Phase 1.1 Energy Projects McKinstry Essention, Inc., Contractor Puget Sound Solar LLC, Subcontractor

Daniel J. Evans Library

Photovoltaic System

Evergreen State College Phase 1.1 Energy Projects Submittals McKinstry Essention, Inc., Contractor Puget Sound Solar LLC, Subcontractor

Contents

3: System Description 4: Production calculations 7: Array location 8: Roof plan 9: Array Details 10: Schematic Diagrams 11: Panel ‘A’ details 12: Equipment schedule 13: Product cut sheets 28: Structural load charts

O&M’s: Contact list Warranties Drawings SMA Inverter manual Sunny Web Box manual Unirac RapidRac Manual Evergreen PV installation manual

Photovoltaic System Description

This photovoltaic system consists of (44) polycrystalline ES-A 205 watt modules installed in four rows on a Unirac RapidRac ballasted mounting system, facing due south on the fourth floor roof of the Daniel J. Evans Library.

The DC electricity generated is converted to, and synchronized with, the AC power in the building at 208 volts via two Sunny Boy SB5000US inverters, and fed into the building power system through an equipment distribution panel on the fourth floor. Any interruption of utility power to the building will cause the inverters to shut off, per UL 1741. When utility power is restored, after a five- minute wait, the inverters will resume operation automatically.

The performance of the system is monitored through the Sunny Web Box, a communication device that generates a web page that can be viewed by any computer connected by network to the Web Box, and by anyone on the world wide web via the Sunny Portal, a free service of SMA.

The system is self-regulating and normally requires no attention. SMA inverters automatically wake up each day and disconnect from the grid each night. PV mounting at low elevation angles, such as with the RapidRac usually leads to some accumulation of atmospheric dust and particulates at the lower edge of the modules. Due to the Library’s location in a forested area, dust will not be as much of a factor as will pollen. Some gentle cleaning may be needed from time to time.

The system is designed to be in service for decades of clean energy production.

3

System Design and Production Calculations

The roof of the Daniel J Evans Library offers excellent solar access but there are some obstacles on the skyline. The orientation of the building is 25 degrees East of South, so the clock tower only causes negligble shading. The other skyline object is the HVAC enclosure at the southwest corner of the fourth floor roof. This only causes minor shading near the end of the day from November through January, the darkest time of year. The tree line adds to the late-year losses.

The sun chart below shows the extent of shading. The net loss to this shading is about 2% of the total possible production.

The attached RETScreen model predicts an average production of 9.9 mWh/yr.

4 RETScreen® Solar Resource and System Load Calculation - Photovoltaic Project

Site Latitude and PV Array Orientation Estimate Notes/Range Nearest location for weather data Olympia, WA See Weather Database Latitude of project location°N 47.0 -90.0 to 90.0 PV array tracking mode- Fixed Slope of PV array ° 10.0 0.0 to 90.0 Azimuth of PV array ° 0.0 0.0 to 180.0

Monthly Inputs

Fraction of Monthly average Monthly Monthly average Monthly month daily radiation average daily radiation solar used on horizontal temperature in plane of fraction surface PV array Month (0 - 1) (kWh/m²/d) (°C) (kWh/m²/d) (%) January 1.00 1.03 3.5 1.24 - February 1.00 1.69 4.9 1.94 - March1.00 2.78 6.3 3.03 - April1.00 3.96 8.7 4.15 - May 1.00 5.01 11.9 5.11 - June1.00 5.59 14.9 5.63 - July 1.00 5.88 17.2 5.96 - August1.00 5.06 17.3 5.26 - September1.00 3.79 14.4 4.11 - October1.00 2.22 9.8 2.54 - November1.00 1.19 6.1 1.42 - December1.00 0.88 3.6 1.08 -

Annual Season of use Solar radiation (horizontal) MWh/m² 1.19 1.19 Solar radiation (tilted surface) MWh/m² 1.26 1.26 Average temperature°C 9.9 9.9

Load Characteristics Estimate Notes/Range Application type - On-grid Return to Energy Model sheet

Version 3.2 © Minister of Natural Resources Canada 1997 - 2005. NRCan/CETC - Varennes

11/3/2008; TESCpv.xls 5 RETScreen® Energy Model - Photovoltaic Project Training & Support

Site Conditions Estimate Notes/Range Project name Evergreen State College See Online Manual Project location Olympia, WA Nearest location for weather data - Olympia, WA Complete SR&SL sheet Latitude of project location °N 47.0 -90.0 to 90.0 Annual solar radiation (tilted surface) MWh/m² 1.26 Annual average temperature °C 9.9 -20.0 to 30.0

System Characteristics Estimate Notes/Range Application type - On-grid Grid type - Central-grid PV energy absorption rate % 100.0% PV Array PV module type - poly-Si PV module manufacturer / model # Evergreen Solar/ ES-240 See Product Database Nominal PV module efficiency % 13.0% 4.0% to 15.0% NOCT °C 45 40 to 55 PV temperature coefficient % / °C 0.40% 0.10% to 0.50% Miscellaneous PV array losses % 4.0% 0.0% to 20.0% Nominal PV array power kWp 9.02 PV array area m² 69.4 Power Conditioning Average inverter efficiency % 94% 80% to 95% Suggested inverter (DC to AC) capacity kW (AC) 8.5 Inverter capacity kW (AC) 9.0 Miscellaneous power conditioning losses % 2% 0% to 10%

Annual Energy Production (12.00 months analysed) Estimate Notes/Range Specific yield kWh/m² 143.1 Overall PV system efficiency % 11.3% PV system capacity factor % 12.6% Renewable energy collected MWh 10.561 Renewable energy delivered MWh 9.927 kWh 9,927 Excess RE available MWh 0.000 Complete Cost Analysis sheet

Version 3.2 © Minister of Natural Resources Canada 1997 - 2005. NRCan/CETC - Varennes

11/3/2008; TESCpv.xls 6 Evergreen State College PV Array Location McKinstry Essention, Inc., Contractor – Puget Sound Solar LLC, Subcontractor

Daniel J. Evans Library Level 5

7 ROOF PLAN

Evans Library Roof Plan

Level 5 (Fourth Floor Roof Plan)

8

Array Plan Detail

9

Panel ‘A’ One Line

PV System Schematic Diagram

10

Panel ‘A’ Location and Detail

11

Photovoltaic Equipment Schedule

Evergreen State College Phase 1.1 Energy Projects

McKinstry Essention, Inc., Contractor Puget Sound Solar LLC, Subcontractor

Item Quantity Description

PV Modules 44 Evergreen Solar ES-A 205 Inverters 2 SMA SB5000US Panel 'PV' 1 Square D QO312L125GRB Panel 'PV' c.b. 2 Square D 2-pole 30A QO230 Panel 'A' c.b. 1 ITE 60A 208V 3-pole QP Q360 Lockable Disconnect 1 Square D HU362RB Ballasted Mount 44 Unirac RapidRac Frame w/mount Ballasted Mount 11 Unirac RapidRac Frame only Monitoring 1 Sunny Web Box Interface 2 Sunny Boy RS-485 modules

12 NEW ES-A SERIES 200, 205 & 210 W photovoltaic panels Best power tolerance available A range of high quality String Ribbon™ solar panels offering exceptional performance, cost effective installation and industry-leading environmental credentials made with our revolutionary wafer technology.

