No. 2047

G. T. TAMURA Member ASHRAE A. G. WlLSON Member ASHRAE Pressures Caused by Action and Mechanical Ventilation Air pressure differences and resulting air leakage Little is known about air leakage in large patterns in affect building performance1 multi-story buildings. In particular, information in a number of ways. The pattern of pressure dif - is lacking on the resistance to air flow within such ferences depends upon the forces in operation. Air buildings. Direct measurement in the field is usu- flow due to chimney action, resulting from differ- ally not feasible, because it is not practicable to ences in the density of inside and outside air, is isolate the flow paths and measure the air quanti- particularly important in multi-story buildings and ties. The net effects can be measured, however, colder climates. When not affected by other forces, in terms of the distribution of pressure differen- air flows in at low levels and out at high levels. tials under known conditions. It would be helpful The total pressure difference causing flow is the in interpreting the results of such pressure mea- difference in weight of the inside and outside air surements to know how these pressures and the for the height of the building involved. resulting air flow are affected by the distribution The distribution of this total pressure difference, of resistances in the exterior enclosure and inter- or theoretical draft, depends upon the relative re- nal separations. Such information would also be sistance to flow at the exterior enclosure and in- helpful in establishing the requirements for control ternal separations. With no internal separations, of air leakage caused by chimney action. the full theoretical draft acts across the enclo- This paper gives the results of an analytical sure; with increasing pressure losses across in- of the distribution of pressure differences ternal separations, the pressure differences a- caused by chimney action in buildings. Results cross the enclosure are correspondingly reduced. are also given of the way in which these pressure Pressure distributions and flow patterns in differences are affected by various arrangements buildings can be influenced by the design and op- of excess supply and exhaust air. eration of ventilation and exhaust systems. A net supply of air is sometimes provided to control air DESCRIPTION OF THE MATHEMATICAL MODEL infiltration at entrances caused by chimney action in multi-story buildings. The effect of net supply The components in the mathematical model for the or exhaust also depends upon the distribution of study are illustrated in Fig. 1 for a three-story leakage openings within the buildings. building. The major separations are the exterior , walls of vertical service shafts, G.T. Tamura is a research officer and A.G. Wilson is head, shafts and stairwells, and the construction. Building Services Section, Division of Building Research, To simplify the model, separations formed by par- National Research Council, Ottawa, Canada. This paper was titions for various on each floor were omit- prepared for presentation at the ASHRAE 74th Annual Meet- ted. These partitions are generally interconnected ing, Wli~eapoLis,Minn., June 26 - 28, 1967. It is a contri- bution from the Division of Building Research, National Re- in office buildings where partitions are movable search Council, Canada, and is published with the approval and there are leaky suspended . Mechan- of the Director of the Division. ical air supply and exhaust ducts are important in terms of their effect on the mass balance at each floor, and if not operating may represent intercon- Inside pressures at various levels are inter-re- nections between in addition to those pro- lated by the weight of the of inside air be- vided by t5e internal separations. Provision was tween levels and the pressure drop across the in- made in the model for net air supply or exhaust at tervening floors. The problem entails determining each floor to determine its effect on pressure dif- the inside pressures in such a way that a mass ferences across the separations. flow balance is obtained for each floor and for the Air leakages in the exterior walls occur vertical shaft. The number of similltaneous equa- through interstices formed by and walls, tions equal the number of floor6 plus one. As the cracks of openable windows, joints of curtainwalls, equations for an exponent of 1/2 are nonlinear, it- and in some instances through the construc- erative calculations are required to solve for the tion. Air leakages through the wall of the vertical unknown inside pressures. shaft occur through cracks formed by elevator and A computer program was formulated to solve stairwell and, in service shafts, through the all unknown absolute pressures inside the building space between pipes and ducts and the wall. Air and the resultant pressure differences across all leakages through the floor construction occur major separations. The solutions were obtained through cracks formed by the various service pipes with the aid of a digital comphter. The computer and interstices formed by the exterior wall and the program was designed to permit variation in the floor construction. In the model building, these number of floors and in orifice areas from floor leakage areas in major separations were lumped to floor. The amount of pressurization due to the and represented by orifice areas. The following operation of the mechanical ventilation system was equation* was used to represent the mass flow defined in terms of the pressure difference across through an orifice. the ventilation orifice at each floor, A Pv. This could be varied from floor to floor.

