3, in which case no limitation in the atrium size is required

(5) To limit the travel distance from any point to reach a door in the required smoke barrier to a distance not exceeding 200 ft (61 m)

(1)

Supplemental Information

File Name Description Approved 101-SR6658.docx Revisions with track changes. For staff use

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 11:27:08 EDT 2019

Committee Statement

Committee The revision is intended to clarify how to determine the area of a smoke compartment Statement: involving an atrium. Response Message: SR-6658-NFPA 101-2019 Public Comment No. 136-NFPA 101-2019 [Section No. 18.3.7.1]

Ballot Results

Page 17 of 373

11 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 18 of 373

12 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6665-NFPA 101-2019 [ Detail ]

Add annex to 19.3.7 Subdivision of Building Spaces.

A.19.3.7 (New) Where two floors communicate via two-story openings with partial enclosure in accordance with 8.6.8 or convenience openings in accordance with 8.6.9, the total smoke compartment area is the combined areas of the compartments exposed to each other on both floors.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 14:41:02 EDT 2019

Committee Statement

Committee Unprotected vertical openings provide no smoke protection; therefore, the combined floor areas Statement: exposed by the openings need to be considered as a single smoke compartment. (Related CI-6877)

Response SR-6665-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 27 Affirmative All 0 Affirmative with Comments 1 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Cummings, Luke Dagenais, David A. Dannaway, Samuel S.

Page 19 of 373

13 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Negative with Comment Crowley, Michael A. The committee justification is not correct. Chapter 8 , 18 and 19 describe allowable protection for these openings. The openings are not UNPROTECTED.

Page 20 of 373

14 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6667-NFPA 101-2019 [ Detail ]

19.3.7.1(4) (4) The area of any smoke compartment that contains an atrium shall not include the area of the atrium separated in accordance with 8.6.719.3.7.3 shall not be limited in size.

Supplemental Information

File Name Description Approved 101-SR6667.docx Revised 19.3.7.1(4) in track changes. For staff use.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 14:53:45 EDT 2019

Committee Statement

Committee The revision is intended to clarify how to determine the area of a smoke compartment Statement: involving an atrium.

Response Message: SR-6667-NFPA 101-2019

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke

Page 21 of 373

15 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 22 of 373

16 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6674-NFPA 101-2019 [ Detail ]

Add new annex to 20.3.7 Subdivision of Building Space.

A.20.3.7 (New) Where two floors communicate via two-story openings with partial enclosure in accordance with 8.6.8 or convenience openings in accordance with 8.6.9, the total smoke compartment area is the combined areas of the compartments exposed to each other on both floors.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 15:44:59 EDT 2019

Committee Statement

Committee Unprotected vertical openings provide no smoke protection; therefore, the combined floor areas Statement: exposed by the openings need to be considered as a single smoke compartment. (Related CI-6878)

Response SR-6674-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 27 Affirmative All 0 Affirmative with Comments 1 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Cummings, Luke Dagenais, David A. Dannaway, Samuel S.

Page 23 of 373

17 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Negative with Comment Crowley, Michael A. The committee justification is not correct. Chapter 8 , 18 and 19 describe allowable protection for these openings. The openings are not UNPROTECTED.

Page 24 of 373

18 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6680-NFPA 101-2019 [ Detail ]

Add new annex to 21.3.7 Subdivision of Building Space.

A.21.3.7 (New) Where two floors communicate via two-story openings with partial enclosure in accordance with 8.6.8 or convenience openings in accordance with 8.6.9, the total smoke compartment area is the combined areas of the compartments exposed to each other on both floors.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Tue Jul 23 09:48:28 EDT 2019

Committee Statement

Committee Unprotected vertical openings provide no smoke protection; therefore, the combined floor areas Statement: exposed by the openings need to be considered as a single smoke compartment. (Related CI-6879) Response SR-6680-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 27 Affirmative All 0 Affirmative with Comments 1 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W.

Page 25 of 373

19 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Negative with Comment Crowley, Michael A. The committee justification is not correct. Chapter 8 , 18 and 19 describe allowable protection for these openings. The openings are not UNPROTECTED.

Page 26 of 373

20 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6504-NFPA 101-2019 [ Section No. 2.3.2 ]

2.3.2 ANSI Publications. American National Standards Institute, Inc., 25 West 43rd Street, 4th floor, New York, NY 10036. ANSI ASC A14.3, American National Standard for Ladders — Fixed — Safety Requirements, 2008 (R2018) . ICC/ANSI A117.1, Accessible and Usable Buildings and Facilities , 2009. ANSI/BHMA A156.3, Exit Devices, 2014. ANSI/BHMA A156.10, Power Operated Pedestrian Doors, 2011 2017 . ANSI/BHMA A156.19, Power Assist and Low Energy Power Operated Doors, 2013. ANSI/BHMA A156.27, Power and Manual Operated Revolving Pedestrian Doors, 2011 2019 . ANSI/BHMA A156.38, Low Energy Power Operated Sliding and Folding Doors, 2014. ANSI Z223.1, National Fuel Gas Code , 2015.

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 05 13:50:24 EDT 2019

Committee Statement

Committee The revision updates the referenced publications to the current editions. ICC/ANSI A117.1 is Statement: now designated as ICC A117.1. Response SR-6504-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Page 27 of 373

21 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 28 of 373

22 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6505-NFPA 101-2019 [ Section No. 2.3.4 ]

2.3.4 ASME Publications. ASME International, Two Park Avenue, New York, NY 10016-5990. www.asme.org ASME A17.1/CSA B44, Safety Code for Elevators and Escalators, 2013 2016 . ASME A17.3, Safety Code for Existing Elevators and Escalators, 2011 2017 . ASME A17.7/CSA B44.7, Performance-Based Safety Code for Elevators and Escalators, 2007, reaffirmed 2012 2017 .

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 05 13:57:37 EDT 2019

Committee Statement

Committee Statement: The revision updates the referenced publications to the current editions. Response Message: SR-6505-NFPA 101-2019

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M

Page 29 of 373

23 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Jacoby, David J. Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 30 of 373

24 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6506-NFPA 101-2019 [ Section No. 2.3.5 ]

2.3.5 ASSE ASSP Publications. American Society of Safety Engineers Professionals , 520 N. Northwest Highway, Park Ridge, IL 60068. ANSI/ASSE ASSP A1264.1, Safety Requirements for Workplace Walking/Working Surfaces and Their Access; Workplace Floor, Wall and Roof Openings; Stairs and Guardrails /Handrail Systems, 2007 2017 .

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 05 13:59:38 EDT 2019

Committee Statement

Committee ASSE has been renamed ASSP. The revision updates the referenced publication to the Statement: current edition. Response Message: SR-6506-NFPA 101-2019

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J.

Page 31 of 373

25 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 32 of 373

26 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6507-NFPA 101-2019 [ Section No. 2.3.6 ]

Page 33 of 373

27 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

2.3.6 ASTM Publications.

Page 34 of 373

28 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. www.astm.org ASTM C1629/C1629M, Standard Classification for Abuse-Resistant Nondecorated Interior Gypsum Panel Products and Fiber-Reinforced Cement Panels, 2014a 2018a . ASTM D1929, Standard Test Method for Determining Ignition Temperatures of Plastic, 2014 2016 . ASTM D2859, Standard Test Method for Ignition Characteristics of Finished Textile Floor Covering Materials, 2015 2016 . ASTM D2898, Standard Test Methods for Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing, 2010 (2017) . ASTM D3201/D3201M , Standard Test Method for Hygroscopic Properties of Fire-Retardant Wood and Wood-Based Products, 2008ae1 2013 . ASTM D5516, Standard Test Method for Evaluating the Flexural Properties of Fire-Retardant-Treated Softwood Plywood Exposed to Elevated Temperatures, 2009 2018 . ASTM D5664, Standard Test Method for Evaluating the Effects of Fire-Retardant Treatments and Elevated Temperatures on Strength Properties of Fire-Retardant-Treated Lumber, 2010 2017 . ASTM D6305, Standard Practice for Calculating Bending Strength Design Adjustment Factors for Fire- Retardant-Treated Plywood Roof Sheathing, 2008 (2015) e1 . ASTM D6841, Standard Practice for Calculating Design Value Treatment Adjustment Factors for Fire- Retardant-Treated Lumber, 2008 2016 . ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, 2015b 2019a . ASTM E108, Standard Test Methods for Fire Tests of Roof Coverings, 2011 2017 . ASTM E119, Standard Test Methods for Fire Tests of Building Construction and Materials, 2016 2018c e1 . ASTM E136, Standard Test Method for Behavior Assessing Combustibility of Materials in Using a Vertical Tube Furnace at 750°C Degrees C , 2016 2019 . ASTM E648, Standard Test Method for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source, 2015 e1 2017a . ASTM E814, Standard Test Method for Fire Tests of Through- Penetration Fire Stops Stop Systems , 2013a (2017) . ASTM E1354, Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter, 2016a 2017 . ASTM E1537, Standard Test Method for Fire Testing of Upholstered Furniture, 2015 2016 . ASTM E1590, Standard Test Method for Fire Testing of Mattresses, 2013 2017 . ASTM E1591, Standard Guide for Obtaining Data for Deterministic Fire Growth Models, 2013. ASTM E1966, Standard Test Method for Fire-Resistive Joint Systems, 2015 (2019) . ASTM E2072, Standard Specification for Photoluminescent (Phosphorescent) Safety Markings, 2014. ASTM E2073, Standard Test Method for Photopic Luminance of Photoluminescent (Phosphorescent) Markings, 2010 2019 . ASTM E2307, Standard Test Method for Determining Fire Resistance of Perimeter Fire Barriers Using Intermediate-Scale, Multi-Story Test Apparatus, 2015a 2015b e1 . ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings, Facings and Veneers, to Assess Surface Burning Characteristics, 2015a 2017 . ASTM E2573, Standard Practice for Specimen Preparation and Mounting of Site-Fabricated Stretch Systems to Assess Surface Burning Characteristics, 2012 2017 . ASTM E2579, Standard Practice for Specimen Preparation and Mounting of Wood Products to Assess Surface Burning Characteristics, 2015 2019 . ASTM E2599, Standard Practice for Specimen Preparation and Mounting of Reflective Insulation, Radiant Barrier and Vinyl Stretch Ceiling Materials for Building Applications to Assess Surface Burning Characteristics, 2015 2018 . ASTM E2652, Standard Test Method for Behavior Assessing Combustibility of Materials in Using a Tube Furnace with a Cone-shaped Airflow Stabilizer, at 750°C Degrees C , 2016 2018 . Page 35 of 373

29 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

ASTM E2768, Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials (30 min Tunnel Test), 2011 (2018) . ASTM E2837, Standard Test Method for Determining the Fire Resistance of Continuity Head-of-Wall Joint Systems Installed Between Rated Wall Assemblies and Nonrated Horizontal Assemblies, 2013 (2017) . ASTM E2965, Standard Test Method for Determination of Low Levels of Heat Release Rate for Materials and Products Using an Oxygen Consumption Calorimeter, 2016 2017 . ASTM E3082, Standard Test Methods for Determining the Effectiveness of Fire Retardant Treatments for Natural Christmas Trees , 2017 e1. ASTM F851, Standard Test Method for Self-Rising Seat Mechanisms, 1987 (2013). ASTM F1085, Standard Specification for Mattress and Box Springs for Use in Berths in Marine Vessels, 2014. ASTM F1577, Standard Test Methods for Detention Locks for Swinging Doors, 2005 (2012 2019 ). ASTM G155, Standard Practice for Operating Xenon Arc Light Apparatus for Exposure of Non-Metallic Materials, 2013.

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 05 14:02:22 EDT 2019

Committee Statement

Committee Statement: The revision updates the referenced publications to the current editions. Response Message: SR-6507-NFPA 101-2019 Public Comment No. 121-NFPA 101-2019 [Section No. 2.3.6]

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E.

Page 36 of 373

30 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 37 of 373

31 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6574-NFPA 101-2019 [ New Section after 2.3.7 ]

2.3.8 ICC Publications. International Code Council, 500 New Jersey Avenue, NW, 6th Floor, Washington, DC 20001-2070. ICC A117.1, Accessible and Usable Buildings and Facilities , 2017.

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Thu Jun 27 13:55:45 EDT 2019

Committee Statement

Committee The revision updates the reference to the former ICC/ANSI A117.1, which is now Statement: designated as ICC A117.1. Response Message: SR-6574-NFPA 101-2019

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris

Page 38 of 373

32 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 39 of 373

33 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6508-NFPA 101-2019 [ Section No. 2.3.7 ]

2.3.7 FM Global Publications. FM Global, 270 Central Avenue, P.O. Box 7500, Johnston, RI 02919. www.fmglobal.com FM Approval 4880, Approval Standard for Class 1 Rating of Insulated Wall or Wall and Roof/Ceiling Panels, Interior Finish Materials or Coatings, and Exterior Wall Systems , 2010. ANSI/FM 4880, American National Standard for Evaluating the Fire Performance of Insulated Building Panel Assemblies and Interior Finish Materials , 2017. FM Approval 6921, Approval Standard for Containers for Combustible Waste, 2004.

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 05 14:57:31 EDT 2019

Committee Statement

Committee Statement: The revision updates the referenced publications to the current editions. Response Message: SR-6508-NFPA 101-2019

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Page 40 of 373

34 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Jacoby, David J. Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 41 of 373

35 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6509-NFPA 101-2019 [ Section No. 2.3.9 ]

2.3.11 UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096. www.ul.com UL 9, Fire Tests of Window Assemblies, 2009, revised 2015. UL 10B, Fire Tests of Door Assemblies, 2008, revised 2015. UL 10C, Positive Pressure Fire Tests of Door Assemblies, 2015 2016 . UL 263, Fire Tests of Building Construction and Materials, 2014 2011, revised 2019 . UL 294, Access Control System Units, 1999, revised 2014 2018 . UL 300, Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment, 2005, revised 2014 2018 . UL 300A, Extinguishing System Units for Residential Range Top Cooking Surfaces, 2006. UL 305, Safety Panic Hardware, 1997 2012 , revised 2014 2017 . UL 555, Fire Dampers, 2006, revised 2014 2016 . UL 555S, Smoke Dampers, 1999 2014 , revised 2014 2016 . UL 723, Test for Surface Burning Characteristics of Building Materials, 2008, revised 2013 2018 . UL 790, Test Methods for Fire Tests of Roof Coverings, 2004, revised 2014 2018 . UL 924, Emergency Lighting and Power Equipment, 2006 2016 , revised 2014 2018 . UL 1040, Fire Test of Insulated Wall Construction, 2009 1996 , revised 2013 2017 . UL 1278, Movable and Wall- or Ceiling-Hung Electric Room Heaters , 2014, revised 2018. UL 1315, Safety for Metal Waste Paper Containers, 2007, revised 2013 2017 . UL 1479, Fire Tests of Through- Penetration Firestops, 2003, revised 2012 2015 . UL 1489, Fire Tests of Fire Resistant Pipe Protection Systems Carrying Combustible Liquids , 2016. UL 1715, Fire Test of Interior Finish Material, 1997, revised 2013 2017 . UL 1784, Air Leakage Tests for of Door Assemblies and Other Opening Protectives , 2001, revised 2015. UL 1975, Fire Tests for Foamed Plastics Used for Decorative Purposes, 2006. UL 1994, Luminous Egress Path Marking Systems, 2004, revised 2015. UL 2079, Tests for Fire Resistance of Building Joint Systems, 2004, revised 2014 2015 .

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 05 15:31:35 EDT 2019

Committee Statement

Committee Statement: The revision updates the referenced publications to the current editions. Response Message: SR-6509-NFPA 101-2019

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned Page 42 of 373

36 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 43 of 373

37 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6510-NFPA 101-2019 [ Section No. 2.4 ]

2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2018 2021 edition.

NFPA 72®, National Fire Alarm and Signaling Code® , 2016 2019 edition. NFPA 80, Standard for Fire Doors and Other Opening Protectives, 2016 2019 edition. NFPA 88A, Standard for Parking Structures, 2015 2019 edition. NFPA 150, Standard on Fire and Life Safety in Animal Housing Facilities Code , 2016 2019 edition. NFPA 221, Standard for High Challenge Fire Walls, Fire Walls, and Fire Barrier Walls, 2018 2021 edition. NFPA 252, Standard Methods of Fire Tests of Door Assemblies, 2017 edition. NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source, 2015 edition. NFPA 288, Standard Methods of Fire Tests of Horizontal Fire Door Assemblies Installed in Horizontal Fire Resistance–Rated Assemblies, 2017 edition. NFPA 301, Code for Safety to Life from Fire on Merchant Vessels, 2018 edition. NFPA 400, Hazardous Materials Code, 2016 2019 edition. NFPA 415, Standard on Airport Terminal Buildings, Fueling Ramp Drainage, and Loading Walkways, 2016 edition. NFPA 703, Standard for Fire Retardant–Treated Wood and Fire-Retardant Coatings for Building Materials, 2018 2021 edition. NFPA 921, Guide for Fire and Explosion Investigations, 2017 2021 edition.

NFPA 5000®, Building Construction and Safety Code® , 2018 2021 edition.

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 05 15:54:11 EDT 2019

Committee Statement

Committee The revision updates the reference for extracts in mandatory sections to the current Statement: editions. Response Message: SR-6510-NFPA 101-2019

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Page 44 of 373

38 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 45 of 373

39 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6557-NFPA 101-2019 [ Section No. 3.3.14 ]

3.3.14 Alarm. 3.3.14.1 Single-Station Alarm. A detector comprising an assembly that incorporates a sensor, control components, and an alarm notification appliance in one unit operated from a power source either located in the unit or obtained at the point of installation. [72,2016 2019 ] (SAF-BSF) 3.3.14.2 Smoke Alarm. A single or multiple-station alarm responsive to smoke. [72,2016 2019 ] (SAF-BSF)

Submitter Information Verification

Committee: SAF-BSF Submittal Date: Thu Jun 13 15:53:29 EDT 2019

Committee Statement

Committee Statement: Updated to latest edition of NFPA 72. Response Message: SR-6557-NFPA 101-2019

Ballot Results

This item has passed ballot

28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Donga, Paul M. Jardin, Joseph M. Klinker, Richard L. White, Kristian

Affirmative All Balido, Jodi S Bradley, Harry L. Brinkman, Kevin L. Chen, Flora F. Dale, Stephen E. Dempsey, Bryan Grill, Raymond A.

Page 46 of 373

40 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Hoskins, Bryan Lawrence Hugo, Jeffrey M. Hutton, Claude O. Kellett, Michael Killian, David A. Larrimer, Peter A. Lazarz, Daniel J. Panowitz, Scott E. Reed, Ray F. Reiswig, Rodger Roberts, Richard Jay Ruchala, Kurt A. Shudak, Lawrence J. Szmanda, Michael R. Warner, Todd W. Wren, Carl D. Wyatt, David M.

Page 47 of 373

41 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6654-NFPA 101-2019 [ New Section after 3.3.22.2.1 ]

3.3.22.2.3* Gross Floor Area (Health Care and Ambulatory Health Care Occupancies). For determining the areas of smoke compartments in health care and ambulatory health care occupancies and determining the areas of health care suites, the floor area within the inside perimeter of the outside walls, or the outside walls and fire walls of a building, or outside and/or inside walls that bound an occupancy or incidental use area with no deductions for hallways, closets, thickness of interior walls, columns, or other features, but excluding floor openings associated with atriums and communicating spaces. (SAF-HEA)

A.3.3.22.2.3 Gross Floor Area (Health Care and Ambulatory Health Care Occupancies).

Stairs and elevator and building services shafts are not included in determining gross floor areas of health care and ambulatory health care smoke compartments and health care suites.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Fri Jul 19 14:30:10 EDT 2019

Committee Statement

Committee The definition of “gross floor area” includes all spaces within the boundary of a building, fire area or Statement: occupancy. Though this may be necessary in some cases, stairs and shafts should not be included when calculating the maximum size of health care suites and health care/ambulatory health care smoke compartments. FR 6769, 6820, 6832, 6833, 6850, 6851 and 6856 inserted the word “gross” in all paragraphs where health care suites and smoke compartment areas in health care and ambulatory health care occupancies have maximum area requirements. (The Code previously was silent.) Though the HEA Committee has taken a clarifying position, depending upon how this was interpreted in the past, this text change may adversely cause some existing health care and ambulatory health care smoke compartments and health care suites to become oversized if those areas include stairs and shafts that were not previously included in area calculations. Stair and shafts should not be counted as part of a health care or ambulatory health care smoke compartment or health care suite as including stairs and shafts would decrease their effective size. This change doesn’t materially impact the size of health care and ambulatory health care smoke compartments or health care suites as they still have travel distances limitations.

Response SR-6654-NFPA 101-2019 Message: Public Comment No. 234-NFPA 101-2019 [New Section after 3.3.22.2]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Page 48 of 373

42 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 49 of 373

43 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6538-NFPA 101-2019 [ New Section after 3.3.22.2.2 ]

3.3.22.2.1* Clear Floor Area. Floor area that is accessible and unobstructed. (SAF-MEA)

A.3.3.22.2.1 Clear Floor Area.

Clear floor area is intended to provide open floor space that is accessible to all building occupants for the purpose of providing protected spaces, portions of means of egress paths, or waiting spaces that might be occupied as needed.

Submitter Information Verification

Committee: SAF-MEA Submittal Date: Tue Jun 11 14:39:56 EDT 2019

Committee Statement

Committee The revision provides a definition of the term 'clear floor area' in response to direction from the Statement: correlating committee. The term was added to the first draft in several locations in Chapter 7. Response SR-6538-NFPA 101-2019 Message: Public Comment No. 23-NFPA 101-2019 [New Section after 7.2.12.3.2] Public Comment No. 25-NFPA 101-2019 [New Section after 7.2.12.2.4.1] Public Comment No. 27-NFPA 101-2019 [New Section after 7.2.4.4.5.2] Public Comment No. 28-NFPA 101-2019 [New Section after 7.15.9.2.1] Public Comment No. 26-NFPA 101-2019 [New Section after 7.2.13.2.2]

Ballot Results

This item has passed ballot

32 Eligible Voters 4 Not Returned 26 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Chan, Mark Di Pilla, Steven Perry, Robert R. Phelan, Kevin

Affirmative All

Page 50 of 373

44 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Alles, Ryan Bales, Fred M. Barlow, Charles V. Bush, Kenneth E. Collins, David S. Coombs, Christopher Crowley, Michael A. Day, Richard L. Farr, Ronald R. Frable, David W. Guest, Rita C. Hoskins, Bryan Lawrence Jackson, Waymon Koffel, William E. Larson, Mark Lujan, Cesar Marcyjanik, Brian A. Mueller, Marc Pappas, Denise L. Quinterno, Vincent Saks, Kenneth Shulman, Michael S. Simard, J. Francois Tilton, Kelly R. Versteeg, Joseph H. Woestman, John

Affirmative with Comment Elvove, Joshua W. Adding a definition for "clear area" is needed, since the term is currently used in 7.2.4.2.4 (and will be used 5 more times within Chapter 7 in the upcoming edition). However, the new term may either be in conflict with, or the better term vis-a-vis "net floor area" which is used in a number of the occupancy chapters for similar purposes (i.e., to provide "accessible and unobstructed" floor area when relocating patients and residents into adjacent smoke compartments). Hence, the occupancy chapters should revisit whether the new definition for "clear floor area" is better suited where the term "net floor area" is currently used. Pauls, Jake I am still concerned about the last sentence being misused if users ignore other aspects of the standard (beyond its scope being limited to stairs of stipulated maximum pitch). To merely consult with the manufacturer is not adequate on its own. Additional mitigating measures beyond consulting with the manufacturer are needed. All such measures should only be implemented by competent inspection personnel complying, especially, with 4.1 of the Standard. Mitigation measures to be considered might include, for example, extra care with selection of only relatively highly experienced operating staff, limiting occupant weight, keeping one flight of the stair (ahead of the device) clear of other evacuees, etc.

Page 51 of 373

45 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6569-NFPA 101-2019 [ Section No. 3.3.22.2.2 ]

3.3.22.2.4 Net Floor Area. The floor area within the inside perimeter of the outside walls, or the outside walls and fire walls of a building, or outside and/or inside walls that bound an occupancy or incidental use area requiring the occupant load to be calculated using net floor area under consideration with deductions for hallways, stairs, closets, shafts, thickness of interior walls, columns, or and other features. (SAF-MEA)

Submitter Information Verification

Committee: SAF-MEA Submittal Date: Fri Jun 14 11:41:32 EDT 2019

Committee Statement

Committee It is not the intent to limit the use of the term “net floor area” strictly to occupant load as currently Statement: implied if the occupancy chapters wish to limit an area based on deductions for hallways, stairs, closets, shafts, thickness of interior walls, columns, and other features. Response SR-6569-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

32 Eligible Voters 4 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Chan, Mark Di Pilla, Steven Perry, Robert R. Phelan, Kevin

Affirmative All Alles, Ryan Bales, Fred M. Barlow, Charles V. Bush, Kenneth E. Collins, David S. Coombs, Christopher Crowley, Michael A. Day, Richard L. Page 52 of 373

46 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Elvove, Joshua W. Farr, Ronald R. Frable, David W. Guest, Rita C. Hoskins, Bryan Lawrence Jackson, Waymon Koffel, William E. Larson, Mark Lujan, Cesar Marcyjanik, Brian A. Mueller, Marc Pappas, Denise L. Pauls, Jake Quinterno, Vincent Saks, Kenneth Shulman, Michael S. Simard, J. Francois Tilton, Kelly R. Versteeg, Joseph H. Woestman, John

Page 53 of 373

47 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6624-NFPA 101-2019 [ Section No. 3.3.37.9 ]

3.3.37.9* Special Amusement Building. A building or portion thereof that is temporary, permanent, or mobile and contains a ride or device or system that conveys passengers or patrons where the patrons can be contained or restrained, or provides a walkway along, around, or over a course in any direction as a form of amusement, or entertainment, or education and arranged so that the egress path is not readily apparent due to visual or audio distractions, contains or an intentionally confounded egress path, or is not readily available due to the mode of conveyance through the building or structure. (SAF-AXM)

Submitter Information Verification

Committee: SAF-AXM Submittal Date: Fri Jul 12 09:23:14 EDT 2019

Committee Statement

Committee The revision provides industry standard verbiage relating to ride systems and their Statement: patrons. Response Message: SR-6624-NFPA 101-2019 Public Comment No. 202-NFPA 101-2019 [Section No. 3.3.37.9]

Ballot Results

This item has passed ballot

28 Eligible Voters 5 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Herrera, Mark A. Keberle, Kenneth F. Scandaliato, Steven J. Thomas, Jr., Elbert R. Tubbs, Jeffrey S.

Affirmative All Center, Eric Conner, William Cook, David Deacon, Nils Finnegan, Daniel P. Gandy, Max L. Page 54 of 373

48 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Goosman, Donald G. Hansen, Harold C. Hesson, Stephen C Hollinger, David W. Humble, Jonathan Lake, John Lambert, Josh Morin, Kevin D. Pauls, Jake Peterson, Ryan Quinterno, Vincent Roether, Ed Rogers, Adam Ruling, Karl G. Schweitzer, Charles J. Sherman, Philip R. Shirey, Jeffrey

Page 55 of 373

49 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6558-NFPA 101-2019 [ Section No. 3.3.63.2 ]

3.3.63.2 Multiple-Station Alarm Device. Two or more single-station alarm devices that can be interconnected so that actuation of one causes all integral or separate audible alarms to operate; or one single-station alarm device having connections to other detectors or to a manual fire alarm box. [72,2016 2019 ] (SAF-BSF)

Submitter Information Verification

Committee: SAF-BSF Submittal Date: Thu Jun 13 16:09:43 EDT 2019

Committee Statement

Committee Statement: Updated to latest edition of NFPA 72. Response Message: SR-6558-NFPA 101-2019

Ballot Results

This item has passed ballot

28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Donga, Paul M. Jardin, Joseph M. Klinker, Richard L. White, Kristian

Affirmative All Balido, Jodi S Bradley, Harry L. Brinkman, Kevin L. Chen, Flora F. Dale, Stephen E. Dempsey, Bryan Grill, Raymond A. Hoskins, Bryan Lawrence Hugo, Jeffrey M. Hutton, Claude O.

Page 56 of 373

50 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Kellett, Michael Killian, David A. Larrimer, Peter A. Lazarz, Daniel J. Panowitz, Scott E. Reed, Ray F. Reiswig, Rodger Roberts, Richard Jay Ruchala, Kurt A. Shudak, Lawrence J. Szmanda, Michael R. Warner, Todd W. Wren, Carl D. Wyatt, David M.

Page 57 of 373

51 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6559-NFPA 101-2019 [ Section No. 3.3.74 ]

3.3.74 Emergency Control Functions. Building, fire, and emergency control elements or systems that are initiated by the fire alarm or signaling system and either increase the level of life safety for occupants or control the spread of the harmful effects of fire or other dangerous products. [72,2016 2019 ] (SAF-BSF)

Submitter Information Verification

Committee: SAF-BSF Submittal Date: Thu Jun 13 16:12:08 EDT 2019

Committee Statement

Committee Statement: Updated to latest edition of NFPA 72. Response Message: SR-6559-NFPA 101-2019

Ballot Results

This item has passed ballot

28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Donga, Paul M. Jardin, Joseph M. Klinker, Richard L. White, Kristian

Affirmative All Balido, Jodi S Bradley, Harry L. Brinkman, Kevin L. Chen, Flora F. Dale, Stephen E. Dempsey, Bryan Grill, Raymond A. Hoskins, Bryan Lawrence Hugo, Jeffrey M. Hutton, Claude O.

Page 58 of 373

52 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Kellett, Michael Killian, David A. Larrimer, Peter A. Lazarz, Daniel J. Panowitz, Scott E. Reed, Ray F. Reiswig, Rodger Roberts, Richard Jay Ruchala, Kurt A. Shudak, Lawrence J. Szmanda, Michael R. Warner, Todd W. Wren, Carl D. Wyatt, David M.

Page 59 of 373

53 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6560-NFPA 101-2019 [ Section No. 3.3.80 ]

3.3.80 Evacuation. The withdrawal of occupants from a building. [72,2016 2019 ] (SAF-BSF)

Submitter Information Verification

Committee: SAF-BSF Submittal Date: Thu Jun 13 16:13:33 EDT 2019

Committee Statement

Committee Statement: Updated to latest edition of NFPA 72. Response Message: SR-6560-NFPA 101-2019

Ballot Results

This item has passed ballot

28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Donga, Paul M. Jardin, Joseph M. Klinker, Richard L. White, Kristian

Affirmative All Balido, Jodi S Bradley, Harry L. Brinkman, Kevin L. Chen, Flora F. Dale, Stephen E. Dempsey, Bryan Grill, Raymond A. Hoskins, Bryan Lawrence Hugo, Jeffrey M. Hutton, Claude O. Kellett, Michael Killian, David A. Page 60 of 373

54 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Larrimer, Peter A. Lazarz, Daniel J. Panowitz, Scott E. Reed, Ray F. Reiswig, Rodger Roberts, Richard Jay Ruchala, Kurt A. Shudak, Lawrence J. Szmanda, Michael R. Warner, Todd W. Wren, Carl D. Wyatt, David M.

Page 61 of 373

55 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6687-NFPA 101-2019 [ Section No. 3.3.93.2 ]

3.3.93.2* Limited Care Facility. A building or portion of a building used on a 24-hour basis for the housing of four or more persons who are incapable of self-preservation because of age; physical limitations due to accident or illness; or limitations such as mental retardation intellectual disability /developmental disability, mental illness, or chemical dependency. (SAF-HEA)

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Wed Jul 24 15:06:08 EDT 2019

Committee Statement

Committee Statement: The revision is consistent with updated language in federal law. Response Message: SR-6687-NFPA 101-2019

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Page 62 of 373

56 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 63 of 373

57 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6562-NFPA 101-2019 [ Section No. 3.3.108 ]

3.3.108 Fire Watch. The assignment of a person or persons to an area for the express purpose of notifying the fire department, the building occupants, or both of an emergency; preventing a fire from occurring; extinguishing small fires; or protecting the public from fire or life safety dangers. [1,2018 2021 ] (SAF- BSF)

Submitter Information Verification

Committee: SAF-BSF Submittal Date: Thu Jun 13 16:23:27 EDT 2019

Committee Statement

Committee Statement: Updated to latest edition of NFPA 1. Response Message: SR-6562-NFPA 101-2019

Ballot Results

This item has passed ballot

28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Donga, Paul M. Jardin, Joseph M. Klinker, Richard L. White, Kristian

Affirmative All Balido, Jodi S Bradley, Harry L. Brinkman, Kevin L. Chen, Flora F. Dale, Stephen E. Dempsey, Bryan Grill, Raymond A. Hoskins, Bryan Lawrence Hugo, Jeffrey M. Hutton, Claude O. Page 64 of 373

58 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Kellett, Michael Killian, David A. Larrimer, Peter A. Lazarz, Daniel J. Panowitz, Scott E. Reed, Ray F. Reiswig, Rodger Roberts, Richard Jay Ruchala, Kurt A. Shudak, Lawrence J. Szmanda, Michael R. Warner, Todd W. Wren, Carl D. Wyatt, David M.

Page 65 of 373

59 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6609-NFPA 101-2019 [ Section No. 3.3.198.5 ]

3.3.198.5* Detention and Correctional Occupancy. An occupancy, other than one whose primary intended use is health care, ambulatory health care, or residential board and care, used to lawfully incarcerate or lawfully detain one or more persons under varied degrees of restraint or security where such occupants are mostly incapable of self-preservation because of security measures not under the occupants’ control. (SAF-DET)

A.3.3.198.5 Detention and Correctional Occupancy.

Detention and correctional occupancies include the following: (1) Adult and juvenile substance abuse centers (2) Adult and juvenile work camps (3) Adult community residential centers (4) Adult correctional institutions (5) Adult local detention facilities (6) Juvenile community residential centers (7) Juvenile detention facilities (8) Juvenile training schools Detention and correctional occupancies do not include psychiatric and dementia units in hospitals, emergency rooms in hospitals, ambulatory health care occupancies, nursing homes, and residential board and care occupancies where persons can be lawfully detained. See A.22.1.1.1.6 and A.23.1.1.1.6.

Submitter Information Verification

Committee: SAF-DET Submittal Date: Thu Jul 11 10:34:07 EDT 2019

Committee Statement

Committee This provides clarification that detention and correctional occupancy provisions are not Statement: intended to be applied to health care occupancies. Response SR-6609-NFPA 101-2019 Message: Public Comment No. 21-NFPA 101-2019 [Section No. 3.3.198.5] Public Comment No. 114-NFPA 101-2019 [Section No. A.3.3.198.5]

Ballot Results

This item has passed ballot

16 Eligible Voters 4 Not Returned 11 Affirmative All 1 Affirmative with Comments 0 Negative with Comments Page 66 of 373

60 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

0 Abstention

Not Returned DiMascio, Michael Patterson, Van Hoover Perry, Robert R. Youngberg, Garrick

Affirmative All Aler, Clay P. Bollig, Tracy Collins, Peter J. Gaw, Randy Griffiths, Nolan T Heffernan, Rick Kelly, John Kruszelnicki, Michael Lumley, Troy A. Poole, Jack Schultz, Terry

Affirmative with Comment Stapleton, Jr., James A. NFPA 101-2018, paragraph 21.1.3.2.2, references ASTM F1577, “Standard Test Methods for Detention Locks for Swinging Doors”. The same paragraph occurs in NFPA 5000-2018. It may be worth considering to add other standards that are pertinent to the reliable performance of detention grade swinging and sliding doors, as well as sidelight and multi-lights door openings. These could be added as a list below each paragraph text as follows: 1. ASTM F1450, Standard Test Methods for Hollow Metal Swinging Door Assemblies for Detention Facilities 2. ASTM F1592, Standard Test Methods for Detention Hollow Metal Vision Systems 3. ASTM F2956, Standard Test Methods for Anchoring Systems for Hollow Metal Vision Systems and Door Assemblies Used in Detention and Correctional Facilities 4. ASTM A627, Standard Test Methods for Tool-Resisting Steel Bars, Flats, and Shapes for Detention and Correctional Facilities 5. ASTM F1643, Standard Test Methods for Detention Sliding Door Locking Device Assembly 6. ASTM F1758, Standard Test Method for Detention Hinges used on Detention Grade Swinging Doors

Page 67 of 373

61 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6561-NFPA 101-2019 [ Section No. 3.3.266 ]

3.3.266 Smoke Detector. A device that detects visible or invisible particles of combustion. [72,2016 2019 ] (SAF-BSF)

Submitter Information Verification

Committee: SAF-BSF Submittal Date: Thu Jun 13 16:22:19 EDT 2019

Committee Statement

Committee Statement: Updated to latest edition of NFPA 72. Response Message: SR-6561-NFPA 101-2019

Ballot Results

This item has passed ballot

28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Donga, Paul M. Jardin, Joseph M. Klinker, Richard L. White, Kristian

Affirmative All Balido, Jodi S Bradley, Harry L. Brinkman, Kevin L. Chen, Flora F. Dale, Stephen E. Dempsey, Bryan Grill, Raymond A. Hoskins, Bryan Lawrence Hugo, Jeffrey M. Hutton, Claude O. Kellett, Michael Killian, David A. Page 68 of 373

62 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Larrimer, Peter A. Lazarz, Daniel J. Panowitz, Scott E. Reed, Ray F. Reiswig, Rodger Roberts, Richard Jay Ruchala, Kurt A. Shudak, Lawrence J. Szmanda, Michael R. Warner, Todd W. Wren, Carl D. Wyatt, David M.

Page 69 of 373

63 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6572-NFPA 101-2019 [ Section No. 4.2.4 ]

4.2.4* Security Features. Where buildings are designed and constructed to include security features to protect occupants or contents, such features shall not compromise compliance with other requirements of this Code.

A.4.2.4

Additional information on building security is provided in NFPA 730 and NFPA 731 .

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 26 13:32:26 EDT 2019

Committee Statement

Committee The revision responds to CN-62 (PC-70) by providing an Annex reference to NFPA 730 and Statement: NFPA 731 for security issues. The committee also reviewed the language in 4.2.4 for coordination with NFPA 5000 and determined no revisions are needed. Response SR-6572-NFPA 101-2019 Message: Public Comment No. 70-NFPA 101-2019 [Section No. 4.2.4]

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W.

Page 70 of 373

64 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 71 of 373

65 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6573-NFPA 101-2019 [ Section No. 4.6.6 ]

4.6.6* Time Allowed for Compliance. A limited but reasonable time, commensurate with the magnitude of expenditure, disruption of services, and degree of hazard, shall be allowed for compliance with any part of this Code for existing buildings.

A.4.6.6

In some cases, appreciable cost might be involved in bringing an existing occupancy into compliance. It would be appropriate for the authority having jurisdiction to prescribe a schedule determined jointly with the building owner(s), or even the local building owners trade association, allowing suitable periods of time for the correction of the various deficiencies. The AHJ and building owner should consider, before establishing a time limit, the amount of time required for the building owner to secure the services of a design professional to execute construction documents; secure the necessary funding; secure tax credits/deductions and adjust insurance premiums; solicit and contact a general contractor; execute the permit process; execute the project while the building is occupied and operating; perform testing and final inspection, and receive a certificate of occupancy. In addition, the AHJ should consider the building stock (i.e., building sizes and quantity) in the jurisdiction. For example, the size of the buildings should be taken into consideration as the automatic sprinkler system retrofit of a high-rise building eight stories tall versus a high-rise building 40 stories tall will require significantly different lengths of time to execute corrective action as a result of the shear volume of each of the buildings.

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 26 13:56:58 EDT 2019

Committee Statement

Committee The revision responds to PC-158, the substantiation for which follows: Statement: The Mercantile and Business Occupancies technical committee created a task group to evaluate the requirements for the retrofit of existing high-rise business buildings with automatic sprinkler system. As part of the work, the task group recommends the relocation of the current Annex Section A.39.4.2.2 to Core Chapter 4 with some additional explanation on the determination for the time allowed to comply with various sections of the code because the task group felt that this is a universal issue. A companion public comment has been submitted to the Mercantile and Business Occupancies Chapter 39 to provide reference to Section 4.6.6 and A.4.6.6. Response SR-6573-NFPA 101-2019 Message: Public Comment No. 158-NFPA 101-2019 [New Section after A.4.6.5]

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments

Page 72 of 373

66 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 73 of 373

67 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6541-NFPA 101-2019 [ Section No. 7.2.1.4.1 ]

Page 74 of 373

68 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

7.2.1.4.1* Swinging-Type Door Assembly Requirement. Any door assembly in a means of egress shall be of the side-hinged or pivoted-swinging type, and shall be installed to be capable of swinging from any position to the full required width of the opening in which it is installed, unless otherwise specified as follows: (1) Door assemblies in dwelling units, as provided in Chapter 24, shall be permitted. (2) Door assemblies in residential board and care occupancies, as provided in Chapters 32 and 33, shall be permitted. (3) Where permitted in Chapters 11 through 43 , horizontal Horizontal -sliding or vertical-rolling security grilles or door assemblies that are part of the required means of egress, where permitted in Chapters 11 through 43 , shall be permitted, provided that all of the following criteria are met: (a) Such grilles or door assemblies shall remain secured in the fully open position during the period of occupancy by the general public. (b) On or adjacent to the grille or door opening, there shall be a readily visible, durable sign in letters not less than 1 in. (25 mm) high on a contrasting background that reads as follows: THIS DOOR TO REMAIN OPEN WHEN THE SPACE IS OCCUPIED. (c) Door leaves or grilles shall not be brought to the closed position when the space is occupied. (d) Door leaves or grilles shall be operable from within the space without the use of any special knowledge or effort. (e) Where two or more means of egress are required, not more than half of the means of egress shall be equipped with horizontal-sliding or vertical-rolling grilles or door assemblies. (4) Horizontal-sliding door assemblies shall be permitted under any of the following conditions: (a) Horizontal-sliding door assemblies in detention and correctional occupancies, as provided in Chapters 22 and 23, shall be permitted. (b) Special-purpose horizontally sliding accordion or folding door assemblies complying with 7.2.1.13 shall be permitted. (c) Unless prohibited by Chapters 11 through 43, horizontal-sliding door assemblies serving a room or area with an occupant load of fewer than 10 shall be permitted, provided that all of the following criteria are met: i. The area served by the door assembly has no high-hazard contents. ii. The door assembly is readily operable from either side without special knowledge or effort. iii. The force required to operate the door assembly in the direction of door leaf travel is not more than 30 lbf (133 N) to set the door leaf in motion and is not more than 15 lbf (67 N) to close the door assembly or open it to the minimum required width. iv. The door assembly complies with any required fire protection rating, and, where rated, is self-closing or automatic-closing by means of smoke detection in accordance with 7.2.1.8 and is installed in accordance with NFPA 80. v. Corridor door assemblies required to be self-latching have a latch or other mechanism that ensures that the door leaf will not rebound into a partially open position if forcefully closed. (d) Where private garages, business areas, industrial areas, and storage areas with an occupant load not exceeding 10 contain only low- or ordinary-hazard contents, door openings to such areas and private garages shall be permitted to be horizontal-sliding door assemblies. (5) Where Vertical-rolling door assemblies shall be permitted in door openings to private garages, business areas, industrial areas, and storage areas with where such areas have an occupant load not exceeding 10 and contain only low or ordinary hazard contents. , door openings to such areas and private garages shall be permitted to be vertical-rolling door assemblies. (6) Revolving door assemblies complying with 7.2.1.10 shall be permitted. (7) Existing fusible-link-operated horizontal-sliding or vertical-rolling fire door assemblies shall be permitted to be used as provided in Chapters 39, 40, and 42.

Submitter Information Verification

Committee: SAF-MEA

Page 75 of 373

69 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Submittal Date: Tue Jun 11 16:59:51 EDT 2019

Committee Statement

Committee Editorial rewording for consistency in showing the door assembly description in the front part of Statement: each numbered section, and for ease of reading by the code user. (The only changes are in Items (3) and (5).) Response SR-6541-NFPA 101-2019 Message: Public Comment No. 122-NFPA 101-2019 [Section No. 7.2.1.4.1]

Ballot Results

This item has passed ballot

32 Eligible Voters 4 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Chan, Mark Di Pilla, Steven Perry, Robert R. Phelan, Kevin

Affirmative All Alles, Ryan Bales, Fred M. Barlow, Charles V. Bush, Kenneth E. Collins, David S. Coombs, Christopher Crowley, Michael A. Day, Richard L. Elvove, Joshua W. Farr, Ronald R. Frable, David W. Guest, Rita C. Hoskins, Bryan Lawrence Jackson, Waymon Koffel, William E. Larson, Mark Lujan, Cesar Marcyjanik, Brian A. Mueller, Marc Page 76 of 373

70 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Pappas, Denise L. Pauls, Jake Quinterno, Vincent Saks, Kenneth Shulman, Michael S. Simard, J. Francois Tilton, Kelly R. Versteeg, Joseph H. Woestman, John

Page 77 of 373

71 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6542-NFPA 101-2019 [ Section No. 7.2.1.5.3.8 ]

7.2.1.5.3.8 Where permitted by Chapters 11 through 43 , two releasing motions shall be permitted for doors secured against unwanted entry.

