Littelfuse Varistor Design Examples

Total Page:16

File Type:pdf, Size:1020Kb

Littelfuse Varistor Design Examples Littelfuse Varistor Design Examples Application Note January 1998 AN9772 This note is meant to be a guide for the user in selecting a Energy and Current varistor by describing common application examples, and µ Ω [ /Title The 100 H inductor will appear to be about 30 to the illustrating the solution process to determine the appropriate transient. The 30Ω is derived from the inductive reactance at (AN97 varistor. Also described are varistor fusing and the transient generator source frequency of 105π rad. Taking a 72) series/parallel connection rules. first estimate of peak varistor current, 2500V/80Ω = 31A. (This /Sub- first estimate is high, since it assumes varistor clamping ject Applications voltage is zero.) With a tentative selection of a 130V Littelfuse (Har- Power Supply Protection Against Line Transient Varistor, we find that a current of 31A yields a voltage of from ris Damage 325V to 380V, depending on the model size, as shown in Figure 2A and Figure 2B. Varis- PROBLEM Revising the estimate, I ≈ (2500V - 325V)/80Ω = 27.2A. For tor It is desired to prevent failure of the power supply shown in model V130LA20A, 27.2A coincides closely with a 320V Design Figure 1B to be used on residential 117V lines. A AC clamping level. There is no need to further refine the estimate of representative transient generator is to be used for testing, Exam- peak current if model 20A remains the final selection. ples) as shown in Figure 1A. To arrive at an energy figure, assume a sawtooth current /Autho If the transient is applied to the existing circuit, the rectifier will waveform of 27A peak, dropping to zero in two time receive high negative voltages, transmitted through the filter r () constants, or 20µs. /Key- capacitor. The LC network is there to prevent RFI from being µ words transmitted into the power line (as in a TV set), but also serves Energy is then roughly equal to (27A x 320V x 20 s)/2, the to reduce the transient voltage. An analysis shows that the area under the power waveform. The result is 0.086J, well (TVS, transient will be reduced approximately by half, resulting in within the capability of the varistor (70J). Peak current is also Tran- about 2.5kV instead of 5kV at the rectifier. within the 6500A rating. sient This is still too high for any practical rectifier, so some Model Selection Sup- suppression must be added. It is desirable to use the built-in pres- The actual varistor selection is a trade-off between the impedance of the coil to drop the remaining voltage, so the clamping voltage desired and the number of transient sion, suppressor would best be applied as shown. A selection current pulses expected in the life of the equipment. A 70J Pro- process for a Littelfuse Varistor is as follows: rated varistor will clamp at 315V and be capable of handling 6 tec- SOLUTION over 10 such pulses. An 11J unit will clamp to tion, approximately 385V and be capable of handling over 105 Steady-State Voltage ESD, such pulses. Furthermore, the clamping voltage determines The 117V , 110% high line condition is 129V. The closest IEC, AC the cost of the rectifier by determining the voltage rating voltage rating available is 130V. required. A smaller, lower cost varistor may result in a more EMC, expensive higher voltage rectifier diode. Elec- tro- 100µHD 50Ω magne ≈ 5kV tic + VT = 0.1µF 150µF Com- - 5π pati- ± 5kV sin 10 t X bility, e-10-5t Harris Sup- FIGURE 1A. TRANSIENT GENERATOR FIGURE 1B. TYPICAL POWER SUPPLY CIRCUIT FIGURE 1. POWER SUPPLY PROTECTION 10-127 1-800-999-9445 or 1-847-824-1188 | Copyright © Littelfuse, Inc. 1998 Application Note 9772 3000 1000 UL1499 CORD CONNECTED AND DIRECT PLUG-IN 800 2000 CATEGORY 1500 600 V130LA2 500 1000 V130LA5 400 800 V130LA10A V130LA20A 600 300 500 400 MAXIMUM PEAK (V) 200 300 MAXIMUM PEAK (V) IMPULSE GENERATOR LOAD LINES 200 (IMPLIED) UL1449 PERMANENTLY CONNECTED CATEGORY, AND ANSI IEEE C61.41 (IEEE587) CATEGORY B 100 100 101 102 100 27 100 101 102 103 104 31 27 31 PEAK AMPERES 8/20µs WAVESHAPE PEAK AMPERES 8/20µs WAVESHAPE FIGURE 2A. FIGURE 2B. FIGURE 2. V130LA VARISTOR V-I CHARACTERISTICS IV 27 IV 27 APPROXIMATION VARISTOR CURRENT VARISTOR t 10µs 20µs VARISTOR CURRENT VARISTOR t 10µs20µs FIGURE 3A. FIGURE 3B. FIGURE 3. ENERGY APPROXIMATION SCR Motor Control SOLUTION PROBLEM Add a varistor to the transformer secondary to clamp the transformer inductive transient voltage spike. Select