Insulation Coordination of Arcing Horns on HVDC Electrode Lines: Protection Performance Evaluation, Influence Factors and Improvement Method

Total Page:16

File Type:pdf, Size:1020Kb

Insulation Coordination of Arcing Horns on HVDC Electrode Lines: Protection Performance Evaluation, Influence Factors and Improvement Method energies Article Insulation Coordination of Arcing Horns on HVDC Electrode Lines: Protection Performance Evaluation, Influence Factors and Improvement Method Xiandong Li 1,2,3,* ID , Hua Li 1,2,3,*, Yi Liu 1,2,3 and Fuchang Lin 1,2,3 1 State Key Laboratory of Advanced Electromagnetic Engineering and Technology, Huazhong University of Science & Technology, Wuhan 430074, China; [email protected] (Y.L.); [email protected] (F.L.) 2 School of Electrical and Electronic Engineering, Huazhong University of Science & Technology, Wuhan 430074, China 3 Key Laboratory of Pulsed Power Technology (Huazhong University of Science and Technology), Ministry of Education, Wuhan 430074, China * Correspondence: [email protected] (X.L.); [email protected] (H.L.) Received: 19 January 2018; Accepted: 11 February 2018; Published: 13 February 2018 Abstract: Arcing horns are widely used in high voltage overhead lines to protect insulator strings from being destroyed by the free burning arcs caused by lightening faults. In this paper, we focus on the insulation coordination of arcing horns on the electrode lines of a 5000 MW, ±800 kV high voltage direct current (HVDC) system. The protection performance of arcing horns are determined by the characteristics of not only the external system but also the fault arc. Therefore, the behaviors and characteristics of long free burning arcs are investigated by the experiments at first. In order to evaluate the protection performance of arcing horns, the static stability criterion U-I characteristic method is introduced. The influence factors on the protection performance of arcing horns are analyzed theoretically. Finally, the improvement methods for the protection performance of arcing horns are proposed, and the diversified configuration strategy of arcing horns is recommended for cost saving. Keywords: HVDC electrode line; arcing horn; insulation coordination; protection performance; long free burning arc; arc behavior and characteristic 1. Introduction 1.1. Insulation Coordination Problem of Arcing Horns on HVDC Electrode Lines Arcing horns are widely used on high voltage overhead transmission lines to protect insulator strings from being destroyed by the free burning arcs caused by lightening faults. However, it is hard to extinguish arcs in high voltage direct current (HVDC) system, since there is no natural current zero point. Besides, it is difficult to detect fault arcs, especially for HVDC electrode lines, so fault arcs may continue to burn once formed if the fault arc is not detected. As a result, both arcing horns and insulator strings will be destroyed in the end. With the fast growing power transfer and transmission distance of HVDC systems, the insulation coordination problem of HVDC electrode lines is becoming more serious. Therefore, research on the performance of the arcing horns on HVDC electrode lines is very necessary. Electrode lines are used for the current return pass and as the voltage reference point of HVDC system. When the system is operating in bi-polar mode, as shown in Figure1a, the unbalanced current on the electrode lines can be ignored. Hence, there will be no problem with the extinction of fault arcs. However, when the system is operating in mono-polar mode, as shown in Figure1b, the operation Energies 2018, 11, 430; doi:10.3390/en11020430 www.mdpi.com/journal/energies Energies 2018, 11, 430 2 of 19 Energies 2018, 11, x FOR PEER REVIEW 2 of 19 currentoperation on the current electrode on the lines electrode is rather lines large. is rather If ala lightningrge. If a lightning fault happens, fault happens, the fault the fault arc arc may may not be extinguished,not be extinguished, then both then the arcingboth the horns arcing and horns insulator and insulator strings strings will be will burned be burned and and destroyed. destroyed. (a) HVDC system operated in bi-polar mode (b) HVDC system operated in mono-polar mode Figure 1. Operation mode of HVDC system. Figure 1. Operation mode of HVDC system. 