Air Combat Command has a long heritage of facilities excellence. Quality facilities which meet the users’ needs, are technically sound and compatible with their environment enhance mission effectiveness and readiness.

The Operations and Aircraft Maintenance Unit facilities are among the most important in the . As such these facilities must provide the space and elements to be functional, safe, and foster pride that will reflect in unit performance.

As we improve the functional- ity of our Squadron Operations/ Aircraft Maintenance Unit facilities with good upfront plan- ning and smart decision-making, Air Combat Command will con- tinue it’s tradition of providing design and facilities excellence.

This guide was developed to set the standard for Squadron Operations and Aircraft Maintenance Unit facilities. This guide should be used during the programming, design, and construction process to ensure we provide quality facilities to our Airmen. The concepts in this document have as much to do with common sense and mindset as with the need for funding. Quality facilities and tight budgets are not mutually exclusive.

Signature

William M. Fraser III

Lieutenant General, USAF CommanderARCHIVED Aircraft Maintenance

Squadron ARCHIVEDOperations TABLE OF CONTENTS

PLANNING, PROGRAM & SPACE CRITERIA ……………………………………… 2

SITE EVALUATION CRITERIA …………………………………………………………… 6

SITE SELECTION AND DESIGN ………………………………………………………… 8

BUILDING DESIGN ………………………………………………………………………… 12

SQUADRON OPERATIONS CENTER (SOC) ………………………………………… 18

AIRCRAFT MAINTENANCE UNIT (AMU) ………………………………………… 28

INTERIOR FINISHES ………………………………………………………………………… 36

SPECIAL PROJECT COSTS ………………………………………………………………… 40 REFERENCESARCHIVED ………………………………………………………………………………… 42 2

PLANNING, PROGRAM & SPACE CRITERIA

������������������������������ � � � � � � � � � �

��� ������������� ������������� ������ ����� ������������������� ��������� ����� ������������ ��� ������������ �������� �������� ������������������������� � ��������� ��������� ���� ����������������������� ����������

�������� ���� ����� ������ ���� �����

��������������������� ��������������������� �������� ��������� ��� ����������� ������������ �������� ���� ��� ������������� ����� �������

��������� ���������� � ������������������� ���������� ������������������������ ���� ��� �������� �������� ������� ��� � ����� ���������������������������� �������� ��������� ���� ������ ������������ ������� ��������� ���������

� ��� �������������� ����������������� ARCHIVED� ��������� �������������� ����������������������

������������������ Planning, Program & Space Criteria 3

A well designed Squadron Operations and Aircraft Maintenance Command and Unit facility is vital for improving the productivity of the Air Force’s Administration most valuable resource - its people. The design and image of the fa- cility have a lasting impact on the quality of mission readiness. It In general, the Command and should establish a high level of professionalism and expectation. Administration area of the facility is home to private office spaces Selection of a logical, convenient site is to be followed by a building that for the command, non-private addresses the street and its neighbors. A well-landscaped, attractive park- offices and areas for crewmembers, ing lot should be situated beside or behind the facility outside of the secure administrative areas and other area and should be large enough to meet the individual needs of the mission. general use support spaces. The building exterior should offer a distinctive character that is appropri- ate to its surrounding facilities with a functional and inspiring interior that Typically there are private offices fulfills the needs of the mission crews dedicated to the Squadron and their support staff. It is essen- Commander, Director of Operations tial for the designer to be aware of (DO) and the Crew Chief. the Base Architectural Standards Some of the Administrative Support and the Air Combat Command offices are individual enclosed offices (ACC) Architectural and Interior spaces to ensure privacy when dealing Design Standards when designing with sensitive personnel matters. the facility, in addition to the gen- eral reference materials as listed Other non-private or shared in the back of this design guide. enclosed office spaces are provided for crewmembers and support staff When planning and programming for to complete paperwork, study and Squadron Operations and Aircraft confer privately with colleagues, and to Maintenance Unit Facilities, four meet the needs of outside contractor typical functions must be included: support where it is anticipated. Command and Administration, These spaces include areas for the Mission Planning and Briefing, Life Flight Operations Orderly Desk, Support Area, and Mission Support. Operations Desk Office, Flight Crew Each of these functions is expanded Shared Offices, Life Support Area on in the sections that follow and and the Communication Center for are revisited in the sections titled computer maintenance and data/ Squadron Operations Center (SOC) telecommunications network support. and Aircraft Maintenance Unit (AMU) later in this design guide. Support spaces for general command Space requirements for each area are and private use include the Scheduling based on the airframe and missions Area, Conference Rooms, Standards hosted by the facility and are determined by the Squadron Commander. and Evaluation Training Classrooms, Ready Room and Heritage Room. A Shared spaces can be usedARCHIVED where scheduling is practical to achieve cost Fitness Room with adjacent Locker savings and reduce the footprint of the building in the valuable real es- Room should also be provided due to tate of the flight line. The design team should consult the Squadron the distance the installation facility Commander to identify those spaces that could be shared without would normally be located from the compromising the readiness or mission capability of the squadron. flightline, the importance of physical Spaces that should be considered for sharing include the non-secure training for flight and maintenance Computer Center, Mechanical and Electrical rooms and Standardization crews, and the incompatibility and Evaluations Training Classrooms. A single secure and non-se- of crew schedules with general cure Large Briefing Room should be provided as shared space be- fitness center hours of operation. tween the Squadron Operations and Aircraft Maintenance Unit. 4 Squadron Operations & Aircraft Maintenance Unit Design Guide

Life Support Area be separate from adjacent bath and Center for this area operating on a shower area. The mobility storage area dedicated, secure network through Although the Life Support Area is not is a climatic controlled space connected shielded fiber optic cabling. located within the secure of the to the flight line through roll up doors facility, this area is secured with access and is large enough for storing and using a code based cipher lock door maneuvering life support pallets. hardware system. The Life Support Mission Support Area includes a private office for the Mission Planning and Briefing Life Support Superintendent, work The Mission Support area of the facility space and counters for the equipment This secure environment should be is organized to support functions of maintenance shop, equipment storage, constructed as a “vault”, in accordance the Aircraft Maintenance Unit. These personal crew equipment lockers with the requirements for a “SCIF”, functions include private office space, and a mobility storage area. The for control and management of non-private office space and areas for Life Support Shop is set up for the classified documents and information. crewmembers, administrative areas, maintenance, testing andARCHIVED storage of Entry into this area is through secure support spaces, aircraft maintenance oxygen equipment, aircrew chemical entry systems. The functional spaces hangar and COSO support. warfare equipment, survival gear, provided in this area include Mission with a separate night vision goggle Planning and Briefing rooms with Typically there are private offices (NVG) fitting and adjustment room. capacity to accommodate at least 60 for the Officer in Charge (OIC), the There are also personalized lockers persons, a Library for storing classified Non-Commissioned Officer in Charge for the storage of Aircrew specific files and reference materials, and an (NCOIC), Section Chief, Production Life Support equipment, such as crew Intelligence and Weapons Center with Supervisor, Technical Representative, equipment, flight suits, helmets and a Weapons Task Trainer. There is a Dispatch, and Scheduled Maintenance. other personal flight gear, which must separate, secure Communications Some of the Administrative Support Planning, Program & Space Criteria 5

offices are individual enclosed offices Locker and Laundry Room, Ready spaces to ensure privacy when dealing Room, Heritage Room and an with sensitive personnel matters. adjacent outdoor recreation space.

Other non-private or shared enclosed The Aircraft Maintenance Hangar office spaces are provided for mission should be co-located with the COSO crewmembers and support staff Support tool storage, tracking and to complete paperwork, study and parts storage (open and secure) confer privately with colleagues, and mobility storage area. and to meet the needs of outside contractor support where it is anticipated. These spaces include areas for the AMU Orderly Desk, Orderly Desk Office, AMU Shared Offices, and the CommunicationARCHIVED CAMS (IMIS) room for non-secure computer maintenance and data/ telecommunications network support.

Support spaces for general mission crew and private use include the Conference Rooms, Roll Call Room, Maintenance Debriefing, Standards and Evaluation Training Classrooms, 6

SITE EVALUATION CRITERIA

ARCHIVED Site Elevation Criteria 7

Squadron Operations and Aircraft Maintenance Unit facilities should Site Checklist be located near or adjacent to the secured area of the flightline, the Squadron’s aircraft maintenance hangars, and near the appropriate air- 1. Is the facility located outside craft simulator facility with clear visual identity and access from a explosive safety clear zones? roadway. The site plan should include provisions for the following: 2. Is the proposed site on desig- • Signage nated wetlands or flood plains? • Landscaping • 45-meter setback from secure perimeter for Force Protection 3. Is project coordination • 25-meter road and parking setbacks within se- with appropriate state cure perimeter for Force Protection and area- wide clearing- • 10-meter setback between Primary Occupied house/agencies required? Buildings for Force Protection • Secure gate into building from parking lot 4. Has the Base General • Two clear points of entry to include a main entrance from Plan been consulted? flightline and a rear entry from the street and/or hangar • Clear level access between the flightline and hangars 5. Is the facility site in a com- • Pedestrian circulation to related facilities patible land use area? • Mission crew and support staff parking of ad- equate size to accommodate shift changes 6. Does construction require • Dedicated parking for Maintenance and Operations GOV’s excessive site work? • Contractor parking • Student parking (where specified as part of the mission) 7. Are utilities readily avail- • Easy access for facility users able and adequate? Note • Delivery and Service entrance with motion sensor activated slid- in CCD when utilities ing glass doors on the Maintenance side of the facility are not adequate. • Maintenance storage area • Covered, outdoor storage area with roll-up garage door 8. Is project coordination with for ISU/pallet build-up and mobility storage the regional Federal Aviation • Future expansion Administration required?

Site Size 9. Is the project located in a for- mer waste disposal area, land- Select a site large enough to provide adequate space for exte- fill site, fuel saturated area, or rior functions, vehicle parking, and future expansion. A pre- other site identified in the In- liminary site design should be designed to ensure the ba- stallation Restoration Program? sic building and site criteria can be accommodated. 10. Has the project been sited Access and Visibility in accordance with all ap- propriate force protec- The facility should be locatedARCHIVED within the secured flight line area tion requirements? with a strong visual relationship and pedestrian connection to the Squadron Operations and Aircraft Maintenance Unit facility, han- gars, and flight lines. This connection is important in providing con- Utility Supply Requirements venient access for flight crew and mission support staff with access or visual connection to the flight simulator facility. Where it does The facility should be located not interfere with movement on and around the flight line by main- near major utilities, including tenance support vehicles and aircraft, the Aircraft Maintenance Unit water, sewage, electricity, may be attached to the Squadron’s aircraft maintenance hangars. communication lines and gas lines. 8

SITE SELECTION AND DESIGN

ARCHIVED Site Selection and Design 9

SITE SELECTION Parking areas should be located on the site away from the street entrance to uphold the public image of This is generally part of the master planning the facility. Encourage co-located parking and facil- process and is completed prior to DD Form ity arrangements to enable occupants and visitors 1391 preparation for an individual project. to conveniently park once and circulate on foot for most flight line activities. Dedicated parking spaces Site Organization should be provided for government owned vehicles (GOV’s), privately owned vehicles (POV’s), student Preserve and take advantage of dominant or attractive and contractor vehicles and motorcycles. POV park- natural landscape elements, such as topography and ing spaces shall be paved asphalt and quantities based foliage, or built features of the site and its surround- on the total positions assigned per largest shift. ings to help define and organize the site. Areas of the Provide one space per building occupant plus spaces site that could benefit from this definition include the main entry, major streets or facilities, related nearby facilities, dominant road axis or other base elements. The overall design should present an attractive image for the facility while maintaining compatibility with the planning and style of adjacent existing structures.

