FLOW RATE INDICATOR / TOTALIZER WITH LINEARIZATION AND ANALOG / PULSE SIGNAL OUTPUTS

Advantages Signal output • Robust IP66, IP67 (NEMA4X) field enclosure. • (0)4 - 20mA / 0 - 10V DC according to linearized It is so rugged, you can even stand on it! flow rate. • Intrinsically Safe available - ATEX and IECEx • Scaled pulse output according to linearized approval for gas and dust applications. accumulated total. • Programming can be done by your own crew, with the sensible menu-driven structure, saving cost Signal input and irritation. Know one, know them all! Flow • Very diverse mounting possibilities: walls, pipes, • Ability to process all types of flowmeter signals: panels or directly onto outdoor sensors! Reed-switch, NAMUR, NPN/PNP pulse, Sine wave (coil), Active pulse signals, (0)4 - 20mA, 0 - 10V DC. Features • Displays instantaneous flow rate, total and Applications accumulated total. • The F-Series is your first and safest choice for field • 15 point linearization of the flowcurve - with mount indicators. Especially in harsh weather interpolation. conditions like rain, snow, salty atmosphers and • Large 17mm (0.67") digits for flow rate or total. temperatures between -40°C up to +80°C (-40°F up • Selectable on-screen engineering units; volumetric to 176°F) for safe and hazardous area applications! or mass. • Liquid flow measurement with mechanical • Explosion/flame proof II 2 GD EEx d IIB T5. flowmeters where a precise calculation over the • Analog and pulse signal outputs. full measurement range is required. Also re-trans- DATASHEETTOTALIZER INDICATOR / RATE F112 - FLOW • Full Modbus communication RS232/485/TTL. mission of the flow rate and/or totalizer functions • Loop or battery powered, 8 - 24V AC/DC or or serial communication is desired. Alternative 115 - 230V AC power supply. basic model: F016 or more advanced F118 or the • Sensor supply 3.2 / 8.2 / 12 / 24V DC. D-Series DIN panel mount flow rate indicators. 1 General information The output signal can be a passive NPN, active Introduction PNP or an isolated electro-mechanical relay. The F112 provide very precise linearization of the flowmeters signal. In addition to the average Signal input K-Factor or Span, fifteen linearization points can be The F112 accepts most pulse and analog input entered with there frequencies or values. signals for volumetric flow or mass flow The unit will interpolate between these points measurement. The input signal type can be greatly enhancing accuracy in any flowrange. Even selected by the user in the configuration menu for very low frequency applications is catered for. without having to adjust any sensitive mechanical This linearization effects all displayed information dip-switches. as well as the signal outputs. A wide selection of options further enhances the capabilities of this Communication model, which includes Intrinsic Safety and full All process data and settings can be read and Modbus communication. modified manually or through the Modbus communication link (RS232 / RS485). Display Full Modbus functionality remains available for the The display has large 17mm (0.67”) and 8mm Intrinsically Safe version (TTL). (0.31”) digits which show flow rate and totals. On-screen engineering units are easily configured Hazardous areas from a comprehensive menu. The linearized This model has been ATEX and IECEx certified accumulated total can register up to 11 digits and Intrinsically Safe for gas and dust applications, is backed-up in EEPROM memory every minute. with an allowed operational temperature of -40°C to +70°C (-40°F to +158°F). Configuration A flame proof enclosure with ATEX certification All configuration settings are accessed via a offers the rating II 2 GD EEx d IIB T5. simple operator menu which can be pass-code protected. Each setting is clearly indicated with an Enclosures alphanumerical description, which avoides Various types of enclosures can be selected, all confusing abbreviations. Once familiar with one ATEX and IECEx approved. As standard the F112 is F-series product, you will be able to program all supplied in an GRP panel mount enclosure, which models in the series without a manual. All settings can be converted to an IP67 / NEMA 4X GRP field are safely stored in EEPROM memory in the event mount enclosure by the addition of a back case. of sudden power failure. Most popular is our rugged aluminum field mount enclosure with IP67 / NEMA 4X rating. Both Analog output signal European or U.S. cable gland entry threads are The linearized flow rate is re-transmitted with the available. (0)4 - 20mA or 0 - 10V DC output signal. The out- put signal is updated ten times per second with a Overview application F112 filter function being available to smoothen out the signal if desired. The output value is user defined in relation to the flow rate, e.g. 4mA equals to 15L/Hr and 20mA Pulse output Analog output Communication link equals to 2000L/Hr. The output signal can be passive, active or isolated where the passive output type will loop power the F112 as well.

