<<

Product Manual PM WHR

Group: Chiller Effective: September 1997 Supersedes: PM 901

Water-Cooled Reciprocating Packaged Water Chillers

WHR 017EW through WHR 210EW 60 Hertz Refrigerant R-22

© 1997 McQuay International Table of Contents

Introduction ...... 3 Features and Benefits ...... 4 Design Advantages...... 5 Selection Procedure...... 9 Application Adjustment Factors...... 11 Performance Data ...... 12 Part Load Data...... 18 Pressure Drop Curves...... 19 Electrical Data ...... 24 Physical Data...... 36 Dimensional Data...... 41 Application Data...... 45 Optional Features ...... 48 Product Specifications...... 52

Our Facility is

"McQuay" is a registered trademarks of McQuay International 1997 McQuay International "Illustrations cover the general appearance of McQuay International products at the time of publication and we reserve the right to make changes in design and construction at anytime without notice"

2 WHR 017EW - 210EW Product Manual WHR Introduction

The WHR packaged water chiller is a product of the McQuay commitment to offer energy efficient equipment design. A design approach carefully matching high quality compressors and shell-and-tube components into a unit of uncompromised operating efficiency.

Efficiency • Compliance with ASHRAE 90.1 • Cross-circuit compressor unloading • Liquid subcooling • Copeland DISCUS compressor • Optional capacity reduction Reliability ƒ Rugged compressor design ƒ Factory installed operating and safety controls Flexibility • Complete factory assembly ƒ 25 available sizes ƒ Factory installed options Serviceability ƒ Semi-hermetic compressors ƒ Suction and discharge service valves ƒ Dual refrigerant circuits (WHR040 and above) Full Factory Testing • Assures trouble-free start-up and operation

Product Manual WHR WHR 017EW - 210EW 3 Features and Benefits

Efficiency All units are in full compliance with ASHRAE 90-1. Operating economy at reduced load is increased by operating each refrigerant circuit partially unloaded, rather than one circuit off and the other circuit fully loaded. At unloaded conditions each compressor will operate at lower compression ratios with substantial power savings. Optional steps of capacity reduction are accomplished by efficient cylinder unloading.

Flexibility Completely factory assembled, piped, wired, and shipped in one piece ready for installation. Power to the single main supply power terminal block can be supplied by one field installed main supply power disconnect switch. The WHR packaged water chillers come in 25 sizes between 17 and 210 nominal tons (50 and 710 kW).

Reliability WHR chillers use Copeland DISCUS semi-hermetic compressors. These compressors are designed for Refrigerant 22. All safety and operating controls are tested and calibrated at the factory. A complete set of safety controls for each circuit is used. Safety controls include compressor crankcase heater(s), freeze protection pressurestats (manual reset), oil switches (manual reset), high pressure safety switches (manual reset), and compressor motor overload protectors. Standard operating controls include time delay relays for 20-second sequence starting of compressors, manual pumpdown switches, low pressure controls, compressor lead-lag switches (WHR-040EW-210EW) and chilled water temperature controller. An optional control circuit transformer is available, eliminating the need for a separate 115V power supply to the controls.

Serviceability Semi-hermetic, 1750 rpm induction type motors are used. The motors are refrigerant gas cooled. A finned motor housing helps dissipate motor heat. Solid-state modules in the motor terminal box respond to temperature sensors imbedded in all three motor windings to provide inherent thermal overload protection for all run and start conditions. Both suction and discharge service valves are provided to allow isolation of the compressor from the refrigerant circuit. All multiple compressor units use two independent refrigerant circuits. Dual refrigerant circuits permit shutdown and routine maintenance and service of one circuit while the second circuit maintains system operation.

Full Factory Testing Each unit is pressure tested, evacuated and charged with Refrigerant 22. With the unit at full load, individual unit performance tests and extensive quality control checks are performed to ensure each control is properly adjusted and operates correctly. Each unit is then rechecked for refrigerant leakage.

4 WHR 017EW - 210EW Product Manual WHR Design Advantages

Unit Arrangements Each unit consists of motor compressors, insulated evaporator and centralized electrical control panel containing all necessary safety and operating controls, and compressor starting controls. Units come complete with water-cooled condensers with integral subcooler circuits.

Compressors WHR chillers use Copeland DISCUS semi-hermetic compressors. These compressors are designed for Refrigerant 22. Semi-hermetic, 1750 rpm induction type motors are used. The motors are refrigerant gas cooled. Solid-state modules in the motor terminal box respond to temperature sensors imbedded in all three motor windings, providing inherent thermal overload protection for all run and start conditions. The compressor housing is constructed from close grained, high nickel content, alloy cast-iron with no bolted joint between the motor and compressor. The housing includes a cast-iron cylinder head and stator cover, and a crankcase oil sightglass. A suction strainer built into the compressor in the gas stream between the suction service valve and the motor, filters out foreign and abrasive particles. An internal relief valve relieves discharge pressure to the suction side for safety protection at high compression ratios as required by ANSI/ASHRAE 15 Safety Code. Main bearings are solid cast bronze insert type with oversized bearing area resulting in ultra-low bearing loading. The crankshaft is die-forged, high strength iron alloy with integral counterweights, statically and dynamically balanced for smooth operation. Connecting rods are lightweight aluminum with integral bearing surfaces on the crankshaft and piston ends. Pistons are close grain cast iron with oil and compression rings. Piston pins are full floating type for long life. Compressors have a force-feed lubrication system with positive oil displacement, a reversible oil pump, and an operating oil charge. The pump feeds oil through rifle-drilled passages in the crankshaft to all bearing surfaces. Magnetic plugs trap particles that enter the crankcase. The oil supply filters through a large area oil strainer. During start-up, a crankcase heater minimizes oil being diluted by refrigerant.

Factory Installed Liquid Line Components Each refrigerant circuit has a filter-drier, liquid line sightglass/moisture indicator, solenoid valve and thermal expansion valve. A manual liquid line shutoff valve, with charging connections, is supplied on all units with water-cooled condensers.

Short Circuit Protection (WHR 017EW through 030EW, WHR 095EW through 210EW) Each compressor is individually protected against short circuit and locked rotor conditions by factory installed circuit breakers. The control circuit is protected by separate fusing. WHR-040EW through 090EW can have circuit breakers factory installed as an option.

Product Manual WHR WHR 017EW - 210EW 5 Part Load Efficiencies Part load efficiencies and Integrated Part Load Values (IPLV) are calculated according to the requirements of the latest ARI Standard 590 and meet or exceed ASHRAE Efficiency Standard 90.1. Since most air conditioning systems operate at less than design full load a majority of the time, IPLV is an excellent method for comparing chillers efficiencies.

Noise All McQuay WHR chillers are available with hot gas discharge line mufflers in each refrigerant circuit to reduce the overall sound levels. Systems using remote air-cooled condensers can transmit noise through the refrigerant piping, these units are supplied with discharge line mufflers as standard. Optional insulated acoustical compressor enclosure to further reduce sound levels is also available for most units.

Unit Base Designed for easy handling , the units are mounted on a compact, rugged formed steel base. Isolator mounting holes are provided.

Electrical Control Center Shipped with all operating and safety controls and motor starting equipment factory wired, operationally tested, and ready for operation. All controls are centrally located in a hinged with keylocked doors. A five minute, solid-state lockout timer is provided to delay compressor restart after safety cutout or power interruption, or under irregular cooling load demands. A lead lag switch is standard on all units not incorporating the single circuit hot gas bypass option.

Evaporator The evaporator is a direct expansion, shell-and-tube type with water flowing in the baffled shell side and refrigerant flowing through the tubes. The evaporator is constructed with a carbon steel shell and seamless high efficiency copper tubes. Rolled expansion anchors the refrigerant tubes in the heavy carbon steel tube sheets. Water baffles are polypropylene to resist corrosion. Refrigerant heads are carbon steel with multi-pass baffles to ensure oil return and are removable to permit access to the tubes from either end. For water removal, 3/8" (10mm) vent and drain plugs are provided on the top and bottom of the shell. Two 1/2” (12.7mm) couplings on each water nozzle allow for easy field installation of sensor equipment. The evaporator is wrapped with 3/4” (19.1mm) thick vinyl nitrate polymer sheet insulation. The insulation has a K factor of 0.28 at 75°F (24°C). The insulation is fitted and cemented in place, then painted with a resilient vinyl base paint to resist cracking. The tube side maximum working pressure is 225 psig (1552kPa). The water side working pressure is 175 psig (1207kPa). All evaporators are designed, constructed, inspected and stamped according to the requirements of the ASME Boiler and Pressure Vessel Code.

6 WHR 017EW - 210EW Product Manual WHR Condensers All water condensers are cleanable shell and thru-tube type with water flowing through the tubes and refrigerant in the shell. Each condenser has full circuit refrigerant charge pumpdown capacity. Independent condensers serve the unit’s dual refrigerant circuits. Each condenser is constructed with a carbon steel shell and seamless integrally finned high efficiency copper tubes. Rolled expansion anchors the tubes in the heavy carbon steel tube sheets. Water heads have drain and vent plugs, and are removable to allow tube cleaning and service. The condensers have as standard equipment a liquid shutoff valve, purge valve and 450 lb. (204kPa) spring loaded relief valve according to ANSI/ASHRAE 15 Safety Code. Refrigerant side (shell) maximum working pressure is 450 psig (3104kPa). All condensers are built and stamped according to the requirements of ASME Boiler and Pressure Vessel Code. A subcooler circuit is provided as an integral part of the condensers. The Subcooler circuit is separated from the condenser by steel baffles, causing all liquid to pass over the subcooler tubes. This ensures positive refrigerant movement in a counterflow direction to the condenser water for maximum performance.

Temperature Control

WHR 040EW through 210EW Available with three different levels of temperature control. • The standard microprocessor leaving water controller • Standard microprocessor based leaving water controller with an indicator light package • MicroTech reciprocating controller. The standard microprocessor leaving water controller is available on all units and provides precise temperature control based on leaving water temperature. The control is pre-set and calibrated. Reset of supply water temperature can be accomplished from outside air temperature, zone temperature or a signal from an EMS system. LED indicator lights display the number of stages in operation. This same controller can be provided with an indicator light package that allows the operator to see the status of all unit safeties, a power on light and compressor staging.

WHR 017EW through 030EW Two-stage units are supplied with a return water electromechanical temperature controller. Three stage units are supplied with a solid state return water temperature controller.

MicroTech Chiller Controller (optional) (WHR 040EW through 210EW) The MicroTech menu structure is separated into three distinct categories, which provide the operator or service technician with a full description of current unit status, control parameters, and alarms. Security protection prevents unauthorized changing of the setpoints and control parameters. MicroTech continuously performs self-diagnostic checks, monitoring all system temperatures, pressures and safeties, and will automatically shutdown a compressor, a refrigerant circuit or the entire unit should a fault occur. The cause of the shutdown will be retained in memory and can be easily displayed in plain English or metric units for operator review. The MicroTech chiller controller can also retain and display the time the fault occurred and the operating conditions that were present at the time of the fault. In addition to displaying alarm diagnostics, the MicroTech chiller controller also provides the operator with a warning of pre-alarm conditions.

Product Manual WHR WHR 017EW - 210EW 7 Programmable Setpoints Precise digital settings of the leaving chilled water temperature setpoint and all other control parameters. This is extremely important in the setting of safeties such as low leaving water temperature cutout, high pressure cutout, suction pressure cutout, and freeze protection.

Compressor Soft Loading Soft loading limits the number of cooling stages to prevent unnecessary electrical demand and possible overshoot of the leaving chilled water temperature setpoint.

Demand Limit Control Based on a 4-20mA DC signal, the controller will determine the maximum number of stages permitted to operate, preventing additional demand charges during high usage periods.

Automatic Circuit Lead-Lag With the keypad, the operator can manually select either refrigerant circuit for the lead position or the controller will automatically select the lead circuit based on the circuit with the fewest operating hours.

Time Clock, Daily and Holiday Start/Stop Control The operator can program daily start/stop schedules including weekends and up to fourteen separate holidays without the need of an external time clock or EMS interface. If desired, an external time clock can be used instead of the internal schedule.

Chilled Water Pump Control If an alarm shuts down the chiller, the chilled water pump will remain on, providing any remaining cooling to the loads.

Thermal Storage Thermal storage is a technique for shifting all or part of a building’s air conditioning requirements from on-peak to off-peak hours. Cooling energy is produced and stored during off-peak hours when utility rates are lower and then used during the on-peak hours. The benefits of thermal storage obtained by the building owner are attractive rate schedules and in many cases rebates from the utility company.

Partial or Full Storage Thermal storage systems can be designed to provide either partial storage or full storage of the air conditioning load. Although a partial storage system shaves the peak load, it will require chiller operation during on-peak periods. A full storage system provides enough storage to meet the building’s full on-peak cooling requirement with the chiller only operating during off-peak hours. The partial storage system achieves less of a demand reduction than full storage but the initial cost of the system is less expensive since less storage capacity is required.

8 WHR 017EW - 210EW Product Manual WHR Selection Procedure

1. Ratings may be interpolated for any chiller water temperature between 40°F and 50°F but cannot be extrapolated. 2. Chilled water quantities - Ratings are based on a 10 degree chilled water range and are applicable from a minimum of 6°F to a maximum of 16°F differential between entering and leaving chilled water temperature. 3. Condenser water quantities - Ratings are based on a 10°F rise in condenser water temperature and are applicable from 1-1/2 to 4 GPM/ton (20°F to 7.5°F rise) except as limited by pressure drop in Figure 2, Evaporator Pressure Drop WHR 040EW through 090EW. 4. Figure 1 and Figure 2 beginning on page 19, indicate evaporator and condenser water pressure drop data. Water flow rates should be maintained within these limits, which are based on minimum and maximum flow rates. The total condenser water flow should be split between condensers according to the nominal tonnage of each refrigerant circuit as shown in Table 5 through Table 7. Pressure drop capacity ratings are based on parallel water connection of condensers. 5. Ratings are based on 0.00025 fouling factor for both condenser and evaporator. For other fouling factors, multiply ratings by evaporator and condenser factors from Table 2 and Table 3. For applications using a glycol solution, see Table 1 and Table 4. Selection Procedure Note: If the Knowing the required chiller capacity in tons, the leaving (supply) water temperature and either the condenser water chilled water temperature range-delta T, or the gpm, determine the unknown quantity using the temperature rise is formula: other than 10 degrees, make GPM×− Delta T certain the condenser Tons = water inlet 24 temperature column corresponding to the Knowing the required chiller capacity (tons), the entering condenser water temperature, and either the correct leaving condenser water temperature range-delta T, or the GPM, determine the unknown quantity using the condenser water temperature is used. formula: ° (i.e., 75 F condenser THR Nominal Tons Cooling Capacity ×30 water, 20 degree rise: Condenser GPM = = use 85°F entering 500 ×−Delta T Cond. CondenserWaterRange condenser water column).

Product Manual WHR WHR 017EW - 210EW 9 Sample Selection Given: Cool 165 GPM of water from 54°F to 44°F with condenser water available at 85°F. Condenser water temperature rise to be 10 degrees. Fouling factor of 0.00025 in evaporator and condenser. Find: A. WHR packaged water chiller selection B. Compressor power input C. Condenser water flow rate D. Evaporator and condenser water pressure drop Solution: 1. Chilled water range: 54°F - 44°F = 10°F (Temperature Difference). GPM× Chilled Water Range 2. Capacity = 24 165× 10 = 68.8 tons 24 3. From Table 6, a model WHR-070EW has the capacity to meet the job requirement. For an evaporator leaving water temperature of 44°F and condenser water entering temperature of 85°F with a 10 degree rise, the unit capacity rating table indicates: Tons = 70.2 kW = 62.9 4. Determine GPM condenser water from the following: Tons Cooling Capacity× 30 Condenser GPM = Nominal Condenser Water Range 70.2 tons × 30 = = 210.6 GPM 10 degrees

5. From Figure 2 and Figure 3 for the WHR-070EW, pressure drops are as follows: a. Evaporator pressure drop at 165 GPM is 6.2 feet water. b. Condenser pressure drop at 210.6 GPM is 12.5 feet water.

10 WHR 017EW - 210EW Product Manual WHR Application Adjustment Factors

Ethylene And Propylene Glycol Factors WHR units are designed to operate with a leaving chilled fluid temperature range of 21°F (-6.1°C) to 50°F (10°C). Leaving chilled fluid temperatures below 40°F (4.6°C) result in suction temperatures at or below the freezing point of water and a glycol solution is required. The use of glycol in the evaporator will reduce the performance of the unit. The reduction in performance depends upon the glycol concentration. This should be taken into consideration during initial system design. McQuay encourages a minimum concentration of 25% be provided on all glycol applications. Glycol concentrations below 25% are to diluted for long-term corrosion protection of ferrous metals.

Note: Glycol in the condenser will have a negligible effect on performance because glycol at higher temperatures will perform with characteristics similar to water. Evaporator and Condenser Temperature Drop Factors Performance tables are based on a 10°F (5°C) temperature difference through the evaporator and condenser. A temperature difference other than 10°F (5°C) will result in unit performance being different from what is shown. Adjustment factors for applications having temperature drops between 6°F and 16°F (3.3°C to 8.9°C) can be found in Table 2 and Table 3. Temperature drops outside of this range may adversely affect the control system’s ability to maintain acceptable control, and are not recommended. Fouling Factor Performance tables are based on water with a fouling factor of 0.00025 ft2 ××° hr F / BTU (0.044 M2°C/kW) according to ARI 590. As fouling is increased, performance decreases. For performance with a fouling factor other than 0.00025 (0.044), see Table 2 and Table 3. To ensure optimum unit operation, proper water treatment must be maintained. Scaling and dirt in a system will vary significantly depending on local water conditions. Water treatment should be based on characteristics of the area’s water. Improper or untreated water may lead to scale build up, erosion and corrosion in both the condenser and evaporator. McQuay will not accept responsibility for poorly or improperly treated water.

