HiLine™ Vertical Stacking Coils Catalog 770-15 Type FHSS and FHSK

Engineered for flexibility and performance™ Table of Contents

Introduction ...... 3 Dimensional Data ...... 18 Daikin HiLine™ fan-coil units ...... 3 Model FHSS (Basic Unit) Low CFM design (300 thru 800 cfm) ...... 4 Sizes 03 Thru 08 (300 thru 800 cfm) ...... 18 High CFM design (1000 thru 1200 cfm) ...... 5 Model FHSK (Knock-down Unit) Sizes 03 Thru 08 (300 thru 800 cfm) ...... 19 Features and Benefits ...... 6 Riser Location — FHSS and FHSK Unit Sizes Design features for high performance and low 03 Thru 08 (300 thru 800 cfm) ...... 20 operating cost ...... 6 Model FHSS (Basic Unit) Sizes Optional features and accessories ...... 9 10 Thru 12 (1000 thru 1200 cfm) ...... 21 Application considerations ...... 11 Riser Location — FHSS Unit Sizes Application Data ...... 11 10 Thru 12 (1000 thru 1200 cfm) ...... 22 Performance Data ...... 14 Riser Location for Master-Slave Units ...... 23 Physical Data ...... 16 Wiring Diagrams ...... 24 Engineering Guide Specifications ...... 26 Model FHSS (Basic Unit) Sizes 03 thru 08 (300 thru 800 cfm) ...... 26 Unit Sizes 10 & 12 (1000 thru 1200 cfm) ...... 27 Model FHSK (Knock-down Unit) Sizes 03 Thru 08 (300 Thru 800 cfm) ...... 28

2 CAT 770-15 Introduction

Daikin HiLine™ fan-coil units The Daikin HiLine fan-coil units are designed for use in multiple floor apartments, office buildings, hotels and other similar applications and require a minimum amount of floor space. Just one HiLine unit may do the job that formerly required more than one conventional unit .

The results of many years of experience in the development, design and manufacture of fan-coil air conditioners have been incorporated in the Daikin HiLine units to provide highly efficient, quiet performance; individual thermostatic control; simple, low cost installation; application flexibility; and low maintenance and operating costs with no sacrifice in room comfort, design, or appearance. For the ultimate in design, performance, efficiency, flexibility of application, and ease of installation and maintenance, look to Daikin HiLine fan-coils . Application flexibility Two distinct designs are available with the complete flexibility necessary for any application requirement. • Low cfm design - The 300 through 800 cfm blow- through configuration units are designed to meet individual room control requirements. • High cfm design - The 1000 and 1200 cfm draw-through configuration units are designed for multiple discharge arrangements so that one unit can serve more than one room . Both designs are available for two-pipe and four-pipe systems with single, double, triple and top discharge arrangements. Optional equipment is available to provide complete application flexibility. Contact your Daikin representative for a copy of the DaikinTools™ selection program to choose a unit meeting your needs . Nomenclature FHS S 1 03 A A Product Category Voltage FHS = Vertical stacking HiLine™ hydronic coil A = 115/60/1 J = 265-277/60/1 Product Identifier S = Standard hideaway shipped assembled K = Shipped in 2 pieces A = Stand-alone M = Master Design Series C = Companion (slave) 1 = Design 1

Nominal CFM 02 = 200 03 = 300 04 = 400 06 = 600 08 = 800 10 = 1,000 12 = 1,200

CAT 770-15 3 Introduction

Low CFM design (300 thru 800 cfm) Blow-through units to meet individual room requirements

Neutral unit shown (risers in back) FAST, SIMPLE INSTALLATION - Simply stack one unit above the other, Low Sound Level Operation - The low cfm design features a quiet, energy efficient sweat the couplings to the risers and motor and fan assembly, carefully located connect the power . The unique nonstop within a fully insulated cabinet to provide low slip couplings require only one person for setting and connecting sound level operation . .

RISERS - Factory cut 104" long . No on-the- job cutting required . Supply and return risers have factory installed sweat ball valves and are factory insulated

DISCHARGE ARRANGEMENTS - Single, double, triple and top discharge arrangements are available .

CONTROLS - Face mounted, plug-in type, combination 3-speed switch and . Thermostat electrical box is adjustable for CABINET - Heavy gauge wall thickness . No wiring required . galvanized steel . Fully insulated for quiet operation . ACCESS & SOUND BAFFLE PANEL - Insulated galvanized steel . Easily removed for complete access for service .

Optional valve packages can be provided for 24V, 115V, and 277V .

COILS - High efficiency type for full rated capacity . AHRI certified.

REMOVABLE CHASSIS - All components are mounted on a single removable chassis so that a different capacity chassis can be installed in the same cabinet should future needs require it .

RETURN AIR PANEL - Heavy gauge FILTER - Easily accessible steel with stamped grille and attractive Antique by simple removal of return MOTOR & FAN ASSEMBLY - Quiet, energy Ivory finish. Available as an accessory. air grille panel . efficient, permanent split capacitor motors and centrifugal fans for low sound level . Fan OPPOSITE HAND UNITS - Two adjacent room units can be housings are of a split type design or have connected to a single set of risers and still retain individual room separate inlet rings to allow easy removal of temperature control. Twin units must be joined in the field. Reverse the fan motor . piping for same hand units not available .

4 CAT 770-15 Introduction

High CFM design (1000 thru 1200 cfm) For Multiple Discharge Arrangements Specially Designed For High CFM Performance - these draw-through type units are ideal for luxury hotel and condominium type buildings where multiple discharge arrangements with a common return air location, high cfm performance and quiet operation are required .

Neutral unit shown (risers in back) Fast, Simple Installation -Simply stack one unit above the other, sweat the couplings to the risers and connect the power . The unique non-stop slip couplings require only one person for setting and connecting .

Risers (Not shown) - Factory cut 104" long . Supply and return risers are factory insulated . The unique non-stop slip couplings Discharge Arrangements - Single, each unit . Twin units must be joined double, triple and top discharge arrangements in the field. Reverse hand piping for are available . same hand units not available .

