<<

January 2005 / FORM 5-200

The - Chart By Dave Demma, Senior Application Engineer - Supermarket

How often have you heard the statement “it isn’t ?” - The amount of cooling required to Well it may seem a bit picky, but it is not entirely accurate to change (freeze) 1 ton of at 32ºF into at 32ºF, in a 24 say the refrigeration system “cools”. If the system is operating hour period. properly, the refrigerated space should be “” than its sur- roundings, but it is the result of a transfer process. Heat is Btu - British Unit: The amount of heat required to transferred from the refrigerated space to the , and raise 1 lb. of water 1ºF. ultimately from the refrigerant to the ambient (at the condens- er). A lower in the refrigerated space is the 1 Ton - 12,000 Btu/hr byproduct of this process. Perhaps this is a minor shift in thinking, but in viewing the refrigeration system for Fig. 1 illustrates some of these definitions, using water as the what it is…a heat transfer process…a more fundamental medium experiencing a heat transfer process. This graph plots approach for diagnosis may be obtained. the water temperature vs. the enthalpy of the water (heat content in Btu/lb). We all know that water boils at 212ºF (atmospheric In an effort to gain a better understanding of the various heat pressure at sea level). By definition, water at atmospheric pres- transfer processes occurring in a refrigeration system, the pres- sure, at a temperature lower than 212ºF, is subcooled. So, we sure-enthalpy chart can be of great use. Additionally, once start with subcooled water at 42ºF, and begin transferring heat to understood, “the chart” can be a tremendous benefit in analyz- it. Assuming we are working with 1 lb. of water, for every Btu ing the relative health of a refrigeration system. Let’s follow added, a corresponding temperature increase of 1ºF will be the refrigerant on a quick journey through a refrigeration sys- achieved (the definition for one Btu). It we continue to add heat, tem to see what it experiences, and plot it on “the chart” as we eventually the water’s temperature will increase to 212ºF (the go. Before we start, a few technical definitions are in order: saturation temperature at ). At this point, the water begins to change states from a to a (boil). Refrigeration - The achievement of a temperature below that As noted on the graph, the water will experience no further tem- of the immediate surroundings. perature increase…for a given pressure, the saturation () temperature is the highest temperature a liquid can ever achieve. of Fusion - The quantity of heat (Btu/lb) required Increasing the amount of heat transferred to the water simply to change 1 lb. of material from the into the liquid increases the rate at which the water boils. If the temperature of phase. the vapor were to be measured, we’d find it to be 212ºF (saturat- ed vapor). Once the vapor has separated from the liquid, addi- Latent Heat of - The quantity of heat (Btu/lb) tional heat transferred to it will result in a temperature increase. required to change 1 lb. of material from the liquid phase into By definition, the vapor at 232ºF (20º above the saturation tem- the vapor phase. perature), is superheated.

Sensible Heat - Heat that is absorbed/rejected by a material, It is interesting to note that while it takes only 1 Btu to raise 1 resulting in a change of temperature. lb. of water 1ºF, it takes almost 1000 times that amount (966.6 Btu) for the 1 lb. of water to change states from liquid to Latent Heat - Heat that is absorbed/rejected by a material vapor. A boiling liquid will always absorb more heat than a resulting in a change of physical state (occurring at constant vapor experiencing a temperature increase (per unit of mass). temperature). Understanding this principle explains why the in a refrigeration system should always be nearly filled with liquid Saturation Temperature - That temperature at which a liquid refrigerant. Otherwise, its full potential as a heat transfer starts to boil (or vapor starts to condense). The saturation tem- device will not be utilized. perature (boiling temperature) is constant at a given pressure,* and increases as the pressure increases. A liquid cannot be The pressure-enthalpy chart, as shown in Fig. 2, displays all raised above its saturation temperature. Whenever the refriger- the pertinent properties for a given refrigerant (in this example ant is present in two states (liquid and vapor) the refrigerant R22). The bubble to the left is the portion of the diagram where mixture will be at the saturation temperature. the refrigerant is in the saturated condition. The blue line on the left of the bubble represents the 100% saturated liquid line, Superheat - At a given pressure, the difference between a the thin dashed line on the right represents the 100% saturated vapor’s temperature and its saturation temperature. vapor line, and anywhere inside the bubble represents the refrigerant as a mixture of saturated liquid and saturated vapor. - At a given pressure, the difference between a liq- uid’s temperature and its saturation temperature. To the left of the saturated liquid line is the area where the * Except for zeotrope refrigerant can exist at a temperature lower than the saturated Page 2 / FORM 5-200 condition; subcooled liquid. To the right of the saturated vapor Specific volu me is expressed in cu.ft/lb. (see orange line). line is the area where the refrigerant can exist at a temperature higher than the saturated condition; superheated vapor. The - Entropy is the mathematical relationship between critical point is the highest temperature that the refrigerant can heat and temperature, and relates to the availability of . experience, and remain in the liquid form. If the temperature These lines extend at an angle from the saturated vapor line. exceeds the critical point, regardless of pressure, the refriger- Their presence on the chart is relevant in that vapor compres- ant can only exist in the vapor state. sion (in the ideal cycle) occurs at constant entropy (see dark blue line). All of the relevant properties are shown in Fig. 2: Quality - Lines of constant quality appear vertically, and only Pressure - The vertical axis of the chart, in psia (see pink line). within the saturation bubble. The refrigerant within the bubble To obtain gauge pressure, subtract atmospheric pressure. is a mixture of liquid and vapor at saturation, and the quality is the percentage of the mixture which is in the vapor state (see Enthalpy - The horizontal axis of the chart shows the heat con- green line). tent of the refrigerant in Btu/lb. The ultimate goal of the refrigeration system is to get the Temperature - Constant temperature lines generally run in a verti- refrigerant into a condition where it can be useful as a medium cal direction in the superheated vapor & sub-cooled liquid portion to transfer heat from the refrigerated space. If the system of the chart. In the saturated bubble, the constant temperature line design requires a -10ºF space temperature, you would expect is along the horizontal, illustrating that the saturation temperature the refrigerant temperature in the evaporator to be somewhat is constant at a given pressure (see black line). lower…say -20ºF (a 10º temperature difference). This allows the relatively warmer air (something above the design of - Specific - Constant volume lines extend from the red 10ºF) to be blown across the evaporator, flowing relatively line saturated vapor line out into the superheated vapor-por- cooler refrigerant (-20ºF). The result is the transfer of heat tion of the chart at a slight angle from the horizontal axis. from the warmer air to the cooler refrigerant.

