Sanitary Gravity Sewer Section 2 GUIDELINES, STANDARDS, AND SPECIFICATIONS DESIGN STANDARDS SECTION 2 – SANITARY GRAVITY SEWER SANITARY GRAVITY SEWER SECTION 2 1. Gravity Sewer Design 1.1. LOCATION/FUTURE CONNECTION Gravity sewers shall be located in dedicated rights‐of‐way or utility easements. Whenever possible, sewers shall be located under pavement in dedicated rights‐of‐way. All sewers located outside of dedicated rights‐ of‐way shall require a minimum 20‐foot easement. Additional easement widths shall be provided when the pipe size or depth of cover so dictate. If a gravity sewer is located adjacent to a road right‐of‐way, a minimum 10‐foot easement shall be provided. Additional easement widths shall be provided if the pipe size or depth of cover so dictate. No gravity sewers shall be placed under retention ponds or other structures. In general, gravity sewers shall not be located along side or rear lot lines. Placement of gravity sewer alongside or rear lot line may be allowed on a case‐by‐case basis if such a configuration results in efficient placement and utilization of the sewer system. Provisions for future connecting mains shall be made by providing appropriate easement and/or extending construction of all wastewater mains to the exterior boundaries of the subdivision where future connections to adjacent subdivisions or lots are anticipated. 1.2. AVERAGE DAILY FLOW Required average daily flow for sanitary use in residential areas shall be based on 350‐gallons per day (gpd) per unit (100‐gpcpd x 3.5 persons) or as approved by HNWS. The required flow for commercial, industrial, or other nonresidential areas shall be as determined and approved by HNWS for each specific instance. Justification for such flows shall be documented within the design calculations. 1.3. PEAK DESIGN FLOW Gravity sewers shall be designed on the basis of ultimate development maximum rates of flow, which shall be the product of selected peak factors times the accumulative average daily flow as calculated above. In general, the following minimum peak factors shall be applicable for the range of average daily flow rates. DESIGN AVERAGE DAILY FLOW MINIMUM PEAK FACTOR Flows to 100,000‐gpd 4 100,000‐gpd to 250,000‐gpd 3.5 250,000‐gpd to 1,000,000‐gpd 3 Flows greater than 1,000,000‐gpd 2.5 For design average daily flows above 2,000,000 gpd, peaking factors less than 2.5 may be considered if substantiated by extensive data. Under no circumstances shall peaking factors less than 2.0 be allowed. Page | 1 Revised 10-5-2018 GUIDELINES, STANDARDS, AND SPECIFICATIONS DESIGN STANDARDS SECTION 2 – SANITARY GRAVITY SEWER 1.4. MINIMUM AND STANDARD MAIN SIZES Minimum gravity main diameter shall be 8” in all areas. Standard sizes of gravity mains used shall have nominal diameters of 8”, 10”, 12”, 15”, 18”, 21”, 24”, 30”, and 36”. 1.5. COVER A minimum cover of 30” must be provided where conditions permit. At road crossings, a minimum separation distance of 30” shall be maintained from the bottom of the base to the top of the pipe or the top of the casing when provided. At buried stream crossings, a minimum cover of 36” is required. 1.6. SLOPE Slopes shall be designed with a hydraulic gradient sufficient to prevent deposition of solids, by developing a minimum velocity of 2.0‐feet per second (fps) as computed using Manning’s formula and an “n” value of not less than .013 while flowing full. The following table establishes the minimum allowable slopes for various size pipes and also indicates their approximate carrying capacity when flowing full at the minimum slope: PIPE SIZE MINIMUM CAPACITY (inches) SLOPE % FULL MGD+ 8 0.4 0.5 10 0.28 0.7 12 0.22 1.0 15 0.15 1.6 18 0.12 2.4 21 0.1 3.7 24 0.08 4.2 30 0.06 6.6 36 0.05 10.0 Under special conditions, if full and justifiable reasons are given, slopes slightly less than those required for the 2‐fps velocity when full may be permitted. Such decreased slopes will only be considered where the depth of flow will be 0.3 of the diameter or greater for design average flow. Whenever such decreased slopes are selected, the Developer must furnish, with his report, his computations for the depths of flow in such pipes at minimum, average, and peak rates of low. The selection of the size of pipe shall be determined on the basis of the most desirable flow characteristics obtainable. In the case of sewers where the slope and volume are such that velocities exceeding 10‐fps will be realized at design flow, special provisions shall be made to protect against erosion. Where velocities greater than 15‐fps are attained, special provisions shall be made to protect against displacement by erosion and shock. Page | 2 Revised 10-5-2018 GUIDELINES, STANDARDS, AND SPECIFICATIONS DESIGN STANDARDS SECTION 2 – SANITARY GRAVITY SEWER Full advantage of suitable topography and paralleling of ground slopes shall be made. Minimum slopes should be maintained when necessary, particularly with 8” pipe. When depth exceeds 10‐feet, check pipe class for strength, and/or specify stricter bedding requirements. Sewers shall be designed and laid with a uniform slope between manholes. 