1.2. Current Reaserches on Insulation Coordination of Arcing Horns on HVDC Electrode Lines 1.2. Current Reaserches on Insulation Coordination of Arcing Horns on HVDC Electrode Lines To solve this problem, the characteristics of fault arcs should be investigated firstly, and an optimizedTo solve insulation this problem, coordination the characteristicsscheme should be of studied fault based arcs the should characteristics be investigated of fault arcs. firstly, andThus, an optimized the whole insulation problem involves coordination two aspects: scheme the shouldcharacteristics be studied of fault based arcs and the characteristicsthe insulation of faultcoordination arcs. Thus, scheme. the whole problem involves two aspects: the characteristics of fault arcs and the insulationThe coordination fault arcs in scheme.HVDC systems are long free burning arcs. The long free burning arc (>100 mm) has quite different properties compared with the short arc (<10 mm) and the arc in closed space The fault arcs in HVDC systems are long free burning arcs. The long free burning arc (>100 mm) because of its complex behavior. The existing studies about long arcs are mainly concerned with its has quite different properties compared with the short arc (<10 mm) and the arc in closed space movement [1–5] and electrical [4–11] characteristics. because ofAs its for complex the insulation behavior. coordinati The existingon scheme, studies some aboutstudies long have arcs been are carried mainly out concerned [12–14]. Those with its movementworks can [1– 5be] andclassified electrical by their [4– methods11] characteristics. into two kinds: the maximum arc extinction current method andAs the for U-I the characteristic insulation method. coordination scheme, some studies have been carried out [12–14]. Those worksCanellas can [12] be classified carried out by studies their methodson the extinction into two of kinds:direct current the maximum (DC) arcs arc on extinctionlong electrode current methodlines and based the on U-I the characteristic experimental method. results of the Itaipu group, and gave the relations between the maximumCanellas [ 12arc] carriedextinction out current studies and on thethe extinctiongap length of of direct arcing current horns. (DC)However, arcs onthe long maximum electrode arc lines basedextinction on the experimental current is only results few hundreds of the Itaipu (≤400 group, A) and and the gavemaximum the relations gap length between is less thethan maximum 500 mm, arc extinctionwhich currentare not suitable and the for gap the length HVDC of systems arcing horns.with large However, operation the currents maximum used arc today. extinction current is Jankov [13] discussed about the protection performance of arcing horns on the HVDC system only few hundreds (≤400 A) and the maximum gap length is less than 500 mm, which are not suitable with neutral conductor. The static stability criterion Voltage-Current characteristic method (or U-I for the HVDC systems with large operation currents used today. characteristic method as usually called) was adopted to find the maximum protection region of arc horns.Jankov In [ 13our] discussedprevious works. about th thee protection protection performance performance of arcing of arcing horns horns in HVDC on the electrode HVDC lines system withwas neutral investigated conductor. also based The staticon the stabilityU-I characterist criterionic method, Voltage-Current and the influence characteristic factors were method analyzed (or U-I characteristicpreliminarily method [14]. Although, as usually the called) U-I characteristic was adopted method to find has the been maximum proved to protection be an effective region way of arc horns.for Inthe our insulation previous coordination works. the of protection arcing horns performance by [13,14], none of arcing of them horns provided in HVDC a comprehensive electrode lines was investigatedstudy on the influence also based factors on theand U-I the characteristicprotection performance method, improvement and the influence strategy factors for arcing were horns. analyzed preliminarily [14]. Although, the U-I characteristic method has been proved to be an effective way for the insulation coordination of arcing horns by [13,14], none of them provided a comprehensive study on the influence factors and the protection performance improvement strategy for arcing horns. Energies 2018, 11, 430 3 of 19 EnergiesIn this 2018 paper,, 11, x FOR the PEER insulation REVIEW coordination of arcing horns on the electrode lines of a3 5000 of 19 MW, ±800 kV HVDC system