Performance of a Selective-Surface Trombe Wall in a Small Commercial
Total Page:16
File Type:pdf, Size:1020Kb
SERI/TP-721-1158 , UC CATEGORY: UC-59a,c PERFORMANCE OF A SELECTIVE SURFACE TROMBE WALL IN A SMALL COMMERCIAL BUILDING R . JUDKOFF SOLAR ENERGY RESEARCH INSTITUTE F. SOKOL INDEPENDENT DESIGN BOULDER, COLORADO MARCH 1981 To BE PRESENTED AT THE AS/ISES ANNUAL ~~EETI NG CIVIC CENTER, PHILADELPHIA, PENN. 26 -30 MAY 1981 PREPARED UNDER TASK No. 1147.00 Solar Energy Research Institute A Division of Midwest Research Institute 1617 Cole Boulevard Golden, Colorado 80401 Prepa red for the U.S. Department of Energy Contract No. EG-77-C-01-4042 Printed in the United States of America Available from: National Technical Information Service U.S. Department of Commerce 5285 Port Royal Road Springfi eld, VA 22161 Price: Microfiche $3.00 Printed Copy $4. 00 NOTICE This report was prepared as an account of work sponsored by the United States Govern ment. Neither the United States nor the United States Department of Energy, nor any of their employees, nor any of their contractors, subcontractors, or their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness or usefulness of any information, apparatus, product or process disclosed, or represents that its use would not infringe privately owned rights. PERFORMANCE OF A SELEC11VE-SURFACE TROMBE WALL IN A SMALL COMMERCIAL BUILDING R. Judkoff Buildings Systems Development Branch Solar Energy Research Institute 1617 Cole Boulevard Golden, Colorado 80401 F. Sokol Independent Design Boulder, Colorado ABSTRACT The design and construction of a 10096 passive cial building. The building was constructed in solar building utilizing a clerestory and a trombe February 1980 and has now completed one heating wall is described. The use of three selectively and cooling season. absorptive and emissive coverings on the trornbe wall outer surface are investigated. One of the coverings and its laminating adhesive are tested 2. THE PROGRAM for degradation after a year of exposure under normal operating conditions. Ambient tempera The key requirements of the client were: ture, room air temperature, trombe wall interior and exterior surface temperatures, and solar • daylighting for the shop area, radiation are measured. • acoustic decoupling from outside to prevent disturbance of nearby residences by machinery noise, 1. INTRODUC110N • security for machinery and wood stocks, Movable insulation is an expensive and incon • stable temperatures for precise setting of furn venient technique for reducing night heat losses iture glue joints, and from direc t gain and trombe wall systems. Vol ume II of the DOE Passive Handbook (1) indicates • minimal auxiliary heating and cooling. that a selective foil applied to the exterior surface of a trombe wall or water wall equals or exceeds the performance of R-9 movable insulation. This 3. THE BUILDING represents an extremely cost-effective alternative to movable insulation. Figures I and 2 show the south elevation and a sectional perspective of the building, respectively. Shortly after Los Alamos National Laboratory obtained these results (1) in test-cell experim ents Although this building would have had enough on selective surfaces, F. Sokol requested design internal storage mass to support an extensive assistance for a small furniture-making factory in direct gain system, the requirements for stable Boulder, Colo. I agreed to assist under the temperatures, security, and acoustic decoupling condition that this novel concept be tested on his suggested the use of a trombe wall. The require building. He consented and we proceeded to de ment for daylighting as well as the building sign and build what to my knowledge is the first occupancy schedule suggested the addition of a field application of a selective surface on a clerestory above the trombe wall. The clerestory masonry trombe wall in a residential or commer- along with the ceiling shape is intended to diffuse the light evenly in the space so that supplementary lighting is rarely needed during the day. Addi tionally, the clerestory provides rapid early morn ing warm-up and utilizes to some extent the great amount of thermal storage mass available in the structural floor slab, block walls, and machinery. The site slopes somewhat to the south, facilitating a 3-ft earth berm on the north wall. The c~erestory allows a solar collection area ~f 100 ft . The trombe wall collection area is 130 ft . Heat loss through the clerestory is prevented at night by a 3-in.