1.7. SIZE TRANSITION AND ALIGNMENTS Changing in pipe shall not occur between manholes: 1.7.1.1. Increasing Size: When a smaller sewer joins a larger one, the invert of the larger sewer shall be lowered sufficiently to maintain the same hydraulic gradient. An approximate method which may be used for securing this result is to place the .08 depth point of both sewers at the same elevations. 1.7.1.2. Decreasing Size: At times, due to increasing sewer slopes, a reduction in the size of the outgoing sewer from a manhole may be justified. Such a reduction shall not be permitted on sewers 24” in diameter or under. Vertical separation when crossing other utilities shall be shown. When crossing under existing paved streets or roads, Developer’s Engineer must determine if open cut will be permitted. If boring will be required, complete details must be shown. Extra effort should be expended to locate any possible conflict with existing utilities. Allow extra slope through bore and specify minimum and maximum allowable deviations. The depth of the line shall be sufficient to receive flows by gravity from all buildings and lots to be served. A 30” minimum cover is required. Less cover may be considered with special provisions for protection of the pipe. It may be necessary to require a few buildings to pump into the line by installing privately maintained lift stations. Privately maintained pump stations for an individual building will be considered when gravity service is not feasible. Sewers shall be laid with straight alignment between manholes. In general, horizontal separation between gravity sewers and other utilities shall be as follows: Bends of greater than 90‐degrees are to be avoided. REQUIRED HORIZONTAL SEPARATION Water Main 10‐feet Reclaimed Water Main 5‐feet 1.8. ADDITIONAL REQUIREMENTS FOR GRAVITY SEWER MAINS Main drain and back wash systems for pools and spas and storm drain systems shall not connect to the gravity sewer system. In general, all sewer extensions for future connections shall terminate at a manhole. HNWS may allow such extensions without a terminal manhole on a case‐by‐case basis subject to all of the following conditions: Page | 3 Revised 10-5-2018 GUIDELINES, STANDARDS, AND SPECIFICATIONS DESIGN STANDARDS SECTION 2 – SANITARY GRAVITY SEWER 1.8.2.1. Total sewer extension length shall be limited to 50‐feet. 1.8.2.2. Sewer extension location at the initiating manhole shall be plugged to the satisfaction of HNWS. 1.8.2.3. All such sewer extensions shall be inspected and accepted as part of the future construction phase. 1.9. MANHOLES Location 1.9.1.1. Manholes shall be installed: at the end of each gravity sewer; at all changes in grade, size or alignment; at all sewer intersections; and at distances not greater than 400‐feet. Type 1.9.2.1. An outside drop pipe shall be provided for a sewer entering a manhole where its invert elevation is 24” or more above the manhole invert (i.e. a drop manhole). 1.9.2.2. Where the difference in elevation between the incoming sewer invert and the manhole invert is less than 24”, the manhole invert shall be filleted to prevent solids deposition. Diameter 1.9.3.1. For sewers 24” in diameter and smaller, the minimum inside diameter of manholes shall be 48”. For sewers between 24” and 36”, the minimum inside diameter shall be 60”. For sewers larger than 36” in diameter, a 72” inside diameter manhole shall be provided. 1.9.3.2. A minimum access cover diameter of 24” shall be provided. Connecting Force Mains 1.9.4.1. Any gravity sewer manhole into which a force main or low‐pressure sewer main is tied‐in to shall be coated as well as the first downstream manhole at a minimum. Additional downstream manholes shall be coated as sewer diameter increases. See table on D‐111 Force Main Connection to Manhole. Flow Channel 1.9.5.1. The flow channel through manholes shall be made to conform in shape and slope to that of the sewers. Flow direction changes in excess of 90‐degrees shall not be included in sewer alignments without special consideration. When directional changes exceeding 45‐degrees occur, an additional flow line elevation drop of 0.1‐foot across manholes shall be provided.
