Single Zone VAV Discover How to Save Money, Reduce Energy Consumption and Lower Sound Levels

Total Page:16

File Type:pdf, Size:1020Kb

Single Zone VAV Discover How to Save Money, Reduce Energy Consumption and Lower Sound Levels Dening Quality. Building Comfort. Single Zone VAV Discover how to save money, reduce energy consumption and lower sound levels. What is single zone VAV? ingle zone VAV, or single zone variable air volume, is an HVAC application in which the HVAC unit varies the airflow at constant temperature to provide space temperature control. A constant volume HVAC unit suppliesS constant airflow with variable temperature to provide temperature control. In the cooling mode, to meet ventilation requirements, the fan operates continuously and the compressor cycles on and off to meet the space cooling load. The fan and compressor operate at full capacity until the temperature drops to a set lower limit below the setpoint; then the compressor turns off. The compressor turns on again at full capacity once the space temperature increases to a set upper limit above the setpoint. The on/off nature of the constant volume unit causes the temperature to constantly fluctuate above and below the room setpoint temperature. In a single zone VAV unit, a variable speed fan controls the amount of airflow provided to the space by modulating the fan motor speed based on the difference between the actual space temperature and the temperature setpoint. The modulating compressor uses the temperature of the supply air leaving the unit to determine how much refrigerant flow is needed to maintain the supply air temperature setpoint. Packaged Single Zone VAV System Variable Cooling Frequency Drive Outdoor Coil Air Intake Filters Return Air Damper Variable Supply Capacity Air Sensor Compressor Exhaust Air Zone Return Supply Thermostat Air Air The fan and compressor continue to modulate to precisely meet the desired space temperature. For part load conditions, the single zone VAV unit will operate at a lower fan speed for a greater amount of time, saving valuable energy and providing the space with more constant temperature and humidity control. HVAC systems generally operate at part load conditions for a majority of the year, and during these part load conditions the operation of a single zone VAV system provides many benefits. First, a single zone VAV system will operate at a lower fan speed than a constant volume system, resulting in less fan energy consumption. Second, with the modulation capabilities of both the fan and compressor a single zone VAV system can provide precise temperature control and additional passive dehumidification. Third, the modulation capabilities of the compressor reduce the amount of compressor on/off cycling, reducing wear on the compressor and providing greater energy savings than hot gas bypass systems. Fourth, lower fan speeds reduce the amount of sound produced by the supply fan. Finally, with the entire modulating control for part load operation provided within the HVAC unit, a single zone VAV system is simple to install, set up and maintain. 2 Single zone VAV is used for areas where the occupancy or space cooling needs vary throughout the day such as classrooms, conference rooms, assembly halls, auditoriums, libraries, hospitals, supermarkets, convenience stores, restaurants, churches, health clubs, museums, office buildings, manufacturing facilities, lodgings, retail buildings, warehouses, etc. AAON is leading the industry in single zone VAV technology with both variable speed fans and variable capacity compressors which have a wide range of modulation capabilities that adapt to full and part load conditions. Benefits of single zone VAV include a more comfortable indoor environment with precise space temperature control and improved humidity control, significant energy savings, less wear on the compressor, a reduction in fan noise and simple installation and maintenance. Single Zone VAV - Required by Energy Standards ingle zone variable air volume is required in two of the most prominent national energy standards, ANSI/ ASHRAE/IES Standard 90.1-2010 and ANSI/ASHRAE/IES Standard 189.1-2009. Following are excerpts fromS the ASHRAE standards showing the requirement for Single Zone Variable-Air-Volume applications. Standard 90.1-2010 Purpose: The purpose of this standard is to provide minimum requirements for the energy- efficient design of buildings except low-rise residential buildings. ANSI/ASHRAE/IES Standard 90.1-2010. Section 6.4.3.10 Single Zone Variable-Air-Volume Controls. HVAC systems shall have variable airflow controls as follows: a. Air handling and fan-coil units with chilled-water cooling coils and supply fans with motors greater than or equal to 5 hp shall have their supply fans controlled by two-speed motors or variable-speed drives. At cooling demands less than or equal to 50%, the supply fan