The building should be located on the site to reflect local climatic conditions and take advantage of pas- sive solar heating and day lighting of administrative and recreation areas where available. Whenever pos- sible, provide protection from undesirable winds and glare, expose activity areas to the sun in cold climates, shade from excessive sun in warm climates, and ori- ent operable windows to utilize summer breezes.

Consideration should be given to the orga- nization of the site when specifying location and proximity between the flight line and air- craft hanger. Minimize the distance workers need to travel when carrying heavy loads.

Refer to the Site Plans within this document for other Squadron Operations and Aircraft Maintenance Unit facility site organization examples.

for visitor parking. Additional student and contrac- Access Design tor parking spaces shall be based on mission and ARCHIVEDanticipated peak requirements and co-use by adjacent Ensure that dimensions of access roadways and facilities. Parking for Tow Vehicles on one side of service entrances meet force protection require- the hangar for Heavies in case of emergencies will be ments for parking and road setback distances and required along with dedicated parking spaces for Life can accommodate anticipated vehicle sizes or fire Support Vehicles outside of the Life Support shop. protection access. Roadways should not be over- sized thus discouraging high-speed traffic. 10 Squadron Operations & Aircraft Maintenance Unit Design Guide

The Life Support shop and the Aircraft Maintenance Unit Tool and Part Storage will need easy, level access provided from the flight line and hangar through mo- tion sensor ac tivated double sliding doors for work- ers carrying heavy loads (parachutes, survival kits, survival gear, tool boxes, etc.) and pushing tool carts. Site Utilities

Standard utilities such as water, sanitary sewer, storm drainage system and fire suppression sprinkler sup- ply, natural gas, steam service or fuel oil system, whichever is used, and electric power supply should be provided. Telephone and fiber optic communi- cation lines for LAN, secure communications and the fire alarm system(s) should also be provided. Landscaping

Provide a zeroscaping landscaping approach or one that includes native landscaping materials low main- tenance using only approved plant material identi- fied in the base’s Architectural Compatibility Guide. Consider using ground cover instead of turf with a water-conserving underground irrigation system when appropriate to the climate and planting design.

Outdoor Recreation Space

Outdoor recreation space, located on the exterior perimeter of the building adjacent to the Ready Room and the Heritage Room, should be provided and include benches, tables, paved walkways and landscaping. The recreation space should be en- closed with secure perimeter fencing, if required to meet AT/FP Standards and base security require- ments for the location, and have a secure entry into the building using card swipe door hardware.

A designated “SmokingARCHIVED Area” should also be pro- vided. This covered and shielded area outside of the hangar should be designed to comple- ment the Squadron Operations and Aircraft Maintenance Unit Facility. No wooden gazebos are allowed to be used for the “Smoking Area”. Other specific requirements will vary by base. Site Selection and Design 11

ARCHIVED 12

BUILDING DESIGN

ARCHIVED Building Design 13

The primary entrance of the facility Provide easy access into the facility for Architectural Character and should be oriented toward the flight servicing of mechanical equipment Interior Design line to allow the crew and mission and maintenance functions such as support staff to easily access the trash disposal. Mechanical areas do To present a cohesive architectural functional areas of the facility. A not need to be located adjacent to the image, the architectural and interior vestibule will be required for sound street or roadway for service access. design must be integrated while control at all entrances with the Reinforced sidewalks with a driveway designing a Squadron Operations lobby containing the orderly desk as curb cut can be used instead. Areas and Aircraft Maintenance Unit the distribution point for directing such as the mechanical yard and the facility. Both involve functional people to the primary functions of trash disposal area will need to be analysis and consideration of the building. A secondary, or rear, screened with a material compatible the appropriate environmental entry should be provided for access with the existing architectural character, building organization to the hangar and the street. character of the base facilities. and circulation, supervision and flexibility requirements, as well Consider easy access to outdoor Refer to the Space Relationship as finishes and furnishings. spaces from Ready Rooms, Operations Diagrams and the sample facility Floor Center, Life Support Shop, Heritage Plans provided in this design guide The overall design of the facility and/or Ready Rooms, and Briefing for a graphic and detailed example of should reflect regional and local and Debriefing when possible. Quiet the building organization, circulation, base architectural character or style spaces within the facility should be room sizes and adjacencies. including major exterior materials shielded from the noise of recreation, and colors. Create a theme that is aircraft, equipment, and traffic. compatible with the base architecture and applies continuously to the entire facility design from an overall

ARCHIVED 14 Squadron Operations & Aircraft Maintenance Unit Design Guide

Handicap Accessibility

All functional public areas, including entrances, corridors, and restrooms, shall be barrier-free and accessible to the physically handicapped in accordance with the Americans with Disabilities Act (ADA) and Uniform Federal Accessibility Standards (UFAS). All signage, door hardware and special equipment such fire alarms located in these areas shall also be barrier-free and meet the codes established by the ADA and UFAS. Special Considerations for Renovations

All design and building organization and circulation criteria apply to renovation projects, as well as new construction. Renovation areas should be phased, with functions on-going in the operating facility. If required, the renovation should transform the image of the existing structure, inside and architectural statement to specific Examples include changing the size of outside, to reinforce its identification interior design. Space planning, Briefing Rooms or other areas subject as a Squadron Operations and Aircraft building form and development to change as result of a change in type Maintenance facility. This may of elevation, materials, and details of airframe or mission (i.e. operational require substantial facade renovation should reinforce continuity of space. squadron to teaching squadron). This and interior redesign to achieve the Be sensitive to the natural flow of can be achieved by using lightgage steel appropriate quality and character. sequenced spaces. Circulation paths framed walls with sound attenuating should accommodate personnel insulation, non-penetrating to the and equipment and finishes are ceiling tiles and grid. Support and to be selected for effectiveness in administrative facilities should allow terms of life cycle cost. Review the flexible layout of furnishings by using base Architectural Compatibility modular-type furnishing systems. Guide to assure the design complements existingARCHIVED architecture. Flexibility and Expansion

Design of the facility should accommodate change and expansion without major redesign of the initial project. Interior partitions should be constructed of materials and methods that enable future users to employ self- help for minor floor plan alterations. Building Design 15

Signage located in the secure area of the facility optic communication lines, equipment, to serve only the secure spaces within and computer cabling required. Interior and exterior signage should be the facility. All internal classified designed and specified in accordance network telecommunication lines Video and Cable with the current ACC Sign Policy. are to be run with shielded fiber Regulation signs should be located optic cabling for security. Verify Videoconferencing capability and cable where specific warning or prohibitory the need for fiber optic cabling television access shall be provided pre- information is required and handicap to and within the facility with the wired with receptacles where required. access signage clearly identified. Squadron Commander and the Videoconferencing capabilities shall be Base Communications Squadron. included for areas such as Classrooms, Data Conference and Briefing Rooms. Cable Locations within the facility requiring television accessibility is required in Locations requiring data accessibility telecommunication and multi-line areas such as Offices, Conference and should be pre-wired with cable and communication capability should Briefing Rooms, Ready and Heritage receptacles provided to accommodate be pre-wired with receptacles and Rooms, Intelligence Weapons Center, computers and printers. Dual shielded access provided from the building COSO parts and storage areas and fiber optic cable and receptacles interior. Please refer to the Matrices the Computer CAMS/IMIS area. shall be used in secure areas. A located in this document for area system of empty raceways should specific telecommunication and Please refer to the Matrices located be provided in ceilings and walls data requirements. Provide for in this document for specific with pull wire, outlets, and cabinets equipment capable of receiving requirements per area. Requirements for future secure communication telecommunication lines display are determined by the Squadron lines and data installations in all devices for hearing impaired calls. operational spaces such as Briefing Rooms, Mission Planning, Offices, Plan for an internal communication Classrooms, Workrooms, Standards system with the central intercom and Evaluation Rooms, Training console located at the Orderly Classrooms and the Life SupportARCHIVED Shop. Desk. The system should include hands-free telephone, a two-way Telecommunication Lines intercom system throughout the facility capable of addressing all Provide a central Communication rooms or a single room at one time Center inside the building, separate and ceiling mounted speakers. from the Mechanical and Electrical rooms, to serve all non-secure Please contact the Base aspects of the facility. An additional Communications Squadron for the Communication Center should be type and quantity of shielded fiber 16 Squadron Operations & Aircraft Maintenance Unit Design Guide

Commander based on airframe and mission of the squadron. Structural

Select an economical structural system based on facility occupancy size, projected load requirements, and local availability of materials and labor. Consideration must also be given to wind, snow, seismic, geologic, frost line, and other site-specific conditions. Design building structural modules to reflect space requirements, economy, and subsystem dimensions (i.e., ceiling grid, masonry units, framing members, etc.). Provide column-free spaces. Heating, Ventilation and Air Conditioning

Provide heating, ventilating, and air conditioning (HVAC) systems with a night setback system and manual override, if required. System design will be a variable air volume (VAV) system with terminal reheat and frequency DoD total energy budget figures. and workspace, and the COSO Support drive or individual water source heat Provide a direct digital control (DDC) storage area, for safety when working pump. Each space will have its own system compatible with the existing with chemicals. Floor drains with trap environmental control system. Provide base energy monitoring system (EMS). primers should be located in all areas, tamper-proof temperature sensors with such as restrooms, janitor’s closets, remote adjustment. An active solar Plumbing showers or other areas with wet floors. space heating system and/or domestic Filtered water coolers are required hot water heating system should be The facility should have domestic hot near the reception area, restrooms, and considered only if the command’s solar and cold water supply, sanitary and Life Support shop. Where required assessment for the base results in a storm drainage and propane or natural by local climatic conditions, frost- savings investment ratio of greater than gas systems with shut-off valves at free hose bibs are to be provided on one. Zone HVAC systems separately all fixtures provided, including gas in secure and non-secure areas. devices in shops and Life Support. Hot water should reach temperature Energy MonitoringARCHIVED of 105°F for general use and 140°F at shops and Life Support. Emergency Perform a life cycle cost analysis of eyewash stations and showers are to available energy sources in accordance be provided in the Life Support shop with the appropriate standards. The uniform present worth factor and the fuel escalation rates should be the latest published by the Department of Energy. The selected systems’ total energy consumption should not exceed Building Design 17

control from 25 to 50 foot-candles and supplemental incandescent accent lighting rated at 2,500 hours. Night lighting should also be provided in the corridors with emergency back up lighting systems throughout facility. Fire Protection

Facilities should be designed of Type B, non-combustible construction with fire protection systems and should comply with the NFPA 101 Life Safety Code. Automatic sprinkler systems are required in newly constructed facilities and renovation projects should receive the same where feasible. Specialized equipment storage areas will require the appropriate type of fire protection system with the Aircraft Maintenance Hangars receiving a High Expansion Foam fire suppression system.

