IAPMO Uniform Codes Highlights
Total Page:16
File Type:pdf, Size:1020Kb
Load more
Recommended publications
-
Article 5A. Mechanical Code
ARTICLE 5A. MECHANICAL CODE 4-5a01. UNIFORM MECHANICAL CODE INCORPORATED. The Uniform Mechanical Code, 1997 edition, including Appendix A, prepared and published by the International Conference of Building Officials, 5360 Workman Mill Road, Whittier, California 90601-2298 is hereby adopted and incorporated by reference as authorized by K.S.A. 12-3009 to 12-3012 inclusive, for the purpose of establishing rules and regulations for mechanical systems installed or modified in the city and jurisdiction thereof, except as otherwise provided in this article. Not less than three copies of the Uniform Mechanical Code, 1997, shall be marked or stamped “Official Copy as Incorporated by the Code of the City of Ulysses,” and shall be filed with the city clerk to be open for inspection and available to the public at all reasonable hours. Persons charged with the enforcement of this code shall be supplied copies at the cost of the city. (Ord. 1025, Sec. 1) 4-5a02. PERMIT FEES. Table 1A of the Uniform Mechanical Code is amended by deleting the original language and substituting the following: (a) For the issuance of each permit - $5; (b) For the installation or relocation of each forced-air or gravity- type furnace or burner, including ducts and vents attached to such appliance, up to and including 10,000 BTU's - $6; (c) For the installation or relocation of each floor furnace, including vent; or each suspended heater, recessed wall heater or floor mounted unit heater - $6; (d) For the installation, relocation or replacement of each appliance vent installed -
Table No. 1-A Uniform Mechanical Code
1997 EDITION TABLE NO. 1-A UNIFORM MECHANICAL CODE * This is a “fixed fee” based permit schedule. * Permit Issuance and Heaters 1. For the issuance of each mechanical permit………………………………….. $23.50 2. For issuing each supplemental permit for which the original permit has not expired, been canceled or finaled……………………………………………….. 7.25 Unit Fee Schedule (Note: The following do not include permit-issuing fee.) 1. Furnaces For the installation or relocation of each forced-air or gravity-type furnace or burner, including ducts and vents attached to such appliance, up to and including 100,000Btu/h(29.3W)…………………………………………………………… 14.80 For the installation or relocation of each forced-air or gravity-type furnace or burner, including ducts and vents attached to such appliance over 100,000 Btu/h(29.3kW).………………………………………………………………….. 18.20 For the installation or relocation of each floor furnace, including vent……………………………………………………….....................………… 14.80 For the installation or relocation of each suspended heater, recessed wall heater or floor-mounted unit heater………………………………………….…………. 14.80 2. Appliance Vents For the installation, relocation or replacement of each appliance vent installed and not included in an appliance permit..…..……...…...................................…… 7.25 3. Repairs or Additions For the repair of, alteration of, or addition to each heating appliance, refrigeration unit, cooling unit, absorption unit, or each heating, cooling, absorption or evaporative cooling system, including installation of controls regulated by the Mechanical Code……………………………………………….. 13.70 4. Boilers, Compressors and Absorption Systems For the installation or relocation of each boiler or compressor to and including 3 horsepower (10.6kW), or each absorption system to and including 100,000 B~ (29.3kW)……..……………….....................……………………………………. -
Cross-Connection Control Manual and Design Criteria for Cross-Connection Control Plans, Ordinances, and Policies