RESULTS where Effect of Interior Openings and Height W = mass flow C = proportionality constant A typical set of results is given in Fig. 2, for a A = orifice area ten-story building with a uniform distribution of P = air density openings in the vertical direction. For this distri- AP = pressure difference across or- bution the neutral zone level, where inside and out- ifice side pressures are equal, is located at mid-height. With no internal resistance to flow (A f/Aw and A / n = flow exponent S For most calculations a flow exponent of 1/2 ,Fig. l Mathematical model building (turbulent flow) was assumed; in some cases it was taken as l (laminar flow). Because of the combina- Air supply and Vertical tion of turbulent and laminar flows the value for exhaust duct shaft leakage paths, as they occur in buildings, will vary \ / between 1/2 and 1; for example, that for cracks in openable windows and doors is generally about 2/5.2 Because the distribution of the available pressure difference due to chimney effect depends Only on the relative resistances to air flow of the various separations, the orifice areas in the ex- terior wall, %, were used as a reference (i.e., taken as unity); and orifice areas in the floor con- struction and in the wall of the vertical shaft, Af uld As, were taken as multiples of the exterior Wall orifice area for each story. For simplifica- tim, the area of the orifice representing the me- chanical air supply or exhaust opening at each floor was the same as that representing the out- Bide wall. The floor height of the model building assumed to be 12 ft. A, = Exterior wall orifice area The value of the outside absolute pressures PO1 of Fig. l was taken as normal atmospheric Af = Floor orifice area P'essure. With no wind, outside air pressures at As = Vertical shaft orifice area ather levels depend only on the specific weight of the air, which is a fmtion of outside temperature. AV = Ventilation duct orifice area =zzzzx- P Absolute pressure levels is less than the theoretical draft by the of the pressure drops between intervening flmm With openings in the shaft only the difference h: tween the pressure drops across the wall of shaft at any two levels is equal to the preseura drop across intervening floors. The ratio of act- to theoretical draft is greater with openings th~ shaft only than with openings in the floor only. The pattern of air flow is evident from pattern and magnitude of the pressure differenceg, Air flows into the building below the neutralzme and flows out above it. Similarly, air flows from the lower floors into the vertical shaft; and frona the shaft into the upper floors. There is alsoan upward fl~wthrough openings in the floors. The results illustrated in Fig. 2 are for outside temperature of 0 F. For practical put- poses the ratio of actual to theoretical draft, how- ever, is independent of temperature when the pres- sures are due to chimney effect alone; any varb- tions in the ratio occur because of the dependence of the flow relation on temperature. The effect of variations in leakage areas and number of floors on the ratio of actual to theoret- ical draft is shown in Fig. 3. Calculations were made for an outside temperature of 0 F and an in- side temperature of 75 F. With interior leakage openings only in the floors, all internal flow paths are in series; the actual draft decreases rapidly as the number of stories increase and is asymp- totic to zero. The draft increases as the ratio of Af/Aw increases, that is, as the resistance to flow Fig. 2 Pressure differences due to chimney effect within the building decreases. With interior leak- age openings only in the verticalshaft and no pres- -4 = ") there is no pressure drop across the W sure loss within the shaft, the resistance of the floors; the sum of the pressure differences across flow path from bottom to top of the building is in- :he exterior wall at the bottom and top of the build- dependent of height, so that the ratio of actual to ;?g is equal to the total theoretical draft for the theoretical draft is constant for any value of As/ building. With openings in the shaft only, there is regardless of the number of stories. In an an equal pressure drop across each floor; with Aw, ~peningsin the floor only, this pressure drop in- actual building some pressure loss within the ver- creases toward the neutral zone level because of tical shafts would occur so that some increase in =creasing flow rates in that direction through the the resistance of the flow path through the vertical 3oor openings. With resistance to flow imposed by shafts would occur with increasing height. For a :he interior separations, the sum of the pressure building with three floors, the resistance to flow Afferences across the exterior wall at any two through openings only in the shaft is the same as

1.2 4 LL a A, 1 for all cases 2 1.0 4 U- C g 0.8 0 Yr C ,0.6 C 2 4 2 0.4 U 4 g 0.2 -0 C 4 CL .::d. 3 Effect of building height 0 4 8 12 16 20 24 28 32 36 40 44 48 md separation openings BUILDING HEIGHT, FLOORS Exterior wall Vertical shaft The resistance to upward flow through the building will be increased if the vertical shafts are 10 not continuous. An example of this is given in Fig. 4 for the ten-story model in which there is com- plete separation of the vertical shaft at mid-height. -Vertical shaft I Thus, all air flowing from the lower half of the building to the upper must pass through the floor opening at mid-height, and there is an increase in 8 pressure drop across the floors and shaft in this region. The relative resistances to flow used for this and succeeding examples (Aw = 1, A = 2, Af =2) m S m 0 appear to be within the range anticipated in actual 6 buildings. 3 For the conditions of Fig. 4 the ratio .L of actual to theoretical draft across the top and r bottom of the building is reduced from 0.86 to 0.58. I 0- The total air leakage into the building is also re- W duced by approximately 34% for the conditions il- I lustrated. 4 With complete separation of the vertical shaft at mid-height, the building acts somewhat as two separate buildings, one above the other, with a neutral zone level associated with each. If there were complete separation of the two halves, in- 2 cluding elimination of the openings in the interven- ing floor, they would act independently and there would be maximum pressure differences across the intervening floor. In an actual building, how- ever, it would be difficult toseparate the upper and .2 PRESSURE DIFFERENCE, IN. OF WATER Fig. 5 Effect of opening main entrance doors Fig. 4 Effect of dividing vertical shaft in two equal compartments 10 that through similar openings only in the floor, so that the ratio of actual to theoretical draft is the same.

