Viking Access Systems July 2014

Viking Access Systems July 2014 631 Wald Irvine, California 92618 Toll Free (800) 908-0884 Fax (949) 753-1640 Website www.vikingaccess.com E-mail [email protected]

Product Guide Specification

Specifier Notes: This product guide specification is written according to the Construction Specifications Institute (CSI) 3-Part Format, including MasterFormat, SectionFormat, and PageFormat, as described in The Project Resource Manual—CSI Manual of Practice, Fifth Edition.

This section must be carefully reviewed and edited by the Architect to meet the requirements of the project and local building code. Coordinate this section with other specification sections and the Drawings. Delete all “Specifier Notes” after editing this section.

Section numbers are from MasterFormat 1995 Edition, with section numbers from MasterFormat 2004 Edition in parentheses. Delete version not required.

SECTION 02829 (32 31 33)

GATE OPERATORS

Specifier Notes: This section covers Viking Access Systems gate operators. Consult Viking Access Systems for assistance in editing this section for the specific application.

PART 1 GENERAL

1.1 SECTION INCLUDES

Specifier Notes: List the type of gate operators specified in Part 2 of this section. Delete types not specified.

A. Swing gate operators.

B. Slide gate operators.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

1.2 RELATED REQUIREMENTS

Specifier Notes: Edit the following list of related sections as required. Delete related sections not required. List other sections with work directly related to this section.

A. Section 02820 (32 31 00) – Fences and Gates.

B. Section 03300 (03 30 00) – Cast-in-Place Concrete: Concrete pads.

C. Section 11150 (11 12 00) – Parking Control Equipment.

D. Division 16 (26) – Electrical.

1.3 REFERENCE STANDARDS

Specifier Notes: List reference standards mentioned in this section, complete with designations and titles. Delete reference standards not included in this edited section. This article does not require compliance with reference standards, but is merely a listing of those used.

A. UL 325 – Standard for Door, Drapery, Gate, Louver, and Window Operators and Systems.

B. UL 991 – Standard for Tests for Safety-Related Controls Employing Solid-State Devices.

1.4 SUBMITTALS

Specifier Notes: Edit submittal requirements as required. Delete submittals not required.

A. Comply with Section 01330 (01 33 00) – Submittal Procedures.

B. Product Data: Submit manufacturer’s product data, including installation instructions.

C. Manufacturer’s Certification: Submit manufacturer’s certification that materials comply with specified requirements and are suitable for intended application.

D. Operation Data: 1. Submit manufacturer’s operation manual; including the following: a. Operation instructions. b. Troubleshooting guide. c. Parts list. d. Electrical wiring diagrams. 2. Provide detailed information required for Owner to properly operate and maintain gate operators.

E. Warranty Documentation: Submit manufacturer’s standard warranty.

1.5 QUALITY ASSURANCE

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

A. Manufacturer’s Qualifications: Manufacturer regularly engaged, for past 10 years, in manufacture of gate operators of similar type to that specified.

B. Installer's Qualifications: 1. Installer regularly engaged, for past 3 years, in installation of gate operators of similar type to that specified. 2. Employ persons trained for installation of gate operators.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Delivery and Acceptance Requirements: Deliver materials to site in manufacturer’s original, unopened containers and packaging, with labels clearly identifying product name and manufacturer.

B. Storage and Handling Requirements: 1. Store and handle materials in accordance with manufacturer’s instructions. 2. Keep materials in manufacturer’s original, unopened containers and packaging until installation. 3. Store materials in clean, dry area indoors. 4. Protect materials during storage, handling, and installation to prevent damage.

PART 2 PRODUCTS

2.1 MANUFACTURER

A. Viking Access Systems, 631 Wald, Irvine, California 92618. Toll Free (800) 908-0884. Fax (949) 753-1640. Website www.vikingaccess.com. E-mail [email protected].

Specifier Notes: Gate operators, operator technology, and accessories described in this section are presented in the same order as they appear in the Viking Access Systems 2009 Product Catalog.

Specify required swing gate operators. Delete operators not required.

2.2 SWING GATE OPERATORS A. Swing Gate Operators: Model “F-1”

1. UL Listed and ETL listed in compliance to UL325 and UL991 2. UL 325, Class I, II, III, and IV vehicular gate operator. 3. Operation: 24 VDC with 1/2 HP motor. 4. Maximum Gate Size: a.i. 12-Foot Gate: 1,500 lbs. a.ii. 16-Foot Gate: 1000 lbs.

5. Maximum Operating Speed: 13 to 16 seconds per 90 degrees.

6. Motor: DC brush motor / helical-bevel gear-head

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

7. Operating temperature: Minus 20 degrees F to160 degrees F.

8. Maximum Duty Cycle: 100 percent; continuous cycle.

9. Chassis: 1/4 "steel, galvanized G90, zinc plated and powder coated.

Specifier Notes: Viking Pipe Stand products are optional. Delete if not required.

10. P/N VA-F1PS Pipe Stand Kit:

a.i. Max 3” O.D. pipe diameter compatible.

a.ii. 1/4 "steel, galvanized G90, zinc plated and powder coated.

11. Power:

a. Main Power Source: 120 or 220 VAC, single phase

a.i.1) Built-in power selector switch

b. Consumption Current: 4 A at 120 VAC and 2 A at 220 VAC.

c. EMI Filter and lightning Protection: For AC line up to 10 kA.

Specifier Notes: Alternative power sources consisting of solar panels or plug-in transformers are optional. Delete if not required. Consult Viking Access Systems for more information.

d. Alternative Power Sources:

d.i. [24 VDC, 80 W solar panel.]

d.ii. [24VAC, 40 VA plug-in transformer.]

d.iii. [24VDC, 40 VA plug-in transformer.]

d.iv. [Built-in Removable Power Supply.]

d.v. [P/N VA-SOCHP Viking Solar Kit.]

e. Built-in Battery: 7 Amp-hr, 12 VDC x 2.

f. Built-in Battery-Backup Operation: 400 full cycles (1500 lbs.).

g. Toroidal Transformer: Up to 360 VA of power.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

h. Unit uses main power source, battery is only needed in case of power failure.

12. Built-in Removable Power Supply

a. Toroidal Transformer.

b. Accessible power switch.

c. Accessible fuse holder.

d. Accessible AC receptacle; up to 3 Amps.

e. Incoming power LED indicator.

f. Outgoing power LED indicator.

g. Surge protection in good status LED indicator.

h. Slide-out design for accessible service.

i. EMI filter board.

j. Surge protection up to 10kA

13. Built-in and pre-wired Loop Rack for up to 3 plug-in loop detectors

14. Accessible battery switch/breaker

15. Accessible motor switch/breaker

16. Built-in heater allowing operation down to minus 20 degrees F.

17. Control Board Enclosure: ABS Plastic V-0 rating according to UL94

18. Logic Board: “VFlex”

a. Redundancy design.

b. Intelligent Obstruction Sensor:

b.i. Multiple algorithms supervising obstructions.

c. Built-in lightning strike protection up to 20 kV and 10 kA.

c.i. Multiple stage protection.

d. Built-in overcurrent and short circuit protected.

d.i. Multiple stage protection.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

e. Regulated power supply for external accessories up to 1 A.

f. Built-in battery charger.

g. Soft start/stop gate control.

h. Self-adaptive and self-learn algorithms for travel control.

i. Self-adaptive and self-learn algorithms for limit of travel accuracy.

j. Self-adaptive and self-learn algorithms for torque control.

k. Speed control algorithm to ensure constant speed of travel independent of power fluctuations.

l. Thermostatic control of the built-in heater.

m. Lock Mode feature detects unauthorized movement of the gate and maintains the limit position.

n. Anti-tailgating feature preventing vehicular tailgating.

o. Multiple ports of connection for plug-and-play devices

p. Pluggable accessory connectors.

q. Fail-Safe or Fail-Secure selections.

r. Master/Slave synchronization in tandem operation between 2 gates.

