63677 Passivent Aircool Vent WEB 12pp_Passivent Aircool Ventilators 16/03/2018 06:45 Page 2

CI/SfB (57.7) Xy Uniclass Ss_65_40_33_56 March 2018

U-VALUE IMPROVED BY 22%

AIRCOOL௡ VENTILATORS

HYBRID PLUS2 NEW AIRCOOL

...... 63677 Passivent Aircool Vent WEB 12pp_Passivent Aircool Ventilators 16/03/2018 06:46 Page 3

......

AIRCOOL᭨ VENTILATORS ......

Passivent Aircool is a range of controllable insulated ventilators primarily for BENEFITS installation in external façades in commercial and similar buildings. ● Improved insulated internal dampers provide a superior U-value as low as The electrically-actuated dampers provide 0.86W/m2K when closed, to minimise controlled air intake and extract in natural heat loss. Contents ventilation systems, and may also be used ● Primary construction materials are Aircool ventilators 2, 3, 4, 5 for air intake or extract in mechanical aluminium and ABS, which are 100% ventilation systems. They are particularly NEW Hybrid Plus2 Aircool® 6, 7 recyclable. suitable for night cooling strategies, where Electrically-actuated low-voltage Thermal Aircool 8 daytime heat build-up is dissipated from the ● dampers provide optimum safety and structure during the night, producing lower Acoustic Aircool 9 flexibility, with virtually silent internal air temperatures with a reduced modulating operation. Other applications 10, 11 need for daytime cooling or . ● Designed to be installed in masonry Further information 12 Natural ventilation methods can save energy, reduce greenhouse gas emissions, and walls, curtain walling, window frames reduce or eliminate the capital and running or profiled sheet cladding. costs of ventilation or air conditioning plant. ● Excellent airtightness performance when closed. ● Excellent weather protection and security are provided by the external weather louvre, even when the internal insulated louvre is open. ● Thermally broken frame, and insulated and orientated dampers minimise the risk of nuisance condensation and draughts. ● Thermal, acoustic and hybrid air mixing variants are available to attenuate or treat the incoming air in various ways as required by the user (see pages 6, 8 and 9). ● Discreet and functional yet aesthetically pleasing, with internal Quality assurance protection cover grilles supplied as The systems and processes by which the standard. product are manufactured have been ● The internal cover grille protects appraised under BS EN ISO 9001 which against impact damage, for covers design, development, manufacture, applications such as gymnasiums or and installation (if by approved installers), sports halls. giving an independently audited and maintained assurance that the products will ● Integrates with the Hybrid Plus2 meet their intended purpose. Aircool for single sided strategies. ● Can be supplied in modular form to Sustainability assurance provide greater flexibility in use All Passivent manufacturing is accredited to (see page 10). ISO 14001, the international standard for environmental management systems. Passivent are committed to minimising our impact on the environment using recycled and recyclable materials where possible.

2 ...... 63677 Passivent Aircool Vent WEB 12pp_Passivent Aircool Ventilators 16/03/2018 06:46 Page 4

......

Internal cover grille

......

DESCRIPTION Composition, manufacture Frame and external weather louvres are extruded aluminium, with ABS thermal break. Internal motorised dampers are fabricated from a double skin of aluminium with ABS thermal break and blade compression seals; supplied as a complete assembly including the actuator. External weather louvre Removable aluminium actuator cover for ease of maintenance. Insect screen is 4mm black Controllable polypropylene. Internal cover motorised grille is fabricated from extruded aluminium. Sizes Aircool window ventilator for window/curtain walling viewed from outside Made to order in the size ranges shown below.

Aircool wall ventilators: Wall sleeve supplied to Heights 255 up to 1490mm; link internal and external lengths 400 up to 2300mm. elements for maximum airtightness, security and Wall thickness from 195mm External weather louvre simpler installation upwards; specify when ordering. Aircool window/curtain wall ventilators: Heights 270 up to 1505mm; lengths 400 up to 2300mm; to suit glazing thickness from 24mm. Depth front to back (including cover grille) 183mm plus glazing thickness. Please enquire for specific size availability. Appearance External louvres and frame are polyester powder coated to order. Internal cover grilles are supplied in white RAL 9016 as standard but can be polyester powder coated to Controllable other colours to specific order. Internal cover grille Internal motorised dampers are motorised damper mill finish aluminium.

