21 HVAC Industry Standards
In order to read and understand an electrical diagram you need to know how different controls and loads are drawn.
22 SYMBOLS
SINGLE POLE SINGLE THROW SPST
23 SYMBOLS
SINGLE POLE SINGLE THROW NORMALLY OPEN SPST - NO
24 SYMBOLS
SINGLE POLE SINGLE THROW NORMALLY CLOSED SPST - NC
25 SYMBOLS
DOUBLE POLE SINGLE THROW DPST – 2 NO
26 SYMBOLS
SINGLE POLE DOUBLE THROW SPDT
27 SYMBOLS
DOUBLE POLE DOUBLE THROW DPDT 28 Relays or Contactors R
Normally Closed Contact R
Normally Open Contact
Relay Coil Relays
C
Contactors
Contactor Coil C 29 Relays
L2
120v M
24v
c
30 Relays
L2
Large Current
120v M
24v Small Current
c
31 Relays or Contactors THE CONTACTS OF A RELAY OR CONTACTOR ARE DRAWN IN A DE-ENERGIZED CONDITION
32 Pressure Switches
High- Pressure Switch SPST Opens on Rise (Safety Control)
Low-Pressure SPST Opens on Drop Switch (Safety Control)
33 Pressure Switches
Air Pressure SPST Closes on Drop (Operating Control) Switch
SPST Closes on Rise Fan Cycling (Operating Control) Pressure Switch
34 Pressure Switches
Differential Air Pressure Switch
SPST Closes on Rise (Differential)
Differential Refrigerant Pressure SPST Opens on Rise (Differential) Switch
35 Pressure Switches THE CONTACTS OF A SAFETY CONTROL ARE DRAWN IN THE NORMAL RUN POSITION, USUALLY CLOSED
36 Temperature Switches
SPST Closes on Drop (Operating Control) Heating Defrost Thermostat Thermostat
SPST Closes on Rise (Operating Control) Return Water Cooling Thermostat Temperature Controller
37 Temperature Switches
SPST Opens on Rise (Safety Control) Overtemperature Discharge Gas Limit Switch Thermostat
SPST Opens on Drop (Safety Control) Freeze Protection Thermostat
38 Temperature Switches
SPDT Temperature (Safety or Operating)
Low-Water Temperature Cutout Control
Klixonâ Bi-Metal Temperature Overtemperature (Safety) Cutout Control
39 Temperature Switches THE CONTACTS OF AN OPERATING CONTROL ARE DRAWN OPEN, WITH NO CALL FOR COOLING, HEATING
40 Humidity Control
SPST Humidistat Closes on Drop (Operating Control)
SPST De-Humidistat Closes on Rise (Operating Control)
41 Time Delay
Time Delay Relay Delays Closing Time Delay Relay (Mechanical/Thermal) (Electronic) (Electronic)
Time Delay Relay Time Delay Relay (Mechanical) Delays Opening (Mechanical/Thermal) (Electronic) Time Delay Relay (Thermal) 42 Time Delay
THE CONTACTS OF A TIMER ARE DRAWN IN THE READY-TO-START POSITION OR AT TIME ZERO ON A BAR CYCLE DIAGRAM
NOTE: BLACK DENOTES CLOSED CIRCUITS
43 Manual Switches
SPST Normally Open Manually Operated Push Button
SPST Normally Closed Manually Operated Momentary Push Button Push Button
SPDT Switch Single-Pole Double-Throw Switch 44 Flow Switches
Flow Switch
SPST Flow Switch Opens on Rise (Safety Control)
Sail Switch
SPST Flow Switch Closes on Rise (Safety and Operating) Thermal Dispersion
Flow Switches 45 Enthalpy Switches
Electronic Enthalpy Control
SPDT Enthalpy Control (Operating Control)
Mechanical Enthalpy Control 46 Capacitors Run Capacitor
Run Capacitor (Marked Terminal) Dual Run Capacitor
Start Start Capacitor Capacitor
47 Fuses
One Time Fuse (Fusible Link)
Fuse - Fusible Link One Time Fuse
48 Transformers
49 230 VAC
24 VAC Fused & Non Fused Secondary
COMM NF F
24 VAC
Multi Tap Primary
575 480 380 230 200 C
50 Dual Secondary Transformer
Dual Secondary With Center Tapped Transformer
51 Transformers
Secondary Volt Amps Voltage
VA RATING TOTAL AMP DRAW OF A CIRCUIT = SECONDARY VOLTAGE 75VA = = 3.1 AMPS 24V 52