Table 1, Adjustment factors for propylene glycol Table 4, Adjustment factors for ethylene glycol Percent Freeze Point Percent Freeze Point P.G °F °C Cap. Power GPM PD E.G °F °C Cap. Power GPM PD 10 26 -3 0.987 0.992 1.010 1.068 10 26 -3 0.991 0.966 1.013 1.070 20 19 -7 0.975 0.985 1.028 1.147 20 18 -8 0.982 0.992 1.040 1.129 30 9 -13 0.962 0.978 1.050 1.248 30 7 -14 0.972 0.986 1.074 1.181 40 -5 -21 0.946 0.971 1.078 1.366 40 -7 -22 0.961 0.976 1.121 1.263 50 -27 -33 0.929 0.965 1.116 1.481 50 -28 -33 0.946 0.966 1.178 1.308

Table 2, Evaporator adjustment factors Table 3, Condenser adjustment factors Chilled Chilled Water Fouling Factor - English (metric) Water Fouling Factor - English (metric) Delta-T 0.00025(0.044) 0.00075 (0.132) Delta-T 0.00025(0.044) 0.00075 (0.132) °F °C Cap. Power Cap. Power °F °C Cap. Power Cap. Power 6 3.3 0.992 0.995 0.965 0.982 6 3.3 1.003 0.999 0.984 1.035 8 4.4 0.995 0.997 0.969 0.984 8 4.4 1.002 1.000 0.982 1.037 10 5.6 1.000 1.000 0.975 0.986 10 5.6 1.000 1.000 0.980 1.038 12 6.6 1.005 1.002 0.980 0.989 12 6.6 0.984 0.973 0.977 1.042 14 7.7 1.010 1.005 0.985 0.991 14 7.7 0.976 0.960 0.963 1.067 16 8.9 1.014 1.007 0.989 0.993 16 8.9 0.968 0.946 0.948 1.092

Product Manual WHR WHR 017EW - 210EW 11 Performance Data

Table 5, WHR-017EW through WHR-060EW, 60 Hz, English units ENTERING CONDENSER WATER TEMPERATURE (10°F DELTA T) WHR LWT 70°F 80°F 85°F 95°F 105°F UNIT (°F) CAP. PWR CAP. PWR CAP. PWR CAP. PWR CAP. PWR SIZE TONS kWi EER TONS kWi EER TONS kWi EER TONS kWi EER TONS kWi EER 40 17.9 13.1 16.4 17.0 14.0 14.6 16.6 14.6 13.6 15.3 15.6 11.8 14.0 16.9 10.0 42 18.6 13.2 16.9 17.6 14.2 14.9 17.0 14.5 14.1 16.0 15.7 12.2 15.0 17.5 10.3 44 19.3 13.3 17.4 18.3 14.5 15.2 17.8 15.0 14.2 16.7 16.2 12.4 15.6 17.6 10.6 017EW 46 19.9 13.4 17.8 18.9 14.7 15.5 18.4 15.2 14.5 17.2 16.3 12.7 16.1 17.7 10.9 48 20.6 13.4 18.5 19.5 14.9 15.8 19.0 15.6 14.6 17.9 16.6 12.9 16.7 17.8 11.2 50 21.3 13.6 18.8 20.2 15.0 16.1 19.6 15.9 14.8 18.4 16.8 13.2 17.2 18.0 11.5 40 21.9 17.3 15.2 20.8 18.5 13.5 20.3 19.2 12.7 18.7 20.5 11.0 17.2 22.3 9.3 42 22.8 17.4 15.7 21.6 18.8 13.8 20.9 19.1 13.1 19.6 20.8 11.3 18.4 23.1 9.5 44 23.6 17.5 16.1 22.4 19.1 14.1 21.8 19.8 13.2 20.4 21.3 11.5 19.1 23.2 9.8 020EW 46 24.4 17.7 16.6 23.2 19.3 14.4 22.5 20.1 13.5 21.1 21.5 11.8 19.8 23.4 10.2 48 25.2 17.6 17.2 23.9 19.6 14.7 23.3 20.5 13.6 21.9 21.9 12.0 20.4 23.5 10.4 50 26.1 18.0 17.5 24.7 19.8 15.0 24.0 20.9 13.7 22.6 22.1 12.2 21.1 23.7 10.7 40 26.1 20.9 15.0 24.9 22.4 13.3 24.3 23.3 12.5 22.4 24.8 10.8 20.5 27.0 9.1 42 27.1 21.1 15.4 25.8 22.7 13.6 24.9 23.2 12.9 23.3 25.1 11.1 21.9 28.0 9.4 44 28.1 21.3 15.9 26.7 23.1 13.9 26.0 24.0 13.0 24.4 25.8 11.3 22.7 28.1 9.7 025EW 46 29.1 21.4 16.3 27.6 23.4 14.2 26.9 24.3 13.2 25.2 26.0 11.6 23.6 28.3 10.0 48 30.1 21.3 16.9 28.5 23.7 14.4 27.7 24.9 13.4 26.1 26.5 11.8 24.4 28.5 10.3 50 31.2 21.8 17.2 29.5 24.0 14.7 28.6 25.4 13.5 26.9 26.8 12.1 25.2 28.6 10.6 40 29.8 23.3 15.3 28.4 25.0 13.6 27.7 26.0 12.8 25.5 27.7 11.1 23.4 30.2 9.3 42 31.0 23.5 15.8 29.4 25.4 13.9 28.4 25.9 13.2 26.7 28.1 11.4 25.0 31.2 9.6 44 32.1 23.7 16.3 30.5 25.8 14.2 29.7 26.8 13.3 27.8 28.8 11.6 26.0 31.4 9.9 030EW 46 33.2 23.9 16.7 31.5 26.1 14.5 30.7 27.2 13.6 28.8 29.0 11.9 26.9 31.6 10.2 48 34.4 23.8 17.3 32.6 26.5 14.8 31.7 27.8 13.7 29.8 29.6 12.1 27.9 31.8 10.5 50 35.6 24.3 17.6 33.7 26.8 15.1 32.7 28.3 13.8 30.7 29.9 12.3 28.8 32.0 10.8 40 38.6 28.9 16.0 36.7 30.9 14.2 35.8 32.2 13.4 33.0 34.3 11.6 30.3 37.3 9.7 42 40.1 29.1 16.5 38.1 31.4 14.5 36.7 32.0 13.8 34.5 34.7 11.9 32.3 38.6 10.0 44 41.5 29.4 17.0 39.4 31.9 14.8 38.4 33.2 13.9 36.0 35.6 12.1 33.6 38.9 10.4 040EW 46 43.0 29.6 17.4 40.8 32.3 15.1 39.7 33.6 14.2 37.2 35.9 12.4 34.8 39.1 10.7 48 44.4 29.5 18.1 42.1 32.7 15.4 41.0 34.3 14.3 38.5 36.6 12.6 36.0 39.3 11.0 50 46.0 30.0 18.4 43.5 33.2 15.7 42.2 35.0 14.5 39.7 37.0 12.9 37.2 39.6 11.3 40 44.3 32.9 16.2 42.2 35.3 14.4 41.1 36.7 13.5 37.9 39.1 11.6 34.8 42.5 9.8 42 46.0 33.2 16.6 43.7 35.8 14.7 42.2 36.5 13.9 39.6 39.6 12.0 37.1 44.0 10.1 44 47.7 33.5 17.1 45.3 36.3 15.0 44.1 37.8 14.0 41.3 40.6 12.2 38.6 44.3 10.4 045EW 46 49.3 33.7 17.6 46.8 36.8 15.3 45.6 38.3 14.3 42.7 41.0 12.5 40.0 44.6 10.8 48 51.0 33.6 18.2 48.4 37.3 15.6 47.1 39.2 14.4 44.2 41.7 12.7 41.4 44.8 11.1 50 52.9 34.3 18.5 50.0 37.8 15.9 48.5 39.9 14.6 45.6 42.2 13.0 42.7 45.1 11.4 40 50.9 40.7 15.0 48.4 43.6 13.3 47.2 45.3 12.5 43.5 48.3 10.8 39.9 52.6 9.1 42 52.8 41.0 15.4 50.2 44.2 13.6 48.4 45.1 12.9 45.4 48.9 11.1 42.6 54.4 9.4 44 54.7 41.4 15.9 52.0 44.9 13.9 50.6 46.7 13.0 47.4 50.2 11.3 44.3 54.8 9.7 050EW 46 56.6 41.6 16.3 53.7 45.5 14.2 52.3 47.3 13.2 49.0 50.6 11.6 45.9 55.1 10.0 48 58.5 41.5 16.9 55.5 46.1 14.4 54.0 48.4 13.4 50.8 51.5 11.8 47.5 55.4 10.3 50 60.7 42.3 17.2 57.3 46.7 14.7 55.7 49.4 13.5 52.4 52.1 12.1 49.0 55.7 10.6 40 58.5 43.4 16.2 55.6 46.5 14.4 54.3 48.4 13.5 50.1 51.6 11.6 45.9 56.1 9.8 42 60.8 43.8 16.6 57.7 47.3 14.7 55.7 48.2 13.9 52.3 52.3 12.0 49.0 58.1 10.1 44 63.0 44.2 17.1 59.8 48.0 15.0 58.2 49.9 14.0 54.5 53.6 12.2 50.9 58.5 10.4 060EW 46 65.1 44.5 17.6 61.8 48.6 15.3 60.1 50.6 14.3 56.4 54.1 12.5 52.8 58.8 10.8 48 67.3 44.3 18.2 63.9 49.3 15.6 62.1 51.7 14.4 58.4 55.0 12.7 54.6 59.2 11.1 50 69.8 45.2 18.5 65.9 49.9 15.9 64.0 52.7 14.6 60.2 55.6 13.0 56.4 59.5 11.4 Notes: 1. Bold box areas certified in accordance with ARI Standard 590. 2. Ratings based on HCFC-22, evaporator fouling of 0.00025, evaporator temperature drop of 10°F and sea level altitude. 3. For 208V units multiply capacity and EER by 0.98. 4. Ratings are based on circuit #1 in lead position and circuit #2 in lag position. 5. Interpolation is allowed; extrapolation is not permitted. Consult McQuay for performance outside the ratings shown. 6. For LWT of 40°F and below please refer to Application Adjustment Factors section.

12 WHR 017EW - 210EW Product Manual WHR Table 6, WHR 070EW through WHR 120EW, 60 Hz, English units ENTERING CONDENSER WATER TEMPERATURE (10°F DELTA T) WHR LWT 70°F 80°F 85°F 95°F 105°F UNIT (°F) CAP. PWR CAP. PWR CAP. PWR CAP. PWR CAP. PWR SIZE TONS kWi EER TONS kWi EER TONS kWi EER TONS kWi EER TONS kWi EER 40 70.6 54.7 15.5 67.1 58.6 13.7 65.5 61.0 12.9 60.4 65.1 11.1 55.4 70.8 9.4 42 73.3 55.2 15.9 69.6 59.5 14.0 67.2 60.7 13.3 63.0 65.9 11.5 59.1 73.2 9.7 44 76.0 55.7 16.4 72.1 60.4 14.3 70.2 62.9 13.4 65.8 67.6 11.7 61.4 73.7 10.0 070EW 46 78.6 56.1 16.8 74.6 61.3 14.6 72.5 63.7 13.7 68.0 68.1 12.0 63.7 74.1 10.3 48 81.2 55.9 17.4 77.1 62.1 14.9 74.9 65.1 13.8 70.4 69.4 12.2 65.8 74.5 10.6 50 84.2 57.0 17.7 79.5 62.9 15.2 77.2 66.4 13.9 72.7 70.1 12.4 68.0 75.0 10.9 40 77.1 60.3 15.3 73.3 64.5 13.6 71.6 67.2 12.8 66.0 71.6 11.1 60.5 77.9 9.3 42 80.1 60.8 15.8 76.0 65.6 13.9 73.4 66.8 13.2 68.9 72.5 11.4 64.6 80.6 9.6 44 83.0 61.3 16.3 78.8 66.5 14.2 76.7 69.2 13.3 71.9 74.4 11.6 67.1 81.1 9.9 080EW 46 85.8 61.7 16.7 81.5 67.5 14.5 79.2 70.2 13.6 74.3 75.0 11.9 69.6 81.6 10.2 48 88.7 61.5 17.3 84.2 68.3 14.8 81.8 71.7 13.7 76.9 76.4 12.1 71.9 82.1 10.5 50 92.0 62.7 17.6 86.9 69.2 15.1 84.4 73.1 13.8 79.4 77.2 12.3 74.3 82.6 10.8 40 84.2 65.8 15.3 80.1 70.5 13.6 78.2 73.4 12.8 72.1 78.2 11.1 66.1 85.1 9.3 42 87.5 66.4 15.8 83.1 71.6 13.9 80.2 73.0 13.2 75.3 79.2 11.4 70.6 88.1 9.6 44 90.7 66.9 16.3 86.0 72.7 14.2 83.8 75.6 13.3 78.5 81.2 11.6 73.3 88.6 9.9 085EW 46 93.8 67.4 16.7 89.0 73.7 14.5 86.6 76.6 13.6 81.2 82.0 11.9 76.0 89.2 10.2 48 97.0 67.2 17.3 92.0 74.7 14.8 89.4 78.3 13.7 84.1 83.4 12.1 78.6 89.7 10.5 50 100.5 68.5 17.6 94.9 75.6 15.1 92.2 79.9 13.8 86.7 84.3 12.3 81.2 90.2 10.8 40 91.3 71.3 15.3 86.8 76.4 13.6 84.7 79.5 12.8 78.1 84.8 11.1 71.6 92.2 9.3 42 94.8 72.0 15.8 90.0 77.6 13.9 86.9 79.1 13.2 81.5 85.8 11.4 76.5 95.4 9.6 44 98.2 72.5 16.3 93.2 78.7 14.2 90.8 81.9 13.3 85.1 88.0 11.6 79.4 96.0 9.9 090EW 46 101.6 73.0 16.7 96.4 79.9 14.5 93.8 83.1 13.6 88.0 88.8 11.9 82.4 96.6 10.2 48 105.1 72.8 17.3 99.7 80.9 14.8 96.9 84.9 13.7 91.1 90.4 12.1 85.2 97.1 10.5 50 108.9 74.2 17.6 102.9 81.9 15.1 99.9 86.6 13.8 94.0 91.4 12.3 88.0 97.8 10.8 40 95.4 71.9 15.9 90.7 77.0 14.1 88.5 80.1 13.3 81.6 85.4 11.5 74.9 92.9 9.7 42 99.1 72.5 16.4 94.1 78.2 14.4 90.8 79.7 13.7 85.2 86.5 11.8 79.9 96.1 10.0 44 102.7 73.1 16.9 97.4 79.3 14.7 94.9 82.5 13.8 88.9 88.7 12.0 83.0 96.7 10.3 095EW 46 106.2 73.6 17.3 100.8 80.4 15.0 98.0 83.7 14.1 92.0 89.4 12.3 86.1 97.3 10.6 48 109.8 73.3 18.0 104.2 81.5 15.3 101.3 85.5 14.2 95.2 91.1 12.5 89.0 97.9 10.9 50 113.8 74.8 18.3 107.5 82.5 15.6 104.4 87.2 14.4 98.2 92.0 12.8 92.0 98.5 11.2 40 101.2 75.7 16.0 96.3 81.1 14.2 94.0 84.4 13.4 86.6 90.0 11.6 79.5 97.8 9.7 42 105.1 76.4 16.5 99.8 82.4 14.5 96.4 84.0 13.8 90.4 91.1 11.9 84.8 101.2 10.0 44 109.0 77.0 17.0 103.4 83.6 14.8 100.7 86.9 13.9 94.4 93.4 12.1 88.1 101.9 10.4 100EW 46 112.7 77.5 17.4 107.0 84.7 15.1 104.0 88.1 14.2 97.6 94.2 12.4 91.3 102.5 10.7 48 116.5 77.3 18.1 110.5 85.9 15.4 107.4 90.1 14.3 101.0 95.9 12.6 94.5 103.1 11.0 50 120.7 78.8 18.4 114.1 86.9 15.7 110.8 91.9 14.5 104.2 97.0 12.9 97.6 103.7 11.3 40 110.7 84.6 15.7 105.3 90.6 13.9 102.7 94.3 13.1 94.7 100.5 11.3 86.9 109.3 9.5 42 114.9 85.4 16.2 109.2 92.0 14.2 105.4 93.8 13.5 98.9 101.8 11.7 92.7 113.1 9.8 44 119.1 86.0 16.6 113.1 93.4 14.5 110.1 97.1 13.6 103.2 104.4 11.9 96.3 113.9 10.1 110EW 46 123.2 86.6 17.1 116.9 94.7 14.8 113.7 98.5 13.9 106.7 105.3 12.2 99.9 114.6 10.5 48 127.4 86.3 17.7 120.8 95.9 15.1 117.5 100.6 14.0 110.4 107.2 12.4 103.3 115.2 10.8 50 132.0 88.0 18.0 124.7 97.1 15.4 121.1 102.7 14.2 114.0 108.3 12.6 106.7 115.9 11.0 40 113.3 85.3 15.9 107.7 91.4 14.1 105.1 95.1 13.3 96.9 101.4 11.5 88.9 110.3 9.7 42 117.7 86.1 16.4 111.7 92.8 14.4 107.9 94.6 13.7 101.2 102.7 11.8 94.9 114.1 10.0 44 121.9 86.8 16.9 115.7 94.2 14.7 112.7 98.0 13.8 105.6 105.3 12.0 98.6 114.9 10.3 115EW 46 126.1 87.4 17.3 119.7 95.5 15.0 116.4 99.3 14.1 109.2 106.2 12.3 102.2 115.6 10.6 48 130.4 87.1 18.0 123.7 96.8 15.3 120.3 101.5 14.2 113.0 108.1 12.5 105.7 116.2 10.9 50 135.1 88.8 18.3 127.7 98.0 15.6 124.0 103.6 14.4 116.6 109.3 12.8 109.2 116.9 11.2 40 122.0 93.3 15.7 116.1 99.9 13.9 113.3 104.0 13.1 104.4 110.9 11.3 95.8 120.6 9.5 42 126.7 94.1 16.2 120.4 101.5 14.2 116.2 103.4 13.5 109.0 112.2 11.7 102.2 124.7 9.8 44 131.4 94.8 16.6 124.7 103.0 14.5 121.4 107.1 13.6 113.8 115.1 11.9 106.2 125.6 10.1 120EW 46 135.8 95.5 17.1 129.0 104.4 14.8 125.4 108.6 13.9 117.6 116.1 12.2 110.1 126.3 10.5 48 140.5 95.2 17.7 133.2 105.8 15.1 129.5 111.0 14.0 121.8 118.2 12.4 113.9 127.0 10.8 50 145.6 97.1 18.0 137.5 107.1 15.4 133.5 113.2 14.2 125.6 119.5 12.6 117.6 127.8 11.0 Notes: 1. Bold box areas certified in accordance with ARI Standard 590. 2. Ratings based on HCFC-22, evaporator fouling of 0.00025, evaporator temperature drop of 10°F and sea level altitude. 3. For 208V units multiply capacity and EER by 0.98. 4. Ratings are based on circuit #1 in lead position and circuit #2 in lag position. 5. Interpolation is allowed; extrapolation is not permitted. Consult McQuay for performance outside the ratings shown. 6. For LWT of 40°F and below please refer to Application Adjustment Factors section.