Provide heat and smoke detectors hard-wired into to the fire alarm system to activate the alarm all exterior walls with atmospheric special power outlets and circuits throughout using audible and visual vacuum breakers on hose bibs. for all user-furnished equipment. fire alarm systems as required by ADA handicap accessibility Electrical Power Lighting codes. Locate the fire detection/ suppression enunciator panel for Local electric service and distribution General exterior lighting at parking the building in the electric room equipment, inc1uding metering, areas and walkways should have high with indicator panels at the primary wiring, and electrical devices, are to intensity discharge (HID) light sources and secondary facility entrances. be provided to the facility; however, provided which are controlled by an emergency backup generator combination time clock/photo cells. should be considered, or may be Provide interior and exterior lighting required, to allow continuous mission control systems, including ambient planning and execution in the event light dimmers and multiple switching of a power outage. Computer and for low ambient light levels, energy network systems will needARCHIVED to have conservation and reduced glare. dedicated uninterruptible power supply on dedicated circuits located General lighting throughout the facility in the Communications Room. should be low glare fluorescent with Provide for communication lines low temperature energy efficient and data wiring, fire alarms, and electronic ballasts and lamps, as intrusion detection system along with applicable. The Computer, Mission Planning, Intel/Mapping, and Briefing Rooms should receive fluorescent light sources with ambient light level 18

SQUADRON OPERATIONS CENTER

ARCHIVED Squadron Operations Center (SOC) 19

Flight Operations Orderly Desk

The Flight Operations Orderly Desk should be lo- cated in a location visible from multiple points of entry near the entry. Enough space for up to four personnel should be allocated at the service coun- ter facing the lobby or corridor. The service counter should include a raised countertop with a stand- ing height writing surface of approximately 40” – 42” for “walk up” use as well as a desk height staff counter facing the customer(s). Sufficient standing room should be anticipated to accommo- date sizes arriving during the same shift.

To accommodate personnel working behind the Flight Operations Orderly Desk, the follow- ing items should be planned for during design:

• Provide space behind counter for radio • Built-in mailboxes for each staff and flight crewmember • Files and storage built-in be- low front and rear counter • Copy machine to support staff and flight crewmembers • Rounded corners on casework for safety • Electric power supply and communications capabil- Operations Desk Office (also known as ity for plasma screens to be mounted on wall behind “Aviation Resource Management”) desk in lieu of recessed computers and monitors The Operations Desk Office, also known as Aviation Resource Management, should be located adja- cent to the Flight Operations Orderly Desk. This area will receive modular systems furniture for approximately four to six (4-6) users, provid- ing an open office environment in this space.

Shelving and storage space shall be provid- ed at each desk unit along with all equipment and required connections for printer and net- worked computers. Reduced glare artificial light- ARCHIVEDing should also be provided in this area. Scheduling Area

Provide a Scheduling Area located adjacent to the Flight Operations Orderly Desk. This area should be equipped with dry mobile tables on lock- able casters for teaming and reconfiguration pur- poses and dry erase marker board material with catch trays along the walls. Floor mounted electri- 20 Squadron Operations & Aircraft Maintenance Unit Design Guide

cal boxes are to be located near the center of the Flight Crew Shared Offices room with the required secure connections for net- worked printers, computers and other required The Flight Crew Shared Offices are constructed as fully enclosed private offices with systems furniture Administrative Support desk, storage, shelving, and a side chair at each of- fice. The shared offices are intended to provide An Administrative Support area should be lo- temporary swing space for office, study and confer- cated adjacent to the Flight Operations Orderly ences for flight and aircraft maintenance crew not Desk area and on an exterior wall for natu- normally requiring an office to perform their primary ral lighting where possible. This area shall re- function. They shall be located near or adjacent to ceive enclosed offices for privacy when counsel- the Ready Room and may be located in an interior ing or dealing with sensitive personnel issues. or exterior location since natural lighting is not necessary for short-term use. Reduced glare artifi- Additional items to be provided in this area include cial lighting shall also be provided in these areas. shelving and file storage space in a location to be shared by staff, reduced glare artificial lighting and all Conference Rooms equipment and required connections for a copy ma- chine, fax machine, printer and networked computers. Conference Rooms shall be located near the Squadron Commander, , Director Squadron Commander of Operations (DO), Flight Crew Chief Offices, Intelligence and Weapons Officer, and Mission A private executive office space shall be provided for Planning. The size of each conference room shall be the Squadron Commander located adjacent to the designed in accordance with the aircraft type be- Flight Operations Orderly Desk and Lobby and on ing served in the facility and the number of ships an exterior wall for natural lighting where possible. anticipated for simultaneous mission briefing. Sufficient room shall be provided to accommodate a desk, credenza, shelving, file cabinet, four-person Each Conference Room shall receive the following: conference table and guest seating. The Squadron Commander will also receive a networked computer, • Wiring and connections for communication printer and all necessary power and data connections. lines, cable television, LAN service, videocon- Reduced glare artificial lighting shall also be provided. ferencing, and dedicated high-speed data con- nections for each person in the room Director of Operations (DO) • Built-in ceiling mounted projection system • Remote controlled recessed projec- The Director of Operations shall be located adjacent tion screen or flat panel plasma screen to the Flight Operations Orderly Desk, Lobby and on • Built-in cabinets for computer, tele- an exterior wall for natural lighting where possible. vision and video storage This executive space shall include sufficient room • Television and videocassette tape or DVD player for a desk, credenza, shelving, file cabinet, four-per- • Two empty ¾” conduits for future tech- son conference table and guest seating. The Director nology infrastructure cabling shall receive a networkedARCHIVED computer, printer and all necessary power and data connections. Reduced glare artificial lighting shall also be provided. Squadron Operations Center (SOC) 21

squadron (i.e. training, operational, combat, support, etc.). Provide one desk, credenza and shelving unit, computer, LAN connection and cable television connection in each office. Large Briefing Room

The Large Briefing Room is to be used for Squadron functions and should impart an appropriate sense of importance and respect for the squadron. The briefing room will generally remain unsecured and may be located in a non-secure area of the facility; however, this large briefing room will require the ability to secure the room for specific conditions and functions.

When planning for occupancy loads, include square footage and fixed seating to accommodate the Squadron Commander, OIC, NCOIC and Flight Crew Chiefs, and eight (8) flight crews and all anticipated occupants Training Classrooms • Built-in ceiling mounted of the building in which it is located. projection system The fixed seating shall be placed on Training classrooms are to be centrally a theater style sloped floor for clear located to be shared between Squadron • Built-in cabinets for computer, sightlines to the fixed rear-projection Operations and Aircraft Maintenance television and video storage or flat-panel plasma screen. Dimmable Units and shall receive the following: lighting shall also be provided for use • Two empty conduits for future during briefings or other functions. • Moveable desks and comfortable technology infrastructure cabling seating suitable for flexible Provide a Media Technology room arrangement with sufficient seating • Minimum STC Rating of 50 linked to LAN, cable television, and to accommodate needs of the furnished with sufficient empty conduit squadron training requirements Flight Crew Chief Offices

• Space for special equipment to be The Flight Crew Chief Offices are to demonstrated for trainingARCHIVED purposes be single person private offices located adjacent to or nearby the briefing • Wiring and connections for rooms required for crewmembers communication lines, cable offices and are not required to be television, LAN service, located in the secure area of the facility. videoconferencing, and dedicated The Squadron Commander must be high-speed data connections consulted to determine the number for each person in the room of flight crew chief offices required depending on the airframe (crew size and type) and the mission of the 22 Squadron Operations & Aircraft Maintenance Unit Design Guide

to provide for future installations A separate, secure computer center All secure areas shall have single point of briefing technologies including for Mission Planning and all secure of entry with an interior corridor secure video and teleconferencing, functions should be centrally located system between rooms, cipher lock laptop computer, projection in a secure environment. Please door hardware at the vestibule and equipment, and video players. refer to Secure Computer and other areas as required for a secure Communications section and the entry system and additional alarmed Communications Center Matrices located in the document fire exits with no hardware for re- for area specific requirements. entry as required. A “hard lid” drywall A central computer and ceiling is required above the lay-in communication room, shared between Secure Areas “VALT” acoustical ceiling with a cabling the Squadron Operations and Aircraft infrastructure for secure data and Maintenance Units, should be designed The Secure Area “VALT” should communications network including to serve all non-secure aspects of be located in accordance with DoD two empty ¾” diameter conduits for the facility. This space should an standards and constructed as a SCIF future cabling. Dimmable lighting open office to accommodate two to provide a secure environment for should be provided as required on assistants with additional countertops storage and handling of classified a per room or per area basis. for computer maintenance work documents. Please refer to the DCID and shelving for storage of tools and 6-9, Physical Security Standard Several separate areas are parts. There should also be one secure for Sensitive Compartmented contained within the Secure storage room provided for storage Information Facilities and DCID Areas “VALT” including Mission of computer parts and software. 1-21, Construction Guide. A US- Planning, Mission Briefing Anticipated growth requirements Only space and a separate Foreign Rooms, Intelligence and Weapons should be considered and additional Nationals space should be provided. Center, a Weapons Task Trainer, space should be provided to satisfy future technology capability expansion.

Other items to consider when planning for the Communications Center include:

• Dedicated conduits for the local area network, cable television, communication lines, and two empty conduits from the computer center to all rooms in the facility

• Dedicated power and HVAC systems designed to accommodate the equipment and personnel loads

• Dedicated power receptaclesARCHIVED to satisfy current and future needs of the facility

• Uninterruptible power supply for servers and individual computers - an electrical generator to supply dedicated computer supply could also address this requirement Squadron Operations Center (SOC) 23

Library, and a Secure Computer and Communications Center.

• Entry into Mission Planning should be from the secure corridor. Standing-height built-in work surfaces 30” wide and 40”- 42” high, wall-mounted erasable “white boards”, storage area for maps and charts and dimmable lighting should be provided in this space.

• The Mission Briefing Rooms should be located within the secure area “VALT” adjacent to the Flight Crew Chief Offices, Intelligence and Weapons Officer, and Mission Planning. The size of the Briefing Rooms shall be designed in accordance with the aircraft type being served in the facility, and the number of ships anticipated for simultaneous mission briefing.

• Example: F-15E’s two-person crew briefing in two-ship configuration should provide due the specialized function and Other requirements for the Large space for simultaneous use by a requirements for audio-visual Briefing Room include the following: four-seat conference table and one equipment and movements around or two (1-2) persons scheduled furniture. Exceptions to this standard • Cipher lock door hardware for to provide the briefing. must be formally submitted to the Air secure entry into the briefing rooms Force to revise AFI IAW Chapter 1. Mission formations flown also impact • Built-in ceiling mounted projection briefing requirements. Missions are Please refer to the current Air system with a remote controlled typically flown in two-ship and four- Force and ACC Guidelines for recessed projection screen ship configurations, which should be specific sizes and quantities for multiplied by the crew size for the Mission Briefing Rooms for Flight • Built-in cabinets for computer, airframe being supported. The typical and Operational Crews, and for television, video cassette tape requirement for a squadron includes shared Large Briefing Rooms. player and video storage four 2-ship briefing rooms, and two 4-ship briefing rooms. PleaseARCHIVED consult Training squadrons have higher • Electric and communications with the Squadron Commander occupancy requirements to connections for plasma screen for specific requirements to verify provide space for instructors and televisions with computer hook up number and size of briefing rooms. classroom activities. Squadron to replace previously used white dry Certain aircraft and their missions mission must be verified and erase marker board with display rail require larger crews with multiple additional space must be provided functions that might be broken for instructions when squadron • Minimum ¾” diameter conduit into additional concurrent mission mission includes training functions. and cable trays (for non-secure briefings. Note that the required sizes wiring) to provide for wiring and will exceed AFI 32-1084 standards connections for communication 24 Squadron Operations & Aircraft Maintenance Unit Design Guide

shelving and storage for CD’s and other electronic file formats, secure files and reference books should be provided along with tables and chairs for approximately six persons.