external Pulse output reset button The scaleable pulse output, reflects the count on Flowmeter input the accumulated display. The pulse length is user defined from 0.008 second up to 2 seconds. The Linearization maximum output frequency is 64Hz.

2 F112 Dimensions enclosures Terminal connections Aluminum & GRP panel mount enclosure + 31 YZ 30 31 mm 29 mm + (1.22") (1.14") 130 mm (5.12") B B 29

115 (4.53") A A 28 RXD TXD RXD TXD 27 + DTR COMMUNICATION / BACKLIGHT COMMUNICATION DTR +12V +12V 120 mm (4.72") 98 (3.86") 26 ZB: Backlight option (With PD / PF PM terminals 26 31 are not available, backlight power supply is integrated.) CB: RS232 CH: RS485 - 2 wire CI: RS485 - 4 wire Intrinsically Safe TTL CT: 25 HB & HC enclosures panel cut-out 24 23 Aluminum & GRP field / wall mount enclosures 22 130 mm (5.12") Ø 7mm (0.27") Ø 7mm (0.27") 21 20 19 120 mm (4.72") 18 60 mm (2.36")

75 mm (2.95") 112 mm (4.40") 17 Aluminum GRP

30mm 30mm 15 16

22,50 mm HD 14 PG9 M20 x 1,5 PG9 13 30mm 30mm 30mm 30mm + RESET INPUT RESET 12 IB: Reset total 22,50 mm 22,50 mm HM HE 11 M16 x 1,5 M20 x 1,5 M16 x 1,5 Ø16Ø20 Ø16 + + + + + + + 10 + + - - I I U 9 FLOWMETER INPUT A: (0)4 - 20mA P: coil P: reed switch / NPN P: PNP P: namur P: active signal U: 0 - 10V A - PL: 4 20mA A 22,50 mm HN HF 22,50 mm ( 0.9")

Ø22 ( 7/ ") M20 x 1,5 8 + + + + + + I I I I I U

25mm 25mm 25mm 25mm 78 I - - U I I I I AA: 4 - 20mA AB: 0 - 20mA AF: 4 - 20mA AI: 4 - 20mA AP: 4 - 20mA AU: 0 - 10V ANALOG OUTPUT 22,50 mm 22,50 mm HO HG = + +

M20 x 1,5 M20 x 1,5 Ø20 Ø20 56 = PULSE OUTPUT 12mm 12mm 12mm 12mm OA: active 24V DC passive trans. OT: OR: mech. relay 17 mm 17 mm = HP HH + + 14 mm 14 mm 34 = PULSE OUTPUT

24mm 24mm 6 x M12 24mm 24mm Ø12 OA: active 24V DC passive trans. OT: OR: mech. relay 36mm 36mm 36mm 36mm 30mm (1.18") 30mm (1.18") 2 + 0.9" 1 HT HJ + + + 22,50 mm ( 0.9") POWER SUPPLY - - - 1 7 7 7 2 GND PD: 8 - 24V AC PD: 8 - 24V PD: 8 - 24V DC PD-XI: 16 - 30V DC PF: 24V AC PF: 24V DC AC - 230V PM: 115 PX: 8 - 30V DC AP Output loop powered unit with type (terminals GND - 1 2 are not available) / "NPT Ø22 ( /8") Ø22 ( /8") Ø22 ( /8") PB / PC: battery powered Internal long life Lithium battery (terminals GND - 1 2 are not available) PL: input loop powered (terminals GND - 1 2 are not available)

1.18" 1.18" Display example - 90 x 40mm (3.5” x 1.6”) 0.9" HU HK

1 1 /2"NPT 1/2"NPT /2"NPT Flat bottom, no holes available.

