BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION

ARC FLASH - NFPA 70E • Training is not a substitute for following corporate safety guidelines.

• Always refer to the latest safety standards when selecting PPE or evaluating hazards. • “What is an electrical arc flash?”

• “How do I calculate the danger posed by an arc flash?”

• “How do I protect myself and others from an arc flash?” TYPES OF ELECTRICAL FAULTS

Bolted Fault:

Bolted faults are characterized by a solidly connected fault path causing high levels of current to flow through this solid connection.

Arcing Fault:

Arcing faults differ in the fact that the current actually flows through ionized air causing an arc. ELECTRICAL ARC FLASH

• Flash Temperature:

up to 35000 [ºF]

• Blast Pressure:

500 to 600 [psi]

• Pressure Wave Velocity:

5500 to 6000 [ft/s] ELECTRICAL ARC FLASH

• Injuries

• 2nd Degree Burn:

176[ºF] @ 0.1[s]

• 3rd Degree Burn:

205[ºF] @ 0.1[s]

• Threshold for 2nd Degree Burn: 1.2 [cal/cm2] ELECTRICAL ARC FLASH

Causes of arcing faults:

• Accidents caused by touching a test probe to the wrong surface.

• Accidental tool slippage.

• Sparks due to breaks or gaps in insulation system.

• Equipment failure due to use of substandard parts, improper installation, or even normal wear and tear.

• Dust, corrosion or other impurities on the surface of the conductor insulation systems. ELECTRICAL ARC FLASH

• 5 to 10 arc flash explosions occur in electric equipment every day in the United States.

• This number does not include cases in which the victim is sent to an ordinary hospital.

• These incidents are so severe the victims require treatment from a special burn center. ELECTRICAL ARC FLASH HAZARD

• NFPA 70E

• Arch Flash Hazard: A dangerous condition associated with the possible release of energy caused by an

• FPN No.1: “…may exist when energized electrical conductors are exposed… a person interacting with equipment in such a manner that could cause an electric arc.” • “What is an electrical arc flash?”

• “How do I calculate the danger posed by an arc flash?”

• “How do I protect myself and others from an arc flash?” ELECTRICAL ARC FLASH HAZARD

• Arc Flash Hazard Analysis: A study investigating a worker’s potential exposure to arc flash energy, conducted for the purpose of injury prevention and the determination of safe work practices, arc flash protection boundary, and appropriate levels of PPE.

• Calculations based on NFPA Annex D ELECTRICAL ARC FLASH HAZARD

• Arc Flash Hazard Analysis Results:

• PPE Selection

• Arc Flash Boundary ELECTRICAL ARC FLASH HAZARD

Arc Flash Boundary:

• Designed to prevent 2nd degree burns when unprotected during an arc flash.

• The higher the arc flash energy the greater the boundary.

• If inside the boundary PPE protection is needed to prevent injury. STOLL EXPERIMENT

Stoll A.M., Greene L.C., “Relationship Between Pain and Tissue Damage Due to ”, Journal of Applied Physiology 14: 373-382, 1959

• Based on experiments on humans.

• Used a flame source with varying times of exposure

• The time and energy was varied to determine a second degree burn threshold relationship. ELECTRICAL ARC FLASH BOUNDARIES

Important Factors: NFPA Annex D:

•Available fault current Multiple Methods

•Transformer kVA •Lee Method

•Transformer Impedance •IEEE 1584 Method

•Motor Contribution •Software Solutions

•Fuse or Breaker Curves and Settings Requires a complete protection coordination study •Conduit Type BREAKER/FUSEBreaker Settings CURVES Comparison

CURRENT IN AMPERES CURRENT IN AMPERES

1000 1000 2000 KVA 2000 KVA 2 sets: 500 Fault clears in 8 2 sets: 500 2000 KVA seconds 2000 KVA 100 125E Incident energy 100 125E = 718 cal/cm2 3000A MAIN 3000A MAIN

10 10 INSECONDS TIME 800A1 No FR class for IE 800A1

TIME INSECONDS TIME values this high IA = 6K IA = 6K

1 IB = 9K 1 IB = 9K

2 sets: 500 2 sets: 500 TX Inrush Fault clears in 0.1 TX Inrush 0.10 second 0.10 Incident energy

0.01 2 0.01 1101001K10K= .97 cal/cm 1101001K10K

Case 3.tcc Ref. Voltage: 480 Current Scale x10^2 Ford Sharonville.drw Case 3.tcc Ref. Voltage: 480 Current Scale x10^2 Ford Sharonville.drw FR class 0

31 Engineering Services ELECTRICAL ARC FLASH HAZARD

• Arc Flash Hazard Analysis Results:

• PPE Selection

• Arc Flash Boundary • “What is an electrical arc flash?”