Submitter Information Verification

Committee: SAF-MEA Submittal Date: Tue Jun 11 17:36:40 EDT 2019

Committee Statement

Committee In response to PC-216, the committee maintains its position that door locks/latches should be Statement: limited to not more than one releasing motion. Response SR-6542-NFPA 101-2019 Message: Public Comment No. 216-NFPA 101-2019 [Section No. 7.2.1.5.3.8]

Ballot Results

This item has passed ballot

32 Eligible Voters 4 Not Returned 26 Affirmative All 0 Affirmative with Comments 2 Negative with Comments 0 Abstention

Not Returned Chan, Mark Di Pilla, Steven Perry, Robert R. Phelan, Kevin

Affirmative All Alles, Ryan Bales, Fred M. Barlow, Charles V. Collins, David S. Coombs, Christopher Crowley, Michael A. Day, Richard L. Elvove, Joshua W. Farr, Ronald R. Page 78 of 373

72 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Frable, David W. Guest, Rita C. Hoskins, Bryan Lawrence Jackson, Waymon Larson, Mark Lujan, Cesar Marcyjanik, Brian A. Mueller, Marc Pappas, Denise L. Pauls, Jake Quinterno, Vincent Saks, Kenneth Shulman, Michael S. Simard, J. Francois Tilton, Kelly R. Versteeg, Joseph H. Woestman, John

Negative with Comment Bush, Kenneth E. This paragraph requires revision to coordinate with the proposed changes to classroom doors in existing educational occupancies. Koffel, William E. The revision requires correlation with other provisions in the Code, specifically Educational Occupancy provisions, that allow for two means of operation.

Page 79 of 373

73 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6530-NFPA 101-2019 [ Section No. 7.2.1.5.6.2 ]

7.2.1.5.6.2* Exterior door assemblies and interior door assemblies to an individual tenant space or to a single tenant space shall be permitted to have key-operated locks from the egress side, provided that all of the following criteria are met: (1) This alternative is permitted in Chapters 11 through 43 for the specific occupancy. (2) Doors remain unlocked when the building or space is occupied. and indicated as such by a readily visible, durable sign in letters not less than 1 in. (25 mm) high on a contrasting background that reads as follows and is located on or adjacent to the door leaf: THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS OCCUPIED. (3) Doors are marked with a readily visible, durable sign in letters not less than 1 in. (25 mm) high on a contrasting background that reads as follows and is located on or adjacent to the door leaf: THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS OCCUPIED, or THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED, as applicable . (4) The locking device is of a type that is readily distinguishable as locked. (5) A key is immediately available to any occupant inside the building when it is locked.

Submitter Information Verification

Committee: SAF-MEA Submittal Date: Mon Jun 10 14:42:14 EDT 2019

Committee Statement

Committee New provisions allow key-operated locks in tenant spaces; signage needs to reflect either the Statement: space or the building is occupied. Response SR-6530-NFPA 101-2019 Message: Public Comment No. 22-NFPA 101-2019 [New Section after 7.2.1.5.6.2]

Ballot Results

This item has passed ballot

32 Eligible Voters 4 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Chan, Mark Di Pilla, Steven Perry, Robert R. Phelan, Kevin

Page 80 of 373

74 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Affirmative All Alles, Ryan Bales, Fred M. Barlow, Charles V. Bush, Kenneth E. Collins, David S. Coombs, Christopher Crowley, Michael A. Day, Richard L. Elvove, Joshua W. Farr, Ronald R. Frable, David W. Guest, Rita C. Hoskins, Bryan Lawrence Jackson, Waymon Koffel, William E. Larson, Mark Lujan, Cesar Marcyjanik, Brian A. Mueller, Marc Pappas, Denise L. Pauls, Jake Quinterno, Vincent Saks, Kenneth Shulman, Michael S. Simard, J. Francois Tilton, Kelly R. Versteeg, Joseph H. Woestman, John

Page 81 of 373

75 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6531-NFPA 101-2019 [ Section No. 7.2.1.7.2 ]

7.2.1.7.2 Where panic or fire exit hardware is installed on a balanced door assembly or pivoted-swinging door assembly , the panic or fire exit hardware shall be of the push-pad type, and the pad shall extend approximately one-half the width of the door leaf, measured from the latch stile.

Submitter Information Verification

Committee: SAF-MEA Submittal Date: Mon Jun 10 14:51:42 EDT 2019

Committee Statement

Committee The revision responds to PC-24 and coordinates 7.2.1.7.1 and 7.2.1.7.2 as suggested by Statement: the correlating committee. Response SR-6531-NFPA 101-2019 Message: Public Comment No. 24-NFPA 101-2019 [New Section after 7.2.1.7.2]

Ballot Results

This item has passed ballot

32 Eligible Voters 4 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Chan, Mark Di Pilla, Steven Perry, Robert R. Phelan, Kevin

Affirmative All Alles, Ryan Bales, Fred M. Barlow, Charles V. Bush, Kenneth E. Collins, David S. Coombs, Christopher Crowley, Michael A. Day, Richard L.

Page 82 of 373

76 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Elvove, Joshua W. Farr, Ronald R. Frable, David W. Guest, Rita C. Hoskins, Bryan Lawrence Jackson, Waymon Koffel, William E. Larson, Mark Lujan, Cesar Marcyjanik, Brian A. Mueller, Marc Pappas, Denise L. Pauls, Jake Quinterno, Vincent Saks, Kenneth Shulman, Michael S. Simard, J. Francois Tilton, Kelly R. Versteeg, Joseph H. Woestman, John

Page 83 of 373

77 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6540-NFPA 101-2019 [ New Section after 7.2.1.14 ]

7.2.1.15* Inspection of Grille Assemblies.

A.7.2.1.15

The provisions of 7.2.1.15 addressing the inspection of grille assemblies are not intended to override the requirements of 7.2.1.4.1 (3).

7.2.1.15.1 Where required by Chapters 11 through 43 , grille assemblies shall be inspected and tested not less than annually in accordance with 7.2.1.15.2 through 7.2.1.15.6 . 7.2.1.15.2 A record of all inspections and testing shall be signed by the inspector and kept for inspection by the authority having jurisdiction. Records of acceptance tests shall be retained for the life of the assembly. 7.2.1.15.3 Functional testing of grille assemblies shall be performed by individuals who can demonstrate knowledge and understanding of the operating components of the type of grille being subjected to testing. 7.2.1.15.4 Grille assemblies shall be visually inspected from both sides of the opening to assess the overall condition of the assembly. 7.2.1.15.5 As a minimum, the following items shall be verified: (1) Floor space on both sides of the openings is clear of obstructions, and the grille assembly opens fully and closes freely. (2) Forces required to set the grille assembly in motion and move to the fully open position do not exceed the requirements of 7.2.1.4.5 . (3) Latching and locking devices comply with 7.2.1.5 . (4) Releasing hardware devices are installed in accordance with 7.2.1.5.3.1 . (5) Grille assemblies are adjusted properly to control the closing speed of grilles in accordance with accessibility requirements. (6) Powered grille assemblies operate in accordance with 7.2.1.9 . (7) Signage required by 7.2.1.4.1 (3), 7.2.1.5.5 , 7.2.1.6 , and 7.2.1.9 is intact and legible. (8) Grille assemblies with special locking arrangements function in accordance with 7.2.1.6 . (9) Security devices that impede egress are not installed on openings as required by 7.2.1.5.10 . (10) Where required by 7.2.2.5.5.7 , grille hardware marking is present and intact. (11) Emergency lighting on grille assemblies equipped with delayed-egress locking systems is present and functioning in accordance with Section 7.9 . 7.2.1.15.6 Grille assemblies not in proper operating condition shall be repaired or replaced without delay.

Submitter Information Verification

Committee: SAF-MEA Submittal Date: Tue Jun 11 16:25:33 EDT 2019

Page 84 of 373

78 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Committee Statement

Committee The revision accepts PC-124 as modified by expanding the application to all grille assemblies Statement: where required by Chapters 11 through 43 and by adding A.7.2.1.15 to clarify the inspection provisions do not supersede the requirements that limit the application of grilles in 7.2.1.4.1(3). Response SR-6540-NFPA 101-2019 Message: Public Comment No. 124-NFPA 101-2019 [New Section after 7.2.1] Public Comment No. 125-NFPA 101-2019 [New Section after A.7.2.1.2.1]

Ballot Results

This item has passed ballot

32 Eligible Voters 4 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Chan, Mark Di Pilla, Steven Perry, Robert R. Phelan, Kevin

Affirmative All Alles, Ryan Bales, Fred M. Barlow, Charles V. Bush, Kenneth E. Collins, David S. Coombs, Christopher Crowley, Michael A. Day, Richard L. Elvove, Joshua W. Farr, Ronald R. Frable, David W. Guest, Rita C. Hoskins, Bryan Lawrence Jackson, Waymon Koffel, William E. Larson, Mark Lujan, Cesar Marcyjanik, Brian A. Mueller, Marc

Page 85 of 373

79 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Pappas, Denise L. Pauls, Jake Quinterno, Vincent Saks, Kenneth Shulman, Michael S. Simard, J. Francois Tilton, Kelly R. Versteeg, Joseph H. Woestman, John

Page 86 of 373

80 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6529-NFPA 101-2019 [ Section No. 7.2.13.2.2 ]

7.2.13.2.2 The elevator lobby shall have a minimum clear floor area capacity of not less than 50 percent of the occupant load of the area served by the lobby. The capacity of clear floor area shall be calculated based on 3 ft 2 (0.28 m 2 ) per person and shall also include one wheelchair space of 30 in. × 48 in. (760 mm × 1220 mm) for every 50 persons, or portion thereof, of the total occupant load served by that lobby. as follows:

(1) The elevator lobby clear floor area shall accommodate, at 3 ft 2 (0.28 m 2 ) per person, at least 50 percent of the occupant load of the floor area served by the lobby.

(2) The capacity of elevator lobby clear floor area shall be calculated based on 3 ft 2 (0.28 m 2 ) per person and shall also include accommodate one wheelchair space of 30 in. × 48 in. (760 mm × 1220 mm) for every each 50 persons, or portion thereof, of the total occupant load of the floor area served by that the lobby.

Supplemental Information

File Name Description Approved 101_SR-6529.docx SR-6529 clean (Terra not displaying correctly) For staff use

Submitter Information Verification

Committee: SAF-MEA Submittal Date: Mon Jun 10 09:43:05 EDT 2019

Committee Statement

Committee Statement: The revision responds to PC-26 (CN-10). Response Message: SR-6529-NFPA 101-2019

Ballot Results

This item has passed ballot

32 Eligible Voters 4 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Chan, Mark Di Pilla, Steven Perry, Robert R. Phelan, Kevin

Affirmative All Page 87 of 373

81 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Alles, Ryan Bales, Fred M. Barlow, Charles V. Bush, Kenneth E. Collins, David S. Coombs, Christopher Crowley, Michael A. Day, Richard L. Elvove, Joshua W. Farr, Ronald R. Frable, David W. Guest, Rita C. Hoskins, Bryan Lawrence Jackson, Waymon Koffel, William E. Larson, Mark Lujan, Cesar Marcyjanik, Brian A. Mueller, Marc Pappas, Denise L. Pauls, Jake Quinterno, Vincent Saks, Kenneth Shulman, Michael S. Simard, J. Francois Tilton, Kelly R. Versteeg, Joseph H. Woestman, John

Page 88 of 373

82 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6567-NFPA 101-2019 [ Section No. 7.7.2 ]

7.7.2 Exit Discharge Through Interior Building Areas.

Page 89 of 373

83 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Exits shall be permitted to discharge through interior building areas, provided that all of the following are met: (1) Not more than 50 percent of the required number of exit stairs serving normally occupied areas of each floor, and not more than 50 percent of the exit stair capacity required for normally occupied areas of each floor, shall discharge through areas on any level of discharge, except as otherwise permitted by one of the following: (a) One hundred percent of the exits shall be permitted to discharge through areas on any level of discharge in detention and correctional occupancies as otherwise provided in Chapters 22 and 23. (b) In existing buildings, the 50 percent limit on egress capacity shall not apply if the 50 percent limit on the required number of exits is met. (2) Each level of discharge shall discharge directly outside at the finished ground level or discharge directly outside and provide access to the finished ground level by outside stairs or outside ramps. (3) The interior exit discharge shall lead to a free and unobstructed way to the exterior of the building, and such way shall be readily apparent or shall be identifiable by exit signage from the point of discharge from the exit. (4) The interior exit discharge shall be protected by one of the following methods: (a) The level of discharge shall be protected throughout by an approved automatic sprinkler system in accordance with Section 9.7, or the portion of the level of discharge used for interior exit discharge shall be protected by an approved automatic sprinkler system in accordance with Section 9.7 and shall be separated from the nonsprinklered portion of the floor by fire barriers with a fire resistance rating meeting the requirements for the enclosure of exits. (See 7.1.3.2.1.) (b) The interior exit discharge area shall be in a vestibule or foyer that meets all of the following criteria: i. The depth from the exterior of the building shall be not more than 10 ft (3050 mm), and the length shall be not more than 30 ft (9.1 m). ii. The foyer shall be separated from the remainder of the level of discharge by fire barriers with a minimum 1-hour fire resistance rating, and existing installations of wired glass in steel frames shall be permitted to be continued in use. iii. The foyer shall serve only as means of egress and shall include an exit directly to the outside. Where 7.7.2 (2) is applied, one of the following shall be permitted: The interior exit discharge shall lead to a free and unobstructed way to the exterior of the building, and such way shall be readily apparent or shall be identifiable by exit signage from the point of discharge from the exit. Up to 75 percent of the exits shall be permitted to discharge through areas on any level of discharge provided the interior exit discharge area is located in a vestibule or foyer that meets all of the following criteria: The depth from the exterior of the building shall be not more than 10 ft (3050 mm), and the length shall be not more than 30 ft (9.1 m). The foyer shall be separated from the remainder of the level of discharge by fire barriers with a minimum 1-hour fire resistance rating, and existing installations of wired glass in steel frames shall be permitted to be continued in use.

Each level of discharge shall discharge directly outside at the finished ground level or discharge directly outside and provide access to the finished ground level by outside stairs or outside ramps. (5) The entire area on the level of discharge shall be separated from areas below by construction having a fire resistance rating not less than that required for the exit enclosure, unless otherwise provided in 7.7.2(6). (6) Levels below the level of discharge in an atrium shall be permitted to be open to the level of discharge where such level of discharge is protected in accordance with 8.6.7.

Page 90 of 373

84 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

A.7.7.2

It does not matter where exits that discharge into interior building areas are located provided that the arrangement of means of egress requirements of Section 7.5 , the travel distance requirements of Section 7.6 , and the requirements of 7.7.2 (1) are met.

Submitter Information Verification

Committee: SAF-MEA Submittal Date: Fri Jun 14 09:58:12 EDT 2019

Committee Statement

Committee Statement: The revision responds to PC-29 (CN-13) and returns 7.7.2 to the previous edition text. Response Message: SR-6567-NFPA 101-2019 Public Comment No. 29-NFPA 101-2019 [New Section after 7.7.2]

Ballot Results

This item has passed ballot

32 Eligible Voters 4 Not Returned 27 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Chan, Mark Di Pilla, Steven Perry, Robert R. Phelan, Kevin

Affirmative All Alles, Ryan Bales, Fred M. Barlow, Charles V. Bush, Kenneth E. Collins, David S. Coombs, Christopher Crowley, Michael A. Day, Richard L. Farr, Ronald R. Frable, David W. Guest, Rita C. Hoskins, Bryan Lawrence

Page 91 of 373

85 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Jackson, Waymon Koffel, William E. Larson, Mark Lujan, Cesar Marcyjanik, Brian A. Mueller, Marc Pappas, Denise L. Pauls, Jake Quinterno, Vincent Saks, Kenneth Shulman, Michael S. Simard, J. Francois Tilton, Kelly R. Versteeg, Joseph H. Woestman, John

Affirmative with Comment Elvove, Joshua W. The MEA Committee needed to take an action to address the Correlating Committee's concern about the language that was accepted by FR 6557 regarding revisions to exit discharge through the building interior that may have been problematic, however, there was text proposed during the second draft meeting that addressed the Correlating Committee's concern. Unfortunately, it was rejected, hence, it's best that text return to the previous edition. However, the MEA Committee should revisit this issue again next cycle as there are alternative arrangements that provide equivalent, if not safer egress options to the current interior exit discharge provisions of 7.7.2.

Page 92 of 373

86 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6539-NFPA 101-2019 [ Section No. 7.10.2 ]

7.10.2* Directional Signs.

A.7.10.2

Directional signage that has the capability to change the displayed information based on real-time conditions presents a series of tradeoffs. The potential benefit of a changing message sign would be to deter occupants from a direction of travel that might be blocked or otherwise unavailable due to adverse conditions such as fire, structural collapse, or other unsafe conditions that might warrant avoidance. However, the potential problems of such a “solution” include the reliability and likely partial level of the information available; the decision-making ability of the individual (if human) or algorithm (if machine) responsible for changing the sign’s message; the capacity and condition of the remaining egress paths; the training and habitual behavior of some building occupants who might not detect the change or might choose to ignore the sign’s information and thus create conflicting movement patterns; the increased probability of sign failure or malfunction due to its enhanced electronics; and the uncertainty for liability if the sign’s change of information leads to injuries or other adverse impacts that otherwise might have been avoided. Directional signs for egress are used at all times of building occupancy. Only a very small percentage of building evacuations would likely benefit from this sign information enhancement. It is also likely that an unavailable egress path will make itself known through other means (such as smoke or other occupants moving away from it), although this might not provide as much advance notice to some occupants approaching from a distance. The product standard for listing exit signs, UL 924, Emergency Lighting and Power Equipment, referenced by 7.10.7.1 , does not currently permit this feature; it requires (clause 41.7c) that a directional indicator be “…secured in a manner that cannot readily be changed.” This requirement deters changes to the building evacuation plan after approval by the authority having jurisdiction. A system that can change based on changing conditions modifies the role of the authority having jurisdiction by inserting a new intermediary responsible for providing occupant egress information.

7.10.2.1 A sign complying with 7.10.3, with a directional indicator showing the direction of travel, shall be placed in every location where the direction of travel to reach the nearest exit is not apparent. 7.10.2.2 Directional exit signs shall be provided within horizontal components of the egress path within exit enclosures as required by 7.10.1.2.2.

Submitter Information Verification

Committee: SAF-MEA Submittal Date: Tue Jun 11 14:55:39 EDT 2019

Committee Statement

Committee Technological advances in sensors, controls, and artificial intelligence algorithms are being designed Statement: into emergency lighting systems to allow them to adjust to changing building circumstances. But neither the Codes nor the product standards have regulations for evaluating the actual efficacy and reliability of these “solutions”. The situation is somewhat analogous to the use of GPS wayfinding systems for changing driving routes due to traffic congestion. But in this circumstance, the data set used for making decisions must be customized to the individual building (where are the sensors to be located and what conditions do they detect?) and the consequences for errors may be more severe than arriving late to an appointment. Some systems may involve humans in a central control area monitoring video cameras and making decisions, while other systems may be fully automated and utilize artificial intelligence algorithms to calculate optimized evacuation strategies. Both approaches, and any combination, has both potential benefits and pitfalls. This proposal for an Annex note is to Page 93 of 373

87 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

stimulate discussion and the development of regulations that respond to this new deployment of advanced technology. Response SR-6539-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

32 Eligible Voters 4 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Chan, Mark Di Pilla, Steven Perry, Robert R. Phelan, Kevin

Affirmative All Alles, Ryan Bales, Fred M. Barlow, Charles V. Bush, Kenneth E. Collins, David S. Coombs, Christopher Crowley, Michael A. Day, Richard L. Elvove, Joshua W. Farr, Ronald R. Frable, David W. Guest, Rita C. Hoskins, Bryan Lawrence Jackson, Waymon Koffel, William E. Larson, Mark Lujan, Cesar Marcyjanik, Brian A. Mueller, Marc Pappas, Denise L. Pauls, Jake Quinterno, Vincent Saks, Kenneth

Page 94 of 373

88 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Shulman, Michael S. Simard, J. Francois Tilton, Kelly R. Versteeg, Joseph H. Woestman, John

Page 95 of 373

89 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6566-NFPA 101-2019 [ Section No. 7.10.9 ]

7.10.9 Testing and Maintenance. Exit signs connected to, or provided with, a battery-operated emergency illumination source, where required in 7.10.4, shall be tested and maintained in accordance with 7.9.3. 7.10.9.1 Inspection. Exit signs shall be visually inspected for operation of the illumination sources at intervals not to exceed 30 days or shall be periodically monitored in accordance with 7.9.3.1.3 . 7.10.9.2 Testing. Exit signs connected to, or provided with, a battery-operated emergency illumination source, where required in 7.10.4 , shall be tested and maintained in accordance with 7.9.3 .

Submitter Information Verification

Committee: SAF-MEA Submittal Date: Fri Jun 14 09:49:08 EDT 2019

Committee Statement

Committee Some are interpreting 7.10.9.1 to inspect the illumination source of all exit signs every thirty days Statement: even when they are not battery operated or when they are externally illuminated. There is no reason to inspect an exit sign for the illumination source unless the exit sign is battery operated and that inspection for a battery operated exit sign is already required under 7.10.9.2. There are provisions in the code (4.6.12) that require building owners to fix/repair/replace the illumination source of exit signs when the required illumination source is broken, but there is no reason to require an owner to inventory 1000s of exit signs and inspect them for the illumination source every 30 days. This is an unnecessary burden especially since many facilities are using LED light sources for exit signs which last a very long time.

The American Society for Health Care Engineering did a study to determine the failure rate of exit signs. This study surveyed 86 health care facilities in regards to exit sign inspections over a one-year period with a specific request for the variations between LED and non-LED exit signs. Eighty-six respondents performed an average of 3,545 yearly LED exit sign inspections along with an average of 2,860 Non-LED exit sign inspections. With an average per year LED failure of 1.29 signs and Non- LED of 10 signs the study concluded that the failure rate of LED exit signs was 0.0004% (1.29/(3,545*86))and for non-LED exit signs the failure rate was 0.004% (10/(2860*86)).

This study indicates that the technological advancements of these devices using LED signs has reduced the failure rate of exit signs from 0.004% to 0.0004%. However, if 99.996% of all exit signs, even those that are not LED signs, pass this inspection, clearly a routine inspection is not warranted and this requirements should be deleted. Even if an exit sign illumination source is not working, there is a very good chance that an occupant will still be able to see the sign due to the illumination from the lighting that is required in the means of egress so having one or two nonworking signs will have almost no affect on the occupants of a building.

Note that battery operated exit signs will still be tested and inspected on a 30 day interval as required by 7.9.3, even if 7.10.9.1 is deleted.

See ASHE study below:

Exit Sign Inspection & Burden Survey:

Pt 1: Quantitative Data: (n = 86)

Testing Cost Analysis. Eighty-six surveyed campuses reported a median of 154 (Mean = 310, SD = 397.42, Range 0 – 2,100) operational LED exit signs, and a median of 2 operational NON-LED exit

Page 96 of 373

90 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

signs (Mean = 88.60, SD = 202.76; Range = 0 - 1200). These reports represent a significant skew, particularly with NON-LED exit signs, as approximately half of the respondents surveyed stated that their facility did not have any Non-LED signs. In addition, respondents reported a median of 1,782 LED light inspections (Mean = 3545.46, SD = 4710.66, Range = 0 – 25,200), and a median of 90 Non- LED exit light inspections across the year (Mean = 2859.60, SD = 11940.35, Range = 0 -80,808).

On average, staff spent a median of approximately 49 hours (Mean = 246.38, SD = 809.5, Range 0 - 6912 with extreme scores) per year conducting exit sign inspections. Furthermore, the individuals conducting these inspections were paid a median wage of $22 an hour (Mean = $27.07, SD = 23.99, Range $0 - $208 hourly rate); which translates to approximately $1326.43 in staffing costs per year.

All respondents conducted monthly exit sign inspections internally; none of them reported having costs related to an independent contractor. Furthermore, roughly three-quarters of the sample (73.3%) reported that they participated in a Zone or Maintenance program.

Testing & Failure Rate Comparisons. The median number of failures for the past year for LED exit signs was 0 (Mean = 1.29, SD = 3.219, Range = 0 – 20) and non-LED exit signs was 10 (average = 0, SD = 68.68, Range = 0 – 600). Alternatively explained, approximately 51% of Non-LED exit sign inspections had zero failures, and three quarters had less than 1 or 2 failures per year (for both Non- LED ad LED Exit signs). All of these analyses indicate an extremely low failure rate across the entire sample; especially when a couple extreme data points are removed from the analysis5.

Between Variable Relationships. Two-tailed bivariate correlations were conducted, yet no statistically significant relationships were found. Number of inspection failures was not related to number of exit signs tested for either type of exit sign. Number of exit sign inspections were also found not to be related to staffing hours or total staffing costs, or whether or not a facility participated in a Zoning Program. This findings may potentially illustrate that there may be external factors that play a much larger role in exit sign failures.

Pt 2 - Qualitative Data Analysis: (n = 40)

Forty respondents included open-ended comments in their Exit Sign Inspection surveys. Of these comments, 31 voiced concrete support for changing current monthly testing standards; and of these, 16 respondents even suggested specific time frames for testing; such as every two-months (n = 2), quarterly (n = 3), and semi-annually (n = 3). However, most individuals supported an annual testing time frame for exit signs (n = 7), or even biannual testing (n = 2). Conversely, only one respondent voiced support for current monthly inspection timeframes. Furthermore, several themes came through in the open-ended commentary: the explanation that separate and specific exit sign inspections were a waste of resources, no longer applicable with the newer, more advanced LED technologies, no longer applicable because signs are connected to emergency power. Some respondents also used the space to advocate for a more risk-based inspection approach. Comments of interest included: “Required monthly inspections are ridiculous. We instinctively react to any failed exit sign through years and years of security awareness,” “With the new LEDs it’s almost not necessary to test them. They are either working or are off if not working,” “…we did this 25 years ago when we had incandescent bulbs, the only failure we have now is when someone hits a light with a cart. NOT a good use of our resources,” “staffing levels will not be adjusted for the increase in work due to non- effective regulations. It would be more cost effective to force everyone to change their fixtures to LED,” “All but 15 of our signs are connected to E-power. The 15 are battery back-up in ORs and other mechanical spaces.” Response SR-6566-NFPA 101-2019 Message:

Public Comment No. 128-NFPA 101-2019 [Section No. 7.10.9]

Ballot Results

This item has passed ballot

32 Eligible Voters 4 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Page 97 of 373

91 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Not Returned Chan, Mark Di Pilla, Steven Perry, Robert R. Phelan, Kevin

Affirmative All Alles, Ryan Bales, Fred M. Barlow, Charles V. Bush, Kenneth E. Collins, David S. Coombs, Christopher Crowley, Michael A. Day, Richard L. Elvove, Joshua W. Farr, Ronald R. Frable, David W. Guest, Rita C. Hoskins, Bryan Lawrence Jackson, Waymon Koffel, William E. Larson, Mark Lujan, Cesar Marcyjanik, Brian A. Mueller, Marc Pappas, Denise L. Pauls, Jake Quinterno, Vincent Saks, Kenneth Shulman, Michael S. Simard, J. Francois Tilton, Kelly R. Versteeg, Joseph H. Woestman, John

Page 98 of 373

92 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6568-NFPA 101-2019 [ Section No. 7.16 ]

7.16* Emergency Stair Travel Devices. Where newly installed emergency stair travel devices are provided, they shall comply with ANSI/RESNA ED-1, Emergency Stair Travel Devices Used by Individuals with Disabilities.

A.7.16

Devices that comply with ANSI/RESNA ED-1, Emergency Stair Travel Devices Used by Individuals with Disabilities , have been evaluated and are intended for use on stairs that comply with Table 7.2.2.2.1.1(a) that are not steeper than 32.5 degrees [maximum 7 in. (180 mm) riser height, minimum 11 in. (280 mm) tread depth]. Such devices have not been evaluated for use on steeper, older stairs that comply with Table 7.2.2.2.1.1(b) and are not steeper than 41.6 degrees [maximum 8 in. (205 mm) riser height, minimum 9 in. (230 mm) tread depth]. Where the building has stairs that are steeper than 32.5 degrees, the device manufacturer should be consulted.

Submitter Information Verification

Committee: SAF-MEA Submittal Date: Fri Jun 14 10:06:30 EDT 2019

Committee Statement

Committee The revision responds to PC-115 and PC-30 (CN-14) by limiting the application of the RESNA Statement: standard to newly installed devices. Annex A language has been added to provide guidance on the use of devices on stairs that are steeper than those for which they have been tested in accordance with the standard. Response SR-6568-NFPA 101-2019 Message: Public Comment No. 115-NFPA 101-2019 [Section No. 7.16] Public Comment No. 30-NFPA 101-2019 [New Section after 7.16]

Ballot Results

This item has passed ballot

32 Eligible Voters 4 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Chan, Mark Di Pilla, Steven Perry, Robert R. Phelan, Kevin

Page 99 of 373

93 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Affirmative All Alles, Ryan Bales, Fred M. Barlow, Charles V. Bush, Kenneth E. Collins, David S. Coombs, Christopher Crowley, Michael A. Day, Richard L. Elvove, Joshua W. Farr, Ronald R. Frable, David W. Guest, Rita C. Hoskins, Bryan Lawrence Jackson, Waymon Koffel, William E. Larson, Mark Lujan, Cesar Marcyjanik, Brian A. Mueller, Marc Pappas, Denise L. Pauls, Jake Quinterno, Vincent Saks, Kenneth Shulman, Michael S. Simard, J. Francois Tilton, Kelly R. Versteeg, Joseph H. Woestman, John

Page 100 of 373

94 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6554-NFPA 101-2019 [ Section No. 8.2.4 ]

8.2.4* Analytical Methods.

A.8.2.4

Performance-based design methods using design fires other than those specified in ASTM E119, Standard Test Methods for Fire Tests of Building Construction and Materials , or UL 263, Fire Tests of Building Construction and Materials , are permitted to be used when approved by the authority having jurisdiction. Methodologies such as Appendix E (“Performance-Based Design Procedures for Fire Effects on Structures”) of ASCE/SEI 7-16, Minimum Design Loads for Buildings and Other Structures , provide a structured framework for conducting such analyses. Additional tools include SFPE S.01, Standard on Calculating Fire Exposures to Structures , which provides a methodology on how to estimate the thermal exposure to a structure from a resulting fire and SFPE S.02, Engineering Standard on Calculation Methods to Predict the Thermal Performance of Structural and Fire Resistive Assemblies , which provides a methodology on how to determine the temperature history with a structure. Other alternative methods based upon sound engineering principles can also be considered as appropriate for the structure based upon more severe design conditions.

8.2.4.1 Analytical methods utilized to determine the fire resistance rating of building assemblies shall comply with 8.2.4.2 through 8.2.4.5. 8.2.4.2* Where calculations are used to establish the fire resistance rating of structural elements or assemblies, they shall be permitted to be performed in accordance with ASCE/SEI/SFPE 29, Standard Calculation Methods for Structural Fire Protection. 8.2.4.3 Where calculations are used to establish the fire resistance rating of concrete or masonry elements or assemblies, the provisions of ACI 216.1/TMS 0216.1, Code Requirements for Determining Fire Resistance of Concrete and Masonry Construction Assemblies, shall be permitted to be used. 8.2.4.4 Except for the methods specified in 8.2.4.2 and 8.2.4.3, analytical methods used to calculate the fire resistance of building assemblies or structural elements shall be approved. 8.2.4.5 Where an approved analytical method is utilized to establish the fire resistance rating of a structural element or building assembly, the calculations shall be based upon the fire exposure and acceptance criteria specified in ASTM E119, Standard Test Methods for Fire Tests of Building Construction and Materials, or UL 263, Fire Tests of Building Construction and Materials.

Submitter Information Verification

Committee: SAF-FIR Submittal Date: Thu Jun 13 14:01:26 EDT 2019

Committee Statement

Committee This was added to correlate with NFPA 5000 SR-8050. Statement: NFPA 5000 SR-8050 Substantiation: This annex noted was added in response to PI-256 to incorporate references relevant for performance-based design of fire-resistance rated construction. Page 101 of 373

95 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Response SR-6554-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

26 Eligible Voters 5 Not Returned 20 Affirmative All 0 Affirmative with Comments 1 Negative with Comments 0 Abstention

Not Returned Gould, Jennifer Klein Hall, William J. Jones, Adam C. Richardson, Dennis A. Shino, Gregory K.

Affirmative All Alday, Eddie Dewayne Cahanin, Gregory J. Cook, David Dawe, Nicholas A. Devlin, John F. Dudley, Jeffry T. Goldhammer, Edward S. Graupmann, Joseph Gump, Jack A. Higgins, Joseph Patrick Hopper, Howard Hugo, Jeffrey M. Jackson, Waymon Koffel, William E. McHugh, Jr., William J. Morris, Jeramie W. Roeper, Kurt A. Stashak, Catherine L. Wittasek, Nathan B. Zivnuska, Alexander Frederick

Negative with Comment Humble, Jonathan I am opposed to the last sentence of the ballot item which states: “Other alternative methods based upon sound

Page 102 of 373

96 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

engineering principals can also be considered as appropriate for the structure based upon more severe design conditions.” The last words “based upon more severe design conditions” indicates that as part of this annex that if a real design conditions are found to be less severe that there is no alternative option. This also appears to suggest (i.e. appearance issue) that the AHJ has no say in the matter, even though Chapter 1 Administration does permit that ruling. Further, while this is annex material that is assumed to represent commentary designed to provide guidance we need to be cognizant of unintended consequences with the language. Engineers or consultants executing performance based design analysis should be free to exercise professional judgment on this subject. My compromise to the FIR would be to delete the language “based upon more severe design conditions” after the word “structure”.

Page 103 of 373

97 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6555-NFPA 101-2019 [ Section No. 8.3.3.3.1 ]

8.3.3.3.1* Fire Required fire door assemblies shall be installed, inspected, tested, and maintained in accordance with NFPA 80.

A.8.3.3.3.1

Where a door or door frame is not required to be fire protection rated and is equipped with a fire protection listing label, the door and the door frame is not required to comply with NFPA 80 .

Submitter Information Verification

Committee: SAF-FIR Submittal Date: Thu Jun 13 14:50:44 EDT 2019

Committee Statement

Committee This change is to correlate with FR-6644. Incorporating the language into the annex provides Statement: clarity as to the code requirements and is in a more appropriate section of the code. Response SR-6555-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

26 Eligible Voters 5 Not Returned 21 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Gould, Jennifer Klein Hall, William J. Jones, Adam C. Richardson, Dennis A. Shino, Gregory K.

Affirmative All Alday, Eddie Dewayne Cahanin, Gregory J. Cook, David Dawe, Nicholas A.

Page 104 of 373

98 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Devlin, John F. Dudley, Jeffry T. Goldhammer, Edward S. Graupmann, Joseph Gump, Jack A. Higgins, Joseph Patrick Hopper, Howard Hugo, Jeffrey M. Humble, Jonathan Jackson, Waymon Koffel, William E. McHugh, Jr., William J. Morris, Jeramie W. Roeper, Kurt A. Stashak, Catherine L. Wittasek, Nathan B. Zivnuska, Alexander Frederick

Page 105 of 373

99 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6546-NFPA 101-2019 [ Section No. 8.3.3.6.10 ]

8.3.3.6.10 The total combined area of fire protection glazing in fire-rated window assemblies and fire-rated door assemblies used in fire barriers shall not exceed 25 percent of the area of the fire barrier that is common with any room, unless the installation is an existing fire window installation of wired glass and or other fire rated protection glazing materials in approved frames. meets one of the following criteria: The installation is an existing fire window installation of wired glass and other fire-rated glazing materials in approved frames. The fire-protection glazing material is installed in approved existing frames.

Submitter Information Verification

Committee: SAF-FIR Submittal Date: Thu Jun 13 09:00:53 EDT 2019

Committee Statement

Committee Statement: This provides clarification to the requirements for fire window assemblies. Response Message: SR-6546-NFPA 101-2019

Ballot Results

This item has passed ballot

26 Eligible Voters 5 Not Returned 21 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Gould, Jennifer Klein Hall, William J. Jones, Adam C. Richardson, Dennis A. Shino, Gregory K.

Affirmative All Alday, Eddie Dewayne Cahanin, Gregory J. Cook, David Dawe, Nicholas A. Devlin, John F. Dudley, Jeffry T. Page 106 of 373

100 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Goldhammer, Edward S. Graupmann, Joseph Gump, Jack A. Higgins, Joseph Patrick Hopper, Howard Hugo, Jeffrey M. Humble, Jonathan Jackson, Waymon Koffel, William E. McHugh, Jr., William J. Morris, Jeramie W. Roeper, Kurt A. Stashak, Catherine L. Wittasek, Nathan B. Zivnuska, Alexander Frederick

Page 107 of 373

101 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6547-NFPA 101-2019 [ Section No. 8.3.3.6.11 ]

8.3.3.6.11

1 In other than existing, previously approved installations, Existing installations of wired glass of ⁄4 in. (6.3 mm) thickness and labeled previously approved for fire protection purposes shall be permitted to be used in approved opening protectives, provided that the maximum size specified by the listing is not exceeded remain in use .

Submitter Information Verification

Committee: SAF-FIR Submittal Date: Thu Jun 13 09:12:27 EDT 2019

Committee Statement

Committee We reviewed the negative ballot and have revised accordingly. Statement: Consider the negative vote of Hopper on FR-6608. The revision appears to achieve the opposite of what is intended.

NOTE: This Public Comment appeared as CC Note No. 16 in the First Draft Report on First Revision No. 6608. Response SR-6547-NFPA 101-2019 Message: Public Comment No. 32-NFPA 101-2019 [Section No. 8.3.3.6.11]

Ballot Results

This item has passed ballot

26 Eligible Voters 5 Not Returned 21 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Gould, Jennifer Klein Hall, William J. Jones, Adam C. Richardson, Dennis A. Shino, Gregory K.

Affirmative All Alday, Eddie Dewayne Cahanin, Gregory J. Page 108 of 373

102 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Cook, David Dawe, Nicholas A. Devlin, John F. Dudley, Jeffry T. Goldhammer, Edward S. Graupmann, Joseph Gump, Jack A. Higgins, Joseph Patrick Hopper, Howard Hugo, Jeffrey M. Humble, Jonathan Jackson, Waymon Koffel, William E. McHugh, Jr., William J. Morris, Jeramie W. Roeper, Kurt A. Stashak, Catherine L. Wittasek, Nathan B. Zivnuska, Alexander Frederick

Page 109 of 373

103 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6552-NFPA 101-2019 [ Section No. 8.6.5 ]

8.6.5* Required Fire Resistance Rating. The minimum fire resistance rating for the enclosure of floor openings shall be not less than as follows: (see 7.1.3.2.1 for enclosure of exits): (1) Enclosures connecting four or more stories in new construction — shall be 2-hour fire barriers. (2) Other enclosures in new construction — shall be 1-hour fire barriers, but not less than the required fire resistance rating of the floor penetrated, and shall not be required to exceed 2 hours.

1 (3) Existing enclosures in existing buildings — shall be ⁄2-hour fire barriers. (4) Enclosures for lodging and rooming houses — as specified in Chapter 26. (5) Enclosures for new hotels — shall be as specified in Chapter 28. (6) Enclosures for new apartment buildings — shall be as specified in Chapter 30. (7) Enclosures for exits shall be in accordance within 7.1.3.2.1 .

Submitter Information Verification

Committee: SAF-FIR Submittal Date: Thu Jun 13 11:13:18 EDT 2019

Committee Statement

Committee Statement: This text was added for correlation with NFPA 5000, 8.12.1.5. Response Message: SR-6552-NFPA 101-2019

Ballot Results

This item has passed ballot

26 Eligible Voters 5 Not Returned 19 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Gould, Jennifer Klein Hall, William J. Jones, Adam C. Richardson, Dennis A. Shino, Gregory K.

Affirmative All Alday, Eddie Dewayne Cahanin, Gregory J.

Page 110 of 373

104 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Cook, David Dawe, Nicholas A. Devlin, John F. Dudley, Jeffry T. Goldhammer, Edward S. Graupmann, Joseph Gump, Jack A. Higgins, Joseph Patrick Hugo, Jeffrey M. Humble, Jonathan Jackson, Waymon McHugh, Jr., William J. Morris, Jeramie W. Roeper, Kurt A. Stashak, Catherine L. Wittasek, Nathan B. Zivnuska, Alexander Frederick

Affirmative with Comment Hopper, Howard Item (4) in 8.6.5 is the only numbered item without "shall be" in the language, and for consistency should editorially be revised to read "(4) Enclosures for lodging and rooming houses shall be as specified in Chapter 26." Koffel, William E. In response to Howard Hopper's ballot comment, the Correlating Committee should either insert the language as recommended in the ballot comment or delete "shall be" from some of the other items. Several of these items (5 and 6) are a relaxation from the base requirements. As such, one could comply with items 1 or 2, as appropriate, and that would be fine.

Page 111 of 373

105 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6548-NFPA 101-2019 [ Section No. 8.6.7 ]

8.6.7* Atriums. Unless prohibited by Chapters 11 through 43, an atrium shall be permitted, provided that all of the following conditions are met: (1) The atrium is separated from the adjacent spaces by fire barriers with not less than a 1-hour fire resistance rating, with opening protectives for corridor walls, unless one of the following is met: (a) The requirement of 8.6.7(1) shall not apply to existing, previously approved atriums. (b) Any number of levels of the building shall be permitted to open directly to the atrium without enclosure, based on the results of the engineering analysis required in 8.6.7(5). (c)* Glass walls and inoperable windows shall be permitted in lieu of the fire barriers where all the following are met: i. Automatic sprinklers are spaced along both sides of the glass wall and the inoperable windows at intervals not to exceed 6 ft (1830 mm). ii. The automatic sprinklers specified in 8.6.7(1)(c)i. are located at a distance from the glass wall not to exceed 12 in. (305 mm) and arranged so that the entire surface of the glass is wet upon operation of the sprinklers. iii. * The glass wall is of tempered, wired, laminated, or ceramic glass held in place by a retention system that allows the glass framing system to deflect without breaking (loading) the glass before the sprinklers operate. iv. The automatic sprinklers required by 8.6.7(1)(c)i. are not required on the atrium side of the glass wall and the inoperable window where there is no walkway or other floor area on the atrium side above the main floor level. v. Doors in the glass walls are of glass or other material that resists the passage of smoke. vi. Doors in the glass walls are self-closing or automatic-closing upon detection of smoke. vii. The glass is continuous vertically, without horizontal mullions, window treatments, or other obstructions that would interfere with the wetting of the entire glass surface. (2) Access to exits is permitted to be within the atrium, and exit discharge in accordance with 7.7.2 is permitted to be within the atrium. (3) The occupancy within the atrium meets the specifications for classification as low- or ordinary-hazard contents. (See 6.2.2.) (4) The entire building is protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7. (5)* For other than existing, previously approved atriums, an engineering analysis is performed that demonstrates that the building is designed to keep the smoke layer interface above the highest unprotected opening to adjoining spaces, or 6 ft (1830 mm) above the highest floor level of exit access open to the atrium, for a period equal to 1.5 times the calculated egress time or 20 minutes, whichever is greater. (6)* For other than existing, previously approved smoke control systems, where an engineered smoke control system is installed to meet the requirements of 8.6.7(5), the system is independently activated by each of the following: (a) Upon initiation of a smoke detector detection system or actuation of the required automatic sprinkler system within the atrium or areas open to the atrium (b) Manual controls that are readily accessible to the fire department

Submitter Information Verification

Committee: SAF-FIR Submittal Date: Thu Jun 13 09:41:56 EDT 2019 Page 112 of 373

106 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Committee Statement

Committee There are other provision in NFPA 101 which requires a smoke detection system to actuate a Statement: smoke control system, and this change is consistent with these other provisions in NFPA 101. Response SR-6548-NFPA 101-2019 Message: Public Comment No. 164-NFPA 101-2019 [Section No. 8.6.7]

Ballot Results

This item has passed ballot

26 Eligible Voters 5 Not Returned 21 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Gould, Jennifer Klein Hall, William J. Jones, Adam C. Richardson, Dennis A. Shino, Gregory K.