controls shall be able to reduce the airflow to no greater than the larger of the following: 1. One half of the full fans speed, or 2. The volume of outdoor air required to meet the ventilation requirements of Standard 62.1. b. Effective January 1, 2012, all air-conditioning equipment and air-handling units with direct expansion cooling and a cooling capacity at AHRI conditions greater than or equal to 110,000 Btu/h that serve single zones shall have their supply fans controlled by two-speed motors or variable-speed drives. At cooling demands less than or equal to 50%, the supply fan controls shall be able to reduce the airflow to no greater than the larger of the following: 1. Two-thirds of the full fan speed, or 2. The volume of outdoor air required to meet the ventilation requirements of Standard 62.1. Standard 189.1-2009 Purpose: The purpose of this standard is to provide minimum requirements for the siting, design, construction, and plan for operation of high performance, green buildings to: a. Balance environmental responsibility, resource efficiency, occupant comfort and well being, and community sensitivity, and b. Support the goal of development that meets the needs of the present without compromising the ability of future generations to meet their own needs. 3 ANSI/ASHRAE/IES Standard 189.1-2009. Section 7.4.3.7 Controls. The following requirements shall apply: a. DX systems with a capacity greater than 65,000 Btu/h (19 kW) shall have a minimum of two stages of cooling capacity. b. Air handling and fan-coil units with chilled-water cooling coils and supply fans with motors greater than or equal to 5 hp shall have their supply fans controlled by two-speed motors or variable-speed drives. At cooling demands less than or equal to 50%, the supply fan controls shall be able to reduce the airflow to no greater than the larger of the following: 1. One half of the full fans speed, or 2. The volume of outdoor air required to meet the ventilation requirements of ANSI/AHSRAE Standard 62.1. c. All air-conditioning equipment and air-handling units with direct expansion cooling and a cooling capacity at AHRI conditions greater than or equal to 110,000 Btu/h (32.2 kW) that serve single zones shall have their supply fans controlled by two-speed motors or variable speed drives. At cooling demands less than or equal to 50%, the supply fan controls shall be able to reduce the airflow to no greater than the larger of the following: 1. Two-thirds of the full fan speed, or 2. The volume of outdoor air required to meet the ventilation requirements of ANSI/ASHRAE Standard 62.1. d. All DX and chilled-water VAV units shall be equipped with variable-speed fans that result in less than 30% power at 50% flow. Energy Savings ne of the main advantages of varying the fan speed is energy savings. It takes less energy to run a Ofan at lower rotational speeds. The fan law that relates fan input horsepower to fan rotational speed is: 5 3 D2 rpm2 t2 HP21= HP :: : c D1 m c rpm1 m t1 where D is the fan diameter, is the air density, HP is the input horsepower, and rpm is the fan rotational speed. This law says that, assuming the diameter and air density do not change, the fan power input is proportional to the cube of the fan rotational speed: 1 1 5 3 3 D2 rpm2 t2 rpm2 HP21==HP :: ::& HP21HP c D1 m ccrpm1 mmt1 rpm1 4 torque airflow brake horsepower For the same fan diameter and air 100% conditions, cutting the fan rotational 90% speed in half cuts the required 80% 70% input horsepower by eight! This law 60% is illustrated graphically in Figure 50% 1, where brake horsepower is the 40% amount of input power needed for the 30% given fan rotational speed. 20% 10% 0% A single zone VAV unit also saves 0 300 600 900 1200 1500 1800 2100 energy due to reduced cycling losses fan speed (rpm) in the compressor. When power is Figure 1: Brake Horsepower, Torque, and Airflow as a Percentage of Full first applied to a motor, the current is Capacity versus Fan Speed significantly higher for a short period of time until the motor reaches its normal operating current. This initial inrush current can be as much as twenty times the normal operating current. Fans and compressors consume significantly more power when the motor is first turned on than at steady state operation. This initial inrush does no useful work but is required to take the motor from a stopped state to a state of motion. In addition to the inrush current, the compressor also loses energy during on/off cycling due to the work the compressor does to initiate the flow of refrigerant through the compressor. As the compressor is turned on, a pressure difference is created from the suction to the discharge of the compressor to start the flow of refrigerant. It takes more work to initially create this pressure difference and start the refrigerant flow than it does to maintain the refrigerant flow during reduced load.