the The circuit shown in Figure 4 experiences failures of the lowest voltage Littelfuse Varistor that is equal to or greater rectifiers and SCR when the transformer primary is switched than the maximum high line secondary AC voltage. The off. The manufacturer has tried 600V components with little V130LA types fulfills this requirement. improvement. Determine the peak suppressed transient voltage produced by the transient energy source. This is based on the peak ARMATURE R1 transient current to the suppressor, assuming the worst-case Ω 330k SPEED condition of zero load current. Zero load current is normally CONTROL a valid assumption. Since the dynamic transient impedance 480V R3 of the Littelfuse Varistor is generally quite low, the parallel AC 60Hz FIELD 250kΩ higher impedance load path can be neglected. SCR SUS Since transient current is the result of stored energy in the R2 4:1 core of the transformer, the transformer equivalent circuit 15kΩ CI 0.2µF shown in Figure 5 will be helpful for analysis. The stored inductive energy is: FIGURE 4. SCR MOTOR CONTROL 1 ˆ2 E = --- L I M LM 2 M 10-128 Application Note 9772 After determining voltage and peak current, energy and power ZP ZS N dissipation requirements must be checked. For the given IM example, the single pulse energy is well below the MUTUAL o INDUCTANCE V130LA20B varistor rating of 70J at 85 C maximum ambient VPRIMARY REPRESENTED LM VSECONDARY BY IRON CORE temperature. Average power dissipation requirements over idling power are not needed because of the non-repetitive nature of the expected transient. Should the transient be IDEAL TRANSFORMER repetitive, then the average power is calculated from the product of the repetition rate times the energy of the transient. FIGURE 5. SIMPLIFIED EQUIVALENT CIRCUIT OF A If this value exceeds the V130LA20B capability of 1.0W, TRANSFORMER power varistors of the HA, DA, or DB Series may be required. The designer needs to know the total energy stored and the Should the ambient temperature exceed 85oC or the surface peak current transformed in the secondary circuit due to the temperature exceed 85oC, the single pulse energy ratings mutual inductance, L . At no load, the magnetizing current, M and the average power ratings must be derated by the (I ), is essentially reactive and is equal to I . This assumes NL M appropriate derating factors supplied on the data sheet. that the primary copper resistance, leakage reactance and equivalent core resistive loss components are small compared to LM. This is a valid assumption for all but the 14 smallest control transformers. Since INL is assumed purely reactive, then: 12 10 Vpri XL = ----------- M INL 8 and 6 f = 50...60Hz iM = INL 4 2 INL can be determined from nameplate data. Where nameplate is not available, Figure 6 and Figure 7 can guide the designer. CURRENT PERCENT MAGNETIZING 2 4 6 8 10 12 Assuming a 3.5% value of magnetizing current from Figure 7 TRANSFORMER RATING (kVA) FIGURE 6. MAGNETIZING CURRENT OF TRANSFORMERS for a 20kVA transformer with 480VAC primary, and 120VAC secondary: WITH LOW SILICON STEEL CORE 20kVA L = X /ω i = ()0.035 ------------------- M L M 480V M = 0.872H = 1.46A 6 2 ˆ 0.872() 2.06 iM = 2iM E = ----------------------------------- 5 LM 2 X = 480V/1.46A LM = 1.85J 4 = 329Ω 3 f = 50...60Hz With this information one can select the needed semiconductor voltage ratings and required varistor energy rating. 2 Peak varistor current is equal to transformed secondary 1 magnetizing current, i.e., îM(N), or 8.24A. From Figure 2, the CURRENT PERCENT MAGNETIZING peak suppressed transient voltage is 310V with the 110102 103 104 V130LA10A selection, 295V with the V130LA20B. This TRANSFORMER RATING (kVA) allows the use of 300V rated semiconductors. Safety FIGURE 7. MAGNETIZING CURRENT OF TRANSFORMERS margins exist in the above approach as a result of the WITH HIGH SILICON STEEL CORE OR SQUARE following assumptions: LOOP CORE 1. All of the energy available in the mutual inductance is transferred to the varistor. Because of core hysteresis Contact Arcing Due to Inductive Load and secondary winding capacitance, only a fraction less PROBLEM than two-thirds is available. To extend the life of the relay contacts shown in Figure 8 and 2. The exciting current is not purely reactive. There is a 10% to 20% safety margin in the peak current assumption. reduce radiated noise, it is desired to eliminate the contact arcing. 10-129 Application Note 9772 subsequent welding. To avoid this inrush current, it is RELAY customary to add a series resistor to limit the capacitive L discharge current. However, this additional component + CC reduces the network effectiveness and adds additional cost to R 28V C C = STRAY CAPACITANCE the solution. DC C L = RELAY COIL INDUCTANCE RC = RELAY COIL RESISTANCE BREAKDOWN LEVEL ARCING 100 FIGURE 8. RELAY CIRCUIT When relays or mechanical switches are used to control VOLTAGE CLAMP ABOVE ARC VOLTAGE inductive loads, it is necessary to use the contacts at only about 50 50% of their resistive load current rating to reduce the wear (V) ARC VOLTAGE VOLTAGE CLAMP BELOW caused by arcing of the contacts.