Product Manual WHR WHR 017EW - 210EW 13 Table 7, WHR 130EW through WHR 210EW, 60 Hz, English units ENTERING CONDENSER WATER TEMPERATURE (10°F DELTA T) WHR LWT 70°F 80°F 85°F 95°F 105°F UNIT (°F) CAP. PWR CAP. PWR CAP. PWR CAP. PWR CAP. PWR SIZE TONS kWi EER TONS kWi EER TONS kWi EER TONS kWi EER TONS kWi EER 40 132.1 103.2 15.3 125.6 110.6 13.6 122.6 115.1 12.8 113.0 122.7 11.1 103.7 133.4 9.3 42 137.2 104.2 15.8 130.3 112.3 13.9 125.7 114.5 13.2 118.0 124.2 11.4 110.6 138.1 9.6 44 142.2 105.0 16.3 134.9 114.0 14.2 131.4 118.6 13.3 123.1 127.4 11.6 114.9 139.0 9.9 130EW 46 147.0 105.7 16.7 139.6 115.6 14.5 135.7 120.2 13.6 127.3 128.5 11.9 119.2 139.8 10.2 48 152.0 105.4 17.3 144.2 117.1 14.8 140.2 122.8 13.7 131.8 130.8 12.1 123.3 140.6 10.5 50 157.5 107.4 17.6 148.9 118.6 15.1 144.5 125.3 13.8 136.0 132.2 12.3 127.3 141.5 10.8 40 144.6 106.7 16.3 137.6 114.2 14.5 134.3 118.9 13.6 123.8 126.7 11.7 113.5 137.8 9.9 42 150.2 107.6 16.8 142.7 116.0 14.8 137.7 118.3 14.0 129.2 128.3 12.1 121.2 142.6 10.2 44 155.7 108.4 17.2 147.8 117.7 15.1 143.9 122.5 14.1 134.8 131.6 12.3 125.9 143.6 10.5 145EW 46 161.0 109.2 17.7 152.9 119.4 15.4 148.6 124.2 14.4 139.4 132.7 12.6 130.5 144.4 10.8 48 166.5 108.8 18.4 157.9 120.9 15.7 153.5 126.9 14.5 144.3 135.1 12.8 135.0 145.2 11.2 50 172.5 111.0 18.7 163.0 122.5 16.0 158.3 129.4 14.7 148.9 136.6 13.1 139.4 146.1 11.4 40 153.3 115.5 15.9 145.8 123.7 14.1 142.3 128.7 13.3 131.2 137.2 11.5 120.3 149.3 9.7 42 159.2 116.5 16.4 151.2 125.6 14.4 145.9 128.1 13.7 136.9 139.0 11.8 128.4 154.4 10.0 44 165.0 117.4 16.9 156.6 127.5 14.7 152.5 132.6 13.8 142.9 142.5 12.0 133.4 155.5 10.3 155EW 46 170.6 118.2 17.3 162.0 129.3 15.0 157.5 134.4 14.1 147.8 143.7 12.3 138.3 156.4 10.6 48 176.4 117.8 18.0 167.4 131.0 15.3 162.7 137.4 14.2 153.0 146.3 12.5 143.0 157.3 10.9 50 182.8 120.2 18.3 172.8 132.6 15.6 167.8 140.1 14.4 157.8 147.9 12.8 147.8 158.2 11.2 40 163.1 128.5 15.2 155.2 137.6 13.5 151.4 143.2 12.7 139.6 152.7 11.0 128.1 166.1 9.3 42 169.4 129.7 15.7 160.9 139.8 13.8 155.3 142.5 13.1 145.7 154.6 11.3 136.7 171.8 9.5 44 175.6 130.6 16.1 166.6 141.8 14.1 162.3 147.5 13.2 152.1 158.5 11.5 141.9 173.0 9.8 165EW 46 181.6 131.6 16.6 172.4 143.8 14.4 167.7 149.6 13.5 157.3 159.9 11.8 147.2 174.0 10.2 48 187.8 131.1 17.2 178.1 145.7 14.7 173.2 152.8 13.6 162.8 162.8 12.0 152.2 175.0 10.4 50 194.6 133.7 17.5 183.9 147.5 15.0 178.5 155.9 13.7 168.0 164.6 12.2 157.3 176.1 10.7 40 177.0 140.5 15.1 168.4 150.5 13.4 164.3 156.6 12.6 151.4 166.9 10.9 138.9 181.6 9.2 42 183.8 141.8 15.6 174.6 152.8 13.7 168.5 155.8 13.0 158.1 169.0 11.2 148.3 187.9 9.5 44 190.5 142.8 16.0 180.8 155.1 14.0 176.1 161.3 13.1 165.0 173.3 11.4 154.0 189.1 9.8 175EW 46 197.1 143.8 16.4 187.1 157.2 14.3 181.9 163.5 13.3 170.6 174.8 11.7 159.7 190.3 10.1 48 203.7 143.3 17.1 193.3 159.3 14.6 187.9 167.1 13.5 176.6 178.0 11.9 165.2 191.3 10.4 50 211.1 146.2 17.3 199.5 161.3 14.8 193.7 170.5 13.6 182.3 179.9 12.2 170.6 192.5 10.6 40 182.9 138.8 15.8 174.0 148.7 14.0 169.8 154.8 13.2 156.5 165.0 11.4 143.6 179.4 9.6 42 190.0 140.1 16.3 180.4 151.0 14.3 174.2 153.9 13.6 163.4 167.0 11.7 153.2 185.7 9.9 44 196.9 141.2 16.7 186.9 153.2 14.6 182.0 159.4 13.7 170.5 171.3 11.9 159.2 186.9 10.2 185EW 46 203.7 142.1 17.2 193.3 155.4 14.9 188.0 161.6 14.0 176.4 172.8 12.2 165.1 188.0 10.5 48 210.6 141.7 17.8 199.8 157.4 15.2 194.2 165.1 14.1 182.5 175.9 12.5 170.7 189.0 10.8 50 218.2 144.5 18.1 206.2 159.4 15.5 200.2 168.5 14.3 188.4 177.8 12.7 176.4 190.2 11.1 40 197.0 157.6 15.0 187.4 168.7 13.3 182.9 175.7 12.5 168.6 187.2 10.8 154.6 203.6 9.1 42 204.6 159.0 15.4 194.3 171.4 13.6 187.6 174.7 12.9 176.0 189.6 11.1 165.0 210.7 9.4 44 212.1 160.2 15.9 201.3 173.9 13.9 196.0 180.9 13.0 183.7 194.4 11.3 171.4 212.1 9.7 195EW 46 219.3 161.3 16.3 208.2 176.3 14.2 202.5 183.4 13.2 189.9 196.1 11.6 177.8 213.4 10.0 48 226.8 160.8 16.9 215.1 178.7 14.4 209.1 187.4 13.4 196.6 199.6 11.8 183.8 214.5 10.3 50 235.0 164.0 17.2 222.1 180.9 14.7 215.6 191.2 13.5 202.9 201.8 12.1 189.9 215.9 10.6 40 210.0 166.7 15.1 199.8 178.6 13.4 195.0 185.9 12.6 179.7 198.1 10.9 164.9 215.5 9.2 42 218.2 168.2 15.6 207.2 181.4 13.7 200.0 184.9 13.0 187.7 200.6 11.2 176.0 223.0 9.5 44 226.1 169.5 16.0 214.6 184.0 14.0 209.0 191.5 13.1 195.8 205.7 11.4 182.8 224.5 9.8 210EW 46 233.9 170.7 16.4 222.0 186.6 14.3 215.9 194.1 13.3 202.5 207.5 11.7 189.6 225.8 10.1 48 241.8 170.1 17.1 229.4 189.1 14.6 223.0 198.3 13.5 209.6 211.2 11.9 196.0 227.0 10.4 50 250.6 173.5 17.3 236.8 191.5 14.8 229.9 202.3 13.6 216.3 213.5 12.2 202.5 228.5 10.6 Notes: 1. Bold box areas certified in accordance with ARI Standard 590. 2. Ratings based on HCFC-22, evaporator fouling of 0.00025, evaporator temperature drop of 10°F and sea level altitude. 3. For 208V units multiply capacity and EER by 0.98 4. Ratings are based on circuit #1 in lead position and circuit #2 in lag position. 5. Interpolation is allowed; extrapolation is not permitted. Consult McQuay for performance outside the ratings shown. 6. For LWT of 40°F and below please refer to Application Adjustment Factors section.

14 WHR 017EW - 210EW Product Manual WHR Table 8, WHR 017EW through WHR 060EW, 60 Hz, Metric units ENTERING CONDENSER WATER TEMPERATURE (°C) WHR LWT 20°C 25°C 30°C 35°C 40°C UNIT (°C) CAP. PWR CAP. PWR CAP. PWR CAP. PWR CAP. PWR SIZE kW kWi COP kW kWi COP kW kWi COP kW kWi COP kW kWi COP 5 65.1 12.9 5.1 61.9 13.8 4.5 60.0 14.3 4.2 55.0 15.6 3.5 50.6 17.4 2.9 6 65.3 12.9 5.1 62.1 13.9 4.5 59.5 14.1 4.2 55.2 15.5 3.6 51.5 17.7 2.9 7 67.9 13.0 5.2 64.6 14.1 4.6 62.8 14.8 4.3 58.0 16.1 3.6 53.7 17.8 3.0 017EW 8 70.5 13.1 5.4 67.1 14.3 4.7 65.0 15.0 4.3 60.2 16.2 3.7 56.0 17.9 3.1 9 73.1 13.0 5.6 69.6 14.4 4.8 67.4 15.3 4.4 62.6 16.6 3.8 58.1 18.0 3.2 10 77.0 13.3 5.8 73.1 14.6 5.0 70.5 15.7 4.5 65.6 16.8 3.9 61.0 18.1 3.4 5 79.7 17.0 4.7 75.8 18.2 4.2 73.4 18.9 3.9 67.4 20.6 3.3 62.0 22.9 2.7 6 80.0 17.0 4.7 76.1 18.3 4.2 72.9 18.5 3.9 67.6 20.6 3.3 63.1 23.3 2.7 7 83.2 17.1 4.9 79.1 18.5 4.3 76.9 19.4 4.0 71.1 21.2 3.3 65.8 23.4 2.8 020EW 8 86.4 17.3 5.0 82.2 18.8 4.4 79.6 19.7 4.0 73.8 21.4 3.4 68.6 23.5 2.9 9 89.6 17.2 5.2 85.2 19.0 4.5 82.5 20.2 4.1 76.6 21.8 3.5 71.2 23.7 3.0 10 94.4 17.6 5.4 89.5 19.3 4.6 86.4 20.7 4.2 80.3 22.1 3.6 74.7 23.8 3.1 5 95.0 20.6 4.6 90.4 22.1 4.1 87.6 22.9 3.8 80.4 25.0 3.2 74.0 27.7 2.7 6 95.4 20.6 4.6 90.7 22.1 4.1 87.0 22.4 3.9 80.7 24.9 3.2 75.3 28.2 2.7 7 99.2 20.7 4.8 94.4 22.4 4.2 91.7 23.5 3.9 84.8 25.7 3.3 78.5 28.3 2.8 025EW 8 103.0 20.9 4.9 98.0 22.8 4.3 95.0 23.9 4.0 88.0 25.9 3.4 81.8 28.5 2.9 9 106.8 20.8 5.1 101.6 23.0 4.4 98.4 24.5 4.0 91.4 26.5 3.5 84.9 28.6 3.0 10 112.5 21.3 5.3 106.7 23.3 4.6 103.0 25.1 4.1 95.8 26.8 3.6 89.1 28.8 3.1 5 108.6 22.9 4.7 103.3 24.7 4.2 100.1 25.6 3.9 91.8 27.9 3.3 84.5 31.0 2.7 6 109.0 23.0 4.7 103.7 24.7 4.2 99.3 25.1 4.0 92.1 27.8 3.3 86.0 31.5 2.7 7 113.4 23.1 4.9 107.8 25.1 4.3 104.7 26.3 4.0 96.8 28.7 3.4 89.7 31.6 2.8 030EW 8 117.6 23.4 5.0 111.9 25.4 4.4 108.5 26.7 4.1 100.5 28.9 3.5 93.4 31.8 2.9 9 122.0 23.2 5.3 116.1 25.6 4.5 112.4 27.3 4.1 104.4 29.5 3.5 96.9 32.0 3.0 10 128.5 23.7 5.4 121.9 26.0 4.7 117.7 28.0 4.2 109.5 29.9 3.7 101.8 32.2 3.2 5 140.4 28.4 4.9 133.5 30.5 4.4 129.4 31.6 4.1 118.7 34.5 3.4 109.2 38.3 2.9 6 140.9 28.4 5.0 134.0 30.6 4.4 128.4 31.0 4.1 119.1 34.4 3.5 111.2 38.9 2.9 7 146.6 28.6 5.1 139.4 31.0 4.5 135.4 32.5 4.2 125.2 35.5 3.5 115.9 39.1 3.0 040EW 8 152.1 28.9 5.3 144.7 31.4 4.6 140.3 33.0 4.3 129.9 35.8 3.6 120.8 39.4 3.1 9 157.8 28.7 5.5 150.1 31.7 4.7 145.3 33.8 4.3 135.0 36.5 3.7 125.3 39.6 3.2 10 166.2 29.4 5.7 157.6 32.2 4.9 152.2 34.6 4.4 141.5 37.0 3.8 131.6 39.8 3.3 5 161.2 32.4 5.0 153.3 34.8 4.4 148.6 36.0 4.1 136.3 39.4 3.5 125.5 43.7 2.9 6 161.8 32.4 5.0 153.9 34.9 4.4 147.5 35.3 4.2 136.8 39.2 3.5 127.7 44.4 2.9 7 168.3 32.6 5.2 160.1 35.3 4.5 155.5 37.1 4.2 143.8 40.5 3.5 133.1 44.6 3.0 045EW 8 174.7 33.0 5.3 166.2 35.8 4.6 161.1 37.6 4.3 149.2 40.8 3.7 138.7 44.9 3.1 9 181.2 32.7 5.5 172.4 36.2 4.8 166.9 38.6 4.3 155.0 41.7 3.7 144.0 45.1 3.2 10 190.9 33.5 5.7 181.0 36.7 4.9 174.8 39.5 4.4 162.5 42.2 3.9 151.1 45.4 3.3 5 185.0 40.0 4.6 175.9 43.0 4.1 170.5 44.5 3.8 156.4 48.6 3.2 144.0 54.0 2.7 6 185.7 40.0 4.6 176.6 43.1 4.1 169.2 43.7 3.9 157.0 48.4 3.2 146.5 54.8 2.7 7 193.1 40.3 4.8 183.7 43.7 4.2 178.4 45.8 3.9 165.0 50.1 3.3 152.8 55.1 2.8 050EW 8 200.4 40.8 4.9 190.7 44.3 4.3 184.8 46.5 4.0 171.2 50.4 3.4 159.2 55.5 2.9 9 207.9 40.5 5.1 197.8 44.7 4.4 191.5 47.6 4.0 177.9 51.5 3.5 165.2 55.7 3.0 10 219.0 41.4 5.3 207.7 45.4 4.6 200.5 48.8 4.1 186.5 52.1 3.6 173.4 56.1 3.1 5 212.8 42.7 5.0 202.4 45.9 4.4 196.1 47.6 4.1 179.9 51.9 3.5 165.6 57.6 2.9 6 213.5 42.8 5.0 203.1 46.0 4.4 194.7 46.6 4.2 180.6 51.7 3.5 168.5 58.6 2.9 7 222.2 43.1 5.2 211.3 46.6 4.5 205.2 48.9 4.2 189.8 53.5 3.5 175.7 58.9 3.0 060EW 8 230.5 43.5 5.3 219.4 47.3 4.6 212.6 49.6 4.3 196.9 53.9 3.7 183.1 59.3 3.1 9 239.1 43.2 5.5 227.5 47.7 4.8 220.3 50.9 4.3 204.6 55.0 3.7 190.0 59.5 3.2 10 251.9 44.2 5.7 238.9 48.5 4.9 230.7 52.1 4.4 214.5 55.6 3.9 199.5 59.9 3.3 Notes: 1. Ratings based on HCFC-22, evaporator and condenser fouling of 0.044, evaporator and condenser temperature drop of 5.6°C. 2. For 208V units multiply capacity and COP by 0.98. 3. Ratings are based on circuit #1 in lead position and circuit #2 in lag position. 4. Interpolation is allowed; extrapolation is not permitted. Consult McQuay for performance outside the ratings shown. 5. KWi input is for compressors only. COP is for the entire unit, including compressors and control power. 6. For LWT of 5°C and below please refer to Application Adjustment Factors section.

Product Manual WHR WHR 017EW - 210EW 15 Table 9, WHR 060EW through WHR 120EW, 60 Hz, Metric units ENTERING CONDENSER WATER TEMPERATURE (°C) WHR LWT 20°C 25°C 30°C 35°C 40°C UNIT (°C) CAP. PWR CAP. PWR CAP. PWR CAP. PWR CAP. PWR SIZE kW kWi COP kW kWi COP kW kWi COP kW kWi COP kW kWi COP 5 256.6 53.8 4.8 244.1 57.9 4.2 236.5 60.0 3.9 217.0 65.5 3.3 199.7 72.6 2.7 6 257.6 53.9 4.8 245.0 58.0 4.2 234.8 58.8 4.0 217.8 65.2 3.3 203.3 73.8 2.8 7 268.0 54.3 4.9 254.9 58.8 4.3 247.5 61.7 4.0 228.9 67.4 3.4 211.9 74.2 2.9 070EW 8 278.1 54.9 5.1 264.6 59.6 4.4 256.4 62.6 4.1 237.5 67.9 3.5 220.8 74.7 3.0 9 288.4 54.5 5.3 274.4 60.1 4.6 265.7 64.1 4.1 246.8 69.3 3.6 229.2 75.0 3.1 10 303.8 55.7 5.5 288.2 61.1 4.7 278.2 65.7 4.2 258.7 70.1 3.7 240.6 75.5 3.2 5 280.4 59.3 4.7 266.7 63.7 4.2 258.4 66.0 3.9 237.0 72.1 3.3 218.2 80.0 2.7 6 281.4 59.3 4.7 267.7 63.8 4.2 256.5 64.7 4.0 238.0 71.8 3.3 222.1 81.2 2.7 7 292.8 59.8 4.9 278.5 64.7 4.3 270.4 67.9 4.0 250.1 74.2 3.4 231.6 81.7 2.8 080EW 8 303.8 60.4 5.0 289.1 65.6 4.4 280.2 68.9 4.1 259.5 74.7 3.5 241.3 82.2 2.9 9 315.1 59.9 5.3 299.8 66.2 4.5 290.3 70.6 4.1 269.6 76.3 3.5 250.4 82.6 3.0 10 332.0 61.3 5.4 314.9 67.3 4.7 304.0 72.3 4.2 282.7 77.2 3.7 262.9 83.1 3.2 5 306.3 64.7 4.7 291.4 69.6 4.2 282.3 72.1 3.9 259.0 78.7 3.3 238.4 87.4 2.7 6 307.5 64.8 4.7 292.5 69.7 4.2 280.3 70.7 4.0 260.0 78.4 3.3 242.7 88.8 2.7 7 319.9 65.3 4.9 304.2 70.7 4.3 295.4 74.2 4.0 273.2 81.0 3.4 253.0 89.2 2.8 085EW 8 331.9 66.0 5.0 315.9 71.7 4.4 306.1 75.2 4.1 283.5 81.7 3.5 263.6 89.8 2.9 9 344.3 65.5 5.3 327.5 72.3 4.5 317.2 77.1 4.1 294.6 83.3 3.5 273.5 90.2 3.0 10 362.7 67.0 5.4 344.0 73.5 4.7 332.1 79.0 4.2 308.9 84.3 3.7 287.2 90.8 3.2 5 331.9 70.1 4.7 315.7 75.4 4.2 305.9 78.1 3.9 280.6 85.3 3.3 258.3 94.7 2.7 6 333.2 70.2 4.7 316.9 75.5 4.2 303.7 76.6 4.0 281.7 85.0 3.3 262.9 96.2 2.7 7 346.6 70.7 4.9 329.7 76.6 4.3 320.1 80.3 4.0 296.1 87.8 3.4 274.1 96.7 2.8 090EW 8 359.7 71.5 5.0 342.2 77.7 4.4 331.7 81.5 4.1 307.2 88.5 3.5 285.6 97.3 2.9 9 373.0 71.0 5.3 354.9 78.4 4.5 343.7 83.6 4.1 319.2 90.3 3.5 296.4 97.8 3.0 10 393.0 72.6 5.4 372.7 79.6 4.7 359.9 85.6 4.2 334.7 91.4 3.7 311.2 98.4 3.2 5 346.9 70.7 4.9 330.0 76.0 4.3 319.7 78.7 4.1 293.3 85.9 3.4 270.0 95.3 2.8 6 348.2 70.7 4.9 331.2 76.1 4.4 317.4 77.2 4.1 294.4 85.6 3.4 274.8 96.9 2.8 7 362.2 71.3 5.1 344.5 77.2 4.5 334.5 80.9 4.1 309.4 88.4 3.5 286.5 97.4 2.9 095EW 8 375.9 72.0 5.2 357.7 78.2 4.6 346.7 82.1 4.2 321.1 89.1 3.6 298.5 98.0 3.0 9 389.9 71.5 5.5 370.9 78.9 4.7 359.2 84.2 4.3 333.6 91.0 3.7 309.8 98.5 3.1 10 410.7 73.1 5.6 389.6 80.2 4.9 376.1 86.2 4.4 349.8 92.0 3.8 325.2 99.1 3.3 5 368.1 74.4 4.9 350.1 80.0 4.4 339.3 82.9 4.1 311.2 90.5 3.4 286.5 100.4 2.9 6 369.5 74.5 5.0 351.5 80.2 4.4 336.8 81.3 4.1 312.4 90.2 3.5 291.6 102.1 2.9 7 384.4 75.1 5.1 365.6 81.3 4.5 355.0 85.3 4.2 328.4 93.2 3.5 304.0 102.6 3.0 100EW 8 398.9 75.9 5.3 379.6 82.4 4.6 367.9 86.5 4.3 340.7 93.9 3.6 316.8 103.3 3.1 9 413.7 75.3 5.5 393.6 83.2 4.7 381.1 88.7 4.3 354.0 95.8 3.7 328.7 103.7 3.2 10 435.8 77.0 5.7 413.4 84.5 4.9 399.1 90.8 4.4 371.1 97.0 3.8 345.1 104.4 3.3 5 402.5 83.2 4.8 382.8 89.4 4.3 370.9 92.6 4.0 340.3 101.2 3.4 313.2 112.2 2.8 6 404.0 83.3 4.9 384.3 89.6 4.3 368.3 90.8 4.1 341.6 100.8 3.4 318.8 114.0 2.8 7 420.3 83.9 5.0 399.7 90.8 4.4 388.1 95.3 4.1 359.0 104.1 3.4 332.4 114.6 2.9 110EW 8 436.1 84.8 5.1 415.0 92.1 4.5 402.2 96.7 4.2 372.5 104.9 3.6 346.3 115.4 3.0 9 452.3 84.1 5.4 430.3 92.9 4.6 416.7 99.1 4.2 387.0 107.1 3.6 359.4 115.9 3.1 10 476.5 86.1 5.5 452.0 94.4 4.8 436.4 101.5 4.3 405.8 108.3 3.7 377.3 116.7 3.2 5 412.0 83.9 4.9 391.9 90.2 4.3 379.7 93.5 4.1 348.3 102.1 3.4 320.6 113.2 2.8 6 413.5 84.0 4.9 393.4 90.4 4.4 376.9 91.6 4.1 349.7 101.6 3.4 326.4 115.0 2.8 7 430.2 84.6 5.1 409.2 91.6 4.5 397.3 96.1 4.1 367.5 105.0 3.5 340.2 115.7 2.9 115EW 8 446.4 85.5 5.2 424.8 92.9 4.6 411.7 97.5 4.2 381.3 105.8 3.6 354.5 116.4 3.0 9 463.0 84.9 5.5 440.5 93.7 4.7 426.6 100.0 4.3 396.2 108.0 3.7 367.9 117.0 3.1 10 487.8 86.8 5.6 462.6 95.2 4.9 446.7 102.4 4.4 415.4 109.3 3.8 386.2 117.7 3.3 5 443.8 91.7 4.8 422.1 98.6 4.3 409.0 102.2 4.0 375.2 111.5 3.4 345.4 123.8 2.8 6 445.4 91.8 4.9 423.7 98.8 4.3 406.0 100.1 4.1 376.6 111.1 3.4 351.6 125.7 2.8 7 463.4 92.5 5.0 440.8 100.2 4.4 428.0 105.1 4.1 395.9 114.8 3.4 366.5 126.4 2.9 120EW 8 480.9 93.5 5.1 457.6 101.6 4.5 443.5 106.6 4.2 410.7 115.7 3.6 381.9 127.3 3.0 9 498.7 92.8 5.4 474.5 102.5 4.6 459.5 109.3 4.2 426.8 118.1 3.6 396.3 127.8 3.1 10 525.4 94.9 5.5 498.4 104.1 4.8 481.2 111.9 4.3 447.4 119.5 3.7 416.1 128.7 3.2 Notes: 1. Ratings based on HCFC-22, evaporator and condenser fouling of 0.044, evaporator and condenser temperature drop of 5.6°C. 2. For 208V units multiply capacity and COP by 0.98 3. Ratings are based on circuit #1 in lead position and circuit #2 in lag position. 4. Interpolation is allowed; extrapolation is not permitted. Consult McQuay for performance outside the ratings shown. 5. KWi input is for compressors only. COP is for the entire unit, including compressors and control power. 6. For LWT of 5°C and below please refer to Application Adjustment Factors section.

