Short-Circuit Current Calculations And SHORT-CIRCUIT CURRENT CALCULATIONS L .. AND PROTECTIVE RELAY COORDINATION FOR INDUSTRIAL AND COMMERCIAL POWER SYSTEMS, A Thesis Presented to The Faculty of the College of Engineering and Technology Ohio University In Partial Fulfillment of the Requirements for the Degree Master of Science Houshang C. Mohammadi s August, 1986 OHIO UNIVERSITY LIBRARY ACKNOWLEDGEMENTS I would like to offer my appreciation and thanks to Dr. Albert J.F. Keri my advisor, and Dr. H.W. Hill for their guidance and encouragement in the preparation of this thesis. I owe a great deal to my employer, E.I. Dupont company who gave me this opportunity to continue my education while I was working. I would also like to express my thanks to Mr. R.L. Doughty senior project engineer at E.I. Dupont company who checked my work through this study. Finally, I would like to express my thanks to the faculty and all members of staff at Ohio University who have contributed a great deal towards this work. TABLE OF CONTENTS ABSTRACT ................................ xii CHAPTER 1 . Introduction ............................ 1 1.1 Statement of the problem ................ 1 1.2 Literature search ....................... 4 1.3 State of the art ......................... 5 CHAPTER 2 . Sources of short circuit ................. 7 2.1 Generator ............................... 8 2.2 Synchronous motors ....................... 8 2.3 Induction motors ......................... 10 2.4 Electric utility systems ................. 11 2.5 Rotating machine reactance ............... 12 2.6 Symmetrical and asymmetrical currents .... 15 CHAPTER 3 . Short-circuit-current calculation ........ 17 3.1 Important assumptions .................... 18 3.2 Single line diagram ...................... 18 3.3 Impedance diagram ........................ 19 3.4 Type and location of faults required ..... 22 3.5 Symmetrical short-circuit current ........ 22 calculation 3.6 Momentary short circuit calculation ...... 25 3.7 Interrupting short circuit calculation ... 27 CHAPTER 4 . General equipment used for protection .... 31 4.1 Overcurrent relays ................. ....... 32 4.2 Fuses .................................... 33 4.3 Circuit breakers ......................... 38 4.4 Generator protection .................... 40 4.5 Transformer protection .................. 44 CHAPTER 5 . Coordination of protective devices ....... 47 5.1 Primary considerations for coordination .. 48 5.2 Data required for a coordination ......... 51 5.3 Methods of coordination .................. 52 5.4 Testing of protective devices ............ 66 CHAPTER 6 . Conclusion .............................. 72 BIBLIOGRAPHY .................... APPENDIX 1 . Impedance data .......................... 77 Al.l ANSI standard reactance values .......... 77 A1.2 Transmission line impedances ............ 78 A1.3 15KV cable impedances ................... 79 A1.4 5KV cable impedances .................... 80 A1.5 Correction factors for non magnetic ducts 81 APPENDIX 2 . Belle plant short circuit study ......... 82 A2.1 Description of the work ................. 82 A2.2 12KV air circuit breaker ratings ........ 84 A2.3 System assumptions ...................... 84 A2.4 Belle plant single line diagram ......... 85 A2.5 Belle plant impedance diagrams .......... 87 A2.6 Belle plant short circuit calculation ... 93 APPENDIX 3 . System generator protection ............. 98 A3.1 Belle plant generator protection ........ 98 A3.2 Belle plant bus protections ............. 115 APPENDIX 4 . Belle plant- transformer protection ..... 120 A4.1 ~~~e HU-1 transformer differential relay 120 APPENDIX 5 . Belle plant coordination curves ........ 126 and detailed diagrams "A" switch house. BANK No.1 and 12KV BUS 126 ECR No.6. 12KV BUS "A'f.................. 128 ECR No.6, 12KV BUS "B" .................. 130 Cogeneration generator .................. 132 BANK No.7 feeder No.18.................. 134 2.4KV 600HP motor river pump house ...... 136 2.4KV 450HP motor boiler feeder pump No.5 138 A5.8 2.4KV 75HP motor ash pump ............... 140 A5.9 2.4KV 200HP motor recirculating pump .... 142 A5.10 2.4KV 200HP motor F.D. fan boilers ...... 144 No.6 & 9 A5.11 2.4KV feeders sheet No.1 & BANK No.60 ... 146 A5.12 2.4KV feeders sheet No.2 & BANK No.59 ... 148 A5.13 2.4KV feeders ECR No.5 .................. 150 A5.14 2.4KV 150HP motor boiler No.10 mills .... 152 A5.15 2.4KV 550HP motor 1.D fan boilers ....... 154 No . 14 & 15 A5.16 2.4KV 400HP motor 1.D fan boilers ....... 156 No.6 & 9 A5.17 480V feeders ECR No.8 sheet 1 ........... 