8 building height increases

V) P: 0 26 L

C I -cl W I 4

2

PRESSURE DIFFERENCE, IN. OF WATER lower halves of the various vertical shafts com- posed pressurization, " was defined in terms of tga pletely, and the effects on the various pressure pressure difference across the air supply or differences would be correspondingly less. haust openings. As these openings were assigaad The examples givenso far have been for model unit area the same as the openings in the extefiol, buildings with a uniform vertical distribution of wall, k,the imposed pressurization can be Fa- openings in the enclosure. In an actual building il~converted to an equivalent air flow through tge one levelmay have larger openings than the others; exterior. The effect of this imposed pressurb. for example, because of doors the area of the tion on both the pressure differences across h ground floor openings may be larger than those at exterior walls, referred to as resultant pressup, other levels. Fig. 5 shows the pressure distribu- ization, and on the pressure differences acrw tions for the ten-story model with Aw for the the interior separations, will depend on the dfs- ground floor of 1 and 8, and A; for the other tributiin of excess supply or exhaust from floor to floor; the effect will also depend on the floors constant at 1. sure distribution prior to pressurization. If there With increasing Aw at the ground floor, the is no initial pressure difference across the enclo- pressure difference across the entrance decreases; sure and the pressurization is imposed uniformly correspondingly, there is a significant increase in at all floors, the resultant pressure difference the pressure difference across the vertical shaft across the enclosure will be the same at all levek and floors at the lower levels. The effects of in- and equal to that imposed. creasing Aw at the ground floor diminish with Fig. 6 illustrates the effects of combine pressurization and chimney action, with equal ex- height; there is some lowering of the neutral zone cess air supply at all levels equivalent to an h- level and some increase in the pressure difference posed pressurization of 0.10 in. of water, which across the exterior walls and vertical shaft at the neutralizes the pressure difference across the top of the building. ground floor entrance. The resultant pressuriza- For the example illustrated by Fig, 5, the tion is somewhat greater than that imposed and in- over-all increase in air leakage resulting from an creases from bottom to top because a non-Linear increase in Aw at the ground floor level from 1 to flow relation is assumed. For a flow exponent of 8 is 35%; the increase in leakage into the 1st floor one, the resultant pressurization would equal that amounts to 194%. Infiltration through outside walls of the second and succeeding floors is decreased. It is sometimes proposed that ground floor en- Fig. 6 Effect of uniform imposed pressurization on trances to high buildings be opened to facilitate stack pressure differences traffic flow to shops. Fig. 5 indicates the effect of this on pressure patterns due to chimney action. As noted, there is a large increase in ground floor (prior to pressurization) infiltration and pressure differences across verti- cal shafts. The use of air curtain entrances is Vertical shaft sometimes suggested to control these pressure (with pressurization) differences and air leakage; it should be recog- nized that, for a given entrance infiltration, the air curtain entrance will operate with the same pressure difference across it as that at any other entrance. For example, to revert to the leakage condition represented by an entrance having Aw = 1, as in Fig. 5, the entrance must sustain a pres- sure difference of about 0.1 in. of water. (bl Bottom level 0.11 in. Curves in Fig. 5 are for an arbitrary ratio of As/Aw and Af/Aw of 2. With larger values of As andA the pressure drop across the entrance for a f given value of A at the entrance, would be greater. W At the same time the pressure loss within the buildingwould be less and there would be a greater pressure drop across the outer walls at the top of the building. The converse would occur with Exterior wall smaller values of A and Af. S