• A separate Secure Computer and Communications Center for Mission Planning and all secure functions should be centrally located in a secure environment. This space should be secured using cipher lock door hardware for secure entry. Although this space is secure, the servers may service computers throughout the facility. The size of this space and computer infrastructure will be determined by the Squadron mission requirements. Please refer to the Matrices located in the document for area specific requirements. Life Support Area

The Life Support Area includes a lines, cable television, LAN service, accommodate one simulator. Superintendent Office, Work Space, videoconferencing, and dedicated One workstation for the Cockpit Shop, Life Support Equipment Storage, high-speed data connections for Trainer should be provided with Lockers, and Mobility Storage. each person in the room, including space to accommodate a CPU and This area should be located on an two empty conduits for future 17” monitors. Special electrical exterior wall for natural lighting at technology infrastructure cabling requirements will need to be the ground floor with convenient coordinated as necessary to provide access from the second floor where • Dimmable lighting electrical supply to the simulator. a multi-story facility is used. Cipher lock door hardware shall be provided • The Intelligence and Weapons Other requirements for this area at the Life Support Area entry for Center will require cipher lock door include a 36” clearance at entry security purposes. Exterior double hardware for secure entry into the for disassembles, cipher lock door doors and/or sliding doors with a space with a 16’ x 20’ Intelligence hardware for secure entry into the motion sensor should be included for Room and a 16’ x 20’ Weapons space, fiber optic cabling for secure moving equipment in and out of the Room. A Plan RoomARCHIVED should also be computer network and a self-contained Mobility Storage area. The Life Support included to accommodate two to area without LAN, dedicated HVAC Superintendent must be involved in the three (2-3) personnel, with document to accommodate servers in this space. preliminary layout of Life Support Area storage shelving and racks. No special ceiling height is required. since space requirements vary by base.

• A Weapons Task Trainer (WTT) • A Library should be located in • The Life Support Superintendent space should be located in the secure the secure area of the Squadron Office is a private administrative area of the Squadron Operations Operations facility with entry office consisting of a desk, facility with an area requirement secured with cipher lock door shelving, locking file cabinets of approximately 10’ x 10’ +/- to hardware. Custom casework and equipment with required Squadron Operations Center (SOC) 25

connections for telephone and A vault for storage of explosive and a wood/plastic laminate computer connections. munitions (weapons, flares and flare countertop locate on one 30’ wall. guns, oxygen bottles, etc.) and 9mm Provide open Work Space with weapons should be provided following Space and hookups for a washer/dryer pre and post flight counters near consultation with the base explosive should be provided in the Life Support the locker room with LAN and safety and security offices to ensure Shop with a dryer vent to the exterior phones for four (4) workstations IAW and DoD standards are met. of the building and a wall mounted in Life Support. Distance between cabinet above the washing machine the work stations and the locker • One dedicated, light and climate and dryer for detergent and supplies. rooms should be minimized. controlled night vision goggle (NVG) A double bowl stainless steel sink maintenance room (approximately with hot and cold water to include a Provide sufficient lighting throughout 30’ x 10’) shall be located on an built in emergency eye wash station the entire Life Support Shop with interior wall to prevent accidental should be provided in addition to a special attention to the equipment light infiltration. This space should mop sink within the janitor’s closet. maintenance work areas. Life include a clear, open area with an Support equipment maintenance unobstructed 25-foot line of sight for An exhaust fan and vent should areas shall have grounding/static rails NVG testing and adjustment and a also be provided in the work area for electrostatic discharge. Ensure darkroom with a light tight door and for removal of glue fumes. Technical Order 00-25-234 is reviewed “In Use” indicator light on outside for applicable guidance. Dedicated of room. Interior walls of the Night Provide a dedicated space within Life space should be provided for personal Vision Goggle (NVG) maintenance Support (approximately 20’x20’) for oxygen testing with a separate area room shall be painted with black storage of Life Support equipment for oxygen bottle maintenance. semi-glass paint with black, lockable with dehumidified/humidified air storage cabinet bins with drawers supply via the HVAC system for proper storage of the equipment. Humidified/Dehumidified air will be dependent upon geographical location.

Provide open Life Support Lockers for storage of crew flight suits, helmets and other personal flight gear. The quantity of lockers, locker unit setup and material will vary with air frame and as per Life Support Superintendent’s requirements. Sufficient space is required around the lockers for dressing during mission preparation. The Aircrew personalized lockers used for storage of their specific life support equipment must ARCHIVEDbe separate from adjacent shower and toilet area. Climate-controlled, ventilated hanging storage area for anti-exposure suits with louvered bi/tri fold doors is required. The size will be unit dependent but should be no smaller than 3’D x 8’L x 8’H for the average fighter life support shop. Units with multiple aircraft will require additional space. 26 Squadron Operations & Aircraft Maintenance Unit Design Guide

Locker Rooms Fixtures to include in each Locker Room are as follows: Locker Room facilities shall be located in proximity to the Fitness • Durable vanity counter top instead Room, Life Support Area, Ready of wall-mounted lavatories Room and near the Classrooms and Lounge. Each Locker Room should • Large, continuous mirrors include a restroom area, shower above vanity facilities and private lockers to accommodate the number of users in • Automatic sensor controls or gang the facility in accordance with ACC sink with foot pedal at lavatories standards. Separate locker facilities shall be provided for men (85%) and • Automatic flush valves on urinals Provide a climate controlled Life women (15%) using the space and Support Mobility Storage bin area use applicable codes to establish • Built-in paper towel, tissue, soap (garage) large enough to hold four (4) the quantity of fixtures. All locker dispensers, trash and sanitary pallets with a roll up door and allow room facilities shall be designed in receptacles, grab bars and coat hooks for maneuvering with a 10K fork lift. accordance and comply with applicable Typical pallets are 88”L x 108”W x codes and standards established by • Automatic sensor controls 96”H each. The roll up door and ceiling the ADA and UFAS. A minimum STC where applicable; i.e. lavatories, should be a minimum of 15’ in height rating of 45 should be used as well as toilets, soap dispensers, paper and a minimum of 20’in width. HVAC and ventilation in each area. towel dispensers, etc.

• Skid resistant ceramic tile floor finish

ARCHIVED Squadron Operations Center (SOC) 27

Mechanical and Electrical Rooms

Mechanical and Electrical Rooms should be located in secondary spaces away from the Conference areas and offices with separate electrical space and communication lines in Electrical Room. Include lockable exterior door sized to service equipment with a sloped floor to floor drain in the mechanical room. A rated enclosure should be provided for equipment using combustible fuel. Do not cool mechanical or electrical spaces and provide a STC rating of 47 to 52 depending on adjacent use.

• Floor drains in wet areas and single bowl sink, wall and base cabinets for storage, paper towel Fitness Room dispenser and trash dispenser, a nook for the anticipated number A Fitness Room shall be provided of vending machines to conceal with space sufficient for a full range the sides and rear of the machines of exercise equipment, free weights and a separate seating area. and aerobic exercise and stretching. Power and mechanical should be Ready and Heritage Rooms considered to operate the vending machines, coffee pot, microwave oven, A Ready Room and Heritage Room and refrigerator. Overhead lighting shall be located near the Lobby and for the Heritage Room should be Restrooms. This space should be located on a separate circuit from acoustically separated fromARCHIVED the Briefing the adjacent Conference Room and Rooms and Offices with fixed partitions should receive neutral finishes to and the Heritage Room separated allow for squadron decorating by from the adjacent Conference Room self help. A vinyl composition tile or with an acoustical folding partition. laminate wood strip flooring surface should also be used in this area for A separate food preparation / maximum durability and ease of care. kitchenette area should be located within this space and should include a handicap accessible counter top 28

AIRCRAFT MAINTENANCE UNIT (AMU)

ARCHIVED Aircraft Maintenance Unit (AMU) 29

AMU Orderly Desk Orderly Desk Office OIC / NCOIC Offices

The Aircraft Maintenance Unit The Orderly Desk Office should be Consult with the OIC and NCOIC (AMU) Orderly Desk should be located adjacent to the AMU Orderly to identify staffing and space located in a location visible from Desk. This area will receive modular requirements to support the specific multiple points of entry near the systems furniture for approximately mission and airframe. These executive entry. The service counter should four to six (4-6) users, providing an spaces should be located adjacent face the lobby or corridor and open office environment in this space. to the Orderly Desk and Lobby with include a raised countertop with a sufficient room for a four-person standing height writing surface of Shelving and storage space shall be conference table or guest seating. approximately 40” – 42” for “walk provided at each desk unit along Each office should receive a desk, up” use as well as a desk height staff with all equipment and required credenza, shelving, file cabinet, counter facing the customer(s). connections for printer and networked computer, and printer. Sufficient standing room should be networked computers. Reduced Data and communications cabling anticipated to accommodate group glare artificial lighting should should be built into the in walls sizes arriving during the same shift. also be provided in this area. and located appropriately for the anticipated furniture layout. Locate To accommodate personnel Administrative Support on an exterior wall, when possible, working behind the AMU Orderly for natural lighting and also provide Desk, the following items should An Administrative Support area reduced glare artificial lighting. be planned for during design: should be located adjacent to the AMU Orderly Desk area and on an exterior Section Chiefs Offices • Built-in mailboxes for each wall for natural lighting where possible. staff and flight crewmember This area shall receive enclosed offices The Section Chiefs are to be located for privacy when counseling or dealing in single person private offices in • Files and storage built-in below with sensitive personnel issues. a non-secure area of the facility front and rear counter adjacent to or nearby the Briefing Additional items to be provided in this Rooms required for crewmembers. • Copy machine to support staff area include shelving and file storage The Squadron Flight Chiefs, AFETS, and flight crewmembers space in a location to be shared by staff, TAMS, and Weapons will need to be reduced glare artificial lighting and all consulted to determine the number • Rounded corners on equipment and required connections of offices necessary for support of casework for safety for a copy machine, fax machine, the squadron mission and airframe. printer and networked computers. • Built-in data and communications Each office shall receive a desk, cabling in service desk and in credenza, shelving and computer, LAN, walls, located appropriately for and cable television connections. anticipated furniture layout.

• Electric power supply and communications capabilityARCHIVED for plasma screens to be mounted on wall behind desk in lieu of recessed computers and monitors 30 Squadron Operations & Aircraft Maintenance Unit Design Guide

AMU Shared Office Conference Room / Roll Call Aircraft Maintenance Debriefing Room The AMU Shared Offices are The Conference Room / Roll Call constructed as fully enclosed private space shall be located adjacent The Aircraft Maintenance Debriefing offices with systems furniture desk, to the Heritage Room and in a Room requires a secure location within storage, shelving, and a side chair central location within the Aircraft the facility adjacent to the entry from at each office. The shared offices Maintenance Unit. The space should the flight line for easy access by flight are intended to provide temporary accommodate approximately 20 crew and adjacent to the Aircraft swing space for office, study and persons for Roll Call. An acoustical Maintenance Unit Administrative conferences for flight and aircraft folding partition should be used Area. The size of maintenance maintenance crew not normally to separate the Conference Room debriefing rooms shall be designed in requiring an office to perform their from adjacent the Heritage Room. accordance with the aircraft type being primary function. They shall be located served in the facility, and the number near or adjacent to the Ready Room Equipment required in the Conference of shifts anticipated for simultaneous and may be located in an interior or Room includes a built-in ceiling mission briefing. A typical debriefing exterior location since natural lighting mounted projection system, wiring room shall accommodate twice is not necessary for short-term use. and connections for communication the flight and mission crew size. Reduced glare artificial lighting shall lines, cable television, LAN service, also be provided in these areas. videoconferencing, and dedicated Each Debriefing Room shall high-speed data connections receive the following: Production Supervisor for each person in the room. • Wiring and connections for The Production Supervisor should communication lines, cable be located near the Section Chief television, LAN service, Offices and have access and direct view to flight line. This single person private office does not require secure location. A desk, credenza, ������������������������������ � � � � � � � � � � shelving units, computer, LAN, ��� ������������� ������������� ������ ����� and cable television connections ������������������� ��������� ����� ������������ should be included in this space. ��� ������������ �������� �������� ������������������������� � ��������� ��������� ���� ����������������������� Technical Representative ���������� �������� ���� ����� Office (Optional) ������ ���� �����

