INTRODUCTION
BRONNS FERRY NUCLEAR PLANT 10CFR50 APPENDIX R SECTION III.G EVALUATION
The modifications made during the recoverv from the March 22, 1975, fire were intended to provide protection azainst the loss of more than one division of safetv equipment in the event of a fire. The modifications included nhysical moving of certain electrical conduits, the application of a fire resistant cable coating, and the addition of extensive fire protection systems. These changes and the plant's original separation criteria for Class 1E circuits as outlined in our FSAR are consistent with the philosophy outlined in section IXI.G.1. However, to be able to respond fully to section III.G and Fire Protection Rule Generic Letter 81-12, TVA performed a detailed analysis to compare the Browns Ferry safe shutdown systems and their associated .circuits for compliance with section III.G. TVA contends that Browns Ferry', upon completion of identifed modifications, will satisfy the intent of the requirements of section III.G. The safe shutdown analvsis and the manner in which it was performed is discussed in Attachment 1. The required shutdown equipment and time frames in which it is required is identified in Attachment 2. An analysis of circuits which can become associated with safe shutdown circuits is presented in Attachment '3. Attachments 0 and 5 discuss the electrical modifications, administrative controls, and fire protection modifications required to bring Browns Ferry into compliance with section III.G. A discussion of the impact on safety due to proposed modifications is presented in Attachment 6. Attachment 7 identifies the exceptions to the requirements of section XII.G and'rovides justification for each exemption requested. The request for additional information made by the NRC in Enclosures 1 and 2 of,'eneric'Letter 81-12 is presented in Attachment 8. l . Attachment 9 is the implementation schedule for modifications described in Attachments 0 and 5.
E52165.01
ATTACHMENT 1
SAFE SHUTDOWN ANALYSIS
l-l E5216 5.01 1.0 SCOPE
The following document summarizes the definitions, limiting safety conditions, separation criteria, requirements and assumptions, and procedure used to perform the Browns Ferry Nuclear Plant safe shutdown analysis considering a fire as the initiating event.
2 .0 DEFINITIONS
2 1 Associated Circuits — Those safety-related and non-saf ety- related circuits that are not directly required to perform a safe shutdown function but have either:
1. A common power source with a shutdown circuit where the power source is not electrically protected from the shutdown circuit by coordinated circuit breakers, fuses or similar devices, or
2. A connection to circuits of equipment whose spurious operation will adversely affect the shutdown capability, or
3 . A common enclosure, cable tray, conduit, panel, or junction box with a shutdown circuit and: a. Are not electrically protected from the shutdown circuit by circuit breakers, fuses, or similar devices, or b. Will allow propagation of the fire into the common enclosure.
2.2 Postulated fire —A fire that is assumed to occur in a specific area of the plant. The origin of the fire and the combustible materials involved are not defined.
2.3 Safe shutdown — The process of bringing all three reactors from . power operation to hot shutdown and then cold shutdown. 2.4 Hot shutdown — A stable plant condition where all three reactors are subcritical and have average coolant temperatures above 212'F.
2.5 Cold shutdown —A stable plant condition where all three reactors are subcritical and have average coolant temperatures below 212'F.
2.6 Fire area —An area completely enclosed by fire-rated barriers.
2.7 Fire zone —A subdivision of a fire area.
1-2 E52165.01 3.0 LIMITING SAFETY CONDITIONS
The .safe shutdown analysis determines the plant modifications required to ensure the following damage limits are not exceeded as a result of a single postulated fire: 3.1 Electrical cables and associated circuits of a minimum set of equipment necessary to achieve hot shutdown must be maintained free of fire damage. 3.2 Electrical cables and associated circuits of equipment necessary to achieve cold shutdown may be damaged. However, the damage must be limited so that a minimum set of equipment can be repaired or made operable within 72 hours using onsite capability. 3.3 Electrical circuits of equipment necessary for mitigation of design basis events may be damaged.
4.0 SEPARATION CRITERIA
The following means of protecting the safe shutdown capability from postulated fires are acceptable: 4.1 Separation of cables and associated circuits of redundant safe shutdown equipment by a fire barrier having a 3-hour rating, or 4.2 Separation of cables and associated circuits of redundant safe shutdown equipment by a horizontal distance of more than 20 feet if there are no intervening combustibles and if fixe detectors and an automatic fire suppression system are installed in the area, or 4.3 Separation of cables and associated circuits of redundant safe shutdown equipment by a fire barrier having a 1-hour rating if ~ fire detectors and an automatic fire suppression system are installed in the area around the barrier.
5.0 REQUIREMENTS AND ASSUMPTIONS
5.1 The only unacceptable consequence of a fire is the inability to safely achieve and maintain safe shutdown conditions ~ 5.2 All three units are operating at 100 percent power when a fire is postulated.
5.3 A postulated fire is not considered inside Primary Containment since it is inerted with nitrogen during power operations.
5.4 A postulated fire is assumed to occur in any other area containing electrical circuits necessary for safe shutdown, whether or not the area contains permanent combustible materials.
1-3 E52165.01 5.5 The zone of influence of a postulated fire is bounded by the largest area defined by the separation criteria of section 4.0.
5.6 Safe shutdown circuits and associated circuits are assumed to be damaged if.-they are in the zone of influence of a postulated fire.
5.7 No failures other than those directly attributable to a postulated fire will be considered.
5.8 No design basis events are considered concurrent with a postulated fire., 5.9 Equipment required for safe shutdown during a postulated fire must be capable of being powered by onsite emergency power systems.
5.10 Equipment required for safe shutdown during a postulated fire need not be designed to meet seismic Category I criteria, single failure criteria, or other design basis event criteria.
5.11 Cables whose exposed surfaces are coated with flamemastic or are enclosed in conduits are not considered an intervening combustible for the purposed of meeting the separation criteria , of section III.G.2.
5.12 For the first hour of a postulated fire, manual actions by operations personnel are limited to manipulation of controls located in the Main Control Room or Backup Control Stations.
5.13 After the first hour of a postulated fire, manual actions by operations personnel may include manipulation of equipment located anywhere in the plant.
5.14 During a post fire shutdown, the fission product boundary integrity must be maintained (e.g., no fuel clad damage, no rupture of any primary coolant boundary, no r upture of the containment boundary).
6.0 PROCEDURE FOR PERFORMING ANALYSIS
6.1 Determine the functions required to achieve and maintain safe plant shutdown. 6.2 Produce shutdown logic diagrams that define minimum systems that can perform required safe shutdown functions and satisfy section 4.0.
1-4 , E52165.01 8' 6.3 Group specific rooms or buildings into fire areas where a postulated fire requires the availability of similar safe shutdown equipment. 6.4 For each fire area defined in 6.3, identify one ox more paths through the Shutdown Logic Diagrams that will satisfy each required shutdown function. Identify one path if the required systems are located outside the fire area under consideration. If a function could not be satisfied with equipment located outside the fire area, identify redundant paths consisting of widely separated equipment inside the fire area. 6.5 Develop functional criteria that define the required equipment for the shutdown paths identified in 6.4. 6.6 Identify power and control cables for:
1. The equipment identified in 6.5 that is directly involved in performing required safe shutdown functions, or 2. Associated cables that are not adequately isolated from the safe'shutdown cable.
6.7 Mark the routing of the cables defined in 6.6 on cable tray or conduit drawings in such a manner that one can distinguish between redundant circuits. 6.8 Identify all interactions of redundant shutdown equipment whose circuits did not meet the separation criteria of section 4.0.
1 6.9 Determine whether the redundant shutdown circuit interactions are to be:
1. Corrected by cable rerouting, or 2 . Corrected by separation of redundant circuits by fire rated barriers, or 3. Corrected by addition of protective devices, or 4. Corrected by relocation or addition of equipment, or 5. Justified by analysis, or 6. Any combination of the above. 6.10 Determine if additional fire suppression and detection systems were needed in the redundant shutdown circuit interaction areas.
1-5 E52165. Ol ATTACHMENT 2
FUNCTIONAL CRXTERIA
2-1 E52165.01 I. SCOPE The functions required for safe shutdown of Browns Ferry Nuclear Plant are identified in shutdown logic diagrams, figures I.a, I.b, and I.c. The methods of accomplishing these functions and the timing of the required operations are addressed in this criteria. For the purpose of the safe shutdown analysis, the plant is divided into the following fire areas: Reactor building/diesel generator building (RB/DGB)—Includes all areas of the diesel generator buildings and reactor buildings with the exception of the shutdown board rooms.
Shutdown board rooms (SBRs) —Each SBR is considered separately, figures 1.d through l.k. Control building (CB)—Includes all areas of the control building with the exception of the battery board rooms.
Battery board rooms (BBR)—Includes the battery and battery board rooms 1, 2, and 3, figures 1.1 through l.n. Turbine building/intake pumping station (TB/IPB)—Includes all areas of the turbine building and the intake pumping station. Existing compartmentation was utilized in the selection of these fire areas. Each area, with the exception of the BBRs, is enclosed by an equivalent 3-hour rated fire barrier. The BBRs are enclosed by 1-1/2- hour rated fire barriers.
The fire area boundaries were selected so that comparable actions are needed to safely shut the plant down for a fire anywhere in the area. II. CRITERIA All times identified in the following discussions are measured from the initiation of fire shutdown procedures and not from the start of the fire. Operating personnel are expected to use normal procedures to bring the plant to a safe shutdown condition when a fire is detected. The equipment outlined in this document will be available for use following emergency procedures if operating personnel determine that the normal procedures cannot be completed due to fire induced equipment failures.
2-2 E52165.01 A. ,Time Less Than One Hour (Figure I.a)
1 . Reactor Coolant System (RCS) Integrity
a. RB/DGB, SBR, BBR, or TB/IPS Fixe
Control of a minimum set of valves is required to maintain RCS integrity during a fire. Table II.A.l lists the individual valves, their mode of operation and their required position. By ensuring the RCS will be isolated, other system requirements can be minimized.
b. CB Fire A minimum of one valve per process line (i.e., inboard or outboard) as listed in Table II.A.l must be controlled at the backup control stations 'with a fire in the CB.
2. Reactor Pressure Vessel (RPV) Rater Inventory Control
a. RPV Depressurization System Figure I.A indicates that an air supply is requixed for (S/R) valves during the first hour. This airthe'afety/relief supply will consist'of the ADS accumulators or the Dxywell Control Aix receivers. This is a passive system, therefore, no other consideration is required.
(1) RB/DGB, TB/IPS, or BBR Fire
A minimum of four S/R valves per unit must be capable of being operated from the main control room (HCR) and no S/R valves may spuriously operate except at their pressure setpoints. See table II.A.2.a for a listing of the valves xequired and their respective mode of operation.
(2) CB Fire
Back-up contxol must be provided for a minimum of four S/R valves per unit with the remaining valves being adequately isolated from the CB to prevent spurious actuation. Refer to table II.A.2.a for the specific valves required.
(3) SBR Fire
Each SBR is considered as a separate fire area as shown in figures I.d-I.k. Board rooms A, C, and E are divided into two separate fire zones as follows: One zone will encompass the panel 25-32 and the closest distribution board (labled Al, Cl,
2-3 E52165.01 and El respectfully in the SBR analysis) while the other zone will include the whole room excluding panel 25-32 (labled A2, C2, and E2 respectfully in the SBR analysis). Refer to figure I.d, I.f, and I.h for the above descriptions.
The requirements for the S/R valves for all board rooms except Al, Cl, and El are the same as those discussed in section II.A.2 .a.(1) . For board rooms Al, Cl, and El, it is possible that some S/R valves can spuriously operate. By having a maximum of seven S/R manual control circuits in one fire area, the assumption is made that no more than four of the S/R valves will operate simultaneously. Figure II.A.2.a.(3) illustrates RPV water level as a function of time with four S/R valves operating to depressurize the vessel and one Core Spray System and one RHR system automatically making up vessel inventory. It is evident that more than adequate inventory makeup is available to reflood the core and then keep the core covered. Therefore, a maximum of seven S/R valve manual control circuits may be grouped together provided a minimum of one, Core Spray System and one RHR System (2 pumps) will function automatically at their respective setpoints for the affected unit. See table II.A.2.a for specific valves required. b. Residual Heat Removal (RHR) System
RB/DGB Fire
One RHR pump and its associated valves must be available at the backup control stations for the fire affected unit. The minimum amount of equipment is justified by ensuring RCS integrity (sections II.A.l.a and II.A.2.a.(1)). The pumps to be used will be pumps 1B and 2D for a unit 1 fire; pumps 1A and 2C for a unit 2 fire; and pump 3C for a unit 3 fire. Table IX.A.2.b.(1) lists the requirements for each unit. The use of one RHR pump in conjunction with manual actuation of four S/R valves to depressurize the vessel as an inventory makeup method is equivalent of one RHR pump operating with the Automatic Depressurization System.
(2) TB/IPS or BBR Fire Since'CS Integrity will be ensured for fires in these areas (see sections II.A.l.a and II.A.2.a.(1)), manual operation and minimal system requirements are justified. Table II.A.2.b.(2) lists the equipment required and their respective mode of operation with control from the MCR.
2-4 E52165.01 (3) CB Fire
The equipment listed in table II.A.2.b.(l) must be operable for a fire in the CB. This will provide a minimum of one RHR system (one pump) per unit to meet RPV inventory requirements.
(4) SBR Fire
For all SBRs except Al, Cl, and El, the requirements are identical to those given in section II.A.2.b.(2).
For board rooms Al, Cl, and El, an RHR System (2 pumps) is required to operate automatically in the unit affected by the spurious S/R valve operation. For those units unaffected by the S/R valves, the requirements are the same as those given in section IX.A.2.b.(2). Refer to table II.A.2.b.(3) for automatic RHR system requirements . c. Core Spray (CS) System
(1) RB/DGB, BBR, TB/IPS or CB Fire
There are no requirements for the CS system for a fire in these areas.
(2) SBRs Fire Areas
For a fire in board room Al, Cl, or El, one CS system is required to operate automatically as shown in table II.A.2.c.(2) for the unit affected by the spurious S/R valves (i.e., Al-unit 1, Cl-unit 2, El-unit 3) ~ For other SBR fire areas see the requirements for CS system in section II.A.2.c.(1). d. High Pressure Core Injection (HPCI) System
(1) RB/DGB, TB/IPS, CB, BBR, or SBR Fire
There are no requirements for the HPCI System for a fire in these areas. e. Reactor Core Isolation Cooling (RCIC) System
(1) RB/DGS, TB/IPS, CB, BBR, or SBR Fire
There are no requirements for the RCIC System for these fire areas.
2-5 E52165.01 f. Emergency Equipment Cooling Water (EECW) System
RB/DGS, TB/IPS, or SBR Fire
A minimum of two RHRSW pumps, which service the EECW system in the same header (i.e., north or south) are required to start automatically and no more than one valve to close in the respective header being relied upon. The requirements for the system are listed in table II.A.2.f.
(2) CB Fire
A minimum of two pumps and three of its associated valves are required to have back-up control isolation. See table II.A.2.f for equipment required. 3. Reactivity Control
a. Reactor Protection System (RPS)
RB/DGB or TB/IPS An automatic scram signal is required if one of the following transients occur and off-site power is available: (a) RPV Low Mater Level or, (b) High RPV Pressure. A manual scram signal is also required for the above fire areas. Once a scram signal is generated, the signal must also reach the Control Rod Drive Hydraulic (CRDH) system to ensure a successful sc ram ~
SBR or BBR Fire
A fire in any of these areas would not defeat the ability of the RPs to generate a scram signal. A loss of power to the logic would be the only effect a fire would have on the RPs for the areas given, and such a loss would generate a scram signal. Therefore, the RPs meets the criteria for these areas with no further analysis.
(3) CB Fire Area
A reactor scram will be obtained by opening the power disconnect to the RPs at the Battery Board. The RPs will generate a scram signal upon loss of power. The RPs Panels are grounded and all connections to power are fused. Therefore, no hot shorts to maintain power are credible and a scram signal can be generated.
2-6 E52165.01 b. Control Rod Drive Hydraulic (CRDH) System
(1) RB/DGB Fire
A signal to the CRDH system to scram will be assured's discussed in the RPs description for the same fire area. The CRDH system will lose power which will cause the control rods to insert. This will limit our concern to hot shorts. No power for the control rod drive solenoid valves will be available except for hot shorts from other systems located in the same area. Therefore, it is highly unlikely that any more than a few will fail to insert due to a fire. These few will then be assured to insert by requiring one set of the back-up scram solenoids to operate, and venting any control air and allowing the remaining rods to insert due to loss of control air. See table II.A.3.b for the CRDH system requirements.
(2) TB/IPS, CB, SBR, or BBR Fire
The RPs description (section II.A.3.a) assures a scram signal will be received at the CRDH system panels. These panels are located solely in the RB area and will be unaffected by a fire in any of these areas. " 4. Process Instrumentation
a. RB/DGB, TB/XPS, CB, SBR, or BBR Fire
The instrumentation required fox all fire areas is (a) RPV Water Level (-155" to +55"), and (b) RPV Pressure (0 to 1500 lb/in g). These variables will provide sufficient information to allow the operator to take all manual actions required. RPV water level and pressure will allow the operator to maintain adequate inventory (see figure I.A). Reactivity contxol and RCS integrity are being assured (sections II.A.l and II.A.3). Therefore, these variables will be adequate to ensure a hot shutdown condition in the first hour of the event.
The minimum instrumentation loops needed to monitor the variables for each fire area are listed in table IX.a.4. For a CB fire the indicators for these variables are required on the backup control panels. Indicators for a fire in any other area are required in the MCR.
2-7 E52165.01 5. Auxiliary Power
a. RB/DGB Pire
Power must be available to the minimum equipment required for a fire in this area. The power requirements are * d xvid e d ino,into three, sections. Sections (1), (2), and ( ) list the minimum distribution boards required for a unit 1 unit 2, and unit 3 fire respectfully.
(1) Unit 1 Fixe
The following distribution boards are required to have power available to accommodate the RHR system circuits associated with the boards:
Unit 1 Untt 2 Unit 3
4-kV Shutdown Bd C 4-kV Shutdown Bd 9 4-kV Shutdown Bd 3EB 480-V Shutdown Bd 1B 480-V Shutdown Bd 2B 480-V Shutdown Bd 3A 480-V RMOV Bd 1B 480-V RMOV Bd 2B 480-V RMOV Bd 3A 480-V RMOV Bd 1E 480-V RMOV Bd 2E 480-V RMOV Bd 3D
The above requirements also hold true for a fare an the units 1 and 2 diesel generator building (DGB). Other distribution boards must be available for the equipment being relied upon.
(2) Unit 2 Pire
The fo llowing distribution boards are required to have power avax'1 abl e to accommodate the RHR system circuits associated with the boards:
Unit 1 Unit 2 Unit 3
4-kV Shutdown Bd A 4-kY Shutdown Bd B 4-kV Shutdown Bd 3EC 480-V Shutdown Bd 1A 480-V Shutdown Bd 2A 480-V Shutdown Bd 3B 480-V RMOV Bd 1A 480-V RMOV Bd 2A 480-V RMOV Bd 3B 480-V RMOV Bd 1D 480-V RMOV Bd 29 480-V RMOV Bd 3E
Other distribution boards must be available for the equipment being relied upon.
K (3) Unit 3 Pire
The following distribution boards axe required to have power available to accommodate the RHR system circuits associated with the boards:
2-8 E52165.01 Unit 1 Unit 2 Unit 3
4-kV Shutdown Bd A 4-kV Shutdown Bd D 4 kV Shutdown Bd 3EB 480-V Shutdown Bd lA 480-7 Shutdown Bd 2B 480-V Shutdown Bd 3A 480-V RHOV Bd 1A 480-V RMOV Bd 2B 480-V RMOV Bd 3A 480-V RMOV Bd 1D 480-V RMOV Bd 2E 480-V RMOV Bd 3D
Other distribution boards must be available for the e uipment being relied upon. In the unit 3 DGB, any combination may be used provided the minimum equipment has the power required.
b. CB, TB/IPS, BBR, or SBR Fire
Adequate powex must be available to supply the equipment being relied upon for the above fire areas.
3.2 Time Greater Than One Hour (Figure X.B)
1. Reactor Coolant System (RCS) Xntegrity,
a. RB/DGB, SBR, BBR, or TB/IPS Fire
The requirements for equipment are the same as those identified in section XI.A.l.a.
b. CB Fire
The requirements fox equipment are the same as those identified in section II.A.I.a.