is studied. The U-I characteristic method is used to evaluate the protection performanceIn this of paper, arcing the horns. insulation Since coordination the protection of arcing performance horns on the of electrode arcing horns lines of is adecided 5000 MW, by the ±800 kV HVDC system is studied. The U-I characteristic method is used to evaluate the protection characteristics of not only electrode line system but also the fault arc, experiments have been carried performance of arcing horns. Since the protection performance of arcing horns is decided by the out tocharacteristics investigate of the not characteristics only electrode ofline long system free but burning also the arcs. fault The arc, factorsexperiments influencing have been the carried protection performanceout to investigate of arcing the horns characteristics are analyzed of long theoretically.free burning arcs. Finally, The factors the improvement influencing the strategy protection
Recommended publications
  • Substation Catalog
    Substation Catalog 618.797.5000 | TURNER ELECTRIC | turnerswitch.com | January 2016 Page 2 618.797.5000 | TURNER ELECTRIC | turnerswitch.com | January 2016 TABLE OF CONTENTS TMX Aluminum Vertical Break Switches (15kV through 345kV) ............................................................................................. 4 TMK40A Aluminum Vertical Break Switches (345kV through 765kV) ......................................................................................... 9 TSB Aluminum Side Break Switches (15kV through 161kV) ............................................................................................... 11 1D Copper Side Break Switches (15kV through 161kV)................................. 15 TDEB Aluminum Double End Break Switches (34kV through 345kV) .......................................................................................... 19 TCV2 Aluminum Center Break (V-Style) Switches (15kV through 161kV) ............................................................................................... 23 TCB2 Aluminum Center Break Switches (15kV through 161kV) ............................................................................................... 27 TECO-Rupter Vacuum Interrupters (15kV through 230kV) ............................................................................................ 29 Motor Operators .................................................................................................................. 33 618.797.5000 | TURNER ELECTRIC | turnerswitch.com | January 2016 Page 3 TMX VERTICAL
    [Show full text]
  • High Voltage Products the Complete Portfolio from One Source
    High Voltage Products The complete portfolio from one source www.siemens.com/energy Answers for energy. 3 1 2 6 3 7 1 2 7 3 4 5 4 2 3 5 6 1 6 1 Bushings 4 Disconnectors 7 Long Rod Insulators 2 Arresters 5 Instrument Transformers 3 Circuit Breakers 6 Reactors Content Foreword 05 Coil Products (HV) 48 – 51 Circuit Breakers and Disconnectors 06 – 29 Bushings 52 – 55 Surge Arresters 30 – 35 Long Rod Insulators 56 – 61 Instrument Transformers 36 – 47 Contact 63 4 Foreword High-voltage products and devices are the basis for an Our specialist subsidiaries Hochspannungsgeräte GmbH, efficient, high-performance, safe and reliable energy Troisdorf (HSP) and Trench Electric are global leaders in transmission. Our high-voltage products meet your their field: HSP is a leading company in the production requirements in terms of low life cycle costs with opti- of bushings. The Trench Group is a worldwide leading mum availability in continuous operation. They have a manufacturer of high voltage products such as instrument long service life and are also extremely earthquake-resis- transformers, bushings and reactors. This includes a wide tant and weatherproof. range of bushings products for Power Transformers, Gas Insulated Substations, Breakers, Generators, Buildings, The technology of our products sets international stan- Test Equipment, Rail Road Systems, HVDC and other dards. We ensure the high quality of the high-voltage specialty applications. products through optimized production processes, con- tinuous product development and a certified quality management system. This brochure showcases our portfolio of high-voltage products and devices. The portfolio comprises circuit breakers and disconnectors, surge arresters, instrument transformers, coil products, and last but not least bush- ings.
