GENERAL PLUMBING PLUMBING ABBREVIATIONS GENERAL PLUMBING NOTES PLUMBING SYMBOLS LEGEND

SPECIFICATIONS AD AREA DRAIN 1. ALL PLUMBING WORK SHALL CONFORM TO MICHIGAN PLUMBING PLUMBING ASR AUTOMATIC SPRINKLER RISER PLUMBING CODE, LATEST APPLICABLE EDITION. ELEC. BFS BELOW SLAB ELEMENT 15050 - BASIC MECHANICAL MATERIALS AND METHODS BWV BACK 2. INSTALL ISOLATION BALL VALVES @ ALL FIXTURE CW COLD WATER GAS COCK 3/4" HW & CW CB CATCH BASIN LINES. CW COLD WATER BELOW FINISH SLAB CHECK VALVE T&P RELIEF CODES AND ORDINANCES CI VALVE COMPLY WITH MICHIGAN PLUMBING CODE CO CLEAN OUT 3. SITE CONTRACTOR TO RUN UTILITIES TO 5'-0" FROM HW HOT WATER GLOBE VALVE CV CONTROL VALVE LINE LP PROPANE BALL VALVE SHUT OFF VALVE DIA DIAMETER (TYPICAL) PIPING SPECIALTIES DN DOWN 4. ALL ELEVATIONS SHOWN ARE INVERTS OF PIPING. THE SAN SANITARY WASTE BELOW FINISH SLAB RELIEF VALVE ESCUTCHEONS: CHROME PLATED, MANUFACTURED , , AND DWH DOMESTIC WATER HEATER SLEEVES SHALL BE COORDINATED WITH THESE ELEVATIONS. V VENT PIPING FLOOR PLATES. DEEP PATTERN TYPE WHERE REQUIRED TO CONCEAL E.T.C. ELECTRICAL TRADES CONTRACTOR & DRAIN END VALVE PROTRUDING FITTINGS AND SLEEVES. INSTALL ON ALL PIPING EXPOSED EWC ELECTRIC WATER COOLER EXTEND TO 5. ALL SIZES SHOWN ARE SERVICE SIZE. SIZE TO VIEW IN FINISH SPACES AND UNDER . DIELECTRIC FITTINGS: EXIST EXISTING DRAIN PAN FD FLOOR DRAIN SLEEVES FOR 1" CLEAR SPACE BETWEEN PIPE AND INSTALL DIELECTRIC FITTINGS WHERE JOINING PIPING OF DISSIMILAR FF FINISH FLOOR SLEEVE FOR INSTALLATION OF MECHANICAL SEAL. PLUMBING EQUIPMENT MISCELLANEOUS NOTES METALS. FT FEET 6. CONTRACTOR TO VERIFY LOCATIONS OF EXISTING FLOW DIRECTION DWH-1 GAL GALLON POINT OF CONNECTION BETWEEN NEW AND PIPE INSULATION GD GARBAGE DISPOSAL UNDERGROUND UTILITIES BEFORE BEGINNING WORK. EXISTING GPH GALLONS PER HOUR PIPING DROP DIELECTRIC UNION DOMESTIC COLD WATER: MINIMUM OF 1/2" CLOSED CELL FOAM OR (TYP) GPM GALLONS PER MINUTE 7. ALL FLOOR DRAINS TO BE EQUIPPED WITH SEALS PIPING RISE X INDICATES PLAN NOTE HOSE END MINERAL FIBER WITH ASJ JACKET WITH SEALED JOINTS TO PREVENT HB HOSE BIB UNLESS OTHERWISE NOTED. DRAIN VALVE FLOOR CLEANOUT CONDENSATION. DOMESTIC HOT WATER: INSULATE SAME AS COLD HD HEAD (FT) DETAIL BUBBLE DRAIN PAN 8. 1% SLOPE FOR ALL SANITARY & RAIN CONDUCTOR WATER. HP HORSE POWER INLINE PIPING DROP FLOOR ID INSIDE DIAMETER PIPING. XX DETAIL NUMBER I.E. INVERT ELEVATION INLINE PIPING RISE WATER DISTRIBUTION PIPING XXXX PAGE LOCATION INDICATES LAV LAVATORY 9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR 3/4" DRAIN PIPE TO MATERIAL: HARD , ASTM B88, TYPE L WATER TUBE, DRAWN MAX MAXIMUM MAINTAINING THE INTEGRITY OF ALL EQUIPMENT AND INLINE CLEANOUT MOP TEMPER WITH COPPER JOINT PRESSURE FITTINGS. JOINING MATERIALS IN A "NEW" CONDITION DURING XX DIRECTION OF DETAIL SECTION MH MAN HOLE PLUMBING TRAP XXXX MATERIAL: SOLDER, ASTM B32, Sn95, Sn94, OR E, FREE. MIN MINIMUM CONSTRUCTION. UNION CLEANING & DISINFECTING: PURGE AND DISINFECT PORTABLE WATER MS MOP SINK 10. ALL WORK SHALL BE PERFORMED BY LICENSED SYSTEMS AS PRESCRIBED BY AUTHORITIES HAVING JURISDICTION. FOR M.T.C. MECHANICAL TRADES CONTRACTOR FLOOR DRAIN & FLOOR SINK NTS NOT TO SCALE CONTRACTORS AND SUBCONTRACTORS AS REQUIRED ELECTRICWATER HEATER DETAIL UNDERGROUND PIPING, USE TYPE K SOFT COPPER TUBE WITH NO JOINTS. 