Recommended publications
  • Insulating Phase of a Two-Dimensional Electron
    Challenges and opportunities of ZnO-related single crystalline heterostructures Y. Kozuka1, A. Tsukazaki2,3, M. Kawasaki1,4,a) 1Department of Applied Physics and Quantum-Phase Electronics Center (QPEC), University of Tokyo, Tokyo 113-8656, Japan 2Institute for Materials Research, Tohoku University, Sendai 980-8577, Japan 3PRESTO, Japan Science and Technology Agency (JST), Tokyo 102-0075, Japan 4 RIKEN Center for Emergent Matter Science (CEMS), Wako 351-0198, Japan Abstract Recent technological advancement in ZnO heterostructures has expanded the possibility of device functionalities to various kinds of applications. In order to extract novel device functionalities in the heterostructures, one needs to fabricate high quality films and interfaces with minimal impurities, defects, and disorder. With employing molecular-beam epitaxy (MBE) and single crystal ZnO substrates, the density of residual impurities and defects can be drastically reduced and the optical and electrical properties have been dramatically improved for the ZnO films and heterostructures with MgxZn1-xO. Here, we overview such recent technological advancement from various aspects of application. Towards optoelectronic devices such as a light emitter and a photodetector in an ultraviolet region, the development of p-type ZnO and the fabrication of excellent Schottky contact, respectively, have been subjected to intensive studies for years. For the former, the fine tuning of the growth conditions to make MgxZn1-xO as intrinsic as possible has opened the possibilities of making p-type MgxZn1-xO through NH3 doping method. For the latter, conducting and transparent polymer films spin-coated on MgxZn1-xO was shown to give almost ideal Schottky junctions. The wavelength-selective detection can be realized with varying the Mg content.
    [Show full text]
  • Application Note TAN 1002 Application Notes from MTL Surge Technologies
    MTL Surge Technologies Lightning and surge protection - basic principles Synopsis This publication discusses the nature of the threat to electronic instrumentation and communications networks posed by voltage surges induced by lightning or other causes. The practical application of surge protection devices (SPDs) designed to prevent damage from such sources is described. Application Note TAN 1002 Application Notes from MTL Surge Technologies MTL Surge Technologies publish an increasing number of Application Notes providing easily understood information on various aspects of lightning and surge protection. At the date of publication of this Application Note, the list included:– TAN1001 Lightning surge protection for electronic equipment – a practical guide A relatively brief and easy to understand introduction to the subject – an excellent starting point. TAN1002 Lightning and surge protection – basic principles A more detailed account of the mechanism of lightning strikes and the measures needed to achieve an adequate level of protection. TAN1003 Earthing guide for surge protection A detailed analysis of the subject of earthing for surge suppression purposes, this is both an easily understood exposition and a valuable reference document. TAN1004 Surge protection for intrinsically safe systems A description of the best methods of combining surge protection and intrinsically safe systems. TAN1005 Surge protection for Zone 0 locations A detailed analysis of this particular aspect of surge suppression in hazardous areas; complements TAN1004. TAN1006 Surge protection for weighing systems Discusses, in some detail, the application of surge suppression to load-cell weighing systems. TAN1007 Surge protection for Local Area Networks Discusses ways in which Local Area Networks can be damaged by lightning induced transients and how they can be protected economically.