    [Show full text]
  • What Is Corona Effect
    What is Corona Effect One of the phenomena associated with all energized electrical devices, including high- voltage transmission lines, is corona. The localized electric field near a conductor can be sufficiently concentrated to ionize air close to the conductors. This can result in a partial discharge of electrical energy called a corona discharge, or corona. What is Corona? • Electric transmission lines can generate a small amount of sound energy as a result of corona. • Corona is a phenomenon associated with all transmission lines. Under certain conditions, the localized electric field near energized components and conductors can produce a tiny electric discharge or corona that causes the surrounding air molecules to ionize, or undergo a slight localized change of electric charge. • Utility companies try to reduce the amount of corona because in addition to the low levels of noise that result, corona is a power loss, and in extreme cases, it can damage system components over time. • Corona occurs on all types of transmission lines, but it becomes more noticeable at higher voltages (345 kV and higher). Under fair weather conditions, the audible noise from corona is minor and rarely noticed. • During wet and humid conditions, water drops collect on the conductors and increase corona activity. Under these conditions, a crackling or humming sound may be heard in the immediate vicinity of the line. • Corona results in a power loss. Power losses like corona result in operating inefficiencies and increase the cost of service for all ratepayers; a major concern in transmission line design is the reduction of losses. Source of Corona: • The amount of corona produced by a transmission line is a function of the voltage of the line, the diameter of the conductors, the locations of the conductors in relation to each other, the elevation of the line above sea level, the condition of the conductors and hardware, and the local weather conditions.
    [Show full text]
  • IMP/007/011 Version 1.1 Date of Issue Aug 2006 Page 1 of 11
    Document Reference IMP/007/011 Version 1.1 Date of Issue Aug 2006 Page 1 of 11 IMP/007/011 - Code of Practice for the Application of Lightning Protection 1.0 Purpose The purpose of this document is to ensure the company achieves its requirements with respect to the Electricity Act 1989 (as amended) (the Act), the Electricity Safety, Quality, and Continuity (ESQC) Regulations 2002, the Electricity at Work (EAW) Regulations 1989, the Distribution Licences and The Distribution Code, by laying out the way in which Northern Powergrid will develop efficient, co-ordinated and economical networks. This document specifies the type of lightning protection and the locations at which it is to be installed on the Northern Powergrid 11 kV, 20kV, 33 kV, 66 kV and 132kV networks. This document supersedes the following documents, all copies of which should be destroyed. There was no equivalent document in Northern Powergrid (Northeast Ltd) Ref Version Title DSS/007/011 Code of Practice for the Application of Surge Arresters 2.0 Scope This document covers the requirements, application, and installation of lightning protection on 11kV, 20kV, 33kV, 66kV and 132kV networks in Northern Powergrid; it is not intended for this policy to be applied retrospectively with the exception of locations suffering from poor performance under lightning conditions. All new networks shall be equipped with Lightning Protection in accordance with this Document. 3.0 Policy 3.1 Assessment of Relevant Drivers The key internal business drivers relating to Lightning Protection policy are: Customer Service This Code of Practice contributes toward quality of supply to customers by defining the application of lightning protection so as to minimise the damage to equipment and prevent interruption of supply.
    [Show full text]
  • Improved Lightning Performance for 132 Kv OHL
    Improved Lightning Performance for 132 kV OHL Master’s thesis in Electric Power Engineering Tomas Ingmarson Johan Stelin Department of Materials and Manufacturing Technology CHALMERS UNIVERSITY OF TECHNOLOGY Gothenburg, Sweden 2017 Master’s thesis 2017:195 Improved Lightning Performance for 132 kV OHL TOMAS INGMARSON JOHAN STELIN Department of Materials and Manufacturing Technology Division of High Voltage Engineering Chalmers University of Technology Gothenburg, Sweden 2017 Improved Lightning Performance for 132 kV OHL TOMAS INGMARSON JOHAN STELIN © TOMAS INGMARSON, JOHAN STELIN, 2017. Supervisor: Per Norberg, Vattenfall Eldistribution AB Examiner: Jörgen Blennow, Department of Materials and Manufacturing Technol- ogy Master’s Thesis 2017:195 Department of Materials and Manufacturing Technology Division of High Voltage Engineering Chalmers University of Technology SE-412 96 Gothenburg Telephone +46 31 772 1000 Cover: An old 132 kV wood portal tower without arcing horns and with two shield wires. Typeset in LATEX Gothenburg, Sweden 2017 iv Improved Lighting Performance for 132 kV OHL TOMAS INGMARSON JOHAN STELIN Department of Materials and Manufacturing Technology Chalmers University of Technology Abstract Lightning strokes to transmission lines causes a majority of the power quality issues that are so severe that sensitive industrial loads are disturbed. Historically Vatten- fall concluded that it is too expensive to use shield wires for the 132 kV grid due to the high soil resistivity in Sweden. Today the situation is different with sensitive industrial loads and the current Vattenfall standard is to build portal tower with one shield wire. The shield wire is however not used to reduce the amount of lightning faults, it is used to ground the cross arm and reduce the amount of short circuits.