CROSS-CONNECTION CONTROL MANUAL AND DESIGN CRITERIA FOR CROSS-CONNECTION CONTROL PLANS, ORDINANCES, AND POLICIES DIVISION OF WATER SUPPLY TENNESSEE DEPARTMENT OF ENVIRONMENT AND CONSERVATION 2008 1. TABLE OF CONTENTS Tennessee Department of Environment and Conservation Guidelines…………..…………….……................. p.1 Definition of Terms............................................................................................................................................p.3 CHAPTER I. Introduction to Backflow Prevention…………………………………………………………..…....…....…..p.6 1.1 Introduction 1.2 Objective 1.3 Causes of Backflow 1.3.1 Backsiphonage 1.3.2 Backpressure II. Responsibility and Authority for Cross-Connection Control…………………………………………….....p.9 2.1 Responsibility 2.1.1 The Water Purveyor 2.1.2 The Customer 2.1.3 Plumbing Inspection Agencies 2.1.4 Installers and Maintenance Personnel 2.1.5 Tennessee Department of Environment and Conservation 2.1.6 Legal Consideration 2.2 Authority 2.2.1 General Discussion 2.2.2 Local Authority 2.2.3 State Wide Authority 2.2.4 Federal Authority III. Developing and Implementing a Cross-Connection Control Program………………………………..….p.14 3.1 Introduction 3.2 Outline of Considerations in Preparing a Plan 3.3 Discussions of Local Cross-Connection Control Plan 3.4 Implementation of the Cross-Connection Control Plan 3.5 Establishing Priorities for Investigation IV. Recommended Practices……………………………………………………………………………………...p.19 4.1 Basic Consideration 4.2 Premises Isolation 4.3 Situations Requiring Maximum Protection 4.4 Establishments -
Cross-Connection Questions, Answers & Illustrations
50 Cross-Connection Questions, 5Answers & Illustrations0 Relating to Backflow Prevention Products and Protection of Safe Drinking Water Supply watts.com What is backsiphonage? 1 Backsiphonage is the reversal of normal flow in a system caused by a negative pressure (vacuum or partial vacuum) in the supply piping. What factors can cause backsiphonage? 2 Backsiphonage can be created when there is stoppage of the water supply due to nearby firefighting, repairs or breaks in city main, etc. The effect is similar to the sipping of a soda by inhaling through a straw, which induces a flow in the opposite direction. What is backpressure backflow? 3 Backpressure backflow is the reversal of normal flow in a system due to an increase in the downstream pressure above that of the supply pressure. Supply Feed Valve What factors can cause a 4 backpressure backflow condition? Backpressure backflow is created whenever the downstream pressure exceeds the supply pres- sure which is possible in installations such as heating systems, elevated tanks, and pressure-producing systems. An example Return would be a hot water space-heating boiler operating under 15-20 Boiler lbs. pressure coincidental with a reduction of the city water supply below such pressure (or higher in most commercial boilers). As wa- ter tends to flow in the direction of least resistance, a backpressure backflow condition would be created and the contaminated boiler water would flow into the potable water supply. What is a cross-connection? 5 A cross-connection is a direct arrangement of a piping line which allows the potable water supply to be connected to a line which contains a contaminant. -
Low-Volume Irrigation Systems for Blueberry with Chemigation and Fertigation Suggestions
Low-Volume Irrigation Systems for Blueberry with Chemigation and Fertigation Suggestions Erick Smith, Department of Horticulture, UGA Tifton campus Wesley Porter, Crop and Soil Sciences, UGA Tifton campus Jonathan Oliver, Department of Plant Pathology, UGA Tifton campus Drip, trickle, microemitters, and subsurface irrigation systems are considered low-volume irrigation. Low-volume irrigation systems are designed to improve irrigation efficiency, delivering water to the crop accurately with minimal water loss. Irrigation efficiency (Table 1) can be categorized into two main concepts: water loss and uniform application. If water loss is significant, or application uniformity is poor, efficiency will be low. Generally, the most significant loss of irrigation water is from overwatering, where the water percolates below the root zone, or from runoff. With good management, losses due to leaks, system drainage, and flushing of filters and lateral lines should not exceed 1%. Low- volume systems have the opportunity to achieve efficiency, and under careful management, will minimize losses from overirrigation. However, using low-volume systems requires increased irrigation frequency and soil moisture monitoring should be used to improve water-use efficiency. Uniformity is desired for each application of water, meaning that the irrigated area receives the same portion of water throughout. A well-designed irrigation system accounts for variability by applying water based on the soil structure (e.g. sandy, silt, loam, clay, and organic matter) and environmental conditions (e.g. wind, temperature, and cloud cover). That said, systems can have losses inherent to the design (Table 1). There may be variability in efficiencies that are noticeable even when comparing low-volume emitters (i.e. -