Motor & Fan Assembly (Not shown) - Quiet, energy efficient, permanent Cabinet - Heavy gauge galvanized steel . split capacitor motors and Fully insulated for quiet operation . centrifugal fans, mounted in the draw-through position Controls - Unit-mounted combination 3-speed switch and with a common return thermostat . Thermostat electrical box is adjustable for wall location, provides high cfm thickness. Thermostat wiring required in the field and centrifugal performance with low sound fans, mounted in the draw-through position with a common levels . return air location, provide high cfm performance with low sound level . (optional molex connections can be provided) .

Sweat Ball Valves - factory mounted on coil .

Optional valve packages can be provided for 24V, 115V, and 277V .

Coils - High efficiency type for full rated capacity. ARI certified.

Return Air Grille Panel - Heavy gauge steel with stamped grille and attractive Antique Ivory finish.

Access & Sound Baffle Panel - Easily removed for complete access to internal controls, motor and fan assembly for service .

Filter - Easily accessible by simple removal of return air grille panel .

OPPOSITE HAND UNITS - Two adjacent room units can be connected to a single set of risers and still retain individual control. Twin units must be joined in the field. Reverse piping for same hand units not available .

CAT 770-15 5 Features and Benefits

Design features for high performance and Unit configuration low operating cost Unit sizes 03 through 08 feature a blow-through design with completely removable chassis. The motor, fan assembly, Telescoping Thermostat Box coil(s), drain pan and valve packages are mounted on a compact chassis which slides out through the return air grille and access panel . Unit sizes 10 and 12 feature a draw-through design. Filter, drain pan and drain line are accessible by removing the return air grille. Controls, valves, motor and fan assembly are accessible by removing the access panel. Knock-down unit The FHSK knock-down unit configuration, available for unit sizes 03 through 08, allows installation, leak testing and insulation of the risers and stub-outs prior to the unit placement. Risers can be field provided or factory supplied Plug-in Field Mounted Thermostat and shipped to the jobsite before the units . After riser installation, the bottom half of the unit is set in place. Connections are then made to the supply, return and drain risers as well as the power supply. Then the top half of the unit is installed . Fast, low-cost installation Installation time is minimized by the unit’s design, riser slip couplings, and unit mounted controls. Units are completely factory assembled and wired and have individual thermostat controls. Risers are factory cut to 104" in length and insulated. Optional riser couplings are available. Installation is accomplished by simply stacking the units one above the other floor-by-floor, brazing the couplings and risers together, and connecting the power. Only one person is required for installation because the slip couplings eliminate the requirement for perfect unit alignment with the swaged riser joints of other manufacturers . Twin units To reduce installed cost, two units of opposite hand on each floor can share a set of supply, return and drain risers. Individual thermostat control is retained by each unit. Units can be placed side-to-side, or side-to-back

6 CAT 770-15 Features and Benefits

Coils Efficient, quiet fans and motors High-capacity, low-flow heating/cooling coils are standard. Three-speed, permanent split capacitor motors coupled with Separate row heating coils are available for 4-pipe systems. DWDI forward curved direct drive fans provide efficient All coils are furnished with manual air vents. operation. Motors have sleeve bearings, oilers and inherent automatic reset thermal overload protection. Unit sizes 03 High performance coils through 04 have a two-piece fan housing with integral scroll Two-pipe system units have a standard low-flow, high and inlet. Unit sizes 06 through 12 have a heavy-gauge steel capacity cooling/heating coil. Four-pipe system units have fan housing with integral scroll and separate inlets. All fan a standard low-flow, high capacity cooling coil and a one- wheels are statically and dynamically balanced. Efficient row heating coil. All coils are seamless copper tubes in a fans, PSC motors, resilient motor mounts and a fully insulated staggered pattern and feature the patented HI-F rippled and cabinet provide quiet operation. corrugated aluminum fins for high efficiency. Full depth collars are drawn in the fin stock for accurate Fan and Motor Assembly control of fin spacing and completely cover the copper tubes to lengthen coil life . Copper tubes are mechanically expanded into the fin collars to provide a positive primary to secondary surface bond. Manual air vents on coils are provided. Ball valves on supply and return lines are provided at the coil on 10 and 12 models. Coils are positioned for rapid condensate drainage, balanced airflow and full rated capacity. Unit capacities are AHRI certified. Control systems A variety of , unit or wall mounted, are offered to control all different options for fan and valve cycling. For Sizes 03 & 04 unit mounted thermostats all wiring is provided to the control box for easy field installation (optional Molex connections are available upon request). A 10K thermistor is mounted in all units. It can be used for factory provided thermostats or for field provided controls. The thermostat electrical box is adjustable for any wall thickness up to 3-7/8" and is provided with a 1/2" mud ring (an optional 5/8" mud ring can be provided upon request). Thermostats • Unit mounted 2- or 4-pipe systems (24v–277v) • Wall mounted 2- or 4-pipe systems (24v–277v)

• Automatic or manual changeover Sizes 06 -12 • Digital display • Optional quick connect for unit mounted thermostats (Please reference ED 18513 for thermostat availability and options)

CAT 770-15 7 Features and Benefits

Factory- and field-installed risers Riser, Slip Coupling and Insulation Insulated risers are available factory-installed or can be shipped with or prior to the units for field installation (factory installed risers are not available for FHSK knock-down units). See details below. On 03 through 08 units, sweat ball valves are included with factory risers. All copper risers are factory cut to 104" in length . Nonstop slip couplings for supply and return risers and stop type couplings for drain risers may be ordered separately . Insulation meets or exceeds current flammability classification UL94. Insulation to cover slip couplings must be field provided. • Supply and return risers are of type “L” copper in nominal 3/4", 1", 1-1/4", 1-1/2", 2", 2-1/2" diameters Slip with 3/4" factory installed, closed cell flexible foam Coupling insulation . • Drain risers are available in PVC or type “L” copper (insulation included), in nominal 3/4" or 1-1/4" diameter . • Optional 1/2" closed cell insulation is available for supply, return, and drain risers. • Optional M or K type copper is available with closed cell insulation . Insulation to cover slip coupling (by others) NOTE: When risers are factory-mounted on master-slave units, the master unit is shipped with the riser attached . This riser will have 3" stubs that match up to the slave unit . The slave unit will not have ball Optional Valve Package Components valves attached to the valve package . See Page 22 for master-slave riser locations . Ball valves, if Automatic required, must be purchased separately and will ship Change-Overcontrol loose for field mounting. See IM 283 for additional information . Motorized Valve Factory-installed valve packages and options Multiple configurations of two- and three-way motorized valves are available as described below, without or without unions. Ball hand valves and flow metering devices are also available. • Standard high voltage valve package 115–277v (includes 2- or 3-way motorized On/Off valve and shutoff valves for supply and return)