    [Show full text]
  • Design and Analysis of Extra High Voltage Non-Ceramic Insulator by Finite Element Method
    World Academy of Science, Engineering and Technology International Journal of Electrical and Computer Engineering Vol:13, No:5, 2019 Design and Analysis of Extra High Voltage Non- Ceramic Insulator by Finite Element Method M. Nageswara Rao, V. S. N. K. Chaitanya, P. Pratyusha earth side which will make the electric field distribution non Abstract—High voltage insulator has to withstand sever uniform in the absence of grading ring. Grading ring will electrical stresses. Higher electrical stresses lead to erosion of the make the electric field distribution uniform by varying insulator surface. Degradation of insulating properties leads to parameters [1]. Electric field is analyzed for sphere to plane flashover and in some extreme cases it may cause to puncture. For gap arrangement with CSM and methods of moment. Results analyzing these electrical stresses and implement necessary actions to diminish the electrical stresses, numerical methods are best. By proved that CSM is better and accurate compared to methods minimizing the electrical stresses, reliability of the power system will of moment [2]. Electric fields of 11 kV and 33 kV silicone improve. In this paper electric field intensity at critical regions of 400 composite insulators are analyzed for various geometrical kV silicone composite insulator is analyzed using finite element configurations as per International Electro-technical method. Insulator is designed using FEMM-2D software package. Commission (IEC) standards by FEM [3]-[6]. With the help of Electric Field Analysis (EFA) results are analyzed for five cases i.e., EFA results, best geometrical configurations are identified. only insulator, insulator with two sides arcing horn, High Voltage (HV) end grading ring, grading ring-arcing horn arrangement and two EFA has been carried out for 400 kV Silicone Composite sides grading ring.
    [Show full text]
  • Comparison of Class 1 Surge Protective Devices
    Information and Communication Technology Technical Comparison of Class 1 surge protective devices by Holger Heckler, Phoenix Contact, Germany and John Ortika, Phoenix Contact, Australia Lightning current arrestors for low-voltage power systems are usually designed and tested only for use in AC power systems. The performance and operational behaviour of a surge protective device, connected to an AC power system, can be completely different to the performance and operational behaviour of the same surge protective device connected to a DC power system. The requirements and tests for surge of surge protective devices for DC power l Max. short-circuit current of one DC power protective devices (SPDs), connected to low systems, have been carried out with a supply: 12,5 A voltage power systems, are described in the specific application in mind, namely, in this l Max. short-circuit current of four DC power international standards IEC 61643-1 [1] and case, the protection of mobile phone base supplies: 50,0 A EN 61643-11 [2]. The scope of the stations with remote radio heads (RRH). IEC 61643-1 includes SPDs for AC applications The investigation, which includes test with a rated voltage of up to 1000 V AC and In this application four DC power supplies procedures for DC arresters has been derived SPDs for DC applications with a rated voltage (Delta power system DPS600B) are from the well-known test procedures for AC of up to 1500 V DC. Unfortunately no test connected in parallel. Consequently, the arresters. The operational behaviour of four DC power supplies, connected in parallel, procedures for the testing of SPDs connected following parameters are of importance to has been taken into consideration as well.
