Timer Relays

w Timer Relays Series ZR5 w Timer Relays Series ZR5

Page 96

w Timer Relays Series ZR4 w Timer Relays Series ZR4

w Timer Relays Series AMPARO w Timer Relays Series ZR6 Timer Relays

Page 97

Timer Relays

w Index Timer Relays Series ZR5 ...... Page 98 Timer Relays Series ZR4 ...... Page 107 Timer Relays Series AMPARO ...... Page 112 Timer Relays Series ZR6 ...... Page 116 Timer Relays

w Timer Relays Series ZR5

Page 98 ZR5E,R,ER ZR5MF ZR5B ZR5SD025

ZR5RT011 w Schrack-Info ZR5E0011 ZR5MF025 ZR5SD025 • 1 CO • Multi-function timer • 2 CO • Mode: "E" • 2 CO • Wide input voltage range • Multi-voltage 24-240 V AC/DC • Modes: "E", "R", "Ws", "Wa", "Es", "Wu" • Mode: "S" & "Bp" • In-line design • Multi-voltage 12-240 V AC/DC • Multi-voltage 12-240 V AC/DC • 17.5 mm component width • In-line design • In-line design ZR5R0011 • 35 mm component width • 35 mm component width • 1 CO ZR5RT011 ZR5B0011 • Mode: "R" • Timer function for emergency lighting • 1 CO tests • Multi-voltage 24-240 V AC/DC • Modes: " lp" & "li" • 1 CO • In-line design • Multi-voltage 12-240 V AC/DC • Integrated test • 17.5 mm component width • In-line design • Mode: "Ws" ZR5ER011 • 17.5 mm component width • 230 V AC • 1 CO ZR5B0025 • In-line design • Modes: "E" & "R" • Multi-function dual time flasher relay • 17.5 mm component width • Multi-voltage 24-240 V AC/DC with internal NOTE: • In-line design • 2 CO • The timer function must be selected in a • 17.5 mm component width • Wide input voltage range de-energised state! ZR5MF011 • Modes: "lp", "li", "ER", "EWu", "EWs", • Multi-function timer relay WsWa" & "Wt" • 1 CO • Multi-voltage 12-240 V AC/DC • Modes: "E", "R", "Ws", "Wa", "Es", "Wu" • In-line design & "Bp" • 35 mm component width • Multi-voltage 12-240 V AC/DC • In-line design • 17.5 mm component width Timer Relays w Timer Relays Series ZR5 w Overview Timer Relays ZR5 Number of contacts Number of Number of Article Voltage range E R Ws Wa Es Wu Bp lp li ER EWu EWs WsWa Wt S WsTe st and type time ranges functions ZR5E0011 1 CO 24-240 V AC / DC 7 1 X ZR5R0011 1 CO 24-240 V AC / DC 7 1 X ZR5ER011 1 CO 24-240 V AC / DC 7 2 X X ZR5MF011 1 CO 12-240 V AC / DC 7 7 X X X X X X X ZR5MF025 2 CO 12-240 V AC / DC 7 7 X X X X X X X ZR5B0011 1 CO 12-240 V AC / DC 7 2 X X ZR5B0025 2 CO 12-240 V AC / DC 7 7 X X X X X X X ZR5SD025 2 CO 12-240 V AC / DC 4 1 X Page ZR5RT011 1 CO 230 V AC 6 1 X 99 w Overview Modes Article ZR5E0011 Time relay ON delay ZR5R0011 Time relay OFF delay ZR5ER011 Time relay ON-OFF delay ZR5MF011 Multifunction time relays ZR5MF025 ZR5B0011 Pulse time relay ZR5B0025 ZR5SD025 Star-Delta relay ZR5RT011 Emergency light test relay

Functions E ON delay R OFF delay (with control contact) Ws Single shot leading edge (with control contact) Wa Single shot trailing edge (with control contact) Es ON delay (with control contact) Wu Single shot leading edge voltage controlled Bp Flasher pause first ER ON and OFF delay (with control contact) EWu ON delay and single shot leading edge voltage controlled EWs ON delay and single shot leading edge (with control contact) WsWa Single shot leading- and single shot trailing edge (with control contact) Wt Pulse sequence monitoring S Star-Delta start-up WsTest Single shot leading edge (with control contact)

ZR5B0011 lp Asymmetric flasher pause first (flashing) li Asymmetric flasher pulse first (flashing)

ZR5B0025 lp Asymmetric flasher pause first (pulsing) li Asymmetric flasher pulse first (pulsing)

Timer Relays

w Timer Relays Series ZR5 w Dimensions (mm)

Page 100

w Configuration & Functionalities w Configuration & Functions Example ZR5MF011 1 Operation display 2 Adjustable time range 50 ms to 100 h 3 Adjustable function area (E, R, Ws, Wa, Es, Wu and Bp) 4 45 mm cap dimension 5 Multi-voltage 12 or 24 V to 240 V AC / DC

w Time Ranges

ZR5E0011, ZR5R0011, ZR5ER011, ZR5MF011, ZR5SD025 ZR5RT011 ZR5MF025, ZR5B0011, ZR5B0025 Time range Adjustment range Time range Adjustment range Time range reversible between 1 s 50 ms - 1 s 10 s 500 ms - 10 s 10min, 30 min, 60 min, 10 s 500 ms - 10 s 30 s 1500 ms - 30 s 90 min, 2 h und 3 h 1 min 3 s - 1 min 1 min 3 s - 1 min 10 min 30 s - 10 min 3 min 9 s - 3 min 1 h 3 min - 1 h 10 h 30 min - 10 h 100 h 5 h - 100 h

Timer Relays w Timer Relays Series ZR5 w Overview Circuit Diagrams

Page 101

Timer Relays

w Timer Relays Series ZR5 w Overview Circuit Diagrams A ON/OFF-DELAY RELAYS A1 ON delay (E) without control contact A2 OFF delay (R) with control contact "S" A3 ON delay (E) without control contact A4 OFF delay (R) with control contact "S" B MULTIFUNCTION RELAYS OFF delay (R), Single shot leading edge (Ws), Single shot trailing edge (Wa) and B1 with control contact "S" ON delay with control input (Es) ON delay (E), Single shot leading edge voltage controlled (Wu) Page B2 without control contact and Flasher pause first (Bp) 102 B3 OFF delay (R), Single shot leading edge (Ws), Single shot trailing edge (Wa) and ON delay with control input (Es) with control contact "S" ON delay (E), Single shot leading edge voltage controlled (Wu) and B4 without control contact Flasher pause first (Bp) C FLASHING RELAYS C1 Asymmetric flasher pause first (lp) and Asymmetric flasher pulse first (li) without control contact Asymmetric flasher pause first (lp), Asymmetric flasher pulse first (li), ON delay and single shot leading edge voltage C2 controlled (EWu), Pulse sequence monitoring (Wt), ON delay and OFF delay with control contact (ER), ON delay and with control contact "S" single shot leading edge (EWs) as well as Single shot leading and single shot trailing edge (WsWa) D TIMER STAR-DELTA D1 Star-delta start up (S) without control contact EMERGENCY LIGHT TEST RELAY E Single shot leading edge (Ws) with control contact "S" E1 Direct connection of emergency lights (I < 16 A) E2 Switching emergency lights with contactor (I > 16 A) E3 Emergency lights with integrated rechargeable power cells Timer Relays w Timer Relays Series ZR5 w Modes

Page 103

w Overview Modes Article E R Ws Wa Es Wu Bp lp li ER EWu EWs WsWa W t S WsTest ZR5E0011 X ZR5R0011 X ZR5ER011 X X ZR5MF011 X X X X X X X ZR5MF025 X X X X X X X ZR5B0011 X X ZR5B0025 X X X X X X X ZR5SD025 X ZR5RT011 X w Detailed Description of Modes (Part 1) ZR5B0011 ZR5B0025 Asymmetric flasher pause first (flashing) Asymmetric flasher pause first (pulsing) When the supply voltage U is applied, the set interval t1 begins (green When the supply voltage U is applied, the set interval t1 begins (green LED U/t flashes slowly). After the interval t1 has expired, the output relay LED U/t flashes slowly). After the interval t1 has expired, the output relay R into on-position (yellow LED illuminated) and the set interval R switches into on-position (yellow LED illuminated) and the set interval lp lp t2 begins (green LED U/t flashes fast). After the interval t2 has expired, t2 begins (green LED U/t flashes fast). After the interval t2 has expired, the output relay switches into off-position (yellow LED not illuminated). The the output relay switches into off-position (yellow LED not illuminated). The output relay is triggered at the ratio of t1:t2 until the supply voltage is output relay is triggered at the ratio of t1:t2 until the supply voltage is interrupted. interrupted.

Asymmetric flasher pulse first (flashing) Asymmetric flasher pulse first (pulsing) When the supply voltage U is applied, the output relay R switches into When the supply voltage U is applied, the output relay R switches into on-position (yellow LED illuminated) and the set interval t1 begins (green on-position (yellow LED illuminated) and the set interval t1 begins (green LED U/t flashes slowly). After the interval t1 has expired, the output relay LED U/t flashes slowly). After the interval t1 has expired, the output relay li li switches into off-position (yellow LED not illuminated) and the set interval t2 switches into off-position (yellow LED not illuminated) and the set interval t2 begins (green LED U/t flashes fast). After the interval t2 has expired, the begins (green LED U/t flashes fast). After the interval t2 has expired, the output relay switches into on-position (yellow LED illuminated). The output output relay switches into on-position (yellow LED illuminated). The output relay is triggered at the ratio of t1:t2 until the supply voltage is interrupted. relay is triggered at the ratio of t1:t2 until the supply voltage is interrupted.

Timer Relays

w Timer Relays Series ZR5 w Detailed Description of Modes (Part 2)

ON delay ON delay and OFF delay with control contact "S" The supply voltage U must be constantly applied to the device (green LED U/t illuminated). When the control contact S is closed, the set interval t1 When the supply voltage U is applied, the set interval t begins (green LED begins (green LED U/t flashes slowly). After the interval t1 has expired, U/t flashes). After the interval t has expired (green LED U/t illuminated) the output relay R switches into on-position (yellow LED illuminated). If the E the output relay R switches into on-position (yellow LED illuminated). This ER control contact is opened, the set interval t2 begins (green LED U/t flashes status remains until the supply voltage is interrupted. If the supply voltage is fast). After the interval t2 has expired, the output relay switches into off- interrupted before the expiry of the interval t, the interval already expired is position (yellow LED not illuminated). If the control contact is opened before erased and is restarted when the supply voltage is next applied. the interval t1 has expired, the interval already expired is erased and is restarted with the next cycle. Page 104 OFF delay with control contact "S" ON delay and single shot leading edge, voltage controlled The supply voltage U must be constantly applied to the device (green LED When the supply voltage U is applied, the set interval t1 begins (green U/t illuminated). When the control contact S is closed, the output relay R LED U/t flashes slowly). After the interval t1 has expired, the output relay switches into on-position (yellow LED illuminated). If the control contact is R switches into on-position (yellow LED illuminated) and the set interval t2 R opened, the set interval t begins (green LED U/t flashes). After the interval EWu begins (green LED U/t flashes fast). After the interval t2 has expired, the

t has expired (green LED U/t illuminated) the output relay switches into off- output relay switches into off-position (yellow LED not illuminated). If the position (yellow LED not illuminated). If the control contact is closed again supply voltage is interrupted before the interval t1+t2 has expired, the before the interval t has expired, the interval already expired is erased and interval already expired is erased and is restarted when the supply voltage is restarted. is next applied.

Single shot leading edge with control contact "S" ON delay and single shot leading edge with control contact "S" The supply voltage U must be constantly applied to the device (green LED The supply voltage U must be constantly applied to the device (green LED U/t illuminated). When the control contact S is closed, the set interval t1 U/t illuminated). When the control contact S is closed, the output relay R begins (green LED U/t flashes slowly). After the interval t1 has expired, switches into on-position (green LED U/t illuminated) and the set interval t the output relay R switches into on-position (yellow LED illuminated) and Ws begins (green LED U/t flashes). After the interval t has expired (green LED EWs the set interval t2 begins (green LED U/t flashes fast). After the interval U/t illuminated) the output relay switches into off-position (yellow LED not t2 has expired, the output relay switches into off-position (yellow LED not illuminated). During the interval, the control contact can be operated any illuminated). During the interval, the control contact can be operated any number of times. A further cycle can only be started when the cycle run has number of times. A further cycle can only be started when the cycle run has been completed. been completed.

Single shot leading and single shot trailing edge with control contact Single shot trailing edge with control contact "S" "S" The supply voltage U must be constantly applied to the device (green LED The supply voltage U must be constantly applied to the device (green LED U/t illuminated). When the control contact S is closed, the output relay R U/t illuminated). Closing the control contact S has no influence on the switches into on-position (yellow LED illuminated) and the set interval t1 condition of the output R. When the control contact is opened, the output begins (green LED U/t flashes slowly). After the interval t1 has expired, the Wa relay switches into on-position (yellow LED illuminated) and the set interval t WsWa output relay R switches into off-position (yellow LED not illuminated). If the begins (green LED U/t flashes). After the interval t has expired (green LED control contact is opened, the output relay again switches into on-position U/t illuminated), the output relay switches into off-position (yellow LED not (yellow LED illuminated) and the set interval t2 begins (green LED U/t illuminated). During the interval, the control contact can be operated any flashes fast). After the interval t2 has expired the output relay switches into number of times. A further cycle can only be started when the cycle run has off-position (yellow LED not illuminated). During the interval, the control been completed. contact can be operated any number of times.

ON delay with control contact "S" Pulse sequence monitoring When the supply voltage U is applied, the set interval t1 begins (green The supply voltage U must be constantly applied to the device (green LED LED U/t flashes slowly) and the output relay R switches into on-position U/t illuminated). When the control contact S is closed, the set interval t (yellow LED illuminated) After the interval t1 has expired, the set interval begins (green LED U/t flashes). After the interval t has expired (green LED t2 begins (green LED U/t flashes fast). So that the output relay R remains Es Wt U/t illuminated) the output relay R switches into on-position (yellow LED into on-position, the control contact S must be closed and opened again illuminated). This status remains until the control contact is opened again. If within the set interval t2 . If this does not happen, the output relay R switches the control contact is opened before the interval t has expired, the interval into off-position (yellow LED not illuminated) and all further pulses at the already expired is erased and is restarted with the next cycle. control contact are ignored. To restart the function the supply voltage must be interrupted and reapplied.