• “How do I calculate the danger posed by an arc flash?”

• “How do I protect myself and others from an arc flash?” ELECTRICAL SHOCK HAZARD

• Shock Hazard Analysis: A shock hazard analysis shall determine the voltage to which personnel will be exposed, boundary requirements, and personal protective equipment necessary in order to minimize the possibility of electrical shock.

• Calculations based on NFPA 130.2 ELECTRICAL SHOCK HAZARD

• Shock Hazard Analysis Results:

• PPE Selection

• Approach Boundary ELECTRICAL PPE

• PPE Selection:

• Based on Arc Flash and Shock Hazard

• FR, Fire Retardant clothing or Arc Flash Suit

• Arc Flash Suit:

• A complete FR clothing and equipment that covers the entire body, except for the hands and feet. This includes pants, jacket, and a beekeeper-type hood fitted with a face shield ELECTRICAL PPE

• Arc Rating: The value attributed to materials that describes their performance to exposure to an electrical arc discharge. The arc rating is expressed in [cal/cm2] and is derived from the determined value of the arc thermal performance value (ATPV) or energy breakopen threshold. ELECTRICAL PPE

• 130.7(C)(10): Category 0

2 • Incident Energy: {0-1.2} [cal/cm ]

• Shirt (Long Sleeve) *1

• Pants (Long) *1

• Safety Glasses or Goggles

• Hearing Protection

• Gloves (As needed)

• *1: Non-melting (according to ASTM F 1506-00) or Untreated Natural Fiber ELECTRICAL PPE

• 130.7(C)(10): Category 1

2 • Incident Energy: {1.2-4} [cal/cm ]

• Arc-rated long sleeve shirt

• Arc-rated pants

• Arc-rated coverall

• Arc-rated jacket, parka, or rainwear

• Hardhat, Safety Glasses, Hearing Protection

• Leather Gloves

• Leather work shoes ELECTRICAL PPE

• 130.7(C)(10): Category 2

2 • Incident Energy: {4-8} [cal/cm ]

• Arc-rated long sleeve shirt

• Arc-rated pants

• Arc-rated coverall

• Arc-rated jacket, parka, or rainwear

• Hardhat, Safety Glasses, Hearing Protection

• Leather Gloves

• Leather work shoes

• Arc-rated flash suit hood, for Cat 2* ELECTRICAL PPE

• 130.7(C)(10): Category 3

2 • Incident Energy: {8-25} [cal/cm ]

• Arc-rated long sleeve shirt

• Arc-rated pants

• Arc-rated coverall

• Arc-rated flash suit jacket, pants, hood

• Arc-rated jacket, parka, or rainwear

• Hardhat with FR lines, Safety Glasses, Hearing Protection

• Arc-rated Gloves

• Leather work shoes ELECTRICAL PPE

• 130.7(C)(10): Category 4

2 • Incident Energy: {25-40} [cal/cm ]

• Arc-rated long sleeve shirt

• Arc-rated pants

• Arc-rated coverall

• Arc-rated flash suit jacket, pants, hood

• Arc-rated jacket, parka, or rainwear

• Hardhat with FR lines, Safety Glasses, Hearing Protection

• Arc-rated Gloves

• Leather work shoes ELECTRICAL HAZARD ANALYSIS

• Approach Boundaries

• Shock

• From Shock Hazard Analysis

• Arc Flash

• From Arc Flash Hazard Analysis ELECTRICAL HAZARD ANALYSIS

• Arc Flash Protection Boundary: When an arc flash hazard exists, an approach limit at a distance from a prospective arc source within which a person could receive a second degree burn if an electrical arc flash were to occur. ELECTRICAL HAZARD ANALYSIS

• 130.7(C)(1) When and employee is working within the Arc Flash Protection Boundary he or she shall wear protective clothing and other personal protective equipment in accordance with 130.3. ELECTRICAL HAZARD ANALYSIS

• NFPA 70E defines an unqualified person as simply "a person who is not a qualified person." There are two kinds of unqualified persons:

• An unqualified who does not know the equipment or has not received safety training on the potential hazards involved.

