GH SERIES Indirect Gas-Fired Duct Furnace Installation, Operation and Maintenance Manual
GH-Series for Indoor and Outdoor Commercial Applications
GH Indoor Series shown GH Rooftop Series shown ACCESSORY GH-Series Indirect Gas-Fired Duct Furnace
WARNING AVERTISSEMENT Ne pas entreposer ni utiliser d’essence ou autre vapeurs ou Do not store or use gasoline or other flammable vapors and liquides inflammable à proximité de cet appareil ou de tout liquids in the vicinity of this or any other appliance. autre appareil. WHAT TO DO IF YOU SMELL GAS QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ u Do not try to light any appliance. u Ne tentez pas d’allumer un appareil. u Do not touch any electrical switch; do not use any phone u Ne touchez pas à un interrupteur; n’utilisez pas de télé- in your building. phone dans l’édifice où vous vous trouvez. u Leave the building immediately. u Sortez de l’édifice immédiatement. u Immediately call your gas supplier from a phone remote u Appelez immédiatement le fournisseur de gaz à par- from the building. Follow the gas supplier’s instructions. tir d’un téléphone à l’exterieur de l’édifice. Suivez les u If you cannot reach your gas supplier, call the fire depart- instructions du fournisseur de gaz. ment. u Si vous ne pouvez joindre le fournisseur de gaz, appelez Installation and service must be performed by a qualified les pompiers. installer, service agency or the gas supplier. L’installation at les réparations doivent être confiées à un installateur qualifié ou au fournisseur de gaz. WARNING AVERTISSEMENT RISQUE FLASH D’ARC ET DE CHOC ÉLECTRIQUE ARC FLASH AND ELECTRIC SHOCK HAZARD Risque d’arc êlectrique et de choc électrique. Débrancher Arc flash and electric shock hazard. Disconnect all electric toutes les alimentation électrique, vérifier avec un voltmètre power supplies, verify with a voltmeter that electric power que l’alimentation électrique est coupée et portez des vête- is off and wear protective equipment per NFPA 70E before ments de protection conformément à la norme NFPA 70E working within electric control enclosure. Failure to comply avant de travailler dans la console de commande électrique. can cause serious injury or death. Le non-respect peut entraîner des blessures graves ou la mort. Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable. Le client doit fournir la terre à l’unité, selon les codes NEC, CEC et locaux, selon le cas. Before proceeding with installation, read all instructions, verifying that all the parts are included and check the Avant de procéder à l’installation, lisez toutes les instruc- nameplate to be sure the voltage matches available utility tions, vérifiez que toutes les pièces sont incluses at vérifier power. la plaque signalétique pour vous assurer que la tension correspond à la puissance disponible du réseau. The line side of the disconnect switch contains live high-voltage. Le côté entrée du sectionneur contient une haute tension active. The only way to ensure that there is NO voltage inside the unit is to install and open a remote disconnect switch and La seule façon de s’assurer qu’il n’y a pas de tension à verify that power is off with a volt meter. Refer to unit elec- l’intérieur de l’unité est d’installer et d’ouvrir un interrupteur trical schematic.Follow all local codes. de déconnexion à distance et de vérifier que l’alimentation est coupée à l’aide d’un voltmètre. Référe-vous au schéma électrique de l’appareil. Suivez tous les codes locaux. WARNING AVERTISSEMENT RISQUE D’INCENDIE OU D’EXPLOSION RISK OF FIRE OR EXPLOSION N'installez pas le four à condoits là oùil peut être exposé à des Do not install duct furnace where it may be exposed to poten- vapeurs potentiellement explosives ou inflammables. tially explosive or flammable vapors! Ne stockez pas et n'utilisez pas d'essence ou d'autres vapeurs Do not store or use gasoline or other flammable vapors and et liquides inflammables à proximité de ce module ou de tout liquids in the vicinity of this or any module. autre module. Ne pas installer dans une atmosphère potentiel- Do not install in potentially explosive atmosphere laden with lement explosive chargée de poussière, de sciure de bois ou de dust, sawdust or similar products. produits similaires.
2 1.800.627.4499 GH-Series Indirect Gas-Fired Duct Furnace ACCESSORY
CAUTION ATTENTION
RISK OF ELECTRIC SHOCK OR EQUIPMENT DAMAGE. RISQUE DE CHOC ELECTRIQUE OU DE DOMMAGE D'APPAREIL Whenever electrical wiring is connected, disconnected Chaque fois que le câblage électrique est connecté, décon- or changed, the power supply to the module and module necté ou changé, l'alimentation électrique du module et des controls must be disconnected. Lock and tag the disconnect commandes du module doit être déconnectée. Verrouillez switch or circuit breaker to prevent accidental reconnection et étiquetez le sectionneur ou le disjoncteur pour éviter une of electric power. reconnexion accidentelle de l'alimentation électrique.