2. Reactor Pressuxe Vessel (RPV) Mater Inventory Control
a. RPV Depressurization System
The control air for the S/R valves is still required after one hour. The air supply is required to be capable of manual manipulation.
(1) RB/DGB, TB/IPS, or BBR Fire
The requirements for equipment are the same as those identified in section IX.A.2 .a.(I) with the exception that only one S/R valve is required to be operable.
(2) CB Fire
The requirements for equipment are the same as those identified in section II.A.2.a.(2) with the exception that only one S/R valve is required to be operable.
2-9 E5216 5.01 (3) SBR Fire
The requirements for equipment are the same as those identified in section II.A.2.a.(3) with the exception that only one S/R valve is required to be operable. b. Residual Heat Removal (RHR) System
See section II.B.5 for additional RHR requirements.
(1) RB/DGB Fire
The requirements for equipment are the same as those identified in section II.A.2.b.(l) with the exception being that FCV-74-52 or FCV-74-66 must be capable of being throttled. h
(2) TB/IPS or BBR Fire
The requirements for equipment are the same as those identified in section II.A.2.b.(2) with the exception that FCV-74-52 or FCV-74-66 must be capable of being throttled.
(3) CB Fire
The requirements for equipment are the same as those identified in section II.A.2.b.(3) with the exception that FCV-74-52 or FCV-74-66 must be capable of being throttled.
(4) SBR Fire
The requirements are the same as those listed in section II.B.2.b.(2). c. Emergency Equipment Cooling Water (EECW) System
(1) RB/DGB, TB/IPS, BBR, CB, or SBR Fire
A minimum of two RHRSW pumps in the same EECW header are required to remain operable and three of its associated valves remain open for all of these areas. See table II.A'.2.f for the equipment required. d. Residual Heat Removal Service Water (RHRSW) System
See section II.B.5.b for RHRSW requirements .
E52165.01 0 3. Reactivity Control
a. RB/DGB Fire
The method for assuring the control rods remain fullful y inserted will be to isolate the contxol air supply to the control rod flow solenoid valves.
b. BBR, CB, TB/XPS or SBR Fire Th fl olenoid valves will remain deenergxzed (safe state) for the above fire areas to preclude wx.thdx w the control rods. 4. Process Instrumentation
a. RB/DGB, TB/IPS, CB, SBR, or BBR Fire
The requirements for equz.pment are sti'll the same as those identified in section II.A.4.a.
5. Decay Heat Removal
a. Residual Heat Removal (RHR) System
(1) RB/DGB, TB/IPS, CB, BBR, or SBR Fire
One RHR pump and its associated valves axe required to be operable in the torus cooling mode. This pump ma be the same pump being used for RPV Water Inventory Control. Figure II.B.5.a il1us traatese the pool heat-up as a function of time with pool cooling begxnnxngb a t 1 hour. The following considerations have been analyzed to ensure one pump is sufficienient ox torusorus cooling:~ (a) RHR Net Positive Suction ead {NPSH), {b) Thermal Stresses on Torus andnd AttachAttached Piping, and (c) Adequate Suppression of Steam. See table II.B.5.a for valve position requirement.
b. RHR Service Mater (RHRSM) System
(1) RB/DGB, TB/IPS, CB, BBR, or SBR Fixe
A one RHRSM. pump per corresponding RHR pump must'fbe operable after one hour. The valves associated with the RHRSM pump must be in their required position to accommodate the flow path or the RHRSW system. See table II.B.5.b for system requirements.
2-11 E5216 5.01 c. Essential Equipment Cooling Water (EECW) System
(1) RB/DGB, TB/IPS, CB, SBR, or BBR Fire
See section XI.B.2.c for EECW requirements. 6. Shutdown Contxol Area Environmental Control
a. Heating, Ventilating, and Air Conditioning (HVAC) System
(1) RB/DGB, TB/IPS, SBR, or BBR Fire
For a fire in these areas the HCR HVAC must be capable of operation via local or remote control after 1 hour. The equipment required is listed in table II.B.6.a.(1).
(2) CB Fire
The equipment listed in table IX.B.6 .a.(2) is xequired to have adequate isolation from the CB fire area.
7. Auxiliary Power
a. RB Fire
The requirements are the same as those specified in section IX.A.5.a for the respective units fire areas with one addition being that either 4-kV Shutdown Board A or C be energized.
b. CB,TB/XPS, SBR, or BBR Fire
See section XI.A.5 .b for the requirement in the above fire areas. c. Time Before Seventy Two Hours (Figure I.c)
1. Reactor Coolant System (RCS) Integrity
a. RB/DGB, CB, SBR, TB/IPS, or BBR Fire
The requirements are the same as those given in section II.A.l.a with exception to the RPV head vent valves and shutdown cooling suction valves. These valves are not required once RPV pressure and RPV temperature are below the setpoints given on figure I.c.
2-12 E52165.01
0 2. Heat Removal and Xnventory Control
a. Residual Heat Removal (RHR) System
(1) RB/DGB, TB/IPS, CB, SBR, or BBR Fire
Once RPV pressure is below 75 lb/in2g, the RHR system being used can be placed in the shutdown cooling mode of operation. This is done by repositioning of some RHR valves . See table XI.C.2 .a fox the RHR system requirements.
b. RHR Service Rater (RHRSM) System
(1) RB/DGB, TB/IPS, CB, BBR, or SBR Fixe See section II.B.5.b for system requirements for the above fire areas. c. Essential Equipment Cooling Rater (EEL) System
(1) RB/DGB, TB/IPS, CB, SBR, or BBR Fire
See section II.B.2.c for EECW requirements. 3. Reactivity Control
a. RB Fire
See section II.B.3 .a for reactivity control requirements.
b. BBR, CB, TB/IPS, or SBR Fixe
See section IX.B.3.b for reactivity control requirements. 4. Process Instrumentation
a. RB/DGB, TB/IPS, CB, SBR, ox BBR Fire
See section IX.B.4.a for instrumentation requirements.
. 5. Shutdown Control Area Environmental Control
a. Heating, Ventilating, and Air Conditioning (HVAC) System
(1) RB/DGB, TB/IPS, SBR, ox BBR Fixe
See section II.B.6 .a.(l) for system requirements .
(2) CB Fire
See section II.B.6.b.(1) for system requirements.
2-13 E52165.01 6. Auxiliary Power
a. RB/DGB, TB/IPS, CB, BBR, or SBR Fire A minimum amount of distribution boards are required to supply power to the necessary equipment.
III. CONCLVSION
By ensuring the minimum equipment in section II will be available for the respective fire areas, a stable hot and cold shutdown can be accomplished regardless of a fire in any area of the plant.
2-14 E5216 5.01 II 1 Pl srh Oper«leon
fDa Otters
l. e I RFS h ala RID pie»seal I proc,cse -„rA Volecgs r
Strsna SsIL C-I.< S goal OA 4>1P.Q+ (Inalaolcl I-.tilt m RPY CRO D.I a~r'real 4qia flaasa a OR litle 1'c RPV M,lar IhaL ~ -ur tracer A,O nol ~ ~ ~Sea 2 RPV Pqnsr Rtatl ar sfS Prcoaara Con'lrc 1
RRR Stela«a I IlSIV'a Clat RNR Sta r SI Io«c CS +Ice« CS t CI or t Rr I ll flr 2 C~ I Itr~)c %. Ctr~ 'fat fsC e f'C HJE aal 0 I
on Rase\or r------a~Sac naia h C»lael Solar 401CSr Ioas Pressers RPV Iolg"lsI I I l. h)cqoaic p««~e ae«al lse. aces/able f R RPV afolcr 1«rerslorq I I tet«ape«o«1 iaa I'4 arplitowa rsl aallooan co'Lls CloLr-op Ca»i.ol ( 'ss 2, I t taatll too'l«ES aenavselagca 4a ~ ~ ~ aaa' 1. toison also«ll '41ln «sallaiea 2O «a'.earl«a. .I Ih~osl i«el;ol»n ~ 'l a coca«a ra1aa\ ac o)el«ala ~ ~ a«11 >o«oollec cnl bee«E is art'ala!'Ie 4 ~color oel:~. APPENDIX R asgO h. 011aar «solar 'Iaaranloral a»oA olo sane',1 ~ rl aat llHIXG..L:D...... g.rc«er Coo lcncq Orceoi~ Irate«EDaaa hl . A~ S11IIIDQWN of lira« cll lo e«oll 1ea aaCDc ~ > I ~ LOGIC c air.l 14 inoc«l«S .I sLa trV. 11.1 SS 1la asaooaal R'CV Tee r otlt BAOMII5 I'callr tria I ac rlalU REII < 1." c Oa c.. Carr 0lfftk4 SIH APR.SlD 1 I igure I.a r Rsrlcsul f~~ Al RPV Y~c RIR't k,(t ~i firer ~ 1 («ev
5ee eel ~ C Arel t(<4 Co ital Beh.up RVCu V.4S l RIIOI Zeal Dr5<<% Rev«a'«r« feu Reev« Cer«I«el He» {'A Ra(Cll Velec4 It< Re~Vie«(y 5LI I» C lr OII Octal 'Cecal Cea(rol Area E~r:r (( I(e»( am RPV Pre< RPV P {All'R RI(R I R«R h a 5t« t I IevRP (Ier f ty« LPCI P44 t QPV ««(<4< T«rce4 g HRlV< Cl TLv CLAW OR t(OVf5< 1 Vhc Rl(R prie( tgu:tck tet leeua ec<«( r«<( RC5 (ee Il«c Sa«e«c purep l«<«g ucch ter t(PY Irllc ft' IIt ~rt3 cr ge«ec~b<«r«l Cenlral. Tl«la u«'Al 4. 4 vc Are()L:g ~ (prep<:ale valves (e t a a : I a I >a«I> Q lke „.. RPl>»qrt>l'r Katf Pate««1 RPC Rre Cowl 8««L Ca«l al l>J rl g er ( Ari«Me Pr« ~ a>tc Pa \ 1 1 4 15>t 4 lr«l P~a.g P«Q > 4$ >s ~I ~ alt >>sent «C44 D» Rst Creel j r al~J Resell«i>~ ll«g'alar«~ ss> ~ ~l>al oR Swig Cwlt lie«4 la 4«a i«<+ k ILL K «. Pan C««l,al lr«l 1 QR {g el >CLl RCD Ts le«r'tQ eggs 1 RPt Ta»g +At'f Ti»~ «'Zl«a hi«Pl tll)1X 8, UNLIT,.i=A :RlU lOO>>IN ) LOGiC %0MtlS ffRR'f NUCLLAR PLAHT Date« P».A4ral,M Dr>lltR ssD S Figure I.c I»s>>t>MK Cl»>lkltt> 'Z Z ' ~ ' + ~ pi. ~ gl /pl I I FAtRT I 1 I 7'-0" I I ~ ~ 4 lI' 2'-3" I 0 /9" l I I p9 I /2" BOARD ZOON A EC GZ/Z5 F/GOjvE 1.cf 2-2 pygmy v'TDA'D O 8 A ~ (~ l~ S O Ir) Z-6 VAR'/ES VARIES~ z BOAS 'ROANB EZ 593.0 ~R/4 b ~ q' ' ~ '- L h "4 6 BOARD h'OON C El 6Z/.ZS FSSuiZ2:5 2-Z 0 ~ ~ I C -'2 a <0 a O ~o g4 ~, e Ct) 6~2 2'-6" 3'-6'" ~ A ~ ~ 4C sr /8"' zs'~ z BOARD ZOON D EL 893.0 F/Elf'y l l "t I l sv. j b 0 p4VEL Z5-9Z-8 VAR/ES l I I 2- g g» I I 1 I I 20" 'b d. ROON BOARD E'L 681.25 F%URE I. A 2-2 2. '20 RZ/ 25'-0" ' P ~ I ~, ~ .'b l. L'' NEIGES I 5'-6 ~rl ~ ~ l ' b ~ . b 'b '. BOARO ROON F EL 599.0 FlGLIRE 2 i 223 ~~REAcfoR BLDG- Uiv/T3 BL 593'-0" ~ ~ ~ ~, /6'-0' COiYS7 dP&VIA5S(Sarah'OTE3) Hi l i i 4/AYSflfDA'DSEA 4(60 Y SIITOiV8jP SEC ~i ii70iVT l 8' '!3PII.Sa 82 -Z8'-2" . -8 ~4'~IZPh'E-S 8 2-'Z.Z8'-Z'e t l orsero WIDOW s/77K'ORN SEA 80848E SLIDING IIRE'OoR LADDER TO &HE'RGB'CY EXIT W ROOF COVZREO NnPI/0/.E IN FI.OOR Herc/ LERNER Oa~ie ro EL Sar.5 0tl SZI4Yb5 Fl)Pf PRIV .C >' 'F C r / IO II 9 IO l2 8 FRONT 250Y BTRY BD I ~250V BTRY CHGR FRONT 250V BTRY 2 8 l2 250V BTRY CHGRS 9 ll IO I p I 0 SATTERY aoAED zoon z EL 593.0 F/BOA'E Z m RIB / 1// " ~/ 7// 2 5 4 250V BTRY BD 5 FRONT ll 9 CQ (g 12 8. 250V,BTRY CHGR ' k~, ''F ~ ~ e 5 ~ ~ p ~ gATPggy 80AFi'J ROOPP 3. Zl 563.0 FIGURE 2: n BFH RPP R STUDY 4 "GRV V I- g) >o Q, CV Ol a tQ I lJ CL lD $7% F Q7 LD C V) I - )gV. 5 ao aa JZO . 160 200 240 280 320 T I HE t SEC ) BFN APP R STUDY '4 SRV TORU$ ~O ll N cb lu Q ~G ~ tL ~ W~ G3 v'. CA > Q cK U7 }—n ~o Q Ol 6000 12000 18000 24000 30000 36000 42000 48000 Ttt1E l SEC) TABLE II.A.I Reactor Coolant System Integrity E ui ment Unit Mode of 0 eration Position PCV-69-16 1,2,3 Manual Closed FCV-69-17. Manual Closed Fcv-69-1 Manual Closed PCV-69-2 Manual Closed FCV-74-47 1,2,3 Stay as is Closed PCV-74-48 1,2,3 Stay as is Closed FCV-1-55 1,2,3 Stay as is Closed PCV-1-56 Stay as is Closed FCV-1-14 1,2,3 Manual/Automaticl Closed PCV-1-15 Manual/Automaticl Closed PCV-,1-26 1,2,3 Manual/Automaticl Closed Fcv-1-27 1,2,3 Manual/Automaticl Closed J Fcv-1-37 152>3 Manual/Automatic Closed PCV-1-38 Manual/Automaticl Closed FCV-1-51 1,2,3 Manual/Automaticl Closed PCV-1-52 Manual/Automaticl Closed Fcv-3-98 1,2,3 Manual, Closed Pcv-3-99 Manual Closed Pcv-43-13 1,2,3 Manual Closed FCV-43-14 Manual Closed Notes: RB and TB 1 ~ Valve must close automatically upon RPV low water for the fire areas. 2-31 E52165.01 TABLE II.A.2.a Reactor Pressure Vessel Water Inventory Control S/R Valve Requirements E ui ment Unit Mode of 0 eration Position PCV-1-4 1,2,3 Manual Non-ADS Operable PCV-1-18 1,2 Manual Non-ADS Operable PCV-1-23 1,2,3 Manual Non-ADS Operable PCV-1-41 1,2 Manual Non-ADS Operable PCV-1-42 1$ 2$ 3 Manual Non-ADS Operable PCV-1-179 Manual Non-ADS Operable ...'CV-1-180 Manual Non-ADS Operable .'.PCV-1-30',' '' 3 Manual Non-ADS Operable PCV-1-31 3 Manual Non-ADS Operable PCV-1-5 1,2,3 Manual ADS Operable PCV-1-19 Manual ADS Operable PCV-1-22 Manual ADS Operable PCV-1-30 1,2 Manual ADS Operable PCV-1-31 1,2 Manual ADS Operable PCV-1-34 1,2,3 Manual ADS Operable PCV-1-18 3 Manual ADS Operable PCV-1-41 3 Manual ADS Operable 2-32 E52165.01 TABLE II.A.2.b.(1) Reactor Pressure Vessel Water Inventory Control RHR Requirements E ui ment Unit Mode of 0 eration S s. Position II RHR Pump A or C 2 j3 Manual I Running RHR Pump Cooler A or C1 2 j3 Automatic I Running FCV-74-1 or 121 2j3 Manual I Open PCV-74-96 or 971 2 j3 Manual Closed PCV-74-.7 2 j3 Manual I Open/Close PCV-74-100 2 j3 Manual- I Closed PCV-74-60 or 61 2 j3 Manual ,I Closed PCV-74-77 or 78 2 j3 Manual I Closed PCV-78-61 or 62 2j3 Manual I Closed PCV-74-58 2 j3 Manual I Closed FCV-74-59 2 j3 Manual I Closed FCV-74-52 2 j3 Manual I Open PCV-74-53 2 j3 Manual I Open PCV-68-79 2 j3 Manual I Closed RHR Pump B or D 1 Manual II Running RHR Room Cooler B or Dl 1 Automatic II Running FCV-74-24 or 351 1 Manual II Open PCV 74 98 or 991,2 1 Manual II Closed PCV-74-30 1 Manual II Open/Close PCV-74-101 1 Manual II Closed PCV-74-74 or 75 1 Manual II Closed PCV-74-77 or 78 1 Manual II Closed FCV-78-61 or 62 1 Manual II Closed PCV-74"73 1 Manual II Closed FCV-74-66 1 Manual II Open PCV-74-'67 1 Manual II Open FCV"68"3 1 Manual II Closed PCV-74-72 1 Manual II Closed Notes: 1. The only piece of equipment required is the one associated with the operating pump. The equipment is listed respectfully (i.e. FCV-74-1 is A FCV-74-12 is required for pump required for pump while C).'. Backup control is not required provided unit 2 has backup control for valves 96 and 97. 2-33 TABLE II.A.2.b.(2) Reactor Pressure Vessel Water Inventory Control RHR Requirements E ui ment Unit Mode of 0 eration S s. Position RHR Pump A or C 1~2s3 Manual I Running RHR Pump Cooler A or Cl Automatic I Running FCV-74-1 or 121 Manual I Open Closed FCV-74-96 or 971 2 $ 3 Manual I FCV-74-7 1,2,3 Automatic I Open/Close FCV-74-100 2 j3 Manual I Closed FCV-74-60 1,2,3 Manual I Closed ~ FCV-74-77 or 78 2 $ 3 Manual I Closed 'CV-78-61 or 62 2 $ 3 Manual I Closed FCV-74-58 1,2,3 Manual I Closed FCV-74-59 Manual I Closed FCV-74-52 Manual I Open FCV-74-53 Manual I Open FCV-68-79 Manual I Closed RHR Pump B or D 1,2,3 Manual II Running RHR Pump Cooler B or Dl Automatic II Running ;'CV-74-24,or-351 Manual II Open FCV-74-98 or 991 1,2 Manual II Closed FCV-74-30 1,2,3 Automatic II Open/Close FCV-74-101 1,2 Manual II Closed FCV-74-74 1,2,3 Manual II Closed FCV-74"77 or 78 1 Manual II Closed FCV-78-61 or 62 1 Manual II Closed FCV-74-72 1,2,3 Manual II Closed FCV«74-73 Manual II Closed FCV-74-66 Manual II Open FCV-74"67 Manual II Open FCV-68"3 Manual II Closed Notes: 1 ~ The only piece of equipment required is the one associated with the operating pump. The equipment is listed respectfully (i.e. FCV-74-1 is required for pump A while FCV-74-12 is required for pump C).'