• A non-electrician, such as a general maintenance worker or painter, who is not expected to work on live electrical equipment. ELECTRICAL HAZARD ANALYSIS

• Shock Hazard Boundary:

• Limited Approach Boundary: An approach limit at a distance from and exposed energized electrical conductor or circuit part within which a shock hazard exists. ELECTRICAL HAZARD ANALYSIS

• Shock Hazard Boundary:

• Restricted Approach Boundary: An approach limit at a distance from and exposed energized electrical conductor or circuit part within which there is an increased risk of shock, due to electrical arc over combined with inadvertent movement, for personnel working in close proximity to the energized electrical conductor or circuit part. ELECTRICAL HAZARD ANALYSIS

• Shock Hazard Boundary:

• Prohibited Approach Boundary: An approach limit at a distance form and exposed energized electrical conductor or circuit part within which work is considered the same as making contact with the electrical conductor or circuit part. ELECTRICAL SHOCK BOUNDARIES

NFPANFPA 70E 70ETable Table 130.4 130.4 (C) (C) (a) (a) Approach BoundariesApproach Boundaries to Energized to Energized Electrical Electrical Conductors Conductors or Circuitor Circuit Parts Parts for for Shock Shock ProtectionProtection fo for Alternatingr Alternating Current Current Systems (aSystemsll dimensions (all dimensions are distances are distances from from energized energized electrical electrical conductor conductor oror circuitcircuit parts parts to toemployee employee) )

(1) (1) (2) (2) (3) (3) (4)(4) (5) (5) b Limited Limited Approach Approach Boundary Boundaryb

