ML50 Compact Logic Controller

AUTOMATION MADE EASY & COMPACT

Honeywell Solutions for Machine Automation

1 | P a g e

M a s t e r L o g i c 5 0 S e r i e s SPECIAL FEATURE

Compact ML50 series is extremely compact providing both powerful functions and performance. The dual combination of Compactness & Performance is what makes ML50 such an ideal product. unit=mm(in) Item W H D W Main Unit MLM-D_ _S 30(1.18) 90(3.54) 60(2.36) MLC(I)-D_32H 114(4.49) 90(3.54) 64(2.52) D MLC(I)-D_64H 180(7.09) 90(3.54) 64(2.52) MLI-D_SU 135(5.3) 90(3.54) 64(2.52) MLI-D20E/30E MLI-D_10E/14E 100(3.94) 90(3.54) 64(2.52) H MLI-D_ _U 135(5.31) 90(3.54) 64(2.52) Expansion Modules 20(0.79) 90(3.54) 60(2.36)

H H

W D W D

H

D

W

For detailed dimension information, please refer to it for each module.

1 | P a g e M a s t e r L o g i c 5 0 S e r i e s SPECIAL FEATURE

Ultimate ‘U’ Performance Block Type (MLI series / MLI-D_ _U_) MLI U sets new standards in Ultimate Performance with its many innovations. IoT(Internet of Things) realizes smart factories, MLI-U series is a ‘User-Oriented’ controller.  Exandable with existed modules for ML50  Applicable max 2 expansion modules with High speed backplane(for network-positioning modules only)  Applicable upto 10 expansion modules  Max. 352 I/O points  Expansion Input/Output module  Special module and functions - Analog input, Analog output, RTD, Thermocouple, High-speed counter, Positioning (Line drive 2 axes, EtherCAT network 8 axes)  Communication modules - RS-232C, RS-422/485, Ethernet, CANopen (Master/Slave), -DP (Master/Slave),EtherNet/IP, RAPIEnet

Data Acquisition with External memory(SD card)  Easy parameter setup for [General save], [Trigger save], [Event save] without instruction  Able to store the working data into max. 16GBytes  Additional Functions : SD memory format, project file up/download, firmware upgrade  Value added service : FTP Link, Diagnostics info, e-mailing with attached data log file

Dual Port Ethernet  2 ports Ethernet switch support  Cost saving through simple wiring  FTP server support(Data acquisition-Logged data, diagnostics info, emailing)

2 | P a g e M a s t e r L o g i c 5 0 S e r i e s SPECIAL FEATURE

Web Server  Monitoring of PLC information and data through web browser (PLC basic info., module info., diagnosis, variables monitoring, special flag monitoring, data log file download from server, firmware/ project file update, etc.)  Time synchronization by setting basic parameters (SNTP: Simple Network Time Protocol)  Email service through commercial email (SMTP: Simple Mail Transfer Protocol)

Built-in Analog Input/Output (Available for MLI-D_ _UA only)  Built-in analog input 4 channels (Voltage/Current, resolution=14bits)  Built-in analog output 4 channels (Voltage/Current, resolution=14bits)

Built-in Position control (Available for MLI-D_ _UP only)  Line drive output positioning function with up to 2Mpps 4-axis.  Parameter set up by Softmaster-PM providing operation data edition, divers monitoring and diagnosis functions.

3 | P a g e M a s t e r L o g i c 5 0 S e r i e s SPECIAL FEATURE

High ‘H’ Performance Modular Type (MLM series / MLI-D_ _SU) With its high-speed processing and system capability, ML50 series offers utmost efficiency for your applications. ∙160ns/Step processing speed and floating-point arithmetic with on-board CPU ∙Max. 7 expansion modules, Max. 256 I/O point control: PLC system for Low-to-Mid level applications ∙Max. 5-Channel Communication with built-in functions and expansion modules

Network(2) *1 Expansion I/O(7) *1 Main Unit Special function(7)*1 MLM series Max. 7 expansion Modules

*1 Each number in ( ) is the number of modules that can be mounted for each function (network, special function, expansion I/O). And the total number of mountable expansion modules is limited to 7.

Block Type (MLC and MLI series, ”H” type) ∙83ns/Step processing speed and floating-point arithmetic with on-board CPU ∙Max. 10 expansion modules, Max. 384 I/O point control: PLC systems for Low-to-Mid level applications ∙Max. 5-Channel Communication with built-in functions and expansion modules

Network(2) *1 Main Unit Special function(10)*1 Expansion I/O(10) *1

Max. 10 expansion Modules

*1 Each number in ( ) is the number of modules that can be mounted for each function (network, special function, expansion I/O). And the total number of mountable expansion modules is limited to 10.

4 | P a g e M a s t e r L o g i c 5 0 S e r i e s SPECIAL FEATURE

Standard ‘SU’ Type (MLI-D_ _SU) ∙94ns/Step processing speed and floating-point arithmetic with on-board CPU ∙Max. 7 expansion modules and Max 2 Option Boards, Max. 284 I/O point control: PLC systems for Low-to-Mid level applications ∙Max. 5-Channel Communication with built-in functions and expansion modules

Main Unit

MLI-D_ _SU Network(2) *1 Expansion I/O(7) *1 Special function(7)*1

Max. 2 option boards Max. 7 Stages(Option + Expansion modules)

*1 Each number in ( ) is the number of modules that can be mounted for each function (network, special function, expansion I/O). And the total number of mountable expansion modules is limited to 7.

Economic ‘E’ Type (MLI-D_ _E) ∙240ns/Step processing speed and floating-point arithmetic with on-board CPU ∙Max. 2 Option Boards, Max. 38 I/O point control: PLC systems for Low level and simple applications ∙Max. 2-Channel Communication with built-in functions(RS232C, RS485)

Main Unit

MLI-D_ _E

Max. 2 option boards

5 | P a g e M a s t e r L o g i c 5 0 S e r i e s SPECIAL FEATURE

Easy & Convenient ML50 series offers ease of use and convenience with features such as: ∙Enhanced user interface with SoftMaster/SoftMaster-NM ∙Various monitoring functions. ∙Network diagnosis and monitoring ∙Battery for back-up for MLC, MLI(Compact type), Batteryless back-up for MLM(Modular type), “SU”/”E” with RTCA

Device monitoring Frame monitoring User event

Special module monitoring Table monitoring

Network scan

Multifunctional The ML50 series provides the optimum solution for your automation tasks with a range of powerful functions such as:

Model MLI-U MLC-H, MLI-H MLI-SU MLI-E MLM-S Phase 100kHz(4ch) 100kHz(2ch) 100kHz(ch) 4kHz 20kHz 1 Phase 20kHz(4Ch) 20kHz(6Ch) 8Ch 8Ch 8Ch 4Ch 4Ch

2 Phase 50kHz(4Ch) 50kHz(1Ch) 2 multiplication: 10kHz 50kHz(4Ch) 2kHz 10kHz(4Ch) 8kHz(3Ch) 4 multiplication: 8kHz 4Ch 4Ch 4Ch 2Ch 2Ch

Encoder Pulse catch HCiX series Input filter Inverter(VVVF) Servo/Stepping drive Servo/Stepping motor

6 | P a g e

M a s t e r L o g i c 5 0 S e r i e s MAIN UNIT

MasterLogic PLC 50 series General specification for MLM, MLC, MLI series

Item Descriptions Standard 1 Ambient 0~55℃ 2 temperatureStorage -25~+75℃ 3 Ambienttemperature humidity 5~95%RH (Non-condensing) 4 Storage humidity 5~95%RH (Non-condensing) Occasional vibration Frequency Acceleration Pulse width 10 ≤ f < 57Hz - 0.075mm 57 ≤ f < 150Hz 9.8m/s2(1G) - 10 times each direction IEC61131-2 5 Vibration resistance Continuous vibration (X, Y and Z) Frequency Acceleration Pulse width 10 ≤ f < 57Hz - 0.035mm 57 ≤ f < 150Hz 4.9m/s2(0.5G) -

∙Peak Acceleration : 147m/s2(15G) ∙Duration : 11ms 6 Shock resistance ∙Pulse waveform : Half-sine, 3times each direction per each axis IEC61131-2

Square wave impulse noise AC±1,500V / DC±900V Internal Standard Electrostatic IEC61131-2 discharge 4kV(Contacted) IEC61000-4-2 7 Noise resistance Radiated IEC61131-2 electromagnetic 80 ~ 1,000MHz, 10V/m IEC61000-4-3 Fast transient/ Main unit Expansion module IEC61131-2 Burst noise 2kV 1kV IEC61000-4-4 8 Operating Ambience Free from corrosive gasses and excessive dust 9 Altitude Up to 2,000m 10 Pollution level *1 Less than equal to 2 11 Cooling Air-cooling *1 Pollution level indicates the degree to which conductive material is generated in the environment where the equipment is used. Pollution level 2 is the condition that only non-conductive pollution occurred but temporary conductivity may be produced due to condensing.

7 | P a g e

M a s t e r L o g i c 5 0 S e r i e s MAIN UNIT i

Ultimate Modular “U” type(MLI-D_ _ U, MLI-D_ _ UA) Performance

Model Model MLI-DN32U MLI-DR28U MLI-DN32UA MLI-DR28UA Specification MLI-DP32U MLI-DP32UA Control method Repetitive, cyclic, interrupt, constant scan Refresh mode (Batch processing by scan synchronization) I/O control mode Direct mode by instruction Programming language Ladder Diagram(LD), Sequential Function Chart(SFC), Instruction List(IL), Structured Text(ST) Instructions Operator 18 Basic Function 136 + Floating-point Arithmatic functions Function block Basic function block : 43 Each special module has own special function blocks Processing speed 60ns /Step (for basic instruction) Program capacity 384kB(32k steps) Main module I/O points 32 points 28 points 32 points 60 points Max. I/O points 352 points 348 points 352 points 284 points Symbolic Area, A 64KB (Max. 64KB retain setting available) Input variable, I 2KB(%IX 15.15.63) Output variable, Q 2KB (%QX 15.15.63) Direct M 32KB (Max. retain setting available) variable R 32KB (2 blocks) W 64KB, Same area as ‘R’ Data memory Flag variable F 4KB, System flag K 16KB, Built-in special flag L 8KB, High speed link flag U 768 Bytes, Analog Flag N 20kB, P2P Parameter Flash 128KB (4 block), R device used Number of program 256 Timer No limit in points (Tim range : 0.001 ~ 4,294,967.295) Operation mode RUN, STOP, DEBUG Self-diagnosis Operation delay monitoring, memory error, I/O error, battery error, power error, etc. Program port USB 1 channel Data retention at power failure Latch area setting at Basic parameter RS-232C, RS485, High-speed counter, PID control, Pulse catch, Input filter, Position control Built-in function External interrupt, Positioning *1 , Analog In/Out *2 Internal current consumption 700mA 990mA 780mA 1,040mA 1,250mA 1,550mA Weight(g) 571g (1.26lb) 630g (1.39lb) 683g (1.51lb) 732g (1.61lb) 673(1.48lb) 722(1.59lb)

*1. MLI-DN_UP, MLI-DP_UP or MLI-DR_UP are available. *2. MLI-DN_UA, MLI-DP_UA or MLI-DR_UA are available.