    [Show full text]
  • TRIAC Overvoltage Protection Using a Transil™
    AN1966 Application note TRIAC overvoltage protection using a Transil™ Introduction In most of their applications, TRIACs are directly exposed to overvoltages coming from the mains, as described in IEC 61000-4-5 or IEC 61000-4-4 standards. When TRIACs are used to drive resistive loads (ex: temperature regulation), it is essential to provide them with efficient overvoltage protection to prevent any turn-on in breakover mode that could lead to device damage. A traditional method to clamp the voltage is to use a varistor in parallel across the TRIAC. But with high power loads (a few kW), the current through the varistor is very high in case of surge voltages (a few hundred amperes). The varistor is then not efficient enough, due to its dynamic resistor, to limit the TRIAC voltage to a low value. We present here a solution that can be used for these kinds of applications and also for all applications where TRIAC voltage protection is required. It should be noted that the overvoltages could also come from the overvoltages that appear at device turn-off due to the TRIAC holding current. This phenomenon occurs mainly with TRIACs controlling low rms current (15-50 mA), high inductive loads like valves. For more information about such behavior, please refer to AN1172. Contents 1 Why overvoltage protection is required . 2 2 Overvoltage protection solution . 3 3 Transil choice for efficient TRIAC voltage protection . 6 3.1 Normal operation: check VRM voltage . 6 3.2 Surge voltage clamping: check max VCL voltage . 6 4 Experimental validation example . 8 5 Conclusion .
    [Show full text]
  • Chip Varistors Countermeasure for Surge Voltage and Static Electricity
    Chip Varistors Countermeasure for surge voltage and static electricity AVR series Type: AVR-M AVRL Issue date: September 2013 • All specifications are subject to change without notice. • Conformity to RoHS Directive: This means that, in conformity with EU Directive 2002/95/EC, lead, cadmium, mercury, hexavalent chromium, and specific bromine-based flame retardants, PBB and PBDE, have not been used, except for exempted applications. (2/11) Varistors(SMD) Conformity to RoHS Directive Countermeasure for Surge Voltage and Static Electricity AVR Series AVR-M, AVRL Types Varistors are voltage dependent nonlinear resistive elements with a resistance that decreases rapidly when the voltage is over the constant value. Varistor is equivalent with Zener diode of two series connection. Therefore, do not have polarity. CURRENT vs. VOLTAGE CHARACTERISTICS EQUIVALENT CIRCUIT 2 Zener Diodes ) 10–1 A ( 10–2 Zener diode /Vz:6.8V –3 Positive direction 10 Chip varistor Current /V1mA:12V 10–4 A capacitance content 10–5 –18 –14–10–610–262 14 18 –10–5 –10–4 –10–3 Negative direction –10–2 –10–1 Voltage(V) THE EFFECT OF THE VARISTOR WITHOUT VARISTOR WITH VARISTOR A malfunction and failure of electronic equipment Suppress abnormal voltage by inserting varistor in a circuit ESD, Surge voltage ESD, Surge voltage Power line IC Power line IC Signal line Signal line Insert a varistor between a line and ground : Chip varistor • All specifications are subject to change without notice. 002-01 / 20130927 / e9c11_avr.fm (3/11) FEATURES INTERNAL STRUCTURE • No polarity, due to symmetrical current-voltage characteristics. Inner electrode Varistor body Equivalent to anode common type Zener diode.