Single shot leading edge, voltage controlled Star-delta start up When the supply voltage U is applied, the output relay R switches into When the supply voltage U is applied, the star-contact switches into on- on-position (yellow LED illuminated) and the set interval t begins (green LED position (yellow LED illuminated) and the set star-time t1 begins (green LED U/t flashes). After the interval t has expired (green LED U/t illuminated) U/t flashes). After the interval t1 has expired (green LED U/t illuminated), Wu the output relay switches into off-position (yellow LED not illuminated). This S the star-contact switches into off-position (yellow LED not illuminated) and status remains until the supply voltage is interrupted. If the supply voltage is the set transit-time t2 begins. After the interval t2 has expired, the contact interrupted before the interval t has expired, the output relay switches into for the delta-contactor switches into on-position. To restart the function, the off-position. The interval already is erased and is restarted when the supply supply voltage must be interrupted and reapplied. voltage is next applied.

Flasher pause first Single shot leading edge with control contact "S" The supply voltage U must be constantly to the device (green LED U/t illuminated). Pressing the integrated test key forces the output relay R to When the supply voltage U is applied, the set interval t begins (green LED switch into on-position (yellow LED illuminated), so the emergency lights are U/t flashes). After the interval t has expired, the output relay R switches disconnected from the mains and the set interval t begins (green LED U/t Bp into on-position (yellow LED illuminated) and the set interval t begins again. WsTest flashes). After the interval t has expired (green LED U/t illuminated), the

After the interval t has expired, the output relay switches into off-position output relay R switches into off-position (yellow LED not illuminated) and the (yellow LED not illuminated). The output relay is triggered at a ratio of 1:1 emergency lights are reconnected to the mains. During the interval, the test until the supply voltage is interrupted. key can be operated any number of times. Prolonged pressure on the test key (>2s) aborts the running test interval (green LED U/t flashes fast) and a further cycle can be started.

Timer Relays w Timer Relays Series ZR5 w Technical Data ZR5E0011 ZR5R0011 ZR5ER011 ZR5MF011 ZR5MF025 INDICATORS Green LED U/t ON Indication of supply voltage Green LED U/t flashes Indication of time period Yellow LED R ON/OFF Indication of relay outputs MECHANICAL DESIGN Housing Self-extinguishing plastic housing IP rating housing IP40 Mounting (EN 50022) DIN-rail TS 35 (VBG 4, PZ1 Terminal Shockproof terminal connection required) IP rating terminal IP20 Page Mounting position Any Tightening torque Max. 1 Nm 105 Terminal capacity 1 x 0.5 to 2.5 mm 2 with/without multicore cable end 1 x 4 mm 2 without multicore cable end 2 x 0.5 to 1.5 mm 2 with/without multicore cable end 2 x 2.5 mm 2 flexible without multicore cable end INPUT CIRCUIT Input Terminals A1(+)-A2 Supply voltage 24 - 240 V AC / DC 12 - 240 V AC/DC Tolerance 24 V...-15 % to 240 V...+10 % 12 V...-10 % to 240 V...+10% Rated consumption 4 VA (1.5 W) 6 VA (2W) Rated frequency 48 to 63 Hz Duty cycle 100 % Reset time 100 ms Residual ripple for DC 10 % Drop-out voltage > 30 % of minimum rated supply voltage Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV 2 potential free OUTPUT CIRCUIT Number of contacts and type 1 CO CO contacts Rated voltage 250 V AC Switching capacity 2000 VA (8 A / 250 V) Fusing 8 A fast acting Mechanical service life 20 x 10 6 operations Electrical service life 2 x 10 5 operations at 1000 VA resistive load Switching frequency Max. 60/min at 100 VA resistive load, (IEC 947-5-1) max. 6/min at 1000 VA resistive load Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV CONTROL INPUT Input not potential free Terminals A1-B1 Loadable NO Yes Max. line length CONTROL 10 m Trigger level (sensitivity) CONTACT Automatic adaption to supply voltage Min. control pulse length DC 50 ms, AC 100 ms ACCURACY Base accuracy ±1 % of maximum scale value Adjustment accuracy < 5 % of maximum scale value Repetition accuracy < 0.5 % or ± 5 ms Voltage influence - Temperature influence ≤ 0.01 % / °C AMBIENT CONDITIONS Ambient temperature (IEC 68-1) -25 °C to +55 °C Storage temperature -25 °C to +70 °C Transport temperature -25 °C to +70 °C Relative humidity (IEC 721-3-3 class 3K3) 15 % to 85 % Pollution degree (IEC 664-1) 2, if built in 3 Vibration resistance (IEC 68-2-6) 10 to 55 Hz, 0.35 mm Shock resistance (IEC 68-2-27) 15 g, 11 ms

Timer Relays

w Timer Relays Series ZR5

DESCRIPTION AVAILABLE ORDER NO. Tripping and Release Delay Timer single function ON-delay 24-240V AC/DC, 1CO, 8A/250V ZR5E0011 Timer single function OFF-delay 24-240V AC/DC, 1CO, 8A/250V ZR5R0011 Timer duo function ON/OFF-delay 24-240V AC/DC, 1CO, 8A/250V ZR5ER011 Multi-function Relays Timer multifunction 12-240V AC/DC, 1CO, 8A/250V ZR5MF011

Page Timer multifunction 12-240V AC/DC, 2CO, 8A/250V ZR5MF025 106 Flasher Relays Timer flashing 12-240V AC/DC, 1CO, 8A/250V ZR5B0011 Two-time multifunction 12-240V AC/DC, 2CO, 8A/250V ZR5B0025 Star-Delta Relays Timer Star-Delta 12-240V AC, 2CO, 8A ZR5SD025 Emergency Lighting Testers Emergency-light-test-relay 230V, modular version ZR5RT011

Order no. blue: on stock, usually ready for delivery on the day of order Timer Relays w Timer Relays Series ZR4, for Round 11 Pole Plug-in Socket

Page ZR4MF025-A ZR4B0025-A YMR78700 107 w Schrack-Info ZR4MF025-A • Multi-function relay • 2 CO • Modes: "E", "R", "Ws", "Wa", "Es", "Wu" & "Bp" • For 11 pole plug-in MT socket • Multi-voltage 12-240 V AC/DC • 38 mm component width • Standard front dimension 45 mm ZR4B0025-A • Flasher relay • 2 CO • Internal clock • Dual time multi-function • Zoom voltage • Modes: "lp", "li", "ER", "EWu", "EWs", WsWa" & "Wt" • For 11 pole plug-in MT socket • Multi-voltage 12-240 V AC/DC • 38 mm component width • Standard front dimension 45 mm YMR78700 • MT socket compatible with pluggable Series ZR4 timer relays w Overview ZR4 Timer Relays Number of contacts Number of Number of Article Voltage range E R Ws Wa Es Wu Bp lp li ER EWu EWs WsWa Wt and type time ranges functions ZR4MF025-A 2 CO 12 - 240 V AC / DC 7 7 X X X X X X X ZR4B0025-A 2 CO 12 - 240 V AC / DC 7 7 X X X X X X X

Timer Relays

w Timer Relays Series ZR4, for Round 11 Pole Plug-in Socket w Overview Modes Article ZR4MF025-A Pluggable multifunction relay ZR4B0025-A Pluggable pulse time relay

Functions E ON delay R OFF delay (with control contact) Page Ws Single shot leading edge (with control contact) Wa Single shot trailing edge (with control contact) 108 Es ON delay (with control contact) Wu Single shot leading edge voltage controlled Bp Flasher pause first ER ON and OFF delay (with control contact) ON delay and single shot leading edge voltage EWu controlled EWs ON delay and single shot leading edge (with control contact) WsWa Single shot leading- and single shot trailing edge (with control contact) Wt Pulse sequence monitoring lp Asymmetric flasher pause first li Asymmetric flasher pulse first

w Dimensions (mm)

w w Circuit Diagrams Overview Time Ranges

ZR4MF025-A, ZR4B0025-A Time range Adjustment range 1 s 50 ms - 1 s 10 s 500 ms - 10 s 1 min 3 s - 1 min 10 min 30 s - 10 min 1 h 3 min - 1 h 10 h 30 min - 10 h 100 h 5 h - 100 h Timer Relays w Timer Relays Series ZR4, for Round 11 Pole Plug-in Socket w Modes

Page 109

w Overview Modes Article E R Ws Wa Es Wu Bp lp li ER EWu EWs WsWa W t ZR4MF025-A X X X X X X X ZR4B0025-A X X X X X X X w Detailed Description of Modes (Part 1)

ON delay Asymmetric flasher pause first When the supply voltage U is applied, the set interval t1 begins (green When the supply voltage U is applied, the set interval t begins (green LED LED U/t flashes slowly). After the interval t1 has expired, the output relay U/t flashes). After the interval t has expired (green LED U/t illuminated) R switches into on-position (yellow LED illuminated) and the set interval E the output relay R switches into on-position (yellow LED illuminated). This lp t2 begins (green LED U/t flashes fast). After the interval t2 has expired, status remains until the supply voltage is interrupted. If the supply voltage is the output relay switches into off-position (yellow LED not illuminated). The interrupted before the expiry of the interval t, the interval already expired is output relay is triggered at the ratio of t1:t2 until the supply voltage is erased and is restarted when the supply voltage is next applied. interrupted.

OFF delay with conrol contact "S" Asymmetric flasher pulse first The supply voltage U must be constantly applied to the device (green LED When the supply voltage U is applied, the output relay R switches into U/t illuminated). When the control contact S is closed, the output relay R on-position (yellow LED illuminated) and the set interval t1 begins (green switches into on-position (yellow LED illuminated). If the control contact is LED U/t flashes slowly). After the interval t1 has expired, the output relay R opened, the set interval t begins (green LED U/t flashes). After the interval li switches into off-position (yellow LED not illuminated) and the set interval t2 t has expired (green LED U/t illuminated) the output relay switches into off- begins (green LED U/t flashes fast). After the interval t2 has expired, the position (yellow LED not illuminated). If the control contact is closed again output relay switches into on-position (yellow LED illuminated). The output before the interval t has expired, the interval already expired is erased and relay is triggered at the ratio of t1:t2 until the supply voltage is interrupted. is restarted.

Single shot leading edge with control contact "S" ON delay and OFF delay with control contact "S" The supply voltage U must be constantly applied to the device (green LED The supply voltage U must be constantly applied to the device (green LED U/t illuminated). When the control contact S is closed, the set interval t1 U/t illuminated). When the control contact S is closed, the output relay R begins (green LED U/t flashes slowly). After the interval t1 has expired, switches into on-position (green LED U/t illuminated) and the set interval t the output relay R switches into on-position (yellow LED illuminated). If the Ws begins (green LED U/t flashes). After the interval t has expired (green LED ER control contact is opened, the set interval t2 begins (green LED U/t flashes

U/t illuminated) the output relay switches into off-position (yellow LED not fast). After the interval t2 has expired, the output relay switches into off- illuminated). During the interval, the control contact can be operated any position (yellow LED not illuminated). If the control contact is opened before number of times. A further cycle can only be started when the cycle run has the interval t1 has expired, the interval already expired is erased and is been completed. restarted with the next cycle.

Timer Relays

w Timer Relays Series ZR4, for Round 11 Pole Plug-in Socket w Detailed Description of Modes (Part 2)

Single shot trailling edge with control contact "S" ON delay and single shot leading edge, voltage controlled The supply voltage U must be constantly applied to the device (green LED When the supply voltage U is applied, the set interval t1 begins (green U/t illuminated). Closing the control contact S has no influence on the LED U/t flashes slowly). After the interval t1 has expired, the output relay condition of the output R. When the control contact is opened, the output R switches into on-position (yellow LED illuminated) and the set interval t2 relay switches into on-position (yellow LED illuminated) and the set interval t Wa EWu begins (green LED U/t flashes fast). After the interval t2 has expired, the begins (green LED U/t flashes). After the interval t has expired (green LED output relay switches into off-position (yellow LED not illuminated). If the U/t illuminated), the ouput relay switches into off-position (yellow LED not supply voltage is interrupted before the interval t1+t2 has expired, the illuminated). During the interval, the control contact can be operated any interval already expired is erased and is restarted when the supply voltage number of times. A further cycle can only be started when the cycle run has is next applied. been completed. Page 110 ON delay with control contact "S" ON delay and single shot leading edge with control contact "S" The supply voltage U must be constantly applied to the device (green LED The supply voltage U must be constantly applied to the device (green LED U/t illuminated). When the control contact S is closed, the set interval t1 U/t illuminated). When the control contact S is closed, the set interval t begins (green LED U/t flashes slowly). After the interval t1 has expired, begins (green LED U/t flashes). After the interval t has expired (green LED the output relay R switches into on-position (yellow LED illuminated) and Es EWs U/t illuminated) the output relay R switches into on-position (yellow LED the set interval t2 begins (green LED U/t flashes fast). After the interval illuminated). This status remains until the control contact is opened again. If t2 has expired, the output relay switches into off-position (yellow LED not the control contact is opened before the interval t has expired, the interval illuminated). During the interval, the control contact can be operated any already expired is erased and is restarted with the next cycle. number of times. A further cycle can only be started when the cycle run has been completed.

Single shot leading and single shot trailing edge with control contact Single shot leading edge, voltage controlled "S" The supply voltage U must be constantly applied to the device (green LED When the supply voltage U is applied, the output relay R switches into U/t illuminated). When the control contact S is closed, the output relay R on-position (yellow LED illuminated) and the set interval t begins (green LED switches into on-position (yellow LED illuminated) and the set interval t1 U/t flashes). After the interval t has expired (green LED U/t illuminated) begins (green LED U/t flashes slowly). After the interval t1 has expired, the Wu WsWa the output relay switches into off-position (yellow LED not illuminated). This output relay R switches into off-position (yellow LED not illuminated). If the

status remains until the supply voltage is interrupted. If the supply voltage control contact is opened, the output relay again switches into on-position is interruted before the interval t has expired, the output relay switches into (yellow LED illuminated) and the set interval t2 begins (green LED U/t off-position. The interval already is erased and is restarted when the supply flashes fast). After the interval t2 has expired the output relay switches into voltage is next applied. off-position (yellow LED not illuminated). During the interval, the control contact can be operated any number of times.