Aircool wall ventilator for masonry wall viewed from inside

...... 3 63677 Passivent Aircool Vent WEB 12pp_Passivent Aircool Ventilators 16/03/2018 06:47 Page 5

...... AIRCOOL VENTILATORS

PERFORMANCE ......

Ventilator performance Complete Aircool units in masonry walls Passivent can advise on the number and and windows/curtain walling size of ventilators needed according to air flow volume required (see Services, Aircool wall ventilator in masonry wall back cover). New and improved performance The average calculated U-VALUE IMPROVED BY U-value of the ventilators for the whole Aircool % range has been improved 22 to 0.86W/m2K in wall applications, one of the best in its class.

Specification clause Fire performance Insect screen Standard Aircool Materials used for internal frame and louvre ventilators for Fixed external masonry walls/ dampers when closed achieve a Class 1 weather louvres windows/curtain walls* rating when tested to BS 476: Part 7. having extruded Controllable motorised aluminium frame with Weather performance insulated internal dampers ABS thermal break, The external louvres provide 98.6% (shown closed) extruded aluminium external weather louvres, (Class B) rain rejection when Internal protective 4mm insect screen, and independently tested at BSRIA to cover grille aluminium internal cover BS EN 13030. When tested to grille. Insulated internal Wall sleeve supplied to motorised controllable BS EN 1027 the closed ventilators are link internal and external dampers fabricated from watertight at over 1000Pa pressure. elements for maximum double skin of aluminium airtightness, security and with ABS thermal break Air leakage performance easier installation and blade compression When tested the air leakage rate of the seals. U-value 0.86W/m²K 3 when closed. 24V closed ventilators is 0.57 m /hour/m at modulating actuator for 50Pa pressure. The linear metre length Aircool window ventilator in curtain walling internal louvres is defined as the perimeter of the unit controlled by eC/ic8000* wall-mounted switch-gear. plus the total length of the louvre-to- Ventilators designed and louvre contact. This equates to an Thermal break manufactured under approximate value in terms of face area BS EN ISO 9001, and 3 2 supplied by of 9.7m /hour/m at 50Pa pressure Passivent, North Frith (depending on unit size). Oasts, Ashes Lane, Hadlow, Kent TN11 9QU Controls and sensors Tel: 01732 850770, Ventilation airflow is continuously Fax: 01732 850949, Fixed external Email: variable by means of 24V modulating weather louvres [email protected] actuators. Ventilators can be controlled (and installed by an by Passivent’s range of thermostatic Insect screen approved installer). controls or programmable controllers, Controllable motorised *Delete as applicable. or linked to a building energy insulated internal dampers (shown open) management system. Passivent also offer a range of control sensors for Internal protective cover grille temperature, CO2 and wind for exposed (alternative fixing shown) locations. Modular applications Aircool ventilators can also be supplied in modular form, see page 10. Glazing

4 ...... 63677 Passivent Aircool Vent WEB 12pp_Passivent Aircool Ventilators 16/03/2018 06:47 Page 6

......

......

...... 5 63677 Passivent Aircool Vent WEB 12pp_Passivent Aircool Ventilators 16/03/2018 06:48 Page 7

...... AIRCOOL VENTILATORS

HYBRID PLUS2 AIRCOOL VENTILATOR ......

The Hybrid Plus2 Aircool ventilator combines the features of the Aircool ventilator with an innovative air tempering and mixing unit utilising a single energy- efficient . It has been primarily designed to be used in a single-sided ventilation strategy and to weather louvre meet the requirements of the Facilities Output Specification for Priority Schools Specification clause Programme Phase 2, the forthcoming Hybrid Plus2 Aircool, incorporating Aircool Building Bulletin 101, ‘Guidelines on ventilator with a mixing ventilation, and indoor chamber. Aircool for air quality in schools’ and Building masonry walls/windows/ curtain walls* having Bulletin 93, ‘Acoustic extruded aluminium design of schools: frame, extruded performance aluminium external weather louvres, 4mm standards’. black polypropylene insect screen. Insulated motorised controllable dampers fabricated from double skin of aluminium with ABS thermal break and blade compression seals. Mixing chamber finished to RAL 9016 wall sleeve white, incorporating variable speed fan, controllable mixing dampers.