s. Magnetic lock control; 250 VAC/10 A contact.

t. LED indicators for external accessories and power status.

u. Hold-Open timer adjustable from 0 to 60 seconds.

v. Speed Control adjustable from –25 % up to +50 % of the nominal speed

w. Overlap delay adjustable from 0 to 6 seconds to control master/slave operation of tandem gates; opening one gate first and after few seconds opening the second gate.

x. Auto-Open feature in case of power outage.

y. Last-Open feature in case the batteries are low during power outage.

z. Pre-operation warning feature; 3 seconds warning before gate starts moving.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

Specifier Notes: Viking Konnect products are optional. Delete if not required.

aa. P/N VA-KONNECT-MS Viking Konnect Master/Slave Kit:

aa.i. Plug-and-play device.

aa.ii. Full duplex communication.

aa.iii. Self-monitor data communication watch-dog-timer.

aa.iv. Secure connection between master and slave modules; single channel communication.

aa.v. Robust wireless Master/Slave communication for up to 100 feet.

aa.vi. Adaptive frequency hopping using spread spectrum.

ab. P/N VA- KONNECT-D Viking Konnect Diagnostic Tool:

ab.i. Plug-and-play device.

ab.ii. Full duplex communication.

ab.iii. Self-monitor data communication watch-dog-timer.

ab.iv. Secure connectivity.

ab.v. Robust wireless communication.

ab.vi. Adaptive frequency hopping using spread spectrum.

ab.vii. Apple, Android and Windows smart devices compatible.

ab.viii. PC and laptop computers via Bluetooth compatible.

ab.ix. Set and adjust operator parameters.

ab.x. Remote diagnostic information

ab.xi. Displays the control board's LED status indicators.

Specifier Notes: Viking Monitor Module is optional. Delete if not required.

ac. P/N VA-MONITOR Viking Monitor Module:

ac.i. Plug and play device.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

ac.ii. Off-site communication using a PC computer via internet and cellular network.

ac.iii. Provides a virtual overview of the gate operators' control board.

ac.iv. Real-time display of the control board's settings.

ac.v. Real-time display of the control board's LED status indicators.

ac.vi. Real-time display of the control board's LCD Display.

ac.vii. Real-time display of the operator's voltage supply and current draw.

ac.viii. Real-time display of the inputs as they are received from the access control and safety devices.

ac.ix. Historical data capture.

ac.x. Capable of monitoring multiple gate operators.

19. Clutch Mechanism:

a. Fail-safe/fail-secure.

b. Allows full and safe operation of gate operator by use of the Clutch-Key.

c. The Clutch-Key in place enables security to prevent clutch action needed in fail-secure system.

d. Versatility to comply with various fire codes.

e. Convenient manual release in case of emergency.

20. Cover:

a. UV-stabilized polyethylene.

b. In compliance with UL746C.

c. Clam-shell design; easily removable, allowing access to entire gate operator.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

B. Swing Gate Operators: Model “G-5”

1.UL Listed and ETL listed in compliance to UL325 and UL991 2.UL 325, Class I, II, III, and IV vehicular gate operator. 3.Operation: 24 VDC with 1/2 HP motor. 4.Maximum Gate Size: a. 10-Foot Gate: 2,000 lbs. b. 18-Foot Gate: 800 lbs. 5. Maximum Operating Speed: 14 to 16 seconds per 90 degrees.

6. Motor: DC brush motor

7. Motor gear head Cover: Aluminum, powder coated.

8. Cable for Motor:

a. Six conductors.

b. Direct burial.

c. Water resistance

d. Shielded; foil overall, with drain wire

9. Operating temperature: Minus 20 degrees F to160 degrees F.

10. Maximum Duty Cycle: 100 percent; continuous cycle.

11. Power:

a. Main Power Source: 120 or 220 VAC, single phase

a.i.1. Built-in power selector switch

b. Consumption Current: 4 A at 120 VAC and 2 A at 220 VAC.

c. EMI Filter and lightning Protection: For AC line up to 10 kA.

c.i. Specifier Notes: Alternative power sources consisting of solar panels or plug-in transformers are optional. Delete if not required. Consult Viking Access Systems for more information.

d. Alternative Power Sources:

d.i. [24 VDC, 80 W solar panel.]

d.ii. [24VAC, 40 VA plug-in transformer.]

d.iii. [24VDC, 40 VA plug-in transformer.]

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

d.iv. [P/N VA-SOCHP Viking Solar Kit.]

e. Built-in Battery: 12 VDC x 2.

f. Built-in Battery-Backup Operation: 400 full cycles (600 lbs.).

g. Toroidal Transformer: Up to 240 VA of power.

h. Unit uses main power source, battery is only needed in case of power failure.

12. Power Supply

a. Toroidal Transformer.

b. Incoming power LED indicator.

c. Outgoing power LED indicator.

d. Surge protection in good status LED indicator.

e. EMI filter board.

f. Surge protection up to 10kA

13. Accessible battery switch/breaker

14. Built-in heater allowing operation down to minus 20 degrees F.

15. Control Board Enclosure: ABS Plastic V-0 rating according to UL94

16. Logic Board: “VFlex”

a. Redundancy design.

b. Intelligent Obstruction Sensor:

b.i. Multiple algorithms supervising obstructions.

c. Built-in lightning strike protection up to 20 kV and 10 kA.

c.i. Multiple stage protection.

d. Built-in overcurrent and short circuit protected.

d.i. Multiple stage protection.

e. Regulated power supply for external accessories up to 1 A.

f. Built-in battery charger.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

g. Soft start/stop gate control.

h. Self-adaptive and self-learn algorithms for travel control.

i. Self-adaptive and self-learn algorithms for limit of travel accuracy.

j. Self-adaptive and self-learn algorithms for torque control.

k. Speed control algorithm to ensure constant speed of travel independent of power fluctuations.

l. Thermostatic control of the built-in heater.

m. Lock Mode feature detects unauthorized movement of the gate and maintains the limit position.

n. Anti-tailgating feature preventing vehicular tailgating.

o. Multiple ports of connection for plug-and-play devices

p. Pluggable accessory connectors.

q. Fail-Safe or Fail-Secure selections.

r. Master/Slave synchronization in tandem operation between 2 gates.

s. Magnetic lock control; 250 VAC/10 A contact.

t. LED indicators for external accessories and power status.

u. Hold-Open timer adjustable from 0 to 60 seconds.

v. Speed Control adjustable from –25 % up to +50 % of the nominal speed

w. Overlap delay adjustable from 0 to 6 seconds to control master/slave operation of tandem gates; opening one gate first and after few seconds opening the second gate.

x. Auto-Open feature in case of power outage.

y. Last-Open feature in case the batteries are low during power outage.

z. Pre-operation warning feature; 3 seconds warning before gate starts moving.

z.i. Specifier Notes: Viking Konnect products are optional. Delete if not required.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

aa. P/N VA-KONNECT-MS Viking Konnect Master/Slave Kit:

aa.i. Plug-and-play device.

aa.ii. Full duplex communication.

aa.iii. Self-monitor data communication watch-dog-timer.

aa.iv. Secure connection between master and slave modules; single channel communication.

aa.v. Robust wireless Master/Slave communication for up to 100 feet.

aa.vi. Adaptive frequency hopping using spread spectrum.

ab. P/N VA- KONNECT-D Viking Konnect Diagnostic Tool:

ab.i. Plug-and-play device.

ab.ii. Full duplex communication.

ab.iii. Self-monitor data communication watch-dog-timer.

ab.iv. Secure connectivity.

ab.v. Robust wireless communication.

ab.vi. Adaptive frequency hopping using spread spectrum.

ab.vii. Apple, Android and Windows smart devices compatible.

ab.viii. PC and laptop computers via Bluetooth compatible.

ab.ix. Set and adjust operator parameters.

ab.x. Remote diagnostic information

ab.xi. Displays the control board's LED status indicators.

ab.xii. Specifier Notes: Viking Monitor Module is optional. Delete if not required.

ac. P/N VA-MONITOR Viking Monitor Module:

ac.i. Plug and play device.

ac.ii. Off-site communication using a PC computer via internet and cellular network.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

ac.iii. Provides a virtual overview of the gate operators' control board.

ac.iv. Real-time display of the control board's settings.

ac.v. Real-time display of the control board's LED status indicators.

ac.vi. Real-time display of the control board's LCD Display.

ac.vii. Real-time display of the operator's voltage supply and current draw.

ac.viii. Real-time display of the inputs as they are received from the access control and safety devices.

ac.ix. Historical data capture.

ac.x. Capable of monitoring multiple gate operators.