Effects of Pressurization The effects of an imbalance of supply and exhaust air were investigated with the 10-story model. -0.3 -0.2 -0.1 0 0.1 0.2 0.3 0.4 The imbalance on any floor, referred to as "im- PRESSURE DIFFERENCE, IN. GF WATER imposed. It will also be noted that the pressure Exterior wall Vertical shalt difference across the floors is less when the build- ing is pressurized uniformly. Because the flow relation is non-linear there is less upward flow through the building; for high values of imposed pressurization the ratio of actual to theoretical chimney draft approaches one. For linear flow conditions this ratio is constant. An equal excess of supply air on all floors, as illustrated in Fig. 6, can be effective in reducing the pressure difference across exterior walls at lower levels, but there is a penalty in increased pressure differences which cause exfiltration at higher levels. The total excess air supply, which mat be provided by outside air, is equivalent to 29a of the air infiltration with no pressurization for the conditions illustrated. Pressure differences across ground floor en- trances can be neutralized by providing an excess air supply only on that floor. In the 10-story model this requires an imposed pressurization on the ground floor of 1.2 in. of water (Fig. 7). The pressure dbtribution across the exterior wall, floors and verticalshaft is essentially the same as that illustrated in Fig. 5, in which pressure dif- ferences across the entrance were neutralized by increasing the area of the entrance opening, A to about 8. W' The excess air supply required in Fig. 7 is approximately equivalent to the air infiltration -0.2 -0.1 0 0.1 0.2 -0.10 0 0.1 through the enlarged entrance opening in Fig. 5. PRESSURE DIFFERENCE, IN. OF WATER B must be supplied by the introduction of outside air through the ventilation system; the amount re- Fig. 7 Effect of first floor pressurization to neu- quired is about equal to the total air infiltration tralize entrance pressure difference without pressurization. Infiltration on other floors below the neutral zone level is about 37%~of the original total infiltration. This infiltration, to- differences across both top and bottom of the en- gether with the excess supply air required to neu- closure are reduced. tralize the pressure difference across the entrance The second example in Fig. 8 is for the 10- story model with vertical shafts split at the mid- in Fig. 7, is substantially less than the total excess 8upply air required with uniform pressurization at height, as in Fig. 4. With the same excess supply all levels. Consequently, the increase in pressure and exhaust in lower and upper halves of the build- difference across upper levels of the building is ing, as in the example above, a much greater much less than that in Fig. 6. With a greater re- pressure difference occurs across the floor at eistance to flow within the building the increase in mid-height. The result is that pressure differ- pressure difference at upper levels would be still ences across the enclosure are essentially bal- kss; with a lower resistance there would be a anced at top and bottom of the building, while there peater effect at upper levels and a greater excess are substantial pressure differences causing exfil- supply required to neutralize the pressure dif- tration immediately below mid-height and infiltra- krence at the entrance. tion immediately above. The greater the increase To counteract pressure differences from in resistance to flow inside the building in relation amney action across exterior walls in the upper to that of the exterior, the greater will be the Qmrs requires an excess of exhaust air over sup- pressure difference across the floors and vertical ply. One approach, involving net supply below the shafts and the resultant pressurization for a given zone and net exhaust above, is illustrated excess of supply or exhaust air. hg. 8, where the imposed pressurization is 0.1 In theory it would be possible to neutralize the b. water for all floors - positive below the neu- pressure difference across outside walls due to zone and negative above it. The resultant chimney action over the full height of the building msurization is less than that when excess air by controlling excess supply or exhaust in each @WPlp at all levels is uniform (Fig. 6), but is story. This is illustrated in Fig. 9 for the 10- qual and of opposite sign at the top and bottom. story model. To maintain an average pressure &sure differences across the floors and verti- difference of zero across the walls of each story, 8bafts are greater than with no pressurization. the pressure difference across each floor separa- arrangement has the advantage that pressure tion must equal the theoretical draft from floor to floor. With uniform floor spacing the total theo- retical draft for the building is thus distributed uniformly between the floors. Similarly, with no pressure difference across openings in the exterior wall the total theoretical draft is divided between the top and bottom open- ings into the vertical shaft in proportion to the re- sistance of these openings. The pressure differ - ence across openings into the vertical shaft at any other floor is then the pressure difference across the ground floor opening less the sum of the pres- sure differences across intervening floors. The pressure difference pattern for the vertical shaft is independent of the resistance to flow of openings in the exterior wall and floors and can be readily established for any assumed distribution of open- ings in the shaft. The excess supply or exhaust air required on any floor to neutralize pressure dif- ferences across the exterior wall is independent of the leakage characteristics of the wall; it depends upon the distribution of openings in the floor and vertical shaft andcan be readily calculated for any assumed distribution once the pressure difference pattern is established. In Fig, 9, the excess supply and exhaust air required is again defined in terms of imposed pressurization, that is, the pressure difference across unit area to provide the necessary flow. Fig. 9 is based on a flow exponent of 1/2; excess -0.3 -U.2 -0.1 0 0.1 0.2 0.) s r supply and exhaust air requirements are thus in PRESSURE DIFFERENCE, IN. OF WATfl proportion to the square root of the imposed pres- Fig. 8 Effect of non-uniform imposed pmssm~s~t*~ surization. As an example, assume that leakage through the exterior wall is equivalent to one air change per hour at a pressure difference of 0.104 in. of water. This is the pressure difference due to chimney action across the ground floor walls in Fig. 9 prior to pressurization and is equivalent to Fig. 9 Imposed pressurization to neutralize a;lf*** the velocity head of a 15 mph wind. Taking Aw and wall pressure differences. Af equal to 2 and Aw equal to unity, the imposed pressurization required to neutralize chimney ac - tion on the ground noor is 1.07 in. of water as in Fig. 9. The excess supply air required on the ground floor then amounts to 1 X (1.07/0.104)$ = 3.35 air changes per hour. By a similar calcula- tion the excess supply required on the second floor is 1.9 air changes. For buildings with several stories, the excess supply or exhaust air required depends primarily on the effective area of openings into the vertical shaft. Pressurization, as il- lustrated in Fig. 8 and 9, could be provided by a separate interior air handling system, exhausting air from floors above the neutral zone level and discharging it in floors below.