Built-in function Specification Item Remark MLI-DN32U MLI-DR28U MLI-DN32UA MLI-DR28UA Control by instruction, auto-tuning, PWM output, Forced output, Operation scan time setting, PID control Anti-windup, Delta MV, PV tracking, Hybrid operation, Cascade operation Serial Protocol Dedicated protocol, protocol, User defined protocol , Embedded00 communication Channel RS-232C 1 port and RS-485 1 port P2P : 01 Transfer Spec Cable: 100Base-TX, Speed: 100Mbps, Auto-MDIX *1, IEEE 802.3 Topology Line, Star Ethernet Diagnosis Module information, service condition Protocol Dedicated protocol, Modbus protocol, User defined protocol Embedded01P2P:02

Service P2P, High Speed link, Remote connection High-speedlink:01 Group Max 10 groups Data set 32 per group Format csv format(Comma Separated Values) Data Log File size Max 16Mbytes for each SD memory type SD,SDHC type(Recommendation : SanDisk, Transcend), File system : FAT32 Memory size Max 16GB Performance 1-phase : 100KHz 8 channels / 2-phase : 50KHz 4 channels 4 counter modes are supported based on input pulse and INC/DEC method 1 pulse operation Mode : INC/DEC count by program High Counter mode 1 pulse operation Mode : INC/DEC count by phase B pulse input Speed 2 pulse operation Mode : INC/DEC count by input pulse Counter 2 pulse operation Mode : INC/DEC count by difference of phase Internal/external preset • Latch counter Function Compare output • No. of rotation per unit time

8 | P a g e

M a s t e r L o g i c 5 0 S e r i e s MAIN UNIT

Built-in function Specification Item Remark MLI-DN32U MLI-DR28U MLI-DN32UA MLI-DR28UA  Protocol : HTTP(Ver 1.1) Webserver  Other functions : Checking the PLC history, Device monitoring, user page, manage the Data log file

Pulse catch 50μ sec 8 channels, %IX0.0.8 ~ %IX0.0.15

External contact interrupt 50μ sec 8 channels, %IX0.0.8 ~ %IX0.0.15

Input Filter Select one of 1,3,5,10,20,70,100msec(available for each module)

Analog input & output, built-in Specification Item Remark Sub-Item MLI-DN32UA MLI-DR28UA Channels No. of channel 4 Voltage: 1~5V, 0~5V, 0~10V, -10~10V, Current: 4~20 mA,0~20 mA Input Range  Current input or voltage input can be selected through the external terminal wiring setting

Analog input Input Resistance  1 MΩ or more(voltage input), 250 Ω (current input) Specification 1/6000 0.250mV(1 ~ 5V), Max. Resolution 1.0μA (4 ~ 20 mA) 0.3125mV(0 ~ 5V) 1.25μA (0 ~ 20 mA) 0.625mV(0 ~ 10V), 1.250mV(±10V)  ±0.2% or less (When ambient temperature is 25ºC ) Accuracy  ±0.3% or less (When ambient temperature is 0 ~ 55 ºC )

9 | P a g e

M a s t e r L o g i c 5 0 S e r i e s MAIN UNIT Modular “S” type(MLM) General specification

Item Descriptions Standard 1 Ambient 0~55℃ 2 temperatureStorage -25~+75℃ 3 Ambienttemperature humidity 5~95%RH (Non-condensing) 4 Storage humidity 5~95%RH (Non-condensing) Occasional vibration Frequency Acceleration Pulse width 10 ≤ f < 57Hz - 0.075mm 57 ≤ f < 150Hz 9.8m/s2(1G) - 10 times each direction IEC61131-2 5 Vibration resistance Continuous vibration (X, Y and Z) Frequency Acceleration Pulse width 10 ≤ f < 57Hz - 0.035mm 57 ≤ f < 150Hz 4.9m/s2(0.5G) -

∙Peak Acceleration : 147m/s2(15G) ∙Duration : 11ms 6 Shock resistance ∙Pulse waveform : Half-sine, 3times each direction per each axis IEC61131-2

Square wave impulse noise AC±1,500V / DC±900V Internal Standard Electrostatic IEC61131-2 discharge 4kV(Contacted) IEC61000-4-2 7 Noise resistance Radiated IEC61131-2 electromagnetic 80 ~ 1,000MHz, 10V/m IEC61000-4-3 Fast transient/ Main unit Expansion module IEC61131-2 Burst noise 2kV 1kV IEC61000-4-4 8 Operating Ambience Free from corrosive gasses and excessive dust 9 Altitude Up to 2,000m 10 Pollution level *1 Less than equal to 2 11 Cooling Air-cooling *1 Pollution level indicates the degree to which conductive material is generated in the environment where the equipment is used. Pollution level 2 is the condition that only non-conductive pollution occurred but temporary conductivity may be produced due to condensing.

Performance

Model Item MLM-DR16S MLM-DN16S MLM-DN32S Control method Repetitive, cyclic, interrupt, constant scan Refresh mode (Batch processing by scan synchronization) I/O control mode Direct mode by instruction Programming language Ladder Diagram, Instruction List No. of instructions Basic : 28, Applied : 677 Processing speed 160ns /Step (for basic instruction) Program capacity 10k steps Max. I/O points 256 points (Main + 7 expansions) P P0000 ~ P127F (2,048 points) M M0000 ~ M255F (4,096 points) K K00000 ~ K2559F (Special area : K2600~2559F) (40,960 points) L L00000 ~ L1279F (20,480 points) F F000 ~ F255F (4,096 points) T 100ms, 10ms, 1ms : T000 ~ T255 (Changeable by Parameter setting) Data memory C C000 ~ C255 S S00.00 ~ S127.99 D D0000 ~ D5119 (5,120 word) U U00.00 ~ U07.31 (Analog data refresh area : 256 word) Z Z000~Z127 (128 word) N N0000~N3935 (3,936 word) Number of program 128 Operation mode RUN, STOP, DEBUG Self diagnosis Operation delay monitoring, memory error, I/O error, battery error, power error, etc. Program port RS-232C (Loader) Remote connection using RS-232C, RS-485 Data retention at power failure Latch range setting at Basic parameter RS-232C/485, High-speed counter, PID control, Pulse catch, Input filter, Position control Built-in function External interrupt, Positioning *1 Internal current consumption 400mA 280mA 300mA Weight 100g

*1 MLM-DR16S doesn’t have built-in positioning function.

10 | P a g e

M a s t e r L o g i c 5 0 S e r i e s MAIN UNIT

Block “H” type(MLC-D_ _H / MLI-D_ _H) General specification

Item Descriptions Standard 1 Ambient 0~55℃ 2 temperatureStorage -25~+75℃ 3 Ambienttemperature humidity 5~95%RH (Non-condensing) 4 Storage humidity 5~95%RH (Non-condensing) Occasional vibration Frequency Acceleration Pulse width 10 ≤ f < 57Hz - 0.075mm 57 ≤ f < 150Hz 9.8m/s2(1G) - 10 times each direction IEC61131-2 5 Vibration resistance Continuous vibration (X, Y and Z) Frequency Acceleration Pulse width 10 ≤ f < 57Hz - 0.035mm 57 ≤ f < 150Hz 4.9m/s2(0.5G) -

∙Peak Acceleration : 147m/s2(15G) ∙Duration : 11ms 6 Shock resistance ∙Pulse waveform : Half-sine, 3times each direction per each axis IEC61131-2

Square wave impulse noise ±1,500V Internal Standard Electrostatic IEC61131-2 discharge 4kV IEC61000-4-2 7 Noise resistance Radiated IEC61131-2 electromagnetic 27 ~ 500MHz, 10V/m IEC61000-4-3 Fast transient/ Main unit Expansion module IEC61131-2 Burst noise 2kV 1kV IEC61000-4-4 8 Operating Ambience Free from corrosive gasses and excessive dust 9 Altitude Up to 2,000m 10 Pollution level *1 Less than equal to 2 11 Cooling Air-cooling *1 Pollution level indicates the degree to which conductive material is generated in the environment where the equipment is used. Pollution level 2 is the condition that only non-conductive pollution occurred but temporary conductivity may be produced due to condensing.