CAUTION ATTENTION N'installez pas les appareils dans des endroits où les produits de combustion peuvent être aspirés dans les ouvertures de Do not install units in locations where flue products can be bâtiment adjacentes, comme les fenêtres, les prises d'air frais, drawn into adjacent building openings such as windows, fresh etc. air intakes, etc. Distance from vent terminal to adjacent public walkways, adjacent buildings, operable windows and building La distance entre le terminal de ventilation et les allées openings shall conform with the local codes. In the absence of publiques adjacentes, les bâtiments adjacents, les fenêtres local codes, installation shall conform with the National Fuel Gas ouvrantes et les ouvertures de bâtiment doivent être conformes Code, ANSI Z223.1 or the Canadian CAN/CGA B-149 aux codes locaux. En l'absence de codes locaux, l'installation Installation Codes. doit être conforme au Code national du gaz combustible, à la norme ANSI Z223.1 ou aux codes d'installation Canadiens CAN / CGA B-149. CAUTION ATTENTION L'installation du câblage doit être conforme aux codes du Installation of wiring must conform with local building codes. In bâtiment locaux. En l'absence de codes de construction locaux, the absence of local building codes, installation must conform l'installation doit être conforme au Code national de l'électricité to the National Electric Code ANSI/NFPA 70 - Latest Edition. ANSI/NFPA 70 - dernière édition. L'unité doit être mise à la Unit must be electrically grounded in conformance with this terre électriquement conformément à ce code. Au Canada, code. In Canada, wiring must comply with CSA C22.1, Canadi- le câblage doit être conforme à la norme CSA C22.1 du Code an Electrical Code. Canadien de l'électricité.
NOTICE IMPORTANT This equipment is to be installed by following Industry Best Cet équipement doit être installé en suivant les meilleures Practices and all applicable codes. Any damage to pratiques de l'industrie et tous les codes applicables. Tout components, assemblies, subassemblies or the cabinet which dommage aux composants, aux assemblages, aux sous-en- is caused by improper installation practices will void the sembles ou à l'armoire qui est causé par des pratiques d'instal- warranty. lation incorrectes annulera la garantie.
NOTE: See additional cautions REMARQUE: Voir les mises en and warnings in Section 7, Gas garde et les avertissements Piping Installation. supplémentaires de la Section 7, Installation de Tuyauterie de Gaz.
1.800.627.4499 3 OWNER INFORMATION
ACCESSORY GH-Series Indirect Gas-Fired Duct Furnace
SAVE THIS MANUAL UNIT RECORDS
Record information as shown below. In the unlikely event that factory assistance is ever required, this information will be needed.
Locate the RenewAire unit label, found inside the removable panel on the furnace. NOTE: This information is for purposes of identifying the specific furnace. Unit-specific option data can then be obtained, as needed, from the Model Number. See Gas Furnace Code in this NOTE: This page manual for further details. is to be completed by the installing Furnace Model No: contractor. The completed document is Serial Number: to be turned over to the owner after start-up. Furnace Turndown: Single Stage Two-Stage Modulated 5:1 Modulated 10:1
TYPICAL UNIT LABEL (FOUND INSIDE THE REMOVABLE PANEL ON THE FURNACE)
4 1.800.627.4499 GH-Series Indirect Gas-Fired Duct Furnace ACCESSORY
THIS PAGE IS INTENTIONALLY LEFT BLANK.