2018 Uniform Mechanical Code Preface
SOUTHERN NEVADA AMENDMENTS TO THE 2018 UNIFORM MECHANICAL CODE PREFACE This document was developed by the Southern Nevada Building Officials' Uniform Mechanical Code (UMC) Committee and presents recommended amendments to the 2018 Uniform Mechanical Code as published by the International Association of Plumbing and Mechanical Officials (IAPM0). Participation in the 2018 UMC Committee was open to all interested parties. However, voting on amendment proposals was limited to one vote each for six of Southern Nevada municipalities (Clark County, Henderson, Las Vegas, North Las Vegas, Boulder City, and Mesquite), the Clark County School District, and three industry representatives. All committee proceedings were conducted in accordance with Robert's Rules of Order. The recommended amendments contained herein are not code unless adopted and codified by governmental jurisdictions. These amendments are not intended to prevent the use of any material or method of construction not specifically prescribed herein, provided any alternates have been approved and their use authorized by the Building Official. This document may be copied and used in whole or in part without permission or approval from the organizations listed on the cover page. Page 2 of 8 Dated: July 3, 2018 Table of Contents Chapter1: Administration 4 Section 203 Definitions Section 304.3.1.2 Permanent Ladders Section 304.4 Appliances in Attics and Under-Floor Spaces Section 504.4 Clothes Dryers 5 Section 504.4.2.1 — Length Limitation Section 510.1.6.1 Bracing and Supports Section 511.2.2.1.1 Performance Test Section 603.4.1 Length Limitation 6 Section 603.13 Air Dispersion Systems Section 608.1 Automatic Shutoffs Section 802.6.1 Termination Requirements Section Chapter 10, Boilers and Pressure Vessels 7 Section 1301.2 Dry Gas Section 1310.1.6 Piping Underground Beneath Buildings Section 1701.1 Standards 8 Page 3 of 8 Dated: July 3, 2018 Section Chapter 1: Administration Delete Chapter 1 in its entirety, except for sections 101.1, 101.2 and 101.3. -
Code Change No: M2-07/08
DOCUMENTATION Code Change No: M2-07/08 Original Proposal Section: 202 Proponent: Bob Eugene, Underwriters Laboratories, Inc. Revise definition as follows: COMBINATION FIRE/SMOKE DAMPER (Supp). A listed device installed in ducts and air transfer openings designed to close automatically upon the detection of heat and resist the passage of flame and smoke. The device is installed to operate automatically, and be controlled by a smoke detection system, and where required, is capable of being positioned from a fire command center. Reason: To provide a consistent definition throughout all the I-codes. The phrase that is added is consistent with the IBC and IMC and is appropriate for the IMC as well considering that the bulk of the smoke control system is installed to the requirements of the IMC. Cost Impact: The code change proposal will not increase the cost of construction. Public Hearing Results Committee Action: Approved as Submitted Committee Reason: The additional phrase makes the definition consistent with the IBC definition. Assembly Action: None Final Hearing Results M2-07/08 AS Code Change No: M3-07/08 Original Proposal Sections: 202 (IFC [M] 602.1) Proponent: Richard Swierczyna, Architectural Energy Corporation, representing the Commercial Kitchen Ventilation Technical Interest Group Revise definition as follows: HOOD (IFC [M] HOOD). An air intake device used to capture by entrapment, impingement, adhesion or similar means, grease, moisture, hot air and similar contaminants before they enter a duct system. Type I. A kitchen hood for collecting and removing grease vapors and smoke. Such hoods are equipped with a fire suppression system. Type II. -
Cross Connections
