Transformer Protection
Total Page:16
File Type:pdf, Size:1020Kb
Load more
Recommended publications
-
Chapter – 3 Electrical Protection System
CHAPTER – 3 ELECTRICAL PROTECTION SYSTEM 3.1 DESIGN CONSIDERATION Protection system adopted for securing protection and the protection scheme i.e. the coordinated arrangement of relays and accessories is discussed for the following elements of power system. i) Hydro Generators ii) Generator Transformers iii) H. V. Bus bars iv) Line Protection and Islanding Primary function of the protective system is to detect and isolate all failed or faulted components as quickly as possible, thereby minimizing the disruption to the remainder of the electric system. Accordingly the protection system should be dependable (operate when required), secure (not operate unnecessarily), selective (only the minimum number of devices should operate) and as fast as required. Without this primary requirement protection system would be largely ineffective and may even become liability. 3.1.1 Reliability of Protection Factors affecting reliability are as follows; i) Quality of relays ii) Component and circuits involved in fault clearance e.g. circuit breaker trip and control circuits, instrument transformers iii) Maintenance of protection equipment iv) Quality of maintenance operating staff Failure records indicate the following order of likelihood of relays failure, breaker, wiring, current transformers, voltage transformers and D C. battery. Accordingly local and remote back up arrangement are required to be provided. 3.1.2 Selectivity Selectivity is required to prevent unnecessary loss of plant and circuits. Protection should be provided in overlapping zones so that no part of the power system remains unprotected and faulty zone is disconnected and isolated. 3.1.3 Speed Factors affecting fault clearance time and speed of relay is as follows: i) Economic consideration ii) Selectivity iii) System stability iv) Equipment damage 3.1.4 Sensitivity Protection must be sufficiently sensitive to operate reliably under minimum fault conditions for a fault within its own zone while remaining stable under maximum load or through fault condition. -
Application Guidelines for Ground Fault Protection
Application Guidelines for Ground Fault Protection Joe Mooney and Jackie Peer Schweitzer Engineering Laboratories, Inc. Presented at the 1998 International Conference Modern Trends in the Protection Schemes of Electric Power Apparatus and Systems New Delhi, India October 28–30, 1998 Previously presented at the 52nd Annual Georgia Tech Protective Relaying Conference, May 1998 Originally presented at the 24th Annual Western Protective Relay Conference, October 1997 APPLICATION GUIDELINES FOR GROUND FAULT PROTECTION Joe Mooney, P.E., Jackie Peer Schweitzer Engineering Laboratories, Inc. INTRODUCTION Modern digital relays provide several outstanding methods for detecting ground faults. New directional elements and distance polarization methods make ground fault detection more sensitive, secure, and precise than ever. Advances in communications-aided protection further advance sensitivity, dependability, speed, and fault resistance coverage. The ground fault detection methods and the attributes of each method discussed in this paper are: • Directional Zero-Sequence Overcurrent • Directional Negative-Sequence Overcurrent • Quadrilateral Ground Distance • Mho Ground Distance Comparison of the ground fault detection methods is on the basis of sensitivity and security. The advantages and disadvantages for each method are presented and compared. Some problem areas of ground fault detection are discussed, including system nonhomogeneity, zero-sequence mutual coupling, remote infeed into high-resistance faults, and system unbalances due to in-line switching. Design and application considerations for each problem area are given to aid in setting the relay elements correctly. This paper offers a selection and setting guide for ground fault detection on noncompensated overhead power lines. The setting guide offers support in selecting the proper ground fault detection element based upon security, dependability, and sensitivity (high-resistance fault coverage). -
Upgrading Power System Protection to Improve Safety, Monitoring, Protection, and Control