THIS PAGE IS INTENTIONALLY LEFT BLANK
1.800.627.4499 5 OPTIONS & ACCESSORIES OPTIONS & ACCESSORIES
DUCT FURNACE DIMENSIONS Indirect Gas-Fired Duct Furnace IN-KI (TOP EXHAUST INDOOR) 4 IN-SI (SEPARATE INLET EXHAUST INDOOR) GH INDOOR Accessory
FLUE GAS EXHAUST 22.92 FLUE GAS EXHAUST INDOOR D (H) D 22.92 (H) 14.89 Indirect Gas-Fired Duct Furnace SPECIFICATIONS COMBUSTION AIR INLET 14.89 D Indirect Gas-Fired Duct Furnace Flame rollout switch COMBUSTION AIR INLET Manual shut off valve 50, 75, 100, 125, 150, 175, 3/8" condensate drain connection
200, 250, 300, 350, 400 23.99 23.99 Single phase - 120V, 208V, 230V OUTDOOR TOP EXHAUST (NO) OUTDOOR TOP EXHAUST (NO) 47.85 Tubular heaters (L) 47.85 (L) Indirect natural gas fi red 24 VAC
W 4510 Helgesen Dr. W 4510 Helgesen Dr. UNLESS OTHERWISE SPECIFIED, Madison, WI 53718 USA UNLESS OTHERWISE SPECIFIED, Madison, WI 53718 USA Indoor installation DIMENSIONS ARE IN INCHES. TEL: (608) 221-4499 DIMENSIONS ARE IN INCHES. TEL: (608) 221-4499 TOLERANCES: RenewAire LLC FAX: (608) 221-2824 TOLERANCES: RenewAire LLC FAX: (608) 221-2824 TOLL FREE: (800) 627-4499 TOLL FREE: (800) 627-4499 LINEAR 0.015 LINEAR 0.015 HOLE SIZE 0.005 TITLE: HOLE SIZE 0.005 TITLE: ANGULARITY 3 ANGULARITY 3 80% thermal effi ciency SURFACE FINISH = SURFACE FINISH = See table 2 63 MICROINCH MINIMUM HDG-400-M-N GAS HEATER OUTDOOR 63 MICROINCH MINIMUM HDG-400-M-N GAS HEATER OUTDOOR DRAWN BY: DATE: DWG. NO. DRAWN BY: DATE: DWG. NO. - MATERIAL: DO NOT SCALE DRAWING. - MATERIAL: DO NOT SCALE DRAWING. Horizontal airfl ow 2 REMOVE ALL BURRS, BREAK CAH 10/19/16 REMOVE ALL BURRS, BREAK CAH 10/19/16 INDOOR TOP EXHAUSTSHARP (KI) EDGES. SK4750A SHARP EDGES. SK4750A FINISH: APPLICABLE STANDARDS: DIM. CHECKED BY: DATE: FINISH: APPLICABLE STANDARDS: DIM. CHECKED BY: DATE: AND TOL. ANSI Y14.5 INDOOR SEPARATED COMBUSTIONAND TOL. ANSI Y14.5 (SI) LEVEL DESCRIPTION OF REVISION DATE BY -- -- SCALE:1:16 SIZE A SHEET 1 OF 1 LEVEL DESCRIPTION OF REVISION DATE BY -- -- SCALE:1:16 SIZE A SHEET 1 OF 1 Rated for elevations from 0 – 2,000 ft. 4510 Helgesen Dr. UNLESS OTHERWISE SPECIFIED, Madison, WI 53718 USA DIMENSIONS ARE IN INCHES. Min/Max Temperature Rise throughTEL: (608) 221-4499 Furnace (°F) Vent Locations Shipped loose with base unit and installed in the fi eld TOLERANCES: RenewAire LLC FAX: (608) 221-2824 LINEAR 0.015 TOLL FREE: (800) 627-4499 4510 Helgesen Dr. 409 stainless steel heat exchanger UNLESS OTHERWISE SPECIFIED, Madison, WI 53718 USA HOLE SIZE 0.005 TITLE: DIMENSIONS ARE IN INCHES. TEL: (608) 221-4499 ANGULARITY 3 TOLERANCES: RenewAire LLC Unit Shipping FAX: (608) 221-2824 SURFACE FINISH = LINEAR 0.015 TOLL FREE: (800) 627-4499 Size Tubes Input Rate Output 63 MICROINCH MINIMUM HDG100-M-KI IN-KI, IN-SI Diameter 409 stainless steel burners HOLE SIZE 0.005 TITLE: ANGULARITY 3 Weight Weight DRAWN BY: DATE: DWG. NO. MATERIAL: 20 DO NOT25 SCALE DRAWING. 30 35 40 45 50 55 60 SURFACE FINISH = Indirect propane fi red fuel REMOVE ALL BURRS, BREAK 63 MICROINCH MINIMUM HDG100-M-KI Flue/combustion air – indoor models SHARP EDGES. SK4700A "W" "L" "H" "D" DRAWN BY: DATE: DWG. NO. FINISH: APPLICABLE STANDARDS: DIM. CHECKED BY: DATE: MATERIAL: DO NOT SCALE DRAWING. AND TOL. ANSI Y14.5 LEVEL DESCRIPTION OF REVISION DATE BY SCALE:1:24 SIZE A SHEET 4 OF 4 REMOVE ALL BURRS, BREAK Vertical (separated indoor) Elevation correction for elevation > 2,000 ft. SHARP EDGES. SK4700A