1 P PUMP BY LAW. BACK FLOW PREVENTER SCALE: NTS PD PRESSURE DROP WALL HYDRANT & HOSE BIBB PIPE HANGERS PVC POLY-VINYL-CHLORIDE 11. DESIGN AND CONSTRUCTION SHALL BE IN ACCORDANCE ADJUSTABLE CLEVIS HANGERS, NOT-METALLIC COATING FOR RC RAIN CONDUCTOR WITH THE CODES AND REGULATIONS ENFORCED BY PIPE BREAK LOCAL BUILDING OFFICIALS. ELECTROLYTIC PROTECTION WHER ATTACHMENTS ARE IN DIRECT RD DRAIN REQ'D REQUIRED M WATER METER CONTACT WITH COPPER. COPPER U-STRAP HANGERS FOR UNINSULATED 12. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF SAN SANITARY P PRESSURE GAUGE PIPE. COMPLY WITH MSS STANDARD PRACTICE #SP-69 SHWR TERMINATION OF PIPES AND SUGGESTED ROUTES. IT IS SK SINK NOT INTENTION OF DRAWINGS TO INDICATE ALL PS PRESSURE SWITCH AND VENT PIPING SP STAND PIPE NECESSARY OFFSETS. INSTALL WORK IN MANNER TO CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, MAY EXTEND AS A WASTE ABOVE GROUND WASTE AND VENT: HUBLESS CAST, SOIL PIPE, C1SP1 301 SQ. FT. SQUARE FEET SS SERVICE SINK PRESERVE HEADROOM AND KEEP OPENINGS AND OR A VENT LINE. WITH HUBLESS CAST-IRON COUPLINGS, C1SP1 310 WITH SS CORRUGATED ST STORM PASSAGEWAYS CLEAR. DO NOT SCALE FROM SHIELD, SS BANDS, AND RUBBER SLEEVE. BELOW GROUND AND DRAWINGS. UR 1 CONCEALED WASTE & VENT: PVC PIPE, ASTM D2665, SCHEDULE 40 VS VENT STACK WITH DRAINAGE PATTERN SOCKET FITTINGS. VTR VENT THRU ROOF 13. CONTRACTOR SHALL PROVIDE AND INSTALL TRAP WC WATER WRAPS ON ALL ACCESSIBLE PLUMBING FIXTURES. WALL WH WALL HYDRANT CHROME WALLCOVER AND SCREW. PLUGGED TEE WITH CLEANOUT. HANGERS FOR CAST IRON PIPE: X-CW EXIST. CW PIPING 14. CONTRACTOR SHALL PROVIDE AND INSTALL ASSE. 1070 ITEM MIXING VALVES ON ALL ACCESSIBLE PLUMBING 1 1/2" & 2" PIPE. 60 INCH MAX SPACING 3/8 INCH EXISTING FIXTURES ROD 3" PIPE 60 INCH MAX SPACING 1/2 INCH 9" ROD FLOOR LINE 4" & 5" PIPE 60 INCH MAX SPACING 5/8 INCH CLEANOUT PLUG W/ COUNTER SUNK HEAD. ROD FINISH GRADE. USE CAST IRON SANITARY PIPING WHERE EXPOSED ON 1ST FLOOR. CAST-IRON PIPE. PRESSURE SWITCH TO PRESSURE PT-1 GAS PIPING CONTROL WELL PUMP GAUGE 6" 16" SQUARE CONC. PAD TROWEL CHECK VALVE COMPLY WITH NFPA 70 AND IPC. SHUT OFF VALVE SMOOTH AND EDGE. PS P STEEL PIPE; ASTM A53, TYPE E OR S, GRADE B, SCH40, BLACK. (TYPICAL) MALLEABLE-IRON THREADED FITTINGS, ASME B16.3, CLASS 150, STANDARD HOSE END 1 1/2" TYP L COPPER 1/8" C.I. BEND. PATTERN. UNIONS: ASME B16.39, CLASS 150, MALLEABLE IRON WITH BRASS C.I. WASTE LINE. DRAIN VALVE ADAPTOR LENGTH TO SUIT. TO IRON STEAT, GROUND JOINT, AND THREADED ENDS. C.I. WASTE LINE. LENGTH TO SUIT. GAS STOPS FLOOR PRESSURE RELIEF VALVE DIELECTRIC 1 1/2" CW FROM WELL PUMP BODY WITH AGA STAMPS, PLUG TYPE WITH BRONZE PLUG AND PIPED TODWH-1 DRAIN PAN UNION WASTE LINE SQUARE HEAD, 2 PSIG MIN PRESSURE RATING. (TYPICAL)