��������������������� ��������������������� �������� ��������� ��� The optional Technical Representative ����������� ������������ Office should be located near the �������� ���� ��� Section Chief and OIC / NCOIC ������������� ����� �������

��������� ���������� offices. This single person private � ������������������� ���������� office does not require secure ������������������������ ���� ��� �������� location. A desk, credenza,ARCHIVED shelving �������� ������� ��� � ����� units, computer, LAN, and cable ���������������������������� �������� ��������� ���� ������ television connections should ������������ ������� ��������� be included in this space. ���������

��� ��������������� � ����������������� �������������� ��������� ����������������������

������������������ Aircraft Maintenance Unit (AMU) 31

videoconferencing, and dedicated connections are to be provided in anticipated growth requirements high-speed data connections this space. A secure location is not for technology capability. for each person in the room necessary; however, cipher lock door hardware is required for secure entry. COSO Support - Tool Storage • Built-in ceiling mounted and Tracking projection system Computer CAMS (IMIS) The COSO Support – Tool Storage • Two empty ¾” conduits for future A Computer CAMS (IMIS) and Tracking area shall include technology infrastructure cabling space, connected to the squadron classified and un-classified tool Computer Center, should be located storage areas, a weapons storage • Cipher lock door hardware in proximity of the Dispatch and bay, cargo netting storage next to for secure entry Scheduled Maintenance offices and Support and offices for the Chief the Maintenance Debriefing Room. Flight Support and Support TODO. Dispatch Office Classified and unclassified areas These areas are to be co-located on should also be provided within this an exterior wall with hangar bays Locate the single person, private space with an adjacent Secure Server and the flight line for direct access Dispatch Office near the Maintenance Room requiring cipher lock door when carrying heavy tools and rolling Debriefing Room and Scheduled hardware for secure entry. Shielded tool carts. Exterior access should Maintenance. This area does not fiber optic cabling must be used include a separate personnel door require secure location; however, for computer and communication and minimum of one pair 10’0” wide it will require a desk, credenza, lines in the secure LAN only. x 10’0” high sliding door with motion shelving along with computer, LAN, sensor for transportation of tools and and cable television connections Include uninterruptible power supply equipment in and out to the flight line. for servers and individual computers The floor throughout COSO Support Scheduled Maintenance with an electrical generator to supply will need to be sealed concrete with dedicated power to computers should a non-skid finish flush with hangar The Scheduled Maintenance also address this critical operational and flight line. A high level of evenly space should be located nearARCHIVED the requirement. Dedicated power and distributed artificial lighting overhead Maintenance Debriefing Room and HVAC systems should be designed lighting is required within the COSO the Dispatch Office. This open office to accommodate the equipment Support area for optimum visibility. space is for use by the required number and personnel loads with dedicated of schedulers identified to accomplish power receptacles included to satisfy • Open and Classified Parts squadron maintenance scheduling current and future electrical needs. Storage requires a 36” high open tasks. Systems furnishings should be service counter for dispensing and used to provide a desk, credenza, and The design of this space should tracking tools and parts with a shelving units for each scheduler and include room for expansion to satisfy computer inventory control system computer, LAN and cable television built into the check out counter. 32 Squadron Operations & Aircraft Maintenance Unit Design Guide

AMU Ready Room AMU Heritage Rooms

Locate the AMU Ready Room near the An AMU Heritage Room shall Lobby and Restrooms with acoustical be located adjacent to the AMU separation from the Briefing Rooms Conference in a central location. This and Offices. A handicap accessible space should be acoustically separated counter top and single bowl sink, wall from the adjacent Conference Room and base cabinets for storage, a paper with an acoustical folding partition. towel dispenser, trash dispenser(s) and a nook for the to conceal the sides A separate food preparation / and rear of the anticipated number of kitchenette area should be located vending machines should be located within this space and should include within the Ready Room. Appropriate a full size refrigerator, dishwasher, Consider moveable high-density power, mechanical and space double-bowl stainless sink, overhead storage shelving in tool storage to requirements should be allocated to and under counter cabinets, microwave reduce floor space requirements operate the vending machines, coffee oven, coffee pot, paper towel and trash and accessible part storage. Open pot, microwave oven, and refrigerator. dispenser, handicap accessible counter access storage shelving is required top and a separate seating area. in the open and classified tool A food preparation area should be storage areas and secure parts provided in an area separate from the Power and mechanical should be storage areas. Classified storage adjacent flexible seating area. Both considered to operate equipment in areas require cipher lock door areas, the Ready Room and food the food preparation equipment. hardware and a security system. preparation area, are to receive a vinyl Provide adequate internal circulation composition tile floor covering. space for rolling tool carts.

• Support Storage requires an open area for receiving deliveries, storage and distribution of mobility materials and other miscellaneous materials necessary for aircraft maintenance and support crews. A storage area for cargo netting is also required near Support Storage.

• The Mobility Storage area requires open space for packing and assembly of mobility units and an open storage space contiguous with the building exterior on the flight line for storage of mobility units. CoveredARCHIVED outdoor storage space next to Mobility is also required for GCE/equipment. Large 10’0” wide x 10’0” high sliding doors with a motion sensor are required for movement of mobility units for transportation of tools and equipment in and out to the flight line. The floor should be flush with flight line for easy movement. Aircraft Maintenance Unit (AMU) 33

Overhead lighting should be located the quantity of fixtures. All locker • Built-in paper towel, tissue, soap on a separate circuit from the room facilities shall be designed in dispensers, trash and sanitary adjacent Conference Room and accordance and comply with applicable receptacles, grab bars and coat hooks should receive neutral finishes to codes and standards established by allow for squadron decorating by the ADA and UFAS. A minimum STC • Automatic sensor controls self help. A vinyl composition tile or rating of 45 should be used as well as where applicable; i.e. lavatories, laminate wood strip flooring surface HVAC and ventilation in each area. toilets, soap dispensers, paper should also be used in this area for towel dispensers, etc. maximum durability and ease of care. Fixtures to include in each Locker Room area are as follows: • Skid resistant ceramic tile floor finish Locker Rooms • Durable vanity counter top instead • Floor drains in wet areas Locker Room facilities shall be located of wall-mounted lavatories in proximity to the Fitness Room, COSO Support, Classrooms and • Large, continuous mirrors Lounge. Each Locker Room should above vanity include a restroom area, shower facilities and private lockers to • Automatic sensor controls or gang accommodate the number of users in sink with foot pedal at lavatories the facility in accordance with ACC standards. Separate locker facilities • Automatic flush valves on urinals shall be provided for men (85%) and women (15%) using the space and use applicable codes to establish

ARCHIVED 34 Squadron Operations & Aircraft Maintenance Unit Design Guide

Training Classrooms

Training Classrooms are to be centrally located between the Squadron Operations and Aircraft Maintenance Unit for shared use. Wall partitions should have a minimum STC Rating of 50 for acoustical sound control. Furnishings and equipment required in the classrooms include the following items:

• Moveable desks and comfortable seating suitable for flexible arrangement

• Sufficient seating to accommodate needs of the squadron training requirements

• Space for demonstration of special equipment for training purposes

• Built-in ceiling mounted projection system with remote controlled recessed projection screen Laundry Room Aircraft Maintenance Hangar • Built-in cabinets for computer, television and video cassette Provide a laundry room with a single The Aircraft Maintenance Hanger player, and video storage commercial top-loading washing must be co-located with the COSO machine and dryer vented to the Support – Tools Storage, Parts and • Television and videocassette exterior. This area requires a wall- Tracking Area but adjacency to the tape player mounted cabinet above washing Squadron Operations Center for machine and dryer for detergent and heavies is not required. Maximum • Wiring and connections for supplies, a single bowl floor-mounted levels of natural lighting should be communication lines, cable fiberglass laundry sink with hot and provided with supplemental artificial television, LAN service, cold water supply, a 24” deep x 6’0” overhead lighting for increased levels videoconferencing, and dedicated long counter for folding laundry of ambient light in this space. Artificial high-speed data connections and resilient sheet flooring (ceramic lighting is required along the interior for each person in the room tile flooring optional) with a floor perimeter of the Hangar walls at ARCHIVEDdrain in the center of the room. approximately 42” above finished • Two empty ¾” conduits for future floor for increased visibility during technology infrastructure cabling. aircraft maintenance and artificial lighting recessed into hangar floor for up lighting onto aircraft during maintenance. Hangar floor requires a gray, non-skid concrete surface with red boundary lines painted on the floor as per base security requirements. Aircraft Maintenance Unit (AMU) 35

Outdoor Recreation Space • In addition to the outdoor recreation space, a covered and shielded area • Outdoor recreation space shall be outside of the hangar should be located adjacent to the Ready Room provided as a designated “Smoking and the Heritage Room on the Area”. The design must complement exterior perimeter of the building the Squadron Operations and with a secure entry into the building Aircraft Maintenance Unit Facility. using card swipe door hardware. No wooden gazebos are allowed to Benches, tables, paved walkways be used for the “Smoking Area”. and landscaping should be included within the enclosed perimeter. Secure fencing should be used as required to meet AT/FP Standards and base security requirements. Other specific requirements will vary byARCHIVED base. 36

INTERIOR FINISHES

ARCHIVED Interior Finishes 37

Interior finishes are to be developed around an understanding of the Floor Finishes elements and principles of design and how the industry works, not around personal taste. It is ACC’s policy to select long lasting, appro- When selecting floor finishes, the priate interior color schemes and finishes, avoiding “trendy” design. function of the space and type of traffic it is to receive should be Finish materials and furnishings should be selected through the use considered. Follow the Air Combat of professional design services. Selections should be based on an- Command (ACC) Architectural ticipated use, maintenance qualities, life-cycle cost, fire and other and Interior Design Standards when life safety requirements, as well as aesthetic qualities. Coordinate deciding upon which type of flooring materials, finish, color, and texture selections to complement the material would be most appropriate. overall building design and image. Select colors and finishes to ex- press professionalism, warmth, and a strong, positive image. Select There are several typical floor local materials to the greatest extent practical. Ensure that car- covering materials to be considered pets and other finish materials comply with applicable criteria. and selected from, depending on the finish required, including vinyl Understated excellence is the standard. Extravagant accessories composition tile, concrete, porcelain must be avoided. Keep selections simple to maintain continuity. tile, ceramic tile, and carpet tile.