15mm 15mm 15 mm HV 16 mm

38mm 4 x M20 x 1.5

HZ

F112 3 Typical wiring diagram F112-P-(AP)-CH-IB-(OT)-PB Typical wiring diagram F112-P-AP-CH-IB-OT-PX

TERMINAL CONNECTORS BATTERY POWERED TERMINAL CONNECTORS OUTPUT LOOP POWERED F100-series F100-series

Modbus communication type CH: RS485 - 2 wire Modbus communication type CH: RS485 - 2 wire

B B 29 29

A A 28 2827

Common ground Common ground 26 26

+ 3.2V 1M + 3.2V 1M low-pass low-pass filter Status input type IB: filter Status input type IB: 13 13 reset total reset total Common ground Common ground 12 12

Supply * Supply * 11 11 Signal Flowmeter input Signal Flowmeter input type: P type: P

type of signal pulse type of signal pulse Circuit depends on Circuit depends on

Common ground 9 10 Common ground 9 10

Analog output type AP: passive 4 - 20mA (loop powered) +

Analog output type AP: 8 8 Passive 4 - 20mA 8 - 30V DC

e.g. indicator (not used in this example) -

Common ground 7 Common ground 7 e.g. counter

Pulse output type OT: 65 65 123456 passive transistor Pulse output (not used in this example) type OT: Common ground Common ground passive transistor

Please note: AP may be used in combination with the battery!

AP will power the unit (output loop powered); the battery will be disabled automatically untill power is disconnected).

* Supply voltage: 1.2 / 3.2V DC to sensor * Supply voltage: 1.2 / 3.2V DC to sensor

4 F112 Typical wiring diagram F112-A-AA-CB-IB-OA-PD Typical wiring diagram F112-A-AI-CI-IB-OR-PM

TERMINAL CONNECTORS 24V AC / DC POWER SUPPLY TERMINAL CONNECTORS 115 - 230V AC POWER SUPPLY F100-series F100-series

Z 3130

Y Modbus communication type CB: RS232 Modbus communication type CI: RS485 - 4 wire

B 29 TXD 29

A RXD 2827 28

DTR 12V Common ground Common ground 26 26

+ 3.2V 1M + 3.2V 1M low-pass low-pass filter Status input type IB: filter Status input type IB: 13 13 reset total reset total Common ground Common ground 12 12 Flowmeter input type A: Supply * Supply * (0)4 - 20mA 11 11 Signal Flowmeter input type A: Signal (0)4 - 20mA

Common ground 9 10 Common ground 9 10

e.g. indicator + +

8 Analog output type AA: 8 Analog output type AI:

- 8 - 30V DC

e.g. indicator active 4 - 20mA passive isolated 4 - 20mA -

Common ground 7 7 +

65 123456 65 123456 - e.g. counter Pulse output type OA: e.g. counter active 24V DC pulse Common ground Pulse output type OR: mechanic relay

L1

2 2 Power supply type PM:

Main supply 8 - 24V AC Main supply + 115 - 230V AC N 1 Power supply type PD: 1

8 - 24V DC

8 - 24V AC / DC -

Common ground 0 Earth Common ground 0 Earth

* Supply voltage: 3.2 / 8.2 / 12 / 24V DC to sensor * Supply voltage: 3.2 / 8.2 / 12 / 24V DC to sensor

F112 5 Hazardous area applications Configuration example IIB / IIIC and IIC The F112-XI has been certified according ATEX F112-P-(AP)-(CT)-IB-(OT)-PC-XI - Battery powered unit and IECEx by DEKRA for use in Intrinsically Safe applications with an ambient temperature of

HAZARDOUS AREA SAFE AREA -40°C to +70°C (-40°F to +158°F). TERMINAL CONNECTORS • The ATEX markings for gas and dust F100-series applications are: II 1 G Ex ia IIB/IIC T4 Modbus communication type CT: TTL II 1 D Ex ia IIIC T100 °C Da IP6X. Possible for battery powered applications TXD • The IECEx markings for gas and dust 29 (not used in this example). Please note: communciation type CT

RXD 28 applications are: Ex ia IIC/IIB T4 Ga and is not allowed in IIC applications.