Affirmative All Alday, Eddie Dewayne Cahanin, Gregory J. Cook, David Dawe, Nicholas A. Devlin, John F. Dudley, Jeffry T. Goldhammer, Edward S. Graupmann, Joseph Gump, Jack A. Higgins, Joseph Patrick Hopper, Howard Hugo, Jeffrey M. Humble, Jonathan Jackson, Waymon Koffel, William E. McHugh, Jr., William J. Morris, Jeramie W. Roeper, Kurt A. Stashak, Catherine L. Wittasek, Nathan B.

Page 113 of 373

107 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Zivnuska, Alexander Frederick

Page 114 of 373

108 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6550-NFPA 101-2019 [ Section No. 8.6.10.2 ]

8.6.10.2 Area Limitations. 8.6.10.2.1 The aggregate area of mezzanines located within a room, other than normally unoccupied equipment platforms, shall not exceed one-third the open area of the room in which the mezzanines are located. Enclosed space shall not be included in a determination of the size of the room in which the mezzanine is located. 8.6.10.2.2 The aggregate area of mezzanines located within a room, other than normally unoccupied equipment platforms, shall not exceed one-half the open area of the room in which the mezzanines are located, where all of following conditions are met: (1) The building is protected throughout with a supervised automatic sprinkler system in accordance with 9.7.1 . (2) All portions of the mezzanines are open to the room in which the mezzanine is located, other than walls not more than 42 in. (1065 mm) high, columns, and posts. 8.6.10.2.3 No limit on the number of mezzanines in a room shall be required. 8.6.10.2.4 For purposes of determining the allowable mezzanine area, the aggregate area of the mezzanines shall not be included in the area of the room. 8.6.10.3 Openness. The openness of mezzanines shall be in accordance with 8.6.10.3.1 or 8.6.10.3.2. 8.6.10.3.1 All portions of a mezzanine, other than walls not more than 42 in. (1065 mm) high, columns, and posts, shall be open to and unobstructed from the room in which the mezzanine is located, unless the occupant load of the aggregate area of the enclosed space does not exceed 10. 8.6.10.3.2 A mezzanine having two or more means of egress shall not be required to open into the room in which it is located if not less than one of the means of egress provides direct access from the enclosed area to an exit at the mezzanine level.

Submitter Information Verification

Committee: SAF-FIR Submittal Date: Thu Jun 13 10:49:13 EDT 2019

Committee Statement

Committee This will allow mezzanines to be up to one-half the area of the room in which it is located in fully Statement: sprinklered buildings, and is consistent with other model building and residential codes. Response SR-6550-NFPA 101-2019 Message: Public Comment No. 163-NFPA 101-2019 [Sections 8.6.10.2, 8.6.10.3]

Ballot Results

This item has passed ballot

Page 115 of 373

109 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

26 Eligible Voters 5 Not Returned 20 Affirmative All 0 Affirmative with Comments 1 Negative with Comments 0 Abstention

Not Returned Gould, Jennifer Klein Hall, William J. Jones, Adam C. Richardson, Dennis A. Shino, Gregory K.

Affirmative All Alday, Eddie Dewayne Cahanin, Gregory J. Cook, David Dawe, Nicholas A. Devlin, John F. Dudley, Jeffry T. Goldhammer, Edward S. Graupmann, Joseph Gump, Jack A. Higgins, Joseph Patrick Hopper, Howard Hugo, Jeffrey M. Humble, Jonathan Jackson, Waymon Koffel, William E. McHugh, Jr., William J. Morris, Jeramie W. Roeper, Kurt A. Stashak, Catherine L. Wittasek, Nathan B.

Negative with Comment Zivnuska, Alexander Frederick I feel the allowance of up to one-half simply due to protection by sprinklers and openness is too permissive

Page 116 of 373

110 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6551-NFPA 101-2019 [ Section No. 8.7.1.4 ]

8.7.1.4 Unless prohibited by Chapters 11 through 43, existing doors with existing nonrated, factory- or field- applied protective plates extending not more than 48 in. (1220 mm) above the bottom of the door shall be permitted where they are installed in accordance with the door manufacturer’s published listing.

Submitter Information Verification

Committee: SAF-FIR Submittal Date: Thu Jun 13 10:59:13 EDT 2019

Committee Statement

Committee Premise of 1st draft substantiation was primary based on existing health care occupancies section Statement: 19.3.2.1.4. Fundamental Chapter 8 applies to new and existing applications dependent upon the occupancy chapters. Proposed comment established that "existing" doors are permitted this exception for nonrated, factory or field-applied protective plates, and not "new" fire rated doors. Proposal is now consistent with 1st draft substantiation and new vs existing applications. Response SR-6551-NFPA 101-2019 Message: Public Comment No. 126-NFPA 101-2019 [Section No. 8.7.1.4]

Ballot Results

This item has passed ballot

26 Eligible Voters 5 Not Returned 21 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Gould, Jennifer Klein Hall, William J. Jones, Adam C. Richardson, Dennis A. Shino, Gregory K.

Affirmative All Alday, Eddie Dewayne Cahanin, Gregory J. Cook, David Dawe, Nicholas A. Devlin, John F.

Page 117 of 373

111 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Dudley, Jeffry T. Goldhammer, Edward S. Graupmann, Joseph Gump, Jack A. Higgins, Joseph Patrick Hopper, Howard Hugo, Jeffrey M. Humble, Jonathan Jackson, Waymon Koffel, William E. McHugh, Jr., William J. Morris, Jeramie W. Roeper, Kurt A. Stashak, Catherine L. Wittasek, Nathan B. Zivnuska, Alexander Frederick

Page 118 of 373

112 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6556-NFPA 101-2019 [ New Section after 9.1.4 ]

9.1.5 Energy Storage Systems. Energy storage systems shall be in accordance with NFPA 855 .

Submitter Information Verification

Committee: SAF-BSF Submittal Date: Thu Jun 13 15:48:33 EDT 2019

Committee Statement

Committee Energy storage systems are an emerging technology. NFPA 855 addresses the specific Statement: hazards associated with ESS. Response SR-6556-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

28 Eligible Voters 4 Not Returned 23 Affirmative All 0 Affirmative with Comments 1 Negative with Comments 0 Abstention

Not Returned Donga, Paul M. Jardin, Joseph M. Klinker, Richard L. White, Kristian

Affirmative All Balido, Jodi S Bradley, Harry L. Brinkman, Kevin L. Chen, Flora F. Dale, Stephen E. Dempsey, Bryan Grill, Raymond A. Hoskins, Bryan Lawrence Hugo, Jeffrey M. Hutton, Claude O.

Page 119 of 373

113 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Kellett, Michael Killian, David A. Lazarz, Daniel J. Panowitz, Scott E. Reed, Ray F. Reiswig, Rodger Roberts, Richard Jay Ruchala, Kurt A. Shudak, Lawrence J. Szmanda, Michael R. Warner, Todd W. Wren, Carl D. Wyatt, David M.

Negative with Comment Larrimer, Peter A. The new 9.1.5 is new material and should not be accepted at this stage. Even though there was a committee input on this topic, NFPA 855 was not published, and in my opinion, it was inappropriate to put a placeholder in at the Public Input stage to accept a document that was not yet published for review by the public. This should wait at least one cycle so that controversial issues in NFPA 855 can be addressed.

Page 120 of 373

114 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6549-NFPA 101-2019 [ Section No. 9.6.2.10.3.1 ]

9.6.2.10.3.1 In new construction, where required by Chapters 11 through 43, the alarm notification signal in sleeping rooms resulting from activation of smoke alarms shall be a 520 Hz low-frequency signal complying with NFPA 72. The effective date for compliance with 9.6.2.10.3.1 shall be January 1, 2023.

Submitter Information Verification

Committee: SAF-BSF Submittal Date: Thu Jun 13 09:46:30 EDT 2019

Committee Statement

Committee The the future effectivity date for smoke alarms to produce a 520 Hz low-frequency signal was Statement: deleted for the following reasons.

1. The NFPA 101 Residential Committee unanimously approved FR 6886 and FR 6892 (to require smoke alarms that are installed in sleeping rooms to produce the 520 Hz low-frequency audible alarm signal) without a future effectivity date

2. The 2021 edition of the International Fire Code will require smoke alarms that are installed in sleeping rooms of new hotels, dormitories and apartment buildings to produce the 520 Hz low- frequency audible alarm signal

3. It is beneficial to have consistent requirements between the various model codes

4. The following product solutions are currently available in the market if the smoke alarm is unable to produce the 520 Hz low-frequency audible alarm signal in sleeping rooms:

a) Smoke detectors with integral sounder bases

b) Fire alarm system horns and horn/strobes

c) Speakers connected to an in-building fire alarm Emergency Voice Alarm Communication (EVAC) system

Any further delay in implementing a technology that is proven to enhance public life safety needs to be avoided. That’s because peer-reviewed research has concluded the wakening effectiveness of the 520 Hz low-frequency signal is superior to standard 3 KHz audible alarm signal for awakening high-risk segments of the population such as such as people over 65, people who are hard of hearing, school age children and people who are alcohol impaired. In addition, there are currently smoke alarm products available that claim to meet the 520 Hz frequency requirement.

Response SR-6549-NFPA 101-2019 Message: Public Comment No. 107-NFPA 101-2019 [Section No. 9.6.2.10.3.1]

Ballot Results

This item has passed ballot

28 Eligible Voters 4 Not Returned 23 Affirmative All

Page 121 of 373

115 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

0 Affirmative with Comments 1 Negative with Comments 0 Abstention

Not Returned Donga, Paul M. Jardin, Joseph M. Klinker, Richard L. White, Kristian

Affirmative All Balido, Jodi S Bradley, Harry L. Brinkman, Kevin L. Chen, Flora F. Dale, Stephen E. Dempsey, Bryan Grill, Raymond A. Hoskins, Bryan Lawrence Hugo, Jeffrey M. Hutton, Claude O. Kellett, Michael Killian, David A. Lazarz, Daniel J. Panowitz, Scott E. Reed, Ray F. Reiswig, Rodger Roberts, Richard Jay Ruchala, Kurt A. Shudak, Lawrence J. Szmanda, Michael R. Warner, Todd W. Wren, Carl D. Wyatt, David M.

Negative with Comment Larrimer, Peter A. NFPA 72, 29.5.10.1 already requires those rooms that are required to be accessible for those with mild to severe hearing loss as identified in NFPA 72 to be provided with the low frequency smoke alarms. Since NFPA 101 references NFPA 72 for the installation of smoke alarms, the low frequency alarms are already going to be required in those rooms that are to be accessible by ADA or similar law. However, this change appears to establish a requirement for all smoke alarms provided in any sleeping room to be designed for those with mild to severe hearing loss as identified in NFPA 72. It doesn’t appear that adequate justification has been provided to mandate this in NFPA 101. If this is such a good idea, why not mandate the installation low frequency alarms in all sleeping rooms in NFPA 72 so there is no apparent conflict. While enhanced audible characteristics in smoke alarms in every sleeping room of every occupancy might be beneficial for some people, the increase in safety versus the increase in costs, has not been established, especially when one considers that NFPA 101 generally requires sprinkler protection in new construction to protect sleeping occupants in the occupancy chapters. This Page 122 of 373

116 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

requirement should be established in NFPA 72 and that committee rejected this idea.

Page 123 of 373

117 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6553-NFPA 101-2019 [ Section No. 9.15 ]

9.15* Two-Way Radio Communication Enhancement Systems. In all new and existing buildings, minimum radio signal strength for fire department communications shall be maintained in accordance with the fire code. 9.15.1 Two-way radio communication enhancement systems shall be in accordance with NFPA 1221 . 9.15.2 In all new and existing buildings, minimum radio signal strength for fire department communications shall be maintained in accordance with the fire code NFPA 1221 . 9.15.3* In existing buildings, radio signal strength for fire department communications shall be as required by the authority having jurisdiction.

A.9.15.3

In existing buildings, it might be difficult to meet the minimum radio signal strength required by NFPA 1221 . The authority having jurisdiction might determine that certain areas of a building do not need to meet the radio signal strength coverage required by NFPA 1221 . The authority having jurisdiction might also determine that compliance with the minimum radio signal strength outlined in NFPA 1221 is appropriate.

Submitter Information Verification

Committee: SAF-BSF Submittal Date: Thu Jun 13 13:45:40 EDT 2019

Committee Statement

Committee It may be difficult for existing buildings to meet the radio signal strength of NFPA 1221 however it Statement: is important that all two-way radio communication enhancement systems meet the other requirements of NFPA 1221 such as a secondary power supply. Response SR-6553-NFPA 101-2019 Message: Public Comment No. 159-NFPA 101-2019 [Section No. 9.15] Public Comment No. 36-NFPA 101-2019 [Section No. 9.15]

Ballot Results

This item has passed ballot

28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Page 124 of 373

118 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Not Returned Donga, Paul M. Jardin, Joseph M. Klinker, Richard L. White, Kristian

Affirmative All Balido, Jodi S Bradley, Harry L. Brinkman, Kevin L. Chen, Flora F. Dale, Stephen E. Dempsey, Bryan Grill, Raymond A. Hoskins, Bryan Lawrence Hugo, Jeffrey M. Hutton, Claude O. Kellett, Michael Killian, David A. Larrimer, Peter A. Lazarz, Daniel J. Panowitz, Scott E. Reed, Ray F. Reiswig, Rodger Roberts, Richard Jay Ruchala, Kurt A. Shudak, Lawrence J. Szmanda, Michael R. Warner, Todd W. Wren, Carl D. Wyatt, David M.

Page 125 of 373

119 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6534-NFPA 101-2019 [ Section No. 10.3 ]

10.3 Contents and Furnishings. 10.3.1* Draperies, Curtains, and Other Hanging or Suspended Furnishings and Decorations. Where required by the applicable provisions of this Code, draperies, curtains, and other similar loosely hanging or suspended furnishings and decorations shall meet the flame propagation performance criteria contained in Test Method 1 or Test Method 2, as appropriate, of NFPA 701. 10.3.2 Smoldering Ignition of Upholstered Furniture and Mattresses . 10.3.2.1* Smoldering Ignition of Upholstered Furniture. Newly introduced upholstered furniture, except as otherwise permitted by Chapters 11 through 43, shall be resistant to a cigarette ignition (i.e., smoldering) in accordance with one of the following: (1) The components of the upholstered furniture shall meet the requirements for Class I when tested in accordance with NFPA 260.

1 (2) Mocked-up composites of the upholstered furniture shall have a char length not exceeding 1 ⁄2 in. (38 mm) when tested in accordance with NFPA 261. 10.3.2.2* Rate of Heat Release and Mass Loss Testing of Upholstered Furniture. and Mattresses. 10.3.2.2.1 Where required by the applicable provisions of this Code, upholstered furniture and other seating furniture, unless the furniture is located in a building protected throughout by an approved automatic sprinkler system, shall have limited rates of heat release when tested in accordance with ASTM E1537, Standard Test Method for Fire Testing of Upholstered Furniture, as follows: (1) The peak rate of heat release for the single furniture item shall not exceed 80 kW. (2) The total heat released by the single furniture item during the first 10 minutes of the test shall not exceed 25 MJ. 10.3.2.2.2 When tests are conducted in accordance with 10.3.2.2 , the formation of flaming droplets during the test shall be reported. 10.3.3 Mattresses. Newly introduced mattresses, except as otherwise permitted by Chapters 11 through 43 , shall have a char length not exceeding 2 in. (51 mm) when tested in accordance with 16 CFR 1632, “Standard for the Flammability of Mattresses and Mattress Pads” (FF 4-72). 10.3.3.1* Smoldering Ignition of Mattresses. Newly introduced mattresses, except as otherwise permitted by Chapters 11 through 43, shall have a char length not exceeding 2 in. (51 mm) when tested in accordance with 16 CFR 1632, “Standard for the Flammability of Mattresses and Mattress Pads” (FF 4-72).

A.10.3.3.1

The char length of not more than 2 in. (51 mm) required in 16 CFR 1632, “Standard for the Flammability of Mattresses and Mattress Pads” (FF 4-72), is an indicator that the mattress is resistant to a cigarette ignition. United States federal regulations require mattresses in this country to comply with 16 CFR 1632.

10.3.3.2* Rate of Heat Release and Mass Loss Testing of Mattresses. Where required by the applicable provisions of this Code, mattresses shall comply with 10.3.3.2.1 or 10.3.3.2.2, unless the mattress is located in a building protected throughout by an approved automatic sprinkler system.

Page 126 of 373

120 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

10.3.3.2.1 The mattress shall have limited rates of heat release when tested in accordance with ASTM E1590, Standard Test Method for Fire Testing of Mattresses, as follows: (1) The peak rate of heat release for the single mattress shall not exceed 100 kW. (2) The total heat released by the mattress during the first 10 minutes of the test shall not exceed 25 MJ. 10.3.3.2.2 The mattress shall have a mass loss not exceeding 15 percent when tested in accordance with the fire test in Appendix A3 of ASTM F1085, Standard Specification for Mattress and Box Springs for Use in Berths in Marine Vessels. 10.3.3.2.3 When tests are conducted in accordance with 10.3.3 10.3.3.2 , the formation of flaming droplets during the test shall be reported. 10.3.4* Explosive or Highly Flammable Furnishings or Decorations. Furnishings or decorations of an explosive or highly flammable character shall not be used.

A.10.3.4

Natural cut Christmas trees that are not effectively flame-retardant treated treated to improve fire performance , ordinary crepe paper decorations, and pyroxylin plastic decorations might be classified as highly flammable. See 10.3.9 for requirements for combustible artificial decorative vegetation. See NFPA 1 , Section 10.13, for provisions for natural cut Christmas trees.

10.3.5 Fire-Retardant Coatings. Fire-retardant coatings shall be maintained to retain the effectiveness of the treatment under service conditions encountered in actual use. 10.3.6* Foamed Plastics. Where required by the applicable provisions of this Code, furnishings and contents made with foamed plastic materials that are unprotected from ignition shall have a heat release rate not exceeding 100 kW when tested in accordance with UL 1975, Fire Tests for Foamed Plastics Used for Decorative Purposes, or when tested in accordance with NFPA 289 using the 20 kW ignition source. 10.3.7 Lockers. Lockers shall be considered interior finish and shall comply with the requirements of 10.2.4.8. 10.3.8 Containers for Waste, or Linen. 10.3.8.1 Where required by Chapters 11 through 43, newly introduced containers for waste or linen, with a capacity of 20 gal (75.7 L) or more, shall meet both of the following: (1) Such containers shall be provided with lids. (2) Such containers and their lids shall be constructed of noncombustible materials or of materials that meet a peak rate of heat release not exceeding 300 kW/m2 when tested at an incident heat flux of 50 2 1 kW/m in the horizontal orientation and at a thickness as used in the container but not less than ⁄4 in. (6.3 mm), in accordance with ASTM E1354, Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter. 10.3.8.2 Where required by Chapters 11 through 43, newly introduced metal wastebaskets and other metal waste, or linen containers with a capacity of 20 gal (75.7 L) or more shall be listed in accordance with UL 1315, Safety for Metal Waste Paper Containers, and shall be provided with a noncombustible lid. 10.3.9 Combustible Artificial Decorative Vegetation.

Page 127 of 373

121 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

10.3.9.1 Flammability of Combustible Artificial Decorative Vegetation . Combustible artificial decorative vegetation shall meet one of the following: (1) The flame propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701 (2) A maximum heat release rate of 100 kW when tested to NFPA 289, using the 20 kW ignition source 10.3.9.2 Fire-Retardant Treatments for Natural Cut Christmas Trees. Where fire-retardant treatments are applied to natural cut Christmas trees, the fire-retardant treatment shall comply with both Test Method 1 and Test Method 2 of ASTM E3082, Standard Test Methods for Determining the Effectiveness of Fire Retardant Treatments for Natural Christmas Trees . 10.3.9.3 Electrical Equipment. 10.3.9.3.1 Electrical wiring and listed luminaires used on combustible artificial decorative vegetation shall be listed for that application. 10.3.9.3.2 The use of electrical wiring and of luminaires constructed entirely of metal shall not be permitted on combustible artificial decorative vegetation. 10.3.9.4 Open Flames. Candles and open flames shall not be used on or near combustible artificial decorative vegetation.

Submitter Information Verification

Committee: SAF-INT Submittal Date: Tue Jun 11 11:57:15 EDT 2019

Committee Statement

Committee The revision incorporates the changes in PC-3 as modified in 10.3.1 to include "hanging or Statement: suspended" furnishings and decorations. The revision also incorporates the changes in PC-17 re. combustible decorative vegetation.

For A.10.3.4, language cleanup and expansion to other potentially highly flammable items based on PC-12. Response SR-6534-NFPA 101-2019 Message: Public Comment No. 3-NFPA 101-2019 [Section No. 10.3] Public Comment No. 17-NFPA 101-2019 [Section No. 10.3.9] Public Comment No. 12-NFPA 101-2019 [Section No. A.10.3.4]

Ballot Results

This item has passed ballot

16 Eligible Voters 3 Not Returned 13 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Carrigan, Matthew

Page 128 of 373

122 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Siegel, Shelley Sloan, Dwayne E.

Affirmative All Babrauskas, Vytenis Chen, Tiffney Arlene-Cates Cutrer, Peter S. Dawe, Nicholas A. Evans, Michael W. Fitch, William E. Hirschler, Marcelo M. Hunter, Matthew M Lathrop, James K. Newman, Kathleen A. Paszczuk, Henry Puchovsky, Milosh T. Richardson, James R.

Page 129 of 373

123 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6535-NFPA 101-2019 [ Section No. 10.4 ]

10.4 Outdoor Furniture. 10.4.1* General. Outdoor furniture placed under a combustible exterior projection shall comply with Section 10.4. 10.4.2 Distance from Buildings. Furniture placed outdoors placed within 2 ft (61 610 mm) of any building shall be located in an area protected by an approved automatic sprinkler system or shall be labeled as having complied with any one of comply with 10.4.3. through 10.4.6 . 10.4.3 Traditional Materials. The furniture shall be constructed entirely of wood identified for outdoor use or noncombustible materials complying with 4.6.13 , or both. Furniture placed outdoors within 2 ft (610 mm) of any building shall comply with one of the following: (1) Traditional materials: The furniture shall be constructed entirely of wood, identified for outdoor use or noncombustible materials complying with 4.6.13, or both. (2) Plastic composites: The furniture shall be constructed entirely of plastic composite materials intended for outdoor use that meet the requirements of a Class C material in accordance with Section 10.2, except that the smoke developed index shall not be limited. (3) Heat release: The furniture shall be constructed entirely of materials intended for outdoor use that exhibit a peak rate of heat release not exceeding 300 kW/m2 when tested in accordance with ASTM E1354, Standard Test Method for Heat and Visible Smoke Release Rate for Materials and Products Using an Oxygen Consumption Calorimeter , at an incident heat flux of 50 kW/m2 in the horizontal orientation. (4) Full-scale testing: The furniture shall be constructed entirely of materials intended for outdoor use and such that the entire item of furniture shall exhibit a maximum rate of heat release not exceeding 100 kW when tested in accordance with NFPA 289 using the 20 kW ignition source. 10.4.4 Plastic Composites. The furniture shall be constructed of plastic composite materials intended for outdoor use that meet the requirements of a Class C material in accordance with Section 10.2 , except that the smoke developed index shall not be limited. 10.4.5 Heat Release. The furniture shall be constructed entirely of materials intended for outdoor use that exhibit a peak rate of heat release not exceeding 300 kW/m 2 when tested in accordance with ASTM E1354 at an incident heat flux of 50 kW/m 2 in the horizontal orientation. 10.4.6 Full-Scale Testing. The furniture shall be constructed entirely of materials intended for outdoor use and the entire item of furniture shall exhibit a maximum rate of heat release not exceeding 100 kW when tested in accordance with NFPA 289 , using the 20 kW ignition source.

Submitter Information Verification

Committee: SAF-INT Submittal Date: Tue Jun 11 12:29:07 EDT 2019

Committee Statement

Committee Statement: The revision incorporates PC-16 with minor editorial changes and responds to CN-23. Response Message: SR-6535-NFPA 101-2019

Page 130 of 373

124 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Public Comment No. 39-NFPA 101-2019 [Section No. 10.4] Public Comment No. 16-NFPA 101-2019 [Section No. 10.4] Public Comment No. 5-NFPA 101-2019 [Section No. 10.4]

Ballot Results

This item has passed ballot

16 Eligible Voters 3 Not Returned 13 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Carrigan, Matthew Siegel, Shelley Sloan, Dwayne E.

Affirmative All Babrauskas, Vytenis Chen, Tiffney Arlene-Cates Cutrer, Peter S. Dawe, Nicholas A. Evans, Michael W. Fitch, William E. Hirschler, Marcelo M. Hunter, Matthew M Lathrop, James K. Newman, Kathleen A. Paszczuk, Henry Puchovsky, Milosh T. Richardson, James R.

Page 131 of 373

125 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6543-NFPA 101-2019 [ Section No. 11.8.1.1 ]

11.8.1.1 The provisions of Section 11.8 shall apply to the following: (1) New high-rise buildings, as defined in 3.3.37.7 (2) Existing high-rise buildings as specifically required by Chapters 13 , 15 , 17 , 19 , 21 , 23 , 26 , 29 , 31 , 33 , 37 , 39 , 40 , 42 , or 11 through 43

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 12 14:04:00 EDT 2019

Committee Statement

Committee Statement: Reference to Chapters 11 through 43 is consistent with the remainder of the Code. Response Message: SR-6543-NFPA 101-2019 Public Comment No. 42-NFPA 101-2019 [Section No. 11.8.1.1]

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Page 132 of 373

126 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Jacoby, David J. Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 133 of 373

127 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6544-NFPA 101-2019 [ Section No. 11.8.4.2.1 ]

11.8.4.2.1 Two-way telephone communication service shall be provided for fire department use. This system shall be in accordance with NFPA 72 . The communications system shall operate between the emergency command center and every elevator car, every elevator lobby, and each floor level of exit stairs. 11.8.4.2.1.1 This system shall be in accordance with NFPA 72. 11.8.4.2.1.2 The two-way telephone communications system shall operate between the emergency command center and every elevator car, every elevator lobby, and each floor level of exit stairs.

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 12 14:05:43 EDT 2019

Committee Statement

Committee The revision removes the vague term "communication system" and uses the precise Statement: language consistent with the earlier text.

Response SR-6544-NFPA 101-2019 Message: Public Comment No. 152-NFPA 101-2019 [Section No. 11.8.4.2.1]

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Page 134 of 373

128 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 135 of 373

129 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6570-NFPA 101-2019 [ Section No. 11.8.6 ]

11.8.6* Emergency Command Center. Emergency command centers shall be in accordance with 11.8.6.1 through 11.8.6.7 . 11.8.6.1 An The location, design, content, and fire department access of the emergency command center shall be provided in a location approved by the fire department. [ 1: 11.9.1] 11.8.6.2 The emergency command center shall be separated from the remainder of the building by a fire barrier having a fire resistance rating of not less than 1 hour, unless otherwise approved by the fire department. 11.8.6.3

The emergency command center room shall be a minimum of 200 ft 2 (19 m 2 ) with a minimum dimension of 10 ft (3050 mm). [ 1: 11.9.3] 11.8.6.4 Existing emergency command center rooms shall be maintained with the minimum square footage and dimensions previously approved by the AHJ. [ 1: 11.9.3.1] 11.8.6.5 The following shall be provided in the emergency command center: shall contain the following: (1) Voice fire alarm system panels and controls The emergency voice/alarm communication system unit Fire department two-way telephone communication service panels and controls where required by another section of this Code (2) Fire detection and fire alarm system annunciation panels annunciator unit Elevator floor location and operation annunciators Elevator fire recall switch in accordance with ASME A17.1/CSA B44, Safety Code for Elevators and Escalators Elevator emergency power selector switch(es) where provided in accordance with ASME A17.1/CSA B44 Sprinkler valve and waterflow annunciators Emergency generator status indicators Controls for any automatic stairway door unlocking system Fire pump status indicators (3) The fire department communication unit (4) Telephone A telephone for fire department use with controlled access to the public telephone system Stairway video monitoring equipment as required by 11.8.8 (5) Schematic building plans indicating the typical floor plan and detailing the building core means of egress, fire protection systems, fire-fighting equipment, and fire department access (6) Work table (7) If applicable, hazardous material management plans for the building (8) Emergency lighting — generator powered with battery backup

Page 136 of 373

130 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

11.8.6.6 Where not provided on the fire alarm control panel, the following devices or functions shall be provided within the emergency command center: (1) Annunciator visually indicating the location of the elevators and whether they are operational (2) Status indicators and controls for air-handling systems (3) Controls for any automatic unlocking stairway door unlocking system s simultaneously if provided (4) Sprinkler valve and waterflow annunciators detector display panel (5) Emergency generator and standby power status indicators (6) Fire pump status indicators (7) Generator supervision devices and manual start and transfer features (8) Public address system, where specifically required by NFPA 1 (9) Controls required for smoke control (10) Stairway video monitoring equipment as required by 11.8.8 (11) Fire department two-way telephone communication service panels and controls where required by another section of this Code (12) Elevator floor location and operation annunciators (13) Elevator fire recall switch in accordance with ASME A17.1/CSA B44, Safety Code for Elevators and Escalators (14) Elevator fire recall switch or switches in accordance with ASME A17.1/CSA B44, Safety Code for Elevators and Escalators 11.8.6.7 Devices, equipment, components, and sequences shall be individually tested in accordance with appropriate standards and manufacturers’ documented instructions. [ 1: 11.9.6]

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 26 12:55:58 EDT 2019

Committee Statement

Committee The revision is intended to coordinate emergency command center requirements in NFPA Statement: 101, NFPA 5000, and NFPA 1. Response SR-6570-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua Page 137 of 373

131 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 138 of 373

132 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6622-NFPA 101-2019 [ New Section after 12.3.4.3.7 ]

12.3.4.3.8 Emergency forces notification shall be provided in accordance with 9.6.4 .

Submitter Information Verification

Committee: SAF-AXM Submittal Date: Fri Jul 12 09:09:18 EDT 2019

Committee Statement

Committee It is reasonable to require emergency forces notification where an assembly occupancy is Statement: required to be provided with a fire alarm system. (Related CI-6719) Response SR-6622-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

28 Eligible Voters 5 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Herrera, Mark A. Keberle, Kenneth F. Scandaliato, Steven J. Thomas, Jr., Elbert R. Tubbs, Jeffrey S.

Affirmative All Center, Eric Conner, William Cook, David Deacon, Nils Finnegan, Daniel P. Gandy, Max L. Goosman, Donald G. Hansen, Harold C. Hesson, Stephen C

Page 139 of 373

133 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Hollinger, David W. Humble, Jonathan Lake, John Lambert, Josh Morin, Kevin D. Pauls, Jake Peterson, Ryan Quinterno, Vincent Roether, Ed Rogers, Adam Ruling, Karl G. Schweitzer, Charles J. Sherman, Philip R. Shirey, Jeffrey

Page 140 of 373

134 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6626-NFPA 101-2019 [ Section No. 12.4.9 ]

12.4.9* Special Amusement Buildings.

A.12.4.9

Special amusement buildings are unique structures that can present challenges not common in assembly or other occupancies. Hazards in special amusement buildings can include industrial, electrical, pneumatic, stored energy systems, or other systems and equipment associated with the ride and/or show systems. Occupants are typically not familiar with their surroundings, and the provided exit access might not be apparent while the building is operating in show conditions. Additionally, special amusement buildings might present design challenges, which the authority having jurisdiction might need to consider. For example, a ride building containing a roller coaster might meet the height requirements for a high-rise structure but only contain one story of height and mezzanines or catwalks at upper levels for evacuation. Portions of a ride might exit and return into the building, traverse to an open structure, be surrounded by water, or contain an atrium. Each of these conditions presents challenges to the design of fire protection, fire alarm, and life safety systems, as well as the emergency action plan required in 12.7.1.3 12.7.13 . Where a special amusement building is installed inside another building on a temporary basis, such as within an exhibit hall, the special amusement building requirements apply only to the portions of the building used as a special amusement. For example, the smoke detectors required by 12.4.9.4.3 are not required to be connected to the building’s fire alarm system. Where installed in an exhibit hall, such smoke detectors are also required to comply with the provisions applicable to an exhibit.

12.4.9.1 General. 12.4.9.1.1* Special amusement buildings, regardless of occupant load, shall meet the requirements for assembly occupancies in addition to the requirements of 12.4.9, unless the special amusement building is a multilevel play structure that is not more than 10 ft (3050 mm) in height and has aggregate horizontal projections not exceeding 160 ft2 (15 m2).

A.12.4.9.1.1

The aggregate horizontal projections of a multilevel play structure are indicative of the number of children who might be within the structure and at risk from a fire or similar emergency. The word “aggregate” is used in recognition of the fact that the platforms and tubes that make up the multilevel play structure run above each other at various levels. In calculating the area of the projections, it is important to account for all areas that might be expected to be occupied within, on top of, or beneath the components of the structure when the structure is used for its intended function.

12.4.9.1.2* Special amusement buildings shall be subclassified as follows: (1) Class A: Permanently installed special amusement buildings that include an amusement ride or device in which patrons are contained or restrained and are unable to evacuate without the assistance of the ride operator (2) Class B: Permanently installed special amusement buildings that do not include an amusement ride or device, or that include an amusement ride or device from which patrons are able to self- evacuate (3) Class C: Temporary or mobile special amusement buildings

Page 141 of 373

135 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

A.12.4.9.1.2

An example of a Class A special amusement building would be a theme park attraction or dark ride where patrons are restrained inside a ride vehicle and guided through a building on a track. An example of a Class B special amusement building would be an escape room or theme park attraction where a patron can exit the building once the amusement or effects are stopped. Temporary rides such as a merry-go-round or train located in a mall would not meet the definition of a Class B special amusement building unless there was an element to the ride where a patron would become confused or is otherwise confined to the ride vehicle and unable to self-evacuate. See A.3.3.37.9 . An example of a Class C special amusement building would be a temporary haunted house, maze, or carnival attraction.

12.4.9.2 Means of Egress. 12.4.9.2.1 Exit Marking. 12.4.9.2.1.1 Exit marking shall be in accordance with Section 7.10. 12.4.9.2.1.2 Floor proximity exit signs shall be provided in accordance with 7.10.1.6. 12.4.9.2.1.3* In special amusement buildings where mazes, mirrors, or other designs are used to confound the egress path, approved directional exit marking that becomes apparent in an emergency shall be provided.

A.12.4.9.2.1.3

Consideration should be given to the provision of directional exit marking on or adjacent to the floor.

12.4.9.2.2 Illumination. 12.4.9.2.2.1* Actuation Unless otherwise permitted by 12.4.9.2.2.2 , actuation of the automatic sprinkler system, or any other suppression system, or actuation of a smoke detection system having an approved verification or cross-zoning operation capability shall provide for both of the following: (1) Increase in illumination in the means of egress to that required by Section 7.8 (2) Termination of any conflicting or confusing sounds and visuals

Page 142 of 373

136 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

A.12.4.9.2.2.1

Lighting levels within special amusement buildings are typically might be reduced to levels that are lower than those required by Section 7.8 for show purposes. In addition, projections, special effects, haze, and other theatrical elements might be combined, which can disorient occupants who are unfamiliar with the egress route. The activation of the automatic sprinkler system or smoke detection system must should immediately increase illumination to the required levels and stop all show elements that would continue to disorient or confuse occupants. Because of the delay in verification or cross-zoning of smoke detectors, positive alarm sequence should not be utilized when alarm-verification or cross-zoned smoke detectors is selected. In the context of a special amusement building, a conflicting or confusing sound or visual is any audio or visual device that is intended to quickly distract the attention the patron of a special amusement building for the purpose of frightening, confounding, disorienting, or otherwise capturing the attention of the patron. Examples of this include strobing and flashing lights, loud sound effects, scare or jump effects, loud music, animated figures, projected animation, and interactive games. These can all interfere with the fire alarm notification devices and live announcements from the attraction operator for the patron’s attention. In addition, effects that simulate the sound, sight, and smell of flames or smoke will confuse the patron if they continue to operate when the fire alarm system has been activated. Some examples of audio and visuals that might occur in a special amusement building, but that might not constitute a conflicting sound or visual, include static or very slow-moving video or projected images, background music, steady state lighting, and ride vehicle triggered effects.

12.4.9.2.2.2* Class A special amusement buildings shall not be required to comply with 12.4.9.2.2.1 where all of the following conditions apply: (1) The emergency action plan required by 12.4.9.6.2 provides specific evacuation instructions to all attraction operators for cycling out the attraction when it is determined that meeting the requirements of 12.4.9.2.2.1 presents a hazard to ride patrons. (2) A means of manually complying with 12.4.9.2.2.1 is provided to the primary attraction operator. (3) Attraction operators are trained on the alternative procedures for evacuations. (4) The authority having jurisdiction approves the modifications.

A.12.4.9.2.2.2

Amusement rides and devices that contain or restrain their patrons such that they are unable to evacuate without the assistance of a ride operator present a unique challenge during an emergency. ASTM F2291, Standard Practice for Design of Amusement Rides or Devices, provides for the design of evacuation paths in case the ride stops before completing its full cycle. The safest and fastest way to exit patrons during an emergency might be to “cycle out” by continuing ride operation until all patrons have exited the ride at the normal exit point (at the unload platform). If a patron were to attempt to exit the ride vehicle while the ride continues operation during an emergency, the patron may potentially be struck by the ride vehicle, or the ride’s safety systems might stop all ride motion, potentially extending the evacuation period. Because increasing the illumination of the means of egress along the ride and terminating any conflicting or confusing sounds or visuals while the ride is cycling out might entice the patrons to attempt to self-evacuate while the ride is in motion, the authority having jurisdiction and the owner are encouraged to work closely to develop a plan that implements the safest and most efficient method to exit the patrons from the ride, which might include continuing normal show operation during cycle out. In addition, the plan should assure that all ride operators and emergency responders understand their roles during cycle out, or during an evacuation if the ride cycle out is interrupted. The ride owner should work with the authority having jurisdiction from an early stage to develop a pre- incident plan in accordance with NFPA 1620 and any required or applicable provisions of 12.4.2.5.2 .

12.4.9.3 Interior Finish. Interior wall and ceiling finish materials complying with Section 10.2 shall be Class A throughout. 12.4.9.4 Detection, Alarm, and Communications Systems. 12.4.9.4.1 General. Page 143 of 373

137 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

12.4.9.4.1.1 Class A and Class B special amusement buildings shall be provided with an approved fire alarm system and smoke detection system in accordance with 9.6.1 and 12.4.9.4 . 12.4.9.4.1.2 Class C special amusement buildings shall be provided with an approved automatic smoke detection system in accordance with Section 9.6 . 12.4.9.4.2* Alarm Initiation. Actuation of any smoke detection system device shall sound an alarm at a constantly attended location on the premises.

A.12.4.9.4.2

Special amusement attractions might contain an operator console or “tower,” which might also serve as a constantly attended location when the ride is operating.

12.4.9.4.2.1 In Class A and Class B special amusement buildings, the required fire alarm system shall be initiated by each of the following: (1) Manual fire alarm box located at a constantly attended location under continuous supervision by competent persons when the special amusement building is open to patrons (2) Required automatic sprinkler system (3) Required automatic detection systems 12.4.9.4.2.2 In Class C special amusement buildings, actuation of any smoke detection system device shall activate an audible and visible alarm in a constantly attended receiving station within the building when occupied for purposes of initiating emergency action. 12.4.9.4.3 Smoke Detection. Where the nature of the special amusement building is such that it operates in reduced lighting levels, the building shall be protected throughout by an approved automatic smoke detection system in accordance with Section 9.6. 12.4.9.4.4* Notification.

A.12.4.9.4.4

Notification in special amusement buildings should be considered carefully depending on the operation of the special amusement. Voice announcements are the required method. However, automatically transmitted evacuation instructions might not be appropriate in some rides when occupants are confined to a ride vehicle and unable to self-evacuate. In order to avoid confusion, manual voice announcements from the ride operator might be preferable to pre-recorded evacuation instructions for some rides.

12.4.9.4.4.1 Occupant notification for Class A and Class B special amusement buildings shall be in accordance with 12.3.4.3 . 12.4.9.4.4.2 Occupant notification for Class C special amusement buildings shall be in accordance with 12.3.4.3 ; however, positive alarm sequence shall not be permitted. 12.4.9.4.4.3* An automatic means for sounding the general evacuation alarm shall be provided when the constantly attended location is not staffed.

Page 144 of 373

138 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

A.12.4.9.4.4.3

Special amusement buildings that contain rides tend be occupied after operating hours by maintenance staff. After-hours maintenance work might take place along the ride track or in an attached maintenance bay where ride vehicles are moved on and off spur tracks. When no ride operator is located at the constantly attended location to receive alarm signals, a means of automatically sounding the general evacuation signal should be provided for after-hours occupants.

12.4.9.5 Automatic Sprinklers Extinguishment Requirements . 12.4.9.5.1* Every special amusement building, other than buildings or structures not exceeding 10 ft (3050 mm) in height and not exceeding 160 ft2 (15 m2) in aggregate horizontal projection, shall be protected throughout by an approved, supervised automatic sprinkler system installed and maintained in accordance with Section 9.7.

A.12.4.9.5.1

See A.12.4.9.1 A.12.4.9.1.1.

12.4.9.5.2 Temporary Water Supply. Where the special amusement building required to be sprinklered by 12.4.9.5 12.4.9.5.1 is movable or portable, the sprinkler water supply shall be permitted to be provided by an approved temporary means. 12.4.9.6 Operating Features. 12.4.9.6.1* Furnishings, Decorations, and Scenery. Furnishings shall be in accordance with 12.7.4 .

A.12.4.9.6.1

Special amusement buildings might simulate different structures, such as an outdoor scene where false walls and ceilings, commonly known as sets, are recreated indoors with various fabrics and materials used to simulate trees, leaves, or other items. Sets in special amusement buildings are often designed by entertainment companies familiar with Broadway-style stage productions. However, unlike stages and theaters, there are no requirements for smoke control or proscenium protection. The authority having jurisdiction should consider and evaluate the total quantity of material introduced into the space.

12.4.9.6.2* Emergency Action Plan. In Class A special amusement buildings, the emergency action plan shall be reviewed and approved by the authority having jurisdiction.

A.12.4.9.6.2

The evacuation plan for special amusement buildings should consider the safest and fastest way to remove occupants from the structure. When a ride stops within the special amusement building, removing occupants from the ride system might present an extended evacuation. Additionally, hazards associated with the ride and show system might present electrical and entanglement challenges to occupants unfamiliar with the building. Evacuation of special amusement buildings can also pose challenges to the local fire department if they are not familiar with the nature of the building or ride system. Specialized equipment for rescue, ride vehicle-specific tools for releasing doors, and high- energy ride vehicle hazard awareness might all be required when evacuating from a location other than a load/unload station. The ride owner should work with the authority having jurisdiction from an early stage to develop a pre- incident plan in accordance with NFPA 1620 and any required or applicable provisions of 12.4.2.5.2 .

Supplemental Information Page 145 of 373

139 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

File Name Description Approved 101-SR6626- Clean version of revised 12.4.9 and associated Annex A paras. For staff Clean.docx use

Submitter Information Verification

Committee: SAF-AXM Submittal Date: Fri Jul 12 10:59:42 EDT 2019

Committee Statement

Committee The committee addressed many public inputs related to special amusements which requested Statement: updates to life safety systems due to new technologies in themed entertainment, fire suppression, detection, and building automation. The reorganization of this section allows for easier application for the user along with creating a classification system for special amusement buildings. Response SR-6626-NFPA 101-2019 Message: Public Comment No. 205-NFPA 101-2019 [Section No. A.12.4.9.6] Public Comment No. 204-NFPA 101-2019 [Section No. A.12.4.9.5]

Ballot Results

This item has passed ballot

28 Eligible Voters 5 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Herrera, Mark A. Keberle, Kenneth F. Scandaliato, Steven J. Thomas, Jr., Elbert R. Tubbs, Jeffrey S.