Recommended publications
  • Hvac System Covid Procedures
    HVAC SYSTEM COVID PROCEDURES August 17, 2020 Prepared by: Johnson Roberts Associates 15 Properzi Way Somerville, MA 02143 Prepared for: City of Cambridge Executive Summary The HVAC COVID procedures are a compilation of Industry Standards and CDC recommendations. However, it should be noted that good PPE (personal protective equipment), social distancing, hand washing/hygiene, and surface cleaning and disinfection strategies should be performed with HVAC system measures, as studies have shown that diseases are easily transmitted via direct person to person contact, contact from inanimate objects (e.g. room furniture, door and door knob surfaces) and through hand to mucous membrane (e.g. those in nose, mouth and eyes) contact than through aerosol transmission via a building’s HVAC system. Prior to re-occupying buildings, it is recommended that existing building HVAC systems are evaluated to ensure the HVAC system is in proper working order and to determine if the existing system or its associated control operation can be modified as part of a HVAC system mitigation strategy. Any identified deficiencies should be repaired and corrected, and if the building HVAC system is a good candidate for modifications those measures should be implemented. In general HVAC system mitigation strategies should include the following recommendations: 1. Increase Outdoor Air. The OA increase must be within Unit's capacity in order to provide adequate heating or cooling so Thermal Comfort is not negatively impacted. Also use caution when increasing OA in polluted areas (e.g. High Traffic/City areas) and during times of high pollen counts. 2. Disable Demand Control Ventilation where present.
    [Show full text]
  • VAV Systems, on the Other Hand, Are Designed to Simultaneously Meet a Variety of Cooling and Heating Loads in a Relatively Efficient Manner
    PDHonline Course M252 (4 PDH) HVAC Design Overview of Variable Air Volume Systems Instructor: A. Bhatia, B.E. 2012 PDH Online | PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.PDHonline.org www.PDHcenter.com An Approved Continuing Education Provider www.PDHcenter.com PDH Course M252 www.PDHonline.org HVAC Design Overview of Variable Air Volume Systems A. Bhatia, B.E. VARIABLE AIR VOLUME SYSTEMS In central air conditioning systems there are two basic methods for delivering air to the conditioned space 1) the constant air volume (CAV) systems and 2) the variable air volume (VAV) systems. As the name implies, constant volume systems deliver a constant air volume to the conditioned space irrespective of the load with the air conditioner cycling on and off as the load varies. The fan may or may not continue to run during the off cycle. VAV systems, on the other hand, are designed to simultaneously meet a variety of cooling and heating loads in a relatively efficient manner. The system achieves this by varying the distribution of air depending on the cooling or heating loads of each area. The air flow variation allows for adjusting the temperature in a single zone without changing the temperature of air in the whole system, minimizing any instances of overcooling or overheating. This flexibility has made this one of the most popular HVAC systems for large buildings with varying conditioning needs such as office buildings, schools, or apartments. How a VAV system works? What distinguishes a variable air volume system from other types of air delivery systems is the use of a variable air volume box in the ductwork.