-34 E52165.01 TABLE II.A.2.b.(3) Reactor pressure Vessel Water Inventory Control RHR Requirements E ui ment Unit Mode of 0 eration S s. Position RHR Pump A and C 1,2,3 Automat ic I Running RHR Pump Cooler A and C Automatic I Running PCV-74«1'nd 12 Stay as is I Open PCV-74-96 3 as is I Closed , and 97 2$ Stay 'FCV-74-7 1$ 2$ 3 Automatic I Open/Close FCV-74-100 2 $ 3 Stay as is I Closed PCV-74-60 or 61 1,2,3 Stay as is I Closed PCV-74-77 or 78 2 $ 3 Stay as is I Closed PCV-78-61 or 62 2 $ 3 Stay as is I Closed FCV-74-58 1,2,3 Stay is is I Closed FCV-74-59 Stay as is I Closed PCV-74-52 Stay as is I Open PCV-74-53 Automatic I Open PCV-68-79 Automatic I Closed RHR Pump B and D 1,2,3 Automatic II Running RHR Pump Cooler B and D Automatic II Running FCV-74-24 and 35 Stay as is II Open PCV-74"98 and 99 1,2 Stay as is II Closed FCV-74-30 1,2,3 Automatic II Open/Close PCV-74-101 1,2 Stay as is II Closed PCV-74-74 or 75 1,2,3 Stay as is II Closed PCV-74-77 or 78 1 Stay as is II Closed PCV-78-61 or 62 1 Stay as is II Closed FCV-74"72 1,2,3 Stay as is II Closed .PCV-74-73 Stay as is II Closed 'FCV-74"66 Stay as is II Open PCV-74-67 Automatic II Open PCV"68-3 Automatic II Closed 2-35 E52165.01 TABLE II.A.2.c.(2) Reactor Pressure Vessel Water Inventory Control CS Requirements E ui ment Unit Mode of 0 eration S s. Position CS Pump A and C 152>3 Automatic I Running CS Room Cooler (A 6 C) Automatic I Running FCV-75-2 Stay as is I Open FCV-75-11 Stay as is I Open FCV-75-9 Automatic I Open/Close FCV-75-23 Stay as is I Open FCV-75-25 Automatic I Open FCV-75-22 1,2,3 Stay as is I Closed CS Pump B and D 1,2,3 Automatic II Running " CS Room Cooler (B & D) Automatic II Running PCV-75-30 Stay as is II Open FCV-75-39 Stay as is II Open FCV-75-37 Automatic II Open/Close FCV-75-51 1~2,3 Stay as is II Open PCV-75-53 1,2,3 Automatic II Open PCV-75-50 1,2,3 Stay as is II Closed . 2-36 TABLE II.A.2.f Reactor Pressure Vessel Mater Inventory Contxol EECW Requirements 'E ui ment Unit Mode of 0 erationl Hdx. Position RHRSW Pump A3 and C3 0 Automatic North Running FCV-67-13 0 Stay as is North Open FCV-67-17 1 Stay as is North Open FCV-67-21 2 Stay as is North Open FCV-67-25 3 Stay as is North Open RHRSM Pump B3 and D3, 0 Automatic South Running FCV-67-14 0 Stay as's South Open FCV-67-18 1 Stay as is South Open FCV-67-22 Stay as is South Open FCV-67-26 3 Stay as is South Open Notes: I. For a CB fire, the mode of operation is manual for backup control. 2-37 E52165.01 TABLE EZ.A.3.b Reactivity Control CRDH Requirements ,E ui ment. Uni.t Mode of 0 eration Position PSV-85-35A 1,2,3 Automatic Energized PSV-85-70A 1,2,3 Automatic Energized PSV-85-35B 1,2,3 Automatic Energized PSV-85-70B Automatic Energized 2-38 E52165.01 TABLE II.A.4 Vital Instrument Loops 1 ~ General Area Fire Reactor Vessel Level LITS-3-46A and LI-3-46A or LITS-3-46B and LI-3-,46B Reactor Vessel Pressure PT-3-207, PI-3-207, PX-3-207, and LM-3-206 or PT-3-61, PX-3-61, PI-3-61, LM-3-60, and XS-3-53 2 ~ Control Ba Fire Reactor Vessel Level LITS-3-58B and LI-3-58A Reactor Vessel Pressure PT«3-79, PX-3-79, and PI«3-79 2-39 E52165.01 TABLE II.B.5.a Decay Heat Removal'HR Requirements E ui ment Unit Mode of 0 eration S s. Position RHR Pump A or C 1$ 2$ 3 Manual I Running RHR Pump Cooler A or Cl Manual I Running PCV-74-1 or 121 Manual I Open FCV-74"96 or 971 2 $ 3 Manual I Closed Pcv-74-7 1,2,3 Manual I , Open/Close PCV-74-100 2 $ 3 Manual I Closed ,', ....Fcv-74-60 1,2,3 Manual I Closed FCV-74-77 or 78 2 $ 3 Manual I Closed FCV-78-61 or 62 2 $ 3 Manual I Closed Pcv-74-58 1,2,3 Manual I Closed Pcv-74-59 Manual- I Open PCV-74-52 or 53 Manual I Closed Fcv-74-57 Manual I Open RHR Pump B or D 1,2,3 Manual II Running RHR Pump Cooler B or Dl Manual II Running Manual Open , FCV-74-24 or 351 II 'I PCV-74-98 or 991 1$ Manual Closed Pcv-74-30 2',2,3 Manual II Open/Close Fcv-74-101 f 1,2 Manual II Closed Pcv-74-74 1,2,3 Manual II Closed PCV-74-77 or- 78; 1 Manual II Closed FCV-78-61 or 62 1 Manual II Closed FCV-74-73 1,2,3 Manual II Open PCV-74-66 or 67 Manual II Closed Pcv-74-71 Manual II Open Pcv-74-72 Manual II Closed Notes: 1 ~ .The only piece of equipment required is the one associated with the operating pump. The equipment is listed respectfully (i.e. FCV-74-1 is required for pump A while FCV-74-12 is required for pump C).'-40 E52165.01 1 ~ TABLE II.B.5.b Decay Heat Removal RHRSW Requirements E ui ment Unit Mode of 0 eration Position RHRSW Pump A2 0 Manual Running RHRSW Pump Al 0 Manual Running FCV-23-34 1,2,3 Manual Open RHRSW.Pump C2 0 Manual Running RHRSW Pump Cl 0 Manual Running FCV-67-49 "0 Manual Closed FCV-23-40 1,2,3 Manual Open RHRSW Pump B2- 0 ~ Manual .Running RHRSW Pump Bl 0 Manual Running FCV-23-46 1,2,3 Manual Open FCV-23-57 2 Manual Closed RHRSW Pump D2 0 Manual Running RHRSW Pump Dl 0 Manual Running FCV-67-48 0 Manual, . Closed FCV-23-52 1,2,3 Manual Open FCV-23-57 1 Manual Closed 2-41 E52165.01 TABLE II.'B~ 6.a. (1) Shutdown Control Area Environmental Control HVAC Requirements E ui ment Unitl Mode of 0 eration Position MCR AHU A 1,2,3 Manual Running FCO-31-81 1,2 Manual Open PCO-31-104 3 Manual Open Chilled H20 Circ Pump A lr2r3 Manual Running Mater Chiller A Manual Running MCR AHU B 1,2,3 Manual Running FCO-31-82 1,2 Manual Open PC0-31-105 3 Manual Open Chilled H20 Circ Pump B 1,2,3 Manual Running Mater Chiller B Manual Running FCO-31-150B 1,2 Manual Closed PCO-31-150D 3 Manual Closed Emerg. Press. Pan A Manual Running 'oard Room Sply Fan lA Manual Running FCO-31-77B Manual Open PCO-31-151 Manual Open Emerg. Press. Fan B Manual Running Board Room Sply Pan 3A Manual Running PCO-31-77F Manual Open PCO-31-152 Manual Open NOTES 1. Units 1 and 2 have common equipment (i.e. one piece of equipment is sufficient for both units). 2-42 E52165.01 TABLE II.B.6.a.(2) Shutdown Control Area Environmental Control HVAC Requirements E ui ment Mode of 0 eration eratin Pos. Shtdn Bd A Emerg Cooling Unit Manual Running Shtdn Bd B Emerg Cooling Unit Manual Running Shtdn Bd C Emerg Cooling Unit Manual Running Shtdn Bd D Emerg Cooling Unit Manual Running Shtdn Bd E Emerg Cooling Unit %manual Running Shtdn Bd P Emerg Cooling Unit Manual Running AHU 3A-1 Manual Running AHU 3A-2 Manual Running Chilled Water Circ. Pump 3A-1 Manual Running Chilled-Water Circ. Pump 3A-2 Manual Running. Bd Rm Water Chiller 3A-1 Manual Running Bd Rm Water Chiller 3A-2 Manual Running FCO-31-110A Automatic Closed FCO-31-110B A Automatic Open PCO-31-110C Automatic Closed FCO-31-112A Automatic Closed PCO-31-112B B Automatic Open PCO-31-112C Automatic Closed FCO-31-116A Automatic Closed PCO-31-116B C Automatic Open PC0-31-116C Automatic Closed PCO-31-118A Automatic Closed PCO-31-118B D Automatic Open PC0-31-118C Automatic Closed PCO-31-121A Automatic Closed FCO-31-121B E Automatic Open FCO-31-121C Automatic Closed PCO-31-123A Automatic Closed PCO-31-123B F Automatic Open PCO-31-123C Automatic Closed NOTE: 1 ~ Dampers operate automatically due to operation of respective cooling unit. 2-43 E5216 5. 01 TABLE II.C.2.a Heat Removal and Inventory Control Requirements E ui ment Unit Mode of 0 eration S s. Position RHR Pump A or C 1,2,3 Manual I Running RHR Pump Cooler A or Cl Manual I Running FCV-74-2 or 131 1,2,3 Manual I Open FCV-74-96 or 971 293 Manual I Closed FCV-74-1 1,2,3 Manual I Closed PCV-74-12 Manual I Closed FCV-74-47 1,2,3 Manual I Open PCV-74-48 1,2,3 Manual I Open PCV-74-7 Manual I Open/Close PCV-74-100 2 s3 Manual I Closed PCV-74-60 or 61 1,2,3 Manual I Closed Closed PCV-78-61 or 62 2 $ 3 Manual I PCV-74-58 1,2,3 Manual I Closed FCV-74-59 Manual I Closed PCV-74-52 Manual I Open FCV-74-53 Manual I Open FCV-68-79 Manual I Closed FCV-74-77 or 78 2 f3 Manual I Closed RHR Pump B or D 1,2,3 Manual II Running RHR Pump Cooler B or Dl 1,2,3 Manual II Running FCV-74-25 or 361 Manual II Open FCV-74-98 or 991 1,2 Manual II Closed FCV-74-24 1,2,3 Manual II Closed PCV-74-35 1,2,3 Manual II Closed PCV-74-47 1,2,3 Manual II Open PCV-74-48 Manual II Open FCV-74-30 Manual II Open/Close PCV-74-101 1,2 Manual II Closed FCV-74-74 or 75 1,2,3 Manual II Closed FCV-78-61 or 62 1 Manual II Closed PCV-74"77 or 78 1 Manual II Closed FCV-74-72 1,2,3 Manual II Closed FCV-74-73 Manual II Closed FCV-74-66 Manual II Open PCV-74-67 Manual II Open FCV-68-3 Manual II Closed NOTES: 1. The only piece of equipment required is the one associated with the operating pump. The equipment is listed'respectfully (i.e. FCV-74-1 is 'required for pump A while FCV-74-12 is required for pump C).'52165.01 ATTACHMENT 3 ANALYSIS OF ASSOCIATED CIRCUITS OF CONCERN 3-1 E52165.02 1.0 SCOPE The Attachment 2 functional criteria addresses the minimum system requirements of those functions necessary for achieving and maintaining a shutdown condition in event of a postulated fire. To determine if modifications axe needed to comply with section III.G.2 of Appendix R, a reassessment was made of associated circuits of concern, whose fire-induced failures could affect the capability to shutdown. This reassessment was made to identify cables that are associated because they are not adequately isolated, and: 1. Have a common power source with 'required shutdown equipment, or 2. Could cause spurious operation of required shutdown equipment, or 3 ~ Share a common enclosure with required shutdown cables. The method used to perform the associated circuit analysis varies from the method=given by NRC in the Generic Letter 81-12 . However, the systematic approach described in this attachment demonstrates that the„ intent of Generic Letter 81-12 has been met. 2.0 DISCUSSION Browns Ferry Nuclear Plant has five different voltage level groupings of raceway (conduit and cable tray) systems, namely: 4160 V, 480'V, control, medium-level signal, and low-level signal cables. The':". 4160 V, 480 V, and control groupings are divided into divisional and nondivisional raceway systems. The 4160-V raceways contain only '-" 4160-V cables and axe located at the top position of verti'cally "->: "„' stacked trays. The 480-V raceways have 480-V power cables, lightiag . cabinet feeders, and instrumentation and control power cables carrying,. 30 A or more. Control level raceways contain alternating current and/or direct- current control cables of 250 V or less that carry less than 30 A and communication cables, such as for telephone circuits. Medium-level signal and low-level signal trays contain only nondivisional cables and are located at or near the lowest level of stacked trays. Divisional medium-level signal cables are routed in conduit. Medium-level signal trays carry the following type cables: signal cables of digital input to and outputs from the computer other than thexmocouples; instrument transmitters, recorders, and indicators; eccentricity and rotor detectors; RTD's, tachometers, and shielded annunciator cables used with solid-state equipment. Signal cables for thermocouples, strain gauges, vibration detectors, and thermal converters are nondivisional and are run in low-level signal raceways. These type cables are for very low power circuits- used to convey information. Instrument control loop and related instrument signal cables operate in a range of 10 to 50 mA with power supply voltages up to 85 V dc. The annunciator circuits operate at approximately 1 mA, 140-V dc intermittent duty. The computer cables 3-2 E52165.02 ~ operate at 160 mV into a high impedance. Thermocouples, strain gauges, accelerometers, and resistance-type temperature detectors are low excitation voltage devices; cables from these devices operate at 15 V or less and carry negligible current. Thus, energy produced by electrical faults in the cables routed in medium-level signal and low-level signal trays is considered insignificant and is considered no challenge to shutdown capability. A non-safety-related cable may be routed in a tray with safety-related cables, but once routed with one division of safety-related cables, it cannot cross over and be mixed with safety-related cables of the redundant division. The non-safety-related cables are the same type and have the same circuit protection,and short circuit rating as the safety-related cables . With respect to identifying associated circuits of concern, TVA has reviewed protection for power and control cables, and has determined that if a cable fault occurs, existing or proposed overcurrent protective devices will interrupt the fault before cable damage occurs. The fault will be cleared before autoignition temperature of the cable insulation is reached. One case was identified per unit where the load/feeder overcurrent protective devices are not adequately coordinated (see Analysis of Cables That Share a Common Power Source). Several cases were identified where existing cables that can share a common enclosure do not have adequate overcurrent protection; these cables require circuit modifications (see Analysis of Cables That Share a Common Enclosure). Cables used for 4160-7 circuits are shielded, 5-kV cables. The minimum size cable used for these circuits is 2/0 AWG. The 4160-V circuits are protected by both phase-to-phase overcuirent and ground fault protective devices. The phase-to-phase fault protection is instantaneous (no intentional delay). The ground fault devices are instantaneous in operation and are set,to operate for 'ground fault currents from 5 to 20 A. The 480-V cables are part of the 480-V ungrounded delta distribution system. Overcurrent protection is provided by molded case circuit breakers with an interrupting time of less than two cycles.and power circuit breakers with interrupting times of lessby'ow-voltage than four cycles if equipped with instantaneous trip devices, or up to 35 cycles if equipped with short time delay devices. In all cases, after circuit modifications are made to selected cables that share a common enclosure the protective device will clear a fault before the cable insulation reaches its auto-ignition temperature. Control level cables are used to provide instrumentat'ion and control power (below 30 A}, to convey information, or to intermittently operate devices controlling power switching or conversion equipment. The 250-V dc control power circuit was determined to have the highest 3-3 E52165.02 available fault energy. Each polarity of this ungrounded 250-V dc circuit is protected by a fuse or circuit breaker sized to protect the cable fxom damage. Thus, a fault will be cleared by a protective device before the cable insulation's,auto-ignition temperature-is reached. 