158 A5.18 480V feeders ECR.No.8 sheet 2 ........... 160 A5.19 480V feeders ECR No.8 sheet 3 ........... 162 A5.20 2.4KV 550HP motors 1.D fan boiler No.10. 164 APPENDIX 6 . Westinghouse overcurrent relay curves ... 166 A6.1 Type CO-7 Over Current Relay ............ 166 A6.2 Type CO-9 Over Current Relay ............ 167 A6.3 Type CO-11 Over Current Relay ........... 168 A6.4 Type COM-5 Over current Relay ........... 169 A6.5 Type CV-2 Under Voltage Relay ............ 170 A6.6 Type CV-7 Under Voltage Relay ........... 171 A6.7 Westinghouse type Amptector 11-A ........ 172 A6.8 Westinghouse type DSL-206 Limiters ...... 173 A6.9 Two pole type AA12P Overload Relay ...... 174 APPENDIX 7 . Buss fuses curves ....................... 180 A7.1 Type LPS-RK Low Peak Dual Element fuse .. 180 A7.2 Type KRP-C HI-CAP Fuses ................ 181 APPENDIX 8 . ASA Device numbers and functions ........ 182 LIST OF FIGURES 2.1 Total short circuit current equals sum of sources 9 2.2 Symmetrical short circuit currents from .......... 13 four surces 5.1 Typical time curves of CO-9 Relay ................ 63 5.2 Portion of Belle plant relaying detailed diagram . 64 5.3 Portion of Belle plant co-ordination curves ...... 65 A2-1 Block diagram of system setup .................... 83 A2-2 Belle plant single line diagram .................. 86 A2-3 Multiplying factors for three phase & line ....... 91 to ground faults A2-4 Belle plant simplified impedance diagram ......... 92 A2-5 Equivalent circuit for fault "A" (momentary) ..... 93 A2-6 Simplified equivalent circu'it for fault "A"...... 94 Wye-Delta transformation for fault "A". .......... 94 Equivalent circuit for fault "A" (interrupting) . 95 Wye-Delta transformation for fault "A"(interrup.) 96 Typical time curves for the 10% sensitivity ...... 100 type CA generator relay Limits for application of the CWC time curves .... 102 Typical time curves of the type CWC relay ........ 103 Generator over voltage curve ..................... 108 Generator reactive capability curve .............. 109 Machine capability curve ......................... 110 A3-7 SDF-1 tripping relay under declining frequency ... 113 A3-8 Operating time variations with changes in ........ 114 time-dial setting A3-9 KAB relay voltage unit setting ................... 118 A3-10 KAB relay current unit setting ................... 119 LIST OF TABLES Machine reactance and multiplying factors ....... Fuse classification ............................. Current limiting characteristics of c-s one ..... time fuse Transformer ANSI data ........................... Rating ratios for safe co-ordinations ........... Power air circuit breaker minimum band .......... ANSI Standard reactance values .................. Transmission line impedances .................... 15KV cable impedances ........................... 5KV cable impedances ............................ Correction factors for non magnetic ducts ........ 81 Result of Belle plant short circuit study ....... 97 Limits for application of CWC relay ............. 101 ABSTRACT The calculation of ac short-circuit currents, essential to the selection of adequately rated protective devices and equipment in industrial and commercial power systems, is becoming increasingly important to the system designer. Today, power systems carry larger blocks of power, are more important to the operation of the plant and building, and have greater safety and reliability requirements. Meeting these requirements necessitates the fulfillment of certain criteria, including the use of adequately rated equipment. This report outlines state of-the-art industrial power system engineering practices which should be especially valuable to industrial plant engineers and electricians, industrial power application engineers and others who are involved with the planning of electrical facilities for industrial plants or commercial buildings. The method of short-circuit-current calculation has been selected, so that adequate ratings of all the air circuit breakers were obtained. Fault protective devices were selected to maintain proper relay coordination throughout the system. These devices has been selected and set so that only the device nearest a fault opened to clear the fault without affecting larger devices nearer the source of power or causing a wider outage than the minimum. -xii- CHAPTER ONE INTRODUCTION All power systems, whether they be utility, industrial, commercial, or residential, have the common purpose of providing electric energy to the utilization equipment as safely and as reliably as is economically feasible. The relative importance of economic, reliability, and safety considerations may vary somewhat with the type of system, but all three elements must be taken into consideration in any good system design, and certain minimum safety and reliability requirements must be satisfied. 1.1 STATEMENT OF THE PROBLEM Electric power system in today's industrial plants and large commercial establishments handle enormous quantities of energy. A review of the trend