Nominal System Voltage Exposed Exposed Fixed Restricted Approach Prohibited Approach Nominal System Voltage 4 Exposed Exposed Fixed Restricted bApproach Prohibited bApproach Range, Phase4 to Phase Movable Circuit Part Boundaryb ; Includes Boundary b Range, Phase to Phase MovableConductor Circuit Part InadvertentBoundary Movement; Includes Adder Boundary 50 V Conductor Not Specified Not Specified Inadvertent Not MovementSpecified Adder Not Specified 50 V 50 V – 300 V Not Specified 3.0 m (10 ft. 0 Notin.) Specified1.0 m (3 ft . 6 in.) Not Avoid Specified Contact Avoid Not Contact Specified 50 V – 300 301V V – 750 V 3.0 m (10 3.0 ft. m 0(10 in.) ft. 0 1.0 in.) m 1.0 (3 mft .(3 6 ft.in.) 6 in.) Avoid 0.3 m Contact(1 ft. 0 in.) 25 Avoidmm (0 ft.Contact 1 in.) 301 V – 750 V 3.0 m (10 ft. 0 in.) 1.0 m (3 ft. 6 in.) 0.3 m (1 ft. 0 in.) 25 mm (0 ft. 1 in.) 751 V – 15 kV 3.0 m (10 ft. 0 in.) 1.5 m (5 ft. 0 in) 0.7 m (2 ft. 2 in.) 0.2 m (0 ft.7 in.) 15.1 kV – 36 kV 3.0 m (10 ft. 0 in.) 1.8 m (6 ft. 0 in.) 0.8 m (2 ft. 7 in.) 0.3 m (0 ft. 10 in.) 751 V – 15 36.1kV kV – 46 kV 3.0 m (10 3.0 ft. m 0(10 in.) ft. 0 1.5in.) m 2.5 (5 mft. (8 0 ft.in) 0 in.) 0.7 0.8 m m (2 (2 ft. ft. 29 in.) 0.4 0.2 m (1 m ft. ( 05 ft.7in.) in.) 15.1 kV – 36 kV 3.0 m (10 ft. 0 in.) 1.8 m (6 ft. 0 in.) 0.8 m (2 ft. 7 in.) 0.3 m (0 ft. 10 in.) 36.1 kV – 4646.1 kV kV – 72.5 kV 3.0 m (10 3.0 ft. m 0(10 in.) ft. 0 2.5in.) m 2.5 (8 mft. (8 0 ft.in.) 0 in.) 0.8 1.0 m m (2 (3 ft. ft. 93 in.) 0.1 0.4 m (2 m ft. (1 2 ft.in.) 5 in.) 72.6 kV – 121 kV 3.3 m (10 ft. 8 in.) 2.5 m (8 ft. 0 in.) 1.0 m (3 ft. 4 in.) 0.8 m (2 ft. 9 in.) 46.1 kV – 72.5138 kV – 145 kV 3.0 m (10 3.4 ft. m 0(11 in.) ft. 0 2.5in.) m 3.0 (8 mft. (10 0 in.) ft. 0 in.) 1.0 1.2 m m (3 (3 ft.ft. 310 in.) in.) 1.0 0.1 m (3 m ft. (2 4 ft.in.) 2 in.) 72.6 kV – 121 kV 3.3 m (10 ft. 8 in.) 2.5 m (8 ft. 0 in.) 1.0 m (3 ft. 4 in.) 0.8 m (2 ft. 9 in.) 138 kV – 145161 kV kV – 169 kV 3.4 m (11 3.6 ft. m 0(11 in.) ft. 8 3.0in.) m 3.6 (10 m ft. (11 0 ft.in.) 8 in.) 1.2 1.3 m m (3 (4 ft. ft. 103 in.) in.) 1.1 1.0 m (3m ft.(3 9 ft. in. 4) in.) 230 kV – 242 kV 4.0 m (13 ft. 0 in.) 4.0 m (13 ft. 0 in.) 1.3 m (4 ft. 3 in.) 1.6 m (5 ft. 2 in.) 345 kV – 363 kV 4.7 m (15 ft. 4 in.) 4.7 m (15 ft. 4 in.) 2.8 m (9 ft. 2 in.) 2.6 m (8 ft. 8 in.) 161 kV – 169 kV 3.6 m (11 ft. 8 in.) 3.6 m (11 ft. 8 in.) 1.3 m (4 ft. 3 in.) 1.1 m (3 ft. 9 in.) 230 kV – 242500 kV kV – 550 kV 4.0 m (13 5.8 ft. m 0(19 in.) ft. 0 4.0in.) m 5.8 (13 m ft. (19 0 ft.in.) 0 in.) 1.3 3.6 m m (4 (11 ft. ft. 3 10in.) in.) 3.5 1.6 m (11 m ft.(5 4ft. in.) 2 in.) 345 kV – 363765 kV kV - 800 kV 4.7 m (15 7.2 ft. m 4(23 in.) ft. 9 in.)4.7 m 7.2 (15 m ft. (23 4 ft.in.) 9 in.) 2.8 4.9 m m (9 (15 ft. ft. 2 11in.) in.) 4.7 2.6 m (15 m (8ft. 5ft. in.) 8 in.)