Refrigeration

Water at Atmospheric Pressure (14.7 psia pressure)

Boiling at constant pressure and temperature Superheated Saturation 20° Superheat (232°– 212°= 20°) Temperature 232 Vapor 212

Subcooled Latent Heat of Vaporization Temperature (°F) Liquid 966.6 Btu per lb 32

200 400 600 800 1000 1200 Enthalpy (Btu per lb)

Fig. 1 – Water undergoing a change of state. FORM 5-200 / Page 3 The purpose of the is to take a low pressure vapor Enough heat must be transferred from the refrigerant to lower and compress it into a high pressure vapor. This occurs its temperature from 180ºF to the saturation temperature of (in theory) at a constant entropy. In an ideal cycle, the refriger- 100ºF (point #2A on the chart). At this point, can ant vapor would enter the compressor as a saturated vapor…no begin. As heat continues to be transferred from the refrigerant superheat. vapor to the air (or water, if a water cooled is used), the quality of the refrigerant (% of the refrigerant in the vapor The Ideal Cycle state) will continue to decrease, until the refrigerant has been If the operating and are known, the completely condensed. In the ideal system, this occurs at the refrigeration system can be plotted on the P-H diagram. Let’s outlet of the condenser (point #3 on the chart). In the real assume our system is operating at a -20ºF evaporator and world, some subcooling would be expected at the condenser 100ºF condensing. outlet. Subcooled liquid provides insurance against liquid flashing as the refrigerant experiences pressure losses in the The saturated vapor entering the compressor suction would be tubing and components. at -20ºF, illustrated by point #1 in Fig. 3. The vapor is com- pressed, following the constant entropy line to the pressure cor- The refrigerant is in the liquid state now, and at a high pressure responding to 100ºF, or 210.7 psia (point #2). The refrigerant and temperature. It must undergo one more change before it vapor experiences a gain during the mechanical becomes a useful heat transfer medium; a reduction in temper- compression process, resulting in a superheated vapor. This is ature. This is accomplished by reducing the pressure. You can illustrated by the location of point #2, to the right of the saturat- count on the refrigerant’s pressure-temperature relationship to ed vapor line. In the ideal system, which does not consider be an infallible law. If the pressure of a saturated i pressure loss in the valves, refrigerant tubing, etc., point #2 rep- reduced, the law governing its existence requires it to assume resents the outlet of the compressor/inlet of the condenser. the saturation temperature at the new pressure.

In the ideal cycle, the condenser serves as a two-fold compo- So, in order to reduce the temperature, the pressure has to be nent. Before any condensation occurs, the high pressure vapor reduced, and some sort of restriction is required for this to must first be brought to a saturated condition (de-superheated). occur. It would be preferable if the restriction could regulate

SCALE CHANGE -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170180190200

5000 0.12 0.13 0.14 0.15 0.16 0.17 0.18 0.19 0.20 0.21 0.22 0.23 0.24 5000 0.016 0.018 0.020 0.022 0.017 0.25 4000 0.025 4000 0.26 3000 REFRIGERANT 22 0.03 600 3000 580 0.27 0.04 560

200 2000 2000 0.05 540 520 180 500 0.07 0.28 1400 1400 480

160°F 460 1000 1000 Critical Point 440 0.10 420 800 800 0.14 200 – 400 600 380 600 180 – 0.2 180 360

160 – 160 – 340 400 400 onstant Entropy 0.3 140 – 140 – C 320 300 300 Constant Pressure 300 120 – 120 – 0.4 280 0.5 100 – 100 – e e 260 200 200 n n i i 240 0.7 L 80 – 80 – L

140 220 140 d r i 60 – 60 – o 1.0 u 200 100 q p 100 i a 180 Volume L 40 – 40 – V onstant 1.4 80 80 C 160 d d e 60 60 20 – 20 – e 140 2.0 t t a a r 120 r

Pressure (psia) u 40 t 0 – 0 – u 3.0 40 t 100 a a 30 30 S 80 4.0 Constant Temperature S -20 – -20 – 5.0

% 60 20 0 % 20 0 0 40 7.0 1 -40 – -40 – 0 1 14 14 20

10.0

10 y 0 t -60 – i -60 – 14 l 8.0 -20 8.0 a

6.0 u -40 20 6.0

Q lb - °F)

-80 – -80 – -60 / t 4.0 4.0 n 30

a -80 3.0 t 3.0 s 40

-100 – n -100 – 3 2.0 o 50 (ft /lb) 2.0 onstant Entropy (Btu C C

0.38 0.39 0.40 0.37 1.4 1.4 0.36 70 0.35 0.34 -120 – -120 – 0.33 1.0 1.0 0.32 0.31 0.8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.30 0.8 0.29 0.6 0.6 -30 -20 10 3020100- 40 50 807060 90 100 110 120 130 140 150 160 170 180 190 200