Indoor IN-KI shown FINISH: APPLICABLE STANDARDS: DIM. CHECKED BY: DATE: AND TOL. ANSI Y14.5 304 stainless steel heat exchanger LEVEL DESCRIPTION OF REVISION DATE BY SCALE:1:24 SIZE A SHEET 3 OF 4 Vertical top exhaust with louvered intake MBH Qty. Btuh Btuh Nom. Duct Opening Airfl ow (CFM) inch inch inch inch lb lb Direct spark ignition 5:1 continuous electronic modulation for all furnaces 10:1 continuous electronic modulation for furnaces 1-stage/2-stage gas controls 50 3 50,000 40,000 1852 1481 1235 1058 926 823 741 673 617 15.7 127 207 renewaire.com/specifications Induced draft venting 200 MBH and larger Terminal block for power and control wiring Duct thermostat for modulation control 75 3 75,000 60,000 2778 2222 1852 1587 1389 1235 1111 1010 926 15.7 127 207 Automatic high limit safety shut-off Disconnect switch 100 4 100,000 80,000 3704 2963 2469 2116 1852 1646 1481 1347 1235 18.4 142 222 Auxiliary manual high limit switch Power fusing 5 125 5 125,000 100,000 4630 3704 3086 2646 2315 2058 1852 1684 1543 21.2 169 249 Combustion air pressure switch Air proving switch Duct thermostat for 1-stage/2-stage control 150 6 150,000 120,000 5556 4444 3704 3175 2778 2469 2222 2020 1852 23.9 160 240 Combination gas valve with shutoff Duct thermostat for modulation control 175 7 175,000 140,000 6481 5185 4321 3704 3241 2881 2593 2357 2160 26.7 47.8 22.9 180 260 200 8 200,000 160,000 7407 5926 4938 4233 3704 3292 2963 2694 2469 29.4 196 276 250 10 250,000 200,000 9259 7407 6173 5291 4630 4115 3704 3367 3086 34.9 245 325 FLUE AND COMBUSTION AIR CONFIGURATION 300 12 300,000 240,000 11111 8889 7407 6349 5556 4938 4444 4040 3704 40.4 6 279 384 IN-KI IN-SI Note: The total equivalent length of vent pipe must not exceed 50 feet. If equivalent length exceeds 50 feet refer 350 14 350,000 280,000 12963 10370 8642 7407 6481 5761 5185 4714 4321 45.9 324 429 (TOP EXHAUST) (SEPARATE INLET EXHAUST) to IOM for recommendations. 400 15 400,000 320,000 14815 11852 9877 8466 7407 6584 5926 5387 4938 48.7 394 499 FLUE FLUE COMBUSTION EXHAUST EXHAUST INTAKE Caution: All indirect gas-fi red duct furnaces to be installed downstream of the ERV and on the positive side of the Note: For a single furnace, 20° F minimum temperature rise, 60° F maximum temperature rise. supply fan. INDIRECT GAS-FIRED DUCT FURNACE DIMENSIONS AIRFLOW AIRFLOW AIRFLOW AIRFLOW
COMBUSTION INTAKE
NOTES 1. UNLESS OTHERWISE SPECIFIED, TEMPERATURE RISE AND PRESSURE DROP DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH. 1 GAS FURNACE 50-200 MBH 2 GAS FURNACE 250-400 MBH 2. SPECIFICATIONS SUBJECT TO Gas Furnace 50 ‐ 200 MBH Gas Furnace 250 ‐ 400 MBH CHANGE WITHOUT NOTICE. 60 0.32 60 1.6
55 0.28 55 1.4 TOP VIEW 200 36" 50 0.24 50 1.2 F) F) 400 Service Area w.c.) ‐ 200 175 350 w.c.) ‐ (deg. 45 0.20 (deg. 45 400 1.0
47 3/8"
175 (in.
300 (inch 350 Rise Rise Case
14 7/8" 40 150 0.16 40 0.8
300 Drop Opening 14 7/8" Drop 125 Opening 35 0.12 35 250 250 0.6 100 View Port 25" 6 1/8" Pressure 6 1/8" Pressure Temperature Temperature 30 75 150 0.08 30 0.4 Case 125 50 100 25 0.04 25 0.2 50/75 24" 24" 20 0.00 20 0.0 Opening Opening 3" 3/8" Condensate 3" 0 1000 2000 3000 4000 5000 6000 7000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 Power Wiring and Drain Tube Airflow (CFM) Airflow (CFM) Control Wiring 3/4" Gas Connection Inlet Fittings LEFT VIEW FRONT VIEW RIGHT VIEW