Affirmative All Center, Eric Conner, William Cook, David Deacon, Nils Finnegan, Daniel P. Gandy, Max L. Goosman, Donald G. Hansen, Harold C. Hesson, Stephen C Hollinger, David W. Humble, Jonathan Page 146 of 373

140 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Lake, John Lambert, Josh Morin, Kevin D. Pauls, Jake Peterson, Ryan Quinterno, Vincent Roether, Ed Rogers, Adam Ruling, Karl G. Schweitzer, Charles J. Sherman, Philip R. Shirey, Jeffrey

Page 147 of 373

141 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6623-NFPA 101-2019 [ New Section after 13.3.4.3.7 ]

13.3.4.3.8 Emergency forces notification shall be provided in accordance with 9.6.4 .

Submitter Information Verification

Committee: SAF-AXM Submittal Date: Fri Jul 12 09:13:27 EDT 2019

Committee Statement

Committee It is reasonable to require automatic emergency forces notification where an assembly Statement: occupancy is required to be provided with a fire alarm system. (Related CI-6720) Response SR-6623-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

28 Eligible Voters 5 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Herrera, Mark A. Keberle, Kenneth F. Scandaliato, Steven J. Thomas, Jr., Elbert R. Tubbs, Jeffrey S.

Affirmative All Center, Eric Conner, William Cook, David Deacon, Nils Finnegan, Daniel P. Gandy, Max L. Goosman, Donald G. Hansen, Harold C. Hesson, Stephen C

Page 148 of 373

142 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Hollinger, David W. Humble, Jonathan Lake, John Lambert, Josh Morin, Kevin D. Pauls, Jake Peterson, Ryan Quinterno, Vincent Roether, Ed Rogers, Adam Ruling, Karl G. Schweitzer, Charles J. Sherman, Philip R. Shirey, Jeffrey

Page 149 of 373

143 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6628-NFPA 101-2019 [ Section No. 13.4.9 ]

13.4.9* Special Amusement Buildings.

A.13.4.9

Special amusement buildings are unique structures that can present challenges not common in assembly or other occupancies. Hazards in special amusement buildings can include industrial, electrical, pneumatic, stored energy systems, or other systems and equipment associated with the ride and/or show systems. Occupants are typically not familiar with their surroundings, and the provided exit access might not be apparent while the building is operating in show conditions. Additionally, special amusement buildings might present design challenges, which the authority having jurisdiction might need to consider. For example, a ride building containing a roller coaster might meet the height requirements for a high-rise structure but only contain one story of height and mezzanines or catwalks at upper levels for evacuation. Portions of a ride might exit and return into the building, traverse to an open structure, be surrounded by water, or contain an atrium. Each of these conditions presents challenges to the design of fire protection, fire alarm, and life safety systems, as well as the emergency action plan required in 13.7.13. Where a special amusement building on a temporary basis is installed inside another building on a temporary basis , such as within an exhibit hall, the special amusement building requirements apply only to the portions of the building used as a special amusement. For example, the smoke detectors required by 13.4.9.4.3 are not required to be connected to the building’s fire alarm system. Where installed in an exhibit hall, such smoke detectors are also required to comply with the provisions applicable to an exhibit.

13.4.9.1 General. 13.4.9.1.1* Special amusement buildings, regardless of occupant load, shall meet the requirements for assembly occupancies in addition to the requirements of 13.4.9, unless the special amusement building is a multilevel play structure that is not more than 10 ft (3050 mm) in height and has aggregate horizontal projections not exceeding 160 ft2 (15 m2).

A.13.4.9.1.1

The aggregate horizontal projections of a multilevel play structure are indicative of the number of children who might be within the structure and at risk from a fire or similar emergency. The word “aggregate” is used in recognition of the fact that the platforms and tubes that make up the multilevel play structure run above each other at various levels. In calculating the area of the projections, it is important to account for all areas that might be expected to be occupied within, on top of, or beneath the components of the structure when the structure is used for its intended function.

13.4.9.1.2* Special amusement buildings shall be subclassified as follows: (1) Class A: Permanently installed special amusement buildings that include an amusement ride or device in which patrons are contained or restrained and are unable to evacuate without the assistance of the ride operator (2) Class B: Permanently installed special amusement buildings that do not include an amusement ride or device, or that include an amusement ride or device from which patrons are able to self- evacuate (3) Class C: Temporary or mobile special amusement buildings

Page 150 of 373

144 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

A.13.4.9.1.2

An example of a Class A special amusement building would be a theme park attraction or dark ride where patrons are restrained inside a ride vehicle and guided through a building on a track. An example of a Class B special amusement building would be an escape room or theme park attraction where a patron can exit the building once the amusement or effects are stopped. Temporary rides such as a merry-go-round or train located in a mall would not meet the definition of a Class B special amusement building unless there was an element to the ride where a patron would become confused or is otherwise confined to the ride vehicle and unable to self-evacuate. See A.3.3.37.9 . An example of a Class C special amusement building would be a temporary haunted house, maze, or carnival attraction.

13.4.9.2 Means of Egress. 13.4.9.2.1 Exit Marking. 13.4.9.2.1.1 Exit marking shall be in accordance with Section 7.10. 13.4.9.2.1.2 Floor proximity exit signs shall be provided in accordance with 7.10.1.6. 13.4.9.2.1.3* In special amusement buildings where mazes, mirrors, or other designs are used to confound the egress path, approved directional exit marking that becomes apparent in an emergency shall be provided.

A.13.4.9.2.1.3

Consideration should be given to the provision of directional exit marking on or adjacent to the floor.

13.4.9.2.2 Illumination. 13.4.9.2.2.1* Actuation Unless otherwise permitted by 13.4.9.2.2.2 , actuation of the automatic sprinkler system, or any other suppression system, or actuation of a smoke detection system having an approved verification or cross-zoning operation capability shall provide for both of the following: (1) Increase in illumination in the means of egress to that required by Section 7.8 (2) Termination of any conflicting or confusing sounds and visuals

Page 151 of 373

145 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

A.13.4.9.2.2.1

Lighting levels within special amusement buildings are typically might be reduced to levels that are lower than those required by Section 7.8 for show purposes. In addition, projections, special effects, haze, and other theatrical elements might be combined, which can disorient occupants who are unfamiliar with the egress route. The activation of the automatic sprinkler system or smoke detection system must should immediately increase illumination to the required levels and stop all show elements that would continue to disorient or confuse occupants. Because of the delay in verification or cross-zoning of smoke detectors, positive alarm sequence should not be utilized when alarm-verification or cross-zoned smoke detectors is selected. In the context of a special amusement building, a conflicting or confusing sound or visual is any audio or visual device that is intended to quickly distract the attention the patron of a special amusement building for the purpose of frightening, confounding, disorienting, or otherwise capturing the attention of the patron. Examples of this include strobing and flashing lights, loud sound effects, scare or jump effects, loud music, animated figures, projected animation, and interactive games. These can all interfere with the fire alarm notification devices and live announcements from the attraction operator for the patron’s attention. In addition, effects that simulate the sound, sight and smell of flames or smoke will confuse the patron if they continue to operate when the fire alarm system has been activated. Some examples of audio and visuals that might occur in a special amusement building, but that might not constitute a conflicting sound or visual, include static or very slow-moving video or projected images, background music, steady state lighting, and ride vehicle triggered effects.

13.4.9.2.2.2* Class A special amusement buildings shall not be required to comply with 13.4.9.2.2.1 where all of the following conditions apply: (1) The emergency action plan required by 13.4.9.6.2 provides specific evacuation instructions to all attraction operators for cycling out the attraction when it is determined that meeting the requirements of 13.4.9.2.2.1 presents a hazard to ride patrons. (2) A means of manually complying with 13.4.9.2.2.1 is provided to the primary attraction operator. (3) Attraction operators are trained on the alternative procedures for evacuations. (4) The authority having jurisdiction approves the modifications.

A.13.4.9.2.2.2

Amusement rides and devices that contain or restrain their patrons such that they are unable to evacuate without the assistance of a ride operator present a unique challenge during an emergency. While ASTM F2291, Standard Practice for Design of Amusement Rides or Devices, provides for the design of evacuation paths in case the ride stops before completing its full cycle. The safest and fastest way to exit patrons during an emergency might be to “cycle out” by continuing ride operation until all patrons have exited the ride at the normal exit point (at the unload platform). If a patron were to attempt to exit the ride vehicle while the ride continues operation during an emergency, the patron may potentially be struck by the ride vehicle, or the ride’s safety systems might stop all ride motion, potentially extending the evacuation period. Because increasing the illumination of the means of egress along the ride and terminating any conflicting or confusing sounds or visuals while the ride is cycling out might entice the patrons to attempt to self-evacuate while the ride is in motion, the authority having jurisdiction and the owner are encouraged to work closely to develop a plan that implements the safest and most efficient method to exit the patrons from the ride, which might include continuing normal show operation during cycle out. In addition, the plan should assure that all ride operators and emergency responders understand their roles during cycle out, or during an evacuation if the ride cycle out is interrupted. The ride owner should work with the authority having jurisdiction from an early stage to develop a pre- incident plan in accordance with NFPA 1620 and any required or applicable provisions of 13.4.2.5.2 .

13.4.9.3 Interior Finish. Interior wall and ceiling finish materials complying with Section 10.2 shall be Class A throughout. 13.4.9.4 Detection, Alarm, and Communications Systems. 13.4.9.4.1 General. Page 152 of 373

146 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

13.4.9.4.1.1 Class A and Class B special amusement buildings shall be provided with an approved fire alarm system and smoke detection system in accordance with 9.6.1 and 13.4.9.4 . 13.4.9.4.1.2 Class C special amusement buildings shall be provided with an approved automatic smoke detection system in accordance with Section 9.6 . 13.4.9.4.2* Alarm Initiation. Actuation of any smoke detection system device shall sound an alarm at a constantly attended location on the premises. 13.4.9.4.2.1 In Class A and Class B special amusement buildings, the required fire alarm system shall be initiated by each of the following: (1) Manual fire alarm box located at a constantly attended location under continuous supervision by competent persons when the special amusement building is open to patrons (2) Required automatic sprinkler system (3) Required automatic detection systems 13.4.9.4.2.2 In Class C special amusement buildings, actuation of any smoke detection system device shall activate an audible and visible alarm in a constantly attended receiving station within the building when occupied for purposes of initiating emergency action. 13.4.9.4.3 Smoke Detection. Where the nature of the special amusement building is such that it operates in reduced lighting levels, the building shall be protected throughout by an approved automatic smoke detection system in accordance with Section 9.6. 13.4.9.4.4* Notification.

A.13.4.9.4.4

Notification in special amusement buildings should be considered carefully depending on the operation of the special amusement. Voice announcements are the required method. However, automatically transmitted evacuation instructions might not be appropriate in some rides when occupants are confined to a ride vehicle and unable to self-evacuate. In order to avoid confusion, manual voice announcements from the ride operator might be preferable to pre-recorded evacuation instructions for some rides.

13.4.9.4.4.1 Occupant notification for Class A and Class B special amusement buildings shall be in accordance with 13.3.4.3 . 13.4.9.4.4.2 Occupant notification for Class C special amusement buildings shall be in accordance with 13.3.4.3 ; however, positive alarm sequence shall not be permitted. 13.4.9.4.4.3* An automatic means for sounding the general evacuation alarm shall be provided when the constantly attended location is not staffed.

A.13.4.9.4.4.3

Special amusement buildings that contain rides tend be occupied after operating hours by maintenance staff. After-hours maintenance work might take place along the ride track or in an attached maintenance bay where ride vehicles are moved on and off spur tracks. When no ride operator is located at the constantly attended location to receive alarm signals, a means of automatically sounding the general evacuation signal should be provided for after-hours occupants.

Page 153 of 373

147 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

13.4.9.5 Automatic Sprinklers Extinguishment Requirements . 13.4.9.5.1* Every special amusement building, other than buildings or structures not exceeding 10 ft (3050 mm) in height and not exceeding 160 ft2 (15 m2) in aggregate horizontal projection, shall be protected throughout by an approved, supervised automatic sprinkler system installed and maintained in accordance with Section 9.7.

A.13.4.9.5.1

See A.13.4.9.1.1.

13.4.9.5.2 Temporary Water Supply. Where the special amusement building required to be sprinklered by 13.4.9.5.1 is movable or portable, the sprinkler water supply shall be permitted to be provided by an approved temporary means. 13.4.9.6 Operating Features. 13.4.9.6.1* Furnishings, Decorations, and Scenery. Furnishings shall be in accordance with 13.7.4 .

A.13.4.9.6.1

Special amusement buildings might simulate different structures, such as an outdoor scene where false walls and ceilings, commonly known as sets, are recreated indoors with various fabrics and materials used to simulate trees, leaves, or other items. Sets in special amusement buildings are often designed by entertainment companies familiar with Broadway-style stage productions. However, unlike stages and theaters, there are no requirements for smoke control or proscenium protection. The authority having jurisdiction should consider and evaluate the total quantity of material introduced into the space.

13.4.9.6.2* Emergency Action Plan. In Class A special amusement buildings, the emergency action plan shall be reviewed and approved by the authority having jurisdiction.

A.13.4.9.6.2

The evacuation plan for special amusement buildings should consider the safest and fastest way to remove occupants from the structure. When a ride stops within the special amusement building, removing occupants from the ride system might present an extended evacuation. Additionally, hazards associated with the ride and show system might present electrical and entanglement challenges to occupants unfamiliar with the building. Evacuation of special amusement buildings can also pose challenges to the local fire department if they are not familiar with the nature of the building or ride system. Specialized equipment for rescue, ride vehicle-specific tools for releasing doors, and high- energy ride vehicle hazard awareness might all be required when evacuating from a location other than a load/unload station. The ride owner should work with the authority having jurisdiction from an early stage to develop a pre- incident plan in accordance with NFPA 1620 and any required or applicable provisions of 13.4.2.5.2 .

Supplemental Information

File Name Description Approved 101-SR6628-Clean.docx Clean version of 13.4.9 and associated Annex A paras. For staff use.

Submitter Information Verification

Committee: SAF-AXM Submittal Date: Fri Jul 12 18:08:02 EDT 2019 Page 154 of 373

148 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Committee Statement

Committee The committee addressed many public inputs related to special amusements which requested Statement: updates to life safety systems due to new technologies in themed entertainment, fire suppression, detection, and building automation. The reorganization of this section allows for easier application for the user along with creating a classification system for special amusement buildings. Response SR-6628-NFPA 101-2019 Message: Public Comment No. 206-NFPA 101-2019 [Section No. A.13.4.9.5] Public Comment No. 207-NFPA 101-2019 [Section No. A.13.4.9.6]

Ballot Results

This item has passed ballot

28 Eligible Voters 5 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Herrera, Mark A. Keberle, Kenneth F. Scandaliato, Steven J. Thomas, Jr., Elbert R. Tubbs, Jeffrey S.

Affirmative All Center, Eric Conner, William Cook, David Deacon, Nils Finnegan, Daniel P. Gandy, Max L. Goosman, Donald G. Hansen, Harold C. Hesson, Stephen C Hollinger, David W. Humble, Jonathan Lake, John Lambert, Josh Morin, Kevin D. Pauls, Jake Peterson, Ryan Quinterno, Vincent Roether, Ed Page 155 of 373

149 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Rogers, Adam Ruling, Karl G. Schweitzer, Charles J. Sherman, Philip R. Shirey, Jeffrey

Page 156 of 373

150 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6636-NFPA 101-2019 [ New Section after 14.7.2.3 ]

14.7.2.4* Where permitted by the authority having jurisdiction, up to two of the emergency egress drills required by 14.7.2.3 shall be permitted to consist of alternative emergency drills for one or both of the following: (1) Targeted violence events (2) Natural hazard events

A.14.7.2.4

Many jurisdictions are now conducting other drills in addition to emergency egress drills. Targeted violence events can include everything from active shooters to use of other weapons intended to cause harm. Natural hazard drills generally consist of tornado or earthquake drills.

Submitter Information Verification

Committee: SAF-END Submittal Date: Mon Jul 15 14:57:53 EDT 2019

Committee Statement

Committee Many jurisdictions have been conducting other types of emergency drills in order to prepare the Statement: students and faculty to properly respond to different types of situations requiring evacuation, relocation, and defend in place actions. The addition of this language offers flexibility to those schools with input from the AHJ to determine if some of the historically required emergency egress drills can be set aside in order to prepare and practice for other types of emergencies. Response SR-6636-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

25 Eligible Voters 2 Not Returned 20 Affirmative All 3 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Beddow, Dorn J Lazebnik, Rosa

Affirmative All Alsulaiti, Mohammed Dannaway, Samuel S.

Page 157 of 373

151 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Day, Richard L. DiMisa, Richard M. Ellis, Jason D. Frangiamore, Keith S. Gandy, Max L. Haidacher, Jeffrey L. Hansen, Raymond N. Hopper, Howard Julka, Terrence J. Marks, Maria B. Merck, Richard E. Mertens, Matthew J. Naber, Michael Roeper, Kurt A. Savage, Sr., Michael L. Sinsigalli, Michael L. Stashak, Catherine L. Szachnowicz, Aleksy L.

Affirmative with Comment Aler, Clay P. No additional comment. Blaser, Scott J. Florida per statute now requires 20 type drills per year, this may help. Longhitano, Alfred J. In addition to the justification provided, under some scenarios, the right thing to do under fire conditions, such as sheltering, could be the same as for those other emergencies.

Page 158 of 373

152 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6639-NFPA 101-2019 [ Section No. 15.2.2.2.4.1 ]

15.2.2.2.4.1 Classroom doors and doors to other instructional spaces shall be permitted to be locked provided that the locking means is approved and all of the following conditions are met: (1) The locking means shall be capable of being engaged from the egress side of the door without opening the door. (2) The unlocking and unlatching from the egress side of the door shall be accomplished without the use of a key, tool, or special knowledge or effort. (3)* Two nonsimultaneous releasing operations motions shall be permitted where approved by the authority having jurisdiction.

A.15.2.2.2.4.1(3)

The installation of new hardware that necessitates two nonsimultaneous releasing motions on existing doors in existing educational occupancies in accordance with 15.2.2.2.4.1 (3) is permitted where such installation is necessary for compliance with the door locking criteria in 15.2.2.2.4.1 . In accordance with 43.1.4.5 , rehabilitation work performed for compliance with the Code’s existing occupancy requirements is exempt from Chapter 43 and the installation of such new equipment is not subject to Section 43.5 , which would require compliance with the new occupancy provisions. Where a new door is installed in an existing educational occupancy, the requirements of 14.2.2.2.4 apply.

(4) The releasing mechanism for unlocking and unlatching shall be located at a height not less than 34 in. (865 mm) and not exceeding 48 in. (1220 mm) above the finished floor. (5) Locks, if remotely engaged, shall be unlockable from the egress side of the door without the use of a key, tool, or special knowledge or effort. (6) The door shall be capable of being unlocked and opened from outside the room with the necessary key or other credential. (7) The locking means shall not modify the door closer, panic hardware, or fire exit hardware or impair their operation. (8) Modifications to fire door assemblies, including door hardware, shall be in accordance with NFPA 80. (9) The emergency action plan, required by 15.7.1, shall address the use of the locking and unlocking means from both sides of the door. (10) Staff shall be drilled in the engagement and release of the locking means, from both sides of the door, as part of the emergency egress drills required by 15.7.2.

Submitter Information Verification

Committee: SAF-END Submittal Date: Mon Jul 15 16:27:57 EDT 2019

Committee Statement

Committee It is the intent of 15.2.2.2.4.1(3) to permit the installation of new equipment that requires two Statement: releasing motions on existing doors to meet the locking provisions of 15.2.2.2.4.1. It was unclear whether the installation of new equipment would invoke the requirements of Section 43.5 for modifications, which would send the user to Chapter 14 for new educational occupancies, limiting the arrangement to one releasing operation. Chapter 43 is clear in 43.1.4.5 that work performed for compliance with the existing occupancy requirements is exempt from its requirements. The proposed annex note clarifies the intent.

Page 159 of 373

153 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

The END committee requests the CC also add the annex note to A.43.X since it relates to a fundamental concept of Chapter 43 (A.43.4.4 might be an appropriate location).

The revision also changes 'releasing operations' to 'releasing motions' in response to direction from the correlating committee with regard to the terminology change in Ch. 7. Response SR-6639-NFPA 101-2019 Message: Public Comment No. 45-NFPA 101-2019 [Section No. 15.2.2.2.4]

Ballot Results

This item has passed ballot

25 Eligible Voters 2 Not Returned 19 Affirmative All 2 Affirmative with Comments 2 Negative with Comments 0 Abstention

Not Returned Beddow, Dorn J Lazebnik, Rosa

Affirmative All Alsulaiti, Mohammed Dannaway, Samuel S. Day, Richard L. DiMisa, Richard M. Ellis, Jason D. Frangiamore, Keith S. Gandy, Max L. Haidacher, Jeffrey L. Hopper, Howard Julka, Terrence J. Longhitano, Alfred J. Marks, Maria B. Merck, Richard E. Mertens, Matthew J. Naber, Michael Savage, Sr., Michael L. Sinsigalli, Michael L. Stashak, Catherine L. Szachnowicz, Aleksy L.

Affirmative with Comment Aler, Clay P. No additional comment. Page 160 of 373

154 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Blaser, Scott J. the word motion better matches with the intent

Negative with Comment Hansen, Raymond N. This change has previously been rejected by the membership body. The argument was made in the TC that this would provide a way to easily add a locking feature inside the room to doors that now only lock from outside the room. However, 15.2.2.2.4.1(6) requires that such a lock be operable from outside the room. The easiest option for schools is to just change out the existing door knob/lock-set to one having a locking feature operable from both inside and outside of the room. The surface-mounted deadbolt envisioned by some members of the TC would be prohibited because it would not be operable from outside the room. This proposed change is likely to create confusion and non-compliance by building owners/users. Roeper, Kurt A. The annex note does not appear to be properly worded. "where such installation is necessary for compliance" is not appropriate language as 15.2.2.2.4.1 is 'shall be permitted'. The text "where such installation is necessary for compliance" should be struck and the sentence restructured.

Page 161 of 373

155 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6584-NFPA 101-2019 [ New Section after 15.3.4.3.2.2 ]

15.3.4.4 Reserved. 15.3.4.5 Risk Analysis for Mass Notification Systems. A risk analysis in accordance with Section 9.14 shall be performed to determine if a mass notification system is required upon replacement of the building fire alarm system.

Submitter Information Verification

Committee: SAF-END Submittal Date: Tue Jul 09 10:08:41 EDT 2019

Committee Statement

Committee Statement: (See CI-6913) Response Message: SR-6584-NFPA 101-2019

Ballot Results

This item has passed ballot

25 Eligible Voters 2 Not Returned 21 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Beddow, Dorn J Lazebnik, Rosa

Affirmative All Alsulaiti, Mohammed Dannaway, Samuel S. Day, Richard L. DiMisa, Richard M. Ellis, Jason D. Frangiamore, Keith S. Gandy, Max L. Haidacher, Jeffrey L. Hansen, Raymond N. Hopper, Howard Julka, Terrence J. Longhitano, Alfred J.

Page 162 of 373

156 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Marks, Maria B. Merck, Richard E. Mertens, Matthew J. Naber, Michael Roeper, Kurt A. Savage, Sr., Michael L. Sinsigalli, Michael L. Stashak, Catherine L. Szachnowicz, Aleksy L.

Affirmative with Comment Aler, Clay P. No additional comment. Blaser, Scott J. affirm

Page 163 of 373

157 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6637-NFPA 101-2019 [ New Section after 15.7.2.3 ]

15.7.2.4* Where permitted by the authority having jurisdiction, up to two of the emergency egress drills required by 15.7.2.3 shall be permitted to consist of alternative emergency drills for one or both of the following: (1) Targeted violence events (2) Natural hazard events

A.15.7.2.4

Many jurisdictions are now conducting other drills in addition to emergency egress drills. Targeted violence events can include everything from active shooters to use of other weapons intended to cause harm. Natural hazard drills generally consist of tornado or earthquake drills.

Submitter Information Verification

Committee: SAF-END Submittal Date: Mon Jul 15 15:07:51 EDT 2019

Committee Statement

Committee Many jurisdictions have been conducting other types of emergency drills in order to prepare the Statement: students and faculty to properly respond to different types of situations requiring evacuation, relocation, and defend in place actions. The addition of this language offers flexibility to those schools with input from the AHJ to determine if some of the historically required emergency egress drills can be set aside in order to prepare and practice for other types of emergencies.

Response SR-6637-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

25 Eligible Voters 2 Not Returned 21 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Beddow, Dorn J Lazebnik, Rosa

Affirmative All Alsulaiti, Mohammed Dannaway, Samuel S. Page 164 of 373

158 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Day, Richard L. DiMisa, Richard M. Ellis, Jason D. Frangiamore, Keith S. Gandy, Max L. Haidacher, Jeffrey L. Hansen, Raymond N. Hopper, Howard Julka, Terrence J. Longhitano, Alfred J. Marks, Maria B. Merck, Richard E. Mertens, Matthew J. Naber, Michael Roeper, Kurt A. Savage, Sr., Michael L. Sinsigalli, Michael L. Stashak, Catherine L. Szachnowicz, Aleksy L.

Affirmative with Comment Aler, Clay P. No additional comment. Blaser, Scott J. Florida per statute now requires 20 type drills per year, this may help.

Page 165 of 373

159 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6638-NFPA 101-2019 [ Section No. 16.3.5.1 ]

16.3.5.1 Any required sprinkler systems shall be All new day care occupancies shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.

Submitter Information Verification

Committee: SAF-END Submittal Date: Mon Jul 15 15:12:01 EDT 2019

Committee Statement

Committee This revision supports the suggested text in CI 6910. Where a new day care is added to an Statement: existing unsprinklered occupancy, this text would require a sprinkler system in the new day care.

Fire sprinklers in day care are effective. According to http://sprinklersaves.com/?s=day+care there are several recent day care facilities where sprinklers provided protection.

Approximately one in ten (11%) structure fires in educational properties in 2011-2015 occurred in day care properties.

Response SR-6638-NFPA 101-2019 Message: Public Comment No. 195-NFPA 101-2019 [Section No. 16.3.5.1]

Ballot Results

This item has passed ballot

25 Eligible Voters 2 Not Returned 20 Affirmative All 1 Affirmative with Comments 2 Negative with Comments 0 Abstention

Not Returned Beddow, Dorn J Lazebnik, Rosa

Affirmative All Alsulaiti, Mohammed Dannaway, Samuel S. Day, Richard L. DiMisa, Richard M. Ellis, Jason D. Frangiamore, Keith S.

Page 166 of 373

160 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Gandy, Max L. Haidacher, Jeffrey L. Hansen, Raymond N. Hopper, Howard Julka, Terrence J. Marks, Maria B. Merck, Richard E. Mertens, Matthew J. Naber, Michael Roeper, Kurt A. Savage, Sr., Michael L. Sinsigalli, Michael L. Stashak, Catherine L. Szachnowicz, Aleksy L.

Affirmative with Comment Blaser, Scott J. affirm

Negative with Comment Aler, Clay P. I think an exception for buildings of less than 1,000 gsf consisting of a single open classroom consistent with that allowed by NFPA 101 14.3.5.2 should be added. Longhitano, Alfred J. In my opinion, this cannot be justified as a MINIMUM standard to provide life safety. I doubt that anyone can convince me that there is no possibility of a facility being safe for use as a day-care unless it is protected by automatic sprinklers.

Page 167 of 373

161 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6640-NFPA 101-2019 [ Section No. 17.2.2.2.6.1 ]

17.2.2.2.6.1 Classroom doors and doors to other client care spaces shall be permitted to be locked provided that the locking means is approved and all of the following conditions are met: (1) The locking means shall be capable of being engaged from the egress side of the door without opening the door. (2) The unlocking and unlatching from the egress side of the door shall be accomplished without the use of a key, tool, or special knowledge or effort. (3)* Two nonsimultaneous releasing operations motions shall be permitted where approved by the authority having jurisdiction.

A.17.2.2.2.6.1(3)

The installation of new hardware that necessitates two nonsimultaneous releasing motions on existing doors in existing educational occupancies in accordance with 17.2.2.2.6.1 (3) is permitted where such installation is necessary for compliance with the door locking criteria in 17.2.2.2.6.1 . In accordance with 43.1.4.5 , rehabilitation work performed for compliance with the Code’s existing occupancy requirements is exempt from Chapter 43 and the installation of such new equipment is not subject to Section 43.5 , which would require compliance with the new occupancy provisions. Where a new door is installed in an existing educational occupancy, the requirements of 17.2.2.2.6 apply.

(4) The releasing mechanism for unlocking and unlatching shall be located at a height not less than 34 in. (865 mm) and not exceeding 48 in. (1220 mm) above the finished floor. (5) Locks, if remotely engaged, shall be unlockable from the egress side of the door without the use of a key, tool, or special knowledge or effort. (6) The door shall be capable of being unlocked and opened from outside the room with the necessary key or other credential. (7) The locking means shall not modify the door closer, panic hardware, or fire exit hardware or impair their operation. (8) Modifications to fire door assemblies, including door hardware, shall be in accordance with NFPA 80. (9) The emergency action plan, required by 17.7.1, shall address the use of the locking and unlocking means from both sides of the door. (10) Staff shall be drilled in the engagement and release of the locking means, from both sides of the door, as part of the emergency egress drills required by 17.7.2.

Submitter Information Verification

Committee: SAF-END Submittal Date: Mon Jul 15 16:33:04 EDT 2019

Committee Statement

Committee It is the intent of 17.2.2.2.6.1(3) to permit the installation of new equipment that requires two Statement: releasing motions on existing doors to meet the locking provisions of 17.2.2.2.6.1. It was unclear whether the installation of new equipment would invoke the requirements of Section 43.5 for modifications, which would send the user to Chapter 16 for new day-care occupancies, limiting the arrangement to one releasing operation. Chapter 43 is clear in 43.1.4.5 that work performed for compliance with the existing occupancy requirements is exempt from its requirements. The proposed annex note clarifies the intent.

Page 168 of 373

162 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

The END committee requests the CC also add the annex note to A.43.X since it relates to a fundamental concept of Chapter 43 (A.43.4.4 might be an appropriate location).

The revision also changes 'releasing operations' to 'releasing motions' in response to direction from the correlating committee with regard to the terminology change in Ch. 7. Response SR-6640-NFPA 101-2019 Message: Public Comment No. 250-NFPA 101-2019 [Section No. 17.2.2.2.6]

Ballot Results

This item has passed ballot

25 Eligible Voters 2 Not Returned 18 Affirmative All 2 Affirmative with Comments 3 Negative with Comments 0 Abstention

Not Returned Beddow, Dorn J Lazebnik, Rosa

Affirmative All Alsulaiti, Mohammed Dannaway, Samuel S. Day, Richard L. DiMisa, Richard M. Ellis, Jason D. Frangiamore, Keith S. Gandy, Max L. Haidacher, Jeffrey L. Hopper, Howard Julka, Terrence J. Marks, Maria B. Merck, Richard E. Mertens, Matthew J. Naber, Michael Savage, Sr., Michael L. Sinsigalli, Michael L. Stashak, Catherine L. Szachnowicz, Aleksy L.

Affirmative with Comment Aler, Clay P. No additional comment. Blaser, Scott J. Page 169 of 373

163 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

the word motion better matches with the intent

Negative with Comment Hansen, Raymond N. This change has previously been rejected by the membership body. The argument was made in the TC that this would provide a way to easily add a locking feature inside the room to doors that now only lock from outside the room. However, 17.2.2.2.6.1(6) requires that such a lock be operable from outside the room. The easiest option for schools is to just change out the existing door knob/lock-set to one having a locking feature operable from both inside and outside of the room. The surface-mounted deadbolt envisioned by some members of the TC would be prohibited because it would not be operable from outside the room. This proposed change is likely to create confusion and non-compliance by building owners/users. Longhitano, Alfred J. Requiring that the door be unlockable from the corridor side mandates a much more costly installation than can be justified in an existing facility. Roeper, Kurt A. The annex note does not appear to be properly worded. Chapter 17 is Existing Day Care, not Existing Education. Additionally, "where such installation is necessary for compliance" is not appropriate language as 17.2.2.2.6.1 is 'shall be permitted'. The text "where such installation is necessary for compliance" should be struck and the sentence restructured.

Page 170 of 373

164 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6655-NFPA 101-2019 [ Section No. 18.1.4.2 ]

18.1.4.2 Special Definitions. The following is a list of special terms used in this chapter: (1) Ambulatory Health Care Occupancy. See 3.3.198.1. (2) Deep-Fat Frying. See 3.3.56. (3) Gross Floor Area (Health Care and Ambulatory Health Care Occupancies). See 3.3.22.2.3 . (4) Hospital. See 3.3.152.) (5) Limited Care Facility. See 3.3.93.2. (6) Nursing Home. See 3.3.150.2. (7) Self-Preservation Capability (Health Care and Ambulatory Health Care Occupancies). See 3.3.253.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Fri Jul 19 15:05:19 EDT 2019

Committee Statement

Committee Statement: The revision is intended to correlate with SR-6654. Response Message: SR-6655-NFPA 101-2019 Public Comment No. 222-NFPA 101-2019 [New Section after 18.1.4.2]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Page 171 of 373

165 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 172 of 373

166 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6603-NFPA 101-2019 [ Section No. 18.1.6.1 ]

18.1.6.1 Health care occupancies shall be limited to the building construction types specified in Table 18.1.6.1, unless otherwise permitted by 18.1.6.2 through 18.1.6.6. (See 8.2.1.) Table 18.1.6.1 Construction Type Limitations

Total Number of Stories of Buildingb Construction Type Sprinklereda 1 2 3 ≥4 I(442) Yes X X X X No NP NP NPNP I(332) Yes X X X X No NP NP NPNP II(222) Yes X X X X No NP NP NPNP II(111) Yes X X XNP No NP NP NPNP II(000) Yes X NP NPNP No NP NP NPNP III(211) Yes X NP NPNP No NP NP NPNP III(200) Yes NP NP NPNP No NP NP NPNP

IV(2HH) Yes X NPc,d NPc NPc No NP NP NPNP V(111) Yes X NP NPNP No NP NP NPNP V(000) Yes NP NP NPNP No NP NP NPNP

X: Permitted. NP: Not permitted. The total number of stories of the building is required to be determined as follows: Notes: (1) The total number of stories is to be counted starting with the level of exit discharge and ending with the highest occupiable story of the building. (2) Stories below the level of exit discharge are not counted as stories. (3) Interstitial spaces used solely for building or process systems directly related to the level above or below are not considered a separate story. (4) A mezzanine in accordance with 8.6.10 is not counted as a story.

aSprinklered throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7. (See 18.3.5.)

bBasements are not counted as stories.

cUp to 7 stories permitted for buildings complying with 7.2.5.6.1.1 of NFPA 5000 and including four stories in height permitted for buildings complying with 4.5.6.1.1 of NFPA 220 .

d Up to and including two stories in height permitted for buildings complying with 4.5.6.1.2 of NFPA 220.

Page 173 of 373

167 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Wed Jul 10 12:44:41 EDT 2019

Committee Statement

Committee The revision is intended for consistency with the mass timber construction limits of NFPA Statement: 220 and NFPA 5000. Response Message: SR-6603-NFPA 101-2019

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 27 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A.

Page 174 of 373

168 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Abstention Koffel, William E. In accordance with the policy of the Standards Council, I have abstained from voting on this Second Revision.

Page 175 of 373

169 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6656-NFPA 101-2019 [ Section No. 18.2.5.7 ]

18.2.5.7 Health Care Suites. 18.2.5.7.1 General. 18.2.5.7.1.1 Suite Permission. Suites complying with 18.2.5.7 shall be permitted to be used to meet the corridor access requirements of 18.2.5.6. 18.2.5.7.1.2* Suite Separation. Suites shall be separated from the remainder of the building, and from other suites, by walls and doors meeting the requirements of 18.3.6.2 through 18.3.6.5. 18.2.5.7.1.3 Suite Hazardous Contents Areas. (A)* Intervening rooms shall not be hazardous areas as defined by 18.3.2. (B) Hazardous areas within a suite shall be separated from the remainder of the suite in accordance with 18.3.2.1, unless otherwise provided in 18.2.5.7.1.3(C). (C)* Hazardous areas within a suite shall not be required to be separated from the remainder of the suite where complying with all of the following: (1) The suite is primarily a hazardous area. (2) The suite is protected by an approved automatic smoke detection system in accordance with Section 9.6. (3) The suite is separated from the rest of the health care facility as required for a hazardous area by 18.3.2.1. 18.2.5.7.1.4 Suite Subdivision. The subdivision of suites shall be by means of noncombustible or limited-combustible partitions or partitions constructed with fire-retardant-treated wood enclosed with noncombustible or limited- combustible materials, and such partitions shall not be required to be fire rated. 18.2.5.7.2 Sleeping Suites. Sleeping suites shall be in accordance with the following: (1) Patient care sleeping suites shall comply with the provisions of 18.2.5.7.2.1 through 18.2.5.7.2.4. (2) Sleeping suites not for patient care shall comply with the provisions of 18.2.5.7.4. 18.2.5.7.2.1 Patient Care Sleeping Suite Supervision. (A) Patient care sleeping suites shall be provided with constant staff supervision within the suite. (B)* Patient care sleeping suites shall be arranged in accordance with one of the following: (1)* Patient sleeping rooms within patient care sleeping suites shall provide one of the following: (a) The patient sleeping rooms shall be arranged to allow for direct supervision from a normally attended location within the suite, such as is provided by glass walls, and cubicle curtains shall be permitted. (b) Any patient sleeping rooms without the direct supervision required by 18.2.5.7.2.1(B)(1)(a) shall be provided with smoke detection in accordance with Section 9.6 and 18.3.4. (2) Patient care sleeping suites shall be provided with a total (complete) coverage automatic smoke detection system in accordance with 9.6.2.9 and 18.3.4. Page 176 of 373

170 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

18.2.5.7.2.2 Patient Care Sleeping Suite Means of Egress. (A)* Patient care sleeping suites shall have exit access to a corridor complying with 18.3.6 or to a horizontal exit, directly from the suite. (B)

Patient care sleeping suites of more than 1000 ft2 (93 m2) gross shall have not less than two exit access doors remotely located from each other. (C)* For suites requiring two exit access doors, one of the exit access doors from the suite shall be permitted to be to one of the following: (1) An exit stair (2) An exit passageway (3) An exit door to the exterior (4) Another suite, provided that the separation between the suites complies with the corridor requirements of 18.3.6.2 through 18.3.6.5 18.2.5.7.2.3 Patient Care Sleeping Suite Maximum Size. (A) Reserved. (B)

Patient care sleeping suites shall not exceed 7500 ft2 (700 m2) gross floor area , unless otherwise provided in 18.2.5.7.2.3(C). (C)

Patient care sleeping suites greater than 7500 ft2 (700 m2) gross floor area and not exceeding 10,000 ft2 (930 m2) gross floor area shall be permitted where both of the following are provided in the suite: (1)* Direct visual supervision in accordance with 18.2.5.7.2.1(B)(1)(a) (2) Total (complete) coverage automatic smoke detection in accordance with 9.6.2.9 and 18.3.4 18.2.5.7.2.4 Patient Care Sleeping Suite Travel Distance. (A) Travel distance between any point in a patient care sleeping suite and an exit access door to another suite, an exit access corridor door, or a horizontal exit door from that suite shall not exceed 100 ft (30 m). (B) Travel distance between any point in a patient care sleeping suite and an exit shall not exceed 200 ft (61 m). 18.2.5.7.3 Patient Care Non-Sleeping sleeping Suites. Nonsleeping suites shall be in accordance with the following: (1) Nonsleeping suites for patient care shall comply with the provisions of 18.2.5.7.3.1 through 18.2.5.7.3.3. (2) Nonsleeping suites not for patient care shall comply with the provisions of 18.2.5.7.4. 18.2.5.7.3.1 Patient Care Non-Sleeping sleeping Suite Means of Egress. (A) Patient care nonsleeping suites shall have exit access to a corridor complying with 18.3.6 or to a horizontal exit, directly from the suite. (B)

Patient care nonsleeping suites of more than 2500 ft2 (230 m2) gross shall have not less than two exit access doors remotely located from each other.

Page 177 of 373

171 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

(C)* For suites requiring two exit access doors, one of the exit access doors shall be permitted to be to one of the following: (1) An exit stair (2) An exit passageway (3) An exit door to the exterior (4) Another suite, provided that the separation between the suites complies with the corridor requirements of 18.3.6.2 through 18.3.6.5. 18.2.5.7.3.2 Patient Care Non-Sleeping sleeping Suite Maximum Size. (A)

Nonsleeping suites shall not exceed 12,500 ft2 (1160 m2) gross floor area , unless otherwise provided in 18.2.5.7.3.2(B). (B)

Nonsleeping suites greater than 12,500 ft2 (1160 m2) gross floor area and not exceeding 15,000 ft2 (1390 m2) gross floor area shall be permitted where provided with total (complete) coverage automatic smoke detection in accordance with 9.6.2.9 and 18.3.4. 18.2.5.7.3.3 Patient Care Non -Sleeping sleeping Suite Travel Distance. (A) Travel distance within a nonsleeping suite to an exit access door to another suite, an exit access corridor door, or a horizontal exit door from the suite shall not exceed 100 ft (30 m). (B) Travel distance between any point in a nonsleeping suite and an exit shall not exceed 200 ft (61 m). 18.2.5.7.4 Non-Patient-Care Suites. The egress provisions for non-patient-care suites shall be in accordance with the primary use and occupancy of the space.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 10:52:15 EDT 2019

Committee Statement

Committee The revision replaces the term 'gross' with 'gross floor area' in six places to correlate with the Statement: new definition added to Chapter 3 to clarify how the area of a suite should be determined. (Note that other underlining is extraneous.) Response SR-6656-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Page 178 of 373

172 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 179 of 373

173 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6657-NFPA 101-2019 [ Section No. 18.3.6.3.7 ]

18.3.6.3.7 Powered doors that comply with the requirements of 7.2.1.9 shall not be required to meet the latching requirements of 18.3.6.3.5, provided that all of the following criteria are met: (1) The door is equipped with a means for keeping the door closed that is acceptable to the authority having jurisdiction. (2) The device used is capable of keeping the door fully closed if a force of 5 lbf (22 N) is applied at the latch edge of a swinging door and applied in any direction to a sliding or folding door, whether or not power is applied. (3) The power-assist mechanism ceases Where door leaves are operated by power by any automatic mechanism, the automatic opening of the doors shall cease to function upon operation of approved smoke detectors installed in accordance with the provisions of NFPA 72 for door release service .

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 11:18:30 EDT 2019

Committee Statement

Committee Section 7.2.1.9 has two options: (1) Doors operated by power by any automatic mechanism and (2) Statement: power assisted manual operation.

7.2.1.9.1* General. Where means of egress door leaves are operated by power by any automatic mechanism or are provided with power-assisted manual operation, the design shall be such that, in the event of power failure, the leaves open manually to allow egress travel or close when necessary to safeguard the means of egress.

This change would not allow doors to automatically open, but it would allow power assisted door to be used without mandating smoke detection to shut down that operation. From BHMA A156.19 Definition of a Power Assist Door: "A door with a power mechanism that activates by pushing or pulling the door, reducing the opening resistance of a self-closing door to allow easier manual opening of the door. If the opening force on the door is released, the door shall come to a stop and either immediately begin to close, or begin to close after a predetermined time."

The time to close is limited to a few seconds in BHMA A156.19. There is no reason to make that function cease. The only function that should cease is when the door automatically opens upon approach of a person (or smoke) and the text has been changed to reflect that.