Cross Connections A cross connection is a direct connection of a non-potable water source with a potable source. Cross connections can result in serious illness and even death. Backflow can be the result of a cross connection, which can affect water quality and create health problems. One of the most notorious incidents of cross connection was the 1969 “Holy Cross Episode,” when many members of the Holy Cross football team developed infectious hepatitis as a result of contact with contaminated water pooled around a sprinkler head. The water supply became contaminated when a partial vacuum in the water distribution system was created due to a nearby fire, which drew contaminated water back into the potable water supply. Another backflow contamination case occurred in Minnesota in 1978 after an herbicide was backsiphoned from a farmer’s tank truck into a city’s water system. The farmer filled his water tank from a hose by the city’s water plant. The water pressure suddenly dropped and the pesticide in the truck was siphoned into the city’s water system. Fortunately, no illness from the contamination occurred, but the city had to limit its water use until the entire system could be flushed and refilled with safe water. BACKFLOW Backflow is defined as undesired, reversed flow of liquid in a piping system. Backflow can be caused by back siphonage, back pressure, or a combination of the two. Back-siphonage backflow occurs when there is a partial vacuum (negative pressures) in a water- supply system, drawing the water from a contaminated source into a potable water supply. -
Chapter 6 Water Supply and Distribution
ChaPTer 6 WaTer SuPPlY and diSTribuTion 601.0 hot and Cold Water required. TION: NONPOTABLE GRAY WATER, DO 601.1 general. Except where not deemed necessary for NOT DRINK” in yellow letters (Pantone 108 safety or sanitation by the Authority Having Jurisdiction, or equivalent). each plumbing fixture shall be provided with an adequate (2) Reclaimed (recycled) water systems shall be supply of potable running water piped thereto in an marked in accordance with this section with approved manner, so arranged as to flush and keep it in a the words: “CAUTION: NONPOTABLE clean and sanitary condition without danger of backflow or RECLAIMED (RECYCLED) WATER, DO cross-connection. Water closets and urinals shall be flushed NOT DRINK” in black letters. by means of an approved flush tank or flushometer valve. (3) On-site treated water systems shall be marked Exception: Listed fixtures that do not require water for in accordance with this section with the their operation and are not connected to the water supply. words: “CAUTION: ON-SITE TREATED In occupancies where plumbing fixtures are installed NONPOTABLE WATER, DO NOT DRINK” for private use, hot water shall be required for bathing, in yellow letters (Pantone 108 or equivalent). washing, laundry, cooking purposes, dishwashing or main- (4) Rainwater catchment systems shall be marked tenance. In occupancies where plumbing fixtures are in accordance with this section with the installed for public use, hot water shall be required for words: “CAUTION: NONPOTABLE RAIN- bathing and washing purposes. This requirement shall not WATER WATER, DO NOT DRINK” in yel- supersede the requirements for individual temperature con- low letters (Pantone 108 or equivalent). -
Code Check Plumbing & Mechanical®
INTRODUCTION u ABBREVIATIONS ® Code 3Check Plumbing & Mechanical Fifth Edition By DOUGLAS HANSEN, SKIP WALKER, & REDWOOD KARDON Illustrations & layout by Paddy Morrissey © 2019 by The Taunton Press, Inc. ISBN 978-1-631186-947-1 Code Check® is a trademark of The Taunton Press, Inc., registered in the U.S. Patent & Trademark Office Code Check Plumbing & Mechanical 5th Edition is a guide to important code KEY TO USING CODE CHECK requirements and common code violations in the plumbing and Mechanical systems of 1- & 2-family dwellings & townhouses. The main codes referenced in this book Code Check Plumbing & Mechanical condenses large amounts of code informa- are the plumbing and mechanical provisions of the 2015 International Residential tion by using “shorthand” conventions that are explained here. Each text line begins ® Code for One- and Two-Family Dwellings (IRC), the 2015 Uniform Plumbing with a checkbox and ends with the code citations. The first code citation is typically Code (UPC), and the 2015 Uniform Mechanical Code (UMC). These codes are the from the IRC, and the second from the UPC or UMC. The following example is most widely used throughout the United States. Other referenced codes used in the taken from p.14 under the topic of plumbing vents: book are listed below in Table 1 (T1). NFPA 54, the National Fuel Gas Code, is the basis for the fuel gas provisions of the IRC, UPC, and UMC. n All fixture traps req venting _______________________ 3101.2.1 901.2 Model codes are published on a three year cycle. Codes are adopted at different This line is stating that all fixture traps require venting, and the rule is found in times in different places around the country. -