SCALE CHANGE Enthalpy (Btu per lb above saturated liquid at -40°F) Fig. 2 – R22 Pressure-Enthalpy Diagram Page 4 / FORM 5-200 itself as the system load demands change. This is exactly what Because the refrigerant must conform to its law of existence, the thermostatic expansion valve does; it is an adjustable when the 210.7 psia (100ºF) liquid experiences the reduction in restriction which causes a reduction in liquid refrigerant pres- pressure to 24.9 psia, it must drop to the new saturation tem- sure, yet will modulate in an effort to maintain constant super- perature of -20ºF. Some of the liquid refrigerant is required to heat at the evaporator outlet. The TEV is a superheat control, boil as a means of removing the heat necessary to achieve this and will not maintain a constant evaporator pressure. It only lower temperature. Yet another heat transfer process, which provides the restriction necessary to reduce the pressure to yields a lower liquid temperature. The liquid that is sacrificed some level, which will be determined by compressor size, TEV in the boiling process explains the increase in refrigerant qual- size, load demand, and system conditions. If a constant evapo- ity. The greater the difference between the liquid temperature rator temperature is required, it can be achieved very simply by and evaporator temperature, the more liquid will have to be maintaining the pressure corresponding to the saturation tem- boiled to achieve the new saturation temperature. This results perature required. This is accomplished by adding an evapora- in an even higher refrigerant quality. tor pressure regulating valve to the system. The final portion of the refrigerant’s journey is as a mixture of Our ideal cycle has experienced a pressure drop in the TEV, saturated liquid and vapor, traveling though the evaporator tub- and for the purpose of discussion we are at a constant 24.9 psia ing. Warm air is blown across the evaporator, where its heat in the evaporator. This is a saturation temperature of -20ºF. You content is transferred to the boiling refrigerant. This is a latent will notice that the refrigerant quality at the TEV inlet was 0%, heat gain to the refrigerant, causing no temperature increase, and has increased to 35% at the evaporator inlet. Subcooling or while experiencing a change of state. In the ideal cycle, the last superheat cannot exist where there is a mixture of liquid and molecule of saturated liquid boils off at the evaporator outlet, vapor. Therefore, any place in the system where the refrigerant which is connected to the compressor inlet. Hence, the vapor exists in two states (the receiver, parts of the evaporator and at the inlet of the compressor is saturated. condenser, the accumulator at times), it will be at the saturation temperature for its pressure. For example, R22 in a saturated The cycle continues this way until the refrigerated space tem- state at 24.9 psia (10.2 psig) will always be at -20ºF. perature is satisfied, and the equipment cycles off.

Enthalpy (Btu per lb above saturated liquid at -40°F)

SCALE CHANGE -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170180190200

5000 0.12 0.13 0.14 0.15 0.16 0.17 0.18 0.19 0.20 0.21 0.22 0.23 0.24 5000 0.016 0.018 0.020 0.022 0.017 0.25 4000 0.025 4000 0.26 3000 REFRIGERANT 22 0.03 600 3000 580 0.27 0.04 560

200 2000 2000 0.05 540 520 180 500 0.07 0.28 1400 1400 480 IDEAL CYCLE 460 0.10 1000 1000 160 440 420 800 800 ° 0.14 F 200 – 400

600 380 C 600 180 – o 0.2 180 360 n Desuperheating Line s t 160 – 160 – 340 a n 400 400 t 320 0.3 140 – 140 – T e 300 3 Condensation Line 2A 2 300 m 0.4 300 120 – 120 – p 280 e r 0.5 a 100 – 260 t 200 200 u

r

240 e r 0.7 80 – 80 – o (

° p 220 140 140 F a )

V 60 – 60 – 1.0 200 d e 100 100 t a 180 40 – 40 – r 1.4 u 80 80 t 160 a S 60 60 Expansion20 L –ine 20 – Com140 pression Line 2.0

120

Pressure (psia) 40 0 – 0 – 3.0 40

100

d i 30 30 u 80 4.0 q i L -20 – -20 – 5.0

60 d e 20 20 t a r 40 7.0 u 4 Line 1 t -40 – -40 – a 14 14 20 S 10.0

10 0 -60 – -60 – 14 8.0 -20 8.0

) 6.0 -40 °F 20 6.0 /lb - -80 – -80 – -60 4.0 4.0 30

-80 3.0 3.0 40 -100 – -100 – 50 Specific Volume (ft3/lb) 2.0 2.0 onstant Entropy (Btu C 0.38 0.39 0.40 0.37 1.4 1.4 0.36 70 0.35 0.34 -120 – -120 – 0.33 1.0 1.0 0.32 0.31 0.8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.30 0.8 0.29 0.6 0.6 -30 -20 10 3020100- 40 50 807060 90 100 110 120 130 140 150 160 170 180 190 200

SCALE CHANGE Fig.3 - Plotting the Ideal Cycle on the P-H Diagram FORM 5-200 / Page 5

Once the system has been plotted, various data points can be Heat of Compression (HOC): This is the amount of heat added read and used for the system design calculations. Admittedly, to the refrigerant from the compression process (represented this information is not typically something the technician will by H2 minus H1 on the chart). need for servicing the refrigeration equipment. However, an understanding of how operating conditions affect system Heat of Rejection (HOR): This is the amount of heat that has design, efficiency, , and particularly com- to be rejected at the condenser…the heat transferred to the pressor performance, should be of great worth to the technician. refrigerant from the refrigerated space (RE), and the heat trans- ferred to the refrigerant during compression (HOC). It is this Data Points and System Design Calculations: value, plus some safety factor, from which the condenser selec- tion is made (represented by H2 minus H3 on the chart). Refrigeration Effect (RE): This is the total heat transfer, in Btu/lb, from the refrigerated space to the refrigerant. H1 minus Refrigerant Circulation Rate (RCR): The amount of refrigerant H4 (H1 is the enthalpy of the refrigerant at point #1 in Fig. 3, in lbs/min which must circulate in the system to meet the and so forth). demands of the load. (200 Btu/min – ton) Note: For the purpose of this discussion, H1 will be considered the RE (Btu/lb) point where the evaporation line intersects with the saturated vapor line. In the real world, the location of H1 would be to the right of the Compressor Required: The horsepower/ton saturated vapor line, reflecting the superheated vapor at the evapora- requirement to meet the load demand. Contrary to popular tor outlet. With an expansion valve maintaining a typical amount of belief, 1 horsepower and 1 ton are not necessarily synonymous. superheat (in the 4° - 6° range for low temperature applications), the heat transferred to the vapor is minimal (less than 1 Btu/lb). The heat RCR (lb/min-ton) X HOC (Btu/lb) X 778 ft-lb/Btu transferred to the vapor between the suction piping outside of the 33,000 ft-lb/min-hp refrigerated space and the compressor cylinder inlet is never consid- ered as part of the refrigeration effect, as this heat was not trans- ferred from the refrigerated space.