Ex ia IIIC T100 °C Da IP6X. DTR 27 +12V Besides the I.S. power supply for the pulse Common ground 26 output, it is allowed to connect up to three I.S. power supplies in IIB/IIIC applications or one in IIC applications. Consult the certificate for the maximum input and output values of the circuits. Full functionality of the F112 remains available, including 4 - 20mA output, pulse output and Modbus communication (type CT). Power supply type PD-XI offers a 8.2V sensor supply e.g. for one Namur sensor. A flame proof enclosure with rating ATEX II 2 GD EEx d IIB T5 is available as well. Please contact your supplier for further details.

Certificate of conformity KEMA 03ATEX1074 X • IECEx DEK 11.0042X

Status input type IB: + 3.2V 1M reset total low-pass filter Ci is negligibly 13 small Common ground 12

Supply * 11 Signal Flowmeter input type: P

type of signal Ci is negligibly pulse

Circuit depends on small Common ground 9 10

Analog output type AP:

8 passive 4 - 20mA (not used in this example)

Common ground 7

Pulse output type OT:

6 passive transistor (not used in this example)

Common ground 5

Please note: AP may be used in combination with the battery!

AP will power the unit (output loop powered); the battery will be disabled automatically untill power is disconnected).

* Note sensor supply voltage: 1.2V DC for coil sensors or 3.2V DC for other pulse sensors.

6 F112 Configuration example IIB / IIIC and IIC - F112-P-AP-(CT)-IB-OT-PX-XI - Output loop powered

HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F100-series

Modbus communication type CT: TTL Please note: communciation type CT is not allowed in IIC applications.

TXD 29 ISOLATOR: Uo=max 30V I.S. Certified Isolator

e.g. PC

RXD 28 + Io=max 250mA TTL to RS232 / RS422 / TTL Po=max 850mW

DTR 27 +12V For example: MTL5051

Common ground - 26

* Note: Communication only allowed when configured as IIB / IIIC.

Status input type IB: + 3.2V 1M reset total low-pass filter

13 Ci is negligibly small Common ground 12

Supply * 11 Signal Flowmeter input type: P Ci is negligibly type of signal pulse

Circuit depends on small

Common ground 9 10 e.g. indicator + Uo=max 30V POWER SUPPLY

8 Ci = 17nF Analog output type AP: e.g. MTL 5525 Io=max 100mA

passive 4 - 20mA (output loop powered) and / or - REPEATER Po=max 750mW

Common ground 7 e.g. MTL 5541 e.g. indicator e.g. counter + Uo=max 30V POWER SUPPLY

6 e.g. MTL 5525 Ci is negligibly Pulse output type OT: 123456 Io=max 100mA or

small passive transistor 123456 - SWITCH INTERFACE Po=max 750mW Common ground 5 e.g. MTL 5511 e.g. counter Note: above values are safety values. Consult the technical specification for operational values.

* Note sensor supply voltage: 1.2V DC for coil sensors or 3.2V DC for other pulse sensors.

F112 7 Configuration example IIB / IIIC and IIC - F112-A-AF-(CT)-IB-OT-PD-XI - Power supply 16 - 30V DC

HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F100-series

Modbus communication type CT: TTL Please note: communciation type CT is not allowed in IIC applications.

TXD 29 ISOLATOR: Uo=max 30V I.S. Certified Isolator TTL to e.g. PC

RXD 28 + Io=max 250mA RS232 / RS422 / TTL Po=max 850mW

DTR 27 For example: MTL5051 +12V

Common ground - 26

* Note: Communication only allowed when configured as IIB / IIIC.