1 1/2" CW SANITARY LINE VALVES 1/8" BEND IF CLEANOUT OCCURS BALL VALVES: 2 PIECE ALLOY, BRONZE BODY WITH FULL PORT, CHORME * WELL PUMP PROVIDER SHALL VERIFY AT END OF LINE. PLATED BALL, TFE STEATS, 600 PSIG MIN CWP RATING, LEVEL HANDLE PRESSURE TANK SIZE WITH EXTENDED STEM FOR INSULATION. 1/8"BEND IF CLEANOUT OCCURS AT END OF LINE. CLEAN-OUT DETAILS PRESURE TANK PIPING DETAIL 3 2 SCALE: NTS SCALE: NTS

M A T R I X

1 ‹&RS\ULJKW2016 Hobbs+Black Associates, Inc. ALL RIGHTS RESERVED

NEW DATA RACK

EXISTING DATA RACK EXISTING PNL "DP-N" 9‘$ RP1-38,40,42

EXISTING PNL "MSB-N" 9‘$

ELECTRICAL KEY NOTES

(1) 2" CND RACEWAY FOR DATA IN NEW BUILDING. CONTRACTOR TO REMOVE AND REPLACE CEILING TILES AS NEEDED. CONTRACTOR TO MATCH EXISTING CEILING TILE.

ELECTRICAL RACEWAY AND WIRE FOR NEW PANEL "RP1". CONTRACTOR TO REMOVE AND REPLACE CEILING TILES ASCONTRACTOR TO MATCH EXISTING CEILING TILE.

(1) 2" CND UNDERGROUND RACEWAY FOR DATA IN NEW BUILDING. FIBER FROM EXISTING DATA RACK TO NEW DATA RACK WILL BE OWNER PROVIDED.

UNDERGROUND ELECTRICAL RACEWAY AND WIRE N FOR NEW PANEL "RP1".

CONTRACTOR SHALL INSTALL 48 PORT MIDDLE ATLANTIC PATCH PANEL OR EQUAL. CONTRACTOR SHALL INSTALL MIDDLE ATLANTIC WALL MOUNTED HALF RACK OR EQUAL. CONTRACTOR SHALL INSTALL MIDDLE ATLANTIC POWER SUPPLY OR EQUAL.

CONTRACTOR SHALL PROVIDE HUBBELL QUAZITE FIBERGLASS HAND HOLE OR EQUAL.