3.0 ANAYLSIS OF-'CABLES THAT SHARE A COMMON POMER SOURCE Each safety-.related and non-safety-related circuit that shares a common power source with required shutdown equipment was analyzed to ensuxe that the power source is or will 'be adequately protected from electrical faults by coordinated breakers, fuses, or similar devices. This analysis consisted of a,review of the overcurrent protective devices for the 480-V switchgear which shares a common power source, to verify proper coordination of the load and feeder breakers. Cooxdination. of protective devices for the 4160-V switchgear had been previously verified by formal xeview of protective relay setting instructions. In all cases, coordination exists between these breakers as designed. Each 4160 V and 480-V s'witchgear ha's' 250-V dc control bus. Since'ontrol level trays occupy a position below the power level trays, a postulated exposure fire could possibly cause a on the control cable for local, control or process interlock. 'ault This fault could trip the control circuit's protective device for a given pump befor'e its power feed cable becomes involved in the fire. Verification was made that each control circuit as designed was properly fused for this switchgear which shaxes a common power source with shutdown equipment. The existing des'ign of the 480-V motor control centers that share a common power source with required shutdown equipment, was determined to have proper coordination between the combination motor starter or circuit breaker for each load.and the feeder bxeaker. Also, the control circuit for each load has its own control transformer and is adequately fused as designed. Each circuit of the instrumentation and contxol power system that shares a common power source with requixed shutdown equipment was analyzed. For this analysis, it was assumed that a fault occurs at the point closest to the distribution panel where nonessential cables could be involved in a postulated fire, without also involving the required cables or the distribution panel itself. Except for one case per unit, the results of the analysis confirmed that the load/feeder overcurrent protective devices are adequately coordinated to ensure that instxument and control power is available to a minimum set of shutdown equipment for any postulated fire. This exception involves a control power load circuit of the unitized 250-V dc RMOV boaxd IA, 2A, and 3A. 3-4 E5216 5.02 4.0 ANALYSIS OF CABLES THAT CAN CAUSE SPURIOUS OPERATION OF EQUIPMENT Spurious operation of equipment due to associated circuits will not 'eopardize the shutdown capability because all equipment whose spurious operation could affect safe shutdown are included in the list of required equipment and will be separated or protected in accordance with section IXI.G.2 of Appendix R. Therefore, if a component does operate spuriously, its redundant counterpart is outside the fire's zone of influence and will not be affected. 5.0 ANALYSIS OF CABLES THAT SHARE -.A COMMON =ENCLOSURE At Browns Ferry nonessential cables can share a common enclosure (e.g., raceway, panel, junction) with required shutdown cables. An analysis was made of all switchgear, distribution panels and cabinets that could affect shutdown capability to determine if the load cables are adequately protected from damage by circuit breakers, fuses, or similar devices'hus, only those cables that are not adequately protected become associated circuits of concern. From the analysis, several cases were identified for each unit where the protective device is inadequate to protect the load cable from possible damage during a faulted condition. Although these cables are not required for shutdown for a postulated fire, they can share a common enclosure with cables that are required for shutdown capability. These cables will be modified to provide adequate cable protection or separation. In addition, exposed surfaces of cables in horiziontal and vertical cable trays have been coated with fire-retardant Flamemastic 71A or Flamemastic 77 in all areas outside primary containment that contain required safe shutdown circuits. The cable coatings coupled with compliance with section III.G.2 requirements provide adequate assurance that a fire can, be detected and extinguished before it prxopagatespa betweeen redundant circuits over intervening cable trays. The open cable trays axe the only common enclosures through w ic i could possibly propagate between xedundant shutdown circuits. 6 0 CONCLUSION After the proposed circuit modifications described in Attachment 4 are made, there will be no associated circuits of concern. Thus, the cables necessary for achieving and maintaining shutdown conditions in the event of a postulated fire will comply with section III.G.2 of Appendix R. 3-5 E52165.02 ATTACHMENT 4 ELECTRICAL MODIFICATIONS AND REQUIRED ADMINISTRATIVEACTIONS 4-1 E52165.02 1.0 SCOPE The electrical modifications and administrative controls required to bring Browns Ferry into compliance with section III.G.2 are the subject of this attachment. 2.0 SAFE SHUTDOW ANALYSIS RESULTS FOR THE REACTOR BUILDING/DIESEL GENERATOR AND TURBINE BUILDING/INTAKEPUMPING STATION FIRE AREAS The following section outlines the results of the Reactor Buildings/Diesel Generators and the Turbine Buildings/Intake Pumping Station. The tables are arranged to indicate all interactions between redundant equipment required for each function defined on the shutdown Logic Diagrams in Attachment 2 (figures I.a, I.b, and I.c). Each table has a sheet 0 which lists interactions between redundant components and a sheet 1 which provides details of each interaction identified on sheet 0 . Sheet 1 also references a corrective action sheet for each identified interaction. Tables are not provided for the RHR, Auxiliary Power, HVAC, and Drywell Control Air Systems due to the complexity or simplicity of the identified interactions. However, corrective action descriptions are provided for all these systems. In addition, diagrams are provided for the Auxiliary Power System illustrating the required power arrangements necessary to meet the functional criteria. 4-2 E52165.02 ~ ~ I. r ~ ar cc>vi H I n a l Cl n~4 n n Ial fl VI n ll rl a n 4 n I ~a 'a T aI V ~ I al aa ~lI II V CP la. aa ~a IL la a,> G FCV.es 1 ~ r ~CV C 0- I4 3 Zy. ICV.I S- I1 fCV 3- ~rCI ar ~ r. // r Y /r/ . rr IC, ~cv. 1 ~ it fet ~ 1 . gI, res. I ~ sr VCV. t-SI I I frr. $ ~ SS lO I fCif-43. It 5YHIÃ)I5l 1aaicr~laoaa IIIIC~~l l4 f~lea~t.~ AIIINnlX II RCACTOR BUII.DING fICACTOR COOLANT 5Z51CM IIIIUilfITY INSIIIS ffRflT fIN(Ihg Plhttf ra«slN.Vl ital ~ %" ' ~ Ilfil1'i'RD RC5'L ~ ya RIII n.. I I'>~ S CAB'LE RCSPOIIS1BLC G ROVI TBG its SEE r. hall g hT 1OIl ~ sf AIC>oAIIE R lf Cnull fhr.NT 'fLIIQ5 Sllf:f.l Of COIIRfCT I E SIIECT PIV>PIQfA YQQf IIVUIILB. 9 BfVXR~Xf PCV 69 1~8'. SET '1 Cab'lc Tra OetofIEB .IkteoS >P ~ Irc3>>~i ercsosell fe >,Q p.c >clif t FCV. GO-P. ID+Sea >I ~ Shr.c) 3 >bit fraf LLOYD cad~ >PC343 ~ SPCssS ~ I t SET> l. ~ IIEB qpcoSIV l> IIOTES> lcv. oo-'i t ~ e C>Mc Tee ~ I ~ recto OC'I 2 >Vari TD s i>V 4 >>> I'. FCV- e9- le IT ' Sloccl ~ v, q ~cvl Rc 4 IKIIl~o~&f I. The corrcclovc ocl eon Io bc ~ ~ >POD>O-U "~ ~ SE'P FCY ~ E> 9 2 1 Cable Te st ~o NEO D' 0 ~ ~ . 'Co acct thi .:nrci ."..: ~ ritcrin for the RAGtl isolation vnlves, one pnth nut o! three'ust l)u oprrnble. For the inteructions described on sheet ~ l, nt nsi plus c'red;Il I t:hruu pnths come wit.hln 20 feet. Therefore, no modiHcatlon is required. r, F ~ APPENDIX R CORRECT I YE IICT ION B RLY1 BKDo Ihn-': t:r'< BFN-IT-RB-RCS-l-Jl I The 480V reactor NOV board canpartment SC breaker will be "racked out" to prevent the spurious operation of the residual heat removal shutdown cooling suction isolation ll 'kd'bk I 'll dbydhal kh y I» h '' ldgggyhdk 'kh 8 Ill I d I 8C breaker "racked out," the possibility of a fire causing a spurious operation of the b I'dhg 4 y I & ddbybdl dd»' b through of two power cables, one of which feeds the ~~~ valve motor, with the subsequent. touching of conductors in the proper phase sequence to open valve is too unlikely to occur to be considered. ~~~ APPENDIX R CORRECTIVE ACTION PREPARED: REVIem: 062161 Ol 0 FN-IT-R -RCS- I-.MI To meet the requirements of Appendix R, the, cables for FCV~3-98 and 1CV-3-99 will be rerouted iA conduit. All cables for FCV-1-14, FCV-1-15, FCV-1-26, FCV-1-27, FCV-1-37, FCV-1-38 that: are presently-routed on elevation 593 in the reactor building will be rerouted in conduit. All cables for valves FCV-1-51, FCV-1-52,-FCV-1-55, FCV-1-56, FCV-43-13, and FCV-43-14 which are presently routed in the reactor building will.be rerouted in conduit. APPENDIX R CORRECT I VE ACT I ON PREPPED: Petiem: BFN-IT-RB-RCS-I-M l 0 jI I ~ ~ cX N a Ct H n c) ~ ) EV r) VI h ~ n J ) n n '7P V V V V V V Ig )L. V V 4. h. )L 4. s,g 0 FCV-6e. f ' ~ gg SCV ~ t 9 IC rcv. (i.'). )l lcv $ - ~~5 rcv- vc-cl 1 ccv I II 1 crt f itcv. f -5I //g(jr'~„.g j,:~:.,'(~~jr~ II y~gxgy')." x',,'g, .'::Q'2 SYHDOI.5) 0 T~)efafen No) C~:k~f IIj l4 falcoMIM Al'I'I'HDIX R ia.r REACTOR Su? I.OING APACTOR COOI.ANT 575'Ll:I'I IHTKGHITT BRSN.") ffRRT tIKL(ARPt Rill <')" „.S O„,fQL. - e Or))41 RSRC52 Itasca 3 ~ CABLE, z RtsfoHsvBLE foal RQU 1 TTPK SEE,. *IIJI LiI>II 111'lllo 'F lt EQUlPHCNT CA BI.ES CORRECT1YL SHEET PR 5 PA FI E R llUQQL llTQ Y ~15QLVLO~ HVHGER. LHKRd V e zwsas 1 SET l. 0>se HEB pele<5/ F ~ ~ lI: — xiii'o 9 F N .'8 R B - R C S -. 2 - J 1 meet tbe success criteria for the RWCU isolation valves, one path nut of. three must be operable. Po'r the interactions described on sheet 1, at no place do «LL three paths come within 20 feet. 'I'.bcrefnre, nn n~~di f i«ation is required. ~ ~ 4 ~ I ~ APPENDIX R ConaEcTivE AcTtoN PHLf'ARED' Q i Pl:VIENED: OA1L: BFH-IT-RB-RCS-2-Jl The 480V reactor NN board canpartment 8C breaker will be "racked out" to prevent the spurious operation of the residual heat removal shutdown cooling suction isolation kd 'b k *'d tMhyd ll kh I IH yl h '' 'khkh I I I 8C breaker "racked out," the possibility of a fire causing a spurious operation of the I d b k I'~k2 I N bbbbbdy dkh through of two power cables, one of which feeds the gg~~8 valve motor, with the subsequent touching of conductors in the proper phase sequence to open valve is too unlikely to occur to be considered. ~g~ APPENDIX R CORRECT I YE ACTION PREPARED 'ATE 062161.01 FN-IT-RRCS-2-0 l To meet the requirements of Appendix R, t:he cables for FCV-3-98 and PCV-3-99 wilI be rerouted ih cond'uit. All cables for FCV-1-14, FCV-1-15, PCV-1-26, FCV-.1-27, FCV-1-. 37, FCV-1-38 that are presently routed on elevation 593 in the reactor building will be rerouted in conduit.. All cables for valves FCV-1-51, PCV-1-52, FCV-1-55, FCV-1-56, PCV-43-13, and FCV-43-14 which are presently routed in the reactor building will be rerouted:in conduit. ,APPENDIX R CORR ECT I VE ACT I,ON PREPARED 'ATE BFN-IT-RB-RCS-2-Ml ~ ~ ~ ~ n ~c co cII n cc cv v) vc n rl tc n J n : I rl '7 ' cc cc C ~ V CI V V c4 Ia IJ, ca l4 IL ~4 ca ry, Vr.c) %5. 1 1 r",3 2)3 n vrv.c.s- cc. yw ~ rcv c 0- I') frv 3 5 rrv- va-c) g..jf i/ rrv. 1- )1 I'rr'rr - 1.?c. rrv ~ ~ l 1 kf ) rcv 1 ~ 5) IO c rrt. 1-~~ 'reV. CS 11 QY)ll)01 .yc v. I~ier¹:1 scc Ho) (~J k). Ne li4o~. )v o Al'I'I:HDIX )I UHE '4P. 'aa c REACTOR 8ULLDIHG ACAC IO)7 C.r)O) A))'1 SYSIC)1 I))IEG)IIf Y P 8AON5 Ya Bast ~ APPf.HOIL> R tI>es I M RLACTOR GUtLOIIIG poao 1> ~ Is> teen REACTOR COOLAIIT Lest 3YSTC,H Or s Baste INTEGRITT p>sp' BROblllS FCRRY )/Ut:LCAR PLAIfl p>4465'+'er y 6 " ot Sttt Ifli5 IIC5-3 6 '':~ ~ ~ 9 ~ . A I I ~ ~ ra Yo meet the:;«c«a'..:: «riterla for the RtlCtt isolation valves, one path nut of three must he operable. For the interactions'escribed on sheet 1, at nn place do all three paths come within 20 feet'herefore, no. mndi.fication is required. ~ ~ nVtEVnIX R CORRECTIVE ACT ION PREPARED .'VIE~D: OWE: ~~< ~8'< BFH-IT-RB-RCS-3-Jl BFH-IT"RB"RCS-3~ The 480V reactor KV board canpartment 8C breaker will be "racked out" to prevent- the spurious operation of the residual heat removal shutdown cooling suction isolation k& "t k '6'&tyd t&1 th dH ~p t a thth4 t d g 8C breaker "racked out," the possibility of a fire causing a spurious operation of the feeds ~open valve and the insulation burn 250V dc breaker which power to ZQL~Z through of two power cables, one of which feeds the ZG~~ valve motor, with the subsequent touching of'onductors in the proper phase'equence to open valve g~~ is too unlikely to occur to be considered. APPENDIX R CORRECT I YE kCT I ON REPARED: thVIem: DATE l 062161.01 BPH-IT-RB-RCS-3~ -0 FN-IT-ARCS-3-Ml To peet;.the requirements of Appendix R, the cables for FCV-3-98 and FCV-3-99 will be reiouted in conduit; All cables for FCV-1-14, FCV-1-51; FCV-1-26, FCV-.1-27, FCV-1-37, FCV-1-38 that are presently routed on elevation 593 in the reactor building wil1 be rerouted in conduit. 'll cables for valves FCV-1-51, FCV-1-52, FCV-1-55, FCV-1-56, FCV-43-13, ~ and FCV-43-14.which are'resently. routed in the reactor building will be rerouted in conduit. APPENDIX R ConaEcvrvE Ac+IoN PnEpnnED; L ~r ~~br ~ ag 4 rO r Vl f 1 ~ ' A rt hl A vr ~ 0 n ~, e. ~r n rl $ ar 0 rJ V V ~I cl IL. Is 4, lL ~ ~ ~ 4. ~L lL wO ~ NI NI ~ r ~,. 1)r ~ NI . . ' r r ~, J ~ h ~ ~ gg SYHISI 5l Ielrrwl~ Hol Le ~ Rf . He fe lrrsc4n Al'PLNDl X R TURBINE BUILDING RCAC TnR COOL AllT ST51L'l't IN1EGAII 'f lÃCMH,"lFERRT llUClEAlfPthllf Csraot''v~ CJ rc ~ ~ * 0 t tO hO tll I v> ~ > n A n ~> n ag n ~t ~ h Tl 'P 'h> r t> t> t> t> h> t> c> c> r 4. Ch. cy D ~ l Vlf gt j ' ref.>/n- rl rff 3 - hhy Wy/g, m ~x (r ref-~e.il V'gh .:„Np rev-1- ll ref- f . pc, ftv ~ 1 . J1 >fcv 1 5l I rvv 1-55 Fth.h> hh ' rg/r.)/v >/ /' c ~ ~ c . c'>'fH]el '.