16 WHR 017EW - 210EW Product Manual WHR Table 10, WHR 130EW through WHR 210EW, 60 Hz, Metric units ENTERING CONDENSER WATER TEMPERATURE (°C) WHR LWT 20°C 25°C 30°C 35°C 40°C UNIT (°C) CAP. PWR CAP. PWR CAP. PWR CAP. PWR CAP. PWR SIZE kW kWi COP kW kWi COP kW kWi COP kW kWi COP kW kWi COP 5 480.3 101.5 4.7 456.9 109.1 4.2 442.7 113.1 3.9 406.1 123.5 3.3 373.8 137.0 2.7 6 482.1 101.6 4.7 458.6 109.3 4.2 439.5 110.8 4.0 407.7 123.0 3.3 380.5 139.2 2.7 7 501.6 102.4 4.9 477.1 110.9 4.3 463.2 116.3 4.0 428.5 127.1 3.4 396.7 139.9 2.8 130EW 8 520.5 103.4 5.0 495.3 112.4 4.4 480.0 118.0 4.1 444.5 128.0 3.5 413.3 140.8 2.9 9 539.8 102.7 5.3 513.6 113.4 4.5 497.3 120.9 4.1 461.9 130.7 3.5 428.9 141.5 3.0 10 568.7 105.1 5.4 539.4 115.2 4.7 520.8 123.9 4.2 484.3 132.2 3.7 450.3 142.4 3.2 5 526.0 104.9 5.0 500.4 112.7 4.4 484.8 116.8 4.2 444.7 127.5 3.5 409.4 141.5 2.9 6 528.0 105.0 5.0 502.3 112.9 4.4 481.3 114.5 4.2 446.5 127.0 3.5 416.7 143.8 2.9 7 549.3 105.8 5.2 522.4 114.5 4.6 507.3 120.1 4.2 469.2 131.3 3.6 434.4 144.5 3.0 145EW 8 570.0 106.9 5.3 542.4 116.1 4.7 525.7 121.9 4.3 486.8 132.3 3.7 452.7 145.5 3.1 9 591.2 106.1 5.6 562.5 117.1 4.8 544.6 124.9 4.4 505.9 135.0 3.7 469.7 146.2 3.2 10 622.8 108.5 5.7 590.7 119.0 5.0 570.3 128.0 4.5 530.4 136.6 3.9 493.2 147.1 3.4 5 557.5 113.5 4.9 530.3 122.1 4.3 513.8 126.5 4.1 471.3 138.1 3.4 433.9 153.2 2.8 6 559.5 113.7 4.9 532.3 122.3 4.4 510.1 124.0 4.1 473.1 137.5 3.4 441.6 155.7 2.8 7 582.1 114.5 5.1 553.7 124.0 4.5 537.6 130.1 4.1 497.3 142.1 3.5 460.4 156.5 2.9 155EW 8 604.1 115.7 5.2 574.8 125.7 4.6 557.1 132.0 4.2 515.9 143.2 3.6 479.7 157.5 3.0 9 626.5 114.9 5.5 596.1 126.8 4.7 577.2 135.3 4.3 536.1 146.2 3.7 497.8 158.3 3.1 10 660.0 117.5 5.6 626.0 128.9 4.9 604.4 138.6 4.4 562.1 147.9 3.8 522.6 159.3 3.3 5 593.3 126.3 4.7 564.3 135.8 4.2 546.8 140.7 3.9 501.6 153.6 3.3 461.7 170.5 2.7 6 595.5 126.5 4.7 566.5 136.0 4.2 542.8 137.9 3.9 503.5 153.0 3.3 470.0 173.2 2.7 7 619.5 127.4 4.9 589.2 138.0 4.3 572.2 144.7 4.0 529.2 158.1 3.3 490.0 174.1 2.8 165EW 8 642.9 128.7 5.0 611.7 139.9 4.4 592.9 146.8 4.0 549.1 159.3 3.4 510.5 175.3 2.9 9 666.7 127.8 5.2 634.4 141.1 4.5 614.3 150.5 4.1 570.5 162.6 3.5 529.8 176.1 3.0 10 702.4 130.7 5.4 666.3 143.4 4.6 643.3 154.2 4.2 598.2 164.6 3.6 556.2 177.2 3.1 5 643.7 138.1 4.7 612.3 148.5 4.1 593.3 153.8 3.9 544.2 168.0 3.2 501.0 186.4 2.7 6 646.1 138.3 4.7 614.7 148.7 4.1 589.0 150.8 3.9 546.4 167.3 3.3 510.0 189.4 2.7 7 672.2 139.3 4.8 639.3 150.8 4.2 620.8 158.2 3.9 574.2 172.9 3.3 531.6 190.4 2.8 175EW 8 697.5 140.8 5.0 663.8 152.9 4.3 643.3 160.5 4.0 595.8 174.2 3.4 553.9 191.6 2.9 9 723.4 139.7 5.2 688.3 154.3 4.5 666.5 164.6 4.1 619.0 177.8 3.5 574.8 192.5 3.0 10 762.2 142.9 5.3 722.9 156.8 4.6 698.0 168.6 4.1 649.0 179.9 3.6 603.5 193.8 3.1 5 665.3 136.5 4.9 632.8 146.7 4.3 613.2 152.0 4.0 562.5 166.0 3.4 517.8 184.2 2.8 6 667.8 136.6 4.9 635.2 147.0 4.3 608.7 149.0 4.1 564.7 165.3 3.4 527.0 187.1 2.8 7 694.7 137.7 5.0 660.8 149.1 4.4 641.6 156.3 4.1 593.5 170.9 3.5 549.4 188.1 2.9 185EW 8 720.9 139.1 5.2 686.0 151.1 4.5 664.9 158.6 4.2 615.7 172.2 3.6 572.5 189.4 3.0 9 747.7 138.1 5.4 711.4 152.5 4.7 688.9 162.6 4.2 639.8 175.7 3.6 594.1 190.2 3.1 10 787.7 141.3 5.6 747.1 154.9 4.8 721.3 166.6 4.3 670.8 177.8 3.8 623.7 191.5 3.3 5 716.5 154.9 4.6 681.5 166.5 4.1 660.3 172.5 3.8 605.8 188.4 3.2 557.6 209.0 2.7 6 719.1 155.1 4.6 684.1 166.8 4.1 655.6 169.2 3.9 608.1 187.6 3.2 567.6 212.4 2.7 7 748.2 156.2 4.8 711.6 169.2 4.2 691.0 177.4 3.9 639.1 193.9 3.3 591.7 213.5 2.8 195EW 8 776.4 157.9 4.9 738.8 171.5 4.3 716.0 180.0 4.0 663.1 195.4 3.4 616.5 214.9 2.9 9 805.2 156.7 5.1 766.1 173.1 4.4 741.8 184.6 4.0 689.0 199.4 3.5 639.8 215.9 3.0 10 848.3 160.3 5.3 804.6 175.8 4.6 776.8 189.1 4.1 722.4 201.8 3.6 671.7 217.3 3.1 5 764.0 163.9 4.7 726.7 176.2 4.1 704.1 182.6 3.9 645.9 199.4 3.2 594.6 221.2 2.7 6 766.8 164.1 4.7 729.5 176.5 4.1 699.0 179.0 3.9 648.4 198.6 3.3 605.2 224.7 2.7 7 797.8 165.3 4.8 758.8 179.0 4.2 736.8 187.8 3.9 681.5 205.2 3.3 631.0 225.9 2.8 210EW 8 827.9 167.0 5.0 787.8 181.5 4.3 763.5 190.5 4.0 707.1 206.8 3.4 657.4 227.4 2.9 9 858.6 165.8 5.2 816.9 183.1 4.5 791.0 195.3 4.1 734.7 211.0 3.5 682.2 228.5 3.0 10 904.6 169.7 5.3 858.0 186.1 4.6 828.3 200.1 4.1 770.3 213.5 3.6 716.3 230.0 3.1 Notes: 1. Ratings based on HCFC-22, evaporator and condenser fouling of 0.044, evaporator and condenser temperature drop of 5.6°C. 2. For 208V units multiply capacity and COP by 0.98. 3. Ratings are based on circuit #1 in lead position and circuit #2 in lag position. 4. Interpolation is allowed; extrapolation is not permitted. Consult McQuay for performance outside the ratings shown. 5. KWi input is for compressors only. COP is for the entire unit, including compressors and control power. 6. For LWT of 5°C and below please refer to Application Adjustment Factors section.

Product Manual WHR WHR 017EW - 210EW 17 Part Load Data

Table 11, Part Load Performance

Unit Size % Load Capacity Power Unit Size % Load Capacity Power Tons kWi EER IPLV Tons kWi EER IPLV 100 17.8 15.0 14.2 100 94.9 82.5 13.8 017E 75 13.4 10.6 15.1 16.01 095E 75 71.2 53.0 16.1 16.47 50 8.9 6.1 17.4 50 47.5 32.2 17.7 25 4.5 3.0 17.9 25 23.7 15.6 18.2 100 21.8 19.8 13.2 100 100.7 86.9 13.9 020E 75 16.4 13.7 14.3 14.87 100E 75 75.5 54.3 16.7 17.37 50 10.9 8.3 15.7 50 50.4 31.5 19.2 25 5.5 3.8 17.0 25 25.2 15.4 19.6 100 26.0 24.0 13.0 100 110.1 97.1 13.6 025E 75 19.5 16.7 14.0 14.67 110E 75 82.6 61.2 16.2 16.84 50 13.0 9.9 15.7 50 55.1 36.1 18.3 25 6.5 4.7 16.5 25 27.5 16.8 19.7 100 29.7 26.8 13.3 100 112.7 98.0 13.8 030E 75 22.3 18.3 14.6 15.02 115E 75 84.5 62.2 16.3 16.36 50 14.9 11.3 15.8 50 56.4 39.1 17.3 25 7.4 5.3 16.8 25 28.2 19.1 17.7 100 38.4 33.2 13.9 100 121.4 107.1 13.6 040E 75 28.8 22.2 15.6 16.22 120E 75 91.1 67.9 16.1 16.74 50 19.2 13.4 17.2 50 60.7 39.6 18.4 25 9.6 6.0 19.1 25 30.4 19.3 18.9 100 44.1 37.8 14.0 100 131.4 118.6 13.3 045E 75 33.1 25.9 15.3 15.79 130E 75 98.6 75.3 15.7 16.63 50 22.1 16.1 16.4 50 65.7 42.8 18.4 25 11.0 7.2 18.5 25 32.9 19.9 19.8 100 50.6 46.7 13.0 100 143.9 122.5 14.1 050E 75 38.0 32.1 14.2 14.66 145E 75 107.9 79.5 16.3 17.11 50 25.3 19.8 15.3 50 72.0 45.9 18.8 25 12.7 9.0 16.9 25 36.0 22.0 19.6 100 58.2 49.9 14.0 100 152.5 132.6 13.8 060E 75 43.7 36.4 14.4 15.21 155E 75 114.4 85.8 16.0 16.73 50 29.1 22.0 15.9 50 76.3 50.0 18.3 25 14.6 9.8 17.9 25 38.1 24.0 19.1 100 70.2 62.9 13.4 100 162.3 147.5 13.2 070E 75 52.7 41.8 15.1 15.30 165E 75 121.7 95.5 15.3 16.43 50 35.1 26.5 15.9 50 81.2 52.6 18.5 25 17.6 12.3 17.1 25 40.6 25.4 19.2 100 76.7 69.2 13.3 100 176.1 161.3 13.1 080E 75 57.5 45.7 15.1 15.29 175E 75 132.1 105.0 15.1 16.48 50 38.4 28.8 16.0 50 88.1 56.2 18.8 25 19.2 13.6 16.9 25 44.0 27.0 19.6 100 83.8 75.6 13.3 100 182.0 159.4 13.7 085E 75 62.9 51.0 14.8 15.18 185E 75 136.5 106.4 15.4 16.23 50 41.9 31.6 15.9 50 91.0 61.3 17.8 25 21.0 14.5 17.3 25 45.5 29.7 18.4 100 90.8 81.9 13.3 100 196.0 180.9 13.0 090E 75 68.1 55.2 14.8 14.93 195E 75 147.0 119.2 14.8 15.70 50 45.4 35.1 15.5 50 98.0 68.4 17.2 25 22.7 16.8 16.2 25 49.0 31.6 18.6 100 209.0 191.5 13.1 210E 75 156.8 125.4 15.0 15.78 50 104.5 72.5 17.3 25 52.3 34.6 18.1

18 WHR 017EW - 210EW Product Manual WHR Pressure Drop Curves

Figure 1, Evaporator Pressure Drop WHR 017EW through 030EW

020EW, 025EW 030EW

017EW

Product Manual WHR WHR 017EW - 210EW 19 Figure 2, Evaporator Pressure Drop WHR 040EW through 090EW

040EW - 050EW 060EW - 080EW 085EW - 090EW

20 WHR 017EW - 210EW Product Manual WHR Figure 3, Condenser Pressure Drop WHR 017EW through 090EW

Product Manual WHR WHR 017EW - 210EW 21 Figure 4, Evaporator Pressure Drop WHR 095EW through 210EW

115EW - 130EW 95EW - 110EW 145EW - 210EW

22 WHR 017EW - 210EW Product Manual WHR Figure 5, Condenser Pressure Drop WHR 095EW through 210EW

Product Manual WHR WHR 017EW - 210EW 23 Electrical Data

Table 12, Compressor Amp Draw, WHR 017EW through WHR 060EW Rated Load Amps (1) Locked Rotor Amps (2) Unit Voltage Freq. w/o Supplemental w/ Supplemental Across-The-Line Part Winding Overloads Overloads Start Start Size 3-Phase (Hz) Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 208 60 - - - 308 - 188 - 230 60 60 - - - 308 - 188 - 017EW 460 31 - - - 154 - 104 - 575 23 - - - 135 - 81 - 208 74 - - - 428 - 250 - 230 60 74 - - - 428 - 250 - 020EW 460 37 - - - 214 - 132 - 575 31 - - - 172 - 103 - 208 85 - - - 470 - 292 - 230 60 85 - - - 470 - 292 - 025EW 460 43 - - - 235 - 141 - 575 36 - - - 200 - 130 - 208 95 - - - 565 - 340 - 230 60 95 - - - 565 - 340 - 030EW 460 48 - - - 283 - 156 - 575 36 - - - 230 - 138 - 208 60 60 48 54 308 374 188 222 230 60 60 60 48 54 308 374 188 222 040EW 460 31 31 24 27 154 187 104 108 575 23 24 19 22 135 135 81 81 208 74 74 62 62 428 428 250 250 230 60 74 74 62 62 428 428 250 250 045EW 460 37 37 31 31 214 214 132 132 575 31 31 25 25 172 172 103 103 208 85 85 77 77 470 470 292 292 230 60 85 85 77 77 470 470 292 292 050EW 460 43 43 38 38 235 235 141 141 575 36 36 31 31 200 200 130 130 208 85 95 76 84 470 565 292 340 230 60 85 95 76 84 470 565 292 340 060EW 460 43 48 38 42 235 283 141 156 575 36 36 31 34 200 230 130 138 NOTES: 1. Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of RLA of all other loads in the circuit including control transformer. Wire size amps for separate 115V control circuit power is 11 amps. 2. Single point power supply requires a single fused disconnect to supply electrical power to the unit. 3. Supplemental overloads can be used in conjunction with standard inherent overload protection on water cooled type "W" units only.

24 WHR 017EW - 210EW Product Manual WHR Table 13, Compressor Amp Draw, WHR 070EW through WHR 120EW Rated Load Amps (1) Locked Rotor Amps (2) Unit Voltage Freq. w/o Supplemental w/ Supplemental Across-The-Line Part Winding Overloads Overloads Size 3-Phase (Hz) Start Start Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 208 122 122 115 115 650 650 400 400 230 60 122 122 100 100 594 594 340 340 070EW 460 60 60 50 50 297 297 195 195 575 42 42 40 40 245 245 152 152 208 135 135 124 124 754 754 463 463 230 60 127 127 108 108 594 594 340 340 080EW 460 64 64 54 54 297 297 195 195 575 48 48 43 43 245 245 152 152 208 135 162 124 147 754 1070 463 654 230 60 127 162 108 147 594 1070 340 654 085EW 460 64 82 54 74 297 535 195 330 575 48 68 43 59 245 405 152 262 208 162 162 147 147 1070 1070 654 654 230 60 162 162 147 147 1070 1070 654 654 090EW 460 82 82 74 74 535 535 330 330 575 68 68 59 59 405 405 262 262 208 74 , 85 74 , 85 62 , 76 62 , 76 428 , 470 428 , 470 250 , 292 250 , 292 230 60 74 , 85 74 , 85 62 , 76 62 , 76 428 , 470 428 , 470 250 , 292 250 , 292 095EW 460 37 , 43 37 , 43 31 , 38 31 , 38 214 , 235 214 , 235 132 , 141 132 , 141 575 31 , 36 31 , 36 25 , 31 25 , 31 172 , 200 172 , 200 103 , 130 103 , 130 208 74 , 95 74 , 95 62 , 84 62 , 84 428 , 565 428 , 565 250 , 340 250 , 340 230 60 74 , 95 74 , 95 62 , 84 62 , 84 428 , 565 428 , 565 250 , 340 250 , 340 100EW 460 37 , 48 37 , 48 31 , 42 31 , 42 214 , 283 214 , 283 132 , 156 132 , 156 575 31 , 36 31 , 36 25 , 34 25 , 34 172 , 230 172 , 230 103 , 138 103 , 138 208 122 , 74 122 , 74 115 , 62 115 , 62 650 , 428 650 , 428 400 , 250 400 , 250 230 60 122 , 74 122 , 74 100 , 62 100 , 62 594 , 428 594 , 428 340 , 250 340 , 250 110EW 460 60 , 37 60 , 37 50 , 31 50 , 31 297 , 214 297 , 214 195 , 132 195 , 132 575 42 , 31 42 , 31 40 , 25 40 , 25 245 , 172 245 , 172 152 , 103 152 , 103 208 122 , 74 122 , 74 115 , 62 115 , 62 650 , 428 650 , 428 400 , 250 400 , 250 230 60 122 , 74 122 , 74 100 , 62 100 , 62 594 , 428 594 , 428 340 , 250 340 , 250 115EW 460 60 , 37 60 , 37 50 , 31 50 , 31 297 , 214 297 , 214 195 , 132 195 , 132 575 42 , 31 42 , 31 40 , 25 40 , 25 245 , 172 245 , 172 152 , 103 152 , 103 208 122 , 74 122 , 122 115 , 62 115 , 115 650 , 428 650 , 650 400 , 250 400 , 400 230 60 122 , 74 122 , 122 100 , 62 100 , 100 594 , 428 594 , 594 340 , 250 340 , 340 120EW 460 60 , 37 60 , 60 50 , 31 50 , 50 297 , 214 297 , 297 195 , 132 195 , 195 575 42 , 31 42 , 42 40 , 25 40 , 40 245 , 172 245 , 245 152 , 103 152 , 152 NOTES: 1. Compressor RLA values are for wire sizing purposes only and do not reflect normal operating current draw. 2. Compressor LRA values for part winding start are for the first winding.