SCALE CHANGE -30 -20 -10 0 10 20 30 4040 50 60 70 80 90102 100 110108 120 130135135 140 150 160 170180190200

5000 0.12 0.13 0.14 0.15 0.16 0.17 0.18 0.19 0.20 0.21 0.22 0.23 0.24 5000 0.016 0.018 0.020 0.022 0.017 0.25 4000 0.025 4000 0.26 3000 REFRIGERANT 22 0.03 600 3000 580 0.27 0.04 560

200 2000 2000 0.05 540 520 TYPICAL CYCLE 180 - 1 500 0.07 0.28 1400 1400 480 Open Drive Compressor 460 1000 440 0.10 1000 40°F Suction S.H. @160 Comp. Inlet 800 420 800 F 0.14 200 – 400

600 215°F Discharge Temp. 380 C 600 180 – o 0.2 180 360 n s t 160 – 160 – 340 a n 400 400 t 320 0.3 140 – 140 – T e 300 300 m 0.4 300 120 – 120 – p 280 e r 0.5 a 100 – 260 t 200 200 u

r

240 e r 0.7 80 – 80 – o (

° p 220 140 140 F a )

V 60 – 60 – 1.0 200 d d i e 100 100 u t q a 180 i 40 – 40 – r 1.4 L u 80 80 t d 160 e a t S a 60 60 r 20 – 20 – 140 2.0 u t a

120 S Pressure (psia) 40 0 – 0 – 3.0 40

100 30 30 80 4.0 -20 – -20 – 5.0

60 20 20

40 7.0 -40 – -40 – 14 14 20 10.0

10 0 -60 – -60 – 14 8.0 -20 8.0

6.0 -40 F) 20 6.0 Btu /lb - 3.23 lb -80 – HOR = 135 – 40 = 95 -80 – -60 REF Circulation Rate = 4.0 4.0 lb min - ton 30

-80 3.0 3.0 Btu 2.05 HP 40 -100 – HOC = 27 -100 – COMP HP Req = 50 Specific Volume (ft3/lb) 2.0 onstant Entropy (Btu 2.0 lb C ton 0.38 0.39 0.40 0.37 1.4 1.4 0.36 70 Btu 0.35 7.39 CFM NRE = 62 0.34 COMP VOL Req = -120 – -120 – 0.33 1.0 1.0 0.32 lb 0.31 ton 0.8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.30 0.8 0.29 0.6 0.6 -30 -20 10 3020100- 40 50 807060 90 100 110 120 130 140 150 160 170 180 190 200

SCALE CHANGE Enthalpy (Btu per lb above saturated liquid at -40°F) Fig. 4 – Typical Cycle #1 Page 6 / FORM 5-200

Compressor Volume Required: The compressor cylinder vol- The suction superheat will insure that the compressor is pro- ume requirement needed to the RCR, in cu ft/ton. The tected from liquid flooding. The cost of this protection comes vapor specific volume is read on the lines of constant volume. in the form of a larger compressor volume requirement. This is due to the warmer, thinner suction vapor; at +20ºF the specific RCR (lb/min-ton) X vapor specific volume (cu ft/lb) volume of the vapor (measured in cu.ft./lb) is greater than it was at -20ºF. The compressor’s cylinders are a measured vol- Let’s look at a few typical system scenarios, plot them on the ume...they never change. The of the refrigerant may P-H diagram, and then compare the performance measurements. change, and this will affect the pounds per minute of refriger- ant that the compressor will pump, however the volume Typical Cycle #1 (Fig. 4): It is neither realistic nor safe to have pumped remains constant. So, because the suction vapor is less a saturated vapor at the compressor inlet. Because liquid can- dense, we now require more compressor cylinder volume to not be present with superheated vapor, some amount of pump the same mass flow. superheat at the compressor inlet becomes the margin nec- essary to insure the safety of the compressor. Here we see While all the various data points and system design calcula- the suction vapor superheated to +20ºF (40º superheat). This is tions are listed, they will appear in a comparative chart later. the result of an expansion valve set to maintain some amount of superheat, plus the temperature increase the refrigerant Typical Cycle #1A (Fig. 5): Using an open drive compressor, vapor experiences in the suction line. The suction line connect- with a 20ºF vapor temperature at the compressor inlet, we see ed to the compressor will have some accumulation of on the benefit of subcooling the liquid to 50ºF. Note the change in it. This is the result of the 20°F temperature and mositure refrigerant quality at the TEV outlet. Instead of 65% liquid, we in the air, NOT the result of floodback. Floodback is not pos- now have 80% liquid. Because the difference between liquid sible when the vapor’s temperature is 40° above the saturation temperature and evaporator temperature has been reduced, temperature (40° superheat). Do not confuse frost buildup with there is less refrigerant flashing during the expansion process. floodback. As a result, the TEV and distributor nozzle (if used) can possi- bly be downsized.

SCALE CHANGE -30 -20 -10 0 1022 20 30 4040 50 60 70 80 90102 100 110108 120 130135135 140 150 160 170180190200

5000 0.12 0.13 0.14 0.15 0.16 0.17 0.18 0.19 0.20 0.21 0.22 0.23 0.24 5000 0.016 0.018 0.020 0.022 0.017 0.25 4000 0.025 4000 0.26 3000 REFRIGERANT 22 0.03 600 3000 580 0.27 0.04 560

200 2000 2000 0.05 540 520 TYPICAL CYCLE 180 - 1A 500 0.07 0.28 1400 1400 480 Open Drive Compressor 460 1000 440 0.10 1000 160 800 40°F Suction S.H. @ Comp. Inlet 420 800 F 0.14 200 – 400

600 Liquid Subcooled to 50°F 380 C 600 180 – o 0.2 180 360 n s t 160 – 160 – 340 a n 400 400 t 320 0.3 140 – 140 – T e 300 300 m 0.4 300 120 – 120 – p 280 e r 0.5 a 100 – 260 t 200 200 u

r

240 e r 0.7 80 – 80 – o (

° p 220 140 140 F a )

V 1.0 60 – 60 – 200 d e 100 100 t a 180 40 – 40 – r 1.4 u 80 80 t 160 a S 60 60 20 – 20 – 140 2.0