    [Show full text]
  • Variable Air Volume Fundamentals Belimo Automation FZE
    ASHRAE Qatar Oryx Chapter Qatar University, Doha-Qatar 20th April 2013 Variable Air Volume Fundamentals Belimo Automation FZE Speaker: Ahmed Khatib Content • VAV Overview and core concepts • Keys of control loop of VAV terminal unit • Fundamentals of VAV terminal unit Parts, Responsibility, Flow measurement, Probe installation & placement, c-factor Pressure drop, Specification, Information and Accuracy • VAV Flow-sensors • Linearization and calibration • Conclusions Target: • Ductwork for VAV systems should be designed for the lowest practical static pressure loss, especially ductwork closest to the fan or air- handling unit. • VAV systems must be selected to operate with efficiency and stability throughout the operating range. • Sound data for VAV units should be obtained according to the procedures specified by the latest ARI Standard 880. • General design consideration and precautions. VAV Overview A variable-air-volume (VAV) system is a single-path system that controls zone temperature by modulating airflow while maintaining constant supply air temperature. VAV terminal units, located at each zone, adjust the quantity of air reaching each zone depending on its load requirements. Reheat coils may be included to provide required heating for perimeter zones. A VAV boxes provide constant or variable airflow depending on the temperature demands of the space. As the temperature raises the VAV damper opens to send a designed amount of airflow to the space/ or room. There are many different types of VAV units: . Single Duct / cooling only, or cooling with reheat . Dual Duct terminal . Induction VAV terminal . Parallel Flow Fan Powered VAV terminal . Series Flow Fan Powered VAV terminal VAV Core concept VAV terminals can also be classified as: VAV - Pressure Independent: A pressure independent teriminal unit is equipped with a flow sensing controller that can be set to limit maximum and minimum primary air discharge from terminal unit.
    [Show full text]
  • Performance Improvement of Airflow Distribution and Contamination Control for an Unoccupied Operating Room
    Performance improvement of airflow distribution and contamination control for an unoccupied operating room F.J. Wang1,*, T.B. Chang2, C.M. Lai3, Z.Y. Liu1 1Department of Refrigeration, Air Conditioning and Energy Engineering, National Chin- Yi University of Technology, Taichung, Taiwan. 2Institute of Energy Engineering, Southern Taiwan University, Tainan, Taiwan. 3Department of Civil Engineering, National Cheng Kung University, Tainan, Taiwan. ABSTRACT The HVAC systems for operating rooms are energy-intensive and sophisticated in that they operate 24 hours per day year-round and use large amount of fresh air to deal with infectious problems and to dilute microorganisms. However, little quantitative information has been investigated about trade-off between energy-efficient HVAC system and indoor environment quality especially when the operating room is not occupied. The objective of this study is to present the field measurement approach on performance evaluation of the HVAC system for an unoccupied operating room. Variable air volume terminal boxes were conducted to verify the compromise of energy-saving potential and indoor environment parameters including particle counts, microbial counts, pressurization, temperature and humidity. Field measurements of a full-scale operating room have been carried out at a district hospital in Taiwan. Numerical simulation has been applied to evaluate the air flow distribution and concentration contours while conducting the velocity reduction approach in the unoccupied operating room. The results reveal that it is feasible to achieve satisfactory indoor environment by reducing the supply air volume (or velocity) in the unoccupied operating room. Optimal face velocity of HEPA filter and percentage of damper opening for the variable air volume terminal boxes could be obtained through compromising of indoor environment quality control and energy consumption.