Recommended publications
  • Chapter – 3 Electrical Protection System
    CHAPTER – 3 ELECTRICAL PROTECTION SYSTEM 3.1 DESIGN CONSIDERATION Protection system adopted for securing protection and the protection scheme i.e. the coordinated arrangement of relays and accessories is discussed for the following elements of power system. i) Hydro Generators ii) Generator Transformers iii) H. V. Bus bars iv) Line Protection and Islanding Primary function of the protective system is to detect and isolate all failed or faulted components as quickly as possible, thereby minimizing the disruption to the remainder of the electric system. Accordingly the protection system should be dependable (operate when required), secure (not operate unnecessarily), selective (only the minimum number of devices should operate) and as fast as required. Without this primary requirement protection system would be largely ineffective and may even become liability. 3.1.1 Reliability of Protection Factors affecting reliability are as follows; i) Quality of relays ii) Component and circuits involved in fault clearance e.g. circuit breaker trip and control circuits, instrument transformers iii) Maintenance of protection equipment iv) Quality of maintenance operating staff Failure records indicate the following order of likelihood of relays failure, breaker, wiring, current transformers, voltage transformers and D C. battery. Accordingly local and remote back up arrangement are required to be provided. 3.1.2 Selectivity Selectivity is required to prevent unnecessary loss of plant and circuits. Protection should be provided in overlapping zones so that no part of the power system remains unprotected and faulty zone is disconnected and isolated. 3.1.3 Speed Factors affecting fault clearance time and speed of relay is as follows: i) Economic consideration ii) Selectivity iii) System stability iv) Equipment damage 3.1.4 Sensitivity Protection must be sufficiently sensitive to operate reliably under minimum fault conditions for a fault within its own zone while remaining stable under maximum load or through fault condition.
    [Show full text]
  • Application Guidelines for Ground Fault Protection
    Application Guidelines for Ground Fault Protection Joe Mooney and Jackie Peer Schweitzer Engineering Laboratories, Inc. Presented at the 1998 International Conference Modern Trends in the Protection Schemes of Electric Power Apparatus and Systems New Delhi, India October 28–30, 1998 Previously presented at the 52nd Annual Georgia Tech Protective Relaying Conference, May 1998 Originally presented at the 24th Annual Western Protective Relay Conference, October 1997 APPLICATION GUIDELINES FOR GROUND FAULT PROTECTION Joe Mooney, P.E., Jackie Peer Schweitzer Engineering Laboratories, Inc. INTRODUCTION Modern digital relays provide several outstanding methods for detecting ground faults. New directional elements and distance polarization methods make ground fault detection more sensitive, secure, and precise than ever. Advances in communications-aided protection further advance sensitivity, dependability, speed, and fault resistance coverage. The ground fault detection methods and the attributes of each method discussed in this paper are: • Directional Zero-Sequence Overcurrent • Directional Negative-Sequence Overcurrent • Quadrilateral Ground Distance • Mho Ground Distance Comparison of the ground fault detection methods is on the basis of sensitivity and security. The advantages and disadvantages for each method are presented and compared. Some problem areas of ground fault detection are discussed, including system nonhomogeneity, zero-sequence mutual coupling, remote infeed into high-resistance faults, and system unbalances due to in-line switching. Design and application considerations for each problem area are given to aid in setting the relay elements correctly. This paper offers a selection and setting guide for ground fault detection on noncompensated overhead power lines. The setting guide offers support in selecting the proper ground fault detection element based upon security, dependability, and sensitivity (high-resistance fault coverage).