    [Show full text]
  • BASIDE. Varistor ASINKE
    USOO7768754B2 (12) United States Patent (10) Patent No.: US 7,768,754 B2 Collins, III et al. (45) Date of Patent: Aug. 3, 2010 (54) CERAMICSUBSTRATE FOR LIGHT 4,506,285 A 3/1985 Einzinger EMITTING DODE WHERE THE SUBSTRATE 5,176,772 A 1, 1993 Ohtaki NCORPORATES ESD PROTECTION 5,235,310 A 8, 1993 Cowman et al. 5,290,375 A 3/1994 Nagasaka et al. (75) Inventors: William David Collins, III, San Jose, 5,540,884 A 7, 1996 Chiao CA (US); Jerome Chandra Bhat, San 5,874,378 A 2/1999 Ishida et al. Francisco, CA (US) 5,889.308 A 3/1999 Hong et al. (73) Assignees: Philips Lumileds Lighting Company, 6,217,990 B1 4/2001 Asai et al. LLC, San Jose, CA (US); Koninklijke 6,339,367 B1 1/2002 Takehana Philips Electronics N.V., Eindhoven 6,535,105 B2 3/2003 Heistand, II et al. (NL) 2001/0043454 A1 11/2001 Yoshii et al. 2002/0179914 A1 12/2002. Sheu (*) Notice: Subject to any disclaimer, the term of this 2003/0043013 A1 3/2003 Shiraishi et al. patent is extended or adjusted under 35 2004/0222433 A1* 11/2004 MaZZochette et al. ......... 257/99 U.S.C. 154(b) by 402 days. (21) Appl. No.: 11/848,055 (22) Filed: Aug. 30, 2007 OTHER PUBLICATIONS O O Lionel M. Levinson et al., “The physics of metal Oxide Varistors'. (65) Prior Publication Data Journal of Applied Physics, vol. 46, No.3, Mar. 1975, pp. 1332-1341. US 2007/O297.108A1 Dec. 27, 2007 Mark Drabkin et al., “Improved Metal Oxide Varistor Packaging Technology For Transient Voltage Surge Suppressers (TVSS)”.
    [Show full text]
  • Electrical Properties & Microstructure Of
    Republic of Iraq Ministry of Higher Education and Scientific Research University of Baghdad College of Education for Pure Science Ibn-AL-Haitham Electrical Properties & Microstructure Of ZnO - Based Varistor Ceramics Doped With Rare Earth A Thesis Submitted to University of Baghdad / College of Education for Pure Science (Ibn-AL-Haitham) in partial Fulfillment of the Requirements for the Degree of Philosophy Doctorate of Science In Physics By Adil Ismaeel Khadim Supervisors Asst. Prof. Dr. Aysar. J. Ibraheem Asst. Prof. Dr. Abdul Hameed.R.Mahdi 2015 Dedication To my teacher and inspirer, Prophet Muhammad, peace be upon him, to each science student aware of the request and benefit reform, my mother and to my father soul. Adil ACKNOWLEDGEMENT In the name of God the Most Gracious the Most Merciful Praise be to God in the start and finish. I would like to express sincere appreciation and gratitude to Asst. Prof. Dr. Aysar. J. Ibraheem and Asst. Prof. Dr. Abdul Hameed.R.Mahdi for supervision, guidance, and suggestions. My special thanks to (Dr.Samir Atta, Dr. Tariq Al-Dhahir, Dr. Mudhir Shihab, Mr.Ayad Ahmad, Dr.Hameed Majeed, Mr. Firas Khadim, and Mr. Samir Ghanim, in department of Physics). Sincere thanks are due to (Dr. Khalid Waleed, Dr. Ismaeel Yaseen, Dr.Husam Saleem, Dr. Tagreed Hashim and Dr. Maha Abdulsattar, in department of Chemistry). Sincere thanks to Assistant Professor Dr. Khalid Fahad Ali the dean of the college of education for pure science, Ibn Al-Haitham. My sincere thanks and gratitude to my family and my aunt Maida Jassim, and my classmate Zainab Tariq.