Performance

Model Item MLC-DR32H MLC-DN32H MLC-DR64H MLC-DN64H MLI- DR32H MLI-DN32H MLI-DR64H MLI-DN64H Control method Repetitive, cyclic, interrupt, constant scan I/O Control mode Refresh mode (Batch processing by scan synchronization), Direct mode by instruction Programming language Ladder Diagram(LD), Instruction List(IL) LD, IL, Structured Text(ST), Sequential Function Chart(SFC) No. of instructions Basic : 28, Applied : 677 Function Blocks Processing speed 83ns /Step (for basic instruction) 83ns /Step (for basic instruction) Program capacity 15k steps 200kB(15k steps) Max. I/O points 384 points (Main + 10 expansions) 384 points (Main + 10 expansions) P P0000 ~ P1023F (16,384 points) A 32KB (Max. 16KB retain setting available) M M0000 ~ M1023F (16,384 points) I 2KB(%IX 15.15.63) K K00000 ~ K4095F (65,536 points) Q 2KB (%QX 15.15.63) L L00000 ~ L2047F (32,768 points) M 16KB (Max. retain setting available) F F000 ~ F1023F (16,384 points) R 20KB (1 block) T 100ms, 10ms, 1ms : T000 ~ T1023 (Changeable by Parameter W 20KB, Same area as ‘R’ Data memory C C000 ~setting) C1023(1,024) F 2KB, System flag S S00.00 ~ S127.99 K 8KB, Built-in special flag D D0000 ~ D10239 (10,240 word) L 4KB, High speed link flag U U00.00 ~ U0A.31 (Analog data refresh area : 352 word) N 10KB, P2P flag Z Z000~Z127 (128 word) U 1KB, Analog Flag N N0000~N5119 (5,120 word) Flash 20KB (2 block), R device used Number of program 128 128 Operation mode RUN, STOP, DEBUG RUN, STOP, DEBUG Self diagnosis Detects error of scan time, memory error, I/O error, battery error, power error, etc. Program port USB (Rev 1.1), RS-232C 1 channel (Loader) Data retention at power failure Latch range setting at Basic parameter RS-232C/485, High-speed counter, PID control, Pulse catch, Input filter Built-in function RTC, External interrupt, Internal current consumption 660mA 260mA 1040mA 33Positioning0mA *1 660mA 260mA 1040mA 330mA Weight 600g 500g 900g 800g 600g 500g 900g 800g

11 | P a g e

M a s t e r L o g i c 5 0 S e r i e s MAIN UNIT Modular “SU” type(MLI-D_ _ SU) and Economic “E”(MLI-D_ _ E) General specification

Item Descriptions Standard 1 Ambient 0~55℃ 2 temperatureStorage -25~+75℃ 3 Ambienttemperature humidity 5~95%RH (Non-condensing) 4 Storage humidity 5~95%RH (Non-condensing) Occasional vibration Frequency Acceleration Pulse width 10 ≤ f < 57Hz - 0.075mm 57 ≤ f < 150Hz 9.8m/s2(1G) - 10 times each direction IEC61131-2 5 Vibration resistance Continuous vibration (X, Y and Z) Frequency Acceleration Pulse width 10 ≤ f < 57Hz - 0.035mm 57 ≤ f < 150Hz 4.9m/s2(0.5G) -

∙Peak Acceleration : 147m/s2(15G) ∙Duration : 11ms 6 Shock resistance ∙Pulse waveform : Half-sine, 3times each direction per each axis IEC61131-2

Square wave impulse noise ±1,500V Internal Standard Electrostatic IEC61131-2 discharge 4kV IEC61000-4-2 7 Noise resistance Radiated IEC61131-2 electromagnetic 27 ~ 500MHz, 10V/m IEC61000-4-3 Fast transient/ Main unit Expansion module IEC61131-2 Burst noise 2kV 1kV IEC61000-4-4 8 Operating Ambience Free from corrosive gasses and excessive dust 9 Altitude Up to 2,000m 10 Pollution level *1 Less than equal to 2 11 Cooling Air-cooling *1 Pollution level indicates the degree to which conductive material is generated in the environment where the equipment is used. Pollution level 2 is the condition that only non-conductive pollution occurred but temporary conductivity may be produced due to condensing.

Performance

Model Model MLI-DN20SU MLI-DN30SU MLI-DN40SU MLI-DN60SU MLI-DN10E MLI-DN14E MLI-DN20E MLI-DN30E Specification MLI-DR20SU MLI-DR30SU MLI-DR40SU MLI-DR60SU MLI-DR10E MLI-DR14E MLI-DR20E MLI-DR30E Control method Repetitive, cyclic, interrupt, constant scan Repetitive, cyclic Refresh mode (Batch processing by scan synchronization) I/O control mode Direct mode by instruction Programming language Ladder Diagram(LD), Sequential Function Chart(SFC), Instruction List(IL), Structured Text(ST) Processing speed 94ns /Step (for basic instruction) 240ns /Step Program capacity 200kB(15k steps) 50kB(4k steps) Main module I/O points 20 points 30 points 40 points 60 points 10 points 14 points 20 points 30 points Max. I/O points 244 points 254 points 264 points 284 points 14 points 18 points 28 points 38 points A 16KB (Max. 16KB retain setting available) 8KB (Max. 8KB retain setting available) I 2KB(%IX 15.15.63) 256 Byte (%IX15.15.63) Q 2KB (%QX 15.15.63) 256 Byte (%QX15.15.63) M 8KB (Max. retain setting available) 4KB R 20KB (1 block) 10KB (1 block) W 20KB, Same area as ‘R’ 10KB Data memory F 2KB, System flag 768 bytes K 8KB, Built-in special flag 5,120 bytes L 4KB, High speed link flag 2,560 bytes U 1KB, Analog Flag 704 bytes Flash 20KB (2 block), R device used - Number of program 128 128 Operation mode RUN, STOP, DEBUG RUN, STOP, DEBUG Self-diagnosis Operation delay monitoring, memory error, I/O error, battery error, Operation delay monitoring, memory error, I/O error, etc power error, etc. Program port RS-232C (Loader) Remote connection using RS-232C, RS-485 1ch RS-232C (Loader) Data retention at power failure Latch range setting at Basic parameter Latch range setting at Basic parameter RS-232C, RS485, High-speed counter, PID control, Pulse catch, Input RS-232C or RS485, High-speed counter, Pulse catch, Built-in function filter, Position control Input filter *2 External interrupt, Positioning *1 - Internal current consumption 252mA / 478mA 270mA / 626mA 288mA / 684mA 340mA / 942mA 180 / 250 mA 190 / 315mA 200 / 355 mA 210 / 485 mA Weight(g) 475g (1.05lb) 474g (1.045lb) 578g (1.27lb) 636g (1.40lb) 313(0.69lb) 315(0.694lb) 418(0.92lb) 423(0.93lb) 514g (1.13lb) 528g (1.16lb) 594g (1.31lb) 804g (1.77lb) 330((0.72lb) 340(0.75lb) 450(0.992lb) 465(1.03lb) *1. MLC-DR_H or MLI-DR_H are not supported. *2. Not allowable to use RS232C and RS485 at the same time.

12 | P a g e

M a s t e r L o g i c 5 0 S e r i e s MAIN UNIT

Name Descriptions Descriptions Red On: Input/output signal On 1 LED for Input, Output Input/Output indication Red Off: Input/output signal Off 2 PADT connection PADT connection Connector for SoftMaster 3 Input connector Input wiring connection - /Terminal block 4 Output connector Output wiring connection - /Terminal block 5 Mode switch *2 Mode setting Setting Run/Stop mode of PLC In case of STOP, the remote operation is available Red On: Input signal On PWR: Power indication Red Off: Input signal Off

Green On: PLC Run RUN: RUN indication Green Off: PLC Stop Red On-and-Off: PLC Error ERR: Error indication 6 Condition LED Red Off: PLC Normal condition Red On : SD card is inserted STATE: Error indication Red off : SD card has error(flickering)

During reading/writing on SD card RD/WR: operating indication of SD card - 7 SD card connector SD card connector

8 Built-in FEnet connector Built-in FEnet connection FEnet, 2ports(one is for switch) 9 Built-in Serial communication Built-in RS-232C/RS485 *3 10 Battery Holder Battery holder

13 | P a g e

M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT

Main Unit Digital Input l DC24V

Model DC24V Specification MLI-DN32U/MLI-DN32UA MLI-DR28U/MLI-DR28UA Input points 16points 16points Insulation method Photo-coupler insulation Rated input voltage/current DC24V / 4mA (Contact 00~03 : 7mA) Operation voltage range DC20.4~28.8V (Ripple rate < 5%) On voltage/On current DC19V or more / 3mA or more Off voltage/Off current DC6V or less / 1mA or less Input resistance 5.6k Ω (Contact 00~07 : 4.7k Ω) Off→On Response time 1 / 3 / 5 / 10 / 20 / 70 / 100ms (setting by CPU parameter) Initial value : 3ms On→Off Insulation pressure AC560Vrms / 3 Cycle (altitude 2000m) Insulation resistance 10㏁ or more by megger COMMON method 16 points/COM Proper cable size Twisted wire 0.3~0.75mm2 (external diameter ≤2.8mm) Operation indication Input On LED On 8-pin terminal block + 10 point terminal connector External connection method

Digital Output l Relay

Model Relay Specification MLI-DR28U / MLI-DR28UA Output point 12 points Insulation method Relay insulation Rated load voltage/current DC24V 2A(resistive load)/AC220V 2A(COSΨ = 1), 2A/COM(00~03), 5A/COM(04~11) Min. load voltage/current DC5V/1mA Max. load voltage/current AC250V or DC125V / 2A Off leakage current 0.1mA (AC220V, 60Hz) Max. on/off frequency 3,600 times/hr Surge absorber None Service life Mechanical 20 million times or more Rated load voltage/current 100,000 times or more AC200V/1.5A, AC240V/1A (COSΨ = 0.7) 100,000 times or more Electrical AC200V/1A, AC240V/0.5A (COSΨ = 0.35) 100,000 times or more DC24V/1A, DC100V/0.1A (L / R = 7ms) 100,000 times or more Off→On 10 ms or less Response time On→Off 12 ms or less COMMON method 1 point/COM(00~03), 4 points/COM(04~11) Cable size Standard cable 0.3~0.75mm2 (External diameter 2.8mm or less) Operation indicator Output On, LED On External connection method 8-pin terminal block connector + 10-point terminal block connector

Digital Output l Open Collector Model Open Collector Specification MLI-DN32U / MLI-DN32UA Output point 16points Insulation method Photo-coupler insulation Rated load voltage DC 12/24V Load voltage range DC 10.2 ~ 26.4V Max. Load current 0.5A/point, 2A/1COM Off leakage current 0.1mA or less Max. Inrush current 4A / 10mse or less Max. voltage drop(On) DC 0.4V or less Surge absorber Zener diode Response time Off→On 1mA or less On→Off 1ms or less (Rated load, resistive load) COMMON Method 16 points/COM External Voltage DC12/24V ± 10% (Ripple voltage ≤ 4 Vp-p) power supply Current 10mA or less (DC 24V connection) Operation indication Output On, LED On External connection method 8-pin terminal block connector + 10-pin terminal block connector

14 | P a g e

M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT

Features and Functions (MLC/MLI “H”, MLI “SU”/”E”, MLM)