Upgrading Power System Protection to Improve Safety, Monitoring, Protection, and Control Jeff Hill Georgia-Pacific Ken Behrendt Schweitzer Engineering Laboratories, Inc. Presented at the Pulp and Paper Industry Technical Conference Seattle, Washington June 22–27, 2008 Upgrading Power System Protection to Improve Safety, Monitoring, Protection, and Control Jeff Hill, Georgia-Pacific Ken Behrendt, Schweitzer Engineering Laboratories, Inc. Abstract—One large Midwestern paper mill is resolving an shown in Fig. 1 and Fig. 2, respectively. Each 5 kV bus in the arc-flash hazard (AFH) problem by installing microprocessor- power plant is supplied from two 15 kV buses. All paper mill based (μP) bus differential protection on medium-voltage and converting loads are supplied from either the 15 kV or switchgear and selectively replacing electromechanical (EM) overcurrent relays with μP relays. In addition to providing 5 kV power plant buses. Three of the power plant’s buses critical bus differential protection, the μP relays will provide utilized high-impedance bus differential relays installed during analog and digital communications for operator monitoring and switchgear upgrades within the last eight years. control via the power plant data and control system (DCS) and The generator neutral points are not grounded. Instead, a will ultimately be used as the backbone to replace an aging 15 kV zigzag grounding transformer had been installed on one hardwired load-shedding system. of the generator buses, establishing a low-impedance ground The low-impedance bus differential protection scheme was source that limits single-line-to-ground faults to 400 A. Each installed with existing current transformers (CTs), using a novel approach that only required monitoring current on two of the of the 5 kV bus source transformers is also low-impedance three phases. -
The Capacitor: Posi- Tive on One Side, Negative on the Other
TESLA COIL by George Trinkaus Third edition, originally ©1989 by George Trinkaus (ISBN 0-9709618-0-4) published by High Voltage Press in paper format High Voltage Press PO Box 1525 Portland, OR 97207 Content copyright ©2003 George Trinkaus Layout, design, and e-book creation are copyright ©2003 Good Idea Creative Services Published by Wheelock Mountain Publications, an imprint of Good Idea Creative Services Good Idea Creative Services 324 Minister Hill Road Wheelock VT 05851 www.tesla-ebooks.com i How To Use This Book Text links Click on red colored text to go to a link within the e-book. Click on blue colored text to go to an external link on the internet. The link will automatically open your browser. You must be connected to the internet to view the externally linked pages. Buttons The TOC button will take you to the table of contents. The left facing arrow will take you to the previous page. The right facing arrow will take you to the next page. ii Table Of Contents Preface . iv Tesla Free Energy . 1 How It Works. 5 How to Build It . 9 Tesla Lighting . 54 Magnifying Transmitter . 60 Tuning Notes. 66 For More Information. 69 Click on the red text or red page number to go to the page. iii Preface Invented by Nikola Tesla back in 1891, the tesla coil can boost power from a wall socket or battery to millions of high frequency volts. In this booklet, the only systematic treatment of the tesla coil for the electrical nonexpert, you’ll find a wealth of information on one of the best-kept secrets of electric technology, plus all the facts you need to build a tesla coil on any scale. -
Protection, Control, Automation, and Integration for Off-Grid Solar-Powered Microgrids in Mexico
Protection, Control, Automation, and Integration for Off-Grid Solar-Powered Microgrids in Mexico Carlos Eduardo Ortiz and José Francisco Álvarez Rada Greenergy Edson Hernández, Juan Lozada, Alejandro Carbajal, and Héctor J. Altuve Schweitzer Engineering Laboratories, Inc. Published in Wide-Area Protection and Control Systems: A Collection of Technical Papers Representing Modern Solutions, 2017 Previous revised edition released October 2013 Originally presented at the 40th Annual Western Protective Relay Conference, October 2013 1 Protection, Control, Automation, and Integration for Off-Grid Solar-Powered Microgrids in Mexico Carlos Eduardo Ortiz and José Francisco Álvarez Rada, Greenergy Edson Hernández, Juan Lozada, Alejandro Carbajal, and Héctor J. Altuve, Schweitzer Engineering Laboratories, Inc. Abstract—Comisión Federal de Electricidad (CFE), the distribution network. Each microgrid includes an integrated national Mexican electric utility, launched the White Flag protection, control, and