4510 Helgesen Dr. Specifi cations may be subject to change without notice. UNLESS OTHERWISE SPECIFIED, Specifi cations may be subject to changeMadison, WIwithout 53718 USA notice. DIMENSIONS ARE IN INCHES. TEL: (608) 221-4499 TOLERANCES: RenewAire LLC FAX: (608) 221-2824 LINEAR 0.015 TOLL FREE: (800) 627-4499 HOLE SIZE 0.005 TITLE: 36 RENEWAIRE.COM 1.800.627.4499 ANGULARITY 3 SURFACE FINISH = 63 MICROINCH MINIMUM HDG100-M-KI DIM SPEC DRAWN BY: DATE: DWG. NO. MATERIAL: DO NOT SCALE DRAWING. REMOVE ALL BURRS, BREAK SHARP EDGES. SK4700A FINISH: APPLICABLE STANDARDS: DIM. CHECKED BY: DATE: 6 1.800.627.4499 AND TOL. ANSI Y14.5 LEVEL DESCRIPTION OF REVISION DATE BY SCALE:1:24 SIZE A SHEET 1 OF 1 OPTIONS & ACCESSORIES OPTIONS & ACCESSORIES
DUCT FURNACE DIMENSIONS Indirect Gas-Fired Duct Furnace IN-KI (TOP EXHAUST INDOOR) 4 IN-SI (SEPARATE INLET EXHAUST INDOOR) GH INDOOR Accessory
FLUE GAS EXHAUST 22.92 FLUE GAS EXHAUST INDOOR D (H) D 22.92 (H) 14.89 Indirect Gas-Fired Duct Furnace SPECIFICATIONS COMBUSTION AIR INLET 14.89 D Indirect Gas-Fired Duct Furnace Flame rollout switch COMBUSTION AIR INLET Manual shut off valve 50, 75, 100, 125, 150, 175, 3/8" condensate drain connection
200, 250, 300, 350, 400 23.99 23.99 Single phase - 120V, 208V, 230V OUTDOOR TOP EXHAUST (NO) OUTDOOR TOP EXHAUST (NO) 47.85 Tubular heaters (L) 47.85 (L) Indirect natural gas fi red 24 VAC
W 4510 Helgesen Dr. W 4510 Helgesen Dr. UNLESS OTHERWISE SPECIFIED, Madison, WI 53718 USA UNLESS OTHERWISE SPECIFIED, Madison, WI 53718 USA Indoor installation DIMENSIONS ARE IN INCHES. TEL: (608) 221-4499 DIMENSIONS ARE IN INCHES. TEL: (608) 221-4499 TOLERANCES: RenewAire LLC FAX: (608) 221-2824 TOLERANCES: RenewAire LLC FAX: (608) 221-2824 TOLL FREE: (800) 627-4499 TOLL FREE: (800) 627-4499 LINEAR 0.015 LINEAR 0.015 HOLE SIZE 0.005 TITLE: HOLE SIZE 0.005 TITLE: ANGULARITY 3 ANGULARITY 3 80% thermal effi ciency SURFACE FINISH = SURFACE FINISH = See table 2 63 MICROINCH MINIMUM HDG-400-M-N GAS HEATER OUTDOOR 63 MICROINCH MINIMUM HDG-400-M-N GAS HEATER OUTDOOR DRAWN BY: DATE: DWG. NO. DRAWN BY: DATE: DWG. NO. - MATERIAL: DO NOT SCALE DRAWING. - MATERIAL: DO NOT SCALE DRAWING. Horizontal airfl ow 2 REMOVE ALL BURRS, BREAK CAH 10/19/16 REMOVE ALL BURRS, BREAK CAH 10/19/16 INDOOR TOP EXHAUSTSHARP (KI) EDGES. SK4750A SHARP EDGES. SK4750A FINISH: APPLICABLE STANDARDS: DIM. CHECKED BY: DATE: FINISH: APPLICABLE STANDARDS: DIM. CHECKED BY: DATE: AND TOL. ANSI Y14.5 INDOOR SEPARATED COMBUSTIONAND TOL. ANSI Y14.5 (SI) LEVEL DESCRIPTION OF REVISION DATE BY -- -- SCALE:1:16 SIZE A SHEET 1 OF 1 LEVEL DESCRIPTION OF REVISION DATE BY -- -- SCALE:1:16 SIZE A SHEET 1 OF 1 Rated for elevations from 0 – 2,000 ft. 4510 Helgesen Dr. UNLESS OTHERWISE SPECIFIED, Madison, WI 53718 USA DIMENSIONS ARE IN INCHES. Min/Max Temperature Rise throughTEL: (608) 221-4499 Furnace (°F) Vent Locations Shipped loose with base unit and installed in the fi eld TOLERANCES: RenewAire LLC FAX: (608) 221-2824 LINEAR 0.015 TOLL FREE: (800) 627-4499 4510 Helgesen Dr. 409 stainless steel heat exchanger UNLESS OTHERWISE SPECIFIED, Madison, WI 53718 USA HOLE SIZE 0.005 TITLE: DIMENSIONS ARE IN INCHES. TEL: (608) 221-4499 ANGULARITY 3 TOLERANCES: RenewAire LLC Unit Shipping FAX: (608) 221-2824 SURFACE FINISH = LINEAR 0.015 TOLL FREE: (800) 627-4499 Size Tubes Input Rate Output 63 MICROINCH MINIMUM HDG100-M-KI IN-KI, IN-SI Diameter 409 stainless steel burners HOLE SIZE 0.005 TITLE: ANGULARITY 3 Weight Weight DRAWN BY: DATE: DWG. NO. MATERIAL: 20 DO NOT25 SCALE DRAWING. 