    [Show full text]
  • CHAPTER-8 SWITCHYARD EQUIPMENT- HV Bus Bars
    CHAPTER-8 SWITCHYARD EQUIPMENT- HV Bus Bars, Switchyard Structures, Isolating Switches, Current Transformers, Voltage Transformers, Lightning Arresters 8.1 Introduction Outdoor step up substations at hydroelectric stations are provided to step up power at generated voltage generally for interconnection with the grid to evacuate power. Generation voltage varies from 415 volts to 11 kV (or higher) and step up voltage of small hydro up to 5 MW capacity may not exceed 36 kV. In case of large hydro stations the step up voltage may be up to 420 kV. Switchyard equipment comprises of main equipment, ancillary equipment and switchyard structures. Step up transformers and circuit breakers are discussed in Section 6 & 7. Insulators switchyard structures, isolating switches current and voltage transformers and lightning arrestors are discussed in this chapter. Auxiliary equipment for switchyards is common with powerhouse auxiliary and discussed in Section II (Chapter 4 & 5). 8.1.1 Standards and Codes Relevant National Standards (Latest edition) are as follows: IS: 9920 Part I to IV – Alternating current switches for rated voltages above 1000 volts and less than 52 kV IS: 9921Part 1 to 5 – Alternating currents disconnectors (isolators) and earthing switches rating, design, construction, tests etc. IS: 1893 – Criteria for Earthquake resistance design of structures IS: 2705 Part 1 to 4 – Current transformer IS: 3156 Part 1 to 4 – voltage transformer IS: 3070 part 1 to 3 – Lightning arrestors IS: 2544 – Porcelain insulators for system above 1000 V IS: 5350 – Part III – post insulator units for systems greater than 1000 V IS: 5621 – Hollow Insulators for use in electrical equipment IS: 5556 – Serrated lock washers – specification IS: 3716 – Application guide for insulation co-ordination IS: 2165 – Phase to earth insulation co-ordination 8.2.
    [Show full text]
  • High-Voltage Products Are the Physical Backbone for Reliable, Safe, Environmentally-Friendly and Economical Power Transmission
    High-Voltage Products High Voltage Products Reliable products for all customer requirements siemens.com/energy-management Content Foreword ................................................................5 Circuit-Breakers ............................................... 6 – 23 Disconnectors ............................................... 24 – 35 Surge Arresters ............................................. 36 – 43 Instrument Transformers ............................... 48 – 67 Coil Products ................................................. 68 – 75 Bushings ....................................................... 76 – 83 Gas-Insulated Switchgear............................... 84 – 97 Silicone Long Rod Insulators ........................ 98 – 107 Service ...................................................... 108 – 111 3 Foreword Energy! The elixir of life on our globe. Energy demand will increase by over 30% by 2040. Our global society depends on a safe, clean and sustainable energy supply. Generating electrical power and its transmission and distribution will be the key to achieving this ambitious task. The huge power demand in cities and industries requires effective power plants, as well as an efficient transmission of electrical power at high-voltage levels. High-voltage products are the physical backbone for reliable, safe, environmentally-friendly and economical power transmission. This brochure showcases our comprehensive portfolio of high-voltage products: circuit-breakers, disconnectors and earthing switches, surge arresters, instrument
    [Show full text]
  • Automatic Transfer Switch, Bypass Isolation, Drawout, Contactor Type
    Technical Paper Cutler-Hammer Effective: June 2001 Page 1 Supersedes SA 199 David D. Roybal, P.E. Automatic pages 1-12, dated January 1996 Cutler-Hammer Fellow Application Engineer Transfer Switches A Performance Comparison — Molded Case Switch Versus Contactor Type Table of Contents Page Part I: Abstract application for mechanically held About the Author . 1 devices is for lighting control, where Molded case switch type automatic using a latched device allows a user Part I: Abstract. 1 transfer switches with trip units and Part II: “Circuit Breaker” to avoid having to reset all contactors “contactor” type automatic transfer after a utility outage. Versus “Contactor” switches protected by circuit breakers Design Transfer Switches . 1 perform equally for various fault Transfer switches are also capable of Part III: Time-Current Coordination . 3 conditions. High withstand molded high endurance, but not nearly as great Part IV: Transfer Switch case switch type automatic transfer as that of a motor starting/lighting Performance During a Fault . 5 switches without trip units perform contactor. UL 1008 defines the mini- Part V: Conclusions . 8 exactly as “contactor” type automatic mum endurance of a transfer switch. Part VI: References . 8 transfer switches, except that “contac- This is detailed in Table 1. Both “con- tor” type designs have limited with- tactor” and “circuit breaker” designs stand capabilities. Such “contactor” meet these minimum UL 1008 require- About the Author type designs have potential problems ments as evidenced by their UL label. in applications with upstream power Some transfer switch manufacturers David D. Roybal received the Bachelor circuit breakers having short delay trip may publish endurance capabilities in of Science degree in electrical engi- characteristics.