120

Pressure (psia) 40 0 – 0 – 3.0 40

100

d i 30 30 u 80 4.0 q i L -20 – -20 – 5.0

60 d e 20 20 t a r 40 7.0 u t -40 – -40 – a 14 14 20 S 10.0

10 0 -60 – -60 – 14 8.0 -20 8.0

-40 ) 6.0 F 20 6.0 Btu /lb - 2.5 lb -80 – HOR = 95 -80 – -60 REF Circulation Rate = 4.0 4.0 lb min - ton 30

-80 3.0 3.0 Btu 1.59 HP 40 -100 – -100 – COMP HP Req = HOC = 27 50 Specific Volume (ft3/lb) 2.0 onstant Entropy (Btu 2.0 lb C ton 0.38 0.39 0.40 0.37 1.4 1.4 0.36 70 Btu 0.35 5.73 CFM NRE = 80 0.34 COMP VOL Req = -120 – -120 – 0.33 1.0 1.0 0.32 lb 0.31 ton 0.8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.30 0.8 0.29 0.6 0.6 -30 -20 10 3020100- 40 50 807060 90 100 110 120 130 140 150 160 170 180 190 200

SCALE CHANGE Enthalpy (Btu per lb above saturated liquid at -40°F) Fig. 5 – Typical Cycle #1A FORM 5-200 / Page 7 The use of a liquid to suction will yield sub- seals. The disadvantage is that there is now an in cooled liquid, but at the expense of higher suction vapor tem- the refrigerant circuit (at least on suction vapor cooled hermet- peratures. While this method of subcooling will insure vapor ic ). In addition to the guaranteed system contam- free liquid refrigerant at the TEV inlet, it has little effect on ination problem when a hermetic motor burns, you have the increasing system efficiency. The benefit realized resulting heat from the motor being transferred to the refrigerant vapor. from subcooling will be offset by the higher suction vapor tem- An approximate 80ºF temperature increase can be expected peratures, and the volume requirement penalty they impose. In between the vapor entering the compressor service valve, and this supermarket example the liquid for the low temperature the vapor entering the compressor cylinders. This brings the rack is subcooled using the medium temperature rack. There is suction vapor temperature up to 100ºF, with a corresponding no heat gain to the low temperature rack as a byproduct of the increase in discharge temperature…now approaching 300ºF. subcooled liquid. The refrigerant is subcooled on a rack that is This is the upper limit at which most compressor manufacturers operating between 2 to 2-1/2 horsepower per ton, and the ben- agree shouldn’t be exceeded. The refrigerant vapor at 100ºF efit is being experienced on a rack that is operating near 5 has a specific volume approximately 20% higher than at 20ºF. horsepower per ton. This translates into a compressor volume requirement which will be approximately 20% greater. The higher suction vapor The comparative chart will show the benefits: reduced refrig- temperature also results in a higher HOC, which raises the erant circulation rate, reduced horsepower requirement, and horsepower requirement. reduced compressor volume requirement. If the subcooling can be accomplished very inexpensively, such as ambient subcool- Typical Cycle #3 (Fig. 7): Now, let’s take a look at the real ing with a receiver bypass, the energy savings can be enor- world. It is now the dead of summer – the most extreme condi- mous. For more details on this see Sporlan Form 90-134. tion for the equipment. When the system design and equipment selection was made, it was this summer weather that was used Typical Cycle #2 (Fig. 6): The advantage of using a hermetic as the worst case condition of operation. Now, your company compressor is the elimination of either belts or drive motor was so busy in the winter that the yearly preventative mainte- couplings which require precise alignment, and crankshaft nance was not done. Or perhaps it’s one of those customers who

SCALE CHANGE -30 -20 -10 0 10 20 30 4040 50 60 70 80 90102 100 110 120121121 130 140 150152152 160 170180190200

5000 0.12 0.13 0.14 0.15 0.16 0.17 0.18 0.19 0.20 0.21 0.22 0.23 0.24 5000 0.016 0.018 0.020 0.022 0.017 0.25 4000 0.025 4000 0.26 3000 REFRIGERANT 22 0.03 600 3000 580 0.27 0.04 560

200 2000 2000 0.05 540 520 TYPICAL CYCLE 180 - 2 500 0.07 0.28 1400 1400 480 Hermetic Compressor160 460 1000 1000 40°F Suction S.H. @F Comp. Inlet 440 0.10 420 800 800 0.14 200 – 400 295°F Discharge Temp. C 600 380 o 600 180 – n 0.2 180 360 s t 160 – 340 a 160 – n t 400 400 320 T 0.3 140 – 140 – e m 300 300 300 120 – 120 – p 0.4 280 e r a 0.5 100 – 260 t 200 u 200 r

e 240 r 0.7 80 – 80 – ( o ° 140 p 220 F 140 a )

V 1.0 60 – 60 – 200 d d i e 100 100 u t q a 180 i 40 – 40 – r 1.4 L u 80 80 t d 160 e a t S a 60 60 r 20 – 20 – 140 2.0 u t a

120 S Pressure (psia) 40 0 – 0 – 3.0 40

100 30 30 80 4.0 -20 – -20 – 5.0

60 20 20

40 7.0 -40 – -40 – 14 14 20 120°F Suction Superheat 10.0 10 80°F Vapor Te0 mperature increase from hermetic motor windings -60 – -60 – 14 8.0 -20 8.0

-40 ) 6.0 F 20 6.0 /lb - -80 – Btu-80 – -60 3.23 lb HOR = 152 - 40 = 112 REF Circulation Rate = 4.0 4.0 30 lb -80 min - ton 3.0 3.0 40 -100 – B-100tu – 2.36 HP 50 Specific Volume (ft3/lb) 2.0 HOC = 152 - 121 = 31 COMP HP Ronstanteq Entropy= (Btu 2.0 lb C ton 0.38 0.39 0.40 0.37 1.4 1.4 0.36 70 0.35 Btu 0.34 8.77 CFM -120 – -120 – 0.33 1.0 1.0 NRE = 62 0.32 COMP VOL Req = lb 0.31 ton 0.8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.30 0.8 0.29 0.6 0.6 -30 -20 10 3020100- 40 50 807060 90 100 110 120 130 140 150 160 170 180 190 200