30 35 40 45 50 55 60 SURFACE FINISH = Indirect propane fi red fuel REMOVE ALL BURRS, BREAK 63 MICROINCH MINIMUM HDG100-M-KI Flue/combustion air – indoor models SHARP EDGES. SK4700A "W" "L" "H" "D" DRAWN BY: DATE: DWG. NO. FINISH: APPLICABLE STANDARDS: DIM. CHECKED BY: DATE: MATERIAL: DO NOT SCALE DRAWING. AND TOL. ANSI Y14.5 LEVEL DESCRIPTION OF REVISION DATE BY SCALE:1:24 SIZE A SHEET 4 OF 4 REMOVE ALL BURRS, BREAK Vertical (separated indoor) Elevation correction for elevation > 2,000 ft. SHARP EDGES. SK4700A Indoor IN-KI shown FINISH: APPLICABLE STANDARDS: DIM. CHECKED BY: DATE: AND TOL. ANSI Y14.5 304 stainless steel heat exchanger LEVEL DESCRIPTION OF REVISION DATE BY SCALE:1:24 SIZE A SHEET 3 OF 4 Vertical top exhaust with louvered intake MBH Qty. Btuh Btuh Nom. Duct Opening Airfl ow (CFM) inch inch inch inch lb lb Direct spark ignition 5:1 continuous electronic modulation for all furnaces 10:1 continuous electronic modulation for furnaces 1-stage/2-stage gas controls 50 3 50,000 40,000 1852 1481 1235 1058 926 823 741 673 617 15.7 127 207 renewaire.com/specifications Induced draft venting 200 MBH and larger Terminal block for power and control wiring Duct thermostat for modulation control 75 3 75,000 60,000 2778 2222 1852 1587 1389 1235 1111 1010 926 15.7 127 207 Automatic high limit safety shut-off Disconnect switch 100 4 100,000 80,000 3704 2963 2469 2116 1852 1646 1481 1347 1235 18.4 142 222 Auxiliary manual high limit switch Power fusing 5 125 5 125,000 100,000 4630 3704 3086 2646 2315 2058 1852 1684 1543 21.2 169 249 Combustion air pressure switch Air proving switch Duct thermostat for 1-stage/2-stage control 150 6 150,000 120,000 5556 4444 3704 3175 2778 2469 2222 2020 1852 23.9 160 240 Combination gas valve with shutoff Duct thermostat for modulation control 175 7 175,000 140,000 6481 5185 4321 3704 3241 2881 2593 2357 2160 26.7 47.8 22.9 180 260 200 8 200,000 160,000 7407 5926 4938 4233 3704 3292 2963 2694 2469 29.4 196 276 250 10 250,000 200,000 9259 7407 6173 5291 4630 4115 3704 3367 3086 34.9 245 325 FLUE AND COMBUSTION AIR CONFIGURATION 300 12 300,000 240,000 11111 8889 7407 6349 5556 4938 4444 4040 3704 40.4 6 279 384 IN-KI IN-SI Note: The total equivalent length of vent pipe must not exceed 50 feet. If equivalent length exceeds 50 feet refer 350 14 350,000 280,000 12963 10370 8642 7407 6481 5761 5185 4714 4321 45.9 324 429 (TOP EXHAUST) (SEPARATE INLET EXHAUST) to IOM for recommendations. 400 15 400,000 320,000 14815 11852 9877 8466 7407 6584 5926 5387 4938 48.7 394 499 FLUE FLUE COMBUSTION EXHAUST EXHAUST INTAKE Caution: All indirect gas-fi red duct furnaces to be installed downstream of the ERV and on the positive side of the Note: For a single furnace, 20° F minimum temperature rise, 60° F maximum temperature rise. supply fan. INDIRECT GAS-FIRED DUCT FURNACE DIMENSIONS AIRFLOW AIRFLOW AIRFLOW AIRFLOW
COMBUSTION INTAKE
NOTES 1. UNLESS OTHERWISE SPECIFIED, TEMPERATURE RISE AND PRESSURE DROP DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH. 1 GAS FURNACE 50-200 MBH 2 GAS FURNACE 250-400 MBH 2. SPECIFICATIONS SUBJECT TO Gas Furnace 50 ‐ 200 MBH Gas Furnace 250 ‐ 400 MBH CHANGE WITHOUT NOTICE. 60 0.32 60 1.6
55 0.28 55 1.4 TOP VIEW 200 36" 50 0.24 50 1.2 F) F) 400 Service Area w.c.) ‐ 200 175 350 w.c.) ‐ (deg. (deg. 45 0.20 45 400 1.0
47 3/8"
175 (in.