• No power below nameplate Never pay for power you’re not getting

• Get up to 5W more than nameplate* For enhanced field performance

• Industry’s lowest voltage per watt rating Delivers the most cost-effective installs

• UL4703 certified cables For use with the highest efficiency transformer-less inverters

• New extended length cables Eliminates home-run wiring

• New lockable connectors** Complies with the latest codes for accessible arrays

• Most extensive range of mounting options Allows installs virtually anywhere and anyhow

• Smallest carbon footprint of any manufacturer For the greenest of the green

• 100% cardboard-free packaging Minimizes job site waste and disposal costs

• 5 year workmanship and 25 year power warranty ***

Born in the USA

*Maximum power up to 4.99 W above nameplate rating; **Locking sleeve not supplied with the panel. ***For full details see the Evergreen Solar Limited Warranty available on request or online. 13 This product is designed to meet UL 1703, UL 4703, UL Fire Safety Class C, IEC 61215 Ed.2 and IEC 61730 Class A standards. String Ribbon is a patented technology and registered trademark of Evergreen Solar, Inc.

Electrical Characteristics Mechanical Specifications Standard Test Conditions (STC)1 PANEL ID LABEL ES-A-200 ES-A-205 ES-A-210

-fa2* -fa2* -fa2* 2.2 4.9

2 mp

P 200 205 210 W 3.1 2.3 JUNCTION BOX tolerance P -0/+4.99 -0/+4.99 -0/+4.99 W (IP65) 8x ø.16 PANEL GROUNDING Pmp, max 204.99 209.99 214.99 W SERIAL NUMBER HOLE

Pmp, min 200.00 205.00 210.00 W

ηmin 12.7 13.1 13.4 % 32.5

3 CABLES Pptc 180.6 185.2 189.8 W (10 AWG, UL4703, PV-WIRE) Vmp 18.1 18.4 18.7 V

Imp 11.05 11.15 11.23 A 42.1

Voc 22.5 22.8 23.1 V

65.0 (+/-0.1) 10x ø.26 PANEL MOUNTING HOLE Isc 12.00 12.10 12.20 A ID LABEL FOR ¼" BOLT Nominal Operating Cell Temperature Conditions (NOCT)4 MC® LOCKABLE 0 CONNECTORS NOCT T 44.8 44.8 44.8 C (TYPE 4)

Pmax 146.4 150.1 153.7 W 26.7

Vmp 16.7 16.8 17.0 V 16.3 2.8 CLEAR ANODIZED 13.0 12x FRAME ALUMINUM FRAME Imp 8.76 8.93 9.04 A DRAINAGE HOLE 2.2 Voc 20.5 20.7 21.0 V 35.9 1.8 (+0.02/-0) 37.5 (+/-0.1) Isc 9.60 9.68 9.76 A

1 1000 W/m2, 25°C cell temperature, AM 1.5 spectrum; All dimensions in inches; panel weight 41 lbs 2 Maximum power point or rated power 3 2 At PV-USA Test Conditions: 1000 W/m , 20°C ambient temperature, Product constructed with 114 poly- solar cells, anti-reflective 1 m/s wind speed 4 800 W/m2, 20°C ambient temperature, 1 m/s wind speed, AM 1.5 spectrum tempered solar glass, EVA encapsulant, polymer back-skin and a double-walled * f-framed, a-low voltage, 2-matt blue (textured) cells anodized aluminum frame. Product packaging tested to International Safe Transit Association (ISTA) Standard 2B. All specifications in this product information sheet Low Irradiance conform to EN50380. See the Evergreen Solar Safety, Installation and Operation The typical relative reduction of module efficiency at an Manual and Mounting Design Guide for further information on approved installa- irradiance of 200W/m2 both at 25oC cell temperature and tion and use of this product. spectrum AM 1.5 is 0%. Due to continuous innovation, research and product improvement, the specifica- tions in this product information sheet are subject to change without notice. No rights can be derived from this product information sheet and Evergreen Solar Temperature Coefficients assumes no liability whatsoever connected to or resulting from the use of any information contained herein. α Pmp -0.45 %/ ºC

α Vmp -0.43 %/ ºC Partner: α Imp -0.02 %/ ºC

α Voc -0.32 %/ ºC

α Isc -0.003 %/ ºC System Design Series Fuse Rating5 20 A Maximum System Voltage (UL) 600 V

5 Also known as Maximum Reverse Current.

ELECTRICAL EQUIPMENT ES-A_200_205_210_US_010908; effective September 1st 2008 CHECK WITH YOUR INSTALLER

Worldwide Headquarters Customer Service - Americas and Asia 138 Bartlett Street, Marlboro, MA 01752 USA 138 Bartlett Street, Marlboro, MA 01752 USA Evergreen Solar, Inc. T: +1 508.357.2221 F: +1 508.229.0747 T: +1 508.357.2221 F: +1 508.229.074714 www.evergreensolar.com [email protected] [email protected]

Sunny WebBox TM

Web enabled data logging and control for alternative energy systems

System access from any Web browser - anywhere in the world

Recording of daily, monthly and annual energy yield via Sunny Portal TM

Remote plant diagnosis

Remote system configuration

Automatic data transfer at chosen intervals

Data storage and display via Ethernet

Compatible with all SMA utility interactive inverters

Low power consumption

Automated communication with Sunny Portal TM

The new Sunny WebBox from SMA is a powerful communications tool that allows the oper- ating data of your solar system to be logged and easily transmitted via modem or Ethernet to the Web or directly to your PC. It can also send the data to SMA’s new internet portal (Sunny Portal) which provides free long-term data storage and graphical display of your system data. Collected information is stored in common file formats so that you can use it in various spread- sheets, graphs or your own web site. The Sunny WebBox is extremely versatile; making the 17 storage, transmission, management and display of your system data easier than ever before. The new way to monitor your system