    [Show full text]
  • Knowing the Surge Protection Device
    Wollemi Technical Incorporation Application Note Knowing the Surge Protection Device There are so many names for protective devices such as 'lightning barriers', 'surge arresters ', 'lightning protection units', etc. In ideal condition, the surge protection devices should dissipate the instantaneous current spike out of the device, module or system to the ground. For long lasting protection, all the SPD (Surge Protection Device) should automatically restore normal operation state right after a sustainable surge has subsided. Protected Surge equipment Surge protection device Here after show and brief most of the practical SPD now engineers can use for surge protection application. Gas Discharge Tubes Gas discharge tubes (GDTs) are developed to overcome some of the disadvantages of air or carbon spark gaps by hermetic sealing, thereby eliminating environmental effects. GDTs can provide a rigorous spark discharge control performance since the breakdown voltage was decided by what kind of the gas filling and the electrode spacing. For example, low voltage protection devices have electrode spacing of around 1mm or and in an argon/hydrogen mixture sealed within a ceramic envelope at about 0.1 Bar presure. Wollemi Technical Incorporation Application Note TVS diode GDT Zener diodes About regular Zener diodes. These devices are fast in operation and are available in a wide range of voltages that provide accurate and repeatable voltage clamping. Standard Zener diodes cannot usually handle high surge currents but some modified dedicated “Surge suppression” diodes can withstand of several kW of power now are getting more and more popular in many electric circuits from power supply to data transmission. Some new applications are developed on using Zener diode to protect ultra small device.
    [Show full text]
  • Thyristors & Triacs
    APPLICATION NOTE Thyristors & Triacs - Ten Golden Rules for Success In Your Application. This Technical Publication aims to provide an threshold current IGT, within a very short time known as interesting, descriptive and practical introduction to the the gate-controlled turn-on time, tgt, the load current can golden rules that should be followed in the successful flow from ’a’ to ’k’. If the gate current consists of a very use of thyristors and triacs in power control applications. narrow pulse, say less than 1µs, its peak level will have to increase for progressively narrower pulse widths to Thyristor guarantee triggering. A thyristor is a controlled rectifier where the When the load current reaches the thyristor’s latching unidirectional current flow from anode to cathode is current IL, load current flow will be maintained even after initiated by a small signal current from gate to cathode. removal of the gate current. As long as adequate load current continues to flow, the thyristor will continue to akconduct without the gate current. It is said to be latched ON. Note that the VGT,IGT and IL specifications given in data g are at 25 ˚C. These parameters will increase at lower temperatures, so the drive circuit must provide adequate Fig. 1. Thyristor. voltage and current amplitude and duration for the The thyristor’s operating characteristic is shown in lowest expected operating temperature. Fig. 2. Rule 1. To turn a thyristor (or triac) ON, a gate current On-state ≥ Forward IGT must be applied until the load current is current characteristic ≥ IL. This condition must be met at the lowest expected operating temperature.
    [Show full text]
  • AUMOV® & LV Ultramov™ Varistor Design Guide for DC & Automotive Applications
    AUMOV® & LV UltraMOV™ Varistor Design Guide for DC & Automotive Applications High Surge Current Varistors Design Guide for Automotive AUMOV® Varistor & LV UltraMOV™ Varistor Series Table of Contents Page About the AUMOV® Varistor Series 3-4 About the LV UltraMOV™ Series Varistor 5-6 Varistor Basic 6 Terminology Used in Varistor Specifications 7 Automotive MOV Background and Application Examples 8-10 LV UltraMOV™ Varistor Application Examples 11- 12 How to Select a Low Voltage DC MOV 13-15 Transient Suppression Techniques 16-17 Introduction to Metal Oxide Varistors (MOVs) 18 Series and Parallel Operation of Varistors 19-20 AUMOV® Varistor Series Specifications and Part Number Cross-References 21-22 LV UltraMOV™ Series Specifications and Part Number Cross-References 23-26 Legal Disclaimers 27 © 2015 Littelfuse, Inc. Specifications descriptions and illustrative material in this literature are as accurate as known at the time of publication, but are subject to changes without notice. Visit littelfuse.com for more information. DC Application Varistor Design Guide About the AUMOV® Varistor Series About the AUMOV® Varistor Series The AUMOV® Varistor Series is designed for circuit protection in low voltage (12VDC, 24VDC and 42VDC) automotive systems. This series is available in five disc sizes with radial leads with a choice of epoxy or phenolic coatings. The Automotive MOV Varistor is AEC-Q200 (Table 10) compliant. It offers robust load dump, jump start, and peak surge current ratings, as well as high energy absorption capabilities. These devices