Ventilator U-value The system has been developed to 0.86W/m²K when closed. provide a simple cost-effective solution for 24V modulating actuator specifiers and main contractors. With a focus control for dampers, on and thermal comfort, controlled by Passivent Hybrid Plus2 Aircool mixing unit iC8000 intelligent the Hybrid Plus2 Aircool is the ideal product controller. Fan flow rate to incorporate into schools and other of up to 145 l/s. educational buildings. Ventilators designed and manufactured under Air quality and thermal comfort BS EN ISO 9001, and Heating and cooling are important in supplied by Passivent, Performance North Frith Oasts, maintaining a comfortable indoor Equivalent free area of each unit: 0.054m2. Ashes Lane, Hadlow, environment, together with the provision Max. flow rate when inlet & outlet resistances are equal and fan Kent TN11 9QU. of good air quality and the removal of Tel: 01732 850770, is in operation: 145 l/s. email: pollutants, especially important in Compliance: Building Bulletins 93 & 101. [email protected]. maintaining CO levels to below 1,500ppm. 2 Appearance *Delete as applicable. The Hybrid Plus2 Aircool system can provide External louvres and frame are polyester powder coated to order. ventilation up to 145 l/s via the fan operation Internal cover grilles are supplied in white RAL 9016 as standard offering an energy-efficient means of but can be polyester powder coated to other colours to specific maintaining thermal comfort in a ‘free order. running building’. The mixing of fresh air Dimensions with internal room air is an integral part of Internal tempering and mixing unit: the design of the unit which reduces the risk 967mm(w) x 330mm(h) x 1253mm(d). of cold draughts during cooler periods. Aircool size would be supplied to suit the building The system is controlled by using a Passivent requirements: typically 842mm(w) x 320mm(h). iC8000 intelligent controller which provides Weight: approximately 30kg. fully automatic control.

6 ...... 63677 Passivent Aircool Vent WEB 12pp_Passivent Aircool Ventilators 16/03/2018 06:49 Page 8

......

Adaptable modes The unit can operate three modes of ventilation dependant on the internal and external environment of the room being ventilated...... Mixing mode 1 In winter, colder spring and autumn periods the Hybrid Plus2 Aircool tempers the incoming air with warmer internal air before it enters the space, thereby minimising the risk of cold draughts for the occupants. By mixing and utilising any excess of heat gains within the space, there is no need to Exceptional design use additional energy to warm the fresh air. Slim and sleek Warm internal air enters the unit at ceiling The unit is one of the slimmest in its level and is also discharged across the ceiling class due to its unique internal design. once mixed to ensure thermal comfort levels Its aesthetic, contemporary look and are the highest possible. flexible design means that it can be ...... mounted exposed or, if preferred, within a bulkhead. Cooling mode Versatile 2 In peak summer conditions, the It can be fitted to external facades, energy-efficient, low power fan can be including all forms of wall construction, activated to promote air movement, keeping curtain walling and window profiles. the ventilation strategy operating and temperature under control. Quiet The ventilator utilises silent, When the building encounters high heat controllable insulated dampers from the gains, the fan can be activated to purge Aircool range. The system can be used the space more rapidly than a passive to meet the acoustic requirements of ventilation system. The fan speed will BB93. automatically adjust to suit the temperature and CO2 requirements within the space. Energy efficient Thanks to the energy-efficient fan and ...... the ultra-energy-efficient passive mode, Passive mode power consumption is kept to a 3 Due to the low airflow resistance of the minimum. system, the Hybrid Plus2 Aircool is able to Scalable operate in a passive mode without any need One unit can accommodate up to 16 for fan assistance. This mode offers single- occupants. The addition of a second unit sided ventilation to provide an equivalent can accommodate up to 32 per room. area of 0.054m2 and is highly cost-effective due to the lack of energy required to motorise the fan unit...... wall sleeve Hybrid Plus2 Aircool mixing unit

weather louvre

Sectional drawing of the unit within a wall strategy

...... 7 63677 Passivent Aircool Vent WEB 12pp_Passivent Aircool Ventilators 16/03/2018 06:49 Page 9

...... AIRCOOL VENTILATORS

THERMAL AIRCOOL ......