A new standard the internet is handled either by Ethernet The Sunny WebBox can also be used in in communication connection or telephone modem. Data combination with SMA's Sunny Portal Web transfer is automatic - all you have to do is site (www.sunnyportal.com). Our internet The Sunny WebBox provides complete plant to set the desired intervals. A single portal offers free graphical presentation of monitoring, remote diagnosis, data storage WebBox can monitor up to 50 Sunny Boy your plant data in charts and diagrams. and display at an affordable price. It fea- inverters, saving even more costs when The Sunny Portal is WebBox ready, simply tures an integrated HTTP web interface that used in larger Sunny Boy solar systems. set up an account and connect the WebBox allows you to access plant information via a to the internet. PC, regardless of operating system or browser type. Around the clock, around the world A perfect match The Sunny WebBox is the link between the Sunny Boy PV plant and its owner. It com- Check the status of your PV plant - from your Sunny WebBox and Sunny Portal are a bines computing power, storage capacity, home, your office or anywhere you may perfectly matched team. They offer you and versatile communication interfaces in a be. A PC with an internet browser is all that long-term storage of your plant compact enclosure. Networked with the is needed to access the WebBox. data, inform you about changes in plant Sunny Portal, the data-logger offers up-to- performance, and let you review the per- date display and control options on the The Sunny WebBox is equipped with its formance of your investment at any time, internet. own web server that is preconfigured to work from anywhere. with your internet browser. This allows you The Sunny WebBox supports RS232 or to view the output of your plant and the To learn more about this new method of RS485 protocols for data transfer to and operating channels of each inverter. You plant monitoring visit www.SunnyPortal.com. from all SMA utility interactive inverters. can also adjust the parameters of the Sunny We have set up demonstration accounts WebBox via your web browser. that allow you to view actual PV plants. Visit Data transfer and plant configuration via www.sunnyportal.com and see for yourself what the Sunny WebBox and Sunny Portal has to offer.

Customer plant in Sunny Portal, 10.4 kWp 18 Sunny Boy 700/1100U

external kWh counter

Solar Irradiation

Large Format Display via PC Outdoor Temperature Sunny Boy 1800/2500U

External Router

Sunny WebBox

Communication with inverters via: Ethernet Large Scale Display - RS485 Sunny Matrix - Ethernet, TCP/IP* Analog (*Sunny Central Only) Sunny Boy 6000U Modem

Sunny Central 125U

Specifications

Interfaces Power Requirements SMACOM RS485 Wall Transformer Typ. 300 mA @ 12 V (up to 50 inverters, max. 4000 ft. cable) (120 VAC 60Hz) Max. 1 A @ 12 V Power Consumption Max. 12W

Ethernet 10Mb / 100 Mb auto sensing Ambient Temperature Rating Ambient Temperature Range 0°C to 55°C Relative Humidity Range 5 % to 95 %, non-condensing External Data Storage SD-Card from 16 MB upwards Miscellaneous USB-Stick USB 2.0 Host Operating System Windows CE.NET Status Display 7 LED´s Mounting Options Wall mount, DIN rail mount, desktop Dimensions Size 8.85 x 2.25 x 5.11 in. (w x d x h) Options Weight 1.65 lb. Integrated Analog Modem

19 Supplied by: Web product Box, your right tomeet SMAhasthe communicationneeds. Sunny homeandcommercialadvanced handlingabilityofthe Beamwirelessaffordable monitorforboth use,tothe data system andcommunicationrelated awiderange products ofdata to suitany From offers applicationandbudget. SMA America the ofdatatechnologyproducts The SMAfamily [email protected] 530.273.4895 Grass Valley, CA.95945 12438 LomaRicaDr. SMA America,Inc. Sales Contact: · · · · Sunny DataControl View performance individualinverter Download stored datatoPC Access system parameters display Total plantoverview durch: · · · · · Sunny Beam www.sma-america.com Power supplied by integrated solarcell Data storage andindividualdisplay USB fordatatransfer toPC Wireless operation Monitor andrecord data inverter via Sunny DataControl · · · · Sunny Portal www.SunnyPortal.com Free registration at viainternet service Remote monitoringand of yoursystem data Storage andindividualdisplay to yourPVplant Free interactive access · SMA AmericaWebSite www.sma-america.com ument downloadsvisit For more informationanddoc- 20

WebBox Flyer 010506 · Specifications subject to change without notice. SMA does not assume any liability for errors or misprints. QO312L125GRB Load Center

Load Center , 125A, Main Type: Fixed - Factory installed main lugs, 3-Phase

Features and Specifications Application: Designed to meet residential, commercial and industrial requirements to protect electrical systems, equipment and people. Ampere Rating: 125A Enclosure Rating: NEMA 3R Catalog Reference Number: 1100CT9901 Enclosure Type: Outdoor/Rainproof Bus Material: Tin Plated Copper Approvals: UL Listed Cover Type: Surface Grounding Bar: Included Short Circuit Current Rating: 65kA Main Type: Fixed - Factory installed main lugs Maximum Single Pole Circuits: 12 Maximum Tandem Circuit Breakers: 0 Wire Size: #6 to 2/0 AWG(Al/Cu) Wiring Configuration: 4-Wire Phase: 3-Phase Spaces: 12 Depth: 4.52 Inches Voltage Rating: 208Y/120VAC - 240/120VAC Delta - 240VAC Delta Height: 18.92 Inches Width: 14.75 Inches

Copyright Schneider Electric USA. All rights reserved

21 QO230 Circuit Breaker

Miniature Circuit Breaker , 120/240VAC, 30A, 1-Phase

Features and Specifications For Use With: QO Load Centers, NQOD Panelboards/Interiors and Speed-D switchboard distribution panels Approvals: UL Listed - CSA Certified Catalog Reference Number: 0730CT9801 Circuit Breaker Type: Standard Features: VISI-TRIP trip indication Ampere Rating: 30A General Application: Provides overload and short circuit protection HACR Rated: Yes Voltage Rating: 120/240VAC Mounting Type: Plug-On Phase: 1-Phase Number of Poles: 2-Pole Short Circuit Current Rating: 10kA Space Required: 2 Terminal Type: Pressure Plate Type: QO Width: 1.50 Inches Height: 3.00 Inches Depth: 2.91 Inches Wire Size: #14-8 AWG(Al/Cu)