    [Show full text]
  • System Controls Engineering Guide
    SECTION G Engineering Guide System Controls System Controls Engineering Guide Introduction to VAV Terminal Units The control of air temperature in a space requires that the loads in the space are offset by some means. Space loads can consist of exterior loads and/or interior loads. Interior loads can consist of people, mechanical equipment, lighting, com puters, etc. In an 'air' conditioning system compensating for the loads is achieved by introducing air into the space at a given temperature and quantity. Since space loads are always fluctuating the compensation to offset the loads must also be changing in a corresponding manner. Varying the air temperature or varying the air volume or a combination of both in a controlled manner will offset the space load as required. The variable air volume terminal unit or VAV box allows us to vary the air volume into a room and in certain cases also lets us vary the air temperature into a room. YSTEM CONTROLS YSTEM S The VAV terminal unit may be pressure dependent or pressure independent. This is a function of the control package. ENGINEERING GUIDE - Pressure Dependent A device is said to be pressure dependent when the flow rate passing through it varies as the system inlet pressure fluctuates. The flow rate is dependent only on the inlet pressure and the damper position of the terminal unit. The pressure dependent terminal unit consists of a damper and a damper actuator controlled directly by a room thermostat. The damper is modulated in response to room temperature only. Since the air volume varies with inlet pressure, the room may experience temperature swings until the thermostat repositions the damper.
    [Show full text]
  • HVAC Operational Adjustments Can Help Mitigate the Spread of COVID-19
    Fan Application ® FA/131-20 A technical bulletin for engineers, contractors and students in the air movement and control industry. HVAC Operational Adjustments Can Help Mitigate the Spread of COVID-19 In response to the COVID-19 pandemic, the American A dedicated ventilation unit provides 100% outdoor Society of Heating, Refrigerating and Air-Conditioning air and controls the latent load, while air handling Engineers (ASHRAE) has published guidelines units (AHUs) control the space sensible load. VAV for HVAC system operation in commercial and systems mix high percentages of outdoor air with educational buildings to help mitigate the spread return air to maintain indoor temperature and of COVID-19 via airborne respiratory droplets. The humidity. Figure 2 shows a single-zone VAV guidelines fall into three general categories: system serving a gymnasium. 1. Increased ventilation 2. Increased filtration efficiency 3. Electronic air cleaners These HVAC system upgrades can pose challenges to building operation and energy usage. However, properly designed dedicated outdoor air systems (DOAS) and variable air volume (VAV) systems help minimize the challenges. DOAS and VAV systems provide high percentages of conditioned outdoor air into buildings. Many of the upgrades recommended by ASHRAE are easily implemented with these systems. Increased Ventilation Increased ventilation dilutes the concentration of indoor contaminants, including infectious respiratory droplets, and mitigates the spread of COVID-19 via airborne transmission.1 DOAS and VAV systems are Figure 2: A gymnasium served well suited for increased ventilation recommendations by a single-zone VAV system. because each has features available to control and condition high percentages of outdoor air efficiently.
    [Show full text]
  • Variable Air Volume (VAV) Air Handling System Control What Makes VAV Box Performance Better Technology
    Air flow Measuring Technology Air Flow Variable air volume (VAV) Air Handling System Control What Makes VAV Box Performance Better Technology Factory Calibrated Yong Zhao Solution Johnson Controls Australia 1 Johnson Controls Variable air volume (VAV) Air Handling System VAV systems are vary popular in many modern buildings • VAV systems contain many zones with diverse airflow needs • VAV systems have “bad” zones • VAV systems are dynamic • VAV systems have minimum airflow zones 2 Johnson Controls Variable air volume (VAV) Terminal Unit Consider the relationship between damper position and airflow System is sensitive as damper starts to open, so large proportional band is needed When damper is almost open, system is not very sensitive, so a small proportional band is needed Consider the “optimal” proportional band for a mixed air control loop It will vary by a factor of ten between summer and winter Good commissioning is critical Air Conventional PI control resulted in Flow Systems tuned for “worst case” (typically low load) conditions and unresponsive at other times Comfort problems High energy (fan consumption) cost Damper Position 3 Johnson Controls Variable air volume (VAV) Terminal Unit 1 2 3 4 5 Velocity Sensor Flow Damper Mixing Box VAV Brain Reheat measures air flow controls air flow reduces noise calculates & controls option air flow 4 Johnson Controls Variable air volume (VAV) Terminal Unit What makes VAV box performance better 1. Air flow measuring – Velocity sensor more accurate to measure the air flow = better control (less hunting) = less temperature variation = less energy consumption not easy to maintain accuracy when flow rate is lower 2.