10 72 1 9 1 3 Name Descriptions Descriptions 4 4 Red On: Input signal On 1 Input LED Input indication 5 Red Off: Input signal Off 5 6 Red On: Input signal On PWR: Power indication 6 Red Off: Input signal Off

Green On: PLC Run 7 8 2 Condition LED RUN: RUN indication Green Off: PLC Stop 11 2 8 3 Red On-and-Off: PLC Error ERR: Error indication 9 10 7 Red Off: PLC Normal condition 1 2 On: Output signal On 4 3 Output LED Output LED Off: Output signal Off 12 Connection of expansion module 6 4 Expansion module connector Expansion module connector *1 (I/O, Special function, Communication) 3 5 PADT connection PADT connection Connector for SoftMaster 5 11 8 SoftMaster-NM connection 6 Mode switch *2 Mode setting Setting Run/Stop mode of PLC 2 7 Input connector Input wiring connection - 3 /Terminal block 1 4 8 Output connector Output wiring connection - /Terminal block 5 6 9 Built-in RS-485 connector Built-in RS-485 connection RS-485 +(TX) / -(RX) terminal connection 10 Built-in RS-232C connector *3 Built-in RS-232C connection RS-232C TxD, RxD, GND terminal 7 8 connection 11 Power connector *4 Power supply connection MLM : DC 24V power supply MLC : AC100~240V /DC 24V power supply MLI “H” : AC100~240V /DC 24V power supply

MLI “SU”, “E” : AC100~240V 9 12 Option board connector Connecting for option board MLI “SU, “E” type only 11 10 *1 MLI “E” series is not available. *2 In the remote mode, set the mode switch to STOP. *3 GND terminal of RS-232C can be used as GND terminal of RS-485. *4 Select DC power supply considering current consumption of PLC system.

MasterLogic 50 configuration

15 | P a g e

M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT

Main Unit Digital Input l DC24V

DC24V Model Modular type(MLM) Block type(MLC, MLI) Specification MLM-DR16S MLM-DN16S MLM-DN32S ML_-DR32H ML_-DN32H ML_-DR64H ML_-DN64H ML_-DR32H/DC ML_-DN32H/DC ML_-DR64H/DC ML_-DN64H/DC Input points 8points 8points 16points 16points 16points 32points 32points Insulation method Photo-coupler insulation Rated input voltage/current DC24V / 4mA (Contact 00~03 : 7mA) DC24V / 4mA (Contact 0~7 : 9mA) Operation voltage range DC20.4~28.8V (Ripple rate < 5%) On voltage/On current DC19V or more / 3mA or more Off voltage/Off current DC6V or less / 1mA or less Input resistance 5.6k Ω (Contact 00~03 : 3.3k Ω) 5.6k Ω (P00~P07 : 2.k Ω) Off→On Response time 1 / 3 / 5 / 10 / 20 / 70 / 100ms (setting by CPU parameter) Initial value : 3ms On→Off Insulation pressure AC560Vrms / 3 Cycle (altitude 2000m) Insulation resistance 10㏁ or more by megger COMMON method 8 points/COM 16 points/COM 16 points/COM 16 points/COM Proper cable size Twisted wire 0.3~0.75mm2 (external diameter ≤2.8mm) Operation indication Input On LED On 9-pin terminal 20-pin 20-pin 24 points connecting connector 42 points connecting connector External connection method block connector connector (M3 x 6 screws) (M3 x 6 screws)

Digital Output l Relay

Model Relay Specification MLM-DR16S MLC-DR32H, MLC-DR32H/DC MLC-DR64H, MLC-DR64H/DC Output point 8points 16points 32points Insulation method Relay insulation Rated load voltage/current DC24V 2A(resistive load)/AC220V 2A(COSΨ = 1), 5A/COM Min. load voltage/current DC5V/1mA Max. load voltage/current AC250V or DC125V / 2A Off leakage current 0.1mA (AC220V, 60Hz) Max. on/off frequency 3,600 times/hr Surge absorber None Service life Mechanical 20 million times or more Rated load voltage/current 100,000 times or more AC200V/1.5A, AC240V/1A (COSΨ = 0.7) 100,000 times or more Electrical AC200V/1A, AC240V/0.5A (COSΨ = 0.35) 100,000 times or more DC24V/1A, DC100V/0.1A (L / R = 7ms) 100,000 times or more Off→On 10 ms or less Response time On→Off 12 ms or less COMMON method 8 points/COM 4 points/COM P20~2F : 4 points/COM P30~3F : 8 points/COM Operation indicator Output On, LED On External connection method 9-pin terminal block connector 9-pin terminal block connector x 2

Digital Output l Open Collector Model Open Collector Specification MLM-DN16S MLM-DN32S MLC-DN32H, MLC-DN32H/DC MLC-DN64H, MLC-DN64H/DC Output point 8points 16points 16points 32points Insulation method Photo-coupler insulation 64points Rated load voltage DC 12/24V Load voltage range DC 10.2 ~ 26.4V Max. Load current 0.2A/point 0.5A/point 0.5A/1 point (P20~23 : 0.1A / point) Off leakage current 0.1mA or less Max. voltage drop(On) DC 0.4V Surge absorber Zener diode Response time Off→On 1mA or less On→Off 1ms or less (Rated load, resistive load) COMMON Method 16 points/COM 16 points/COM 4 points/COM P20~2F : 4 points/COM P30~3F : 8 points/COM Voltage DC12/24V ± 10% (Ripple voltage ≤ 4 Vp-p) External 20mA or less 10mA or less power supply Current 10mA or less (DC 24V connection) (DC 24V connection) (DC 24V connection) Operation indication Output On, LED On 24 points connecting connector 42 points connecting connector External connection method 20-pin connector (M3 x 6 screws) (M3 x 6 screws)

16 | P a g e

M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT

Main Unit for MLM, MLC and MLI “H” Digital Input l DC24V

DC24V Model Modular type(MLM) Block type(MLC, MLI) MLM-DR16S MLM-DN16S MLM-DN32S ML_-DR32H ML_-DN32H ML_-DR64H ML_-DN64H Specification ML_-DR32H/DC ML_-DN32H/DC ML_-DR64H/DC ML_-DN64H/DC Input points 8points 8points 16points 16points 16points 32points 32points Insulation method Photo-coupler insulation Rated input voltage/current DC24V / 4mA (Contact 00~03 : 7mA) DC24V / 4mA (Contact 0~7 : 9mA) Operation voltage range DC20.4~28.8V (Ripple rate < 5%) On voltage/On current DC19V or more / 3mA or more Off voltage/Off current DC6V or less / 1mA or less Input resistance 5.6k Ω (Contact 00~03 : 3.3k Ω) 5.6k Ω (P00~P07 : 2.k Ω) Off→On Response time 1 / 3 / 5 / 10 / 20 / 70 / 100ms (setting by CPU parameter) Initial value : 3ms On→Off Insulation pressure AC560Vrms / 3 Cycle (altitude 2000m) Insulation resistance 10㏁ or more by megger COMMON method 8 points/COM 16 points/COM 16 points/COM 16 points/COM Proper cable size Twisted wire 0.3~0.75mm2 (external diameter ≤2.8mm) Operation indication Input On LED On 9-pin terminal 20-pin 20-pin 24 points connecting connector 42 points connecting connector External connection method block connector connector (M3 x 6 screws) (M3 x 6 screws)

Digital Output l Relay

Model Relay MLM-DR16S MLC-DR32H, MLC-DR32H/DC MLC-DR64H, MLC-DR64H/DC Specification MLI-DR32H, MLI-DR32H/D1 MLI-DR64H, MLC-DR64H/D1 Output point 8points 16points 32points Insulation method Relay insulation Rated load voltage/current DC24V 2A(resistive load)/AC220V 2A(COSΨ = 1), 5A/COM Min. load voltage/current DC5V/1mA Max. load voltage/current AC250V or DC125V / 2A Off leakage current 0.1mA (AC220V, 60Hz) Max. on/off frequency 3,600 times/hr Surge absorber None Service life Mechanical 20 million times or more Rated load voltage/current 100,000 times or more AC200V/1.5A, AC240V/1A (COSΨ = 0.7) 100,000 times or more Electrical AC200V/1A, AC240V/0.5A (COSΨ = 0.35) 100,000 times or more DC24V/1A, DC100V/0.1A (L / R = 7ms) 100,000 times or more Off→On 10 ms or less Response time On→Off 12 ms or less COMMON method 8 points/COM 4 points/COM P20~2F : 4 points/COM P30~3F : 8 points/COM Operation indicator Output On, LED On External connection method 9-pin terminal block connector 9-pin terminal block connector x 2

Digital Output l Open Collector Model Open Collector MLM-DN16S MLM-DN32S MLC-DN32H, MLC-DN32H/DC MLC-DN64H, MLC-DN64H/DC Specification MLI-DN32H, MLI-DN32H/D1 MLI-DN64H, MLI-DN64H/D1 Output point 8points 16points 16points 32points Insulation method Photo-coupler insulation 64points Rated load voltage DC 12/24V Load voltage range DC 10.2 ~ 26.4V Max. Load current 0.2A/point 0.5A/point 0.5A/1 point (P20~23 : 0.1A / point) Off leakage current 0.1mA or less Max. voltage drop(On) DC 0.4V Surge absorber Zener diode Response time Off→On 1mA or less On→Off 1ms or less (Rated load, resistive load) COMMON Method 16 points/COM 16 points/COM 4 points/COM P20~2F : 4 points/COM P30~3F : 8 points/COM Voltage DC12/24V ± 10% (Ripple voltage ≤ 4 Vp-p) External 20mA or less 10mA or less power supply Current 10mA or less (DC 24V connection) (DC 24V connection) (DC 24V connection) Operation indication Output On, LED On 24 points connecting connector 42 points connecting connector External connection method 20-pin connector (M3 x 6 screws) (M3 x 6 screws)