SCALE CHANGE Enthalpy (Btu per lb above saturated liquid at -40°F) Fig. 6 – Typical Cycle #2 Page 8 / FORM 5-200 never wants to spend money on prevention…the one you tell for the vapor trapped in the clearance volume. It too is at the “you can either pay me a little now, or you can pay me a lot discharge pressure. Before any suction vapor can re-enter the more, later”. In either case, the condenser is dirty, and the bot- cylinders, the clearance volume vapor must experience a reduc- tom line is that the condensing temperature has increased; from tion in pressure to a level slightly below that of the suction pres- 100ºF to 120ºF. sure. Otherwise, there would be no flow into the cylinder. It is travel, which increases the cylinder volume, that reduces With the higher discharge pressure, the compression ratio has this clearance volume pressure. This portion of the piston trav- increased from 8.5:1 to 11:1. This higher pressure that the el, which is entirely dedicated to lowering the clearance volume compressor is pumping against has a twofold negative impact. pressure, performs no useful at all. In fact, it is advanta- First, the motor amperage will be higher. Secondly, the volu- geous to keep this to a minimum. The higher the clearance vol- metric efficiency of the compressor will be reduced. ume pressure is above the suction pressure, the more of this wasted piston travel will be required. Simply put, this is the def- There is a pocket of vapor between the bottom of the valve inition of a high compression ratio (substituting discharge pres- plate, and the top of the piston, called the clearance volume. It sure for clearance volume pressure, as they are one and the is there to insure that the piston does not run into the valve same). plate during the operation of the compressor. The vapor in this pocket requires re-expansion to a lower pressure before any Note the higher HOC. Referring to the system design calcula- new suction vapor can enter the compressor’s cylinders. tions reveals that more horsepower will be required. In addi- tion, the quality of the saturated liquid/vapor mixture at the Let’s take a look at the compression cycle. It begins when suc- TEV outlet has further deteriorated, resulting in a lower RE. tion vapor enters a cylinder as its piston is traveling down. As Referring again to the system design calculations will reveal the piston starts to travel back up, reducing the volume of the that the lower the RE is, the higher the RCR has to be. This, in cylinder, the increases. When the piston reaches turn, will require more cylinder volume to meet the demand of the top of its , the entire volume of compressed vapor will an increased RCR. In a typical supermarket there are backup have exited the cylinder through the discharge valves EXCEPT compressors that only operate under high load conditions, so

SCALE CHANGE -30 -20 -10 0 10 20 3040 4045 50 60 70 80 90102 100 110 120121121 130 140152152 1501551 16055 170180190200

5000 0.12 0.13 0.14 0.15 0.16 0.17 0.18 0.19 0.20 0.21 0.22 0.23 0.24 5000 0.016 0.018 0.020 0.022 0.017 0.25 4000 0.025 4000 0.26 3000 REFRIGERANT 22 0.03 600 3000 580 0.27 0.04 560

200 2000 2000 0.05 540 520 TYPICAL CYCLE 180 - 3 500 0.07 0.28 1400 1400 480 Dirty Condenser - 120°F Cond. Temp 460 1000 440 0.10 1000 160 800 Hermetic Compressor 420 800

F 0.14 200 – 400

600 120°F S.H. @ Cylinder Inlet 380 C 600 180 – o 0.2 180 360 n s t 160 – 160 – 340 a n 400 400 t 320 0.3 140 – 140 – T e 300 300 332020°F Dm ischarg0.4e Temp. 300 120 – 120 – p 280 e r 0.5 a 100 – 260 t 200 200 229595°F Duischarge Temp.

r

240 e r 0.7 80 – 80 – o (

° p 220 140 140 F a )

V 60 – 60 – 1.0 200 d e 100 100 t a 180 40 – 40 – r 1.4 u 80 80 t 160 a S 60 60 20 – 20 – 140 2.0

120

Pressure (psia) 40 0 – 0 – 3.0 40

100

d i 30 30 u 80 4.0 q i L -20 – -20 – 5.0

60 d e 20 20 t a r 40 7.0 u t -40 – -40 – a 14 14 20 S 10.0

10 0 -60 – -60 – 14 8.0 Btu -20 Btu 3.5 lb 8.0 HOR @ 100°F = 112 HOR @ 120°F = 110 REF Circulation) Rate = 6.0 lb -40 lb F min - ton 20 6.0 /lb -

-80 – -80 – -60 4.0 4.0 Btu Btu 2.81 HP 30 HOC @ 100°F = 31 HOC-80 @ 120°F = 34 COMP HP Req = 3.0 lb 3.0 lb ton 40 -100 – -100 – 50 Specific Volume (ft3/lb) 2.0 Btu Btu onstant Entropy (Btu 9.54 CFM 2.0 NRE @ 100°F Cond. = 62 NRE @ 120°F Cond. = 57 CCOMP VOL Req = lb 0.38 0.39 0.40 ton lb 0.37 1.4 1.4 0.36 70 0.35 0.34 -120 – -120 – 0.33 1.0 1.0 0.32 0.31 0.8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.30 0.8 0.29 0.6 0.6 -30 -20 10 3020100- 40 50 807060 90 100 110 120 130 140 150 160 170 180 190 200