Flasher pause first Pulse sequence monitoring When the supply voltage U is applied, the set interval t1 begins (green LED U/t flashes slowly) and the output relay R switches into on-position When the supply voltage U is applied, the set interval t begins (green LED (yellow LED illuminated) After the interval t1 has expired, the set interval U/t flashes). After the interval t has expired, the output relay R switches t2 begins (green LED U/t flashes fast). So that the output relay R remains Bp into on-position (yellow LED illuminated) and the set interval t begins again. Wt into on-position, the control contact S must be closed and opened again After the interval t has expired, the output relay switches into off-position within the set interval t2 . If this does not happen, the output relay R switches (yellow LED not illuminated). The output relay is triggered at a ratio of 1:1 into off-position (yellow LED not illuminated) and all further pulses at the until the supply voltage is interrupted. control contact are ignored. To restart the function the supply voltage must be interrupted and reapplied.

Timer Relays

w Timer Relays Series ZR4, for Round 11 Pole Plug-in Socket w Technical Data ZR4MF025-A ZR4B0025-A INDICATORS Green LED U/t ON Indication of supply voltage Green LED U/t flashes Indication of time period Indication of time period t1 Green LED U/t flashes fast - Indication of time period t2 Yellow LED R ON/OFF Indication of relay output MECHANICAL DESIGN Housing Self-extinguishing plastic housing IP rating housing IP40

Mounting (IEC 60067-1-18 a) 11-pole socket YMR78700 (VBG 4, PZ1 Terminal Shockproof terminal connection required) Page IP rating terminal IP20 Mounting position Any 111 Tightening torque Max. 1 Nm Terminal capacity 1 x 0.5 to 2.5 mm 2 with/without multicore cable end 1 x 4 mm 2 without multicore cable end 2 x 0.5 to 1.5 mm 2 with/without multicore cable end 2 x 2.5 mm 2 flexible without multicore cable end INPUT CIRCUIT Pins S2(+)-S10 / A1(+)-A2 Supply voltage 12 - 240 V AC / DC Tolerance -10 % to +10 % Rated consumption 6 VA (2 W) Reated frequency 48 to 63 Hz Duty cycle 100 % Reset time 100 ms Residual ripple for DC 10 % Drop-out voltage > 30 % of the supply voltage Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV Number of contacts OUTPUT CIRCUIT 2 potential free CO contacts and type Rated voltage 250 V AC Switching capacity 2000 VA (8A / 250 V) Fusing 8 A fast acting Mechanical service life 20 x 10 6 operations Electrical service life 2 x 10 5 operations at 1000 VA resistive load Switching frequency (IEC 60947-5-1) Max. 6 / min at 1000 VA resistive load Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV CONTROL CIRCUIT Input not potential free Pins S2-S5 Loadable Yes Max. line length 10 m Trigger level (sensitivity) Automatic adaption to supply voltage Min. control pulse length DC 50 ms, AC 100 ms ACCURACY Base accuracy ± 1 % of maximum scale value Adjusting accuracy < 5 % of maximum scale value Repition accuracy < 0.5 % or ± 5ms Temperature influence ≤ 0.01 % / °C AMBIENT CONDITIONS Ambient temperature -25 °C to +55 °C Storage temperature -25 °C to +70 °C Transport temperature -25 °C to +70 °C Relative humidity (IEC 60721-3-3 class 3K3) 15 % to 85 % Pollution degree (IEC 60664-1) 2, if built in 3

DESCRIPTION AVAILABLE ORDER NO. Multi-function Relays Timer multifunction 12-240V AC/DC, 2CO, 8A, plug-version ZR4MF025-A Flasher Relays Two-time multifunction 12-240VAC/DC, 2CO, 8A, 250V, plug-version ZR4B0025-A Sockets DIN rail mounted plug-in socket for MT3 relays and timer relays series ZR4, 11 pole, 10A (3 CO), with screw terminals, not compatible with function modules YMR78700

Order no. blue: on stock, usually ready for delivery on the day of order Timer Relays

w Timer Relays Series AMPARO

Page 112 ZRAE,R,AMF ZRAE0011 ZRAR0011 ZRAMF011 w Schrack-Info ZRAE0011 • Tripping delayed timer relay • Mode: "E" • 1 CO, 5 A • 24-48 V DC / 24-240 V AC • Time range 0.05 seconds - 10 hours • Component width 17.5 mm ZRAR0011 • Release delayed timer relay • Mode: "R" • 1 CO, 5 A • 24-48 V DC / 24-240 V AC • Time range 0.05 seconds - 10 hours • Component width 17.5 mm ZRAMF011 • Multi-function timer relay • Modes: "E", "R", "Ws", "Wu", "Wa", "Bp" & "F" • 1 CO, 5 A • 24-48 V DC / 24-240 V AC • Time range 0.05 seconds - 10 hours • Component width 17.5 mm

w Overview AMPARO Timer Relays Number of contacts Number of Number of Article Voltage range E R Ws Wu Wa Bp F and type time ranges functions ZRAE0011 1 CO 24 - 240 V AC / DC 6 1 X ZRAR0011 1 CO 24 - 240 V AC / DC 6 1 X ZRAMF011 1 CO 24 - 240 V AC / DC 6 7 X X X X X X X

Timer Relays w Timer Relays Series AMPARO w Overview Modes Article ZRAE0011 Time relay ON delay ZRAR0011 Time relay OFF delay ZRAMF011 Multifunction time relays

Functions E ON delay R OFF delay (with control contact) Page Ws Single shot leading edge (with control contact) Wu Single shot leading edge voltage controlled 113 Wa Single shot trailing edge (with control contact) Bp Flasher pause first F T-FlipFlop (Toggle) w w Dimensions (mm) Configuration & Settings

w Configuration & Functionalities 1 Fine adjustment 2 Setting of time range 3 Selection of the desired function Status indication 4 U/t : LED green...Supply voltage applied R : LED yellow…Relay is active w Overview Circuit Diagrams

Timer Relays

w Timer Relays Series AMPARO w Modes

Page 114

w Overview Modes Article E R Ws Wu Wa Bp F ZRAE0011 X ZRAR0011 X ZRAMF011 X X X X X X X

w Description of Modes E ON delay R OFF delay with control contact Ws Single shot leading edge with control contact Single shot leading edge voltage controlled Wu (function selector must be set on Ws and fixed jumper A1 - B1) #1 Function Ws with fixed jumper A1 - B1 Wa Single shot trailing edge with control contact Bp Flasher pause first F T-FlipFlop (Toggle)

Timer Relays w Timer Relays Series AMPARO w Technical Data ZRAE0011 ZRAR0011 ZRAMF011 INDICATORS Green LED U/t ON Indication of supply voltage Green LED U/t flashes Indication of time period Yellow LED R ON/OFF Relay is energized INPUT CIRCUIT Terminals A1 - A2 Supply voltage 24 - 48 V DC / 24 - 240 V~ Duty cycle 100 % Bridging time < 30 ms Reset time 100 ms Drop-out voltage > 30 % Page Power loss 1 W 115 OUTPUT CIRCUIT Number of contacts and type 1 CO Terminals 15 - 16 - 18 Type Relay Contact material AgNi Rated voltage 250 V Max. switching voltage 250 V Max. switching current 5 A Rated current 5 A / 250 V Service life Mechanical 1 x 10 6 operations Electrical 1 x 10 5 operations Switching frequency With load 6 / min Without load 1200 / min Fusing 5 A fast acting DATAS OF INSULATION Pollution degree (IEC 61812-1) 2 Overvoltage category (IEC 61812-1) II Rated insulation voltage (IEC 61812-1) Input circuit/ output circuit 300 V Rated surge voltage (IEC 61812-1) Input circuit/ output circuit 2500 V Insulation-test-voltage (IEC 61812-1) Input circuit/ output circuit 1600 V Insulation Input circuit/ output circuit Basic insulation ELECTRICAL CONNECTION Terminal Screw-terminal Terminal capacity Rated terminal capacity 2.5 mm 2 Max. terminal capacity Flexible with /without ferrule 1 x 0.25…2.5 mm 2 (23 AWG…14AWG) Flexible without sleeve 2 x 0.25…1.5 mm 2 (23 AWG…14AWG) Flexible with twin-sleeve 2 x 0.25…1.5 mm 2 (23 AWG…14AWG) Stranded without sleeve 1 x 0.25…2.5 mm 2 (23 AWG…14AWG) Length without insulation 7 mm Tightening torque Max. 0.5 Nm GENERAL DATA Ambient temperature Operation -25…+50 °C Dimensions (DIN 43880) LxHxD 17.5 x 97 x 57.9 mm Mounting (EN 60715) DIN-rail Mounting position Any IP rating Housing IP40 Terminals IP20

DESCRIPTION AVAILABLE ORDER NO. Tripping and Release Delay Timer single function ON-delay AMPARO, 24V AC/DC or 230V AC, 1 CO, 5A/230V ZRAE0011 Timer single function OFF-delay AMPARO, 24V AC/DC or 230V AC, 1 CO, 5A/230V ZRAR0011 Multi-function Relays Timer multifunction AMPARO, 24V AC/DC or 230V AC, 1 CO, 5A/230V ZRAMF011

Order no. blue: on stock, usually ready for delivery on the day of order Timer Relays

w Timer Relays Series ZR6 w Schrack-Info • 16 different modes • 16 time ranges • 2 CO • Zoom voltage 24 to 240 V AC/DC • Remote potentiometer connection • Component width 22.5 mm Page • Industrial type design 116 ZR6MF052 ZR6MF052

w w Overview Modes Dimensions (mm)

1 delayed contact (terminals 15-16-18) and 1 instantaneous contact (terminals 25-26-28) E11 ON delay R11 OFF delay with control contact "S" Es11 ON delay with control contact "S" Wu11 Single shot leading edge voltage controlled Ws11 Single shot leading edge with control contact "S" Wa11 Single shot trailing edge with control contact "S" Bi11 Flasher pulse first Bp11 Flasher pause first

2 delayed contacts E20 ON delay R20 OFF delay with control contact "S" Es20 ON delay with control contact "S" Wu20 Single shot leading edge voltage controlled Ws20 Single shot leading edge with control contact "S" Wa20 Single shot trailing edge with control contact "S" Bi20 Flasher pulse first Bp20 Flasher pause first

w w Circuit Diagram Time Ranges

Time range Adjustment range 1 s 50 ms - 1 s 3 s 150 ms - 10 s 10 s 500 ms - 10 s 30 s 1500 ms - 30 s 1 min 3 s - 1 min 3 min 9 s - 3 min 10 min 30 s - 10 min 30 min 90 s - 30 min 1 h 3 min - 1 h 3 h 9 min - 3 h 10 h 30 min - 10 h 30 h 90 min - 30 h 1 d 72 min - 1 d 3 d 216 min - 3 d 10 d 12 h - 10 d 30 d 36 h - 30 d Timer Relays w Timer Relays Series ZR6 w Modes (Part 1)

Page 117

w Detailed Description of Modes (Part 1) The internal potentiometer is deactivated when a remote potentiometer is connected! The function has to be set before connecting the relay to the supply voltage. ON delay ON delay When the supply voltage U is applied, the instantaneous contact switches When the supply voltage U is applied, the set interval t begins (green into on-position and the set interval t begins (green LED flashes). After the LED flashes). After the interval t has expired (green LED illuminated) the interval t has expired (green LED illuminated) the delayed contact switches E11 E20 output relay R switches into on-position (yellow LED illuminated). This into on-position (yellow LED illuminated). This status remains until the supply status remains until the supply voltage is interrupted. If the supply voltage is voltage is interrupted. If the supply voltage is interrupted before the expiry interrupted before the expiry of the interval t, the interval already expired is of the interval t, the interval already expired is erased and is restarted when erased and is restarted when the supply voltage is next applied. the supply voltage is next applied.

OFF delay with control contact "S" OFF delay with control contact "S" The supply voltage U must be constantly applied to the device (green LED The supply voltage U must be constantly applied to the device (green LED illuminated). When the control contact Y1-Y2 is closed, both contacts illuminated). When the control contact Y1-Y2 is closed, the output relay R switch into on-position (yellow LED illuminated). If the control contact is switches into on-position (yellow LED illuminated). If the control contact is opened, the instantaneous contact switches into off-position and the set R11 R20 opened, the set interval t begins (green LED flashes). After the interval t has interval t begins (green LED flashes). After the interval t has expired (green expired (green LED illuminated) the output relay switches into off-position LED illuminated) the delayed contact switches into off-position (yellow LED (yellow LED not illuminated). If the control contact is closed again before the not illuminated). If the control contact is closed again before the interval t interval t has expired, the interval already expired is erased and is restarted has expired, the interval already expired is erased and is restarted with the with the next cycle. next cycle.

ON delay with control contact "S" ON delay with control contact "S" The supply voltage U must be constantly applied to the device (green LED The supply voltage U must be constantly applied to the device (green LED illuminated). When the control contact Y1-Y2 is closed, the instantaneous illuminated). When the control contact Y1-Y2 is closed, the set interval contact switches into on-position and the set interval t begins (green LED t begins (green LED flashes). After the interval t has expired (green LED Es11 flashes). After the interval t has expired (green LED illuminated) the delayed Es20 illuminated) the output relay R switches into on-position (yellow LED contact switches into on-position (yellow LED illuminated). This status illuminated). This status remains until the control contact is opened again. If remains until the control contact is opened again. If the control contact is the control contact is opened before the interval t has expired, the interval opened before the interval t has expired, the interval already expired is already expired is erased and is restarted with the next cycle. erased and is restarted with the next cycle.

Single shot leading edge voltage controlled (Wu11) Single shot leading edge voltage controlled When the supply voltage U is applied, both contacts switch into on-position When the supply voltage U is applied, the output relay R switches into (yellow LED illuminated) and the set interval t begins (green LED flashes). on-position (yellow LED illuminated) and the set interval t begins (green After the interval t has expired (green LED illuminated) the delayed contact LED flashes). After the interval t has expired (green LED illuminated) the Wu11 switches into off-position (yellow LED not illuminated). This status remains Wu20 output relay switches into off-position (yellow LED not illuminated). This

until the supply voltage is interrupted. If the supply voltage is interrupted status remains until the supply voltage is interrupted. If the supply voltage is before the interval t has expired, the both contacts switch into off-position. interrupted before the interval t has expired, the output relay switches into The interval already expired is erased and is restarted when the supply off-position. The interval already expired is erased and is restarted when the voltage is next applied. supply voltage is next applied.