300 (inch 350 Rise Rise Case
14 7/8" 40 150 0.16 40 0.8
300 Drop Opening 14 7/8" Drop 125 Opening 35 0.12 35 250 250 0.6 100 View Port 25" 6 1/8" Pressure 6 1/8" Pressure Temperature Temperature 30 75 150 0.08 30 0.4 Case 125 50 100 25 0.04 25 0.2 50/75 24" 24" 20 0.00 20 0.0 Opening Opening 3" 3/8" Condensate 3" 0 1000 2000 3000 4000 5000 6000 7000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 Power Wiring and Drain Tube Airflow (CFM) Airflow (CFM) Control Wiring 3/4" Gas Connection Inlet Fittings LEFT VIEW FRONT VIEW RIGHT VIEW
4510 Helgesen Dr. Specifi cations may be subject to change without notice. UNLESS OTHERWISE SPECIFIED, Specifi cations may be subject to changeMadison, WIwithout 53718 USA notice. DIMENSIONS ARE IN INCHES. TEL: (608) 221-4499 TOLERANCES: RenewAire LLC FAX: (608) 221-2824 LINEAR 0.015 TOLL FREE: (800) 627-4499 HOLE SIZE 0.005 TITLE: ANGULARITY 3 FOR THE MOST COMPLETE AND CURRENT INFORMATION VISIT RENEWAIRE.COM 37 SURFACE FINISH = 63 MICROINCH MINIMUM HDG100-M-KI DIM SPEC DRAWN BY: DATE: DWG. NO. MATERIAL: DO NOT SCALE DRAWING. REMOVE ALL BURRS, BREAK SHARP EDGES. SK4700A FINISH: APPLICABLE STANDARDS: DIM. CHECKED BY: DATE: AND TOL. ANSI Y14.5 LEVEL DESCRIPTION OF REVISION DATE BY SCALE:1:24 SIZE A SHEET 1 OF 1 1.800.627.4499 7 6 1/8" SHEET 1 OF 1 1 SHEET 14 7/8" 4510 Helgesen Dr. Helgesen 4510 TEL: (608) 221-4499 (608) TEL: FAX: (608) 221-2824 Opening Madison, WI 53718 USA 53718 WI Madison, A TOLL FREE: (800)TOLL FREE: 627-4499 SIZE SK4700A SCALE:1:24 DWG. NO. DWG. 3" DIM SPEC Case DATE: DATE: 47 3/8" RIGHT VIEW 24" UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH. SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE. CHECKED BY: DRAWN BY: DRAWN Opening NOTES 1. 2. 25" Case HDG100-M-KI RenewAire LLC TITLE: AND TOL. ANSI Y14.5 ANSI TOL. AND DO NOT SCALE DRAWING. REMOVE ALL BREAK BURRS, EDGES. SHARP DIM. STANDARDS: APPLICABLE View Port Drain Tube Drain 3/8" Condensate 3/4" Gas Connection 3 0.005 0.015 TOP VIEW FRONT VIEW FINISH: UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE IN INCHES. TOLERANCES: LINEAR HOLE SIZE ANGULARITY = FINISH SURFACE 63 MICROINCH MINIMUM MICROINCH 63 MATERIAL: BY 36" DATE Service Area Inlet Fittings Power Wiring and Control Wiring 24" Opening LEFT VIEW 3" DESCRIPTION OF REVISION 14 7/8" Opening 6 1/8"
MODEL GH INDOOR DIMENSIONED DRAWING LEVEL
8 1.800.627.4499 OPTIONS & ACCESSORIES OPTIONS & ACCESSORIES
DUCT FURNACE DIMENSIONS Indirect Gas-Fired Duct Furnace RT-NO (TOP EXHAUST OUTDOOR) 4 RT-WO (FRONT EXHAUST OUTDOOR) GH OUTDOOR Accessory
FLUE GAS EXHAUST ROOFTOP D
Indirect Gas-Fired Duct Furnace SPECIFICATIONS 22.92 (H) FLUE GAS EXHAUST 34.92 14.89 (H) Indirect Gas-Fired Duct Furnace Combination gas valve with shutoff COMBUSTION AIR INLET 14.89 Flame rollout switch COMBUSTION AIR INLET 50, 75, 100, 125, 150, 175, Manual shut off valve 200, 250, 300, 350, 400 3/8" condensate drain connection 23.99 Tubular heaters Single phase - 120V, 208V, 230V 23.99 W 47.85 Indirect natural gas fi red (L) Outdoor installation 24 VAC W 47.85 (L) 80% thermal effi ciency OUTDOOR TOP EXHAUST (NO) Horizontal airfl ow See table 1 1 4510 Helgesen Dr. Rated for elevations from 0 – 2,000 ft. UNLESS OTHERWISE SPECIFIED, Madison, WI 53718 USA OUTDOOR FRONT EXHAUST (WO) DIMENSIONS ARE IN INCHES. TEL: (608) 221-4499 TOLERANCES: RenewAire LLC FAX: (608) 221-2824 LINEAR 0.015 TOLL FREE: (800) 627-4499 4510 Helgesen Dr. 409 stainless steel heat exchanger HOLE SIZE 0.005 TITLE: Min/Max Temperature