500 kV – 550 kV 5.8 m (19 ft. 0 in.) 5.8 m (19 ft. 0 in.) 3.6 m (11 ft. 10 in.) 3.5 m (11 ft. 4 in.) 765 kV - 800 kV 7.2 m (23 ft. 9 in.) 7.2NFPA m (23 70E ft. 9Table in.) 130.4 (C) 4.9 (a) m (15 ft. 11 in.) 4.7 m (15 ft. 5 in.) Approach Boundaries to Energized Electrical Conductors or Circuit Parts for Shock Protection for Voltage Systems (1) (2) (3) (4) (5) NFPA 70E Tableb 130.4 (C) (a) Limited Approach Boundary Approach Boundaries to Energized Electrical Conductors or Circuit Parts for Shock Protection for Nominal Potential ExposedDirect CurrentExposed VoltageFixed SystemsRestricted Approach Prohibited Approach (1) Difference (2) Movable (3)Circuit Part Boundary(4)b; Includes Boundary(5)b c Limited ApproachConductor Boundaryb Inadvertent Movement Adder <100 V Not Specified Not Specified Not Specified Not Specified 100 V – 300 V 3.0 m (10 ft. 0 in.) 1.0 m (3 ft. 6 in.) Avoid Contact Avoid Contact Nominal301 Potential V – 1 kV Exposed 3.0 m (10 ft. 0 Exposedin.) 1.0 m Fixed (3 ft. 6 in.) Restricted 0.3 m (1 Approach ft. 0 in.) 25Prohibited mm (0 ft. 1Approach in.) Difference1.1 kV – 5 kV Movable 3.0 m (10 ft. 0 in.)Circuit 1.5 m Part (5 ft. 0 in) Boundary 0.5 m (1b; ft.Includes 5 in.) 0.1 m (0Boundary ft.4 in.) b 5.1 kV – 15 kV Conductor 3.0 m (10c ft. 0 in.) 1.5 m (5 ft. 0 in.) Inadvertent 0.7 mMovement (2 ft. 2 in.) Adder 0.2 m (0 ft. 7 in.) <100 V 15.1 kV – 45 kV Not Specified 3.0 m (10 ft. 0 in.)Not Specified2.5 m (8 ft. 0 in.) Not 0.8 mSpecified (2 ft. 9 in.) 0.4 m Not (1 ft. Specified 5 in.) 100 V – 30045 V.1 kV – 75 kV 3.0 m (10 3.0 ft. m 0(10 in.) ft. 0 1.0in.) m 2.5 (3 mft. (8 6 ft.in.) 0 in.) Avoid 1.0 m (3Contact ft. 2 in.) 0.7 mAvoid (2 ft. 1Contact in.) 75.1 kV –150 kV 3.3 m (10 ft. 8 in.) 3.0 m (10 ft. 0 in.) 1.2 m (4 ft. 0 in.) 1.0 m (3 ft. 2 in.) 301 V – 1 kV150.1 kV – 250 kV 3.0 m (10 3.6 ft. m 0(11 in.) ft. 8 1.0in.) m 3.6 (3 mft. (11 6 in.) ft. 8 in.) 0.3 1.6 m m (1 (5 ft. ft. 03 in.) 1.5 25 m (mm5 ft. (00 in.) ft. 1 in.) 1.1 kV – 5 kV250.1 kV – 500 kV 3.0 m (10 6.0 ft. m 0(20 in.) ft. 0 1.5in.) m 6.0 (5 mft. ( 200 in) ft. 0 in.) 0.5 3.5 m m (1 (11 ft. ft. 5 6in.) in.) 3.3 0.1 m ( 10m (0ft. 10ft.4 in.) in.) 5.1 kV – 15500 kV.1 kV – 800 kV 3.0 m (10 8.0 ft. m 0(26 in.) ft. 0 1.5in.) m 8.0 (5 mft. ( 260 in.) ft. 0 in.) 0.7 5.0m m (2(16 ft. ft. 2 5 in.) in.) 5.0 0. m2 (16 m (0ft. 5ft. in.) 7 in.) 15.1 kV – 45 kV 3.0 m (10 ft. 0 in.) 2.5 m (8 ft. 0 in.) 0.8 m (2 ft. 9 in.) 0.4 m (1 ft. 5 in.) 45.1 kV – 75a All kV dimensions are 3.0 distance m (10 ft.from 0 in.) exposed 2.5 energizedm (8 ft. 0 electricalin.) conductors 1.0 m or(3 circuitft. 2 in.) parts to worker. 0.7 m (2 ft. 1 in.) 75.1 kV –150b This kV term describes 3.3 a m condition (10 ft. 8 in in.) which 3.0 the m distance(10 ft. 0 between in.) the conductor 1.2 m (4 andft. 0 a in.) person is not under 1.0the controlm (3 ft. of 2 thein.) 150.1 kV –person. 250 kV The term normally 3.6 m (11 is ft.applied 8 in.) to overhead3.6 m (11 line ft. 8conductors in.) supported 1.6 m (by5 ft. poles. 3 in.) 1.5 m (5 ft. 0 in.) 250.1 kV – 500 kV 6.0 m (20 ft. 0 in.) 6.0 m (20 ft. 0 in.) 3.5 m (11 ft. 6 in.) 3.3 m (10 ft. 10 in.) 500.1 kV – 800 kV 8.0 m (26 ft. 0 in.) 8.0 m (26 ft. 0 in.) 5.0m (16 ft. 5 in.) 5.0 m (16 ft. 5 in.) Attachment D, pg. 1 OP 64.14 a All dimensions are distance from exposed energized electrical conductors or circuit parts to worker. b 4/29/13 This term describes a condition in which the distance between the conductor and a person is not under the control of the person. The term normally is applied to overhead line conductors supported by poles.