Timer Relays

w Timer Relays Series ZR6 w Modes (Part 2)

Page 118

w Detailed Description of Modes (Part 2) The internal potentiometer is deactivated when a remote potentiometer is connected! The function has to be set before connecting the relay to the supply voltage. Single shot leading edge with control contact "S" Single shot leading edge with control contact "S" The supply voltage U must be constantly applied to the device (green LED The supply voltage U must be constantly applied to the device (green LED illuminated). When the control contact Y1-Y2 is closed, both contacts illuminated). When the control contact Y1-Y2 is closed, the output relay switch into on-position (yellow LED illuminated) and the set interval t begins R switches into on-position (yellow LED illuminated) and the set interval (green LED flashes). After the interval t has expired (green LED illuminated) Ws11 Ws20 t begins (green LED flashes). After the interval t has expired (green LED the delayed contact switches into off-position (yellow LED not illuminated). illuminated) the output relay switches into off-position (yellow LED not The instantaneous contact remains in on-position, until the control illuminated). During the interval, the control contact can be operated any contact is opened again. During the interval, the control contact (and the number of times. A further cycle can only be started when the cycle run has instantaneous contact) can be operated any number of times. A further been completed. cycle can only be started when the cycle run has been completed.

Single shot trailing edge with control contact "S" Single shot trailing edge with control contact "S" The supply voltage U must be constantly applied to the device (green LED The supply voltage U must be constantly applied to the device (green LED illuminated). When the control contact Y1-Y2 is closed the instantaneous illuminated). Closing the control contact Y1-Y2 has no influence on the contact switches into on-position. When the control contact is opened, condition of the output relay R. When the control contact is opened, the the instantaneous contact switches into off-position, the delayed contact output relay switches into on-position (yellow LED illuminated) and the set Wa11 switches into on-position (yellow LED illuminated) and the set interval t Wa20 interval t begins (green LED flashes). After the interval t has expired (green begins (green LED flashes). After the interval t has expired (green LED LED illuminated), the output relay switches into off-position (yellow LED not illuminated), the delayed contact switches into off-position (yellow LED not illuminated). During the interval, the control contact can be operated any illuminated). During the interval, the control contact (and the instantaneous number of times. A further cycle can only be started when the cycle run has contact) can be operated any number of times. A further cycle can only be been completed. started when the cycle run has been completed.

Flasher pulse first Flasher pulse first When the supply voltage U is applied, the instantaneous contact and the When the supply voltage U is applied, the output relay R switches into delayed contact switch into on-position (yellow LED illuminated) and the on-position (yellow LED illuminated) and the set interval t begins (green Bi11 set interval t begins (green LED flashes). After the interval t has expired, the Bi20 LED flashes). After the interval t has expired, the output relay switches into

delayed contact switches into off-position (yellow LED not illuminated) and off-position (yellow LED not illuminated) and the set interval t begins again. the set interval t begins again. The delayed contact is triggered at a ratio of The output relay is triggered at a ratio of 1:1 until the supply voltage is 1:1 until the supply voltage is interrupted. interrupted.

Flasher pause first Flasher pause first When the supply voltage U is applied, the instantaneous contact switches When the supply voltage U is applied, the set interval t begins (green LED into on-position and the set interval t begins (green LED flashes). After the flashes). After the interval t has expired, the output relay R switches into on- interval t has expired, the delayed contact switches into on-position (yellow Bp11 Bp20 position (yellow LED illuminated) and the set interval t begins again. After LED illuminated) and the set interval t begins again. After the interval t the interval t has expired, the output relay switches into off-position (yellow has expired, the delayed contact switches into off-position (yellow LED LED not illuminated). The output relay is triggered at a ratio of 1:1 until the not illuminated). The delayed contact is triggered at a ratio of 1:1 until the supply voltage is interrupted. supply voltage is interrupted.

Timer Relays w Timer Relays Series ZR6 w Technical Data ZR6MF052 INDICATORS Green LED U/t ON Indication of supply voltage Green LED U/t flashes Indication of time period Yellow LED R ON/OFF Indication of relay output MECHANICAL DESIGN Housing Self-extinguishing plastic housing IP rating housing IP40 Mounting (EN 60715) DIN-rail TS 35 Terminal (VBG 4, PZ1 required) Shockproof terminal connection IP rating terminal IP20 Mounting position Any Tightening torque Max. 1 Nm Page Terminal capacity 1 x 0.5 to 2.5 mm 2 with/without multicore cable end 1 x 4 mm 2 without multicore cable end 119 2 x 0.5 to 1.5 mm 2 with/without multicore cable end 2 x 2.5 mm 2 flexible without multicore cable end INPUT CIRCUIT Input Terminals A1-A2 (galvanically separated) Supply voltage AC/DC 24 V to 240 V~ Tolerance 24 to 240 V DC -20 % to +25 % 24 to 240 V AC -15 % to +10 % Rated frequency 48 to 400 Hz 24 to 240 V~ 16 to 48 Hz 48 to 240 V~ Rated consumption 2.5 VA (1 W) Duration of operation 100 % Reset time 500 ms Wave form For AC Sinus Residual ripple For DC 10 % Drop-out voltage > 15% of the supply voltage Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV OUTPUT CIRCUIT Number of contacts and type 2 potential free CO contacts Rated voltage 250 V AC Switching capacity (distance < 5 mm) 750 VA (3 A / 250 V~) (distance > 5 mm) 1250 VA (5A / 250 V~) Fusing 5 A fast acting Mechanical service life 20 x 10 6 operations Electrical service life 2 x 10 5 operations at 1000VA resistive load Switching capacity Max. 60 / min at 100 VA resistive load, (IEC 60947-5-1) Max. 6 / min at 1000 VA resistive load Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV CONTROL CONTACT Activation Bridge Y1-Y2 Potential free Yes, basic isolation against input and output circuit Loadable No Control voltage Max. 5 V Short circuit current Max. 1 mA Line length Max. 10 m Control pulse length Min. 50 ms The internal potentiometer is de-activated when a remote REMOTE POTENTIOMETER (not included) potentiometer is connected! Connections 1 M ȍ potentiometer, terminals Z1-Y2 Line type Twisted pair Control voltage Max. 5 V Short circuit current Max. µA range Line length Max. 5 m ± 1 % (of maximum scale value) using 1 M remote ACCURACY Base accuracy ȍ potentiometer Frequency response - < 5 % (of maximum scale value) using 1 M remote Adjustment accuracy ȍ potentiometer Repetition accuracy < 0.5 % or ± 5 ms Temperature influence ≤ 0,01 % / °C AMBIENT CONDITIONS Ambient temperature (IEC 60068-1) -25 °C to +55 °C (UL 508) -25 °C to +40 °C Storage temperature -25 °C to +70 °C Transport temperature -25 °C to +70 °C Relative humidity (IEC 60721-3-3 class 3K3) 15 % to 85 % Pollution degree (IEC 60664-1) 3 Vibration resistance (IEC 60068-2-6) 10 to 55 Hz, 0.35 mm Shock resistance (IEC 60068-2-27) 15 g, 11 ms *The potentiometer is used for remote setting of the time. Here, the internal potentiometer (knob for fine adjustment of the time) is automatically disabled. The nominal value of the potentiometer is 1 Mȍ. At a value approximately > 1.6 Mȍ at this input the time fine-tuning is again determined by the internal potentiometer.

DESCRIPTION AVAILABLE ORDER NO.

Multi-function Relays Timer multifunction 12-240V AC/DC, 2CO, 8A/250V ZR6MF052

Order no. blue: on stock, usually ready for delivery on the day of order Measuring and Monitoring Relays

w Measuring and Monitoring Relays Series UR5 w Measuring and Monitoring Relays Series AMPARO

Page 120

w Measuring and Monitoring Relays Series UR6 w Relay Module

w Summary Alarm Indicators w Diode Combination DBS Measuring and Monitoring Relays

Page 121

Measuring and Monitoring Relays

w Index Measuring and Monitoring Relays Series UR5 ...... Page 122 Measuring and Monitoring Relays Series AMPARO ...... Page 132 Measuring and Monitoring Relays Series UR6 ...... Page 137 Relay Module ...... Page 150 Summary Alarm Indicators ...... Page 152 Diode Combination DBS ...... Page 154 Measuring and Monitoring Relays

w Measuring and Monitoring Relays Series UR5

UR5U UR5I, UR5P UR5R1021 UR5L1021 w Schrack-Info UR5U1011 UR5P3011 • Voltage monitoring for AC and DC in 1-phase networks • Phase sequence, phase failure and phase imbalance monitoring • Undervoltage monitoring • 1 floating CO (output relay) Page • 1 CO • Component width 17.5 mm 122 • Component width 17.5 mm • In-line design • In-line design UR5R1021 UR5U3011 • Tripping unit for motor winding temperature monitoring with or without short-circuit monitoring of the circuit (selectable • 3-phase voltage monitoring with terminal bridges) • Undervoltage monitoring • Optional reading of a temperature sensor • Supply voltage = measured voltage • Test functionality with integrated Reset switch • 1 CO • Max. rated insulation voltage sensor circuit up to 690 V • Component width 17.5 mm • 1 CO • In-line design • Component width 35 mm UR5U3N11 • In-line design • 3-phase undervoltage monitoring UR5L1021 • Fixed switching threshold US and fixed hysteresis • Filling level monitoring of conductive liquids • 1 CO • Multiple modes • Component width 17.5 mm • Safe disconnection of measuring circuits • In-line design • 1 CO UR5I1011 • Component width 35 mm • AC monitoring in 1-phase networks • In-line design • 1 CO • Component width 17.5 mm • In-line design Measuring and Monitoring Relays w Measuring and Monitoring Relays Series UR5 w Overview Modes

Article number Functions AC/DC under voltage monitoring in 1-phase mains with adjustable UR5U1011 threshold and hysteresis. UNDER = Under voltage monitoring Undervoltage monitoring in 3-phase mains (each phase against UR5U3011 the neutral wire) with fixed or adjustable threshold voltage US and fixed hysteresis. Undervoltage monitoring in 3-phase mains (each phase against the UR5U3N11 neutral wire) with fixed threshold voltage US and fixed hysteresis. AC current monitoring in 1-phase mains with adjustable threshold and UR5I1011 fixed hysteresis. Monitoring of phase sequence, phase failure and asymmetry UR5P3011 with adjustable asymmetry, connection of neutral wire optional. Temperature monitoring of the motor winding (max. 6 PTC) with fault latch for temperature sensors in accordance with DIN 44081, short UR5R1021 circuit monitoring of the thermistor line (selectable by means of terminals), integrated test/reset key. Level monitoring of conductive liquid, timing for tripping delay and turn-off delay separately adjustable and the following functions (selectable UR5L1021 by means of rotary switch): Page Pump up = Pump up or minimum monitoring Pump down = Pump down or maximum monitoring 123 w Dimensions (mm)

Measuring and Monitoring Relays

w Measuring and Monitoring Relays Series UR5 w Time Ranges Article number Adjustment range UR5U1011 Tripping delay (delay): - UR5U3011 Tripping delay: fixed approx. 200 ms Tripping delay: fixed approx. 200 ms UR5U3N11 Threshold Us: (L - N) fixed, 195.5 V (L - N) UR5I1011 Tripping delay (delay): - UR5P3011 Tripping delay: fixed approx. 100 ms Start-up suppression time (start): - UR5R1021 Tripping delay (delay): - Tripping delay (delay ON): 0.5 to 10 s UR5L1021 Turn-off delay (delay OFF): 0.5 to 10 s

w Circuit Diagrams

Page 124

w Circuit Diagrams A Monitoring temperature sensors B Monitoring thermal contact C Reset D Probe max. E Probe min. F Mass probe

Measuring and Monitoring Relays w Measuring and Monitoring Relays Series UR5 w Modes

Page 125

Measuring and Monitoring Relays

w Measuring and Monitoring Relays Series UR5 w Detailed Description of Modes (Part 1)

The supply voltage U must be constantly applied to the device (green LED illuminated). The output relay R switches into on-position (yellow LED UR5U1011 illuminated) when the measured voltage U exceeds the value adjusted at the Us regulator. The output relay R switches into off-position (yellow LED not illuminated) when the measured value for the voltage falls below the set value by more than the fixed hysteresis.

Under voltage monitoring for 3-phase AC mains with variable threshold voltage Us and fixed hysteresis. All measuring inputs (L1, L2 and L3) must be connected to phase voltage. If single or 2-phase monitoring is required, unused input terminals (L) must be connected to mains voltage to have proper L-N voltage on the terminals L1 , L2 and L3 . A phase failure can not be detected, if the reverse voltage coming from the load exceeds the threshold US relay. Test function (optional) UR5U3011 The test function enables a manually disconnection of the output relay. Under voltage monitoring The output relay R switches into on-position (yellow LED illuminated), when the measuring voltage of all connected phases exceeds the fixed threshold US by more than the fixed hysteresis H. When the voltage of one of the connected phases (L1, L2 or L3) falls below the fixed threshold, the output relay R switches into off-position again (yellow LED not illuminated).

Under voltage monitoring for 3-phase AC mains with fixed threshold voltage US and fixed hysteresis. All measuring inputs (L1, L2 and L3) must be connected to phase voltage. If single or 2-phase monitoringis required, unused input terminals (L) must be connected to mains voltage to have proper L-N voltage on the terminals L1 , L2 and L3 . A phase failure can not be detected, if the reverse voltage coming from the load exceeds the threshold US relay. Test function (optional) Page UR5U3N11 The test function enables a manually disconnection of the output relay. Under voltage monitoring 126 The output relay R switches into on-position (yellow LED illuminated), when the measuring voltage of all connected phases exceeds the fixed threshold US by more than the fixed hysteresis H. When the voltage of one of the connected phases (L1, L2 or L3) falls below the fixed threshold, the output relay R switches into off-position again (yellow LED not illuminated).

The supply voltage U must be constantly applied to the device (green LED illuminated). The output relay R switches into on-position (yellow LED illuminated) when the UR5I1011 measured current exceeds the value adjusted at the Is regulator. The output relay R switches into off-position (yellow LED not illuminated) when the measured value for the current falls below the set value by more than the fixed hysteresis.

Phase sequence monitoring When all the phases are connected in the correct sequence and the measured asymmetry is less than the fixed value, the output relay switches A into on-position (yellow LED illuminated). When the phase sequence changes, the output relay switches into off-position (yellow LED not illuminated). UR5P3011 Phase failure monitoring B The output relay R switches into off-position (yellow LED not illuminated), when one of the three phases fails. Asymmetry monitoring C The output relay R switches into off-position (yellow LED not illuminated), when the asymmetry exceeds the value set at the ASYM-regulator. Reverse voltages of a consumer (e.g. a motor which continues to run on two phases only) do not effect the disconnection.