    [Show full text]
  • Upgrading Power System Protection to Improve Safety, Monitoring, Protection, and Control
    Upgrading Power System Protection to Improve Safety, Monitoring, Protection, and Control Jeff Hill Georgia-Pacific Ken Behrendt Schweitzer Engineering Laboratories, Inc. Presented at the Pulp and Paper Industry Technical Conference Seattle, Washington June 22–27, 2008 Upgrading Power System Protection to Improve Safety, Monitoring, Protection, and Control Jeff Hill, Georgia-Pacific Ken Behrendt, Schweitzer Engineering Laboratories, Inc. Abstract—One large Midwestern paper mill is resolving an shown in Fig. 1 and Fig. 2, respectively. Each 5 kV bus in the arc-flash hazard (AFH) problem by installing microprocessor- power plant is supplied from two 15 kV buses. All paper mill based (μP) bus differential protection on medium-voltage and converting loads are supplied from either the 15 kV or switchgear and selectively replacing electromechanical (EM) overcurrent relays with μP relays. In addition to providing 5 kV power plant buses. Three of the power plant’s buses critical bus differential protection, the μP relays will provide utilized high-impedance bus differential relays installed during analog and digital communications for operator monitoring and switchgear upgrades within the last eight years. control via the power plant data and control system (DCS) and The generator neutral points are not grounded. Instead, a will ultimately be used as the backbone to replace an aging 15 kV zigzag grounding transformer had been installed on one hardwired load-shedding system. of the generator buses, establishing a low-impedance ground The low-impedance bus differential protection scheme was source that limits single-line-to-ground faults to 400 A. Each installed with existing current transformers (CTs), using a novel approach that only required monitoring current on two of the of the 5 kV bus source transformers is also low-impedance three phases.
    [Show full text]
  • Transformer Protection
    Power System Elements Relay Applications PJM State & Member Training Dept. PJM©2018 6/05/2018 Objectives • At the end of this presentation the Learner will be able to: • Describe the purpose of protective relays, their characteristics and components • Identify the characteristics of the various protection schemes used for transmission lines • Given a simulated fault on a transmission line, identify the expected relay actions • Identify the characteristics of the various protection schemes used for transformers and buses • Identify the characteristics of the various protection schemes used for generators • Describe the purpose and functionality of Special Protection/Remedial Action Schemes associated with the BES • Identify operator considerations and actions to be taken during relay testing and following a relay operation PJM©2018 2 6/05/2018 Basic Concepts in Protection PJM©2018 3 6/05/2018 Purpose of Protective Relaying • Detect and isolate equipment failures ‒ Transmission equipment and generator fault protection • Improve system stability • Protect against overloads • Protect against abnormal conditions ‒ Voltage, frequency, current, etc. • Protect public PJM©2018 4 6/05/2018 Purpose of Protective Relaying • Intelligence in a Protective Scheme ‒ Monitor system “inputs” ‒ Operate when the monitored quantity exceeds a predefined limit • Current exceeds preset value • Oil level below required spec • Temperature above required spec ‒ Will initiate a desirable system event that will aid in maintaining system reliability (i.e. trip a circuit
    [Show full text]
  • Protection, Control, Automation, and Integration for Off-Grid Solar-Powered Microgrids in Mexico
    Protection, Control, Automation, and Integration for Off-Grid Solar-Powered Microgrids in Mexico Carlos Eduardo Ortiz and José Francisco Álvarez Rada Greenergy Edson Hernández, Juan Lozada, Alejandro Carbajal, and Héctor J. Altuve Schweitzer Engineering Laboratories, Inc. Published in Wide-Area Protection and Control Systems: A Collection of Technical Papers Representing Modern Solutions, 2017 Previous revised edition released October 2013 Originally presented at the 40th Annual Western Protective Relay Conference, October 2013 1 Protection, Control, Automation, and Integration for Off-Grid Solar-Powered Microgrids in Mexico Carlos Eduardo Ortiz and José Francisco Álvarez Rada, Greenergy Edson Hernández, Juan Lozada, Alejandro Carbajal, and Héctor J. Altuve, Schweitzer Engineering Laboratories, Inc. Abstract—Comisión Federal de Electricidad (CFE), the distribution