Product Manual WHR WHR 017EW - 210EW 25 Table 14, Compressor Amp Draw, WHR 130EW through WHR 210EW Rated Load Amps (1) Locked Rotor Amps (2) Unit Voltage Freq. w/o Supplemental w/ Supplemental Across-The-Line Part Winding Overloads Overloads Size 3-Phase (Hz) Start Start Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 208 122 , 122 122 , 122 115 , 115 115 , 115 650 , 650 650 , 650 400 , 400 400 , 463 230 60 122 , 122 122 , 122 100 , 100 100 , 100 594 , 594 594 , 594 340 , 340 340 , 340 130EW 460 60 , 60 60 , 60 50 , 50 50 , 50 297 , 297 297 , 297 195 , 195 195 , 195 575 42 , 42 42 , 42 40 , 40 40 , 40 245 , 245 245 , 245 152 , 152 152 , 152 208 122 , 122 122 , 135 115 , 115 115 , 124 650 , 650 650 , 754 400 , 400 400 , 463 230 60 122 , 122 122 , 127 100 , 100 100 , 108 594 , 594 594 , 594 340 , 340 340 , 340 145EW 460 60 , 60 60 , 64 50 , 50 50 , 54 297 , 297 297 , 297 195 , 195 195 , 195 575 42 , 42 42 , 48 40 , 40 40 , 43 245 , 245 245 , 245 152 , 152 152 , 152 208 135 , 135 135 , 135 124 , 124 124 , 124 754 , 754 754 , 754 463 , 463 463 , 463 230 60 127 , 127 127 , 127 108 , 108 108 , 108 594 , 594 594 , 594 340 , 340 340 , 340 155EW 460 64 , 64 64 , 64 54 , 54 54 , 54 297 , 297 297 , 297 195 , 195 195 , 195 575 48 , 48 48 , 48 43 , 43 43 , 43 245 , 245 245 , 245 152 , 152 152 , 152 208 135 , 162 135 , 162 124 , 147 124 , 147 754 , 1070 754 , 1070 463 , 654 463 , 654 230 60 127 , 162 127 , 162 108 , 147 108 , 147 594 , 1070 594 , 1070 340 , 654 340 , 654 165EW 460 64 , 82 64 , 82 54 , 74 54 , 74 297 , 535 297 , 535 195 , 330 195 , 330 575 48 , 68 48 , 68 43 , 59 43 , 59 245 , 405 245 , 405 152 , 262 152 , 262 208 135 , 202 135 , 202 124 , 176 124 , 176 754 , 1070 754 , 1070 463 , 654 463 , 654 230 60 127 , 202 127 , 202 108 , 176 108 , 176 594 , 1070 594 , 1070 340 , 654 340 , 654 175EW 460 64 , 93 64 , 93 54 , 88 54 , 88 297 , 535 297 , 535 195 , 330 195 , 330 575 48 , 75 48 , 75 43 , 71 43 , 71 245 , 405 245 , 405 152 , 262 152 , 262 208 162 , 162 162 , 162 147 , 147 147 , 147 1070 , 1070 1070 , 1070 654 , 654 654 , 654 230 60 162 , 162 162 , 162 147 , 147 147 , 147 1070 , 1070 1070 , 1070 654 , 654 654 , 654 185EW 460 82 , 82 82 , 82 74 , 74 74 , 74 535 , 535 535 , 535 330 , 330 330 , 330 575 68 , 68 68 , 68 59 , 59 59 , 59 405 , 405 405 , 405 262 , 262 262 , 262 208 162 , 202 162 , 202 147 , 176 147 , 176 1070 , 1070 1070 , 1070 654 , 654 654 , 654 230 60 162 , 202 162 , 202 147 , 176 147 , 176 1070 , 1070 1070 , 1070 654 , 654 654 , 654 195EW 460 82 , 93 82 , 93 74 , 88 74 , 88 535 , 535 535 , 535 330 , 330 330 , 330 575 68 , 75 68 , 75 59 , 71 59 , 71 405 , 405 405 , 405 262 , 262 262 , 262 208 202 , 202 202 , 202 176 , 176 176 , 176 1070 , 1070 1070 , 1070 654 , 654 654 , 654 230 60 202 , 202 202 , 202 176 , 176 176 , 176 1070 , 1070 1070 , 1070 654 , 654 654 , 654 210EW 460 88 , 93 88 , 93 88 , 88 88 , 88 535 , 535 535 , 535 330 , 330 330 , 330 575 72 , 75 72 , 75 71 , 71 71 , 71 405 , 405 405 , 405 262 , 262 262 , 262 NOTES: 1. Compressor RLA values are for wire sizing purposes only and do not reflect normal operating current draw. 2. Compressor LRA values for part winding start are for the first winding.

26 WHR 017EW - 210EW Product Manual WHR Table 15, Wire Sizing Amps, WHR 017 through WHR 080EW w/o Supplemental Overloads (1) w/ Supplemental Overloads (1) Unit Voltage Freq. Minimum Circuit Ampacity (MCA) Minimum Circuit Ampacity (MCA) Size 3-Phase (Hz) Single Point Multiple Point Power Single Point Multiple Point Power Supply(3) Supply(3) Power Circuit 1 Circuit 2 Power Circuit 1 Circuit 2 Supply(2) Supply(2) 208 75 - - 60 - - 230 60 75 - - 60 - - 017EW 460 39 - - 30 - - 575 29 - - 24 - - 208 93 - - 78 - - 230 60 93 - - 78 - - 020EW 460 46 - - 39 - - 575 39 - - 31 - - 208 106 - - 95 - - 230 60 106 - - 95 - - 025EW 460 54 - - 48 - - 575 45 - - 39 - - 208 119 - - 105 - - 230 60 119 - - 105 - - 030EW 460 60 - - 53 - - 575 45 - - 43 - - 208 135 75 75 116 60 68 230 60 135 75 75 116 60 68 040EW 460 70 39 39 58 30 34 575 53 29 30 47 24 28 208 167 93 93 140 78 78 230 60 167 93 93 140 78 78 045EW 460 83 46 46 70 39 39 575 70 39 39 56 31 31 208 191 106 106 173 96 96 230 60 191 106 106 173 96 96 050EW 460 97 54 54 86 48 48 575 81 45 45 70 39 39 208 204 106 105 183 95 105 230 60 204 106 105 183 95 105 060EW 460 103 54 53 91 48 53 575 81 45 45 74 39 43 208 275 153 153 259 144 144 230 60 254 141 141 225 125 125 070EW 460 135 75 75 113 63 63 575 95 53 53 90 50 50 208 304 169 169 279 155 155 230 60 286 159 159 243 135 135 080EW 460 144 80 80 122 68 68 575 108 60 60 97 54 54 NOTES: 1. Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of RLA of all other loads in the circuit including control transformer. Wire size amps for separate 115V control circuit power is 11 amps. 2. Single point power supply requires a single fused disconnect to supply electrical power to the unit. 3. Multiple point power supply requires three independent power circuits with separate fused disconnects. (Two compressor circuits, one control circuit.)

Product Manual WHR WHR 017EW - 210EW 27 Table 16,Wire Sizing, WHR 085EW through WHR 130EW w/o Supplemental Overloads (1) w/ Supplemental Overloads (1) Unit Voltage Freq Minimum Circuit Ampacity (MCA) Minimum Circuit Ampacity (MCA) Size 3-Phase (Hz) Single Multiple Point Power Single Multiple Point Power Point Supply(3) Point Supply(3) Power Circuit 1 Circuit 2 Power Circuit 1 Circuit 2 Supply(2) Supply(2) 208 338 169 203 308 155 184 230 60 330 159 203 292 135 184 085EW 460 167 80 103 147 68 93 575 133 60 85 117 54 74 208 365 203 203 331 184 184 230 60 365 203 203 331 184 184 090EW 460 185 103 103 167 93 93 575 153 85 85 133 74 74 208 339 180 180 297 158 158 230 60 339 180 180 297 158 158 095EW 460 171 91 91 148 79 79 575 143 76 76 120 64 64 208 362 193 193 313 167 167 230 60 362 193 193 313 167 167 100EW 460 182 97 97 157 84 84 575 143 76 76 127 68 68 208 423 227 227 383 206 206 230 60 402 215 215 349 187 187 110EW 460 209 112 112 175 94 94 575 157 84 84 140 75 75 208 471 227 227 383 206 206 230 60 441 215 215 349 187 187 115EW 460 232 112 112 175 94 94 575 168 84 84 140 75 75 208 519 227 275 436 206 259 230 60 480 215 255 387 187 225 120EW 460 255 112 135 194 94 113 575 179 84 95 155 75 90 208 535 275 275 498 259 259 230 60 498 255 255 425 225 225 130EW 460 260 135 135 213 113 113 575 186 95 95 170 90 90 NOTES: 1. Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of RLA of all other loads in the circuit including control transformer. Wire size amps for separate 115V control circuit power is 11 amps. 2. Single point power supply requires a single fused disconnect to supply electrical power to the unit. 3. Multiple point power supply requires three independent power circuits with separate fused disconnects. (Two compressor circuits, one control circuit.)

28 WHR 017EW - 210EW Product Manual WHR Table 17, Wire Sizing Amps, WHR 145EW through WHR 210EW w/o Supplemental Overloads (1) w/ Supplemental Overloads (1) Unit Voltage Freq. Minimum Circuit Ampacity (MCA) Minimum Circuit Ampacity (MCA) Size 3-Phase (Hz) Multiple Point Power Supply(3) Multiple Point Power Supply(3) Single Point Single Point Power Circuit 1 Circuit 2 Power Circuit 1 Circuit 2 Supply(2) Supply(2) 208 535 275 291 500 259 270 230 60 498 255 272 435 225 235 145EW 460 260 135 135 218 113 118 575 186 95 102 174 90 94 208 574 304 304 527 279 279 230 60 540 286 286 459 243 243 155EW 460 272 144 144 230 122 122 575 204 108 108 183 97 97 208 635 338 338 578 308 308 230 60 619 330 330 547 292 292 165EW 460 313 167 167 275 147 147 575 249 133 133 219 117 117 208 725 388 388 644 344 344 230 60 709 380 380 612 328 328 175EW 460 326 174 174 306 164 164 575 258 138 138 246 132 132 208 689 365 365 625 331 331 230 60 689 365 365 625 331 331 185EW 460 349 185 185 315 167 167 575 289 153 153 251 133 133 208 779 415 415 661 367 367 230 60 779 415 415 661 367 367 195EW 460 362 192 192 346 184 184 575 298 158 158 278 148 148 208 859 455 455 748 396 396 230 60 859 455 455 748 396 396 210EW 460 374 198 198 374 198 198 575 306 162 162 302 160 160 NOTES: 1. Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of RLA of all other loads in the circuit including control transformer. Wire size amps for separate 115V control circuit power is 11 amps. 2. Single point power supply requires a single fused disconnect to supply electrical power to the unit. 3. Multiple point power supply requires three independent power circuits with separate fused disconnects. (Two compressor circuits, one control circuit.)

Product Manual WHR WHR 017EW - 210EW 29 Table 18, Single Point Fuse Sizing, WHR 017EW through WHR 060EW Recommended Fuse Size(1) Maximum Fuse Size(2) Unit Voltage Freq. Single Point Power Single Point Power Size 3-Phase (Hz) w/o Supplemental w/ Supplemental w/o Supplemental w/ Supplemental Overloads Overloads Overloads Overloads 208 110 - 125 - 230 60 110 - 125 - 017EW 460 50 - 70 - 575 40 - 50 - 208 125 - 150 - 230 60 125 - 150 - 020EW 460 70 - 80 - 575 60 - 70 - 208 150 - 175 - 230 60 150 - 175 - 025EW 460 80 - 90 - 575 70 - 80 - 208 175 - 200 - 230 60 175 - 200 - 030EW 460 80 - 100 - 575 70 - 80 - 208 175 150 175 150 230 60 175 150 175 150 040EW 460 90 80 100 80 575 70 60 70 60 208 200 175 225 200 230 60 200 175 225 200 045EW 460 200 90 110 100 575 90 70 100 80 208 225 225 250 250 230 60 225 225 250 250 050EW 460 110 100 125 110 575 100 90 110 100 208 250 225 250 250 230 60 250 225 250 250 060EW 460 125 110 150 125 575 100 90 110 100 208 350 350 350 350 230 60 300 300 350 300 070EW 460 175 150 175 150 575 110 110 125 125 208 400 350 400 400 230 60 350 300 400 350 080EW 460 175 150 200 175 575 125 125 150 125 NOTES: 1. "Recommended Fuse Size" are selected at approximately 150% of the largest compressor RLA, plus 100% of all other loads in the circuit. 2. "Maximum Fuse Sizes" are selected at approximately 225% of the largest compressor RLA, plus 100% of all other loads in the circuit.

30 WHR 017EW - 210EW Product Manual WHR Table 19, Single Point Fuse Sizing, WHR 085EW through WHR 130EW Recommended Fuse Size(1) Maximum Fuse Size(2) Unit Voltage Freq. Single Point Power Single Point Power Size 3-Phase (Hz) w/o Supplemental w/ Supplemen'l w/o Supplemental w/ Supplemental Overloads Overloads Overloads Overloads 208 450 400 500 450 230 60 400 400 450 400 085EW 460 200 200 225 200 575 175 150 200 175 208 450 400 500 450 230 60 450 400 500 450 090EW 460 225 200 250 225 575 175 150 200 175 208 400 350 400 350 230 60 400 350 400 350 095EW 460 200 175 200 175 575 175 150 175 150 208 450 350 450 350 230 60 450 350 450 350 100EW 460 225 175 225 175 575 175 150 175 150 208 500 450 500 450 230 60 450 400 500 400 110EW 460 225 200 250 225 575 175 175 175 175 208 500 450 500 450 230 60 450 400 500 400 115EW 460 250 200 250 225 575 175 175 175 175 208 500 500 500 500 230 60 500 450 500 450 120EW 460 250 225 250 225 575 200 175 200 175 208 600 600 600 600 230 60 500 500 500 500 130EW 460 300 250 300 250 575 200 200 200 200 208 600 600 600 600 230 60 600 500 600 500 145EW 460 300 250 300 250 575 225 200 225 200 NOTES: 1. "Recommended Fuse Size" are selected at approximately 150% of the largest compressor RLA, plus 100% of all other loads in the circuit. 2. "Maximum Fuse Sizes" are selected at approximately 225% of the largest compressor RLA, plus 100% of all other loads in the circuit.

Product Manual WHR WHR 017EW - 210EW 31 Table 20,Single Point Fuse Size, WHR 155EW through WHR 210EW Recommended Fuse Size(1) Maximum Fuse Size(2) Unit Voltage Freq. Single Point Power Single Point Power Size 3-Phase (Hz) w/o Supplemental w/ Supplemen'l w/o Supplemental w/ Supplemental Overloads Overloads Overloads Overloads 208 700 600 700 600 230 60 600 500 600 500 155EW 460 300 250 300 250 575 225 200 250 225 208 700 700 700 700 230 60 700 600 700 600 165EW 460 350 300 350 300 575 300 250 300 250 208 800 800 800 800 230 60 800 700 800 700 175EW 460 400 350 400 350 575 300 300 300 300 208 800 700 800 700 230 60 800 700 800 700 185EW 460 400 350 400 350 575 350 300 350 300 208 800 800 800 800 230 60 800 800 800 800 195EW 460 400 400 450 400 575 350 300 350 300 208 1000 800 1000 800 230 60 1000 800 1000 800 210EW 460 450 450 450 450 575 350 350 350 350 NOTES: 1. "Recommended Fuse Size" are selected at approximately 150% of the largest compressor RLA, plus 100% of all other loads in the circuit. 2. "Maximum Fuse Sizes" are selected at approximately 225% of the largest compressor RLA, plus 100% of all other loads in the circuit.

32 WHR 017EW - 210EW Product Manual WHR Table 21, Multiple-Point Fuse Sizing, WHR 040EW through WHR 145EW Recommended Fuse Size(1) Maximum Fuse Size(2) Unit Voltage Freq. Multiple Point Power Multiple Point Power Size 3-Phase (Hz) Circuit 1 Circuit 2 Circuit 1 Circuit 2 w/o w/ w/o w/ w/o w/ w/o w/ Supplemental Supplemental Supplemental Supplemental Supplemental Supplemental Supplemental Supplemental Overloads Overloads Overloads Overloads Overloads Overloads Overloads Overloads 208 110 90 110 100 125 100 125 110 230 60 110 90 110 100 125 100 125 110 040EW 460 60 45 60 50 70 50 70 60 208 125 150 125 150 150 125 150 125 230 60 125 150 125 150 150 125 150 125 045EW 460 70 80 70 80 80 70 80 70 575 60 70 60 70 70 50 70 50 208 150 125 150 125 175 150 175 150 230 60 150 125 150 125 175 150 175 150 050EW 460 80 70 80 70 90 80 90 80 575 70 60 70 60 80 70 80 70 208 150 125 150 150 175 150 200 175 230 60 150 125 150 150 175 150 200 175 060EW 460 80 70 90 80 90 80 100 90 575 70 60 70 60 80 70 80 70 208 225 200 225 200 250 250 250 250 230 60 225 175 225 175 250 225 250 225 070EW 460 110 90 110 90 125 110 125 110 575 80 70 80 70 90 90 90 90 208 225 225 225 225 300 250 300 250 230 60 225 200 225 200 250 225 250 225 080EW 460 110 100 110 100 125 110 125 110 575 90 80 90 80 100 90 100 90 208 250 225 300 250 300 250 350 300 230 60 225 200 300 250 250 225 350 300 085EW 460 110 100 150 125 125 110 175 150 575 90 80 125 100 100 90 150 125 208 300 250 300 250 350 300 350 300 230 60 300 250 300 250 350 300 350 300 090EW 460 150 125 150 125 175 150 175 150 575 125 100 125 100 150 125 150 125 208 225 200 225 200 250 225 250 225 230 60 225 200 225 200 250 225 250 225 095EW 460 110 100 110 100 125 110 125 110 575 100 80 100 80 110 90 110 90 208 225 200 225 200 250 250 250 250 230 60 225 200 225 200 250 250 250 250 100EW 460 110 100 110 100 125 125 125 125 575 90 90 90 90 110 100 110 100 208 300 250 300 250 300 300 300 300 230 60 250 225 250 225 300 250 300 250 110EW 460 150 110 150 110 150 125 150 125 575 100 90 100 90 125 110 125 110 208 300 250 300 250 300 300 300 300 230 60 350 225 250 225 300 250 300 250 115EW 460 150 110 150 110 150 125 150 125 575 100 90 100 90 125 110 125 110 208 300 250 350 300 300 300 350 350 230 60 250 225 300 250 300 250 350 300 120EW 460 150 110 175 125 150 125 175 150 575 110 90 110 110 125 110 125 125 208 350 300 350 300 350 350 350 350 230 60 300 250 300 250 350 300 350 300 130EW 460 175 125 175 125 175 150 175 150 575 110 110 110 110 125 125 125 125 208 350 300 400 350 350 350 400 350 230 60 300 250 350 300 350 300 350 300 145EW 460 175 125 175 150 175 150 175 150 575 110 110 110 110 125 125 125 125 NOTES: 1. "Recommended Fuse Size" are selected at approximately 150% of the largest compressor RLA, plus 100% of all other loads in the circuit. 2. "Maximum Fuse Sizes" are selected at approximately 225% of the largest compressor RLA, plus 100% of all other loads in the circuit.