Copyright Schneider Electric USA. All rights reserved

22 Heavy Duty Safety Switches www.us.schneider-electric.com FOR CURRENT INFORMATION Table 3.12: 600 Volt—Single Throw Non-Fusible NEMA 4, 4X, 5 a Horsepower Ratings 304 Stainless Steel NEMA 12K NEMA 12, 3Rb (Max.) c NEMA 3R (for 316 stainless, see With Without NEMA 1 Volts ac Rating Indoor Rainproof page 3-7) Knockouts Knockouts System (A) (Bolt-on Hubs, page 3-9) Dust tight, Watertight (Watertight Hubs, (Watertight Hubs, dcd Corrosion Resistant page 3-9) page 3-9) 240 480 600 (Watertight Hubs, page 3-9) Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price 1Ø 3Ø 1Ø 3Ø 1Ø 3Ø 250 600 2 Wire (2 Blades)—600 Vac, 600 Vdc 30 —— — ——— — — 60 Use 3 Wire Devices —— — ——— — — 100 For 2 Wire Applications —— — ——— — — 200 —— — ——— — — 400 HU265 1833.00 HU265R 2509.00 HU265DS 8541.00 — — HU265AWK 2141.00 — — — — — — 50 50 600 HU266 3264.00 HU266R 5022.00 HU266DS 12303.00 — — HU266AWK 3605.00 — — — — — — 50 50 800 HU267 4978.00 HU267Re 8589.00 — — — — HU267AWK 8638.00 50 — 50 — 50 —— 50 1200 HU268 6817.00 HU268Re 11595.00 — — — — HU268AWK 11681.00 50 — 50 ——— 50 50 3 Wire (3 Blades)—600 Vac, 600 Vdc 30 HU361 186.00 HU361RB 325.00 HU361DS 1413.00 HU361A 459.00 HU361AWK 431.00 5 10 7-1/2 20 10 30 5 15 30 HU361EIf 425.00 HU361RBEIf 564.00 HU361DSEIf 1653.00 HU361AEIf 698.00 HU361AWKEIf 671.00 5 10 7-1/2 20 10 30 5 15 30 HU3612g 246.00 HU3612RBg 425.00 — — HU3612Ag 473.00 HU3612AWKg 444.00 5 10 7-1/2 20 10 30 5 15 60 HU362 325.00 HU362RB 584.00 HU362DS 1680.00 HU362A 583.00 HU362AWK 555.00 10 20 25 50 30 60 10 30 60 —— — —HU362DSEIf 1981.00 — — — — 10 20 25 50 30 60 10 30 100 HU363 522.00 HU363RB 817.00 HU363DS 3401.00 HU363A 843.00 HU363AWK 796.00 20 40 40 75 40 100 20 50 200 HU364 806.00 HU364RB 990.00 HU364DS 4640.00 HU364A 1131.00 HU364AWK 1069.00 15 60 50 125 50 150 40 50 400 HU365 1869.00 HU365R 2560.00 HU365DS 9529.00 — — HU365AWK 2682.00 — 125 — 250 — 350 50 50 600 HU366 3328.00 HU366R 5122.00 HU366DS 12708.00 — — HU366AWK 4474.00 — 200 — 400 — 500 50 50 800 HU367 6652.00 HU367R e 8700.00 — — — — HU367AWK 8731.00 50 250 50 500 50 500 50 50 1200 HU368 8947.00 HU368R e 11911.00 — — — — HU368AWK 11960.00 50 250 50 500 50 500 50 50 4 Wire (4 Blades)—600 Vac, 600 Vdc k 2Ø 3Ø 2Ø 3Ø 2Ø 3Ø 30 HU461h 551.00 — — HU461DS 1724.00 — — HU461AWKi 610.00 10 10 20 20 25 30 10j 15j 60 HU462h 609.00 — — HU462DS 2018.00 — — HU462AWK 672.00 20 20 40 50 50 60 10 30 100 HU463h 1098.00 — — HU463DS 4934.00 — — HU463AWK 1194.00 30 40 50 75 50 75 20 30 200 HU464h 1599.00 — — HU464DS 7496.00 — — HU464AWK 1888.00 50 60 50 125 50 150 40 50 400 HU465 3467.00 — — — — — — HU465AWK 3781.00 — 125 — 250 — 350 50 50 600 HU466 6048.00 — — — — — — — — — 200 — 400 — 500 50 50 6 Wire (6 Blades)—600 Vack 3Ø 3Ø 3Ø 30 —— — —HU661DS 7935.00 — — HU661AWKl 2238.00 — 10 — 20 — 30 —— 60 —— — —HU662DS 8836.00 — — HU662AWKl 2589.00 — 20 — 50 — 60 —— 100 —— — —HU663DS 13762.00 — — HU663AWKl 3195.00 — 40 — 75 — 75 —— 200 —— — —HU664DS 18877.00 — — HU664AWKl 7025.00 — 60 — 125 — 150 —— a Complete rating is NEMA 3, 3R, 4, 4X, 5 and 12. b 3 Also suitable for NEMA 3R application by removing drain screw from bottom endwall. c Refer to page 6-35 for additional motor application data. d For switching dc, use two switching poles. e Suitable for NEMA 5 applications with drain screw installed. f Switches with EI suffix are stocked with factory-installed electrical interlocks with one normally open and one normally closed contact. g Use 60 A enclosure accessories, including electrical interlocks. h No knockouts are provided. SAFETY SWITCHES i Check series number on switch for correct accessory. See page 3-13. j HU461AWK (Series E1) is rated 5 hp@250 Vdc, 10 hp@600 Vdc. k Not suitable for use as service equipment. l One enclosure for NEMA 1, 3, 3R or 12 applications. UL Listed. UL Listed Maximum Short Circuit Current Ratings—AC only NOTE: Consult the wiring diagram of the switch to verify the Any brand of circuit breaker or fuse not exceeding the ampere rating of UL Listed short circuit current rating. the switch may be used in conjunction with an non-fused safety switch when there is up to 10 kA short circuit current available. (See table below.) Above 10, kA—When applied on systems with greater than 10 kA short Table 3.13: Fusible Safety Switches circuit current available, the UL Listed short circuit current rating for For the short circuit current rating, refer to the table below. Square D non-fused switches is based upon the switch being used in Heavy Duty UL Listed UL Listed Short Circuit conjunction with fuses or Square D circuit breakers or Mag-Gard motor Safety Switch Type Fuse Class Current Ratings circuit protectors. H, K 10 kA Fusible R, J, L 200 kAm Table 3.15: Non-Fusible Safety Switches m On 600 V, 200 A switches, 100,000 A max. on corner grounded delta when protected by Heavy Duty Safety Switch Rating Fuse or Circuit Breaker UL Listed Short Circuit Class J or R fuses. Switch Type (A) o Typep Current Rating Table 3.14: Maximum I2t and I Ratings of Heavy Duty Switchesn Any Brand Circuit Breaker p Up to 10 kA All H, K Switch Rating Max. I2t Rating Max Ip Rating (A) (Amp2 sec.) (A) R,T,J.L 200 kA 30–100 FA 14 kA 30 50,000 14,000 30–100 FH 18 kA 60 200,000 26,000 Non-Fused 200 KA 100 500,000 32,000 Switches 400 LA 22 kA 200 2,000,000 50,000 600 MA 400 6,000,000 75,000 200 KH 600 12,000,000 100,000 400 LH 25 kA 800 10,000,000 80,000 600 MH 1200 15,000,000 120,000 o Applies to NEMA 1, 3R, 4X stainless, 12 switches. n Per UL 489, Table 7.12, page 7-11. p Ampere rating of fuse or circuit breaker not to exceed switch ampere rating.