17 | P a g e

M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT

Main Unit for MLI “SU”, “E” Digital Input l DC24V

Model DC24V MLI-DN10E MLI-DN14E MLI-DN20E MLI-DN30E MLI-DN20SU MLI-DN30SU MLI-DN40SU MLI-DN60SU Specification MLI-DR10E MLI-DR14E MLI-DR20E MLI-DR30E MLI-DR20SU MLI-DR30SU MLI-DR40SU MLI-DR60SU Input points 6 points 8 points 12 points 18 points 12points 18points 24points 36points Insulation method Photo-coupler insulation Rated input voltage/current DC24V / 4mA (Contact 00~03 : 7mA) DC24V / 4mA (Contact 0~7 : 9mA) Operation voltage range DC20.4~28.8V (Ripple rate < 5%) On voltage/On current DC19V or more / 3mA or more Off voltage/Off current DC6V or less / 1mA or less Input resistance 5.6k Ω (Contact 00~03 : 3.3k Ω) 5.6k Ω (P00~P07 : 2.k Ω) Off→On Response time 1 / 3 / 5 / 10 / 20 / 70 / 100ms (setting by CPU parameter) Initial value : 3ms On→Off Insulation pressure AC560Vrms / 3 Cycle (altitude 2000m) Insulation resistance 10㏁ or more by megger COMMON method 6 points 8 points 12 points 18 points 12points 18points 24points 36points Proper cable size Twisted wire 0.3 mm2 Operation indication Input On LED On External connection method 14 points connector 24 points connector 24 points connecting connector 42 points connecting connector *Connecting method : M3 x 6 screws

Digital Output l Relay

Model Relay Specification MLI-DR10E MLI-DR14E MLI-DR20E MLI-DR30E MLI-DR20SU MLI-DR30SU MLI-DR40SU MLI-DR60SU Output point 4 points 6 points 8 points 12 points 8points 12points 16points 24points Insulation method Relay insulation Rated load voltage/current DC24V 2A(resistive load)/AC220V 2A(COSΨ = 1), 5A/COM Min. load voltage/current DC5V/1mA Max. load voltage/current AC250V or DC125V / 2A Off leakage current 0.1mA (AC220V, 60Hz) Max. on/off frequency 3,600 times/hr Surge absorber None Service life Mechanical 20 million times or more Rated load voltage/current 100,000 times or more AC200V/1.5A, AC240V/1A (COSΨ = 0.7) 100,000 times or more Electrical AC200V/1A, AC240V/0.5A (COSΨ = 0.35) 100,000 times or more DC24V/1A, DC100V/0.1A (L / R = 7ms) 100,000 times or more Off→On 10 ms or less Response time On→Off 12 ms or less COMMON method 2 points/COM 4 points/COM 4 points/COM Operation indicator Output On, LED On External connection method 24-pin terminal block connector 24-pin terminal block connector 30 pin teminal 42 pin terminal

Digital Output l Open Collector Model Open Collector MLI-DN10E MLI-DN14E MLI-DN20E MLI-DN30E MLI-DN20SU MLI-DN30SU MLI-DN40SU MLI-DN60SU Specification Output point 4 points 6 points 8 points 12 points 8points 12points 16points 24points Insulation method Photo-coupler insulation Rated load voltage DC 12/24V Load voltage range DC 10.2 ~ 26.4V Max. Load current 0.5A/1 point, 2A / 1COM 0.5A/1 point, 2A / 1COM Off leakage current 0.1mA or less Max. voltage drop(On) DC 0.4V Surge absorber Zener diode Response time Off→On 1mA or less On→Off 1ms or less (Rated load, resistive load) COMMON Method 4 points/COM 4 points/COM Voltage DC12/24V ± 10% (Ripple voltage ≤ 4 Vp-p) External power supply Current 25mA or less (DC 24V connection) 25mA or less (DC 24V connection) Operation indication Output On, LED On External connection method 14-pin connector 24-pin connector 24-pin connector 30-pin connector 42-pin connector *Connecting method : M3 x 6 screws

18 | P a g e

M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT

Expansion Digital Input l DC24V

Model DC24V Expansion module Specification MLE-DC08A MLE-DC16A MLE-DC32A MLE-DR16A Input points 8points 16points 32points 8points Insulation method Photo-coupler insulation Rated input voltage/current DC24V / 4mA Operation voltage range DC20.4~28.8V (Ripple rate < 5%) On voltage/On current DC19V or more / 3mA or more Off voltage/Off current DC6V or less / 1mA or less Input resistance 5.6k Ω Off→On Response time 1 / 3 / 5 / 10 / 20 / 70 / 100ms (setting by CPU parameter) Initial value : 3ms On→Off Insulation pressure AC560Vrms / 3 Cycle (altitude 2000m) Insulation resistance 10㏁ or more by megger COMMON method 8 points/COM 16 points/COM 32 points/COM Proper cable size Twisted wire 0.3~0.75mm2 (external diameter ≤ 2.8mm) Operation indication Input On LED On 9-pin terminal block 8-pin + 10-pin terminal block 40-pin connector 9-pin terminal block External connection method

Digital Output l Relay

Model Relay Specification MLE-RY08A MLE-RY16A MLE-DR16A Output point 8points 16points 8points Insulation method Relay insulation Rated load voltage/current DC24V 2A(resistive load)/AC220V 2A(COSΨ = 1), 5A/COM Min. load voltage/current DC5V/1mA Max. load voltage/current AC250V, DC125V Off leakage current 0.1mA (AC220V, 60Hz) Max. on/off frequency 3,600 times/hr Surge absorber None Service life Mechanical 20 million times or more Rated load voltage/current 100,000 times or more AC200V/1.5A, AC240V/1A (COSΨ = 0.7) 100,000 times or more Electrical AC200V/1A, AC240V/0.5A (COSΨ = 0.35) 100,000 times or more DC24V/1A, DC100V/0.1A (L / R = 7ms) 100,000 times or more Off→On 10 ms or less Response time On→Off 12 ms or less COMMON method 8 points/1COM Operation indicator Output On, LED On External connection method 9-pin terminal block connector 9-pin terminal block connector x 2 9-pin terminal block connector

Digital Output l Open Collector

Model Digital output Specification MLE-TN08A MLE-TN16A MLE-TN32A Output point 8points 16points 32points Insulation method Photo-coupler insulation Rated load voltage DC12/24V Load Voltage range DC10.2 ~ 26.4V Max. Load Current 0.5A / 1 point 0.2A / 1 point, 2A / COM Off leakage current 0.1mA or less Max. voltage drop(On) DC0.4V Surge absorber Zener diode Response time Off  On 1ms or less On  Off 1 ms or less(Rated load, Resistive load) Common method 8 points/COM 16 points/COM 32 points/COM External power Voltage DC12/24V ± 10% (Ripple voltage ≤ 4 Vp-p) supply Current 10mA or less (DC 24V connection) 20mA or less (DC 24V connection) Operation Indication Output On, LED On External Connection Method 10-pin terminal block 8-pin + 10-pin terminal block 40-pin connector

19 | P a g e

M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT Expansion Analog Input l Model MLF-AD04A MLF-AD08A Remark Specification Voltage Current Voltage Current Number of Channels 4 channels 8 channels Analog Item DC voltage DC current DC Voltage DC Current Range Range DC 0~10V DC 4~20mA, DC 0~20 mA DC 1~5V, DC 0~5V DC 4~20mA, (Input resistance : 1MΩ min.) (Input resistance : 250Ω) DC 0~10V, DC-10~10V DC 0~20 mA (Input resistance : 1MΩ min.) (Input resistance : 250Ω)

Digital Type 12bit binary data 12bit binary data output Range Unsigned value 0~4000 0~4000 Signed value -2000~2000 -2000~2000 Precise value 0~1000 400~2000 / 0~2000 1~5V : 100~500 4~20mA : 400~2000 0~5V : 0~500 0~20mA : 0~2000 0~10V : 0~1000 Percentile value 0~1000 0~1000 Resolution 2.5mV (1/4000) 5µA (1/4000) 1/4000 1.25mV (DV 1~5V, 0~5V) 5µA (DC4~20mA, 0~20mA) 2.5mV ( DC 0~10V) Accuracy ±0.5% less Max. Conversion Speed 1.5msec / channel Max. Absolute input ±15V ±25mA ±15V ±25mA Analog Input channels 4 channel / module 8 channel Insulation Photo-coupler insulation between I/O terminal and power Photo-coupler insulation between I/O terminal and supply power supply Connection Terminal 11-point terminal block 11-point terminal block Occupied I/O points Fixed type : 64 points Consumption DC5V(Internal) 120mA 105mA Current DC24V(External) 62mA 85mA Additional Filtering Digital Filter(4~64,000) Function Average Time average(4~16,000ms) Count average(2~64,000counts) - Movement(2~100 sets) Alarm - Burn-out detection(DC 1~5V, DC 4~20mA) Max. Connectable modules 7sets (MLM series, “S” type), 10sets(MLC series, “H” type) Weight 64g 81g Supplying Voltage 20.4~28.8Vdc

For analog module(8channel), it’s needed to connect the following version info.

Basic unit Required Version MLM-D_S / MLI-D_SU V2.6 or later / V1.0 or later MLC-D_H / MLI-D_H V1.9 or later / V1.0 or later 1 No Name Descriptions ►Indicates condition of modules 1 RUN LED  LED ON : Normal Condition  LED ON and OFF : Flickering

2  LED Off : Power Off or Module malfunction

►Voltage / Current selection switch 2 Input selection S/W  V : Voltage input selection  I : Current input selection 3 Terminal Block ►External device connection 3 External power 4 ►External DC24V input supply terminal

4 Wiring with 2-wire sensor Wiring with 4-wire sensor

►in wiring between input module and external device, please use 22AWG and 2-core, twisted- shielded wire. 20 | P a g e

M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT

Expansion Analog Output l Model MLF-DV04A MLF-DC04A Remark Specification Voltage Current Number of Channels 4 Channels 4 Channels Analog Range DC 0~10V (Load resistance ≥ 2kΩ) DC 4~20mA / DC 0~20 mA (Load resistance ≤ 510Ω) Analog range selection - Softmaster I/O parameter Output Range 0 ~ 10V 4 ~ 20mA / 0 ~ 20mA Unsigned Value 0 ~ 4000 0 ~ 4000 Singed Value -2000 ~ 2000 -2000 ~ 2000 Digital data Precise value 0 ~ 1000 200 ~ 2000 / 0 ~ 2000 Percentile value 0 ~ 1000 0 ~ 1000 Data format of digital input is set by user program or I/O parameter Data Format (Setting for each channel is available) 1/4000 1/4000 Resolution 2.5mV 5µA Accuracy ±0.5% less Max. Conversion Speed 1.0msec / channel Max. Absolute input DC ±15V DC ±25mA Analog Input channels 4 channel / module Photo-coupler insulation between I/O terminal and Photo-coupler insulation between I/O terminal and Insulation power supply power supply Connection Terminal 11-point terminal block 11-point terminal block Occupied I/O points Fixed type : 64 points Consumption DC5V(Internal) 110mA 110mA Current DC24V(External) 70mA 120mA Max Connectable modules 7sets (MLM series, “S” type), 10sets(MLC series, “H” type) Weight 64g 70g