Product Manual WHR WHR 017EW - 210EW 33 Table 22, Multiple Point Fuse Size, WHR 155EW through WHR 210EW Recommended Fuse Size(1) Maximum Fuse Size(2) Unit Voltage Freq. Multiple Point Power Multiple Point Power Size 3-Phase (Hz) Circuit 1 Circuit 2 Circuit 1 Circuit 2 w/o w/ w/o w/ w/o w/ w/o w/ Supplemental Supplemental Supplemental Supplemental Supplemental Supplemental Supplemental Supplemental Overloads Overloads Overloads Overloads Overloads Overloads Overloads Overloads 208 400 350 400 350 400 400 400 400 230 60 350 300 350 300 400 350 400 350 155EW 460 175 150 175 150 200 175 200 175 575 125 110 125 110 150 125 150 125 208 400 400 400 400 500 450 500 450 230 60 400 350 400 350 450 400 450 400 165EW 460 200 175 200 175 225 200 225 200 575 175 150 175 150 200 175 200 175 208 450 450 450 450 500 500 500 500 230 60 450 450 450 450 500 500 500 500 175EW 460 225 225 225 225 250 250 250 250 575 175 175 175 175 200 200 200 200 208 500 400 500 400 500 450 500 450 230 60 500 400 500 400 500 450 500 450 185EW 460 225 200 225 200 250 225 250 225 575 200 175 200 175 200 175 200 175 208 500 450 500 450 600 500 600 500 230 60 500 450 500 450 600 500 600 500 195EW 460 225 225 225 225 250 250 250 250 575 200 175 200 175 225 200 225 200 208 600 450 600 450 600 500 600 500 230 60 600 450 600 450 600 500 600 500 210EW 460 250 225 250 225 250 250 250 250 575 200 200 200 200 225 225 225 225 NOTES: 1. "Recommended Fuse Size" are selected at approximately 150% of the largest compressor RLA, plus 100% of all other loads in the circuit. 2. "Maximum Fuse Sizes" are selected at approximately 225% of the largest compressor RLA, plus 100% of all other loads in the circuit

34 WHR 017EW - 210EW Product Manual WHR Figure 6, Field Wiring Diagram

WHR 017EW - 030EW only

WHR 040EW - 220EW only

Field connection terminal

Field wiring

Product Manual WHR WHR 017EW - 210EW 35 Physical Data

Table 23, WHR-017EW through WHR-030EW WHR UNIT SIZE 017EW 020EW 025EW 030EW Unit capacity @ ARI conditions tons, (kW) (1) 17.8 (62.6) 21.8 (76.6) 26.0 (91.4) 29.7 (104.4) No. Circuits 1 1 1 1 COMPRESSORS Nominal Horsepower 20 25 30 30 Number 1 1 1 1 Speed RPM 1750 1750 1750 1750 No. of Cylinders 4 4 4 6 Oil Charge Oz., (L) 135 (4.0) 130 (3.8) 140 (4.1) 140 (4.1) Discharge Valve In., (mm) 1 3/8 (35) 1 3/8 (35) 1 3/8 (35) 1 5/8 (41) CONDENSERS Number 1 1 1 1 Diameter In., (mm) 8 5/8 (219) 8 5/8 (219) 8 5/8 (219) 8 5/8 (219) Tube Length In., (mm) 96 (2438) 96 (2438) 96 (2438) 96 (2438) Design W.P.PSIG, (kPa): Refrigerant Side 450 (3104) 450 (3104) 450 (3104) 450 (3104) Water Side 150 (1035) 150 (1035) 150 (1035) 150 (1035) No. of Passes 2 2 2 2 Pump-Out Capacity Lb., (kg) (2) 104 (47) 104 (47) 100 (45) 91 (41) Connections: Water Inlet & Outlet In., (mm) (3) 2 (51) 2 (51) 2 (51) 2 (51) Relief Flare In., (mm) 5/8 (16) 5/8 (16) 5/8 (16) 5/8 (16) Purge Valve Flare In., (mm) 1/4 (6) 1/4 (6) 1/4 (6) 1/4 (6) Liquid Subcooling Integral Integral Integral Integral EVAPORATOR No. Refrigerant Circuits 1 1 1 1 Diameter In., (mm) 8 (203) 8 (203) 8 (203) 8 (203) Tube Length In., (mm) 60 (1524) 60 (1524) 72 (1829) 84 (2134) Water Volume Gallons, (L) 6.3 (.4) 6.3 (.4) 7.6 (.5) 9.0 (.6) Refrigerant Side D.W.P. 200 (1379) 200 (1379) 200 (1379) 200 (1379) PSIG, (kPa) Water Side D.W.P. PSIG, (kPa) 150 (1035) 150 (1035) 150 (1035) 150 (1035) Water Connections: Inlet & Outlet(3) 2 (51) 2 (51) 2 (51) 2 (51) Drain & Vent(NPT INT.) 3/4 (19)/1/4 (6) 3/4 (19)/1/4 (6) 3/4 (19)/1/4 (6) 3/4 (19)/1/4 (6) DIMENSIONS Length In., (mm) 104 1/4 (2648) 104 1/4 (2648) 104 1/2 (2578) 106 (2692) Width In., (mm) 26 1/4 (667) 26 1/4 (667) 29 1/2 (749) 29 1/2 (749) Height In., (mm) 46 1/2 (1181) 46 1/2 (1181) 47 1/2 (1207) 46 1/2 (1181) WEIGHTS Operating Weight, Lb., (kg) 1478 (671) 1498 (680) 1654 (750) 1726 (783) Shipping Weight, Lb., (kg) 1573 (714) 1590 (721) 1747 (792) 1806 (819) Operating Charge Lb., (kg) R-22 40 (18) 42 (19) 50 (23) 52 (24) Notes: 1. Certified in accordance with ARI Standard 590. 2. Full R-22 at 90F (32C) per refrigerant circuit. 3. NPT external WHR017-030.

36 WHR 017EW - 210EW Product Manual WHR Table 24, WHR-040EW through WHR-070EW WHR UNIT SIZE 040EW 045EW 050EW 060EW 070EW Unit capacity @ ARI conditions tons, (kW) (1) 38.4 (135.0) 44.1(155.1) 50.6 (177.9) 58.2 (204.6) 70.2 (246.8) No. Circuits 2 2 2 2 2 COMPRESSORS Nominal Horsepower 20 22 25 25 30 30 30 30 35 35 Number 1 1 1 1111111 Speed RPM 1750 1750 1750 1750 1750 No. of Cylinders 4 4 4 4444666 Oil Charge Oz., (L) 135 (4.0) 130 (3.8) 130 (3.8) 130 (3.8) 140 (4.1) 140 (4.1) 140 (4.1) 140 (4.1) 140 (4.1) 140 (4.1) Discharge Valve In., (mm) 1 3/8 (35) 1 3/8 (35) 1 3/8 (35) 1 3/8 (35) 1 3/8 (35) 1 3/8 (35) 1 3/8 (35) 1 5/8 (41) 1 5/8 (41) 1 5/8 (41) CONDENSERS Number 2 2 2 2 2 Diameter In., (mm) 8 5/8 8 5/8 8 5/8 8 5/8 8 5/8 8 5/8 8 5/8 8 5/8 8 5/8 8 5/8 (219 (219 (219 (219 (219 (219 (219 (219 (219 (219 Tube Length In., (mm) 96 (2438) 96 (2438) 96 (2438) 96 (2438) 96 (2438) 96 (2438) 96 (2438) 96 (2438) 96 (2438) 96 (2438) Design W.P.PSIG, (kPa): Refrigerant Side 450 (3104) 450 (3104) 450 (3104) 450 (3104) 450 (3104) Water Side 250 (1724) 250 (1724) 250 (1724) 250 (1724) 250 (1724) No. of Passes 2 2 2 2222222 Pump-Out Capacity Lb., (kg) (2) 130 (60) 130 (60) 125 (58) 125 (58) 125 (58) 125 (58) 116 (53) 116 (53) 116 (53) 116 (53) Connections: Water Inlet & Outlet In., (mm) (3) 2 1/2 (64) 2 1/2 (64) 2 1/2 (64) 2 1/2 (64) 2 1/2 (64) 2 1/2 (64) 2 1/2 (64) 2 1/2 (64) 2 1/2 (64) 2 1/2 (64) Relief Flare In., (mm) 1/2 (13) 1/2 (13) 1/2 (13) 1/2 (13) 1/2 (13) Purge Valve Flare In., (mm) 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 (6) & (13) (6) & (13) (6) & (13) (6) & (13) (6) & (13) Liquid Subcooling Integral Integral Integral Integral Integral EVAPORATOR No. Refrigerant Circuits 2 2 2 2 2 Diameter In., (mm) 10 3/4 (273) 10 3/4 (273) 10 3/4 (273) 12 3/4 (324) 12 3/4 (324) Tube Length In., (mm) 96 (2438) 96 (2438) 96 (2438) 96 (2438) 96 (2438) Water Volume Gallons, (L) 17.9 (1.1) 17.9 (1.1) 17.9 (1.1) 24.3 (1.5) 24.3 (1.5) Refrigerant Side D.W.P. 225 (1552) 225 (1552) 225 (1552) 225 (1552) 225 (1552) PSIG, (kPa) Water Side D.W.P. PSIG, (kPa) 175 (1207) 175 (1207) 175 (1207) 175 (1207) 175 (1207) Water Connections: Inlet & Outlet(4) 4 (102) 4 (102) 4 (102) 5 (127) 5 (127) Drain & Vent(NPT INT.) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) DIMENSIONS Length In., (mm) 117 (2972) 117 (2972) 117 (2972) 117 (2972) 117 (2972) Width In., (mm) 34 (864) 34 (864) 34 (864) 34 (864) 34 (864) Height In., (mm) 62 1/4 (1581) 62 1/4 (1581) 62 1/4 (1581) 63 3/4 (1619) 63 3/4 (1619) WEIGHTS Operating Weight, Lb., (kg) 3614 (1639) 3686 (1672) 3696 (1676) 3980 (1805) 4057 (1840) Shipping Weight, Lb., (kg) 3644 (1653) 3716 (1686) 3726 (1690) 3925 (1780) 4002 (1815) Operating Charge Lb., (kg) R-22 45 (20) 45 (20) 50 (23) 50 (23) 50 (23) 50 (23) 55 (25) 55 (25) 60 (27) 60 (27) Notes: 1. Certified in accordance with ARI Standard 590. 2. 80% Full R-22 at 90F (32C) per refrigerant circuit. 3. NPT External WHR040-070. 4. Victaulic WHR040-070.

Product Manual WHR WHR 017EW - 210EW 37 Table 25, WHR-080EW through WHR-110EW WHR UNIT SIZE 080E 085E 090EW 095E 100E 110EW Unit capacity @ ARI conditions tons, (kW) (1) 76.7 (269.7) 83.8 (294.6) 90.8 (319.3) 94.9 (333.7) 100.7 (354.1) 110.1 (387.1) No. Circuits 2 2 2 2 2 2 COMPRESSORS Nominal Horsepower 40 40 40 50 50 50 30/25 30/25 30/25 30/25 35/25 35/25 Number (2) 1 1 1 1 1 1 2 2 2 2 2 2 Speed RPM 1750/1450 1750/1450 1750/1450 1750/1450 1750/1450 1750/1450 No. of Cylinders 6 6 6 8 8 8 4/4 4/4 6/4 6/4 6/4 6/4 Oil Charge Oz. 255 255 255 255 255 255 140/130 140/130 140/130 140/130 140/130 140/130 (L) (7.5) (7.5) (7.5) (7.5) (7.5) (7.5) (4.1)/(3.8) (4.1)/(3.8) (4.1)/(3.8) (4.1)/(3.8) (4.1)/(3.8) (4.1)/(3.8) Discharge Valve In. (mm) 1 5/8 1 5/8 1 5/8(41) 1 5/8 1 5/8 1 5/8 1 3/8/ 1 3/8/ 1 3/8/ 1 3/8/ 1 3/8/ 1 3/8/ (41) (41) (41) (41) (41) 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 (35) / (35) (35) / (35) (35) / (35) (35) / (35) (35) / (35) (35) / (35) CONDENSERS Number 2 2 2 2 2 2 Diameter In., (mm) 8 5/8 8 5/8 10 3/4 10 3/4 10 3/4 10 3/4 10 3/4 10 3/4 10 3/4 10 3/4 10 3/4 10 3/4 (219) (219) (273) (273) (273) (273) (273) (273) (273) (273) (273) (273) Tube Length In., (mm) 96 96 96 96 96 96 120 120 120 120 120 120 (2438) (2438) (2438) (2438) (2438) (2438) (3048) (3048) (3048) (3048) (3048) (3048) Design W.P.PSIG, (kPa): Refrigerant Side 450 (3104) 450 (3104) 450 (3104) 450 (3104) 450 (3104) 450 (3104) Water Side 250 (1724) 250 (1724) 250 (1724) 250 (1724) 250 (1724) 250 (1724) No. of Passes 2 2 2 2 2 2 2 2 2 2 2 2 Pump-Out Capacity Lb., (kg) (3) 199 (90) 199 (90) 185 (84) 185 (84) 185 (84) 185 (84) 252 (114) 252 (114) 252 (114) 252 (114) 252 (114) 252 (114) Connections: Water Inlet & Outlet In., (mm) 2 1/2 2 1/2 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) (4) (64) (64) Relief Flare In., (mm) 1/2 (13) 1/2 (13) 1/2 (13) 5/8 (16) 5/8 (16) 5/8 (16) Purge Valve Flare In. 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 (mm) (6) & (13) (6) & (13) (6) & (13) (6) & (13) (6) & (13) (6) & (13) Liquid Subcooling Integral Integral Integral Integral Integral Integral EVAPORATOR No. Refrigerant Circuits 2 2 2 2 2 2 Diameter In., (mm) 12 3/4 (324) 14 (356) 14 (356) 14 (356) 14 (356) 14 (356) Tube Length In., (mm) 96 (2438) 96 (2438) 96 (2438) 120 (3048) 120 (3048) 120 (3048) Water Volume Gallons, (L) 24.3 (1.5) 27.8 (1.8) 27.8 (1.8) 38.2 (2.4) 38.2 (2.4) 38.2 (2.4) Refrigerant Side D.W.P. PSIG, 225 (1552) 225 (1552) 225 (1552) 225 (1552) 225 (1552) 225 (1552) (kPa) Water Side D.W.P. PSIG, (kPa) 175 (1207) 175 (1207) 175 (1207) 175 (1207) 175 (1207) 175 (1207) Water Connections: Inlet & Outlet(5) 5 (127) 5 (127) 5 (127) 6 (152) 6 (152) 6 (152) Drain & Vent(NPT INT.) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) DIMENSIONS Length In., (mm) 117 (2972) 115 3/4 (2940) 115 3/4 (2940) 142 3/4 (3626) 142 3/4 (3626) 142 3/4 (3626) Width In., (mm) 34 (864) 34 (864) 34 (864) 34 (864) 34 (864) 34 (864) Height In., (mm) 63 3/4 (1619) 66 1/4 (1683) 66 1/4 (1683) 77 (1956) 77 (1956) 77 (1956) WEIGHTS Operating Weight, Lb., (kg) 4242 (1924) 5316 (2411) 5626 (2552) 6090 (2762) 6170 (2799) 6170 (2799) Shipping Weight, Lb., (kg) 4187 (1899) 5176 (2348) 5486 (2488) 5900 (2676) 5980 (2713) 5980 (2713) Operating Charge Lb., (kg) R-22 65 (29) 65 (29) 70 (32) 70 (32) 80 (36) 80 (36) 85 (39) 85 (39) 90 (41) 90 (41) 90 (41) 90 (41) Notes: 1. Certified in accordance with ARI Standard 590. 2. Unit sizes WHR095 through 210 have two compressors per circuit in parallel. 3. 80% Full R-22 at 90F (32C) per refrigerant circuit. 4. NPT External WHR080 - 110. 5. Victaulic connections, WHR080 - 110.

38 WHR 017EW - 210EW Product Manual WHR Table 26, WHR-115EW through WHR-165EW WHR UNIT SIZE 115EW 120EW 130EW 145EW 155EW 165EW Unit capacity @ ARI conditions tons, (kW) (1) 112.7 (396.3) 121.4 (426.8) 131.4 (462.0) 143.9 (505.9) 152.5 (536.2) 162.3 (570.6) No. Circuits 222222 COMPRESSORS Nominal Horsepower 35/25 35/25 35/25 35/35 35/35 35/35 35/35 35/40 40/40 40/40 40/50 40/50 Number (2) 222222222222 Speed RPM(60 Hz/50 Hz) 1750/1450 1750/1450 1750/1450 1750/1450 1750/1450 1750/1450 No. of Cylinders 6/4 6/4 6/4 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/8 6/8 Oil Charge Oz. 140/130 140/130 140/130 140/140 140/140 140/140 140/140 140/255 225/255 225/255 225/255 225/255 (L) (4.1)/(3.8) (4.1)/(3.8) (4.1)/(3.8) (4.1)/(4.1) (4.1)/(4.1) (4.1)/(4.1) (4.1)/(4.1) (4.1)/(7.5) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) Discharge Valve In. (mm) 1 5/8/ 1 5/8/ 1 5/8/ 1 5/8/ 1 5/8 1 5/8/ 1 5/8/ 1 5/8/ 1 5/8/ 1 5/8/ 1 5/8/ 1 5/8/ 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 (41) / (35) (41) / (35) (41) / (35) (41) / (41) (41) / (41) (41) / (41) (41) / (41) (41) / (41) (41) / (41) (41) / (41) (41) / (41) (41) / (41) CONDENSERS Number 222222 Diameter In., (mm) 10 3/4 10 3/4 10 3/4 10 3/4 10 3/4 10 3/4 10 3/4 10 3/4 10 3/4 10 3/4 10 3/4 10 3/4 (273) (273) (273) (273) (273) (273) (273) (273) (273) (273) (273) (273) Tube Length In., (mm) 120 120 120 120 120 120 120 120 120 120 120 120 (3048) (3048) (3048) (3048) (3048) (3048) (3048) (3048) (3048) (3048) (3048) (3048) Design W.P.PSIG, (kPa): Refrigerant Side 450 (3104) 450 (3104) 450 (3104) 450 (3104) 450 (3104) 450 (3104) Water Side 250 (1724) 250 (1724) 250 (1724) 250 (1724) 250 (1724) 250 (1724) No. of Passes 222222222222 Pump-Out Capacity Lb., (kg) 227 (103) 227 (103) 227 (103) 227 (103) 227 (103) 227 (103) 215 (97.5) 215 (97.5) 205 (93) 205 (93) 190 (86.2) 190 (86.2) (3) Connections: Water Inlet & Outlet In., 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) (mm) (4) Relief Flare In., (mm) 1/2 (13) 1/2 (13) 5/8 (16) 5/8 (16) 5/8 (16) 5/8 (16) Purge Valve Flare In. 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 (mm) (6) & (13) (6) & (13) (6) & (13) (6) & (13) (6) & (13) (6) & (13) Liquid Subcooling Integral Integral Integral Integral Integral Integral EVAPORATOR No. Refrigerant Circuits 222222 Diameter In., (mm) 14 (356) 14 (356) 14 (356) 16 (406) 16 (406) 16 (406) Tube Length In., (mm) 120 (3048) 120 (3048) 120 (3048) 120 (3048) 120 (3048) 120 (3048) Water Volume Gallons, (L) 36.1 (2.3) 36.1 (2.3) 36.1 (2.3) 45.1 (2.9) 45.1 (2.9) 45.1 (2.9) Refrigerant Side D.W.P. PSIG, 225 (1552) 225 (1552) 225 (1552) 225 (1552) 225 (1552) 225 (1552) (kPa) Water Side D.W.P. 175 (1207) 175 (1207) 175 (1207) 175 (1207) 175 (1207) 175 (1207) PSIG, (kPa) Water Connections: Inlet & Outlet(5) 6 (152) 6 (152) 6 (152) 6 (152) 6 (152) 6 (152) Drain & Vent(NPT INT.) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) DIMENSIONS Length In., (mm) 142 3/4 (3626) 142 3/4 (3626) 142 3/4 (3626) 142 3/4 (3626) 142 3/4 (3626) 142 3/4 (3626) Width In., (mm) 34 (864) 34 (864) 34 (864) 34 (864) 34 (864) 34 (864) Height In., (mm) 77 (1956) 77 (1956) 77 (1956) 77 (1956) 77 (1956) 77 (1956) WEIGHTS Operating Weight, Lb., (kg) 6340 (2876) 6480 (2939) 6565 (2978) 7195 (3264) 7340 (3329) 7870 (3547) Shipping Weight, Lb. (kg) 6150 (2790) 6290 (2853) 6375 (2892) 6895 (3128) 7020 (3148) 7470 (3388) Operating Charge Lb., (kg) R- 95 (43) 95 (43) 95 (43) 95 (43) 100 (45) 100 (45) 100 (45) 100 (45) 100 (45) 100 (45) 100 (45) 100 (45) 22 Notes: 1. Certified in accordance with ARI Standard 590. 2. Unit sizes WHR095 through 210 have two compressors per circuit in parallel. 3. 80% Full R-22 at 90F (32C) per refrigerant circuit. 4. NPT External WHR115 - 165. 5. Victaulic connections, WHR115 - 165.Certified in accordance with ARI Standard 590.