The new text clarifies that smoke detectors are to be installed in accordance with the specific provision in NFPA 72 for door release service. Response SR-6657-NFPA 101-2019 Message: Public Comment No. 97-NFPA 101-2019 [Section No. 18.3.6.3.7] Public Comment No. 193-NFPA 101-2019 [Section No. 18.3.6.3.7]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned

Page 180 of 373

174 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 181 of 373

175 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6659-NFPA 101-2019 [ Section No. 18.3.7.1 ]

Detail SR-6658 18.3.7.1 Buildings containing health care facilities shall be subdivided by smoke barriers (see 18.2.4.3), unless otherwise permitted by 18.3.7.2 and 18.3.7.3 , as follows: (1) To divide every story used by inpatients for sleeping or treatment into not less than two smoke compartments (2) To divide every story having an occupant load of 50 or more persons, regardless of use, into not less than two smoke compartments (3) To limit the size of each smoke compartment required by 18.3.7.1(1) and 18.3.7.1(2) to an area not exceeding one of the following:

(a) 22,500 ft2 (2100 m2) gross floor area in hospital smoke compartments where any patient sleeping room is configured for two or more patients

(b) 40,000 ft2 (3720 m2) gross floor area in hospital smoke compartments where all patient sleeping rooms are configured for only one patient, in which case suites in accordance with 18.2.5.7 shall be permitted where every occupiable sleeping room within the suite is configured for only one patient

(c) 40,000 ft2 (3720 m2) gross floor area in hospital smoke compartments that contain no patient sleeping rooms

(d) 22,500 ft2 (2100 m2) gross floor area in nursing homes and limited care facilities (4) To separate atriums in accordance with 8.6.7 18.3.7.3 , in which case no limitation in the atrium size is required (5) To limit the travel distance from any point to reach a door in the required smoke barrier to a distance not exceeding 200 ft (61 m)

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 11:42:51 EDT 2019

Committee Statement

Committee The revision correlates with the definition of 'gross floor area (health care and ambulatory health Statement: care occupancies)' added to Chapter 3 to clarify how to determine the area of smoke compartments and suites. Response SR-6659-NFPA 101-2019 Message: Public Comment No. 73-NFPA 101-2019 [Section No. 18.3.7.1]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments Page 182 of 373

176 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 183 of 373

177 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6660-NFPA 101-2019 [ Section No. 18.3.7.3 ]

18.3.7.3 Any required smoke barrier shall be constructed in accordance with Section 8.5 and shall have a minimum 1-hour fire resistance rating, unless otherwise permitted by one of the following: (1) This requirement shall not apply where an atrium is used, and in which case both of the following criteria also shall apply: (a) Smoke barriers shall be permitted to terminate at an atrium wall constructed in accordance with 8.6.7(1)(c). (b) Not less than two separate smoke compartments shall be provided on each floor. (2)* Smoke dampers shall not be required in duct penetrations of smoke barriers in fully ducted heating, ventilating, and air-conditioning systems. (3) The provisions of 8.5.6.5 and 8.5.7.2 shall not apply.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 11:52:30 EDT 2019

Committee Statement

Committee The revision is intended to coordinate with changes to 18.3.7.1 in Detail SR-6658. (The Statement: revision only changes 'and' to 'in which case'.) Response SR-6660-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip

Page 184 of 373

178 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 185 of 373

179 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6605-NFPA 101-2019 [ Section No. 18.4.2 ]

18.4.2 Underground Structures and Limited Access Buildings Structures . Limited access buildings or Underground structures and limited access portions of buildings shall not be used for patient sleeping rooms and shall structures shall comply with Section 11.7.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Wed Jul 10 16:04:27 EDT 2019

Committee Statement

Committee The revision is intended for consistency with Ch. 11. The requirements of Ch. 18 adequately Statement: address egress provision for patient sleeping areas. Response SR-6605-NFPA 101-2019 Message: Public Comment No. 226-NFPA 101-2019 [Section No. 18.4.2]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Page 186 of 373

180 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 187 of 373

181 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6606-NFPA 101-2019 [ Section No. 18.7.1.4 ]

18.7.1.4* Fire drills in health care occupancies shall include the simulation of emergency fire conditions and, except as indicated in 18.7.1.7 , include activation of the fire alarm system notification appliances.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Wed Jul 10 16:11:44 EDT 2019

Committee Statement

Committee 18.7.1.7 is an exception to 18.7.1.4. AHJ's are requiring facilities to operate notification appliance Statement: even at night in spite of what 18.7.1.7 says. As written, this section does indicate that 18.7.1.7 is an exception to the requirement to activate notification appliances. This change will clarify that patients do not have to be unnecessarily bothered by notification appliances during drills on the third shift. Response SR-6606-NFPA 101-2019 Message: Public Comment No. 98-NFPA 101-2019 [Section No. 18.7.1.4]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W.

Page 188 of 373

182 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 189 of 373

183 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6661-NFPA 101-2019 [ Section No. 18.7.5.7 ]

18.7.5.7 Soiled Linen and Trash Receptacles. 18.7.5.7.1* Soiled linen or trash collection receptacles shall not exceed 64 gal (242 L) in capacity and shall meet all of the following requirements: with capacities greater than 64 gal (242 L) shall be located in a hazardous area when not attended.

The average density of container capacity in a room or space shall not exceed 1.0 gal/ft 2 (40.7 L/m 2 ). Mobile soiled linen or trash collection receptacles with capacities greater than 64 gal (242 L) shall be located in a room protected as a hazardous area when not attended. Container size and density shall not be limited in hazardous areas.

A.18.7.5.7.1

It is not the intent to permit collection receptacles with a capacity greater than 32 64 gal (121 242 L) to be positioned at or near a nurses’ station based on the argument that such nurses’ station is constantly attended. The large collection receptacle itself needs to be actively attended by staff. Staff might leave the large receptacle in the corridor outside a patient room while entering the room to collect soiled linen or trash, but staff is expected to return to the receptacle, move on to the next room, and repeat the collection function. Where staff is not actively collecting material for placement in the receptacle, the receptacle is to be moved to a room protected as a hazardous area.

18.7.5.7.2* Containers greater than 64 gal (242 L) used solely for recycling clean waste or for patient records awaiting destruction shall be permitted to be excluded from the requirements of 18.7.5.7.1 where all the following conditions are met: (1) Each container shall be limited to a maximum capacity of 96 gal (363 L)., except as permitted by 18.7.5.7.2(2) or (3). * Containers with capacities greater than 96 gal (363 L) shall be located in a room protected as a hazardous area when not attended.

A.18.7.5.7.2(2)

See 18.7.5.7.1(3) .

Container size shall not be limited in hazardous areas. (2) Containers for combustibles shall be labeled and listed as meeting the requirements of FM Approval 6921, Approval Standard for Containers for Combustible Waste; however, such testing, listing, and labeling shall not be limited to FM Approvals.

Page 190 of 373

184 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

A.18.7.5.7.2

It is the intent that this provision permits recycling of bottles, cans, paper, and similar clean items that do not contain grease, oil, flammable liquids, or significant plastic materials using larger containers or several adjacent containers and not require locating such containers in a room protected as a hazardous area. Containers for medical records awaiting shredding are often larger than 32 64 gal (121 242 L). These containers are not to be included in the calculations and limitations of 18.7.5.7.1. There is no limit on the number of these containers, as FM Approval 6921, Approval Standard for Containers for Combustible Waste, ensures that the fire will not spread outside of the container. FM approval standards are written for use with FM Approvals. The tests can be conducted by any approved laboratory. The portions of the standard referring to FM Approvals are not included in this reference.

18.7.5.7.3 The provisions of 10.3.8, applicable to containers for waste or linen, shall not apply.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 12:01:55 EDT 2019

Committee Statement

Committee The revisions were drafted by a task group on waste container sizes, which provided the following Statement: substantiation:

1. Many standard patient recycling containers currently in use in health care facilities slightly exceed 32 gallons

2. Unable to locate any patient recycling containers meeting FM Approval Standard 6921 which also comply with HIPPA for patient privacy by providing a securable container. This limits container size to 32 gallons for patient records.

3. A kitchen located in a health care occupancy is not permitted to be provided with a standard size trash can of 50 gallons.

4. NFPA Research Report Structure Fires in Health Care Facilities 2011 – 2015 indicates that trash/rubbish/waste is not a major contributor to injuries related to a fire event. There was no documented instances of fires spreading from one trash can to another. A summary of the data in the report is below:

Number of Fires Number of Injuries Number of Deaths

Hospitals 320 3 0

Nursing Homes 120 1 0

Hospitals and Hospices 100 1 0

Mental Health Facilities 50 0 0

Clinics and Dr. Offices 50 0 0

a. The NFPA report did not distinguish between trash/rubbish/waste container located outside vs. inside.

5. Modifying the 32 gallon limitation to 64 gallons would make the requirement consistent with the threshold for a room storing soiled linen or trash to be considered a hazardous area is 64 gallons in the Protections for Hazards section.

Response SR-6661-NFPA 101-2019 Message:

Page 191 of 373

185 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Public Comment No. 48-NFPA 101-2019 [Section No. 18.7.5.7.1]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 26 Affirmative All 0 Affirmative with Comments 2 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 192 of 373

186 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Negative with Comment Bush, Kenneth E. The revised wording for 18.7.5.7.2 would permit containers of 64 gal or less capacity used solely for recycling clean waste or for patient records awaiting destruction to be used without restriction. This is a significant change from the existing Code text that has not been provided with sufficient technical justification. Koffel, William E. I remain concerned that this relaxation is too significant without a density restriction. Other than not normally expected in a health care occupancy, what would prevent one from located several large containers (but less than 64 gal) in a room and in close proximity to each other?

Page 193 of 373

187 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6600-NFPA 101-2019 [ Section No. 18.7.7.1 ]

18.7.7.1 New engineered smoke control systems shall be designed, installed, tested, and maintained in accordance with NFPA 92 Section 9.3 .

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Wed Jul 10 11:58:35 EDT 2019

Committee Statement

Committee Section 9.3 provides the requirements for smoke control systems via reference to NFPA Statement: 92. Response Message: SR-6600-NFPA 101-2019

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J.

Page 194 of 373

188 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 195 of 373

189 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6607-NFPA 101-2019 [ Section No. 18.7.9.3 ]

18.7.9.3 For repair, renovation, rehabilitation activities or preparation for construction rehabilitation activities of a duration not greater than 30 days that do not cause the classification of the construction area as a hazardous area as identified in 18.3.2, fire-retardant flame-resistant plastic in accordance with NFPA 701, or equivalent, shall be permitted to be used to separate the construction area from the other spaces. provided that both the construction area and the adjacent occupied spaces are protected by an approved automatic sprinkler system.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Wed Jul 10 17:18:20 EDT 2019

Committee Statement

Committee This option has already been allowed (at least by The Joint Commission Jan/Feb 1999 EC News) Statement: even when the space is not sprinkler protected and new text will require sprinklers in a space that was previously not required to be sprinkler protected. Some minor repair/renovation operations that would not be considered to constitute a hazardous area could be separated by fire retardant plastic and those repair/renovation operations might include the removal of the ceiling, which would then render the sprinkler system inoperative. If that is the case, this new text would not allow the plastic.

If this change is not made, the entire paragraph should be deleted as the requirement will inadvertently be more stringent than what is presently permitted by some AHJs.

Coordination of terminology with Chapter 43. Recognition that new construction might occur in nonsprinklered areas per 18.4.4.

Response SR-6607-NFPA 101-2019 Message: Public Comment No. 99-NFPA 101-2019 [Section No. 18.7.9.3] Public Comment No. 49-NFPA 101-2019 [Section No. 18.7.9.3]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 25 Affirmative All 0 Affirmative with Comments 3 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Page 196 of 373

190 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Affirmative All Brooks, Bruce D. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Widdekind, Michael D.

Negative with Comment Bush, Kenneth E. Even though required to be constructed of flame resistant plastic, the use of plastic sheets as separations between areas which may not be provided with automatic sprinkler protection establishes an unsafe level of protection without sufficient technical justification. Plastic sheets offer little protection against fire or heat especially that which may be generated in areas that do not comply with applicable requirements. Knippa, Kevin When a portion of a building does not conform with the requirements for the occupancy, it must be separated by a fire barrier having at least a one hour fire resistance. How does plastic, combustible or not, provide protection equal to a two-hour fire barrier? Under NFPA 13, a facility could conduct a fire watch in lieu of having a working fire sprinkler system. Victor, Terry L. The committee statement that the “… new text will require sprinklers in a space that was previously not required to be sprinkler protected” could be true in some cases if misinterpreted and/or misapplied. However, an additional requirement or annex text should have been included that explains when sprinklers do exist, protection shall be maintained on both sides of the flame-resistant plastic. The construction area may be the only means of egress in some instances so sprinkler protection is critical. Without additional guidance in NFPA 101, it will be up to the AHJ to enforce requirements in other NFPA documents such as NFPA 25 and NFPA 241 to maintain sprinkler protection during construction.

Page 197 of 373

191 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6662-NFPA 101-2019 [ Section No. 19.1.4.2 ]

19.1.4.2 Special Definitions. The following is a list of special terms used in this chapter: (1) Ambulatory Health Care Occupancy. See 3.3.198.1. (2) Deep-Fat Frying. See 3.3.56. (3) Gross Floor Area (Health Care and Ambulatory Health Care Occupancies). See 3.3.22.2.3 . (4) Hospital. See 3.3.152. (5) Limited Care Facility. See 3.3.93.2. (6) Nursing Home. See 3.3.150.2. (7) Self-Preservation Capability (Health Care and Ambulatory Health Care Occupancies). See 3.3.253.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 13:47:00 EDT 2019

Committee Statement

Committee Statement: The revision correlates with the definition added to Chapter 3. Response Message: SR-6662-NFPA 101-2019 Public Comment No. 231-NFPA 101-2019 [New Section after 19.1.4.2]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Page 198 of 373

192 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 199 of 373

193 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6684-NFPA 101-2019 [ Section No. 19.1.6.1 ]

Page 200 of 373

194 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

19.1.6.1* Health care occupancies shall be limited to the building construction types specified in Table 19.1.6.1, unless otherwise permitted by 19.1.6.2 through 19.1.6.6. (See 8.2.1.) Table 19.1.6.1 Construction Type Limitations

Total Number of Stories of Buildingb

Construction Type Sprinklereda 1 2 3 ≥4 I (442) Yes XX X X No XX X X I (332) Yes XX X X No XX X X II (222) Yes XX X X No XX X X II (111) Yes XX X NPc No X NP NP NP II (000) Yes XX NPc NPd No NP NP NP NP III (211) Yes XX NPc NPc No NP NP NP NP III (200) Yes X NPc NPd NP No NP NP NP NP

IV (2HH) Yes X Xe,f NPc,e NPc,e No NP NP NP NP V (111) Yes XX NPc NPc No NP NP NP NP V (000) Yes X NPc NPd NP No NP NP NP NP

X: Permitted. NP: Not permitted. The total number of stories of the building is to be determined as follows: Notes: (1) The total number of stories is to be counted starting with the level of exit discharge and ending with the highest occupiable story of the building. (2) Stories below the level of exit discharge are not counted as stories. (3) Interstitial spaces used solely for building or process systems directly related to the level above or below are not considered a separate story. (4) A mezzanine in accordance with 8.6.10 is not counted as a story.

aSprinklered throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7. (See 19.3.5.)

bBasements are not counted as stories.

cPermitted for nursing homes where the requirements of 19.1.6.7 are met.

dPermitted for nursing homes where the requirements of 19.1.6.8 are met.

eBuildings complying with NFPA 5000, 7.2.5.6.1.1, shall be permitted to be up to 7 stories. Up to and including four stories in height permitted for buildings complying with 4.5.6.1.1 of NFPA 220.

f Up to and including two stories in height permitted for buildings complying with 4.5.6.1.2 of NFPA 220.

Page 201 of 373

195 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Tue Jul 23 11:21:53 EDT 2019

Committee Statement

Committee The revision is intended for consistency with the mass timber construction limits of NFPA Statement: 220 and NFPA 5000. Response Message: SR-6684-NFPA 101-2019

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 27 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A.

Page 202 of 373

196 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Abstention Koffel, William E. In accordance with the policy of the Standards Council, I have abstained from voting on this Second Revision.

Page 203 of 373

197 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6663-NFPA 101-2019 [ Section No. 19.2.5.7 ]

19.2.5.7 Health Care Suites. 19.2.5.7.1 General. 19.2.5.7.1.1 Suite Permission. Suites complying with 19.2.5.7 shall be permitted to be used to meet the corridor access requirements of 19.2.5.6. 19.2.5.7.1.2* Suite Separation. Suites shall be separated from the remainder of the building, and from other suites, by one of the following: (1) Walls and doors meeting the requirements of 19.3.6.2 through 19.3.6.5 (2) Existing approved barriers and doors that limit the transfer of smoke 19.2.5.7.1.3 Suite Hazardous Contents Areas. (A)* Intervening rooms shall not be hazardous areas as defined by 19.3.2. (B) Hazardous areas within a suite shall be separated from the remainder of the suite in accordance with 19.3.2.1, unless otherwise provided in 19.2.5.7.1.3(C) or 19.2.5.7.1.3(D). (C)* Hazardous areas within a suite shall not be required to be separated from the remainder of the suite where complying with both of the following: (1) The suite is primarily a hazardous area. (2) The suite is separated from the rest of the health care facility as required for a hazardous area by 19.3.2.1. (D)* Spaces containing sterile surgical materials limited to a one-day supply in operating suites or similar spaces that are sprinklered in accordance with 19.3.5.7 shall be permitted to be open to the remainder of the suite without separation. 19.2.5.7.1.4 Suite Subdivision. The subdivision of suites shall be by means of noncombustible or limited-combustible partitions or partitions constructed with fire-retardant-treated wood enclosed with noncombustible or limited- combustible materials, and such partitions shall not be required to be fire rated. 19.2.5.7.2 Sleeping Suites. Sleeping suites shall be in accordance with the following: (1) Patient care sleeping suites shall comply with the provisions of 19.2.5.7.2.1 through 19.2.5.7.2.4. (2) Sleeping suites not for patient care shall comply with the provisions of 19.2.5.7.4. 19.2.5.7.2.1 Patient Care Sleeping Suite Supervision. (A) Patient care sleeping suites shall be provided with constant staff supervision within the suite.

Page 204 of 373

198 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

(B)* Patient care sleeping suites shall be arranged in accordance with one of the following:

(1)* Patient sleeping rooms within patient care sleeping suites shall provide one of the following: (a) The patient sleeping rooms shall be arranged to allow for direct supervision from a normally attended location within the suite, such as is provided by glass walls, and cubicle curtains shall be permitted. (b) Any patient sleeping rooms without the direct supervision required by 19.2.5.7.2.1(B)(1)(a) shall be provided with smoke detection in accordance with Section 9.6 and 19.3.4. (2) Patient care sleeping suites shall be provided with a total (complete) coverage automatic smoke detection system in accordance with 9.6.2.9 and 19.3.4. 19.2.5.7.2.2 Patient Care Sleeping Suite Means of Egress. (A)* Patient care sleeping suites shall have exit access to a corridor complying with 19.3.6 or to a horizontal exit, directly from the suite. (B)

Patient care sleeping suites of more than 1000 ft2 (93 m2) gross floor area shall have not less than two exit access doors remotely located from each other. (C)* For suites requiring two exit access doors, one of the exit access doors from the suite shall be permitted to be to one of the following: (1) An exit stair (2) An exit passageway (3) An exit door to the exterior (4) Another suite, provided that the separation between the suites complies with the corridor requirements of 19.3.6.2 through 19.3.6.5 19.2.5.7.2.3 Patient Care Sleeping Suite Maximum Size. (A)

Patient care sleeping suites shall not exceed 5000 ft2 (460 m2) gross floor area , unless otherwise provided in 19.2.5.7.2.3(B) or 19.2.5.7.2.3(C). (B)

Patient care sleeping suites shall not exceed 7500 ft2 (700 m2) gross floor area where the smoke compartment is protected throughout by one of the following: (1) Approved electrically supervised sprinkler system in accordance with 19.3.5.7 and total (complete) coverage automatic smoke detection in accordance with 9.6.2.9 and 19.3.4 (2) Approved electrically supervised sprinkler system protection complying with 19.3.5.8 (C)

Patient care sleeping suites greater than 7500 ft2 (700 m2) gross floor area , and not exceeding 10,000 ft2 (930 m2) gross floor area , shall be permitted where all of the following are provided in the suite: (1)* Direct visual supervision in accordance with 19.2.5.7.2.1(B)(1)(a) (2) Total (complete) coverage automatic smoke detection in accordance with 9.6.2.9 and 19.3.4 (3) Approved electrically supervised sprinkler system protection complying with 19.3.5.8 19.2.5.7.2.4 Patient Care Sleeping Suite Travel Distance. (A) Travel distance between any point in a sleeping suite and an exit access door to another suite, an exit access corridor door, or a horizontal exit door from that suite shall not exceed 100 ft (30 m).

Page 205 of 373

199 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

(B) Travel distance between any point in a sleeping suite and an exit shall not exceed the following: (1) 150 ft (46 m) if the building is not protected throughout by an approved electrically supervised sprinkler system complying with 19.3.5.7 (2) 200 ft (61 m) if the building is protected throughout by an approved electrically supervised sprinkler system complying with 19.3.5.7 19.2.5.7.3 Patient Care Non-Sleeping Nonsleeping Suites. Nonsleeping suites shall be in accordance with the following: (1) Nonsleeping suites for patient care shall comply with the provisions of 19.2.5.7.3.1 through 19.2.5.7.3.3. (2) Nonsleeping suites not for patient care shall comply with the provisions of 19.2.5.7.4. 19.2.5.7.3.1 Patient Care Non-Sleeping Nonsleeping Suite Means of Egress. (A) Patient care nonsleeping suites shall have exit access to a corridor complying with 19.3.6 or to a horizontal exit, directly from the suite. (B)

Patient care nonsleeping suites of more than 2500 ft2 (230 m2) gross floor area shall have not less than two exit access doors remotely located from each other. (C)* For suites requiring two exit access doors, one of the exit access doors shall be permitted to be to one of the following: (1) An exit stair (2) An exit passageway (3) An exit door to the exterior (4) Another suite, provided that the separation between the suites complies with the corridor requirements of 19.3.6.2 through 19.3.6.5 19.2.5.7.3.2 Patient Care Non-Sleeping Nonsleeping Suite Maximum Size.

Patient care nonsleeping suites shall not exceed 10,000 ft2 (930 m2) gross floor area , unless otherwise provided in 19.2.5.7.3.2(A) or 19.2.5.7.3.2(B). (A)

Patient care nonsleeping suites greater than 10,000 ft2 (930 m2) gross floor area and not exceeding 12,500 ft2 (1161 m2) gross floor area shall be permitted where the smoke compartment is protected throughout by one of the following: (1) Approved electrically supervised sprinkler system in accordance with 19.3.5.7 and total (complete) coverage automatic smoke detection in accordance with 9.6.2.9 and 19.3.4 (2) Approved electrically supervised sprinkler system protection complying with 19.3.5.8 (B)

Patient care nonsleeping suites greater than 12,500 ft2 (1161 m2) gross floor area and not exceeding 15,000 ft2 (1394 m2) gross floor area shall be permitted where both of the following are provided in the suite: (1) Total (complete) coverage automatic smoke detection in accordance with 9.6.2.9 and 19.3.4 (2) Approved electrically supervised sprinkler system protection complying with 19.3.5.8 19.2.5.7.3.3 Patient Care Non-Sleeping Nonsleeping Suite Travel Distance. (A) Travel distance within a patient care nonsleeping suite to an exit access door to another suite, an exit access corridor door, or a horizontal exit door from the suite shall not exceed 100 ft (30 m).

Page 206 of 373

200 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

(B) Travel distance between any point in a nonsleeping suite and an exit shall not exceed the following: (1) 150 ft (46 m) if the building is not protected throughout by an approved electrically supervised sprinkler system complying with 19.3.5.7 (2) 200 ft (61 m) if the building is protected throughout by an approved electrically supervised sprinkler system complying with 19.3.5.7 19.2.5.7.4 Non-Patient-Care Suites. The egress provisions for non-patient-care suites shall be in accordance with the primary use and occupancy of the space.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 14:01:10 EDT 2019

Committee Statement

Committee The revision replaces the term 'gross' with 'gross floor area' in nine places to correlate with the Statement: new definition added to Chapter 3 to clarify how the area of a suite should be determined.

Response SR-6663-NFPA 101-2019 Message: Public Comment No. 230-NFPA 101-2019 [Section No. 19.2.5.7]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W.

Page 207 of 373

201 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 208 of 373

202 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6664-NFPA 101-2019 [ Section No. 19.3.6.3.7 ]

19.3.6.3.7 Powered doors that comply with the requirements of 7.2.1.9 shall be considered as complying with the requirements of 19.3.6.3.5, provided that all of the following criteria are met: (1) The door is equipped with a means for keeping the door closed that is acceptable to the authority having jurisdiction. (2) The device used is capable of keeping the door fully closed if a force of 5 lbf (22 N) is applied at the latch edge of a swinging door and applied in any direction to a sliding or folding door, whether or not power is applied. (3) The power-assist mechanism ceases to function upon operation Where door leaves are operated by power by any automatic mechanism, the automatic opening of the doors shall cease to function upon operation of approved smoke detectors installed in accordance with the provisions of NFPA 72 for door release service .

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 14:09:57 EDT 2019

Committee Statement

Committee Section 7.2.1.9 has two options: (1) Doors operated by power by any automatic mechanism and (2) Statement: power assisted manual operation.

7.2.1.9.1* General. Where means of egress door leaves are operated by power by any automatic mechanism or are provided with power-assisted manual operation, the design shall be such that, in the event of power failure, the leaves open manually to allow egress travel or close when necessary to safeguard the means of egress.

This change would not allow doors to automatically open, but it would allow power assisted door to be used without mandating smoke detection to shut down that operation. From BHMA A156.19 Definition of a Power Assist Door: "A door with a power mechanism that activates by pushing or pulling the door, reducing the opening resistance of a self-closing door to allow easier manual opening of the door. If the opening force on the door is released, the door shall come to a stop and either immediately begin to close, or begin to close after a predetermined time."

The time to close is limited to a few seconds in BHMA A156.19. There is no reason to make that function cease. The only function that should cease is when the door automatically opens upon approach of a person (or smoke) and the text has been changed to reflect that.

The new text clarifies that smoke detectors are to be installed in accordance with the specific provision in NFPA 72 for door release service. Response SR-6664-NFPA 101-2019 Message: Public Comment No. 199-NFPA 101-2019 [Section No. 19.3.6.3.7] Public Comment No. 100-NFPA 101-2019 [Section No. 19.3.6.3.7]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned Page 209 of 373

203 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 210 of 373

204 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6666-NFPA 101-2019 [ Section No. 19.3.7.1 ]

Detail SR-6667 19.3.7.1* Smoke barriers shall be provided to divide every story used for sleeping rooms for more than 30 patients into not less than two smoke compartments (see 19.2.4.4), and the following also shall apply: (1) The size of any such smoke compartment shall comply with one of the following:

(a) Smoke compartments shall not exceed 22,500 ft2 (2100 m2) gross floor area. (b) Where the building is sprinklered in accordance with 19.3.5.8, hospital smoke compartments shall not exceed 40,000 ft2 (3720 m2) gross floor area where all sleeping rooms are configured for only one patient. Suites in accordance with 19.2.5.7 shall be permitted where every occupiable sleeping room within the suite is configured for only one patient. (c) Where the building is sprinklered in accordance with 19.3.5.8, hospital smoke compartments shall not exceed 40,000 ft2 (3720 m2) gross floor area where the smoke compartment contains no patient sleeping rooms.

(2) The travel distance from any point to reach a door in the required smoke barrier shall not exceed 200 ft (61 m). (3) Where neither the length nor width of the smoke compartment exceeds 150 ft (46 m), the travel distance to reach the smoke barrier door shall not be limited. (4) The area of any smoke compartment that contains an atrium shall not include the area of the atrium separated in accordance with 8.6.7 19.3.7.3 shall not be limited in size.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 14:48:02 EDT 2019

Committee Statement

Committee The revision adds 'gross floor area' in (1)(a), (1)(b), and (1)(c). Statement: The revision correlates with the definition of 'gross floor area (health care and ambulatory health care occupancies)' added to Chapter 3 to clarify how to determine the area of smoke compartments and suites.

Response SR-6666-NFPA 101-2019 Message: Public Comment No. 76-NFPA 101-2019 [Section No. 19.3.7.1]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments

Page 211 of 373

205 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 212 of 373

206 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6668-NFPA 101-2019 [ Section No. 19.3.7.3 ]

19.3.7.3 Any required smoke barrier shall be constructed in accordance with Section 8.5 and shall have a minimum 1 ⁄2-hour fire resistance rating, unless otherwise permitted by one of the following: (1) This requirement shall not apply where an atrium is used, and in which case both of the following criteria also shall apply: (a) Smoke barriers shall be permitted to terminate at an atrium wall constructed in accordance with 8.6.7(1)(c). (b) Not less than two separate smoke compartments shall be provided on each floor. (2)* Smoke dampers shall not be required in duct penetrations of smoke barriers in fully ducted heating, ventilating, and air-conditioning systems where an approved, supervised automatic sprinkler system in accordance with 19.3.5.8 has been provided for smoke compartments adjacent to the smoke barrier.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 14:58:32 EDT 2019

Committee Statement

Committee The revision is intended to coordinate with changes to 19.3.7.1 in Detail SR-6667. (The Statement: revision only changes 'and' to 'in which case'.)

Response SR-6668-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E.

Page 213 of 373

207 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 214 of 373

208 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6669-NFPA 101-2019 [ Section No. 19.4.2 ]

19.4.2 Underground Structures and Limited Access Buildings Structures . See Underground structures and limited access structures shall comply with Section 11.7. for requirements for limited access buildings.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 15:02:34 EDT 2019

Committee Statement

Committee At the First Draft meeting, the Task Group on Special Structures provided recommended language Statement: for cleaning up this section. This change takes the clean-up a step further by using the terminology (adding underground structures and changing "building" to "structures") that is in Section 11.7 and adding "shall comply with" language to be consistent with other sections of the Code. Response SR-6669-NFPA 101-2019 Message: Public Comment No. 227-NFPA 101-2019 [Section No. 19.4.2]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W.

Page 215 of 373

209 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 216 of 373

210 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6670-NFPA 101-2019 [ Section No. 19.7.1.4 ]

19.7.1.4* Fire drills in health care occupancies shall include the simulation of emergency fire conditions and, except as indicated in 19.7.1.7 , include activation of the fire alarm system notification appliances.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 15:14:30 EDT 2019

Committee Statement

Committee 19.7.1.7 is an exception to 19.7.1.4. AHJ's are requiring facilities to operate notification appliance Statement: even at night in spite of what 19.7.1.7 says. As written, this section does indicate that 19.7.1.7 is an exception to the requirement to activate notification appliances. This change will clarify that patients do not have to be unnecessarily bothered by notification appliances during drills on the third shift.

Response SR-6670-NFPA 101-2019 Message: Public Comment No. 101-NFPA 101-2019 [Section No. 19.7.1.4]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. Page 217 of 373

211 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 218 of 373

212 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6671-NFPA 101-2019 [ Section No. 19.7.5.7 ]

19.7.5.7 Soiled Linen and Trash Receptacles. 19.7.5.7.1* Soiled linen or trash collection receptacles shall not exceed 64 gal (242 L) in capacity and shall meet all of the following requirements: with capacities greater than 64 gal (242 L) shall be located in a hazardous area when not attended.

The average density of container capacity in a room or space shall not exceed 1.0 gal/ft 2 (40.7 L/m 2 ). Mobile soiled linen or trash collection receptacles with capacities greater than 64 gal (242 L) shall be located in a room protected as a hazardous area when not attended. Container size and density shall not be limited in hazardous areas.

A.19.7.5.7.1

It is not the intent to permit collection receptacles with a capacity greater than 32 64 gal (121 242 L) to be positioned at or near a nurses’ station based on the argument that such nurses’ station is constantly attended. The large collection receptacle itself needs to be actively attended by staff. Staff might leave the large receptacle in the corridor outside a patient room while entering the room to collect soiled linen or trash, but staff is expected to return to the receptacle, move on to the next room, and repeat the collection function. Where staff is not actively collecting material for placement in the receptacle, the receptacle is to be moved to a room protected as a hazardous area.

19.7.5.7.2* Containers greater than 64 gal (242 L) used solely for recycling clean waste or for patient records awaiting destruction shall be permitted to be excluded from the requirements of 19.7.5.7.1 where all the following conditions are met: (1) Each container shall be limited to a maximum capacity of 96 gal (363 L). , except as permitted by 19.7.5.7.2(2) or (3). * Containers with capacities greater than 96 gal (363 L) shall be located in a room protected as a hazardous area when not attended.

A.19.7.5.7.2(2)

See 19.7.5.7.1(3) .

Container size shall not be limited in hazardous areas. (2) Containers for combustibles shall be labeled and listed as meeting the requirements of FM Approval 6921, Approval Standard for Containers for Combustible Waste; however, such testing, listing, and labeling shall not be limited to FM Approvals.

Page 219 of 373

213 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

A.19.7.5.7.2

It is the intent that this provision permits recycling of bottles, cans, paper, and similar clean items that do not contain grease, oil, flammable liquids, or significant plastic materials, using larger containers or several adjacent containers, and not require locating such containers in a room protected as a hazardous area. Containers for medical records awaiting shredding are often larger than 32 64 gal (121 242 L). These containers are not to be included in the calculations and limitations of 19.7.5.7.1. There is no limit on the number of these containers, as FM Approval 6921, Approval Standard for Containers for Combustible Waste, ensures that the fire will not spread outside of the container. FM approval standards are written for use with FM Approvals. The tests can be conducted by any approved laboratory. The portions of the standard referring to FM Approvals are not included in this reference.

19.7.5.7.3 The provisions of 10.3.8, applicable to containers for waste or linen, shall not apply.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 15:17:48 EDT 2019

Committee Statement

Committee The revisions were drafted by a task group on waste container sizes, which provided the following Statement: substantiation:

1. Many standard patient recycling containers currently in use in health care facilities slightly exceed 32 gallons

2. Unable to locate any patient recycling containers meeting FM Approval Standard 6921 which also comply with HIPPA for patient privacy by providing a securable container. This limits container size to 32 gallons for patient records.

3. A kitchen located in a health care occupancy is not permitted to be provided with a standard size trash can of 50 gallons.

4. NFPA Research Report Structure Fires in Health Care Facilities 2011 – 2015 indicates that trash/rubbish/waste is not a major contributor to injuries related to a fire event. There was no documented instances of fires spreading from one trash can to another. A summary of the data in the report is below:

Number of Fires Number of Injuries Number of Deaths

Hospitals 320 3 0

Nursing Homes 120 1 0

Hospitals and Hospices 100 1 0

Mental Health Facilities 50 0 0

Clinics and Dr. Offices 50 0 0

a. The NFPA report did not distinguish between trash/rubbish/waste container located outside vs. inside.

5. Modifying the 32 gallon limitation to 64 gallons would make the requirement consistent with the threshold for a room storing soiled linen or trash to be considered a hazardous area is 64 gallons in the Protections for Hazards section.

Response SR-6671-NFPA 101-2019 Message:

Page 220 of 373

214 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Public Comment No. 50-NFPA 101-2019 [Section No. 19.7.5.7.1]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 26 Affirmative All 0 Affirmative with Comments 2 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 221 of 373

215 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Negative with Comment Bush, Kenneth E. The revised wording for 19.7.5.7.2 would permit containers of 64 gal or less capacity used solely for recycling clean waste or for patient records awaiting destruction to be used without restriction. This is a significant change from the existing Code text that has not been provided with sufficient technical justification. Koffel, William E. I remain concerned that this relaxation is too significant without a density restriction. Other than not normally expected in a health care occupancy, what would prevent one from located several large containers (but less than 64 gal) in a room and in close proximity to each other?

Page 222 of 373

216 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6672-NFPA 101-2019 [ Section No. 19.7.9.3 ]

19.7.9.3 For repair, renovation, rehabilitation activities or preparation for construction rehabilitation activities of a duration not greater than 30 days that do not cause the classification of the construction area as a hazardous area as identified in 19.3.2, fire-retardant flame-resistant plastic in accordance with NFPA 701, or equivalent, shall be permitted to be used to separate the construction area from the other spaces. provided that both the construction area and the adjacent occupied spaces are protected by an approved automatic sprinkler system.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 15:26:45 EDT 2019

Committee Statement

Committee This option has already been allowed (at least by The Joint Commission Jan/Feb 1999 EC News) Statement: even when the space is not sprinkler protected and new text will require sprinklers in a space that was previously not required to be sprinkler protected. Some minor repair/renovation operations that would not be considered to constitute a hazardous area could be separated by fire retardant plastic and those repair/renovation operations might include the removal of the ceiling, which would then render the sprinkler system inoperative. If that is the case, this new text would not allow the plastic.

If this change is not made, the entire paragraph should be deleted as the requirement will inadvertently be more stringent than what is presently permitted by some AHJs.

Coordination of terminology with Chapter 43. Recognition that new construction might occur in nonsprinklered areas per 18.4.4.

Response SR-6672-NFPA 101-2019 Message: Public Comment No. 51-NFPA 101-2019 [Section No. 19.7.9.3] Public Comment No. 102-NFPA 101-2019 [Section No. 19.7.9.3]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 25 Affirmative All 0 Affirmative with Comments 3 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Page 223 of 373

217 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Affirmative All Brooks, Bruce D. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Widdekind, Michael D.

Negative with Comment Bush, Kenneth E. Even though required to be constructed of flame resistant plastic, the use of plastic sheets as separations between areas which may not be provided with automatic sprinkler protection establishes an unsafe level of protection without sufficient technical justification. Plastic sheets offer little protection against fire or heat especially that which may be generated in areas that do not comply with applicable requirements. Knippa, Kevin When a portion of a building does not conform with the requirements for the occupancy, it must be separated by a fire barrier having at least a one hour fire resistance. How does plastic, combustible or not, provide protection equal to a two-hour fire barrier? Under NFPA 13, a facility could conduct a fire watch in lieu of having a working fire sprinkler system. Victor, Terry L. The committee statement that the “… new text will require sprinklers in a space that was previously not required to be sprinkler protected” could be true in some cases if misinterpreted and/or misapplied. However, an additional requirement or annex text should have been included that explains when sprinklers do exist, protection shall be maintained on both sides of the flame-resistant plastic. The construction area may be the only means of egress in some instances so sprinkler protection is critical. Without additional guidance in NFPA 101, it will be up to the AHJ to enforce requirements in other NFPA documents such as NFPA 25 and NFPA 241 to maintain sprinkler protection during construction.

Page 224 of 373

218 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6685-NFPA 101-2019 [ Section No. 20.1.1.4.3 ]

20.1.1.4.3 Construction, Repair, and Improvement Operations. See 4.6.10 . 20.1.1.4.3.1 Construction, repair, and improvement operations shall comply with 4.6.10 . 20.1.1.4.3.2 For rehabilitation activities or preparation for rehabilitation activities of a duration not greater than 30 days that do not cause the classification of the construction area as a hazardous area as identified in 20.3.2 , flame-resistant plastic in accordance with NFPA 701 or equivalent shall be permitted to be used to separate the construction area from the other spaces.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Tue Jul 23 11:30:15 EDT 2019

Committee Statement

Committee Statement: The revision is intended for consistency with Chapter 18. Response Message: SR-6685-NFPA 101-2019

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 27 Affirmative All 0 Affirmative with Comments 1 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Page 225 of 373

219 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Negative with Comment Knippa, Kevin When a portion of a building does not conform with the requirements for the occupancy, it must be separated by a fire barrier having at least a one hour fire resistance. How does plastic, combustible or not, provide protection equal to a two-hour fire barrier? Under NFPA 13, a facility could conduct a fire watch in lieu of having a working fire sprinkler system.

Page 226 of 373

220 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6673-NFPA 101-2019 [ Section No. 20.1.4.2 ]

20.1.4.2 Special Definitions. The following is a list of special definitions used in this chapter: (1) Ambulatory Health Care Occupancy. See 3.3.198.1. (2) Gross Floor Area (Health Care and Ambulatory Health Care Occupancies). See 3.3.22.2.3 . (3) Self-Preservation Capability (Health Care and Ambulatory Health Care Occupancies). See 3.3.253.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 15:39:41 EDT 2019

Committee Statement

Committee Statement: The revision correlates with the new definition added to Chapter 3. Response Message: SR-6673-NFPA 101-2019 Public Comment No. 235-NFPA 101-2019 [New Section after 20.1.4.2]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. Page 227 of 373

221 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 228 of 373

222 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6675-NFPA 101-2019 [ Section No. 20.3.7.2 ]

20.3.7.2 Every story of an ambulatory health care occupancy shall be divided into not less than two smoke compartments, unless otherwise permitted by one of the following: (1) This requirement shall not apply where the area of the ambulatory health care occupancy is less than 5000 ft2 (465 m2) gross per story and that area is protected by an approved automatic smoke detection system. (2) This requirement shall not apply where the area of the ambulatory health care occupancy is less than 10,000 ft2 (929 m2) gross per story and the building is protected throughout by an approved, supervised automatic sprinkler system installed in accordance with Section 9.7. (3) An area in an adjoining occupancy shall be permitted to serve as a smoke compartment for an ambulatory health care occupancy if all of the following criteria are met: (a) The separating wall and both compartments meet the requirements of 20.3.7. (b) The ambulatory health care occupancy does not exceed one of the following:

i. 22,500 ft2 (2100 m2) of gross floor area

ii. 40,000 ft2 (3720 m2) of gross floor area in buildings protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7 (c) Access from the ambulatory health care occupancy to the other occupancy is unrestricted.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 15:47:55 EDT 2019

Committee Statement

Committee The revision adds 'of gross floor area' to (3)(b)i and ii. Statement: The revision correlates with the new definition of 'gross floor area (health care and ambulatory health care occupancies)' which clarifies how to determine the floor area of smoke compartments and suites. Response SR-6675-NFPA 101-2019 Message: Public Comment No. 77-NFPA 101-2019 [Section No. 20.3.7.2]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Page 229 of 373

223 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 230 of 373

224 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6676-NFPA 101-2019 [ Section No. 20.4.2 ]

20.4.2 Underground Structures and Limited Access or Underground Buildings Structures . See Underground structures and limited access structures shall comply with Section 11.7.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Mon Jul 22 16:11:01 EDT 2019

Committee Statement

Committee At the First Draft meeting, the Task Group on Special Structures provided recommended language Statement: for cleaning up this section. This change takes the clean-up a step further by using the terminology (adding underground structures and changing "building" to "structures") that is in Section 11.7 and adding "shall comply with" language to be consistent with other sections of the Code. Response SR-6676-NFPA 101-2019 Message: Public Comment No. 228-NFPA 101-2019 [Section No. 20.4.2]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M.

Page 231 of 373

225 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 232 of 373

226 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6677-NFPA 101-2019 [ Section No. 20.7.5.5 ]

20.7.5.5 Soiled Linen and Trash Receptacles. 20.7.5.5.1 Soiled linen or trash collection receptacles shall not exceed 64 gal (242 L) in capacity, and all of the following also shall apply: with capacities greater than 64 gal (242 L) shall be located in a hazardous area when not attended.

The average density of container capacity in a room or space shall not exceed 1.0 gal/ft 2 (40.7 L/m 2 ). Mobile soiled linen or trash collection receptacles with capacities greater than 64 gal (242 L) shall be located in a room protected as a hazardous area when not attended. Container size and density shall not be limited in hazardous areas. 20.7.5.5.2* Containers greater than 64 gal (242 L) used solely for recycling clean waste or for patient records awaiting destruction shall be permitted to be excluded from the requirements of 20.7.5.5.1 where all the following conditions are met: (1) Each container shall be limited to a maximum capacity of 96 gal (363 L). , except as permitted by 20.7.5.5.2(2) or (3). * Containers with capacities greater than 96 gal (363 L) shall be located in a room protected as a hazardous area when not attended.

A.20.7.5.5.2(2)

See 20.7.5.5.1(3) .

Container size shall not be limited in hazardous areas. (2) Containers for combustibles shall be labeled and listed as meeting the requirements of FM Approval 6921, Approval Standard for Containers for Combustible Waste; however, such testing, listing, and labeling shall not be limited to FM Approvals.

A.20.7.5.5.2

It is the intent that this provision permits recycling of bottles, cans, paper, and similar clean items that do not contain grease, oil, flammable liquids, or significant plastic materials using larger containers or several adjacent containers and not require locating such containers in a room protected as a hazardous area. Containers for medical records awaiting shredding are often larger than 32 64 gal (121 242 L). These containers are not to be included in the calculations and limitations of 20.7.5.5.1. There is no limit on the number of these containers, as FM Approval 6921, Approval Standard for Containers for Combustible Waste, ensures that the fire will not spread outside of the container. FM approval standards are written for use with FM Approvals. The tests can be conducted by any approved laboratory. The portions of the standard referring to FM Approvals are not included in this reference.