Recommended publications
  • Infiltration/Inflow Task Force Report
    INFILTRATION/INFLOW TASK FORCE REPORT A GUIDANCE DOCUMENT FOR MWRA MEMBER SEWER COMMUNITIES AND REGIONAL STAKEHOLDERS MARCH 2001 INFILTRATION/INFLOW TASK FORCE REPORT A GUIDANCE DOCUMENT FOR MWRA MEMBER SEWER COMMUNITIES AND REGIONAL STAKEHOLDERS MARCH 2001 Executive Summary This report is the product of the Infiltration/Inflow (I/I) Task Force. It has been developed through the cooperative efforts of the 43 Massachusetts Water Resources Authority (MWRA) member sewer communities, MWRA Advisory Board, The Wastewater Advisory Committee (WAC) to the MWRA, Charles River Watershed Association (CRWA), Fore River Watershed Association (FRWA), Mystic River Watershed Association (MRWA), Neponset River Watershed Association (NRWA), South Shore Chamber of Commerce (SSCC), Massachusetts Department of Environmental Protection (DEP), United States Environmental Protection Agency (EPA), and MWRA. The I/I Task Force recommends implementation of the regional I/I reduction goals and implementation strategies detailed in this report. The report outlines a regional I/I reduction plan with appropriate burdens and benefits for stakeholders. The report is intended to be a guidance document for use by local sewer communities, as well as other regional stakeholders, who may tailor appropriate aspects of the report recommendations to their unique situations. Severe storms in October 1996 and June 1998 led to the unusual circumstance of numerous sanitary sewer overflows (SSOs) from local and MWRA collection systems. In the aftermath of these events, EPA and DEP began an aggressive effort to make MWRA regulate flows from community sewer systems. MWRA recommended cooperative efforts by local collection system operators, as well as regulators and environmental advocates, would be more effective than a prescriptive, enforcement based approach.
    [Show full text]
  • Inflow and Infiltration Reduction in Sanitary Sewers
    Appendix E-4 – Inflow and Infiltration Reduction in Sanitary Sewers INFLOW AND INFILTRATION REDUCTION IN SANITARY SEWERS D.1 Introduction to RDII in Sanitary Sewers A properly designed, operated and maintained sanitary sewer system is meant to collect and convey all of the sewage that flows into it to a wastewater treatment plant. Rainfall dependent infiltration and inflow (RDII) into sanitary sewer systems has long been recognized as a major source of operating problems that cause poor performance of many sewer systems including system overflows. The extent of infiltration also correlates with the condition of aging sewers. The three major components of wet-weather wastewater flow into a sanitary system – base wastewater flow (BWWF), groundwater infiltration (GWI), and RDII are illustrated in Figure D-1 and are discussed below. Figure D-1: Three components of wet-weather wastewater flow BWWF, often called base sanitary flow, is the residential, commercial, institutional, and industrial flow discharged to a sanitary sewer system for collection and treatment. BWWF normally varies with water use patterns within a service area throughout a 24-hour period with higher flows during the morning period and lower during the night. In most cases, the average daily BWWF is more or less constant during a given day, but varies monthly and seasonally. BWWF often represents a significant portion of the flows treated at wastewater treatment facilities. GWI represents the infiltration of groundwater that enters the collection system through leaking pipes, pipe joints, and manhole walls. GWI varies throughout the year, often trending higher in late winter and spring as groundwater levels and soil moisture levels rise, and subsiding in late summer or after an extended dry period.