>- . f~>r/vlhen hi~1 CwJnJ gf gt ftll/tktltttt AftPL WOI X R UllU TURBINE. BUILDING ACACTOR COOLANT SY!llf;8 INTA'RITY BRnnlS IIf'Rf NKEEAH PlAHf c' 8hc> O(t'1' OrN ll 'T8 RCS'l.~O ieijfg 0 c> ~ Vl %I vl ~V n vs J n fS, N A vs h hh n aP n r ti '7 s' aP hr ~r ~ V I N. \I cr „c ~a 4 lL I~ . i>d ' F(v 4e-1 tII Nl h rCV l 9 ~ Iran rCV-e «J- ll frv 3. yy. rCV- 14 . f1 ' ~ / X'h. rcv I li K p I - t4 h I rCV 1 51 NT err 1 5$ \ , ICS'3 H x'THIMli'sr N. T~lcro:iso Itnl Cr .Jar XI... lie la1ei~ l~e AI'I'INdt l Ii IS tIN~ S ',. TUIIBlNC, BUILDING ~ Pj, tti:ACTOlt COOI.AIIT 'T51L'tl ltlltGltlfY ' / HRCMN5 f[RRT IIVG)AR Plhlif cg 'c n 0 n vl n ct ft vt ~ t d.l tc T ct 4 T V ~t ct ~ ct ~t IL 0 0 11 0 0 4o 1 1 Par ~ 1 1 1 1 IXV- 1 -Zs 1 1 1 1 Pcv-l, -met 3 1 1 1 1 1 PCv- S- Sl 1 1 ~ 1 fcv- S ft 3 3 3 3 J 1 1 Pcr S t19 I'Cv $ ~ IQO 3 3 5 r 4t v c r1 0 vt 0 4t n 4 ~1 I g, ~I ~I V ~t ct L 0 D vt D 2 2 2 2 2 1 2 2 2 2 2 1 2 2 2 SVHBOI.~: 2 2 III .. tI~ ?4ICv eel ycvc 2 2 2 2 2 2 2 2 2 j 2 2 2 2 2 APPI: NDlX 8 REACTOR BUD.DlNG ~ I RPV '4fhlfR 1NVLIITGAT CAII 5/R VALVE CONROL BSOWIS r ERRT uu'.SCAR A.Au> ftctri>~'c''I ii<.~a.< ~v III IT RB mV.O .tc '=clSL . all ChGLE gcspDNsxsct 8 ROUT INg .(PE SEE c.kslg thy lO EOVIPFlENT CABLES SNEU OF COHlfCCTIYC S1IB BT, FN R PA 11 B N CV EYE~ RUliUCfLZQQMCLlO MJJQll HlMlQlBDJ)vtM. hll SlA Vela»S All A»actor >1/ g.( 10 PeAci Ocis TOP,D scesc»l Cor UNIT 1 QaM\s feeoleens flc, 6 Pe«l ' Bcaa~ Valses Broiler Bld) 'tSc hll BIN 5E,T lb Paocl 1 «TPP Deco5.18. NOI oeolvlo UHCT goMe ~ t e) ate A)fl g2 „,gg,n, O'Ceo l0 1 u I, flse cerracsovC a»lien I~ bc ~ ere AN Rassler AR pig SW) loll oa acloeess 't 5QT lb Passel " ~ fer »4 ietef vc '3 QeMe c evelelon) UslIT ~ Il .,':Joule"" gaea»relic»4 eia 14 folio«eec) SCo~al os a a osc e' Oooo polis h Ncroul Teevele»d Csblctsl B eo Dele 8- Prov'sdc F~c Bwricr reise Bise C. Circe'o't Had sf sca'l son Ocos Disso poses 0. Pier:Jc Fir» Seopprcssiees Bs Oe Jo Aesalysi ~, illsr o 0~ fcc cerrecliva s»ls ~ ~ »se 4 aoos Oe ec o 1Lc elov» scl oa ~ vr eeef flare goosl;~c ae 4eeee( o oo O'sos I'lis i~ ~ re'leronsv le lloc 1'e< ~ o dascrispl'em eaf llsc roieacloce »cloaca, Tioe 41 cel n velar cas Ov c. ~roll la ereardJ b) Sl if Aces cvrreclerc hob.c, oe 0 es «acl s ~ ed ls 5" el ~ clip B oeae Deice ~os»d. Oasis ~ esc alseol esvoelacr IVsr o ae ) L» ra(eros cad. Ci ~ . 0 ale I ~ cv »slice «l. ~ «eo'@co lA, «'.B Oees ~ Deere c u sc «g la «Q re M o ~ 4 s'll cveccl4e ~ a'l.on ~44 B decor:Lcd a 14l decO Coo beers decare pneo Tho 9sogn aoojcol ic over«clo Rcc fee 4 aeoedoot*lo o( 1l t >e»eo« Ocoe Ball »eqsoisac vs f' cveecb v». sveee ecl.a«. '»Be roe(~'.llc ~ ala=.is(e r g ~s 4« »sfceo Lie 4r lie Ocv bas ~ i cacL(seel'ev or joel (Nsl ov i'eee »1ov« Oo«o Csosee e U eoo bees pee eo Bc ev basso APPENDII R 11 see R»elf Rf.'AC,TOR ' BUILDING . 0«o s\n raise RPV WATER ItfVERTORT CONf Rim 5IR VALVE, COHTROL Oa e base ~ Aors 8ROlfNSfERRT WCLEAR FIAKf V beccsrVV &r.V~~< o BEN llft5 SsRV F)' 0 ~ i « ~ s oal 1 I. ~ s ' o s FN-IT- SRV-O-Ml To meet the requirements of Appendix R, all. cables required for'he 'safety/relief valves which are routed in the reactor building will.be rerouted in conduit and wrapped with a fire barrier to preclude any damage to the cables which could cause spurious actuation. .APPENDIX R CORRECT I YE ACT I ON PREWnED: Par>em: DATE 6 -/7- gZ BFN-IT-RB- SRV-0- Ml FN-IT-R -SRV-0- M2 To meet the requirements of Appendix R, all cables required for'he"safety/relief valves which are routed in the reactor building will be rerouted in conduit and wrapped with a fire barrier to preclude any damage to the cables which could cause spurious actuation.. APPENDIX R CORRECTIVE ACT ION PREV RED RarIE m; ATE: -' "/T-S Z BFN-IT-RB-SRV-0-M2 To meet the requirements of Appendix R, all cables required for. the'safety/relief valves which are routed 'in'he reactor building will be rerouted in conduit and wrapped with a fire barrier to preclude any damage to the cables which could cause spurious actuation. APPENDIX R CORRECT I VE ACT ION PAEWnED: RV/IE m: ' DATE: -/7- gZ BFN-IT™RB-SRV-,O-M5 .0 c g Tn n «I 0 (0 n H iI ~) n I r( q4 ~ I ( ~ I rl j I Iy ~ ~ V V V V V V 4 4 n. do 0 4V I« 4o EI T. Ht Ar HZ I'CV ~ f 4 f4l Hr pev ~ I ~ n t4I Hf Ht Ht Hr Pcl 5 Ig Ht ur Hl I'cV- 5 -4.'s'l Nt HZ Pvv f PS El J Hr Ht llr Hr tcv-I .an Ht Elt Hr'4t Ht 'At Pci-5- el HT llt Ht PCi- 5-SL Hr Ht Ht Hg «Lt - H[ ~ NJ, PCV- 5 Ig Hr Hr I'Ci I lt Nt Nt Ht Pr.V 5 ITS NI Ht fit Hr Pcv- 5- ny fit Ht I4t HZ Nt I4Z ~ ~ Prv -5 ~ lhh lItNL Ht Pci I 4+0 Nt Nt Nt Nr f 'c nl 0 iij H n 4 ~0 ~ ( ~ ( H V V gl V V U>ILT 2 n 4 4 4 I'CV f ELt EEL. Elr. ! ~ It >Lt «Lt. ELr. Hl E4t 4Yt 5UOL~( pcv f <1 Ht Ht Ht Ht lll H« teleia(loon Lxv ~ V 47 HZ 54L At I'Or ~ 5 ~ Elf Ht Ht Xe'v- 4 -Ito Ht Ht HT. APPCNU1X R UB ~ TURBTELE OULLOt)LG RPV WAtLR 1llYERT(QT TXNT 5/R YALYE CON1ROL 8iue45 r ERAT LLLXLt'Nf'thill ~<'V' r,v(.~IIr'< ~ Oai(o IE ~ GTII IT 10 AV0 rrP( Ema ~0. The are to ensure the RllR system following modifications required will meet'he Functiona1 Criteria: I 1. Route all power cables in the Reactor Building (RB) required for the equipment given in table II.A.2.b. (1) in conduit and provide a one hour fire barrier for each conduit. 2. All cables located in the RB. involved in the back-up control circuitry for the above equipment are also required to be routed in conduit and provided with a one hour fire barrier. 3. All cables required for the redundant RHR System (System I for unit 1; ~ System II for units 2 and 3)'are to be re-routed where they will meet the separation requirements of Appendix R between the cables and the active equipment for the system required in step 1 above (see table below for active equipment). 4. The RllR pump back-up control switch will be revised as shown in the attached drawing to allow bypass of the position switch on the RHR drain valve. See attached schematic for exact change. By making the above corrective actions, one RflR system will be available for any RB fire. Active ~Rui ment 'Peble Unit l Unit 2 Unit 3 RliR Puicp U RllR Pump C. RHR Pump U I'CV-74-30 PCV-74-7 FCV-74-7 PCV-74-67 I:CV-74-53 FCV-74-53 APPENDIX R RllR Pump Room Cooler B RHR Pump Room Cooler C RHR Pump Room Cooler C CORA ECT I YE MG Set ll'.N MG Set 2DN eMG Set 3DN ACTION 480-V RMOV Bd 480-V RMOV Bd 2D 480-V RMOV Bd 3D 1L'-kV/480-V TS1B 4-kV/480-V xfmr xfmr TS2h 4;kV/480-V xfmr TS3E eEPAREU: C. REYIem: ~/4'FN-IT-RB-RHR-0-Nl ~ ~ N II I 4 I A 4 IK P X x II Il II ~ IL Cl IL IL lL IL HZ s)z Hz Nr HZ HZ NE Hz HZ hlI gz Hz Hz 3 Hz ~ I HZ Hz )4z 10 I I ) I lorn QYHt)ALSI g, I)o lealae L, A)~ ) L))0)X R REACTOR DOZLOING E55EN) IAL EOUIP COO) J)JG ECCW STSTEH naOW5 ireT RXlWR t'INn Iluls< III'~ Patt f Cl 'I erII'1()lb tfc< 0 .Cl 4" 'h'tc ir' CADK I Rtsfp>1$ 78LE t3 IIOVI iNO SKK ~LII af >ala ff EOIIIPHENT CAB!.'ES OIIEF.I Of CORRECTIVE BIIEET fiiiiiil\ if IIIIUIIEfL~IIV~V iXL IIIlllilfll EBhCIIQI HllfSQUl BfVIr'atf Ossa IIEQ paa ~ eS'If'5) RIIR5>bf Pv p AS O'C51581-I 5KT 12 Cd,4, Tts 'stfsls>!S>csisfe f Hf feet.oa.(.LJJ@ FCV-P$7- Sc.et IS C>blc > 26 II$LoofMnttf ~ 7 ~e1~ ta~iltat ~ RIIRSbf P„p C3 QEK!591 ~ I SKT 12 Cable 7„! ~ IIEO gosag.stet> NOTKSI ic ~ ts1$ 1F, scsieMv n sn Qa. GJnOQ.< FCV-67-26 $ SI et CS Cable Tn,f Jta tSt LII~ Ie 5 ts soiree I TI» cstrcclive sclien ti bc 't5'>$ ~ f'C'V ~ $ 7 poise 5-If' I 67 - 13 5ET 12 C>%4 Tw! ~, NC 0 lAin for CLe»lersctlenS stt tsstpc -E A,E n.lra Q.ff. EJ fJ4,< eiencrelac el ael Ibg, Me4ire) FCV-6 I- 14 7 Csb'4 Tts Shccl Iis>ass~at vnfnc ~neneatrl te FCV. 67 - 13 E$ 755 7 SET 12 Cable T rl Oaai t)EB paaeaf I>5 It)as>6 fss>.gfs GJnloc h. Ifcre>s>I into!ctd Cab)ala) ItSCPIS'te t Cable'.Te FCV. 67. 1 'JR>el II>etrcJ~ ~ lcsslp t ~ ltsf>>6 )oaa posaS.lf I . fCV.67 I I SET 12 Cable Tref !if8 O. Provide Fart Larrftr 'fasfe~ ....Qa.81 Of4, I'CV ~ CSSt5>G It Tta -67 14 Slice I 7 Cable Ota at C. Cltcoel Hoalif't.sl epn a>IO ICSC15 I ~ Ses I CV -G7- 17 5E.T IZ CA'lc Tea! neo> IIEB I«» S.lf tt f Ielcfg 7 Ianf neet ~ OO. Io! +et O. Prat'oo} c Fere aatatao tsnlnts FCY 6T- 18 ii,, i .. Sbael I.B Cab!c Tsrf I ES t?1 IL11 he>> ~a~"'i4~. Ic)al>5 I tcs ~ Is I 12 Orna lltll Pa>cag.tf I heaslypis FCV-67- 21 1!)SIL t st ts" tn'L .'jET Cable Ttrf 1~>> ~ f>JofJJ c>IS>e ~ ~ cscs'ls s Qti t fOIRSM Pa>mf> 83 Sla>CI 15 C>NG Tfeq if~a rLstet Cl~s>c IIac corrie'lore spline ~ csn bc CIS ~ >$ Case Iea ;\ ~ t 'feel nao> Ilt8 0 ataS If I I: FCY- 61- 2I ttbttl:.t>PCPK+43. SE.T 12 Cable csc(nt c conc ~ s Iss ~ sQQfcJ (U» t b'~bien If,erenC ~ ts BI>eel Ig Cable Test I RllRSbV Pu.np 03 EbtGPS=% bt>sd gtsc Is'lalts ~ ll'I>CI>e> S~'ll FCV-67- Zl EC)Ãtf>LigtsStft.t. GF.T 12 Csbfc 7>at nese gt8 If>a>f5 TI>.e i~ I refcrtntv se Ibac ~ ~ ~ Cist'>ll ~ Sate>l >IC>l>IS > I"it 0.0. CLQbt lescs ipI:rn nl liat .em>et!ate $ i\ II,I) C)MC T.pf FCV.61-22 CCSCS5P ACS~o Sc!atn. Tl.i eb r! nombcr '> ant~~ ~ S 5 ~ e a $ S ~ II 5 ~ J I e I II p> 5K,T 12 C>Mc Ttc ncaa pool ~ 5'-If ~ >fill bc paeceda H FCV-67-25 It)IJft.st cnsntc. IIt8 I b5 if .>I>Isis St)r I ~ >«tat fs,n Og.cJ lbf.. cearrccler c 8.C et 0 ae aaac) 10 5> If>16 t ~ FC Y - fc>7- 26 f.'> >n I gt>SSS >IS~~as Bctltcdt~lt~ snd bq l at acies» E ea Ossa Os«> vtcd. f)ea!S reae sbrcl tsenber I>est o sa II Iee referent".k. (Le. 11'bc i o ~ raealiie oa! on seo!ore belli pena ps ~ te t & t 4 s! «iI! ~bf be~A ra s t ~ ~J sll c«teel:tc ecl..n . II In afava dc>sr:fed oo llasl sbcrQ Ca 8>e« feet> 71> ~ kcoqn sar>col ie ecetna.sl ~ ka f Ibr soe04 a% A Ibo >>~Q, Soa best 4>ganesa>era F» Ibnf cer>ocb ice. ~ t ~ ~aliene 'T4 r ~ efeiL IS>e ~ tl>SS ~ oa po>ls peen b«le APPENDIX R Iles> tallJ IICACTOR BUILIIING Oeoi ps>re taste ESSENTIAL EQUIP CCA.IHG tcc> hEC'8 SYb'I Dace bS>ti EN testa f'ERRV Btnl BRObJNS NUCLEAR PLAIII po>sef If <' fks>DIr~te dr. KIIIllK!I KEC>ofo ~ I ~+~ ~ ~ ~ ~ ~ ~ ~ I I ~ ~ a ~ I ~ ~ ~ ~ I ~ ~ I ~ ~ ~ ~ ~ ~ I ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ I ~ ~ ~ ~ ~ ~ I ~ ~ g g I I ll ~ t4 ~ ~ ~ ~ ~ ~ tl I gl I ~ II III~ I ~ ~ I ~ ~ ~ I I I ~ ~ * ~ ~ 1 ~ ~ 0 ~ ~ tt Ill To meet the success criteria for one EECW System, both pumps on that system must be operable and no more than one valve in the system may be closed. Therefore, the success criteria for both EECW systems would not be met if any one of the following situations occur Failure System I System II One Pump fail One Pump fail 2. 2 Valves closed One P)mp fail 3. One Pump fail 2 Valves closed 4. 2 Valves'closed 2 Valves closed Situation 1 does not occur as examining sheet 0 shows that there are no interactions between system I pumps (A3,C3) and system II pumps (83,D3). Situations 2 and 3 do not occur as'one system's pumps interact with only one of the other system's valves. Situation 4 dogs occur due to interactions 3-6 all being within the same area. Therefore, cable ES753-I will be relocated to assure the success cr5 teria is met. 'APPENDIX R -.CORRECTIVE ACTION REPARED:- ~IEWm: ~ +'ma: — 8 F 5 I T.- 8 8.- F E 6 H.- 0 - H 1 n " (II Q Id t N N IL I'I I 4 I n J If P II V 4. L IL L RIIRSV R NX gr biz Rl(AgV (I~~ (ted ttr NZ Ifv C'V If .Nr Nr ICV~ I 1- I( Ha Hr Fcv- cT tt ur oz rev. cl-as ttr Ar 5YffDOLSI Nt II+ gyltoP tkII A(I(It.t(01X R TURDTNC BUILDING C55EN1 tht. rnuIP Owl 1Q-. CCCW GYSTEtd OROVtlS l fRRY Nt CABLE, 2 ties PO)tsaSL'I 6 ai ROVIING O'E K ra hat ZhT ISING MLIIPNEHT . CABLES BIIEU CORII ECTIVE 5)I CRT Pit C Ph tt E il Y IYOULM—IffllfUEIL IUUBBBLR ~V Cart )csssso Jtslsac'c RIIRS'M P l ~ SET 12 C»cd«al asoT CB .Dasao giga aa ~ S ~ raL'LC C.oaa C~SZD S tt ~ ESZS74'B -- RttttS~ RLol I 6 Cable T O«o Daslo EECH STSTCTI feats 080M)f5 KRRY IIUC|.EAR 0 Afft c ~ tl vs e Data< a~Vs Sr roo rarBEErrr0 r C» 4a 1 BPH-IT-TB-EKN-OHQ. This modification involves wrapping the division I conduits (listed below} containing cables shown on BFH-IT-TB EECN-O, sheet 1, for RHBSiT pumps A3 and C3 with a one-hour fire-rated barrier in the intake pumping station, where 20-foot separation or a three-hour fire-rated barrier does not exist between redundant division II cable trays for RHRSà pumps B3 and D3. Conduits: 3ES1580-I 3ES1582-I 3ES1590-I 3ES1592-I ES86-I ES82-I ES81-I ES87-I APPENDIX R CORRECT t YE ACT I ON PRWARm: PeviF. m: DAm d /P ez O62166 02 BFH-IT TB-~P ~ Co II ~ ~ ~ / cr s \ LI r Cl 'x c «n O 'c> Z 4 2 oo (n ~I J V rl g rl or rr ll rr rt X Vo cr ~ v» I n ( ~r sr ]I ~ ss « y 'r N ~ Jr ~ « 5 ~ o oo r ls ll H oo r 55 rl lo oo c~ tr Co Cl 55 rl Sl S'l ~o. ~ ~ 5 Vo r ~ I u sl rc J IC cr o). ~ CL l. 0 or 15 c~ X oJ Cocr)IVII An ht C< 0 ((('V S~ hfrlcr ~ I Irr.( hl 1 j/' I (I.l"~~s F.l'V 'X ' to o N)lre Qx /,' ~ l ~ s;I 2(QQ . i I? I'V llsgls A 'V'/ I I'..c ore hl (r.z ~~zhb.. o ',g~ I I?I'V II~S. ~ I ~~ ". "oo'e A' LI. V Clc )w C o/ I s 'o (i ) l Ihi 5 5 rhino(V Clsso«e /yp,$ . ~ (r-- 1 ls'l 5 5 5 5 ' rN LLJIV also'wc / Iro- I - zc'S 5 5 oc Co II~ ( V CI 5~ e P fr..-h- t I) 5 5 / ~ I/o IC (V Clr)«c lr... 1 ~ «i Sor Ilhlf V CI o,.or '(r." I- I 'l I I ~ s.lr I V Ol.'o Ifrv- I ~ Sf I ~ SIS f T CI ~ s.oc I(rc ~ l -BA r F55. i;.g I lr S a 4 gygPPI, ne( t(IDIX R UUl ~ „, REACTOR 8?iTLDIHG RLACTIVITY CO((II(OL RPS ) CAD .".T'IEN 5 «- Uf(OMNJ ('IPR( sNQ EAI( P(ANT ' ~ Ihllr+ Wio~ ~ Cr'C I IVK ll I?Il IIC 1 ~ ere 1ulhv~>., I ":I:C I I e . Bg o 's ~ o ' 'or ~ ~ ' ~ t CABI.E t RTSPD>ISZBtt 6 IIOUIING ~ r SEE r,> a>l kl TOII If EOVIPMEIIT. CABLE5 BIIE'U OF I CORR'EC'f LYE OIICCT >>RCPARER Ill2LtKFL IIYIKY~I QLVEQ ILUTE BETE ER ELI - ~ I-? S 3 caO) A IRPZO TA ~ ET 13 CL lc'al Oa> ECB Dssa> Plpf t>e>e T~ IT>gs+~r i e R>tae'I IO > r 'IOTEO> t~() ~loses > l~p9 I! Clnelv.l e>naa Z~iu ~ . ~ ~ LIB- 3c20>B IRP281-ZB :>K.T l3 CsnLg EEB Dc>sffyfs nsess 1 +Pr P g ~'stet> IO C~k '.I Ts 4L~ ~hIL>JIIP E Fhc corrcctevc oct>on I~ Lc PIS-3. P-24 LRPZO rA BET 13 C.ehlssl o, Oe«s Dent >>eee L>a» roe p>e>e Pe(n Io esse APPEIIDIX TI It>re P>r REAC'TOR BUILVIIIG Ores p»re reen REACT lY IT Y CONTROL R>r> ITP3 CRLI Da e To>te ) SYSTEM h ~ teen BROMHS I'CRRY )OJCLCAR PLAIfl so Ie! Dae>>5 It 1> Ike ~ bAC t ea Ptlt 'll IIB RC B>e»aC ': f>ccLI ~ ~ h' I This equipment and .its associated cables are not required by the,final functional «r1teria. Therefolc', no ful (lu r consideratinn is required. ~ y ~ ~ APPENDIX R CORRECT I YE ACT I Ob BkL:I'hRL.D: - - ' 0 BF T-RB-'RC 1-.J2, sheet 1 of 2 '... ~,'... ~...', ~ '..