Temperature monitoring of the motor winding with fault latch If the supply voltage U is applied (green LED illuminated) and the cumulative resistance of the PTC-circuit is less than 3.6kȍ (standard temperature of the motor), the output relay switches into on-position.

Pressing the test/reset key under this conditions, forces the output relay to switch into off-position. It remains in state as long as the test/reset key is pressed and thus the switching function can be checked in case of fault. The test function is not effective by using an external reset key.

When the cumulative resistance of the PTC-circuit exceeds 3.6k ȍ (at least one of the PTCs has reached the cut-off temperature), the output relay switches into off-position (red LED illuminated). UR5R1021 The output relay R switches into on-position again (red LED not illuminated), if the cumulative resistance drops below 1.65k ȍ by cooling down of the PTC and either a reset key (internal or external) was pressed or the supply voltage was disconnected and reapplied. D Application of an external reset D1 External reset E Application of internal test/reset key E1 Test/Reset #1 LED Failure #2 PTC (Positive Temperature Coefficient)

Measuring and Monitoring Relays w Measuring and Monitoring Relays Series UR5 w Modes

Page 127 Measuring and Monitoring Relays

w Measuring and Monitoring Relays Series UR5 w Detailed Description of Modes (Part 2)

Note Use cables with low capacity for wiring the probes especially with extended wiring length! Following processes are suggested for the adjustment: • The existent time delay should be to minimum (0.5s). • The function selector switch must be in position pump down. • Turn the sensitivity controller slowly clockwise from "min." to "max." until the relays switches into on-position (probes must be in dipped state). • The moistened probes should be taken out of the liquid to control if the relays switches into off-position. If the relays doesn't switch into off-position, turn the sensitivity controller slightly back to "min." (counter clockwise). • Set the existent time delay to desired value to fade out a short term moisten the probes by waves in the liquid. • Set the function selector switch to desired position (either pump up or pump down).

Pump up Connection of the probe rods E1 , E2 and E3 . Alternatively the electrically conducting container can be connected in lieu of the test probe E3 . When the F air-fluid level falls below the minimum probe E2 the set interval of tripping delay (Delay ON) begins. After the expiration of the interval, the output relays R switches into on-position (yellow LED illuminated). When the air-fluid level again rises above the maximum probe E1 , the set interval of turn-off delay (Delay OFF) begins. After the expiration of the interval the output relays R switches into off-position (yellow LED not illuminated). Pump down Connection of the probe rods E1 , E2 and E3 . Alternatively the electrically conducting container can be connected in lieu of the test probe E3 . When the UR5L1021 G maximum probe E1 gets moistened the set interval of tripping delay (Delay ON) begins. After the expiration of the interval the output relays R switches Page into on-position (yellow LED illuminated). When the air-fluid level falls below the minimum probe E2 , the set interval of turn-off delay (Delay OFF) begins. 128 After the expiration of the interval, the output relays R switches into off-position (yellow LED not illuminated). Minimum monitoring (Pump up) Connection the probe rods E2 and E3 (bridge E1-E3). Alternatively the electrically conducting container can be connected in lieu of the test probe E3 . H When the air-fluid level falls below the probe E2 the set interval of tripping delay (Delay ON) begins. After the expiration of the interval, the output relays R switches into on-position (yellow LED illuminated). When the air-fluid level again rises above the probe E2 , the set interval of turn-off delay (Delay OFF) begins. After the expiration of the interval the output relays R switches into off-position (yellow LED not illuminated). Maximum monitoring (Pump down) Connection of probe rods E2 and E3 (bridge E1-E3). Alternatively the electrically conducting container can be connected in lieu of the test probe E3 . I When the probe E2 gets moistened the set interval of tripping delay (Delay ON) begins. After the expiration of the interval the output relays R switches into on-position (yellow LED illuminated). When the air-fluid level sinks below the probe E2 , the set interval of turn-off delay (Delay OFF) begins. After the expiration of the interval the output relays R switches into off-position (yellow LED not illuminated). #3 Level #4 Probe E1 #5 Probe E2 #6 Probe E3 #7 Delay ON #8 Delay OFF

Measuring and Monitoring Relays w Measuring and Monitoring Relays Series UR5 w Technical Data (Part 1) UR5U1011 UR5U3011 UR5U3N11 UR5I1011 Indication of Indication of INDICATORS Green LED ON/OFF - - supply voltage supply voltage Indication of Green LED L1 ON/OFF - supply voltage - - L1 - N Indication of Green LED L2 ON/OFF - supply voltage - - L2 - N Indication of Green LED L3 ON/OFF - supply voltage - - L3 - N Yellow LED ON/OFF Indication of relay output MECHANICAL DESIGN Housing Self-extinguishing plastic housing Degree of protection housing IP40 Mounting (EN 60715) DIN-rail TS 35 (VBG 4, PZ1 Terminal Shockproof terminal connection required) Degree of protection terminal IP20 Mounting position Any Page Tightening torque Max. 1 Nm 2 129 Terminal capacity 1 x 0.5 to 2.5 mm with/without multicore cable end 1 x 4 mm 2 without multicore cable end 2 x 0.5 to 1.5 mm 2 with/without multicore cable end 2 x 2.5 mm 2 flexible without multicore cable end INPUT CIRCUIT Supply voltage Measuring voltage 24 V AC / DC, 230 V~ Rated voltage U 3(N) 230 / 400 V~ N 230 V~ Terminals 230 V~ E - F3 N - L1 - L2 - L3 Li - N E - F2 24 V~ (distance > 5 mm) 24 V DC E - F1(+) -25 % to +20 % -30 % to +10 % -30 % to +15 % -15 % to +15 % Tolerance of UN of UN of UN of UN 10 VA Rated consumption 230 V~ 5 VA (0.6 W) 5 VA (0.6 W) 5 VA (0.8 W) (0.6 W) 1.3 VA 24 V~ 8 VA (0.8 W) (0.8 W) 24 V DC 0.6 W Rated frequency AC 48 to 63 Hz Duration of operation 100 % Reset time 500 ms Wave form AC / DC Sinus - Sinus Hold-up time - > 60 % of > 20% of Determined by undervoltage detection Drop-out voltage supply supply (see measured circuit) voltage voltage Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV OUTPUT CIRCUIT Number of contacts and type 1 potential free CO Rated voltage 250 V~ Switching capacity 1250 VA (5 A / 250 V~) Fusing 5 A fast acting Mechanical service life 20 x 10 6 operations Electrical service life 2 x 10 5 operations at 1000VA resistive load Switching capacity (IEC 60947-5-1) Max. 6 / min at 1000 VA resistive load Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV AC or DC Sinus, MEASURING VOLTAGE Measuring variable AC Sinus, 48 to 63Hz 48 to 63 Hz Measuring input Supply voltage 160 - 240 V~ Supply voltage 5A AC Terminals 230 V~ E - F3 N - L1 - L2 - L3 Li, Lk 24 V~ E - F2 * 24 V DC E - F1(+) 7 A (ex 5 A: Determined by tolerance specified for Overload capacity 120 % of U distance N supply voltage > 5 mm!) Starting current 1 s 40 A - 3 s 20 A Input resistance - 10 m ȍ

Switching threshold Us 80 - 120 % 160 - 240 V fix, 195.5 V (L - N) 10 - 100 % of I N Hysteresis H Fixed, 5 % Approx. 5 % Fixed, 10 % Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV

Measuring and Monitoring Relays

w Measuring and Monitoring Relays Series UR5 w Technical Data (Part 2) UR5U1011 UR5U3011 UR5U3N11 UR5I1011 ACCURACY Base accuracy < 5 % of rated value ± 5 % of rated ± 5 % of rated Adjustment accuracy - value value Repetition accuracy < 2 % of rated value Voltage influence - Temperature influence ≤ 0.05 % / °C AMBIENT CONDITIONS Ambient temperature (IEC 60068-1) -25 °C to +55 °C Storage temperature -25 °C to +70 °C Transport temperature -25 °C to +70 °C (IEC 60721-3-3 Relative humidity 15 % to 85 % class 3K3) Pollution degree (IEC 60664-1) 2 2, if built in 3 10 to 55 Hz, 0.35 10 to 55 Hz, 0.35 Vibration resistance (IEC 68-2-6) - mm mm Shock resistance (IEC 68-2-27) 15 g, 11 ms - 15 g, 11 ms *The distance between the devices must be greater than 5 mm !

w Page Technical Data (Part 3) 130 UR5P3011 UR5R1021 UR5L1021 INDICATORS Green LED ON/OFF Indication of supply voltage Indication of relay Yellow LED ON/OFF Indication of relay output - output Red LED ON/OFF - Indication of failure MECHANICAL DESIGN Housing Self-extinguishing plastic housing Degree of protection housing IP40 Mounting (EN 60715) DIN-rail TS 35 (VBG 4, PZ1 Terminal Shockproof terminal connection required) Degree of protection terminal IP20 Mounting position Any Tightening torque Max. 1 Nm Terminal capacity 1 x 0.5 to 2.5 mm 2 with/without multicore cable end 1 x 4 mm 2 without multicore cable end 2 x 0.5 to 1.5 mm 2 with/without multicore cable end 2 x 2.5 mm 2 flexible without multicore cable end INPUT CIRCUIT Supply voltage Measured voltage 230 V~

Rated voltage U N 3(N) 230 / 400 V~ 230 V~ Terminals N-L1-L2-L3 A1 - A2

Tolerance -30 % to +30 % of U N -15 % to +10 % of U N Rated consumption 8 VA (0.8 W) 1.3 VA (1 W) 2 VA (1 W) Rated frequency AC 48 to 63 Hz Duty cycle 100 % Reset time 500 ms 250 ms 500 ms Residual ripple for DC - 50 ms - Drop out voltage > 20 % of the supply voltage > 30 % of the supply voltage Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV 6 kV OUTPUT CIRCUIT Number of contacts and type 1 potential free CO Rated voltage 250 V~ Terminals - 11 - 12 - 14 - 1250 VA AC1 B300/P300 (IEC Switching capacity 1250 VA (5 A / 250 V~) 60947-5-1), therm. constant current 5 A Fusing 5 A fast acting Mechanical service life 15 x 10 6 operations 20 x 10 6 operations 100 x 10 3 operations at 2 x 10 5 operations at 1000 VA resistive Electrical service life 1000 VA resistive load load Switching frequency (IEC 60947-5-1) Max. 6 / min at 1000 VA resistive load Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV 6 kV

Measuring and Monitoring Relays w Measuring and Monitoring Relays Series UR5 w Technical Data (Part 4) UR5P3011 UR5R1021 UR5L1021 3 (N)~, sinus, 48 MEASURING CIRCUIT Measuring variable to 63 Hz Measuring input Supply voltage Conductive probes Terminals (N) - L1 - L2 - L3 T1 - T2 or T1 - T3 E1 - E2 - E3 Determined by Overload capacity tolerance specified for supply voltage Internal resistance < 1.5 k ȍ Response value (relay in off-position) ≥ 3.6 k ȍ Release value (relay in on-position) ≤ 1.65 k ȍ Disconnection (short circuit Yes At T1 - T2 thermistor) No At T1 - T3 Measuring voltage T1-T2 (EN 60947-8) ≤ 7.5 V at R ≤ 4 k ȍ 5 % to 25 % Asymmetry adjustable or disengageable 0.25 to 100 k (4 Sensitivity ȍ Page mS to 10 S) Sensor voltage 12 V~ 131 Sensor current Max. 7 mA Wiring distance Set value < 50 % Max. 1000 m (capacity of cable 100 nF / km) Set value 100 % Max. 100 m Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV 6 kV ±5 % of maximum ACCURACY Base accuracy ±5 % - scale value Adjustment accuracy < 5 % - Repetition accuracy < 2 % < 1 % - Voltage influence - Temperature influence ≤ 0.05 % / °C ≤ 0.15 % / °C - Connection of an CONTROL CONTACT R* Function external reset key Loadable No Max. 10 m Line length R1 - R2 (twisted pair) Control pulse length Min. 50 ms Potential free NO Reset contact, terminals R1 - R2 AMBIENT CONDITIONS Ambient temperature (IEC 60068-1) -25 °C to +55 °C Storage temperature -25 °C to +70 °C Transport temperature -25 °C to +70 °C (IEC 60721-3-3 Relative humidity 15 % to 85 % class 3K3) Pollution degree (IEC 60664-1) 2 2, if built in 3 2 *Note: The terminals R2 - T2 are internal affiliated with each other!