    [Show full text]
  • Section 9 Sewer Collection Systems
    SECTION 9 SEWER COLLECTION SYSTEMS TABLE OF CONTENTS 9.1 PURPOSE AND DEFINITIONS .......................................................................................... 1 9.1.1 Purpose ........................................................................................................................ 1 9.1.2 DOU Sewer System ...................................................................................................... 1 9.1.3 Definitions ..................................................................................................................... 2 9.2 GENERAL REQUIREMENTS ........................................................................................... 11 9.2.1 Authority and Responsibility ....................................................................................... 11 9.2.2 Disclaimer ................................................................................................................... 11 9.2.3 Acceptance ................................................................................................................. 12 9.2.4 Variances .................................................................................................................... 12 9.2.5 Gravity vs. Pumped Systems ...................................................................................... 12 9.2.6 New Sewer Systems ................................................................................................... 13 9.2.7 Diversion of Flows .....................................................................................................
    [Show full text]
  • A Case Study of a Small Diameter Gravity Sewerage System in Zolkiewka Commune, Poland
    water Article A Case Study of a Small Diameter Gravity Sewerage System in Zolkiewka Commune, Poland Tadeusz Nawrot *, Radosław Matz, Ryszard Błazejewski˙ and Marcin Spychała Department of Hydraulic and Sanitary Engineering, Poznan University of Life Sciences, Pi ˛atkowskaSt. 94A, 60-649 Pozna´n,Poland; [email protected] (R.M.); [email protected] (R.B.); [email protected] (M.S.) * Correspondence: [email protected]; Tel.: +48-61-848-77-29 Received: 31 July 2018; Accepted: 27 September 2018; Published: 29 September 2018 Abstract: This article presents a small diameter gravity sewerage system in a rural area. In this system, domestic wastewater was preliminarily treated in septic tanks equipped with outlet filters, so the effluent features were similar to those of clear water. Additionally, some outlets were equipped with floating-ball check valves to avoid backflow. One of the pressure mains was used as a gravity collector conveying septic tank effluent in the direction of the pumping station during pump idle time. The operation of the system was simulated using SWMM computer code. The simulation results were validated for data obtained from part of a sewerage system in Kolonia Zolkiew and Rozki village consisting of two pumping stations and 86 serviced households using polyethylene pipes of outer diameter 50–63 mm. The results of the measurement of the outflows from one pumping station are presented. The simulation results showed good agreement with the empirical data, especially after several simulation days. The greatest discrepancy during the start-up period was the consequence of the initial conditions describing the empty pipework.
    [Show full text]
  • PART VI - SANITARY SEWER SYSTEM DESIGN CRITERIA (Public & Private)
    PART VI - SANITARY SEWER SYSTEM DESIGN CRITERIA (Public & Private) A. Definitions a Main - is that portion of the sewer system between manholes, or between manhole and the end of the main line provided with a lamphole. b Lateral - is that portion of the sewer system which is connected to the main and which serves one parcel or building. B. Size Criteria 1. The gravity sewer main lines shall be a minimum of eight inch (8") in diameter except that dead end lines of less than 300 feet can be 6 inches in diameter. Laterals shall be a minimum of 4" in diameter for single family residences and 6" for commercial, duplex and multi-family lots. 2. Laterals shall be placed at least 3' below top of curb grade elevation with 2% minimum slope and with a cleanout located per City Standard Detail S-1. 3. Minimum slopes for various pipe diameters shall be as shown in the following table. Pipe slopes less than those listed shall not be used without the approval from the City. Pipe Diameter (in) Slope (%) Slope ft/ft 6 0.50 0.0050 8 0.35 0.0035 10 0.25 0.0025 12 0.20 0.0020 15 0.15 0.0015 18 0.12 0.0012 4. The sewer mains shall be designed with the sewer flowing 3/4 full at peak flow condition or d/D = 0.75 where d is the depth of flow and D is the diameter of sewer pipe. 5. For gravity flow, use the Manning formula. The minimum design velocity shall be 2 fps for the design flow, and the design "n" factor shall be 0.013.