• Deluxe high voltage valve package 115–277v (includes P/T Plug 2- or 3-way motorized On/Off valve, strainer, circuit Ball Valve setter, P/T ports, and shut-off valves) • Optional 24v On/Off or valve packages (standard or deluxe) • Custom valve packages available • Fixed flow control • Optional stainless steel braided hoses

“Y” Strainer

Flow Control Device

8 CAT 770-15 Features and Benefits

Optional features and accessories Motors Electric Heat 115/60/1 and 277/60/1 motors are available. All motors are 3-speed permanent split capacitor type with sleeve bearings, oilers, resilient mounts and automatic reset internal overload protection . Electric heat A specially designed, optional electric heat unit is available for supplementary heat between seasons or to provide full . All heaters are protected by automatic-reset, high-limit thermal cutouts. Service access to electric heaters is through the return air grille and access panel for unit sizes 03 through 08. It is through the discharge grille for unit sizes Fresh Air Dampers 10 and 12. Cabinet insulation 1/2" multi-density glass fiber is standard. Cabinets can be supplied fully insulated with 1/2" closed cell insulation . Fresh air dampers (Accessory) A motorized, two-position fresh air kit is available for field mounting in one of three locations. A manual fresh air damper kit is also available. Outside fresh air must be tempered before entering the unit if freezing conditions are expected . Discharge Arrangements Return air (Accessory) Return air grille options include the standard stamped return air grille or an optional bar type grille . Both grilles are manufactured of heavy-gauge steel and coated with an Antique Ivory finish. A plaster frame is standard to provide easy access for filter replacement. Filters One inch throwaway filters are standard. Discharge arrangements and grilles (Accessory) Discharge Grilles Two sizes of aluminum single deflection or double deflection grilles are available. Grilles may be field mounted on the panel opposite the riser and on one or both panels adjacent to the risers. A top discharge opening is also available. Line-of-sight baffle (Accessory) A line-of-sight baffle is available for applications involving two opposing discharge openings. Single Deflection

Double Deflection

CAT 770-15 9 Features and Benefits

Installing The FHSS (Basic) Unit: Installing the FHSK* (Knock-down) Unit:

1 . The Daikin HiLine basic unit is 1. Unlike the basic unit, the FHSK simply lifted into place directly unit allows installation, leak above the unit on the floor below. testing and insulation of the risers and stubouts prior to unit placement .

2 . The bottom half of the unit is set in place, and the supply, return and drain risers are connected to the unit along with the power 2. This unit has been set in place, supply . ready to accept the unit above.

3. Next, using factory available slip couplings, connect the 3. The top half of the unit is then prefabricated supply, return and easily installed and the factory drain risers together, connect the suppled thermostat harness is power, and your basic installation connected . is completed . Wall board can be applied directly to the unit .

4. Finishing the installation is the 4. After the unit has been “furred- same with either the standard in” and the room painted, it takes FHSS model or the knock-down only a few minutes to attach the FHSK model . grilles and plug in the thermostat .

5 . Both HiLine units can be located away from an outside wall to form a curtain cove, or built into a room divider. It’s easy 5 . When the installation is to conceal the units in a corner completed, the unit blends in or build them into a wall to serve beautifully with the surrounding two or more rooms. And, of decor and takes up a minimum of course, the creative architect will floor space. think of many more applications for this versatile unit.

*The “FHSK sectioned cabinet for room air condition- ing unit” is covered under U .S . Patent No . 4,426,120 .

10 CAT 770-15 Application Data

Application considerations Cooling Coil Requirements - Having checked the minimum unit size to meet the ventilation requirement, the unit size System design is generally selected on the basis of matching the sensible The achievement of an efficient fan coil system is dependent cooling capacity of the unit with the calculated requirements upon accurate system design and proper equipment selection. when operating at high speed. Variations, limitations and control of fan coil systems, design The initial unit selection should be checked for air volume in conditions and design load calculations are not described in the design system and the cooling capacities checked at the detail in this catalog . More detailed information may be found actual operating conditions . While units selected on the basis in the ASHRAE Handbook series . of sensible load will generally meet the total cooling load, Prior to selecting the individual unit sizes, the design total load should be checked in all cases . engineer must fix or determine the following factors: Coil Type - Standard low flow coils are available for all units 1 . Inside and outside wet and dry bulb temperatures. sizes to permit unit selections for optimum performance. Low flow coils are designed to meet both the normal cooling and 2 . Method of introducing the ventilation. heating requirements while operating with reduced GPM and 3. Wet and dry bulb temperatures of the air mixture correspondingly higher water temperature rises. Their use is entering the unit coil . enhanced by the lower first cost of both riser piping and pump 4. Total and gains and losses of the area to be plus lower overall fan coil unit and water pump operating served. cost . 5 . Properties of the heating and cooling mediums . Heating Requirements - Heating requirements for two- pipe systems are generally met by employing the same 6 . Available electric power service. water flow rate as cooling and adjusting the entering hot 7. Any special design requirements of the building or water temperature to obtain a matching unit heat output at system . low fan speed. Four-pipe systems are generally designed by specifying a design hot water temperature and adjusting Computer fan coil selection the flow rate through the separate heating coil to meet the The capacity ratings presented in this catalog are provided required heat load with the fan operating at low speed. for initial unit selection only . Unit size selection should be Maximum water temperature in coils should be limited determined by using the DaikinTools™ fan coil selection to 200°F (160°F for FHSS sizes 10 and 12), and should be computer program. Water cooling and heating capacities, adjusted to reflect outside temperatures. unit airflow, static pressure, electric heat, glycol solutions and jobsite elevation are all incorporated into the program Electric heaters are available for primary year-round heating to provide the best possible selection. Consult your or intermediate between-seasons heat loads for two-pipe representative for a selection tailored to your application. systems when is in the system. Units having Unit sizes for the ideal system should be selected by top discharge and electric heat must have a discharge calculating the peak load requirements due to unusually duct face area equal to or greater than the top duct high occupancy or severe climatic conditions and with fan opening. operating at high speed . Ordinary day to day cooling and heating requirements are then achieved at low and medium speeds. Ventilation requirements should be considered along with the following to determine the proper unit size.