Attachment D, pg. 1 OP 64.14 4/29/13

ELECTRICAL HAZARD BOUNDARIES

• Approach Boundaries

• Shock

• From Shock Hazard Analysis

• Calculations based on NFPA 130.2

• Arc Flash

• From Arc Flash Hazard Analysis

• Calculations based on NFPA Annex D ELECTRICAL HAZARD BOUNDARIES

• 130.2(D)(1) Working at or close to the limited approach boundary: Where one or more unqualified persons are working at or close to the limited approach boundary, the designated person in charge of the work space where the electrical hazard exists shall advise the unqualified person(s) of the electrical hazard and warn them to stay outside of the limited approach boundary. ELECTRICAL HAZARD BOUNDARIES

• 130.2(D)(2) Entering the limited approach boundary: Where there is a need for an unqualified person(s) to cross the limited approach boundary, a qualified person shall advise them of the possible hazards and continuously escort the unqualified person(s) while inside the limited approach boundary. Under no circumstances should the unqualified person(s) be allowed to cross the restricted approach boundary. • “What is an electrical arc flash?”

• “How do I calculate the danger posed by an arc flash?”

• “How do I protect myself and others from an arc flash?” HAZARD RISK CATEGORY CLASSIFICATIONS

• What if the hazard analysis process has not been completed?

• You can use the Hazard Risk Category Classifications 130.7(C)(9) HAZARD RISK CATEGORY CLASSIFICATIONS

Table130.7(C)(9): Table 1

Hazard/Risk Rubber Insulating Insulated and Tasks Performed on Energized Equipment Category Gloves Insulating Hand Tools

Panelboards or Other Equipment Rated 240 V and Below- Note 1

Perform thermography & other non-contact inspections outside the restricted approach boundary 0 N N

Circuit breaker (CB) or fused switch operation with covers on 0 N N

Circuit breaker (CB) or fused switch operation with covers off 0 N N

Work on energized electrical conductors and circuit parts, including voltage testing 1 Y Y

Remove/Install CBs of fused switches 1 Y Y

Removal of bolted covers (to expose bare, energized electrical conductors and circuit parts) 0 N N

Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) 0 N N

Work on energized electrical conductors and circuit parts of utilization equipment fed directly by a branch circuit of the 1 Y Y panelboard HAZARD RISK CATEGORY CLASSIFICATIONS

Table130.7(C)(9): Table 1

Hazard/Risk Rubber Insulating Insulated and Tasks Performed on Energized Equipment Category Gloves Insulating Hand Tools

Panelboards or Switchboards Rated.240 V and up to 600 V (with molded case or insulated case circuit breakers)

- Note 1

Perform infrared thermography & other non-contact inspections outside the restricted approach boundary 1 N N

Circuit breaker (CB) or fused switch operation with covers on 0 N N

Circuit breaker (CB) or fused switch operation with covers off 1 Y Y

Work on energized electrical conductors and circuit parts, including voltage testing 2 Y Y

Work on energized electrical conductors and circuit parts of utilization equipment fed directly by a branch circuit of the 2 Y Y panelboard HAZARD RISK CATEGORY CLASSIFICATIONS

Table130.7(C)(9): Table 1

Hazard/Risk Rubber Insulating Insulated and Tasks Performed on Energized Equipment Category Gloves Insulating Hand Tools

600 V Class Motor Control Center (MCCs) - Note 2

Perform infrared thermography & other non-contact inspections outside the restricted approach boundary 1 N N

CB or fused switch or starter operation with enclosure doors closed 0 N N

Reading a panel meter while operating a meter switch 0 N N

CB or fused switch or starter operation with enclosure doors open 1 N N

Work on energized electrical conductors and circuit parts, including voltage testing 2 Y Y