Colors and Finishes Vinyl composition tile should be used in all AMU spaces including offices Use colors and finishes of surface materials to highlight and dif- and maintenance areas, Life Support ferentiate spaces. For example, the support areas such as rest- Shop and Locker Areas and all service, rooms and Ready Rooms require extremely durable and easy to janitorial, maintenance areas and other maintain finishes. The designer should consider environmental high-soil areas throughout the facility. and climate issues for all areas when selecting a color scheme. Benefits are ease of maintenance and durability. Use through color, Permanent materials such as toilet partitions, fixtures, laminates and ⅛”thick tile for extended wear. cabinetry should be in neutral color tones. Squadron specific colors may be used to accent non-permanent surfaces such as floor cover- Use sealed concrete in the tool and ings, wall finishes and furnishing fabrics that can easily be changed. part storage areas and the aircraft maintenance hangar. Areas with The Squadron Commander should be consulted prior to fin- sealed concrete flooring shall be ish selections to determine the function of each space and the protected during construction and required level of material maintenance and durability. cleaned of all construction marks prior to sealing. Optional epoxy coating (textured) may be used in areas for slip resistant properties. Exposed or unsealed concrete may be used in the mechanical and ARCHIVEDelectrical rooms for reduced cost. Porcelain tile can be used in high- maintenance areas where extreme durability is required, and where water and moisture are both present. Can be used for both indoor and outdoor projects in appropriate climates. If used outdoors, include a non-skid finish with abrasive flecks. 38 Squadron Operations & Aircraft Maintenance Unit Design Guide

28 oz. Static resistant carpet tile is used public corridors, conference rooms or in communication centers or areas where and upgraded finish is desired such as training classrooms, weapons requiring a high level of durability. task trainer or where electronic This type of vinyl wall covering is equipment will be used. Carpet tiles preferred for most areas of installations may also be used to create borders where a long life cycle is expected. or as an accent in public areas, such as hallways, and reception rooms, Ceramic Wall Tile is generally used or wherever a definition of space is in areas where water and moisture are required. Border may be solid color or present, such as restrooms or showers, patterned and should fill indentations for ease of maintenance and durability. such as doorways and wall recesses. Ceramic wall base should be used in conjunction with ceramic wall tile. Wall Finishes Wall paint is recommended in areas Wall construction and finishes where ease of maintenance is necessary should be selected in consideration and vinyl covering is not an option. of the function of the space and Paint used in all areas should be low potential wear. Generally, materials sheen, but not flat. Select one overall should be selected to be durable paint color to use on walls and use and provide the best appearance throughout entire area, except where possible. Typical wall finish options accent walls are desired or necessary include wall base, vinyl wall covering, to enhance the design of the space ceramic wall tile, and paint. or differentiate between areas. One color should be selected to use on all Standard vinyl wall base will be doors and/or door frames and other Ceramic Tile is most often used used throughout the facility on architectural accents, such as columns, in areas where water and moisture most projects. It provides ease of throughout the facility. Where are present, such as restrooms. This maintenance and durability. Use columns are not an architectural material provides ease of maintenance straight-footed base with carpet tile accent, but an architectural element, and durability. Ceramic tile can to allow for ease during replacement use the wall color of that area. A also be used to create borders or of carpet tiles. Ceramic wall base semi-gloss paint should be used on accentuations area in public areas, should be used in areas where ceramic wall surfaces with a primed oil based such as hallways, and reception rooms, tile is used on the floors, such as paint on all doorframes and trim for or wherever a definition of space is restrooms and shower facilities. ease of maintenance. Select accent required. Border may be solid color or paint colors to be used in areas patterned and should fill indentations There are two types ofvinyl wall where space definition is required. such as doorways and wall recesses. covering available on the market for Accent paint colors must be approved purchase. Type I vinyl wall covering by the Squadron Commander. There are two types ofcarpet tile should be used as an overall wall primarily used on commercialARCHIVED covering in low traffic areas, such as Window Treatments installations: primary/general use and private offices, where an upgraded static resistant. The primary type of finish is desired but will not require Where window treatments are carpet tile is for general use wherever a high level of durability. This type required within the facility, one carpet is required, including offices. It of wall covering is used in areas of manufacturer style and color must is easy to install, and the overall pattern installations that will not need to be used throughout to provide an easily conceals stains and traffic wear. last for many years. Type II vinyl overall uniform appearance. Provides easy replacement, storage, wall covering should be used as an and flexibility. Generally use a tweed overall wall covering in high traffic level loop with a face weight of at least areas such as lobbies, reception areas, Interior Finishes 39

Ceiling Materials

Ceiling materials and construction should be selected based on the type of area it will be used in (secure or non-secure), function of the space, durability required and the desired level of aesthetic appearance. Typical ceiling materials and construction include acoustical drop-in ceiling systems, gypsum wallboard ceilings and exposed ceiling systems. Mechanical and Electrical Finish Level Key Acoustical drop-in ceiling systems Systems Finish using a 2’x 2’ standard reveal edge tile Category Location Description and grid should be used in most areas Base standards have been established Ceiling Premium Drop-in Acoustical Tile or throughout the facility. Exceptions for plumbing, electrical, and Painted Gypsum Board Walls Paint of Vinyl Wall Covering Public would be areas such as restrooms with mechanical fixture selections. See Base Rubber, Vinyl or Tile shower facilities, Fitness and Locker Civil Engineer Flight Chief. Floor Carpet, Carpet Tile, Ceramic Tile or Rooms where high moisture levels are Porcelain Tile expected. Upgraded ceiling tiles can Furnishings Ceiling Premium Drop-in Acoustical Tile or be used in a standard grid system in Painted Gypsum Board areas such as Conference Rooms where Furnishings are an integral part of the Executive Walls Paint of Vinyl Wall Covering an enhanced professional appearance overall building design and image. Base Rubber or Vinyl is desired Gypsum wallboard ceilings Coordinate furnishing selections Floor Carpet or Carpet Tile should be used at main entrances to a for consistency of finish materials, Ceiling Premium Drop-in Acoustical Tile or facility and lobby areas for enhanced textures, and colors of architectural Painted Gypsum Board Walls Paint of Vinyl Wall Covering and professional appearance or in areas elements. Choose furniture that is Mid-Grade with high moisture concentrations durable, comfortable, and flexible. Base Rubber or Vinyl Floor Carpet Tile, Vinyl Composition Tile such as showers or locker rooms. Systems furniture is recommended (VCT) or Laminate Flooring for all administrative areas, open Gypsum wallboard ceilings should office, or shared use office spaces. Ceiling Exposed Systems / Painted Walls Paint (washable) be provided in secure areas above Workshop Signage Base Rubber or Vinyl acoustical drop-in ceilings and Floor Sealed Concrete other areas recommended by their function and ACC Standards. All interior and exterior signage must Ceiling Painted Gypsum Board or Drop-in comply with codes and standards Acoustical Tile Walls Ceramic Wall Tile and Paint Exposed ceiling systems can established by the ADA, UFAS and Restroom (washable) be used in areas such as the base specific ACC Standards. A Base Ceramic Tile Aircraft Maintenance Hangar. facility directory should be located Floor Ceramic Tile / Porcelain Tile ARCHIVEDnear the facility entrance and / or Ceiling Painted Gypsum Board or Drop-in at the core elevators. Information Acoustical Tile kiosks or boards should be used in Utility Walls Paint (washable) a handsome manner as tools for the Base Rubber of Vinyl education center and the institutions Floor Vinyl Composition Tile (VCT) with strategically located bulletin boards for staff, student, and institution use. The use of electronic information centers should also be considered. 40

SPECIAL PROJECT COSTS

ARCHIVED Special Project Costs 41

In addition to the usual cost- estimating considerations, the following special factors also should be considered when establishing initial project cost projections. Please refer to the current Air Force and ACC Guidelines for specific design requirements for each factor.

• Ergonomic and flexible furniture and equipment for classrooms and equipment maintenance areas, which may be obtained with Operation/Maintenance funds. criteria and loads due to people and large quantities of computers. • Special construction items such as public address system equipment, • SCIF construction and sprinkler systems, and special mechanical access hardware. fire suppression systems. • Storage lockers and cabinets • Telecommunications equipment, for specialized equipment, local area network, air technology parts and tools. network, compressed video, video teleconferencing, ceiling mounted • Special work surfaces for LCD projectors, wall mounted maintenance and repair televisions or plasma screens, of equipment. “smart boards”, and high quality projection screens are normallyARCHIVED • Security system to lockdown in the equipment budget. hangar to PL3 asset requirements.

• Noise transfer reduction • Sound control on flight line side of between major spaces such the facility shall be achieved through as flexible classrooms and use of sound insulation in exterior furniture systems partitions. walls, ceilings, roof and windows.

• The mechanical system has to satisfy particular zone control 42

REFERENCES

Space Relationship Diagram - Single Story Design …………………………………… 43

Space Relationship Diagram - Two Story Design ……………………………… 44 – 45

Floor Plans - Two Story Design …………………………………………………… 46 – 47

Space Matrix …………………………………………………………………………… 48 – 55

Facility Planning ……………………………………………………………………………… 56

General References …………………………………………………………………………… 58 ARCHIVED Space Relationship Diagram -

��������������������������� � � � � � � � � � �

������� ��� ���� ��������� ���� ������ ��� ������ ������� ������� ��������� ��������� �������� ������������� ������ ����� ����� ������ ������� ������������������� ������ ������������ ��������� ���� ����� ���� ��������� � ������������ ��������� ��������� ��������� ������������ ��������� ������� ����������

��������������� ��� ��������� ARCHIVED������� ���������� ��������������������� ���� ��������������� ���� �������

AIRCRAFT MAINTENANCE HANGAR ����������� �������� ���� ����� �����������

���������� ��������� SPACE RECREATION OUTDOOR ���������� ����� ���������� ������������ ���������� ��������� ����������� ��������������������������

������������ ��������� Single Story Design �������������������� ����������� ������������ ��� ������ ���������� ����������� ������ ������� ���������� �������� ����� ���� ����������� �������������� ��������� ���� ����������� ����������� ������ ��� ������������� ��� ��������� ���������� ������� ����������������� ������ ����

����� �� ������������������������ ���������������������������

������� �������� ��������� �������� �������� ����� ������������������� �������������������� ���������� ���� ������������������������ ��������� ���� ����� ������������������������ �����

������������������

������������������� References ���������������� Diagram Key ����������� 43 44 Ground Floor (AMU Facility) (AMU Floor Ground Space Relationship Diagram - Squadron Operations &Aircraft Maintenance UnitDesign Guide ARCHIVED AIRCRAFT MAINTENANCE HANGAR Two Story Design RECREATION RECREATION OUTDOOR OUTDOOR SPACE

Diagram Key

�������������������

����������������

����������� Second Story (Squad Ops Facility) Ops (Squad Story Second ARCHIVED AIRCRAFT MAINTENANCE HANGAR

Diagram Key

�������������������

����������������

����������� References 45 46 Ground Floor Plan Floor Ground Floor Plans - Squadron Operations &Aircraft Maintenance UnitDesign Guide 42 34 33 41 35 39 Two Story Design 30 37 40 43 38 ARCHIVED36 32 31 10 11 31 516 15 14 13 44 12 9 27 34 Secure Area 46 7 8 29 28 2 45 56 25 24 26 23 17 18 19 20 22 21 1 Number Room 0S 40 tair No.2tair utdoor EquipmentutdoorArea 6O 46 4Mechanic 44 8IMIS 28 0LAN 20 8Mens 38 29 0C 30 Debrief lassified OSO Support Section Support OSO C 26 9Mens 39 or Closet or 6Janit 36 42 4C 24 ommunications Room ommunications 5E 45 lectrical Room lectrical No.tair 3 torageSupport 4S 34 3S 43 2OIC 22 / NCOICAssistants / 2Suppor 32 / NCOIC/ 5Mobilit 25 3OIC 23 7IMIS 27 5L 35 aundry torageClassified 3S 33 7Mens 37 8T 18 AMS onference 0C 10 AMS T 19 6Spec 16 roduct Super roduct 4P 14 41 2Heritage 12 dmin Tech 1A 21 5AFET 15 hief Support Flight Support hief S/FSR Generation ortie eapons S 13 1C 31 7W 17 1Heritage 11 S 8 chedule Maintenancechedule O Training NC 9 Snack 6 levatorEquipment E 4 S 2 tair No.tair 1 R 5 eady Room eady levator E 3 Snack 7 V 1 estibule IMIS Name Room Server Room Server & StorageCloset& W & Locker& Room W omens Toilet omens Showeromens Classified Un-Classified Classified Flight Toilet Shower Locker Dish Storage Dish SecureDish Area y t TODO Room Galley AreaGalley al Room al References 47

