To: All Plan holders for the Invitation for Bid entitled “West Villages Elementary School Hot Water Circulation Pump Replacement (Reissued) ” dated July 18, 2013

Bids due: August 15, 2013, No Later than 2:00 pm, Bid Opening immediately following in basement conference room.

ADDENDUM #1

Addendum 1 issued to provide revised specifications per attached.

Addendum #1 must be acknowledged on the Bid Form. All other terms and conditions are to remain the same as previously stated.

Johanna F. Boucher Purchasing Agent Town of Barnstable

Addendum 1, July 24, 2013 1 Barnstable Public Schools West Villages Elementary School Hot Water Circulation Pump Replacement Revision # 1, Addendum 1, 7/24/13

Scope of services:

Provide supply and replacement of eight (8) water circulating pumps and all required motors, piping and labor for upgrades to current system. Pump configurations are as follows :

Condenser Water Pumps:  Replace existing Taco Pumps (2) FM2508 rated for 290 GPM @ 40’  Supply pumps with 5HP/1750/TEFC/230/460 Premium Efficiency Motors  Reuse existing concrete pads.  Replace suction diffusers with 5” x 4” Diffusers  Replace suction and discharge isolation valves with 5” Lug style butterfly valves.  Install 5”Wafer style silent check valves.  Replace Suction and Discharge Braided Flex Connectors  Modify existing suction and discharge piping as required  Wire new motors to existing power leads.  Provide new gauges and thermometers.

Chilled Water Pumps:  Replace existing Taco Pumps (2) FM2508 rated for 270 GPM @ 40’  Reuse existing concrete pads.  Replace suction diffusers with 5” x 4” diffusers.  Replace suction and discharge isolation valves with 5” Lug style butterfly valves.  Install 5” Wafer style silent check valves.  Replace suction and discharge braided flex connectors.  Modify existing suction and discharge piping as required.  Insulate piping as necessary.  Provide new gauges and thermometers.

Addendum 1, July 24, 2013 2 West Villages Pumps (cont.)

Heat Circulation Pumps:  Replace existing Taco Vertical Inline Pumps (3) with the following flow rates, 1-110 GPM @117’, 1-100 GPM @ 82’, and 1-60 GPM @ 115’.  Provide 1-5HP/1750/ TEFC/230/460 Premium Efficiency Motor  Each pump to have 3” x 2” suction diffusers.  New suction and discharge isolation lug style butterfly valves to be installed on each pump.  Each pump to be outfitted with 3” wafer style silent check valves.  Provide and install 3” braided flex connectors on each pump’s suction and discharge.  Electrically connect each primary heat pump to its respective VFD drive.  Install (1) manual disconnect switch to new backup circulator pump, ( to be wired to source by BPS ).  Insulate all piping as necessary.  Provide new gauges and thermometers.

Notes: 1. All work warranted for a period of two years. 2. All work to be substantially complete by October 18, 2013. 3. Prevailing Rates do apply. 4. A minimum of 3 references is required. 5. Certificate of insurance is required. 6. All personnel must submit to a CORI check.