Work on control circuits with energized electrical conductors and circuit parts 120 V or below, exposed 0 Y Y

Work on control circuits with energized electrical conductors and circuit parts >120 V or below, exposed 2 Y Y

Insertion or removal of individual starter “buckets” from MCC- Note 3 4 Y N

Application of safety grounds, after voltage test 2 Y N

Removal of bolted covers (to expose bare, energized electrical conductors and circuit parts)- Note 3 4 N N

Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) - Note 3 1 N N

Work on energized electrical conductors and circuit parts of utilization equipment fed directly by a branch circuit of the 2 Y Y motor control center HAZARD RISK CATEGORY CLASSIFICATIONS

Table130.7(C)(9): Table 1

Hazard/Risk Rubber Insulating Insulated and Tasks Performed on Energized Equipment Category Gloves Insulating Hand Tools

600V Class (with power circuit breakers or fused switches) - Note 4

Perform infrared thermography & other non-contact inspections outside the restricted approach boundary 2 N N

CB or fused switch or starter operation with enclosure doors closed 0 N N

Reading a panel meter while operating a meter switch 0 N N

CB or fused switch or starter operation with enclosure doors open 1 N N

Work on energized electrical conductors and circuit parts, including voltage testing 2 Y Y

Work on control circuits with energized electrical conductors and circuit parts 120 V or below, exposed 0 Y Y

Work on control circuits with energized electrical conductors and circuit parts >120 V or below, exposed 2 Y Y

Insertion or removal (racking) of CBs from cubicles, doors open or closed 4 N N

Application of safety grounds, after voltage test 2 Y N

Removal of bolted covers (to expose bare, energized electrical conductors and circuit parts) 4 N N

Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) 2 N N HAZARD RISK CATEGORY CLASSIFICATIONS

Table130.7(C)(9): Table 1

Hazard/Risk Rubber Insulating Insulated and Tasks Performed on Energized Equipment Category Gloves Insulating Hand Tools

Other 600 V Class (277 V through 600, nominal) Equipment - Note 2 (except as indicated) Lighting or small power transformers (600 V Maximum)

Removal of bolted covers (to expose bare, energized electrical conductors and circuit parts) 2 N N

Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) 1 N N

Work on energized electrical conductors and circuit parts, including voltage testing 2 Y Y

Application of safety grounds, after voltage test 2 Y N

Revenue Meters (kW-hour at primary voltage and current) insertion or removal 2 Y N

Cable trough or tray cover removal or installation 1 N N

Misc Equipment Cover removal or installation 1 N N

Work on energized electrical conductors and circuit parts, including voltage testing 2 Y Y

Application of safety grounds, after voltage test 2 Y N

Insertion or removal of plug in devices into or from busways 2 Y N HAZARD RISK CATEGORY CLASSIFICATIONS

Table130.7(C)(9): Table 1

Hazard/Risk Rubber Insulating Insulated and Tasks Performed on Energized Equipment Category Gloves Insulating Hand Tools

NEMA E2 (Fused contractor) Motor Starters, 2.3 kV through 7.2 kV

Perform infrared thermography & other non-contact inspections outside the restricted approach boundary 3 N N

Contractor operation with enclosure 0 N N

Reading a panel meter while operating a meter switch 0 N N

Contractor operation with enclosure door open 2 N N

Work on energized electrical conductors and circuit parts, including voltage testing 4 Y Y

Work on control circuits with energized electrical conductors and circuit parts 120 V or below, exposed 0 Y Y

Work on control circuits with energized electrical conductors and circuit parts >120 V, exposed 3 Y Y

Insertion or removal (racking) of CBs from cubicles, doors open or closed 4 N N

Application of safety grounds, after voltage test 3 Y N

Removal of bolted covers (to expose bare, energized electrical conductors and circuit parts) 4 N N

Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) 3 N N

Insertion or removal (racking) of starters from cubicles of arc-resistant construction, tested in accordance with IEEE C37 0 N N 20.7 doors closed only HAZARD RISK CATEGORY CLASSIFICATIONS

Table130.7(C)(9): Table 1

Hazard/Risk Rubber Insulating Insulated and Tasks Performed on Energized Equipment Category Gloves Insulating Hand Tools