Status input type IB: + 3.2V 1M reset total TOTAL Co OF ALL CONNECTED low-pass ANALOG APPARATUS IN IIC filter APPLICATIONS MAY NOT

13 Ci is negligibly small EXCEED 66nF MINUS 17nF (17nF IS USED BY THE ANALOG Common ground

12 OUTPUT SIGNAL TERMINAL 7 + 8).

Supply *

11 Flowmeter input type: A Signal (0)4 - 20mA

type of signal Ci is negligibly

Circuit depends on small Common ground 9 10

8 Analog output type AF: Ci = 17nF e.g. indicator passive floating 4 - 20mA

7 + Uo=max 30V POWER SUPPLY e.g. MTL 5525 6 Ci is negligibly Pulse output type OT: 123456 e.g. counter Io=max 100mA or

small passive transistor 123456 - SWITCH INTERFACE Po=max 750mW Common ground 5 e.g. MTL 5511 e.g. counter

2 + Uo=max 30V POWER SUPPLY

Main supply 1 Power supply type PD: 16 - 30V DC Io=max 100mA

(please note: PD and battery supply (type PC) is NOT allowed in IIC applications). For example - Po=max 750mW MTL5525 Common ground 0 Note: above values are safety values. Consult the technical specification for operational values. * Note power supply type PD: the supply voltage to pulse sensors is maximum 8.7V (Uo=max 8.7V Io=max 25mA Po=max 150mW) and to analog sensors as connected to terminal 1 (internally linked).

8 F112 Configuration example IIB / IIIC - F112-A-AF-CT-IB-OT-(PC)-(PD)-XI - Power supply 16 - 30V DC or battery powered

HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F100-series

Modbus communication type CT: TTL

TXD 29 ISOLATOR: Uo=max 30V I.S. Certified Isolator

e.g. PC

RXD 28 + Io=max 250mA TTL to RS232 / RS422 / TTL Po=max 850mW

DTR 27 +12V For example: MTL5051

Common ground - 26

Status input type IB: + 3.2V 1M reset total low-pass filter

13 Ci is negligibly small Common ground 12

Supply * 11

Signal + Uo=max 30V Flowmeter input type: A REPEATER type of signal Ci is negligibly Io=max 100mA

small (0)4 - 20mA For example Circuit depends on

- Po=max 750mW MTL5541

Common ground 9 10 e.g. indicator + Uo=max 30V POWER SUPPLY e.g. MTL 5525 8 Ci = 17nF Analog output type AF: Io=max 100mA and / or

passive floating 4 - 20mA - REPEATER Po=max 750mW

e.g. MTL 5541 e.g. indicator e.g. counter + Uo=max 30V POWER SUPPLY e.g. MTL 5525 6 Ci is negligibly Pulse output type OT: 123456 Io=max 100mA or

small passive transistor 123456 - SWITCH INTERFACE Po=max 750mW Common ground 5 e.g. MTL 5511 e.g. counter

Due to analog output type AF, the unit has to be powered with

27 battery type PC or with external power supply type PD. + Uo=max 30V POWER SUPPLY

Main supply 1 Power supply type PD: 16 - 30V DC Io=max 100mA

For example - Po=max 750mW MTL5525 Common ground 0 Note: above values are safety values. Consult the technical specification for operational values.

* Note power supply type PD: the supply voltage to pulse sensors is maximum 8.7V (Uo=max 8.7V Io=max 25mA Po=max 150mW) and to analog sensors as connected to terminal 1 (internally linked).