network. Each microgrid includes an integrated national Mexican electric utility, launched the White Flag protection, control, and monitoring (PCM) system. The Program (Programa Bandera Blanca) with the objective of system collects and processes data from the microgrid providing electricity to rural communities with more than 100 inhabitants. In 2012, CFE launched two projects to provide substations and sends the data to the supervisory control and electric service to two communities belonging to the Huichol data acquisition (SCADA) master of two remote CFE control indigenous group, Guásimas del Metate and Tierra Blanca del centers. The system includes local and remote controls to Picacho, which are both located in the mountains near Tepic, operate the microgrid breaker. Nayarit, Mexico. Each microgrid consists of a photovoltaic power CFE is studying the possibility of interconnecting plant, a step-up transformer bank, and a radial medium-voltage neighboring microgrids in the future to improve service distribution network.
    [Show full text]
  • Power System Selectivity: the Basics of Protective Coordination by Gary H
    Power System Selectivity: The Basics Of Protective Coordination By Gary H. Fox, PE, GE Specification Engineer The intent of this article is to provide a brief primer about the essence of coordinating the basic protective components of the electrical power system, including circuit breakers, fuses and protective relays, and to enable the reader to review a plot of time current curves and evaluate several key concerns: • How well do the devices work with each other? • Will a minimal amount of the power system be lost by a fault? • How well are the power system components protected? • Could the chosen ratings and settings cause nuisance trips? The Objectives of Protection Determining the protective devices for a power system The Intended Result and their settings usually puts two competing goals against each other. On the one hand you want the system available for use 100% of the time. To this extreme end all power outages, whether due to maintenance or failures, are to be avoided. You would want the protective device ratings and settings to be Isc as high as possible, and these settings would be further desensitized by a considerable time delay, so Page 2 that extra time is allowed before the circuit is tripped. Fig. 1 An example of short circuit On the other hand there is a concern for the protection flow in a radial system of the load and system components. The degree of damage from a short circuit fault is proportional to the amount of time that fault persists and the square of the current that flows.
    [Show full text]
  • Power System Protective Relaying: Basic Concepts, Industrial-Grade Devices, and Communication Mechanisms Internal Report
    Power System Protective Relaying: basic concepts, industrial-grade devices, and communication mechanisms Internal Report Report # Smarts-Lab-2011-003 July 2011 Principal Investigators: Rujiroj Leelaruji Dr. Luigi Vanfretti Affiliation: KTH Royal Institute of Technology Electric Power Systems Department KTH • Electric Power Systems Division • School of Electrical Engineering • Teknikringen 33 • SE 100 44 Stockholm • Sweden Dr. Luigi Vanfretti • Tel.: +46-8 790 6625 • [email protected] • www.vanfretti.com DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITIES THIS DOCUMENT WAS PREPARED BY THE ORGANIZATION(S) NAMED BELOW AS AN ACCOUNT OF WORK SPONSORED OR COSPONSORED BY KUNGLIGA TEKNISKA HOGSKOLAN¨ (KTH) . NEITHER KTH, ANY MEMBER OF KTH, ANY COSPONSOR, THE ORGANIZATION(S) BELOW, NOR ANY PERSON ACTING ON BEHALF OF ANY OF THEM: (A) MAKES ANY WARRANTY OR REPRESENTATION WHATSOEVER, EXPRESS OR IMPLIED, (I) WITH RESPECT TO THE USE OF ANY INFORMATION, APPARATUS, METHOD, PROCESS, OR SIMILAR ITEM DISCLOSED IN THIS DOCUMENT, INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, OR (II) THAT SUCH USE DOES NOT INFRINGE ON OR INTERFERE WITH PRIVATELY OWNED RIGHTS, INCLUDING ANY PARTY’S INTELLECTUAL PROPERTY, OR (III) THAT THIS DOCUMENT IS SUITABLE TO ANY PARTICULAR USER’S CIRCUMSTANCE; OR (B) ASSUMES RESPONSIBILITY FOR ANY DAMAGES OR OTHER LIABILITY WHATSOEVER (INCLUDING ANY CONSEQUENTIAL DAMAGES, EVEN IF KTH OR ANY KTH REPRESENTATIVE HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES) RESULTING FROM YOUR SELECTION OR USE OF THIS DOCUMENT OR ANY INFORMATION, APPARATUS, METHOD, PROCESS, OR SIMILAR ITEM DISCLOSED IN THIS DOCUMENT. ORGANIZATIONS THAT PREPARED THIS DOCUMENT: KUNGLIGA TEKNISKA HOGSKOLAN¨ CITING THIS DOCUMENT Leelaruji, R., and Vanfretti, L.