CAT 770-15 11 Application Data

Piping systems Expansion and contraction Reverse Return Piping Systems - If possible, the same size Proper allowance must be made for pipe expansion. HiLine units should be installed one above the other all the Provisions have been designed into the HiLine unit to allow way up each stack in the building. This way, each unit in the for plus or minus 1" of riser movement. For riser systems stack requires the same amount of water. No balancing is where the movement exceeds ±1", provisions must be provided required, because the loop of water from each unit travels the in the riser system to restrict the movement. As a rule of same distance and has the same pressure drop . thumb, 100 feet of copper pipe will expand 1" when exposed Our experience indicates that the reverse return piping to a 100°F temperature difference. See Figure 4 for thermal system, Figure 1, is the most popular one because the system expansion of copper risers . The temperature difference is the tends to be self-balancing. Only one express riser is required difference between the temperature at which the piping is to gather the return water, at the top or bottom of the building, installed and the water temperature during operation. On a and return it to the or . two-pipe system, this temperature difference becomes even greater due to the change in water temperature from cooling Direct Return Piping System - In the direct return piping to heating . system, Figure 2, each unit must be individually balanced to obtain proper water flow through each unit. One method of limiting riser expansion is by anchoring the riser pipes at the center of the riser stack and allowing the pipes to expand away from the anchor point. Thus, a Figure 1: Reverse Return Piping System 200 ft. length would expand approximately 1" each way. Another method is anchoring the riser pipes at the end and absorbing the expansion with an expansion compensator. If an expansion compensator is used, the pipe should be guided. In some situations, a combination of both methods may be required. The risers must be secured at some point as the units have not been designed to support the riser weight. Number of floors per riser The standard HiLine unit with service valves, expansion loops, etc., will operate at 250 PSI working pressure which is equivalent to a 35 to 40 story building.

Figure 2: Direct Return Piping System

12 CAT 770-15 Application Data

Selection of riser piping Insulation limitations Riser piping should be selected based on economic Under high start-up conditions, care should be taken considerations . Detailed information may be found in the by utilizing a gradual pull-down to minimize sweating of ASRHAE Handbook series . The guidelines offered in Figure cabinet and/or risers. 4 are based on water velocity only. A water velocity of 2 FPS is considered to be the minimum requirement for entraining Temperature control and carrying air with water flow. Water velocities of over 8 A wide variety of fan and valve cycle control systems are FPS may cause undue erosion of water pipe. Risers may be offered for Daikin HiLine units. Valve cycle control systems sized on the highest water velocity that will not cause noise or have a higher first cost but offer significantly lower operating erosion. We recommend that the water velocity in risers and costs than fan cycle systems. Valve cycle control systems units fall within the range of 4 FPS to 6 FPS. Since HiLine provide superior temperature control resulting in improved units have risers outside the unit cabinet and usually within a occupant comfort. partition wall, noise should not be a problem. Riser sizes need Both unit mounted and remote wall mounted thermostats are not be changed at every floor to accommodate flow changes available. The 10K thermistor is positioned in front of the but may be carried at one size until water velocities fall filter and is provided with all units. The thermostat electrical outside the recommended ranges . box is field adjustable for any wall thickness up to 3-7/8" . Contractor piping responsibility Direct sunlight falling on thermostats for either unit or remote mounted control applications should be avoided. Factory available copper riser couplings are non-stop type for ease of installation. PVC couplings have stops. Field Twin units installation involves clamping the slip coupling in place Equipment and installation costs can be significantly reduced and brazing or sweat soldering it to the risers above and by designing a floor layout involving twin units. Twin units, below. PVC couplings are field cemented to the drain risers. of opposite hand, are placed side-to-side, or side-to-back and Reducing couplings, anchors and expansion compensators, if share a common set of risers. Individual thermostat control is required, must be provided by the contractor. retained by each unit. Twin unit risers have two sets of stub- Insulation to cover slip couplings must be field provided. outs to accept piping from both units. A short link of field Providing a good cement bond at the joints between the field supplied copper tubing may be required depending upon wall installed insulation and the factory installed riser insulation is thickness between units. the contractor’s responsibility . Fire stop For building code compliance, a fire stop must be provided by the contractor in the riser opening between floors and between twin units serving adjacent rooms.

CAT 770-15 13 Performance Data

AHRI approved standard ratings

Table 1: Low Flow Coil Water Cooling Capacity Ratings1 Cooling Capacity2 Unit Size Water Flow (GPM) Water Flow P .D . (Ft-WC) (Total Btuh) (Sensible Btuh) 03 11000 7200 2 3. 14 .6 04 17000 11400 3 5. 44 .7 06 23000 16100 4 7. 28 .8 08 28800 20600 6 0. 44 .1 10 39600 26600 8 2. 29 .7 12 44900 30400 9 3. 39 .6 NOTE: 1 . Rated in accordance with ARI Standard 440 . Cooling capacities based on 80°F DB/67°F WB entering air, 45°F entering water, 10°F water temperature rise and high fan speed . See Table 6 for air volume capacities . 2 . For cooling coil capacity ratings at conditions other than that listed, refer to the Rep Tools computer selection program or consult your Daikin representative .

Table 2: Low Flow Coil Capacity Ratings1 Heating Capacity2 Unit Size Water Flow (GPM) Water Flow P D. . (Ft-WC) (Sensible Btuh) 03 21776 2 .2 9 8. 04 27596 2 .8 22 .1 06 38932 3 .9 15 .5 08 48229 4 .9 22 .6 10 65287 6 .6 14 .5 12 77078 7 .8 20 .8

NOTE: 1 . Water heating coils rated at 70°F DB entering air, 140°F entering water, 20°F water temperature drop and high fan speed . 2 . For heating coil capacity ratings at conditions other than that listed refer to the Rep Tools computer selection program or consult your Daikin representative .