17. Release Mechanism:

a. Fail-safe/fail-secure.

b. Allows full and safe manual operation of gate by use of a switch.

C. Swing Gate Operators: Model “R-6”

1.UL Listed and ETL listed in compliance to UL325 and UL991 2.UL 325, Class I 3.Operation: 24 VDC 4.Maximum Gate Size: a. 14-Foot Gate: 700 lbs. 5. Maximum Operating Speed: 13 to 16 seconds per 90 degrees.

6. Motor: DC brush motor

7. Operating temperature: Minus 20 degrees F to160 degrees F.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

8. Maximum Duty Cycle: 100 percent; continuous cycle.

9. Chassis: steel, galvanized G90, zinc plated and powder coated.

a.i. Specifier Notes: Viking Pipe Stand products are optional. Delete if not required.

10. P/N VA-F1PS Pipe Stand Kit:

a. Max 3” O.D. pipe diameter compatible.

b. 1/4 "steel, galvanized G90, zinc plated and powder coated.

11. Power:

a. Main Power Source: 120 or 220 VAC, single phase

a.i.1. Built-in power selector switch

b. Consumption Current: 4 A at 120 VAC and 2 A at 220 VAC.

c. EMI Filter and lightning Protection: For AC line up to 10 kA.

c.i. Specifier Notes: Alternative power sources consisting of solar panels or plug-in transformers are optional. Delete if not required. Consult Viking Access Systems for more information.

d. Alternative Power Sources:

d.i. [24 VDC, 80 W solar panel.]

d.ii. [24VAC, 40 VA plug-in transformer.]

d.iii. [24VDC, 40 VA plug-in transformer.]

d.iv. [P/N VA-SOCHP Viking Solar Kit.]

e. Built-in Battery: 12 VDC x 2.

f. Built-in Battery-Backup Operation: 400 full cycles (600 lbs.).

g. Toroidal Transformer: Up to 240 VA of power.

h. Unit uses main power source, battery is only needed in case of power failure.

12. Built-in Power Supply

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

a. Toroidal Transformer.

b. Accessible power switch.

c. Accessible fuse holder.

d. Accessible AC receptacle; up to 3 Amps.

e. Incoming power LED indicator.

f. Outgoing power LED indicator.

g. Surge protection in good status LED indicator.

h. Slide-able for accessible service.

i. EMI filter board.

j. Surge protection up to 10kA

13. Accessible battery switch/breaker

14. Accessible motor switch/breaker

15. Built-in heater allowing operation down to minus 20 degrees F.

16. Control Board Enclosure: ABS Plastic V-0 rating according to UL94

17. Logic Board: “VFlex”

a. Redundancy design.

b. Intelligent Obstruction Sensor:

b.i. Multiple algorithms supervising obstructions.

c. Built-in lightning strike protection up to 20 kV and 10 kA.

c.i. Multiple stage protection.

d. Built-in overcurrent and short circuit protected.

d.i. Multiple stage protection.

e. Regulated power supply for external accessories up to 1 A.

f. Built-in battery charger.

g. Soft start/stop gate control.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

h. Self-adaptive and self-learn algorithms for travel control.

i. Self-adaptive and self-learn algorithms for limit of travel accuracy.

j. Self-adaptive and self-learn algorithms for torque control.

k. Speed control algorithm to ensure constant speed of travel independent of power fluctuations.

l. Thermostatic control of the built-in heater.

m. Lock Mode feature detects unauthorized movement of the gate and maintains the limit position.

n. Anti-tailgating feature preventing vehicular tailgating.

o. Multiple ports of connection for plug-and-play devices

p. Pluggable accessory connectors.

q. Master/Slave synchronization in tandem operation between 2 gates.

r. Magnetic lock control; 250 VAC/10 A contact.

s. LED indicators for external accessories and power status.

t. Hold-Open timer adjustable from 0 to 60 seconds.

u. Speed Control adjustable from –25 % up to +50 % of the nominal speed

v. Overlap delay adjustable from 0 to 6 seconds to control master/slave operation of tandem gates; opening one gate first and after few seconds opening the second gate.

w. Auto-Open feature in case of power outage.

x. Last-Open feature in case the batteries are low during power outage.

y. Pre-operation warning feature; 3 seconds warning before gate starts moving.

y.i. Specifier Notes: Viking Konnect products are optional. Delete if not required.

z. P/N VA-KONNECT-MS Viking Konnect Master/Slave Kit:

z.i. Plug-and-play device.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

z.ii. Full duplex communication.

z.iii. Self-monitor data communication watch-dog-timer.

z.iv. Secure connection between master and slave modules; single channel communication.

z.v. Robust wireless Master/Slave communication for up to 100 feet.

z.vi. Adaptive frequency hopping using spread spectrum.

aa. P/N VA- KONNECT-D Viking Konnect Diagnostic Tool:

aa.i. Plug-and-play device.

aa.ii. Full duplex communication.

aa.iii. Self-monitor data communication watch-dog-timer.

aa.iv. Secure connectivity.

aa.v. Robust wireless communication.

aa.vi. Adaptive frequency hopping using spread spectrum.

aa.vii. Apple, Android and Windows smart devices compatible.

aa.viii. PC and laptop computers via Bluetooth compatible.

aa.ix. Set and adjust operator parameters.

aa.x. Remote diagnostic information

aa.xi. Displays the control board's LED status indicators.

aa.xii. Specifier Notes: Viking Monitor Module is optional. Delete if not required.

ab. P/N VA-MONITOR Viking Monitor Module:

ab.i. Plug and play device.

ab.ii. Off-site communication using a PC computer via internet and cellular network.

ab.iii. Provides a virtual overview of the gate operators' control board.

ab.iv. Real-time display of the control board's settings.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

ab.v. Real-time display of the control board's LED status indicators.

ab.vi. Real-time display of the control board's LCD Display.

ab.vii. Real-time display of the operator's voltage supply and current draw.

ab.viii. Real-time display of the inputs as they are received from the access control and safety devices.

ab.ix. Historical data capture.

ab.x. Capable of monitoring multiple gate operators.

18. Clutch Mechanism:

a. Fail-safe/fail-secure.

b. Allows full and safe operation of gate operator by use of the Clutch-Key.

c. The Clutch-Key in place enables security to prevent clutch action needed in fail-secure system.

d. Versatility to comply with various fire codes.

e. Convenient manual release in case of emergency.

19. Cover:

a. UV-stabilized polyethylene.

b. In compliance with UL746C.

c. Clam-shell design; easily removable, allowing access to entire gate operator.

D. Swing Gate Operators: Model “T-21”

1.UL Listed and ETL listed in compliance to UL325 and UL991 2.UL 325, Class I, II, III, and IV vehicular gate operator. 3.Operation: 24 VDC with 1 HP motor. 4.Maximum Gate Size: a. 12-Foot Gate: 2,000 lbs. b. 20-Foot Gate: 1,200 lbs.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

5. Maximum Operating Speed: 13 to 16 seconds per 90 degrees.

6. Motor: DC brush motor / helical-bevel gear-head

7. Operating temperature: Minus 20 degrees F to160 degrees F.

8. Maximum Duty Cycle: 100 percent; continuous cycle.

9. Chassis: 1/4 "steel, galvanized G90, zinc plated and powder coated.

a.i. Specifier Notes: Viking Pipe Stand products are optional. Delete if not required.