CONCLUSIONS 1. With no other forces in operation, the total or theoretical pressure difference caused by chimney action is distributed across the exterior enclosure and internal separations in proportion to the rela- tive resistances to flow of these components. With a high resistance to upward flow in the building (in relation to the resistance of the building enclosure) the pressure differences across the enclosure are r&~~edand those across internal separations in- 5. If the building provides a significant resis - creased. For buildings with many floors (e.g., tance to upward air flow, it is possible to minimize more than ten) the resistance to air flow through chimney pressure differences across the building floor openings tends to become high, and the re- enclosure by providing an excess of supply air at sistance of openings into vertical shafts becomes lower levels and an excess of exhaust air at upper- - the dominant factor in determining the ratio of ac- levels. The ultimate arrangement would neutral- tual to theoreticalpressure differences from chim- ize these pressure differences on each floor. The ney effect. Construction and design features that amount of excess supply or exhaust required de- increase the resistance of the flow path through the pends upon the resistance to flow within the build- "erti-1 shafts will have the most effect in reduc- ing and is independent of the leakage characteris - ing pressure differences across the building en- tics of the enclosure. For multi-story buildings closure. the resistance to flowdependsprimarily on the re- 2. The effect on pressure differences of in- sistance imposed by the vertical shafts. creasing the entrance area at the ground floor de- 6. The distribution of pressure difference due pends on the resistance to flow within the building to chimney action and excess supply or exhaust air, in relation to that of the building enclosure. In and the air flows that result can be determined an- there is a reduction in the pressure dif- alytically if leakage characteristics are known. ference across the entrance and a corresponding Appropriatevalues for the leakage characteristics, increase in the pressure difference across sepa- particularly those for openings between floors and rations above; with a significant resistance to up- into vertical shafts, can only be determined by ward flow, most of this increase in pressure dif- measurements on actual buildings. Interpretation ference occurs across the ground floor entrance to of such measurements can be assisted by the re- vertical shafts and across the floor construction sults of mathematical studies such as those pre- above. sented in this paper. 3. Pressurization (providing an excess of supply or exhaust air) offers possibilities for the ACKNOWLEDGEMENT control of pressure differences from chimney ef- fect by altering the distribution of the theoretical The authors wish to acknowledge the contribution pressure difference across the various separa- made by Mr. H.A. Smith, Computation Centre, has. Bcess supply air introduced uniformly at National Research Council, in assisting with the all levels can be effective in neutralizing the pres- analysis of the mathematical model. The authors sure difference across ground floor entrances, but also acknowledge the contribution made by Dr. there will be a corresponding increase in the pres - W.G. Brown in deriving the mass flow equation sure differences causing exfiltration at upper lev - given in this paper. cls. The total amount of excess outside air re- quired depends upon the tightness of the building REFERENCES mclosure. 1. G.T. Tamura and A. G. Wilson, Pressure Differences 4. If pressurization is to minimize pressure for a Nine-Story Building as a Result of Chimney Effect Uerences at the entrance, there is a potential and Ventilation System Operation, ASHRAE Tram., Vol. tage in pressurizing only the ground floor. If 72, Part I, 1966. ere is a significant resistance to upward flow Within the building: the resulting pressurization at 2. J.R. Sasaki and A.G. Wilson, Air Leakage Values for Residential Windows, ASHRAE Trans., Vol. 71, Part 11, Bahgr levels will be significantly less than that at 1965. ground floor, and the total excess air required h less than with uniform pressurization S. G.T. Tamura and A.G. Wilson, Pressure Differences all floors. Caused by Chimney Effect in Three High Buildings. APPENDIX A