DESCRIPTION AVAILABLE ORDER NO. Voltage Monitoring Relays Voltage monitoring relay, 1 phase, 1CO UR5U1011 Voltage monitoring relay with adjustable voltage range 160-240V, 3-phase, 1CO UR5U3011 Voltage monitoring relay, 3 phase against N, fixed Us=195.5V, 1CO UR5U3N11 Current Monitoring Relays Current monitoring relay 1 phase, input 230V, 1CO UR5I1011 Phase Monitoring Relays Phase monitoring relay, 3 phase, 1CO UR5P3011 Thermistor Monitoring Relays Thermistor monitoring relay, 1 phase, 1CO UR5R1021 Level Monitoring Relays Level monitoring relay, 1 phase, 1CO UR5L1021

Order no. blue: on stock, usually ready for delivery on the day of order Measuring and Monitoring Relays

w Measuring and Monitoring Relays Series AMPARO

URAU, URAP URAU3011 URAU3N11 URAP3011 w Schrack-Info URAU3011 • 1- and 3-phase undervoltage monitoring with settable switching threshold • 1 CO, 5 A Page • Supply voltage 230/400 V 132 • Supply circuit = measuring circuit • Neutral conductor is required • Component width 17.5 mm URAU3N11 • 1- and 3-phase undervoltage monitoring with fixed switching threshold • 1 CO, 5 A • Supply voltage 230/400 V • Supply circuit = measuring circuit • Neutral conductor is required • Component width 17.5 mm URAP3011 • Phase sequence and phase failure monitoring • Fixed phase imbalance monitoring • Supply voltage 230/400 V • Neutral conductor is required • Component width 17.5 mm

w w Dimensions (mm) Circuit Diagrams

Measuring and Monitoring Relays w Measuring and Monitoring Relays Series AMPARO w Configuration & Functionalities

Page 133 w Configuration & Settings

URAU3011 and URAU3N11 Status indication 1 LED yellow R = Relay is active

URAP3011 Status indication LED green 2 U = Supply voltage is applied LED yellow R = Relay is active

Electrical connection Supply and measuring voltage L1-L2-L3-N 3 N~ 230 / 400 V, 50 / 60 Hz Output relay 11-12-14 AC1 5 A / 250 V

Measuring and Monitoring Relays

w Measuring and Monitoring Relays Series AMPARO w Modes

Page 134

w Modes

URAU3011 Undervoltage monitoring for 3-phase AC mains with variable threshold voltage Us and fixed hysteresis. All measuring inputs (L1, L2 and L3) must be connected to phase voltage. If single-phase monitoring is required, unused input terminals (L) must be connected to mains voltage to have proper L-N voltage on the terminals L1 , L2 and L3 . A phase failure can not be detected, if the reverse voltage coming from the load exceeds the threshold Us relay. U Undervoltage monitoring The output relay R switches into on-position (yellow LED illuminated), when the measuring voltage of all connected phases exceeds the fixed threshold Us by more than the fixed hysteresis H. When the voltage of one of the connected phases (L1, L2 or L3) falls below the fixed threshold, the output relay R switches into off-position again (yellow LED not illuminated). #1 Hysteresis

URAU3N11 Undervoltage monitoring for 3-phase AC mains with fixed threshold voltage Us (=195.5 V) and fixed hysteresis. All measuring inputs (L1, L2 and L3) must be connected to phase voltage. If single-phase monitoring is required, unused input terminals (L) must be connected to mains voltage to have proper L-N voltage on the terminals L1 , L2 and L3 . A phase failure can not be detected, if the reverse voltage coming from the load exceeds the threshold Us relay. U Undervoltage monitoring The output relay R switches into on-position (yellow LED illuminated), when the measuring voltage of all connected phases exceeds the fixed threshold Us by more than the fixed hysteresis H. When the voltage of one of the connected phases (L1, L2 or L3) falls below the fixed threshold, the output relay R switches into off-position again (yellow LED not illuminated). #1 Hysteresis

URAP3011 Monitoring of phase sequence When all the phases are connected in the correct sequence and the measured asymmetry PS is less than the fixed value, the output relay R switches into on-position. When the phase sequence changes, the output relay R switches into off-position. Phase failure monitoring PL The output relay R switches into off-position, when one of the three phases fails.

Measuring and Monitoring Relays w Measuring and Monitoring Relays Series AMPARO w Technical Data URAU3011 URAU3N11 URAP3011 INPUT CIRCUIT Terminals L1 - L2 - L3 - N Supply voltage 230 / 400 V~

Tolerance -30 % to +15 % of U N Rated frequency 50 / 60 Hz Duty cycle 100 % Bridging time 10 ms Reset time 500 ms According to Drop-out voltage < 30 % switching threshold < 30 %

0.85 of UN Power loss 0.8 W MEASURING CIRCUIT Terminals L1 - L2 - L3 - N Measure Voltage 3-phase Measurement methods Rectified value Phase sequence, Monitoring functions Undervoltage Undervoltage phase failure, asymmetry Measuring range U N=230 / 400 V~ Page Overload See tolerances of the supply voltage Thresholds Max. - - - 135

Min. 85 % of U N 85 % of U N - Adjustable Yes No No Asymmetry - - Fixed, 30 % Hysteresis 5 % - TIME CIRCLES ON delay Fixed Approx. 400 ms OFF delay < 250 ms Indication of INDICATION Supply voltage Green LED U ON - supply voltage Relay status Yellow LED R ON Relay is energized OUTPUT CIRCUIT Number of contacts and type 1 CO Terminals 11 - 12 - 14 Type Relay Contact material AgNi Rated voltage 250 V Max. switching voltage 250 V Max. switching current 5 A Rated current 5 A / 250 V Lifetime Mechanical 1 x 10 6 operations Electrical (AC - 1) 1 x 10 5 operations Switching frequency With load 6 / min Without load 300 / min Fusing 5 A fast acting ACCURACY Basic accuracy < 5 % Setting accuracy - Repeatability < 2 % Influence of temperature < 0.05 % / °C STANDARDS Product standards EN 61010-2-201:2013 Immunity EN 61326-1 Basic electromagnetic environment Emission EN 61326-1 Class B DATAS OF INSULATION accord. to Pollution degree 2 IEC 61010-2-201 Overvoltage category II Rated insulation voltage Input circuit/ output circuit 300 V Rated surge voltage Input circuit/ output circuit 2500 V Insulation test voltage Input circuit/ output circuit 1500 V Insulation Input circuit/ output circuit Basic insulation ELECTRICAL CONNECTION Terminal Screw-terminal Rated terminal capacity 2.5 mm 2 Max. terminal capacity Flexible with/without ferrule 1 x 0.25…2.5 mm 2 (23 AWG…14AWG) Flexible without sleeve 2 x 0.25…1.5 mm 2 (23 AWG…14AWG) Flexible with twin-sleeve 2 x 0.25…1.5 mm 2 (23 AWG…14AWG) Stranded without sleeve 1 x 0.25…2.5 mm 2 (23 AWG…14AWG) Length without insulation 7 mm Tightening torque Max. 0.5 Nm GENERAL DATA Ambient temperature Operation -25…+50 °C Dimensions (DIN LxHxD 17.5 x 97 x 57.9 mm 43880) Mounting (EN 60715) DIN-rail Mounting position Any Degree of protection Housing IP40 Terminals IP20

Measuring and Monitoring Relays

w Measuring and Monitoring Relays Series AMPARO

DESCRIPTION AVAILABLE ORDER NO. Voltage Monitoring Relays Voltage monitoring relay AMPARO with adjustable voltage range 160-240V, 230V-AC, 3 phase, 1CO , 5A/230V URAU3011 Voltage monitoring relay AMPARO, 230V-AC, with fixed switching threshold Us=195.5V, 3 phase against N, 1 CO, 5A/230V URAU3N11 Phase Monitoring Relays Phase monitoring relay AMPARO, 230V-AC, 3 phase, 1CO, 5A/230V URAP3011

Page 136

Order no. blue: on stock, usually ready for delivery on the day of order Measuring and Monitoring Relays w Measuring and Monitoring Relays Series UR6

UR6U UR6I1052 UR6P3052 UR6R1052

Page 137

UR6L1052 w Schrack-Info UR6U1052 UR6P3052 • Multi-function monitoring relay • Voltage monitoring in 3-phase networks • Voltage monitoring for AC and DC in 1-phase networks • Phase sequence and phase failure monitoring • Error memory • Supply voltage = measured voltage • 16.6 to 400 Hz • Reverse voltage detection • 2 CO • Neutral conductor connection optional • Zoom voltage 24 to 240 V AC/DC • 2 CO • Component width 22.5 mm • Component width 22.5 mm • Industrial type design • Industrial type design UR6U3052 UR6R1052 • Multi-function monitoring relay • Motor winding temperature monitoring • Voltage monitoring in 3-phase networks • 2 CO • Phase sequence and phase failure monitoring • Supply voltage 230 V AC • Phase imbalance monitoring can be activated/deactivated • Connection of external Reset switch possible • Neutral conductor connection optional • Component width 22.5 mm • Loss of neutral wire detection • Industrial type design • 2 CO UR6L1052 • Zoom voltage 24 to 240 V AC/DC • Multi-function monitoring relay • Component width 22.5 mm • Filling level monitoring of conductive liquids • Industrial type design • Safe disconnection of measuring circuits UR6I1052 • 2 CO • Multi-function monitoring relay • Component width 22.5 mm • Current monitoring for AC and DC in 1-phase networks • Industrial type design • Error memory • 16.6 to 400 Hz • 2 CO • Zoom voltage 24 to 240 V AC/DC • Component width 22.5 mm • Industrial type design Measuring and Monitoring Relays

w Measuring and Monitoring Relays Series UR6 w Technical Data (Part 1) UR6U1052 UR6U3052 UR6I1052 Indication of supply Indication of supply INDICATORS Green LED ON - voltage voltage Indication of start-up Indication of start-up Green LED flashes - suppression time suppression time Yellow LED ON/OFF Indication of relay output Red LED ON/OFF Indication of failure of the corresponding threshold Red LED flashes Indication of tripping delay of the corresponding threshold MECHANICAL DESIGN Housing Self-extinguishing plastic housing Degree of protection housing IP40 Mounting (EN 60715) DIN-rail TS 35 (VBG 4, PZ1 Terminal Shockproof terminal connection required) Degree of protection terminal IP20 Mounting position Any Tightening torque Max. 1 Nm Terminal capacity 1 x 0.5 to 2.5 mm 2 with/without multicore cable end 1 x 4 mm 2 without multicore cable end 2 x 0.5 to 1.5 mm 2 with/without multicore cable end Page 2 x 2.5 mm 2 flexible without multicore cable end 138 INPUT CIRCUIT Terminals A1 - A2 (galvanically separated) Supply voltage 24 - 240V AC / DC Tolerance 24 to 240 V DC -20 % to +25 % 24 to 240 V AC -15 % to +10 % Rated consumption 4.5 VA (1 W) Rated frequency 24 to 240 V AC 48 to 400 Hz 48 to 240 V AC 16 to 48 Hz Duration of operation 100 % Reset time 500 ms Wave form for AC Sinus Residual ripple for DC 10 % Drop-out voltage >15% of the supply voltage Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV OUTPUT CIRCUIT Number of contacts and type 2 potential free CO contacts Rated voltage AC 250 V~ Distance between the devices is Switching capacity 750 VA (3 A / 250 V~) < 5 mm Distance between the devices is 1250 VA (5 A / 250 V~) > 5 mm Fusing 5 A fast acting Mechanical service life 20 x 10 6 operations Electrical service life 2 x 10 5 operations at 1000VA resistive load Switching frequency (IEC 60947-5-1) max. 60 / min at 100 VA resistive load max. 6 / min at 1000 VA resistive load Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV

Measuring and Monitoring Relays w Measuring and Monitoring Relays Series UR6 w Technical Data (Part 2) UR6U1052 UR6U3052 UR6I1052 MEASURING CIRCUIT Fusing (UL 508) Max. 20 A DC or AC Sinus AC Sinus (48 to 63 DC or AC Sinus Measured variable (16.6 to 400 Hz) Hz) (16.6 to 400 Hz) 30 V Terminals 2 mA Terminals Input AC/DC E - F1 (+) AC/DC K - I1 (+) Terminals 60 V Terminals 1 A Terminals 3 (N)~ (N) L1 - L2 AC/DC E - F2 (+) AC/DC K - I2 (+) - L3 300 V Terminals 5 A Terminals

AC/DC E - F3 (+) AC/DC K - I3 (+) 30 V 20 mA Overload capacity 100 V 250 mA AC/DC rms AC/DC 60 V 1 A 150 V 3 (N)~ 3 (N)~ 3 A AC/DC rms AC/DC 300 V 5 A 440 V 10 A AC/DC rms AC/DC 30 V 20 mA Input resistance 47 2.7 AC/DC ȍ AC/DC ȍ 60 V 1 A 100 3 (N)~ 1 M 47 m AC/DC ȍ ȍ AC/DC ȍ Page 300 V 5 A 470 10 m AC/DC ȍ AC/DC ȍ 139 Switching threshold Max. 10 % to 100 % of U N -20 % to +30 % of U N 10 % to 100 % of I N

Min. 5 % to 95 % of U N -30 % to +20 % of U N 5 % to 95 % of I N Asymmetry - 5 % to 25 % - Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV ACCURACY Base accuracy ≤ 3 % (of maximum scale value) -10 % to 5 % (16.6 to -10 % to 5 % (16.6 to Frequency response - 400 Hz) 400 Hz) Adjustment accuracy ≤ 5 % (of maximum scale value) Repetition accuracy ≤ 2 % Voltage influence - Temperature influence ≤ 0.05 % / °C AMBIENT CONDITIONS Ambient temperature (IEC 60068-1) -25 °C to +55 °C (UL 508) -25 °C to +40 °C Storage temperature -25 °C to +70 °C Transport temperature -25 °C to +70 °C Relative humidity (IEC 721 - 3-3 class 3K3) 15 % to 85 % Pollution degree (IEC 60664-1) 3 10 to 55 Vibration resistance (IEC 60068-2-6) 0.35 mm Hz Shock resistance (IEC 60068-2-27) 15 g 11 ms

Measuring and Monitoring Relays

w Measuring and Monitoring Relays Series UR6 w Technical Data (Part 3) UR6P3052 UR6R1052 UR6L1052 INDICATORS Green LED ON Indication of supply voltage Yellow LED ON/OFF Indication of relay output - Indication of relay output Red LED ON/OFF - Indication of failure - MECHANICAL DESIGN Housing Self-extinguishing plastic housing Degree of protection housing IP40 Mounting (EN 60715) DIN-rail TS 35 Terminal (VBG 4, PZ1 required) Shockproof terminal connection Degree of protection terminal IP20 Mounting position Any Tightening torque Max. 1 Nm Terminal capacity 1 x 0.5 to 2.5 mm 2 with/without multicore cable end 1 x 4 mm 2 without multicore cable end 2 x 0.5 to 1.5 mm 2 with/without multicore cable end 2 x 2.5 mm 2 flexible without multicore cable end A1 - A2 (N) L1 - L2 - L3 [= measuring INPUT CIRCUIT Terminals (galvanically A1 - A2 voltage] separated) Page Supply voltage 3 (N)~ 230 / 400 V AC 230 V AC Tolerance 230 V AC - -15 % to +15 % 140 3 (N)~ 230 / 400 V AC 3 (N)~ 342 to 457 V - Rated consumption 9 VA 2 VA (1.5 W) Rated frequency 50 / 60 Hz Duration of operation 100 % Reset time 500 ms Wave form for AC - Residual ripple for DC - > 15 % of the > 30 % of the supply Drop-out voltage > 20 % of the supply voltage supply voltage voltage Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV Number of contacts OUTPUT CIRCUIT 2 potential free CO contacts and type Rated voltage AC 250 V~ Distance between the devices is Switching capacity 750 VA (3 A / 250 V~) < 5 mm Distance between the devices is 1250 VA (5 A / 250 V~) > 5 mm Fusing 5 A fast acting Mechanical service life 20 x 10 6 operations Electrical service life 2 x 10 5 operations at 1000 VA resistive load Switching frequency (IEC 60947-5-1) Max. 60 / min at 100 VA resistive load Max. 6 / min at 1000 VA resistive load Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV

Measuring and Monitoring Relays

w Measuring and Monitoring Relays Series UR6 w Technical Data (Part 4) UR6P3052 UR6R1052 UR6L1052 MEASURING CIRCUIT Measured variable AC Sinus (48 to 63 Hz) - - 3 (N)~ 230 / (N) L1 - L2 Conductive Terminals Input Terminals T1 - T2 400 V - L3 probes E1 - E2 - E3 3 (N)~ 230 / 3(N)~ 264 / Overlord capacity 400 V 457 V 3 (N)~ 230 / Input resistance 15 k 400 V ȍ Asymmetry Fixed, typ. 30 % Initial resistance < 1.5 k ȍ Response value (Relay in off-position) > 3.6 k ȍ Release value (Relay in on-position) < 1.8 k ȍ Disconnection (Short circuit thermistor) No Measuring voltage < 2.5 V DC at R (DIN VDE 0660 part 302) T1-T2 < 4 kȍ 0.25 to 100 k (4 mS Sensitivity ȍ to 10 ȝS) Sensor voltage 12 V~ Sensor current Max. 7 mA Max. 1000 Set value < Page Wiring distance (Capacity of cable 100 nF / km) m 50 % 141 Max. 100 Set value

m 100 % Overvoltage category (IEC 60664-1) III Rated surge voltage 4 kV 6 kV CONTROL CONTACT R Function External reset key Loadable No Max. 10 m Line length R-T2 (twisted pair) Control pulse length - Potential free NO Reset contact, terminals R - T2 +10 % of ACCURACY Base accuracy maximum scale value Frequency response - Adjustment accuracy - Repetition accuracy < 1 % Voltage influence < 2.2 % Temperature influence ≤0.1 % / °C AMBIENT TEMPERATURE Ambient temperature (IEC 60068-1) -25 °C to +55 °C (UL 508) -25 °C to +40 °C Storage temperature -25 °C to +70 °C Transport temperature -25 °C to +70 °C Relative humidity (IEC 721-3-3 class 3K3) 15 % to 85 % Pollution degree (IEC 60664-1) 3 10 to 55 Vibration resistance (IEC 60068-2-6) 0.35 mm Hz Shock resistance (IEC 60068-2-27) 15 g 11 ms Measuring and Monitoring Relays

w Measuring and Monitoring Relays Series UR6 w Overview Modes

AC/DC voltage monitoring in 1-phase mains with adjustable thresholds, timing for start-up suppression and tripping delay separately adjustable as well as the following functions (selectable by means of rotary switch): OVER Overvoltage monitoring OVER + LATCH Overvoltage monitoring with fault latch UR6U1052 UNDER Undervoltage monitoring UNDER + LATCH Undervoltage monitoring with fault latch WIN Monitoring the window between "Min." with "Max." WIN + LATCH Monitoring the window between "Min." with "Max." with fault latch

Voltage monitoring in 3-phase mains with adjustable thresholds, adjustable tripping delay, monitoring of phase sequence and phase failure, monitoring of asymmetry with adjustable threshold as well as the following functions (selectable by means of rotary switch): UR6U3052 UNDER Undervoltage monitoring UNDER + SEQ Undervoltage monitoring and monitoring of phase sequence WIN Monitoring the window between "Min." and "Max." WIN + SEQ Monitoring the window between "Min." and "Max." and monitoring of phase sequence

AC/DC current monitoring in 1-phase mains with adjustable thresholds, timing for start-up suppression and tripping delay separately Page adjustable as well as the following functions (selectable by means of rotary switch): OVER Overcurrent monitoring 142 OVER + LATCH Overcurrent monitoring with fault latch UR6I1052 UNDER Undercurrent monitoring UNDER + LATCH Undercurrent monitoring with fault latch WIN Monitoring the window between "Min." and "Max." WIN + LATCH Monitoring the window between "Min." and "Max." with fault latch

UR6P3052 Monitoring of phase sequence, phase failure and detection of return voltage (by means of evaluating the asymmetry)

Temperature monitoring of the motor winding (max. 6 PTC) with fault latch for temperature probes in accordance with DIN 44081 and UR6R1052 test function with integrated test/reset key

Level monitoring of conductive liquid, timing for tripping delay and turnoff delay separately adjustable as well as the following functions (selectable by means of rotary switch): UR6L1052 PUMP UP Pump up or minimum monitoring PUMP DOWN Pump down or maximum monitoring

w Dimensions (mm)

w Time Ranges

Article number Adjustment range Start-up suppression time 0 s 10 s UR6U1052 Tripping delay 0.1 s 10 s Start-up suppression time - UR6U3052 Tripping delay 0.1 s 10 s Start-up suppression time 0 s 10 s UR6I1052 Tripping delay 0.1 s 10 s Start-up suppression time Fixed, max. 500 ms UR6P3052 Tripping delay Fixed, max. 350 ms Start-up suppression time - UR6R1052 Tripping delay - Tripping delay (DELAY ON) 0.5 s 10 s UR6L1052 Turn-off delay (DELAY OFF) 0.5 s 10 s

Measuring and Monitoring Relays w Measuring and Monitoring Relays Series UR6 w Circuit Diagrams Overview

Page 143

w Overview Circuit Diagrams UR6U1052 UR6I1052 Supply voltage 24 V AC / DC Supply voltage 24 V AC / DC A F Range 30 V and fault latch Range 20 mA and fault latch Supply voltage 230 V AC / DC Supply voltage 24 V AC / DC B G Range 60 V and fault latch Range 5 A without fault latch Supply voltage 24 V AC / DC Supply voltage 230 V AC C H Range 300 V and fault latch Range 1 A and fault latch

UR6U3052 UR6L1052 D Supply voltage 24 V AC / DC I1 Probe max. E Supply voltage 230 V AC I2 Probe min. I3 Mass probe

Measuring and Monitoring Relays

w Measuring and Monitoring Relays Series UR6 w UR6U1052 Modes

Page 144

w Detailed Description of UR6U1052 Modes

When the supply voltage U is applied, the output relays switch into on-position (yellow LED illuminated) and the set interval of the start-up suppression (START ) begins (green LED U flashes). Changes of the measured voltage during this period do not affect the state of the output relay. After the interval has expired the green LED is illumi-nated steadily. For all the functions the LEDs "MIN" and "MAX" are flashing alternating, when the minimum value for the measured voltage was chosen to be greater than the maximum value. Overvoltage monitoring When the measured voltage exceeds the value adjusted at the MAX-regulator, the set interval of the tripping delay (DELAY ) begins (red LED MAX flashes). After the interval has expired (red LED MAX illuminated), the output relays switch into off-position (yellow LED not illuminated). The output relays again switch into on-position (yellow LED illuminated), when the measured voltage falls below the value adjusted at the MIN-regulator (red OVER, 1.1 LED MAX not illuminated). If the fault latch is activated (OVER+LATCH ) and the measured voltage remains OVER + LATCH above the MAX-value longer than the set interval of the tripping delay, the output relays remain in the off-position even if the measured voltage falls below the value adjusted at the MIN-regulator. After resetting the failure (interrupting and reapplying the supply voltage), the output relays switch into on-position and a new measuring cycle begins with the set interval of the start-up suppression (START ). Undervoltage monitoring When the measured voltage falls below the value adjusted at the MIN-regulator, the set interval of the tripping delay (DELAY ) begins (red LED MIN flashes). After the interval has expired (red LED MIN illuminated), the output relays switch into off-position (yellow LED not illuminated). The output relays again switch into on-position (yellow LED illuminated), when the measured voltage exceeds the value adjusted at the MAX-regulator.If the fault UNDER, 1.2 latch is activated (UNDER+LATCH ) and the measured volt-age remains below the MIN-value longer than the UNDER + LATCH set interval of the tripping delay, the output relays remain in the off-position even if the measured voltage exceeds the value adjusted at the MAX-regulator. After resetting the failure (interrupting and re-applying the supply voltage), the output relays switch into on-position and a new measuring cycle begins with the set interval of the UR6U1052 start-up suppression (START ). Window function The output relays switch into on-position (yellow LED illuminated) when the measured voltage exceeds the value adjusted at the MIN-regulator. When the measured voltage exceeds the valueadjusted at the MAX-regulator, the set interval of the tripping delay ( DELAY ) begins (red LED MAX flashes). After the interval has expired (red LED MAX illuminated), the output relays switch into off-position (yellow LED not illuminated). The output relays 1.3 again switch into on-position (yellow LED illuminated) when the measured voltage falls below the value adjusted at the MAX-regulator (red LED MAX not illuminated). When the measured voltage falls below the value adjusted at the MIN-regulator, the set interval of the tripping delay (DELAY ) begins again (red LED MIN flashes). After the interval has expired (red LED MIN illuminated), the output relays switch into off-position (yellow LED not WIN, illuminated). WIN+LATCH

If the fault latch is activated ( WIN+LATCH ) and the measured voltage remains below the MIN-value longer than the set interval of the tripping delay, the output relays remain in the off-position even if the measured voltage exceeds the value adjusted at the MIN-regulator. If the measured voltage remains above the MAX-value longer 1.4 than the set interval of the tripping delay, the output relays remain in the off-position even if the measured voltage falls below the value adjusted at the MAX-regulator. After resetting the failure (interrupting and re-applying the supply voltage), the output relays switch into on-position and a new measuring cycle begins with the set interval of the start-up suppression (START ). 1 Latch activated (Y1-Y2 bridged) 2 Start Diagram 3 Delay 4 >Delay

Measuring and Monitoring Relays w Measuring and Monitoring Relays Series UR6 w UR6U3052 Modes

Page 145

w Detailed Description of UR6U3052 Modes

For all the functions the LEDs MIN and MAX are flashing alternating, when the minimum value for the measured voltage was chosen to be greater than the maximum value. If a failure already exists when the device is activated, the output relays remain in off-position and the LED for the corresponding threshold is illuminated. Undervoltage monitoring When the measured voltage (mean value of phase-to-phase voltages) falls below the value adjusted at the MIN-regulator, the set interval of the tripping delay (DELAY ) begins (red LED MIN flashes). After the interval UNDER, 2.1 has expired (red LED MIN illuminated), the output relays switch into off-position (yellow LED not illuminated). The UNDER + SEQ output relays again switch into on-position (yellow LED illuminated), when the measured voltage exceeds the value adjusted at the MAX-regulator. Window function The output relays switch into on-position (yellow LED illuminated) when the measured voltage (mean value of phase-to-phase voltages) exceeds the value adjusted at the MIN-regulator. When themeasured voltage exceeds the value adjusted at the MAX-regulator, the set interval of the tripping delay ( DELAY ) begins (red LED MAX flashes). After the interval has expired (red LED MAX illuminated), the output relays switch into off-position WIN, 2.2 (yellow LED not illuminated). The output relays again switch into on-position (yellow LED illuminated) when the WIN + SEQ measured voltage falls below the value adjusted at the MAX-regulator (red LED MAX not illuminated). When the measured voltage falls below the value adjusted at the MIN-regulator, the set interval of the tripping delay (DELAY ) begins again (red LED MIN flashes). After the interval has expired (red LED MIN illuminated), the output relays switch into off-position (yellow LED not illuminated). Phase sequence monitoring Phase sequence monitoring is selectable for all functions. If a change in phase sequence is detected (red LED SEQ 2.3 SEQ illuminated), the output relays switch into off-position immediately (yellow LED not illuminated). UR6U3052 Phase failure monitoring If one of the phase voltages fails, the set interval of the tripping delay ( DELAY ) begins (red LED SEQ flashes). After the interval has expired (red LED SEQ illuminated), the output relays switch into off-position (yellow LED not SEQ 2.4 illuminated). Reverse voltages of a consumer (e.g. a motor which continues to run on two phases only) do not effect the disconnection but can be monitored by using a proper value for the asymmetry. Asymmetry monitoring If the asymmetry of the phase-to-phase voltages exceeds the value set at the ASYM-regulator, the set interval of the tripping delay (DELAY ) begins (red LED ASYM flashes). After the interval has expired (red LED ASYM illuminated), the output relays switch into off-position (yellow LED not illuminated). If the neutral wire is connected 2.5 to the device, the asymmetry of the phase voltages referred to the neutral wire (Y-voltage) is monitored also. In that case both values of the asymmetry are evaluated and if one of the values exceeds the value set at the ASYM- regulator, the set interval of the tripping delay ( DELAY ) begins (red LED ASYM flashes). After the interval has expired (red LED ASYM illuminated), the output relays switch into off-position (yellow LED not illuminated). Loss of neutral wire by means of evaluation of asymmetry A break of the neutral wire between power line and machinery is detected as soon as asymmetry between phase-to-phase voltage and neutral wire occurs. If the asymmetry exceeds the value set atthe ASYM-regulator, 2.6 the set interval of the tripping delay ( DELAY ) begins (red LED ASYM flashes). After the interval has expired (red LED ASYM illuminated), the output relays switch into off-position(yellow LED not illuminated). A break of the neutral wire between our device and the machinery can not be detected. A Shift of neutral point (asymmetry) caused by asymmetrical phase loads and missing neutral wire. Diagram 2 Start 3 Delay Measuring and Monitoring Relays

w Measuring and Monitoring Relays Series UR6 w UR6I1052 Modes

Page 146

w Detailed Description of UR6I1052 Modes

When the supply voltage U is applied, the output relays switch into on-position (yellow LED illuminated) and the set interval of the startup suppression (START ) begins (green LED U flashes). Changes of the measured current during this period do not affect the state of the output relay. After the interval has expired the green LED is illuminated steadily. For all the functions the LEDs "MIN" and "MAX" are flashing alternating, when the minimum value for the measured current was chosen to be greater than the maximum value. Overcurrent monitoring When the measured current exceeds the value adjusted at the MAX-regulator, the set interval of the tripping delay (DELAY ) begins (red LED MAX flashes). After the interval has expired (red LED MAX illuminated), the output relays switch into off-position (yellow LED not illuminated). The output relays again switch into on-position (yellow LED illuminated), when the measured current falls below the value adjusted at the MIN-regulator (red OVER, 3.1 LED MAX not illuminated). If the fault latch is activated (OVER+LATCH ) and the measured current remains above OVER + LATCH the MAX-value longer than the set interval of the tripping delay, the output relays remain in the off-position even if the measured current falls below the value adjusted at the MIN-regulator. After resetting the failure (interrupting and reapplying the supply voltage), the output relays switch into on-position and a new measuring cycle begins with the set interval of the start-up suppression (START ). Undercurrent monitoring When the measured current falls below the value adjusted at the MIN-regulator, the set interval of the tripping delay (DELAY ) begins (red LED MIN flashes). After the interval has expired (red LED MIN illuminated), the output relays switch into off-position (yellow LED not illuminated). The output relays again switch into on-position (yellow LED illuminated), when the measured current exceeds the value adjusted at the MAX-regulator. If the fault UNDER, 3.2 latch is activated (UNDER+LATCH ) and the measured current remains below the MIN-value longer than the set UNDER + LATCH interval of the tripping delay, the output relays remain in the off-position even if the measured current exceeds the value adjusted at the MAX-regulator. After resetting the failure (interrupting and reapplying the supply voltage), the output relays switch into on-position and a new measuring cycle begins with the set interval of the start-up UR6I1052 suppression (START ). Window function The output relays switch into on-position (yellow LED illuminated) when the measured current exceeds the value adjusted at the MIN-regulator. When the measured current exceeds the valueadjusted at the MAX-regulator, the set interval of the tripping delay ( DELAY ) begins (red LED MAX flashes). After the interval has expired (red LED MAX illuminated), the output relays switch into off-position (yellow LED not illuminated). The output relays 3.3 again switch into on-position (yellow LED illuminated) when the measured current falls below the value adjusted at the MAX-regulator (red LED MAX not illuminated). When the measured current falls below the value adjusted at the MIN-regulator, the set interval of the tripping delay (DELAY ) begins again (red LED MIN flashes). After the interval has expired (red LED MIN illuminated), the output relays switch into off-position (yellow LED not WIN, illuminated). WIN + LATCH