1

No Name Descriptions ►Indicates condition of modules  LED ON : Normal Condition 1 RUN LED  LED ON and OFF : Flickering  LED Off : Power Off or Module malfunction 2 Terminal Block ►External device connection 2 External power 3 ►External DC24V input supply terminal

3

Wiring 2kΩ or more 510Ω or more

MLF- MLF- DV04A 2kΩ or more DC04A 510Ω or more

21 | P a g e

M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT Expansion Analog Input and Output l MLF-AH04A Model Remark Specification Voltage Current Voltage Current Analog Item DC Voltage DC Current DC Voltage DC Current Range Range DC 1~5V, DC 0~5V DC 4~20mA, DC 1~5V, DC 0~5V DC 4~20mA, DC 0~10V, DC-10~10V DC 0~20 mA DC 0~10V, DC-10~10V DC 0~20 mA (Input resistance : 1MΩ min.) (Input resistance : 250Ω) (Input resistance : 2kΩ min.) (Input resistance : 510Ω)

Digital Type 12bit binary data(Output) 12bit binary data(Input) Data Range Unsigned value 0~4000 0~4000 Signed value -2000 ~ 2000 -2000 ~ 2000 Precise value 1~5V : 100~500 4~20mA : 400~2000 1~5V : 100~500 4~20mA : 400~2000 0~5V : 0~500 0~20mA : 0~2000 0~5V : 0~500 0~20mA : 0~2000 0~10V : 0~1000 0~10V : 0~1000 Percentile value 0~1000 0~1000 Resolution 1/4000 1/4000 1.25mV (DV 1~5V, 0~5V) 5µA (DC4~20mA, 0~20mA) 1.25mV (DV 1~5V, 0~5V) 5µA (DC4~20mA, 0~20mA) 2.5mV ( DC 0~10V) 2.5mV ( DC 0~10V) Accuracy ±0.5% less Max. Conversion Speed 1msec / channel Max. Absolute input ±15V ±25mA ±15V ±25mA Analog channels 4 channel / module for Analog input 4 channel / module for Analog output Insulation Photo-coupler insulation between I/O terminal and power Photo-coupler insulation between I/O terminal and supply power supply Connection Terminal 11-point terminal block 11-point terminal block Occupied I/O points Fixed type : 64 points Consumption DC5V(Internal) 120mA Current DC24V(External) 130mA Additional Filtering Digital Filter(4~64,000) - Function Average Time average(4~16,000ms) - Count average(2~64,000counts) - - Movement(2~100 sets) Alarm - Burn-out detection(DC 1~5V, DC 4~20mA) Max. Connectable modules 7sets (MLM series, “S” type), 10sets(MLC series, “H” type) Weight 80g Supplying Voltage 20.4~28.8Vdc

For analog IO(4channel), it’s needed to connect the following version info.

Basic unit Required Version MLM-D_S / MLI-D_SU V2.6 or later / V1.0 or later MLC-D_H / MLI-D_H V1.9 or later / V1.0 or later No Name Descriptions 1 ►Indicates working condition of inputs  LED ON : Normal Condition 2 1 INPUT LED  LED ON and OFF : Flickering  LED Off : Power Off or Module malfunction

►Indicates working condition of outputs 3 2 OUTPUT LED  LED ON : Normal Condition  LED ON and OFF : Flickering 4  LED Off : Power Off or Module malfunction

Input(3) / output(4) ►Voltage / Current selection switch 3,4 5 selection S/W  V : Voltage input selection  I : Current input selection

5 6 Terminals for INPUT ►External device connection with Inputs 6 Terminals for OUTPUT ►External device connection with Outputs

External power 7 ►External DC24V input 7 supply terminal

►in wiring between input module and external device, please use 22AWG and 2-core, twisted- shielded wire.

22 | P a g e

M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT

Expansion RTD input l

Model RTD input 1 Specification MLF-RD04A MLF-RD01A Number of channels 4 1 2 Sensor type Pt100 JISC 1840-1997 5 JPt100 JIS C 1604-1981, KS C 1603-1991 Pt100 -200 ~ 600℃ Temperature range JPt100 -200 ~ 600℃ Digital output Pt100 -2000 ~ 6000 3 JPt100 -2000 ~ 6000 Scaling 0 ~ 4000 Accuracy 25℃ ±0.3% or less

0 ~ 55℃ ±0.5% or less 4 Conversion speed 40ms / Ch Wiring method 3-wire DC 5V 100mA Current consumption DC 24V 100mA Between Channels Non-Isolation Insulation Other Photo-coupler insulation between I/O terminal and power supply Connection terminal 15 points terminal Occupied I/O points Fixed type : 64 points Weight

No Name of parts Name Descriptions ►Indicates condition of modules  LED ON : Normal Condition 1 RUN LED  LED ON and OFF : Flickering  LED Off : Power Off or Module malfunction

►Displays the status of the channels (Light fault) 2 ALM LED  Flickering : Line disconnection(Burn-out) flickering ever 1sec  LED OFF : Normal status

3 Terminal Block ►3-wire RTD sensor can be connected

4 External power terminal ►External DC24V input 6 Expansion Connector ►Connects the module with an expansion module

2-wire 3-wire 4-wire Wiring

23 | P a g e

M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT

Expansion TC input l

Model TC(Thermo-couple) input Specification 1 MLF-TC04S Number of channels 4 Thermo-couple, K/J/T/R 2 Sensor type JISC 1602-1995 5 K -200 ~ 1300℃ (- 328.0℉ ~ 2372.0℉) J -200 ~ 1200℃ (- 328.0℉ ~ 2192.0℉) Temperature range T -200 ~ 400℃ (- 328.0℉ ~ 752.0℉) R 0.0 ~ 1700℃ (32.0℉ ~ 3092.0℉) Temperature Display Display down to one decimal place K, J, T : 0.1℃, R : 0.5℃) 6 unit 3 Digital output Scaling display (defined Unsigned Scaling (0 ~ 65536) by user) Signed Scaling (-32768 ~ 32767) Normal 25℃ ±0.2% or less 4 Accuracy Temperature coefficient ±100 ppm / ℃ (0 ~ 55℃) Conversion speed 50ms / Ch Cold junction Compensation Method Auto-compensated by RJC sensor (Thermistor) compensation Accuracy ±1.0 ℃ Warming-up time 15 minutes or more Current DC 5V 100mA consumption DC 24V 100mA Between Channels Photo-MOS relay insulation Between terminal and Photo-coupler insulation Insulation internal circuit Between terminal and DC-DC converter insulation power supply Withstand voltage 400Vac, 50/60Hz for 1min., leakage current 10mA or less Insulation resistance 10MΩ over at 500Vdc Megger Connection terminal 11 points terminal Occupied I/O points Fixed type : 64 points Weight For MLF-TC04S, MLM series shall be V1.8 or later. Except MLC, MLI series.

No Name of parts Name Descriptions ►Indicates condition of modules  LED ON : Normal Condition 1 RUN LED  LED ON and OFF : Flickering  LED Off : Power Off or Module malfunction

►Displays the status of the channels (Light fault) 2 ALM LED  Flickering : Line disconnection(Burn-out) flickering ever 1sec  LED OFF : Normal status

3 Terminal Block ►3-wire RTD sensor can be connected

4 External power terminal ►External DC24V input 5 Expansion Connector ►Connects the module with an expansion module 6 RJC ►Device for Cold Junction Compensation(Sensor)

Compensation Module Terminals Shield cable Sensor cable

24 | P a g e

M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT

Expansion Positioning Module l

Model Position control Specification MLF-PD02A 1 Number of control Axis 2 Pulse output type Line Drive Max Pulse output 2 Mbps Max Connection Length 10m(32.8 feets) Position control, Speed control, Speed / Position switching control, Control Mode Position / Speed switching control Interpolation Linear interpolation, Circula interpolation Positioning Data 150 operation data for each axis 2 Configuration Tool Built-in Function Parameters on XoftMaster Back-up Flash memory Positioning Positioning method Absolute / Incremental method Unit Pulse Positioning range - 2,147,483,648 ~ 2,147,483,648 Speed range 1~2,000,000(pulse/sec) Acceleration/Deceleration type Trapezoidal acceleration / deceleration Acceleration/Deceleration time 0~65,535ms, Asymmetric acceleration / deceleration Max Encoder input 200kpps(Line drive) Error / Operation LED Occupied I/O points Fixed type : 64 points Connection Terminal 40pin Connector Current Consumption 500mA Weight 80g

Basic unit Required Version MLM-D_S V3.0 or later MLC-D_H V1.8 or later MLI-D_H, MLI-D_SU V1.2 or later

Name of parts No Name Descriptions 1. RUN 2. X_Axis, Y_Axis ►Indicates condition of modules  ON : Operation 1 RUN LED  LED ON : Normal Condition  Flickering : Error  LED Off : Abnormal Condition