monitoring (PCM) system. The Program (Programa Bandera Blanca) with the objective of system collects and processes data from the microgrid providing electricity to rural communities with more than 100 inhabitants. In 2012, CFE launched two projects to provide substations and sends the data to the supervisory control and electric service to two communities belonging to the Huichol data acquisition (SCADA) master of two remote CFE control indigenous group, Guásimas del Metate and Tierra Blanca del centers. The system includes local and remote controls to Picacho, which are both located in the mountains near Tepic, operate the microgrid breaker. Nayarit, Mexico. Each microgrid consists of a photovoltaic power CFE is studying the possibility of interconnecting plant, a step-up transformer bank, and a radial medium-voltage neighboring microgrids in the future to improve service distribution network. -
Electrical Control and Protection System of Geothermal Power Plants
Orkustofnun, Grensasvegur 9, Reports 2014 IS-108 Reykjavik, Iceland Number 13 ELECTRICAL CONTROL AND PROTECTION SYSTEM OF GEOTHERMAL POWER PLANTS Daniel Gorfie Beyene Ethiopian Electric Power Company P.O. Box 1233 Addis Ababa ETHIOPIA [email protected] ABSTRACT This study explores the use of electrical controls and a protection system in a geothermal power plant for smooth and reliable operation of the plant. Geothermal power is a renewable energy and is also used as a baseload for the supply of electricity in the grid. To fulfil this goal, great measures must be taken in the selection of electrical protection equipment for the different electrical components, such as the transformer and the generator, as described in the report. A geothermal power plant must also be furnished with a proper control system for controlling different components of the plant such as the turbine, the generator, the transformer, the excitation system and other related accessories so that when some abnormal condition occurs in the system, proper action can be taken. 1. INTRODUCTION Energy is one of the most fundamental elements of our universe. The significance of energy is especially vital for developing countries like Ethiopia. On-demand energy in the form of electricity and modern fuels is the lifeblood of modern civilization and is a critical factor for economic development and employment. In 2013, the total installed capacity of electrical power in Ethiopia was more than 2,200 MW, mainly from hydro power plants, with some help from wind and a small pilot geothermal power plant. Ethiopia launched a long-term geothermal exploration undertaking in 1969. -
The Impulse Design of Transformer Oil-Cellulose Structures
IEEE Transactions on Dielectrics and Electrical Insulation Vol. 13, No. 3; June 2006 477 The Impulse Design of Transformer Oil-Cellulose Structures J.K. Nelson and C. Shaw Rensselaer Polytechnic Institute. Dept. of Electrical, Computer and Systems Engineering Troy, NY 12180-3590, USA ABSTRACT Transformer oil/cellulose structures are often designed based on a cumulative stress criterion derived from experimental tests at power frequency. However, such structures must also meet stringent impulse requirements defined by a Basic Insulation Level (BIL). The industry has tried to establish an equivalence factor to permit power frequency cumulative stress methods to be used to estimate impulse withstand strength. Since the mechanisms of failure differ substantially under surge conditions, there would seem no good reason to suppose that a universal equivalence factor is appropriate. Tests are reported using a 2.3 MV generator to document impulse failure of a number of bulk, creep and hybrid structures to establish the nature of this relationship through statistical comparisons with the established 50/60 Hz methods. Factors varied from 1.94 to 3.34, depending on the configuration. The methodology is described and the results discussed in the context of the design of oil-cellulose structures, having regard to complicating factors such as waveshape and electrode covering. The study permits some speculation about impulse design under hybrid situations (i.e. failure paths involving both creep and bulk liquid). Index Terms — Insulation design, oil/cellulose structures, cumulative stress, impulse withstand. 1 BACKGROUND paths may be categorized as either “bulk” through oil volumes, “creep” along cellulose surfaces (paper or THE “cumulative stress” method is in industrial use for the pressboard) or some combination of the two. -