Table 3: Separate Hot Water Coil Water Heating Capacity Ratings1 Heating Capacity2 Unit Size Water Flow (GPM) Water Flow P D. . (Ft-WC) (Sensible Btuh) 03 12206 1 2. 1 .6 04 16355 1 7. 3 .5 06 22086 2 2. 7 .3 08 25783 2 6. 9 .6 10 40258 4 1. 27 9. 12 46626 4 7. 39 6. NOTE: 1 . Water heating coils rated at 70°F DB entering air, 140°F entering water, 20°F water temperature drop and high fan speed . 2 . For heating coil capacity ratings at conditions other than that listed refer to the Rep Tools computer selection program or consult your Daikin representative .

External Static Pressure (Inches H20) Unit TableSize 4: Air0 Volume.00 versus0 .05External Static0 .10 Pressure. 0 15. 0 .20 0 .25 0 30. HI MED LO HI MED LO HI MED LO HI MED LO HI MED LO HI MED LO HI MED LO 03 339 258 183 311 243 173 281 222 159 249 197 140 — — — — — — — — — 04 408 310 221 397 298 207 384 284 193 368 268 178 350 252 160 — — — — — — 06 609 519 422 588 499 404 565 479 383 539 456 360 512 429 315 — — — — — — 08 798 621 452 781 606 440 759 590 428 736 574 416 712 556 402 686 535 386 — — — 10 1020 800 646 1000 780 630 976 761 614 950 741 598 923 720 581 895 698 564 868 677 547 12 1220 972 778 1192 954 765 1164 932 755 1137 910 748 1109 887 745 1080 865 747 1050 840 753

NOTE: 1 . Air volumes based on 115/60/1 electrical services, normal unit features and dry coils . 2 . Medium and low speed air volume based on unit performance in a system with tabulated external static pressure produced at high speed .

14 CAT 770-15 Performance Data

Figure 3: Type “L” Copper Riser Pressure Drop

Area outside of recommended design range .

Figure 4: Thermal Expansion of Copper Risers

CAT 770-15 15 Physical Data

Table 5: Motor and Physical Data. Nominal Motor Data At High Speed Maximum Return Air Unit Size 115/60/1 277/60/1 Discharge Grille Filter Size Size Amps Watts Amps Watts) 03 0 65. 70 0 .40 70 13-¾" × 18-⅞" × 1" 16" × 12" 04 1 30. 146 0 .45 120 13-¾" × 18-⅞" × 1" 16" × 12" 06 1 60. 195 0 .70 200 13-¾" × 18-⅞" × 1" 16" × 12" 08 2 40. 314 1 .10 290 13-¾" × 18-⅞" × 1" 16" × 12" 10 3 60. 350 1 .30 350 (1) 24" × 24" × 1" 24" × 14" 12 4 80. 498 2 .10 500 (1) 24" × 24" × 1" 24" × 14"

Table 6: Approximate FHSS Shipping Weights (Lbs.) Unit Size Single Unit - No Pallet Single Unit with Pallet Two Units with Pallet Four Units with Pallet1 03 155 205 380 720 04 160 210 390 740 06 175 225 420 800 08 180 230 430 820 10 256 306 585 1130 12 267 317 605 1180

NOTE: 1 . Standard shipping arrangement .

Table 7: Approximate FHSK (Knock-down Unit) Shipping Weights (Lbs.) Unit Size Single Unit - No Pallet Two Units with Pallet Four Units with Pallet1 03 155 380 720 04 160 390 740 06 175 420 800 08 180 430 820

NOTE: 1 . Standard shipping arrangement .

16 CAT 770-15 Physical Data

Table 8: Electric Heat Data 120V/60/1 277/60/1 Unit Size WATTS BTUH AMPS WATTS BTUH AMPS 1000 3413 8 3. 1000 3413 3 .6 2000 6826 16 7. 2000 6826 7 .2 03 — — — 2500 8533 9 .0 — — — 3000 10239 10 8. 1000 3413 8 3. 1000 3413 3 6. 2000 6826 16 7. 2000 6826 7 .2 04 — — — 2500 8533 9 .0 — — — 3000 10239 10 .8 — — — 4000 13652 14 .4 1000 3413 8 3. 1000 3413 3 6. 2000 6826 16 7. 2000 6826 7 .2 — — — 2500 8533 9 .0 06 — — — 3000 10239 10 8. — — — 4000 13652 14 4. — — — 5000 17065 18 1. — — — 6000 20478 21 7. 1000 3413 8 .3 2000 6826 7 .2 — — — 2500 8533 9 .0 2000 6826 16 7. 3000 10239 10 .8 08 — — — 4000 13652 14 .4 — — — 5000 17065 18 .1 — — — 6000 20748 21 .6 2000 6826 16 7. 2000 6826 7 .2 — — — 3000 10239 10 8. 10 — — — 6000 20748 21 6. — — — 8000 27304 28 8. 2000 6826 16 .7 2000 6826 7 2. — — — 3000 10239 10 .8 12 — — — 6000 20748 21 .6 — — — 8000 27304 28 .8 * Electric heat voltage must match motor voltage

CAT 770-15 17 Dimensional Data

Model FHSS (Basic Unit) Sizes 03 Thru 08 (300 thru 800 cfm)

Recommended Riser Hole Size in Floor (inches) Right hand unit shown RISER ¾ 1 .0 1-¼ 1-½ 2 0. 2-¼ 3 .0 Hand of unit determined by facing A 3-½ 4 .0 4 0. 4-½ 5 0. 5-½ 6 .0 return air opening . • Risers on right = Right hand of unit . (TWO PIPE) B 13-½ 14 .0 14 0. 14-½ 15 .0 15-½ 16 0. • Risers on left = Left hand of unit . • Risers on back = Neutral unit . (FOUR PIPE) B 17 .0 17-½ 17-½ 18 0. 18-½ 19 0. 19-½ All dimensions approximate. Certified drawings available upon request.