-thick panel of bead board insula Fig. I. South Elevation tion which is controlled by a timer and a l/lS-hp Dayton motor. Fig. 2. Sectional Perspective Figure 3 illustrates the different modes of opera Figure 4 shows a typical wall section, and Table 1 tion of the building. In summer the north doors lists the building materials and the thermal prop can be opened along with the vents low on the erties of typical sec tions. trombe wall and those high on the south wall. This facilitates a strong ventilative flow which is rein forced by any heating at the outer surface of the 4. TIlE SELECTIVE SURFACE trombe wall. The roof overhang provides total shading of the clerestory and about 50% shading of In choosing the selective surface, Microsorb paint, the trombe wall through the summer months. On Berry Products selective foil, and Maxorb selec summer nights the north doors are shut for secur tive foil were investigated. These products were ity reasons. However, vents in these doors allow tested in July 1979 for solar spectrum absorptivity natural flushing of the building mass with cool and long-wave emissivity at the Solar Energy night air. The movable insulation panel may be Research Institute Materials Laboratory. The left in the open position throughout the summer. results are presented in Table 2. In winter the trombe wall vents are sealed. The selective surface keeps the air-gap temperature relatively cool so that there is little to be gained The Mlcrosorb paint was not selective enough and by allowing thermocirculation of the wall. The was eliminated from further consideration. The clerestory provides morning warm-up and more two foils were equally selective; however, the than offsets any daytime heat losses from the Berry product had several advantages. It came in building. It is better, therefore, to store that wider strips and was thus easier to apply. It did energy, which would otherwise be transferred into not have an adhesive backing. This was crucial the building during the day via thermosyphoning, in since the adhesive backing on Max orb foil was in the trombe wall for night use. tended for the metallic surfaces of active solar collector panels; and Maxorb could not guarantee their adhesive over the long term when applied to a masonry substrateo Winter II n/';-"'" Operable Night Insulation on-\ri1Hfr=~::::::"~=~'...!======:!..!::==';;==';;;;:;::;:::: Automatic Timer Bead Beare R-9 Night Position. Selective Surface Trombe Wall 8" Concrete Block Grout-Filled ~--'i:['I 4" Moss-Rock Double Glass Vent -1" Air Gap Structural Slab Fig.3. Modes of Operation Table 1. BUll..DING CHARACTERISTICS a"Concrete Block Location: Boulder, Colo. Latitude: 39.7 north 3" Bead Board Orientation: 120 east of s~uth Insulation --*"l'O'GI\.l Trombe wall area: 130 ~t R-12 Clerestory area: 1 ft 200 Expanded Floor area: 800 ft Metal Lath----o\!l!x'\61 Typical Floor Slab: U = 0.4/perimeter· ft Stucco----ji~~Si~~ In-In. structural slab Glue Joinl---+IioY~ Perimeter insulation: 36 in. x 3 in. Dow Styrofoam SM Tie Wire ----1<1 Typical Roof Section: R-38 Outside Inside 0.5-in. gypsum board 10-in. loose fill insulation Fig. 4. Typical Wall Section o.s-t-. exterior ply Tar paper Pro-panel metal roofing Trombe Wall 6. ONE-YEAR DEGRADATION TEST OF SELEC TIVE FOIL AND LAMINATING AGENT Double-glazed, lI8-in. standard glass Selective surface: Berry Products On 13 March 1981, several small samples of selec selec tive foil, black chrome on tive foil were removed from the trombe wall sur copper substrate face to be tested for solar spectrum absorptivity Laminating adhesive: Dow Corning 795 and infrared emissivity. The results of the tests silicone building sealant are shown in Table 3. s-In. concrete block, grout-filled 4-in. moss rock Other Features Table 3. Date of Test: March 13, 1981 Air-lock vestibule entry R-9 night insulation on single-glazed clerestory Solar Coating Spectrum Infrared Emissivity 5. SELECnON OF AN ADHESIVE Absorptivity The selection of an adhesive to affix the selective Berry Products 0.89 0.05 foil to the masonry trombe wall involved a rather selective foil lengthy investigation. Los Alamos Natio~al after 1 year of Laboratory used a neoprene-based construetion normal operating adhesive in their test-cell experiment with selec exposure tive foils; however, their investigation lasted only several weeks, leaving doubt as to the long-term Adhesive Delamination BUbbling performance of the neoprene in contact with copper and masonry. A number of constru~ti~n Dow Silicone #795 None None observable adhesive manufacturers and Berry Products indi building and joint in addition to cated that we were the first to attempt such an sealer after 1 that noted at application in a full-scale building intended for year of normal time 0 f installa long-term usage, and they gave no guarantees. r:ve operating exposure tion eliminated neoprene-based glues at the suggestion of several adhesive company technical representa tives (2). We finally selected the silicone-based building sealant #795 by Dow Corning. TABLE 2. Solar Infrared Selective Surface Coating Substrate Cost Spectrum Emissivity Absorptivity Microsorb paint, well agitated, Dry standard finish, hollow $32/gal 0.91 0.75 2 coats applied core concrete block Berry Products selective foil NA $1.35/ft2 0.87 0.08 Maxorb selective foil NA $1.35/ft2 0.88 0.09 The results indicate no measurable degradation exterior surface temperature is primarily a tune after a year of normal operating exposure.