~ In order to show compliahce with the Appendix.R criteria'for required, circuits'whose failure te operate could adversely. affect shutdown capability, justificaBon'is provided below for (A) not requiring separation-of the power supply "cables to Reactor Protection System (RPS)'. logic.an) (B). not.requiring separation qf the cables from the RPS logic panels to the Hydraulic Control Units (HCUS) of the Control Rod Drive (CRD) system: I For A and B above, the following design requirements. are=essential to the justification analysiq: 1. All wiring foz'the RPS outside of. the enclosures. in the control zoom is. run in rigid metallic conduits used for no other wiring. (refer to section 7.2;3.10 of the BFNP FSAR). The RPS and CRD HCUS are fail'afe (scram is initiated) on loss of power.. 3. The-CRD 'HCUS require control'ir to pull control. r'ods. Since the RPS s'ensozs are routed separately', 'the~gic..will.function for al1 but the.control bay. fires. ~ ~ ~ ~ ~ ~ ~ i 5 Scram time is less than seconds 3.5 for 90 percent insertion'of.control..rods,' : ..6. The. power supply cables from;the RPS logic panels to. the. HCUS.are pouted:.in'separate conduit from.the . power return..cables. 4 r For A above there are four failure modes for. the logic'power supply cables; they're! ~ ~ ~ 1 Ground short, "- " .. ": '" ': ".... ''ot 2. short',. ~ ~ ~ ~ 3. Open circuit, \ ~ 4. Line short ~' \ APPENDIX' I i ~ -'-.CORRECT ~ ,'. I VE ACT ION '' ~ ~ PaEmED: ~ ~ ~ I - ~ Palms: 4 ~ ~ BFN-IT-RB-RC-l-J2, sheet 1 of 2 BFN- -RB-RC-1-02, sheet 2 of 2 Both the ground short and line short will trfp the cables'ircuit breaker which will initiate a scram on loss :of power. The open circuit failure mode will also initiate a scram on loss of power. The hot short failure. mode can only impose another RPS power supply on the failed power supply cable; therefore, the logic circuit is still protected from damage by qualified trips of the power supply and will function to disconnect power to the CRD HCU's, thus inducing a scram. For B above the cables from the RPS logic panels to the HCUS provide power to the scram valves in the HCUS. This power is removed to cause the HCUS to insert the rods. If these subject cables are involved in a fire, they will degrade while the conduit is still intact. Because of this degradation, they will either open circuit or short to the conduit, either of which will remove power to the HCUS, causing insertion of the affected control rods. Refer to figure 1, attached, for a block diagram level representation of the power supply cable connections to the RPS logic and of the RPS logic cable connections to the HCUS. P APPENDIX R CORRECTIVE ACTION fhEFARED: PEVIWm: DATF.: 4 C>l < BFN-IT-RB-RC-1-J2, sheet 2 of 2 0 arm-IT-RB-RC-1-Nl This modification involves wrapping the division I conduits (listed below) containing cables for LIS-3-203A, LIS-3-203B, PIS-3-22A, and PIS-3-22B shown on BFH-IT-RB RC-l, sheet 1, with a one-hour fire-rated barrier in the unit 1 reactor building, where 20-foot separation or a three-hour fire-rated barrier does not exist between division II conduits containing cables for LIS-3-203C, LIS-3-203D, PIS-3-22C, and PIS-3-22D, respectively. Conduits: lRP52-IA 1RP53-IA 1RP54-IA lRP277-XB 1RP278-IB 1RP290-IB APPENDIX R CORRECTIVE ACTION PREPARED l ~ cv t'A PATE 6'H 8'z. 062l66.05 This modification involves wrapping either the c'onduits (listed below) for FSV-85-35A and FSV-85-70A or for FSV-85-35B and FSV-85-70B shown on BFH-IT-RB-RC-l, sheet 1, in the unit 1 reactor building where 20-foot separation or a three-hour fire-rated barrier does not exist between the conduits to be wrapped and panel 25-25C or panel 25-25D. Conduits to be wrapped will be determined by field survey (e.g., ease of wrapping) . r Conduits for FSV-85-35A Conduits for FSV-85-35B and FSV-85-70A: and FSV-85-70B: lRP222-IIIA 1RP437-IIIB- 1RP215-IIIA 1RP429-IIIB 1RP207-IIIA lRP419-IIIB 1RP206-IIIA 1RP423-IIIB I APPENDIX R CORRECTIVE ACTION PREPARED 7 D /@rnid fj REVIE ZP: BATE' Z Z 062166.10 :0 0 0 v n I .0 CI . jr. 'n O C 'al J o ev J 8 a a $ 3„ H Ih n 1 CI en vl V vl J 1 TI Vl 41 ~ CO ~ ~ h C ~ ee H 11 v v ~ e ~ v n n h etl n 'n CL ~ v el v r Ce e( n n Ji CC a ~ & h. X ls Nle CvMTI,I I(('V 1 v 1(~Ic r lre-.l hl e (I.I-- W III'T Le~ u.IC) 1 ee«1 . 111 2 A r', l.leM 2C«U lll'V lie)le r I'eve:.eee C h1 (I'L =- EC.Q.. Clvh 'ee' p, ~ I'.r.r.e,e r Yel > CI ~ (V ('.Ic Cevr. .~/7)Y ~ (C.S 1 ~ 14) < I ,p. 5 5 .5 tkry( V CI~ Le« c (err 1 ~ lS I Cl 5 5 5 / 'I I-15]V Cl.eve ee, IC T 1 ~ 24) kl 5 5 5 'C P N. I'I ClrC «C i''.~.'A'h'. r'y ~ ~ (C.- a ~ O'I) ':y. 5 5 g 5 J v CI(( V CleC vt / ~ ~ '' ( z ~ I 14) I'II 'Pl (V rl '(CS-I" I- CS) ~ 1:'I V ~ ~ 1 Tl IC ~ . I ~ 'll er «r r RI. I T e', g.. ~, ~ / r r l '(c-. - 1 . C~.) (rT.f "~.h 7 1 SVHBOLSc 5.. (vlcrhCIm Nil (.'~g4ig II V ~ >II Tnh .7 II( .. I(v 1alarocl eon h('('(WDIX LJND~ R REA('TOR B(jI(.DING I(l:A( TIVI T T COH1 l tahe ~ ~ Csas too te> ~ Ie roon Es baisi APPEHOIS R Ilare sr> e eo REACTOR BUILI}I}}C Ooe ~ s»to re<»'are REACTIVITY CONTROL IIPS CRD Oeas Os>go f SYSTE,N Casts ROM}}5FERRY HllCLEAR PEA}fi tt.CI 4 O„sa5 fts ~ fehtt.ut ' SfN ff25 RC«Z ~ ~ h' t ~ or«se .e )o" J e e ~ ~ ~ ~ ~ ~ ~ ~ e I * o ~ i ~ ~ e :tl ll~ BFH-IyRB-RC-2-:J 1 This eq«lpmcnt and its. associated "cables are not required by the Sinai fllnctlonn 1 criteI ln ~ ThereCnrc, no fu~ ther consideration is required. ~ g APPENDIX R ConaEcvtvE Ac T l ON A REvlLwm: PyE: ~~< 8'< BFH- IT-RB-RC-2- Jl . ~ !. BF - -RB-RC-2-J2; sheet 1 of 2. ~ 'n order to.show compliance;with the Appendix R 'criteria for req'uired .ctrcuits whose, failure to operate could adversely affect shutdown capability, justificat'ion's.provided. below not " for (A) requiring separation. of the .power supply cables .to Reactor Protection System (RPS).'logic and (B) not requiring'separation of the cables from the RPS logic panels. to the Hydraulic. Control Units .(HCUS).'of the, Control Rod Drive-.(CRD) system. . For A and B above, the following design*requirements are essential to the Justification.analysis:. " .'"'". I. All w'iring for the RPS outside of the enclosures in the control room is run in rigid metallic conduits used for no other wir.ing (refer to section.7..2.3:10. of the BFNP FSAR). .. 2. The RPS and CRD HCUS are fail safe (scram is initiated). on loss'of. power. 3. The CRD HCUS require control.air to pull control rods. ~ ~ ~ —. 4.. Since the RPS sensors are routed separately, the logic will:fUnction.for al] but the'control bay fires.. .5. Scram time is less than.3.5 seconds for 90 percent insertion..of. control rods..'.'. ' ~ 6'. The power supp1y cables from the'RPS logic panels to the HCUS are rout'ed in. separate conduit from'the . power return cables, For A above there are four failure modes for. the lo'gic power 'supply cables.;. they.,are:, 1.. Ground short; . '. Hot short, * ~ ' 3~ Open circuit, 4.'ine short. I' APPCNDrX S t -.CORRECTIVE ACTION r "' ~ ~, "/'( ,. fhapma>: ~ ' Rerrem: D~: Yra Y~~ 1 BFN-IT-RB-RC-2-JZ, sheet 1 of 2 ~ ~ ~ . ~ ~ ' 'O. ~ . ~ " .' ~ ~ BFx-. IT-RB-RC-2-J2, sheet 2 .of 2. . ': ~ ..Both the ground shortand line. short will trip.the cab'les'ircuit breaker which wi11 initiate a.scram on loss of power. ~ * The open circuit failure mode will also initiate a scram on loss of power. The.hot short'failure mode 'can only impose another RPS power-.supply on the: failed power supply. cable; therefore, the logic circuit is still protected from damage by qualified trips of the power. supply and will function to disconnect power to the CRD HCU's, thus. inducing a scram'. For B above the cables .from .the RPS logic panels to the HCUS proyide.power. to the scram valves in the HCUS. ~ 'his power is removed to cause the HCUS ta.insert the rods. If these subject cables are involved in a fire, '-.they will degrade while the conduit is still.intacf. Because'of this degradation, they.'will either open circuit or short to the conduit, either of which will remove. power to the HCUS; causing insertion of the affected control rods. Refer to figpre. I,: attached, for a block diagram leve1 representation of the. power supply cable connections to. the RPS logic and of. the. RPS lhgic cable connec'tions to 'the HCUS. ~ ~ s ~ ~ Y ~ ~ ~ ~ J' 'L ' "~ ~0 r 4, ~ fl ~ L ~ ~ I ~ Y ~ ~ j \ ~ r APPENDIX R Y ~ ~ '. ':.CORRECT I VE ACT„ION ~ ~ REWRED ~ r . PerIem: ~ ~ E~ "Y BFN-IT-RB-RC-2-J2, sheet 2 of 2 This modification involves wrapping the division I conduits (listed below) containing cables for LIS-3-203A, LIS-3-203B, PIS-3-22A, and PIS-3-22B shown on BFN-IT-RB-RC-2, sheet lf with a one-hour fire-rated barrier in the unit 2 reactor building, where 20-foot separation or a three-hour fire-rated barrier does not exist between division II conduits containing cables for LIS-3-203C, LIS-3-203D, PIS-3-22C, and PIS-3-22D, respectively. Conduits: 2RP52-IA 2RP53-IA 2RP54-IA 2RP277-IB 2RP278-IB 2RP290-IB APPENDIX R CORRECTIVE ACTION RE| ARED. 7~ n ~ Wi" R&'IENEDl DATE: 062166.04 -BFH-IT-RB"RC-2-Ml BFH-IT-RB-RC-2-M2 This modification involves wrapping either the conduits (listed below) for FSV-85-35A and FSV-85-70A or FSV-85-35B and FSV-85-70B shown on BFN-IT-RB-RC-l, sheet 1, in the unit 2 reactor building where 20-foot separation or a three-hour fire-rated barrier does not exist between the conduits to be wrapped and panel 25-25C or panel 25-25D. Conduits to be wrapped will be determined by field survey (e.g., ease of wrapping) . Conduits for FSV-85-35A Conduits for FSV-85-35B and FPT-85-70A: and FSV-85-70B: 2RP206-IIIA 2RP419-IIIB 2RP222-IIIA 2RP437-IIIB 2RP215-IIIA 2RP429-IIIB 2RP207-IIIA 2RP423-IIIB APPENDIX R CORRECT I VE ACT I ON PREWnED: -7 rent REVIem: DATE: ~ r8'~ 062166.11 BFH-IT-RB-RC-2-N2 4 ~ .C 'to I o V »I V tD 'X ~ fr rn na 1 J ot 0 S~ V o'ot tt ~ »1 »t n V oot tt tt do o N l tr g M )t 4 ~ » v ~o to H tt ' ~ r o v H ~ 'r , \ V eo f„ A rt tt 'I ~ v o. ~I rt ~ ~ ot I oe J tf. v CC ~ 0 X E~ I KPrr Cothttotlt Ao . h dg ad t P.IV tlqlo ' r I't e>o.oor C 11 / >. V ~ o r ~ MvtV Clttov» r g (r„- 1 ~ IA th.olV I:los~» Crr. d ~ tA 5 5 Ll3JV CI r» o ~ ta ~ I ~ ZS) r ~ X'i r i'r i . l> 5 5 = ~ o ~ I(,IV I I ooor (r rv I trr) I 6I ICI ~ I Cot ~ t ~ Cy., I Pt I I I l.l. 'I f C'I,»...r Itr... 1 ~ 1h) 1 Ir.V ~ f5.Svh ' i7 I ÃHUOL5t r:V IIS dnh III ... It [~I»re»lm o tlt'I'lttttlX tt oo o Uttl REACTOR BUtLOlttG ttCACtlVttY COtt(HI'L cps f canto s>51''N *,~'> r NouNS rlRRS o WOLhR PthN ~ g dgdt jIG.»o o toity, littt tt'Rl'IIC 3 ~ry Lh r ~ r ta.iLQ ~ t el as Ia) li I'. h ~ 'i I Chebf, t Rtsrollstol.t 8 es ROV'I IRG gr,Lul hT IOII r SEE \ If 'WVIPNENT CABINS . OIICEI CORRICf IYE. BIIEfT, I'RfPhII fA UVI5UKB ~maLYJP M)@YE.Q W VillKH..333IKRhCIlQH IIlhUKQ Kfuuull ~ a ~ c,fb a ~ L[5-3 ~ 203A 3RP2D. IA SET 13 C l«:I 0 ogl 1 '.I5 - ~ 3-203C 3RP94 KA 5 oi l2 "."+ZAN;-i l.l5 - 3. 2O3 B 3nP 25'- IB IIOTf5 I LT5- 3.2o3D 3RP319- shoal C..l;,I KB'l I. ytw cetrcelovc aelooea I~ bc - 5. 3 22.A 3RP2o- lA 5Kf 13 c 1-s «a Ifb Sos( ~ 3gtrtrde Iailcsa fer il ~ ullcr ~ eleonS atc n an I +. ry"*.v~ 3 r ' cpncroliced in ibc feIIoulohI PJS -3 22C 3f t'ats Qatao 11 b dgbs Iatan eirrcclorc hob.C, er D ss eccl Ssrsa ~ nd bl ) of cali ~ ts C os Ona o Oaree used ~ Otsls rnc alstv I nvrabcr Pere ee Ii bc referenced. (a.c. TI a4 fat cvecal'ooc asl en shtobca br'b Othe ee e C t l ehl e ~ ah»li eblbe ned re at ~ ~t3 all a«tealuc ~ alorsa oOI ba Sacs Jc ate:feed ee llosl abaci ) aao Bells * y lee ltoqh er ',eol s ~ ocoron.sir Rsr'a f» abe aeape~h A abe n~e ~ at beta ~ etqassag es oon f» Ibc aee e ael o ve atro eel.~. Tl» r«er~.'Ll ~ eel~lao ra@ay 4n ~ ore ~ blc I» Oi. Oau beers ea J:I ital » a jebel;I+a1.$ + reer dvtat or \ Oet, Dont sWot) 'eseal o "lettre eton lt r k ~ no basso APPEAOly A s iles( r ~ K Ml REACTOR BIIXLD1RG ~ I* Oioo Qe(n roon e REACTIVITY COHTROl r ftrs RP5 CRO STSTE'H Oa s fatso $ re<> ~ ORO'4HS PLAN1 ccs f CHAT HUClt:AR friy T'r ~ ~ ~ ~ ~ ~ ~,' -'..1 o ~' ~ ~ Ij () Il'll B F jl-,RH- RE-5- J 1 '0 This equlpmcnt nnd its associated cables nre not required by the final functional «riti via. Thercfovo, no fuvthnr consideration is required; I ~ l APPENDIX R COAREC'T l'YE ACT10H BiLi'NEED: I:.VtENL-O: ) V gATE: 4/Zlg BFH-IT-RB-RC-5- Jl BFN-IT-RB-RC-3-J2, sheet 1 of 2 In order to.'how compliance'-with the Appendix 'R criteria for required.'circuits whose failure to operate'ould adversely affect shutdown capability, justification is:provided.below for (A) not requiring separation of the power supply cables to Reactor Protection-System (RPS) logic.and (B) not requiring separation of the cables from the RPS logic panels to the Hydraulic. Control Units (HCUS) of the Control Rod Drive (CRD) system. For A and B above, the following design requirements are essential.to.the justification analysis: 1; All wiring for the RPS outside of the enclosures.ih the control room is run in rigid metallic conduits used for no "other wir'ing (refer to section 7.2.3.10 of the BFNP FSAR). I 2; The RPS and CRD HCUS are fail safe (scral is initiated) on loss'f power. 3.. The CRD HCUS require control air 'to pull control rods. 4. Since the RPS sensors are routed separately, the logic will function for all.but the control bay fires. .'. Scram time is less than 3.5 seconds for 90 .percent. insertion of control r'ods..'- -. 6. The power- supply cables from the RPS logic..panels.to the HCUS are routed in separate conduit from the power retorn cables. . ~ ~ For. A above thete're four failure modes for the logic power su'pply cables;. they".are: 1. Ground short, 2. Hot short, 3. Open circuit, . 4.. Line, short. APPENDIX R . '.CORRECTIVE ~ I': ACTION ..