10. P/N VA-F1PS Pipe Stand Kit:

a. Max 3” O.D. pipe diameter compatible.

b. 1/4 "steel, galvanized G90, zinc plated and powder coated.

11. Power:

a. Main Power Source: 120 or 220 VAC, single phase

a.i.1. Built-in power selector switch

b. Consumption Current: 4 A at 120 VAC and 2 A at 220 VAC.

c. EMI Filter and lightning Protection: For AC line up to 10 kA.

c.i. Specifier Notes: Alternative power sources consisting of solar panels or plug-in transformers are optional. Delete if not required. Consult Viking Access Systems for more information.

d. Alternative Power Sources:

d.i. [24 VDC, 80 W solar panel.]

d.ii. [24VAC, 40 VA plug-in transformer.]

d.iii. [24VDC, 40 VA plug-in transformer.]

d.iv. [Built-in Power Supply remotely used.]

d.v. [P/N VA-SOCHP Viking Solar Kit.]

e. Built-in Battery: 7 Amp-hr, 12 VDC x 2.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

f. Built-in Battery-Backup Operation: 400 full cycles (2000 lbs.).

g. Toroidal Transformer: Up to 360 VA of power.

h. Unit uses main power source, battery is only needed in case of power failure.

12. Built-in Removable Power Supply

a. Toroidal Transformer.

b. Accessible power switch.

c. Accessible fuse holder.

d. Accessible AC receptacle up to 3 Amps.

e. Incoming power LED indicator.

f. Outgoing power LED indicator.

g. Surge protection in good status LED indicator.

h. Slide-out design for accessible service.

i. EMI filter board.

j. Surge protection up to 10kA

13. Built-in and pre-wired Loop Rack for up to 3 plug-in loop detectors

14. Accessible battery switch/breaker

15. Accessible motor switch/breaker

16. Built-in heater allowing operation down to minus 20 degrees F.

17. Control Board Enclosure: ABS Plastic V-0 rating according to UL94

18. Logic Board: “VFlex”

a. Redundancy design.

b. Intelligent Obstruction Sensor:

b.i. Multiple algorithms supervising obstructions.

c. Built-in lightning strike protection up to 20 kV and 10 kA.

c.i. Multiple stage protection.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

d. Built-in overcurrent and short circuit protected.

d.i. Multiple stage protection.

e. Regulated power supply for external accessories up to 1 A.

f. Built-in battery charger.

g. Soft start/stop gate control.

h. Self-adaptive and self-learn algorithms for travel control.

i. Self-adaptive and self-learn algorithms for limit of travel accuracy.

j. Self-adaptive and self-learn algorithms for torque control.

k. Speed control algorithm to ensure constant speed of travel independent of power fluctuations.

l. Thermostatic control of the built-in heater.

m. Lock Mode feature detects unauthorized movement of the gate and maintains the limit position.

n. Anti-tailgating feature preventing vehicular tailgating.

o. Multiple ports of connection for plug-and-play devices

p. Pluggable accessory connectors.

q. Master/Slave synchronization in tandem operation between 2 gates.

r. Magnetic lock control; 250 VAC/10 A contact.

s. LED indicators for external accessories and power status.

t. Hold-Open timer adjustable from 0 to 60 seconds.

u. Speed Control adjustable from –25 % up to +50 % of the nominal speed

v. Overlap delay adjustable from 0 to 6 seconds to control master/slave operation of tandem gates; opening one gate first and after few seconds opening the second gate.

w. Auto-Open feature in case of power outage.

x. Last-Open feature in case the batteries are low during power outage.

y. Pre-operation warning feature; 3 seconds warning before gate starts moving.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

y.i. Specifier Notes: Viking Konnect products are optional. Delete if not required.

z. P/N VA-KONNECT-MS Viking Konnect Master/Slave Kit:

z.i. Plug-and-play device.

z.ii. Full duplex communication.

z.iii. Self-monitor data communication watch-dog-timer.

z.iv. Secure connection between master and slave modules; single channel communication.

z.v. Robust wireless Master/Slave communication for up to 100 feet.

z.vi. Adaptive frequency hopping using spread spectrum.

aa. P/N VA- KONNECT-D Viking Konnect Diagnostic Tool:

aa.i. Plug-and-play device.

aa.ii. Full duplex communication.

aa.iii. Self-monitor data communication watch-dog-timer.

aa.iv. Secure connectivity.

aa.v. Robust wireless communication.

aa.vi. Adaptive frequency hopping using spread spectrum.

aa.vii. Apple, Android and Windows smart devices compatible.

aa.viii. PC and laptop computers via Bluetooth compatible.

aa.ix. Set and adjust operator parameters.

aa.x. Remote diagnostic information

aa.xi. Displays the control board's LED status indicators.

aa.xii. Specifier Notes: Viking Monitor Module is optional. Delete if not required.

ab. P/N VA-MONITOR Viking Monitor Module:

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

ab.i. Plug and play device.

ab.ii. Off-site communication using a PC computer via internet and cellular network.

ab.iii. Provides a virtual overview of the gate operators' control board.

ab.iv. Real-time display of the control board's settings.

ab.v. Real-time display of the control board's LED status indicators.

ab.vi. Real-time display of the control board's LCD Display.

ab.vii. Real-time display of the operator's voltage supply and current draw.

ab.viii. Real-time display of the inputs as they are received from the access control and safety devices.

ab.ix. Historical data capture.

ab.x. Capable of monitoring multiple gate operators.

19. Clutch Mechanism:

a. Fail-safe/fail-secure.

b. Allows full and safe operation of gate operator by use of the Clutch-Key.

c. The Clutch-Key in place enables security to prevent clutch action needed in fail-secure system.

d. Versatility to comply with various fire codes.

e. Convenient manual release in case of emergency.

20. Cover:

a. UV-stabilized polyethylene.

b. In compliance with UL746C.

c. Clam-shell design; easily removable, allowing access to entire gate operator.

E. Underground Swing Gate Operators: Model “I-8”

1.UL Listed and ETL listed in compliance to UL325 and UL991

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

2.UL 325, Class I, II, III, and IV vehicular gate operator. 3.Operation: 24 VDC with 1/2 HP motor. 4.Maximum Gate Size: a. 12-Foot Gate: 650 lbs. 5. Maximum Operating Speed: 10 to 13 seconds per 90 degrees.

6. Motor: DC brush motor

7. Operating temperature: Minus 20 degrees F to160 degrees F.

8. Maximum Duty Cycle: 100 percent; continuous cycle.

a.i. Specifier Notes: Specify steel or stainless steel casing. Steel is standard. Stainless steel is optional.

9. Chassis:

a.i. [Steel]

a.ii. [Stainless steel]

10. Power:

a. Main Power Source: 120 or 220 VAC, single phase

a.i.1. Built-in power selector switch

b. Consumption Current: 4 A at 120 VAC and 2 A at 220 VAC.

c. EMI Filter and lightning Protection: For AC line up to 10 kA.

c.i. Specifier Notes: Alternative power sources consisting of solar panels or plug-in transformers are optional. Delete if not required. Consult Viking Access Systems for more information.

d. Alternative Power Sources:

d.i. [24 VDC, 80 W solar panel.]

d.ii. [24VAC, 40 VA plug-in transformer.]

d.iii. [24VDC, 40 VA plug-in transformer.]

d.iv. [Built-in Power Supply remotely used.]

d.v. [P/N VA-SOCHP Viking Solar Kit.]

e. Built-in Battery: 12 VDC x 2.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

f. Built-in Battery-Backup Operation: 400 full cycles (600 lbs.).

g. Toroidal Transformer: Up to 240 VA of power.

h. Unit uses main power source, battery is only needed in case of power failure.