23 3-6 DE1 Discount © 2007 Schneider Electric Schedule All Rights Reserved Heavy Duty Safety Switches NEMA Type 1 and 3R—Dimensions, Lug Data Class 3110 www.us.schneider-electric.com FOR CURRENT INFORMATION

Table 3.34: Terminal Lug Data (NEMA 1, 3R, 4, 4X, 5, 7, 9, 12)a Conductors Wire Range Wire Bending Space Optional Versa-Crimp® W W Rating Lug Wire Range (A) Per Phase Per NEC Table 312.6 AWG/kcmil Compression Lug and Neutral AWG/kcmil Field-Installableb 1 12–6 (Al) or 14–6 (Cu) 12–2 (Al) 30c 14–10 (Cu) solid or 14–10 (Cu) or — 2 stranded 14–2 (Cu) 60d 1 14–3 (Al) or 14–3 (Cu) 12–2 (Al) or 14–2 (Cu) — H H 100 1 12–1/0 (Al) or 14–1/0 (Cu) 12–1/0 (Al) or 14–1/0 (Cu) VCEL02114S1 200e 1 6–250 (Al/Cu) 6–300 (Al/Cu) VCEL030516H1 VCEL07512H1 1 1/0–750 (Al/Cu)f 1/0–750 (Al/Cu) or 400 or or and VCEL030516H1g 2 1/0–300 (Al/Cu) 1/0–300 (Al/Cu) and W/H D W/H D VCEL05012H1 Typical NEMA 1 Typical NEMA 3R 600 2 3/0–500 (Al/Cu) 3/0–500 (Al/Cu) VCEL05012H1 800 3 3/0–750 (Al/Cu) 3/0–750 (Al/Cu) H8LKE2h 1200 4 3/0–750 (Al/Cu) 3/0–750 (Al/Cu) H12LKE2 h a 30–100 A switches suitable for 60°C or 75°C conductors. 200–1200 A switches suitable for 75oC conductors. b For NEMA 1 and R3 only. c HU461AWK— 14–6 AWG (Cu). d H60XFA— 14–6 AWG (Cu). e H225XKA— 4 AWG–300 kcmil (Cu). f Max. wire range 600 Al/Cu on NEMA 4-4X Stainless and NEMA 12. g Order two PK516KN mounting kits ($5.80 each. Lexington Order Point) when installing VCEL030516H1 lugs. Only one kit is required on 2-Pole switches. h See page 3-11, 800 and 1200 A compression lug kits for additional information.