Product Manual WHR WHR 017EW - 210EW 39 Table 27, WHR-175EW through WHR-210EW WHR UNIT SIZE 175EW 185EW 195EW 210EW Unit capacity @ ARI conditions tons, (kW) (1) 176.1 (619.2) 182.0 (639.9) 196.0 (689.1) 209.0 (734.8) No. Circuits 2222 COMPRESSORS Nominal Horsepower 40/60 40/60 50/50 50/50 50/60 50/60 60/60 60/60 Number (2) 2 2 2 2 2 2 2 2 Speed RPM(60 Hz/50 Hz) 1750/1450 1750/1450 1750/1450 1750/1450 No. of Cylinders 6/8 6/8 8/8 8/8 8/8 8/8 8/8 8/8 Oil Charge Oz. 255/255 255/255 255/255 255/255 255/255 255/255 255/255 255/255 (L) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) Discharge Valve In. (mm) 1 5/8/ 1 5/8/ 1 5/8/ 1 5/8/ 1 5/8/ 1 5/8/ 1 5/8/ 1 5/8/ 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 (41) / (41) (41) / (41) (41) / (41) (41) / (41) (41) / (41) (41) / (41) (41) / (41) (41) / (41) CONDENSERS Number 2222 Diameter In., (mm) 10 3/4 10 3/4 12 3/4 12 3/4 12 3/4 12 3/4 12 3/4 12 3/4 (273) (273) (323.9) (323.9) (323.9) (323.9) (323.9) (323.9) Tube Length In., (mm) 120 120 120 120 120 120 120 120 (3048) (3048) (3048) (3048) (3048) (3048) (3048) (3048) Design W.P.PSIG, (kPa): Refrigerant Side 450 (3104) 450 (3104) 450 (3104) 450 (3104) Water Side 250 (1724) 250 (1724) 250 (1724) 250 (1724) No. of Passes 2 2 2 2 2 2 2 2 Pump-Out Capacity 190 190 270 270 253 253 253 253 Lb., (kg) (3) (86.2) (86.2) (122.5) (122.5) (114.8) (114.8) (114.8) (114.8) Connections: Water Inlet & Outlet 3 (76) 3 (76) 4 (101.6) 4 (101.6) 4 (101.6) 4 (101.6) 4 (101.6) 4 (101.6) In., (mm) (4) Relief Flare In., (mm) 5/8 (16) 5/8 (16) 5/8 (16) 5/8 (16) Purge Valve Flare In. 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 (mm) (6) & (13) (6) & (13) (6) & (13) (6) & (13) Liquid Subcooling Integral Integral Integral Integral EVAPORATOR No. Refrigerant Circuits 2222 Diameter In., (mm) 16 (406) 18 (457.2) 18 (457.2) 18 (457.2) Tube Length In., (mm) 120 (3048) 120 (3048) 120 (3048) 120 (3048) Water Volume Gallons, (L) 45.1 (2.9) 57.3 (3.6) 57.3 (3.6) 57.3 (3.6) Refrigerant Side D.W.P. 225 (1552) 225 (1552) 225 (1552) 225 (1552) PSIG, (kPa) Water Side D.W.P. PSIG, 175 (1207) 175 (1207) 175 (1207) 175 (1207) (kPa) Water Connections: Inlet & Outlet(5) 6 (152) 6 (152) 6 (152) 6 (152) Drain & Vent(NPT INT.) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) DIMENSIONS Length In., (mm) 142 3/4 (3626) 145 7/8 (3705) 145 7/8 (3705) 145 7/8 (3705) Width In., (mm) 34 (864) 35 (889) 35 (889) 35 (889) Height In., (mm) 77 (1956) 79 (2007) 79 (2007) 79 (2007) WEIGHTS Operating Weight, Lb., (kg) 7870 (3547) 9195 (4171) 9290 (4214) 9300 (4218) Shipping Weight, Lb., (kg) 7470 (3388) 8795 (3989) 8890 (4033) 8900 (4037) Operating Charge Lb., 110 (50) 110 (50) 125 (57) 125 (57) 130 (60) 130 (60) 130 (60) 130 (60) (kg) R-22 Notes: 1. Certified in accordance with ARI Standard 590. 2. Unit sizes WHR095 through 210 have two compressors per circuit in parallel. 3. 80% Full R-22 at 90F (32C) per refrigerant circuit. 4. NPT External WHR175. FPT Internal WHR185 - 210. 5. Victaulic connections, WHR175 - 210Certified in accordance with ARI Standard 590.

40 WHR 017EW - 210EW Product Manual WHR Dimensional Data

Figure 7, WHR 017EW through WHR 030EW (all dimensions in inches (mm))

WHR Maximum Overall Chilled Water Condenser Water Model Dimensions Connections Connections Number L W H SIZE A D N SIZE P 017EW 104 1/4 26-1/4 46-1/2 2 NPT 13-1/2 17-3/4 51 2 NPT (INT) 1-1/2 (2648) (667) (1181) (EXT) (51) (343) (451) (1295) (51) (38) 020EW 104-1/4 26-1/4 46-1/2 2 NPT 13-1/2 17-3/4 51 2 NPT (INT) 1-2 (2648) (667) (1181) (EXT) (51) (343) (451) (1295) (51) (38) 025EW 101-1/2 29-1/2 47-1/2 2 NPT 7-1/2 18-3/4 51 2 NPT (INT) 1-3/4 (2578) (749) (1207) (EXT) (51) (191) (476) (1295) (51) (44) 030EW 106 29-1/2 46-1/2 2 NPT 13-1/2 18-3/4 51 2 NPT (INT) 1-3/4 (2692) (749) (1181) (EXT) (51) (343) (476) (1295) (51) (44)

Product Manual WHR WHR 017EW - 210EW 41 Figure 8, WHR 040EW through WHR 090EW (all dimensions in inches (mm))

WHR Maximum Overall Condenser Water MODEL Dimensions Connections (NPT) NUMBER L W H E F G J P 040EW 116-7/8 (2969) 34 (864) 62-1/4 (1581) 6-5/8 (168) 11-3/8 (289) 4-3/4 (121) 4-3/4 (121) 2-1/2 (64) 045EW 116-7/8 (2969) 34 (864) 62-1/4 (1581) 6-5/8 (168) 11-3/8 (289) 4-3/4 (121) 4-3/4 (121) 2-1/2 (64 050EW 116-7/8 (2969) 34 (864) 62-1/4 (1581) 6-5/8 (168) 11-3/8 (289) 4-34 (121) 4-34/ (121) 2-1/2 (64) 060EW 116-7/8 (2969) 34 (864) 63-3/4 (1619) 6-5/8 (168) 11-3/8 (289) 4-3/4 (121) 4-3/4 (121) 2-1/2 (64) 070EW 116-7/8 (2969) 34 (864) 63-3/4 (1619) 6-5/8 (168) 11-3/8 (289) 4-3/4 (121) 4-3/4 (121) 2-1/2 (64) 080EW 116-7/8 (2969) 34 (864) 63-3/4 (1619) 6-5/8 (168) 11-3/8 (289) 4-3/4 (121) 4-3/4 (121) 2-1/2 (64) 085EW 115-3/4 (2940) 34 (864) 66-1/4 (1683) 7-1/2 (191) 13-1/8 (333) 5-3/4 (146) 5-5/8 (143) 3 (76) 090EW 115-3/4 (2940) 34 (864) 66-1/4 (1683) 7-1/2 (191) 13-1/8 (333) 5-3/4 (146) 5-5/8 (143) 3 (76)

WHR Evaporator Water Center of MODEL Connections (Victaulic) Gravity NUMBER A C D T U X Y Z 040EW 2-3/4 (70) 23-3/8 (594) 4 (102) 19-5/8 (498) 58-1/8 (1476) 42-5/8 (1089) 23 (584) 13 (330) 045EW 2-3/4 (70) 23-3/8 (594) 4 (102) 19-5/8 (498) 58-1/8 (1476) 42-5/8 (1089) 23 (584) 13 (330) 050EW 2-3/4 (70) 23-3/8 (594) 4 (102) 19-5/8 (498) 58-1/8 (1476) 42-5/8 (1089) 23 (584) 13 (330) 060EW 3-1/2 (89) 24-7/8 (632) 5 (127) 19 5/8 (498) 59-5/8 (1495) 43 (1092) 25-1/8 (638) 12-3/4 (324) 070EW 3-1/2 (89) 24-7/8 (632) 5 (127) 19-5/8 (498) 59-5/8 (1495) 43 (1092) 25-1/8 (638) 12-3/4 (324) 080EW 3-1/2 (89) 24-7/8 (632) 5 (127) 19-5/8 (498) 59-5/8 (1495) 43 (1092) 25-1/8 (638) 12-3/4 (324) 085EW 3-1/2 (89) 27-1/8 (689) 6 (152) 18-1/2 (470) 62-1/8 (1578) 48 (1219) 23 (584) 13 (330) 090EW 3-1/2 (89) 27-1/8 (689) 6 (152) 18-1/2 (470) 62-1/8 (1578) 48 (1219) 23 (584) 13 (330) Notes: 1. Control box size: 76” (1930mm) L x 38½” H x 7¼” (184mm) D.

42 WHR 017EW - 210EW Product Manual WHR Figure 9, WHR 095EW through WHR 175EW (all dimensions in inches (mm))

WHR Maximum Overall Center of MODEL Dimensions Gravity NUMBER L W H X Y Z 095EW 142-3/4 (3626) 34 (864) 77 (1956) 55-1/4 (1403) 32-5/8 (829) 13-5/8 (346) 100EW 142-3/4 (3626) 34 (864) 77 (1956) 55-1/4 (1403) 32-5/8 (829) 13-5/8 (346) 110EW 142-3/4 (3626 34 (864) 77 (1956) 55-1/4 (1403) 32-5/8 (829) 13-5/8 (346) 115EW 142-3/4 (3626) 34 (864) 77 (1956) 55-7/8 (1419) 32-5/8 (829) 13-1/2 (343) 120EW 142-3/4 (3626) 34 (864) 77 (1956) 56-1/8 (1419) 32-5/8 (829) 13-1/2 (343) 130EW 142-3/4 (3626) 34 (864) 77 (1956) 56-1/8 (1426) 32-7/8 (835) 13-1/2 (343) 145EW 142-3/4 (3626) 34 (864) 77 (1956) 56-5/8 (1438) 32-5/8 (835) 13-1/2 (343) 155EW 142-3/4 (3626) 34 (864) 77 (1956) 56-1/4 (1429) 33-1/2 (845) 13-3/8 (340) 165EW 142-3/4 (3626) 34 (864) 77 (1956) 56-1/4 (1429) 33-1/2 (845) 13-3/8 (340) 175EW 142-3/4 (3626) 34 (864) 77 (1956) 56-1/4 (1429) 33-1/2 (845) 13-3/8 (340) Notes: 1. Control box size: 76” (1930mm) L x 38½” (978mm) H x 7¼” (184mm) D.

Product Manual WHR WHR 017EW - 210EW 43 Figure 10, WHR-185EW through WHR-210EW (all dimensions in inches (mm))

WHR Maximum Overall Center of MODEL Dimensions Gravity NUMBER L W H X Y Z 185EW 145-7/8 (3705) 35 (889) 79 (2007) 55 (1397) 36 (914) 13-1/2 (343) 195EW 145-7/8 (3705) 35 (889) 79 (2007) 55 (1397) 36 (914) 13-1/2 (343) 210EW 145-7/8 (3705) 35 (889) 79 (2007) 55 (1397) 36 (914) 13-1/2 (343) Notes: 1. Control box size: 76” (1930mm) L x 38½” (978mm) H x 7¼” x (184mm) D.

44 WHR 017EW - 210EW Product Manual WHR Application Data

Location and Space Requirements Unit is designed for indoor application and must be located in a space where the temperature is 40°F (4.4°C) or above. Provide clearance of 2 to 3 ft. (609 to 914mm) on each side and ends for piping and to help when servicing unit. Provide clearance at either end of the unit to permit cleaning of condenser tubes or for removal of tubes from condenser or cooler (see dimensional data). If a door or window is provided at one end of the unit, the tubes may be replaced through the opening provided.

Foundation Mount the unit on a level concrete foundation. Floors must be strong enough to support the unit weight. If necessary, use structural supports to transfer the weight of the unit to the nearest beams.

Vibration Isolation Vibration mounts are recommended for upper floor installations or where compressor noises might be objectionable ( to occupied spaces such as offices, meeting rooms, etc.). Vibration eliminators may be used for water piping connected to the unit to avoid transmission of water or pump noise into occupied spaces.

Typical Chilled Water Piping Flush the system water piping thoroughly before making connections to the unit evaporator. Install a 40 mesh strainer in the return water line before the inlet to the chiller. Design the water piping so the chilled water circulating pump discharges into the evaporator inlet. Connect return water line to evaporator inlet connection. Connect supply water line to evaporator outlet connection. Install a flow switch in the horizontal piping of the supply (evaporator outlet) water line. Provide drain connections at low points in the system to permit complete drainage of the system. Air vents should be located at the high points in the system to purge air out of the system. A vent connection on top of the evaporator vessel allows air to be purged. Purge air from the water system before unit start-up to ensure adequate flow through the evaporator. Install pressure gauges in the inlet and outlet water lines to the evaporator. Measure pressure drop through the evaporator to calculate proper flow. Vibration eliminators are recommended in both the supply and return water lines. Chilled water piping should be insulated to reduce heat loss and prevent condensation. Chillers not running in the winter should have their water systems thoroughly drained to protect against freezing. If the chiller operates year round, or if the system is not drained for the winter. Protect the outdoor chilled water piping against freezing. Wrap the lines with a heater cable and add proper amount of glycol to the system to further protect the system.

Product Manual WHR WHR 017EW - 210EW 45 Figure 11, Typical chilled water piping

Vent

Outlet Vibration Flow Balancing Gate valve Eliminator Valved Switch valve pressure gauge Protect all field piping against freezing Vibration Gate valve Eliminator Water Drain strainer

Condenser Water Be certain the condenser water enters the bottom connection of the condenser. The condenser water will exit the condenser from the top connection. Head pressure control must be provided. Fan cycling and modulating discharge dampers on the cooling towers or a three-way bypass valve around the tower is often used. Consult the tower manufacturer for information on specific applications. If city or well water is used for condensing, a two-way pressure actuated water regulating valve should be installed in the outlet piping of each condenser. The condenser purge valve provides a convenient pressure tap for the regulating valve. The valve can modulate in response to head pressure. When the compressor shuts down, this valve closes, preventing water from being siphoned out of the condenser.

Series or Parallel Operation Consider system pressure drop when designing the water piping. Parallel piped systems have half of the total system flow going through the evaporator of each chiller, reducing the individual unit and total system pressure drop. Series piped evaporators require that the total system water flows through both evaporators. Not only is the pressure drop through each evaporator increased but the pressure drops must be added together to obtain the total evaporator pressure drop. Series piped evaporators normally require larger circulating pumps for the chilled water system.

Electrical Hookup Every WHR chiller requires field installation of the main supply power, 115V hookup of the control circuit, system timeclock on-off switch, flow switch, and COPS pump starter relay. An optional “control circuit transformer” installed at the factory eliminates the need for field hookup of a separate 115V supply to the control circuit. See Figure 6 for field electrical hookups. The diagram shown represent all WHR units; however, individual terminal may vary between unit sizes. Each unit is provided with its specific wiring diagram in the control panel. All wiring must be done according to local and national codes.

Main Power Supply Disconnect Switch Every WHR unit uses a single factory installed main power supply terminal block. The main power supply terminal block will accept single or parallel power supply wiring. A factory installed non-fused disconnect switch is available as an option on WHR 040EW and above with single point power supply. The disconnect is properly sized for the model and voltage supplied.

46 WHR 017EW - 210EW Product Manual WHR Control Circuit Terminals are provided in the unit control center (terminals 1 and NB, typical field wiring diagram) for field hook-up of the control circuit to a 115V power supply. An optional control circuit transformer installed at the factory eliminates the requirement for a separate power supply to the control circuit. Terminals are also provided for field connection of the chilled water flow switch, unit time clock, ambient thermostat and/or remote on/off switch.

Compressor Time Lockout A fixed 5-minute solid-state lockout time delays compressor restart after safety cutout or power interruption, or under irregular cooling load demands.

Interlock Wiring The condenser water pump should be interlocked to cycle with the compressor(s). This will prevent the refrigerant pressure from being overly depressed during the off cycle and allows the energy savings of pump shutdown. Interlock terminals are provided in the unit control panel.

Design Limitations 1. Maximum allowable condenser water pressure is 250 psig (1724 kPa) (WHR 017EW through 210EW). 2. Maximum allowable evaporator water pressure is 175 psig (1207 kPa) (WHR 017EW through 210EW) 3. Maximum design saturated discharge temperature (SDT) is 140°F (60°C). SDT=Condensing temperature + discharge line loss. 4. Maximum allowable water temperature to evaporator in a non-operating cycling is 100°F (37.8°C). Maximum entering water temperature for operating cycle is 90°F (32.2°C) (during system changeover from heating to cooling cycle). 5. Minimum design leaving water temperature from the evaporator without freeze protection is 42°F (6°C). 6. Contact your McQuay representative for operation with tower condenser water entering the chiller below 70°F (21.1°C).

Product Manual WHR WHR 017EW - 210EW 47 Optional Features

Control Circuit Transformer For applications where a separate 115 volt power source is not available. The transformer is factory installed and wired between the line voltage power terminal block and the 115 volt control circuit.

Part Winding Start Part winding start works in conjunction with the unit’s standard compressor sequence start timers to reduce current inrush by providing two-step starting of each compressor. Not normally required on McQuay’s multiple compressor, sequence start design.

Hot Gas Bypass Hot gas bypass permits unit operation down to 10% of full load capacity and includes a hot gas bypass valve, solenoid valve and manual shutoff valve. Hot gas bypass can be provided on the first refrigerant circuit only or on both refrigerant circuits. If the hot gas bypass is only added to the first circuit (WHR-040EW through 210EW), the compressor lead-lag switch is omitted.

Vibration Isolators Spring or rubber-in-shear vibration isolators are available for field installation to reduce vibration transmission through the unit base.

Gauges Includes high side and low side refrigerant pressure gauges per refrigerant circuit and oil pressure gauges per compressor. The gauges are factory mounted on service gauge connections.