    [Show full text]
  • Electing the Inlet Size of a Variable Air Volume (VAV) Terminal Box Requires
    The following article was published in ASHRAE Journal, March 2004. © Copyright 2004 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes only. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. By Steven T. Taylor, P.E., Fellow ASHRAE, and Jeff Stein, P.E., Member ASHRAE schematic for a parallel fan-powered VAV (FPV) box. For both box types, Vmax is electing the inlet size of a variable air volume (VAV) terminal box typically the design cooling airflow rate. For VRH boxes, V is typically selected S requires the consideration of five factors: (1) pressure drop across min S to be the largest of the following: the box; (2) ability of the VAV box controller to measure and control 1. The airflow required to meet the de- the desired minimum and maximum airflow setpoints; (3) first costs of sign heating load at a supply air tem- the VAV box, its installation, and controls; (4) noise generation; and (5) perature that is not too warm, e.g., ≤ 90°F (≤ 32°C). Warmer temperatures tend to space constraints. result in poor temperature control due to stratification and short circuiting.2 The first three considerations affect using pressure independent control 2. The airflow required to prevent energy costs and first costs and ideally logic. Pressure independent controls use “dumping” and poor distribution. This should be balanced to minimize life- two cascading control loops. The first limit depends on the diffuser style and cycle cost (LCC). The last two consider- loop controls space temperature; its out- sizing.
    [Show full text]
  • VAV Diffusers Engineering Guide
    Engineering Guide VAV Diffusers Please refer to the Price Engineer’s HVAC Handbook for more information on VAV Diffusers. Variable Air Volume Diffusers Engineering Guide Diffuser Types Conventional air distribution systems typically group several rooms into a zone that is controlled by a single thermostat. Because rooms Figure 1: Thermally powered VAV diffuser within the zone can have different heating/cooling requirements, the system’s response to heating/cooling loads within the zone may not be consistent with load requirements. The result can be a system that compromises the comfort of the occupants in each room by providing a blanket response to individual needs. As well, there is resulting system inefficiency due to the overheating/overcooling of rooms within the building. Self-modulating Variable Air Volume (VAV) diffusers allow for smaller, comfortable zones. They monitor local space conditions and regulate air flow to satisfy the occupants’ selected level of comfort. As air flow varies, the unique design of VAV diffusers adjusts an integral damper to maintain face discharge velocities and excellent throw characteristics. VAV diffusers can help solve the inconsistent throws or dumping that may occur with some overhead diffusers due to varying supply conditions. Several different types of VAV diffusers exist, however most can be grouped into two models: Thermally Powered and Electronically Powered. Thermally Powered VAV Diffusers Thermally powered VAV diffusers, shown in Figure 1, commonly use thermal actuators to modulate the flow rate of supply air into a room according to a desired temperature setting. The diffuser works independent of a BAS and does not require external power.
    [Show full text]
  • Industrial Application Variable Air Volume Controller
    What is a Industrial Application Variable Air Volume (VAV) Variable Air Volume Controller Controller? How does it work? Temperatures The Variable Air Volume A VAV system maintains the air VAV systems are most easily (VAV) controller is an supply at a constant temperature understood by first considering them electronic device for while individual zone thermostats as cooling applications. As the zone digital control of single vary the flow of air to each space temperature increases and if the Air duct, dual duct, fan maintaining the desired zone Handling Unit is supplying cool air, powered, and supply/ temperature. This is unlike a constant the VAV controller opens the VAV exhaust VAV terminal volume system that maintains a box damper to allow more cool air to configurations. constant volume of airflow to the reach the space. space, but varies the temperature of Along with the control the air stream in response to space The specific amount of air volume capability of the VAV temperature changes. VAV systems required to maintain a particular zone box, the controller are predominantly single duct, but temperature setpoint is dictated by can also integrate the about 15% are dual duct designs. the size of the space and the internal control of the room or and external heat loads. zone baseboard heat Air Handling System and lighting logic. In addition, since the size of the VAV The air handling system typically box dictates its maximum cooling maintains about 1 inch W.C. static capacity, a VAV box’s performance pressure inside the longest run of is dependent upon the mechanical duct work away from the supply fan.
