ANNEX - PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (NORMATIVE)

BACnet Protocol Implementation Conformance Statement

Date: 09/16/2020 Vendor Name: SDATAWAY SA Product Name: EASY3 Product Model Number: EASY3-9--B- Application Software Version: 0.99 Firmware Revision: 1.11 BACnet Protocol Revision: 16

Product Description: The EasyBus3® system is designed remotely control slave peripherals via a proprietary powerline communication system (Powerline carrier current). The slave devices are specially designed to meet the needs of ventilation systems for building automation, such as fire dampers, smoke dampers, VAVs and smoke detectors.

BACnet Standardized Device Profile (Annex L):

 BACnet Operator Workstation (B-OWS)  BACnet Advanced Operator Workstation (B-AWS)  BACnet Operator Display (B-OD)  BACnet Building Controller (B-BC)  BACnet Advanced Application Controller (B-AAC) ◼ BACnet Application Specific Controller (B-ASC)  BACnet Smart Sensor (B-SS)  BACnet Smart Actuator (B-SA)

List all BACnet Interoperability Building Blocks Supported (Annex K): DS-RP-B DS-RPM-B DS-WP-B DS-WPM-B DS-COV-B DM-DDB-B DM-DOB-B DM-DCC-B DM-RD-B

Segmentation Capability:

◼ Able to transmit segmented messages Window Size 3 ◼ Able to receive segmented messages Window Size 3

ANNEX A - PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (NORMATIVE)

Standard Object Types Supported:

Optional Conditionally Object Dynamically Dynamically Writable Proprietary Properties Writable Type Creatable Deletable Properties Properties Supported Properties Device No None None None None Analog Present No No None None None Output Value Analog No No None None None None Input Binary No No None None None None Input Binary Present No No None None None Output Value Multi- state No No None None None None Input Multi- Present state No No None None None Value Output

BACnet Object List:

Present Object Object Present Value Object Name Units Value Type Instance Range R/W Analog 1 WDG Type Countdown secs 0-65535 R Input Binary INACTIVE, 2 WDG Type Reset - R/W Output ACTIVE Binary INACTIVE, 3 WDG Type Control - R/W Output ACTIVE Multi-State MST1 Easy_Master Type Stop (1), Run 4 - R/W Output Control master (2), Fire (3) Stop (1), Run (2), Scan (3), Multi-State MST1 Easy_Master Type 5 - Fire (4), R Input Status master AllOpenSlave (5) Analog MST1 Easy_Master Type 6 - 0-128 R Input Quantity of slave Analog MST1 Easy_Master Type 7 - 0-128 R Input Err quantity of slave MST1 Easy_Master Type INACTIVE, Binary Input 8 - R Fire ACTIVE Analog MST1 Easy_Master Type 9 ms 0-65535 R Input EasyBus cycle time Analog MST1 Easy_Master Type 10 - 0 - 1999 R Input Firmware version Analog MST1 Easy_Master Type 11 - 0-65535 R Input Unique id1 ANNEX A - PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (NORMATIVE)

Analog MST1 Easy_Master Type 12 - 0-65535 R Input Unique id2 Analog MST1 Easy_Master Type 13 - 1-99 R Input Channel Easy2 Analog MST1 Easy_Master Type 14 - 1-255 R Input Channel Easy3 Err (1), Open Multi-State Mst 1 Slv 7 Mod Easy_B24 15 - (2), Close (3), R Input Type State Transition (4) Mst 1 Slv 7 Mod Easy_B24 INACTIVE, Binary Input 16 - R Type Smoke ACTIVE

Binary Mst 1 Slv 7 Mod INACTIVE, 17 - R/W Output Easy_B24 Type CMD ACTIVE Binary Mst Slv 7 Mod Easy_B24 INACTIVE, 18 - R/W Output Type ClearAlarm ACTIVE Analog Mst 1 Slv 120 Mod 19 x10 mV 0-1000 R Input Easy_V Type Flow_VAV1 Analog Mst 1 Slv 120 Mod 20 x10 mV 0-1000 R Input Easy_V Type Flow_VAV2 Analog Mst 1 Slv 120 Mod 21 x10 mV 0-1000 R/W Output Easy_V Type SP_VAV1 Analog Mst 1 Slv 120 Mod 22 x10 mV 0-1000 R/W Output Easy_V Type SP_VAV2 Analog Mst 1 Slv 120 Mod 23 R Input Easy_V Type Probe_1 Analog Mst 1 Slv 120 Mod 24 R Input Easy_V Type Probe_2 Binary Mst 1 Slv 120 Mod INACTIVE, 25 R Input Easy_V Type Comm_Err ACTIVE

Data Link Layer Options:

◼ BACnet IP, (Annex J)  BACnet IP, (Annex J), Foreign Device  ISO 8802-3, Ethernet (Clause 7)  ATA 878.1, 2.5 Mb. ARCNET (Clause 8)  ATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s) ______◼ MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400,76800  MS/TP slave (Clause 9), baud rate(s):  Point-To-Point, EIA 232 (Clause 10), baud rate(s):  Point-To-Point, modem, (Clause 10), baud rate(s):  LonTalk, (Clause 11), medium: ______ BACnet/ZigBee (ANNEX )  Other:

ANNEX A - PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (NORMATIVE)

Device Address Binding:

Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.)  Yes ◼ No

Networking Options:

 Router, Clause 6 - List all routing configurations, .g., ARCNET-Ethernet, Ethernet-MS/TP, etc.  Annex H, BACnet Tunneling Router over IP  BACnet/IP Broadcast Management Device (BBMD) Does the BBMD support registrations by Foreign Devices?  Yes  No Does the BBMD support network address translation?  Yes  No

Network Security Options:

◼ Non-secure Device - is capable of operating without BACnet Network Security  Secure Device - is capable of using BACnet Network Security (NS-SD BIBB)  Multiple Application-Specific Keys:  Supports encryption (NS-ED BIBB)  Key Server (NS-KS BIBB)

Character Sets Supported:

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

◼ ISO 10646 (UTF-8)  IBM/Microsoft DBCS  ISO 8859-1  ISO 10646 (UCS-2)  ISO 10646 (UCS-4)  JIS X 0208

If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports: N/A