    [Show full text]
  • Low Pressure Sewer a Proven Technology
    Low Pressure Sewer Solutions to Wet Weather Problems Michigan Water Environment Association WWAdCon 2014 Keith J McHale, P.E. Environment One Corporation Principles of Low Pressure Sewer ◦ What is a Low Pressure Sewer System ◦ Advantages of Low Pressure Sewer LPS Solutions to Wet Weather Problems ◦ Infiltration and Inflow (I&I) ◦ Basement flooding solution Agenda Wastewater collection systems that use individual residential pumps to convey the flow to a central treatment system, lift station, gravity sewer, or force main System consists of: ◦ Grinder pumps ◦ Small diameter pressure pipe Sewer main follows the natural contour of the land What is a LPS System First used in the early 1970’s Provides daily service to millions of users worldwide Demonstrated performance, high reliability, and low operating and maintenance costs Low Pressure Sewer A Proven Technology Gained popularity due to the ability to provide central sewer service to areas with gravity sewer could not be installed or the cost to do so was cost prohibitive ◦ High ground water ◦ Lake communities ◦ Rural areas ◦ Flat terrain ◦ Undulating terrain ◦ Rocky ground conditions Early Development Experience and demonstrated advantages have expanded the use of low pressure sewer Competitive alternative to convention gravity sewer ◦ Flexibility ◦ Lower capital cost ◦ Construction phasing ◦ Increased construction schedule ◦ Lower environment impact and social costs Wider Acceptance The System • Grinder pump unit is located in the yard or basement of each home The System •
    [Show full text]
  • Sanitary Sewer Overflow Report Side a Category 1: Discharge of Untreated Or Partially Treated Wastewater of Any Volume Resulting
    Sanitary Sewer Overflow Report Side A Category 1: Discharge of untreated or partially treated wastewater of any volume resulting from a sanitary sewer system failure of flow condition that either (1) reaches surface water and/or drainage channel tributary to a surface water; OR (2) Reached a Municipal Separate Storm Sewer System (MS$) and was not fully captured and returned to the sanitary sewer system or otherwise captured and disposed of properly. Category 2: Discharge of untreated or partially treated wastewater greater than or equal to 1,000 gallons resulting from a sanitary sewer system failure or flow condition that either (1) Does not reach surface water, a drainage channel, or an MS4, OR (2) The entire SSO discharged to the storm drain system was fully recovered and disposed of properly. Category 3: All other discharges of untreated or partially treated wastewater resulting from a sanitary sewer system failure or flow condition. Spill from Private Lateral Describe in detail the basis for choosing the spill category: IMMEDIATE NOTIFICATION: If this is a Category 1 spill greater than or equal to 1,000 gallons, contact CalEMA within 2 hours at (800) 852-7550. A. SPILL LOCATION Spill Location Name: Latitude Coordinates*: Longitude Coordinates: Street Name and Number: Nearest Cross Street: City: Rancho Palos Verdes Zip: 90275 County: Los Angeles Spill Location Description: B. SPILL DESCRIPTION Spill Appearance Point (check one or more): Building/Structure Force Main Gravity Sewer Pump Station Other Structure (i.e. cleanout) Manhole-Structure ID# Other (specify): Did the spill reach a drainage channel and/or surface water: Yes (Category 1) No If the spill reached a storm sewer, was it fully captured and returned to the Sanitary Sewer? Yes No (Cat.