The Passivent Thermal Aircool has been specifically designed to supply buildings with warm, fresh air during cooler weather particularly when the Hybrid Plus2 Aircool is not suitable due to inadequate availability of “free heat” from the room itself or a requirement for higher airflows than can be provided when in passive mode. Internal cover grille The Thermal Aircool will also provide a Airflow heater coil fresh air inlet in warmer conditions, when air warming is not required thus provide Controllable motorised fresh air ventilation throughout the year and dampers (shown open) Specification clause Thermal Aircool louvre a secure night cooling strategy in warmer ventilators for masonry weather. walls/windows/curtain walls* having extruded The Thermal Aircool system incorporates a Channel option for aluminium frame with low resistance airflow heater coil, which has pipework ABS thermal break, extruded aluminium been specially designed for natural external weather louvres, ventilation systems and is connected into the 4mm insect screen, and main central of the building. aluminium internal cover grille. Includes heater An integral sensor clipped to the coil reports coil. Insulated internal the temperature of the incoming air so that motorised controllable the water flow and temperature can be dampers fabricated from double skin of aluminium regulated via third party heating controls. with ABS thermal break When combined with the Passivent range of and blade compression natural ventilation controllers, the seals. U-value 0.86W/m²K when closed. 24V motorised damper ensures the correct modulating actuator for level of ventilation is supplied. internal louvres Wall sleeve supplied to controlled by iC8000. The Thermal Aircool also incorporates all link internal and external Ventilators designed and the features and benefits of the standard elements for maximum manufactured under Aircool (see page 4). airtightness, security and BS EN ISO 9001, and easier installation supplied by Passivent, North Frith Sizes Oasts, Ashes Lane, Enquire for available sizes Hadlow, Kent TN11 9QU and minimum depth Tel: 01732 850770, Fax: 01732 850949, requirements. Email: [email protected] (and installed by an approved installer). *Delete as applicable

Airflow heater coil

Note: Pipework and connectors by others

8 ...... 63677 Passivent Aircool Vent WEB 12pp_Passivent Aircool Ventilators 16/03/2018 06:50 Page 10

...... AIRCOOL VENTILATORS

ACOUSTIC AIRCOOL ......

Specification clause The Acoustic Aircool range is available in Aircool acoustic wall ventilator Acoustic Aircool wall and window versions. The range has 797 x 315 x 390mm, with external ventilators for masonry weather louvre and single internal walls/windows/curtain been developed to meet increased acoustic chevrons, providing a walls* having extruded regulation requirements for sound weighted normalised sound level aluminium frame with reduction, and the increased noise difference Dn,e,w of 22dB ABS thermal break, (when open) extruded aluminium exposure resulting from the greater use of external weather louvres, brownfield sites. 4mm insect screen, and Controllable motorised aluminium internal cover Independent test data to BS EN 20140-10 dampers (shown open) grille. Units to have is available on request, with detailed single/double* acoustic chevrons to achieve a performance figures for each application. weighted normalised sound level difference of Depending on requirements, acoustic up to 22/26dB* Dn,e,w ventilators may have a single or double across the ventilator to row of internal acoustic chevrons, acoustic BS EN 20140-10. Insulated internal liners. For special high noise reduction motorised controllable requirements, Passivent can design and dampers fabricated from manufacture bespoke ventilators to double skin of aluminium with ABS thermal break maximise sound reduction and minimise and blade compression airflow resistance so as to achieve target seals. U-value air change rates. 0.86W/m²K when closed. 24V modulating actuator Passivent Aircool acoustic façade for internal louvres controlled by iC8000. ventilators can be complemented by Ventilators designed and Passivent Soundscoop᭨ and Soundscoop manufactured under iAT (intelligent airflow technology) BS EN ISO 9001, and supplied by acoustic ventilators for internal air Passivent, North Frith transfer. Oasts, Ashes Lane, Hadlow, Kent TN11 9QU This broader product range provides Tel: 01732 850770, designers with the opportunity to adopt Aircool acoustic Fax: 01732 850949, wall ventilator Email: complete natural ventilation solutions 797 x 315 x [email protected] where buildings have high external noise 570mm, with (and installed by an levels. external weather approved installer). louvre and double internal acoustic *Delete as applicable chevrons, providing a weighted normalised sound level difference Dn,e,w of 26dB (when open)