Mud ring can be mounted vertically or horizontally . Opening is 2" × 4"

NOTE: (1) With return air grille mounted on unit, dimension becomes 2-⅜" can be field adjusted to 3-⅜" for furred-in applications . (2) Fire Stop, if required, must be provided by the contractor . Field riser location and discharge openings: see page 19 for detail .

18 CAT 770-15 Dimensional Data

Model FHSK (Knock-down Unit) Sizes 03 Thru 08 (300 thru 800 cfm)

Recommended Riser Hole Size in Floor (inches) Neutral hand unit shown RISER ¾ 1 .0 1-¼ 1-½ 2 0. 2-¼ 3 .0 Hand of unit determined by facing A 3-½ 4 .0 4 0. 4-½ 5 0. 5-½ 6 .0 return air opening . • Risers on right = Right hand of unit . (TWO PIPE) B 13-½ 14 .0 14 0. 14-½ 15 .0 15-½ 16 0. • Risers on left = Left hand of unit . • Risers on back = Neutral unit . (FOUR PIPE) B 17 .0 17-½ 17-½ 18 0. 18-½ 19 0. 19-½ All dimensions approximate. Certified drawings available upon request.

Mud ring can be mounted vertically or horizontally . Opening is 2" × 4"

NOTE: (1) With return air grille mounted on unit, dimension becomes 2-⅜" can be field adjusted to 3-⅜" for furred-in applications . (2) Fire Stop, if required, must be provided by the contractor . Field riser location and discharge openings: see page 19 for detail .

CAT 770-15 19 Dimensional Data

Riser Location — FHSS and FHSK Unit Sizes 03 Thru 08 (300 thru 800 cfm) 1 2 3 4 Represent air discharge positions determined by facing return air opening .

Discharge openings with one opening only, locations 1 2 3 4 should be 16" × 12" . With two or more openings, locations 1 2 3 4 should be 16" x 6" .

20 CAT 770-15 Dimensional Data

Model FHSS (Basic Unit) Sizes 10 Thru 12 (1000 thru 1200 cfm)

Recommended Riser Hole Size in Floor (inches) Right hand unit shown RISER ¾ 1 .0 1-¼ 1-½ 2 0. 2-¼ 3 .0 Hand of unit determined by facing A 3-½ 4 .0 4 0. 4-½ 5 0. 5-½ 6 .0 return air opening . • Risers on right = Right hand of unit . (TWO PIPE) B 13-½ 14 .0 14 0. 14-½ 15 .0 15-½ 16 0. • Risers on left = Left hand of unit . • Risers on back = Neutral unit . (FOUR PIPE) B 17 .0 17-½ 17-½ 18 0. 18-½ 19 0. 19-½ All dimensions approximate. Certified drawings available upon request.

Mud ring can be mounted vertically or horizontally . Opening is 2" × 4"

NOTE: (1) With return air grille mounted on unit, dimension becomes 2-⅜" can be field adjusted to 3-⅜" for furred-in applications . (2) Fire Stop, if required, must be provided by the contractor . Field riser location and discharge openings: see page 21 for detail .

CAT 770-15 21 Dimensional Data

Riser Location — FHSS Unit Sizes 10 Thru 12 (1000 thru 1200 cfm) 1 2 3 4 Represent air discharge positions determined by facing return air opening .

DISCHARGE OPENINGS WITH ONE OPENING ONLY, LOCATIONS 1 3 SHOULD BE 24" × 14"; LOCATIONS 2 4 SHOULD BE 16" × 12" .

WITH TWO OR MORE OPENINGS, LOCATIONS 1 2 SHOULD BE 24" × 7"; LOCATIONS 3 4 SHOULD BE 16" × 6"

22 CAT 770-15 Dimensional Data

Riser Location for Master-Slave Units

= Return Air = Discharge Air

Right-Hand Left-Hand Master Slave

Right-Hand Left-Hand Slave Master

Master units ship with risers attached to the unit . These risers Neutral have 3" stub-out’s to match with our slave unit piping . Master Slave units do not have ball valves attached to the valve package. Ball valves must be purchased separately for field installation (see IM 283-8) .