    [Show full text]
  • 2-1 INTRODUCTION SECTION 2 SANITARY SEWER DESIGN and CONSTRUCTION REQUIREMENTS the City of Battle Ground's Engineering Departmen
    SECTION 2 SANITARY SEWER DESIGN AND CONSTRUCTION REQUIREMENTS 2-1 INTRODUCTION The City of Battle Ground's Engineering Department provides technical management, comprehensive planning, and sound engineering to expand and maintain sewer collection and conveyance systems for service to residential, commercial, and industrial customers in a safe, environmentally protective manner. As of December 2006, the City has nearly 53 miles of piping dedicated to the collection of wastewater within the City's sewer area. Sanitary sewers are designed to collect the domestic sewage and industrial wastewater from residential and commercial sewer customers. They also deliver the collected wastewater to the Salmon Creek Wastewater Treatment Plant. These systems are not designed to handle flows from street or roof drainage. Materials and construction methods shall be in conformance with the most current version of the Standard Specifications for Road, Bridge & Municipal Construction as prepared by Washington State Department of Transportation. City-approved Engineering plans, stamped by a qualified engineer licensed in the State of Washington, will be reguired for sewer improvements: If a public sewer main extension is required, or If the City of Battle Ground Engineering Department determines public sewer service requires special approval and inspection. Developing properties must extend utility lines to the site, across the frontage and through the property, to allow connection and provide for future extensions for the development of adjacent parcels consistent with the General Sewer Plan. Proposed sewer main sizes, elevations, alignments and capacities must be designed in accordance with the latest General Sewer Plan or other appropriate master plans as determined by the City staff for overall system development.
    [Show full text]
  • Sewer Design Guide (Revised May, 2015)
    Sewer Design Guide (Revised May, 2015) City of San Diego Public Utilities Department 9192 Topaz Way • San Diego, CA 92123 Tel (858) 292-6300 Fax (858) 292-6310 Sewer Design Guide PREFACE The Sewer Design Guide is a guide for the engineer when planning and designing wastewater facilities and should be used for both public facilities and private facilities which serve multiple lots. This guide summarizes and outlines relevant City policies, applicable codes, and engineering and operational practices and procedures that have been developed in an effort to establish a cost-effective, reliable, and safe wastewater collection system. Also to be considered and used in conjunction with this design guide are all applicable current standard drawings, specifications, codes, laws and industry requirements for the planning and design of wastewater infrastructures. This guide is not intended to be an instructional text and is not a substitute for professional experience, nor is it meant to relieve the design engineer from his/her responsibility to use good engineering judgment. The design engineer shall be responsible for providing a design that, within industry standards, can be safely repaired and maintained, will provide good service and life, and will not create a public nuisance or hazard. Under most conditions, this guide should serve as a minimum standard. However, it is not meant to preclude alternative designs when the standards cannot be met, or when special or emergency conditions warrant, as long as proper authorization is obtained. The Public Utilities Department encourages “partnering”, the creation of an open working relationship between staff in each section/department and our customers, to promote achievement of mutual and beneficial goals.