Second Floor Plan

Room Room Number Name 1 Stair No. 1 2 Elevator 3 Lobby 4 Ops Desk 5 Aviation Resource Management 6 Life Support 7 Storage Work Room 8 Life Support Locker Room 42 & Exposure Suits 9 Mens Locker Room 16 17 18 19 20 21 10 Mens Shower 11 Mens Toilet 12 Womens Toilet 41 13 Womens Shower & Locker Room 22 14 Main Briefing 43 15 Main Briefing Storage 24 23 16 Stair No. 3 44 17 Mech Room 14 18 Flight Commander D Flight 40 45 19 Flight Commander C Flight 5 25 20 Flight Commander B Flight 21 Flight Commander A Flight 46 15 4 26 22 Scheduling 1213 23 Heritage Room 39 47 24 Heritage Galley Area 3 25 Communications Room 26 ADO 11 2 27 DO 38 27 28 Section Commander 1 29 Commander Support Staff 48 10 30 Commander 28 49 8 6 31 Conference Room 37 32 Mobility 33 Mechanical Room 36 9 29 34 Stair No.2 35 Main Classified Briefing 50 7 36 Briefing No. 6 37 Briefing No. 5 38 Briefing No. 4 30 39 Weapons Office 35 34 ARCHIVED33 32 31 40 Weapons Task Trainer 41 Intelligence / Weapons 42 Mission and Tactical Planning 43 SAR Entry 44 Toilet Secure Area 45 Galley 46 Intelligence Office 47 Briefing / Debriefing No. 3 48 Briefing / Debriefing No. 2 49 Briefing / Debriefing No. 1 50 Secure Communications Room 48 Squadron Operations & Aircraft Maintenance Unit Design Guide

Space Matrix * Additional spaces and square footage may be required as per squadron mission requirements Notes Raised counter; Raised(4) persons; counter; File below; Storage space behind counter for radio Open Office for (4-6) persons electricalFloor mounted boxes for (4) persons Conference for (4) persons Conference to Squadron Commander Consult determine number of offices and sizes necessary; number depends on the airframe and mission of the squadron for furniture Systems multiple users (number dependent on airframe and mission of the storage squadron), and shelving and storage furniture, Systems shelving for two persons Movable desks for flexibility; Built-in for storage television, computer and video Minimumstorage; STC Rating of 50 20 space for Provide approximately persons Theatre-style sloped fixed seating; dimmable lighting Special Equipment

Plasma screens, copy Plasma screens, machine; one computer facing lobby / corridor on countertop or recessed within the countertop use “walk-up” surface for and Printer networked computers Mobile tables, Dry erase boards and Printer networked computer and Printer networked computer Desk, Television, Computer, Shelving Credenza, Computer Computer Videoconferencing, television, individual high-speed connections, ceiling projection mounted system, videotape player, recessed controlled remote projection screen Television, Cable Computer, videoconferencing, high-speed dedicated data connections, ceiling projection mounted system projection/ rear Fixed plasma secure screen, videoconferencing, television, video players

Phone

         

Cipher Lock Cipher

CATV

        

Detection

trusion trusion In

Nipernet

          Sipernet   ecutive Public inishes Working Level of Level Executive Ex Executive Executive F Mid-Grade Mid-Grade Mid-Grade Preferred Preferred Adjacency

ps Desk eady eady Room entral location entral

raining raining Classrooms Working O R C between Squad Ops and AMU location T exterior wall exterior wall Area Required Area 341 Ops Lobby; Desk; 341 Ops Lobby; Desk; 316 Ops Desk 207 Near entry; central 15sf/ 15sf/ 1000 90sf/ 90sf/ 120sf/ person person person person person See Notes Near Briefing Rooms Mid-Grade    Work Work Station Station Type Station     

Office Private Private

eas Ar Unoccupied Unoccupied ARCHIVED   * Briefing Room Station Station or Space Required Non-Secure Non-Secure Areas DeskOperations Orderly Flight Squadron Squadron Operations Facility General Space Requirements Management Resource Aviation Scheduling Area Squadron Commander Director of Operations Chief Offices Crew Flight Offices Shared Crew Flight Office Training NCO Classrooms Training Rooms Conference Main References 49 Notes Climate controlled space (garage) controlled Climate enough large for four (4) pallets with a up roll door; pallets 88”L are x 108”W x 96”; allow additional space for maneuvering a 10K fork lift This area MUST area This the be from separate and showers adjacent toilet area Size will be unit dependent but should be no smaller than 3’D x 8’L x 8’H for life the fighter average support Units shop. with multiple additional will space aircraft require Superintendent needs Superintendent to be involved in planning; on locate floor; ground dehumidified / humidified air supply as required desk,locking file shelving, cabinets Open work space with and pre post 4 flight counters; workstations; space for dedicated personal oxygen light testing; and dedicated climiatic night vision contolled goggle (NVG) (approximately room maintenance 30’x10’) and cabinets storage with view lane wall; 25’ on drawers one 30’ on located wall interior to prevent light infiltration Nook for vending machines; separate seating from area food preparation flexible area; seating arrangement; breifing from acoustical separation and rooms offices; vinyl floor finish or wood stip laminate flooring Galley vinyl floor Area; finish or wood stip laminate flooring; Heritage neutral Room finishes; to receive acoustical folding partition between Heritage and Conference adjacent Room Special Equipment

Roll up door and ceiling height minimum 15”H x 20”W Open for lockers flight crew suits, helmet and other personal flight gear a controlled, climate Provide hanging storage ventilated for area anti-exposure suits bi/tri with fold louvered doors. Washer/dryer space (dryer Washer/dryer to outside); vented double bowl stainless steel sink with mop hot/cold water; area sink in janitor’s Television Computer, for explosive Vault office with administrative Private munitions, weapons, lithium battery storage, and flares guns; flare black lockable for storage night vision goggles (NVG); eye wash station; exhaust fan with in vent for work area glue fumes; use darkroom light on indicator outside of with room light tight door machines, coffee Vending oven, pot, microwave paper towel refrigerator, trash dispenser, dispenser, handicap counter accessible top and single bowl sink, wall and base cabinets for storage In Galley - Area coffee oven, pot, microwave paper towel refrigerator, trash dispenser, dispenser, handicap counter accessible top and single bowl sink, wall and base cabinets for storage

Phone

   

Cipher Lock Cipher

 

CATV

  

Detection

trusion trusion In

Nipernet

   Sipernet Utility Utility Utility Utility inishes Level of Level F Workshop Mid-Grade Mid-Grade Preferred Preferred Adjacency

from pilot from equipment room (locker) storage Lobby, RestroomsLobby, Mid-Grade Restrooms Area Required Area 571 337 100 493 Minimal distance  Work Work Station Station Type Station 

Office Private Private

eas Ar Unoccupied Unoccupied  ARCHIVED     * Station Station or Space Required Life Support Area Ready Ready Room Exposure Suits Exposure Mobility Storage Squadron Squadron Operations Facility General Space Requirements Office Superintendent Space Work Equipment & Support Shop Lockers Equipment Crew Heritage Rooms 50 Squadron Operations & Aircraft Maintenance Unit Design Guide

Space Matrix * Additional spaces and square footage may be required as per squadron mission requirements Notes Space Space sufficient for full range of equipment; additional space exercise and exercise aerobic for weights, free stretching and Include shower restrooms facilities, 85%men and 15% women; tile skid ceramic flooring; resistant floor drains in minimum wet areas; of rating 45 STC SCIF; single point Secure environment drywall lid” of “hard entry security; ceiling lay-in acoustical; above secure data and network; communications dimmable US- lighting as required; Nationals Only space space; Foreign with air Size in Force accordance typeGuidelines, aircraft and ACC served and number of ships (2-ship or 4-ship); for consult Commander quantitiy; built-in provide storage television and videos; for computer, dimmable lighting corridor; standing secure from Enter height build-in work surfaces 30” high; dimmable wide and 40” for lighting; area storage maps and charts Weapons x 20’; Room Intelligence 16’ x 20’; Plans Rooms Room for 16’ 2-3 personnel with document storage shelving and racks fiber Trainer; for workstation Cockpit optic cabling for network; secure for servers; 36” HVAC dedicated at clearance entry for disassembles; special for electrical requirements simulator Special Equipment

Private lockers; automatic automatic lockers; Private or sensor gang controls sink with foot pedal lavatory; sensor automatic controls on soap toilets, dispensers, paper dispensers, etc. towel Cipher lock door hardware at vestibule Videoconferencing; individual high-speed connections; ceiling projection mounted system; videotape player; recessed controlled remote projection plasma screen; television with screens hook-up computer erasable mounted Wall white boards Television Computer, SimulatorFlight +/- for one one simulator; x 10’ 10’

Phone

   

Cipher Lock Cipher

   

CATV

  

Detection

trusion trusion

In    

Nipernet Sipernet         inishes Level of Level Executive F Mid-Grade Mid-Grade Mid-Grade Mid-Grade Mid-Grade Utility / Restroom Preferred Preferred Adjacency

Weapons Office, Weapons Trainer Task Weapons Life Support, Ready Room, Classrooms Intel/Weapons Officer, Officer, Intel/Weapons Chief Crew Flight Offices Area Required Area 142 279 348 Office, Intelligence 588 See Notes Mission Planning,  Work Work Station Station Type Station 

Office Private Private

eas Ar Unoccupied Unoccupied  ARCHIVED      * Station Station or Space Required ission Briefing Fitness Fitness Room Squadron Squadron Operations Facility General Space Requirements Rooms Locker Secure Areas ”VALT” Secure Areas M Mission Planning Officer Weapons / Intelligence Center Weapons and Intelligence Trainer Task Weapons References 51 Notes Non-secure communications, communications, Non-secure open and power dedicated HVAC, office for (2) persons and work for counter equipment , repair LAN, cable and lines communications Custom casework for storage of cd’s for casework of storage Custom cd’s and electronic files; shelving and for storage files secure and reference books; table and chairs for 6 persons Size and as infrastructure per Squadron Mission requirements Size Size shall be based on building code entrysecure provide requirements; exterior; from finishes interior shall also meet of standards all applicable codes Size shall be based on building code and load requirements Size shall be based on building code and load requirements Size shall be based on building code and occupancy load requirements Special Equipment

Dedicated un-interruptable Dedicated un-interruptable supply power with generator Door hardware to be Doorbarrier hardware and free with compliant codes established by the and ADA UFAS

Phone

Cipher Lock Cipher

   

CATV

Detection

trusion trusion In

Nipernet Sipernet  Utility Utility Utility Public Public inishes Level of Level F Restroom Mid-Grade Preferred Preferred Adjacency

between Squad Ops and AMU between Squad Ops and AMU Area Required Area 77 location Central 231 location Central See Notes See Notes See Notes See Notes   Work Work Station Station Type Station

Office Private Private

eas Ar Unoccupied Unoccupied  ARCHIVED     * Station Station or Space Required Library Restrooms Squadron Squadron Operations Facility General Space Requirements Center (Secure) Communications General Building Spaces Vestibule Elevator / Stairs Elevator Mechanical and Electrical Rooms / ServerCommunications Room (non-secure) 52 Squadron Operations & Aircraft Maintenance Unit Design Guide

Space Matrix * Additional spaces and square footage may be required as per squadron mission requirements Notes Raised counter; Raised(4) persons; counter; File below Storage Openmodular office environment; 4-6 systems for approximately artificialpersons; glare reduced lighting shelving Shared and file storage; artificialglare reduced lighting with Consult OIC and NCOIC to identify staffing and space to support requirements the specific mission and airframe;space executive with for room a 4-person conference table and guest seating; reduced artificialglare lighting; built-in data and cabling communication in walls to Weapons and TAMS AFETS, determine number of offices necessary shelving Must and access have direct view to flight line 20 space for Provide approximately persons; acoustical folding partition space adjacent from to separate Heritage Room; lighting overhead on Heritage from circuit Room separate high open service high counter; 36” level of distributed evenly artificial light; exterior - acces personnel door high sliding door with and motion 10’ no-skidsealed concrete floor sensor, flush with hangar and flightline, for tool circulation rolling internal carts, offices for SupportChief Flight Classified Storage and TODO, Support space Special Equipment