Metal Clad Switchgear, 1 kV through 38 kV

Perform infrared thermography & other non-contact inspections outside the restricted approach boundary 3 N N

CB Operation with enclosure doors closed 2 N N

Reading a panel meter while operating a meter switch 0 N N

CB Or fused switch or starter operation with enclosure doors open 4 N N

Work on energized electrical conductors and circuit parts, including voltage testing 4 Y Y

Work on control circuits with energized electrical conductors and circuit parts 120 V or below, exposed 2 Y Y

Work on control circuits with energized electrical conductors and circuit parts >120 V or below, exposed Insertion or 4 Y Y removal (racking) of CBs from cubicles, doors open or closed

Insertion or removal (racking) of CBs from cubicles, doors open or closed 4 N N

Application of safety grounds, after voltage test 4 Y N

Removal of bolted covers (to expose bare, energized electrical conductors and circuit parts) 4 N N

Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) 3 N N

Opening voltage transformer or control power transformer compartments 4 N N HAZARD RISK CATEGORY CLASSIFICATIONS

Table130.7(C)(9):

Table 1

Hazard/Risk Rubber Insulating Insulated and Tasks Performed on Energized Equipment Category Gloves Insulating Hand Tools

ARC Resistant Switchgear Type 1 or 2 (for clearing times of <.05 with a perspective fault current not to exceed the Arc resistant rating of the equipment)

CB operation with enclosure doors closed 0 N N

Insertion or removal (racking) of CBs from cubicles, doors open or closed 0 N N

Insertion or removal of CBs from cubicles with door open 4 N N

Work on control circuits with energized electrical conductors and circuit parts 120 V or below, exposed 2 Y Y

Insertion or removal (racking) of ground and test device with door closed 0 N N

Insertion or removal (racking) of voltage transformers on or off the bus door closed 0 N N HAZARD RISK CATEGORY CLASSIFICATIONS

Table130.7(C)(9): Table 1

Hazard/Risk Rubber Insulating Insulated and Tasks Performed on Energized Equipment Category Gloves Insulating Hand Tools

Other Equipment 1kV Through 38 kV Metal-enclosed interupter switch gear, fused or unfused

Switch operation of arc-resistant-type construction, tested in accordance with IEEE C37.20.7, doors closed only Switch 0 N N operation, doors closed

Switch operation, doors closed 2 N N

Work on energized electrical conductors and circuit parts, including voltage testing 4 Y Y

Removal of bolted covers (to expose bare, energized electrical conductors and circuit parts) 4 N N

Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) 3 N N

Outdoor disconnect switch operation (hook stick operated) 3 Y Y

Outdoor disconnect switch operation (gang-operated, from grade) 2 Y N

Insulated cable examination, in man hole or other confined spaces 4 Y N

Insulated cable examination, in open area 2 Y N HAZARD RISK CATEGORY CLASSIFICATIONS

Table130.7(C)(9): Table 1

Notes a) Rubber insulating gloves rated for the maximum line-to-line voltage upon which work will be done.

(b) Insulated and insulating hand tools are tools rated and tested for the maximum line-to-line voltage upon which work will be done, and are manufactured and tested in accordance with ASTM zg 1505. Standard Specification for Insulated Hand Tools.

(c) Y = yes (required), N = no (not required) (d) For systems rated less than 1000 volts, the fault currents and upstream protective device clearing times are based on an 18 in. working distance.

(e) For systems rated 1 kV and greater, the Hazard/Risk Categories are based on a 36 in. working distance.

(f) For equipment protected by upstream current limiting fuses with arcing fault current in their current limiting range (1/2 cycle fault clearing time or less), the hazard/risk category required may be reduced by one number.

Specific Notes (as referenced in the table): 1. Maximum of 25 kA short circuit current available ; maximum of 0.03 sec (2 cycle) fault clearing time.

2. Maximum of 65 kA short circuit current available ; maximum of 0.33 sec (2 cycle) fault clearing time.

3. Maximum of 42 kA short circuit current available ; maximum of 0.33 sec (20 cycle) fault clearing time.

4. Maximum of 25 kA short circuit current available ; maximum of up to 0.5 sec (30 cycle) fault clearing time. BRANDON AND CLARK INC. ELECTRICAL CONTINUING EDUCATION