Approximate Dimensions Approximate Dimensions Cat. No. HWDW/HCat. No. HWDW/H Series Series in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm H221N F5 14.60 371 6.50 165 4.88 124 7.55 192 H364, N F5 29.00 737 17.13 435 8.25 210 18.50 470 H221NRB F5 14.88 378 6.63 168 4.88 124 7.55 192 H364RB, NRB F5 29.25 743 17.25 438 8.50 216 18.63 473 H222N F5 14.60 371 6.50 165 4.88 124 7.55 192 H365, N E4 50.25 1276 27.63 702 10.13 257 27.63 702 H222NRB F5 14.88 378 6.63 168 4.88 124 7.55 192 H365R, NR E4 50.31 1278 27.88 708 10.13 257 27.88 708 H223N F5 21.25 540 8.50 216 6.38 162 10.50 267 H366, N E4 50.25 1276 27.63 702 10.13 257 27.63 702 H223NRB F5 21.25 540 8.50 216 6.38 162 10.50 267 H366NR, R E4 50.31 1278 27.88 708 10.13 257 27.88 708 H224N F5 29.00 737 17.13 435 8.25 210 18.50 470 H367, N E4 69.13 1756 36.62 930 17.75 451 36.62 930 H224NRB F5 29.25 743 17.25 438 8.50 216 18.63 473 H367NR, R E4 69.13 1756 36.62 930 17.75 451 36.62 930 H225, N E4 50.25 1276 27.63 702 10.13 257 27.63 702 H368, N E4 69.13 1756 36.62 930 17.75 451 36.62 930 H225NR, R E4 50.31 1278 27.88 708 10.13 257 27.88 708 H368NR, R E4 69.13 1756 36.62 930 17.75 451 36.62 930 H226, N E4 50.25 1276 27.63 702 10.13 257 27.63 702 H461 F5 20.50 521 14.75 375 6.85 174 16.13 410 H226NR, R E4 50.31 1278 27.88 708 10.13 257 27.88 708 H462 F5 20.50 521 14.75 375 6.85 174 16.13 410 H227, N E4 69.13 1756 36.62 930 17.75 451 36.62 930 H463 F5 20.50 521 14.75 375 6.85 174 16.13 410 3 H227NR, R E4 69.13 1756 36.62 930 17.75 451 36.62 930 H464 F5 29.00 737 23.25 591 8.75 222 24.88 632 H228, N E4 69.13 1756 36.62 930 17.75 451 36.62 930 H465 E4 50.25 1276 33.88 861 10.13 257 33.88 861 H228NR, R E4 69.13 1756 36.62 930 17.75 451 36.62 930 H466 E4 50.25 1276 33.88 861 10.13 257 33.88 861 H265 E4 50.25 1276 27.63 702 10.13 257 27.63 702 HU265 E4 50.25 1276 27.63 702 10.13 257 27.63 702 H265R E4 50.31 1278 27.88 708 10.13 257 27.88 708 HU265R E4 50.31 1278 27.88 708 10.13 257 27.88 708 H266 E4 50.25 1276 27.63 702 10.13 257 27.63 702 HU266 E4 50.25 1276 27.63 702 10.13 257 27.63 702 SAFETY SWITCHES H266R E4 50.31 1278 27.88 708 10.13 257 27.88 708 HU266R E4 50.31 1278 27.88 708 10.13 257 27.88 708 H267 E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU267 E4 69.13 1756 36.62 930 17.75 451 36.62 930 H267R E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU267R E4 69.13 1756 36.62 930 17.75 451 36.62 930 H268 E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU268 E4 69.13 1756 36.62 930 17.75 451 36.62 930 H268R E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU268R E4 69.13 1756 36.62 930 17.75 451 36.62 930 H321N F5 14.60 371 6.50 165 4.88 124 7.55 192 HU361 F5 14.60 371 6.50 165 4.88 124 7.55 192 H321NRB F5 14.88 378 6.63 168 4.88 124 7.55 192 HU361RB F5 14.88 378 6.63 168 4.88 124 7.55 192 H322N F5 14.60 371 6.50 165 4.88 124 7.55 192 HU361WA F6 18.19 462 9.00 229 6.81 173 10.50 267 H322NRB F5 14.88 378 6.63 168 4.88 124 7.55 192 HU361WC F6 18.19 462 9.00 229 6.81 173 10.50 267 H323N F5 21.25 540 8.50 216 6.38 162 10.50 267 HU362 F5 17.50 445 9.00 229 6.38 162 10.50 267 H323NRB F5 21.25 540 8.50 216 6.38 162 10.50 267 HU362RB F5 17.50 445 9.00 229 6.38 162 10.50 267 H324N F5 29.00 737 17.13 435 8.25 210 18.50 470 HU362WA F6 18.19 462 9.00 229 6.81 173 10.50 267 H324NRB F5 29.25 743 17.25 438 8.50 216 18.63 473 HU362WC F6 16.75 425 9.00 229 7.00 178 10.50 267 H325, N E4 50.25 1276 27.88 708 10.13 257 27.88 708 HU362WH F5 18.19 462 9.00 229 6.81 173 10.50 267 H325R, NR E4 50.31 1278 27.88 708 10.13 257 27.88 708 HU363 F5 21.25 540 8.50 216 6.38 162 10.50 267 H326, N E4 50.25 1276 27.63 702 10.13 257 27.63 702 HU363RB F5 21.25 540 8.50 216 6.38 162 10.50 267 H326R, NR E4 50.31 1278 27.88 708 10.13 257 27.88 708 HU363WA F6 21.85 462 9.00 229 6.81 173 10.50 267 H327, N E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU363WC F6 21.85 555 9.00 229 6.81 173 10.50 267 H327R, NR E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU364 F5 29.00 737 17.13 435 8.25 210 18.50 470 H328, N E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU364RB F5 29.25 743 17.25 438 8.50 216 18.63 473 H328R, NR E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU365 E4 50.25 1276 27.63 702 10.13 257 27.63 702 H361, N F5 14.60 371 6.50 165 4.88 124 7.55 192 HU365R E4 50.31 1278 27.88 708 10.13 257 27.88 708 H361-2 F5 17.50 445 9.00 229 6.38 162 10.50 267 HU366 E4 50.25 1276 27.63 702 10.13 257 27.63 702 H361NRB, RB F5 14.88 378 6.63 168 4.88 124 7.55 192 HU366R E4 50.31 1278 27.88 708 10.13 257 27.88 708 H361WA F6 18.19 462 9.00 229 6.81 173 10.50 267 HU367 E4 69.13 1756 36.62 930 17.75 451 36.62 930 H361WC F6 18.19 462 9.00 229 6.81 173 10.50 267 HU367R E4 69.13 1756 36.62 930 17.75 451 36.62 930 H362, N F5 17.50 445 9.00 229 6.38 162 10.50 267 HU368 E4 69.13 1756 36.62 930 17.75 451 36.62 930 H362NRB, RB F5 17.50 445 9.00 229 6.38 162 10.50 267 HU368R E4 69.13 1756 36.62 930 17.75 451 36.62 930 H362WA F6 18.19 462 9.00 229 6.81 173 10.50 267 HU461 F5 20.50 521 14.75 375 6.85 174 16.13 410 H362WC F6 16.75 425 9.00 229 7.00 178 10.50 267 HU462 F5 20.50 521 14.75 375 6.85 174 16.13 410 H362WH F5 18.19 462 9.00 229 6.81 173 10.50 267 HU463 F5 20.50 521 14.75 375 6.85 174 16.13 410 H363, N F5 21.25 540 8.50 216 6.38 162 10.50 267 HU464 F5 29.00 737 23.25 591 8.75 222 24.88 632 H363NRB, RB F5 21.25 540 8.50 216 6.38 162 10.50 267 HU465 E4 50.25 1276 33.88 861 10.13 257 33.88 861 H363WA F6 21.85 462 9.00 229 6.81 173 10.50 267 HU466 E4 50.25 1276 33.88 861 10.13 257 33.88 861 H363WC F6 21.85 555 9.00 229 6.81 173 10.50 267 24 3-12 © 2007 Schneider Electric All Rights Reserved Heavy Duty Safety Switches Accessories Class 3110 www.us.schneider-electric.com FOR CURRENT INFORMATION Neutral Assemblies—Field-Installable Neutral Assemblies For Fusible and Non-Fusible 240 and 600 Volt Safety Switches Switch Standard Rating Series Number Neutral Kit Terminal Data .rice Optional Copper Only Terminal Data $ Price (A) (Seepages 3-12, 3-13) Cat. No. AWG/kcmil Neutral Kit Cat. No. AWG/kcmil 30 F1, F5–F6 SN03a (3) 2 Max. Al/Cu 55.00 SN03Ca (3) 6 Max. Cu 68.00 F1–F3, (2) 1/0 Max. Al/Cu (2) 1/0 Max. Cu F5–F6 (600 V) SN0610 71.00 SN0610C 76.00 60 (2) 2 Max. Al/Cu (2) 6 Max. Cu F4, a a F5–F6 (240 V) SN03 (3) 2 Max. Al/Cu 55.00 SN03C (3) 6 Max. Cu 68.00 (2) 1/0 Max. Al/Cu (2) 1/0 Max. Cu 100 F2–F6 SN0610 71.00 SN0610C 76.00 (2) 6 Max. Al/Cu (2) 6 Max. Cu b (2) 250 Max. Al/Cu (2) 250 Max. Cu 200 F5–F6 SN20A (1) 1/0 Max. Al/Cu 133.00 SN20C (1) 1/0 Max. Cu 164.00 (2) 600 Max. Cu (4) 750 Max. Al/Cu 400 & 600 E1–E4 H600SN (1) 300 Max. Al/Cu 218.00 H600SNC (2) 350 Max. Cu 301.00 (1) 250 Max. Cu (6) 750 Max. Al/Cu 800 E2–E4 H800SNE4 502.00 — — — (2) 350 Max. Al/Cu (8) 750 Max. Al/Cu 1200 E2–E4 H1200SNE4 689.00 — — — (2) 350 Max. Al/Cu Note: Neutrals cannot be installed in 4P, 6P, or NEMA 4X fiberglass reinforced polyester safety switches. a The following series -F5–F6 devices use SN0610(C): H-361-2, H-361-2RB, H-361-2A and H-361-2AWK. b For 200% neutral, order (2) neutral kits and (1) SN20NI neutral jumper kit. Price $18.40. (2) 350 Max. Al/Cu.

Equipment Grounding Kits Equipment grounding kits are field-installable and UL Listed in 30–1200 A heavy duty switches. For factory installation of equipment grounding kit, add suffix GL to standard Cat. No. (Example: H361GL). Price = Switch + Kit Price. NOTE: Kits are factory-installed standard in 30–200 A series F NEMA 4-4X-5 (stainless) and 12, and in all NEMA 30–200 A Series F 4–6P switches. Equipment Grounding Kits—Field- or Factory-Installable Equipment Grounding Kits–240 and 600 V Switch Rating Series Number Standard Terminal Data Optional Copper Only Terminal Data (A) (See pages 3-12, 3-13) Cat. No. AWG/kcmil $ Price Cat. No. AWG/kcmil $ Price 30 F1, F5–F7 GTK03 c (2) 12 Cu or (2) 10 Al or (1) 4 Max. Al/Cu 7.60 GTK03Cc (1) 6 Max. Cu 8.90 d F1–F3d, d d 60 F5–F7 (600 V) GTK0610 (2) 2/0 Max. Al/Cu 12.60 GTK0610C (2) 4 Max. Cu 15.10 F4, 60 F5–F6 (240 V) GTK03 (2) 12 Cu or (2) 10 Al or (1) 4 Max. Al/Cu 7.60 GTK03C (1) 6 Max. Cu 8.90 3 100 F2–F7 GTK0610 (2) 2/0 Max. Al/Cu 12.60 GTK0610C (2) 4 Max. Cu 15.10 200 F5–F7 PKOGTA2 (2) 2/0 Max. Al/Cu 36.80 PKOGTC2 (2) 4 Max. Cu 38.90 PKOGTA2e 400 & 600 E2–E4 (2) 2/0 Max. Al/Cu 36.80 PKOGTC3 (4) 1/0 Max. Cu 71.00f (2 Required) 800 E2–E4 PKOGTA7 (4) 350 Max. Al/Cu 132.00f ——— 1200 E2–E4 PKOGTA8 (8) 350 Max. Al/Cu 135.00f ——— SAFETY SWITCHES c The following series -F5–F6 devices use GTK0610(C): H-361-2 and H-361-2RB d 4- and 6-pole 30 A F Series. e Two required if grounding conductors are run in parallel. f PE1A Discount Schedule