2 Terminal Block ► Terminals to connect the MPG, external device and drive device.

25 | P a g e

M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT

Expansion High Speed Counter Module l

Model Specification 1 Specification MLF-HO02A MLF-HD02A Count input Signal A-phase, B-phase signal Input type Voltage input (Open Collector) Differential input (Line Drive) Signal level DC 5/12/24V RS-422A Line Drive/HTL LEVEL Line Drive Max. Coefficient speed 200 kpps 500 kpps(HTL input : 250 kpps) Number of channels 2 channels Coefficient Range Signed 32-bit (-2,147,483,648 ~ 2,147,483,647) Linear Count (When 32-bit range exceeded, Carry /Borrow occurs, The count value stopped) Count Mode Ring Count (Repeated count within setting range) 1-phase input 2 Input Pulse Mode 2-phase input CW/CCW input Increasing / Decreasing operation setting by B-phase input 1 phase input Increasing / Decreasing operation setting by program Up/down 2 phase input Automatic setting by difference in phase setting A-phase input: Increasing operation CW/CCW B-phase input: Decreasing operation 1 phase input 1/2 multiplication Multiplication 2 phase input 1/2/4 multiplication CW/CCW 1 multiplication Signal Preset instruction input, Auxiliary mode instruction input Control input Signal level DC 5V/12V/24V (by terminal selection) input type Signal type Voltage Output points 2-point/channel (for each channel): Terminal output available External Select single-compared (>, >=, =, =<, <) or Type output section compared output (Included or excluded) Output type Open collector output (Sink) Input Signal A-phase input, B-phase input, Preset instruction input, Auxiliary mode instruction input Operation Output Signal External output 0, External output 1 Status Display Busy Status Module Ready Count enable To be set through program (Count available only in enable status) Preset function To be set through terminal or program Count clear, Count latch, Section count(time setting value: 0~60000㎳), Auxiliary mode function Measurement of input frequency(for respective input phase), Measurement of counts per hour(time setting value: 0~60000㎳) Count prohibited function Terminal 40 pin connector I/O occupied points Fixed point: 64 Current consumption(mA) 200 260 Weight 90g

Basic unit Required Version MLM-D_S V3.0 or later MLC-D_H V1.8 or later MLI-D_H, MLI-D_SU V1.2 or later

Name of parts No Name Descriptions ▶ On: Relevant channel pulse inputting, Preset/Auxiliary function signal inputting, Outputting 1 RUN LED (Ø A,Ø B, P, G, 00, 01) ▶ Off: No input of relevant channel pulse, No input of preset/ Auxiliary function signal, No output of comparison

▶ On: HSC module normal

Ready signal (RDY) ▶ Off: Power off or CPU module reset, HSC module error

 Flicker: HSC module error▶ On: HSC module normal

2 External wiring ▶► Off:Connector Power tooff con or CPUnect withmodule external reset, I/O HSC. module error connector �Flicker: HSC module error

26 | P a g e

M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT

Option Board MLI “SU” and “E” of ML50 PLC provides the optimal solution of cost-effective and attachable for MLI series.

Attachable Max. 2set Attachable Max. 1set

Name of parts

No Name Descriptions

1,4 Hook for fixing Hook for fixing on front side of Main module

2 Terminals to connect with external device(wires) Terminal Block

3 Cover Cover for protecting circuit of module

5 Expansion Connector Connects the option board with an main module

6 Connector for wiring Connects the option board with an main module

27 | P a g e

M a s t e r L o g i c 5 0 S e r i e s COMMUNICATIONS

Fast Ethernet l Network with Ethernet & Performance specifications

HMI HMI

HCiX ML50 ML200 HC900/Other Controller

Item MLL-EMTA Communication spec. 10/100BASE-TX Protocol TCP/IP, UDP/IP Service With ML PLCs High-speed link, P2P service With other devices P2P service Application Dedicated protocol service, SoftMaster service HS link sending/receiving data 200words/block(Max.128blocks) No. of channel connectable to upper stage 8 channels Service Communication with PC(HMI) and external devices, High-speed communication among ML PLCs Media UTP/STP Category 5 Current consumption (mA) 410

Snet l System configuration & Performance specifications

RS-232C

SoftMaster

Main unit

Dedicated modem

RS-232C/485 Dedicated modem Other net Smart I/O devices HCi/HCiX ML50 Inverter

Specification Item Built-in RS-232C MLL-C21A Built-in RS-485 MLL-C41A interface RS-232C 1Ch RS-232C 1Ch RS-485 1Ch RS-422/485 1Ch Modem connection Remote communication with external devices via modem connection, Available for only RS-232C port. communication Dedicated mode 1:1 or 1:N communication using MLDP mode SoftMaster mode Program upload/download and remote control P2P mode Communication by protocal using SoftMaster-NM (Interface with other PLCs), MLDP, MODBUS RTU/ASCII master communication Operation Server(Slave) Remote connection simultaneoualy using MLDP/Modbus Server, user-defined mode Master MLDP, MODBUS RTU/ASCII master, user-defined Start Bit 1 Data Bit 7 or 8 Data type Stop Bit 1 or 2 Parity Even/Odd/None Setting Basic parameter setting with SoftMaster-NM Synchronization Asynchronous Transmission speed (bps) Selectable among 1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 bps Station number setting Up tp 32 stations from 0 to 31 with SoftMaster-NM Transmission distsnce RS-232C: Max. 15m (Extendfible by using modem), RS-422/485: Max. 500m Modem communication Not available Available Not available Not available Network configuration 1:1 1:N Diagnosis function Available through LED and SoftMaster-NM dagnosis service Max. number of installation Built-in 2 Built-in 2

28 | P a g e

M a s t e r L o g i c 5 0 S e r i e s COMMUNICATIONS

Ethernet IP l Network with Ethernet IP & Extensive Client Messaging Support

Features-Ethernet IP  Communication : Extensive Client Messaging Support - Encapsulated Messages, UCMM Explicit Messaging - Class 3 Connected Explicit Messaging(Server only) - Class 1 Connected Implicit(IO) Messaging(Cyclic I/O Service Oly)  Compatibility : Complied with Ethernet/IP conformance Test Suite Ver 2.10  Not required to add any Switch Hub by internal function, but provided wiring reduction and flexibility of installation  Diagnostics and status of each module and Network - Provided the status of Communication module, Communication service(EIP, non-cyclic server) - Automatic scanning to detect all module information for Honeywell or other makers - Forecasting network traffic from various packets and data rate to receive into communication module - Diagnosis of communication module over network

Item MLL-EIPT Transmission Speed 10Mbps Transmission Method Base band Max. Extension distance Transmission Standard 100meters(328 feets) between nodes Access Method to service zone CSMA / CD Frame Error Check CRC 32 = X32+ X26 + X23 + ,,,,, + X2 + X + 1 Topology Linear, Star Periodic Client Implicit IO Client Service Aperiodic Client UCMM Client Periodic Server Implicit IO Server The number of TCP 16 / 32 connections(Client/Server) CIP(IO communication) 32 / 64 No. of Max. services(P2P) 2 No. of Max. installations 2 Max setting data size Periodic client 500 bytes per block Non-periodic client 512 bytes Dimension (mm) H x W x D = 90 x 27 x 60 mm (3.54 x 1.06 x 2.36 inch) Basic standard Current consumption (mA) 290 Weight(g) 102

29 | P a g e

M a s t e r L o g i c 5 0 S e r i e s COMMUNICATIONS

CANopen l Network with CIA : CAN in Automation Support

CANopen Slaves

CANopen CANopen Master HMI Speed Driver Encoder Configuration

120 120

Features-CANopen  Open network to use on industrial fields - Transmitting Method : CSMA/BA(Carrier Sense Multiple Access/Bitwise Arbitration) - Compliant with CANopen(CiA DS301) standard  Attachable up to 2 sets per basic unit  8kinds of Communication speed are available. (10, 20, 50, 100, 125, 250, 500, 800, 1000Kbps)  Connectable max 32sets for slaves, provided Diagnostics and status information for each module  With provision of switch function internally, not needed to add any switch-hub. Benefit to reduced wirings and flexible for installation  Due to Auto Cross-over function, ease to wiring and cable work  Diagnostics and status of each module and Network - Provided the status of Communication between Master and Slave over Device Diagnosis - Automatic scanning to detect all module information for Honeywell or other makers - Shows the recent 10 items of historical information (MLL-CSEA)

Item MLL-CMEA MLL-CSEA Transmission Speed 10, 20, 50, 100, 125, 250, 500, 800, 1000kbps Number of CANopen port 1 Max. Connectable nodes 32 - TPDO 64 Number of PDO Totally 32 RPDO 64 Max Data size per PDO 8 bytes Synchronous acyclic(0), synchronous cyclic(1~240), RTR(252~253), Transmission type of PDO time-event trigger(254~255) Support SDO 127 for Client / 1 for Server 1 for Server Transmission type of SDO Expedited, Normal - How to Access to Media CSMA/BA(Carrier Sense Multiple Access/Bitwise Arbitration) Topology BUS Sync Service Producer support, Period=20~5000msec Consumer support NMT Node Control Support of NMT Master Support of NMT Slave Emergency Save max recent 5 items per Slave Save max recent 10 items NMT Error Control Support Heartbeat, Life Guarding Support Heartbeat Network Scan Support - Dimension H x W x D = 90×27×60 mm (3.54 x 1.06 x 2.36 inch) Current consumption (mA) 211 202 Weight 78 g (0.172 lbs)

30 | P a g e

M a s t e r L o g i c 5 0 S e r i e s COMMUNICATIONS

Name of LED and meanings

Common Specs

No Name Descriptions Remark

1 RUN ON Normal Operation

(Green) Flickering Ready to operate, MLL-CMEA only Green ON 200ms Green OFF 200ms Display by CiA303-3 Flickering Stopped. ON 200ms OFF 1000ms

OFF Not configured parameters or not connected

2 Flickering Interface status with main unit - Normal In abnormal case, I/F (Yellow) Stopped ON or OFF OFF or ON Not interface status with main unit

3 Green Flickering Sending a packet frame TX Display sending (Green) status of frame OFF or ON Not sending Green 4 RX Flickering Receiving a packet Display receiving (Green) OFF or ON Not receiving status of frame Green 5 ERR ON/Flickering On Error (Red) Display by CiA303-3 OFF Normal operation Green

Error Status and Messages

Descriptions Item Operation MLL-CMEA MLL-CSEA OFF No Error

Flickering1 Count of Slave on Parameter is ERR different from actual slaves on - network.