F112 9 Technical specification Casing General General Display Window Polycarbonate window. Type High intensity reflective numeric and Sealing Silicone. alphanumeric LCD, UV-resistant. Control keys Three industrial micro-switch keys. UV-resistant Dimensions 90 x 40mm (3.5” x 1.6”). silicone keypad. Digits Seven 17mm (0.67") and eleven 8mm (0.31") digits. Various symbols and measuring units. Aluminum wall / field mount enclosures Refresh rate User definable: fast, 1sec , 3sec, 15sec, 30sec, off. General Die-cast aluminum wall/field mount enclosure IP67 / Option ZB Transflective LCD with green LED backlight. NEMA 4X with 2-component UV-resistant coating. Good readings in full sunlight and darkness. Dimensions 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D. Note ZB Only available for safe area applications. Weight 1100 gr. Type HA Cable entry: 2 x PG9 and 1 x M20. Operating temperature Type HM Cable entry: 2 x M16 and 1 x M20. Standard unit -40°C to +80°C (-40°F to +176°F). Type HN Cable entry: 1 x M20. Intrinsically Safe -40°C to +70°C (-40°F to +158°F). Type HO Cable entry: 2 x M20. Type HP Cable entry: 6 x M12. Type HT Cable entry: 1 x 1/ " NPT. Power requirements 2 Type HU Cable entry: 3 x 1/ " NPT. Type PB Long life Lithium battery - life-time depends upon 2 Type HV Cable entry: 4 x M20. settings and configuration - up to 5 years. Type HZ Cable entry: no holes. Type PC Intrinsically Safe long life lithium battery - life-time depends upon settings and configuration - up to 5 years. GRP wall / field mount enclosures Type PD 8 - 24V AC / DC ± 10%. Power consumption max. 10 General GRP wall/field mount enclosure IP67 / NEMA 4X, Watt. Intrinsically Safe: 16 - 30V DC; power UV-resistant and flame retardant. consumption max. 0.75 Watt. Dimensions 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D. Type PF 24V AC / DC ± 10%. Power consumption max. 15 Watt. Weight 600 gr. Type PL Input loop powered from sensor signal 4 - 20mA Type HD Cable entry: no holes. (type “A”) - requires types AI and OT (not Xi). Type HE Cable entry: 2 x Ø 16mm and 1 x Ø 20mm. 7 Type PM 115 - 230V AC ± 10%. Power consumption max. 15 Watt. Type HF Cable entry: 1 x Ø 22mm ( /8"). Type PX 8 - 30V DC. Power consumption max. 0.5 Watt. Type HG Cable entry: 2 x Ø 20mm. Type ZB 12 - 24V DC ± 10% or internally powered with type PD Type HH Cable entry: 6 x Ø 12mm. 7 / PF / PM. Power consumption max. 1 Watt. Type HJ Cable entry: 3 x Ø 22mm ( /8"). Note PB/PF/PM Not availble Intrinsically Safe. Type HK Flat bottom, cable entry: no holes. Note PF/PM The total consumption of the sensors and outputs may not exceed 400mA @ 24V. Panel mount enclosures Note For Intrinsically Safe applications, consult the safety Dimensions 130 x 120 x 60mm (5.12" x 4.72" x 2.36") - W x H x D. values in the certificate. Panel cut-out 115 x 98mm (4.53" x 3.86") L x H. Type HB Die-cast aluminum panel mount enclosure IP65 / Sensor excitation NEMA 4X. Type PB/PC/PX 3.2V DC for pulse signals and 1.2V DC for coil pick-up. Weight 600 gr. Note This is not a real sensor supply. Only suitable for Type HC GRP panel mount enclosure IP65 / NEMA 4X, sensors with a very low power consumption like coils UV-resistant and flame retardant. (sine wave) and reed-switches. Weight 450 gr. Type PD 1.2 / 3.2 / 8.2 / 12 / 24V DC - max. 50mA @ 24V DC. Type PD-XI 1.2 / 3.2 / 8.2V DC - max. 7mA @ 8.2V DC and mains power supply voltage (as connected to terminal 1). Note In case PD-XI and signal A or U: the sensor supply voltage is according to the power supply voltage connected to terminal 1. Also terminal 2 offers the same voltage. Type PF / PM 1.2 / 3.2 / 8.2 / 12 / 24V DC - max. 400mA @ 24V DC.

Terminal connections Type Removable plug-in terminal strip. Wire max. 1.5mm2 and 2.5mm2.

Data protection Type EEPROM backup of all settings. Backup of running totals every minute. Data retention at least 10 years. Pass-code Configuration settings can be pass-code protected.