    [Show full text]
  • Varistors: Ideal Solution to Surge Protection
    Varistors: Ideal Solution to Surge Protection By Bruno van Beneden, Vishay BCcomponents, Malvern, Pa. If you’re looking for a surge protection device that delivers high levels of performance while address- ing pressures to reduce product size and compo- nent count, then voltage dependent resistor or varistor technologies might be the ideal solution. ew regulations concerning surge protection limit the voltage to a defined level. The crowbar group in- are forcing engineers to look for solutions cludes devices triggered by the breakdown of a gas or in- that allow such protection to be incorpo- sulating layer, such as air gap protectors, carbon block de- rated at minimal cost penalty, particularly tectors, gas discharge tubes (GDTs), or break over diodes in cost-sensitive consumer products. In the (BODs), or by the turn-on of a thyristor; these include automotiveN sector, surge protection is also a growing ne- overvoltage triggered SCRs and surgectors. cessity—thanks to the rapid growth of electronic content One advantage of the crowbar-type device is that its very in even the most basic production cars combined with the low impedance allows a high current to pass without dissi- acknowledged problems of relatively unstable supply volt- pating a considerable amount of energy within the protec- age and interference from the vehicle’s ignition system. tor. On the other hand, there’s a finite volt-time response Another growing market for surge protection is in the as the device switches or transitions to its breakdown mode, telecom sector, where continuously increasing intelligence during which the load may be exposed to damaging over- in exchanges and throughout the networks leads to greater voltage.
    [Show full text]
  • How to Select a Surge Diode
    Application Report SLVAE37–January 2019 How to select a Surge Diode Alec Forbes ABSTRACT For systems in harsh industrial environments, one of the most important parts of system protection is the input TVS diode selection. The input TVS diode is designed to protect fragile system inputs from large transient spikes that are caused by nearby machinery, lightning strikes, or power surges. These surges are modeled and regulated by IEC 61000-4-5, which standardizes the protection requirements systems must meet in order to ensure that they will not see failures when exposed to these transients. However, passing these standards is not trivial, especially to a designer who is unfamiliar with protection diodes and the specifications. This document will provide an introduction to TVS diodes, comparing them to other transient protection solutions, discussing some of the key specifications and then providing a system example. An understanding of these specifications will allow a designer to have a more solid fundamental understanding of how to select a TVS diode for surge protection, which will directly translate to a more robust system. Contents 1 Types of Transient Suppression Components ........................................................................... 1 2 TVS Diode Specifications................................................................................................... 2 3 Example: Selecting a TVS for a PLC 4/20 mA Input.................................................................... 6 4 Conclusion ...................................................................................................................
    [Show full text]
  • High Power Solutions for Surge Protection
    New Product Brief High Power Solutions for Surge Protection Power line failures, lightning, and switching surges can cause permanent product damage, data loss, or worse. Designers need to choose the most appropriate protection to guard against these risks. Five types of popular high power protection solutions are provided for different requirements. Current Rating / Peak Pulse Power Typical Voltage Solution Types Component Lifetime (@8/20µS) Clamping Speeds High Power TVS Diode 1kA-20kA Fastest Excellent SIDACtor® Protection Thyristor + Varistor 500A-10kA Very Fast Very Good GDT+ Varistor 1kA-20kA Fast Good Varistor 500A-22kA Moderate Fair GDT 500A-100kA Fast Very Good DC Power AC Power Protection Protection © 2019 Littelfuse Littelfuse.com New Product Brief High Power Solutions Test 1. High Power Solutions Test 2. (Clamping Performance Comparison) (Overshoot Voltage Comparison) AK TVS vs. SIDACtor+Varistor vs. Varistor GDT+Varistor vs. SIDACtor+Varistor, Ipp=5kA High Power Varistor + SIDACtor® Varistor + SIDACtor® Types Varistor Types GDT+ Varistor TVS Diode Protection Thyristor Protection Thyristor Component(s) used Component(s) used AK3-430 V20E250P + P3500FNL V20E385P CG2600+V20H385P V20H385P + P3800MEL for below test for below test CG2600+V20H385P V20E385P P3800MEL+V20H385P V20E250P + P3500FNL AK3-430C 6kV Surge Current High Power Products Offering Unidirectional/ Series Description Voltage Package Type Product Type Bidirectional AK familes Series ( including LTKAK) 1kA-20kA@8/20µS 12-530V Uni / Bi Axial /SMT P600 Packaged Series
    [Show full text]