    [Show full text]
  • Protective Relaying Philosophy and Design Guidelines
    Protective Relaying Philosophy and Design Guidelines PJM Relay Subcommittee July 12, 2018 Protective Relaying Philosophy and Design Guidelines Contents SECTION 1: Introduction .................................................................................................................. 1 SECTION 2: Protective Relaying Philosophy .................................................................................... 2 SECTION 3: Generator Protection .................................................................................................... 4 SECTION 4: Unit Power Transformer and Lead Protection ............................................................... 7 SECTION 5: Unit Auxiliary Transformer and Lead Protection ........................................................... 8 SECTION 6: Start-up Station Service Transformer and Lead Protection ........................................... 9 SECTION 7: Line Protection ........................................................................................................... 10 SECTION 8: Substation Transformer Protection ............................................................................. 12 SECTION 9: Bus Protection ............................................................................................................ 14 SECTION 10: Shunt Reactor Protection .......................................................................................... 15 SECTION 11: Shunt Capacitor Protection ......................................................................................
    [Show full text]
  • Coordination of Protection System and VSC-HVDC to Mitigate Cascading Failures
    Coordination of protection system and VSC-HVDC to mitigate cascading failures RUJIROJ LEELARUJI Licentiate Thesis Royal Institute of Technology School of Electrical Engineering Electric Power Systems Stockholm, Sweden, 2010 School of Electrical Engineering Electric Power Systems TRITA-EE 2010:28 Royal Institute of Technology ISSN 1653-5146 SE-100 44 Stockholm ISBN 978-91-7415-688-1 Sweden Akademisk avhandling som med tillstånd av Kungl Tekniska högskolan fram- lägges till offentlig granskning för avläggande av teknologie licentiatexamen tis- dagen den 15 June 2010 kl 10.00 i V21, Kungl Tekniska Högskolan, Stockholm. © Rujiroj Leelaruji, June 2010 Tryck: Universitetsservice US-AB Abstract The rapid development of the global economics has made power systems all over the world become large-scale interconnected grids. This increases the ca- pability of power grids to transfer power over the long distance to serve the de- sired power demand with the minimum cost of operation. Unfortunately, it also enables the propagation of local failures into global networks. In other words, if a blackout happens in a power system, the size and the damage may signifi- cantly increase. One of the main ways in which blackouts become widespread is cascading failures. This type of failure originates after a critical component of the system has been removed from the service by protective relaying. As a consequence, the load handled by the failed component needs to be redistributed which might cause an overloading on other components in the system. On the other hand, the high power electronics controllable devices such as Voltage Source Converters-based High Voltage Direct Current (VSC-HVDC) transmission are recently developed.