- REPARED: ./" PerIem: r ~ ~ . BFN-IT-RB-RC-3-J2, sheet 1 of 2 I ~ ~ ~ 4 ~ ' : B T-RB-'RC-.3-.J2, sheet 2 of 2 ": ~ L ~ ~ Both the ground.shortand line. short'will .tr)p.the cables'.circu$ t breaker which:will initiate a, scram on loss of power. The open circuit'ailure mode will also initiat'e a scram.on'loss of power. The.ttot shor't failure mode'can only impose another RPS.power. supply on the. failed power supply cable;.therefore..the logic circuit is still protected from:damage by qualified trips:of t3e power supply and will function to disconnect power to . the CRD HCU's, thus inducing" a scram.'or 8 above the cables from.the'RPS logic panels to the HCUS provide.power. to the scram valves, in.the HCUS. This power is removed to cause the-HCUS to insert the rods..If these subject. cables are involved in a fire they will degrade'while the conduit st'ill '. is intact. Because of this degradation they. will either open .. circuit or short to the conduit, either of which wi.ll remove power to the HCUS; causing insertion of the affected control rods. ~ ~ * - Refer to figure 1, attached, for a block diagram level representation of the power supply cable connections to the RPS'ogic and of. the RPS logic. cable connections to-the,HCUS. ~ ~ ~ ~ ~ ~ ~ r ~ 'LL'~ L ~ L ' r n. ' oi. r ~ I ~ * ~ I L ~ : APPENDIX=- R ~ ~ :.CORREcTIVE At:T)ON ! L , PREi ARED: '. RVIem: ~ ~ DA~: dZrs g~ r BFN-IT-RB-RC-3-J2, sheet 2 of 2 ~ ~ asm-IT-RB-RC-3-ml This modification involves wrapping the division I'onduits (listed below) containing cables for LIS-3-203A, LIS 3 203Bg PIS 3 22'nd PIS 3 22B shown on BFH-IT-RB-RC-3, sheet l, with a one-hour fire-rated barrier in the unit 3 reactor building, where 20-foot separation or a three-hour fire-rated barrier does not exist between division II conduits containing cables for LIS-3-203C, LIS-3-203D, PIS-3-22C, and PIS-3-22D, respectively. Conduits: 3RP52-IA 3RP53-IA 3RP54-IA 3RP277-IB 3RP278-IB 3RP290-IB APPENDIX R CORRECTIVE ACTION .PREWaED: REV Iem: IlATE: lE 8'z 062166.03 BFH-IT-RB-RC-3~ BFB-IT-RB-RC-3-lQ This modification involves wrapping either the conduits (listed below) for FSV-85-35A and FSV-85-70A or FSV-85-35B and FSV-85-70B shown on BFN-IT-.RB-RC-l, sheet 1, in the unit 3 reactor building where 20-foot separation or a three-hour fire-rated barrier does not exist between the conduits to be wrapped and panel 25-2SC or panel 25-25D. Conduits to be wrapped will be determined. by field survey (e.g., ease of wrapping) . Conduits for FSV-85-35A Conduits for FSV-85-35B and FSV-85-70A: and FSV-85-70B: 3RP206-IIIA 3RP419-IIIB 3RP222-IIIA 3RP437-IIIB 3RP215-IIIA 3RP429-IIIB 3RP207-IIIA 3RP423-IIIB APPENDIX R CORRECTIVE ACTION PREPARED: 7 E REVIEWED: ICE: 4 r'H dPz. 062166 12 BFN-IT-RB-RC-3~ Failure Modes Analysis for the RPS System f g ~g ~sons rf c~tr lay $888 Ps're use~ S<'re ~S RPS Pe~~fs 8 Bc ct(uP R B~k~p 5g ytcg~ Vss!VCj sc.~ vd& (sr si'c swot &ouhg ~pt~ R5'- 25 g,y- 8 v~(uo$ ) >~6~tu~) x5',', ~ ~ ls ~ ~ ~ s ~ ~ ~ ~ ~ ~ ~ ~ (es)'a~Sf'if fcoCtssr tfCl4$ PRST~f''essc4oe H Cn nero t ~ Tu>L>ne Gui>cking ~sr'rea a's ~ Fcv- 3b~l Figure 1 RPS Block Diagram Scram = (IA + IIA) (IB + IIB) 'a ~I et .C «r Le ce r t v ~ ~ i «n O )$ . Z C gn jn ~ t» n Jn gr ee ee ale et ve ve ~~v . ~ ep at ~ . v ~ V ~ e ve ve ? 7 ct Ct J« ~ ~ ~ a ~ ~ f aa tt 4< V 'p ~ ~ ~ v 'fl Vh et h n 7 ~ 4n ~ \ ee ee n ~a. ~ ~ ~ v+ te n OC ~ e/ ec ea. Je n ~ c Jc J 0 g T ar 15 ea la eie'rr Ao. CVMtatfI ,. Itl III'V ) ~ )t,)cr Yig F aa I1 t e' (au~ Jll ear ttf'V le a vtelce I eer1 !SI Hj Jam.Zn I] . ttl'V t)ella I'a ~ .,aae C, ;ihip'~. ier 4'I - 0 fc.h]. . aae .e''a. g ea Ie)'V ~ II «tl a :,qy "... Pxx~, i'; ~II'1 >. ~ ZZth L).a]V C4 ca»c .(a,~y/g.+,"a a~ (tr 111 ea I H$ HZ l gt ' v e','aa ~ I tie«a] V Cta~r i « I(r I ~ e$3 tl! At HI r Ll.e]V I:laea«c X .y.i lr.- ~ 1 ~ ze) Ht Nl 'aa 'v' LI« 'l'I Cta ~ «C ;rga~, 'ra tr.. 1 t't) / p,'t HI Hl II] ll:]V C)et«r I - )4] Hl Hg Ht 'Ih: ) V Ct a»ar (r ~ I ~ e=,l t I HI Ht Ht Ht .I ~ eg ) V ea,e.t lr . s Ptl Hl Hl Ht Ht LI )f e 1 ~ ga ~ Ht ~ (r" ~ I 3 te) le I I«V- P.Se. 5rh SII]BOLSt ]»ttrtct~ Hrt ~'N4 r:V ter Vteh ttl . tt» tglcrcclun n]P « e ~a»»««a « aa e ~ e v .C ~ Le D 3r l gr c eft gn $ eI 0 VI ve VI V ~J gp vf ~ ~ pv II J v» I J, Iff vI CI g e J ~ '7 ct c N ~ e H~ ~ n n e H ~ e v V v'g IC I/n V ~\ p 7 VI n n r CL ~ n 4 ec el vl n t v( ec Jw h. cc 4.0 X 'C IIv fVQe c lv ..l -rf3 Hl HI 4 ~ e/ / I«lv rl I-l / r, q~; 'e~g';x e! H% HI l/Jc ~ r A hl HI HI JI '/4 Y .r e ~ al. I V Cle~~c lt;- I-H) X Hf. HZ III Iv) lV nl I ee' les I Pts 'HZ Hf HI I l/V F "5/h Ht Hl SxtIDOLSI fcl,/eel~ @el f.'~cjenf r:v w/ vugh gl . Il~ galrracleveI nl'Ie(II01X R Hl TURGINf BUILDIffG fll:ACflV1IY CfINf f ' 0 ~ ~ ~ f s ~ s v as r 'va 'Z v s 0 .C /j =O a r 4l ~ « 1 J sr » ~ g tn ar rl ! r vs $ vs ~ sn ar r >v. ~ s ar ar aI, al I 'X » h va 1 )s ~ aI ao r~ sj ~ > s ~ s ~ r aa ~ ss + a aa ~ ~ a ~ iv 'n n rs n n P 4 r j n h n aa 4 ~ ra rI Jw asc J ~ ~ 4 sj sJ > jJ g >I N'.. rrhs«SI gn I .b ~t2a 4t. . 4t ttt'T L~ @sacr /Y rP! hg 1+rgt hl r n). ReT ts«uiaa;s I ~ sr\ IR Ll'i.'b=20nvtt... R'I'T I\abls Iss ~ C sss g hl ssa V (I'.IG. 3M2h), IIIV alvlas ). l so j ssrr Rl ' If1 0 =2245 s- ~r''I / sa: I v Cls as4c . 'P, Ib„tv Clsa.ve ~" ~ s ~ 1 ~ a $3 NK„HI ~ .. I Ql ~ ssc 8 IT :, gx-.',: 4 ~ Ra) al Hl Al / v II-ss CI / p sj''g / r,'/ I ..a-q'a$ hl lit N tlat tlat ttL ttt, 1'I 'I V CI ~ ttL str ~ I ar) I NL ) ~ ISN'T a'a a ss IIt .1411 I ttl ttl ttt ttl II!.IT a'I.s»s. ~ l4t yX 1 aA sll AL tlat, ttI IrT.VJ 55h Elt SY ttBOLSa 5 .. Iaarrrrt'vrs ttrl t/ns*rnt III.. „.. It» fnlsrnatnvs ht'PLtlD[tt R 81~ tttl(IMPAR TURBltK BIILLDItlG ftCACIIVllf CQtt I t RPS $ CRO 5Y.aft'tttttMNJIftttRI t'thNt Ca O„lag Ir r a LilnW'14" ei»» m IIC.> ~ ss Ir - suscc 'I s ws ss gsj ir. ~ ~ I, I I ~" I~ lC..I .. ~ ~ A Cl ' \ ~ .* Cl ~ I It . '0 ~ 0 I ~ It tL3 Ol I I 1 a 0 n n In f0 JF ~ ~ I I - Yl I4 I H n l4I 0 O. I- I- LTTS-3- 44A HI N! ~ ~ a-3-4eh Nl 1 PX ~ 3 2o7 tl! tt? PT 3 201 H! NZ PT. 3 20'7 H! NL Ng LH 3-ZOCI tt! H! I ~ ~ Ta-c 4-ssg Nl H1 ttI ~ 114 64 555 N! tt! ttI WL TL ~ c4- SSA tt! HI xs-c 4-ssb HI W! SYNBDLSC Ã5 Cr4 ~ 35C N1. tlat HZ N!', C lntcrv.ten flItCenIl HI NO [nls n.liras I ~ ~ ~ 'cttDIX R ~ KAC'!OR BttIt.OItt(' ROCt:S5 VARTASLE, ~ ~ g lttSTttut4C tnA11OH \ 0 DROWNS FCRRT hXKLEAR PL%< Da>C I S. tt tg,+,a.'c w I I gn ZT m.tITg l ~ ~ ~ .. -.'rCLO p ~ ' I' I f I ~ ~ e jIjlI CAGK RcsfoRsIOLT, 6 ROUT IRS 'T'I, S'EK r L "Ij~'V'eis< l I 5 0 ce B. Prerodt fire Sorrier I ~ ~ te lb 0 to.. 0 Csee ~ ~ SF'- I RB-PVI-1:- Jl This equipment nnd i.ts associated cables nre not required by the fina1 functional criteria. Therefore, no further consideration is required. ~ ~ APPENDIX R (,ORRECT I VE ACTION Ftirw PFV I LHED I IhTE; R ~ APPENDIX CORRECTIVE ACT I ON PREpnnED; PerIWCO: DATE: BFN-IT-RB-PVI- I-Ml l ~ .> , ~ ~ ~ f 0 ' ~ ~ ~ ~ ~ V I ~ ~ I In 4 In )3 0 0 0 In I Itt I I (3 I I V tl n n IO "I In I )r I I ~ H ) l 3o UT5-Z- 14A ~' V ~" ~ ' ~ ~ f.z-s- Cc A PX- S. Zo't , the clI Pl 5- CCIW I Ht H1 VV ~ ~ ~ V I PZ 3 801 HI Ht At NI 1 I ~ ' I LQ ~ S-204 Nt TIT. I ,I - ~ ~ TE c4.55E HZ AI.. Hl AI, ) ~ TH - 64-555 Ht p TI ~ 44 55A NI, H1 ~ ~ XS-t W-558 HT Ht Nt ~ ~ YNBOLSf ffs Ce4 ~ 55C O Inleioclen IIol Con J HI C4o Inleraslton APPDlplà R REACTOR I3UIl.Dltl(j PROCKS5 VARIABLES INSTRufeCflTATION BROwll5f[RRT bKLfAR PLAIIT fNtitgnt II P ~ AA) t 'lft' sf% Il.lt5 Pfl 2 I ~ d) x' 1 ~ ~ ~ « 1! a I~ (r ~ 'I "i-j ~ ~ CABLE tiESPotloT8lf 9 ROUTING co t N LT 10 EQUIPMENT CASUS GREET CORRECT IV'E StlffT PttCPARf R QElV V N CIST 'IE2hCXIQN NIIMKR ~Vf.W PT ~ 3- 2C17 2R933 SET 15 CILlc ~ s> T+P, O.se>ScPta P„rg, r.'4~ PT-3-1" I . RRD37 . Pl cl lg CsMc Tray - 6>l All a in a'>le 'f )oo, llt8 ~ ss g 11 1 TE -55E col>le ET 15 Cs'go T~c tt 1.1)c '118. 8 ra,t, I)>O,tpSJ4H 2 Les'te Tee. TE- ()>1 55F Col 4 E rt» carrcctsvc oct>m to Lc Os>le tat>a/I 1st lfo salcrsctsotsc otc rser ~ qcncralscc4 in 14, folio»snT ataasc sts ~ esne e' Oooo t)t>~ I Psa h A. ttcrovt Irrolrcd Coblctol Oo1 ~ B. Provide 1'lrc Barrier >I> ~ te Sana C. Ci 11 '8 deaf ~.ol on Oass t)ass P>ers 0. Prov:Jc Fire S«pprccoion h>aa Or«I Anoly>is. s, Pe ~ l ~ TLc cartes'1>vc act>a«a can LC Otal Oe>c ~ ~>st of lLc cL>rc oclieoo or wof ra>ra coo>bit»1 ots tlsaeaofo Eav sas Oer le Tts.s ia s rc Tcrcnev 1 ~ 14 P>eet doscriopl >co ~ ol tlsc co trccloec I I Cclosn. Tt c al ecl no.nLcr ~ aI Os>it ~v>ll Lc orrerd oI Ly tt if P>ets corrcclsec A,b.c.ar D sa «scI 444 Q S ~ 1 oslo ~ es 8 Oea I 0>la ~ acl. O„l) e,c sls 1 Peer> » 11 Lc ref cree cch. (I.a. Tt sic I ~ rtc reste Tls ~ Ie>q>s pteacel s ~ scar».)olr («)L ~ eagayt>1 A aLc ea> Oe>h otqs ssal en f tL» aveacl'vc. ~ t ~ ~al's«T4 reap>«>.L4 ~ ay '1>l» @co tv)pro ~ .Llc Fer alc. 0ai ~ para> J:I: «:» o,,r0»sl rear t Oea O»)t ls ~ ~ ~ be ~ I~ t)eels re> n I 'it 'ba> ~ I APPENDIX R n ".'-"-. !!* ao~ . KACTOR BitILOING O>ao ., o>sle ro>n'eca PROCESS VARIABLE NBTRUPTENTATIOH Oaas ',Oa) t> t>an '. BROGANS I'EttHY HUCLCAR PIN>t Oaaa>$ 't are Ot> ~ fttt II4tt PVI 2 ~ I r t r ~ t)Lt ~ ~ ~ ~ ~ R B, lf L"." - 8 F H - I"i R B - P Y I 2:- J 1 This cquiiww nt:uul its ns: ucintc'd cnbles nre not required hy the final func tion:i 1 r r it c r in. Therefore, no fuvt.lu r consideration is required. APPENDIX R CORRECT I'E ACT ION Pni.WnLD: PJ'.V I LNED: BFH- I T- RB-PY I -2- Jl - BFN IT= -PVI-2-M I To meet the separations requirements of Appendix R for uni.t 2; "cable-2R937 will be rerouted in conduit. ~ ~ APPENDIX R CORRECT I VE ACT I ON PREWnED: Pe IESm: DATE: - xr- Ez- BFN-IT-RB-PYI-2-Ml 0 „ i )li ~ ~ I N( < ~ :- r ~ ~ I ~ ~ ~ I ~ ' \'I~ ~ CI 'll. Cl ~ ~ 4 . Vi ~ 'i 4 O ltl 'Ifl r It} 'I \ I I ~ ~ PI I I I I I + + n n fl 4 I w ~ n I I I I I Vl II n III II }- I t.tt5-Z- 4c A t.r-a- 44 A ~ r PX ~ 5 ZOl HI NI Pl. HI ~ ~ PT. 5- Coo HI H! HI Ha HI PZ- S. Z01 HI HI 'tIHI t}! }.M-3-Zotr t}I tl! )l! BI C4 55E K t}4-S4-SSS TT.- c4 55A tl? HI XS kt4 558 HL HL 5'fNBO}.SI X5 04 554 HE HZ HI ln}crcc};~ }try ~) HI Hc It }erne}IIIII !P}'Et(Dr}t R I REACTOR 8UIl.DI}ts \ I PROCESS Vht}TAB}.C ~ ~ INST}tVHD}TAT!OH I BROW}lS FERRT }%K}EAR PLART it ~ c ~ I ~ Qgtc I 5'71'I PIIrtlbit.~}I s ZTIl.gt.tm.P~g S ~ ~ ~ e ~ ~ I rf ~ Ie ~ I ~' ~ CAGK 7 Rt>I (ae Ool ~ e I'sais Tla ~ 1raqn r»<<»i ~ < ecocr Oe»» Da» 5 pea» Ds»C ~ ret n » bello LPPE)IDIà R Cia n o»o CACTOR GUILOIHG peo» Deere assn 'ROCKS VARlABLK, Ra '4< I) I ~ ' I » ' ~ 1I l.,: — BF tl- I +8- P Y I -3: J 1 4: the final This e Therefnrv., no fnvtlu r cnns5deration is required. I ~ ~ ~ ~ APPENDIX R CORRECT1'VE IICT?ON B(El%l(LD: Rt:.viLe;n: ~1.'v. DwE: to~4 O'8 ~o BFN-IT-RB-PVI-3-Jl FN-IT-8 -HVAG-0-MI To meet the requirements of Appendix R, cables .ES3912-II, HS3795, ES3?96„- ES3913, ES3914, ES1400-I,. ES1293» ES1401, ES1294, and ES1402 will be rerouted in conduit as necessary to provide the required separation between the control bay and cabling to water chillers A and B. Cables E81240-1 and. ES3740-II will be rerouted in conduit as necessary to provide the required separation between the control bay and cabling to water chillers 3A and 38.'PPENDIX R CORRECT I VE ACT I ON .PREPARED: PeriEWCO: BATE: BFN-IT-RB- HVAC-0-Ml '1 ~ ~ ~ <+ iw ~ o.$ '}'» l. ~ ~ ~ ~ ~ ~ ' ~ ~ ~ V. O ~f s) < LrTs-~- ca,a NT. Nl O-5- 4c A PX 3- 2oq Nr N$ N1 Nr ~ ~ ~ Pr- a- cc % ~ C PI- NL Nr NI 5-2'.M. ~ I< g ~ ~ 5 20c< Nr )t I NT }'lI Tt-44.55K t}I tlr TH-6<-~~a }tI l}I rl. c.l-55A HI }lr N$ . ~ ~ ~ ~ xa -Q4-55c< HI NI SYMBOLS< l<$ C»4 55C N. t'lr NI I~}r.eel<~ llcl Gs<,)<.el Pf He Inta cJ'n~ ~ ~ APPE}}01X 8 TVRGI}}C, ger t.gr }tr,. ' PROCESS yhl}TABLE, ~ ~ IHSTRUp}ENTATrp}t t}ROM}tSrfRRY ht ~ ~ ~ ~ ~, + ~ ~ r ~ ~ ~ ~ l~ ~ h ~ 0 ~ ~ ~ ~ ~ ~ I ~ ~ ~,lr' gV A lL 0 Vl In Vl VI )3 4 A Vl N ,'s 4 IL3 r t d , ~ ~ ~ r n n r0 V I ~r n )r I re H n rJ X' 0. O. I- x 30 ~ ~ I LfT5-a- 1c i LZ-S- CC A ~ ~ ~ PX- S- Row )J I t)I t)T hl Z ~ PT ~ S- Cow YZ- S- gog HI ttf t)E t)I ' L)1- S-Zoo llI t)I 'lI t)I tti TE- C 4-SSK 'T H 6( SSB ~ Tl C 4 ~ 5SA t)E XS tel -SSB XS Ci i 55C 5YNBOLS) Ie)er~tw Rrl C~„4 .i$ t)l t)e I )cree)lee APPC)IDIX 8 ~ ~ fURDIt)L BUS LOIN(i PROM'nR TAO).E JIISTRU)1C)IIAIIO)I 9ROQ)IS I'[RRI KKIfAR PLARI ~ ~ 4 ~ e S'ST Oasg r IlaroOr) ~ <~ ~ r gt'W S'vr !T TS PTT a. ra I, « ~ ~ ~ ~ ~ r co II. h ct )3 c 0 lO c 4 8.3 Ipt c I I 4 c n cc .n 4 I n c I Ic I H cd T 0. C. I I- )C 3o $ 5-S- LI.5 PX ~ 5- 201 tlt tl! Ht pgf Pt 5-2O1 III HE H! Hf ~ r PZ 5 201 I !If Itf ~ ~ c r 5-2OI« HZ It! H! Nt . ~ ".p t 7'E C 4 55K Ht Itf ttf At ~ ~ lH 64-55B H! Itt Itf n- C e-55A gj nlI Hf H! ~ ~ ~ r5 ~ e a -55a V ui ntf XS G i 55C ntt « kYH80LSc tnlcrscl4~ Hot t:a~QeL Ht It« tpptcrncl ppprc hPrCHOtf n IIttRSIHE Otjift. In@ PROC'S VhRlbSLt: 1HSlRUHfItthtlOH ~ cc ~ GROWTHS FCART htKWAR PLNT c ~ ~ ~ bkeg ~ s I c'a,rpQ It »I ~ @ cc 11.th. Fv! .' v. pr I c'r r. ~ 0 r p ~ n «'««p« I p r 0' I( '"l'IPTE5« I I -"Qc I I I. C u.la Circ I rl-il~ 43~ I I«streets o«r Il 4 veetotlira E I I t 0 ooiieets reyoeol I~ rot«et 1 II I «I t (I 41414 ~ l 4 Zaeee it aes;Iolelc c Rc 44 etc tete 1 44c rrlclte I c I I «I 3-:II.4I . I 4 I I. .l I er ~ T I ee 7I seersl 43 4LA««44 14IAc ~c I- R I 0 14 Iotas's 4«st«os) ssl e«s is cs S....I. —. te I r- ccc I 8 (I rcgoierh lo s)cga 13«is I- 't . "r- I L I I C«41441«e«S (ee Ala 4SSaegh ) «0 Qlyo««color II 1-( I n 0%«olhoccscs f00te I cc cp I I «0 oe PI I- I I I a I I 0 cc O eec4 .I e I DPI I cele S Oil l 1 '. e 'Cl, ~ 1 «) rsel c ~ e pe ~c I I II I I SY!1IIOESI I I S I T C&atl r:Ile I'ro IIrear I I ( I c I il I I I Jr'll l LI I I I I I I"" J a rs e.(/ I I I I e 3 ( eEI e'e I I I ( -I I I I I I tl0 ) )I I I I I L-e-- —-I I- HII- -'I J ~ I ( Lrs I ~ ~ I t N.f' Ec ee I es a I r e r «X' I oa I t 43 I II. g r3 I - 1 r. II-' c J ~c 0 0 Il vd a ~ ~l ~s JIJ l v I I l as 0 9 ~ 4&0 '1IIsr sD -III- ~ II- .c lcol I~r41 4ILV 51~II~ 8J 5CA u ——~ E Ss.5 l R.IV 54I JPJ0 IIJ SEC I r~\ t L EI Q j I Wll- Sic«l J«eco BI ~ I N N Vetoer I ~ I V er'l.el«I«acc Bl 3 E 0 ec Soc nolcr R ~c hcI'PCIIOIX 8 1 0 4 Z Z tr or lll.ACTOR BulLOIHG n0 AVX1L'IARY POWCR ~r 5YSTCM I InE t 1 2 Ueerr 3 IIROMHS fERILY HUCL EAR PLAN ~ L petr« I'est. OQ IJ bIII TT RB sr' I t ~ ~ r.v. See cc BFH-IT-RB-APS-1-Ml Manual transfers in conjunction with wrapping of conduits shown symbolically on BFH-IT-RB-APS-1 and listed below to provide a one-hour fire-rated barrier within the unit 1 reactor building to ensure adequate power is available to supply electrical boards required for shutdown equignent in the event of a unit 1 reactor building fire. Conduits: 1ES3930-II. lES3 925-II PP629-II lPL451-II '*lB92-IB PP465-IB PP466-IB "This conduit number is subject to change dependent on rerouting from cable tray system. AP P END I K R CORRECT! YE ACTION REPARED; fhVIem: DATE: 062165. 04 N r,: Il ~ j c tta dhrr >t t(OTfea l. Ca«lv.la I l a4»a»rl'rarr(afa ara ELIa var ~ rem I I. orlrons rrguorad I~ cna«re I sdaIL«aE4 paarer Ia arallaMa .I Iar ~ fiora in r ail Eaao I 4 'building. 