20.7.5.5.3 The provisions of 10.3.8, applicable to containers for waste or linen, shall not apply.

Submitter Information Verification

Committee: SAF-HEA

Page 233 of 373

227 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Submittal Date: Tue Jul 23 09:17:41 EDT 2019

Committee Statement

Committee The revisions were drafted by a task group on waste container sizes, which provided the following Statement: substantiation:

1. Many standard patient recycling containers currently in use in health care facilities slightly exceed 32 gallons

2. Unable to locate any patient recycling containers meeting FM Approval Standard 6921 which also comply with HIPPA for patient privacy by providing a securable container. This limits container size to 32 gallons for patient records.

3. A kitchen located in a health care occupancy is not permitted to be provided with a standard size trash can of 50 gallons.

4. NFPA Research Report Structure Fires in Health Care Facilities 2011 – 2015 indicates that trash/rubbish/waste is not a major contributor to injuries related to a fire event. There was no documented instances of fires spreading from one trash can to another. A summary of the data in the report is below:

Number of Fires Number of Injuries Number of Deaths

Hospitals 320 3 0

Nursing Homes 120 1 0

Hospitals and Hospices 100 1 0

Mental Health Facilities 50 0 0

Clinics and Dr. Offices 50 0 0

a. The NFPA report did not distinguish between trash/rubbish/waste container located outside vs. inside.

5. Modifying the 32 gallon limitation to 64 gallons would make the requirement consistent with the threshold for a room storing soiled linen or trash to be considered a hazardous area is 64 gallons in the Protections for Hazards section. Response SR-6677-NFPA 101-2019 Message: Public Comment No. 52-NFPA 101-2019 [Section No. 20.7.5.5.1]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 26 Affirmative All 0 Affirmative with Comments 2 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua Page 234 of 373

228 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Affirmative All Brooks, Bruce D. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Negative with Comment Bush, Kenneth E. The revised wording for 20.7.5.5.2 would permit containers of 64 gal or less capacity used solely for recycling clean waste or for patient records awaiting destruction to be used without restriction. This is a significant change from the existing Code text that has not been provided with sufficient technical justification. Koffel, William E. I remain concerned that this relaxation is too significant without a density restriction. Other than not normally expected in an ambulatory health care occupancy, what would prevent one from located several large containers (but less than 64 gal) in a room and in close proximity to each other?

Page 235 of 373

229 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6678-NFPA 101-2019 [ Section No. 20.7.7.1 ]

20.7.7.1 New engineered smoke control systems shall be designed, installed, tested, and maintained in accordance with NFPA 92 Section 9.3 .

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Tue Jul 23 09:35:06 EDT 2019

Committee Statement

Committee Section 9.3 provides the requirements for smoke control systems via reference to NFPA Statement: 92. Response Message: SR-6678-NFPA 101-2019 Public Comment No. 53-NFPA 101-2019 [Section No. 20.7.7]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L.

Page 236 of 373

230 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 237 of 373

231 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6686-NFPA 101-2019 [ Section No. 21.1.1.4.3 ]

21.1.1.4.3 Construction, Repair, and Improvement Operations. See 4.6.10 . 21.1.1.4.3.1 Construction, repair, and improvement operations shall comply with 4.6.10 . 21.1.1.4.3.2 For rehabilitation activities or preparation for rehabilitation activities of a duration not greater than 30 days that do not cause the classification of the construction area as a hazardous area as identified in 21.3.2 , flame-resistant plastic in accordance with NFPA 701 or equivalent shall be permitted to be used to separate the construction area from the other spaces.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Tue Jul 23 11:35:22 EDT 2019

Committee Statement

Committee Statement: The revision is intended for consistency with Ch. 19. Response Message: SR-6686-NFPA 101-2019

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 25 Affirmative All 0 Affirmative with Comments 3 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. Page 238 of 373

232 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Widdekind, Michael D.

Negative with Comment Bush, Kenneth E. Even though required to be constructed of flame resistant plastic, the use of plastic sheets as separations between areas which may not be provided with automatic sprinkler protection establishes an unsafe level of protection without sufficient technical justification. Plastic sheets offer little protection against fire or heat especially that which may be generated in areas that do not comply with applicable requirements. Knippa, Kevin When a portion of a building does not conform with the requirements for the occupancy, it must be separated by a fire barrier having at least a one hour fire resistance. How does plastic, combustible or not, provide protection equal to a two-hour fire barrier? Under NFPA 13, a facility could conduct a fire watch in lieu of having a working fire sprinkler system. Victor, Terry L. An additional requirement or annex text should have been included that explains when sprinklers do exist, protection shall be maintained on both sides of the flame-resistant plastic. The construction area may be the only means of egress in some instances so sprinkler protection is critical. Without additional guidance in NFPA 101, it will be up to the AHJ to enforce requirements in other NFPA documents such as NFPA 25 and NFPA 241 to maintain sprinkler protection during construction.

Page 239 of 373

233 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6679-NFPA 101-2019 [ Section No. 21.1.4.2 ]

21.1.4.2 Special Definitions. The following is a list of special definitions used in this chapter: (1) Ambulatory Health Care Occupancy. See 3.3.198.1. (2) Gross Floor Area (Health Care and Ambulatory Health Care Occupancies). 3.3.22.2.3 . (3) Self-Preservation Capability (Health Care and Ambulatory Health Care Occupancies). See 3.3.253.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Tue Jul 23 09:37:09 EDT 2019

Committee Statement

Committee Statement: The revision is intended to correlate with SR-6654. Response Message: SR-6679-NFPA 101-2019 Public Comment No. 236-NFPA 101-2019 [New Section after 21.1.4.2]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. Page 240 of 373

234 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 241 of 373

235 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6688-NFPA 101-2019 [ Section No. 21.2.2.2.11 ]

21.2.2.2.11 Horizontal or vertical security grilles or doors complying with 7.2.1.4.1(3), 7.2.1.5.6 shall be permitted to be used as part of the required means of egress from a tenant space.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Wed Sep 11 10:40:13 EDT 2019

Committee Statement

Committee Statement: Editorial correction. (Inadvertently added incorrect cross-reference in 2018 edition.) Response Message: SR-6688-NFPA 101-2019

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary

Page 242 of 373

236 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 243 of 373

237 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6681-NFPA 101-2019 [ Section No. 21.3.7.2 ]

21.3.7.2 Every story of an ambulatory health care occupancy shall be divided into not less than two smoke compartments, unless otherwise permitted by one of the following: (1) This requirement shall not apply where the area of the ambulatory health care occupancy is less than 5000 ft2 (465 m2) gross per story and that area is protected by an approved automatic smoke detection system. (2) This requirement shall not apply where the area of the ambulatory health care occupancy is less than 10,000 ft2 (929 m2) gross per story and the building is protected throughout by an approved, supervised automatic sprinkler system installed in accordance with Section 9.7. (3) An area in an adjoining occupancy shall be permitted to serve as a smoke compartment for an ambulatory health care occupancy if all of the following criteria are met: (a) The separating wall and both compartments meet the requirements of 21.3.7. (b) The ambulatory health care occupancy does not exceed one of the following:

i. 22,500 ft2 (2100 m2) of gross floor area

ii. 40,000 ft2 (3720 m2) of gross floor area in buildings protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7 (c) Access from the ambulatory health care occupancy to the other occupancy is unrestricted.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Tue Jul 23 09:50:45 EDT 2019

Committee Statement

Committee The revision adds 'of gross floor area' to (3)(b)i and ii. Statement: The revision correlates with the new definition of 'gross floor area (health care and ambulatory health care occupancies)' which clarifies how to determine the floor area of smoke compartments and suites. Response SR-6681-NFPA 101-2019 Message: Public Comment No. 78-NFPA 101-2019 [Section No. 21.3.7.2]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Page 244 of 373

238 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 245 of 373

239 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6682-NFPA 101-2019 [ Section No. 21.4.2 ]

21.4.2 Underground Structures and Limited Access or Underground Buildings Structures . See Underground structures and limited access structures shall comply with Section 11.7.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Tue Jul 23 09:53:41 EDT 2019

Committee Statement

Committee At the First Draft meeting, the Task Group on Special Structures provided recommended language Statement: for cleaning up this section. This change takes the clean-up a step further by using the terminology (adding underground structures and changing "building" to "structures") that is in Section 11.7 and adding "shall comply with" language to be consistent with other sections of the Code. Response SR-6682-NFPA 101-2019 Message: Public Comment No. 229-NFPA 101-2019 [Section No. 21.4.2]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M.

Page 246 of 373

240 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 247 of 373

241 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6683-NFPA 101-2019 [ Section No. 21.7.5.5 ]

21.7.5.5 Soiled Linen and Trash Receptacles. 21.7.5.5.1 Soiled linen or trash collection receptacles shall not exceed 64 gal (242 L) in capacity, and all of the following also shall apply: with capacities greater than 64 gal (242 L) shall be located in a hazardous area when not attended.

The average density of container capacity in a room or space shall not exceed 1.0 gal/ft 2 (40.7 L/m 2 ). Mobile soiled linen or trash collection receptacles with capacities greater than 64 gal (242 L) shall be located in a room protected as a hazardous area when not attended. Container size and density shall not be limited in hazardous areas. 21.7.5.5.2* Containers greater than 64 gal (242 L) used solely for recycling clean waste or for patient records awaiting destruction shall be permitted to be excluded from the requirements of 21.7.5.5.1 where all the following conditions are met: (1) Each container shall be limited to a maximum capacity of 96 gal (363 L). , except as permitted by 21.7.5.5.2(2) or 21.7.5.5.2(2) . * Containers with capacities greater than 96 gal (363 L) shall be located in a room protected as a hazardous area when not attended.

A.21.7.5.5.2(2)

See 21.7.5.5.1(3) .

Container size shall not be limited in hazardous areas. (2) Containers for combustibles shall be labeled and listed as meeting the requirements of FM Approval 6921, Approval Standard for Containers for Combustible Waste; however, such testing, listing, and labeling shall not be limited to FM Approvals.

A.21.7.5.5.2

It is the intent that this provision permits recycling of bottles, cans, paper, and similar clean items that do not contain grease, oil, flammable liquids, or significant plastic materials using larger containers or several adjacent containers and not require locating such containers in a room protected as a hazardous area. Containers for medical records awaiting shredding are often larger than 32 64 gal (121 242 L). These containers are not to be included in the calculations and limitations of 21.7.5.5.1. There is no limit on the number of these containers, as FM Approval 6921, Approval Standard for Containers for Combustible Waste, ensures that the fire will not spread outside of the container. FM approval standards are written for use with FM Approvals. The tests can be conducted by any approved laboratory. The portions of the standard referring to FM Approvals are not included in this reference.

21.7.5.5.3 The provisions of 10.3.8, applicable to containers for waste or linen, shall not apply.

Submitter Information Verification

Committee: SAF-HEA

Page 248 of 373

242 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Submittal Date: Tue Jul 23 10:12:28 EDT 2019

Committee Statement

Committee The revisions were drafted by a task group on waste container sizes, which provided the following Statement: substantiation:

1. Many standard patient recycling containers currently in use in health care facilities slightly exceed 32 gallons

2. Unable to locate any patient recycling containers meeting FM Approval Standard 6921 which also comply with HIPPA for patient privacy by providing a securable container. This limits container size to 32 gallons for patient records.

3. A kitchen located in a health care occupancy is not permitted to be provided with a standard size trash can of 50 gallons.

4. NFPA Research Report Structure Fires in Health Care Facilities 2011 – 2015 indicates that trash/rubbish/waste is not a major contributor to injuries related to a fire event. There was no documented instances of fires spreading from one trash can to another. A summary of the data in the report is below:

Number of Fires Number of Injuries Number of Deaths

Hospitals 320 3 0

Nursing Homes 120 1 0

Hospitals and Hospices 100 1 0

Mental Health Facilities 50 0 0

Clinics and Dr. Offices 50 0 0

a. The NFPA report did not distinguish between trash/rubbish/waste container located outside vs. inside.

5. Modifying the 32 gallon limitation to 64 gallons would make the requirement consistent with the threshold for a room storing soiled linen or trash to be considered a hazardous area is 64 gallons in the Protections for Hazards section. Response SR-6683-NFPA 101-2019 Message: Public Comment No. 54-NFPA 101-2019 [Section No. 21.7.5.5.1]

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 26 Affirmative All 0 Affirmative with Comments 2 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua Page 249 of 373

243 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Affirmative All Brooks, Bruce D. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Negative with Comment Bush, Kenneth E. The revised wording for 21.7.5.5.2 would permit containers of 64 gal or less capacity used solely for recycling clean waste or for patient records awaiting destruction to be used without restriction. This is a significant change from the existing Code text that has not been provided with sufficient technical justification. Koffel, William E. I remain concerned that this relaxation is too significant without a density restriction. Other than not normally expected in an ambulatory health care occupancy, what would prevent one from located several large containers (but less than 64 gal) in a room and in close proximity to each other?

Page 250 of 373

244 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6610-NFPA 101-2019 [ Section No. 22.1.6.1 ]

22.1.6.1 Detention and correctional occupancies shall be limited to the building construction types specified in Table 22.1.6.1. (See 8.2.1.) Table 22.1.6.1 Construction Type Limitations

Stories in Height † b Construction 1 With 1 Without >3 But Not High- Type Sprinklered* a Basement Basement 2 3 High-Rise Rise I(442) Yes X XXXXX No NP NP NP NP NP NP I(332) Yes X XXXXX No NP NP NP NP NP NP II(222) Yes X XXXXX No NP NP NP NP NP NP II(111) Yes X X X NP NP NP No NP NP NP NP NP NP II(000) Yes X X X NP NP NP No NP NP NP NP NP NP III(211) Yes X X X NP NP NP No NP NP NP NP NP NP III(200) Yes X X X NP NP NP No NP NP NP NP NP NP

IV(2HH) Yes X XX A NP c A NP c B NP No NP NP NP NP NP NP V(111) Yes X X X NP NP NP No NP NP NP NP NP NP V(000) Yes X X X NP NP NP No NP NP NP NP NP NP

X: Permitted for Use Conditions II, III, IV, and V. (See 22.1.2.3 for Use Condition I.) A: Permitted for Type IV buildings in accordance with 7.5.3 of NFPA 5000 . B: Permitted for Type IV buildings in accordance with 7.5.3.1 of NFPA 5000 . NP: Not permitted.

* a Sprinklered throughout by an approved, supervised automatic sprinkler system in accordance with 9.7.1.1(1). (See 22.3.5.)

† b See 4.6.3.

c Permitted for buildings up to 4 stories that comply with 4.5.6.1.1 of NFPA 220.

Submitter Information Verification

Committee: SAF-DET Submittal Date: Thu Jul 11 11:00:55 EDT 2019

Committee Statement Page 251 of 373

245 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Committee The committee has concerns with the use of mass timber exceeding 4 stories in height in detention Statement: and correctional occupancies. Although there is data available regarding the use mass timber, there is currently a lack of data regarding the specific use of mass timber in detention and correctional occupancies, and the impact on life safety in these occupancies due to the defend-in-place strategy and difficulties moving or evacuating occupants.

Response SR-6610-NFPA 101-2019 Message: Public Comment No. 63-NFPA 101-2019 [Section No. 22.1.6.1]

Ballot Results

This item has passed ballot

16 Eligible Voters 4 Not Returned 11 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned DiMascio, Michael Patterson, Van Hoover Perry, Robert R. Youngberg, Garrick

Affirmative All Aler, Clay P. Bollig, Tracy Collins, Peter J. Gaw, Randy Griffiths, Nolan T Heffernan, Rick Kelly, John Kruszelnicki, Michael Lumley, Troy A. Poole, Jack Schultz, Terry

Affirmative with Comment Stapleton, Jr., James A. NFPA 101-2018, paragraph 21.1.3.2.2, references ASTM F1577, “Standard Test Methods for Detention Locks for Swinging Doors”. The same paragraph occurs in NFPA 5000-2018. It may be worth considering to add other standards that are pertinent to the reliable performance of detention grade swinging and sliding doors, as well as sidelight and multi-lights door openings. These could be added as a list below each paragraph text as follows: 1. ASTM F1450, Standard Test Methods for Hollow Metal Swinging Door Assemblies for Detention Facilities 2. ASTM F1592, Standard Test Methods for Detention Hollow Metal Vision Systems 3. ASTM F2956, Standard Test Methods for Anchoring Systems for Hollow Metal Vision Systems and Door Assemblies Used in Detention and Page 252 of 373

246 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Correctional Facilities 4. ASTM A627, Standard Test Methods for Tool-Resisting Steel Bars, Flats, and Shapes for Detention and Correctional Facilities 5. ASTM F1643, Standard Test Methods for Detention Sliding Door Locking Device Assembly 6. ASTM F1758, Standard Test Method for Detention Hinges used on Detention Grade Swinging Doors

Page 253 of 373

247 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6615-NFPA 101-2019 [ Section No. 22.7.2 ]

22.7.2* Combustible Personal Property. in Sleeping Rooms. Books, clothing, and other combustible personal property allowed in sleeping rooms shall be stored in closable metal lockers or an approved fire-resistant container.

A.22.7.2

Personal property provides combustible contents for fire development. Therefore, adequate controls are needed to limit the quantity and combustibility of the fuels available to burn to reduce the probability of room flashover. The provisions of 22.7.4 will not, by themselves, prevent room flashover if personal property controls are not provided. Preventing room flashover with sprinkler protection does not necessarily ensure room tenability, and consideration should be given to an approved automatic smoke detection system.

22.7.2.1 Books, clothing, and other combustible personal property shall be stored in closable metal lockers or an approved fire-resistant container. 22.7.2.2 In buildings protected throughout with automatic sprinklers in accordance with Section 9.7 , where combustible personal property is not obstructed from sprinkler discharge, it shall be permitted to be stored on open shelving or in an approved storage location.

Submitter Information Verification

Committee: SAF-DET Submittal Date: Thu Jul 11 12:12:34 EDT 2019

Committee Statement

Committee This is reverting to the previous edition text. The revised language added in first draft introduced Statement: additional complications to the proper administration of storage of personal property. For the annex, the correlating main body text relates to limiting fire load and secure storage, and is not related to active fire protection systems. Response SR-6615-NFPA 101-2019 Message: Public Comment No. 188-NFPA 101-2019 [Section No. A.22.7.2]

Ballot Results

This item has passed ballot

16 Eligible Voters 4 Not Returned 11 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Page 254 of 373

248 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

DiMascio, Michael Patterson, Van Hoover Perry, Robert R. Youngberg, Garrick

Affirmative All Aler, Clay P. Bollig, Tracy Collins, Peter J. Gaw, Randy Griffiths, Nolan T Heffernan, Rick Kelly, John Kruszelnicki, Michael Lumley, Troy A. Poole, Jack Schultz, Terry

Affirmative with Comment Stapleton, Jr., James A. NFPA 101-2018, paragraph 21.1.3.2.2, references ASTM F1577, “Standard Test Methods for Detention Locks for Swinging Doors”. The same paragraph occurs in NFPA 5000-2018. It may be worth considering to add other standards that are pertinent to the reliable performance of detention grade swinging and sliding doors, as well as sidelight and multi-lights door openings. These could be added as a list below each paragraph text as follows: 1. ASTM F1450, Standard Test Methods for Hollow Metal Swinging Door Assemblies for Detention Facilities 2. ASTM F1592, Standard Test Methods for Detention Hollow Metal Vision Systems 3. ASTM F2956, Standard Test Methods for Anchoring Systems for Hollow Metal Vision Systems and Door Assemblies Used in Detention and Correctional Facilities 4. ASTM A627, Standard Test Methods for Tool-Resisting Steel Bars, Flats, and Shapes for Detention and Correctional Facilities 5. ASTM F1643, Standard Test Methods for Detention Sliding Door Locking Device Assembly 6. ASTM F1758, Standard Test Method for Detention Hinges used on Detention Grade Swinging Doors

Page 255 of 373

249 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6647-NFPA 101-2019 [ Section No. 23.7.2 ]

23.7.2* Combustible Personal Property. in Sleeping Rooms. Books, clothing, and other combustible personal property allowed in sleeping rooms shall be stored in closable metal lockers or an approved fire-resistant container.

A.23.7.2

Personal property provides combustible contents for fire development. Therefore, adequate controls are needed to limit the quantity and combustibility of the fuels available to burn to reduce the probability of room flashover. The provisions of 23.7.4 will not, by themselves, prevent room flashover if personal property controls are not provided. Preventing room flashover with sprinkler protection does not necessarily ensure room tenability, and consideration should be given to an approved automatic smoke detection system.

23.7.2.1 Books, clothing, and other combustible personal property shall be stored in closable metal lockers or an approved fire-resistant container. 23.7.2.2 In buildings protected throughout with automatic sprinklers in accordance with Section 9.7 , where combustible personal property is not obstructed from sprinkler discharge, it shall be permitted to be stored on open shelving or in an approved storage location.

Submitter Information Verification

Committee: SAF-DET Submittal Date: Tue Jul 16 11:11:34 EDT 2019

Committee Statement

Committee This is reverting to previous edition text. The revised language added in first draft introduced Statement: additional complication to the proper administration of storage of personal property. For the annex, the correlating main body text relates to limiting fire load and secure storage, and is not related to active fire protection systems. Response SR-6647-NFPA 101-2019 Message: Public Comment No. 189-NFPA 101-2019 [Section No. A.23.7.2]

Ballot Results

This item has passed ballot

16 Eligible Voters 4 Not Returned 11 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Page 256 of 373

250 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

DiMascio, Michael Patterson, Van Hoover Perry, Robert R. Youngberg, Garrick

Affirmative All Aler, Clay P. Bollig, Tracy Collins, Peter J. Gaw, Randy Griffiths, Nolan T Heffernan, Rick Kelly, John Kruszelnicki, Michael Lumley, Troy A. Poole, Jack Schultz, Terry

Affirmative with Comment Stapleton, Jr., James A. NFPA 101-2018, paragraph 21.1.3.2.2, references ASTM F1577, “Standard Test Methods for Detention Locks for Swinging Doors”. The same paragraph occurs in NFPA 5000-2018. It may be worth considering to add other standards that are pertinent to the reliable performance of detention grade swinging and sliding doors, as well as sidelight and multi-lights door openings. These could be added as a list below each paragraph text as follows: 1. ASTM F1450, Standard Test Methods for Hollow Metal Swinging Door Assemblies for Detention Facilities 2. ASTM F1592, Standard Test Methods for Detention Hollow Metal Vision Systems 3. ASTM F2956, Standard Test Methods for Anchoring Systems for Hollow Metal Vision Systems and Door Assemblies Used in Detention and Correctional Facilities 4. ASTM A627, Standard Test Methods for Tool-Resisting Steel Bars, Flats, and Shapes for Detention and Correctional Facilities 5. ASTM F1643, Standard Test Methods for Detention Sliding Door Locking Device Assembly 6. ASTM F1758, Standard Test Method for Detention Hinges used on Detention Grade Swinging Doors

Page 257 of 373

251 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6576-NFPA 101-2019 [ Section No. 28.2.5 ]

28.2.5 Arrangement of Means of Egress. 28.2.5.1 Means of egress shall be arranged in accordance with 28.2.5.1.1 and 28.2.5.1.2. 28.2.5.1.1 Means of egress shall be arranged in accordance with Section 7.5. 28.2.5.1.2 The distance between exits addressed by 7.5.1.3 shall not apply to common nonlooped exit access corridors in buildings that have corridor doors from the guest room or guest suite that are arranged such that the exits are located in opposite directions from such doors. 28.2.5.2 Limitations on common Common path of travel shall be in accordance comply with 28.2.5.2.1 or 28.2.5.2.2. 28.2.5.2.1 In buildings protected throughout by an approved, supervised automatic sprinkler system in accordance with 28.3.5, common path of travel shall not exceed 50 ft (15 m). 28.2.5.2.2 In buildings not protected throughout by an approved, supervised automatic sprinkler system in accordance with 28.3.5 other than those complying with 28.2.5.2.1 , common path of travel shall not exceed 35 ft (10.7 m). , which does not include travel within a guest room or guest suite when calculating common path of travel. 28.2.5.2.3 Travel within a guest room or guest suite shall not be included when calculating determining common path of travel. 28.2.5.3 Dead-end corridors shall be permitted in accordance with 28.2.5.3.1 or 28.2.5.3.2. 28.2.5.3.1 In buildings protected throughout by an approved, supervised automatic sprinkler system in accordance with 28.3.5, dead-end corridors shall not exceed 50 ft (15 m). 28.2.5.3.2 In buildings other than those complying with 28.2.5.3.1, dead-end corridors shall not exceed 35 ft (10.7 m). 28.2.5.4

Any guest room or any guest suite of rooms in excess of 2000 ft2 (185 m2) shall be provided with not less than two exit access doors remotely located from each other.

Supplemental Information

File Name Description Approved 101_PC-55.docx For staff use

Submitter Information Verification

Committee: SAF-RES Submittal Date: Mon Jul 08 11:26:23 EDT 2019

Page 258 of 373

252 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Committee Statement

Committee These changes were made to be consistent with formatting from other residential occupancy Statement: chapters.

Review format of arrangement criteria for consistency with other residential occupancy chapters and consider revising as appropriate.

NOTE: This Public Comment appeared as CC Note No. 42 in the First Draft Report on First Revision No. 6921. Response SR-6576-NFPA 101-2019 Message: Public Comment No. 55-NFPA 101-2019 [Section No. 28.2.5]

Ballot Results

This item has passed ballot

31 Eligible Voters 6 Not Returned 25 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Boyd, H. Wayne Damron, Donald P. Gould, Jennifer Klein Hall, William J. Sharry, John A. Zwirn, Jeffrey D.

Affirmative All Almannai, Ali Asp, Roland A. Bradley, Harry L. Buuck, Daniel Coats, Paul D. Cook, David Cotter, Patrick B. Cronin, Bradford T. Dawe, Nicholas A. Finnegan, Daniel P. Haidar, Abir Isman, Kenneth E. Lambert, Josh Larson, Mark Lathrop, James K.

Page 259 of 373

253 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Longhitano, Alfred J. Mayl, Eric N. Noble, Thomas William Paszczuk, Henry Pauls, Jake Pullen, William Davison Roberts, Richard Jay Spangler, Kevin Versteeg, Joseph H. Zubair Sarwar, Muhammad Ahmad

Page 260 of 373

254 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6629-NFPA 101-2019 [ Section No. 28.3.4.3.2 ]

28.3.4.3.2* In hotels and dormitories that are required by 28.3.4 to have a fire alarm system, the audible alarm notification signal provided in sleeping rooms of guest rooms or guest suites that is activated by the fire alarm system shall be a 520 Hz low-frequency signal in accordance with 9.6.2.10.3.

A.28.3.4.3.2

The standard audible alarm signal used in all fire alarm horns and integral sounders of smoke detectors for the past 30 years utilized a typical frequency of approximately 3 KHz. Peer‐reviewed research has concluded the waking effectiveness of a 520 Hz low-frequency signal is superior to the standard 3 KHz audible alarm signal for waking high‐risk segments of the population such as people over 65, people who are hard of hearing, school‐age children, and people who are alcohol‐impaired. Therefore, the 520 Hz low‐frequency audible alarm signal is now required in areas intended for sleeping within hotels and dormitories that are required to have a fire alarm system. The following product solutions are currently available in the market to produce the 520 Hz low‐frequency audible alarm signal in sleeping rooms: (1) Smoke detectors with integral sounder bases (2) Fire alarm system horns and horn/strobes (3) Speakers connected to an in‐building fire alarm emergency voice alarm communication (EVAC) system The peer-reviewed research project — Optimizing Fire Alarm Notification for High Risk Groups: Waking Effectiveness of Alarms (Auditory, Visual and Tactile) for Adults Who Are Hard of Hearing and Waking Effectiveness of Alarms (Auditory, Visual and Tactile) for the Alcohol Impaired — was conducted under the auspices of the Fire Protection Research Foundation.

Submitter Information Verification

Committee: SAF-RES Submittal Date: Mon Jul 15 09:12:38 EDT 2019

Committee Statement

Committee This language was developed by a task group to provide clarification to the intent of new Statement: section 28.3.4.3.2. Response Message: SR-6629-NFPA 101-2019 Public Comment No. 79-NFPA 101-2019 [New Section after A.28.3.4.3.1]

Ballot Results

This item has passed ballot

31 Eligible Voters 6 Not Returned 25 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Page 261 of 373

255 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Not Returned Boyd, H. Wayne Damron, Donald P. Gould, Jennifer Klein Hall, William J. Sharry, John A. Zwirn, Jeffrey D.

Affirmative All Almannai, Ali Asp, Roland A. Bradley, Harry L. Buuck, Daniel Coats, Paul D. Cook, David Cotter, Patrick B. Cronin, Bradford T. Dawe, Nicholas A. Finnegan, Daniel P. Haidar, Abir Isman, Kenneth E. Lambert, Josh Larson, Mark Lathrop, James K. Longhitano, Alfred J. Mayl, Eric N. Noble, Thomas William Paszczuk, Henry Pauls, Jake Pullen, William Davison Roberts, Richard Jay Spangler, Kevin Versteeg, Joseph H. Zubair Sarwar, Muhammad Ahmad

Page 262 of 373

256 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6630-NFPA 101-2019 [ Section No. 28.3.4.6.1 ]

28.3.4.6.1* In hotels and dormitories that are required by 28.3.4 to have a fire alarm system, the audible alarm notification signal provided in sleeping rooms of guest rooms or guest suites that is activated by smoke alarms shall be a 520 Hz low-frequency signal in accordance with 9.6.2.10.3.

A.28.3.4.6.1

The standard audible alarm signal used in all smoke alarms for the past 30 years utilized a typical frequency of approximately 3 KHz. Peer-reviewed research has concluded the waking effectiveness of the 520 Hz low-frequency signal is superior to the standard 3 KHz audible alarm signal for waking high-risk segments of the population such as people over 65, people who are hard of hearing, school- age children, and people who are alcohol impaired. Therefore, the 520 Hz low-frequency audible alarm signal is now required for smoke alarms in areas intended for sleeping within hotels and dormitories that are required to have a fire alarm system. If smoke alarms capable of producing the low-frequency audible alarm signal are not available, smoke detectors arranged to function in the same manner as smoke alarms in accordance with 9.6.2.10.8 would be required. The following product solutions are currently available in the market if the smoke alarm is unable to produce the 520 Hz low-frequency audible alarm signal in sleeping rooms: (1) Smoke detectors with integral sounder bases (2) Fire alarm system horns and horn/strobes (3) Speakers connected to an in-building fire alarm emergency voice alarm communication (EVAC) system The peer-reviewed research project — Optimizing Fire Alarm Notification for High Risk Groups: Waking Effectiveness of Alarms (Auditory, Visual and Tactile) for Adults Who Are Hard of Hearing and Waking Effectiveness of Alarms (Auditory, Visual and Tactile) for the Alcohol Impaired — was conducted under the auspices of the Fire Protection Research Foundation.

Submitter Information Verification

Committee: SAF-RES Submittal Date: Mon Jul 15 09:22:29 EDT 2019

Committee Statement

Committee This language was developed by a task group to provide clarification to the intent of new Statement: section 28.3.4.6.1. Response Message: SR-6630-NFPA 101-2019 Public Comment No. 80-NFPA 101-2019 [New Section after A.28.3.4.6]

Ballot Results

This item has passed ballot

31 Eligible Voters 6 Not Returned 25 Affirmative All 0 Affirmative with Comments 0 Negative with Comments

Page 263 of 373

257 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

0 Abstention

Not Returned Boyd, H. Wayne Damron, Donald P. Gould, Jennifer Klein Hall, William J. Sharry, John A. Zwirn, Jeffrey D.

Affirmative All Almannai, Ali Asp, Roland A. Bradley, Harry L. Buuck, Daniel Coats, Paul D. Cook, David Cotter, Patrick B. Cronin, Bradford T. Dawe, Nicholas A. Finnegan, Daniel P. Haidar, Abir Isman, Kenneth E. Lambert, Josh Larson, Mark Lathrop, James K. Longhitano, Alfred J. Mayl, Eric N. Noble, Thomas William Paszczuk, Henry Pauls, Jake Pullen, William Davison Roberts, Richard Jay Spangler, Kevin Versteeg, Joseph H. Zubair Sarwar, Muhammad Ahmad

Page 264 of 373

258 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6582-NFPA 101-2019 [ Section No. 28.3.4.7.2 ]

28.3.4.7.2 Where required by 28.3.4.7.1, carbon monoxide alarms or carbon monoxide detectors shall be installed in the following locations: on every occupiable level of a guest room and guest suite and in the immediate vicinity of the sleeping rooms. Outside of each separate guest room or guest suite sleeping area in the immediate vicinity of the sleeping rooms On every occupiable level of a guest room and guest suite

Submitter Information Verification

Committee: SAF-RES Submittal Date: Mon Jul 08 19:46:07 EDT 2019

Committee Statement

Committee This provides clarification on the requirements for where CO alarms are required to be Statement: provided. Response Message: SR-6582-NFPA 101-2019

Ballot Results

This item has passed ballot

31 Eligible Voters 6 Not Returned 25 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Boyd, H. Wayne Damron, Donald P. Gould, Jennifer Klein Hall, William J. Sharry, John A. Zwirn, Jeffrey D.

Affirmative All Almannai, Ali Asp, Roland A. Bradley, Harry L. Buuck, Daniel Coats, Paul D. Page 265 of 373

259 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Cook, David Cotter, Patrick B. Cronin, Bradford T. Dawe, Nicholas A. Finnegan, Daniel P. Haidar, Abir Isman, Kenneth E. Lambert, Josh Larson, Mark Lathrop, James K. Longhitano, Alfred J. Mayl, Eric N. Noble, Thomas William Paszczuk, Henry Pauls, Jake Pullen, William Davison Roberts, Richard Jay Spangler, Kevin Versteeg, Joseph H. Zubair Sarwar, Muhammad Ahmad

Page 266 of 373

260 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6578-NFPA 101-2019 [ Section No. 28.3.5.1 ]

28.3.5.1 All buildings, other than those complying with 28.3.5.2 , shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with 28.3.5.3.

Submitter Information Verification

Committee: SAF-RES Submittal Date: Mon Jul 08 12:16:25 EDT 2019

Committee Statement

Committee Section 28.3.5.2 is reserved and contains no sprinkler exemption. Statement: NOTE: This Public Comment appeared as CC Note No. 43 in the First Draft Report on First Revision No. 6934.

Response Message: SR-6578-NFPA 101-2019 Public Comment No. 56-NFPA 101-2019 [Section No. 28.3.5.1]

Ballot Results

This item has passed ballot

31 Eligible Voters 6 Not Returned 24 Affirmative All 0 Affirmative with Comments 1 Negative with Comments 0 Abstention

Not Returned Boyd, H. Wayne Damron, Donald P. Gould, Jennifer Klein Hall, William J. Sharry, John A. Zwirn, Jeffrey D.

Affirmative All Almannai, Ali Asp, Roland A. Bradley, Harry L. Page 267 of 373

261 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Buuck, Daniel Coats, Paul D. Cook, David Cotter, Patrick B. Cronin, Bradford T. Dawe, Nicholas A. Finnegan, Daniel P. Haidar, Abir Isman, Kenneth E. Lambert, Josh Larson, Mark Lathrop, James K. Mayl, Eric N. Noble, Thomas William Paszczuk, Henry Pauls, Jake Pullen, William Davison Roberts, Richard Jay Spangler, Kevin Versteeg, Joseph H. Zubair Sarwar, Muhammad Ahmad

Negative with Comment Longhitano, Alfred J. I cannot vote for a provision that requires sprinklers in a single story motel with every room having a direct exit to grade. Nobody can consider that a MINIMUM requirement for life safety. I realize that the requirement is in the 2018 edition, but to support this change would look like support for this vastly overreaching provision.

Page 268 of 373

262 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6594-NFPA 101-2019 [ Section No. 29.3.4.6.2 ]

29.3.4.6.2 Where required by 29.3.4.6.1, carbon monoxide alarms or carbon monoxide detectors shall be installed in the following locations: on every occupiable level of a guest room and guest suite and in the immediate vicinity of the sleeping rooms. Outside of each separate guest room or guest suite sleeping area in the immediate vicinity of the sleeping rooms On every occupiable level of a guest room and guest suite

Submitter Information Verification

Committee: SAF-RES Submittal Date: Wed Jul 10 08:28:20 EDT 2019

Committee Statement

Committee This change provides clarification on the requirements for where CO alarms are required to Statement: be provided. Response Message: SR-6594-NFPA 101-2019

Ballot Results

This item has passed ballot

31 Eligible Voters 6 Not Returned 25 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Boyd, H. Wayne Damron, Donald P. Gould, Jennifer Klein Hall, William J. Sharry, John A. Zwirn, Jeffrey D.

Affirmative All Almannai, Ali Asp, Roland A. Bradley, Harry L. Buuck, Daniel Coats, Paul D. Page 269 of 373

263 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Cook, David Cotter, Patrick B. Cronin, Bradford T. Dawe, Nicholas A. Finnegan, Daniel P. Haidar, Abir Isman, Kenneth E. Lambert, Josh Larson, Mark Lathrop, James K. Longhitano, Alfred J. Mayl, Eric N. Noble, Thomas William Paszczuk, Henry Pauls, Jake Pullen, William Davison Roberts, Richard Jay Spangler, Kevin Versteeg, Joseph H. Zubair Sarwar, Muhammad Ahmad

Page 270 of 373

264 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6577-NFPA 101-2019 [ Section No. 30.2.5.2.2 ]

30.2.5.2.2 In buildings other than those complying with 30.2.5.2.1, common path of travel shall not exceed 35 ft (10.7 m).

Submitter Information Verification

Committee: SAF-RES Submittal Date: Mon Jul 08 11:28:02 EDT 2019

Committee Statement

Committee This section is supposed to reference 30.2.5.2.1, and this change is correct the section Statement: reference. Response Message: SR-6577-NFPA 101-2019

Ballot Results

This item has passed ballot

31 Eligible Voters 6 Not Returned 25 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Boyd, H. Wayne Damron, Donald P. Gould, Jennifer Klein Hall, William J. Sharry, John A. Zwirn, Jeffrey D.

Affirmative All Almannai, Ali Asp, Roland A. Bradley, Harry L. Buuck, Daniel Coats, Paul D. Cook, David Cotter, Patrick B. Cronin, Bradford T.

Page 271 of 373

265 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Dawe, Nicholas A. Finnegan, Daniel P. Haidar, Abir Isman, Kenneth E. Lambert, Josh Larson, Mark Lathrop, James K. Longhitano, Alfred J. Mayl, Eric N. Noble, Thomas William Paszczuk, Henry Pauls, Jake Pullen, William Davison Roberts, Richard Jay Spangler, Kevin Versteeg, Joseph H. Zubair Sarwar, Muhammad Ahmad

Page 272 of 373

266 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6631-NFPA 101-2019 [ Section No. 30.3.4.3.2 ]

30.3.4.3.2* In apartment buildings that are required by 30.3.4.1 to have a fire alarm system, the audible alarm notification signal provided in sleeping rooms of dwelling units that is activated by the fire alarm system shall be a 520 Hz low-frequency signal in accordance with 9.6.3.9.

A.30.3.4.3.2

The standard audible alarm signal used in all fire alarm horns and integral sounders of smoke detectors for the past 30 years utilized a typical frequency of approximately 3 KHz. Peer‐reviewed research has concluded the waking effectiveness of a 520 Hz low-frequency signal is superior to the standard 3 KHz audible alarm signal for waking high‐risk segments of the population such as people over 65, people who are hard of hearing, school‐age children, and people who are alcohol impaired. Therefore, the 520 Hz low‐frequency audible alarm signal is now required in areas intended for sleeping within apartment buildings that are required to have a fire alarm system. The following product solutions are currently available in the market to produce the 520 Hz low‐frequency audible alarm signal in sleeping rooms: (1) Smoke detectors with integral sounder bases (2) Fire alarm system horns and horn/strobes (3) Speakers connected to an in‐building fire alarm emergency voice alarm communication (EVAC) system The peer-reviewed research project — Optimizing Fire Alarm Notification for High Risk Groups: Waking Effectiveness of Alarms (Auditory, Visual and Tactile) for Adults Who Are Hard of Hearing and Waking Effectiveness of Alarms (Auditory, Visual and Tactile) for the Alcohol Impaired — was conducted under the auspices of the Fire Protection Research Foundation.

Submitter Information Verification

Committee: SAF-RES Submittal Date: Mon Jul 15 09:28:06 EDT 2019

Committee Statement

Committee This language was developed by a task group to provide clarification to the intent of new Statement: section 30.3.4.3.2. Response Message: SR-6631-NFPA 101-2019 Public Comment No. 81-NFPA 101-2019 [New Section after A.30.2.2.12.2]

Ballot Results

This item has passed ballot

31 Eligible Voters 6 Not Returned 25 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Page 273 of 373

267 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Not Returned Boyd, H. Wayne Damron, Donald P. Gould, Jennifer Klein Hall, William J. Sharry, John A. Zwirn, Jeffrey D.

Affirmative All Almannai, Ali Asp, Roland A. Bradley, Harry L. Buuck, Daniel Coats, Paul D. Cook, David Cotter, Patrick B. Cronin, Bradford T. Dawe, Nicholas A. Finnegan, Daniel P. Haidar, Abir Isman, Kenneth E. Lambert, Josh Larson, Mark Lathrop, James K. Longhitano, Alfred J. Mayl, Eric N. Noble, Thomas William Paszczuk, Henry Pauls, Jake Pullen, William Davison Roberts, Richard Jay Spangler, Kevin Versteeg, Joseph H. Zubair Sarwar, Muhammad Ahmad

Page 274 of 373

268 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6632-NFPA 101-2019 [ Section No. 30.3.4.5.1 ]

30.3.4.5.1* In apartment buildings that are required by 30.3.4 to have a fire alarm system, the audible alarm notification signal provided in sleeping rooms that is activated by smoke alarms shall be a 520 Hz low- frequency signal in accordance with 9.6.2.10.3.

A.30.3.4.5.1

The standard audible alarm signal used in all smoke alarms for the past 30 years utilized a typical frequency of approximately 3 KHz. Peer-reviewed research has concluded the waking effectiveness of the 520 Hz low-frequency signal is superior to the standard 3 KHz audible alarm signal for waking high-risk segments of the population such as people over 65, people who are hard of hearing, school- age children, and people who are alcohol impaired. Therefore, the 520 Hz low-frequency audible alarm signal is now required for smoke alarms in areas intended for sleeping within apartment buildings that are required to have a fire alarm system. If smoke alarms that are capable of producing the low- frequency audible alarm signal are not available, smoke detectors arranged to function in the same manner as smoke alarms in accordance with 9.6.2.10.8 would be required. The following product solutions are currently available in the market if the smoke alarm is unable to produce the 520 Hz low- frequency audible alarm signal in sleeping rooms: (1) Smoke detectors with integral sounder bases (2) Fire alarm system horns and horn/strobes (3) Speakers connected to an in-building fire alarm emergency voice alarm communication (EVAC) system The peer-reviewed research project — Optimizing Fire Alarm Notification for High Risk Groups: Waking Effectiveness of Alarms (Auditory, Visual and Tactile) for Adults Who Are Hard of Hearing and Waking Effectiveness of Alarms (Auditory, Visual and Tactile) for the Alcohol Impaired — was conducted under the auspices of the Fire Protection Research Foundation.

Submitter Information Verification

Committee: SAF-RES Submittal Date: Mon Jul 15 09:34:54 EDT 2019

Committee Statement

Committee This language was developed by a task group to provide clarification to the intent of new Statement: section 30.3.4.5.1. Response Message: SR-6632-NFPA 101-2019 Public Comment No. 82-NFPA 101-2019 [New Section after A.30.2.2.12.2]

Ballot Results

This item has passed ballot

31 Eligible Voters 6 Not Returned 25 Affirmative All 0 Affirmative with Comments 0 Negative with Comments

Page 275 of 373

269 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

0 Abstention

Not Returned Boyd, H. Wayne Damron, Donald P. Gould, Jennifer Klein Hall, William J. Sharry, John A. Zwirn, Jeffrey D.