    [Show full text]
  • How Disruptions in DC Power and Communications Circuits Can Affect Protection
    How Disruptions in DC Power and Communications Circuits Can Affect Protection Karl Zimmerman and David Costello Schweitzer Engineering Laboratories, Inc. © 2015 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works. This paper was presented at the 68th Annual Conference for Protective Relay Engineers and can be accessed at: http://dx.doi.org/10.1109/CPRE.2015.7102189. For the complete history of this paper, refer to the next page. Presented at the 43rd Annual Western Protective Relay Conference Spokane, Washington October 18–20, 2016 Previously presented at the 70th Annual Georgia Tech Protective Relaying Conference, April 2016, PowerTest Conference, March 2016, and 2nd Annual PAC World Americas Conference, September 2015 Originally presented at the 68th Annual Conference for Protective Relay Engineers, March 2015 1 How Disruptions in DC Power and Communications Circuits Can Affect Protection Karl Zimmerman and David Costello, Schweitzer Engineering Laboratories, Inc. Abstract—Modern microprocessor-based relays are designed factors must perform correctly to ensure that the protection to provide robust and reliable protection even with disruptions in scheme correctly restrains for out-of-section faults or when no the dc supply, dc control circuits, or interconnected fault is present. communications system. Noisy battery voltage supplies, interruptions in the dc supply, and communications interference are just a few of the challenges that relays encounter.
    [Show full text]
  • Modern Design Principles for Numerical Busbar Differential Protection
    Modern Design Principles for Numerical Busbar Differential Protection Zoran Gajić, Hamdy Faramawy, Li He, Klas Mike Kockott Koppari, Lee Max ABB Inc. ABB AB Raleigh, NC, USA Västerås, Sweden [email protected] Summary 6. Easy incorporation of bus-section and/or bus-coupler bays (that is, tie-breakers) with one or two sets of CTs into the For busbar protection, it is extremely important to have protection scheme. good security since an unwanted operation might have severe consequences. The unwanted operation of the bus differential 7. Disconnector and/or circuit breaker status supervision. relay will have the similar effect as simultaneous faults on all power system elements connected to the bus. On the other hand, the relay has to be dependable as well. Failure to operate Modern design for a Busbar Differential Protection IED or even slow operation of the differential relay, in case of an [10] containing six differential protection zones and fulfilling actual internal fault, can have fatal consequences. These two all of the above mentioned requirements will be presented in requirements are contradictory to each other. To design the the paper. differential relay to satisfy both requirements at the same time is not an easy task. Keywords Busbar protection shall also be able to dynamically Busbar Protection, Differential Protection, Dynamic Zone include and/or exclude individual bay currents from Selection. differential zones. Therefore it must contain so-called dynamic zone selection in order to adapt to changing topology of substation for multi-zone applications. The software based I INTRODUCTION dynamic zone selection ensures: 1. Dynamic linking of measured bay currents to the The bus zone protection has experienced several decades appropriate differential protection zone(s) as required by of changes.
    [Show full text]
  • Using Protective Relays for Microgrid Controls
    Using Protective Relays for Microgrid Controls William Edwards and Scott Manson, Schweitzer Engineering Laboratories, Inc. Abstract—This paper explains how microprocessor-based Distributed microgrid controls being performed in protective relays are used to provide both control and protection protective relays is practical because smaller microgrids require functions for small microgrids. Features described in the paper less complicated controls, fewer features, less communication, include automatic islanding, reconnection to the electric power system, dispatch of distributed generation, compliance to IEEE and less data storage. In smaller microgrids, relays are specifications, load shedding, volt/VAR control, and frequency commonly utilized for control, metering, and protection and power control at the point of interface. functions. In larger microgrids, the functionality of the microgrid controls is predominantly performed in one or more I. INTRODUCTION centralized controllers. Protective relays in larger microgrids This paper elaborates on the most common forms of tend to only be used as metering and protection devices with microgrid control accomplished in modern protective relays for controls being performed in a central device. Centralized grids with less than 10 MW of generation. The control controls dominate in large grids because distributed controls strategies described include islanding, load and generation become impractical to maintain, develop, and test when the shedding, reconnection, dispatch, and load sharing. number of distributed relays grows into the hundreds or Multifunction protective relays are an economical choice for thousands. microgrid controls because the hardware is commonly required at the point of interface (POI) to the electric power system III. ISLANDING (EPS) and at each distributed energy resource (DER). The This section describes the automatic islanding functionality relays at the POI and DER provide mandatory protection and required at the POI between a microgrid and the EPS.
    [Show full text]