Flickering2 Error Passive Status (TEC>=128 or REC>=128) (When there is any node of different speed or disconnected wire) Flickering3 Error Control event.(Occured Heartbeat error)

OFF Bus OFF Status (TEC>=255 or REC>=255)

31 | P a g e

M a s t e r L o g i c 5 0 S e r i e s COMMUNICATIONS

Smart I/O l Expandable type with IOs for ML50

Modbus TCP Device Net Profibus-DP Features- Ethernet IP  Easy configuration of remote system using ML50 expansion IO  Up to 8 expandable modules with Network adapter  Max. 256 point digital I/O  Max. 16-channel Analog I/O  Various network adapters : Profibus-DP, Device net, Modbus TCP, Ethernet IP

Device Net : MDL-BSSA Profibus-DP :MPL-BSSA

Ethernet : MEL-BSSA(Modbus TCP), MEL-BSSB(Ethernet IP)

When I/O module is installed, check the current consumption, supplicable Max 1.5A

32 | P a g e

M a s t e r L o g i c 5 0 S e r i e s COMMUNICATIONS

Product List l

Item Model Descriptions Non-IEC MLC-DN32H 100~240Vac, 16 points DC input, 16 points TR output

MLC-DR32H 100~240Vac, 16 points DC input, 16 points Relay output MLC-DN64H 100~240Vac, 32 points DC input, 32 points TR output Block type (High MLC-DR64H 100~240Vac, 32 points DC input, 32 points Relay output Performance) MLC-DN32H/DC 24Vdc, 16 points DC input, 16 points TR output MLC-DR32H/DC 24Vdc, 16 points DC input, 16 points Relay output MLC-DN64H/DC 24Vdc, 32 points DC input, 32 points TR output MLC-DR64H/DC 24Vdc, 32 points DC input, 32 points Relay output Non-IEC MLM-DN16S 24Vdc, 8 points DC24V input, 8 points TR output Modular type MLM-DR16S 24Vdc, 8 points DC24V input, 8 points Relay output MLM-DN32S 24Vdc, 16 points DC24V input, 16 points TR output IEC MLI-DN32H 100~240Vac, 16 points DC input, 16 points TR output MLI-DR32H 100~240Vac, 16 points DC input, 16 points Relay output Block type MLI-DN64H (High 100~240Vac, 32 points DC input, 32 points TR output Performance) MLI-DR64H 100~240Vac, 32 points DC input, 32 points Relay output MLI-DR32H/D1 DC 12/24V, 16-point DC input, 16-point Relay output MLI-DR64H/D1 DC 12/24V, 32-point DC input, 32-point Relay output IEC MLI-DR10E 100~240Vac, 6 points DC input, 4 points Relay output MLI-DR14E 100~240Vac, 8 points DC input, 6 points Relay output MLI-DR20E 100~240Vac, 12 points DC input, 8 points Relay output MLI-DR30E 100~240Vac, 18 points DC input, 12 points Relay output MLI-DN10E 100~240Vac, 6 points DC input, 4 points TR output(Sink) MLI-DN14E 100~240Vac, 8 points DC input, 6 points TR output(Sink) Block type “E” (Economic MLI-DN20E 100~240Vac, 12 points DC input, 8 points TR output(Sink) type) MLI-DN30E 100~240Vac, 18 points DC input, 12 points TR output(Sink) MLI-DP10E 100~240Vac, 6 points DC input, 4 points TR output(Source) MLI-DP14E 100~240Vac, 8 points DC input, 6 points TR output(Source) MLI-DP20E 100~240Vac, 12 points DC input, 8 points TR output(Source) MLI-DP30E 100~240Vac, 18 points DC input, 12 points TR output(Source) IEC MLI-DN20SU 100~240Vac, 12 points DC input, 8 points TR output(Sink) MLI-DR20SU 100~240Vac, 12 points DC input, 8 points Relay output MLI-DN30SU 100~240Vac, 18 points DC input, 12 points TR output(Sink) Block type “SU” MLI-DR30SU 100~240Vac, 18 points DC input, 12 points Relay output (Standard type) MLI-DN40SU 100~240Vac, 24 points DC input, 16 points TR output(Sink) MLI-DR40SU 100~240Vac, 24 points DC input, 16 points Relay output MLI-DN60SU 100~240Vac, 36 points DC input, 24 points TR output(Sink) MLI-DR60SU 100~240Vac, 36 points DC input, 24 points Relay output IEC MLI-DN32U 100~240Vac, 16 DC input, 16 TR output(Sink), Enet MLI-DR28U 100~240Vac, 16 DC input, 12 Relay output, Enet Block type “U” (Ultimate type) MLI-DN32UA 100~240Vac, 16 DC input, 16 TR output(Sink), 8 AIO, Enet MLI-DR28UA 100~240Vac, 16 DC input, 12 Relay output, 8AIO, Enet 33 | P a g e

M a s t e r L o g i c 5 0 S e r i e s COMMUNICATIONS

Product List l Item Model Descriptions

MLE-DC08A 8-point DC24V input MLE-DC16A 16-point DC24V input

MLE-DC32A 32-point DC24V input Expansion MLE-RY08A 8-point Relay output I/O module MLE-RY16A 16-point Relay output MLE-TN08A 8-point TR(SINK) output

MLE-TN16A 16-point TR(SINK) output MLE-TN32A 32-point TR(SINK) output

MLE-DR16A 8-point DC24V input, 8-point Relay output

MLE-TP08A 8-point Transistor (source) output MLE-TP16A 16-point Transistor (source) output

MLE-TP32A 32-point Transistor (source) output MLF-AD04A 4-channel Analog input (Current/Voltage)

MLF-AD04C 4-channel Analog input (Current/Voltage, resolution : 1/16000) MLF-AH04A 2-ch Analog input (Current/Voltage), 2-ch Analog output (Current/Voltage)

MLF-DV04A 4-channel Analog output (Voltage) Special module MLF-DC04A 4-channel Analog output (Current) (Analog IO) MLF-RD04A 4-channel RTD input MLF-TC04S 4-channel Thermo-couple input(Isolation)

MLF-AD08A 8-channel Analog input (Current/Voltage) MLL-C41A Snet(RS422/485), 1channel

MLL-C21A Snet(RS232C), 1channel MLL-EMTA Fast Ethernet (100Mbps), 1ch Communication module MLL-EIPT Ethernet/IP, 2channel MLL-CMEA CANopen(max 1000kbps, Num of PDO : 32)

MLL-CSEA CANopen(max 1000kbps, Num of PDO : 64) MLL-PMEC Profibus-DP, Master

PMC-310S Configuring Cable serial, PC(9pin)-PLC(6pin)

USB-301A Configuring Cable, USB

MLO-AD02A 2-channel Analog input (Current/Voltage)

MLO-DA02A 2-channel Analog output Option Boards MLO-AH02A 1-ch Analog input(I/V), 1ch Analog output(I/V) for “SU”, “E” MLO-TC02A 2-channel Thermo-couple input(non-isolation) MLO-RD01A 1-channel RTD input

MLO-RTCA RTC, BAT for back-up MLO-M2MB Option Memory, 2Mbytes

Smart IO MPL-BSSA Profibus-DP Adapter Extendable MDL-BSSA Device Net Adapter

MEL-BSSA Ethernet, Modbus TCP adapter MEL-BSSB Ethernet IP adapter

34 | P a g e

M a s t e r L o g i c 5 0 S e r i e s COMMUNICATIONS

Smart Link

Terminal MLM-DN16S Connection Cable MLE-DC32A MLE-TN32A Cable Length Remark Board MLM-DN32S

R40H/20HH-05S 0.5m R40H/20HH-10S 1.0m TG7-1H40S C40HH-15S-XBI 1.5m C40HH-30S-XBI 3.0m

Configuration Cable

PC side

(9pin, Female)

ML50 (6pin, Male)

Local HMI – HCiX series

35 | P a g e

Australia Japan Philippines Honeywell Ltd. Honeywell Inc. Honeywell Systems (Philippines) Inc. Phone: (61) 2-9353-7000 Phone: (81) 3-6730-7149 Phone: (63) 2-633-2830/31 Fax: (61) 7-3840-6488 Fax: (81) 3-6730-7228 Fax: (63) 2-638-4013

Indonesia South Korea Honeywell Co., Singapore Honeywell Pte PT Honeywell Indonesia Ltd. Phone: (82) 2-799- Ltd. Phone: (65) 6355- Phone: (62) 21-535-8833 6114 2828 Fax: (62) 21-536-71008 Fax: (82) 2-792-9015 Fax: (65) 6445-3033

India Malaysia Thailand Honeywell Automation India Limited. Honeywell Engineering Sdn Bhd. Honeywell Systems (Thailand) Ltd. Phone: (91) 20-6603-9400 Phone: (603) 7958-4988 Phone: (662) 693-3099 Fax: (91) 20-6603-9800 Fax: (603) 7958-8922 Fax: (662) 693-3085

Taiwan New Zealand Honeywell Taiwan Ltd. Phone: Honeywell Ltd. (886) 2-2245-1000 Phone: (64) 9-623-5050 Fax: (886) 2-2245-3243 Fax: (64) 9-623-5060

For Countries (SEAsia) Listed below, See Honeywell Singapore Office Pakistan, Cambodia, Laos, Myanmar, Vietnam and East Timor.

For Countries Listed below, See Honeywell Automation India Limited. Bangladesh, Nepal and Sri Lanka.

Honeywell offers a complete portfolio of products and solutions for process and machine control applications, including controllers, recorders, transmitters, actuators, smart sensors, and analytical instruments. To learn more about these offerings and how they can help your organization achieve breakthrough results, contact your local Honeywell representative, or contact us at the following phone numbers:

U.S.A.: 1-800-784-3011 France: 33 1 60 19 80 75 Canada: 1-800-461-0013 Italy: 39 02 9214 6503 UK: 44 1344 655251 Spain: 34 91313.61.00 Germany: 49 69 8064-336 Asia/Pacific: 65 6355 2828 Latin America: 1-305-805-8188

Warranty / Remedy Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship. Contact your local sales office for warranty information. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or replace without charge those items it finds defective. The foregoing is Buyer's sole remedy and is in lieu of all other warranties, expressed or implied, including those of merchantability and fitness for a particular purpose. Specifications may change without notice. The information we supply is believed to be accurate and reliable as of this printing. However, we assume no responsibility for its use. While we provide application assistance personally, through our literature and the Honeywell web site, it is up to the customer to determine the suitability of the product in the application.

Specifications are subject to change without notice.

Honeywell Process Solution

HFS Asia Pacific Honeywell Building http://www.honeywellprocess.com

17 Changi Business Park Central 1 10-23-30-14-EN REV5 Singapore 486073 Aug 2016

Copyright 2013 Honeywell International Inc. 36 | P a g e