Plasma screens, Copy Copy Plasma screens, machine” and Printer networked Shelving, computers, Storage Printer, machine, Fax, Copy Networked computers and Printer networked Desk, computers, Credenza, File cabinet Shelving, Television Computer, Chiefs, Squadron Flight Consult PrinterComputer, Desk, Television, Computer, Credenza Shelving, and storage furniture, Systems Television Computer, Television Computer, Desk, credenza shelves, Television Computer, Desk, credenza shelves, television, Cable Computer, Videoconferencing, Desk, credenza shelves, Dedicated high-speed data connections, Ceiling System Projection mounted inventory control Computer system

Phone

          

Cipher Lock Cipher

CATV

      

Detection

trusion trusion In

Nipernet

           Sipernet  inishes Level of Level Executive F Workshop Mid-Grade Mid-Grade Mid-Grade Mid-Grade Mid-Grade Preferred Preferred Adjacency

rderly Deskrderly MU Orderly MU DeskOrderly Mid-Grade eady eady Room

A O R Debriefing, SchedulingDebriefing, Analysis Heritage Room, central location within AMU Exterior Wall Exterior bays bays and flightline OIC / Offices NCOIC Area Required Area 151 Section Chief Offices, 178 Dispatch Debriefing, Mid-Grade 186 Section Chief Offices Mid-Grade 207 Near entry; central Public 1933 Exterior hangar wall, 90sf/ 90sf/ 90sf/ person person person See Notes Desk,Orderly Lobby, See Notes Near Briefing Rooms Executive   Work Work Station Station Type Station        

Office Private Private

eas Ar Unoccupied Unoccupied ARCHIVED  * Station Station or Space Required Non-Secure Non-Secure Areas AMU DeskOrderly Aircraft Aircraft Maintenance Facility General Space Requirements DeskOrderly Office SupportAdministrative OIC / Offices NCOIC Section Chief Office AMU Offices Shared SupervisorProduction Office Respresentative Technical (Optional) Dispatch Scheduled Maintenance Room / Roll Conference Call and Storage SupportCOSO Tool - Tracking References 53 Notes Include restrooms and Include shower restrooms facilities, 85%men and 15% women; tile skid ceramic flooring; resistant floor drains in minimum wet areas; of rating 45” STC shelving, Secure open storage, access shelving, with Parts Storage open shelving Open for deliveries, area receiving and storage distribution of mobility and materials other miscellaneous near area storage materials; Support for netting Storage cargo Open space for assembly packing, and of storage mobility units; large sliding glass doors with motion nextstorage sensor; to covered Mobility for GCE/equipment office for Private two persons with desk and file storage office for Private two persons with desk and file storage Nook for vending machines, counter top and single bowl sink, wall and base cabinets for separate storage, seating from area food preparation flexible area, seating arrangement, briefing from acoustical separation and rooms offices, vinyl floor finish or wood strip laminate flooring top Handicap counter accessible and single bowl sink; wall and base cabinets for vinyl storage; floor finish flooring cabinet above Wall-mounted washing machine for supply storage; long for counter deep by 6’ 24” folding laundry; sheet resilient flooring with floor drain in center of room Special Equipment

Private lockers; automatic automatic lockers; Private or sensor gang controls sink with foot pedal lavatory; sensor automatic controls on soap toilets, dispensers, paper dispensers towel Cipher Lock door Cipher Lock hardware high-density Moveable storage Networked Computer, Television Networked Computer, Television machines, coffee Vending oven, pot, microwave paper towel refrigerator, trash dispenser dispenser, oven, pot, microwave Coffee paper towel refrigerator, trash dispenser dispenser, Single top- commercial loading washing machine and dryer; Single bowl, fiberglass floor-mounted laundry sink

Phone

      

Cipher Lock Cipher

CATV

     

Detection

trusion trusion In

Nipernet

     Sipernet inishes Level of Level F Workshop Workshop Workshop Mid-Grade Utility / Restroom Preferred Preferred Adjacency

Room Support Area Required Area 214 176 187 AMU Ready Room Mid-Grade 158 Chief Flight COSO, 164 TODOSupport COSO, Mid-Grade 100 Rooms Locker Fitness, Utility 1352 restrooms Lobby, Mid-Grade 1859 Ready Classrooms, Work Work Station Station Type Station  

Office Private Private

eas Ar Unoccupied Unoccupied  ARCHIVED      * Station Station or Space Required ocker Roomsocker Parts Storage (Open and Parts Storage Classified) Laundry Room Aircraft Aircraft Maintenance Facility General Space Requirements Support Storage Mobility Storage SupportChief Flight TODO Support AMU Ready Room Snack Bar and Storage L 54 Squadron Operations & Aircraft Maintenance Unit Design Guide

Space Matrix * Additional spaces and square footage may be required as per squadron mission requirements Notes lexible lexible space to be by customized secure entry/access secure the into building using swipe card door hardware; enclose perimeter with secure Standards fencing as per AT/FP and base no security requirements; wooden to gazebos allowed be used for the smoking designated area F typeto aircraft Size in and accordance mission; maximum provide levels of lighting natural by supplemented artificial lighting; overhead artificial lighting along perimeter interior of finished above Hangar walls at 42”” floor hangar and into floor recessed visibility;for maintenance increased floor; non-skid red concrete gray, boundary lines on floor as per AT/FP standards each command; Adjacent each Galley command; Adjacent with top and Area counter double bowl sink, wall and base cabinets for food separate preparation storage, seating flexible from area, area acoustical seating arrangement, folding partition from separation / vinyl Roll rooms, Call Conference floor finish or wood strip laminate flooring; neutral finishes to allow for by self decorating help; overhead lighting from on circuit separate / Roll room Call Conference adjacent Special Equipment

enches, enches, tables and walkways landscaping; Paved

Vending machines, coffee Vending oven, pot, microwave dishwasher, refrigerator, trash paper dispenser, towel dispenser B

Phone

 

Cipher Lock Cipher

CATV

Detection

trusion trusion In

Nipernet

  Sipernet  N/A inishes Level of Level F Mid-Grade Preferred Preferred Adjacency

Ready Ready Room, exterior perimeter of building Area Required Area 617 See Notes Support COSO Workshop Work Work Station Station Type Station

Office Private Private

eas Ar Unoccupied Unoccupied  ARCHIVED  * Station Station or Space Required Heritage Room Aircraft Aircraft Maintenance Facility General Space Requirements Outdoor Space Recreation Aircraft Maintenance Hangar Maintenance Aircraft References 55 Notes Non-secure communications, communications, Non-secure open and power dedicated HVAC, office for (2) persons and work for counter equipment , repair LAN, cable and lines communications Size in accordance with aircraft Size in accordance type served and number of shifts (typical for accommodation twice the flight and mision crew). Consult for Commander quantity. Connect to computer squadron unclassified center; (556sf)area and classified (268 area sf) with adjacent server (89sf);room Classified Area Entry must be with secured a cipher lock system; or access reader card shielded fiber optic cabling; room to expand Size Size shall be based on building code entrysecure provide requirements; exterior; from finishes interior shall also meet of standards all applicable codes Size shall be based on building code and load requirements Size shall be based on building code and load requirements Size shall be based on building code and occupancy load requirements Special Equipment

Dedicated un-interruptable Dedicated un-interruptable supply power with generator Videoconferencing, Videoconferencing, individual high-speed connections, ceiling projection mounted system, plasma television with screens computer cable television, hook-up, with white boards marker display rail Dedicated and power HVAC systems for equipment and personnel loads; dedicated to power satisfy future and need; current un- supply power interruptible for servers and computers Door hardware to be Doorbarrier hardware and free with compliant codes established by the and ADA UFAS

Phone

 Cipher Lock Cipher

See Notes

CATV

  

Detection

trusion trusion In

Nipernet Sipernet     Utility Utility Utility Public Public inishes Level of Level Executive F Restroom Preferred Preferred Adjacency

between Squad Ops and AMU Dispatch, Dispatch, Scheduled Maintenance, De-Maintenance Briefing Room Aircraft Maintenance Maintenance Aircraft Unit Administrative Area Area Required Area 231 location Central 913 See Notes) See See Notes Line, to Flight Adjacent See Notes See Notes See Notes See Notes (  Work Work Station Station Type Station

Office Private Private

eas Ar Unoccupied Unoccupied  ARCHIVED     * Station Station or Space Required Secure Secure Areas De-BriefingMaintenance Aircraft & Room Conference Restrooms Aircraft Aircraft Maintenance Facility General Space Requirements CAMS (IMIS) Computer General Building Spaces Vestibule Elevator / Stairs Elevator Mechanical and Electrical Rooms / ServerCommunications Room (non-secure) 56 Squadron Operations & Aircraft Maintenance Unit Design Guide

Facility Planning Concept Designing for Facilities

Context Plan

ARCHIVED

Site Plan References 57

South Elevation

ARCHIVED

Floor Plan 58 Squadron Operations & Aircraft Maintenance Unit Design Guide

General References

This list is not meant to be all-inclusive. Architects, engineers, plan- ADA American with Disabilities Act ners, and designers should check with their Design Agent or gov- ernment project manager for the latest guidelines. Current Air Base Engineering Standards Force publications may be found at http://afpubs.hq.af.mil. (if available)

Base Architectural Standards Local Building Codes AFI Air Force National Fire Protection Association National Electric Codes 32-1024 Instruction for Standard Facility Requirements NFPA 13 Standard for AFPD Air Force Sprinkler Systems AFI Air Force 32-10 Pamphlet for NFPA 72 Standard for Fire Installations and Facilities 32-1032 Instruction for Planning Protection Signaling Systems and Programming Appropriated AFJMAN Air Force Joint Funded Maintenance, Repair NFPA 72E Standard for 32-1008 Manual for and Construction Projects Automatic Fire Detectors

Installation Design AFI Air Force NFPA 101 Life Safety Code

AFI Air Force 32-1084 Facility Requirements Military Handbook 1008c

23-110V1, Part 1, Section 4C, AFI Air Force Sign 32-1097 NFPA 101 Life Safety Code Storage and Handling of Lithium Standards Pamphlet Batteries, Paragraph 4.37. AFMAN 91-201 Explosives AFI Air Force Safety Standard AFI Air Force 32-7062 Instruction for Air Force AFOSHSTD 91-56 Walking 32-1021 Instruction for Planning Comprehensive Planning Surfaces, Guarding Floor and Wall and Programming of Facility Construction Projects UFC 4-010-01 Department of Defense Openings and Holes, Fixed Industrial Antiterrorism Standards for Buildings Stairs and Portable and Fixed Ladders AFI Air Force Air Force Installation Force AFHOSHSTD 91-20 Vehicle 32-1022 Instruction for Planning Protection Guide Maintenance Shops and Programming Non-appropriated Fund Facility Construction Projects ACCI Air Combat T.O. 15X-1-1 Technical Manual, Maintenance Instructions, AFI Air Force ARCHIVED32-1054 Command Instruction Oxygen Equipment dated for Exterior Signs 32-1023 Instruction for Design 15 September 1999 with revision 5 and Construction Standards and Air Combat Command Commander’s on 1 April 2002. Published by US Execution of Facility Construction Guide to Facilities Standards Government Printing Office. (for researching the minimum space ACC Supplement to AFI 32- UFAS Uniform Federal, requirements for a Life Support Shop) 1023 (ACC Architectural and Accessibility Standards Interior Design Standards) ARCHIVED ARCHIVED