Rise through Furnace (°F) Vent LocationsUNLESS OTHERWISE SPECIFIED, Madison, WI 53718 USA ANGULARITY 3 DIMENSIONS ARE IN INCHES. TEL: (608) 221-4499 Shipped loose with base unit and installed in the fi eld SURFACE FINISH = TOLERANCES: RenewAire LLC FAX: (608) 221-2824 63 MICROINCH MINIMUM HDG-400-M-N GAS HEATER OUTDOOR LINEAR 0.015 TOLL FREE: (800) 627-4499 409 stainless steel burners HOLE SIZE 0.005 Unit Shipping DRAWN BY: DATE: DWG. NO. TITLE: Size Tubes Input Rate Output- MATERIAL: DO NOT SCALE DRAWING. RT-NO, RT-WOANGULARITYRT-NO 3 RT-WO Diameter REMOVE ALL BURRS, BREAK CAH 10/19/16 SURFACE FINISH = Flue/combustion air – outdoor models SHARP EDGES. SK4750A 63 MICROINCH MINIMUM FRONT EXHAUSTWeight OUTDOOR Weight (WO) FINISH: 20 APPLICABLE25 STANDARDS: DIM.30CHECKED BY: 35 40 45 50 55 60 DATE: DWG. NO. AND TOL. ANSI Y14.5 MATERIAL: DRAWN BY: DATE: LEVEL DESCRIPTION OF REVISION DATE BY -- -- SCALE:1:16 SIZE A SHEET 1 OF 1 DO NOT SCALE DRAWING. Indirect propane fi red fuel "W" "L" "H" "H"REMOVE ALL BURRS, BREAK"D" Horizontal separated outdoor with hoods SHARP EDGES. HDG-400-M-W FINISH: APPLICABLE STANDARDS: DIM. CHECKED BY: DATE: AND TOL. ANSI Y14.5 Vertical top exhaust with intake hood Elevation correction for elevation > 2,000 ft. LEVEL DESCRIPTION OF REVISION DATE BY SCALE:1:16 SIZE A SHEET 1 OF 1 Direct spark ignition 304 stainless steel heat exchanger MBH Qty. Btuh Btuh Nom. Duct Opening Airfl ow (CFM) inch inch inch inch inch lb lb 2-stage gas controls 5:1 continuous electronic modulation for all furnaces Rooftop RT-NO shown Induced draft venting 10:1 continuous electronic modulation for furnaces 50 3 50,000 40,000 1852 1481 1235 1058 926 823 741 673 617 15.7 127 207 200 MBH and larger Terminal block for power and control wiring 75 3 75,000 60,000 2778 2222 1852 1587 1389 1235 1111 1010 926 15.7 127 207 Automatic high limit safety shut-off Duct thermostat for modulation control Auxiliary manual high limit switch Disconnect switch 100 4 100,000 80,000 3704 2963 2469 2116 1852 1646 1481 1347 1235 18.4 142 222 5 Combustion air pressure switch Power fusing renewaire.com/specifications 125 5 125,000 100,000 4630 3704 3086 2646 2315 2058 1852 1684 1543 21.2 169 249 Air proving switch 150 6 150,000 120,000 5556 4444 3704 3175 2778 2469 2222 2020 1852 23.9 160 240 Duct thermostat for 2-stage control Duct thermostat for modulation control 175 7 175,000 140,000 6481 5185 4321 3704 3241 2881 2593 2357 2160 26.7 47.8 22.9 34.9 180 260 Duct curb 200 8 200,000 160,000 7407 5926 4938 4233 3704 3292 2963 2694 2469 29.4 196 276 250 10 250,000 200,000 9259 7407 6173 5291 4630 4115 3704 3367 3086 34.9 245 325 300 12 300,000 240,000 11111 8889 7407 6349 5556 4938 4444 4040 3704 40.4 6 279 384 FLUE AND COMBUSTION AIR CONFIGURATION 350 14 350,000 280,000 12963 10370 8642 7407 6481 5761 5185 4714 4321 45.9 324 429 RT-NO RT-WO Caution: All indirect gas-fi red duct furnaces to be installed downstream of the ERV and on the positive side of the 400 15 400,000 320,000 14815 11852 9877 8466 7407 6584 5926 5387 4938 48.7 394 499 (TOP EXHAUST) (FRONT EXHAUST) supply fan. Note: For a single furnace, 20° F minimum temperature rise, 60° F maximum temperature rise. FLUE EXHAUST FLUE INDIRECT GAS-FIRED DUCT FURNACE DIMENSIONS EXHAUST
AIRFLOW AIRFLOW AIRFLOW AIRFLOW
COMBUSTION COMBUSTION INTAKE INTAKE NOTES 1. UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH. TEMPERATURE RISE AND PRESSURE DROP 2. SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.