Affirmative All Almannai, Ali Asp, Roland A. Bradley, Harry L. Buuck, Daniel Coats, Paul D. Cook, David Cotter, Patrick B. Cronin, Bradford T. Dawe, Nicholas A. Finnegan, Daniel P. Haidar, Abir Isman, Kenneth E. Lambert, Josh Larson, Mark Lathrop, James K. Longhitano, Alfred J. Mayl, Eric N. Noble, Thomas William Paszczuk, Henry Pauls, Jake Pullen, William Davison Roberts, Richard Jay Spangler, Kevin Versteeg, Joseph H. Zubair Sarwar, Muhammad Ahmad

Page 276 of 373

270 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6602-NFPA 101-2019 [ Section No. 30.3.5 ]

30.3.5 Extinguishment Requirements. 30.3.5.1 General. All buildings shall be protected throughout by an approved, supervised automatic sprinkler system installed in accordance with 30.3.5.2 30.3.5.1 through 30.3.5.6 . 30.3.5.1.1 Where an automatic sprinkler system is installed, the system shall be in accordance with Section 9.7, as modified by 30.3.5.4 30.3.5.5 . In apartment buildings up to and including four stories in height, that are located in buildings not exceeding 60 ft (18.3 m) in height above grade plane, systems in accordance with NFPA 13R shall be permitted. 30.3.5.1.2 In apartment buildings up to and including four stories in height, that are located in buildings not exceeding 60 ft (18.3 m) in height above grade plane, systems in accordance with NFPA 13R shall be permitted. 30.3.5.2 Attics. Where located in a building of Type III, Type IV, or Type V construction designed in accordance with 4.6.3(5) and where the roof assembly is located more than 55 ft (17 m) above the lowest level of required fire department vehicle access, attics shall comply with 30.3.5.1.1.2.1 30.3.5.2.1 , 30.3.5.1.1.2.2 30.3.5.2.2 , and one of the following: (1) Attics shall be provided with sprinkler protection. (2) Attics shall be constructed with noncombustible materials. (3) Attics shall be constructed with fire-retardant-treated wood (4) Attics shall be filled with noncombustible insulation 30.3.5.2.1 The height of the roof assembly shall be determined by measuring the distance from the lowest level of required fire department vehicle access adjacent to the building to the eave of the highest pitched roof, the intersection of the highest roof to the exterior wall, or the top of the highest parapet, whichever yields the greatest distance. 30.3.5.2.2 Required fire department vehicle access roads used in 30.3.5.1.1.2.1 30.3.5.2.1 shall include only those roads that are necessary for required fire department vehicle access in compliance with the fire code. 30.3.5.3* Closets. In buildings sprinklered in accordance with NFPA 13, closets shall meet the following requirements:

(1) Closets of less than 12 ft2 (1.1 m2) in individual dwelling units shall not be required to be sprinklered. (2) Closets that contain equipment such as washers, dryers, furnaces, or water heaters shall be sprinklered, regardless of size. 30.3.5.4 Convenience Openings. The draft stop and closely spaced sprinkler requirements of NFPA 13 shall not be required for convenience openings complying with 8.6.9.1 where the convenience opening is within the dwelling unit. 30.3.5.5 Open Parking Structures. Open parking structures complying with NFPA 88A that are contiguous with apartment buildings shall be exempt from the sprinkler requirements of 30.3.5.1. 30.3.5.6 Unprotected Openings. Buildings with unprotected openings in accordance with 8.6.6 shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with 30.3.5. 30.3.5.7 Reserved. Page 277 of 373

271 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

30.3.5.8 Reserved. 30.3.5.9 Reserved. 30.3.5.10 Reserved. 30.3.5.7 Portable Fire Extinguishers. Portable fire extinguishers in accordance with Section 9.9 shall be provided in hazardous areas addressed by 30.3.2.1, unless the building is protected throughout with an approved, supervised automatic sprinkler system in accordance with 30.3.5.1.1.

Supplemental Information

File Name Description Approved 101_30.3.5_Reorg.docx For staff use

Submitter Information Verification

Committee: SAF-RES Submittal Date: Wed Jul 10 12:33:07 EDT 2019

Committee Statement

Committee The following changes are a reorganization to correlate organization of 101, 30.3.5 and 5000, Statement: 25.3.5. The change is limited to formatting and does not include technical changes. Response SR-6602-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

31 Eligible Voters 6 Not Returned 25 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Boyd, H. Wayne Damron, Donald P. Gould, Jennifer Klein Hall, William J. Sharry, John A. Zwirn, Jeffrey D.

Affirmative All Almannai, Ali Asp, Roland A. Bradley, Harry L. Buuck, Daniel Coats, Paul D.

Page 278 of 373

272 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Cook, David Cotter, Patrick B. Cronin, Bradford T. Dawe, Nicholas A. Finnegan, Daniel P. Haidar, Abir Isman, Kenneth E. Lambert, Josh Larson, Mark Lathrop, James K. Longhitano, Alfred J. Mayl, Eric N. Noble, Thomas William Paszczuk, Henry Pauls, Jake Pullen, William Davison Roberts, Richard Jay Spangler, Kevin Versteeg, Joseph H. Zubair Sarwar, Muhammad Ahmad

Page 279 of 373

273 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6579-NFPA 101-2019 [ Section No. 30.4 ]

30.4 Special Provisions. 30.4.1 Special Structures. Apartments buildings or portions thereof shall comply with Chapter 11 where located in a special structure. 30.4.2 High-Rise Buildings. 30.4.2.1 High-rise buildings shall comply with Section 11.8. The provisions of 30.3.5.2 30.3.5.3 and 30.3.4.5 shall be permitted. 30.4.2.2* Emergency action plans in accordance with Section 4.8 shall be provided and shall include all of the following: (1) Egress procedures (2) Methods (3) Preferred evacuation routes for each event, including appropriate use of elevators 30.4.3 Alcohol-Based Hand-Rub Dispensers. Alcohol-based hand-rub dispensers in accordance with 8.7.3.3 shall be permitted.

Submitter Information Verification

Committee: SAF-RES Submittal Date: Mon Jul 08 12:26:03 EDT 2019

Committee Statement

Committee This provides clarification that this section is applicable to buildings containing apartments, not Statement: the individual apartments.

Consider revising 30.4.1 to read, "Apartment buildings shall comply with Chapter 11 where located in a special structure." The term 'apartment building' refers to the occupancy classification, whereas 'apartment' refers to an individual dwelling unit.

NOTE: This Public Comment appeared as CC Note No. 44 in the First Draft Report on First Revision No. 6928. Response SR-6579-NFPA 101-2019 Message: Public Comment No. 57-NFPA 101-2019 [Section No. 30.4]

Ballot Results

This item has passed ballot

31 Eligible Voters 6 Not Returned 25 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Page 280 of 373

274 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Not Returned Boyd, H. Wayne Damron, Donald P. Gould, Jennifer Klein Hall, William J. Sharry, John A. Zwirn, Jeffrey D.

Affirmative All Almannai, Ali Asp, Roland A. Bradley, Harry L. Buuck, Daniel Coats, Paul D. Cook, David Cotter, Patrick B. Cronin, Bradford T. Dawe, Nicholas A. Finnegan, Daniel P. Haidar, Abir Isman, Kenneth E. Lambert, Josh Larson, Mark Lathrop, James K. Longhitano, Alfred J. Mayl, Eric N. Noble, Thomas William Paszczuk, Henry Pauls, Jake Pullen, William Davison Roberts, Richard Jay Spangler, Kevin Versteeg, Joseph H. Zubair Sarwar, Muhammad Ahmad

Page 281 of 373

275 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6587-NFPA 101-2019 [ Section No. 30.7.5 ]

30.7.5 Valet Trash Collection Services. 30.7.5.1 Combustible trash or recyclable materials in corridors or on egress balconies awaiting scheduled valet trash collection shall be placed completely inside a container that does not exceed a capacity of 15 gal (60 L) in corridors and 22 gal (95 L) on egress balconies and is equipped with a tight-fitting lid. 30.7.5.2 Containers and lids shall be constructed entirely of noncombustible materials or materials that meet a peak rate of heat release not exceeding 300 kW/m2 when tested in accordance with ASTM E1354, Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter, at an incident heat flux of 50 kW/m2 in the horizontal orientation. 30.7.5.3 Containers shall not be required to comply with 30.7.5.2 for the following: (1) Containers in sprinklered corridors or egress balconies in buildings provided with a sprinkler system complying with 30.3.5 (2) Containers on egress balconies in buildings with noncombustible or limited combustible exteriors 30.7.5.4 Containers shall not occupy a corridor for a single period exceeding 18 hours and shall not obstruct the minimum egress width required by 30.2.3. 30.7.5.5 Containers shall not occupy a corridor for a single period exceeding 18 hours. 30.7.5.6 Combustible trash or recycling materials shall not occupy a corridor for a single period exceeding 5 hours.

Submitter Information Verification

Committee: SAF-RES Submittal Date: Tue Jul 09 15:51:56 EDT 2019

Committee Statement

Committee The committee has reviewed the numerous public comments as well as the language from the first Statement: draft report and has decided upon the following language. The addition of alternate materials for containers in sprinklered building or buildings with non-combustible exterior addresses the increased protection in these buildings, and therefore, it is not necessary to provided non-combustible containers. The requirement for tight-fitting lids was removed due to the potential entrapment for children and animals. The increased in larger containers for exterior egress balconies was added due to the reduced risk of smoke accumulation in exterior locations. The addition of requirement time limitations for trash and recycling materials was added to address the largest risk is from the combustible materials within the containers. Response SR-6587-NFPA 101-2019 Message: Public Comment No. 242-NFPA 101-2019 [Section No. 30.7.5] Public Comment No. 244-NFPA 101-2019 [Section No. 30.7.5] Public Comment No. 214-NFPA 101-2019 [Section No. 30.7.5] Public Comment No. 92-NFPA 101-2019 [Section No. 30.7.5]

Page 282 of 373

276 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Public Comment No. 246-NFPA 101-2019 [Section No. 30.7.5.3] Public Comment No. 239-NFPA 101-2019 [Section No. 30.7.5] Public Comment No. 186-NFPA 101-2019 [Section No. 30.7.5] Public Comment No. 177-NFPA 101-2019 [Section No. 30.7.5] Public Comment No. 172-NFPA 101-2019 [Section No. 30.7.5] Public Comment No. 173-NFPA 101-2019 [Section No. 30.7.5] Public Comment No. 200-NFPA 101-2019 [Section No. 30.7.5] Public Comment No. 241-NFPA 101-2019 [Section No. 30.7.5]

Ballot Results

This item has passed ballot

31 Eligible Voters 6 Not Returned 22 Affirmative All 1 Affirmative with Comments 2 Negative with Comments 0 Abstention

Not Returned Boyd, H. Wayne Damron, Donald P. Gould, Jennifer Klein Hall, William J. Sharry, John A. Zwirn, Jeffrey D.

Affirmative All Almannai, Ali Asp, Roland A. Buuck, Daniel Coats, Paul D. Cook, David Cotter, Patrick B. Cronin, Bradford T. Dawe, Nicholas A. Finnegan, Daniel P. Haidar, Abir Isman, Kenneth E. Lambert, Josh Larson, Mark Lathrop, James K. Longhitano, Alfred J. Noble, Thomas William Pauls, Jake Page 283 of 373

277 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Pullen, William Davison Roberts, Richard Jay Spangler, Kevin Versteeg, Joseph H. Zubair Sarwar, Muhammad Ahmad

Affirmative with Comment Mayl, Eric N. The intent of §307.5.6 is not clear. As written it is not clear if the intent is to limit containers containing combustible trash to less than 5hours or if the intent is to limit combustible trash not in a container to less than 5hhours. More appropriate wording would be, containers containing combustible trash or recycling materials shall not occupy a corridor for a single period exceeding 5 hours.

Negative with Comment Bradley, Harry L. The IFMA opposes this change Paszczuk, Henry The CT State Fire Marshal's Office opposes this proposal due to the 18 hour time limit would be difficult for an enforcer to monitor and that there exists a potential for the the receptacles to be moved and placed within the the means of egress which could led to an obstructed path of travel.

Page 284 of 373

278 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6589-NFPA 101-2019 [ Section No. 31.3.5.12 ]

31.3.5.12* High-Rise Building Sprinklers.

Detail SR-6581 31.3.5.12.1* All high-rise buildings, other than those meeting 31.3.5.12.2, 31.3.5.12.3 , or 31.3.5.12.6 , shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with 31.3.5.2within 12 years of the adoption of this Code by January 1, 2033. 31.3.5.12.2 An automatic sprinkler system shall not be required where every dwelling unit has exterior exit access in accordance with 7.5.3. 31.3.5.12.3 An automatic sprinkler system shall not be required in buildings that have a previously approved and implemented engineered life safety system that was developed in accordance with 31.3.5.12.4 and 31.3.5.12.6 . 31.3.5.12.4 The engineered life safety system shall have been developed by a registered professional engineer experienced in fire and life safety system design, approved by the authority having jurisdiction, and inspected for compliance by the authority having jurisdiction, and shall include any or all of the following: (1) Partial automatic sprinkler protection (2) Smoke detection systems (3) Smoke control systems (4) Compartmentation (5) Other approved systems 31.3.5.12.5 Previously approved engineered life safety systems shall be maintained in accordance with the approved design documents and applicable standard. If the system is not maintained, then the building shall comply with 31.3.5.12.1 or 31.3.5.12.6 . 31.3.5.12.6 An automatic sprinkler system shall not be required in buildings having an approved performance-based option in compliance with Chapter 5 .

Submitter Information Verification

Committee: SAF-RES Submittal Date: Tue Jul 09 16:21:13 EDT 2019

Committee Statement

Committee The committee felt that existing approved engineered life safety systems should be permitted to Statement: maintain. It is important that the existing engineered life safety system is both inspected and maintained per the original design. Response SR-6589-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot Page 285 of 373

279 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

31 Eligible Voters 6 Not Returned 25 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Boyd, H. Wayne Damron, Donald P. Gould, Jennifer Klein Hall, William J. Sharry, John A. Zwirn, Jeffrey D.

Affirmative All Almannai, Ali Asp, Roland A. Bradley, Harry L. Buuck, Daniel Coats, Paul D. Cook, David Cotter, Patrick B. Cronin, Bradford T. Dawe, Nicholas A. Finnegan, Daniel P. Haidar, Abir Isman, Kenneth E. Lambert, Josh Larson, Mark Lathrop, James K. Longhitano, Alfred J. Mayl, Eric N. Noble, Thomas William Paszczuk, Henry Pauls, Jake Pullen, William Davison Roberts, Richard Jay Spangler, Kevin Versteeg, Joseph H. Zubair Sarwar, Muhammad Ahmad

Page 286 of 373

280 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6588-NFPA 101-2019 [ Section No. 31.7.5 ]

31.7.5 Valet Trash and Recycling Collection Services. 31.7.5.1 Combustible trash or recyclable materials in corridors or on egress balconies awaiting scheduled valet trash collection shall be permitted in accordance with 31.7.5.2 through 31.7.5.5 . 31.7.5.2 Containers shall not obstruct the minimum egress width required by 31.2.3 . 31.7.5.1 Combustible trash or recyclable materials in corridors or on egress balconies awaiting scheduled collection shall be placed completely inside a container that does not exceed a capacity of 15 gal (60 L) in corridors and 22 gal (95 L) on egress balconies and is equipped with a tight-fitting lid. 31.7.5.2 Containers and lids shall be constructed entirely of noncombustible materials or materials that meet a peak rate of heat release not exceeding 300 kW/m2 when tested in accordance with ASTM E1354, Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter, at an incident heat flux of 50 kW/m2 in the horizontal orientation. 31.7.5.3 Containers shall not be required to comply with 31.7.5.2 for the following: (1) Containers in sprinklered corridors or egress balconies in buildings provided with a sprinkler system complying with 30.3.5 (2) Containers on egress balconies in buildings with noncombustible or limited combustible exteriors 31.7.5.4 Containers shall not obstruct the minimum egress width required by 31.2.3 . 31.7.5.5 Containers shall not occupy a corridor for a single period exceeding 18 hours. 31.7.5.6 Combustible trash or recycling materials shall not occupy a corridor for a single period exceeding 5 hours.

Submitter Information Verification

Committee: SAF-RES Submittal Date: Tue Jul 09 16:05:42 EDT 2019

Committee Statement

Committee The committee has reviewed the numerous public comments as well as the language from the first Statement: draft report and has decided upon the following language. The addition of alternate materials for containers in sprinklered building or buildings with non-combustible exterior addresses the increased protection in these buildings, and therefore, it is not necessary to provided non-combustible containers. The requirement for tight-fitting lids was removed due to the potential entrapment for children and animals. The increased in larger containers for exterior egress balconies was added due to the reduced risk of smoke accumulation in exterior locations. The addition of requirement time limitations for trash and recycling materials was added to address the largest risk is from the combustible materials within the containers. Response SR-6588-NFPA 101-2019 Message:

Page 287 of 373

281 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Public Comment No. 93-NFPA 101-2019 [Section No. 31.7.5] Public Comment No. 180-NFPA 101-2019 [Section No. 31.7.5] Public Comment No. 181-NFPA 101-2019 [Section No. 31.7.5] Public Comment No. 182-NFPA 101-2019 [Section No. 31.7.5] Public Comment No. 201-NFPA 101-2019 [Section No. 31.7.5] Public Comment No. 211-NFPA 101-2019 [Section No. 31.7.5] Public Comment No. 215-NFPA 101-2019 [Section No. 31.7.5] Public Comment No. 240-NFPA 101-2019 [Section No. 31.7.5] Public Comment No. 243-NFPA 101-2019 [Section No. 31.7.5] Public Comment No. 248-NFPA 101-2019 [Section No. 31.7.5.3] Public Comment No. 249-NFPA 101-2019 [Section No. 31.7.5.4] Public Comment No. 247-NFPA 101-2019 [Section No. 31.7.5.5]

Ballot Results

This item has passed ballot

31 Eligible Voters 6 Not Returned 22 Affirmative All 1 Affirmative with Comments 2 Negative with Comments 0 Abstention

Not Returned Boyd, H. Wayne Damron, Donald P. Gould, Jennifer Klein Hall, William J. Sharry, John A. Zwirn, Jeffrey D.

Affirmative All Almannai, Ali Asp, Roland A. Buuck, Daniel Coats, Paul D. Cook, David Cotter, Patrick B. Cronin, Bradford T. Dawe, Nicholas A. Finnegan, Daniel P. Haidar, Abir Isman, Kenneth E. Lambert, Josh Larson, Mark Page 288 of 373

282 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Lathrop, James K. Longhitano, Alfred J. Noble, Thomas William Pauls, Jake Pullen, William Davison Roberts, Richard Jay Spangler, Kevin Versteeg, Joseph H. Zubair Sarwar, Muhammad Ahmad

Affirmative with Comment Mayl, Eric N. The intent of §307.5.6 is not clear. As written it is not clear if the intent is to limit containers containing combustible trash to less than 5hours or if the intent is to limit combustible trash not in a container to less than 5hhours. More appropriate wording would be, containers containing combustible trash or recycling materials shall not occupy a corridor for a single period exceeding 5 hours.

Negative with Comment Bradley, Harry L. The IFMA opposes this Change Paszczuk, Henry The CT State Fire Marshal's Office opposes this proposal due to the 18 hour time limit would be difficult for an enforcer to monitor and that there exists a potential for the the receptacles to be moved and placed within the the means of egress which could led to an obstructed path of travel.

Page 289 of 373

283 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6583-NFPA 101-2019 [ Section No. 32.1.1.5 ]

32.1.1.5 Chapter Sections. This chapter is divided into three five sections as follows: (1) Section 32.1 — General Requirements (2) Section 32.2 — Small Facilities (that is, sleeping accommodations for not more than 16 residents) (3) Section 32.3 — Large Facilities (that is, sleeping accommodations for more than 16 residents) (4) Section 32.4 — Suitability of an Apartment Building to House a Board and Care Occupancy (Sections 32.5 and 32.6 are reserved.) (5) Section 32.7 — Operating Features

Submitter Information Verification

Committee: SAF-BCF Submittal Date: Tue Jul 09 09:57:10 EDT 2019

Committee Statement

Committee This is restoring text from previous edition which was removed at first draft to correlated with Statement: 5000, however, these chapters exist in 101 and not in 5000. Response SR-6583-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

24 Eligible Voters 2 Not Returned 22 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Allen, Scott D. Jones, Adam C.

Affirmative All Asp, Roland A. Beebe, Chad E. Bell, Kerry M. Bellamy, Tracey D. Bradley, Harry L. Day, Richard L.

Page 290 of 373

284 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Eaddy, Rebekah L. Farraher, Martin J. Gabriele, Nicholas E. Grant, Kurtis Heaney, Steven Larrimer, Peter A. Larson, Mark Pacholzuk, Gayanne Coral Rickard, John A. Rierson, Carter J. Roth, Heather Schmitt, Dennis L. Schultz, Terry Talley, Joshua Taluba, Jon Utiskul, Yunyong Pock

Page 291 of 373

285 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6585-NFPA 101-2019 [ Section No. 32.3.1.3 ]

Page 292 of 373

286 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

32.3.1.3 Minimum Construction Requirements.

Page 293 of 373

287 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Large board and care facilities shall be limited to the building construction types specified in Table 32.3.1.3 (see 8.2.1), based on the number of stories in height as defined in 4.6.3. Table 32.3.1.3 Construction Type Limitations

Stories in Heightb

Construction Type Sprinklereda 1 2 3 4–12 >12

I(442)c, d Yes XXXXX No NP NP NP NP NP I(332)c, d Yes XXXXX No NP NP NP NP NP II(222)c, d Yes X X X X NP No NP NP NP NP NP II(111)c, d Yes X X X NP NP No NP NP NP NP NP II(000) Yes X X NP NP NP No NP NP NP NP NP III(211) Yes X X NP NP NP No NP NP NP NP NP III(200) Yes X NP NP NP NP No NP NP NP NP NP IV(2HH) Yes X X NP NP NP No NP NP NP NP NP

V(111) Yes XX NPe,f NPe NP No NP NP NP NP NP V(000) Yes X NP NP NP NP No NP NP NP NP NP

X: Permitted. NP: Not permitted.

aBuilding protected throughout by an approved automatic sprinkler system installed in accordance with 9.7.1.1(1), and provided with quick-response or residential sprinklers throughout. (See 32.3.3.5.)

bSee 4.6.3.

cAny building of Type I, Type II(222), or Type II(111) construction is permitted to include roofing systems involving combustible supports, decking, or roofing, provided that all of the following criteria are met: (1) The roof covering meets Class A requirements in accordance with ASTM E108, Standard Test Methods for Fire Tests of Roof Coverings, or UL 790, Test Methods for Fire Tests of Roof Coverings. (2) The roof is separated from all occupied portions of the building by a noncombustible floor assembly 1 having not less than a 2-hour fire resistance rating that includes not less than 2 ⁄2 in. (63 mm) of concrete or gypsum fill. (3) The structural elements supporting the 2-hour fire-resistance-rated floor assembly specified in item (2) are required to have only the fire resistance rating required of the building.

dAny building of Type I, Type II(222), or Type II(111) construction is permitted to include roofing systems involving combustible supports, decking, or roofing, provided that all of the following criteria are met: (1) The roof covering meets Class A requirements in accordance with ASTM E108, Standard Test Methods for Fire Tests of Roof Coverings, or UL 790, Test Methods for Fire Tests of Roof Coverings. (2) The roof/ceiling assembly is constructed with fire-retardant-treated wood meeting the requirements of NFPA 220. (3) The roof/ceiling assembly has the required fire resistance rating for the type of construction.

e Buildings complying with 4.5.6.1.1 of NFPA 220 are permitted to be up to and including 8 stories in height. Page 294 of 373

288 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

f Buildings complying with 4.5.6.1.2 of NFPA 220 are permitted to be up to and including 4 stories in height.

Submitter Information Verification

Committee: SAF-BCF Submittal Date: Tue Jul 09 10:32:15 EDT 2019

Committee Statement

Committee This change was made to permit the use of Type IV mass timber construction up to and including 8 Statement: stories and 4 stories to correlate with NFPA 5000. The technical committee provided reference to NFPA 220 for the construction to correlate with the remainder of the table, and NFPA 220 is a more appropriate reference than 5000. Response SR-6585-NFPA 101-2019 Message: Public Comment No. 160-NFPA 101-2019 [Section No. 32.3.1.3]

Ballot Results

This item has passed ballot

24 Eligible Voters 2 Not Returned 21 Affirmative All 0 Affirmative with Comments 1 Negative with Comments 0 Abstention

Not Returned Allen, Scott D. Jones, Adam C.

Affirmative All Asp, Roland A. Beebe, Chad E. Bell, Kerry M. Bellamy, Tracey D. Bradley, Harry L. Day, Richard L. Eaddy, Rebekah L. Farraher, Martin J. Gabriele, Nicholas E. Grant, Kurtis Heaney, Steven Larrimer, Peter A. Larson, Mark Pacholzuk, Gayanne Coral Rickard, John A. Page 295 of 373

289 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Rierson, Carter J. Roth, Heather Schmitt, Dennis L. Schultz, Terry Talley, Joshua Utiskul, Yunyong Pock

Negative with Comment Taluba, Jon This would allow a building type that has was previously not allowed. In addition with the amount of levels that would be permitted, is a cause for concern. In addition the formatting of the "e" and "f" and the title columns being "stories" of "3" and "4-12" do not match the wording in the e and f section. Also is in conflict with building construction table in section 33.

Page 296 of 373

290 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6627-NFPA 101-2019 [ Sections 32.3.3.7.9, 32.3.3.7.10, 32.3.3.7.11 ]

32.3.3.7.9 Smoke barriers shall be constructed in accordance with Section 8.5 and shall have a minimum 1-hour fire resistance rating, unless they meet the requirement of 32.3.3.7.10 or 32.3.3.7.11 . otherwise permitted by one of the following: (1) This requirement shall not apply where an atrium is used and both of the following criteria apply: (a) Smoke barriers shall be permitted to terminate at an atrium wall constructed in accordance with 8.6.7(1)(c), . (b) Not less than two separate smoke compartments shall be provided on each floor. (2)* Smoke dampers shall not be required in duct penetrations of smoke barriers in fully ducted heating, ventilating, and air-conditioning systems.

A.32.3.3.7.9(2)

Where the smoke control system design requires dampers in order that the system functions effectively, it is not the intent of 32.3.3.7.11 32.3.3.7.9 (2) to permit the damper to be omitted. The term fully ducted means the supply and return-air systems are provided with continuous ducts from all air registers to the air-handling unit.

(3) The provisions of 8.5.6.5 and 8.5.7.2 shall not apply. 32.3.3.7.10 Where an atrium is used, smoke barriers shall be permitted to terminate at an atrium wall constructed in accordance with 8.6.7 (1)(c), in which case not less than two separate smoke compartments shall be provided on each floor. 32.3.3.7.11 Dampers shall not be required in duct penetrations of smoke barriers in fully ducted heating, ventilating, and air-conditioning systems.

Submitter Information Verification

Committee: SAF-BCF Submittal Date: Fri Jul 12 14:24:05 EDT 2019

Committee Statement

Committee Section 32.3.3.7.9 through 32.3.3.7.11 were consolidated for clarity and consistency with other Statement: chapters. Technical changes in this SR are limited to 32.3.3.7.9(3). There is no documented evidence that smoke leakage has been an issue in board and care facilities. The detailed requirement in Chapter 8 for leakage rates are not necessary in fully sprinkler protected buildings. This creates an unnecessary burden when other items in the barriers do not have leakage ratings. This exemption already exists in healthcare and ambulatory healthcare occupancies for new construction. Response SR-6627-NFPA 101-2019 Message: Public Comment No. 134-NFPA 101-2019 [New Section after 32.3.3.7.9]

Ballot Results

This item has passed ballot

Page 297 of 373

291 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

24 Eligible Voters 2 Not Returned 21 Affirmative All 0 Affirmative with Comments 1 Negative with Comments 0 Abstention

Not Returned Allen, Scott D. Jones, Adam C.

Affirmative All Asp, Roland A. Beebe, Chad E. Bell, Kerry M. Bellamy, Tracey D. Bradley, Harry L. Day, Richard L. Eaddy, Rebekah L. Gabriele, Nicholas E. Grant, Kurtis Heaney, Steven Larrimer, Peter A. Larson, Mark Pacholzuk, Gayanne Coral Rickard, John A. Rierson, Carter J. Roth, Heather Schmitt, Dennis L. Schultz, Terry Talley, Joshua Taluba, Jon Utiskul, Yunyong Pock

Negative with Comment Farraher, Martin J. NEMA does not support the permission to omit the damper to be placed in the annex. The enforceable language no longer permits omitting the damper because the permission has been moved to an unenforceable annex. A definition for “fully ducted” has been created and placed in the annex. The enforceable language needs to include the description of the fully ducted system instead of placing an explanation in the annex.

Page 298 of 373

292 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6586-NFPA 101-2019 [ Section No. 33.3.3.2.4 ]

33.3.3.2.4 Medical Gas. Areas where medical gas is stored or administered and the The operation, testing, and maintenance of medical gases shall be in accordance with NFPA 99.

Submitter Information Verification

Committee: SAF-BCF Submittal Date: Tue Jul 09 12:40:14 EDT 2019

Committee Statement

Committee The infrastructure provisions of NFPA 99 for storage of medical gases should not apply to Statement: existing facilities. Response Message: SR-6586-NFPA 101-2019 Public Comment No. 67-NFPA 101-2019 [Section No. 33.3.3.2.4]

Ballot Results

This item has passed ballot

24 Eligible Voters 2 Not Returned 22 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Allen, Scott D. Jones, Adam C.

Affirmative All Asp, Roland A. Beebe, Chad E. Bell, Kerry M. Bellamy, Tracey D. Bradley, Harry L. Day, Richard L. Eaddy, Rebekah L. Farraher, Martin J. Gabriele, Nicholas E. Grant, Kurtis Heaney, Steven

Page 299 of 373

293 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Larrimer, Peter A. Larson, Mark Pacholzuk, Gayanne Coral Rickard, John A. Rierson, Carter J. Roth, Heather Schmitt, Dennis L. Schultz, Terry Talley, Joshua Taluba, Jon Utiskul, Yunyong Pock

Page 300 of 373

294 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6619-NFPA 101-2019 [ Section No. 36.2.2.7.2 ]

36.2.2.7.2* Exit passageways in a mall structure shall be permitted to accommodate the following occupant loads independently: (1) Portion of the occupant load assigned to the exit passageway from only the mall/pedestrian way concourse (2) Largest occupant load assigned to the exit passageway from a single tenant space

Submitter Information Verification

Committee: SAF-MER Submittal Date: Thu Jul 11 16:22:01 EDT 2019

Committee Statement

Committee This revision is a follow up to the significant work done in 2018 edition updating the Statement: terminology for the provisions for mall structures. Response SR-6619-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

28 Eligible Voters 2 Not Returned 25 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Campbell, Kina Rice, Sarah A.

Affirmative All Alsulaiti, Mohammed Bellamy, Tracey D. Bush, Kenneth E. Coats, Paul D. Cole, Anthony W. Dawe, Nicholas A. Derr, Kevin L. Dodge, David A. Donovan, Scott Page 301 of 373

295 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Frable, David W. Freels, Douglas R. Garriss, Marvin Dwayne Garzone, Joseph R. Gauvin, Daniel J. Gumkowski, Anthony C. Humble, Jonathan Kauffman, Conor J. Martin, Jeff Mourao, Bridget Murdock, Amy J. Shirey, Jeffrey Stocker, Warren G. Tabar, David C. Wensus, Timothy Yonkers, Ernest D.

Affirmative with Comment Ford, Daniel Agree - this is consistent with the chapter terminology.

Page 302 of 373

296 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6648-NFPA 101-2019 [ Sections 36.3.5.1, 36.3.5.2 ]

36.3.5.1 Mercantile occupancies shall be protected by an approved, supervised automatic sprinkler system in accordance with 9.7.1.1(1) in any of the following specified locations: (1) Throughout all mercantile occupancies three or more stories in height

(2) Throughout all mercantile occupancies exceeding 12,000 ft2 (1115 m2) in gross area (3) Throughout stories below the level of exit discharge where such stories have an area exceeding 2500 ft2 (232 m2) and are used for the sale, storage, or handling of combustible goods and merchandise (4) Throughout multiple occupancies protected as mixed occupancies in accordance with 6.1.14 where the conditions of 36.3.5.1(1), 36.3.5.1(2), or 36.3.5.1(3) apply to the mercantile occupancy 36.3.5.2 Automatic sprinkler systems in Class A mercantile occupancies shall be supervised in accordance with 9.7.2 .

Submitter Information Verification

Committee: SAF-MER Submittal Date: Tue Jul 16 11:39:35 EDT 2019

Committee Statement

Committee New mercantile occupancies in NFPA 5000 are required to be supervised. This change Statement: correlates to NFPA 5000. Section 9.7.2.2 requires all supervised systems to be electrically supervised.

Section 36.3.5.1 requires all sprinkler systems to be supervised. Per section 9.7.2.2 all supervised systems are required to be electrically supervised. Therefore Section 36.3.5.2 is no longer necessary.

Response SR-6648-NFPA 101-2019 Message: Public Comment No. 178-NFPA 101-2019 [Section No. 36.3.5.1]

Ballot Results

This item has passed ballot

28 Eligible Voters 2 Not Returned 26 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Campbell, Kina Rice, Sarah A.

Page 303 of 373

297 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Affirmative All Alsulaiti, Mohammed Bellamy, Tracey D. Bush, Kenneth E. Coats, Paul D. Cole, Anthony W. Dawe, Nicholas A. Derr, Kevin L. Dodge, David A. Donovan, Scott Ford, Daniel Frable, David W. Freels, Douglas R. Garriss, Marvin Dwayne Garzone, Joseph R. Gauvin, Daniel J. Gumkowski, Anthony C. Humble, Jonathan Kauffman, Conor J. Martin, Jeff Mourao, Bridget Murdock, Amy J. Shirey, Jeffrey Stocker, Warren G. Tabar, David C. Wensus, Timothy Yonkers, Ernest D.

Page 304 of 373

298 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6620-NFPA 101-2019 [ Section No. 37.2.2.7.2 ]

37.2.2.7.2* Exit passageways in a mall structure shall be permitted to accommodate the following occupant loads independently: (1) Portion of the occupant load assigned to the exit passageway from only the mall/pedestrian way concourse (2) Largest occupant load assigned to the exit passageway from a single tenant space

Submitter Information Verification

Committee: SAF-MER Submittal Date: Thu Jul 11 16:32:00 EDT 2019

Committee Statement

Committee This revision is a follow up to the significant work done in 2018 edition updating the Statement: terminology for the provisions for mall structures. Response SR-6620-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

28 Eligible Voters 2 Not Returned 25 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Campbell, Kina Rice, Sarah A.

Affirmative All Alsulaiti, Mohammed Bellamy, Tracey D. Bush, Kenneth E. Coats, Paul D. Cole, Anthony W. Dawe, Nicholas A. Derr, Kevin L. Dodge, David A. Donovan, Scott Page 305 of 373

299 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Frable, David W. Freels, Douglas R. Garriss, Marvin Dwayne Garzone, Joseph R. Gauvin, Daniel J. Gumkowski, Anthony C. Humble, Jonathan Kauffman, Conor J. Martin, Jeff Mourao, Bridget Murdock, Amy J. Shirey, Jeffrey Stocker, Warren G. Tabar, David C. Wensus, Timothy Yonkers, Ernest D.

Affirmative with Comment Ford, Daniel Agree - this is consistent with the chapter terminology.

Page 306 of 373

300 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6643-NFPA 101-2019 [ Section No. 37.4.4.2 ]

37.4.4.2 Special Definitions. The following is a list of special terms used in this chapter: (1) Anchor Building. A building housing any occupancy having low- or ordinary-hazard contents and having direct access to a mall structure, but having all required means of egress independent of the mall concourse. (See 3.3.37.2.) (2) Food Court. A public seating area located in a mall concourse that serves adjacent food preparation tenant spaces. (See 3.3.51.2.) (3) Gross Leasable Area. Fifty percent of major tenant areas, and 100 percent of all other floor areas designated for tenant occupancy and exclusive use, including storage areas. The area of tenant occupancy is measured from the centerlines of joint partitions to the outside of the tenant walls. (See 3.3.22.3.) (4) Mall Concourse. A common pedestrian area within a mall structure that serves as access for two or more tenants and does not exceed three levels that are open to each other. (See 3.3.177.)

(a)* Open Mall Concourse. A mall concourse that either (1) has 50 percent or more of the total area of the solid mall concourse perimeter walls and solid roof area open to the atmosphere with openings distributed uniformly over the length of the mall concourse, or (2) has an approved open mall concourse engineering analysis. (b) Enclosed Mall Concourse. A mall concourse that does not meet the definition of open mall concourse.

(5)* Mall Structure. A single building enclosing a number of tenants and occupancies wherein two or more tenants have a main entrance into one or more mall concourses. For the purpose of this chapter, anchor buildings shall not be considered as a part of the mall structure. (See 3.3.284.4.)

A.37.4.4.2(5) Mall Structure.

A mall structure can include either an enclosed mall concourse or an open mall concourse. A mall structure might be enclosed by construction that could range from total enclosure to construction that is open, either partially or totally, to the outer air. For structures without complete walls and/or roof, the termination of the mall exit discharge would determine the extent of the structure. A mall structure might enclose one or more uses, such as retail and wholesale stores, drinking and dining establishments, entertainment and amusement facilities, transportation facilities, offices, and other similar uses.

(6) Major Tenant. A tenant space, in a mall structure, with one or more main entrances from the exterior that also serve as exits and are independent of the mall concourse. (See 3.3.176.)

A.37.4.4.2(6)

A mall structure can include either an enclosed mall concourse or an open mall concourse. A mall structure might be enclosed by construction that could range from total enclosure to construction that is open, either partially or totally, to the outer air. For structures without complete walls and/or roof, the termination of the mall exit discharge would determine the extent of the structure.

Submitter Information Verification

Committee: SAF-MER Submittal Date: Tue Jul 16 10:37:57 EDT 2019

Page 307 of 373

301 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Committee Statement

Committee This revision is a follow up to the significant work done in 2018 edition updating the Statement: terminology for the provisions for mall structures. Response SR-6643-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

28 Eligible Voters 2 Not Returned 26 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Campbell, Kina Rice, Sarah A.

Affirmative All Alsulaiti, Mohammed Bellamy, Tracey D. Bush, Kenneth E. Coats, Paul D. Cole, Anthony W. Dawe, Nicholas A. Derr, Kevin L. Dodge, David A. Donovan, Scott Ford, Daniel Frable, David W. Freels, Douglas R. Garriss, Marvin Dwayne Garzone, Joseph R. Gauvin, Daniel J. Gumkowski, Anthony C. Humble, Jonathan Kauffman, Conor J. Martin, Jeff Mourao, Bridget Murdock, Amy J. Shirey, Jeffrey Stocker, Warren G. Tabar, David C.

Page 308 of 373

302 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Wensus, Timothy Yonkers, Ernest D.

Page 309 of 373

303 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6646-NFPA 101-2019 [ Section No. 37.4.4.6.2 [Excluding any Sub-

Sections] ]

Every story of a covered mall structure shall be provided with the number of means of egress specified by Section 7.4 and as modified by 37.4.4.6.2.1 or 37.4.4.6.2.2.

Submitter Information Verification

Committee: SAF-MER Submittal Date: Tue Jul 16 10:44:08 EDT 2019

Committee Statement

Committee This revision is a follow up to the significant work done in 2018 edition updating the Statement: terminology for the provisions for mall structures. Response SR-6646-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

28 Eligible Voters 2 Not Returned 26 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Campbell, Kina Rice, Sarah A.

Affirmative All Alsulaiti, Mohammed Bellamy, Tracey D. Bush, Kenneth E. Coats, Paul D. Cole, Anthony W. Dawe, Nicholas A. Derr, Kevin L. Dodge, David A. Donovan, Scott Ford, Daniel Frable, David W. Freels, Douglas R. Page 310 of 373

304 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Garriss, Marvin Dwayne Garzone, Joseph R. Gauvin, Daniel J. Gumkowski, Anthony C. Humble, Jonathan Kauffman, Conor J. Martin, Jeff Mourao, Bridget Murdock, Amy J. Shirey, Jeffrey Stocker, Warren G. Tabar, David C. Wensus, Timothy Yonkers, Ernest D.

Page 311 of 373

305 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6621-NFPA 101-2019 [ Section No. 37.4.4.12 ]

37.4.4.12* Automatic Extinguishing Systems. 37.4.4.12.1 Mall structures shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with 37.3.5.1 . 37.4.4.12.2 Kiosks or similar structures located within the enclosed mall concourse shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.

Submitter Information Verification

Committee: SAF-MER Submittal Date: Thu Jul 11 16:33:09 EDT 2019

Committee Statement

Committee The existing language only requires kiosks or similar structures located within an enclosed mall Statement: concourse require sprinkler protection. The entire mall structure should be sprinklered and not just the kiosks or similar structures. Response SR-6621-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

28 Eligible Voters 2 Not Returned 25 Affirmative All 0 Affirmative with Comments 1 Negative with Comments 0 Abstention

Not Returned Campbell, Kina Rice, Sarah A.

Affirmative All Alsulaiti, Mohammed Bellamy, Tracey D. Bush, Kenneth E. Coats, Paul D. Cole, Anthony W. Dawe, Nicholas A. Derr, Kevin L.

Page 312 of 373

306 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Dodge, David A. Donovan, Scott Frable, David W. Freels, Douglas R. Garriss, Marvin Dwayne Garzone, Joseph R. Gauvin, Daniel J. Gumkowski, Anthony C. Humble, Jonathan Kauffman, Conor J. Martin, Jeff Mourao, Bridget Murdock, Amy J. Shirey, Jeffrey Stocker, Warren G. Tabar, David C. Wensus, Timothy Yonkers, Ernest D.

Negative with Comment Ford, Daniel NFPA 101 37.3.5 already address this. 37.4.4.12 serves to confirm that sprinklers are required fr kiosks within existing malls.

Page 313 of 373

307 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6641-NFPA 101-2019 [ Section No. 39.4.2 ]

39.4.2 High-Rise Buildings. 39.4.2.1 All high-rise business occupancy buildings shall be provided with a reasonable degree of safety from fire, and such degree of safety shall be accomplished by one of the following means: an approved, supervised automatic sprinkler system in accordance with 9.7.1.1 (1) unless the building is provided with an approved engineered life safety system developed by a registered professional engineer experienced in fire and life safety systems. Installation of a complete, approved, supervised automatic sprinkler system in accordance with 9.7.1.1(1) Installation of an engineered life safety system complying with all of the following: The engineered life safety system shall be developed by a registered professional engineer experienced in fire and life safety systems design. The life safety system shall be approved by the authority having jurisdiction and shall be permitted to include any or all of the following systems: Partial automatic sprinkler protection Smoke detection alarms Smoke control Elevators Compartmentation Other approved systems

39.4.2.2* A limited, but reasonable, time shall be permitted for compliance with any part of 39.4.2.1 , commensurate with the magnitude of expenditure and the disruption of services.

A.39.4.2.2

In some cases, appreciable cost might be involved in bringing an existing occupancy into compliance. Where this is true, it would be appropriate for the authority having jurisdiction to prescribe a schedule determined jointly with the facility, allowing suitable periods of time for the correction of the various deficiencies and giving due weight to the ability of the owner to secure the necessary funds.

39.4.2.3 In addition to the requirements of 39.4.2.1 and 39.4.2.2 , all buildings, regardless of height, shall comply with all other applicable provisions of this chapter. 39.4.2.2* Previously approved engineered life safety systems shall be maintained in accordance with the approved design documents and applicable standards.

Page 314 of 373

308 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

A.39.4.2.2

The intent of this requirement is to provide a reasonable degree of safety from fire for all occupants of high-rise business occupancy buildings. This reasonable degree of safety can be accomplished by the installation of an automatic sprinkler system or application of an engineered life safety system. The engineered life safety system is similar to alternative protection concepts contained in most building and fire codes. Alternative systems, methods, or devices achieving a reasonable level of protection and meeting the intent of the specific code requirement can be used if the level of life safety provided by that engineered life safety system is proven to the satisfaction of the authority having jurisdiction. The engineered life safety system should be documented and include a narrative discussion of the features of the building structure, function, operational support systems, and occupant activities that impact fire protection and life safety. The submission to the authority having jurisdiction for approval should describe potential reasonable worst-case fire scenarios and their impact on building occupants and the facility's structures. Specific issues that should be addressed include rate of fire growth, type and location of fuel items, space layout, building construction, openings and ventilation, suppression capability, detection time, occupant notification, occupant reaction time, occupant mobility, and means of egress. Elements of the engineered life safety system might include but are not limited to the following: (1) Partial automatic sprinkler protection (2) Smoke detection alarms (3) Elevators (4) Smoke control (5) Compartmentation Analytical and empirical tools, including fire models and performance-based design methods, such as those outlined in the SFPE Engineering Guide to Performance-Based Fire Protection and Chapter 5 of this Code can be used to support the engineered life safety system. If fire modeling is used as part of an analysis, an assessment of the predictive capabilities of the fire models should be included.