Neutral Slave

CAT 770-15 23 Wiring Diagrams

Figure 5: Typical Fan Cycle Control System Wiring Diagrams – 2-Pipe

Figure 6: Typical Fan Cycle Control System Wiring Diagrams – 4-Pipe

24 CAT 770-15 Wiring Diagrams

Figure 7: 2-Pipe with 1 Circuit Electric Heat Wiring Diagram

Figure 8: 4-Pipe with 1 Circuit Electric Heat Wiring Diagram

CAT 770-15 25 Engineering Guide Specifications

Model FHSS (Basic Unit) Supply & Return Risers – Supply and return risers shall be Sizes 03 thru 08 (300 thru 800 cfm) type “L” copper (optional copper types and diameters shall be as tabulated in the schedule), with 3/4" closed cell flexible Furnish and install where shown on plans Daikin low cfm foam insulation, factory installed ball valves on risers. Slip design HiLine fan coil units. Unit sizes, performance and couplings shall be factory available for field connection. equipment shall be as tabulated in the schedule. Unit Insulation shall meet or exceed current flammability performance shall be substantiated by software-generated classification UL94. output datasheets . Drain Riser – Drain riser shall be PVC. (Optional copper Unit Configuration – Unit shall be (two-pipe)(four-pipe) types and diameters shall be as tabulated in the schedule) . system blow-through configuration with completely Stop type couplings shall be factory available for field removable chassis. Filter, fan assembly, drain line and motor connection . shall be accessible by removing the return air grille panel. Internal controls, service valves, drain pan and coil shall be Control Systems – A unit- or wall-mounted thermostat, accessible by removing the access and sound baffle panel. shall be offered to control fan and/or valve cycling. For Hand of unit shall be tabulated in the schedule . unit mounted thermostats all wiring shall be provided to the control box for easy field installation (optional Molex Cabinet – Cabinet shall be fabricated of heavy-gauge connections shall be available upon request). A 10K galvanized steel and fully insulated with 1/2" multi-density thermistor shall be mounted in all units. The 10K thermistor glass fiber. An insulated galvanized steel access and sound shall be used for factory provided thermostats or for field baffle panel shall completely enclose the coil section. provided controls. The thermostat electrical box shall be Plaster Frame and Return Grille – The return air grille adjustable for any wall thickness up to 3-7/8" and a 1/2" mud panel shall be heavy-gauge steel with a stamped (bar type) ring shall be provided (an optional 5/8" mud ring shall be grille and semi-gloss finish and extend 5/8" in front of unit provided upon request). face. A plaster frame shall be provided to hold the return air Filters – Filters shall be nominal 1" thick throwaway. grille panel away from the wall when the unit is furred in. A snap-on return air grille panel shall be provided with the Discharge Grilles (Optional) – Optional aluminum (single plaster frame . deflection) (double deflection) discharge grilles shall be provided in sizes and positions as tabulated in the schedule. Coils – Units shall be AHRI certified with standard low flow heating/cooling coils in two-pipe systems, or, standard Line-of-Sight Baffle (Optional) – An optional line-of-sight low flow cooling coil plus one-row heating coil in four- baffle shall be supplied as tabulated in the schedule. pipe systems . All coils shall be seamless copper tubes in a Fresh Air Dampers (Optional) – Two-position (motorized) staggered pattern with rippled and corrugated aluminum fins. (manual) fresh air damper shall be factory available as Tubes shall be mechanically expanded into the fin collars for tabulated in the schedule . positive fin-to-tube bond. Coils shall have manual air vents. Electric Heat (Optional) – Electric heating elements and Internal piping shall allow for vertical riser expansion of ±1". controls shall be completely installed, wired and enclosed at Coil performance shall be as tabulated in the schedule . Coil the factory . Heating element shall be fully protected by a high shall be positioned to provide positive condensate drainage. limit cut-out with automatic reset. Fan Assembly – Unit sizes 03 and 04: Fan housings shall be Controls & Valves (Optional) – Valve cycle control for two-piece with integral scroll and inlets. Fan wheels shall be two-pipe (four-pipe) systems, two-way (three-way) motorized DWDI forward curved centrifugal direct drive type. valves and other combinations of ball valves and automatic Unit sizes 06 and 08: Fan housings shall be painted steel with flow metering devices shall be installed as tabulated in the integral scroll and separate inlets. Fan wheels shall be painted schedule . steel DWDI forward curved centrifugal direct type. Twin Units (Optional) – Twin unit configuration, as All fan wheels shall be statically and dynamically balanced. tabulated, shall be such that two adjacent room units will be Motors – Motors shall be permanent split capacitor type piped to a single set of risers and will operate with separate (115/60/1) (277/60/1) with sleeve bearings, oilers, inherent controls on each unit . thermal overload protection with automatic reset and resilient mounts . Drain Pan – Drain pan shall be galvanized (stainless) steel with drain line and closed cell insulation on the external surface to prevent condensation.

26 CAT 770-15 Engineering Guide Specifications

Unit Sizes 10 & 12 (1000 thru 1200 cfm) Supply & Return Risers – Supply and return risers shall be type “L” copper (optional copper types and diameters shall Furnish and install where shown on plans Daikin low cfm be as tabulated in the schedule), with 3/4" closed cell flexible design HiLine fan coil units. Unit sizes, performance and foam insulation, factory installed ball valves on risers. Slip equipment shall be as tabulated in the schedule. Unit couplings shall be factory available for field connection. performance shall be substantiated by software-generated Insulation shall meet or exceed current flammability output datasheets . classification UL94. Unit Configuration – Unit shall be (two-pipe)(four-pipe) Drain Riser – Drain riser shall be PVC. (Optional copper system blow-through configuration with completely types and diameters shall be as tabulated in the schedule) . removable chassis. Filter, fan assembly, drain line and motor Stop type couplings shall be factory available for field shall be accessible by removing the return air grille panel. connection . Internal controls, service valves, drain pan and coil shall be accessible by removing the access and sound baffle panel. Control Systems – A unit- or wall-mounted thermostat, Hand of unit shall be tabulated in the schedule . shall be offered to control fan and/or valve cycling. For unit mounted thermostats all wiring shall be provided to Cabinet – Cabinet shall be fabricated of heavy-gauge the control box for easy field installation (optional Molex galvanized steel and fully insulated with 1/2" multi-density connections shall be available upon request). A 10K glass fiber. An insulated galvanized steel access and sound thermistor shall be mounted in all units. The 10K thermistor baffle panel shall completely enclose the coil section. shall be used for factory provided thermostats or for field Plaster Frame and Return Grille – The return air grille provided controls. The thermostat electrical box shall be panel shall be heavy-gauge steel with a stamped (bar type) adjustable for any wall thickness up to 3-7/8" and a 1/2" mud grille and semi-gloss finish and extend 5/8" in front of unit ring shall be provided (an optional 5/8" mud ring shall be face. A plaster frame shall be provided to hold the return air provided upon request). grille panel away from the wall when the unit is furred in. Filters – Filters shall be nominal 1" thick throwaway. A snap-on return air grille panel shall be provided with the plaster frame . Discharge Grilles (Optional) – Optional aluminum (single deflection) (double deflection) discharge grilles shall be Coils – Units shall be AHRI certified with standard low provided in sizes and positions as tabulated in the schedule. flow heating/cooling coils in two-pipe systems, or, standard low flow cooling coil plus one-row heating coil in four- Line-of-Sight Baffle (Optional) – An optional line-of-sight pipe systems . All coils shall be seamless copper tubes in a baffle shall be supplied as tabulated in the schedule. staggered pattern with rippled and corrugated aluminum fins. Fresh Air Dampers (Optional) – Two-position (motorized) Tubes shall be mechanically expanded into the fin collars for (manual) fresh air damper shall be factory available as positive fin-to-tube bond. Coils shall have manual air vents. tabulated in the schedule . Internal piping shall allow for vertical riser expansion of ±1". Coil performance shall be as tabulated in the schedule . Coil Electric Heat (Optional) – Electric heating elements and shall be positioned to provide positive condensate drainage. controls shall be completely installed, wired and enclosed at the factory . Heating element shall be fully protected by a high Fan Assembly – Unit sizes 03 and 04: Fan housings shall be limit cut-out with automatic reset. two-piece with integral scroll and inlets. Fan wheels shall be DWDI forward curved centrifugal direct drive type. Controls & Valves (Optional) – Valve cycle control for two-pipe (four-pipe) systems, two-way (three-way) motorized Unit sizes 06 and 08: Fan housings shall be painted steel with valves and other combinations of ball valves and automatic integral scroll and separate inlets. Fan wheels shall be painted flow metering devices shall be installed as tabulated in the steel DWDI forward curved centrifugal direct type. schedule . All fan wheels shall be statically and dynamically balanced. Twin Units (Optional) – Twin unit configuration, as Motors – Motors shall be permanent split capacitor type tabulated, shall be such that two adjacent room units will be (115/60/1) (277/60/1) with sleeve bearings, oilers, inherent piped to a single set of risers and will operate with separate thermal overload protection with automatic reset and resilient controls on each unit . mounts . Drain Pan – Drain pan shall be galvanized (stainless) steel with drain line and closed cell insulation on the external surface to prevent condensation.