DERIVATION OF MASS FLOW EQUATION FOR A FLOW SYSTEM

For the flow problem considered in this paper it can be expected that

where

E = Euler's number

R, = Reynold's number For small ranges of AP and V

Let

Let

DISCUSSION

NEIL B. HUTCHEON (Ottawa, Ontario): It will be situations presented to him. Problems arising evident that this kind of study is important, but it from chimney effect must be faced in the initial is also verg demanding and a difficult kind of study stages of planning of buildings. It may even be to carry out. Not only is the situation you are necessary to change our whole approach to the de- trying to analyze quite complex, but, in addition, sign of walls and floors to provide the necessary you must have available a building in which to control over air movements in tall buildings. make the measurements. It will be quite evident, I have one other comment. We have talked I think, that it requires a very understanding and here about the heating season, primarily. Under cooperative owner to allow you to enter a building a cooling season the chimney effect is reversed. at odd hours, punch holes in his walls, and clutter The tendency is greatly reduced, however, be- up his equipment . We have been extremely cause you get only a few degrees temperature dif- fortunate in getting such cooperation from the ference in the summer conditions compared with owners of these buildings. very large temperature differences in the winter' I have one comment that adds a bit of rein- forcement to the point stressed by Mr. Locklin RIcXIARI) E. BARRETT AND DAVTD W. LOCKLD and Mr. Wilson. I think it is quite clear that (Colurnbus, Ohio): This paper (Trans. No. 2046 architects often design buildings without regard makes a significant contribution to the design 0 for some of the technical problems. The mechani- tall buildings by providing a detailed look at three cal engineer must then do the best he can with the actual buildings. The concept of theoretical draf has been known and used for many years but, until fected by changes in exterior wall leakage as well now, there has been a noticeable void in relating as by changes in interior leakage. Therefore, a theoretical models to actual buildings. The lack more plausible explanation of the lower ratios of of data ir this area has been partly due to the actual to theoretical draft obtained with the air- complexities of the problem, with air leakage, conditioning systems operating may be that the pressure differentials, air-conditioning fans and resistance to leakage through the exterior wall by and environmental aspects all interre- way of open intake and exhaust dampers uas re- lated. The authors are to be complimented for duced rather than that resistance to flow through tackling such a problem and producing meaningful the internal flow paths was increased. results. The second paper (Trans. No. 2047) provides We at Battelle Memorial Institute have used an interesting analysis of a problem which is suf- detailed computer models to evaluate air flows ficiently complex that it is difficult to visualize and pressure differentials for important leakage intuitively. By investigating a simplified model, in several tall buildings, and find that the the authors have presented a generalized picture measurements presented in this paper generally of the effect of changes in air leakage and pres- verify the results we predicted for similar situa- surization and have avoided the complicating de- tions. tails associated with specific buildings. The re- The difference between the measured air sults of this paper can guide engineers in the se- leakage rates through exterior walls and the Na- lection of allowable leakage ratios to achieve the tional Association of Metal Manufacturers' stand- particular mode of building operation that is de- ard points up the real problem of discrepancy be- sired. tween design and construction. Tests of building The authors were concerned primarily with sections may show that a building wall design is pressure differentials in this paper. But, as they adequate to provide a relatively tight wall; but it mentioned, there is an air flow of significant is another question as to whether the same leak- quantity associated with these pressure differen- age values can be maintained in the construction tials. In fact, some buildings have had heating of a complete building. The problems of working equipment removed from upper floors because the in more taxing environments of temperature, wind, flow of air from the lower parts of the and elevation undoubtedly reduce the degree of building warms the upper floors. Some of the ap- care used in actual construction. Tests of the proaches discussed by the authors for reducing type performed by the authors are definitely im- pressure differentials, per se, would result in a portant in providing the engineer with data on significant increase in stack effect air flow and, actual buildings and will enable better prediction therefore, would probably be undesirable. These of leakage values when designing new buildings. include pressurization of the first floor only and The Wge pressure differentials measured pressurizing the lower half while depressurizing across shaft doors to mechanical equipment rooms the upper half of the building. point to a possible problem area. The authors One point that the authors mentioned should measured a pressure differential of 0.30 in. of be emphasized; a total pressure differential equal vater with a 40 F outdoor temperature and an in- in value to the theoretical draft will occur in the temperature probably near 70 F. For an building. This total pressure differential will be &door temperature of -10 F, the pressure dif- equal to the sum of (1) the pressure differential aredial would increase to about 0.8 in. of water across the entrance doors, (2) the pressure dif- or 4.2 psf. This would be a force of 84 lb on a ferential across the exterior wall at the top floor, 20 eq ft door. Some rather simple measurements and (3) the pressure differentials encountered in we made using a spring scale and several subjects going from the first floor to the top floor