Table 3.26: Square D Gray Paint Description Cat. No. $ Price 16 oz. Aerosol Paint Can, Square D Gray Paint PK49SP 26.00 ea. Note: Shipped in quantities of 6. Special Paint Phenolic Legend Plate UL Listed heavy duty switches are available painted with special safety Available engraved and mounted on all heavy duty safety switches, colors. Special colors available include: safety red, safety orange, safety except NEMA 7 and 9. Legend engraved in 1/4 in. high white letters on yellow, safety green, safety blue, safety purple, black and white. black background. Customer must provide legend. UL Listed. All colors comply with OSHA Standard 1910.144 and ANSI Specification To order, add suffix NP to standard Cat. No. Example: H363-NP Z535.1 for marking physical hazards. Price adder per legend plate—$111.00 A minimum quantity of 10 is required. To order, add suffix SP to standard Cat. No. Specify color on order. Price Adder Each Switch $ Price Quantity 30 A 60 A 100 A 200 A 400 A 600 A 10 161.00 185.00 289.00 319.00 758.00 1867.00

25 3-10 DE1 PE1A Discount © 2007 Schneider Electric Schedule All Rights Reserved THE STANDARD IN PV MOUNTING STRUCTURES

PV’s UNIVERSAL FLAT ROOF SOLUTION

UniRac’s new universal fl at roof solution accommodates a wide range of modules, Design Tools providing customers with fl exibility & options. Our RapidRac® G10 Minimal parts, faster installation, reduced Estimator generates quotes on the spot. Use it to weigh labor expenses and versatility; all customer- any number of options and driven demands that helped engineer this configurations. unique fl at roof solution. www.unirac.com It’s accompanied by a technical support system that provides complete installation and code compliance documentation, an on-line Estimator and design assistance to help you solve the toughest challenges.

26 Benefi ts of Selecting

The RapidRac® G10 was developed through signifi cant computational fl uid dynamics and wind tunnel engineering. The effi cient design, built at a fi xed 10 degree tilt angle, optimizes natural convective cooling of the modules and was designed to meet the requirements of current applicable building codes.

1 Speed of Installation The unique design of the RapidRac® G10 allows installation in less than half the time as the primary competitive products, requiring a 4-page installation guide.

2 Simplicity The RapidRac® G10 requires only 1 wrench and 6 parts to complete the install, a signifi cant reduction over current offerings.

3 Versatility and Choice The RapidRac® G10 accommodates most PV modules, providing the market with tremendous versatility and choice. The fl exibility of design allows it to meet most weight, height and wind conditions. UniRac also offers the RapidFoot®, an optional attachment accessory for the RapidRac® system, designed to provide additional support for higher seismic restraint and ballast trade off.

4 Value The RapidRac® G10 provides a highly competitive price per watt. UniRac estimates that the simplicity and ease of installation could provide labor savings of as much as $10,000 on a 250kw project.

Code Compliant Warranty The RapidRac® G10 system is PE certifi ed. Call All RapidRac® G10 components are covered by a 10- UniRac for documentation applicable to your building year limited product warranty. For details, download code or visit us at www.unirac.com. RapidRac® installation manual at www.unirac.com. Component Specifi cations RapidRac® G10 6061-T6 and 6105-T5 • 2-bay frame • 1-bay frame 5052-H32 aluminum sheet • Module Bracket 18-8 stainless steel • Fasteners

THE STANDARD IN PV MOUNTING STRUCTURES Pub 071130-1ds • November 2007 1411 Broadway NE, Albuquerque NM 87102-1545 USA © 2007 UniRac, Inc. All rights 27reserved. RapidRac™ Engineering Documentation, Planning and Assembly

Part II. Procedures for installations using the RapidRac™ ballasted PV Module Mounting System

This bulletin is designed to support applications for • The roof on which the RapidRac™ Mounting System building permits for installations using the RapidRac™ will be installed must have the capacity to resist the minimally attached, ballasted PV Module Mounting System, combined Design Dead Load and Live Load from the manufactured by UniRac, Inc. Follow the seven steps below installed array. and the installation instructions on pages 6 –9 to install RapidRac™ in compliance with the 2006 International Building Code and ASCE 7-05. Before proceeding, note the Step 1. Determine Your Design Wind Speed following: For the United States, the design wind speed is determined • This bulletin addresses seismic, snow, and wind loads. from the American Society of Civil Engineers Standard 7-05, Wind produces the maximum load factor affecting chapter 6, pages 32-33, fi gure 6-1. This gives the nominal an installation. Verify that other local factors, such design 3 second gust wind speed measured over 50 years. This as snow loads and earth quake effects, do not exceed is the design speed used to determine wind loading. Your the wind loads. Snow loading must be addressed for local building department will also have information for your the building but should not exceed the capacity of area on design wind speeds. If your installation is outside the the racking structure. Earthquake calculations are United States or if you need further assistance, consult a local done based on spectral response acceleration for the professional engineer or your local building authority. maximum considered earthquake of 2.0, and Appendix B is based on the same. Adjustments can be made if local maximum considered earthquake factors are known. Wind loads create lift and drag proportional to the projected area of the modules normal to the plane of the roof.

Figure 1. Basic Wind Speeds. ASCE/SEI 7-05, chap. 6, “Wind Loads,” p. 32–33, fi g. 6-1.

Notes: 1. Values are nominal design 3-second gust wind speeds in miles per hour (m/s) at 33 ft. (10 m) above ground for Exposure C category. 2. Linear interpolation between wind contours is permitted. 3. Islands and coastal areas outside the last contour shall use the last wind speed contour of the coastal area. 4. Mountainous terrain, gorges, ocean promontories, and special wind regions shall be examined for unusual wind condition.