11. Power Supply

a. Toroidal Transformer.

b. Incoming power LED indicator.

c. Outgoing power LED indicator.

d. Surge protection in good status LED indicator.

e. EMI filter board.

f. Surge protection up to 10kA

12. Accessible battery switch/breaker

13. Built-in heater allowing operation down to minus 20 degrees F.

14. Control Board Enclosure: ABS Plastic V-0 rating according to UL94

15. Logic Board: “VFlex”

a. Redundancy design.

b. Intelligent Obstruction Sensor:

b.i. Multiple algorithms supervising obstructions.

c. Built-in lightning strike protection up to 20 kV and 10 kA.

c.i. Multiple stage protection.

d. Built-in overcurrent and short circuit protected.

d.i. Multiple stage protection.

e. Regulated power supply for external accessories up to 1 A.

f. Built-in battery charger.

g. Soft start/stop gate control.

h. Self-adaptive and self-learn algorithms for travel control.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

i. Self-adaptive and self-learn algorithms for limit of travel accuracy.

j. Self-adaptive and self-learn algorithms for torque control.

k. Speed control algorithm to ensure constant speed of travel independent of power fluctuations.

l. Thermostatic control of the built-in heater.

m. Lock Mode feature detects unauthorized movement of the gate and maintains the limit position.

n. Anti-tailgating feature preventing vehicular tailgating.

o. Multiple ports of connection for plug-and-play devices

p. Pluggable accessory connectors.

q. Master/Slave synchronization in tandem operation between 2 gates.

r. Magnetic lock control; 250 VAC/10 A contact.

s. LED indicators for external accessories and power status.

t. Hold-Open timer adjustable from 0 to 60 seconds.

u. Speed Control adjustable from –25 % up to +50 % of the nominal speed

v. Overlap delay adjustable from 0 to 6 seconds to control master/slave operation of tandem gates; opening one gate first and after few seconds opening the second gate.

w. Auto-Open feature in case of power outage.

x. Last-Open feature in case the batteries are low during power outage.

y. Pre-operation warning feature; 3 seconds warning before gate starts moving.

y.i. Specifier Notes: Viking Konnect products are optional. Delete if not required.

z. P/N VA-KONNECT-MS Viking Konnect Master/Slave Kit:

z.i. Plug-and-play device.

z.ii. Full duplex communication.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

z.iii. Self-monitor data communication watch-dog-timer.

z.iv. Secure connection between master and slave modules; single channel communication.

z.v. Robust wireless Master/Slave communication for up to 100 feet.

z.vi. Adaptive frequency hopping using spread spectrum.

aa. P/N VA- KONNECT-D Viking Konnect Diagnostic Tool:

aa.i. Plug-and-play device.

aa.ii. Full duplex communication.

aa.iii. Self-monitor data communication watch-dog-timer.

aa.iv. Secure connectivity.

aa.v. Robust wireless communication.

aa.vi. Adaptive frequency hopping using spread spectrum.

aa.vii. Apple, Android and Windows smart devices compatible.

aa.viii. PC and laptop computers via Bluetooth compatible.

aa.ix. Set and adjust operator parameters.

aa.x. Remote diagnostic information

aa.xi. Displays the control board's LED status indicators.

aa.xii. Specifier Notes: Viking Monitor Module is optional. Delete if not required.

ab. P/N VA-MONITOR Viking Monitor Module:

ab.i. Plug and play device.

ab.ii. Off-site communication using a PC computer via internet and cellular network.

ab.iii. Provides a virtual overview of the gate operators' control board.

ab.iv. Real-time display of the control board's settings.

ab.v. Real-time display of the control board's LED status indicators.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

ab.vi. Real-time display of the control board's LCD Display.

ab.vii. Real-time display of the operator's voltage supply and current draw.

ab.viii. Real-time display of the inputs as they are received from the access control and safety devices.

ab.ix. Historical data capture.

ab.x. Capable of monitoring multiple gate operators.

16. Manual Release: Allows full and safe manual operation of gate by use of a key.

2.3 SLIDE GATE OPERATORS A. Slide Gate Operators: Model “L-3”

1.UL Listed and ETL listed in compliance to UL325 and UL991 2.UL 325, Class I, II, III, and IV vehicular gate operator. 3.Operation: 24 VDC with 1/2 HP motor. 4.Maximum Gate Size: a. 60-Foot Gate: 1,600 lbs. 5. Maximum Operating Speed: 12 in/sec.

6. Motor: DC brush motor

7. Operating temperature: Minus 20 degrees F to160 degrees F.

8. Maximum Duty Cycle: 100 percent; continuous cycle.

9. Chassis: Steel, Galvanized G90, zinc plated and powder coated.

10. Chassis: Post-mount ready

a. Max 3” O.D. pipe diameter compatible.

11. Power:

a. Main Power Source: 120 or 220 VAC, single phase

a.i.1. Built-in power selector switch

b. Consumption Current: 4 A at 120 VAC and 2 A at 220 VAC.

c. EMI Filter and lightning Protection: For AC line up to 10 kA.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

c.i. Specifier Notes: Alternative power sources consisting of solar panels or plug-in transformers are optional. Delete if not required. Consult Viking Access Systems for more information.

d. Alternative Power Sources:

d.i. [24 VDC, 80 W solar panel.]

d.ii. [24VAC, 40 VA plug-in transformer.]

d.iii. [24VDC, 40 VA plug-in transformer.]

d.iv. [Built-in Removable Power Supply.]

d.v. [P/N VA-SOCHP Viking Solar Kit.]

e. Built-in Battery: 7 Amp-hr, 12 VDC x 2.

f. Built-in Battery-Backup Operation: 100 full cycles (1600 lbs.).

g. Toroidal Transformer: Up to 360 VA of power.

h. Unit uses main power source, battery is only needed in case of power failure.

12. Built-in Removable Power Supply

a. Toroidal Transformer.

b. Accessible power switch.

c. Accessible fuse holder.

d. Accessible AC receptacle; up to 3 Amps.

e. Incoming power LED indicator.

f. Outgoing power LED indicator.

g. Surge protection in good status LED indicator.

h. Slide-out design for accessible service.

i. EMI filter board.

j. Surge protection up to 10kA

13. Built-in and pre-wired Loop Rack for up to 3 plug-in loop detectors

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

14. Accessible battery switch/breaker

15. Accessible motor switch/breaker

16. Built-in heater allowing operation down to minus 20 degrees F.

17. Control Board Enclosure: ABS Plastic V-0 rating according to UL94

18. Logic Board: “VFlex”

a. Redundancy design.

b. Intelligent Obstruction Sensor:

b.i. Multiple algorithms supervising obstructions.

c. Built-in lightning strike protection up to 20 kV and 10 kA.

c.i. Multiple stage protection.

d. Built-in overcurrent and short circuit protected.

d.i. Multiple stage protection.

e. Regulated power supply for external accessories up to 1 A.

f. Built-in battery charger.

g. Soft start/stop gate control.

h. Self-adaptive and self-learn algorithms for travel control.

i. Self-adaptive and self-learn algorithms for limit of travel accuracy.

j. Self-adaptive and self-learn algorithms for torque control.

k. Speed control algorithm to ensure constant speed of travel independent of power fluctuations.

l. Thermostatic control of the built-in heater.

m. Lock Mode feature detects unauthorized movement of the gate and maintains the limit position.

n. Anti-tailgating feature preventing vehicular tailgating.

o. Multiple ports of connection for plug-and-play devices

p. Pluggable accessory connectors.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

q. Fail-Safe or Fail-Secure selections.

r. Master/Slave synchronization in tandem operation between 2 gates.

s. Magnetic lock control; 250 VAC/10 A contact.

t. LED indicators for external accessories and power status.

u. Hold-Open timer adjustable from 0 to 60 seconds.

v. Speed Control adjustable from –25 % up to +50 % of the nominal speed

w. Auto-Open feature in case of power outage.

x. Last-Open feature in case the batteries are low during power outage.

y. Pre-operation warning feature; 3 seconds warning before gate starts moving.

y.i. Specifier Notes: Viking Konnect products are optional. Delete if not required.