CAT 770-15 27 Engineering Guide Specifications

Model FHSK (Knock-down Unit) Supply & Return Risers – Supply and return risers shall be Sizes 03 Thru 08 (300 Thru 800 cfm) type “L” copper (optional copper types and diameters shall be as tabulated in the schedule), with 3/4" closed cell flexible Furnish and install where shown on plans Daikin low cfm foam insulation, factory installed ball valves on risers. Slip design HiLine fan coil units. Unit sizes, performance and couplings shall be factory available for field connection. equipment shall be as tabulated in the schedule. Unit Insulation shall meet or exceed current flammability performance shall be substantiated by software-generated classification UL94. output datasheets . Drain Riser – Drain riser shall be PVC. (Optional copper Unit Configuration – Unit shall be (two-pipe)(four-pipe) types and diameters shall be as tabulated in the schedule) . system blow-through configuration with completely Stop type couplings shall be factory available for field removable chassis. Filter, fan assembly, drain line and motor connection . shall be accessible by removing the return air grille panel. Internal controls, service valves, drain pan and coil shall be Control Systems – A unit- or wall-mounted thermostat, accessible by removing the access and sound baffle panel. shall be offered to control fan and/or valve cycling. For Hand of unit shall be tabulated in the schedule . unit mounted thermostats all wiring shall be provided to the control box for easy field installation (optional Molex Cabinet – Cabinet shall be fabricated of heavy-gauge connections shall be available upon request). A 10K galvanized steel and fully insulated with 1/2" multi-density thermistor shall be mounted in all units. The 10K thermistor glass fiber. An insulated galvanized steel access and sound shall be used for factory provided thermostats or for field baffle panel shall completely enclose the coil section. provided controls. The thermostat electrical box shall be Plaster Frame and Return Grille – The return air grille adjustable for any wall thickness up to 3-7/8" and a 1/2" mud panel shall be heavy-gauge steel with a stamped (bar type) ring shall be provided (an optional 5/8" mud ring shall be grille and semi-gloss finish and extend 5/8" in front of unit provided upon request). face. A plaster frame shall be provided to hold the return air Filters – Filters shall be nominal 1" thick throwaway. grille panel away from the wall when the unit is furred in. A snap-on return air grille panel shall be provided with the Discharge Grilles (Optional) – Optional aluminum (single plaster frame . deflection) (double deflection) discharge grilles shall be provided in sizes and positions as tabulated in the schedule. Coils – Units shall be AHRI certified with standard low flow heating/cooling coils in two-pipe systems, or, standard Line-of-Sight Baffle (Optional) – An optional line-of-sight low flow cooling coil plus one-row heating coil in four- baffle shall be supplied as tabulated in the schedule. pipe systems . All coils shall be seamless copper tubes in a Fresh Air Dampers (Optional) – Two-position (motorized) staggered pattern with rippled and corrugated aluminum fins. (manual) fresh air damper shall be factory available as Tubes shall be mechanically expanded into the fin collars for tabulated in the schedule . positive fin-to-tube bond. Coils shall have manual air vents. Electric Heat (Optional) – Electric heating elements and Internal piping shall allow for vertical riser expansion of ±1". controls shall be completely installed, wired and enclosed at Coil performance shall be as tabulated in the schedule . Coil the factory . Heating element shall be fully protected by a high shall be positioned to provide positive condensate drainage. limit cut-out with automatic reset. Fan Assembly – Unit sizes 03 and 04: Fan housings shall be Controls & Valves (Optional) – Valve cycle control for two-piece with integral scroll and inlets. Fan wheels shall be two-pipe (four-pipe) systems, two-way (three-way) motorized DWDI forward curved centrifugal direct drive type. valves and other combinations of ball valves and automatic Unit sizes 06 and 08: Fan housings shall be painted steel with flow metering devices shall be installed as tabulated in the integral scroll and separate inlets. Fan wheels shall be painted schedule . steel DWDI forward curved centrifugal direct type. Twin Units (Optional) – Twin unit configuration, as All fan wheels shall be statically and dynamically balanced. tabulated, shall be such that two adjacent room units will be Motors – Motors shall be permanent split capacitor type piped to a single set of risers and will operate with separate (115/60/1) (277/60/1) with sleeve bearings, oilers, inherent controls on each unit . . thermal overload protection with automatic reset and resilient mounts . Drain Pan – Drain pan shall be galvanized (stainless) steel with drain line and closed cell insulation on the external surface to prevent condensation.

28 CAT 770-15

Total system capability ThinLine™ Fan-coils

HiLine™ Fan-coil

Horizontal Vertical (Slope Top)

Large Capacity Fan-coils

Hideaway

Cabinet Unit Heaters

Vertical Unit Heater Horizontal Unit Heater

Daikin Training and Development

Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com and click on training, or call 540-248-9646 and ask for the Training Department.

Warranty

All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local Daikin Representative for warranty details. Refer to Form 933-430285Y. To find your local Daikin Representative, go to www.DaikinApplied.com.

Aftermarket Services To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787). To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.

This document contains the most current product information as of this printing. For the most up- to-date product information, please go to www.DaikinApplied.com.

Products Manufactured in an ISO Certified Facility.

Daikin Applied 800.432.1342 www.DaikinApplied.com

© 2013 Daikin 01/13