10 F112 Hazardous area Analog output Intrinsically Safe (Type XI) Function Transmitting linearized flow rate. Accuracy 10 bit. Error 0.05%. Analog output signal can be ATEX II 1 G Ex ia IIB/IIC T4 Ga. < scaled to any desired range. certification II 1 D Ex ia IIIC T100 °C Da IP6X. Update time Ten times per second. IECEx Ex ia IIC/IIB T4 Ga. Type AA Active 4 - 20mA output (requires PD, PF or PM). certification Ex ia IIIC T100 °C Da IP6X. Type AB Active 0 - 20mA output (requires PD, PF or PM). Ambient Ta -40°C to +70°C (-40°F to +158°F). Type AF Passive floating 4 - 20mA output for Intrinsically Explosion proof (Type XF) Safe applications (requires XI + PC or PD). Type AI Passive galvanically isolated 4 - 20mA output - also ATEX certification II 2 GD EEx d IIB T5. available for battery powered models (requires PB, Dimensions 300 x 250 x 200mm (11.8" x 9.9" x 7.9") L x H x D. PD, PF, PL or PM). Weight Appr. 15kg. Type AP Passive 4 - 20mA output - not isolated. Unit will be European Directives loop powered. Type AU Active 0 - 10V DC output (requires PD, PF or PM). EMC & Safety Compliant ref: EN 61326-1, EN 61010-1. Directive Pulse output Signal inputs Function Pulse output - transmitting accumulated total. Flowmeter Frequency Max. 64Hz. Pulse length user definable between 7.8 msec up to 2 seconds. Type P Coil / sine wave (minimum 20mVpp or 80mVpp - Type OA One active 24V DC transistor output (PNP); sensitivity selectable), NPN/PNP, open collector, reed- max. 50mA per output (requires PD, PF or PM). switch, Namur, active pulse signals 8 - 12 and 24V DC. Type OR One electro-mechanical relay output - isolated; Frequency Minimum 0Hz - maximum 7kHz for total and flow rate. max. switch power 230V AC (N.O.) - 0.5A per relay Maximum frequency depends on signal type and (requires PF or PM). internal low-pass filter. E.g. reed switch with Type OT One passive transistor output (NPN) - not isolated. low-pass filter: max. frequency 120Hz. Max. 50V DC - 300mA per output. K-Factor 0.000010 - 9,999,999 with variable decimal position. Low-pass filter Available for all pulse signals. Option ZF coil sensitivity 10mVpp. Operational Type A (0)4 - 20mA. Analog input signal can be scaled to any Operator functions desired range within 0 - 20mA. Displayed • Linearized flow rate and / or total. Type U 0 - 10V DC. Analog input signal can be scaled to any Functions • Linearized total and accumulated total. desired range within 0 - 10V DC. • Total can be reset to zero by pressing the Accuracy Resolution: 14 bit. Error 0.025mA / ± 0.125% FS. < CLEAR-key twice. Low level cut-off programmable. Span 0.000010 - 9,999,999 with variable decimal position. Total Update time Four times per second. Digits 7 digits. Voltage drop Type A: 2.5V @ 2omA. Units L, m3, GAL, USGAL, kg, lb, bbl, no unit. Load impedance Type U: 3kOhm. Decimals 0 - 1 - 2 or 3. Relationship Linear and square root calculation. Note Total can be reset to zero. Note For signal type A and U: external power to sensor is required; e.g. type PD. Accumulated total Logic inputs Digits 11 digits. Function • Terminal input to reset total remotely. Units / decimals According to selection for total. • If this terminal input is closed, the “clear total”- Note Can not be reset to zero. function is disabled. Type IB Internally pulled-up switch contact - NPN. Flow rate Duration Minimum pulse duration 100msec. Digits 7 digits. Units mL, L, m3, Gallons, kg, Ton, lb, bl, cf, RND, ft3, scf, Signal outputs Nm3, Nl, igal - no units. Communication option Decimals 0 - 1 - 2 or 3. Function Reading display information, reading / writing all Time units /sec - /min - /hr - /day. configuration settings. Protocol Modbus RTU. Speed 1200 - 2400 - 4800 - 9600 baud. Addressing Maximum 255 addresses. Type CB RS232 Type CH RS485 2-wire Type CI RS485 4-wire Type CT TTL Intrinsically Safe.