z. P/N VA-KONNECT-MS Viking Konnect Master/Slave Kit:

z.i. Plug-and-play device.

z.ii. Full duplex communication.

z.iii. Self-monitor data communication watch-dog-timer.

z.iv. Secure connection between master and slave modules; single channel communication.

z.v. Robust wireless Master/Slave communication for up to 100 feet.

z.vi. Adaptive frequency hopping using spread spectrum.

aa. P/N VA- KONNECT-D Viking Konnect Diagnostic Tool:

aa.i. Plug-and-play device.

aa.ii. Full duplex communication.

aa.iii. Self-monitor data communication watch-dog-timer.

aa.iv. Secure connectivity.

aa.v. Robust wireless communication.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

aa.vi. Adaptive frequency hopping using spread spectrum.

aa.vii. Apple, Android and Windows smart devices compatible.

aa.viii. PC and laptop computers via Bluetooth compatible.

aa.ix. Set and adjust operator parameters.

aa.x. Remote diagnostic information

aa.xi. Displays the control board's LED status indicators.

aa.xii. Specifier Notes: Viking Monitor Module is optional. Delete if not required.

ab. P/N VA-MONITOR Viking Monitor Module:

ab.i. Plug and play device.

ab.ii. Off-site communication using a PC computer via internet and cellular network.

ab.iii. Provides a virtual overview of the gate operators' control board.

ab.iv. Real-time display of the control board's settings.

ab.v. Real-time display of the control board's LED status indicators.

ab.vi. Real-time display of the control board's LCD Display.

ab.vii. Real-time display of the operator's voltage supply and current draw.

ab.viii. Real-time display of the inputs as they are received from the access control and safety devices.

ab.ix. Historical data capture.

ab.x. Capable of monitoring multiple gate operators.

19. Cover:

a. UV-stabilized polyethylene.

b. In compliance with UL746C.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

B. Slide Gate Operators: Model “H-10”

1.UL Listed and ETL listed in compliance to UL325 and UL991 2.UL 325, Class I, II, III, and IV vehicular gate operator. 3.Operation: 24 VDC with 1 HP motor. 4.Maximum Gate Size: a. 75-Foot Gate: 2,200 lbs. 5. Maximum Operating Speed: 12 in/sec.

6. Motor: DC brush motor

7. Operating temperature: Minus 20 degrees F to160 degrees F.

8. Maximum Duty Cycle: 100 percent; continuous cycle.

9. Chassis: Galvanized G90, zinc plated and powder coated.

10. Chassis: Post Mount ready

a. Max 3” O.D. pipe diameter compatible.

11. Power:

a. Main Power Source: 120 or 220 VAC, single phase

a.i.1. Built-in power selector switch

b. Consumption Current: 4 A at 120 VAC and 2 A at 220 VAC.

c. EMI Filter and lightning Protection: For AC line up to 10 kA.

c.i. Specifier Notes: Alternative power sources consisting of solar panels or plug-in transformers are optional. Delete if not required. Consult Viking Access Systems for more information.

d. Alternative Power Sources:

d.i. [24 VDC, 80 W solar panel.]

d.ii. [24VAC, 40 VA plug-in transformer.]

d.iii. [24VDC, 40 VA plug-in transformer.]

d.iv. [Built-in Removable Power Supply.]

d.v. [P/N VA-SOCHP Viking Solar Kit.]

e. Built-in Battery: 7 Amp-hr, 12 VDC x 2.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

f. Built-in Battery-Backup Operation: 100 full cycles (2200 lbs.).

g. Toroidal Transformer: Up to 360 VA of power.

h. Unit uses main power source, battery is only needed in case of power failure.

12. Built-in Removable Power Supply

a. Toroidal Transformer.

b. Accessible power switch.

c. Accessible fuse holder.

d. Accessible AC receptacle; up to 3 Amps.

e. Incoming power LED indicator.

f. Outgoing power LED indicator.

g. Surge protection in good status LED indicator.

h. Slide-out design for accessible service.

i. EMI filter board.

j. Surge protection up to 10kA

13. Built-in and pre-wired Loop Rack for up to 3 plug-in loop detectors

14. Accessible battery switch/breaker

15. Accessible motor switch/breaker

16. Built-in heater allowing operation down to minus 20 degrees F.

17. Control Board Enclosure: ABS Plastic V-0 rating according to UL94

18. Logic Board: “VFlex”

a. Redundancy design.

b. Intelligent Obstruction Sensor:

b.i. Multiple algorithms supervising obstructions.

c. Built-in lightning strike protection up to 20 kV and 10 kA.

c.i. Multiple stage protection.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

d. Built-in overcurrent and short circuit protected.

d.i. Multiple stage protection.

e. Regulated power supply for external accessories up to 1 A.

f. Built-in battery charger.

g. Soft start/stop gate control.

h. Self-adaptive and self-learn algorithms for travel control.

i. Self-adaptive and self-learn algorithms for limit of travel accuracy.

j. Self-adaptive and self-learn algorithms for torque control.

k. Speed control algorithm to ensure constant speed of travel independent of power fluctuations.

l. Thermostatic control of the built-in heater.

m. Lock Mode feature detects unauthorized movement of the gate and maintains the limit position.

n. Anti-tailgating feature preventing vehicular tailgating.

o. Multiple ports of connection for plug-and-play devices

p. Pluggable accessory connectors.

q. Fail-Safe or Fail-Secure selections.

r. Master/Slave synchronization in tandem operation between 2 gates.

s. Magnetic lock control; 250 VAC/10 A contact.

t. LED indicators for external accessories and power status.

u. Hold-Open timer adjustable from 0 to 60 seconds.

v. Speed Control adjustable from –25 % up to +50 % of the nominal speed

w. Auto-Open feature in case of power outage.

x. Last-Open feature in case the batteries are low during power outage.

y. Pre-operation warning feature; 3 seconds warning before gate starts moving.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

y.i. Specifier Notes: Viking Konnect products are optional. Delete if not required.

z. P/N VA-KONNECT-MS Viking Konnect Master/Slave Kit:

z.i. Plug-and-play device.

z.ii. Full duplex communication.

z.iii. Self-monitor data communication watch-dog-timer.

z.iv. Secure connection between master and slave modules; single channel communication.

z.v. Robust wireless Master/Slave communication for up to 100 feet.

z.vi. Adaptive frequency hopping using spread spectrum.

aa. P/N VA- KONNECT-D Viking Konnect Diagnostic Tool:

aa.i. Plug-and-play device.

aa.ii. Full duplex communication.

aa.iii. Self-monitor data communication watch-dog-timer.

aa.iv. Secure connectivity.

aa.v. Robust wireless communication.

aa.vi. Adaptive frequency hopping using spread spectrum.

aa.vii. Apple, Android and Windows smart devices compatible.

aa.viii. PC and laptop computers via Bluetooth compatible.

aa.ix. Set and adjust operator parameters.

aa.x. Remote diagnostic information

aa.xi. Displays the control board's LED status indicators.

aa.xii. Specifier Notes: Viking Monitor Module is optional. Delete if not required.

ab. P/N VA-MONITOR Viking Monitor Module:

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

ab.i. Plug and play device.

ab.ii. Off-site communication using a PC computer via internet and cellular network.

ab.iii. Provides a virtual overview of the gate operators' control board.

ab.iv. Real-time display of the control board's settings.

ab.v. Real-time display of the control board's LED status indicators.

ab.vi. Real-time display of the control board's LCD Display.

ab.vii. Real-time display of the operator's voltage supply and current draw.

ab.viii. Real-time display of the inputs as they are received from the access control and safety devices.

ab.ix. Historical data capture.

ab.x. Capable of monitoring multiple gate operators.

19. Cover:

a. UV-stabilized polyethylene.

b. In compliance with UL746C.

C. Slide Gate Operators: Model “K-2”

1.UL Listed and ETL listed in compliance to UL325 and UL991 2.UL 325, Class I vehicular gate operator. 3.Operation: 24 VDC 4.Maximum Gate Size: a. 30-Foot Gate: 700 lbs. 5. Maximum Operating Speed: 12 in/sec.