If the fault latch is activated ( WIN+LATCH ) and the measured current remains below the MIN-value longer than the set interval of the tripping delay, the output relays remain in the off-position even if the measured current exceeds the value adjusted at the MIN-regulator. If the measured current remains above the MAX-value longer 3.4 than the set interval of the tripping delay, the output relays remain in the off-position even if the measured current falls below the value adjusted at the MAX-regulator. After resetting the failure (interrupting and reapplying the supply voltage), the output relays switch into on-position and a new measuring cycle begins with the set interval of the start-up suppression (START ). 1 Latch activated 2 Start Diagram 3 Delay 4 >Delay

Measuring and Monitoring Relays w Measuring and Monitoring Relays Series UR6 w UR6P3052 Modes

Page 147

w Detailed Description of UR6P3052 Modes

Phase sequence monitoring When all the phases are connected in the correct sequence and the measured asymmetry is less than the fixed value, the output relays switch 4.1 into on-position (yellow LED illuminated). When the phase sequence changes, the output relays switch into off-position (yellow LED not illuminated). Phase failure monitoring UR6P3052 4.2 When one of the three phases fails, the output relays switch into off-position (yellow LED not illuminated). Detection of reverse voltage (by means of evaluation of asymmetry) The output relays switch into off-position (yellow LED not illuminated) when the asymmetry between the phase voltages exceeds the fixed value 4.3 of the asymmetry. An asymmetry caused by the reverse voltage of a consumer (e.g. a motor which continues to run on two phases only) does not effect the disconnection. w UR6R1052 Modes

w Detailed Description of UR6R1052 Modes

If the supply voltage U is applied (green LED illuminated) and the cumulative resistance of the PTC-circuit* is less than 3.6kȍ (standard 5.1 temperature of the motor), the output relays switch into on-position. Pressing the test/reset key under this conditions forces the output relays to switch into off-position. They remain in this state as long as the test/reset key is pressed and thus the switching function can be checked in case UR6R1052 of fault. The test function is not effective using an external reset key. When the cumulative resistance of the PTC-circuit exceeds 3.6kȍ (at least one of the PTCs has reached the cut-off temperature), the output relays switch into off-position (red LED illuminated). The output relays again 5.2 switch into on-position (red LED not illuminated), if the cumulative resistance drops below 1.8k ȍ by cooling down of the PTC and either a reset key (internal or external) was pressed or the supply voltage was disconnected and reapplied. *PTC = Positive Temperature Coefficient

Measuring and Monitoring Relays

w Measuring and Monitoring Relays Series UR6 w UR6L1052 Modes

Page 148 w Detailed Description of UR6L1052 Modes Pump up Connection of the probe rods E1 , E2 and E3 . Alternatively the electrically conducting container can be connected in lieu of the test probe E3 . When the air-fluid level falls below the minimum probe E2 the set interval of tripping delay ( Delay PUMP UP 6.1 ON ) begins. After the expiration of the interval, the output relays R switches into on-position (yellow LED illuminated). When the air-fluid level again rises above the maximum probe E1 , the set interval of turn-off delay ( Delay OFF ) begins. After the expiration of the interval the output relays R switches into off-position (yellow LED not illuminated). Minimum monitoring (Pump up) Connection the probe rods E2 and E3 (bridge E1-E3). Alternatively the electrically conducting container can be connected in lieu of the test probe E3 . When the air-fluid level falls below the probe E2 the set interval of tripping delay PUMP UP 6.2 (Delay ON ) begins. After the expiration of the interval, the output relays R switches into on-position (yellow LED illuminated). When the air-fluid level again rises above the probe E2 , the set interval of turn-off delay ( Delay OFF ) begins. After the expiration of the interval the output relays R switches into off-position (yellow LED not illuminated). Pump down Connection of the probe rods E1 , E2 and E3 . Alternatively the electrically conducting container can be connected in lieu of the test probe E3 . When the maximum probe E1 gets moistened the set interval of tripping delay ( Delay ON ) begins. UR6L1052 PUMP DOWN 6.3 After the expiration of the interval the output relays R switches into on-position (yellow LED illuminated). When the air- fluid level falls below the minimum probe E2 , the set interval of turn-off delay ( Delay OFF ) begins. After the expiration of the interval, the output relays R switches into off-position (yellow LED not illuminated). Maximum monitoring (Pump down) Connection of probe rods E2 and E3 (bridge E1-E3). Alternatively the electrically conducting container can be connected in lieu of the test probe E3 . When the probe E2 gets moistened the set interval of tripping delay ( Delay ON ) PUMP DOWN 6.4 begins. After the expiration of the interval the output relays R switches into on-position (yellow LED illuminated). When the air-fluid level sinks below the probe E2 , the set interval of turn-off delay ( Delay OFF ) begins. After the expiration of the interval the output relays R switches into off-position (yellow LED not illuminated). 5 Level 6 Probe E1 7 Probe E2 Diagram 8 Probe E3 9 Delay ON 10 Delay OFF

DESCRIPTION AVAILABLE ORDER NO. Voltage Monitoring Relays Voltage monitoring relay, 1 phase, AC/DC, 2 CO UR6U1052 Voltage monitoring relay, 3 phase, AC/DC, 2 CO UR6U3052 Current Monitoring Relays Current monitoring relay, 1 phase, input 24-240V-AC/DC, 1CO UR6I1052 Phase Monitoring Relays Phase monitoring relay, 3 phase, 2 CO UR6P3052 Thermistor Monitoring Relays Thermistor monitoring relay, 1 phase, 230V-AC, 2 CO UR6R1052 Level Monitoring Relays Level monitoring relay, 1 phase, input 230V-AC/5A, 2 CO UR6L1052

Order no. blue: on stock, usually ready for delivery on the day of order Measuring and Monitoring Relays w Accessories, Probes for Level Monitoring Relays

URL91010 URL900xx URL90010 w Schrack-Info URL90010, URL90020, URL90030 • Maximum pressure range 1000 kPa • Operating temperature up to 70°C • Coated with Nylon 66 Page • For use in all application, except for certain fields of the food processing industry where Nylon 66 is prohibited as insulating material 149 URL91010 • Probe element can be connected to cable w w

Dimensions URL90010 (mm) Dimensions URL90010

Thread A (inch) 1.5

w Technical Data URL90010, URL90020 & URL90030 Holder / Conductive probe Material Nylon Thread Inch 1,5 British standard Degree of protection IP65 Max. temperature +70 °C Conductor / Electrode rods Material Stainless steel AISI 316 Coating Black powder epoxy Length 1 m Number of conductors URL90010 1 x 1 metre rod URL90020 2 x 1 metre rod URL90030 3 x 1 metre rod Note: Coating of rods improves resistance to false switching caused by frothing of condensation.

DESCRIPTION AVAILABLE ORDER NO.

Level monitoring immersion probe URL91010 Level monitoring 1 probe, 1x1 meter URL90010 Level monitoring 2 probes, 2x1 meter URL90020 Level monitoring 3 probes, 3x1 meter URL90030

Order no. blue: on stock, usually ready for delivery on the day of order Relay Module

w Relay PCB w Schrack-Info • 8 pcs. relay module (24 V DC/8 A) • Version with plug-in relay • 2 CO per relay • DC control voltage • Negative control voltage • LED operating lights • Fast and easy DIN rail mounting IK022176

w Dimensions (mm)

Page 150

w w Circuit Diagram Circuit Diagram A 8 piece relay module B Power on General data The height dimension includes 35 mm DIN rail

Relay Module w Relay PCB w Technical Data 8 relay module Number of contacts and type 8 channels each with 2 CO Rated current 8 A Supply voltage AC 250 V~ Coil voltage DC 24 V + 10% Coil current (1 channel) 22 mA + 10% Turn ON time 15 ms Turn OFF time 10 ms Protection circuit Damping- and protection diode LED colors Yellow and green Contact material AgNi Housing material UL94V-0 plastic material Connection terminal Screw terminal 2.5 mm 2 Degree of protection IEC 529, EN 60529 IP00 Coil-/ contact isolation 2.5 kVA / 60 s Isolation between output terminals (open contacts) 1 kVA / 60 s Overvoltage category III Pollution degree 2 Ambient temperature Operation -10 °C to +50 °C Page Approx. weight ca. 419 g 151 Reference standard IEC 664-1, DIN VDE 0110.1 Mounting Vertical on DIN-rail

DESCRIPTION AVAILABLE ORDER NO.

Relay module, 8 pcs. plug-in relays, 24V DC/8A, each with 2CO, for DIN-rail IK022176

Order no. blue: on stock, usually ready for delivery on the day of order Summary Alarm Indicators

w Summary Alarm Indicators SSM11-24V-DC

YY494006 YY494006 YY494006 YMR78700 w Schrack-Info YY494006 The type SSM11 summary alarm indicator is a safe low-cost solution for many purposes, combining several functionalities in one unit: • Motor monitoring Page • Contact monitoring with change over contact 152 • High reliability lighting • Acoustic signalling • Optical collective signalling • Compatible with 11 pole plug-in socket YMR78700

w Dimensions SSM11 (mm)

Summary Alarm Indicators

w Summary Alarm Indicators SSM11-24V-DC w Dimensions YMR78700 (mm) w Functionalities SSM11

Motor Monitoring If the motor is not running, the light ( H1 ) will be off; if the motor is running, the light will be on. In the event of faulty operation of the motor (F1 ), the light will flash on-off.

Contact monitoring with Change Over Contact During regular operation the light will be on ( H2 ); in the event of an interruption, the light will flash on-off (H3 ).

High Reliability Lighting To maintain the functionality of acoustic and optical collective signalling, connecting a parallel resistor is recommended (at 24 V, 2K2 ȍ / ½ W).

Acoustic Signalling In the event of an interruption, the horn will signal approx. 15 sec. afterwards ( H5 ). It can be reset by pressing the Acknowledge (B4 ) key. Page Optical Collective Signalling The Fault light ( H4 ) will be on as long as there is one (or several) 153 interruptions-regardless of whether the Acknowledge key has been pressed or not.

w Circuit Diagram SSM11 w Circuit Diagram SSM11 1 Option 1 2 Option 2 3 Option 3 B1 On-switch B2 Operating- and fault signal contact (contactor) B3 Fault message contact (contactor or control system) B4 Acknowledge button BS Flashing bar F1 Overcurrent relay H1 Motor operation lamp H2 Operation lamp H3 Failure lamp H4 Failure lamp H5 Horn K1 Motor contactor

w Technical Data Rated voltage 24 V DC +20 % Contacts 250 V~ Max. 8A Power consumption Idle ca. 1 VA In operation ca. 4 VA Assembly 11-pole socket YMR78700

DESCRIPTION AVAILABLE ORDER NO.

Indicator for Summary-alarm SSM11-24V YY494006 DIN rail mounted plug-in socket for MT3 relays and timer relays Series ZR4, 11 pole, 10A (3 CO), with screw terminals, not compatible with function modules YMR78700

Order no. blue: on stock, usually ready for delivery on the day of order Diode Combination

w Diode Combination DBS

YY494007 YY494007 YY494007 YMR78700

Page 154

YY494107 YY494107 YY494107 w Schrack-Info • Despite their compact size the diode combinations DBS10 (YY494007) and DBS01 (YY494107) are suitable for up to 10 indicators. If there are light bulbs/glow lamps or LEDs for signalling operating states, integrating the diode combination can be a simple way to retrofit an alarm verification. By connecting multiple combinations it is possible to scan any number of alarms. Every diode combinations contains a protective diode, which limits the impact of a defective individual diode on other components of the system (e.g. contactors). Both diode combinations DBS10 and DBS01 can be used as protection diodes for relays and contactors. • The DBS10 and DBS01 have different polarities, which are explained in detail in the circuit diagrams • Both types are compatible with the 11 pole plug-in socket YMR78700 w Dimensions DBS10 & DBS01 (mm)

w Dimensions YMR78700 (mm) Diode Combination

w Diode Combination DBS w Circuit Diagrams DBS10 & DBS01

Page 155

w Technical Data Rated voltage 250 V~ Max. Peak voltage 1000 V~ Current 1 A per single message Max. Peak current 20 A / 10 ms Input 1N4007 (Pin 1) Diode Output 1N4007 (Pin2-11) Insulation class VDE 0110 Group C 250 V~ Assembly 11-pole socket YMR78700

DESCRIPTION AVAILABLE ORDER NO.

Diode-combination DBS10 YY494007 Diode-combination DBS01 YY494107 DIN rail mounted plug-in socket for MT3 relays and timer relays Series ZR4, 11 pole, 10A (3 CO), with screw terminals, not compatible with function modules YMR78700

Order no. blue: on stock, usually ready for delivery on the day of order