by any Wicated that (1) the force needed to open a door path. It is not possible to eliminate completely all Pbout 10 lb greater than one-half the total pres- of these pressure differentials. meforce on the door, and (2) the maximum pull- The task of the building designer is to force %3 force a typical subject can exert is about 40 to the greatest portion of the total pressure differ- ~UJ.For the door given above, and for a -10 F ential or theoretical draft to occur at locations in abrtemperakre, the opening forces would be the building which will cause the fewest problems 32 lb, which indicates a problem in opening the for building operation and building tenants. For h~runder these conditions. The opening force some buildings, a possible location for a large Proportionally greater for taller buildings, pressure differential to occur with a minimum of amgh using a two-door reduces open- problems is across the exterior wall in the upper @ faces. This condition could be eliminated by part of the building. This can be achieved by &-sing the pressure in the mechanical equip- pressurizing the building. But, for pressurization rooms by providing a positive means of to be practical, the exterior wall must be rela- Supply air into these rooms rather than tively tight to keep net supply air to a minimum. spill from return air ducts or The authors have shown in the companion paper OXrnbmrangements typically employed in pres- (Trans. No. 2046) that pressurization may not be h *sign practice. practical without significant improvements in 'he authors pointed out a difference in the tightness of exterior wall construction. actual to theoretical draft with the air- bing systems on and off. The ratio is af- AUTHOR WILSON: We appreciate the constructive 1 comments of Messrs. Barrett and Locklin; in air, thus over-estimating the quantity of outsb 1 particular their emphasis on the dilemma of the air. 1 design~r,who must consider how best to distrib- Thirdly, although the outside dampers of 1 ute the pressure difference due to chimney action, n%t in operation were in the closed position, lea, as it cannot be eliminated. age openings through their damper S would repre. We should make it clear that the intent of the sent additional openings in the exterior wall. bear first paper was not to promote any particular ap- with these possible sources of error, however, tb~ proach for controlling or altering the distribution air leakage rates of the exterior wall obtained of pressure differences resulting from chiinney would appear to be considerably higher than action. Our intent was to illustrate by example would estimate from air leakage data on WQ the manner in which the distribution of pressure components. differences would be affected by the relative re- In general, pressure differences across th sistance~to flow of the building enclosure and in- interior separations were small and did not give terior separations, and the operation of the me- rise to any problems. Relatively large pressure chanical air distribution system. differences occurred across the stairwell doors The best approach in altering or controlling leading to the top of the tallest af these pressure differences will, of course, depend the three buildings. These doors were difficu on the particular circumstances; but for Canadian to open. As pointed out by Messrs. Barrett and conditions with extended periods of sub-freezing Locklin, the pressure difference across the door outdoor temperatures in winter, I would be very was 0.30 in. of water. In this same building noise hesitant to recommend to designers that they due to air flow was very noticeable at the door af pressurize buildings in such a way as to increase the elevator serving the forty-first to the forb- significantly pressure differences leading to ex- fifth observation floor. The pressure difference filtration through the enclosure in the upper parts across these doors was approximately 0.20 in. cg of the building. Warm, moist air exfiltrating water. Opening of these elevator doors was ac- through joints and porous materials which occur companied by a noticeable gust of air, especially in building enclosures as commonly designed and at the forty-fifth floor. Noise arising from air- constructed, carries with it moisture which under flow through ckack openings around the doors wintertime conditions, will condense in the flow depend on the configuration of the cracks and on path. This mechanism to the deposition of the pressure difference across them. h an iso- very large quantities of water in the form of frost lated case a loud air noise occurred across a door or ice, which can cause early and severe degrada- with a pressure difference of as low as 0.08 in. af tion of the structure. water. Tests conducted by Mr. Barrett and Mr. A number of serious examples of this type of Locklin on door openings are helpful in stating a problem have come to our attention in recent maximum allowable pressure difference across years. We believe this is one of the more serious interior separations. implications of air leakage, particularly in hu- As to their final comments relative to the midif ied buildings. lower values of the ratio of actual to theoretical draft with the ventilation system on, as compared AUTHOR TAMURA: First of all, I would like to to the values with it off, I find that I do not under- thank Mr. Barrett and Mr. Locklin for their help- stand their explanation. As pointed out in the ful comments. paper, with the system off, duct openings into the With reference to the second paper, perhaps various floors would act as interconnections anc it would be appropriate to make some additional reduce the resistance to vertical flow within tht comments on our estimate of the leakage charac- building, thus tending to increase the ratio d teristics of the exterior walls. In our tests there actual to theoretical draft as defined; intake ant were several sources of error, most of which exhaust dampers, if open, would act as opening: would tend to over-estimate the leakage rate. in the exterior wall and would have the opposit~ First, there is the estimate of the flow through