    [Show full text]
  • SANITARY SEWER EVALUATION of INFLOW/INFILTRATION REDUCTION TECHNIQUES by Geoffrey Trent Vanallen a Thesis Submitted to the Facul
    SANITARY SEWER EVALUATION OF INFLOW/INFILTRATION REDUCTION TECHNIQUES by Geoffrey Trent VanAllen A Thesis Submitted to the Faculty of The College of Engineering and Computer Science in Partial Fulfillment of the Requirements for the Degree of Master of Science Florida Atlantic University Boca Raton, Florida May 2015 Copyright by Geoffrey VanAllen 2015 ii ACKOWLEDGEMENTS I am using this opportunity to express my gratitude to everyone who supported me throughout the course of this project. I am thankful for their aspiring guidance, invaluably constructive criticism and friendly advice during the project work. I am sincerely grateful to them for sharing their truthful and illuminating views on a number of issues related to the project. iv ABSTRACT Author: Trent VanAllen Title: Sanitary Sewer Evaluation of Inflow/Infiltration Reduction Techniques Institution: Florida Atlantic University Thesis Advisor: Dr. Frederick Bloetscher Degree: Masters of Science Year: 2015 Substantial savings in operations can be achieved by reducing the amount of wastewater that must be pumped and treated. Utilities have long dealt with the infiltration and inflow (I and I) issues in their system by televising their pipes and identifying leak points, but this primarily addresses only the infiltration part of “I and I.” Inflow, which creates hydraulic issues during rain events, leads to sanitary sewer overflows and can subject the utility to fines from regulatory agencies. As a result, dealing with the inflow portion of I and I is needed. The goal of this thesis is to differentiate inflow and infiltration from baseflow and to determine the effectiveness of different methods used to reduce inflow and infiltration in sanitary sewer lines.
    [Show full text]
  • Federal Facility Technical Standards
    FEDERAL FACILITY TECHNICAL STANDARDS TABLE OF CONTENTS Table of Contents .......................................................................................................................... 1 List of Figures 4 List of Tables 4 SECTION 1 INTRODUCTION AND PURPOSE ............................................................... 1-1 1.1 INTRODUCTION ......................................................................................................... 1-1 1.2 PURPOSE ..................................................................................................................... 1-1 1.3 SUMMARY OF THE FEDERAL FACILITY TECHNICAL STANDARDS ............ 1-1 1.4 TECHNICAL STANDARDS REQUIREMENTS, SUBMITTALS & SCHEDULES 1-3 SECTION 2 DEFINITION OF TERMS .............................................................................. 2-1 SECTION 3 PRE-REHAB FLOW, PRESSURE, RAINFALL (FPR) MONITORING AND DATA COLLECTION .................................................................................................... 3-1 3.1 REVIEW OF EXISTING INFORMATION ................................................................. 3-1 3.1.1 Sanitary Sewer Overflow Characterization ........................................................... 3-1 3.1.2 Prior Studies/Planned Construction ....................................................................... 3-2 3.1.3 Engineering and Operations ................................................................................... 3-3 3.1.4 Other Performance Documentation ......................................................................
    [Show full text]
  • Modelling Concrete Deterioration in Sewers Using Theory and Field
    Cement and Concrete Research 77 (2015) 82–96 Contents lists available at ScienceDirect Cement and Concrete Research journal homepage: http://ees.elsevier.com/CEMCON/default.asp Modelling concrete deterioration in sewers using theory and field observations T. Wells ⁎,R.E.Melchers Centre for Infrastructure Performance and Reliability, School of Engineering, The University of Newcastle, Callaghan, New South Wales 2308, Australia article info abstract Article history: Samples of new and 70 year old pre-corroded OPC concrete were exposed for up to 48 months in 6 sewers Received 24 February 2015 throughout Australia. Corrosion losses at each site followed the bi-linear trend originally proposed by Wells Accepted 13 July 2015 and Melchers [1]. During an initial phase (lasting b2 years) negligible loss of material occurs however once the Available online 31 July 2015 surface pH = 6 losses commence and accumulate linearly at a rate that is likely to remain constant over time. Cor- rosion rates were found to be sensitive to humidity but insensitive to concrete alkalinity. A first pass model which Keywords: Reaction (A) predicts the rate of concrete sewer pipe corrosion from a knowledge of local average sewer gas temperature, hu- Corrosion (C) midity and H2S concentrations was also developed. The equation predictions were in good agreement with rates Concrete (E) determined from field observation and historical data. Modelling (E) © 2015 Published by Elsevier Ltd. 1. Introduction part of the sewer submerged in wastewater. The sulphate reducing bac- teria (SRB) present in the biofilms convert the sulphates in the waste- Long-term deterioration is a major challenge for the continued reli- water to H2S.
    [Show full text]