Designed for Service in All Parts O F the World
AUTOMATIC including T runk Main Rural designed for service Unit Private in all parts o f the world Private Branch DY dose attention to technical detail MANUAL EXCHANGES of all types the Company has maintained Its position in the forefront of Telecom CARRIER TRANSMISSION EQUIPMENT munication Engineers throughout its long experience. Its products enjoy TELEPHONE INSTRUMENTS of all types a world-wide reputation for sound TELEPHONE SWITCHING EQUIPMENT • design and technical excellence. PROTECTIVE DEVICES The Company undertakes the supply and installation of complete Auto- RELAYS matlcandManualTelephoneExchanges for Public and Private service, Auto TELEPHONE CABLES, WIRES & CORDS matic and Manual Trunk Exchanges, all types of Telephone Cables for LOADING COILS Trunk and Local Service, C arrier Transmission Equipment and Cables, MARINE RADIO EQUIPMENT Radio Equipments for Ships. SHIPS’ TELEGRAPHS & TELEPHONES CELLS & BATTERIES Dry, Fluid & Inert SIEMENS BROTHERS & CO., LIMITED ISTAtusHEPms WOOLWICH. LONDON. S.E.I8 TELEPHONE : WOOLWICH 2020 30 MAY 1947 SIXPENCE mm: «»». H k 3*ï RM »a BJS&» ¥ L*: b u i L ELECTROFLUX ‘ MAGNETIC CRACK DETECTION APPARATUS The Electroflux Universal Crack Detector will locate cracks in all directions. It is ideal for the rapid inspection of mass produced articles. Semi-automatic operation. TRAFFORD PARK ••• MANCHESTER 17. N/C70I THE ELECTRICIAN 30 M A Y 1947 1409 The Factory Manager gets asato hot w ater ! •VO'S e»V Yiot > %<>» to r i i0 o0.t& Ca° e?3 so in rfíXf tef ... • • 19 5OO VÖ1 fe<4o.Vr® •yec t o O-®” tn° î f lor VS° r&° ti» 6- / * # ie* - J / provÍ ct,at:¡A ^adj^L^ter 1,0 i.°°Ô !£* The model illustrated is just one from the w ide range o f G .E.C. -
Dissolved Gas Analysis in Transformer Oil Using Transformer Oil Gas Analyzer
APPLICATION NOTE Gas Chromatography Authors: Tracy Dini Manny Farag PerkinElmer, Inc. Shelton, CT Dissolved Gas Analysis in Transformer Oil Using Introduction Nearly 90% of the world’s population does not Transformer Oil Gas Analyzer know life without the ubiquity of electricity. It is a luxury that gets taken for granted by most people and TurboMatrix HS Sampler every day. Panic often ensues when the electricity supply is interrupted, as witnessed in Manhattan during the July 13, 2019 blackout that left over 73,000 people without electricity for several hours. While no injuries or fatalities were reported in this case, history offers many accounts of chaos and safety risks following blackouts of this magnitude, especially in a major metropolitan city. To prevent such interruptions in electrical power, transformers must be properly maintained and monitored. An effective means of conducting routine monitoring towards this goal of reduced blackouts includes the analysis of oil insulting the transformers. Acting as both an insulator and coolant, insulating oil in electrical transformers is expected to meet demanding chemical, electrical, and physical properties to ensure proper functioning of the transformer and its internal components. The American Society for Testing and Materials (ASTM) offers reference test methods as guidance for performing required routine analysis on the oil. As the insulating oil is subjected to high intensity thermal and electrical conditions, decomposition occurs over time and forms gases that dissolve into the oil. ASTM D3612 Method C is a standard test method using a headspace sampler to extract these dissolved gases for GC analysis. Dissolved gas analysis (DGA) is performed on the oil to identify the gases and their concentrations. -
A Novel Busbar Protection Based on the Average Product of Fault Components
energies Article A Novel Busbar Protection Based on the Average Product of Fault Components Guibin Zou 1,* ID , Shenglan Song 2, Shuo Zhang 1 ID , Yuzhi Li 2 and Houlei Gao 1 1 Key Laboratory of Power System Intelligent Dispatch and Control of Ministry of Education, Shandong University, Jinan 250000, China; [email protected] (S.Z.); [email protected] (H.G.) 2 State Grid Weifang Power Supply Company, Weifang 261000, China; [email protected] (S.S.); [email protected] (Y.L.) * Correspondence: [email protected]; Tel.: +86-135-0541-6354 Received: 13 March 2018; Accepted: 1 May 2018; Published: 3 May 2018 Abstract: This paper proposes an original busbar protection method, based on the characteristics of the