Page 28 3 Engineering Documentation, Planning and Assembly RapidRac™

Step 2. Determine Your Exposure Category Step 3. Determine Your Design Wind Pressure The International Building Code, section 1609.4.2, and Design Wind Pressure is the amount of wind pressure that a 1609.4.3, pg. 293 (also referencing ASCE 7, chapter 6) defi nes structure is designed to withstand, expressed here in pounds wind exposure categories as follows: per square foot (psf). To determine the Design Wind Pressure required for your installation, apply the following factors: exposure b Exposure B shall apply where the ground surface roughness condition, as defi ned by the • Basic Wind Speed (determined in step 1), surface roughness classifi cation B existing upwind of • Exposure category (determined in step 2) and the structure in question for at least 2600 feet. (For buildings whose mean roof height is less than or equal • Height of your roof above the ground. to 30 feet, the upwind distance is permitted to be These factors can be used to look up your design wind pressure reduced to 1500 feet). Surface roughness category B is on the Wind Loading Tables on the following page. defi ned as: Urban and suburban living areas, wooded If your values fall signifi cantly outside the range of the table, areas or other terrain with numerous closely spaced consult a professional engineer, your local building authority, obstructions having the size of a single-family dwelling or your UniRac distributor. or larger. The Wind force analysis is based on ASCE 7-05, Chapter 6. exposure c Exposure C shall apply for all cases where The details of how the wind tables are calculated are included Exposures B or D do not apply. in appendix A. exposure d Exposure D shall apply where the ground surface roughness, as defi ned by surface roughness D, prevails in the upwind direction for a distance of at least 5000 feet, or 20 times the height of the building, whichever is greater. Exposure D shall extend inland from the shoreline for a distance of 6000 feet or 20 times the height of the building, whichever is greater. Surface roughness category D is defi ned as; Flat, unobstructed areas and water surfaces outside hurricane-prone regions, including smooth mud fl ats, salt fl ats, and unbroken ice.

Table 1. Exposure Category B Wind Loading Table Basic Wind Speed (mph) Height above ground (ft.) 75 80 85 90 95 100 110 120 (- #) = Lift lb/ft2 (#) = Down Force lb/ft2 0-15' (-4.64) 6.6 (-5.28) 7.51 (-5.96) 8.48 (-6.69) 9.51 (-7.45) 10.6 (-8.25) 11.74 (-9.99) 14.21 (-11.89) 16.91 20' (-5.05) 7.18 (-5.75) 8.17 (-6.49) 9.23 (-7.27) 10.34 (-8.1) 11.53 (-8.98) 12.77 (-10.86) 15.45 (-12.93) 18.39 25' (-5.38) 7.65 (-6.12) 8.7 (-6.91) 9.82 (-7.74) 11.01 (-8.63) 12.27 (-9.56) 13.59 (-11.57) 16.45 (-13.76) 19.58 30' (-5.7) 8.11 (-6.49) 9.23 (-7.32) 10.42 (-8.21) 11.68 (-9.15) 13.01 (-10.14) 14.42 (-12.27) 17.45 (-14.6) 20.76 40' (-6.19) 8.81 (-7.04) 10.02 (-7.95) 11.31 (-8.92) 12.68 (-9.93) 14.13 (-11.01) 15.65 (-13.32) 18.94 (-15.85) 22.54 50' (-6.6) 9.38 (-7.51) 10.68 (-8.48) 12.05 (-9.5) 13.51 (-10.59) 15.06 (-11.73) 16.68 (-14.19) 20.19 (-16.89) 24.02 60' (-6.92) 9.85 (-7.88) 11.2 (-8.89) 12.65 (-9.97) 14.18 (-11.11) 15.8 (-12.31) 17.51 (-14.9) 21.18 (-17.73) 25.21 70' (-7.25) 10.31 (-8.25) 11.73 (-9.31) 13.24 (-10.44) 14.85 (-11.63) 16.54 (-12.89) 18.33 (-15.6) 22.18 (-18.56) 26.4 80' (-7.58) 10.77 (-8.62) 12.26 (-9.73) 13.84 (-10.91) 15.52 (-12.16) 17.29 (-13.47) 19.16 (-16.3) 23.18 (-19.39) 27.58 90' (-7.82) 11.12 (-8.9) 12.65 (-10.04) 14.29 (-11.26) 16.02 (-12.55) 17.85 (-13.9) 19.77 (-16.82) 23.93 (-20.02) 28.47 100' (-8.06) 11.47 (-9.18) 13.05 (-10.36) 14.73 (-11.61) 16.52 (-12.94) 18.4 (-14.34) 20.39 (-17.35) 24.67 (-20.65) 29.36

Page 4 29 62 38 33 16 Evergreen ES-190-RL or SL 2.1 Safty Factor Double bay frame Part number 310350-0503 Single bay frame Part number 310360-0503 Design wind presure(lift) psf.From Table 1 Design wind presure(lift) psf.From Table 1 Area ft2 32.38 5 7.5 10 12.5 15 17.5 Area ft2 25.38 5 7.5 10 12.5 15 17.5 Frame load psf 1.82 1.82 1.82 1.82 1.82 1.82Frame load psf 1.82 1.82 1.82 1.82 1.82 1.82 Ballast load psf 1.29 3.84 6.4 8.95 11.51 14.06Ballast load psf 2.7 5.96 9.22 12.47 15.73 18.99 Dead load psf 3.11 5.66 8.22 10.77 13.33 15.88Dead load psf 4.52 7.78 11.04 14.29 17.55 20.81 Req. blocks2 5 8****** Req. blocks 3 610****** Max live load psf 3.51 5.26 7.02 8.77 10.53 12.28Max live load psf 4.48 6.71 8.95 11.19 13.43 15.67 max# of blocks 11 ** Requires attachment please reffer to attachment tables for adjustments. 62 38 33 16 Evergreen ES-180-RL or SL 2.1 Safty Factor Double bay frame Part number 310350-0502 Single bay frame Part number 310360-0502 Design wind presure(lift) psf.From Table 1 Design wind presure(lift) psf.From Table 1 Area ft2 32.38 5 7.5 10 12.5 15 17.5 Area ft2 25.38 5 7.5 10 12.5 15 17.5 Frame load psf 1.82 1.82 1.82 1.82 1.82 1.82Frame load psf 1.82 1.82 1.82 1.82 1.82 1.82 Ballast load psf 1.29 3.84 6.4 8.95 11.51 14.06Ballast load psf 2.7 5.96 9.22 12.47 15.73 18.99 Dead load psf 3.11 5.66 8.22 10.77 13.33 15.88Dead load psf 4.52 7.78 11.04 14.29 17.55 20.81 Req. blocks2 5 8****** Req. blocks 3 610****** Max live load psf 3.51 5.26 7.02 8.77 10.53 12.28Max live load psf 4.48 6.71 8.95 11.19 13.43 15.67 max# of blocks 11 ** Requires attachment please reffer to attachment tables for adjustments.

Area: is the foot print of the frame plus module. Req blocks: ballast load\ 26lbs times a 2.1 saftey factor. Frame load: module weight + frame weight\area Max live load: (Down force wind * module area)/area Dead load: ballast load + frame load Down force wind is based on a south to north wind direction. Ballast load: ballast requirments are calculated using uplift wind presure and a north to south wind direction.

30