Building Air Intake and Exhaust Design
CHAPTER 46 BUILDING AIR INTAKE AND EXHAUST DESIGN Exhaust Stack and Air Intake Design Strategies........................................................................... 46.1 Geometric Method for Estimating Stack Height ........................................................................... 46.5 Exhaust-To-Intake Dilution or Concentration Calculations......................................................... 46.7 Other Considerations.................................................................................................................. 46.10 UTDOOR air enters a building through its air intake to provide O ventilation air to building occupants. Likewise, building ex- haust systems remove air from a building and expel the contaminants to the atmosphere. If the intake or exhaust system is not well de- signed, contaminants from nearby outdoor sources (e.g., vehicle ex- haust, emergency generators, exhaust stacks on nearby buildings) or from the building itself (e.g., laboratory fume hood exhaust, plumb- ing vents) can enter the building before dilution. Poorly diluted con- taminants may cause odors, health impacts, and reduced indoor air quality. This chapter discusses proper design of exhaust stacks and placement of air intakes to avoid adverse air quality impacts. Chapter 24 of the 2017 ASHRAE Handbook—Fundamentals de- scribes wind and airflow patterns around buildings in greater detail. Related information can also be found in Chapters 9, 18, 33, 34, and 35 of this volume, Chapters 11 and 12 of the 2017 ASHRAE Hand- Fig. 1 Flow Recirculation Regions and Exhaust Parameters book—Fundamentals, and Chapters 29, 30, and 35 of the 2016 (Wilson 1982) ASHRAE Handbook—HVAC Systems and Equipment. of ganged stacks. In general, for a tight cluster to be considered as a 1. EXHAUST STACK AND AIR INTAKE single stack (i.e., to add stack momentums together) in dilution cal- DESIGN STRATEGIES culations, the stacks must be uncapped and nearly be touching the middle stack of the group. -
Methods and Devices for the Prevention of Backflow and Back
Chapter Four Air Gap (2) The air gap may be easily Methods and Devices defeated in the event that the Air gaps are non-mechanical “2D” requirement was purposely backflow preventers that are or inadvertently compromised. for the Prevention of very effective devices to be used Excessive splash may be encoun- where either backsiphonage or tered in the event that higher Backflow and backpressure conditions may than anticipated pressures or exist. Their use is as old as flows occur. The splash may be a Back-Siphonage piping and plumbing itself, but cosmetic or true potential only relatively recently have hazard—the simple solution standards been issued that being to reduce the “2D” wide choice of devices standardize their design. In dimension by thrusting the Aexists that can be used to general, the air gap must be supply pipe into the receiving prevent backsiphonage and twice the supply pipe diameter funnel. By so doing, the air gap backpressure from adding but never less than one inch. is defeated. contaminated fluids or gases See Figure 12. into a potable water supply (3) At an air gap, we expose the system. Generally, the selection water to the surrounding air FIGURE 12. with its inherent bacteria, dust of the proper device to use is Air gap. based upon the degree of hazard particles, and other airborne posed by the cross-connection. pollutants or contaminants. In addition, the aspiration effect of Additional considerations are Diameter based upon piping size, location, “D” the flowing water can drag down and the potential need to surrounding pollutants into the periodically test the devices to “2D” reservoir or holding tank.