    [Show full text]
  • Impact of Air-Side Economizer Control Considering Air Quality Index on Variable Air Volume System Performance
    ctbuh.org/papers Title: Impact of Air-side Economizer Control Considering Air Quality Index on Variable Air Volume System Performance Authors: Sang-Hyeon Cho, Department of Architectural Engineering, Hanyang University Joon-Young Park, Department of Architectural Engineering, Hanyang University Jae-Weon Jeong, Department of Architectural Engineering, Hanyang University Subject: Architectural/Design Keywords: Environment Structural Health Monitoring Publication Date: 2017 Original Publication: International Journal of High-Rise Buildings Volume 6 Number 1 Paper Type: 1. Book chapter/Part chapter 2. Journal paper 3. Conference proceeding 4. Unpublished conference paper 5. Magazine article 6. Unpublished © Council on Tall Buildings and Urban Habitat / Sang-Hyeon Cho; Joon-Young Park; Jae-Weon Jeong International Journal of High-Rise Buildings International Journal of March 2017, Vol 6, No 1, 101-111 High-Rise Buildings https://doi.org/10.21022/IJHRB.2017.6.1.101 www.ctbuh-korea.org/ijhrb/index.php Impact of Air-side Economizer Control Considering Air Quality Index on Variable Air Volume System Performance Sang-Hyeon Cho, Joon-Young Park, and Jae-Weon Jeong† Department of Architectural Engineering, College of Engineeing, Hanyang Univeristy, Seoul 04763, Korea Abstract The objective of this study is to determine the effectiveness of a modified air-side economizer in improving indoor air quality (IAQ). An air-side economizer, which uses all outdoor air for cooling, affects the building’s IAQ depending on the outside air quality and can significantly affect the occupants’ health, leading to respiratory and heart disease. The Air Quality Index (AQI), developed by the US Environmental Protection Agency (US EPA), measures air contaminants that adversely affect human beings: PM10, PM2.5, SO2, NO2, O3, and CO.
    [Show full text]
  • Variable Air Volume (VAV) for Laboratories
    145.pdf A SunCam online continuing education course Variable Air Volume (VAV) For Laboratories by Steven G. Liescheidt, PE, CCS, CCPR 145.pdf Variable Air Volume (VAV) For Laboratories A SunCam online continuing education course Overview: Variable Air Volume (VAV) systems have been used for many years in commercial HVAC systems for a variety of reasons. Energy savings in HVAC systems is where the future of good engineering needs to focus. This is also true in facilities where large amounts of outside air are needed to replace exhaust air such as in laboratory facilities. VAV systems have been used in laboratory exhaust and supply systems for years also. This is mainly done for energy savings and not so much for comfort. Applying VAV to labs is a challenge to the engineering due to the need to maintain pressurization control in the lab spaces and the need to exhaust the air from the building in a safe manner where the fume hood exhaust is forced away from the building and surrounding buildings so as not to be re-entrained into outside air intakes. In general, peak full load analysis and HVAC system equipment and component selection is fairly straight forward and simple to “design”. The challenge in “engineering” is understanding how to optimize a system from every aspect of energy savings, functional performance and comfort during the majority of the time that the system is in a “part load” condition. The understanding of part-load operation is what separates “engineering” from “design” in the HVAC industry. In order to “right size” an HVAC system for a lab it is essential to not only understand the full load conditions; but to also understand how the system and components of the system will respond to part load conditions.
    [Show full text]