    [Show full text]
  • Power Switches Catalog
    POWER SWITCHES CATALOG USCO POWER SWITCHES 8100 Churchill Ave., Leeds, Alabama 35094 Telephone (573) 682-5521 Facsimile (573) 682-8714 www.uscopower.com [email protected] www.hubbellpowersystems.com NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice. ©Copyright 2013 Hubbell Incorporated • 210 North Allen Street • Centralia, MO 65240 Bulletin USCO-6 2 G E N E R A L These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation, or maintenance. I Should further information be desired or should particular problems arise which are not covered N sufficiently for the purchaser’s purposes, the matter should be referred to your USCO representa- F tive, or direct to the USCO factory. O R M A T UNPACKING INSTRUCTIONS I O N ALL GANG OPERATED SWITCHES (Grounding Switch Not Included) Each switch consists of three or more packaged items; the control parts box, the switch units, a bundle of pipe and the insulators when not assembled to the switch. Check packing list, attached to the switch crate, to determine if all material has been received. Check insulators carefully for cracked or broken por- celain. Check all other materials for possible shipment damage or loss. Report any claims to the carrier. 8.3 thru 48.3kV switch units are shipped completely assembled with insulators unless specified otherwise by the purchaser. 72.5kV thru 245kV switch units are shipped assembled, less insulators, unless specified by the purchaser or switch construction necessitates the complete assembly.
    [Show full text]
  • In the Early Power Systems Were Mainly Neutral Ungrounded Due to the Fact That the First Ground Fault Did Not Require the Tripping of the System
    UNIT I INTRODUCTION Introduction: In the early power systems were mainly Neutral ungrounded due to the fact that the first ground fault did not require the tripping of the system. An unscheduled shutdown on the first ground fault was particularly undesirable for continuous process industries. These power systems required ground detection systems, but locating the fault often proved difficult. Although achieving the initial goal, the ungrounded system provided no control of transient over-voltages. A capacitive coupling exists between the system conductors and ground in a typical distribution system. As a result, this series resonant L-C circuit can create over- voltages well in excess of line-to-line voltage when subjected to repetitive re-strikes of one phase to ground. This in turn, reduces insulation life resulting in possible equipment failure. Neutral grounding systems are similar to fuses in that they do nothing until something in the system goes wrong. Then, like fuses, they protect personnel and equipment from damage. “Damage comes from two factors, how long the fault lasts Iandmp ohowrtanlacregeoftheNeufatultralcGurroreundnt iis.n g:Ground relays trip breakers and limit how long a fault lasts and Neutral grounding resistors limit how large the fault current is”. There are many neutral grounding options available for both Low and Medium voltage power systems. The neutral points of transformers, generators and rotating machinery to the earth ground network provides a reference point of zero volts. This protective measure offers many advantages over an ungrounded system, like, 1. Reduced magnitude of transient over voltages 2. Simplified ground fault location 3. Improved system and equipment fault protection 4.
    [Show full text]