SCALE CHANGE Enthalpy (Btu per lb above saturated liquid at -40°F) Fig. 7 – Typical Cycle #3 FORM 5-200 / Page 9 extra capacity is not a problem. For the store owner, paying for So, this makes sense…if a lower discharge air temperature is the additional to operate the extra compressor(s) required, what easier way is there to accomplish it? By reduc- might be a major problem. ing the refrigerant pressure in the evaporator, the saturation temperature will be reduced. This allows for a higher tempera- Finally, the discharge temperature has increased to 320ºF. At ture difference between the air entering the evaporator and the this elevated temperature the mineral oil’s lubrication qualities heat transfer medium (the refrigerant), resulting in a higher rate will be diminished. Additionally, at 320ºF mineral oil will most of heat transfer…or in simple terms a lower discharge air tem- certainly start to decompose. Under certain circumstances, the perature. There is only one problem. The EPR is already wide refrigerant (R22) may start to decompose as well. All of this open. Hey…how about lowering the set point for the common spells a short destructive life for the compressor. suction pressure on the rack’s energy management control sys- tem. There’s plenty of extra horsepower in the form of idle Typical Cycle #4 (Fig. 8): Now for the double whammy. Not compressors, so capacity isn’t an issue…just bring another only is the condenser filthy, but the TEV’s were never adjust- compressor on. ed. They are operating at abnormally high superheats, which in effect have reduced the size of the . As a result, the With a simple adjustment, the fixture lineup’s discharge air discharge air temperature in the frozen food display temperature can be brought in line. The pressure set point is cases is too high, causing the frozen juice to melt. lowered to 20 psia (-29ºF). Simple…yes…but there’s a doozy of a problem with this approach. Because it is the dead of summer, and the service call log is overflowing, a quick solution to this problem would be great. Lowering the suction pressure will increase the compression So, in order to compensate for the high discharge air tempera- ratio: in this example from 11:1 to 13.6:1…an approximate tures in the fixture lineup mentioned above, the service techni- 20% increase over the compression ratio in Typical Cycle #3. cian decides to lower the EPR setting. It doesn’t occur to him This further reduces the compressor , and that a -20ºF saturated suction temperature should be low increases the horsepower requirement. enough to achieve a -10ºF discharge air temperature.

SCALE CHANGE -30 -20 -10 0 10 20 30 4045 50 60 70 80 90102 100 110 120124124 130 140 150 160165165 170180190200

5000 0.12 0.13 0.14 0.15 0.16 0.17 0.18 0.19 0.20 0.21 0.22 0.23 0.24 5000 0.016 0.018 0.020 0.022 0.017 0.25 4000 0.025 4000 0.26 3000 REFRIGERANT 22 0.03 600 3000 580 0.27 0.04 560

200 2000 2000 0.05 540 520 TYPICAL CYCLE 180 - 4 500 1400 0.07 0.28 1400 Dirty Condenser - 120°F Cond. Temp 480 460 1000 440 0.10 1000 Hermetic Compressor160 800 420 800 F 0.14 130°F S.H. @ Cylinder Inlet200 – 400

600 380 C 600 180 – o 0.2 Suction Pressure lowered to 20 psia (-29°F180) 360 n s t 160 – 160 – 340 a n 400 400 t 320 0.3 140 – 140 – T e 300 300 m 0.4 300 120 – 120 – p 280 e r 0.5 a 100 – 100 – 260 t 200 200 u

r

240 e r 0.7 80 – 80 – o (

° p 220 140 140 F a )

V 60 – 60 – 1.0 200 d e 100 100 t a 180 40 – 40 – r 1.4 u 80 80 t 160 a S 60 60 20 – 20 – 140 2.0

120

Pressure (psia) 40 0 – 0 – 3.0 40

100

d i 30 30 u 80 4.0 q i L -20 – -20 – 5.0

60 d e 20 20 t a r 40 7.0 u t -40 – -40 – a 14 14 20 S 10.0

10 0 -60 – -60 – 14 8.0 -20 8.0

6.0 -40 F) 20 6.0 Btu /lb - 3.51 lb -80 – HOR = 120 -80 – -60 REF Circulation Rate = 4.0 4.0 lb min - ton 30

-80 3.0 3.0 Btu 3.4 HP 40 -100 – -100 – COMP HP Req = HOC = 41 50 Specific Volume (ft3/lb) 2.0 onstant Entropy (Btu 2.0 lb C ton 0.38 0.39 0.40 0.37 1.4 1.4 0.36 70 Btu 0.35 12.42 CFM NRE = 57 0.34 COMP VOL Req = -120 – -120 – 0.33 1.0 1.0 0.32 lb 0.31 ton 0.8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.30 0.8 0.29 0.6 0.6 -30 -20 10 3020100- 40 50 807060 90 100 110 120 130 140 150 160 170 180 190 200