F112 11 Ordering information Standard configuration: F112-P-AP-CX-EX-HC-IX-OT-PX-TX-XX-ZX. Ordering information: F112 -_ -A _ -C _ _EX -H _ -I _ -O _ -P _ -TX -X _ -Z _ Flowmeter input signal A (0)4 - 20mA input. P Pulse input: coil, npn, pnp, namur, reed-switch. U 0 - 10V DC input. Analog output signal AA Active 4 - 20mA output - requires PD, PF or PM. AB Active 0 - 20mA output - requires PD, PF or PM. AF I.S. floating 4 - 20mA output - requires XI + PC or PD. AI Isolated 4 - 20mA output - requires PB, PD, PF, PL or PM. AP Passive 4 - 20mA output, loop powered unit. AU Active 0 - 10V DC output - requires PD, PF or PM. Communication CB Communication RS232 - Modbus RTU. CH Communication RS485 - 2-wire - Modbus RTU. CI Communication RS485 - 4-wire - Modbus RTU. CT Intrinsically Safe TTL - Modbus RTU. CX No communication. Flow equations EX No flow equations. Panel mount enclosures - IP65 / NEMA4X HB Aluminum enclosure. HC GRP enclosure. GRP field / wall mount enclosures - IP67 / NEMA4X HD Cable entry: no holes. HE Cable entry: 2 x Ø 16mm & 1 x Ø 20mm. HF Cable entry: 1 x Ø 22mm (7/8”). HG Cable entry: 2 x Ø 20mm. HH Cable entry: 6 x Ø 12mm. HJ Cable entry: 3 x Ø 22mm (7/8”). HK Flat bottom, cable entry: no holes. Aluminum field / wall mount enclosures - IP67 / NEMA4X HA Cable entry: 2 x PG9 + 1 x M20. HM Cable entry: 2 x M16 + 1 x M20. HN Cable entry: 1 x M20. HO Cable entry: 2 x M20. HP Cable entry: 6 x M12. HT Cable entry: 1 x 1/2”NPT. HU Cable entry: 3 x 1/2”NPT. HV Cable entry: 4 x M20. HZ Cable entry: no holes. Additional inputs IB Terminal input to reset total. IX No external input. Outputs OA One active transistor output - requires PD, PF or PM. OR One mechanical relay output - requires PF or PM. OT One passive transistor output - standard configuration. Power supply PB Lithium battery powered. PC Lithium battery powered - Intrinsically Safe. PD 8 - 24V AC/DC + sensor supply - with XI: 16 - 30V DC. PF 24V AC/DC + sensor supply. PL Input loop powered from sensor signal type “A” - requires AI and OT (not Xi). PM 115 - 230V AC + sensor supply. PX Basic power supply 8 - 30V DC (no real sensor supply). Unit requires external loop AP. Temperature input signal TX No temperature input signal. Hazardous area XI Intrinsically Safe, according ATEX and IECEx. XF EExd enclosure - 3 keys. XX Safe area only. Other options ZB Backlight. ZF Coil input 10mVpp. ZX No options. The bold marked text contains the standard configuration. Available Intrinsically Safe.

Specifications are subject to change without notice.

FAURE HERMAN FAURE HERMAN METER Route de Bonnétable • BP 20154 4702 North Sam Houston Parkway West - Suite 100 72406 Ferté Bernard, France Houston TX. 77086 (U.S.A.) Tel : +33 (0)2 43 60 28 60 Phone : +1713 623 0808 Fax: +33 (0)2 43 60 28 70 Fax : +1713 623 2332 E-mail : [email protected] E-mail : [email protected] 12 Copyright: Fluidwell bv - 2013 - F112FH-DATA-EN-V1341