6. Motor: DC brush motor

7. Operating temperature: Minus 20 degrees F to160 degrees F.

8. Maximum Duty Cycle: 100 percent; continuous cycle.

9. Chassis: Steel, Galvanized G90, zinc plated and powder coated.

10. Chain: 25 Feet of nickel plated number 40 size chain

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

a.i. Specifier Notes: Viking Pipe Stand products are optional. Delete if not required.

11. Power:

a. Main Power Source: 120 or 220 VAC, single phase

a.i.1. Built-in power selector switch

b. Consumption Current: 4 A at 120 VAC and 2 A at 220 VAC.

c. EMI Filter and lightning Protection: For AC line up to 10 kA.

c.i. Specifier Notes: Alternative power sources consisting of solar panels or plug-in transformers are optional. Delete if not required. Consult Viking Access Systems for more information.

d. Alternative Power Sources:

d.i. [24 VDC, 80 W solar panel.]

d.ii. [24VAC, 40 VA plug-in transformer.]

d.iii. [24VDC, 40 VA plug-in transformer.]

d.iv. [P/N VA-SOCHP Viking Solar Kit.]

e. Built-in Battery: 12 VDC x 2.

f. Built-in Battery-Backup Operation: 100 full cycles (700 lbs.).

g. Toroidal Transformer: Up to 240 VA of power.

h. Unit uses main power source, battery is only needed in case of power failure.

12. Built-in Power Supply

a. Toroidal Transformer.

b. Accessible power switch.

c. Accessible fuse holder.

d. Accessible AC receptacle; up to 3 Amps.

e. Incoming power LED indicator.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

f. Outgoing power LED indicator.

g. Surge protection in good status LED indicator.

h. Slide-out design for accessible service.

i. EMI filter board.

j. Surge protection up to 10kA

13. Accessible battery switch/breaker

14. Accessible motor switch/breaker

15. Built-in heater allowing operation down to minus 20 degrees F.

16. Control Board Enclosure: ABS Plastic V-0 rating according to UL94

17. Logic Board: “VFlex”

a. Redundancy design.

b. Intelligent Obstruction Sensor:

b.i. Multiple algorithms supervising obstructions.

c. Built-in lightning strike protection up to 20 kV and 10 kA.

c.i. Multiple stage protection.

d. Built-in overcurrent and short circuit protected.

d.i. Multiple stage protection.

e. Regulated power supply for external accessories up to 1 A.

f. Built-in battery charger.

g. Soft start/stop gate control.

h. Self-adaptive and self-learn algorithms for travel control.

i. Self-adaptive and self-learn algorithms for limit of travel accuracy.

j. Self-adaptive and self-learn algorithms for torque control.

k. Speed control algorithm to ensure constant speed of travel independent of power fluctuations.

l. Thermostatic control of the built-in heater.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

m. Lock Mode feature detects unauthorized movement of the gate and maintains the limit position.

n. Anti-tailgating feature preventing vehicular tailgating.

o. Multiple ports of connection for plug-and-play devices

p. Pluggable accessory connectors.

q. Fail-Safe or Fail-Secure selections.

r. Master/Slave synchronization in tandem operation between 2 gates.

s. Magnetic lock control; 250 VAC/10 A contact.

t. LED indicators for external accessories and power status.

u. Hold-Open timer adjustable from 0 to 60 seconds.

v. Speed Control adjustable from –25 % up to +50 % of the nominal speed

w. Auto-Open feature in case of power outage.

x. Last-Open feature in case the batteries are low during power outage.

y. Pre-operation warning feature; 3 seconds warning before gate starts moving.

y.i. Specifier Notes: Viking Konnect products are optional. Delete if not required.

z. P/N VA-KONNECT-MS Viking Konnect Master/Slave Kit:

z.i. Plug-and-play device.

z.ii. Full duplex communication.

z.iii. Self-monitor data communication watch-dog-timer.

z.iv. Secure connection between master and slave modules; single channel communication.

z.v. Robust wireless Master/Slave communication for up to 100 feet.

z.vi. Adaptive frequency hopping using spread spectrum.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

z.vii. Specifier Notes: Viking Konnect products are optional. Delete if not required.

aa. P/N VA- KONNECT-D Viking Konnect Diagnostic Tool:

aa.i. Plug-and-play device.

aa.ii. Full duplex communication.

aa.iii. Self-monitor data communication watch-dog-timer.

aa.iv. Secure connectivity.

aa.v. Robust wireless communication.

aa.vi. Adaptive frequency hopping using spread spectrum.

aa.vii. Apple, Android and Windows smart devices compatible.

aa.viii. PC and laptop computers via Bluetooth compatible.

aa.ix. Set and adjust operator parameters.

aa.x. Remote diagnostic information

aa.xi. Displays the control board's LED status indicators.

aa.xii. Specifier Notes: Viking Monitor Module is optional. Delete if not required.

ab. P/N VA-MONITOR Viking Monitor Module:

ab.i. Plug and play device.

ab.ii. Off-site communication using a PC computer via internet and cellular network.

ab.iii. Provides a virtual overview of the gate operators' control board.

ab.iv. Real-time display of the control board's settings.

ab.v. Real-time display of the control board's LED status indicators.

ab.vi. Real-time display of the control board's LCD Display.

ab.vii. Real-time display of the operator's voltage supply and current draw.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

ab.viii. Real-time display of the inputs as they are received from the access control and safety devices.

ab.ix. Historical data capture.

ab.x. Capable of monitoring multiple gate operators.

18. Cover:

a. UV-stabilized polyethylene.

b. In compliance with UL746C.

D. Slide Gate Operators: Model “Q-7”

1.UL Listed and ETL listed in compliance to UL325 and UL991 2.UL 325, Class I, III, and IV vehicular gate operator. 3.Operation: 24 VDC with 1 HP motor. 4.Maximum Gate Size: a. 120-Foot Gate: 7,000 lbs. 5. Maximum Operating Speed: 14 in/sec.

6. Motor: DC brush motor

7. Manual Release allowing moving of the gate independent of the gate operator.

8. Operating temperature: Minus 20 degrees F to160 degrees F.

9. Maximum Duty Cycle: 100 percent; continuous cycle.

10. Chassis: ¼” thickness, Galvanized G90, zinc plated and powder coated.

11. Power:

a. Main Power Source: 120 or 220 VAC, single phase

a.i.1. Built-in power selector switch

b. Consumption Current: 8 A at 120 VAC and 4 A at 220 VAC.

c. EMI Filter and lightning Protection: For AC line up to 10 kA.

c.i. Specifier Notes: Alternative power sources consisting of solar panels or plug-in transformers are optional. Delete if not required. Consult Viking Access Systems for more information.

d. Built-in Battery: 35 Amp-hr, 12 VDC x 2.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

e. Built-in Battery-Backup Operation: 100 full cycles (4000 lbs. / 40ft).

f. Toroidal Transformer: Up to 720 VA of power.

g. Unit uses main power source, battery is only needed in case of power failure.