MicroTech Chiller Controller Options (WHR 040EW through 210EW)

Optional Network Master Panel (NMP) The MicroTech Network Master Panel (NMP) allows multiple reciprocating chiller controllers to be incorporated into a building-wide network with other MicroTech units and auxiliary controllers. In conjunction with a personal computer, it provides the building operator with the capability to perform advanced equipment control and monitoring from a central or remote location. The following features are provided by the optional NMP: • Remote unit monitoring • Advanced scheduling features • Advanced alarm management features • Global operator override • Global unit shutdown input • Demand metering • Historical electrical data logging

48 WHR 017EW - 210EW Product Manual WHR Optional Remote Monitoring And Sequencing Panel (RMS) One to three reciprocating chiller controllers can be incorporated into a network with this economical MicroTech remote monitoring and sequencing (RMS) panel. The optional RMS panel provides the following features: • Remote chiller monitoring (up to 3) • Automatic or manual chiller sequencing • Automatic or manual lead-lag designation • Common chiller scheduling • Optimal start control • Chilled water reset by outdoor air temperature or external 4-20 mA signal • Chiller run time totals by month, current year, and prior year • Cooling degree-day totals by month, current year, and prior year The RMS panel is equipped with a keypad/display that is identical to the chiller controller’s keypad/display. With a special keystroke combination, the RMS keypad/display can be interfaced with any chiller controller. It then operates identical to the chiller-mounted keypad/display.

Monitor A direct or remote connected PC can be used for monitoring unit operation, changing setpoints, scheduling, trend logging, downloading controller software, and diagnostics. For MicroTech network systems, the PC gives the operator access to all unit and auxiliary controllers in the network. Specific controller or global data can be displayed as desired. All keypad status information and control capability is available at the PC in a full-screen format. Many additional unit control parameters, which are not available at the unit controller’s keypad, are also available. Monitor software provides the following features: • High resolution, unit-specific graphic representations • One-touch function keys • Multiple unit display screen • Automatic screen refresher • Help text • Dial-up communications • Alarm monitoring and management • Scheduling • Trend logging • Downloading capability • Multi-level password protection • Controller Diagnostics

Open Protocol Open Protocol provides an interface between MicroTech unit controllers and the building automation system of one of several participating manufacturer. A protocol is a set of rules governing data exchange between microprocessors, permitting communications between unlike controllers. Because there is no universally standard protocol, McQuay has “opened” MicroTech protocol to a growing number of building automation system partners. As a result, building designers, owners and operators can obtain the advantages of McQuay equipment, and the control versatility MicroTech has to offer.

Product Manual WHR WHR 017EW - 210EW 49 Water Flow Switch A water flow safety switch in the chilled water piping prevents evaporator freeze-up under low or no flow conditions. Terminals are provided in the unit control center for field hookup of the water flow safety switch.

Discharge Line Mufflers Discharge line mufflers are available as an option on all units and are standard on units 185 tons and above. Discharge line mufflers are recommended on any water cooled unit with entering condenser water temperature in excess of 100°F (37.8°C) or when optional acoustical enclosure is ordered.

Chilled Water Reset (WHR 040EW through 210EW) In applications when outside temperature has a major effect on the load of the building outdoor air reset can be provided to increase the system efficiency by resetting the supply water temperature upward as the outside temperature drops. The amount of reset is adjustable between 5°F (2.8°C) and 20°C (11.1°C).

Indicator Light Package (WHR 040EW through 210EW) Units can be provided with factory installed diagnostic indicator lights which illuminate upon a safety fault as well as lights displaying power on and compressor staging. Each safety has an individually labeled light.

Disconnect Switch (WHR 404EW through 210EW) A factory installed non-fused disconnect switch is available as an option with single point power supply. The disconnect is properly sized for model and voltage required.

Circuit Breakers Factory installed circuit breakers are available as an option of unit sizes WHR 040EW through 090EW with single point power supply. Circuit breakers are standard on unit sizes WHR 017EW through 030EW and WHR 095EW through 210EW with single point power. This option provides unit installed compressor short circuit protection.

Additional Capacity Reduction Steps Additional steps of cylinder unloading is available on the compressor to provide additional capacity control on unit sizes WHR 025EW and WHR 030EW, and on unit sizes WHR 070EW through 210EW. (See Capacity Reduction Steps under “Physical Data”).

Alarm Bell With Cycle Counter and Hour Meters (WHR-040EW through 210EW) A 24 volt alarm bell signals safety trip of the freeze protection pressurestat, high pressure cutout, oil failure cutout, or motor overload. The bell is factory mounted on the unit control center. A time clock is also available with a spring carryover. During normal operation, the spring is wound to operate the clock for up to ten hours should the power be lost to the unit.

50 WHR 017EW - 210EW Product Manual WHR Time Clock The 24-hour clock for remote field installation for night and weekend system shutdown. The time clock is field connected to the remote shutdown terminals provided in the unit control center. A time clock is also available with a spring carryover. During normal operation, the spring is wound to operate the clock for up to ten hours should the power be lost to the unit.

Short Circuit/Overload Protection Companion trip automatic circuit breakers are available per compressor. External (supplemental) overloads added per compressor (in addition to standard compressor internal overload protection) is available on 40 tons and above.

Phase Loss/Voltage Protection Three levels of phase failure protection are available as a factory installed option on all units. Phase loss with under voltage protection, phase loss with under/over voltage protection, and phase loss with under/over voltage protection and multiple LED indication of fault type.

High Return Water Unloader (WHR 040EW through 210EW) A factory installed high return water unloader thermostat is available for applications where the return water temperature to the evaporator exceeds an adjustable setpoint for short periods of time at startup.

Acoustical Compressor Enclosure A factory installed acoustical compressor enclosure is available for all units when low sound levels are a consideration. The sheet metal enclosure is acoustically lined with 1 inch fiberglass insulation.

Product Manual WHR WHR 017EW - 210EW 51 Product Specifications

WHR 017EW through 030EW

PART 1 - GENERAL

1.01 SUMMARY

Section includes design, performance criteria, refrigerants, controls, and installation requirements for water-cooled reciprocating compressor packaged chillers.

1.02 REFERENCES

Comply with applicable Standards/Codes of ARI 590, ANSI/ASHRAE 15, ASHRAE 90.1, ASME Section VIII, NEC, and OSHA as adopted by the State.

1.03 SUBMITTALS

A. Submit shop drawings and product data in accordance with contract specifications

B. Submittals shall include the following:

1. Dimensioned plan and elevation view drawings, required clearances, and location of all field connections.

2. Summary of all auxiliary utility requirements such as: electricity, water, compressed air, etc. Summary shall indicate quality and quantity of each required utility.

3. Single line schematic drawing of the power field hookup requirements, indicating all items which are furnished.

4. Schematic diagram of control system indicating points for field interface/connection. Diagram shall fully delineate field and factory wiring.

5. Manufacturer’s certification of factory run test of chiller unit signed by company officer.

6. Installation manuals.

1.04 QUALITY ASSURANCE

A. Qualifications; Equipment manufacturer must specialize in the manufacture of the products specified and have five years experience with the equipment and refrigerant offered.

B Regulatory Requirements: Comply with the codes and standards specified

C Chiller manufacturer must be ISO 9002 registered.

52 WHR 017EW - 210EW Product Manual WHR 1.05 DELIVERY AND HANDLING

A. Chillers shall be delivered to the job site completely assembled and charged with refrigerant and oil by the manufacturer

B. Comply with the manufacturers instructions for rigging and handling equipment.

1.06 WARRANTY

The equipment manufacturer’s warranty shall be for a period of one year from date of equipment start and acceptance but not more than 18 months from shipment. The warranty shall cover defective material and workmanship within the above period, excluding refrigerant.

PART 2--PRODUCTS

2.01 ACCEPTABLE MANUFACTURERS

A. McQuay International

B. (Approved Equal)

2.02 UNIT DESCRIPTION

Provide and install as shown on the plans factory assembled, factory charged, and factory run tested, water-cooled reciprocating compressor packaged chillers in the quantity specified. Each chiller shall consist of hermetic reciprocating compressor, direct expansion evaporator, water-cooled condenser, control system and all components necessary for safe and controlled unit operation.

2.03 DESIGN REQUIREMENTS

A. General: Provide a complete reciprocation packaged chiller as specified herein and as shown on the drawings . The unit shall be in accordance with the standards referenced in section 1.02 and any local codes in effect.

B. Performance: Refer to the schedule of performance on the drawings. Performance shall be in accordance with applicable ARI Standard.

C. Acoustics: Sound pressure levels for the unit shall not exceed the following specified levels. The manufacturer shall provide the necessary sound treatment to meet these levels if required. Sound data shall be provided with the quotation. Test shall be in accordance with ARI Standard 575.

Octave Band

63 125 250 500 1000 2000 4000 8000 dBA

Product Manual WHR WHR 017EW - 210EW 53 2.04 CHILLER COMPONENTS

A. Compressor: The compressor shall be of the accessible hermetic reciprocating type with suction and discharge service valves, crankcase oil heater and suction strainer. Compressor shall have a forced feed lubrication system with a reversible oil pump, oil sight glass, and oil charge. The compressor motor shall be refrigerant gas cooled, high torque, hermetic induction type, four-pole, with inherent thermal protection on all three phases and shall be mounted on spring vibration isolators.

B. Evaporator: The evaporator shall be direct expansion type with steel shell, internal water baffles, and internally finned copper tubes roller expanded into carbon steel tube sheets. Refrigerant heads shall be removable. The cooler shall be insulated with a heavy layer of closed cell foamed insulation. It shall be designed, tested and stamped in accordance with ASME Code requirements.

C. Condenser: Horizontal shell and finned tube type with steel shell and integral finned copper tubes rolled into steel tube sheets which are to be drilled, and multiple grooved to facilitate gas-tight rolling. The condenser shall be equipped with intermediate tube supports. Construct condenser in accordance with the requirements of ASME Section VIII Unfired Pressure Vessel Code. It shall be designed for 225 psi (1552 kPa) water side working pressure and 450 psig (3104 kPa) refrigerant side pressure and be provided with an ASME, pressure relief valve.

D. Refrigerant Circuit: The refrigerant circuit shall include a liquid line shutoff valve, replaceable core filter-drier, sight glass with moisture indicator, liquid line solenoid valve (no exceptions), thermal expansion valve, discharge gas muffler, insulated suction line and a 450 psig (3104 kPa) relief valve.

E. Control System: A centrally located control panel shall contain the field power connection points, control interlock terminals, and control system. Power and starting components shall include automatic circuit breakers, fused control circuit, a motor contactor, solid-state start timer, solid-state compressor three-phase motor overload protection, and unit power terminal blocks for connection to remote disconnect switch. Hinged access doors shall be lockable. Deadfront panels are required to protect against accidental contact with line voltage when accessing the control system.

Safety and operating control shall include unit control stop switch, recycling pumpdown control, oil safety switch, high and low pressure safety switch, water temperature controller, freeze protection pressurestat, Unit shall provide limited recycling pumpdown protection at all times.

F. The following options are to be included: • Control circuit transformer • Part winding start • Three phase power loss with under and over voltage protection • Refrigerant and oil pressure gauges • High return water thermostat to keep compressor unloaded with high startup water temperatures. Contractor to field mount sensor and field wire to control panel. • Hot gas bypass on all circuits • Factory installed cycle counter an run hour meter • Chilled water flow switch to be field mounted by the contractor in the chilled water line and field wired to terminals in the control panel. • Spring vibration isolators for field installation

54 WHR 017EW - 210EW Product Manual WHR PART 3 - EXECUTION

3.01 INSTALLATION

A. Install in strict accordance with manufacturer’s requirements, shop drawings, and Contract Documents.

B. Adjust and level chiller in alignment on supports.

C. Coordinate electrical installation with electrical contractor.

D. Coordinate controls with control contractor.

E. Provide all appurtenances required to insure a fully operational and functional chiller.

3.02 START-UP

A. Insure proper charge of refrigerant and oil.

B. Provide testing, and starting of machine, and instruct the Owner in its proper operation and maintenance.

END OF SECTION

Product Manual WHR WHR 017EW - 210EW 55 WHR 040E through WHR 210E PART 1 - GENERAL

1.01 SUMMARY

Section includes design, performance criteria, refrigerants, controls, and installation requirements for water-cooled reciprocating compressor packaged chillers.

1.02 REFERENCES

Comply with applicable Standards/Codes of ARI 590, ANSI/ASHRAE 15, ASHRAE Standard 90.1, ASME Section VIII, NEC, and OSHA as adopted by the State.

1.03 SUBMITTALS

A. Submit shop drawings and product data in accordance with contract specifications.

B. Submittals shall include the following:

1. Dimensioned plan and elevation view drawings, required clearances, and location of all field connections.

2. Summary of all auxiliary utility requirements such as: electricity, water, compressed air, etc. Summary shall indicate quality and quantity of each required utility.

3. Single line schematic drawing of the power field hookup requirements, indicating all items which are furnished.

4. Schematic diagram of control system indicating points for field connection. Diagram shall fully delineate field and factory wiring.

5. Certification of factory run test of chiller unit signed by company officer.

6. Installation manual.

1.04 QUALITY ASSURANCE

A. Qualifications; Equipment manufacturer must specialize in the manufacture of the products specified and have five years experience with the equipment and refrigerant offered.

B Regulatory Requirements: Comply with the codes and standards specified

C Chiller manufacturer must be ISO 9002 registered.

56 WHR 017EW - 210EW Product Manual WHR 1.05 DELIVERY AND HANDLING

A. Chillers shall be delivered to the job site completely assembled and charged with refrigerant and oil by the manufacturer

B. Comply with the manufacturers instructions for rigging and handling equipment.

1.04 WARRANTY

The equipment manufacturer’s warranty shall be for a period of one year from date of equipment start up but not more than 18 months from shipment. The warranty shall cover defective material and workmanship within the above period, excluding refrigerant.

PART 2--PRODUCTS

2.01 ACCEPTABLE MANUFACTURERS

A. McQuay International

B. (Approved Equal)

2.02 UNIT DESCRIPTION

Provide and install as shown on the plans factory assembled, factory charged, and factory run tested water-cooled reciprocating compressor packaged chillers in the quantity specified. Each chiller shall consist of multiple accessible-hermetic reciprocating compressors, multicircuit direct expansion evaporator, water-cooled condensers, control system and all components necessary for safe and controlled unit operation.

2.03 DESIGN REQUIREMENTS

A. General: Provide a complete reciprocating packaged chiller as specified herein and as shown on the drawings . The unit shall be in accordance with the standards referenced in section 1.02 and any local codes in effect.

B. Performance: Refer to the schedule of performance on the drawings. Performance shall be in accordance with applicable ARI Standard.

C. Acoustics: Sound pressure levels for the unit shall not exceed the following specified levels. The manufacturer shall provide the necessary sound treatment to meet these levels if required. Sound data shall be provided with the quotation. Test shall be in accordance with ARI Standard 575.

Octave Band

63 125 250 500 1000 2000 4000 8000 dBA

Product Manual WHR WHR 017EW - 210EW 57 2.04 CHILLER COMPONENTS

A. Compressors: The compressors shall be accessible hermetic reciprocating type with suction and discharge service valves, crankcase oil heaters and suction strainers. The compressors shall have a forced feed lubrication system with a reversible oil pump, oil sight glass, and oil charge. The compressor motors shall be refrigerant gas cooled, high torque, hermetic induction type, four-pole, with inherent thermal protection on all three phases and shall be mounted on spring vibration isolators.

B. Evaporator: The evaporator shall be direct expansion type with steel shell, polypropylene water baffles, and internally finned copper tubes roller expanded into carbon steel tube sheets. Refrigerant heads shall be removable. The cooler shall be insulated with 3/4 inch (12.7mm) closed cell insulation and painted with resilient paint to resist cracking. It shall be designed, tested and stamped in accordance with ASME Code requirements.

C. Condensers: Horizontal shell and finned tube type with steel shell and integral finned copper tubes rolled into steel tube sheets which are to be drilled, and multiple grooved to facilitate gas-tight rolling. The chiller shall be equipped with intermediate tube supports. Construct condenser in accordance with the requirements of ASME Section VIII Unfired Pressure Vessel Code and ANSI B9.1 Safety Code. It shall be designed for 250 psi (1724 kPa) water side working pressure and 450 psig (3104 kPa) refrigerant side pressure and be provided with ASME, ANSI B9.1 pressure relief valves.

D. Refrigerant Circuit: Each refrigerant circuit shall include a liquid line shutoff valve, replaceable core filter-drier, sight glass with moisture indicator, liquid line solenoid valve (no exceptions), thermal expansion valve, and insulated suction line.

E. Control System: A centrally located control panel shall contain the field power connection points, control interlock terminals, and control system. Power and starting components shall include automatic circuit breakers, fused control circuit, a motor contactor, solid-state start timer, solid-state compressor three-phase motor overload protection, and unit power terminal blocks for connection to remote disconnect switch. Hinged access doors shall be lockable. Deadfront panels are required to protect against accidental contact with line voltage when accessing the control system.

Safety and operating control shall include unit control stop switch, recycling pumpdown control, oil safety switch, high and low pressure safety switch, water temperature controller, freeze protection pressurestat. The unit shall unload each refrigerant circuit alternately. Unit shall provide recycling pumpdown protection at all times. --OR-- E. Microprocessor based control system: A centrally located weatherproof control panel shall contain the field power connection points, control interlock terminals, and control system. Power and starting components shall include factory fusing of control circuit, solid-state start timer, solid-state compressor three-phase motor overload protection, and unit power terminal blocks for connection to remote disconnect switch. Hinged access doors shall be lockable. Deadfront panels are required to protect against accidental contact with line voltage when accessing the control system.

58 WHR 017EW - 210EW Product Manual WHR The system shall stage the unit based on the leaving water temperature. Safeties controlled by the microprocessor include oil differential pressure, motor protection, high pressure, loss of refrigerant, loss of water flow, freeze protection, and low refrigerant pressure. Controls shall include auto/stop switch, chilled water setpoint adjustment, anti-recycle timer, and digital display with water temperature and setpoint, operating temperatures and pressures, and diagnostic . The following features and functions shall be included:

1. The LCD type display shall have a minimum of 32 characters with all messages in plain English. Coded messages and LED displays are not acceptable.

2. Critical parameters shall have their own section of control and be password protected.

3. Resetting chilled water temperature by either controlling the return chilled water temperature or by a remote 4-20mA DC signal.

4. A soft load function to prevent the system from operating at full load during the chilled water pulldown period.

5. An electronic time clock to allow programming of a yearly schedule accommodating weekends and holidays.

6. Auto restart after a power failure, not requiring external battery back-up or auxiliary power for maintaining program memory.

7. Safety shutdowns shall be date and time stamped with system temperatures and pressures recorded. A minimum of six previous occurrences shall be kept in a revolving memory.

8. Start-to-start and stop-to-start timers to provide minimum compressor off- time with maximum motor protection.

9. Capability of communication with a PC or remote monitoring through a twisted pair RS-232 interface.

10. Lead-lag by manual selection or automatically by circuit run hours.

11. Continuous diagnostic checks of unit operation to provide a pre-alarm signal in advance of a shutdown allowing time for remedial action to be taken.

F. The following options are to be included:

• Control circuit transformer

• Part winding start

• Three phase power loss with under and over voltage protection

• Refrigerant and oil pressure gauges for non-microprocessor controls

• High return water thermostat to keep compressor unloaded with high startup water temperatures. Contractor to field mount sensor and field wire to control panel.

• Hot gas bypass on all circuits

• Factory installed cycle counter and run hour-meter

Product Manual WHR WHR 017EW - 210EW 59 • Chilled water flow switch to be field mounted in the chilled water line and field wired to terminals in the control panel.

• Spring vibration isolators for field installation

• Discharge line mufflers

• Disconnect switch factory installed

• Acoustical compressor enclosures

PART 3 - EXECUTION

3.01 INSTALLATION

A. Install in strict accordance with manufacturer’s requirements, shop drawings, and Contract Documents.

B. Adjust and level chiller in alignment on supports.

C. Coordinate electrical installation with electrical contractor.

D. Coordinate controls with control contractor.

E. Provide all appurtenances required to insure a fully operational and functional chiller.

3.02 START-UP

A. Ensure proper charge of refrigerant and oil.

B. Provide testing, and starting of machine, and instruct the Owner in its proper operation and maintenance.

END OF SECTION

60 WHR 017EW - 210EW Product Manual WHR Product Manual WHR WHR 017EW - 210EW 61 Post Office Box 2510 Staunton, Virginia 24402 USA (540) 248.0711