SCALE CHANGE Enthalpy (Btu per lb above saturated liquid at -40°F) Fig. 8 – Typical Cycle #4 Page 10 / FORM 5-200 The lower the suction pressure is, the higher the refrigerant’s Compressor Horsepower: We can all relate to horsepower. specific volume will be, which translates into a greater com- The higher the horsepower requirement, the higher the electric pressor volume requirement. Simply reducing the suction pres- bill will be at the end of the month. The subcooled liquid sure has resulted in a 30% increase in volume requirement over reduced the horsepower requirement. Because the refrigerant Typical Cycle #3. quality was reduced at the outlet of the TEV (more liquid pres- ent), it was used more efficiently. Therefore less of it was The final blow is a higher discharge temperature, which is now requ ired to circulate, which caused a reduction in the horse- approaching 370ºF…way beyond any margin of safety. It’s required. guaranteed that the mineral oil will vaporize off the cylinder walls. This leaves the compressor’s metal to metal moving HOC and RCR are the two values which will determine the parts vulnerable to accelerated wear, and certain failure. A look horsepower requirement. We see a 20% increase in the horse- in the crankcase will reveal a black sludge where oil used to be. power requirement in Typical Cycle #3 (as compared to The crankshaft lubrication passages are now in danger of plug- Typical Cycle #2). This comes from the discharge pressure ging up with the oil breakdown. It’s quite possible that some of being raised (from 210 psia to 274 psia, an increase in the this oil breakdown will end up in TEV ports, which will leave HOC). Such an easy thing to keep the condenser clean; yet them unable to control proper superheat. Unless preventative how huge the impact is, if not done. measures are taken, this compressor is headed for the scrap heap. In addition, the operation has become extremely ineffi- In Typical Cycle #4 the suction pressure is lowered from 24 cient, resulting in even higher energy costs. psia to 19 psia. This 5 psi reduction in suction pressure results in a 20% increase in the system horsepower requirement as Let’s take a look at the chart comparing the system design cal- well. The lower suction pressure yields a smaller refrigeration culations of the various cycles discussed. This can be seen in effect, which results in a higher RCR. It also to a higher Fig. 9. The important values to look at are: HOC. Since lowering the suction pressure will increase the HOC and RCR, it is important to keep the suction pressure as Compression Ratio: The ratio of absolute discharge high as possible. pressure/absolute suction pressure. The compressor motor amperage will increase as the compression ratio increases. Compressor Volume: The compressor horsepower and the Also, the higher compression ratio results in reduced compres- cylinder volume requirement are independent of one another. sor volumetric efficiency. The net result is that it will take more We see that from Typical Cycle #1 where there is no suction energy to run a less efficient compressor. So, additional com- superheat, to Typical Cycle #2 where there is 40º of superheat, pressors will have to operate to compensate for this. there is an approximate 20% increase in the cylinder volume requirement. The horsepower remains constant, however. It is Discharge Temperature: A good measure of the relative health the warmer, thinner suction vapor which drives the volume or sickness of the system. Most compressor manufacturers requirement up. One can see the tremendous penalty for using highly suggest the discharge temperature be kept below 300ºF. a hermetic compressor. Perhaps the reduced maintenance off- It is not realistic to put a temperature probe inside the cylinder sets the higher power bills. While high suction superheat to monitor temperature. Experience has shown that the dis- increases the vapor specific volume (cu. ft./lb), it is the lower charge temperature 6” from the discharge service valve will be suction pressure in Typical Cycle #4 which has the greatest between 50º - 75º less than the actual discharge temperature. In impact on increasing the specific volume. addition to cleaning condensers, discharge temperatures can be reduced by proper expansion valve setting, compressor body There is a threefold negative affect from lower suction pressure: cooling motors, good suction line insulation, liquid injec- tion and…keeping the suction pressure as high as possible. For First, it will cause an increase in compression ratio, and more details regarding discharge temperatures and liquid injec- the resulting decrease in volumetric efficiency. Lowering tion, refer to Sporlan Form 10-197. the suction pressure by a few pounds will result in a much greater increase to the compression ratio than by Refrigerant Circulation Rate: The larger this number is, the raising the discharge pressure the same amount. more compressors will be required in operation to achieve capacity. It would be ideal to search out ways to reduce the Secondly, the refrigerant’s specific volume increases amount of refrigerant to be pumped. Anything that affects the with a decrease in pressure. As the specific volume refrigerant quality at the TEV outlet will influence the RCR. increases (a decrease in density), more cylinder volume It’s not how much refrigerant we are feeding to the TEV, but is required to pump the same mass flow. how much of it remains after the expansion process, for the liq- uid refrigerant remaining is our only medium for transferring Thirdly, the compression process follows the constant heat from the refrigerated space. Higher condensing tempera- entropy lines. Therefore, the lower the suction pressue is, tures have a negative affect on this. Notice the great reduction while following a constant entropy line during compres- in the RCR where liquid subcooling is employed. Again, if the sion to a given condensing pressure, the higher the result- subcooling can be accomplished inexpensively, the potential ing discharge temperature will be. This has destructive for savings is great. It was the increase in discharge pressure consequences on the chemicals in the system, of which in (temperature) in Typical Cycle #3 which increased the RCR. part the compressor relies on for a long life. FORM 5-200 / Page 11 The simplest way to insure against abnormally low suction While several “realistic” system scenarios have been plotted pressure is to set the expansion valve for the proper superheat. and dissected, as stated earlier there are still some aspects of When the TEV is set properly, the evaporator is efficiently each cycle that are represented in an ideal fashion. There are used as a heat transfer device due to the boiling liquid present pressure losses in the tubing, valves, accessories, etc. which through most of its tubing length. High superheat settings are not shown. The compression process occurs at a constant reduce the amount of liquid available for heat transfer, in effect entropy ONLY in the ideal cycle. In the real world, entropy reducing the evaporator capacity. This can be negated by low- will increase during the compression process, resulting in even ering the suction pressure, which lowers the saturation temper- higher discharge temperatures and HOC values. These factors ature, and yields a higher temperature difference between the should not detract from the basic focus of this article: to give entering air and the refrigerant. Evaporator capacities increase one a solid foundation of the refrigeration cycle, based on what as the TD increases, so this allows for proper product temper- happens to the refrigerant as it travels throughout the system, ature. It is done at the expense of lower suction pressure, and and how the operating conditions can influence the relative the negative impact it has on system health. health and efficiency of the system.

REFRIGERANT 22 Comparative Data with Varying Conditions Evaporator Temp Suction Temp Suction Superheat Condenser Temp Discharge Temp Compressor Ratio Discharge Superheat Heat of Compression Heat of Rejection Refrigeration Effect COP REF Circulation Rate Comp Reqd HP Vapor Vol Spec Comp Req Vol (°F) (°F) (°F) (°F) (°F) (°F) Btu/lb Btu/lb Btu/lb lb/min-ton hp/ton cu ft/lb cfm/ton Ideal Cycle -20 -200 100 180 8.5 80 27 89 62 2.30 3.23 2.05 2.07 6.68

Typical Cycle - 1 Open Drive Compressor -20 2040 100 215 8.5 115 27 95 62 2.30 3.23 2.05 2.29 7.39 (40°F Suction S.H.)

Typical Cycle - 1A Open Drive Compressor -20 2040 100 215 8.5 115 27 95 80 2.96 2.50 1.59 2.29 5.73 (40°F Suction S.H.) Liquid subcooled to 50°F

Typical Cycle - 2 Hermetic Compressor (add 80°F S.H.) -20 100 120 100 295 8.5 195 31 112 62 2.00 3.23 2.36 2.72 8.77 120°F S.H. vapor entering cylinders

Typical Cycle - 3 Hermetic Compressor (add 80°F S.H.) -20 100120 120 320 11.1 200 34 110 57 1.68 3.51 2.81 2.72 9.54 120°F S.H. vapor entering cylinders Dirty Condenser (120°F Cond. Temp)

Typical Cycle - 4 Hermetic Compressor (add 80°F S.H.) 120°F S.H. vapor entering cylinders -30 100130 120 365 13.9 245 41 120 57 1.39 3.51 3.39 3.54 12.42 Dirty Condenser - 120°F Cond. Temp Suction pressure lowered to compensate for starving TEV's

Fig. 9 – Comparison of System Design Calculations Printed in the U. S. of A. © Copyright 2005 Parker Hannifin Corporation, Washington, Missouri 105