Controllable motorised dampers (shown closed)

...... 9 63677 Passivent Aircool Vent WEB 12pp_Passivent Aircool Ventilators 16/03/2018 06:50 Page 11

...... AIRCOOL VENTILATORS

OTHER APPLICATIONS ......

Modular applications Aircool ventilators and the various elements that make the total unit can also be supplied in modular form, with the external weather louvres (also with the patented double bank weather louvre system), internal insulated dampers and internal cover grilles as separate components, providing extra flexibility in ventilation design.

External weather louvre

Sidcot School, showing external weather louvres separated from internal controllable louvres and cover grille.

Controllable motorised insulated damper

Internal cover grille

10 ...... 63677 Passivent Aircool Vent WEB 12pp_Passivent Aircool Ventilators 16/03/2018 06:50 Page 12

......

......

Aircool external Passive stack ventilation weather louvres with This design using passive stack ventilation secondary weather was successfully adopted in a multi-storey baffles building to meet fire regulations and reduce risk of ‘cross talk’ (ie sound leakage between floors). Natural ventilation was achieved by passive induced cross ventilation before entering the stack. Fresh air was introduced at the windows and drawn across rooms, then through Aircool dampers, and extracted at high level through Aircool window Motorised ventilators located at the top of the light internal damper well/stack. with fireproof sleeve and

Passive ventilation stack

Motorised internal damper with fireproof sleeve Aircool insulated dampers were used in and fire damper combination with fire dampers to maintain and acoustic the integrity of fire protection between chevrons floors. Acoustic chevrons were fitted behind the Aircool dampers to the louvres to provide acoustic attenuation between floors. Aircool dampers positioned in the rooms gave the users controllability with individual room air volume control, and provided thermal insulation during unoccupied periods. In exposed locations Passivent patented secondary weather baffles were fitted behind the external weather louvres to provide a Class A weather rejection performance. Aircool extracts can be located in high level window frames, behind weather louvres, within a terminal arrangement or in purpose-designed parapet walls.

...... 11 63677 Passivent Aircool Vent WEB 12pp_Passivent Aircool Ventilators 16/03/2018 06:44 Page 1

...... AIRCOOL VENTILATORS

FURTHER INFORMATION ......

SERVICES OTHER PASSIVENT PRODUCTS Passivent has its own in-house research Passivent offers a range of other natural team dedicated to developing techniques and ventilation and daylighting products products for natural ventilation, and has including: been a leading partner in some of the most SoundScoop acoustic transfer ventilation important research projects in this field products. including NatVent™, a consortium of European organisations headed by BRE. Roof ventilation terminals incorporating Airstract᭨, Airscoop᭨ and combined We offer a comprehensive design and rooflights/ventilators. advisory service tailored to your specific project, covering both natural ventilation Ventilation control systems. design and product selection. Advanced iMEV intelligent mechanical extract software based on CIBSE AM10 is used to ventilation systems. calculate sizes of air inlets and outlets to achieve optimum performance. Names of approved installers can be provided on request.

......

PASSIVENT North Frith Oasts, Ashes Lane, Hadlow, Kent TN11 9QU Tel: 01732 850770 Fax: 01732 850949 Email: [email protected] Web: www.passivent.com

Passivent maintains a policy of continuous development and reserves the right to amend product specifications without notice.

A division of Building Product Design Ltd. Company Registration No; 3944123

...... 910058 March 2018

ISO 9001 OHSAS 18001