4 .I reaalor 5 I Tf nae»al all«lJo aa palla r I s K f. / I K is I sl, »an«sl acV.an is 4 4 "r S II ( rq,,rcd t al 5n tlla cannaaloan (K )ha aaa~cl J A'I I Jab~ (5. R sh«ldaJn taA. r ~ 4 Q la Zl ( S. C»joIL aaala la lla sara(fad a ~ l 4 f «nial to 4all Satal EL%% c (.» alE ..aEa. w((l):a ~a I aria' ' 1 (A«:)»'.LlrK4e«rw I I 4 I I I &I Cskin I I I I a) 1 .. ~r I al ra r ~ I I ~a e I I I c Kf I I p I I ~a 4 ( ~a 4 I I g I * I I T I I P»ayr'YH6ocSL a» L "l 5 ra I g p ~ I N I ~A L ——g)f-I~' -%It a a 1.F I 0 I A I EL SOS 0™ 5 ra s.o D cc Nas.ta ~ 4do khr (30 4 gV 55 I(.rn 8( 3ffi I l~ '1 3s. ID5 \ .e 'r I 4nt daatfi ~a Q >fC Z J O J aa ~ ~ Y I ~5 4 LV'Spalla«a Ll 3fd ~a I /J C»l rrL SLO ta 5 WaLL5( aK Slat(o«n lt 3CO dec n.lc a fl. «S.5 'an naEe tr APPEN>LX LL ra 4 c 5: Daltr PaL,Q(l. bfll LY-lt(L-A'PSE ~P rlr~ BFH-IT"BB-APS-2-Ml Manual transfers in conjunction with wrapping of conduits shown symbolically on BFN-IT-RB-APS-2 and listed below.to provide a one-hour fire-rated barrier within the unit 2 reactor building to ensuie adequate power is available to supply electrical boards required for shutdown equignent in the event of a unit 2 reactor building fire. Conduits: PP465-IB PP466-IB PP459-IA PP460-IA **38180-IE 2ES3l0-I *PP633-I 2ES320-I 2PL450-I *Ttus conduit number is subject to change dependent on rerouting fran cable tray system. ~*This conduit only has to be wrapped until it attains a 20-foot separation distance fran the alternate control power feeder to 4-kV shutdown board 3EA. APPENDIX R CORRECT I YE ACTION PREPARED;~< L . ~n Bl Vr. REYIEWED: 062l65.05 BFH-IT-RB"APS-2-Ml es 0 ai ~ si 'C* its tAil sC stat t:Ss ~ ~ eisa C t: t.'Ae SS ahra ~" 4 l a I e V. sea sic i«is ~e v ~ e 0 « r 4I ~ 1 ~ I r T r dl fstc I es Lsnel ~e Lts, I oe SYl1BoLSs ef I f T .'I l CsaL.t «etio FVC ))»tm I I I stI I I esMc I i$ ol I I I)j I os I I I ~s r I g t I e 544 ae)4 2 sv I te l ) ti ~i I I I I I I I I J l I I l I t- —t- —— I O I ~ i ' is C l s I I 4 e 4i I I l 0 ~s I I 1 its ass.es c 5 as ts' l CL st5s.o t t< 5tlta bt slA V ts N f1 5 S5 'P I t'sV 5LI 4 Bl Wa f' I S ~ tt ~ et c' I t LV 5V) blitt lait 5c 5.S ss tt t sv stot btgtts t t5.S sl APPC))D1X R ti 4\ fIF.ACTOR OU1I.DING re AUXILIARY POWER e $ SYSYFM Uott V UssLV 8 0 sstV lsROWIIS FERRY HUCI.CAR P).Lt) Dst Ce Fata, .C ~ Btl lt ))B.MSQ I te 9 2- 'V. tv~ ~ ~ I ~ s BFN-IT-RB"APS-3-1'il Manual transfers in conjunction with wrapping of conduits shown symbolxcaLly on BFB-IT-RB-APS-3 and listed below to provide a one-hour fire-rated barrier within the unit 3 reactor building to ensure adequate power is available to supply electricaL boards required for shutdown equignent in the event of a unit 3 reactor building fire. Conduits: *3B88-IE 3ES310-I 3ES320-I 3PL450-I PP465-IB PP466-IB PP643-IE PP644-IE 3PP733-I *Sos conduit number is subject to change dependent on rerouting fran cable tray system. APPENDIX R CoaaccTive AcTroN flaws: utee>: IhTF: 4 l8 8z 062165.06 BFH-IT-RB-APS-3-Ml C t n 2 g 2 IC rr.' rv.' p2 9 Ill AT At Ilf III Al HT IIT IIT AT AT Ag ~ T. 11t 11t 11 I gl tlf II! 1 rrc gT AK alt Hr II! IIl 8 'foal II! Irf IIT ll! 5 6YNViALS1 @.... ~ esolm III.I C~. @eh OI 7IIlirsrlioII Appr.lrolx R UBLL'3 ILL'hCI{)A BUILDI NG Dt:CAY IIEAI Rf:HOVAL I OROMIIS I'fRRY N1K1,CtN Pl@I oars ~ S P'0" 4IIe .II)I u arrl 'lr'11$ 'fIIIIR 11r-fl u AA. ~ I '.11II CABLE, t, ~ I >'esto(IOT81.'C? 15 ROIIIING s, SEE r,ha( kT 18 1T EQU? PHENT CABLES SIIED CORRECT1'VE SI I K ET tgapAIICII ~ ~ 'LYQ1XL IILIIfQQi. JllKEXXIQH 8~~ aWBf.K Esses-C - Oaa>(ICS 0.> ~ >coca RIIRsW Cbrit hl Esy5-I, SET Iy C.bi. T" . '„(If3.a.ddlL RHIIsrI I' Aa ESBB-I Essa-T goals 1,B Cble T ~ nc(bc~>1)a~~ RIIROW P~A1 K515 I 5E f I'I >IICC 044> a a 1( NOTES( E. ra .O.a~aO4~ .:- RRIIsw Is.~ Ci Esiao I ~ ESIct I :~,( 1,8 Coblc fiat," na(c~~~(> I Th coereclave act>on Io 'bc 9cce II~>4 4 i. I l 'ES'IS-I S< ll C,Ll~f„ ~>(ats Irl(. C 1 ~ ben for (Lo shieracrona a ~ a sate r la Rllllsai P«w A2 ES88-I SET I c 4 'I~s po(>C B. Provide Flic Barrier r.. ESI(1-I s~',8 @,g.M11.» ESIIS-Is CLQc Tro 8 ((acr C. C>rcv'at Hrdsf >col aon 'S RIIRSal Po~C1 Es lop I, E510t-I 5'ET 11 Csbir fca. Oeseeaea pee>C + A,E 0 a<. Q.O.L~ O. Pro a>le Fire Svpprcssion IVIQSW Pvost C2 ES ll)-I, EsII1-I 5(J>sa l>8 C,bl f 8(nac~e C.9') I HHRsvf Po~E 01 s< aaa~ sac n I'dvlat pro> ((CO p>iaa Analysis. Hi'>«oIS><(> Q,fi Q>0?wc sL i'~i: Section II.13.5.b. (1). of the Functional Criteria requires that one RllRSW pump bt opurnb1e Cor each RflR pomp.: In the RB, three separate R1fR pumps are bel»g relied upon {i.e. 18, 2D,:3C for u»Lt 1 fi,re; 1A, 2C, 38 for unit 2 fire; and 1A, 2D, 3C for unit 3 fire). ~ Sheet 0 indicates this criteria could only be defeated where h and C RHRSW pumps have interactions. Therefore, by rerouting cables for the RHRSW Pump C2 (ES113-I and ES117-I) to meet Appendix R separation requirements in the RB fire area, the cri- teria will be met. APPEND I X R CORRECT I'E ACT I OH REpmED: G. lhvtE m:~4' DATE; Nil"/$~8 BF H- I T- RB- RMRSM-0-Ml ~4 ~V ol P IV m Rc cs ~ o c c E Q c 4. 3 3 7 Pc cl 2 1 OC OC 2 flC g ~$ OlksvF Pa «F A'I I 1 I 1 RllBsrf 9, g AB 1 RQRsd P~ P Ct RNesd I4.F Cx j 1 Illgsvt l4»p Bl 1 1 IFNPsrF IFE I4 F IIINI.Pf P~»F 51 1 1 1 PARsvl 14soF bs GYH8OL5c @. lal«ccl.sa cLI Cee.'4«L ill fl I'+1 UI~all'PCIIDIX 8 «]uIIiIII Oul Q Let c 4'r'fc P~c ~ 0. Stm 11.as cwcA C ir Ea. &mLQ cc9 CABK rLRSPOLLsIGLC Cp ~ ~ r. Lssr A'1 OLE LEOLET IELG I ~ ~ SKK I SLEEK'f OF CORRECT PILL PAIL C R IT EQLE? PPLENT 'CABEK5 ' SLLCLT'PLLLLLikI V e LEtEIE ~QQLK EXQ EEEELIEEE l 5Er L7 Oaa ~ KKB .O so>C.O.ra REIRSM P «gELl E515-I 'Hi. C.4;E Q . tot> tfgi/gol~~ gfc~ow p, >I EBS Q- T. 5Errr + ELLLRSH PvscPCL ES LOO- T. SET 17 "B ~ KE 5 Dose c.%ra ELOTKSI R~>R>w p 2 Es>>I saeE + C.nh.'Il','alle 21u ~~+M~~+~ E. TL>o eorrcclive seL'eon lo Lsc 'kon ELLLEl5H Punp BE 3KD4080-E SEI 17 r ~ I r LL~ Lcr sel >ons otc Trs) generoLLCC4 in Lhc TPLL>4>any ~ I RELRbvC PuM 62 ES Z5SS- TL blusl + ~nsnncrt pea> se 1(LLLi.'SH Puo>E Dl DES +OBO. EI 5ET 17 Egg rs Cs le Trsg Pasta eI/ A. Rerou'1 Involved Cablclsl BELLES'un> DZ. E52t L3 - TI DLroE el >J Ooai 5. Provide f'rre Boirier r> ~ Ia LL>aac C. C:rco:1 Hodifico'Ison Osis r>n ~ I Paste , . ~ D, Prov>dc F;rc Sa>ppressl>on htaa Ol>os Os> u C. Analysis. rs sr ~ Krroc>r EL>e eorreclsv ~ scL>ons can lsc Dao I rlw>a> ~nL ot Llac \La>ac cela>ea ~ os'lif rsct i csoalsino1 an LlicrooC> a I Oooo Oae ~ s 2, TL>i~ aa ~ relerencv 1 ~ t Post ~ dose repl eon n'I Ilia eatrcclsvc e aclaovi. Trio olios 1 nvsnbcs Pa> ~ Oaes> so>El bc prost&. Iy sc if IL>an cos reel ~ re A ~ Q Cs or 0 ' asacl ~ nl Lal 3:I eel>en C as Os>a Oas ~ s wael. Oe>L> vnc shool ns>en\acr * P>ats is.i 'be rsTcrenccl. (i.~ . Tl >'4 Rata ~ «ec>LL c aalson anv>1 ts Loch oi> Deere A ail R as> M o> LL aoL>L bc ae>$ r>ae ~ aJ sll 4> tc>L'ete ~ sla>aa ~LL L s s Jose>:L>c) os 11>al ILICCL,) cu D>st> 'nL I ~ Itt * 'll>~ le4$ A plass>E e» ec I ~ s ( abt ~ >spica\ oI cE>e scar'esnLE> I~ I Pat I. wga~csr'.~ t: i& ~scc1ivc. as>I ~ 4 LC» scars ~ )Lc F» al~ 'L. Ocai PIS ~ I J:I; ~ o;.,r.( l: Ptas de>>4t >p 1 san. I 4 ra>ns Dans ctaste l«w t> I peer> P» ti oaa bail ~ APPENDIX R riots Rassler TUf ~ ~ — — B F N "~>-"T. - R B D C A 0 - 0 j. I 'l'he Drywell Control Air System wi11 be modified to provide a means of a longterm air supply to the S/R valves. This modification is in the design study stage due to previous safety concerns. APPENDIX R CORRECTIYE 'ACTlON PcvtEwco: ~ Dave; ~i~"C 8 ~ BF.H-IT-RB-DCA-O-M1 3.0 SAFE SHUTDOWN ANALYSIS RESULTS'FOR THE SHUTDOWN BOARD ROOM, BATTERY BOARD ROOM, AND CONTROL BUILDING FIRE AREAS Each Shutdown Board Room (SBR), Battery Board Room (BBR), and the Control Building are considered as separate fire areas in the Functional Criteria (FC). Each of the areas has been analyzed to ensure a minimum amount of equipment will remain available for the fire areas defined in the FC. The results axe indicated in the attached tables with corrective actions identified where deficiencies were found. The following criteria was used in the analysis for the respective areas. 3.1 SBRs and BBRs Each piece of equipment was reviewed to determine the affects a fixe would have on the function of the equipment for that specific fire area. The following abbreviations were used to. indicate the effects on the equipment: EFD — Equipment Function Defeated —The required function of the equipment for that specific fire area cannot be accomplished. NPS — Normal Power Supply Lost — One of the normal power supplies (e.g. logic power, control power, equipment power) required for the equipment to perform its function for that specific fire area is affected. However, a manual transfer to an alternate power supply is available. Once all effects were identified, each piece of equipment was then reviewed to see if the FC was met with the following additional considerations for the RHR system: The RHR system requirements are satisfied. provided the flow path integrity for each RHR system in use (see table) is assured. SBRs RHR Pump Operation SBR Unit I Unit Unit 3 Al B>D C B,D A2 B,D C B,D B A B B,D C1 D A,C A>C C2 A,C D A,C D B A C,B>D El A,C B,D E2 A,C B,D B,D F A>C C A 3EA A>C B,D C>B>D 3EB A>C B,D 3EC A,C B,D 3ED A>C B,D 4-3 E52165.02 3.2 CB If adequate back-up control isolation (BCI) from the CB fire area is provided for the equipment required, the FC is met. 3.3 The type of corrective actions required to provide BCI or meet the functional criteria are coded as follows: a. Reroute involved cable(s). b. Provide fire barrier. c ~ Circuit modification. d ~ Provide fire suppression. e. Analyze. The corrective actions sheets correspond to identified inter- actions from the tables. 4-4 E52165.02 J j II ~ . 58R>, BBR~, anA,t 8 Analljs!~.....,.„.l... ~EHDBR=BBR Reac Coo)an I)sh e.(n .I.nhejrllg,. I*«««II«O)g. «III ply «7, p'Bz ~ ~ „.d,'«II«I II gii/i.i ~ R'4 ' ' IJ C 7W «« ~ ~ ~ ««l«li w «a z ~J«l I,~ I I «Al«7M L74 Il ~ ~ l« al'or 0Q1 Gt.I I It UllI1 2 4 S G 0t >L>z — 1 'tI 'L. II, 'LV'.c 2 ~ Cot .'k; ~ir~ 3 :Cm. ~C« l '(r:. 'k . FCV 2 ..'!e . (Ie1 .'Cc,s. lt(w fFQ .'ls~ Yc'(CS FCO i'- t.tt(1 .'.b.x 5 1.!V.». !>tA, 3 ~ l I!/(l Vc> ~ 2. »(n C ~ (« I 3 »/Lt l lQ, da ECY -l7 ? .t':. 'L . Jcs 3 t7 1-:5 ÃC'r .'km. ~ ~ 'l',», Y»s 'few. ') FCY 'tc*. Yre I(C.. ~IL~I '(»;. 3s' ~ l 11 « 'l.", I5'~. 'I I ~ « lfS. YC I. Ye~ 'A F t»D i .3I."-. .'C ~. ~ I 1 (.-.. - ~ I 1 C )'(.. '(»»I .'I'». JC'e. ~ ~ 3 Ia" . 'I'.:1., .'I'r .. . 3'I'< ~ I l. II."~ .He. QC1. I i' LE.t) ~ I I.C tie. de E $'tp 14. Yes.. ~ I I "« . the [<1. (~ I .6u. Des. I'l.; ... t:t10 Ay. .'l»» '(v..», 'I II, ~, ~ \ ~ g I ('» .Ae.. .ta i .'!c... 'I YYS ...'((.1. .6, .VLe h .! Ae Dx . .h. tbL I( I 1!»\; 1tS.. .X I., A I ~ t.4, H 0 5GRS, OGRE> encl C.H AnSlgSia...... I'III. 2. cc. l't ~ ~ I ~ ~ >or'oolsn t 5Igs) em Xn'j e,qrI.'r g. .IC ~ cocci,034) e 'Ila e ~ bc I~ I I AIJIA~ . C» IL .» ~ ~- ra at Mac %&ca '\ Qmg, l~'R ONG M ~M I. IS" tgn Ws. 'c.. ~ (o P .. r:ru . Ao. Je=. . A 3 r; Erc. '{es Pn '{cs. I( , ~ rI.» terr. 'as '{r- F.CV .tre . oc- ~ I 3. /~( ..6~.. ~, ~ Il l.- C.LI .I 4." . J4. 3~~ ,p. (rD MCM I=.C'{ cZ Cc F.D. hjo lt~, Yc'rI 3c.~ 3 EFD, . AQ. 'k. .'{r.s. r:rn Ic' Ao '{r,s .'.(e . Fcv El. D Yr;, rl. '{r s 8 gCp '(rs A~ .Yes.. .:(c ~ ~ ~ I c c"». .r.) e ( 5'.I.s 'I l I I ~ lCV l3- .. (II P. II.'.% .h)d.. L .YC c 3 .I. Y(: pro ..'k . I h)o Yc* FCV C r:. Cr? Y":I t la.. .VCs., 3 LFf? Wd '{e. ..'fr.s. P - Vf.alcr Tnvcnl or<1 Canlrol ~ (tn ~ t« ~ < ~ / tll< ;~)r/r";- ~ .. tnt l d'le +tata( n '.LL PCY I II"~ Iln. 11».. Yc;. flu h EE6 3 Lo L' ,I la .. 3e. 3)a k XEII Dl 1 I I I ~ I lr Ilo „fl( .h. ...C EE.|'. .QL ', Pcl 2 Ef b. .E,I:r I 1((. I k h G Pc. . (55 . llo 14's .1.. I'In Ao.. .'Csi > 1(>. h.. C EJC. PcV Z3, 2 gFD I.lo. .I.l(( C, U.p .111 3 I l. '(" ~A Eh. I I<, As. f.'lr ~ ma. EI:I> 1 '(~r. P I .Y 2 I .(t I;ln C XZa. .+1 Qt h .E.t '1 ....LI.I) Ilf;:~ tin I'lo.. ..'(cs .. h .. ...EEe, .I.U, (> fs i- I> Ilo .k3o '(c Ll h CW. J.1i 3 flo ..'(cs h. .C.. ,EEP. ~ t, 1 liP> I 1.. f'Ln. (cs. } )(> fl C.. EO!. .I~ n EFD I Il I) Ilo. . I 3(> ....h.. 'CE gb I,'(. ~ '(s E.F.D. ll„ .. I,l,t h. , C... LLb'l4:1f.:re H1 I'11. ('qadi I lu (C, ~. h . C.. F EL. I PCY lf>0 tlv. ,'( 5 .A», C LCD. .GL'01. 1.1" 3 III I!u, 'hs ..h. . C ECO l.':.'( 1 I! 'l.;. 'b;. h . E6. .Qi t >I( ~ ." '(<'. I l. ..'t EEJ(. f11. I ~ I (< >in 'k.. . 'k. E.E.(. 'I -. Ij.. .'(cs ~J,ls il. .t1L '(.:.. I)o :!r.f ~ ((:1 h .EE6 J I. I:.I? '(s 5 I!n '(os ... EF6 f.'U I't 't . Wn '(~s. .ECG I ~ -.a 2 Il». 'k~. .h ECO QJ(( I.ln. ..'(c: „h. 0 I I('. I. !1.. ..'.(c.s, Lf.0 ~ tt ~ ~ QO i' ( .Ys h LCd Ili", I l ( tl<, '(s.. ..I?l A. U 'l3 ~ ~ >II ~ ., >.0" h LEI>. ' . I'l f l.. «5 .'.(v. ..h U. III ;1 I I( Y«g A... 11.1 .5BR~, GORs, a(1(l CD.... Anat()si>...... " .. d...... "..(< ALG=GBR= BBR=.C8M .RPV. Water . Inventor g Control. ~ tstt(st+I() sss(.P11g XTs l>5< Isnss ~ SS(SS' sn Sgt(lf g ~ ~ ~ ~ ', s ~ s ~ s" sst ~ 's r» t s $ 't s's ~ s '/, Jbs r a r. a as ~ ss ass s A( DC.I 3(( I pH na UnlI3 A.II 8 Qgc 1. L'r 0 1L(sr, 'lc=. I:1( J- X.E6. 1- 3q 2 ~Yl';. I 1(s xi% I"I<(. 'Ls. $ s ~ ~ I t CFC! 1.!lh.. J5 A '((s 'h. P(((s P .A 2 I, (.(D 3 LE!i 'f(st Qr QII- .(j'.C.Y ~ 1 ~ s I!ht 't . I]Q ..Pu p,C .. 2 .E.EU 1»s. Qt Yn 3 ,F;LD. Y= Y~ ' i I cjlh Y»s. IIta 2 I, .'I ca Yc( 'fe „ 1('(!"~ 3 'l(( . .'(« l Illa', Yr. ) n)il '( ~ Il FCY ( Ll D ..Icss )("p t'r . Y(ss E I'9 '.(rs, 'bs. —l '<».. Yrs .nI/A t I I »/W'l.. rc, -T4 7 2 I '(»( .'1(rs Ih J~ I ll'; ~(r'r .'(». !ass L17 . I CFD I(!II :((-.. . Yes. ..(!Ii) - '((- '(I." t4 12. I'l . .Vrc ..Yc ~ I (a» ,'rc'.. g'c s .:(ys.. 1 !In ...(cs, .uln. -.1h - 13 'I'1 .. '(r) 'I'.",. ~ L»l II/ll '1(IS ..Ill(i. rCY ('1 -52 lot '(e;. .'.(r.~ ( ~ ~ 11'.,'I. !(s i. gc ~ ((r'. !Ilk ..Il .. .r!Ih,. I Q'e .)~t(:: ~ ~ 11 .53 2 ... LI 9 11}s !" 'ss. 11L! Yr 5 ..C .III(la ~ ~ ~ ~ .) 1(" I1 "0 iti '4 5QRs, BORD, a 3 I'6 bnsigs i s 1al ~ ~ Q Ol I M=BBB.B BR=LB=Q I . .Wafer Invent nrem Control .u 714). Vp (& {su ~ < ~ P>/' ~ iu 'I . ~ UWI4 I 'ILl8 A JIL'VW MVl~ 'PP UtllfAL I ) Li ! Ill) 2, I lib 3 Iilh Ye~. I!/IL, I 1 I }D I/I) t? Iil .,. I rb I ~ '. 'Cr.. Qe". gc t '3 Jt.< tt/II 'A.~ 2 tlu fl,. 'I. ..1 1!IA .'dr" Jl 2 . Yc. 'go~ 3 1'c . i(pc .)!IA. 'tc.O ."Vs>Cf< NOuII5 ffrlIY sllIQ(hR Plgif '.I 54cIS t+vf IS v &Ca.l ~ e +lull II.IIIAC-2 ~ e/ / IfcfI