fault components. The method firstly extracts the fault components of the current and voltage after the occurrence of a fault, secondly it uses a novel phase-mode transformation array to obtain the aerial mode components, and lastly, it obtains the sign of the average product of the aerial mode voltage and current. For a fault on the busbar, the average products that are detected on all of the lines that are linked to the faulted busbar are all positive within a specific duration of the post-fault. However, for a fault at any one of these lines, the average product that has been detected on the faulted line is negative, while those on the non-faulted lines are positive. On the basis of the characteristic difference that is mentioned above, the identification criterion of the fault direction is established. Through comparing the fault directions on all of the lines, the busbar protection can quickly discriminate between an internal fault and an external fault. -
Power System Selectivity: the Basics of Protective Coordination by Gary H
Power System Selectivity: The Basics Of Protective Coordination By Gary H. Fox, PE, GE Specification Engineer The intent of this article is to provide a brief primer about the essence of coordinating the basic protective components of the electrical power system, including circuit breakers, fuses and protective relays, and to enable the reader to review a plot of time current curves and evaluate several key concerns: • How well do the devices work with each other? • Will a minimal amount of the power system be lost by a fault? • How well are the power system components protected? • Could the chosen ratings and settings cause nuisance trips? The Objectives of Protection Determining the protective devices for a power system The Intended Result and their settings usually puts two competing goals against each other. On the one hand you want the system available for use 100% of the time. To this extreme end all power outages, whether due to maintenance or failures, are to be avoided. You would want the protective device ratings and settings to be Isc as high as possible, and these settings would be further desensitized by a considerable time delay, so Page 2 that extra time is allowed before the circuit is tripped. Fig. 1 An example of short circuit On the other hand there is a concern for the protection flow in a radial system of the load and system components. The degree of damage from a short circuit fault is proportional to the amount of time that fault persists and the square of the current that flows. -
Power System Protective Relaying: Basic Concepts, Industrial-Grade Devices, and Communication Mechanisms Internal Report
Power System Protective Relaying: basic concepts, industrial-grade devices, and communication mechanisms Internal Report Report # Smarts-Lab-2011-003 July 2011 Principal Investigators: Rujiroj Leelaruji Dr. Luigi Vanfretti Affiliation: KTH Royal Institute of Technology Electric Power Systems Department KTH • Electric Power Systems Division • School of Electrical Engineering • Teknikringen 33 • SE 100 44 Stockholm • Sweden Dr. Luigi Vanfretti • Tel.: +46-8 790 6625 • [email protected] • www.vanfretti.com DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITIES THIS DOCUMENT WAS PREPARED BY THE ORGANIZATION(S) NAMED BELOW AS AN ACCOUNT OF WORK SPONSORED OR COSPONSORED BY KUNGLIGA TEKNISKA HOGSKOLAN¨ (KTH) . NEITHER KTH, ANY MEMBER OF KTH, ANY COSPONSOR, THE ORGANIZATION(S) BELOW, NOR ANY PERSON ACTING ON BEHALF OF ANY OF THEM: (A) MAKES ANY WARRANTY OR REPRESENTATION WHATSOEVER, EXPRESS OR IMPLIED, (I) WITH RESPECT TO THE USE OF ANY INFORMATION, APPARATUS, METHOD, PROCESS, OR SIMILAR ITEM DISCLOSED IN THIS DOCUMENT, INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, OR (II) THAT SUCH USE DOES NOT INFRINGE ON OR INTERFERE WITH PRIVATELY OWNED RIGHTS, INCLUDING ANY PARTY’S INTELLECTUAL PROPERTY, OR (III) THAT THIS DOCUMENT IS SUITABLE TO ANY PARTICULAR USER’S CIRCUMSTANCE; OR (B) ASSUMES RESPONSIBILITY FOR ANY DAMAGES OR OTHER LIABILITY WHATSOEVER (INCLUDING ANY CONSEQUENTIAL DAMAGES, EVEN IF KTH OR ANY KTH REPRESENTATIVE HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES) RESULTING FROM YOUR SELECTION OR USE OF THIS DOCUMENT OR ANY INFORMATION, APPARATUS, METHOD, PROCESS, OR SIMILAR ITEM DISCLOSED IN THIS DOCUMENT. ORGANIZATIONS THAT PREPARED THIS DOCUMENT: KUNGLIGA TEKNISKA HOGSKOLAN¨ CITING THIS DOCUMENT Leelaruji, R., and Vanfretti, L.