effect. With the system on, however, we do no the fan. Prior to the test the static pressure drop think that it is a useful concept to regard the sup across each fan and fan speed were measured and ply and exhaust openings as simple, passive open recorded. Only those fans whose readings agreed ings in the enclosure. Instead we regard them a approximately with the contractor 'S figures were sources of excess supply or exhaust air, their ef used in the pressurization test. These readings fect depending upon the final distribution of thj were taken prior to the pressurization test. The net supply or exhaust throughout the building flow rates of the fans would be affected to some extent, however, by changes in the air flow re- P. R. ACHENBACH (Washington, D.C.): Th sistance of the system during the pressurization authors ought to be complimented for these uset tests from its characteristics under normal papers. However, I would like to ask a questic operation. or two about Fig. 13 in the second paper (Tran Secondly, although the return air dampers No. 2047). The authors say, in applying the were in a closed position to obtain 100% outside data, that they used the average pressure diffe: air, it is probable that some leakage flow occurred ences across the enclosure from top to bottom. through the return air dampers, even though they am wondering whether this is an arithmetic were in the closed position to obtain 100% outside algebraic average and whether, in fact, this Fig. geful in evaluating what was happening in the paper, along with that across the ground floor en- a.ig.of airflow. In Fig. 11 they deny that there trance, and by determining the arithmetic average f& a neutral zone in part of the building and an of these values. This amounted to averaging the ,dsard flow in the remainder. Even so, it would pressurization effects at three levels in buildings that Fig. 13 might have been useful in com- A and B, and at five levels in building C. The $rson with Fig. 11 when the building was pres- amount of pressurization measured in this way &;zed virtually throughout its whole height with naturally varied with the outside air temperature, B - ,, ventilation system operating. In this case that is, with the amount of pressure difference due was an average pressure difference of about to chimney action, because of the non-linear flow 5 10, and in Fig. 13 I find there was a wall leak- characteristics of the building enclosure. This is @ af 4/10 to 6/10 cfm per sq ft of water, or total evident in Fig. 13 when comparing the two curves e somewhere between 100,000 and 150,000 for building B. Thus, in utilizing Fig. 13 with &,A in building B. I would like a little clarifica- reference to conditions in Fig. 11, the building ,m of the basis on which Fig. 13 was plotted, and leakage characteristic for an outside air tempera- ,dether it is, in fact, applicable to the other ture of 32 F would be applicable. pphs. In connection with Mr. Achenbach's comments Then, referring to the first paper (Trans. on the internal air handling system, I might re- W. 2046), it seems to me that one of the most iterate that it was not our intention in this paper ,dicant statements was in the last sentence be- to promote any particular way of achieving a bal- t&the conclusions, where the authors are talk- anced air pressure across the enclosure at any or a about pressurization to reduce the effects. In all levels. Zero pressure difference across the wir presentation they seemed to mention doing walls from top to bottom could be achieved by ex- by appropriate selection of supply and exhaust cess supply or exhaust of air obtained either from U, but in this last sentence they suggest doing it inside or outside the building. When obtained in- a an interior air handling system. It seems to side the building there is potential saving in heat- this is the right way to do it; by providing a ing costs but there is the added cost of the interi- indoors, especially for equalization, putting or air handling system. off in the neutral zone and using a blower at We were talking about this with our Chair- &at level to draw air from the upper floors to man, D. S. Cooper. He mentioned that in some gapply it to the lower floors, you could exactly buildings there is a separate mechanical equip- gattralize the indoor-outdoor pressure level at ment room and air handling system for each floor. mry level and neutralize the pressure differ- In this case it would be a relatively simple mat- msacross your stairway doors, not only al- ter to control net supply and exhaust of outside air ing the problem of door opening, but mini- to balance exterior wall pressure differences. g the total air exchange with the out-of -doors The outside air quantities required and therefore - md you could do this using air that has already the increased heating costs would depend on the onditioned by your heating or air-condi- tightness of the floor separations. spstem. Lf the pressure differences across the exteri- or walls are neutralized at each floor level, uti- &?2THOR WILSON: In reply to Mr. Achenbach's lizing either inside or outside air, the pressure %micomment, regarding Fig. 13, we would say differences due to chimney action are then dis- m his application of it to the conditions of tributed uniformly across each floor. This does h.11 is appropriate, within the limitations of not overcome, however, the problem of excessive W rir flow data as outlined in Mr. Tamura's re- pressure differences across entrances to vertical to the comments of Messrs. Barrett and shafts. Disregarding pressure losses within the . In constructing Fig. 13, the average shaft, the sum of the pressure differences across ization corresponding to a given net ex- the doors of the vertical shafts at top and bottom air was obtained by determining values of the of the building is equal to the total theoretical -aance between exterior wall pressure differ- draft. The pressure difference across the doors %@ With and without pressurization at the per- of the shafts decreases uniformly toward the m&pressure top locations described in the neutral zone of the shafts where it becomes zero.