12. Power Supply

a. Toroidal Transformer.

b. Accessible power switch.

c. Accessible fuse holder.

d. Two accessible AC receptacle; up to 3 Amps.

e. Incoming power LED indicator.

f. Outgoing power LED indicator.

g. Surge protection in good status LED indicator.

h. EMI filter board.

i. Surge protection up to 10kA

13. Built-in and pre-wired Loop Rack for up to 3 plug-in loop detectors

14. Accessible battery switch/breaker

15. Accessible motor switch/breaker

16. Built-in heater allowing operation down to minus 20 degrees F.

17. Control Board Enclosure: ABS Plastic V-0 rating according to UL94

18. Logic Board: “VFlex”

a. Redundancy design.

b. Intelligent Obstruction Sensor:

b.i. Multiple algorithms supervising obstructions.

c. Built-in lightning strike protection up to 20 kV and 10 kA.

c.i. Multiple stage protection.

d. Built-in overcurrent and short circuit protected.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

d.i. Multiple stage protection.

e. Regulated power supply for external accessories up to 1 A.

f. Built-in battery charger.

g. Soft start/stop gate control.

h. Self-adaptive and self-learn algorithms for travel control.

i. Self-adaptive and self-learn algorithms for limit of travel accuracy.

j. Self-adaptive and self-learn algorithms for torque control.

k. Speed control algorithm to ensure constant speed of travel independent of power fluctuations.

l. Thermostatic control of the built-in heater.

m. Lock Mode feature detects unauthorized movement of the gate and maintains the limit position.

n. Anti-tailgating feature preventing vehicular tailgating.

o. Multiple ports of connection for plug-and-play devices

p. Pluggable accessory connectors.

q. Fail-Safe or Fail-Secure selections.

r. Master/Slave synchronization in tandem operation between 2 gates.

s. Magnetic lock control; 250 VAC/10 A contact.

t. LED indicators for external accessories and power status.

u. Hold-Open timer adjustable from 0 to 60 seconds.

v. Speed Control adjustable from –25 % up to +50 % of the nominal speed

w. Auto-Open feature in case of power outage.

x. Last-Open feature in case the batteries are low during power outage.

y. Pre-operation warning feature; 3 seconds warning before gate starts moving.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

y.i. Specifier Notes: Viking Konnect products are optional. Delete if not required.

z. P/N VA-KONNECT-MS Viking Konnect Master/Slave Kit:

z.i. Plug-and-play device.

z.ii. Full duplex communication.

z.iii. Self-monitor data communication watch-dog-timer.

z.iv. Secure connection between master and slave modules; single channel communication.

z.v. Robust wireless Master/Slave communication for up to 100 feet.

z.vi. Adaptive frequency hopping using spread spectrum.

aa. P/N VA- KONNECT-D Viking Konnect Diagnostic Tool:

aa.i. Plug-and-play device.

aa.ii. Full duplex communication.

aa.iii. Self-monitor data communication watch-dog-timer.

aa.iv. Secure connectivity.

aa.v. Robust wireless communication.

aa.vi. Adaptive frequency hopping using spread spectrum.

aa.vii. Apple, Android and Windows smart devices compatible.

aa.viii. PC and laptop computers via Bluetooth compatible.

aa.ix. Set and adjust operator parameters.

aa.x. Remote diagnostic information

aa.xi. Displays the control board's LED status indicators.

aa.xii. Specifier Notes: Viking Monitor Module is optional. Delete if not required.

ab. P/N VA-MONITOR Viking Monitor Module:

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

ab.i. Plug and play device.

ab.ii. Off-site communication using a PC computer via internet and cellular network.

ab.iii. Provides a virtual overview of the gate operators' control board.

ab.iv. Real-time display of the control board's settings.

ab.v. Real-time display of the control board's LED status indicators.

ab.vi. Real-time display of the control board's LCD Display.

ab.vii. Real-time display of the operator's voltage supply and current draw.

ab.viii. Real-time display of the inputs as they are received from the access control and safety devices.

ab.ix. Historical data capture.

ab.x. Capable of monitoring multiple gate operators.

19. Cover:

a. Galvanized G90, zinc plated and powder coated.s

2.4 OPERATOR TECHNOLOGY b.i. Specifier Notes: Viking Konnect products are optional. Delete if not required.

A. P/N VA-KONNECT-MS Viking Konnect Master/Slave Kit:

A.i. Plug-and-play device.

A.ii. Full duplex communication.

A.iii. Self-monitor data communication watch-dog-timer.

A.iv. Secure connection between master and slave modules; single channel communication.

A.v. Robust wireless Master/Slave communication for up to 100 feet.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

A.vi. Adaptive frequency hopping using spread spectrum.

A.vii. Specifier Notes: Viking Konnect products are optional. Delete if not required.

B. P/N VA- KONNECT-D Viking Konnect Diagnostic Tool:

B.i. Plug-and-play device.

B.ii. Full duplex communication.

B.iii. Self-monitor data communication watch-dog-timer.

B.iv. Secure connectivity.

B.v. Robust wireless communication.

B.vi. Adaptive frequency hopping using spread spectrum.

B.vii. Apple, Android and Windows smart devices compatible.

B.viii. PC and laptop computers via Bluetooth compatible.

B.ix. Set and adjust operator parameters.

B.x. Remote diagnostic information

B.xi. Displays the control board's LED status indicators.

B.xii. Specifier Notes: Viking Monitor Module is optional. Delete if not required.

C. P/N VA-MONITOR Viking Monitor Module:

C.i. Plug and play device.

C.ii. Off-site communication using a PC computer via internet and cellular network.

C.iii. Provides a virtual overview of the gate operators' control board.

C.iv. Real-time display of the control board's settings.

C.v. Real-time display of the control board's LED status indicators.

C.vi. Real-time display of the control board's LCD Display.

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

C.vii. Real-time display of the operator's voltage supply and current draw.

C.viii. Real-time display of the inputs as they are received from the access control and safety devices.

C.ix. Historical data capture.

C.x. Capable of monitoring multiple gate operators.

2.5 ACCESSORIES

Specifier Notes: Specify required accessories. Delete accessories not required. Consult Viking Access Systems for more information.

A. Loop Rack:

Specifier Notes: Loop rack is standard with gate operators F-1, T-21, L-3, H-10, and Q-7.

1. Interfaces with up to 3 plug-in loop detectors. 2. Eliminates extra wiring or normal size loop detectors. 3. Uses 2 connectors for complete installation with 3 loop detectors.

B. Gear Head Heater: 1. Use when gate operators operate in temperatures below 0 degrees F. 2. Self-adhesive blanket with integrated thermostat that wraps around motor gear head. 3. Ensures proper viscosity of lubricant inside gear head.

C. Power Box: 1. Use when gate operators are not near 120 V AC or 220 V AC power supply. 2. Provides means to run low-voltage wires as power supply instead of providing high voltage. 3. Ensures continuous operation of gate operators.

Specifier Notes: Custom pipe stands are available for gate operators F-1, R-6, L-3, and H-10

D. Custom pipe stands.

E. Solar Panels: 1. Solar Output, Nominal Voltage: 12 V DC, 40 W. 2. Use 2 solar panels connected in series for 24 V DC solar system for gate operators.

PART 3 EXECUTION

3.1 EXAMINATION

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

A. Examine areas and gates to receive gate operators.

B. Notify Architect of conditions that would adversely affect installation or subsequent use.

C. Do not begin installation until unacceptable conditions are corrected.

3.2 PREPARATION

Specifier Notes: Include section number for gates.

A. Verify gates are installed as specified in Section ______and as indicated on the Drawings.

B. Verify gates are properly installed and move freely in both directions.

C. Verify gates are plumb, level, square, and without sag or damage.

3.3 INSTALLATION

A. Install gate operators in accordance with manufacturer’s instructions at locations indicated on the Drawings.

B. Install gate operators plumb, level, square, and secure on concrete pads.

Specifier Notes: Include section number for cast-in-place concrete.

C. Concrete for Pads: As specified in Section ______.

D. Install gate operators weather tight.

3.4 ADJUSTING

A. Adjust gate operators for proper operation in accordance with manufacturer’s instructions.

B. Adjust gate operators to operate smoothly and to open and close gates properly.

Specifier Notes: Edit the Demonstration article as required. Delete if a demonstration of the gate operators is not required.

3.5 DEMONSTRATION

A. Demonstrate for Owner and Architect: 1. Gate operators function properly. 2. Proper operation of gate operators.

3.6 PROTECTION

Gate Operators 02829 (32 31 33) - 2 Viking Access Systems July 2014

A. Protect installed gate operators to ensure that, except for normal weathering, gate operators will be without damage or deterioration at time of Substantial Completion.

END OF SECTION

Gate Operators 02829 (32 31 33) - 2