Submitter Information Verification

Committee: SAF-MER Submittal Date: Tue Jul 16 08:25:53 EDT 2019

Committee Statement

Committee The engineered life safety system is a viable solution that meets the goals stated in 4.1 of NFPA Statement: 101. Previously the requirements for an ELSS were vague. The committee provided additional explanatory material to clarify the elements of an acceptable ELSS and qualifications for who can perform this type of analysis.

Existing section 39.4.2.2 was deleted and a general pointer to 4.6.6 was added to the annex. The language in 39.4.2.2 was simply stating the same thing already allowed by 4.6.6.

The concept of a comprehensive life safety system for high-rise buildings goes back to the 1973 edition. Specifically, the LSC has permitted the use of the alternative protection in existing high-rise business buildings since the 1981 edition and in existing high-rise residential buildings since the 1997 edition. These provisions have been used by many architects, engineers and authorities having jurisdiction as a means to provide a reasonable level of protection without the costs and related hardships associated with sprinkler installations in existing buildings. The ELSS works for many properties and communities where an alternative was sought by the local stakeholders.

Existing section 39.4.2.3 was deleted because it is redundant and unnecessary, the rest of the Code always applies.

Response SR-6641-NFPA 101-2019 Message: Page 315 of 373

309 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Public Comment No. 157-NFPA 101-2019 [Section No. A.39.4.2.2] Public Comment No. 208-NFPA 101-2019 [Section No. 39.4.2.1] Public Comment No. 237-NFPA 101-2019 [Section No. 39.4.2.1] Public Comment No. 212-NFPA 101-2019 [Global Input] Public Comment No. 153-NFPA 101-2019 [Section No. 39.4.2] Public Comment No. 197-NFPA 101-2019 [Section No. 39.4.2] Public Comment No. 168-NFPA 101-2019 [Section No. 39.4.2.1]

Ballot Results

This item has passed ballot

28 Eligible Voters 2 Not Returned 24 Affirmative All 0 Affirmative with Comments 2 Negative with Comments 0 Abstention

Not Returned Campbell, Kina Rice, Sarah A.

Affirmative All Alsulaiti, Mohammed Bellamy, Tracey D. Bush, Kenneth E. Coats, Paul D. Cole, Anthony W. Dawe, Nicholas A. Derr, Kevin L. Dodge, David A. Donovan, Scott Frable, David W. Freels, Douglas R. Garriss, Marvin Dwayne Garzone, Joseph R. Gumkowski, Anthony C. Humble, Jonathan Kauffman, Conor J. Martin, Jeff Mourao, Bridget Murdock, Amy J. Shirey, Jeffrey Stocker, Warren G. Tabar, David C. Page 316 of 373

310 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Wensus, Timothy Yonkers, Ernest D.

Negative with Comment Ford, Daniel The proposed change could reduce the level of analysis which is undertaken by the registered professional engineer. The requirements of 39.4.2.1 reinforce the requirements of the code based upon the occupancy. Gauvin, Daniel J. This revision moves required elements of an engineered life safety system to the annex where they are unenforceable without sufficient justification.

Page 317 of 373

311 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6596-NFPA 101-2019 [ Section No. 40.1.2.1.3 ]

40.1.2.1.3* High-Hazard Industrial Occupancy. High-hazard industrial occupancies shall include all of the following: (1) Existing industrial occupancies that conduct industrial operations that use, process, store, or handle high-hazard contents, as defined by 6.2.2.4 (2) New industrial occupancies that conduct industrial operations that use, process, store, or handle high- hazard contentsor hazardous materials , as defined by 6.2.2.4 , in excess of the maximum allowable quantities (MAQ) as permitted by the fire code (3) Industrial occupancies in which incidental high-hazard operations in low- or ordinary-hazard occupancies that are protected in accordance with Section 8.7 and 40.3.2 are not required to be the basis for overall occupancy classification

Submitter Information Verification

Committee: SAF-IND Submittal Date: Wed Jul 10 10:57:09 EDT 2019

Committee Statement

Committee Deleting the phrase 'hazardous materials' limits the concept of high-hazard industrial occupancies to Statement: those materials with a fire related hazard. This revision clarifies that this section is only addressing fire hazard of the materials and deferring to NFPA 400 for other chemical hazards

There are redundant and contradictory requirements created when classifying NFPA 101 occupancy type based off of the MAQ of the fire code. NFPA 400 is already required for industrial occupancies per Sections 40.2.11.3 and 40.3.2.6. It is more effective for NFPA 101 to allow for NFPA 400 to dictate the requirements for exceeding the MAQ. It does not make sense to require all of the requirements of a NFPA 101 High Hazard Industrial Occupancy for a building that exceeds the MAQ for corrosives. NFPA 400 has more pertinent requirements for buildings that exceed the corrosive MAQ as the NFPA 400 requirements are broken down by the different hazardous material classifications. NFPA 101 has a one size fits all high hazard industrial occupancy classification that was originally intended for high fire hazards only. Response SR-6596-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

30 Eligible Voters 6 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Almannai, Ali Birchler, Donald C. Culp, Christopher Page 318 of 373

312 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Johnson, Aaron Jones, Adam C. Richardson, Dennis A.

Affirmative All Cummings, Ryan Cusimano, Alberto Dacus, Sheldon Dale, Stephen E. Dawe, Nicholas A. Desrosier, John Dudley, Jeffry T. Early, Rob Hanson, Robert E. Humble, Jonathan Klein, Andrew S. Krantz, Sr., Neal W. Laberge, Todd Lozano-Rosales, Roberto McLaughlin, Patrick A. Olsen, Brian L. Pierrottie, Jerald Pruett, Scot Sheldon, Steven A. Skinker, Cleveland B. Swiecicki, Bruce J. Tabar, David C. White, Michael S. Wren, Carl D.

Page 319 of 373

313 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6604-NFPA 101-2019 [ Section No. 40.2.6.1 ]

40.2.6.1 Travel distance, measured in accordance with Section 7.6, shall not exceed that provided by Table 40.2.6.1 except as otherwise permitted by 40.2.6.2 or the fire code. Table 40.2.6.1 Maximum Travel Distance to Exits Special- General Purpose High-Hazard Industrial Industrial Industrial Occupancy Occupancy Occupancy* Level of Protection ft m ft m ft m Protected throughout by an approved, supervised 250* † 76* † 400 122 75 23 automatic sprinkler system in accordance with 9.7.1.1(1) Not protected throughout by an approved, supervised 200 61 300 91 NP NP automatic sprinkler system in accordance with 9.7.1.1(1)

NP: Not permitted. *In high-hazard industrial occupancies, where required to comply with NFPA 400 Protection Level 1 through Protection Level 4, travel distance is permitted to be in accordance with NFPA 400. * † In one-story buildings, a travel distance of 400 ft (122 m) is permitted, provided that a performance- based analysis demonstrates that safe egress can be accomplished.

Submitter Information Verification

Committee: SAF-IND Submittal Date: Wed Jul 10 13:36:41 EDT 2019

Committee Statement

Committee Statement: Last paragraph of CI 6721 Response Message: SR-6604-NFPA 101-2019

Ballot Results

This item has passed ballot

30 Eligible Voters 6 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Almannai, Ali Birchler, Donald C. Culp, Christopher Johnson, Aaron Page 320 of 373

314 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Jones, Adam C. Richardson, Dennis A.

Affirmative All Cummings, Ryan Cusimano, Alberto Dacus, Sheldon Dale, Stephen E. Dawe, Nicholas A. Desrosier, John Dudley, Jeffry T. Early, Rob Hanson, Robert E. Humble, Jonathan Klein, Andrew S. Krantz, Sr., Neal W. Laberge, Todd Lozano-Rosales, Roberto McLaughlin, Patrick A. Olsen, Brian L. Pierrottie, Jerald Pruett, Scot Sheldon, Steven A. Skinker, Cleveland B. Swiecicki, Bruce J. Tabar, David C. White, Michael S. Wren, Carl D.

Page 321 of 373

315 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6597-NFPA 101-2019 [ New Section after 40.3.2.6 ]

40.3.2.7 Energy storage systems shall be protected in accordance with NFPA 855 .

Submitter Information Verification

Committee: SAF-IND Submittal Date: Wed Jul 10 11:07:26 EDT 2019

Committee Statement

Committee Energy storage systems present a unique hazard and should be protected in accordance with Statement: the applicable standard (NFPA 855). Response SR-6597-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

30 Eligible Voters 6 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Almannai, Ali Birchler, Donald C. Culp, Christopher Johnson, Aaron Jones, Adam C. Richardson, Dennis A.

Affirmative All Cummings, Ryan Cusimano, Alberto Dacus, Sheldon Dale, Stephen E. Dawe, Nicholas A. Desrosier, John Dudley, Jeffry T. Early, Rob

Page 322 of 373

316 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Hanson, Robert E. Humble, Jonathan Klein, Andrew S. Krantz, Sr., Neal W. Laberge, Todd Lozano-Rosales, Roberto McLaughlin, Patrick A. Olsen, Brian L. Pierrottie, Jerald Pruett, Scot Sheldon, Steven A. Skinker, Cleveland B. Swiecicki, Bruce J. Tabar, David C. White, Michael S. Wren, Carl D.

Page 323 of 373

317 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6595-NFPA 101-2019 [ New Section after 40.4.2.1 ]

40.4.2.2 All existing high-rise industrial occupancy buildings shall be provided with a reasonable degree of safety from fire, and such degree of safety shall be accomplished by one of the following means: (1) Installation of a complete, approved, supervised automatic sprinkler system in accordance with 9.7.1.1(1) (2)* Installation of an engineered life safety system complying with all of the following: (a) The engineered life safety system shall be developed by a registered professional engineer experienced in fire and life safety systems design. (b) The life safety system shall be approved by the authority having jurisdiction and shall be permitted to include any or all of the following systems: i. Partial automatic sprinkler protection ii. Smoke detection alarms iii. Smoke control iv. Elevators v. Compartmentation vi. Other approved systems

A.40.4.2.2(2)

It is recognized that industrial occupancy buildings impose a wide range of risks and hazards. The purpose of the engineered life safety system is to allow the building owner and the authority having jurisdiction the leeway to develop a protection method appropriate to the risk.

40.4.2.3 All high-rise buildings shall comply with 40.4.2.2 within 12 years of the adoption of this Code .

Submitter Information Verification

Committee: SAF-IND Submittal Date: Wed Jul 10 10:35:05 EDT 2019

Committee Statement

Committee There have been a number of high-rise building fires in industrial occupancies which show the need Statement: for sprinklers. Examples go as far back as the Triangle Shirtwaist Factory Fire. More recent examples include:

• The 2010 fire in a clothing factory in Bangladesh, 27 people died and 100 were injured

• The 2012 Tazreen Fire in Bangladesh, 112 people died

• The 2017 fire in a garment factory in Bangladesh, 13 people died and 50 injured

• The 2017 Plasco Fire in a high-rise building housing a shopping center and clothing workshop in Tehran, 20 people died and 200 were injured

The Life Safety Code is applied internationally. There are many examples of high-rise industrial Page 324 of 373

318 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

facilities around the world and, in the future, could be found more frequently in the United States. New industrial occupancies are required to be sprinklered and occupants of existing industrial occupancies should be provided with the same level of life safety. The committee acknowledges that retrofitting an industrial occupancy may be challenging and therefore, has provided the engineered life safety system as an alternative approach to life safety. The language for the engineered life safety system is the same language that has appeared in the Code for other occupancies for several cycles of the code and has not presented an enforceability issue. A 12 year requirement for compliance was included to align with retrofit requirements found in other occupancies.

Response SR-6595-NFPA 101-2019 Message: Public Comment No. 198-NFPA 101-2019 [New Section after 40.4.2.1]

Ballot Results

This item has passed ballot

30 Eligible Voters 6 Not Returned 23 Affirmative All 0 Affirmative with Comments 1 Negative with Comments 0 Abstention

Not Returned Almannai, Ali Birchler, Donald C. Culp, Christopher Johnson, Aaron Jones, Adam C. Richardson, Dennis A.

Affirmative All Cummings, Ryan Cusimano, Alberto Dacus, Sheldon Dale, Stephen E. Dawe, Nicholas A. Desrosier, John Dudley, Jeffry T. Early, Rob Hanson, Robert E. Humble, Jonathan Klein, Andrew S. Krantz, Sr., Neal W. Laberge, Todd Lozano-Rosales, Roberto McLaughlin, Patrick A. Pierrottie, Jerald Page 325 of 373

319 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Pruett, Scot Sheldon, Steven A. Skinker, Cleveland B. Swiecicki, Bruce J. Tabar, David C. White, Michael S. Wren, Carl D.

Negative with Comment Olsen, Brian L. It is understood that a multitude of failures were involved in the tragic fires utilized as justification for this code change. Included are interior finish, overcrowding, means of egress, fire separation, and enforcement related concerns. It is unclear that introduction of sprinklers alone in these situations would result in significantly improved outcomes without additional measures being undertaken.

Page 326 of 373

320 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6598-NFPA 101-2019 [ Section No. 42.1.5.2 ]

42.1.5.2 In new New storage occupancies, hazardous materials that where high-hazard contents as defined in 6.2.2.4 exceed the maximum allowable quantities (MAQ) as permitted in the fire code, shall be classified as high-hazard contents storage occupancies .

Submitter Information Verification

Committee: SAF-IND Submittal Date: Wed Jul 10 11:17:07 EDT 2019

Committee Statement

Committee Deleting the phrase 'hazardous materials' limits the concept of high-hazard industrial occupancies Statement: to those materials with a fire related hazard. This revision clarifies that this section is only addressing fire hazard of the materials and deferring to NFPA 400 for other chemical hazards.

Response SR-6598-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

30 Eligible Voters 6 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Almannai, Ali Birchler, Donald C. Culp, Christopher Johnson, Aaron Jones, Adam C. Richardson, Dennis A.

Affirmative All Cummings, Ryan Cusimano, Alberto Dacus, Sheldon Dale, Stephen E. Dawe, Nicholas A. Desrosier, John Page 327 of 373

321 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Dudley, Jeffry T. Early, Rob Hanson, Robert E. Humble, Jonathan Klein, Andrew S. Krantz, Sr., Neal W. Laberge, Todd Lozano-Rosales, Roberto McLaughlin, Patrick A. Olsen, Brian L. Pierrottie, Jerald Pruett, Scot Sheldon, Steven A. Skinker, Cleveland B. Swiecicki, Bruce J. Tabar, David C. White, Michael S. Wren, Carl D.

Page 328 of 373

322 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6599-NFPA 101-2019 [ Section No. 42.3.2 ]

42.3.2 Protection from Hazards. 42.3.2.1 Where hazardous materials are stored, used, or handled, the provisions of 8.7.3.1 shall apply. 42.3.2.2 Energy storage systems shall be protected in accordance with NFPA 855 .

Submitter Information Verification

Committee: SAF-IND Submittal Date: Wed Jul 10 11:45:38 EDT 2019

Committee Statement

Committee Energy storage systems present a unique hazard and should be protected in accordance with Statement: the applicable standard (NFPA 855). Response SR-6599-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

30 Eligible Voters 6 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Almannai, Ali Birchler, Donald C. Culp, Christopher Johnson, Aaron Jones, Adam C. Richardson, Dennis A.

Affirmative All Cummings, Ryan Cusimano, Alberto Dacus, Sheldon Dale, Stephen E. Dawe, Nicholas A.

Page 329 of 373

323 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Desrosier, John Dudley, Jeffry T. Early, Rob Hanson, Robert E. Humble, Jonathan Klein, Andrew S. Krantz, Sr., Neal W. Laberge, Todd Lozano-Rosales, Roberto McLaughlin, Patrick A. Olsen, Brian L. Pierrottie, Jerald Pruett, Scot Sheldon, Steven A. Skinker, Cleveland B. Swiecicki, Bruce J. Tabar, David C. White, Michael S. Wren, Carl D.

Page 330 of 373

324 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6625-NFPA 101-2019 [ Section No. A.3.3.37.9 ]

A.3.3.37.9 Special Amusement Building. Special amusement buildings include amusements typically found in theme parks such as a roller coaster–type ride within a building, a multilevel play structure within a building, a submarine ride, and similar amusements where the occupants are not in the open air and might or might not be confined to a ride vehicle and/or unable to self-evacuate. Examples of temporary special amusement buildings include mobile fun houses typically found in carnivals or a gymnasium converted to a haunted house for Halloween. Three conditions are essential to the definition of a special amusement building: First, the area might be either an entire building or a portion of a building. A rollercoaster within a theme park would not be a special amusement building if it is open to the air along its entire length. On the other hand, if portions of the rollercoaster were partially enclosed within buildings that house the show elements, it would then be a special amusement building. Second, a special amusement building contains either an amusement ride or device, or a walkway over a course intended to provide amusement or entertainment. A theater with fixed seats and a performance platform or stage would typically not be a special amusement building because there is no amusement ride or device, and there is no walkway that is used to provide amusement or entertainment. Third, a special amusement building is intended to either divert the patron’s attention away from the egress path, either through audio or visual distractions or by intentionally confounding the patron, or it contains or restrains the patron such that the patron is unable to self-evacuate when the amusement ride has ceased motion. A carousel or small train inside a shopping mall might not be considered to be a special amusement building if, once ride motion has ceased, the patron can step out of the vehicle without assistance and is aware of the egress path. Other occupancies might also fall into the classification of special amusement building if the conditions described in the definition apply. Escape rooms are an example of where such conditions might exist. It is incumbent on the authority having jurisdiction to inquire if the conditions in the escape room meet the definition of a special amusement building. Where such conditions exist, escape rooms should be classified as special amusement buildings. Where such conditions do not exist, escape rooms might be classified as another occupancy type, such as business. It is important for the authority having jurisdiction to recognize that the Code requires an occupancy to be classified as a special amusement building if the conditions in the space meet the definition of special amusement building, regardless of the occupant load of the space. No minimum occupant load threshold must be met for a space to be classified as a special amusement building. A space could be classified as a special amusement building even where the occupant load is significantly fewer than the 50 occupants required for classification of other assembly occupancies. The requirements for special amusement buildings are not intended to apply to the design of the actual amusement ride or device, but rather that of the facility that houses the ride or device. The design of an amusement ride or device, including all platforms and stairs that are attached to the ride structure, is governed by other standards, such as ASTM F2291, Standard Practice for Design of Amusement Rides or Devices . The design of facilities elements around the ride, including stairs and platforms that are not part of the ride structure, should be in accordance with the applicable requirements of this Code .

Submitter Information Verification

Committee: SAF-AXM Submittal Date: Fri Jul 12 10:00:23 EDT 2019

Committee Statement

Committee The revision addresses the use of portions of a building not being used as a special amusement Statement: occupancy and clarifies how mixed occupancy is approached when special amusement buildings are involved. The revision also includes industry standard verbiage relating to ride systems and their patrons. The revision also adds a reference to ASTM F2291-2019 for guidance.

Page 331 of 373

325 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

See related revisions to 3.3.37.9 in SR-6624. Response SR-6625-NFPA 101-2019 Message: Public Comment No. 203-NFPA 101-2019 [Section No. A.3.3.37.9]

Ballot Results

This item has passed ballot

28 Eligible Voters 5 Not Returned 23 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Herrera, Mark A. Keberle, Kenneth F. Scandaliato, Steven J. Thomas, Jr., Elbert R. Tubbs, Jeffrey S.

Affirmative All Center, Eric Conner, William Cook, David Deacon, Nils Finnegan, Daniel P. Gandy, Max L. Goosman, Donald G. Hansen, Harold C. Hesson, Stephen C Hollinger, David W. Humble, Jonathan Lake, John Lambert, Josh Morin, Kevin D. Pauls, Jake Peterson, Ryan Quinterno, Vincent Roether, Ed Rogers, Adam Ruling, Karl G. Schweitzer, Charles J. Sherman, Philip R.

Page 332 of 373

326 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Shirey, Jeffrey

Page 333 of 373

327 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6536-NFPA 101-2019 [ Section No. A.10.2.3.1.2 ]

A.10.2.3.1.2 The converse is not true. Class A materials do not automatically meet the requirements of NFPA 286 Materials tested per NFPA 286 and meeting the criteria of 10.2.3.2 are considered Class A materials. However, not all materials that meet the requirements for Class A based on testing per ASTM E84 or UL 723 will meet the requirements of this Code for testing in accordance with NFPA 286 .

Submitter Information Verification

Committee: SAF-INT Submittal Date: Tue Jun 11 13:15:55 EDT 2019

Committee Statement

Committee Statement: The revision clarifies A.10.2.3.1.2 as requested by the correlating committee. Response Message: SR-6536-NFPA 101-2019 Public Comment No. 40-NFPA 101-2019 [Section No. A.10.2.3.1.2]

Ballot Results

This item has passed ballot

16 Eligible Voters 3 Not Returned 13 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Carrigan, Matthew Siegel, Shelley Sloan, Dwayne E.

Affirmative All Babrauskas, Vytenis Chen, Tiffney Arlene-Cates Cutrer, Peter S. Dawe, Nicholas A. Evans, Michael W. Fitch, William E. Hirschler, Marcelo M. Hunter, Matthew M Lathrop, James K. Newman, Kathleen A. Page 334 of 373

328 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Paszczuk, Henry Puchovsky, Milosh T. Richardson, James R.

Page 335 of 373

329 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6649-NFPA 101-2019 [ Section No. A.18.3.5.10 ]

A.18.3.5.10 This exception is limited to hospitals, as nursing homes and many limited care facilities might have more combustibles within the closets. The limited amount of clothing found in the small clothes closets in hospital patient rooms is typically far less than the amount of combustibles in casework cabinets that do not require sprinkler protection, such as nurse servers. In many hospitals, especially new hospitals, it is difficult to make a distinction between clothes closets and cabinet work. The exception is far more restrictive than similar exceptions for hotels and apartment buildings. NFPA 13 already permits the omission of sprinklers in wardrobes. [see 8.1.1(7) of NFPA 13 ]. It is not the intent of 18.3.5.10 to affect the wardrobe provisions of NFPA 13. It is the intent that the sprinkler protection in the room covers the closet as if there were no door on the closet. (See 8.5.3.2.3 of NFPA 13 .)

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Thu Jul 18 14:55:37 EDT 2019

Committee Statement

Committee The revision responds to correlating committee direction to update references to NFPA 13. The Statement: specific references are not needed and are subject to change. This revision eliminates the specific references to preclude the need to update them in the future. Response SR-6649-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke

Page 336 of 373

330 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 337 of 373

331 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6652-NFPA 101-2019 [ Section No. A.18.3.7 ]

A.18.3.7 See A.18.2.2. Where two floors communicate via two-story openings with partial enclosure in accordance with 8.6.8 or convenience openings in accordance with 8.6.9 , the total smoke compartment area is the combined areas of the compartments exposed to each other on both floors.

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Thu Jul 18 15:51:38 EDT 2019

Committee Statement

Committee Unprotected vertical openings provide no smoke protection; therefore, the combined floor areas Statement: exposed by the openings need to be considered as a single smoke compartment. (Related CI-6876) Response SR-6652-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 27 Affirmative All 0 Affirmative with Comments 1 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Cummings, Luke Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M.

Page 338 of 373

332 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Negative with Comment Crowley, Michael A. The committee justification is not correct. Chapter 8 , 18 and 19 describe allowable protection for these openings. The openings are not UNPROTECTED.

Page 339 of 373

333 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6650-NFPA 101-2019 [ Section No. A.19.3.5.10 ]

A.19.3.5.10 This exception is limited to hospitals, as nursing homes and many limited care facilities might have more combustibles within the closets. The limited amount of clothing found in the small clothes closets in hospital patient rooms is typically far less than the amount of combustibles in casework cabinets that do not require sprinkler protection, such as nurse servers. In many hospitals, especially new hospitals, it is difficult to make a distinction between clothes closets and cabinet work. The exception is far more restrictive than similar exceptions for hotels and apartment buildings. NFPA 13 already permits the omission of sprinklers in wardrobes. [see 8.1.1(7) of NFPA 13 ]. It is not the intent of 19.3.5.10 to affect the wardrobe provisions of NFPA 13. It is the intent that the sprinkler protection in the room covers the closet as if there were no door on the closet. (See 8.5.3.2.3 of NFPA 13 .)

Submitter Information Verification

Committee: SAF-HEA Submittal Date: Thu Jul 18 14:58:53 EDT 2019

Committee Statement

Committee The revision responds to correlating committee direction to update references to NFPA 13. The Statement: specific references are not needed and are subject to change. This revision eliminates the specific references to preclude the need to update them in the future. Response SR-6650-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

31 Eligible Voters 3 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Harris, Donald W. Pethe, Ben Vann, Joshua

Affirmative All Brooks, Bruce D. Bush, Kenneth E. Carson, Wayne G. Chip Crowley, Michael A. Cummings, Luke

Page 340 of 373

334 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Dagenais, David A. Dannaway, Samuel S. Davy, Matthew W. DeRosier, Joseph M. Epstein, Alice L. Farraher, Martin J. Furdell, Gary Horeis, Richard M. Klein, David P. Knippa, Kevin Koffel, William E. McKenzie, Herman Merrill II, James Prediger, G. Brian Rickard, John A. Roberts, Richard Jay Roeper, Kurt A. Schmitt, Dennis L. Schultz, Terry Spaanbroek, Steven G. Stinnett, Neil Victor, Terry L. Widdekind, Michael D.

Page 341 of 373

335 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6580-NFPA 101-2019 [ Section No. A.31.3.5.4 ]

A.31.3.5.4 The provision of 31.3.5.4 differs from NFPA 13 because fire data shows that in apartment fires where sprinklers were present, bathrooms were the area of origin in 1 percent of the total fires, and resulted in no civilian deaths, civilian injuries, or property loss. NFPA 101 and NFPA 13 both allow sprinklers to be omitted in small bathrooms in dwelling units. Historically, NFPA 13 sometimes differed in this requirement. Maintaining this provision in NFPA 101 allows all previously approved sprinkler installations to remain compliant.

Submitter Information Verification

Committee: SAF-RES Submittal Date: Mon Jul 08 18:39:52 EDT 2019

Committee Statement

Committee The annex note has been updated to reflect the current status of the requirements in NFPA Statement: 101 and NFPA 13. Response Message: SR-6580-NFPA 101-2019

Ballot Results

This item has passed ballot

31 Eligible Voters 6 Not Returned 25 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Boyd, H. Wayne Damron, Donald P. Gould, Jennifer Klein Hall, William J. Sharry, John A. Zwirn, Jeffrey D.

Affirmative All Almannai, Ali Asp, Roland A. Bradley, Harry L. Buuck, Daniel Coats, Paul D. Cook, David Page 342 of 373

336 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Cotter, Patrick B. Cronin, Bradford T. Dawe, Nicholas A. Finnegan, Daniel P. Haidar, Abir Isman, Kenneth E. Lambert, Josh Larson, Mark Lathrop, James K. Longhitano, Alfred J. Mayl, Eric N. Noble, Thomas William Paszczuk, Henry Pauls, Jake Pullen, William Davison Roberts, Richard Jay Spangler, Kevin Versteeg, Joseph H. Zubair Sarwar, Muhammad Ahmad

Page 343 of 373

337 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6642-NFPA 101-2019 [ Section No. A.36.4.4 ]

A.36.4.4 This section provides an optional, not mandatory, arrangement for the design and construction of mall concourse structures. At the discretion of the designer, these structures can be designed as a single building as long as they comply with the applicable requirements of the intended occupancy and with the requirements of 6.1.14 for buildings housing more than one occupancy.

Submitter Information Verification

Committee: SAF-MER Submittal Date: Tue Jul 16 10:35:28 EDT 2019

Committee Statement

Committee This revision is a follow up to the significant work done in 2018 edition updating the Statement: terminology for the provisions for mall structures. Response SR-6642-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

28 Eligible Voters 2 Not Returned 25 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Campbell, Kina Rice, Sarah A.

Affirmative All Alsulaiti, Mohammed Bellamy, Tracey D. Bush, Kenneth E. Coats, Paul D. Cole, Anthony W. Dawe, Nicholas A. Derr, Kevin L. Dodge, David A. Donovan, Scott Frable, David W.

Page 344 of 373

338 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Freels, Douglas R. Garriss, Marvin Dwayne Garzone, Joseph R. Gauvin, Daniel J. Gumkowski, Anthony C. Humble, Jonathan Kauffman, Conor J. Martin, Jeff Mourao, Bridget Murdock, Amy J. Shirey, Jeffrey Stocker, Warren G. Tabar, David C. Wensus, Timothy Yonkers, Ernest D.

Affirmative with Comment Ford, Daniel Agree - this is consistent with the chapter terminology.

Page 345 of 373

339 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6644-NFPA 101-2019 [ Section No. A.36.4.4.4 ]

A.36.4.4.4 Where a pedestrian way mall concourse meets the requirements for a public way, the means of egress from each tenant space or building is permitted to terminate at the pedestrian way mall concourse . For those arrangements, the pedestrian way mall concourse would not be considered to be a portion of the means of egress.

Submitter Information Verification

Committee: SAF-MER Submittal Date: Tue Jul 16 10:41:37 EDT 2019

Committee Statement

Committee This revision is a follow up to the significant work done in 2018 edition updating the Statement: terminology for the provisions for mall structures. Response SR-6644-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

28 Eligible Voters 2 Not Returned 25 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Campbell, Kina Rice, Sarah A.

Affirmative All Alsulaiti, Mohammed Bellamy, Tracey D. Bush, Kenneth E. Coats, Paul D. Cole, Anthony W. Dawe, Nicholas A. Derr, Kevin L. Dodge, David A. Donovan, Scott Frable, David W.

Page 346 of 373

340 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Freels, Douglas R. Garriss, Marvin Dwayne Garzone, Joseph R. Gauvin, Daniel J. Gumkowski, Anthony C. Humble, Jonathan Kauffman, Conor J. Martin, Jeff Mourao, Bridget Murdock, Amy J. Shirey, Jeffrey Stocker, Warren G. Tabar, David C. Wensus, Timothy Yonkers, Ernest D.

Affirmative with Comment Ford, Daniel Agree - this is consistent with the chapter terminology.

Page 347 of 373

341 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6645-NFPA 101-2019 [ Section No. A.37.4.4.4 ]

A.37.4.4.4 Where a pedestrian way mall concourse meets the requirements for a public way, the means of egress from each tenant space or building is permitted to terminate at the pedestrian way mall concourse . For those arrangements, the pedestrian way mall concourse would not be considered to be a portion of the means of egress.

Submitter Information Verification

Committee: SAF-MER Submittal Date: Tue Jul 16 10:42:53 EDT 2019

Committee Statement

Committee This revision is a follow up to the significant work done in 2018 edition updating the Statement: terminology for the provisions for mall structures. Response SR-6645-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

28 Eligible Voters 2 Not Returned 25 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Campbell, Kina Rice, Sarah A.

Affirmative All Alsulaiti, Mohammed Bellamy, Tracey D. Bush, Kenneth E. Coats, Paul D. Cole, Anthony W. Dawe, Nicholas A. Derr, Kevin L. Dodge, David A. Donovan, Scott Frable, David W.

Page 348 of 373

342 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Freels, Douglas R. Garriss, Marvin Dwayne Garzone, Joseph R. Gauvin, Daniel J. Gumkowski, Anthony C. Humble, Jonathan Kauffman, Conor J. Martin, Jeff Mourao, Bridget Murdock, Amy J. Shirey, Jeffrey Stocker, Warren G. Tabar, David C. Wensus, Timothy Yonkers, Ernest D.

Affirmative with Comment Ford, Daniel Agree - this is consistent with the chapter terminology.

Page 349 of 373

343 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6511-NFPA 101-2019 [ Section No. D.1.2.2 ]

D.1.2.2 ANSI Publications. American National Standards Institute, Inc., 25 West 43rd Street, 4th Floor, New York, NY 10036. www.ansi.org ANSI/BHMA A156.10, Power Operated Pedestrian Doors, 2011 2017 . ANSI/BHMA A156.19, Power Assist and Low Energy Power Operated Doors, 2013. ANSI/BHMA A156.38, Low Energy Power Operated Sliding and Folding Doors , 2014. ANSI/BHMA A156.41, Standard for Door Hardware Single Motion for Egress, 2017. ANSI Z97.1, Safety Glazing Materials Used in Buildings — Safety Performance Specifications and Methods of Test, 2015. ICC/ANSI A117.1, Accessible and Usable Buildings and Facilities , 2009.

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 05 15:59:04 EDT 2019

Committee Statement

Committee The revision updates the referenced publications to the current editions. The former ICC/ANSI Statement: A117.1 is now designated as ICC A117.1 and has been moved to ICC Publications. Response SR-6511-NFPA 101-2019 Message:

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P.

Page 350 of 373

344 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 351 of 373

345 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6512-NFPA 101-2019 [ Section No. D.1.2.4 ]

D.1.2.4 ASHRAE Publications. ASHRAE, 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. www.ashrae.org ASHRAE Handbook — Fundamentals, 2013 2017 . Klote, J.H. and Milke, J.A., Principles of Smoke Management, 2002.

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 05 16:01:34 EDT 2019

Committee Statement

Committee Statement: The revision updates the referenced publication to the current edition. Response Message: SR-6512-NFPA 101-2019

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris Page 352 of 373

346 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 353 of 373

347 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6513-NFPA 101-2019 [ Section No. D.1.2.5 ]

D.1.2.5 ASME Publications. ASME International, Two Park Avenue, New York, NY 10016-5990. www.asme.org ASME A17.1/CSA B44, Safety Code for Elevators and Escalators, 2013 2016 . ASME A17.3, Safety Code for Existing Elevators and Escalators, 2011 2017 .

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 05 16:03:07 EDT 2019

Committee Statement

Committee Statement: The revision updates the referenced publications to the current editions. Response Message: SR-6513-NFPA 101-2019

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris Page 354 of 373

348 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 355 of 373

349 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6514-NFPA 101-2019 [ Section No. D.1.2.6 ]

D.1.2.6 ASSE ASSP Publications. American Society of Safety Engineers Professionals , 520 N. Northwest Highway, Park Ridge, IL 60068. ANSI/ASSE ASSP A1264.2, Standard for the Provision of Slip Resistance on Walking/Working Surfaces, 2012.

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 05 16:07:25 EDT 2019

Committee Statement

Committee ASSE is now known as ASSP. The revision updates the referenced publication to the Statement: current edition. Response Message: SR-6514-NFPA 101-2019

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J.

Page 356 of 373

350 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 357 of 373

351 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6515-NFPA 101-2019 [ Section No. D.1.2.7 ]

D.1.2.7 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. www.astm.org ASTM C1629/C1629M, Standard Classification for Abuse-Resistant Nondecorated Interior Gypsum Panel Products and Fiber-Reinforced Cement Panels , 2006 (2011). ASTM D2859, Standard Test Method for Ignition Characteristics of Finished Textile Floor Covering Materials, 2006 (2011) 2016 . ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, 2015a 2019a . ASTM E119, Standard Test Methods for Fire Tests of Building Construction and Materials, 2014 2018c e1 . ASTM E648, Standard Test Method for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source, 2014c 2017a . ASTM E814, Standard Test Method for Fire Tests of Through- Penetration Fire Stops Stop Systems , 2013a (2017) . ASTM E1352, Standard Test Method for Cigarette Ignition Resistance of Mock-Up Upholstered Furniture Assemblies, 2008 2016 . ASTM E1353, Standard Test Methods for Cigarette Ignition Resistance of Components of Upholstered Furniture, 2008 2016 . ASTM E1472, Standard Guide for Documenting Computer Software for Fire Models, 2007 (withdrawn 2011). ASTM E1537, Standard Test Method for Fire Testing of Upholstered Furniture, 2013 2016 . ASTM E1590, Standard Test Method for Fire Testing of Mattresses, 2013 2017 . ASTM E1966, Standard Test Method for Fire-Resistive Joint Systems, 2007 (2011) 2015 (2019) . ASTM E2030, Standard Guide for Recommended Uses of Photoluminescent (Phosphorescent) Safety Markings, 2009a (withdrawn 2018) . ASTM E2174, Standard Practice for On-Site Inspection of Installed Fire Stops Firestops ,2010a e1 2018 . ASTM E2238, Standard Guide for Evacuation Route Diagrams, 2012. ASTM E2280, Standard Guide for Fire Hazard Assessment of the Effect of Upholstered Seating Furniture Within Patient Rooms of Health Care Facilities, 2013 2017 . ASTM E2307, Standard Test Method for Determining Fire Resistance of Perimeter Fire Barrier Systems Using Intermediate-Scale, Multi-Story Test Apparatus, 2015a 2015b e1 . ASTM E2393, Standard Practice for On-Site Inspection of Installed Fire Resistive Joint Systems and Perimeter Fire Barriers, 2010a (2015) . ASTM E2484, Standard Specification for Multi-Story Building External Evacuation Controlled Descent Devices, 2008 (2015) . ASTM E2513, Standard Specification for Multi-Story Building External Evacuation Platform Rescue Systems, 2007 (2012) . ASTM E2768, Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials, 2011 (2018) . ASTM F1637, Standard Practice for Safe Walking Surfaces, 2010 2019 . ASTM F1870, Standard Guide for Selection of Fire Test Methods for the Assessment of Upholstered Furnishings in Detention and Correctional Facilities, 2011 2016 . ASTM F2291, Standard Practice for Design and Amusement Rides or Devices , 2019.

Submitter Information Verification

Page 358 of 373

352 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Committee: SAF-FUN Submittal Date: Wed Jun 05 16:10:17 EDT 2019 Committee Statement

Committee Statement: The revisions updates the referenced publications to the current editions. Response Message: SR-6515-NFPA 101-2019

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 359 of 373

353 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6575-NFPA 101-2019 [ New Section after D.1.2.9 ]

D.1.2.10 ICC Publications. International Code Council, 500 New Jersey Avenue, NW, 6th Floor, Washington, DC 20001-2070. ICC A117.1, Accessible and Usable Buildings and Facilities , 2017.

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Thu Jun 27 14:32:50 EDT 2019

Committee Statement

Committee Statement: Referenced publication update. Response Message: SR-6575-NFPA 101-2019

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris Klein, David P. Page 360 of 373

354 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 361 of 373

355 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6516-NFPA 101-2019 [ Section No. D.1.2.9 ]

D.1.2.9 FM Global Publications. FM Global, 270 Central Avenue, P.O. Box 7500, Johnston, RI 02919-4949 . www.fmglobal.com ANSI/ FM Approval 4880, Approval American National Standard for Class 1 Rating of Insulated Wall or Wall and Roof/Ceiling Panels, Interior Finish Materials or Coatings, and Exterior Wall Systems Evaluating the Fire Performance of Insulated Building Panel Assemblies and Interior Finish Materials , 2010 2017 . FM Approval 6921, Approval Standard for Containers for Combustible Waste, 2004.

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 05 16:22:57 EDT 2019

Committee Statement

Committee Statement: The revision updates the referenced publications to the current edition. Response Message: SR-6516-NFPA 101-2019

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M

Page 362 of 373

356 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Jacoby, David J. Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 363 of 373

357 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6517-NFPA 101-2019 [ Section No. D.1.2.10 ]

D.1.2.11 NEMA Publications. National Electrical Manufacturers Association, 1300 North 17th Street, Suite 900, Arlington, VA 22209. ANSI/NEMA Z535.1, Standard for Safety Colors, 2006, reaffirmed 2011 2017 .

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 05 16:25:20 EDT 2019

Committee Statement

Committee Statement: The revision updates the referenced publication to the current edition. Response Message: SR-6517-NFPA 101-2019

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris Klein, David P. Page 364 of 373

358 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 365 of 373

359 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6521-NFPA 101-2019 [ Section No. D.1.2.12 ]

D.1.2.13 RESNA Publications. Rehabilitation Engineering and Assistive Technology Society of North America, 1700 N Moore St, Suite 1540 1560 Wilson Blvd., Suite 850 , Arlingtron Arlington , VA 22209. ANSI/RESNA ED-1, Emergency Stair Travel Devices Used by Individuals with Disabilities, Volume 1, 2013 2019 .

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 05 16:51:43 EDT 2019

Committee Statement

Committee Statement: The revision updates the referenced publication to the current edition. Response Message: SR-6521-NFPA 101-2019

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J.

Page 366 of 373

360 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 367 of 373

361 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6519-NFPA 101-2019 [ Section No. D.1.2.13 ]

D.1.2.14 SFPE Publications. SFPE, 9711 Washington Blvd., Suite 380, Gaithersburg, MD 20878. www.sfpe.org SFPE Code Official’s Guide to Performance-Based Design Review, 2004. SFPE Engineering Guide — Evaluation of the Computer Fire Model DETACT-QS, 2002. SFPE Engineering Guide to Human Behavior in Fire,2003 2018 . SFPE Engineering Guide to Performance-Based Fire Protection, 2007. SFPE Guidelines for Peer Review in the Fire Protection Design Process, 2009. SFPE Guidelines for Substantiating a Fire Model for a Given Application, 2011. SFPE Handbook of Fire Protection Engineering, 5th edition, 2015 2016 . SFPE S.01, Standard on Calculating Fire Exposures to Structures , 2011. SFPE S.02, Engineering Standard on Calculation Methods to Predict the Thermal Performance of Structural and Fire Resistive Assemblies , 2015.

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 05 16:41:01 EDT 2019

Committee Statement

Committee Statement: The revision updates the referenced publications to the current editions. Response Message: SR-6519-NFPA 101-2019

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y.

Page 368 of 373

362 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 369 of 373

363 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6520-NFPA 101-2019 [ Section No. D.1.2.14 ]

D.1.2.15 UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096. www.ul.com UL Fire Resistance Directory, 2013 2018 . UL 217, Single and Multiple Station Smoke Alarms, 2012, revised 2015 2018 . UL 263, Fire Tests of Building Construction and Materials, 2003 2011 , revised 2014 2019 . UL 723, Test for Surface Burning Characteristics of Building Materials, 2008, revised 2013 2018 . UL 1040, Fire Test of Insulated Wall Construction, 2009 1996 , revised 2013 2017 . UL 1479, Fire Tests of Through- Penetration Firestops, 2003, revised 2012 2015 . UL 1715, Fire Test of Interior Finish Material, 1997, revised 2013 2017 . UL 1975, Fire Tests for Foamed Plastics Used for Decorative Purposes, 2006. UL 2079, Tests for Fire Resistance of Building Joint Systems, 2004, revised 2014 2015 .

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 05 16:46:14 EDT 2019

Committee Statement

Committee Statement: The revision updates the referenced publications to the current editions. Response Message: SR-6520-NFPA 101-2019

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Page 370 of 373

364 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Frable, David W. Groner, Norman E. Harbuck, Stanley C. Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 371 of 373

365 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Second Revision No. 6518-NFPA 101-2019 [ Section No. D.3 ]

D.3 References for Extracts in Informational Sections.

NFPA 72®, National Fire Alarm and Signaling Code®, 2016 2019 edition. NFPA 88A, Standard for Parking Structures, 2015 2019 edition. NFPA 101A , Guide on Alternative Approaches to Life Safety , 2019 edition. NFPA 301 , Code for Safety to Life from Fire on Merchant Vessels , 2018 edition. NFPA 400 , Hazardous Materials Code , 2019 edition.

NFPA 5000®, Building Construction and Safety Code®, 2018 2021 edition.

Submitter Information Verification

Committee: SAF-FUN Submittal Date: Wed Jun 05 16:38:34 EDT 2019

Committee Statement

Committee The revision updates the references for extracts in informational sections to the current Statement: editions. Response Message: SR-6518-NFPA 101-2019

Ballot Results

This item has passed ballot

21 Eligible Voters 2 Not Returned 19 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention

Not Returned Laramee, Scott T. Vann, Joshua

Affirmative All Al Zeyara, Nasser Ahmed Alfawakhiri, Farid Carson, Wayne G. Chip Cheng, Amy Y. Finnegan, Daniel P. Frable, David W. Groner, Norman E. Harbuck, Stanley C. Page 372 of 373

366 of 367 10/21/2019, 3:45 PM National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

Hopkins, Mark Hunter, Matthew M Jacoby, David J. Jelenewicz, Chris Klein, David P. Lathrop, James K. Murga, Ricardo Puchovsky, Milosh T. Reiswig, Rodger Roberts, Jon G. Schmeida, Michael

Page 373 of 373

367 of 367 10/21/2019, 3:45 PM